SlideShare a Scribd company logo
1 of 25
Download to read offline
CHK Power QualityPtyLtd Page 1
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Electric Shock
Investigations
Introduction
Electric shocks can be of a minor nature or can be devastating,
resulting in severe injury or death. Technicians involved in the
investigation of electric shock incidents need to be well trained
and equipped with high quality test equipment so that the
incident is resolved quickly to prevent further incidents and in
case of litigation. A multimeter, fault loop impedance tester,
safety switch tester and a power quality logger may be some of
the requiredtestequipment. The PM45 is an excellent logger to
assistininvestigationsasithas an additional voltage channel for
logging shock voltages (see Figure 1).
Causes of Electric Shock
Electric shocks can occur for a variety of reasons such as:
 Raised neutral-earth voltages caused by:
 Poor or open circuit neutral connections in the
grid or within an electricity users installation;
 Long runs of neutral conductor in the grid or
within an electricity users installation;
 Reverse polarity connection of an installation or at another installation;
 Overloading of the neutral conductor because of unbalance loads;
 Faulty wiring or equipment that has not tripped circuit protection.
 Touching fallen powerlines;
 Live roofs where a nail or screw has punctured an energised electricity cable;
 Faulty wiring or equipment;
 Misuse of electrical equipment;
 Low energy shocks such as static, induced voltages or leakage through a high impedance path.
Effects of Electric Shock
Personsmayreceive a‘tingle’withlittleornolongterm physical or mental effects. More severe shocks
can have devastating health effects both mentally and physically for the victim.
Animalsmayalsobe affectedbyelectric shocks. Large animals such as cows and horses are affected by
stepvoltagesmuchmore thanpeople due tothe large distance betweenfrontandbacklegs.Dairy cows
may sufferfromnervousness,excessive defecationandurination,reducedmilk supply and may have an
elevated mastitis count even if only receiving very minor tingles.
The causes of electricshockproblems,as detailedabove,canalsodamage electrical equipment. A poor
or open circuit neutral connection or a long run of neutral often results in damaging low and/or high
volts being delivered to electrical equipment.
Figure 1 - A trained technician
installing a PM45 to log the
neutral-earth voltage. The remote
earth lead should be installed not
to create a trip or electrical hazard.
CHK Power QualityPtyLtd Page 2
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
A reverse polarity of a multiphase installation can result in severe electric shocks and phase to phase
voltage beingappliedtophase toneutral equipment.Thisequipmentisgenerallydamaged severely and
may cause a fire that could also raze premises to the ground.
Required Standard
AS/NZS60479 detailsthe effectsof electriccurrentonhumanbeingsandlivestock. However,it does not
setacceptable levelsfortouchvoltages. IEC61200-413 provides curves with limits of touch voltage that
can be sustained indefinitely depending on normal or wet conditions. The levels provided by these
curves can result in a nasty shock and so many Australian distributors rely on a limit of 10 volts or less
for neutral-earth voltages.
Case Study
A customerinan urban situationhadbeenreceivingelectricshocksinthe shower for the last 2 months.
A trainedtechnician investigated and found minor voltages of up to 3 volts in the shower when all the
load in the installation was turned on. This level of voltage would not normally be of concern but the
customer was adamant that the problem had recently started.
Furtherinvestigationsfoundthata neutral connectioninthe street mains was open circuit. The neutral
currentwas forcedto take alternate paths back to the distribution transformer resulting in the voltage
on the neutral conductorbeingelevatedabove normal levels. This voltage is then transferred onto the
water pipes by the equipotential earthing bond.
A PM45 was connected to monitor the neutral-earth voltage at the customer’s installation to ensure
that all was backto normal (see Figure 1). The loggerwas removedaday lateranddownloaded.Figure2
showsthe resultsof that downloadwiththe neutral-earthvoltage peakingat0.52 voltswhichmeantthe
problem had been rectified. The customer also advised they were no longer receiving shocks in the
shower and everything was back to normal.
Figure 2 - PM45 neutral-earth voltage trace showing very minor voltage levels
Conclusions
Technicians involved in the investigation of electric shock need high quality equipment such as
multimeters,fault loop impedance testers, safety switch testers and power quality loggers e.g. PM45.
Thistestequipmentcanassistinidentifyingthe cause of the problem soa solution canbe implemented
to preventfurtherincidents.A faultyneutral connection will simply need to be replaced. A long run of
neutral conductor, that is causing an elevated voltage on the taps in a shower, may need to be re-
conductored with larger cable or a transformer installed closer to the load.
CHK Power QualityPtyLtd Page 3
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
A power quality logger, such as the PM45, can log the supply voltages and load current, as well the
neutral to earth voltage and verify if the problem is related to the load. Supply voltages that vary
considerably may be caused by a floating neutral/open circuit or poor neutral connection.
All in all, the PM45 is an excellent tool to assist in the investigation and resolution of electric shock
problems.
CHK Power QualityPtyLtd Page 4
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Excessive Energy Usage
Introduction
Electricity costs are continually increasing and the need to minimise
climate change requiresthe reductioninenergyusage.Aspartof this,
manygovernments are also requiring energy conservation and more
stringent control and management of energy usage, particularly for
large energy users.
The PM45 issimple to use,accurate and an essential tool for those in
the energymanagementfieldtoassistinthe reductionof greenhouse
gases and electricity costs (Figure 1).
Causes of Excessive Costs
Excessive Usage
If electrical equipment is not turned on then it is not costing. This is a simple message but not easy to
manage for those with large numbers of electricity users in the premise and/or a larger premise.
However,electricityusage canbe recordedbya powerqualityorenergylogger to determine when and
where electricity is being used. This then allows an analysis of where energy can be saved.
Poor Power Factor
Poorpowerfactor ismostlycausedby inductionmotorswhere the currentlags the voltage. This results
inadditional wastedenergyandgreenhouse gases. There will be no reduction in electricity costs if the
premise isonlybeingchargedforkilowatthours and power factor correction equipment was installed.
But, there may be significant savings if the electricity tariff penalises for poor power factor e.g. a kVA
charge on top of kilowatt hours.
If there are no cost savings to be made, then the only benefits may be a release in capacity of the
supplying transformer and mains if power factor correction capacitors were installed. This may save
significant upgrade costs as well as reducing greenhouse gases.
Powerfactorstandardsare setby the National ElectricityRulesforabove 1kV andby local distributorfor
less than 1kV.
Wrong Tariff or Wrong Time of Use
The most suitable tariff for the premise can be determined by logging the electrical load. The logged
data isthenanalysedtodetermine the mostappropriate tariff. Changing tariffs can result in significant
savings and in one case resulted in an annual reduction from $20,000 to $14,000 – a saving of
$6000/year.
Figure 1 - A PM45 being
installed for an energy audit
CHK Power QualityPtyLtd Page 5
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Time of Use tariffscharge more for electrical usage whenthe electricityis used in peak periods than for
shoulderoroff-peakperiods.Careful analysisof PM45 graphsand an intimate knowledge of operations
may allow for movement of load from higher tariff periods to cheaper times of use, thus saving costs.
Case Study
A factorywas payingan annual electricityaccountthattheybelieved was excessive for the size of their
operations. An installed a PM45 recorded the electricity usage and power factor over one week.
The audit found that the considerable energy was being used at nights when only the cleaning crews
were on-site, attributed to the turning on all air conditioning at the facility. Discussions with cleaners
determined that most of the air conditioners could be left off at night except as required in each
location,as the cleaners moved from location to location, to maintain air quality. The factory’s energy
management system was programmed to prevent the use of all air conditioners at night.
The power factor at the site was extremely poor and down to about 0.65 lagging on one phase and
neverabove the required0.9standard on any phase at any time (Figure 2). Installation of power factor
correction capacitors saw a reduction in kVA demand, line losses and greenhouse gases. The power
factor correctionunitshowedareturnon assetswithinapproximately18 months. After this period, the
reductioninelectricitycostscontributedtoannual profitswhilstassistingingreenhouse gasabatement.
Figure 2 - Power Factor Graph for Factory
The audit alsodetermined that significant loads could be transferred to off-peak operation to provide
for betterplantutilisationandsignificantenergysavings.Unfortunately,awardpaymentsforstaff wages
offsetanysavingsandso the transferdidnotgo aheadat that stage.Awardnegotiations are continuing
with the union involved.
CHK Power QualityPtyLtd Page 6
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Conclusions
The PM45 can be an extremely valuable tool in reducing electricity costs and in the reduction of
greenhouse gases. The PM45 can be used to check when and where electricity is being used and at
what power factor.
CHK Power QualityPtyLtd Page 7
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Harmonic Pollution
Introduction
The quality of the electricity supply is a quite complex issue.
The focus of powerproblemsinyearsgone by has been more
on voltage quality than the more technical aspects of power
quality. This may still be the case in some power companies
where problems are referred to as voltage complaints.
The requirement for a higher quality electricity supply has
come with the proliferation of sensitive equipment which
generate more harmonics themselves.
The PM45 records levels of individual harmonics as well as
THD-f, which is Total Harmonic Distortion (THD) - a measure
of the effective valueof harmonicdistortion.More specifically
it is the ratio of the rms value of the harmonic content of an alternating voltage or current to the rms
value of the fundamental component of the voltage or current. Inter-harmonics can also be recorded
which are harmonic frequencies that are not an integer of the fundamental.
Causes of Harmonics
Harmonicsare sinusoidal voltagesorcurrentshavingfrequenciesthatare integermultiplesof the supply
frequency. Harmonicsare generallycausedbynon-linear loads i.e. equipment that has a capacitor and
a diode or diode type device (e.g. Silicon Controlled Rectifier). This type of combination is generally
foundin equipmentwithaswitchmode powersupply. Harmonicsare generallyatmuchhigherlevelsin
industrial premisesorcommercial premises which oftenhave variablespeeddrivesor many computers.
Inter-harmonicsare voltagesorcurrenthavingfrequencycomponents that are not integer multiples of
the supplyfrequency.The mainsourcesof inter-harmonicsare heavy industry equipment such as static
frequency converters, cyclo-converters, induction furnaces and arcing devices. Power-line-carrier
signals are regarded as inter-harmonics.
Effects of Harmonic Pollution
The effects of harmonics include:
• Eddy current heating in equipment
• Noise and torque oscillation in motors
• Vibration or noise in panels
• Nuisance tripping of breakers & fuses
• Metering errors
• Electronic equipment malfunctions
• Generator speed/frequency instability
• Telephone noise interference
• Data transfer errors
CHK Power QualityPtyLtd Page 8
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
• Resonance causing large voltages &
currents
The effects of Inter-harmonics include:
• Distortion of power-line-carrier signals
• Flicker of fluorescent and arc lighting
• Flicker of computer display devices
Required Standard
Levels of harmonic
distortion should meet
the compatibility levels
of AS/NZS61000.3.6
(Figure 2).
The standard also allows
a distributor to record
harmonic levels before
and after the connection
of a new installation or
load to ensure the
customer does not
exceed the distributor’s
emmission limits.
Case Study
A plantwashaving problems in the early hours of the morning with circuit breakers tripping randomly
for nogood reason. Monitoring was carried out with a PM45 configured to record harmonic problems.
Voltage THD levelswere foundtobe nearing10% at timesand well above allowable compatibilitylevels
(Figure 3). It was believed that harmonics were causing the circuit breakers to trip.
A Variable Speed Drive (VSD) on the premise was controlling a quite large motor that was started at
