SlideShare a Scribd company logo
1 of 36
ELECTRICAL ENGINEERING DEPARTMENT
SYMMETRICAL COMPONENTS
PRESENTED BY -
-GOPAL KRISHNA MOTI -SURENDRA M. BUTLE
-UDAY DILIPRAO WANKAR - VILAS JAIPAL DORLE
STAFF IN CHARGE -
PROF.AWALE MADAM
𝐼𝑁𝐷𝐸𝑋
1. INTRODUCTION
2. 3-PHASE SYSTEM
3. SIGNIFICANCE OF POSITIVE,NEGATIVEAND ZERO
SEQUENCE COMPONENTS
4. AVERAGE 3-PHAE POWER IN TERMS OF SYMMETRICAL
COMPONENTS
5. SEQUENCE IMPEDANCES
6. FAULT CALCULATION
7. SEQUENCE NETWORK EQUATION
8. SINGLE LINE TO GROUND FAULT
9. SEQUENCE NETWORKS
10. FAULTS ON POWER SYSTEMS
11. REACTORS
12. APPLICATIONS
13. CONCLUSION
14. REFERENCES
INTRODUCTION
 IN 1918,DR.C.L.FORTESCUE PRESENTESENTED A PAPER ENTITLED-
METHOD OF SYMMETRICAL CO-ORDINATES APPLIED TO
SOLUTION OF POLYPHASE NETWORKS
AT AIEE.
 HE PROVED THAT, β€œ A SYSTEM OF n VECTORS OR QUANTITIES MAY BE
RESOLVED, WHEN n IS PRIME, INTO n DIFFERENT SYMETRICAL GROUPS OR
SYSTEMS, ONE OF WHICH CONSISTS OF n EQUAL VECTORS AND THE
REMAINING (n-1) SYSTEM CONSISTS OF n EQUISPACED VECTORS WHICH WITH
FIRST MENTIONED GROUP OF EQUAL VECTORS FORMS AN EQUAL NUMBER
OF SYMMETRICAL n PHASE SYSTEMS.”
 THE METHOD OF SYMMETRICAL COMPNENT IS A GENERAL ONE APPLICABLE
TO ANY POLYPHASE SYSTEM.
 GENERALLY, SYMMETRCAL COMPONENT METHOD IS USED FOR ANALYSIS OF
3-PH SYSTEM AS IT IS MORE FAMILIAR TO ELECRICAL ENGINEERS.
3-PHASE SYSTEM
 ANY THREE COPLANAR VECTORS π‘‰π‘Ž ,𝑉𝑏 AND 𝑉𝑐 CAN BE EXPRESSED IN TERMS OF
THREE NEW VECTORS 𝑉1, 𝑉2 AND 𝑉3 BY THREE SILMULTANEOUS LINEAR
EQUATIONS WITH CONSTANT COEFFICIENTS.
 THUS-
π‘‰π‘Ž = π‘Ž11 𝑉1 + π‘Ž12 𝑉2 + π‘Ž13 𝑉3 --------(1)
𝑉𝑏 = π‘Ž21 𝑉1 + π‘Ž22 𝑉2 + π‘Ž23 𝑉3 ---------(2)
𝑉𝑐 = π‘Ž31 𝑉1 + π‘Ž32 𝑉2 + π‘Ž33 𝑉3 ---------(3)
 EACH OF THE ORIGINAL VECTORS IS REPLACED BY A SET OF THREE VECTORS
MAKING A TOTAL OF NINE VECTORS.
 CONDITIONS:-
1. CALCULATIONS SHOULD BE SIMPLIFIED BY THE USE OF THE CHOSEN
SYSTEM OF COMPONENTS.THIS IS POSSIBLE ONLY IF THE IMPEDANCES(OR
ADMITTANCES)ASSOCIATED WITH THE COMPONENTS OF CURRENT(OR VOLTAGE)
CAN BE OBTAINED READILY BY CALCULATIONS OR TEST.
2. THE SYSTEM OF COMPONENTS CHOSEN SHOULD HAVE PHYSICA SIGNIFICANCE
AND BE AN AID IN DETERMINING POWER SYSTEM PERFORMANCE.
FUNDAMENTAL PRINCIPLE
οƒ˜ ACCORDING TO FORTESCUE THEOREM, THE THREE UNBALANCED VECTORS π‘‰π‘Ž ,𝑉𝑏
AND 𝑉𝑐 CAN BE REPLACED BY A SET OF THREE BALANCED SYSTEM OF VECTORS.
οƒ˜ A BALANCED SYSTEM OF THREE VECTORS IS ONE IN WHICH THE VECTORS ARE
EQUAL IN MAGNITUDE AND ARE EQUI-SPACED.
οƒ˜ THE THREE SYMMETRICAL COMPONENT VECTORS REPLACING π‘‰π‘Ž , 𝑉𝑏 AND 𝑉𝑐 ARE-
β€’ POSITIVE SEQUENCE COMPONENTS :- IT HAS THREE VECTORS OF EQUAL
MAGNITUDE BUT DISPLACED IN PHASE FROM EACH OTHER BY 1200
AND
HAS THE SAME PHASE SEQUENCE AS THE ORIGINAL VECTORS.
β€’ NEGATIVE SEQUENCE COMPONENTS :- IT HAS THREE VECTORS OF EQUAL
MAGNITUDE BUT DISPALCED IN PHASE FROM EACH OTHER BY 1200
AND
HAS THE PHASE SEQUENCE OPPOSITE TO THE ORIGINAL VECTORS.
β€’ ZERO SEQUENCE COMPONENTS :- IT HAS THREE VECTORS OF EQUAL
MAGNITUDE AND ALSO ARE IN PHASE WITH EACH OTHER.
A. POSITIVE SEQUENCE COMPONENTS
π‘‰π‘Ž1
𝑉𝑐1
𝑉𝑏1
B. NEGATIVE SEQUENCE COMPONENTS C. ZERO SEQUENCE COMPONENTS
π‘‰π‘Ž2
𝑉𝑏2
𝑉𝑐2
π‘‰π‘Ž0
𝑉𝑏0
𝑉𝐢0
NOTE: a , b , c denote phase sequence
1 , 2 ,0 denote positive , negative and zero
sequence quantities resp.
SIGNIFICANCE OF POSITIVE, NEGATIVE AND ZERO SEQUENCE
COMPONENTS
β€’ IF A SET OF POSITIVE SEQUENCE VOLTAGES IS APPLIED TO THE STATOR
WINDING OF THE ALTERNATOR,THE DIRECTION OF ROTATION OF THE
STATOR FIELD IS THE SAME AS THAT OF ROTOR.
β€’ IF A SET OF NEGATIVE SEQUENCE VOLTAGES IS APPLIED TO THE STATOR
WINDING OF THE OF THE ALTERNATOR, THE DIRECTION OF ROTATION
OF STATOR FIELD IS OPPOSITE TO THAT OF ROTOR.
β€’ THE ZERO SEQUENCE VOLTAGES ARE SINGLE PHASE VOLTAGES AND,
THEREFORE THEY GIVE RISE TO AN ALTERNATING FIELD IN SPACE.
PHASE VOLTAGES IN TERMS OF THE SYMMETRICAL
COMPONENTS OF PHASE β€˜A’
β€’ RELATION BETWEEN ORIGINAL UNBALANCED VECTORS AND THEIR
CORRESPONDING SYMM. COMPONENTS :-
π‘‰π‘Ž = π‘‰π‘Ž1 + π‘‰π‘Ž2 + π‘‰π‘Ž0 ---------(4)
𝑉𝑏 = 𝑉𝑏1 + 𝑉𝑏2 + 𝑉𝑏0 ---------(5)
𝑉𝑐 = 𝑉𝑐1 + 𝑉𝑐2 + 𝑉𝑐0 ---------(6)
β€’ CONSIDER OPERATOR ʎ WHICH HAS MAGNITUDE UNITY AND ROTATION
THROUGH 1200
.
IMPORTANT RELATIONS:-
ʎ= 1∠1200 = -0.5+j0.866
ʎ2= -1∠1200 =-0.5-j0.866
ʎ3
= 1 ,
ʎ4
= ʎ ,
ʎ2+ʎ+1=0
CONT….
RELATION BETWEEN THE SYMMETRICAL COMPONENTS OF PHASE β€˜b’AND
β€˜c’ IN TERMS OF SYMM.COMPONENTS OF PHASE β€˜a’
β€’ POSITIVE SEQUENCE VECTORS :-
π‘‰π‘Ž1
𝑉𝑐1
𝑉𝑏1
ʎ
ʎ
𝑉𝑏1 = ʎ2 π‘‰π‘Ž1 ; 𝑉𝑐1 = ΚŽπ‘‰π‘Ž1
β€’ NEGATIVE SEQUENCE VECTORS:-
π‘‰π‘Ž2
𝑉𝑏2
𝑉𝑐2
ʎ
ʎ
𝑉𝑏2 =ΚŽπ‘‰π‘Ž1 ; 𝑉𝑐2 = ʎ2 π‘‰π‘Ž2
β€’ ZERO SEQUENCE VECTORS :-
π‘‰π‘Ž0
𝑉𝑏0
𝑉𝑐0
π‘‰π‘Ž0 = 𝑉𝑏0 = 𝑉𝐢0
CONT….
SUSTITUTING THE VALUES OF SYMM.COMPONENTS IN EQU.(4),(5) & (6) , WE
GET,
π‘‰π‘Ž = π‘‰π‘Ž1 + π‘‰π‘Ž2 + π‘‰π‘Ž0 ----------(7)
𝑉𝑏=ʎ2
π‘‰π‘Ž1+ ΚŽπ‘‰π‘Ž2 + π‘‰π‘Ž0 ---------(8)
𝑉𝑐= ʎ π‘‰π‘Ž1+ ʎ2
π‘‰π‘Ž2 + π‘‰π‘Ž0 -------(9)
SIMILARLLY, RELATION BETWEEN PHASE CURRENTS IN TERMS OF THE
SYMMETRICAL COMPONENTS OF CURRENTS TAKING PHASE β€˜a’, IS GIVEN
AS FOLLOWS:-
I π‘Ž = I π‘Ž1 + I π‘Ž2 + I π‘Ž0----------(10)
I 𝑏=ʎ2I π‘Ž1+ ʎI π‘Ž2 + I π‘Ž0---------(11)
I 𝑐= ʎ I π‘Ž1+ ʎ2I π‘Ž2 + I π‘Ž0-------(12)
CONT….
TO FIND THE SYMMETRICAL COMPONENTS :-
 TO FIND POSITIVE SEQUENCE COMPONENT π‘‰π‘Ž1--
MULTIPLY EQU.(7), (8) & (9) BY 1 , ʎ , ʎ2
AND ADDING THEM , WE GET,
 TO FIND NEGATIVE SEQUENCE COMPONENT π‘‰π‘Ž2--
MULTIPLY EQU.(7), (8) & (9) BY 1 , ʎ2
,ʎ AND ADDING THEM , WE GET
π‘‰π‘Ž2=
1
3
π‘‰π‘Ž + ʎ2
𝑉𝑏 + ΚŽπ‘‰π‘ --------(14)
 TO FIND ZERO SEQUENCE COMPONENT π‘‰π‘Ž0--
ADD EQU.(7), (8) & (9) , WE GET
π‘‰π‘Ž0=
1
3
π‘‰π‘Ž + 𝑉𝑏 + 𝑉𝑐 --------(15)
π‘‰π‘Ž1=
1
3
π‘‰π‘Ž + ΚŽπ‘‰π‘ + ʎ2 𝑉𝑐 --------(13)
CONT….
SIMILLARLY SYMMETRICAL COMPONENTS ARE GIVEN AS :--
I π‘Ž1=
1
3
I π‘Ž + ʎI 𝑏 + ʎ2
I 𝑐 --------(16)
I π‘Ž2=
1
3
I π‘Ž + ʎ2Ib + ʎI 𝑐 --------(17)
I π‘Ž0=
1
3
I π‘Ž + I 𝑏 + I 𝑐 --------(18)
AVERAGE 3-PHASE POWER IN TERMS OF SYMMETRICAL
COMPONENTS:-
THE AVERAGE POWER ,
P = π‘‰π‘Ž 𝐼 π‘Ž cos βˆ… π‘Ž + 𝑉𝑏 𝐼 𝑏 cos βˆ… 𝑏+𝑉𝑐 𝐼𝑐 cos βˆ… 𝑐
= π‘‰π‘Ž. 𝐼 π‘Ž +𝑉𝑏. 𝐼 𝑏+𝑉𝑐. 𝐼𝑐
=(π‘‰π‘Ž1 + π‘‰π‘Ž2 + π‘‰π‘Ž0).(I π‘Ž1 + I π‘Ž2 + I π‘Ž0) + (ʎ2 π‘‰π‘Ž1+ ΚŽπ‘‰π‘Ž2 + π‘‰π‘Ž0).(ʎ2
I π‘Ž1+ʎI π‘Ž2 + I π‘Ž0)
+ (ʎ π‘‰π‘Ž1+ ʎ2
π‘‰π‘Ž2 + π‘‰π‘Ž0) .(ʎ I π‘Ž1+ ʎ2
I π‘Ž2 + I π‘Ž0)
TAKE EACH TERM ON RHS ,EXPAND AND REARRANGE THE EQUATION, WE GET,
P = 3[ |π‘‰π‘Ž1| 𝐼 π‘Ž1 cos πœƒ1 + |π‘‰π‘Ž2| 𝐼 π‘Ž2 cos πœƒ2 + |π‘‰π‘Ž0| 𝐼 π‘Ž0 cos πœƒ0]
SEQUENCE IMPEDANCES
β€’ THE SEQUENCE IMPEDANCES OF AN EQUIPMENT OR A COMPONENT OF POWER SYSTEM
ARE THE POSITIVE , NEGATIVE AND ZERO SEQUENCE IMPEDANCES.
POSITIVE SEQUENCE IMPEDANCE (𝑍1) :- IT IS THE IMPEDANCE OFFERED BY THE
EQUIPMENT TO THE FLOW OF POSITIVE SEQUENCE CURRENTS.
NEGATIVE SEQUENCE IMPEDANCES(𝑍2) :- IT IS THE IMPEDANCE OFFERED BY THE
EQUIPMENT TO THE FLOW OF NEGATIVE SEQUENCE CURRENTS.
ZERO SEQUENCE IMPEDANCES(𝑍0):- IT IS THE IMPEDANCE OFFERED BY THE
EQUIPMENT TO THE FLOW OF ZERO SEQUENCE CURRENTS.
β€’ FOR 3 PH ,SYMM. STATIC CIRCUIT WTHOUT INTERNAL VOLTAGES LIKE
TRANSFORMER AND TRANSMISION LINE, THE IMPEDANCES TO THE CURRENTS OF
ANY SEQ. ARE THE SAME IN THREE PHASE.
β€’ ALSO CURRENTS OF PARTICULAR SEQUENCE WILL PRODUCE DROP OF THE SAME
SEQUENCE ONLY.
β€’ HOWEVER, FOR STATIC CIRCUIT, POSITIVE AND NEGATIVE SEQUENCE IMPEDANCES
