SlideShare a Scribd company logo
1 of 64
1 
Prof Chandrabhan sharma
SYMMETRICAL COMPONENTS 
End of this topic, you should be able to: 
- Explain the importance of symmetrical 
component. 
- Construct positive sequence networks for a 
power system. 
- Construct negative sequence networks for a 
power system. 
- Construct zero sequence networks for a 
power system. 
- Use the networks to calculate fault current and voltages 
under SLG, DL, DLG and OC conditions 
2
SYMMETRICAL COMPONENTS 
Symmetrical Components: 
- Theory originally expounded by Stokvis L.G. 
(1915) but was given practical application to 
Electrical Engineering by C.L. Fortescue in 1918. 
- A mathematical model for representing an 
unbalanced system of ‘n’ phasors as ‘n’ systems of 
balanced phasors known as symmetrical 
components. 
N.B. : this is only a model for analysis since symmetrical 
components do not exist in real life 
3
Used for analyzing unbalanced fault conditions in a power system, 
since fault on a balanced 3 system is usually NOT symmetrical. 
They are usually: 
- SLG (Single Line – Ground) 
- DL (Double Line or Line - Line) 
- DLG (Double Line – Ground) 
- Open conductor 
4
If either SLG, DLG, LL, OC occur then 
- they will cause currents and voltages to be of 
unequal magnitude, and 
- the usual 3 phasor diagram is no longer displaced 
by 120apart from each other. 
It is imperative that values of short circuit currents be obtained 
for these types of faults since the information is necessary for: 
(a) Ordering protective equipment 
(b) the determination of protective relay settings 
(b) transient stability studies for interconnected systems 
5
THEORY 
The theory postulates that a 3 unbalanced system of voltage and 
current phasors can be resolved into three balanced system of phasors. 
These are : 
A positive phase sequence system 
- comprising three phasors of equal magnitude 
- displaced by 120 from each other 
- and with the same phase sequence as the original phasors. 
6
A negative phase sequence system 
- comprising three phasors of equal magnitude 
- displaced by 120 from each other 
- but with a phase sequence opposite to the original phasors. 
A zero phase sequence system 
- comprising three phasors equal in magnitude and phase, 
- and revolving in the positive phase rotation. 
7
Equivalent unbalanced system 
B1 
   
= + + 
B 
Y 
R R1 
Y1 
R2 
Y2 B2 
Y0 
B0 
R0 
120 
120 
120 
120 
120 120 
 
 
 
  
 
Faulted System +ve sequence -ve sequence zero sequence 
From the theory: 
VR = VR1 + VR2 + VR0………………(1) 
VY = VY1 + VY2 + VY0………………(2) 
VB = VB1 + VB2 + VB0……………….(3) 
8
For a 3 system, the theory states that: 
R1 Y1 B1 V  V  V 
R2 Y2 B2 R0 Y0 B0 V V V and V V V 
Also, 
    
The ‘a’ operator (or ‘h’) 
Since we will be dealing with three phasors displaced by 120, 
it would be helpful/convenient to define a new operator ‘a’ such 
that: 
a  1120 = ej2/3 = - 0.5 + j0.866 
9
And: 
a2 = 1240 = ej4/3 = - 0.5 – j0.866, and 
a3 = 1360 = 1 + j0 
Note, unlike the ‘j’ operator, -a ≠ 1-120 
Recall -j = 1-90  = (j2)(j) = j3 = 1-90  
but -a = (j2)(a) = 1(120 + 180) = 1300  = 160  
Note also a2 + a + 1 = 0 = a3 + a2 + a 
10
From the positive sequence diagram we have: 
VY1 = a2 VR1……………………(4) 
VB1 = a VR1 …………………...(5) 
From the negative sequence, 
VY2 = a VR2…………………….(6) 
VB2 = a2 VR2 ……………………(7) 
And from the zero sequence, 
VR0 = VY0 = VB0 ………………..(8) 
11
Substitute eqs. 4-8 into eqs. 1-3 we obtain: 
VR = VR0 +VR1 + VR2 
VY = VR0 + a2 VR1 + aVR2 
VB = VR0 + aVR1 + a2 VR2 
Written in matrix : 
 
 
...........................(9) 
V 
R0 
V 
R1 
V 
1 1 1 
 
 
 
 
1 a a 
 
1 a a 
V 
R 
V 
Y 
V 
R2 
2 
2 
B 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
12
1 1 1 
 
 
 
1 a a 
 
1 a a 
T 
Let, 
2 
2 
 
 
 
 
 
 
 
'T' is known as the symmetrical component transformation matrix 
1 1 1 
 
 
-1 2 
1 a a 
 
1 a a 
1 
3 
T 
2 
 
 
 
 
 
 
 
 
13 
From matrix inversion
Applying T-1 to eq. (9): 
 
 
.............................1(0) 
V 
R 
V 
Y 
V 
1 1 1 
 
 
1 a a 
 
1 a a 
1 
3 
V 
R0 
V 
R1 
V 
B 
2 
2 
R2 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
1 
  
  
V a V aV ............................1(3) 
3 
   
R0 R Y B 
1 
   
1 
V 
V aV a V ............................1(2) 
3 
V 
V V V .................................(11) 
3 
V 
OR 
Y B 
2 
R2 R 
B 
2 
R1 R Y 
   
14
Similarly: 
 
 
.............................1(4) 
I 
I 
I 
1 1 1 
 
 
1 a a 
 
1 a a 
1 
3 
I 
I 
I 
R 
Y 
B 
2 
2 
R0 
R1 
R2 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
1 
  
  
I a I aI ............................1(7) 
3 
   
R0 R Y B 
1 
   
1 
I 
I aI a I ............................1(6) 
3 
I 
I I I .................................(15) 
3 
I 
OR 
Y B 
2 
R2 R 
B 
2 
R1 R Y 
   
15
Analyzing equations (11) and (15) ….. 
(11) → for balanced 3 system VR +VY + VB = 0 
Balanced  voltage magnitude and angle normal 
(current unbalanced) 
(15) → IR + IY + IB = IN 
 IN = 3IR0 
 if the system is ungrounded  IN = 0 = IR0 
→ no zero sequence currents 
Hence  connected loads have no zero sequence currents. 
16
Example: 
(Higher Electrical Engineering – Sheppard, Morton and Spence) 
The currents flowing in an unbalanced 4-wire system are 
IR = 1000 A; IY = 200-90 A ; IB = 100120 A 
Find the +ve, -ve and zero sequence components of these currents. 
17
Solution: 
 
 
 
 
 
R0 
R1 
1 
I 
I 
  
   
I I I 
R0 R Y B 
 
 
 
 
 
 
 
 
 
