HERS® Raters
    &
   HVAC
     Brett Dillon
RESNET Conference 2010
ENERGY
AHRI   ACCA
                  STAR®


              Responsibilities
HVAC
• Comfort
• Indoor Air Quality
• Efficiency
AHRI
• ARI & GAMA
• Publishes HVAC & DWH data
AHRI Data
•   Region IV

•   80°F indoor cooling test temperature

•   67°F indoor wet bulb temperature

•   90°F outdoor test temperature

•   47°F outdoor heating test temperature

•   17°F outdoor heating test temperature
System Concept                     Manual RS


    Load Calculation                    Manual J


                     Air Distribution   Manual T

Equipment                               Manual S
Selection

            Duct Size Calculation       Manual D
     Adjust, Test & Balance
Heating                          Cooling
    T-stat setpoint                     70°F                             75°F
          RH                            25%                              40%
    Temp @ T-stat                    68°F - 72°F                      72°F - 78°F
Room-Room or Level-
                                         + 4°F                             + 6°F
     Level ∆ T

  Temp in any room                + 2°F of set point               + 3°F of set point
Floor temp over slab or
                               > 65°F, 4” above floor
 unconditioned space
        Filtration                   > MERV 8                         > MERV 8
                              7.5 cfm/person + 1 cfm/             7.5 cfm/person + 1
      Ventilation
                                       100 ft2                        cfm/100 ft2
    Duct Leakage                        < 6%                             < 6%



              Sources: ACCA Manual RS, ENERGY STAR, ASHRAE Standard 62.2
ACCA Manual J
• Every home is required to have a Manual J, 8th
  edition, load calculation
 –Using the 99% winter design temperature
 –Using the 1% summer design temperature


             IRC Section M1401.3
Oversized Furnaces

    Furnaces that are sized > 40%
    over the calculated load:
  • furnace & vent can cool, causing
   condensation and rust
  • airflow across exchanger can be
   too much, causing corrosion from
   condensation
Oversized Air
 Conditioners
  Air conditioners that are sized >
    15% over the calculated load:
• duct leakage increases
• latent cooling capacity decreases
•Blower motor uses more energy
• equipment life is shortened
Oversized Heat Pumps
     Heat pumps that are sized > 15%
     over the calculated load:
   • duct leakage increases
   • latent cooling capacity decreases
   •blower motor uses more energy
   • equipment life is shortened
   • register temperatures are low
    during heating season
Undersized Furnaces

    Furnaces that are sized under the
    calculated load:
  • may not have enough airflow
   across the heat exchanger,
   leading to deformation or cracking
Undersized Air Conditioners & Heat
             Pumps

     Air conditioners & heat pumps that
     are sized under the calculated load:
    • may not have enough capacity
    • latent cooling capacity increases,
     decreasing the sensible capacity
Manual T

• Select, size & locate
 • supply outlets
 • return inlets
Spread
Throw
Drop
Manual T




Source: Hart & Cooley Engineering Data
Manual S



       Sensible    Supply              Temperature
                            Room Air
      Heat Ratio     Air                Difference
        < 80%       54        75           21
      80% to 85%    56        75           19
        > 85%       58        75           17
Manual D
•   Required under IRC M1601.1
    •   Implies room-by-room load calculation must be
        performed
    •   CFM
        •   SHR
            •   ΔT supply-return
        •   Sensible load
    •   Friction rate
        •   Pressure drop x 100 / total effective length
Cooling Size
• CFM = (Sensible / (1.1 x ΔT)
 • SHR = 0.87
   • ΔT = 17°F
 • Sensible Room Load = 4,537 Btu/hr
       CFM = 4537 / (1.1 x 17)
         CFM = 4537 / 18.7
            CFM = 243
Cooling Size
•   Friction Rate = Pressure drop x 100 / total
    effective length
    •   Pressure drop = 0.10 i.w.c.
    •   TEL = straight flex duct + fittings
        •   90° elbow = 30’
        •   90° supply air boot fitting = 80’
        •  Straight duct = 20’
        Friction Rate = (0.10 x 100) / (20’+30’+80”)
                       FR = 10 / 130
                         FR = 0.077
ENERGY STAR
•   All cooling equipment must be sized
    according to latest editions of Manuals J &
    S, ASHRAE Handbook of Fundamentals,
    or equivalent procedure
•   Maximum oversizing is 15%
•   Outdoor design temps 99% & 1%
•   Indoor cooling temp = 75°F
•   Infiltration rate = Tight or equivalent
Responsibilities
•   Verify matched coils
•   Enter data into rating software tool
•   Review (verify)
    •   Approved tool
    •   Design values
    •   Infiltration
    •   Selected to meet MJ & MS
Contact