ARE EQUAL. ZERO SEQUENCE IMPEDANCES INCLUDES THE IMPEDANCE PATH
THROUGH GROUND.
CONT….
β€’ IN SYMMETRICAL ROTATING MACHINE, THE IMPEDANCE MET BY
ARMATURE CURRENTS OF A GIVEN SEQUENCE ARE EQUAL IN 3-PH.
β€’ BUT BY DEFINITION OF IT WILL DEPEND UPON THE PHASE ORDER OF
THE SEQUENCE CURRENT RELATIVE TO DIRECTION OF ROTATION OF
ROTOR.
β€’ HENCE, IN GENERAL, POSITIVE AND NEGATIVE SEQUENCE IMPEDANCES
ARE UNEQUAL.
β€’ IN FACT, FOR A ROTATING MACHINE, POSITIVE SEQ. IMPEDANCE VARIES,
HAVING MINIUM VALUE IMMEDIATELY FOLLOWING FAULT AND THEN
INCREASES WITH THE TIME UNTILL STEADY STATE CONDITIONS ARE
REACHED WHEN THE POSITIVE SEQUENCE IMPEDANCES CORRESPONDS
TO SYNCHRONOUS IMPEDANCE.
β€’ THUS FOR SYMMETRICAL SYSTEM, THERE IS NO MUTUTAL COUPLING
BETWEEN THE SEQUENCE NETWORKS.
FAULT CALCULATIONS
FAULTS CAN BE CLASSIFIED AS :-
1. SHUNT FAULTS (SHORT CIRCUIT)
2. SERIES FAULTS (OPEN CONDUCTOR)
1. SHUNT FAULTS :--
A. IT INVOLVES POWER CONDUCTOR OR CONDUCTORS TO GROUND OR SHORT
CIRCUIT FAULT.
B. SHUNT TYPE OF FAULTS ARE CLASSIFIED ASβ€”
1. LINE TO GROUND FAULT
2. LINE TO LINE FAULT
3. DOUBLE LINE TO GROUND FAULT
4. 3 PH FAULT.
2. SERIES FAULTS :--
A. WHEN CIRCUITS ARE CONTROLLED BY FUSES OR ANY DEVICE WHICH DOES
NOT OPEN ALL THREE PHASES OF THE CIRCUIT MAY BE OPENED WHILE OTHER
PHASES OR PHASE IS CLOSED,THEN CALLED AS SERIES TYPE OF FAULT.
B. SERIES TYPES OF FAULT ARE CLASSIFIED AS:-
1. ONE OPEN CONDUCTOR FAULT.
2. TWO OPEN CONDUCTOR FAULT.
VOLTAGE OF THE NEUTRAL :--
β€’ THE VOLTAGE OF THE NEUTRAL WHEN IT S GROUNDED THROUGH
SOME IMPEDANCE OR ISOLATED, WILL NOT BE AT GROUND POTENTIAL
UNDET UNBALANCED CONDITIONS SUCH AS UNSYMMETRICAL FAULTS.
β€’ THE POTENTIAL OF THE NEUTRAL IS GIVEN AS
𝑉𝑛 = βˆ’πΌ 𝑛 𝑍 𝑛
WHERE, 𝑍 𝑛= NEUTRAL GROUNDING IMPEDANCE.
NEGATIVE SIGN DENOTES CURENT FLOW FROM THE GROUND TO
NEUTRAL OF THE SYSTEM.
β€’ FOR 3 PHASE SYSTEM,
𝐼 𝑛= 𝐼 π‘Ž + 𝐼 𝑏 + 𝐼𝑐
= (I π‘Ž1 + I π‘Ž2 + I π‘Ž0)+(ʎ2I π‘Ž1+ ʎI π‘Ž2 + I π‘Ž0)+(ʎ I π‘Ž1+ ʎ2I π‘Ž2 + I π‘Ž0)
= 3 𝐼0
THEREFORE,
𝑉𝑛= βˆ’3𝐼 π‘Ž0 𝑍 𝑛
SINCE THE POSITIVE AND NEGATIVE SEQUENCE COMPONENTS ARE
ABSENT THROUGH NEUTRAL.
SEQUENCE NETWORK EQUATIONS
β€’ THESE EQU. ARE DERIVED FOR AN UNLOADED ALTERNATOR WITH NEUTRAL
SOLIDLY GROUNDED, ASSUMING BALANCED SYSTEM.
1.POSITIVE SEQUENCE VOLTAGE IS GIVEN BY–
π‘‰π‘Ž1 = 𝐸 π‘Ž βˆ’ 𝐼 π‘Ž1 𝑍1
2.NEGATIVE SEQUENCE VOLTAGE IS GIVEN BY-
π‘‰π‘Ž2 = 𝐸 π‘Ž2 βˆ’ 𝐼 π‘Ž2 𝑍2
= 0 - 𝐼 π‘Ž2 𝑍2
π‘‰π‘Ž2=βˆ’πΌ π‘Ž2 𝑍2
3.ZERO SEQUENCE VOLTAGES IS GIVEN BY –
π‘‰π‘Ž0 = 𝑉𝑛 βˆ’ 𝐼 π‘Ž0 𝑍 𝑔0
=βˆ’3𝐼 π‘Ž0 𝑍 𝑛 βˆ’ 𝐼 π‘Ž0 𝑍 𝑔0
= βˆ’πΌ π‘Ž0(𝑍 𝑔0+3𝑍 𝑛)
π‘‰π‘Ž0 = βˆ’πΌ π‘Ž0 𝑍0
where, 𝑍 𝑔0 = 𝑍𝐸𝑅0 𝑆𝐸𝑄. 𝐼𝑀𝑃𝐸𝐷𝐴𝑁𝐢𝐸 𝑂𝐹 𝐺𝐸𝑁.
𝑍 𝑛 = π‘πΈπ‘ˆπ‘‡π‘…π΄πΏ 𝐼𝑀𝑃𝐸𝐷𝐴𝑁𝐢𝐸
CONT….
THUS CORRSONDING SEQUENCE NETWORKS FOR THE ULOADED
ALTERNATOR ARE SHOWN BELOW ;
SINGLE LINE TO GROUND FAULT
1.LET THE FAULT TAKES PLACE ON PHASE A.
2. THE BOUNDARY CONDITIONS ARE-
π‘‰π‘Ž = 0 , 𝐼 𝑏 = 0, 𝐼𝑐 = 0
THE SEQUENCE NETWORK EQUATIONS ARE :-
π‘‰π‘Ž1 = 𝐸 π‘Ž βˆ’ 𝐼 π‘Ž1 𝑍1
π‘‰π‘Ž2=βˆ’πΌ π‘Ž2 𝑍2
π‘‰π‘Ž0 = βˆ’πΌ π‘Ž0 𝑍0
THE SOLUTION FOR THESE EQUATION WILL GIVE SIX UNKNOWNS π‘‰π‘Ž1
, π‘‰π‘Ž2, π‘‰π‘Ž0 AND 𝐼 π‘Ž1 ,𝐼 π‘Ž2 AND 𝐼 π‘Ž0.
WE HAVE,
I π‘Ž1=
1
3
I π‘Ž + ʎI 𝑏 + ʎ2
I 𝑐
I π‘Ž2=
1
3
I π‘Ž + ʎ2
Ib + ʎI 𝑐
I π‘Ž0=
1
3
I π‘Ž + I 𝑏 + I 𝑐
SUBSTITUTING THE VALUES OF 𝐼 𝑏 AND 𝐼𝑐 IN ABOVE EQUATIONS WE GET,
𝐼 π‘Ž1=𝐼 π‘Ž2= 𝐼 π‘Ž0.= 𝐼 π‘Ž/3
CONT….
NOW, SUBSTITUTUING THE VALUES OF π‘‰π‘Ž1 , π‘‰π‘Ž2,π‘‰π‘Ž0FROM THE
SEQUENCE NETWORK EQUATION, WE GET,
THE EQUATION π‘‰π‘Ž = 0 CAN BE WRITTEN IN TERMS OF SYMMETRICAL
COMPONENTS ,
π‘‰π‘Ž = 0 = π‘‰π‘Ž1 + π‘‰π‘Ž2 + π‘‰π‘Ž0
𝐸 π‘Ž βˆ’ 𝐼 π‘Ž1 𝑍1 βˆ’ 𝐼 π‘Ž2 𝑍2 βˆ’ 𝐼 π‘Ž0 𝑍0=0
SINCE,
𝐼 π‘Ž1 =𝐼 π‘Ž2 = 𝐼 π‘Ž0
WE GET,
𝐸 π‘Ž βˆ’ 𝐼 π‘Ž1 𝑍1 βˆ’ 𝐼 π‘Ž1 𝑍2 βˆ’ 𝐼 π‘Ž1 𝑍0=0
𝐼 π‘Ž1 =
𝐸 π‘Ž
𝑍1 + 𝑍2 + 𝑍0
CONT….
IT IS CLEAR THAT, TO SIMULATE A L-G FAULT ALL THE SEQUENCE
NETWORKS ARE REQUIRED AND SINCE THE CURRENTS ARE ALL EQUAL IN
MAGNITUDE AND PHASE ANGLE, THEREFORE,THE THREE SEQUENCE
NETWORKS MUST BE CONNECTED IN SERIES.
CONT….
IN CASE OF LINE TO GROUND FAULT,
𝐼 𝑛 = 3𝐼 π‘Ž0
IF THE NEUTRAL IS NOT GROUNDED THE ZERO SEQUENCE IMPEDANCE
𝑍0 ,BECOMES INFINITE. THEREFORE,
𝐼 π‘Ž1 =
𝐸 π‘Ž
𝑍1 + 𝑍2 + ∞
= 0
HENCE, 𝐼 π‘Ž1 =𝐼 π‘Ž2 = 𝐼 π‘Ž0=0
THIS MEANS THAT,FOR THIS SYSTEM,THE FAULT CURRENT 𝐼 π‘Ž=0
LINE TO LINE FAULT
1.THE LINE TO LINE-LINE FAULT TAKES PLACE ON PHASE B AND C .
2. THE BOUNDARY CONDITIONS ARE :-
𝐼 π‘Ž=0
𝐼 π‘Ž + 𝐼 𝑏 = 0
𝑉𝑏 = 𝑉𝑐
FOR LINE-LINE FAULT,THE ZERO SEQUENCE COMPONENT OF CURRENT IS
ABSENT AND POSITIVE SEQUENCE COMPONENT OF CURRENT IS EQUAL IN
MAGNITUDE BUT OPPOSITE IN PHASE TO NEGATIVE SEQUENCE
COMPONENT OF CURRENT, I.E.
𝐼 π‘Ž1 = βˆ’ 𝐼 π‘Ž2
IN LINE-LINE FAULT, ZERO SEQUENCE COMPONENT OF CURRENT IS ABSENT.
𝐼 π‘Ž0=0
ALSO,
POSITIVE SEQUENCE COMPONENT OF VOLTAGE EQUALS THE NEGATIVE
SEQUENCE COMPONENT OF VOLTAGE.THEREFORE THE SEQUENCE NETWORK
ARE CONNECTED IN PARALLEL.
π‘‰π‘Ž1 = π‘‰π‘Ž2
𝐸 π‘Ž βˆ’ 𝐼 π‘Ž1 𝑍1=-𝐼 π‘Ž2 𝑍1 = 𝐼 π‘Ž1 𝑍1
𝐼 π‘Ž1=
𝐸 π‘Ž
𝑍1+𝑍2
INTERCONECTION OF SEQUENCE NETWORKS FOR L-L FAULT
IS SHOWN BELOW:-
DOUBLE LINE TO GROUND FAULT
1.DOUBLE LINE TO GROUND FAULT TAKES PLACE ON PHASE B AND C.
2.THE BOUNDARY CONDITIONS AREβ€”
𝐼 π‘Ž=0,𝑉𝑏 =0,𝑉𝐢 = 0
3. THE SEQUENCE NETWORK IS SHOWN BELOW:-
IN L-L-G FAULT, POSITIVE SEQUENCE,NEGATIVE SEQUENCE AND
ZERO SEQUENCE VOLTAGES ARE SAME.
π‘‰π‘Ž1 = π‘‰π‘Ž2=π‘‰π‘Ž3
ALSO,
I π‘Ž = I π‘Ž1 + I π‘Ž2 + I π‘Ž0 = 0
SUBSTITUTING VALUES OF I π‘Ž2 AND I π‘Ž0 FROM EQU.
I π‘Ž1 βˆ’
𝐸 π‘Ž βˆ’ 𝐼 π‘Ž1 𝑍1
𝑍2
βˆ’
𝐸 π‘Ž βˆ’ 𝐼 π‘Ž1 𝑍0
𝑍0
= 0
REARRANGING THE TERMS,WE GET,
I π‘Ž1 =
𝐸 π‘Ž
𝑍1 +
𝑍0 𝑍2
𝑍0 + 𝑍2
β€’ IT IS CLEAR THAT, ALL THE THREE SEQUENCE NETWORKS ARE
REQUIRED TO SIMULATE L-L-G FAULT.
β€’ ALSO, THE NEG. AND ZERO SEQ. NETWORKS ARE CONNECTED IN
PARALLEL.
β€’ THE SEQUENCE NETWORK INTERCONNECTION NETWORK IS
SHOWN BELOW:-
3-PHASE FAULT
1. THE BOUNDARY CONDITIONS ARE--
𝐼 π‘Ž + 𝐼 𝑏 + 𝐼𝑐 = 0
π‘‰π‘Ž = 𝑉𝑏=𝑉𝐢
2. CIRCUIT DIAGRAM:-
3.SINCE,
| I π‘Ž|= |I 𝑏| = |I 𝑐|
4.TAKE I π‘Ž AS REFERRENCE. WE GET
𝐼 𝑏 = ʎ2
𝐼 π‘ŽAND 𝐼 𝐢 = ʎ𝐼 π‘Ž
5. USING THE RELATION,
I π‘Ž1=
1
3
I π‘Ž + ʎI 𝑏 + ʎ2I 𝑐
I π‘Ž2=
1
3
I π‘Ž + ʎ2
Ib + ʎI 𝑐
I π‘Ž0=
1
3
I π‘Ž + I 𝑏 + I 𝑐
6. WE GET,
I π‘Ž1=I π‘Ž , I π‘Ž2=0 AND I π‘Ž0=0
7. IN THIS SYSTEM, ZERO AND NEG.SEQ.COMPONENT OF CURRENT
ARE ABSENT.
8. THE POSITIVE SEQUENCE COMPONENT OF CURRENT IS EQUAL
TO PHASE CURRENT.
9. SIMILLARY,
π‘‰π‘Ž1 = π‘‰π‘Ž2 = π‘‰π‘Ž0 = 0
β€’ FROM THE ANALYSIS OF THE VARIOUS FAULTS,THE OBSERVATIONS ARE
MADE.
1. THE POSITIVE SEQUENCE CURRENTS ARE PRESENT ON ALL TYPES OF
FAULT.
2. NEGATIVE SEQUENCE CURRENTS ARE PRESENT IN ALL
UNSYMMETRICAL FAULTS.
3. ZERO SEQUENCE CURRENTS ARE PRESENT WHEN THE NEUTRAL OF THE
SYSTEM IS GROUNDED AND THE FAULT ALSO INVOLVES THE GROUND,
AND MAGNITUDE OF THE NEUTRAL CURRENT IS EQUAL TO 3𝐼 π‘Ž0.
SEQUENCE NETWORK
1. THE ZERO SEQUENCE NETWORK IS SIMILAR TO POSITIVE SEQUENCE
NETWORK EXCEPT FOR THE FACT THAT SINCE NO NEGATIVE SEQUENCE
VOLTAGES ARE GENENRATED,THE SOURCE OF EMF IS ABSENT.
2. THE GENERAL CIRCUIT :-
β€’ THERE ARE TWO SERIES AND SHUNT SWITCHES.
β€’ ONE SERIES AND ONE SHUNT SWITCH ARE FOR BOTH THE SIDES
SEPARATELY.
β€’ THE SERIES SWITCH OF PARTICULAR SIDE IS CLOSED IF IT IS STAR
GROUNDED AND THE SHUNT SWITCH IS CLOSED IF THAT SIDE IS
DELTA CONNECTED,OTHERWISE OPEN.
Symmertical components