around 2 am in the morning. The VSD was confirmed as the source of problems and the manufacturer
was contactedto solve the problem. Circuit breakers did not trip after the solution was implemented.
Figure 3 - Graph showing excessive harmonics at the circuit breaker panel
Figure 2: Compatibility levels for harmonic voltages (in percent of the nominal
voltage) in LV and MV power systems
Odd harmonics
non multiple of 3
Odd harmonics
multiple of 3
Even Harmonics
Order
h
Harmonic
voltage %
Order
H
Harmonic
voltage %
Order
H
Harmonic
voltage %
5
7
11
13
17
19
23
25
>25
6
5
3.5
3
2
1.5
1.5
1.5
0.2+
1.3 (25/h)
3
9
15
21
>21
5
1.5
0.3
0.2
0.2
2
4
8
10
12
>12
2
1
0.5
0.5
0.5
0.2
0.2
NOTE – Total harmonic distortion (THD): 8%
CHK Power QualityPtyLtd Page 9
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Conclusions
Harmonicsare causedby non-linearloadsandare oftena probleminindustrial and commercial supply.
The PM45 can be a valuable tool indeterminingif harmonics or inter-harmonics are at excessive levels
and in locating the source of the problem.
CHK Power QualityPtyLtd Page 10
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Monitoring Zone
Substations
Introduction
A PowerMonic (power quality loggers) may be installed at zone
substations, either for a short-term investigation or as a long-term
monitoringdevice.The zone substation may be either owned by the
power company or the electricity customer/user.
Remote communication with the PowerMonic may be important to
save travel time, particularly where permanently installed.
The PM45 provides a particularly good option for such situations as
it is robust, provides quality data and is easy to install (Figure 1).
Reasons for Installing Loggers at Zone Substations
The installation of a logger at a zone substation may occur for the
following reasons:
1. Compliance withregulatororstate code requirements –insome states the state regulator requires
that a power quality monitor be installed at each power company’s zone substations.
2. Power quality check before payment of claims – customers are increasingly claiming from power
companiesfordamagedelectrical orelectronicequipment.The zone substation graphs can be used
by the powercompany to verifythe qualityof the supplyleaving the zone substation at the time of
the incidentthatallegedlydamagedthe equipment. Checkingpowerqualitylogsmaybe part of the
investigationif aclaim is to be rejected by the power company or as justification for a claim by the
customerif the loggerwas installed. A disrupting event may cost a plant thousands or hundreds of
thousands of dollars, so it is important to have the detail to justify the claim.
3. Continual checking of zone substation capacity – zone substation loads are generally on the
increase. A power quality logger allows continual checking of the available capacity at the zone
substation. Thereby helping to ensure that overloads and loss of supply do not occur.
4. Newconnectionof alarge customerand providingpowerquality indices –. The collection of power
quality data can allow power quality indices to be collated that can be very beneficial to the new
customers,especiallyif theyare connecting directly from the zone substation. This allows the new
customer to determine the level of robustness of their plant and equipment, which is particularly
important when specifications for the plant and equipment are being developed.
5. Exceedancescapturedcanbe usedto checkthe operationof zone substationprotectionequipment
– Events can be captured by the power quality logger that can verify if protection equipment has
Figure 1 - A PM45 being installed
on a zone substation indoor
transformer panel to monitor
power quality on a temporary
basis.
CHK Power QualityPtyLtd Page 11
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
performed as it should when a network problem occurs. An exceedance may show that a circuit
breaker did not work as intended and took an excessive time to open.
6. Check of frequency injection or ripple signal loads – frequency injection signals can cause large
jumps in load if the connection of the controllers is not adequately controlled.
Installation of the Logger
The loggerwill need tobe configuredtocapture the required data. Part of this set-up will be to set the
nominal voltage to the nominal output voltage of the voltage transformer (VT).
The powerqualityloggershouldbe connectedtothe zone substationoutputbusbar’sVTsupplyand the
powertransformer’scurrent transformers (CT). Alternatively, the logger can be connected to a feeder
circuit breaker CT’s. The connection to the CT’s is best performed using a GridSense Substation CT
Converter Kit which isolates the CT circuit from the PowerMonic to ensure integrity of the CT circuit.
The logger is now set-up and running. A land-line or cellular modem may be connected for the data
communication. A system needs to be established for data storage to ensure that the data is readily
available for the analysis of events or long-term trending of power quality indices.
Case Study
A powercompanywashavingcustomercomplaintsthatcorrelatedtoone zone substationthatsupplied
a large component of commerical load. The zone substation was supplied from a long transmission
network that supplied numerous zone substations.
A PM45 logger was installed at the zone substation on the output from the zone substation power
transformer.Figure 2showsthat the voltage outputfromthe zone substationwasdroopingatpeakload
times.The transformertapchangerwas suspectedof runningout of boost taps following an analysis of
the graph. Tap positioninformationwasanalysedfromthe dataaquistionsystematthe zone substation
and yes, the transformer was running out of boost taps.
The transmission campany was asked to include Line Drop Compensation settings on their supply, so
that supplyvoltage wasboostedatpeak times, as a short to medium term fix. This solved the problem
and a long-term fix was scheduled in the following year.
CHK Power QualityPtyLtd Page 12
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Figure 2 - Graph showing voltage drooping at peak load from a zone substation
Conclusions
A PowerMonic can be easily configured and installed in a zone substation for a short or long-term
investigation. The benefits for long-term monitoring are many and the costs are easily justified.
CHK Power QualityPtyLtd Page 13
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Steady-State Voltage
Problems
Introduction
Steady-state voltageproblemsrelateto long duration over and/or
undervoltage situations.Thisiswhere the voltage istypicallymore
than 10% above or below the nominal voltage for long durations,
typically longer than 1 minute. International standards require
logging equipment to be set at 10 minute averages when logging
for steady-state voltage problems.This is required if an electricity
customer was to have a dispute with the distribution company.
However, it may be more appropriate to record at much shorter
averages when trying to determine what is causing problems.
The PM45 can logat averagesdownto10 seconds.Figure 1 shows
a PM45, powerqualitylogger,beinginstalled in response to a voltage problem. The PM45 has memory
allocatedforsteadystate logging,orprofilingasitis sometimescalled,isindependent of logged events
and so the requiredprofilingperiodisassuredandcannotbe usedif excessive numberof eventswereto
occur.
Causes of Steady-State Voltage Problems
Overloading
Overloading of distribution cables and transformers or cabling within the installation often results in
longdurationunder-voltage problems. Overvoltageproblemscanalsooccur,but lessfrequently, where
a single phase is over loaded on a three phase system. This can offset the neutral point in a star three
phase systemandcause one of the phases to go above and the other phases to go below the standard.
Inappropriate Design
Networks or installations are occasionally installed with inappropriate sized conductors and hence an
overloadsituationcanoccurright fromthe outset.The PM45 can be usedto assist in determining if the
designer has designed less than ideally.
Load Switching
Switching on or off large loads can cause large variations in the voltage. Network automatic tap
changers(voltage adjustingequipment) cantake some minutestorespondandsolong duration voltage
variations can occur. Under-voltage can occur where large loads are switched on and over-voltage
where the large load has been switched off.
Figure 1 - A PM45 being installed at a
house where the stove is not cooking
effectively.
CHK Power QualityPtyLtd Page 14
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Faulty Regulating Equipment
Distribution companies have automatic regulator equipment as described above on their high and
mediumvoltage networks.Some are eveninstallingthemontheir low voltage distribution networks to
correct localised problems. This equipment can fail and is likely to cause over and/or under voltage
depending on what has occurred and the amount of load on the feeder/circuit.
Network Reconfiguration
Distribution companies need to reconfigure their networks for various reasons, including for
maintenance and repair which results in less than ideal supply voltage. This may be until regulating
equipment responds or for much longer durations until the network is returned to normal.
Effects of Steady-State Voltage Problems
The effects of steady-state voltage problems are divided into two categories as follows:
Sustained Over-voltage
 Lights globes reduced life span
 Electronic equipment life reduction
 Equipment destruction - high voltages
 Increased motor losses
 Overvoltage protection operation
Sustained Under-voltage
 Slowness with cooking
 Dullness in incandescent lighting
 Discharge lighting drop outs
 Contactor chatter and heating
 Increased motor losses
Required Standard
The required level of voltage to be supplied by a distributor in Australia is either set by the National
ElectricityRules,AS60038 and/orstate basedlegislation.Atlow voltage,the distributor should supply a
nominal voltage of 230 volts, plus 10% and minus 6% at the point of supply.
A voltage transformerwillbe requiredtomeasure voltagesathighvoltage anda GridSense PowerMonic
substationconverterkittoconnectto substation CTs(ApplicationNote –MonitoringZone Substations).
Case Study
A motherishavingproblemswithcookingthe eveningmeal andwithdull lights.A PM45 was installedat
the point of supply to determine if the incoming supply was up to standard.
Figure 2 showsthe resultsof the loggingwiththe voltage below the requiredstandard for unacceptable
periodsof time.The graphwas suppliedto the distribution company, who investigated and found that
the user had increased their load and overloaded the low voltage supply network.
CHK Power QualityPtyLtd Page 15
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Figure 2 - Graph showing long duration under voltage problem in the evening
Conclusions
The PM45 can be an extremely valuable tool in determining the cause of long duration under and/or
over voltage problems. The logger will need to be set to log for 10 minute averages if there is dispute
and maybe setat intervalsmuch less than 10 minutes to assist in locating the source of problems. The
PM45 can also be useful with other steady-state problems such as voltage unbalance and harmonics.
CHK Power QualityPtyLtd Page 16
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Voltage and Current
Unbalance
Introduction
Voltage unbalance occurs in a three-phase system where
there is a difference in the values of voltages or where the
phase separation is not 120 degrees. Current unbalance is
similar except the values are for current instead of voltage.
Large levels of current unbalance generally cause voltage
unbalance.
Voltage unbalance is normally calculated using two
methods.The firstiswhere the negative sequence voltage is
expressedasapercentage of the positive sequence voltage
(the method used in the PowerMonic). The second method
usesthe maximumdeviationfromthe meanof the three line
values expressed as a percentage of the mean of the three
line voltages. The values for this method can be obtained
from a PowerMonic using an export of the voltage data to a
spreadsheet and then calculated. Current unbalanced is calculated simile using values for current.
The PowerMonicisan excellentinstrumentforloggingvoltage and current unbalance. Figure 1 shows a
PM45 being installed where a motor is becoming overheated.
Causes of Voltage and Current Unbalance
Currentunbalance isthe primarycause of voltage unbalance, as described in the introduction. Current
unbalance may be caused by the following:
• Large and/or unequal distribution of single-phase load – this often occurs with overhead
networkswhere the linespersonconnectslow voltage single-phaseservicestothe closest phase
to the neutral (nicknamed“short-armedlinesman’ssyndrome”).The same problem can occur at
medium voltage levels where single-phase distribution transformers are all connected to the
easiest to reach conductors.
• Phase to phase loads – thisoccurs withsome equipmentthatsimplyrequiressingle phasebutat
line-to-line voltage e.g. 415 volt welder.
• Unbalancedthree phase loads –some three phase loadsare made up of single and three phase
equipment. It is important that these loads are balanced to meet the power company’s
requirements.