1 1 1 
 
 
1 a a 
 
R 
Y 
I 
I 
  
1 
3 
1 
         
100 0 200 90 100 120 
3 
From which 
    
I 41.3 66.2 A 
I 
R0 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
B 
2 
2 
R2 
I 
1 a a 
3 
I 
Re call : 
18
  
1 
   
I aI a I 
3 
  
             
100 0 (1.0 120 ).(200 90 ) (1.0 240 ).(100 120 ) 
3 
I 128.79 15 A 
1 
Also, 
I 
R1 
B 
2 
R1 R Y 
    
2 
     
R2 R Y B 
  
              
    
R2 
And, 
1 
I I a I aI 
3 
1 
100 0 (1.0 240 ).(200 90 ) (1.0 120 ).(100 120 ) 
3 
I 41.3 174 A 
19
SEQUENCE NETWORKS 
Since 
- component currents of one phase sequence 
cause 
- voltage drops of like sequence only 
and 
- independent of the other sequences (in a 
balanced system) 
- currents of any one sequence may be 
considered to flow in an independent 
network composed of impedances to 
the current of that sequence. 
20
SEQUENCE NETWORKS 
The single phase equivalent circuit composed of the 
impedances to current of any one sequence only is called the 
sequence network for that particular sequence. 
In static symmetrical systems, conversion of a +ve sequence to 
a –ve sequence network is accomplished by changing only the 
impedances representing rotating machinery and by omitting 
any generated e.m.fs 
21
Synchronous Machines: 
- +ve sequence ≠ -ve sequence 
- Xd”, Xd’ and Xd are +ve sequence 
- the generated e.m.fs are +ve sequence only 
- the ref. bus for +ve and –ve sequence n/w is the 
generator neutral 
- the ref. Bus for the zero sequence n/w is the 
ground of the generator or earth 
- there are no generated e.m.fs in the –ve and zero 
sequence n/w 
22
Positive Sequence Networks: 
- For a given power system the positive sequence network shows 
all the paths for the flow of positive sequence currents in the 
system. 
- The one-line diagram of the system is converted to an 
impedance diagram that shows the equivalent circuit of each 
component under balanced operating conditions 
- Each generator in the system is represented by a source voltage 
in series with the appropriate reactance and resistance. 
- To simplify the calculations, all resistance and the 
magnetizing current for each transformer are neglected. 
23
Positive Sequencenetwork of Synchronous generator: 
24
Negative Sequence Networks: 
- Three-phase generators and motors have only positive 
sequence generated voltages. Thus, the negative sequence 
network model will not contain voltage sources associated 
with rotating machinery. 
- The negative sequence impedance will in general be 
different from the positive sequence values. 
- For static devices such as transmission lines and 
transformers, the negative sequence impedances have the 
same values as the corresponding positive sequence 
impedances. 
25
Negative Sequence network of Synchronous generator: 
26
Zero Sequence Networks: 
- The zero sequence network of a system depends on the 
nature of the connections of the three-phase windings for 
each of the system’s components. 
27
Zero Sequence Networks: 
28
Zero Sequence Networks: 
29
Zero Sequence Networks: 
30
Lines and cables: 
- +ve and –ve sequence impedances are the 
normal balanced values. 
- zero sequence impedances depends on the nature 
of the return path through earth. 
The following factors can be used in the absence of 
manufacturer data: 
Cable Zero Seq. Impedance 
3 – core Z0 =3Z1 to 5Z1 
1 – core Z0 =1.5Z1 
31
Single Circuit Double Circuit 
No ground wire  Z0 =3.5Z1 Z0 = 5.5Z1 
Steel ground wire  Z0 =3.5Z1 Z0 =5Z1 
Non-metallic ground wire 
 Z0 =3.5Z1 Z0 =3Z1 
Lines: 
32
Transformers: 
- +ve and –ve sequence impedances are the same i.e. 
(Z1 = Z2) 
- zero sequence cct depends on whether a return path exists 
through which a completed circuit can be provided 
Recall the equivalent cct for a transformer is: 
33
The equivalent circuit becomes: 
For +ve and –ve sequence Z1 = Z2 
For zero sequence the equivalent circuit changes depending on 
the configuration of the transformer. 
34
Zero Sequence Network (Transformer) 
- Close ‘a’ contact whenever zero sequence currents 
can flow, i.e. earth connection exists. 
- Close ‘b’ contact whenever zero sequence currents 
can circulate, i.e.  connection. 
- circuit is left open when neither condition exists, 
for example unearthed star connection. 
35
Transformer zero sequence models 
36
Transformer zero sequence models 
37
Static Loads 
38
Static Loads 
39
The A-phase of the unloaded generator shown below is subjected 
to a SLG fault. The pre-faulted L-N voltage of the generator is EA 
Volts. The generator has positive, negative and zero sequence 
impedance of Z1, Z2 and Zo respectively. Find the fault current 
and phase voltages under the fault condition. 
40 
Line to Ground Fault (SLG)
Conditions under SLG fault: 
VA = 0 ; and IB = IC = 0 (i.e. neglecting load currents) 
 
 
 
 
 
 
 
 
 
 
I 
I  
0 
 
 
 
 
 
 
1 1 1 
 
 
1 a a 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
B 
I 0 
1 a a 
1 
3 
I 
I 
I 
C 
A 
2 
2 
A0 
A1 
A2 
1 
A0 A1 A2 A I 
3 
I  I  I  
Since IA1 = IA2 = IA0 then the seq. n/ws must be connected in series 
41
From the interconnected networks 
42 
A 
E 
1 
A0 A1 A2 A Z Z Z 
1 2 0 
I 
3 
I I I 
  
    
Also 
VA = VA0 +VA1 + VA2 
VB= VA0 + a2 VA1 + aVA2 
VC= VA0 + aVA1 + a2 VA2 
Where: 
VA1= EA - IA1 Z1 
VA2= 0 - IA2 Z2 
VA0= 0 - IA0 Z0
A 3-phase star connected solidly earthed, unloaded generator has it’s A-phase 
subjected to a solidly grounded earth fault. Given that the pre-faulted 
L-N voltage of the generator is 100 V and Z1 = j1.0Ω, Z2 = j0.5Ω 
and Zo = j0.1Ω, calculate the fault currents developed and the L-L 
voltages attained due to a fault. 
43 
Example
100 
j1.6 
From analysis of the ckt we obtain 
E 
A 
A0 A1 A2 A  
Z Z Z 
1 
I 
3 
I I I 
  
1 2 0 
    
     
I I I j62.5 A 
A0 A1 A2 
      
I I 3( j62.5) A j187.5 A 
F A 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
we also know that 
 
1 1 1 
 
 
 
 
1 a a 
 
 
 
 
 
 
 
 
 
 
 