More Related Content

What's hot

Tcsc ppt
Tcsc pptTcsc ppt
Tcsc pptPrabhu R
Β 
Objectives of shunt compensation
Objectives of shunt compensationObjectives of shunt compensation
Objectives of shunt compensationAyyarao T S L V
Β 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relaysPremanandDesai
Β 
STate Space Analysis
STate Space AnalysisSTate Space Analysis
STate Space AnalysisHussain K
Β 
Faults on Power System
Faults on Power SystemFaults on Power System
Faults on Power SystemVinod Srivastava
Β 
Power systems symmetrical components
Power systems symmetrical componentsPower systems symmetrical components
Power systems symmetrical componentsanoopeluvathingal
Β 
UNSYMMETRICAL FAULTS IN POWER SYSTEM
UNSYMMETRICAL FAULTS IN POWER SYSTEMUNSYMMETRICAL FAULTS IN POWER SYSTEM
UNSYMMETRICAL FAULTS IN POWER SYSTEMerramansaini1947
Β 
Instrument Transformer Presentation
Instrument Transformer PresentationInstrument Transformer Presentation
Instrument Transformer PresentationRishi Raj
Β 
Protective relay
Protective relay Protective relay
Protective relay Uday Wankar
Β 
Symmetrical Fault Analysis
Symmetrical Fault AnalysisSymmetrical Fault Analysis
Symmetrical Fault AnalysisSANTOSH GADEKAR
Β 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION moiz89
Β 
Power system protection devices
Power system protection devicesPower system protection devices
Power system protection devicesPrakash_13209
Β 
Power Electronics
Power ElectronicsPower Electronics
Power Electronicsguestcfebed3
Β 
Representation of power system components
Representation of power system componentsRepresentation of power system components
Representation of power system componentsPrasanna Rao
Β 
Sequence impedances of transformersΒ 
Sequence impedances of transformersΒ Sequence impedances of transformersΒ 
Sequence impedances of transformersΒ Muhammad Moin
Β 
Infinite bus bar in power system
Infinite bus bar in power systemInfinite bus bar in power system
Infinite bus bar in power systemEklavya Sharma
Β 
Three phase transformers
Three phase transformersThree phase transformers
Three phase transformersZiyaulhaq
Β 