Figure 1 – A PM45, configured for voltage
unbalance, is being installed at a motor to
determine the cause of over heating - voltage
unbalance is suspected.
CHK Power QualityPtyLtd Page 17
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Unequal impedances of a three-phase transmission and distribution networks also causes voltage
unbalance – this occurs where the overhead transmission or distribution system does not have
adequate and regular transposition of the phases to balance the system impedance.
Effects of Voltage Unbalance
Resistive loadsare relativelyunaffected
by voltage unbalance. However, the
major problem with voltage unbalance
is that it causes additional
heating/losses with three-phase
motors. Motors may also be noisy due
to torque and speed variations caused
by the voltage unbalance and will have
less effective torque and speed than
normal. The voltage unbalance also
causesan increase incurrent unbalance
well in excess of the voltage unbalance
percentage. Figure 2 shows a standard that allows for de-rating motors based on the percentage of
voltage unbalance.
Variable speeddrives(VSD) maytripoff due toan increase inac line currentscausedby a compensation
for the voltage unbalance.Increasedthermalstress of VSD diodes and dc link capacitors and additional
triplen harmonics can also occur.
Required Standard
The National Electricity Rules sets the limits for voltage unbalance as per Figure 3.
Figure 3: Voltage Unbalance Limits
Nominal Supply Voltage Negative Sequence Voltage(% of Nominal Voltage)
Column 1 Column 2 Column 3 Column 4 Column 5
no contingency
event
credible
contingency
event
General Once per hour
30 minute
average
30 minute
average
10 minute
average
1 minute
average
>100kV 0.5% 0.7% 1.0% 2.0%
Figure 2 – De-rating Curve for Motors
CHK Power QualityPtyLtd Page 18
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Current balance requirements are also set by the National Electricity Rules, distributor or state based
Service Rules and in state based legislation. Check the requirements for the location being logged.
Measurement of Voltage Unbalance
Voltage unbalance shouldbe measuredwithline toline valuesof voltage.Gridsense’s 6-wire lead is the
only way of measuring this when using PowerMonics.
The logger should be set to 10-minute averages in case logs need to be compared with standards e.g.
where there isa dispute. Voltage unbalance is more a steady-state issue and so 10-minute averages is
oftensuffice.However, voltage or current unbalance protection may be tripping and shorter averages
may be better suited to assist in determining the cause.
Case Study
The motor inFigure 1 wasoverheatingandvoltage unbalance was suspected as the cause. A PM45 was
installedandthe graphinFigure 4 obtained.Itshowsexcessive voltage unbalance andthe likelycause of
the overheating.
Figure 4 - Graph showing excessive voltage unbalance to a motor
Conclusions
The major cause of currentunbalance isthe “short-armedlinesmen’s syndrome” that results in voltage
unbalance.The majoreffectof voltage unbalance isadditional heatingandlossesinthree-phasemotors.
Voltage and current unbalance can be easily tracked down using a PM45.
10kV to100kV 1.3% 1.3% 2.0% 2.5%
<10kV 2.0% 2.0% 2.5% 3.0%
CHK Power QualityPtyLtd Page 19
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Voltage Flicker
Introduction
Voltage fluctuations and flicker can be a real nuisance with the
source of the problem often difficult to locate. The PM45 is
arguably the best logger for locating the source of voltage
fluctuations, particularly where motor starting is a problem.
Figure 1 showsa PM45 beinginstalledtotrackdownthe source of
voltage fluctuations caused by a motor.
The PM 45 has shortand longterm flickermonitoringcapabilityas
well as event recording for rolling average voltage variations or
threshold settings.
The eventrecordingcomesintoits own when trying to locate the
motor that is causing voltage fluctuations or when determining
the best time to swap a motor from the start to run sequence. The PM45 has memory allocated for
events that is independent of steady state logging, or profiling as it is sometimes called, assuring that
profiling is not disrupted should significant numbers of events occur.
Causes of Voltage Fluctuations and Flicker
Motor Starting
Motor startingis a major source of complaintsregardingvoltage variations. A motor can draw up to ten
timesitsrunningcurrenton start up. This huge increase in current causes the voltage to sag due to the
source impedance. Reduced voltage starting seeks to limit the start-up current and hence limit the
voltage fluctuation during the start-up process.
Swappingamotor to run before ithasgottenup to full speedwill cause the currenttopeakmuchhigher
than it would if started when up to speed. The PM45 can capture the start up sequence if set
appropriately.Analysisof the eventrecordedfromthe startupsequence willshow whether the voltage
fluctuation complies with the required standard and if the controller, that swaps the motor to run, is
appropriately set. Generally a simple timer is used for the swap over process and it may be that this
timer needs to be more appropriately set (tweaked) to prevent the excessive voltage fluctuation.
Heavy Industry
Heavy industry is most often the cause of flicker. Electric arc furnaces, induction furnaces, static
frequency converters and cyclo-converters are some of the more common offending equipment.
Figure 1 - A PM45 being installed to
help locate a motor start issue. It is
arguably the best test instrument
for this task.
CHK Power QualityPtyLtd Page 20
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Loose Connections
Loose connectionscanalsocause voltage fluctuationsorflicker whether on the low or medium voltage
network.Heavilyloadedconnectionstendtoburnoutquickerbutlightlyloadedconnections may cause
fluctuations or flicker for long periods.
Effects of Voltage Fluctuations and Flicker
The most common effect of voltage fluctuations and flicker is to do with lighting and the human eye.
The incandescentlight globe is sensitive to voltage fluctuations and flicker. Fluorescent lighting is not
immune from such problems but is less prone to problems and tends to dampen voltage variations.
Required Standard
The flickercompatibilitylevel forLV andMV powersystemsisset by AS/NZS61000.3.7 at 1.0 for P-st and
0.8 for P-lt. AS/NZS61000.3.3, AS/NZS61000.3.5 and AS/NZS61000.3.7 set the limits for fluctuations.
Case Study
A customerina semi-rural situationwascomplainingtothe distribution company that their lights were
flickeringall day.A technicianwassentouttoinvestigate.The loggerwassettorecord flickerandrolling
voltage events set at 5%. The logger was down loaded a few days later and the Pst was continually
above the 1.0 limit. The logger failed to record any events outside the 5% rolling level.
The loggerwas reprogrammedwitha3% rollingvoltage setting.The resultsclearlyshowed that a motor
was startingapproximatelyeveryminuteandthe motorwasnot at the complainingcustomer’spremise
(Figure 2).There were twoneighbors,bothwithsingle phase supply, supplied from a common point of
supplyonpowerpole.One logger was installed with A phase C/T clipped over the active to one house
and B phase to the other house.
The results from this logging clearly showed that one house had a motor causing the problems.
Discussionswiththe customer revealed that the motor was on a pressure pump and the pressure tank
had lostitspressure.The customeralsohad a very leaky tap that was causing the pressure pump to cut
inand out, all day long. The customer replaced the valve in the pressure tank, and fixed the leaky tap.
CHK Power QualityPtyLtd Page 21
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Figure 2 - Graph showing a motor start. The starter was continually cutting in and out and causing a nuisance
Conclusions
The PM45 can be a valuable tool in determining the source of voltage fluctuations and flicker and is
arguably the best instrument on the market for locating motor starting problems and in assisting with
the settingof starters. Thisloggeris easyto set,obtainthe loggeddata and then to analyse the results.
CHK Power QualityPtyLtd Page 22
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Event Recording
Introduction
The PM45 notonlyprofiles/logssteady state issues such as voltage
and harmonic levels but can also record one off power quality
events.The memoryallocatedforeventsisindependentof profiling
to ensure thatprofilingisnotdisrupted should significant numbers
of events occur.
Events are divided into the following classes:
 Sag/Swell detection
 RMS capture;
 Transient capture (dV/dt).
Sag/Swell Detection
Sag/Swell detection is used where a list of sag and swell events is
requiredinatable formator where these eventsare required to be
plotted on a curve such as the ITIC curve. Table data includes the time, duration and the maximum or
minimum voltage of the event. Powerview automatically graphs the events on the ITIC curve when
selected.Plottingtoothercurves or manipulation of the data can be achieved by exporting the data to
Excel.
RMS Capture
RMS capture isideal to capture temporary (3 s – 1 min), momentary (30 cycles – 3 s) and instantaneous
(0.5 – 30 cycle) sag, swell and/or interruption events. It is an excellent tool to locate motor start
problemsandwhensettingthe changeover timer for motor starters. Voltage or current can be used to
setthe RMS capture.Interruptionscanbe clearlyseentodetermineif networkprotection equipment is
operating as it should. RMS capture allow comparison with customer logs to determine the cause of
equipment malfunctions or plant failures. Up to 30 seconds of 10 ms data points for 50 Hz supplies are
captured.
Waveformcapture can alsobe selectedwithRMScapture to allow directcorrelation with an RMS event
captured at the same time. This can be handy to see what happened at the onset of the RMS event in
more detail. 400ms of data points are captured at 98 micro-second intervals.
Transient Waveform Capture
Transient waveform capture allows the capture of low frequency oscillatory waveforms that would
occur as a result of the energisation of a capacitor bank and notching caused by the commutation of
electronic devices such as Silicon Controlled Rectifiers.
Setting the Logger
A detailedexplanationof settingthe loggertocapture eventdataandallocationof memory isprovided
inGridsense’sConfigurationGuidesavailable at www.gridsense.net
Figure 1 - A PM45 being installed
at a plastic plant to determine
the cause of plant shutdowns
(see Case Study).
CHK Power QualityPtyLtd Page 23
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
CHK Power QualityPtyLtd Page 24
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
Required Standard
The following provides a summary of the standards that apply to events captured by the PM45:
 Sags – no standard applies at this stage other than the input sags have on flicker and voltage
fluctuations;
 Swells – the National Electricity Rules Figure S5.1a.1;
 RMS voltage capture – voltage fluctuations are managed by AS/NZS61000.3.3, AS/NZS61000.3.5
and AS/NZS61000.3.7;
 RMS currentcapture – large swingsincurrentcause voltage fluctuations and so current capture
isgenerallymanagedthroughthe managementof voltage fluctuations though distributors may
have requirements in local service rules;
 Transient waveform capture – compatibility limits have not been applied for transients and
notchingat thisstage.ObsolescentstandardAS2270.2 providesguidance onthe managementof
notching and oscillatory transients should be managed through good industry practice.
Case Study
A plasticsfactorywashavingproblemswiththe plant’sVariable Speed Drive (VSD) equipment shutting
downrandomlyforno apparentreason.Unblockingof equipmentwas timing consuming and damaging
client relationships due to delays in the supply of their products.
Unseeneventswere suspectedasthe cause andso a PM45 was installedatthe mainswitchboardsetup
to logTransientWaveformcapture,aswell aslogging for RMS capture, voltage and harmonics. Figure 2
shows a low frequency oscillatory transient that was captured by the logger. This event related to a
major shutdown at the plant.
Figure 2 – A Transient Waveform event captured by a PM45 at the plasitcs plant
The networkpowercompanywascontactedto see if theywere switchingcapacitorsatthe time thatthe
oscillatorytransientoccurred.The powercompanyadmittedthatacapacitor bankhad beenswitchedat
the local zone substation at that time and that the bank did not have transient mitigation equipment.
The problemsatthe plasticsplantwasexplained and the power company agreed to stop switching the
capacitorswhenthe plantwas operatingandthat theywouldintroduce transientmitigation equipment
to the capacitor bank as soon as possibe.
Conclusions
The PM45 can be very useful in detecting event based power quality problems. The instrument will
record low frequency oscillatory transients and notching type events. Steady state profiling can be
CHK Power QualityPtyLtd Page 25
Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945
Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105
Website:www.chkpowerquality.com.au ABN: 53 169 840 831
carried out at the same time as event recording. This profiling will not affect the event logging as the
memory is partitioned and separate memory allocated for profiling and events.