V 
A0 
V 
A1 
A2 
2 
2 
V 
A 
V 
B 
C 
V 
1 a a 
V 
44
 VA = VA0 +VA1 + VA2………………(1) 
VB= VA0 + a2 VA1 + aVA2…………..(2) 
VC= VA0 + aVA1 + a2 VA2…………...(3) 
From the ckt: VA1= EA - IA1 Z1= 100 – [(-j62.5)(j1.0)] = 37.5 V/gn 
Similarly, 
VA2= 0 - IA2 Z2 = - (-j62.5) (j0.5) = -31.25 V/gn 
And, 
VA0= 0 – IA0 Z0 = - (-j62.5) (j0.1) = -6.25 V/gn 
45
Substitute V1, V2 and V0 into equations (1), (2) and (3) 
VA = VA0 +VA1 + VA2 = 0 
And 
VB= VA0 + a2 VA1 + aVA2 = - 9.37 – j59.5 = 60.23-98.9 V 
VC= VA0 + aVA1 + a2 VA2 = - 9.37 + j59.5 = 60.23 98.9 V 
Also, 
VAB= VA - VB = 9.37 + j59.5 = 60.23 81.1 V 
VBC= VB - VC = - j119 = 119 -90 V 
VCA= VC - VA = - 9.37 + j59.5 = 60.23 98.9 V 
46
DOUBLE LINE FAULT (DL) 
Condition when fault occur 
IA = 0 ; IB + IC = 0 ; and phase voltage VB = VC 
47
1 
1 1 1 
 
 
1 a a 
1 
 
 
 
 
  
  
 B B  
A0 
A1 
I 
I 
 
 
 
 
 
    
A0 B B 
2 
A2 
B 
2 
1 
  
A1 B 
I  
0 
B 
A 
I 
C B 
2 
2 
A2 
1 
0 a I - aI 
3 
I 
 
 
 
0 aI - a I and 
3 
I 
0 I - I 0; 
3 
I 
I I 
1 a a 
3 
I 
  
 
 
 
 
 
 
 
  
 
 
 
 
 
 
 
 
 
 
1 
a - a 2 
 I 
3 
A0 A1 A2     
I 0 a nd I - I B 
48 
j 
But a - a j1.732 j 3 I - I A1 A2 B 
I 
3 
2      
Since IA0 = 0 then the zero sequence ckt is open
Equivalent sequence ckt becomes 
From which we obtain 
E 
A 
A1  
Z Z 
I 
1 2 
 
IA1 = - j66.67 
IA2 = j66.67 
- 114.94 A 
 
A1 B 
- j 66.67 
    
j0.58 
I - I 
j 
I 
3 
But I 
B C 
49
Also, 
VA1 = EA - IA1Z1 = 100 - (-j66.67)(j1.0) 
= 100 - 66.67 
= 33.33 V/gn 
Therefore, VA1 = VA2 = 33.33 V/gn 
Now 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
1 1 1 
 
 
 
 
1 a a 
 
 
 
 
 
 
 
 
 
 
 
 
V 
A0 
V 
A1 
A2 
2 
2 
V 
A 
V 
B 
C 
V 
1 a a 
V 
50
 VA =VA1 + VA2 = 66.67 V/gn 
VB =VA1(a2 + a) = VC 
But a2 + a = -1  VB = -33.33 V/gn = VC 
51
DOUBLE LINE TO GROUND FAULT (DLG) 
Condition when fault occur 
IA = 0 ; VB = VC = 0 ; IB + IC = IF 
52
From inspection IA = 0 and VB = VC 
 
 
 
 
 
 
 
 
 
 
V 
V  
0 
 
 
 
 
 
 
1 1 1 
 
 
1 a a 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
B 
V 0 
1 a a 
1 
3 
V 
0 
V 
1 
V 
C 
A 
2 
2 
2 
1 
0 1 2 A V 
3 
V  V  V  
Hence, the sequence networks are in parallel 
53
Since Z2 //Z0 then the circuit reduces to: 
Z Z 
2 0 
P Z Z 
2 0 
where Z 
 
 
A 
E 
1 Z Z 
1 P 
I 
 
  
54 
2 
Z 
 
 
where I  
0 I 
Z Z 
Z 
 
 
I and  
2 I 
1 
0 
Z Z 
0 2 
 
 
 
 
 
1 
0 2 
 
 
 
 

Example: 
The diagram shows two generators connected to a transmission system 
comprising two parallel 66kV transmission lines via transformers. The data of 
this system is given below 
GA and GB – 13.8kV, 100 MVA, Z1 = j0.15, Z2 = j0.1 and Z0 = j0.03 (all p.u) 
TFA – 13.8/66kV, 100 MVA, Z1 = Z2 = Z0 = j0.15 p.u 
TFB – 13.8/66kV, 100 MVA, Z1 = Z2 = Z0 = j0.1 p.u 
Each Transmission Line - Z1 = j0.4, Z2 = j0.4 and Z0 = j0.7 (all p.u) 
All star points are solidly earthed, except that of generator B which is 
unearthed. All p.u. values are on the 100 MVA base. Calculate the fault current 
for a DLG fault at the feeder terminals of transformer A. 
55
Soln 
+ ve 
- ve 
zero 
56
 
 
+ ve seq n/w 
reduces to 
- ve seq n/w 
reduces to 
zero seq n/w 
reduces to 
57
For DLG fault, the three sequence networks are connected in 
parallel (as seen earlier). 
 
j3.8 p.u. 
1 
I pu 
1   
j(0.18 0.083) 
V 
Z 
 
  
j2.05 p.u. 
j0.18 
 
 
2 1    
j0.334 
(j3.8) 
Z 
0 
Z Z 
I I 
0 2 
 
 
 
 
 
 
 
58
j1.75 p.u. 
j0.154 
 
 
0 1    
j0.334 
(j3.8) 
Z 
2 
Z Z 
I I 
0 2 
 
 
 
 
 
 
  
I 
I 
A 
B 
 
 
 
 
 
 
 
 
I I I I j1.75 ( j3.8 ) j2.05 0 A 0 1 2          
I 
0 
I 
I 
1 1 1 
 
1 a a 
 
1 a a 
I 
Substitute the seq current values in the matrix 
1 
2 
2 
2 
C 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
2 
I  I  a I  
aIB 0 
1 2 
           
j1.75 (1 240 )(3.8 90 ) (1 120 )(2.05 90 ) 
   
5.72 152.7 p.u. 
59
874.8A 
100 x 10 
pu    
3 x 66 x 10 
MVA 
3V 
But I 
3 
6 
base 
base 
I 874.8 (5.72 152.7 ) 5003.9 152.7 A B        
Similarly, I 5003.9 27.37 A 
And I  I  I  
j5.26 p.u. 
F B C 
I j4601.5 A 
or 
F 
C 
 