What's hot (20)

Tcsc ppt
Tcsc pptTcsc ppt
Tcsc ppt
Β 
Objectives of shunt compensation
Objectives of shunt compensationObjectives of shunt compensation
Objectives of shunt compensation
Β 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
Β 
STate Space Analysis
STate Space AnalysisSTate Space Analysis
STate Space Analysis
Β 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
Β 
Faults on Power System
Faults on Power SystemFaults on Power System
Faults on Power System
Β 
Power systems symmetrical components
Power systems symmetrical componentsPower systems symmetrical components
Power systems symmetrical components
Β 
UNSYMMETRICAL FAULTS IN POWER SYSTEM
UNSYMMETRICAL FAULTS IN POWER SYSTEMUNSYMMETRICAL FAULTS IN POWER SYSTEM
UNSYMMETRICAL FAULTS IN POWER SYSTEM
Β 
Sssc
SsscSssc
Sssc
Β 
Instrument Transformer Presentation
Instrument Transformer PresentationInstrument Transformer Presentation
Instrument Transformer Presentation
Β 
Protective relay
Protective relay Protective relay
Protective relay
Β 
Symmetrical Fault Analysis
Symmetrical Fault AnalysisSymmetrical Fault Analysis
Symmetrical Fault Analysis
Β 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
Β 
Power system protection devices
Power system protection devicesPower system protection devices
Power system protection devices
Β 
Power Electronics
Power ElectronicsPower Electronics
Power Electronics
Β 
TCSC
TCSCTCSC
TCSC
Β 
Representation of power system components
Representation of power system componentsRepresentation of power system components
Representation of power system components
Β 
Sequence impedances of transformersΒ 
Sequence impedances of transformersΒ Sequence impedances of transformersΒ 
Sequence impedances of transformersΒ 
Β 
Infinite bus bar in power system
Infinite bus bar in power systemInfinite bus bar in power system
Infinite bus bar in power system
Β 
Three phase transformers
Three phase transformersThree phase transformers
Three phase transformers
Β 

Viewers also liked

CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...vaibyfrndz
Β 
Symmetrical Components Fault Calculations
Symmetrical Components Fault CalculationsSymmetrical Components Fault Calculations
Symmetrical Components Fault Calculationsmichaeljmack
Β 
Symmetrical and un-symmetrical fault
Symmetrical and un-symmetrical faultSymmetrical and un-symmetrical fault
Symmetrical and un-symmetrical faultsiddiqui arshad hussain
Β 
Power System Analysis!
Power System Analysis!Power System Analysis!
Power System Analysis!PRABHAHARAN429
Β 
Power system fault analysis ppt
Power system fault analysis pptPower system fault analysis ppt
Power system fault analysis pptkarikalan123
Β 
Illumination
IlluminationIllumination
IlluminationJAY THAKAR
Β 
ECNG 3015 Industrial and Commercial Electrical Systems
ECNG 3015   Industrial and Commercial Electrical SystemsECNG 3015   Industrial and Commercial Electrical Systems
ECNG 3015 Industrial and Commercial Electrical SystemsChandrabhan Sharma
Β 
unsymmetrical fault
unsymmetrical faultunsymmetrical fault
unsymmetrical faultsahed dewan
Β 
Analysis of unsymmetrical faults using bus impedence matrix
Analysis of unsymmetrical faults using bus impedence matrixAnalysis of unsymmetrical faults using bus impedence matrix
Analysis of unsymmetrical faults using bus impedence matrixTrupesh Rupareliya
Β 
Bs ii-electricity-unit-iv-2012-four
Bs ii-electricity-unit-iv-2012-fourBs ii-electricity-unit-iv-2012-four
Bs ii-electricity-unit-iv-2012-fourBattula Choudary
Β 
Diagnosis in orthodontics /certified fixed orthodontic courses by Indian den...
Diagnosis in orthodontics  /certified fixed orthodontic courses by Indian den...Diagnosis in orthodontics  /certified fixed orthodontic courses by Indian den...
Diagnosis in orthodontics /certified fixed orthodontic courses by Indian den...Indian dental academy
Β 
Illumination project
Illumination projectIllumination project
Illumination projectI11008341
Β 
Unsymmetrical fault in transmission line
Unsymmetrical fault in transmission lineUnsymmetrical fault in transmission line
Unsymmetrical fault in transmission linevishalgohel12195
Β 
Advances in diagnostic aids/certified fixed orthodontic courses by Indian den...
Advances in diagnostic aids/certified fixed orthodontic courses by Indian den...Advances in diagnostic aids/certified fixed orthodontic courses by Indian den...
Advances in diagnostic aids/certified fixed orthodontic courses by Indian den...Indian dental academy
Β 
CT design aspects - Nageswar-6
CT design aspects - Nageswar-6CT design aspects - Nageswar-6
CT design aspects - Nageswar-6Nageswar Rao
Β 
Recent advances in diagnostic aids /certified fixed orthodontic courses by In...
Recent advances in diagnostic aids /certified fixed orthodontic courses by In...Recent advances in diagnostic aids /certified fixed orthodontic courses by In...
Recent advances in diagnostic aids /certified fixed orthodontic courses by In...Indian dental academy
Β 
RECENT ADVANCES IN DIAGNOSIS OF TUBERCULOSIS
RECENT ADVANCES IN DIAGNOSIS OF TUBERCULOSISRECENT ADVANCES IN DIAGNOSIS OF TUBERCULOSIS
RECENT ADVANCES IN DIAGNOSIS OF TUBERCULOSISANGAN KARMAKAR
Β 
Recent advances in diagnostic aids /certified fixed orthodontic courses by In...
Recent advances in diagnostic aids /certified fixed orthodontic courses by In...Recent advances in diagnostic aids /certified fixed orthodontic courses by In...
Recent advances in diagnostic aids /certified fixed orthodontic courses by In...Indian dental academy
Β 

Viewers also liked (20)

CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
Β 
Symmetrical Components Fault Calculations
Symmetrical Components Fault CalculationsSymmetrical Components Fault Calculations
Symmetrical Components Fault Calculations
Β 
Symmetrical and un-symmetrical fault
Symmetrical and un-symmetrical faultSymmetrical and un-symmetrical fault
Symmetrical and un-symmetrical fault
Β 
Power System Analysis!
Power System Analysis!Power System Analysis!
Power System Analysis!
Β 
Power system fault analysis ppt
Power system fault analysis pptPower system fault analysis ppt
Power system fault analysis ppt
Β 
Illumination
IlluminationIllumination
Illumination
Β 
ECNG 3015 Industrial and Commercial Electrical Systems
ECNG 3015   Industrial and Commercial Electrical SystemsECNG 3015   Industrial and Commercial Electrical Systems
ECNG 3015 Industrial and Commercial Electrical Systems
Β 
Illumination
IlluminationIllumination
Illumination
Β 
unsymmetrical fault
unsymmetrical faultunsymmetrical fault
unsymmetrical fault
Β 
Analysis of unsymmetrical faults using bus impedence matrix
Analysis of unsymmetrical faults using bus impedence matrixAnalysis of unsymmetrical faults using bus impedence matrix
Analysis of unsymmetrical faults using bus impedence matrix
Β 
Bs ii-electricity-unit-iv-2012-four
Bs ii-electricity-unit-iv-2012-fourBs ii-electricity-unit-iv-2012-four
Bs ii-electricity-unit-iv-2012-four
Β 
Diagnosis in orthodontics /certified fixed orthodontic courses by Indian den...
Diagnosis in orthodontics  /certified fixed orthodontic courses by Indian den...Diagnosis in orthodontics  /certified fixed orthodontic courses by Indian den...
Diagnosis in orthodontics /certified fixed orthodontic courses by Indian den...
Β 
Illumination project
Illumination projectIllumination project
Illumination project
Β 
Unsymmetrical fault in transmission line
Unsymmetrical fault in transmission lineUnsymmetrical fault in transmission line
Unsymmetrical fault in transmission line
Β 
Advances in diagnostic aids/certified fixed orthodontic courses by Indian den...
Advances in diagnostic aids/certified fixed orthodontic courses by Indian den...Advances in diagnostic aids/certified fixed orthodontic courses by Indian den...
Advances in diagnostic aids/certified fixed orthodontic courses by Indian den...
Β 
Unsymmetrical Fault
Unsymmetrical FaultUnsymmetrical Fault
Unsymmetrical Fault
Β 
CT design aspects - Nageswar-6
CT design aspects - Nageswar-6CT design aspects - Nageswar-6
CT design aspects - Nageswar-6
Β 
Recent advances in diagnostic aids /certified fixed orthodontic courses by In...
Recent advances in diagnostic aids /certified fixed orthodontic courses by In...Recent advances in diagnostic aids /certified fixed orthodontic courses by In...
Recent advances in diagnostic aids /certified fixed orthodontic courses by In...
Β 
RECENT ADVANCES IN DIAGNOSIS OF TUBERCULOSIS
RECENT ADVANCES IN DIAGNOSIS OF TUBERCULOSISRECENT ADVANCES IN DIAGNOSIS OF TUBERCULOSIS
RECENT ADVANCES IN DIAGNOSIS OF TUBERCULOSIS
Β 
Recent advances in diagnostic aids /certified fixed orthodontic courses by In...
Recent advances in diagnostic aids /certified fixed orthodontic courses by In...Recent advances in diagnostic aids /certified fixed orthodontic courses by In...
Recent advances in diagnostic aids /certified fixed orthodontic courses by In...
Β 