More Related Content

What's hot

Power quality 1341013148
Power quality 1341013148Power quality 1341013148
Power quality 1341013148Pradosh Dhal
 
Lind Equipment - Static Bonding, Grounding, Earthing & Lighting Equipment
Lind Equipment - Static Bonding, Grounding, Earthing & Lighting EquipmentLind Equipment - Static Bonding, Grounding, Earthing & Lighting Equipment
Lind Equipment - Static Bonding, Grounding, Earthing & Lighting EquipmentThorne & Derrick International
 
Determining Multiple Fault Ride-Through Requirements for Generating Systems i...
Determining Multiple Fault Ride-Through Requirements for Generating Systems i...Determining Multiple Fault Ride-Through Requirements for Generating Systems i...
Determining Multiple Fault Ride-Through Requirements for Generating Systems i...Power System Operation
 
Analysis of Fault Detection and its Location using Microcontroller for Underg...
Analysis of Fault Detection and its Location using Microcontroller for Underg...Analysis of Fault Detection and its Location using Microcontroller for Underg...
Analysis of Fault Detection and its Location using Microcontroller for Underg...IRJET Journal
 
Pq3 transient over voltages
Pq3 transient over voltagesPq3 transient over voltages
Pq3 transient over voltagesDheeraj Suri
 
EHVAC transmission line maintenance techniques
EHVAC transmission line maintenance techniquesEHVAC transmission line maintenance techniques
EHVAC transmission line maintenance techniquesYashwant Chaudhari
 
What is Power Quality?
What is Power Quality?What is Power Quality?
What is Power Quality?svergin
 
Power Quality Basics_Complex Compatibility_Aclara
Power Quality Basics_Complex Compatibility_AclaraPower Quality Basics_Complex Compatibility_Aclara
Power Quality Basics_Complex Compatibility_AclaraAclara
 
Power Quality & Power Quality Problems
Power Quality & Power Quality ProblemsPower Quality & Power Quality Problems
Power Quality & Power Quality ProblemsPower System Operation
 
POWER QUALITY AUDIT -PM ELECTRONICS
POWER QUALITY AUDIT -PM ELECTRONICSPOWER QUALITY AUDIT -PM ELECTRONICS
POWER QUALITY AUDIT -PM ELECTRONICSPM ELECTRONICS
 
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...IRJET Journal
 
Transcat and Megger: Power Quality 101 Webinar
Transcat and Megger: Power Quality 101 WebinarTranscat and Megger: Power Quality 101 Webinar
Transcat and Megger: Power Quality 101 WebinarTranscat
 
Power quality unit i ANNA UNIVERSITY SYALLABUS
Power quality unit i ANNA UNIVERSITY SYALLABUSPower quality unit i ANNA UNIVERSITY SYALLABUS
Power quality unit i ANNA UNIVERSITY SYALLABUSMOHANASUNDARAM ANTHONY
 
VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER...
 VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER... VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER...
VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER...Gaddafi Sani
 
Condition based monitoring
Condition based monitoringCondition based monitoring
Condition based monitoringNiraj Agrawal
 
Power Quality Issues
Power Quality IssuesPower Quality Issues
Power Quality Issuesmaneesh001
 

What's hot (20)

Power quality 1341013148
Power quality 1341013148Power quality 1341013148
Power quality 1341013148
 
Lind Equipment - Static Bonding, Grounding, Earthing & Lighting Equipment
Lind Equipment - Static Bonding, Grounding, Earthing & Lighting EquipmentLind Equipment - Static Bonding, Grounding, Earthing & Lighting Equipment
Lind Equipment - Static Bonding, Grounding, Earthing & Lighting Equipment
 
Determining Multiple Fault Ride-Through Requirements for Generating Systems i...
Determining Multiple Fault Ride-Through Requirements for Generating Systems i...Determining Multiple Fault Ride-Through Requirements for Generating Systems i...
Determining Multiple Fault Ride-Through Requirements for Generating Systems i...
 
Analysis of Fault Detection and its Location using Microcontroller for Underg...
Analysis of Fault Detection and its Location using Microcontroller for Underg...Analysis of Fault Detection and its Location using Microcontroller for Underg...
Analysis of Fault Detection and its Location using Microcontroller for Underg...
 