   
60
One line Open Circuit 
61 
Under this condition consider the elemental values of V. 
From inspection IA = 0 and VB = VC
Applying these conditions: 
 
 
 
 
 
 
 
 
 
 
 
V 
  
V 0 
B 
  
 
 
 
 
 
1 1 1 
 
 
1 a a 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
V 0 
1 a a 
1 
3 
V 
0 
V 
1 
V 
C 
A 
2 
2 
2 
1 
0 1 2 A V 
3 
V  V  V  
Hence, the sequence networks are in parallel as shown below: 
62
From the example before: EA = 1000 
and Z1 = j1.0 ; Z2 = j0.5 ; Z0 = j0.1 
Since Z2 //Z0 then the circuit reduces to: 
j0.083 
(j0.5)(j0. 1) 
P   
j0.6 
Z Z 
2 0 
Z Z 
where Z 
 
2 0 
 
j92.31 
100 
1   
1 j0.083 
E 
A 
Z Z 
I 
1 P 
 
 
 
  
     
V E - I Z 100 [( j92.31)(j1.0)] 
   
2 0 
1 A 1 1 
7.69 V/gn V V 
63
j15.38 A 
7.69 
2      
j0.5 
V 
Z 
Also, I 
2 
2 
j76.9 A 
7.69 
0      
j0.1 
V 
Z 
And, I 
0 
0 
But, 3V1 = VA  VA = 23.07 V/gn 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
1 1 1 
 
 
 
 
1 a a 
 
 
 
 
 
 
 
 
 
 
 
 
 
I 
 
I 
 
0 
I 
I 
1 
2 
2 
2 
A 
B 
C 
B C 
I 
1 a a 
I 
To determine I and I we use: 
I I I I 0 A 0 1 2      
Also I I a (-j92.31) a(j15.38) - 93.3 j115.4 2 
B 0       
And I I a(-j92.31) a (j15.38) 93.3 j115.4 2 
C 0       
64

More Related Content

What's hot

Symmetrical components
Symmetrical componentsSymmetrical components
Symmetrical componentsSirat Mahmood
 
Power System Analysis and Design
Power System Analysis and DesignPower System Analysis and Design
Power System Analysis and DesignZainUlAbdeen41
 
Single and three phase Transformers
Single and three phase TransformersSingle and three phase Transformers
Single and three phase TransformersMohammed Waris Senan
 
Fundamentals of power system
Fundamentals of power systemFundamentals of power system
Fundamentals of power systemBalaram Das
 
Ee 1351 power system analysis
Ee 1351 power system analysisEe 1351 power system analysis
Ee 1351 power system analysisHari Kumar
 
ANALYSIS OF FLYBACK CONVERTER
ANALYSIS OF FLYBACK CONVERTERANALYSIS OF FLYBACK CONVERTER
ANALYSIS OF FLYBACK CONVERTERshiv kapil
 
Symmetrical Fault Analysis
Symmetrical Fault AnalysisSymmetrical Fault Analysis
Symmetrical Fault AnalysisSANTOSH GADEKAR
 
Power System Analysis!
Power System Analysis!Power System Analysis!
Power System Analysis!PRABHAHARAN429
 
Per unit representation
Per unit representationPer unit representation
Per unit representationMd. Rimon Mia
 
Newton Raphson
Newton RaphsonNewton Raphson
Newton RaphsonAisu
 
Symmertical components
Symmertical componentsSymmertical components
Symmertical componentsUday Wankar
 
Borrador de clases Sistemas de Potencia versión 5
Borrador de clases Sistemas de Potencia versión 5Borrador de clases Sistemas de Potencia versión 5
Borrador de clases Sistemas de Potencia versión 5Julio Molina
 
Unit 2 Reactive Power Management
Unit 2 Reactive Power ManagementUnit 2 Reactive Power Management
Unit 2 Reactive Power ManagementSANTOSH GADEKAR
 

What's hot (20)

Symmetrical components
Symmetrical componentsSymmetrical components
Symmetrical components
 
Power System Analysis and Design
Power System Analysis and DesignPower System Analysis and Design
Power System Analysis and Design
 
Fault analysis using z bus
Fault analysis using z busFault analysis using z bus
Fault analysis using z bus
 
Transformer
TransformerTransformer
Transformer
 
Single and three phase Transformers
Single and three phase TransformersSingle and three phase Transformers
Single and three phase Transformers
 
Fundamentals of power system
Fundamentals of power systemFundamentals of power system
Fundamentals of power system
 
Ee 1351 power system analysis
Ee 1351 power system analysisEe 1351 power system analysis
Ee 1351 power system analysis
 
ANALYSIS OF FLYBACK CONVERTER
ANALYSIS OF FLYBACK CONVERTERANALYSIS OF FLYBACK CONVERTER
ANALYSIS OF FLYBACK CONVERTER
 
Symmetrical Fault Analysis
Symmetrical Fault AnalysisSymmetrical Fault Analysis
Symmetrical Fault Analysis
 
A.c circuits
A.c circuitsA.c circuits
A.c circuits
 
Power System Analysis!
Power System Analysis!Power System Analysis!
Power System Analysis!
 
Per unit representation
Per unit representationPer unit representation
Per unit representation
 
Newton Raphson
Newton RaphsonNewton Raphson
Newton Raphson
 
Load flow studies
Load flow studiesLoad flow studies
Load flow studies
 
Symmertical components
Symmertical componentsSymmertical components
Symmertical components
 
Unsymmetrical Fault
Unsymmetrical FaultUnsymmetrical Fault
Unsymmetrical Fault
 
Amplidyne
AmplidyneAmplidyne
Amplidyne
 
Lecture 02.pptx
Lecture 02.pptxLecture 02.pptx
Lecture 02.pptx
 
Borrador de clases Sistemas de Potencia versión 5
Borrador de clases Sistemas de Potencia versión 5Borrador de clases Sistemas de Potencia versión 5
Borrador de clases Sistemas de Potencia versión 5
 
Unit 2 Reactive Power Management
Unit 2 Reactive Power ManagementUnit 2 Reactive Power Management
Unit 2 Reactive Power Management
 

Viewers also liked (11)

ECNG 6509 Switchgear Technology
ECNG 6509    Switchgear TechnologyECNG 6509    Switchgear Technology
ECNG 6509 Switchgear Technology
 
ECNG 6509 Transformer Technology
ECNG 6509  Transformer TechnologyECNG 6509  Transformer Technology
ECNG 6509 Transformer Technology
 
ECNG 3013 A
ECNG 3013 AECNG 3013 A
ECNG 3013 A
 
ECNH 3015 Examples of PU system
ECNH 3015  Examples of PU systemECNH 3015  Examples of PU system
ECNH 3015 Examples of PU system
 