Similar to Symmertical components

BEF43303_-_201620171_W5 Analysis of fault.pdf
BEF43303_-_201620171_W5 Analysis of fault.pdfBEF43303_-_201620171_W5 Analysis of fault.pdf
BEF43303_-_201620171_W5 Analysis of fault.pdfLiewChiaPing
Β 
Lecture no 4 power system analysis elc353 et313
Lecture no 4 power system analysis elc353 et313Lecture no 4 power system analysis elc353 et313
Lecture no 4 power system analysis elc353 et313Fazal Ur Rehman
Β 
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of ExcitationPerformance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitationpaperpublications3
Β 
Section 7 Fault Analysis.pdf
Section 7 Fault Analysis.pdfSection 7 Fault Analysis.pdf
Section 7 Fault Analysis.pdfALIFEVIOUSCHRISTIANX
Β 
Transient Stability Analysis of IEEE 9 Bus System in Power World Simulator
Transient Stability Analysis of IEEE 9 Bus System in Power World SimulatorTransient Stability Analysis of IEEE 9 Bus System in Power World Simulator
Transient Stability Analysis of IEEE 9 Bus System in Power World SimulatorIJERA Editor
Β 
Transient Stability Analysis of IEEE 9 Bus System in Power World Simulator
Transient Stability Analysis of IEEE 9 Bus System in Power World SimulatorTransient Stability Analysis of IEEE 9 Bus System in Power World Simulator
Transient Stability Analysis of IEEE 9 Bus System in Power World SimulatorIJERA Editor
Β 
Ee423 fault analysis_notes
Ee423  fault analysis_notesEe423  fault analysis_notes
Ee423 fault analysis_notesAcot Benard
Β 
283481961-POWER-SYSTEM-FAULTS-ppt.ppt
283481961-POWER-SYSTEM-FAULTS-ppt.ppt283481961-POWER-SYSTEM-FAULTS-ppt.ppt
283481961-POWER-SYSTEM-FAULTS-ppt.pptAshaLatha456489
Β 
Ee 1351 power system analysis
Ee 1351 power system analysisEe 1351 power system analysis
Ee 1351 power system analysisHari Kumar
Β 
Control of Grid- Interfacing Inverters with Integrated Voltage Unbalance Corr...
Control of Grid- Interfacing Inverters with Integrated Voltage Unbalance Corr...Control of Grid- Interfacing Inverters with Integrated Voltage Unbalance Corr...
Control of Grid- Interfacing Inverters with Integrated Voltage Unbalance Corr...IOSR Journals
Β 
Assignment 1 170901 interconnected power system
Assignment 1 170901 interconnected power systemAssignment 1 170901 interconnected power system
Assignment 1 170901 interconnected power systemVara Prasad
Β 
Assignment 1 170901 interconnected power system
Assignment 1 170901 interconnected power systemAssignment 1 170901 interconnected power system
Assignment 1 170901 interconnected power systemVara Prasad
Β 
BEF43303_-_201620171_W6 Analysis of Fault.pdf
BEF43303_-_201620171_W6 Analysis of Fault.pdfBEF43303_-_201620171_W6 Analysis of Fault.pdf
BEF43303_-_201620171_W6 Analysis of Fault.pdfLiewChiaPing
Β 
F0315040047
F0315040047F0315040047
F0315040047theijes
Β 
Design And Simulation Of Distributed Statcom Controller For Power Factor Impr...
Design And Simulation Of Distributed Statcom Controller For Power Factor Impr...Design And Simulation Of Distributed Statcom Controller For Power Factor Impr...
Design And Simulation Of Distributed Statcom Controller For Power Factor Impr...IJERA Editor
Β 
Power System Analysis Unit - V
Power System Analysis Unit - VPower System Analysis Unit - V
Power System Analysis Unit - Varunatshare
Β 
Distance Algorithm for Transmission Line with Mid-Point Connected STATCOM
Distance Algorithm for Transmission Line with Mid-Point Connected STATCOMDistance Algorithm for Transmission Line with Mid-Point Connected STATCOM
Distance Algorithm for Transmission Line with Mid-Point Connected STATCOMIRJET Journal
Β 

Similar to Symmertical components (20)

BEF43303_-_201620171_W5 Analysis of fault.pdf
BEF43303_-_201620171_W5 Analysis of fault.pdfBEF43303_-_201620171_W5 Analysis of fault.pdf
BEF43303_-_201620171_W5 Analysis of fault.pdf
Β 
Symmetrical component
Symmetrical componentSymmetrical component
Symmetrical component
Β 
Lecture no 4 power system analysis elc353 et313
Lecture no 4 power system analysis elc353 et313Lecture no 4 power system analysis elc353 et313
Lecture no 4 power system analysis elc353 et313
Β 
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of ExcitationPerformance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Β 
H06 elo f
H06 elo fH06 elo f
H06 elo f
Β 
Section 7 Fault Analysis.pdf
Section 7 Fault Analysis.pdfSection 7 Fault Analysis.pdf
Section 7 Fault Analysis.pdf
Β 
Transient Stability Analysis of IEEE 9 Bus System in Power World Simulator
Transient Stability Analysis of IEEE 9 Bus System in Power World SimulatorTransient Stability Analysis of IEEE 9 Bus System in Power World Simulator
Transient Stability Analysis of IEEE 9 Bus System in Power World Simulator
Β 
Transient Stability Analysis of IEEE 9 Bus System in Power World Simulator
Transient Stability Analysis of IEEE 9 Bus System in Power World SimulatorTransient Stability Analysis of IEEE 9 Bus System in Power World Simulator
Transient Stability Analysis of IEEE 9 Bus System in Power World Simulator
Β 
Ee423 fault analysis_notes
Ee423  fault analysis_notesEe423  fault analysis_notes
Ee423 fault analysis_notes
Β 
283481961-POWER-SYSTEM-FAULTS-ppt.ppt
283481961-POWER-SYSTEM-FAULTS-ppt.ppt283481961-POWER-SYSTEM-FAULTS-ppt.ppt
283481961-POWER-SYSTEM-FAULTS-ppt.ppt
Β 
Ee 1351 power system analysis
Ee 1351 power system analysisEe 1351 power system analysis
Ee 1351 power system analysis
Β 
Control of Grid- Interfacing Inverters with Integrated Voltage Unbalance Corr...
Control of Grid- Interfacing Inverters with Integrated Voltage Unbalance Corr...Control of Grid- Interfacing Inverters with Integrated Voltage Unbalance Corr...
Control of Grid- Interfacing Inverters with Integrated Voltage Unbalance Corr...
Β 
40220140501007 2
40220140501007 240220140501007 2
40220140501007 2
Β 
Assignment 1 170901 interconnected power system
Assignment 1 170901 interconnected power systemAssignment 1 170901 interconnected power system
Assignment 1 170901 interconnected power system
Β 
Assignment 1 170901 interconnected power system
Assignment 1 170901 interconnected power systemAssignment 1 170901 interconnected power system
Assignment 1 170901 interconnected power system
Β 
BEF43303_-_201620171_W6 Analysis of Fault.pdf
BEF43303_-_201620171_W6 Analysis of Fault.pdfBEF43303_-_201620171_W6 Analysis of Fault.pdf
BEF43303_-_201620171_W6 Analysis of Fault.pdf
Β 
F0315040047
F0315040047F0315040047
F0315040047
Β 
Design And Simulation Of Distributed Statcom Controller For Power Factor Impr...
Design And Simulation Of Distributed Statcom Controller For Power Factor Impr...Design And Simulation Of Distributed Statcom Controller For Power Factor Impr...
Design And Simulation Of Distributed Statcom Controller For Power Factor Impr...
Β 
Power System Analysis Unit - V
Power System Analysis Unit - VPower System Analysis Unit - V
Power System Analysis Unit - V
Β 
Distance Algorithm for Transmission Line with Mid-Point Connected STATCOM
Distance Algorithm for Transmission Line with Mid-Point Connected STATCOMDistance Algorithm for Transmission Line with Mid-Point Connected STATCOM
Distance Algorithm for Transmission Line with Mid-Point Connected STATCOM
Β 

More from Uday Wankar

TEACHING AND LEARNING BASED OPTIMISATION
TEACHING AND LEARNING BASED OPTIMISATIONTEACHING AND LEARNING BASED OPTIMISATION
TEACHING AND LEARNING BASED OPTIMISATIONUday Wankar
Β 
Optimization Simulated Annealing
Optimization Simulated AnnealingOptimization Simulated Annealing
Optimization Simulated AnnealingUday Wankar
Β 
Optimization Shuffled Frog Leaping Algorithm
Optimization Shuffled Frog Leaping AlgorithmOptimization Shuffled Frog Leaping Algorithm
Optimization Shuffled Frog Leaping AlgorithmUday Wankar
Β 
Optimization technique genetic algorithm
Optimization technique genetic algorithmOptimization technique genetic algorithm
Optimization technique genetic algorithmUday Wankar
Β 
Optimization Technique Harmony Search
Optimization Technique Harmony Search Optimization Technique Harmony Search
Optimization Technique Harmony Search Uday Wankar
Β 
Optimization by Ant Colony Method
Optimization by Ant Colony MethodOptimization by Ant Colony Method
Optimization by Ant Colony MethodUday Wankar
Β 
Gas turbine engine
Gas turbine engineGas turbine engine
Gas turbine engineUday Wankar
Β 
Gas turbine engine
Gas turbine engineGas turbine engine
Gas turbine engineUday Wankar
Β 
Rewinding a brushless motor
Rewinding a brushless motorRewinding a brushless motor
Rewinding a brushless motorUday Wankar
Β 
Rewinding a bldc motor
Rewinding a bldc motorRewinding a bldc motor
Rewinding a bldc motorUday Wankar
Β 
Persistence of Vision Display
Persistence of Vision DisplayPersistence of Vision Display
Persistence of Vision DisplayUday Wankar
Β 
Arm cortex (lpc 2148) based motor speed
Arm cortex (lpc 2148) based motor speedArm cortex (lpc 2148) based motor speed
Arm cortex (lpc 2148) based motor speedUday Wankar
Β 
Arm Processor Based Speed Control Of BLDC Motor
Arm Processor Based Speed Control Of BLDC MotorArm Processor Based Speed Control Of BLDC Motor
Arm Processor Based Speed Control Of BLDC MotorUday Wankar
Β 
Arm cortex ( lpc 2148 ) based motor speed control
Arm cortex ( lpc 2148 ) based motor speed control Arm cortex ( lpc 2148 ) based motor speed control
Arm cortex ( lpc 2148 ) based motor speed control Uday Wankar
Β 
Arm cortex ( lpc 2148 ) based motor speed control
Arm cortex ( lpc 2148 ) based motor speed control Arm cortex ( lpc 2148 ) based motor speed control
Arm cortex ( lpc 2148 ) based motor speed control Uday Wankar
Β 
POWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENTPOWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENTUday Wankar
Β 
CSTPS training REPORT
CSTPS training REPORTCSTPS training REPORT
CSTPS training REPORTUday Wankar
Β 
Hybrid power generation by solar –wind
Hybrid power generation by solar –windHybrid power generation by solar –wind
Hybrid power generation by solar –windUday Wankar
Β 
Hybrid power generation by and solar –wind
Hybrid power generation by and solar –windHybrid power generation by and solar –wind
Hybrid power generation by and solar –windUday Wankar
Β 
Grid solving robot
Grid solving robotGrid solving robot
Grid solving robotUday Wankar
Β 

More from Uday Wankar (20)