Pq3 transient over voltages
Pq3 transient over voltagesPq3 transient over voltages
Pq3 transient over voltages
 
EHVAC transmission line maintenance techniques
EHVAC transmission line maintenance techniquesEHVAC transmission line maintenance techniques
EHVAC transmission line maintenance techniques
 
What is Power Quality?
What is Power Quality?What is Power Quality?
What is Power Quality?
 
Power quality
Power qualityPower quality
Power quality
 
Power Quality Basics_Complex Compatibility_Aclara
Power Quality Basics_Complex Compatibility_AclaraPower Quality Basics_Complex Compatibility_Aclara
Power Quality Basics_Complex Compatibility_Aclara
 
Power Quality & Power Quality Problems
Power Quality & Power Quality ProblemsPower Quality & Power Quality Problems
Power Quality & Power Quality Problems
 
An Overview of Power Quality
An Overview of Power QualityAn Overview of Power Quality
An Overview of Power Quality
 
POWER QUALITY AUDIT -PM ELECTRONICS
POWER QUALITY AUDIT -PM ELECTRONICSPOWER QUALITY AUDIT -PM ELECTRONICS
POWER QUALITY AUDIT -PM ELECTRONICS
 
5standards
5standards5standards
5standards
 
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
 
Transcat and Megger: Power Quality 101 Webinar
Transcat and Megger: Power Quality 101 WebinarTranscat and Megger: Power Quality 101 Webinar
Transcat and Megger: Power Quality 101 Webinar
 
Power quality unit i ANNA UNIVERSITY SYALLABUS
Power quality unit i ANNA UNIVERSITY SYALLABUSPower quality unit i ANNA UNIVERSITY SYALLABUS
Power quality unit i ANNA UNIVERSITY SYALLABUS
 
BMES 2013 Abstract
BMES 2013 AbstractBMES 2013 Abstract
BMES 2013 Abstract
 
VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER...
 VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER... VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER...
VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER...
 
Condition based monitoring
Condition based monitoringCondition based monitoring
Condition based monitoring
 
Power Quality Issues
Power Quality IssuesPower Quality Issues
Power Quality Issues
 

Viewers also liked

Power quality harmonics and accuracy april 2013
Power quality harmonics and accuracy   april 2013Power quality harmonics and accuracy   april 2013
Power quality harmonics and accuracy april 2013Hyteps B.V.
 
Thesis on harmonic distortion ps
Thesis on harmonic distortion psThesis on harmonic distortion ps
Thesis on harmonic distortion pskavithasasidharan
 
Detection and analysis of power quality disturbances under faulty conditions ...
Detection and analysis of power quality disturbances under faulty conditions ...Detection and analysis of power quality disturbances under faulty conditions ...
Detection and analysis of power quality disturbances under faulty conditions ...IAEME Publication
 
Power Quality Site Survey Presentation
Power Quality Site Survey PresentationPower Quality Site Survey Presentation
Power Quality Site Survey PresentationAugusto Abreu
 
Power quality (IV-EEE)
Power quality (IV-EEE)Power quality (IV-EEE)
Power quality (IV-EEE)betasam
 
POWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENTPOWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENTUday Wankar
 
WHY HARMONICS IS UNWANTED ?
WHY HARMONICS IS UNWANTED ?WHY HARMONICS IS UNWANTED ?
WHY HARMONICS IS UNWANTED ?FELIDAE SYSTEMS
 
UG POWER QUALITY (EE2028) ppt
UG POWER QUALITY (EE2028) pptUG POWER QUALITY (EE2028) ppt
UG POWER QUALITY (EE2028) pptHarris Raj
 
Power Quality Systems and Power Factor Correction Presentation
Power Quality Systems and Power Factor Correction PresentationPower Quality Systems and Power Factor Correction Presentation
Power Quality Systems and Power Factor Correction PresentationMircea Gingu
 
grid power quality improvement and battery energy storage in wind energy systems
grid power quality improvement and battery energy storage in wind energy systemsgrid power quality improvement and battery energy storage in wind energy systems
grid power quality improvement and battery energy storage in wind energy systemsST. MARTIN'S ENGINEERING COLLEGE
 
Introduction to Power Quality
Introduction to Power QualityIntroduction to Power Quality
Introduction to Power QualitySteve Johnson
 

Viewers also liked (20)

Power quality harmonics and accuracy april 2013
Power quality harmonics and accuracy   april 2013Power quality harmonics and accuracy   april 2013
Power quality harmonics and accuracy april 2013
 
Thesis on harmonic distortion ps
Thesis on harmonic distortion psThesis on harmonic distortion ps
Thesis on harmonic distortion ps
 
R09 power quality
R09 power qualityR09 power quality
R09 power quality
 
Detection and analysis of power quality disturbances under faulty conditions ...
Detection and analysis of power quality disturbances under faulty conditions ...Detection and analysis of power quality disturbances under faulty conditions ...
Detection and analysis of power quality disturbances under faulty conditions ...
 
Power Quality Standards
Power Quality StandardsPower Quality Standards
Power Quality Standards
 
Power Quality Site Survey Presentation
Power Quality Site Survey PresentationPower Quality Site Survey Presentation
Power Quality Site Survey Presentation
 
Power quality-asia
Power quality-asiaPower quality-asia
Power quality-asia
 
UST Power Quality Basics
UST Power Quality BasicsUST Power Quality Basics
UST Power Quality Basics
 
Power quality (IV-EEE)
Power quality (IV-EEE)Power quality (IV-EEE)
Power quality (IV-EEE)
 
Hormonics impact and_mitigation
Hormonics impact and_mitigationHormonics impact and_mitigation
Hormonics impact and_mitigation
 
POWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENTPOWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENT
 
WHY HARMONICS IS UNWANTED ?
WHY HARMONICS IS UNWANTED ?WHY HARMONICS IS UNWANTED ?
WHY HARMONICS IS UNWANTED ?
 
Ieee power quality distribution systems
Ieee power quality distribution systemsIeee power quality distribution systems
Ieee power quality distribution systems
 
Harmonics
HarmonicsHarmonics
Harmonics
 
Harmonics
HarmonicsHarmonics
Harmonics
 
UG POWER QUALITY (EE2028) ppt
UG POWER QUALITY (EE2028) pptUG POWER QUALITY (EE2028) ppt
UG POWER QUALITY (EE2028) ppt
 
Power Quality Systems and Power Factor Correction Presentation
Power Quality Systems and Power Factor Correction PresentationPower Quality Systems and Power Factor Correction Presentation
Power Quality Systems and Power Factor Correction Presentation
 
General Power Quality
General Power QualityGeneral Power Quality
General Power Quality
 
grid power quality improvement and battery energy storage in wind energy systems
grid power quality improvement and battery energy storage in wind energy systemsgrid power quality improvement and battery energy storage in wind energy systems
grid power quality improvement and battery energy storage in wind energy systems
 
Introduction to Power Quality
Introduction to Power QualityIntroduction to Power Quality
Introduction to Power Quality
 

Similar to Power monic application notes chk power quality

Fluke1748 - power quality measurements on overhead lines
Fluke1748 - power quality measurements  on overhead lines Fluke1748 - power quality measurements  on overhead lines
Fluke1748 - power quality measurements on overhead lines Karol Bielecki
 
EA Technology Electricity North West Savings Case Study
EA Technology Electricity North West Savings Case StudyEA Technology Electricity North West Savings Case Study
EA Technology Electricity North West Savings Case StudyThorne & Derrick International
 
CenterPoint Energy: Preparing for a Hurricane and its Aftermath
CenterPoint Energy: Preparing for a Hurricane and its AftermathCenterPoint Energy: Preparing for a Hurricane and its Aftermath
CenterPoint Energy: Preparing for a Hurricane and its Aftermathaectnet
 
Design Development and Testing of an Overvoltage and Undervoltage Protection ...
Design Development and Testing of an Overvoltage and Undervoltage Protection ...Design Development and Testing of an Overvoltage and Undervoltage Protection ...
Design Development and Testing of an Overvoltage and Undervoltage Protection ...Kunal Maity
 
Preparing for a Hurricane and its Aftermath
Preparing for a Hurricane and its AftermathPreparing for a Hurricane and its Aftermath
Preparing for a Hurricane and its Aftermathaectnet
 
windfarmgridissues.pdf
windfarmgridissues.pdfwindfarmgridissues.pdf
windfarmgridissues.pdfsundeepsiddula
 
Singapore Smart Grid From Concept to Reality Slides.pdf
Singapore Smart Grid From Concept to Reality Slides.pdfSingapore Smart Grid From Concept to Reality Slides.pdf
Singapore Smart Grid From Concept to Reality Slides.pdfPohLianLam1
 
Power distribution system fault monitoring device for supply networks in Nigeria
Power distribution system fault monitoring device for supply networks in NigeriaPower distribution system fault monitoring device for supply networks in Nigeria
Power distribution system fault monitoring device for supply networks in NigeriaIJECEIAES
 
Earthing and disconnecting panel report.pdf
Earthing and disconnecting panel report.pdfEarthing and disconnecting panel report.pdf
Earthing and disconnecting panel report.pdfMohitKumar989420
 
Implementation of a Microcontroller Base Single Phase Automatic Changeover
Implementation of a Microcontroller Base Single Phase Automatic Changeover Implementation of a Microcontroller Base Single Phase Automatic Changeover
Implementation of a Microcontroller Base Single Phase Automatic Changeover IJSRED
 
The value of power factor testing
The value of power factor testingThe value of power factor testing
The value of power factor testingAbi finni
 
Chep 02 Power Frequency Disturbance
Chep 02 Power Frequency DisturbanceChep 02 Power Frequency Disturbance
Chep 02 Power Frequency DisturbancePiyush Tandel
 