ECNG 3015 chapter 2 - pu system
ECNG 3015  chapter 2 - pu systemECNG 3015  chapter 2 - pu system
ECNG 3015 chapter 2 - pu system
 
Circuit breaker arc phenomena
Circuit breaker arc phenomenaCircuit breaker arc phenomena
Circuit breaker arc phenomena
 
ECNG 3013 C
ECNG 3013 CECNG 3013 C
ECNG 3013 C
 
ECNG 3013 B
ECNG 3013 BECNG 3013 B
ECNG 3013 B
 
ECNG 3013 E
ECNG 3013 EECNG 3013 E
ECNG 3013 E
 
ECNG 3013 D
ECNG 3013 DECNG 3013 D
ECNG 3013 D
 
ECNG 3015 chapter 1 - Basics
ECNG 3015  chapter 1 - BasicsECNG 3015  chapter 1 - Basics
ECNG 3015 chapter 1 - Basics
 

Similar to ECNG 3015 Industrial and Commercial Electrical Systems

Three phase circuits
Three phase circuitsThree phase circuits
Three phase circuitsEkeeda
 
Design And Simulation Of Distributed Statcom Controller For Power Factor Impr...
Design And Simulation Of Distributed Statcom Controller For Power Factor Impr...Design And Simulation Of Distributed Statcom Controller For Power Factor Impr...
Design And Simulation Of Distributed Statcom Controller For Power Factor Impr...IJERA Editor
 
Distance Algorithm for Transmission Line with Mid-Point Connected STATCOM
Distance Algorithm for Transmission Line with Mid-Point Connected STATCOMDistance Algorithm for Transmission Line with Mid-Point Connected STATCOM
Distance Algorithm for Transmission Line with Mid-Point Connected STATCOMIRJET Journal
 
4.three phase circuits
4.three phase circuits 4.three phase circuits
4.three phase circuits Ekeeda
 
power system analysis lecture 1
power system analysis lecture 1power system analysis lecture 1
power system analysis lecture 1Audih Alfaoury
 
Lecture no 4 power system analysis elc353 et313
Lecture no 4 power system analysis elc353 et313Lecture no 4 power system analysis elc353 et313
Lecture no 4 power system analysis elc353 et313Fazal Ur Rehman
 
BEF43303_-_201620171_W5 Analysis of fault.pdf
BEF43303_-_201620171_W5 Analysis of fault.pdfBEF43303_-_201620171_W5 Analysis of fault.pdf
BEF43303_-_201620171_W5 Analysis of fault.pdfLiewChiaPing
 
Power system Analysis By Sharif Kakar
Power system Analysis   By Sharif KakarPower system Analysis   By Sharif Kakar
Power system Analysis By Sharif KakarSharif Ullah
 
06 -synchronous_machine_parameter_measurement
06  -synchronous_machine_parameter_measurement06  -synchronous_machine_parameter_measurement
06 -synchronous_machine_parameter_measurementEllixies Fair
 
Electrical Circuit.pdf
Electrical Circuit.pdfElectrical Circuit.pdf
Electrical Circuit.pdfssuserf798a5
 
UNIT-III complex reactive three phase.ppt
UNIT-III complex reactive three phase.pptUNIT-III complex reactive three phase.ppt
UNIT-III complex reactive three phase.pptAbinaya Saraswathy T
 
Lecture Notes ELE A6.pdf
Lecture Notes ELE A6.pdfLecture Notes ELE A6.pdf
Lecture Notes ELE A6.pdfRubaiyatJaky
 
Lecture Notes ELE A6.pdf
Lecture Notes ELE A6.pdfLecture Notes ELE A6.pdf
Lecture Notes ELE A6.pdfRubaiyatJaky
 
Ee423 fault analysis_notes
Ee423  fault analysis_notesEe423  fault analysis_notes
Ee423 fault analysis_notesAcot Benard
 

Similar to ECNG 3015 Industrial and Commercial Electrical Systems (20)

Three phase circuits
Three phase circuitsThree phase circuits
Three phase circuits
 
Design And Simulation Of Distributed Statcom Controller For Power Factor Impr...
Design And Simulation Of Distributed Statcom Controller For Power Factor Impr...Design And Simulation Of Distributed Statcom Controller For Power Factor Impr...
Design And Simulation Of Distributed Statcom Controller For Power Factor Impr...
 
UNIT-3-PPT (2).pptx
UNIT-3-PPT (2).pptxUNIT-3-PPT (2).pptx
UNIT-3-PPT (2).pptx
 
Distance Algorithm for Transmission Line with Mid-Point Connected STATCOM
Distance Algorithm for Transmission Line with Mid-Point Connected STATCOMDistance Algorithm for Transmission Line with Mid-Point Connected STATCOM
Distance Algorithm for Transmission Line with Mid-Point Connected STATCOM
 
AC CIRCUIT
AC CIRCUITAC CIRCUIT
AC CIRCUIT
 
4.three phase circuits
4.three phase circuits 4.three phase circuits
4.three phase circuits
 
Lec 20.pptx
Lec 20.pptxLec 20.pptx
Lec 20.pptx
 
power system analysis lecture 1
power system analysis lecture 1power system analysis lecture 1
power system analysis lecture 1
 
Lecture no 4 power system analysis elc353 et313
Lecture no 4 power system analysis elc353 et313Lecture no 4 power system analysis elc353 et313
Lecture no 4 power system analysis elc353 et313
 
BEF43303_-_201620171_W5 Analysis of fault.pdf
BEF43303_-_201620171_W5 Analysis of fault.pdfBEF43303_-_201620171_W5 Analysis of fault.pdf
BEF43303_-_201620171_W5 Analysis of fault.pdf
 
Lecture1
Lecture1Lecture1
Lecture1
 
Power system Analysis By Sharif Kakar
Power system Analysis   By Sharif KakarPower system Analysis   By Sharif Kakar
Power system Analysis By Sharif Kakar
 
06 -synchronous_machine_parameter_measurement
06  -synchronous_machine_parameter_measurement06  -synchronous_machine_parameter_measurement
06 -synchronous_machine_parameter_measurement
 
Electrical Circuit.pdf
Electrical Circuit.pdfElectrical Circuit.pdf
Electrical Circuit.pdf
 
Measurement of various line and phase quantities for a three phase ac circuit
Measurement of various line and phase quantities for a three phase ac circuitMeasurement of various line and phase quantities for a three phase ac circuit
Measurement of various line and phase quantities for a three phase ac circuit
 
3 phase ac circuit
3 phase ac circuit3 phase ac circuit
3 phase ac circuit
 
UNIT-III complex reactive three phase.ppt
UNIT-III complex reactive three phase.pptUNIT-III complex reactive three phase.ppt
UNIT-III complex reactive three phase.ppt
 