TEACHING AND LEARNING BASED OPTIMISATION
TEACHING AND LEARNING BASED OPTIMISATIONTEACHING AND LEARNING BASED OPTIMISATION
TEACHING AND LEARNING BASED OPTIMISATION
Β 
Optimization Simulated Annealing
Optimization Simulated AnnealingOptimization Simulated Annealing
Optimization Simulated Annealing
Β 
Optimization Shuffled Frog Leaping Algorithm
Optimization Shuffled Frog Leaping AlgorithmOptimization Shuffled Frog Leaping Algorithm
Optimization Shuffled Frog Leaping Algorithm
Β 
Optimization technique genetic algorithm
Optimization technique genetic algorithmOptimization technique genetic algorithm
Optimization technique genetic algorithm
Β 
Optimization Technique Harmony Search
Optimization Technique Harmony Search Optimization Technique Harmony Search
Optimization Technique Harmony Search
Β 
Optimization by Ant Colony Method
Optimization by Ant Colony MethodOptimization by Ant Colony Method
Optimization by Ant Colony Method
Β 
Gas turbine engine
Gas turbine engineGas turbine engine
Gas turbine engine
Β 
Gas turbine engine
Gas turbine engineGas turbine engine
Gas turbine engine
Β 
Rewinding a brushless motor
Rewinding a brushless motorRewinding a brushless motor
Rewinding a brushless motor
Β 
Rewinding a bldc motor
Rewinding a bldc motorRewinding a bldc motor
Rewinding a bldc motor
Β 
Persistence of Vision Display
Persistence of Vision DisplayPersistence of Vision Display
Persistence of Vision Display
Β 
Arm cortex (lpc 2148) based motor speed
Arm cortex (lpc 2148) based motor speedArm cortex (lpc 2148) based motor speed
Arm cortex (lpc 2148) based motor speed
Β 
Arm Processor Based Speed Control Of BLDC Motor
Arm Processor Based Speed Control Of BLDC MotorArm Processor Based Speed Control Of BLDC Motor
Arm Processor Based Speed Control Of BLDC Motor
Β 
Arm cortex ( lpc 2148 ) based motor speed control
Arm cortex ( lpc 2148 ) based motor speed control Arm cortex ( lpc 2148 ) based motor speed control
Arm cortex ( lpc 2148 ) based motor speed control
Β 
Arm cortex ( lpc 2148 ) based motor speed control
Arm cortex ( lpc 2148 ) based motor speed control Arm cortex ( lpc 2148 ) based motor speed control
Arm cortex ( lpc 2148 ) based motor speed control
Β 
POWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENTPOWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENT
Β 
CSTPS training REPORT
CSTPS training REPORTCSTPS training REPORT
CSTPS training REPORT
Β 
Hybrid power generation by solar –wind
Hybrid power generation by solar –windHybrid power generation by solar –wind
Hybrid power generation by solar –wind
Β 
Hybrid power generation by and solar –wind
Hybrid power generation by and solar –windHybrid power generation by and solar –wind
Hybrid power generation by and solar –wind
Β 
Grid solving robot
Grid solving robotGrid solving robot
Grid solving robot
Β 

Recently uploaded

APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
Β 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2RajaP95
Β 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
Β 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
Β 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
Β 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
Β 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
Β 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
Β 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
Β 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
Β 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacingjaychoudhary37
Β 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
Β 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
Β 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
Β 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
Β 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
Β 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
Β 

Recently uploaded (20)

APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
Β 
β˜… CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
β˜… CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCRβ˜… CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
β˜… CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
Β 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
Β 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
Β 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
Β 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
Β 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Β 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
Β 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
Β 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
Β 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
Β 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Β 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacing
Β 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
Β 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Β 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
Β 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Β 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
Β 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
Β 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
Β 