Smart Wireless Battery Charger with Charging Monitor: A Review
Smart Wireless Battery Charger with Charging Monitor: A ReviewSmart Wireless Battery Charger with Charging Monitor: A Review
Smart Wireless Battery Charger with Charging Monitor: A ReviewIRJET Journal
 
Simulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra CapacitorSimulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra CapacitorIRJET Journal
 
IRJET- Voltage Swells and Transient Research Considering ARC Load
IRJET-  	  Voltage Swells and Transient Research Considering ARC LoadIRJET-  	  Voltage Swells and Transient Research Considering ARC Load
IRJET- Voltage Swells and Transient Research Considering ARC LoadIRJET Journal
 
Save on Energy - Learn How To Save On Your Electricity Bill
Save on Energy - Learn How To Save On Your Electricity BillSave on Energy - Learn How To Save On Your Electricity Bill
Save on Energy - Learn How To Save On Your Electricity BillCatherine Bryenton
 

Similar to Power monic application notes chk power quality (20)

High voltage megger electric shock Omer Saeed
High voltage megger electric shock   Omer SaeedHigh voltage megger electric shock   Omer Saeed
High voltage megger electric shock Omer Saeed
 
Fluke1748 - power quality measurements on overhead lines
Fluke1748 - power quality measurements  on overhead lines Fluke1748 - power quality measurements  on overhead lines
Fluke1748 - power quality measurements on overhead lines
 
EA Technology Electricity North West Savings Case Study
EA Technology Electricity North West Savings Case StudyEA Technology Electricity North West Savings Case Study
EA Technology Electricity North West Savings Case Study
 
CenterPoint Energy: Preparing for a Hurricane and its Aftermath
CenterPoint Energy: Preparing for a Hurricane and its AftermathCenterPoint Energy: Preparing for a Hurricane and its Aftermath
CenterPoint Energy: Preparing for a Hurricane and its Aftermath
 
Design Development and Testing of an Overvoltage and Undervoltage Protection ...
Design Development and Testing of an Overvoltage and Undervoltage Protection ...Design Development and Testing of an Overvoltage and Undervoltage Protection ...
Design Development and Testing of an Overvoltage and Undervoltage Protection ...
 
Preparing for a Hurricane and its Aftermath
Preparing for a Hurricane and its AftermathPreparing for a Hurricane and its Aftermath
Preparing for a Hurricane and its Aftermath
 
windfarmgridissues.pdf
windfarmgridissues.pdfwindfarmgridissues.pdf
windfarmgridissues.pdf
 
Singapore Smart Grid From Concept to Reality Slides.pdf
Singapore Smart Grid From Concept to Reality Slides.pdfSingapore Smart Grid From Concept to Reality Slides.pdf
Singapore Smart Grid From Concept to Reality Slides.pdf
 
Wireless Charging
Wireless ChargingWireless Charging
Wireless Charging
 
Power distribution system fault monitoring device for supply networks in Nigeria
Power distribution system fault monitoring device for supply networks in NigeriaPower distribution system fault monitoring device for supply networks in Nigeria
Power distribution system fault monitoring device for supply networks in Nigeria
 
EA Technology Electricity North West Case Study
EA Technology Electricity North West Case StudyEA Technology Electricity North West Case Study
EA Technology Electricity North West Case Study
 
Earthing and disconnecting panel report.pdf
Earthing and disconnecting panel report.pdfEarthing and disconnecting panel report.pdf
Earthing and disconnecting panel report.pdf
 
Implementation of a Microcontroller Base Single Phase Automatic Changeover
Implementation of a Microcontroller Base Single Phase Automatic Changeover Implementation of a Microcontroller Base Single Phase Automatic Changeover
Implementation of a Microcontroller Base Single Phase Automatic Changeover
 
The value of power factor testing
The value of power factor testingThe value of power factor testing
The value of power factor testing
 
wireless power transfer
wireless power transferwireless power transfer
wireless power transfer
 
Chep 02 Power Frequency Disturbance
Chep 02 Power Frequency DisturbanceChep 02 Power Frequency Disturbance
Chep 02 Power Frequency Disturbance
 
Smart Wireless Battery Charger with Charging Monitor: A Review
Smart Wireless Battery Charger with Charging Monitor: A ReviewSmart Wireless Battery Charger with Charging Monitor: A Review
Smart Wireless Battery Charger with Charging Monitor: A Review
 
Simulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra CapacitorSimulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra Capacitor
 
IRJET- Voltage Swells and Transient Research Considering ARC Load
IRJET-  	  Voltage Swells and Transient Research Considering ARC LoadIRJET-  	  Voltage Swells and Transient Research Considering ARC Load
IRJET- Voltage Swells and Transient Research Considering ARC Load
 
Save on Energy - Learn How To Save On Your Electricity Bill
Save on Energy - Learn How To Save On Your Electricity BillSave on Energy - Learn How To Save On Your Electricity Bill
Save on Energy - Learn How To Save On Your Electricity Bill
 

More from Ajeesh Joseph

Transformer monitor and logger
Transformer monitor and loggerTransformer monitor and logger
Transformer monitor and loggerAjeesh Joseph
 
Technical note Miro automatic ftp uploads - r 30 sep 16
Technical note   Miro automatic ftp uploads - r 30 sep 16Technical note   Miro automatic ftp uploads - r 30 sep 16
Technical note Miro automatic ftp uploads - r 30 sep 16Ajeesh Joseph
 
Technical note configuring the miro for cellular communications - r 30 sep 16
Technical note   configuring the miro for cellular communications - r 30 sep 16Technical note   configuring the miro for cellular communications - r 30 sep 16
Technical note configuring the miro for cellular communications - r 30 sep 16Ajeesh Joseph
 
Brochure - Maximum demand indicator using Mirrin
Brochure - Maximum demand indicator using MirrinBrochure - Maximum demand indicator using Mirrin
Brochure - Maximum demand indicator using MirrinAjeesh Joseph
 
Brochure - Pole top Transformer Monitoring using Mirrin
Brochure - Pole top Transformer Monitoring using MirrinBrochure - Pole top Transformer Monitoring using Mirrin
Brochure - Pole top Transformer Monitoring using MirrinAjeesh Joseph
 
Brochure pq investigations
Brochure pq investigationsBrochure pq investigations
Brochure pq investigationsAjeesh Joseph
 
Miro class a power quality analyzer and logger.compressed
Miro class a power quality analyzer and logger.compressedMiro class a power quality analyzer and logger.compressed
Miro class a power quality analyzer and logger.compressedAjeesh Joseph
 
Miro power quality analyser Class A user manual Apr-2016-compressed
Miro power quality analyser Class A user manual Apr-2016-compressedMiro power quality analyser Class A user manual Apr-2016-compressed
Miro power quality analyser Class A user manual Apr-2016-compressedAjeesh Joseph
 
Pm45 brochure a4 25 sep08
Pm45 brochure a4 25 sep08Pm45 brochure a4 25 sep08
Pm45 brochure a4 25 sep08Ajeesh Joseph
 
Typical applications for mirrin ll400 load logger
Typical applications for mirrin ll400 load loggerTypical applications for mirrin ll400 load logger
Typical applications for mirrin ll400 load loggerAjeesh Joseph
 
CHK Power Quality products & services catalogue 22 sep 14 release
CHK Power Quality products & services catalogue 22 sep 14 releaseCHK Power Quality products & services catalogue 22 sep 14 release
CHK Power Quality products & services catalogue 22 sep 14 releaseAjeesh Joseph
 
CHK Power Quality - Products and Services catalogue 2014
CHK Power Quality - Products and Services catalogue 2014CHK Power Quality - Products and Services catalogue 2014
CHK Power Quality - Products and Services catalogue 2014Ajeesh Joseph
 

More from Ajeesh Joseph (13)

Transformer monitor and logger
Transformer monitor and loggerTransformer monitor and logger
Transformer monitor and logger
 
Technical note Miro automatic ftp uploads - r 30 sep 16
Technical note   Miro automatic ftp uploads - r 30 sep 16Technical note   Miro automatic ftp uploads - r 30 sep 16
Technical note Miro automatic ftp uploads - r 30 sep 16
 
Technical note configuring the miro for cellular communications - r 30 sep 16
Technical note   configuring the miro for cellular communications - r 30 sep 16Technical note   configuring the miro for cellular communications - r 30 sep 16
Technical note configuring the miro for cellular communications - r 30 sep 16
 
Brochure - Maximum demand indicator using Mirrin
Brochure - Maximum demand indicator using MirrinBrochure - Maximum demand indicator using Mirrin
Brochure - Maximum demand indicator using Mirrin
 
Brochure - Pole top Transformer Monitoring using Mirrin
Brochure - Pole top Transformer Monitoring using MirrinBrochure - Pole top Transformer Monitoring using Mirrin
Brochure - Pole top Transformer Monitoring using Mirrin
 
Brochure pq investigations
Brochure pq investigationsBrochure pq investigations
Brochure pq investigations
 
Miro class a power quality analyzer and logger.compressed
Miro class a power quality analyzer and logger.compressedMiro class a power quality analyzer and logger.compressed
Miro class a power quality analyzer and logger.compressed
 
Miro power quality analyser Class A user manual Apr-2016-compressed
Miro power quality analyser Class A user manual Apr-2016-compressedMiro power quality analyser Class A user manual Apr-2016-compressed
Miro power quality analyser Class A user manual Apr-2016-compressed
 
Liq 60 tech spec
Liq 60 tech specLiq 60 tech spec
Liq 60 tech spec
 
Pm45 brochure a4 25 sep08
Pm45 brochure a4 25 sep08Pm45 brochure a4 25 sep08
Pm45 brochure a4 25 sep08
 