          Brett Dillon
  bdillon@ibsadvisorsllc.com
   www.ibsadvisorsllc.com

Design support by Backyard Studios
     www.backyardstudios.net

Raters &amp; HVAC

  • 1.
    HERS® Raters & HVAC Brett Dillon RESNET Conference 2010
  • 2.
    ENERGY AHRI ACCA STAR® Responsibilities
  • 3.
    HVAC • Comfort • IndoorAir Quality • Efficiency
  • 4.
    AHRI • ARI &GAMA • Publishes HVAC & DWH data
  • 6.
    AHRI Data • Region IV • 80°F indoor cooling test temperature • 67°F indoor wet bulb temperature • 90°F outdoor test temperature • 47°F outdoor heating test temperature • 17°F outdoor heating test temperature
  • 7.
    System Concept Manual RS Load Calculation Manual J Air Distribution Manual T Equipment Manual S Selection Duct Size Calculation Manual D Adjust, Test & Balance
  • 8.
    Heating Cooling T-stat setpoint 70°F 75°F RH 25% 40% Temp @ T-stat 68°F - 72°F 72°F - 78°F Room-Room or Level- + 4°F + 6°F Level ∆ T Temp in any room + 2°F of set point + 3°F of set point Floor temp over slab or > 65°F, 4” above floor unconditioned space Filtration > MERV 8 > MERV 8 7.5 cfm/person + 1 cfm/ 7.5 cfm/person + 1 Ventilation 100 ft2 cfm/100 ft2 Duct Leakage < 6% < 6% Sources: ACCA Manual RS, ENERGY STAR, ASHRAE Standard 62.2
  • 9.
    ACCA Manual J •Every home is required to have a Manual J, 8th edition, load calculation –Using the 99% winter design temperature –Using the 1% summer design temperature IRC Section M1401.3
  • 11.
    Oversized Furnaces Furnaces that are sized > 40% over the calculated load: • furnace & vent can cool, causing condensation and rust • airflow across exchanger can be too much, causing corrosion from condensation
  • 12.
    Oversized Air Conditioners Air conditioners that are sized > 15% over the calculated load: • duct leakage increases • latent cooling capacity decreases •Blower motor uses more energy • equipment life is shortened
  • 13.
    Oversized Heat Pumps Heat pumps that are sized > 15% over the calculated load: • duct leakage increases • latent cooling capacity decreases •blower motor uses more energy • equipment life is shortened • register temperatures are low during heating season
  • 14.
    Undersized Furnaces Furnaces that are sized under the calculated load: • may not have enough airflow across the heat exchanger, leading to deformation or cracking
  • 15.
    Undersized Air Conditioners& Heat Pumps Air conditioners & heat pumps that are sized under the calculated load: • may not have enough capacity • latent cooling capacity increases, decreasing the sensible capacity
  • 16.
    Manual T • Select,size & locate • supply outlets • return inlets
  • 17.
  • 18.
  • 19.
  • 20.
    Manual T Source: Hart& Cooley Engineering Data
  • 21.
    Manual S Sensible Supply Temperature Room Air Heat Ratio Air Difference < 80% 54 75 21 80% to 85% 56 75 19 > 85% 58 75 17
  • 23.
    Manual D • Required under IRC M1601.1 • Implies room-by-room load calculation must be performed • CFM • SHR • ΔT supply-return • Sensible load • Friction rate • Pressure drop x 100 / total effective length
  • 24.
    Cooling Size • CFM= (Sensible / (1.1 x ΔT) • SHR = 0.87 • ΔT = 17°F • Sensible Room Load = 4,537 Btu/hr CFM = 4537 / (1.1 x 17) CFM = 4537 / 18.7 CFM = 243
  • 25.
    Cooling Size • Friction Rate = Pressure drop x 100 / total effective length • Pressure drop = 0.10 i.w.c. • TEL = straight flex duct + fittings • 90° elbow = 30’ • 90° supply air boot fitting = 80’ • Straight duct = 20’ Friction Rate = (0.10 x 100) / (20’+30’+80”) FR = 10 / 130 FR = 0.077
  • 36.
    ENERGY STAR • All cooling equipment must be sized according to latest editions of Manuals J & S, ASHRAE Handbook of Fundamentals, or equivalent procedure • Maximum oversizing is 15% • Outdoor design temps 99% & 1% • Indoor cooling temp = 75°F • Infiltration rate = Tight or equivalent
  • 39.
    Responsibilities • Verify matched coils • Enter data into rating software tool • Review (verify) • Approved tool • Design values • Infiltration • Selected to meet MJ & MS
  • 40.
    Contact Brett Dillon bdillon@ibsadvisorsllc.com www.ibsadvisorsllc.com Design support by Backyard Studios www.backyardstudios.net