Symmertical components

  • 1. ELECTRICAL ENGINEERING DEPARTMENT SYMMETRICAL COMPONENTS PRESENTED BY - -GOPAL KRISHNA MOTI -SURENDRA M. BUTLE -UDAY DILIPRAO WANKAR - VILAS JAIPAL DORLE STAFF IN CHARGE - PROF.AWALE MADAM
  • 2. 𝐼𝑁𝐷𝐸𝑋 1. INTRODUCTION 2. 3-PHASE SYSTEM 3. SIGNIFICANCE OF POSITIVE,NEGATIVEAND ZERO SEQUENCE COMPONENTS 4. AVERAGE 3-PHAE POWER IN TERMS OF SYMMETRICAL COMPONENTS 5. SEQUENCE IMPEDANCES 6. FAULT CALCULATION 7. SEQUENCE NETWORK EQUATION 8. SINGLE LINE TO GROUND FAULT 9. SEQUENCE NETWORKS 10. FAULTS ON POWER SYSTEMS 11. REACTORS 12. APPLICATIONS 13. CONCLUSION 14. REFERENCES
  • 3. INTRODUCTION  IN 1918,DR.C.L.FORTESCUE PRESENTESENTED A PAPER ENTITLED- METHOD OF SYMMETRICAL CO-ORDINATES APPLIED TO SOLUTION OF POLYPHASE NETWORKS AT AIEE.  HE PROVED THAT, β€œ A SYSTEM OF n VECTORS OR QUANTITIES MAY BE RESOLVED, WHEN n IS PRIME, INTO n DIFFERENT SYMETRICAL GROUPS OR SYSTEMS, ONE OF WHICH CONSISTS OF n EQUAL VECTORS AND THE REMAINING (n-1) SYSTEM CONSISTS OF n EQUISPACED VECTORS WHICH WITH FIRST MENTIONED GROUP OF EQUAL VECTORS FORMS AN EQUAL NUMBER OF SYMMETRICAL n PHASE SYSTEMS.”  THE METHOD OF SYMMETRICAL COMPNENT IS A GENERAL ONE APPLICABLE TO ANY POLYPHASE SYSTEM.  GENERALLY, SYMMETRCAL COMPONENT METHOD IS USED FOR ANALYSIS OF 3-PH SYSTEM AS IT IS MORE FAMILIAR TO ELECRICAL ENGINEERS.
  • 4. 3-PHASE SYSTEM  ANY THREE COPLANAR VECTORS π‘‰π‘Ž ,𝑉𝑏 AND 𝑉𝑐 CAN BE EXPRESSED IN TERMS OF THREE NEW VECTORS 𝑉1, 𝑉2 AND 𝑉3 BY THREE SILMULTANEOUS LINEAR EQUATIONS WITH CONSTANT COEFFICIENTS.  THUS- π‘‰π‘Ž = π‘Ž11 𝑉1 + π‘Ž12 𝑉2 + π‘Ž13 𝑉3 --------(1) 𝑉𝑏 = π‘Ž21 𝑉1 + π‘Ž22 𝑉2 + π‘Ž23 𝑉3 ---------(2) 𝑉𝑐 = π‘Ž31 𝑉1 + π‘Ž32 𝑉2 + π‘Ž33 𝑉3 ---------(3)  EACH OF THE ORIGINAL VECTORS IS REPLACED BY A SET OF THREE VECTORS MAKING A TOTAL OF NINE VECTORS.  CONDITIONS:- 1. CALCULATIONS SHOULD BE SIMPLIFIED BY THE USE OF THE CHOSEN SYSTEM OF COMPONENTS.THIS IS POSSIBLE ONLY IF THE IMPEDANCES(OR ADMITTANCES)ASSOCIATED WITH THE COMPONENTS OF CURRENT(OR VOLTAGE) CAN BE OBTAINED READILY BY CALCULATIONS OR TEST. 2. THE SYSTEM OF COMPONENTS CHOSEN SHOULD HAVE PHYSICA SIGNIFICANCE AND BE AN AID IN DETERMINING POWER SYSTEM PERFORMANCE.
  • 5. FUNDAMENTAL PRINCIPLE οƒ˜ ACCORDING TO FORTESCUE THEOREM, THE THREE UNBALANCED VECTORS π‘‰π‘Ž ,𝑉𝑏 AND 𝑉𝑐 CAN BE REPLACED BY A SET OF THREE BALANCED SYSTEM OF VECTORS. οƒ˜ A BALANCED SYSTEM OF THREE VECTORS IS ONE IN WHICH THE VECTORS ARE EQUAL IN MAGNITUDE AND ARE EQUI-SPACED. οƒ˜ THE THREE SYMMETRICAL COMPONENT VECTORS REPLACING π‘‰π‘Ž , 𝑉𝑏 AND 𝑉𝑐 ARE- β€’ POSITIVE SEQUENCE COMPONENTS :- IT HAS THREE VECTORS OF EQUAL MAGNITUDE BUT DISPLACED IN PHASE FROM EACH OTHER BY 1200 AND HAS THE SAME PHASE SEQUENCE AS THE ORIGINAL VECTORS. β€’ NEGATIVE SEQUENCE COMPONENTS :- IT HAS THREE VECTORS OF EQUAL MAGNITUDE BUT DISPALCED IN PHASE FROM EACH OTHER BY 1200 AND HAS THE PHASE SEQUENCE OPPOSITE TO THE ORIGINAL VECTORS. β€’ ZERO SEQUENCE COMPONENTS :- IT HAS THREE VECTORS OF EQUAL MAGNITUDE AND ALSO ARE IN PHASE WITH EACH OTHER.
  • 6. A. POSITIVE SEQUENCE COMPONENTS π‘‰π‘Ž1 𝑉𝑐1 𝑉𝑏1 B. NEGATIVE SEQUENCE COMPONENTS C. ZERO SEQUENCE COMPONENTS π‘‰π‘Ž2 𝑉𝑏2 𝑉𝑐2 π‘‰π‘Ž0 𝑉𝑏0 𝑉𝐢0 NOTE: a , b , c denote phase sequence 1 , 2 ,0 denote positive , negative and zero sequence quantities resp.
  • 7. SIGNIFICANCE OF POSITIVE, NEGATIVE AND ZERO SEQUENCE COMPONENTS β€’ IF A SET OF POSITIVE SEQUENCE VOLTAGES IS APPLIED TO THE STATOR WINDING OF THE ALTERNATOR,THE DIRECTION OF ROTATION OF THE STATOR FIELD IS THE SAME AS THAT OF ROTOR. β€’ IF A SET OF NEGATIVE SEQUENCE VOLTAGES IS APPLIED TO THE STATOR WINDING OF THE OF THE ALTERNATOR, THE DIRECTION OF ROTATION OF STATOR FIELD IS OPPOSITE TO THAT OF ROTOR. β€’ THE ZERO SEQUENCE VOLTAGES ARE SINGLE PHASE VOLTAGES AND, THEREFORE THEY GIVE RISE TO AN ALTERNATING FIELD IN SPACE.
  • 8. PHASE VOLTAGES IN TERMS OF THE SYMMETRICAL COMPONENTS OF PHASE β€˜A’ β€’ RELATION BETWEEN ORIGINAL UNBALANCED VECTORS AND THEIR CORRESPONDING SYMM. COMPONENTS :- π‘‰π‘Ž = π‘‰π‘Ž1 + π‘‰π‘Ž2 + π‘‰π‘Ž0 ---------(4) 𝑉𝑏 = 𝑉𝑏1 + 𝑉𝑏2 + 𝑉𝑏0 ---------(5) 𝑉𝑐 = 𝑉𝑐1 + 𝑉𝑐2 + 𝑉𝑐0 ---------(6) β€’ CONSIDER OPERATOR ʎ WHICH HAS MAGNITUDE UNITY AND ROTATION THROUGH 1200 . IMPORTANT RELATIONS:- ʎ= 1∠1200 = -0.5+j0.866 ʎ2= -1∠1200 =-0.5-j0.866 ʎ3 = 1 , ʎ4 = ʎ , ʎ2+ʎ+1=0
  • 9. CONT…. RELATION BETWEEN THE SYMMETRICAL COMPONENTS OF PHASE β€˜b’AND β€˜c’ IN TERMS OF SYMM.COMPONENTS OF PHASE β€˜a’ β€’ POSITIVE SEQUENCE VECTORS :- π‘‰π‘Ž1 𝑉𝑐1 𝑉𝑏1 ʎ ʎ 𝑉𝑏1 = ʎ2 π‘‰π‘Ž1 ; 𝑉𝑐1 = ΚŽπ‘‰π‘Ž1 β€’ NEGATIVE SEQUENCE VECTORS:- π‘‰π‘Ž2 𝑉𝑏2 𝑉𝑐2 ʎ ʎ 𝑉𝑏2 =ΚŽπ‘‰π‘Ž1 ; 𝑉𝑐2 = ʎ2 π‘‰π‘Ž2 β€’ ZERO SEQUENCE VECTORS :- π‘‰π‘Ž0 𝑉𝑏0 𝑉𝑐0 π‘‰π‘Ž0 = 𝑉𝑏0 = 𝑉𝐢0
  • 10. CONT…. SUSTITUTING THE VALUES OF SYMM.COMPONENTS IN EQU.(4),(5) & (6) , WE GET, π‘‰π‘Ž = π‘‰π‘Ž1 + π‘‰π‘Ž2 + π‘‰π‘Ž0 ----------(7) 𝑉𝑏=ʎ2 π‘‰π‘Ž1+ ΚŽπ‘‰π‘Ž2 + π‘‰π‘Ž0 ---------(8) 𝑉𝑐= ʎ π‘‰π‘Ž1+ ʎ2 π‘‰π‘Ž2 + π‘‰π‘Ž0 -------(9) SIMILARLLY, RELATION BETWEEN PHASE CURRENTS IN TERMS OF THE SYMMETRICAL COMPONENTS OF CURRENTS TAKING PHASE β€˜a’, IS GIVEN AS FOLLOWS:- I π‘Ž = I π‘Ž1 + I π‘Ž2 + I π‘Ž0----------(10) I 𝑏=ʎ2I π‘Ž1+ ʎI π‘Ž2 + I π‘Ž0---------(11) I 𝑐= ʎ I π‘Ž1+ ʎ2I π‘Ž2 + I π‘Ž0-------(12)
  • 11. CONT…. TO FIND THE SYMMETRICAL COMPONENTS :-  TO FIND POSITIVE SEQUENCE COMPONENT π‘‰π‘Ž1-- MULTIPLY EQU.(7), (8) & (9) BY 1 , ʎ , ʎ2 AND ADDING THEM , WE GET,  TO FIND NEGATIVE SEQUENCE COMPONENT π‘‰π‘Ž2-- MULTIPLY EQU.(7), (8) & (9) BY 1 , ʎ2 ,ʎ AND ADDING THEM , WE GET π‘‰π‘Ž2= 1 3 π‘‰π‘Ž + ʎ2 𝑉𝑏 + ΚŽπ‘‰π‘ --------(14)  TO FIND ZERO SEQUENCE COMPONENT π‘‰π‘Ž0-- ADD EQU.(7), (8) & (9) , WE GET π‘‰π‘Ž0= 1 3 π‘‰π‘Ž + 𝑉𝑏 + 𝑉𝑐 --------(15) π‘‰π‘Ž1= 1 3 π‘‰π‘Ž + ΚŽπ‘‰π‘ + ʎ2 𝑉𝑐 --------(13)
  • 12. CONT…. SIMILLARLY SYMMETRICAL COMPONENTS ARE GIVEN AS :-- I π‘Ž1= 1 3 I π‘Ž + ʎI 𝑏 + ʎ2 I 𝑐 --------(16) I π‘Ž2= 1 3 I π‘Ž + ʎ2Ib + ʎI 𝑐 --------(17) I π‘Ž0= 1 3 I π‘Ž + I 𝑏 + I 𝑐 --------(18) AVERAGE 3-PHASE POWER IN TERMS OF SYMMETRICAL COMPONENTS:- THE AVERAGE POWER , P = π‘‰π‘Ž 𝐼 π‘Ž cos βˆ… π‘Ž + 𝑉𝑏 𝐼 𝑏 cos βˆ… 𝑏+𝑉𝑐 𝐼𝑐 cos βˆ… 𝑐 = π‘‰π‘Ž. 𝐼 π‘Ž +𝑉𝑏. 𝐼 𝑏+𝑉𝑐. 𝐼𝑐 =(π‘‰π‘Ž1 + π‘‰π‘Ž2 + π‘‰π‘Ž0).(I π‘Ž1 + I π‘Ž2 + I π‘Ž0) + (ʎ2 π‘‰π‘Ž1+ ΚŽπ‘‰π‘Ž2 + π‘‰π‘Ž0).(ʎ2 I π‘Ž1+ʎI π‘Ž2 + I π‘Ž0) + (ʎ π‘‰π‘Ž1+ ʎ2 π‘‰π‘Ž2 + π‘‰π‘Ž0) .(ʎ I π‘Ž1+ ʎ2 I π‘Ž2 + I π‘Ž0) TAKE EACH TERM ON RHS ,EXPAND AND REARRANGE THE EQUATION, WE GET, P = 3[ |π‘‰π‘Ž1| 𝐼 π‘Ž1 cos πœƒ1 + |π‘‰π‘Ž2| 𝐼 π‘Ž2 cos πœƒ2 + |π‘‰π‘Ž0| 𝐼 π‘Ž0 cos πœƒ0]
  • 13. SEQUENCE IMPEDANCES β€’ THE SEQUENCE IMPEDANCES OF AN EQUIPMENT OR A COMPONENT OF POWER SYSTEM ARE THE POSITIVE , NEGATIVE AND ZERO SEQUENCE IMPEDANCES. POSITIVE SEQUENCE IMPEDANCE (𝑍1) :- IT IS THE IMPEDANCE OFFERED BY THE EQUIPMENT TO THE FLOW OF POSITIVE SEQUENCE CURRENTS. NEGATIVE SEQUENCE IMPEDANCES(𝑍2) :- IT IS THE IMPEDANCE OFFERED BY THE EQUIPMENT TO THE FLOW OF NEGATIVE SEQUENCE CURRENTS. ZERO SEQUENCE IMPEDANCES(𝑍0):- IT IS THE IMPEDANCE OFFERED BY THE EQUIPMENT TO THE FLOW OF ZERO SEQUENCE CURRENTS. β€’ FOR 3 PH ,SYMM. STATIC CIRCUIT WTHOUT INTERNAL VOLTAGES LIKE TRANSFORMER AND TRANSMISION LINE, THE IMPEDANCES TO THE CURRENTS OF ANY SEQ. ARE THE SAME IN THREE PHASE. β€’ ALSO CURRENTS OF PARTICULAR SEQUENCE WILL PRODUCE DROP OF THE SAME SEQUENCE ONLY. β€’ HOWEVER, FOR STATIC CIRCUIT, POSITIVE AND NEGATIVE SEQUENCE IMPEDANCES ARE EQUAL. ZERO SEQUENCE IMPEDANCES INCLUDES THE IMPEDANCE PATH THROUGH GROUND.