Typical applications for mirrin ll400 load logger
Typical applications for mirrin ll400 load loggerTypical applications for mirrin ll400 load logger
Typical applications for mirrin ll400 load logger
 
CHK Power Quality products & services catalogue 22 sep 14 release
CHK Power Quality products & services catalogue 22 sep 14 releaseCHK Power Quality products & services catalogue 22 sep 14 release
CHK Power Quality products & services catalogue 22 sep 14 release
 
CHK Power Quality - Products and Services catalogue 2014
CHK Power Quality - Products and Services catalogue 2014CHK Power Quality - Products and Services catalogue 2014
CHK Power Quality - Products and Services catalogue 2014
 

Recently uploaded

High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 

Recently uploaded (20)

High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 

Power monic application notes chk power quality

  • 1. CHK Power QualityPtyLtd Page 1 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Electric Shock Investigations Introduction Electric shocks can be of a minor nature or can be devastating, resulting in severe injury or death. Technicians involved in the investigation of electric shock incidents need to be well trained and equipped with high quality test equipment so that the incident is resolved quickly to prevent further incidents and in case of litigation. A multimeter, fault loop impedance tester, safety switch tester and a power quality logger may be some of the requiredtestequipment. The PM45 is an excellent logger to assistininvestigationsasithas an additional voltage channel for logging shock voltages (see Figure 1). Causes of Electric Shock Electric shocks can occur for a variety of reasons such as:  Raised neutral-earth voltages caused by:  Poor or open circuit neutral connections in the grid or within an electricity users installation;  Long runs of neutral conductor in the grid or within an electricity users installation;  Reverse polarity connection of an installation or at another installation;  Overloading of the neutral conductor because of unbalance loads;  Faulty wiring or equipment that has not tripped circuit protection.  Touching fallen powerlines;  Live roofs where a nail or screw has punctured an energised electricity cable;  Faulty wiring or equipment;  Misuse of electrical equipment;  Low energy shocks such as static, induced voltages or leakage through a high impedance path. Effects of Electric Shock Personsmayreceive a‘tingle’withlittleornolongterm physical or mental effects. More severe shocks can have devastating health effects both mentally and physically for the victim. Animalsmayalsobe affectedbyelectric shocks. Large animals such as cows and horses are affected by stepvoltagesmuchmore thanpeople due tothe large distance betweenfrontandbacklegs.Dairy cows may sufferfromnervousness,excessive defecationandurination,reducedmilk supply and may have an elevated mastitis count even if only receiving very minor tingles. The causes of electricshockproblems,as detailedabove,canalsodamage electrical equipment. A poor or open circuit neutral connection or a long run of neutral often results in damaging low and/or high volts being delivered to electrical equipment. Figure 1 - A trained technician installing a PM45 to log the neutral-earth voltage. The remote earth lead should be installed not to create a trip or electrical hazard.
  • 2. CHK Power QualityPtyLtd Page 2 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 A reverse polarity of a multiphase installation can result in severe electric shocks and phase to phase voltage beingappliedtophase toneutral equipment.Thisequipmentisgenerallydamaged severely and may cause a fire that could also raze premises to the ground. Required Standard AS/NZS60479 detailsthe effectsof electriccurrentonhumanbeingsandlivestock. However,it does not setacceptable levelsfortouchvoltages. IEC61200-413 provides curves with limits of touch voltage that can be sustained indefinitely depending on normal or wet conditions. The levels provided by these curves can result in a nasty shock and so many Australian distributors rely on a limit of 10 volts or less for neutral-earth voltages. Case Study A customerinan urban situationhadbeenreceivingelectricshocksinthe shower for the last 2 months. A trainedtechnician investigated and found minor voltages of up to 3 volts in the shower when all the load in the installation was turned on. This level of voltage would not normally be of concern but the customer was adamant that the problem had recently started. Furtherinvestigationsfoundthata neutral connectioninthe street mains was open circuit. The neutral currentwas forcedto take alternate paths back to the distribution transformer resulting in the voltage on the neutral conductorbeingelevatedabove normal levels. This voltage is then transferred onto the water pipes by the equipotential earthing bond. A PM45 was connected to monitor the neutral-earth voltage at the customer’s installation to ensure that all was backto normal (see Figure 1). The loggerwas removedaday lateranddownloaded.Figure2 showsthe resultsof that downloadwiththe neutral-earthvoltage peakingat0.52 voltswhichmeantthe problem had been rectified. The customer also advised they were no longer receiving shocks in the shower and everything was back to normal. Figure 2 - PM45 neutral-earth voltage trace showing very minor voltage levels Conclusions Technicians involved in the investigation of electric shock need high quality equipment such as multimeters,fault loop impedance testers, safety switch testers and power quality loggers e.g. PM45. Thistestequipmentcanassistinidentifyingthe cause of the problem soa solution canbe implemented to preventfurtherincidents.A faultyneutral connection will simply need to be replaced. A long run of neutral conductor, that is causing an elevated voltage on the taps in a shower, may need to be re- conductored with larger cable or a transformer installed closer to the load.
  • 3. CHK Power QualityPtyLtd Page 3 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 A power quality logger, such as the PM45, can log the supply voltages and load current, as well the neutral to earth voltage and verify if the problem is related to the load. Supply voltages that vary considerably may be caused by a floating neutral/open circuit or poor neutral connection. All in all, the PM45 is an excellent tool to assist in the investigation and resolution of electric shock problems.
  • 4. CHK Power QualityPtyLtd Page 4 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Excessive Energy Usage Introduction Electricity costs are continually increasing and the need to minimise climate change requiresthe reductioninenergyusage.Aspartof this, manygovernments are also requiring energy conservation and more stringent control and management of energy usage, particularly for large energy users. The PM45 issimple to use,accurate and an essential tool for those in the energymanagementfieldtoassistinthe reductionof greenhouse gases and electricity costs (Figure 1). Causes of Excessive Costs Excessive Usage If electrical equipment is not turned on then it is not costing. This is a simple message but not easy to manage for those with large numbers of electricity users in the premise and/or a larger premise. However,electricityusage canbe recordedbya powerqualityorenergylogger to determine when and where electricity is being used. This then allows an analysis of where energy can be saved. Poor Power Factor Poorpowerfactor ismostlycausedby inductionmotorswhere the currentlags the voltage. This results inadditional wastedenergyandgreenhouse gases. There will be no reduction in electricity costs if the premise isonlybeingchargedforkilowatthours and power factor correction equipment was installed. But, there may be significant savings if the electricity tariff penalises for poor power factor e.g. a kVA charge on top of kilowatt hours. If there are no cost savings to be made, then the only benefits may be a release in capacity of the supplying transformer and mains if power factor correction capacitors were installed. This may save significant upgrade costs as well as reducing greenhouse gases. Powerfactorstandardsare setby the National ElectricityRulesforabove 1kV andby local distributorfor less than 1kV. Wrong Tariff or Wrong Time of Use The most suitable tariff for the premise can be determined by logging the electrical load. The logged data isthenanalysedtodetermine the mostappropriate tariff. Changing tariffs can result in significant savings and in one case resulted in an annual reduction from $20,000 to $14,000 – a saving of $6000/year. Figure 1 - A PM45 being installed for an energy audit
  • 5. CHK Power QualityPtyLtd Page 5 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Time of Use tariffscharge more for electrical usage whenthe electricityis used in peak periods than for shoulderoroff-peakperiods.Careful analysisof PM45 graphsand an intimate knowledge of operations may allow for movement of load from higher tariff periods to cheaper times of use, thus saving costs. Case Study A factorywas payingan annual electricityaccountthattheybelieved was excessive for the size of their operations. An installed a PM45 recorded the electricity usage and power factor over one week. The audit found that the considerable energy was being used at nights when only the cleaning crews were on-site, attributed to the turning on all air conditioning at the facility. Discussions with cleaners determined that most of the air conditioners could be left off at night except as required in each location,as the cleaners moved from location to location, to maintain air quality. The factory’s energy management system was programmed to prevent the use of all air conditioners at night. The power factor at the site was extremely poor and down to about 0.65 lagging on one phase and neverabove the required0.9standard on any phase at any time (Figure 2). Installation of power factor correction capacitors saw a reduction in kVA demand, line losses and greenhouse gases. The power factor correctionunitshowedareturnon assetswithinapproximately18 months. After this period, the reductioninelectricitycostscontributedtoannual profitswhilstassistingingreenhouse gasabatement. Figure 2 - Power Factor Graph for Factory The audit alsodetermined that significant loads could be transferred to off-peak operation to provide for betterplantutilisationandsignificantenergysavings.Unfortunately,awardpaymentsforstaff wages offsetanysavingsandso the transferdidnotgo aheadat that stage.Awardnegotiations are continuing with the union involved.
  • 6. CHK Power QualityPtyLtd Page 6 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Conclusions The PM45 can be an extremely valuable tool in reducing electricity costs and in the reduction of greenhouse gases. The PM45 can be used to check when and where electricity is being used and at what power factor.