Lecture Notes ELE A6.pdf
Lecture Notes ELE A6.pdfLecture Notes ELE A6.pdf
Lecture Notes ELE A6.pdf
 
Lecture Notes ELE A6.pdf
Lecture Notes ELE A6.pdfLecture Notes ELE A6.pdf
Lecture Notes ELE A6.pdf
 
Ee423 fault analysis_notes
Ee423  fault analysis_notesEe423  fault analysis_notes
Ee423 fault analysis_notes
 

More from Chandrabhan Sharma

More from Chandrabhan Sharma (8)

ECNG 3015 chapter 6 - switchgear technology
ECNG 3015  chapter 6 - switchgear technologyECNG 3015  chapter 6 - switchgear technology
ECNG 3015 chapter 6 - switchgear technology
 
Ices chapter 8 - illumination engineering
Ices   chapter 8 - illumination engineeringIces   chapter 8 - illumination engineering
Ices chapter 8 - illumination engineering
 
ECNG 3015 - Overcurrent Protection
ECNG 3015 - Overcurrent ProtectionECNG 3015 - Overcurrent Protection
ECNG 3015 - Overcurrent Protection
 
ECNG 3015 Power System Protection
ECNG 3015    Power System ProtectionECNG 3015    Power System Protection
ECNG 3015 Power System Protection
 
ECNG 6503 #4
ECNG 6503 #4ECNG 6503 #4
ECNG 6503 #4
 
ECNG 6503 # 3
ECNG 6503 # 3ECNG 6503 # 3
ECNG 6503 # 3
 
ECNG 6503 #2
ECNG 6503  #2ECNG 6503  #2
ECNG 6503 #2
 
ECNG 6503 #1
ECNG 6503 #1 ECNG 6503 #1
ECNG 6503 #1
 

Recently uploaded

Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdfKamal Acharya
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesPrabhanshu Chaturvedi
 

Recently uploaded (20)

Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 

ECNG 3015 Industrial and Commercial Electrical Systems

  • 2. SYMMETRICAL COMPONENTS End of this topic, you should be able to: - Explain the importance of symmetrical component. - Construct positive sequence networks for a power system. - Construct negative sequence networks for a power system. - Construct zero sequence networks for a power system. - Use the networks to calculate fault current and voltages under SLG, DL, DLG and OC conditions 2
  • 3. SYMMETRICAL COMPONENTS Symmetrical Components: - Theory originally expounded by Stokvis L.G. (1915) but was given practical application to Electrical Engineering by C.L. Fortescue in 1918. - A mathematical model for representing an unbalanced system of ‘n’ phasors as ‘n’ systems of balanced phasors known as symmetrical components. N.B. : this is only a model for analysis since symmetrical components do not exist in real life 3
  • 4. Used for analyzing unbalanced fault conditions in a power system, since fault on a balanced 3 system is usually NOT symmetrical. They are usually: - SLG (Single Line – Ground) - DL (Double Line or Line - Line) - DLG (Double Line – Ground) - Open conductor 4
  • 5. If either SLG, DLG, LL, OC occur then - they will cause currents and voltages to be of unequal magnitude, and - the usual 3 phasor diagram is no longer displaced by 120apart from each other. It is imperative that values of short circuit currents be obtained for these types of faults since the information is necessary for: (a) Ordering protective equipment (b) the determination of protective relay settings (b) transient stability studies for interconnected systems 5
  • 6. THEORY The theory postulates that a 3 unbalanced system of voltage and current phasors can be resolved into three balanced system of phasors. These are : A positive phase sequence system - comprising three phasors of equal magnitude - displaced by 120 from each other - and with the same phase sequence as the original phasors. 6
  • 7. A negative phase sequence system - comprising three phasors of equal magnitude - displaced by 120 from each other - but with a phase sequence opposite to the original phasors. A zero phase sequence system - comprising three phasors equal in magnitude and phase, - and revolving in the positive phase rotation. 7
  • 8. Equivalent unbalanced system B1    = + + B Y R R1 Y1 R2 Y2 B2 Y0 B0 R0 120 120 120 120 120 120       Faulted System +ve sequence -ve sequence zero sequence From the theory: VR = VR1 + VR2 + VR0………………(1) VY = VY1 + VY2 + VY0………………(2) VB = VB1 + VB2 + VB0……………….(3) 8
  • 9. For a 3 system, the theory states that: R1 Y1 B1 V  V  V R2 Y2 B2 R0 Y0 B0 V V V and V V V Also,     The ‘a’ operator (or ‘h’) Since we will be dealing with three phasors displaced by 120, it would be helpful/convenient to define a new operator ‘a’ such that: a  1120 = ej2/3 = - 0.5 + j0.866 9
  • 10. And: a2 = 1240 = ej4/3 = - 0.5 – j0.866, and a3 = 1360 = 1 + j0 Note, unlike the ‘j’ operator, -a ≠ 1-120 Recall -j = 1-90  = (j2)(j) = j3 = 1-90  but -a = (j2)(a) = 1(120 + 180) = 1300  = 160  Note also a2 + a + 1 = 0 = a3 + a2 + a 10
  • 11. From the positive sequence diagram we have: VY1 = a2 VR1……………………(4) VB1 = a VR1 …………………...(5) From the negative sequence, VY2 = a VR2…………………….(6) VB2 = a2 VR2 ……………………(7) And from the zero sequence, VR0 = VY0 = VB0 ………………..(8) 11
  • 12. Substitute eqs. 4-8 into eqs. 1-3 we obtain: VR = VR0 +VR1 + VR2 VY = VR0 + a2 VR1 + aVR2 VB = VR0 + aVR1 + a2 VR2 Written in matrix :   ...........................(9) V R0 V R1 V 1 1 1     1 a a  1 a a V R V Y V R2 2 2 B                         12
  • 13. 1 1 1    1 a a  1 a a T Let, 2 2        'T' is known as the symmetrical component transformation matrix 1 1 1   -1 2 1 a a  1 a a 1 3 T 2         13 From matrix inversion
  • 14. Applying T-1 to eq. (9):   .............................1(0) V R V Y V 1 1 1   1 a a  1 a a 1 3 V R0 V R1 V B 2 2 R2                           1     V a V aV ............................1(3) 3    R0 R Y B 1    1 V V aV a V ............................1(2) 3 V V V V .................................(11) 3 V OR Y B 2 R2 R B 2 R1 R Y    14
  • 15. Similarly:   .............................1(4) I I I 1 1 1   1 a a  1 a a 1 3 I I I R Y B 2 2 R0 R1 R2                           1     I a I aI ............................1(7) 3    R0 R Y B 1    1 I I aI a I ............................1(6) 3 I I I I .................................(15) 3 I OR Y B 2 R2 R B 2 R1 R Y    15
  • 16. Analyzing equations (11) and (15) ….. (11) → for balanced 3 system VR +VY + VB = 0 Balanced  voltage magnitude and angle normal (current unbalanced) (15) → IR + IY + IB = IN  IN = 3IR0  if the system is ungrounded  IN = 0 = IR0 → no zero sequence currents Hence  connected loads have no zero sequence currents. 16
  • 17. Example: (Higher Electrical Engineering – Sheppard, Morton and Spence) The currents flowing in an unbalanced 4-wire system are IR = 1000 A; IY = 200-90 A ; IB = 100120 A Find the +ve, -ve and zero sequence components of these currents. 17
  • 18. Solution:      R0 R1 1 I I      I I I R0 R Y B          1 1 1   1 a a  R Y I I   1 3 1          100 0 200 90 100 120 3 From which     I 41.3 66.2 A I R0               B 2 2 R2 I 1 a a 3 I Re call : 18
  • 19.   1    I aI a I 3                100 0 (1.0 120 ).(200 90 ) (1.0 240 ).(100 120 ) 3 I 128.79 15 A 1 Also, I R1 B 2 R1 R Y     2      R2 R Y B                     R2 And, 1 I I a I aI 3 1 100 0 (1.0 240 ).(200 90 ) (1.0 120 ).(100 120 ) 3 I 41.3 174 A 19
  • 20. SEQUENCE NETWORKS Since - component currents of one phase sequence cause - voltage drops of like sequence only and - independent of the other sequences (in a balanced system) - currents of any one sequence may be considered to flow in an independent network composed of impedances to the current of that sequence. 20
  • 21. SEQUENCE NETWORKS The single phase equivalent circuit composed of the impedances to current of any one sequence only is called the sequence network for that particular sequence. In static symmetrical systems, conversion of a +ve sequence to a –ve sequence network is accomplished by changing only the impedances representing rotating machinery and by omitting any generated e.m.fs 21
  • 22. Synchronous Machines: - +ve sequence ≠ -ve sequence - Xd”, Xd’ and Xd are +ve sequence - the generated e.m.fs are +ve sequence only - the ref. bus for +ve and –ve sequence n/w is the generator neutral - the ref. Bus for the zero sequence n/w is the ground of the generator or earth - there are no generated e.m.fs in the –ve and zero sequence n/w 22
  • 23. Positive Sequence Networks: - For a given power system the positive sequence network shows all the paths for the flow of positive sequence currents in the system. - The one-line diagram of the system is converted to an impedance diagram that shows the equivalent circuit of each component under balanced operating conditions - Each generator in the system is represented by a source voltage in series with the appropriate reactance and resistance. - To simplify the calculations, all resistance and the magnetizing current for each transformer are neglected. 23
  • 24. Positive Sequencenetwork of Synchronous generator: 24
  • 25. Negative Sequence Networks: - Three-phase generators and motors have only positive sequence generated voltages. Thus, the negative sequence network model will not contain voltage sources associated with rotating machinery. - The negative sequence impedance will in general be different from the positive sequence values. - For static devices such as transmission lines and transformers, the negative sequence impedances have the same values as the corresponding positive sequence impedances. 25