  • 14. CONT…. β€’ IN SYMMETRICAL ROTATING MACHINE, THE IMPEDANCE MET BY ARMATURE CURRENTS OF A GIVEN SEQUENCE ARE EQUAL IN 3-PH. β€’ BUT BY DEFINITION OF IT WILL DEPEND UPON THE PHASE ORDER OF THE SEQUENCE CURRENT RELATIVE TO DIRECTION OF ROTATION OF ROTOR. β€’ HENCE, IN GENERAL, POSITIVE AND NEGATIVE SEQUENCE IMPEDANCES ARE UNEQUAL. β€’ IN FACT, FOR A ROTATING MACHINE, POSITIVE SEQ. IMPEDANCE VARIES, HAVING MINIUM VALUE IMMEDIATELY FOLLOWING FAULT AND THEN INCREASES WITH THE TIME UNTILL STEADY STATE CONDITIONS ARE REACHED WHEN THE POSITIVE SEQUENCE IMPEDANCES CORRESPONDS TO SYNCHRONOUS IMPEDANCE. β€’ THUS FOR SYMMETRICAL SYSTEM, THERE IS NO MUTUTAL COUPLING BETWEEN THE SEQUENCE NETWORKS.
  • 15. FAULT CALCULATIONS FAULTS CAN BE CLASSIFIED AS :- 1. SHUNT FAULTS (SHORT CIRCUIT) 2. SERIES FAULTS (OPEN CONDUCTOR) 1. SHUNT FAULTS :-- A. IT INVOLVES POWER CONDUCTOR OR CONDUCTORS TO GROUND OR SHORT CIRCUIT FAULT. B. SHUNT TYPE OF FAULTS ARE CLASSIFIED ASβ€” 1. LINE TO GROUND FAULT 2. LINE TO LINE FAULT 3. DOUBLE LINE TO GROUND FAULT 4. 3 PH FAULT. 2. SERIES FAULTS :-- A. WHEN CIRCUITS ARE CONTROLLED BY FUSES OR ANY DEVICE WHICH DOES NOT OPEN ALL THREE PHASES OF THE CIRCUIT MAY BE OPENED WHILE OTHER PHASES OR PHASE IS CLOSED,THEN CALLED AS SERIES TYPE OF FAULT. B. SERIES TYPES OF FAULT ARE CLASSIFIED AS:- 1. ONE OPEN CONDUCTOR FAULT. 2. TWO OPEN CONDUCTOR FAULT.
  • 16. VOLTAGE OF THE NEUTRAL :-- β€’ THE VOLTAGE OF THE NEUTRAL WHEN IT S GROUNDED THROUGH SOME IMPEDANCE OR ISOLATED, WILL NOT BE AT GROUND POTENTIAL UNDET UNBALANCED CONDITIONS SUCH AS UNSYMMETRICAL FAULTS. β€’ THE POTENTIAL OF THE NEUTRAL IS GIVEN AS 𝑉𝑛 = βˆ’πΌ 𝑛 𝑍 𝑛 WHERE, 𝑍 𝑛= NEUTRAL GROUNDING IMPEDANCE. NEGATIVE SIGN DENOTES CURENT FLOW FROM THE GROUND TO NEUTRAL OF THE SYSTEM. β€’ FOR 3 PHASE SYSTEM, 𝐼 𝑛= 𝐼 π‘Ž + 𝐼 𝑏 + 𝐼𝑐 = (I π‘Ž1 + I π‘Ž2 + I π‘Ž0)+(ʎ2I π‘Ž1+ ʎI π‘Ž2 + I π‘Ž0)+(ʎ I π‘Ž1+ ʎ2I π‘Ž2 + I π‘Ž0) = 3 𝐼0 THEREFORE, 𝑉𝑛= βˆ’3𝐼 π‘Ž0 𝑍 𝑛 SINCE THE POSITIVE AND NEGATIVE SEQUENCE COMPONENTS ARE ABSENT THROUGH NEUTRAL.
  • 17. SEQUENCE NETWORK EQUATIONS β€’ THESE EQU. ARE DERIVED FOR AN UNLOADED ALTERNATOR WITH NEUTRAL SOLIDLY GROUNDED, ASSUMING BALANCED SYSTEM.
  • 18. 1.POSITIVE SEQUENCE VOLTAGE IS GIVEN BY– π‘‰π‘Ž1 = 𝐸 π‘Ž βˆ’ 𝐼 π‘Ž1 𝑍1 2.NEGATIVE SEQUENCE VOLTAGE IS GIVEN BY- π‘‰π‘Ž2 = 𝐸 π‘Ž2 βˆ’ 𝐼 π‘Ž2 𝑍2 = 0 - 𝐼 π‘Ž2 𝑍2 π‘‰π‘Ž2=βˆ’πΌ π‘Ž2 𝑍2 3.ZERO SEQUENCE VOLTAGES IS GIVEN BY – π‘‰π‘Ž0 = 𝑉𝑛 βˆ’ 𝐼 π‘Ž0 𝑍 𝑔0 =βˆ’3𝐼 π‘Ž0 𝑍 𝑛 βˆ’ 𝐼 π‘Ž0 𝑍 𝑔0 = βˆ’πΌ π‘Ž0(𝑍 𝑔0+3𝑍 𝑛) π‘‰π‘Ž0 = βˆ’πΌ π‘Ž0 𝑍0 where, 𝑍 𝑔0 = 𝑍𝐸𝑅0 𝑆𝐸𝑄. 𝐼𝑀𝑃𝐸𝐷𝐴𝑁𝐢𝐸 𝑂𝐹 𝐺𝐸𝑁. 𝑍 𝑛 = π‘πΈπ‘ˆπ‘‡π‘…π΄πΏ 𝐼𝑀𝑃𝐸𝐷𝐴𝑁𝐢𝐸
  • 19. CONT…. THUS CORRSONDING SEQUENCE NETWORKS FOR THE ULOADED ALTERNATOR ARE SHOWN BELOW ;
  • 20. SINGLE LINE TO GROUND FAULT 1.LET THE FAULT TAKES PLACE ON PHASE A. 2. THE BOUNDARY CONDITIONS ARE- π‘‰π‘Ž = 0 , 𝐼 𝑏 = 0, 𝐼𝑐 = 0
  • 21. THE SEQUENCE NETWORK EQUATIONS ARE :- π‘‰π‘Ž1 = 𝐸 π‘Ž βˆ’ 𝐼 π‘Ž1 𝑍1 π‘‰π‘Ž2=βˆ’πΌ π‘Ž2 𝑍2 π‘‰π‘Ž0 = βˆ’πΌ π‘Ž0 𝑍0 THE SOLUTION FOR THESE EQUATION WILL GIVE SIX UNKNOWNS π‘‰π‘Ž1 , π‘‰π‘Ž2, π‘‰π‘Ž0 AND 𝐼 π‘Ž1 ,𝐼 π‘Ž2 AND 𝐼 π‘Ž0. WE HAVE, I π‘Ž1= 1 3 I π‘Ž + ʎI 𝑏 + ʎ2 I 𝑐 I π‘Ž2= 1 3 I π‘Ž + ʎ2 Ib + ʎI 𝑐 I π‘Ž0= 1 3 I π‘Ž + I 𝑏 + I 𝑐 SUBSTITUTING THE VALUES OF 𝐼 𝑏 AND 𝐼𝑐 IN ABOVE EQUATIONS WE GET, 𝐼 π‘Ž1=𝐼 π‘Ž2= 𝐼 π‘Ž0.= 𝐼 π‘Ž/3 CONT….
  • 22. NOW, SUBSTITUTUING THE VALUES OF π‘‰π‘Ž1 , π‘‰π‘Ž2,π‘‰π‘Ž0FROM THE SEQUENCE NETWORK EQUATION, WE GET, THE EQUATION π‘‰π‘Ž = 0 CAN BE WRITTEN IN TERMS OF SYMMETRICAL COMPONENTS , π‘‰π‘Ž = 0 = π‘‰π‘Ž1 + π‘‰π‘Ž2 + π‘‰π‘Ž0 𝐸 π‘Ž βˆ’ 𝐼 π‘Ž1 𝑍1 βˆ’ 𝐼 π‘Ž2 𝑍2 βˆ’ 𝐼 π‘Ž0 𝑍0=0 SINCE, 𝐼 π‘Ž1 =𝐼 π‘Ž2 = 𝐼 π‘Ž0 WE GET, 𝐸 π‘Ž βˆ’ 𝐼 π‘Ž1 𝑍1 βˆ’ 𝐼 π‘Ž1 𝑍2 βˆ’ 𝐼 π‘Ž1 𝑍0=0 𝐼 π‘Ž1 = 𝐸 π‘Ž 𝑍1 + 𝑍2 + 𝑍0 CONT….
  • 23. IT IS CLEAR THAT, TO SIMULATE A L-G FAULT ALL THE SEQUENCE NETWORKS ARE REQUIRED AND SINCE THE CURRENTS ARE ALL EQUAL IN MAGNITUDE AND PHASE ANGLE, THEREFORE,THE THREE SEQUENCE NETWORKS MUST BE CONNECTED IN SERIES. CONT….
  • 24. IN CASE OF LINE TO GROUND FAULT, 𝐼 𝑛 = 3𝐼 π‘Ž0 IF THE NEUTRAL IS NOT GROUNDED THE ZERO SEQUENCE IMPEDANCE 𝑍0 ,BECOMES INFINITE. THEREFORE, 𝐼 π‘Ž1 = 𝐸 π‘Ž 𝑍1 + 𝑍2 + ∞ = 0 HENCE, 𝐼 π‘Ž1 =𝐼 π‘Ž2 = 𝐼 π‘Ž0=0 THIS MEANS THAT,FOR THIS SYSTEM,THE FAULT CURRENT 𝐼 π‘Ž=0
  • 25. LINE TO LINE FAULT 1.THE LINE TO LINE-LINE FAULT TAKES PLACE ON PHASE B AND C . 2. THE BOUNDARY CONDITIONS ARE :- 𝐼 π‘Ž=0 𝐼 π‘Ž + 𝐼 𝑏 = 0 𝑉𝑏 = 𝑉𝑐
  • 26. FOR LINE-LINE FAULT,THE ZERO SEQUENCE COMPONENT OF CURRENT IS ABSENT AND POSITIVE SEQUENCE COMPONENT OF CURRENT IS EQUAL IN MAGNITUDE BUT OPPOSITE IN PHASE TO NEGATIVE SEQUENCE COMPONENT OF CURRENT, I.E. 𝐼 π‘Ž1 = βˆ’ 𝐼 π‘Ž2 IN LINE-LINE FAULT, ZERO SEQUENCE COMPONENT OF CURRENT IS ABSENT. 𝐼 π‘Ž0=0 ALSO, POSITIVE SEQUENCE COMPONENT OF VOLTAGE EQUALS THE NEGATIVE SEQUENCE COMPONENT OF VOLTAGE.THEREFORE THE SEQUENCE NETWORK ARE CONNECTED IN PARALLEL. π‘‰π‘Ž1 = π‘‰π‘Ž2 𝐸 π‘Ž βˆ’ 𝐼 π‘Ž1 𝑍1=-𝐼 π‘Ž2 𝑍1 = 𝐼 π‘Ž1 𝑍1 𝐼 π‘Ž1= 𝐸 π‘Ž 𝑍1+𝑍2
  • 27. INTERCONECTION OF SEQUENCE NETWORKS FOR L-L FAULT IS SHOWN BELOW:-
  • 28. DOUBLE LINE TO GROUND FAULT 1.DOUBLE LINE TO GROUND FAULT TAKES PLACE ON PHASE B AND C. 2.THE BOUNDARY CONDITIONS AREβ€” 𝐼 π‘Ž=0,𝑉𝑏 =0,𝑉𝐢 = 0 3. THE SEQUENCE NETWORK IS SHOWN BELOW:-
  • 29. IN L-L-G FAULT, POSITIVE SEQUENCE,NEGATIVE SEQUENCE AND ZERO SEQUENCE VOLTAGES ARE SAME. π‘‰π‘Ž1 = π‘‰π‘Ž2=π‘‰π‘Ž3 ALSO, I π‘Ž = I π‘Ž1 + I π‘Ž2 + I π‘Ž0 = 0 SUBSTITUTING VALUES OF I π‘Ž2 AND I π‘Ž0 FROM EQU. I π‘Ž1 βˆ’ 𝐸 π‘Ž βˆ’ 𝐼 π‘Ž1 𝑍1 𝑍2 βˆ’ 𝐸 π‘Ž βˆ’ 𝐼 π‘Ž1 𝑍0 𝑍0 = 0 REARRANGING THE TERMS,WE GET, I π‘Ž1 = 𝐸 π‘Ž 𝑍1 + 𝑍0 𝑍2 𝑍0 + 𝑍2
  • 30. β€’ IT IS CLEAR THAT, ALL THE THREE SEQUENCE NETWORKS ARE REQUIRED TO SIMULATE L-L-G FAULT. β€’ ALSO, THE NEG. AND ZERO SEQ. NETWORKS ARE CONNECTED IN PARALLEL. β€’ THE SEQUENCE NETWORK INTERCONNECTION NETWORK IS SHOWN BELOW:-
  • 31. 3-PHASE FAULT 1. THE BOUNDARY CONDITIONS ARE-- 𝐼 π‘Ž + 𝐼 𝑏 + 𝐼𝑐 = 0 π‘‰π‘Ž = 𝑉𝑏=𝑉𝐢 2. CIRCUIT DIAGRAM:-
  • 32. 3.SINCE, | I π‘Ž|= |I 𝑏| = |I 𝑐| 4.TAKE I π‘Ž AS REFERRENCE. WE GET 𝐼 𝑏 = ʎ2 𝐼 π‘ŽAND 𝐼 𝐢 = ʎ𝐼 π‘Ž 5. USING THE RELATION, I π‘Ž1= 1 3 I π‘Ž + ʎI 𝑏 + ʎ2I 𝑐 I π‘Ž2= 1 3 I π‘Ž + ʎ2 Ib + ʎI 𝑐 I π‘Ž0= 1 3 I π‘Ž + I 𝑏 + I 𝑐 6. WE GET, I π‘Ž1=I π‘Ž , I π‘Ž2=0 AND I π‘Ž0=0 7. IN THIS SYSTEM, ZERO AND NEG.SEQ.COMPONENT OF CURRENT ARE ABSENT. 8. THE POSITIVE SEQUENCE COMPONENT OF CURRENT IS EQUAL TO PHASE CURRENT. 9. SIMILLARY, π‘‰π‘Ž1 = π‘‰π‘Ž2 = π‘‰π‘Ž0 = 0
  • 33. β€’ FROM THE ANALYSIS OF THE VARIOUS FAULTS,THE OBSERVATIONS ARE MADE. 1. THE POSITIVE SEQUENCE CURRENTS ARE PRESENT ON ALL TYPES OF FAULT. 2. NEGATIVE SEQUENCE CURRENTS ARE PRESENT IN ALL UNSYMMETRICAL FAULTS. 3. ZERO SEQUENCE CURRENTS ARE PRESENT WHEN THE NEUTRAL OF THE SYSTEM IS GROUNDED AND THE FAULT ALSO INVOLVES THE GROUND, AND MAGNITUDE OF THE NEUTRAL CURRENT IS EQUAL TO 3𝐼 π‘Ž0.
  • 34. SEQUENCE NETWORK 1. THE ZERO SEQUENCE NETWORK IS SIMILAR TO POSITIVE SEQUENCE NETWORK EXCEPT FOR THE FACT THAT SINCE NO NEGATIVE SEQUENCE VOLTAGES ARE GENENRATED,THE SOURCE OF EMF IS ABSENT. 2. THE GENERAL CIRCUIT :-
  • 35. β€’ THERE ARE TWO SERIES AND SHUNT SWITCHES. β€’ ONE SERIES AND ONE SHUNT SWITCH ARE FOR BOTH THE SIDES SEPARATELY. β€’ THE SERIES SWITCH OF PARTICULAR SIDE IS CLOSED IF IT IS STAR GROUNDED AND THE SHUNT SWITCH IS CLOSED IF THAT SIDE IS DELTA CONNECTED,OTHERWISE OPEN.