  • 26. Negative Sequence network of Synchronous generator: 26
  • 27. Zero Sequence Networks: - The zero sequence network of a system depends on the nature of the connections of the three-phase windings for each of the system’s components. 27
  • 31. Lines and cables: - +ve and –ve sequence impedances are the normal balanced values. - zero sequence impedances depends on the nature of the return path through earth. The following factors can be used in the absence of manufacturer data: Cable Zero Seq. Impedance 3 – core Z0 =3Z1 to 5Z1 1 – core Z0 =1.5Z1 31
  • 32. Single Circuit Double Circuit No ground wire  Z0 =3.5Z1 Z0 = 5.5Z1 Steel ground wire  Z0 =3.5Z1 Z0 =5Z1 Non-metallic ground wire  Z0 =3.5Z1 Z0 =3Z1 Lines: 32
  • 33. Transformers: - +ve and –ve sequence impedances are the same i.e. (Z1 = Z2) - zero sequence cct depends on whether a return path exists through which a completed circuit can be provided Recall the equivalent cct for a transformer is: 33
  • 34. The equivalent circuit becomes: For +ve and –ve sequence Z1 = Z2 For zero sequence the equivalent circuit changes depending on the configuration of the transformer. 34
  • 35. Zero Sequence Network (Transformer) - Close ‘a’ contact whenever zero sequence currents can flow, i.e. earth connection exists. - Close ‘b’ contact whenever zero sequence currents can circulate, i.e.  connection. - circuit is left open when neither condition exists, for example unearthed star connection. 35
  • 40. The A-phase of the unloaded generator shown below is subjected to a SLG fault. The pre-faulted L-N voltage of the generator is EA Volts. The generator has positive, negative and zero sequence impedance of Z1, Z2 and Zo respectively. Find the fault current and phase voltages under the fault condition. 40 Line to Ground Fault (SLG)
  • 41. Conditions under SLG fault: VA = 0 ; and IB = IC = 0 (i.e. neglecting load currents)           I I  0       1 1 1   1 a a                B I 0 1 a a 1 3 I I I C A 2 2 A0 A1 A2 1 A0 A1 A2 A I 3 I  I  I  Since IA1 = IA2 = IA0 then the seq. n/ws must be connected in series 41
  • 42. From the interconnected networks 42 A E 1 A0 A1 A2 A Z Z Z 1 2 0 I 3 I I I       Also VA = VA0 +VA1 + VA2 VB= VA0 + a2 VA1 + aVA2 VC= VA0 + aVA1 + a2 VA2 Where: VA1= EA - IA1 Z1 VA2= 0 - IA2 Z2 VA0= 0 - IA0 Z0
  • 43. A 3-phase star connected solidly earthed, unloaded generator has it’s A-phase subjected to a solidly grounded earth fault. Given that the pre-faulted L-N voltage of the generator is 100 V and Z1 = j1.0Ω, Z2 = j0.5Ω and Zo = j0.1Ω, calculate the fault currents developed and the L-L voltages attained due to a fault. 43 Example
  • 44. 100 j1.6 From analysis of the ckt we obtain E A A0 A1 A2 A  Z Z Z 1 I 3 I I I   1 2 0          I I I j62.5 A A0 A1 A2       I I 3( j62.5) A j187.5 A F A                we also know that  1 1 1     1 a a            V A0 V A1 A2 2 2 V A V B C V 1 a a V 44
  • 45.  VA = VA0 +VA1 + VA2………………(1) VB= VA0 + a2 VA1 + aVA2…………..(2) VC= VA0 + aVA1 + a2 VA2…………...(3) From the ckt: VA1= EA - IA1 Z1= 100 – [(-j62.5)(j1.0)] = 37.5 V/gn Similarly, VA2= 0 - IA2 Z2 = - (-j62.5) (j0.5) = -31.25 V/gn And, VA0= 0 – IA0 Z0 = - (-j62.5) (j0.1) = -6.25 V/gn 45
  • 46. Substitute V1, V2 and V0 into equations (1), (2) and (3) VA = VA0 +VA1 + VA2 = 0 And VB= VA0 + a2 VA1 + aVA2 = - 9.37 – j59.5 = 60.23-98.9 V VC= VA0 + aVA1 + a2 VA2 = - 9.37 + j59.5 = 60.23 98.9 V Also, VAB= VA - VB = 9.37 + j59.5 = 60.23 81.1 V VBC= VB - VC = - j119 = 119 -90 V VCA= VC - VA = - 9.37 + j59.5 = 60.23 98.9 V 46
  • 47. DOUBLE LINE FAULT (DL) Condition when fault occur IA = 0 ; IB + IC = 0 ; and phase voltage VB = VC 47
  • 48. 1 1 1 1   1 a a 1          B B  A0 A1 I I          A0 B B 2 A2 B 2 1   A1 B I  0 B A I C B 2 2 A2 1 0 a I - aI 3 I    0 aI - a I and 3 I 0 I - I 0; 3 I I I 1 a a 3 I                      1 a - a 2  I 3 A0 A1 A2     I 0 a nd I - I B 48 j But a - a j1.732 j 3 I - I A1 A2 B I 3 2      Since IA0 = 0 then the zero sequence ckt is open
  • 49. Equivalent sequence ckt becomes From which we obtain E A A1  Z Z I 1 2  IA1 = - j66.67 IA2 = j66.67 - 114.94 A  A1 B - j 66.67     j0.58 I - I j I 3 But I B C 49
  • 50. Also, VA1 = EA - IA1Z1 = 100 - (-j66.67)(j1.0) = 100 - 66.67 = 33.33 V/gn Therefore, VA1 = VA2 = 33.33 V/gn Now                1 1 1     1 a a             V A0 V A1 A2 2 2 V A V B C V 1 a a V 50
  • 51.  VA =VA1 + VA2 = 66.67 V/gn VB =VA1(a2 + a) = VC But a2 + a = -1  VB = -33.33 V/gn = VC 51
  • 52. DOUBLE LINE TO GROUND FAULT (DLG) Condition when fault occur IA = 0 ; VB = VC = 0 ; IB + IC = IF 52
  • 53. From inspection IA = 0 and VB = VC           V V  0       1 1 1   1 a a               B V 0 1 a a 1 3 V 0 V 1 V C A 2 2 2 1 0 1 2 A V 3 V  V  V  Hence, the sequence networks are in parallel 53
  • 54. Since Z2 //Z0 then the circuit reduces to: Z Z 2 0 P Z Z 2 0 where Z   A E 1 Z Z 1 P I    54 2 Z   where I  0 I Z Z Z   I and  2 I 1 0 Z Z 0 2      1 0 2     
  • 55. Example: The diagram shows two generators connected to a transmission system comprising two parallel 66kV transmission lines via transformers. The data of this system is given below GA and GB – 13.8kV, 100 MVA, Z1 = j0.15, Z2 = j0.1 and Z0 = j0.03 (all p.u) TFA – 13.8/66kV, 100 MVA, Z1 = Z2 = Z0 = j0.15 p.u TFB – 13.8/66kV, 100 MVA, Z1 = Z2 = Z0 = j0.1 p.u Each Transmission Line - Z1 = j0.4, Z2 = j0.4 and Z0 = j0.7 (all p.u) All star points are solidly earthed, except that of generator B which is unearthed. All p.u. values are on the 100 MVA base. Calculate the fault current for a DLG fault at the feeder terminals of transformer A. 55
  • 56. Soln + ve - ve zero 56
  • 57.   + ve seq n/w reduces to - ve seq n/w reduces to zero seq n/w reduces to 57
  • 58. For DLG fault, the three sequence networks are connected in parallel (as seen earlier).  j3.8 p.u. 1 I pu 1   j(0.18 0.083) V Z    j2.05 p.u. j0.18   2 1    j0.334 (j3.8) Z 0 Z Z I I 0 2        58
  • 59. j1.75 p.u. j0.154   0 1    j0.334 (j3.8) Z 2 Z Z I I 0 2         I I A B         I I I I j1.75 ( j3.8 ) j2.05 0 A 0 1 2          I 0 I I 1 1 1  1 a a  1 a a I Substitute the seq current values in the matrix 1 2 2 2 C                      2 I  I  a I  aIB 0 1 2            j1.75 (1 240 )(3.8 90 ) (1 120 )(2.05 90 )    5.72 152.7 p.u. 59
  • 60. 874.8A 100 x 10 pu    3 x 66 x 10 MVA 3V But I 3 6 base base I 874.8 (5.72 152.7 ) 5003.9 152.7 A B        Similarly, I 5003.9 27.37 A And I  I  I  j5.26 p.u. F B C I j4601.5 A or F C     60
  • 61. One line Open Circuit 61 Under this condition consider the elemental values of V. From inspection IA = 0 and VB = VC
  • 62. Applying these conditions:            V   V 0 B        1 1 1   1 a a               V 0 1 a a 1 3 V 0 V 1 V C A 2 2 2 1 0 1 2 A V 3 V  V  V  Hence, the sequence networks are in parallel as shown below: 62
  • 63. From the example before: EA = 1000 and Z1 = j1.0 ; Z2 = j0.5 ; Z0 = j0.1 Since Z2 //Z0 then the circuit reduces to: j0.083 (j0.5)(j0. 1) P   j0.6 Z Z 2 0 Z Z where Z  2 0  j92.31 100 1   1 j0.083 E A Z Z I 1 P           V E - I Z 100 [( j92.31)(j1.0)]    2 0 1 A 1 1 7.69 V/gn V V 63
  • 64. j15.38 A 7.69 2      j0.5 V Z Also, I 2 2 j76.9 A 7.69 0      j0.1 V Z And, I 0 0 But, 3V1 = VA  VA = 23.07 V/gn                1 1 1     1 a a              I  I  0 I I 1 2 2 2 A B C B C I 1 a a I To determine I and I we use: I I I I 0 A 0 1 2      Also I I a (-j92.31) a(j15.38) - 93.3 j115.4 2 B 0       And I I a(-j92.31) a (j15.38) 93.3 j115.4 2 C 0       64