  • 7. CHK Power QualityPtyLtd Page 7 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Harmonic Pollution Introduction The quality of the electricity supply is a quite complex issue. The focus of powerproblemsinyearsgone by has been more on voltage quality than the more technical aspects of power quality. This may still be the case in some power companies where problems are referred to as voltage complaints. The requirement for a higher quality electricity supply has come with the proliferation of sensitive equipment which generate more harmonics themselves. The PM45 records levels of individual harmonics as well as THD-f, which is Total Harmonic Distortion (THD) - a measure of the effective valueof harmonicdistortion.More specifically it is the ratio of the rms value of the harmonic content of an alternating voltage or current to the rms value of the fundamental component of the voltage or current. Inter-harmonics can also be recorded which are harmonic frequencies that are not an integer of the fundamental. Causes of Harmonics Harmonicsare sinusoidal voltagesorcurrentshavingfrequenciesthatare integermultiplesof the supply frequency. Harmonicsare generallycausedbynon-linear loads i.e. equipment that has a capacitor and a diode or diode type device (e.g. Silicon Controlled Rectifier). This type of combination is generally foundin equipmentwithaswitchmode powersupply. Harmonicsare generallyatmuchhigherlevelsin industrial premisesorcommercial premises which oftenhave variablespeeddrivesor many computers. Inter-harmonicsare voltagesorcurrenthavingfrequencycomponents that are not integer multiples of the supplyfrequency.The mainsourcesof inter-harmonicsare heavy industry equipment such as static frequency converters, cyclo-converters, induction furnaces and arcing devices. Power-line-carrier signals are regarded as inter-harmonics. Effects of Harmonic Pollution The effects of harmonics include: • Eddy current heating in equipment • Noise and torque oscillation in motors • Vibration or noise in panels • Nuisance tripping of breakers & fuses • Metering errors • Electronic equipment malfunctions • Generator speed/frequency instability • Telephone noise interference • Data transfer errors
  • 8. CHK Power QualityPtyLtd Page 8 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 • Resonance causing large voltages & currents The effects of Inter-harmonics include: • Distortion of power-line-carrier signals • Flicker of fluorescent and arc lighting • Flicker of computer display devices Required Standard Levels of harmonic distortion should meet the compatibility levels of AS/NZS61000.3.6 (Figure 2). The standard also allows a distributor to record harmonic levels before and after the connection of a new installation or load to ensure the customer does not exceed the distributor’s emmission limits. Case Study A plantwashaving problems in the early hours of the morning with circuit breakers tripping randomly for nogood reason. Monitoring was carried out with a PM45 configured to record harmonic problems. Voltage THD levelswere foundtobe nearing10% at timesand well above allowable compatibilitylevels (Figure 3). It was believed that harmonics were causing the circuit breakers to trip. A Variable Speed Drive (VSD) on the premise was controlling a quite large motor that was started at around 2 am in the morning. The VSD was confirmed as the source of problems and the manufacturer was contactedto solve the problem. Circuit breakers did not trip after the solution was implemented. Figure 3 - Graph showing excessive harmonics at the circuit breaker panel Figure 2: Compatibility levels for harmonic voltages (in percent of the nominal voltage) in LV and MV power systems Odd harmonics non multiple of 3 Odd harmonics multiple of 3 Even Harmonics Order h Harmonic voltage % Order H Harmonic voltage % Order H Harmonic voltage % 5 7 11 13 17 19 23 25 >25 6 5 3.5 3 2 1.5 1.5 1.5 0.2+ 1.3 (25/h) 3 9 15 21 >21 5 1.5 0.3 0.2 0.2 2 4 8 10 12 >12 2 1 0.5 0.5 0.5 0.2 0.2 NOTE – Total harmonic distortion (THD): 8%
  • 9. CHK Power QualityPtyLtd Page 9 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Conclusions Harmonicsare causedby non-linearloadsandare oftena probleminindustrial and commercial supply. The PM45 can be a valuable tool indeterminingif harmonics or inter-harmonics are at excessive levels and in locating the source of the problem.
  • 10. CHK Power QualityPtyLtd Page 10 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Monitoring Zone Substations Introduction A PowerMonic (power quality loggers) may be installed at zone substations, either for a short-term investigation or as a long-term monitoringdevice.The zone substation may be either owned by the power company or the electricity customer/user. Remote communication with the PowerMonic may be important to save travel time, particularly where permanently installed. The PM45 provides a particularly good option for such situations as it is robust, provides quality data and is easy to install (Figure 1). Reasons for Installing Loggers at Zone Substations The installation of a logger at a zone substation may occur for the following reasons: 1. Compliance withregulatororstate code requirements –insome states the state regulator requires that a power quality monitor be installed at each power company’s zone substations. 2. Power quality check before payment of claims – customers are increasingly claiming from power companiesfordamagedelectrical orelectronicequipment.The zone substation graphs can be used by the powercompany to verifythe qualityof the supplyleaving the zone substation at the time of the incidentthatallegedlydamagedthe equipment. Checkingpowerqualitylogsmaybe part of the investigationif aclaim is to be rejected by the power company or as justification for a claim by the customerif the loggerwas installed. A disrupting event may cost a plant thousands or hundreds of thousands of dollars, so it is important to have the detail to justify the claim. 3. Continual checking of zone substation capacity – zone substation loads are generally on the increase. A power quality logger allows continual checking of the available capacity at the zone substation. Thereby helping to ensure that overloads and loss of supply do not occur. 4. Newconnectionof alarge customerand providingpowerquality indices –. The collection of power quality data can allow power quality indices to be collated that can be very beneficial to the new customers,especiallyif theyare connecting directly from the zone substation. This allows the new customer to determine the level of robustness of their plant and equipment, which is particularly important when specifications for the plant and equipment are being developed. 5. Exceedancescapturedcanbe usedto checkthe operationof zone substationprotectionequipment – Events can be captured by the power quality logger that can verify if protection equipment has Figure 1 - A PM45 being installed on a zone substation indoor transformer panel to monitor power quality on a temporary basis.
  • 11. CHK Power QualityPtyLtd Page 11 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 performed as it should when a network problem occurs. An exceedance may show that a circuit breaker did not work as intended and took an excessive time to open. 6. Check of frequency injection or ripple signal loads – frequency injection signals can cause large jumps in load if the connection of the controllers is not adequately controlled. Installation of the Logger The loggerwill need tobe configuredtocapture the required data. Part of this set-up will be to set the nominal voltage to the nominal output voltage of the voltage transformer (VT). The powerqualityloggershouldbe connectedtothe zone substationoutputbusbar’sVTsupplyand the powertransformer’scurrent transformers (CT). Alternatively, the logger can be connected to a feeder circuit breaker CT’s. The connection to the CT’s is best performed using a GridSense Substation CT Converter Kit which isolates the CT circuit from the PowerMonic to ensure integrity of the CT circuit. The logger is now set-up and running. A land-line or cellular modem may be connected for the data communication. A system needs to be established for data storage to ensure that the data is readily available for the analysis of events or long-term trending of power quality indices. Case Study A powercompanywashavingcustomercomplaintsthatcorrelatedtoone zone substationthatsupplied a large component of commerical load. The zone substation was supplied from a long transmission network that supplied numerous zone substations. A PM45 logger was installed at the zone substation on the output from the zone substation power transformer.Figure 2showsthat the voltage outputfromthe zone substationwasdroopingatpeakload times.The transformertapchangerwas suspectedof runningout of boost taps following an analysis of the graph. Tap positioninformationwasanalysedfromthe dataaquistionsystematthe zone substation and yes, the transformer was running out of boost taps. The transmission campany was asked to include Line Drop Compensation settings on their supply, so that supplyvoltage wasboostedatpeak times, as a short to medium term fix. This solved the problem and a long-term fix was scheduled in the following year.
  • 12. CHK Power QualityPtyLtd Page 12 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Figure 2 - Graph showing voltage drooping at peak load from a zone substation Conclusions A PowerMonic can be easily configured and installed in a zone substation for a short or long-term investigation. The benefits for long-term monitoring are many and the costs are easily justified.
  • 13. CHK Power QualityPtyLtd Page 13 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Steady-State Voltage Problems Introduction Steady-state voltageproblemsrelateto long duration over and/or undervoltage situations.Thisiswhere the voltage istypicallymore than 10% above or below the nominal voltage for long durations, typically longer than 1 minute. International standards require logging equipment to be set at 10 minute averages when logging for steady-state voltage problems.This is required if an electricity customer was to have a dispute with the distribution company. However, it may be more appropriate to record at much shorter averages when trying to determine what is causing problems. The PM45 can logat averagesdownto10 seconds.Figure 1 shows a PM45, powerqualitylogger,beinginstalled in response to a voltage problem. The PM45 has memory allocatedforsteadystate logging,orprofilingasitis sometimescalled,isindependent of logged events and so the requiredprofilingperiodisassuredandcannotbe usedif excessive numberof eventswereto occur. Causes of Steady-State Voltage Problems Overloading Overloading of distribution cables and transformers or cabling within the installation often results in longdurationunder-voltage problems. Overvoltageproblemscanalsooccur,but lessfrequently, where a single phase is over loaded on a three phase system. This can offset the neutral point in a star three phase systemandcause one of the phases to go above and the other phases to go below the standard. Inappropriate Design Networks or installations are occasionally installed with inappropriate sized conductors and hence an overloadsituationcanoccurright fromthe outset.The PM45 can be usedto assist in determining if the designer has designed less than ideally. Load Switching Switching on or off large loads can cause large variations in the voltage. Network automatic tap changers(voltage adjustingequipment) cantake some minutestorespondandsolong duration voltage variations can occur. Under-voltage can occur where large loads are switched on and over-voltage where the large load has been switched off. Figure 1 - A PM45 being installed at a house where the stove is not cooking effectively.
  • 14. CHK Power QualityPtyLtd Page 14 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Faulty Regulating Equipment Distribution companies have automatic regulator equipment as described above on their high and mediumvoltage networks.Some are eveninstallingthemontheir low voltage distribution networks to correct localised problems. This equipment can fail and is likely to cause over and/or under voltage depending on what has occurred and the amount of load on the feeder/circuit. Network Reconfiguration Distribution companies need to reconfigure their networks for various reasons, including for maintenance and repair which results in less than ideal supply voltage. This may be until regulating equipment responds or for much longer durations until the network is returned to normal. Effects of Steady-State Voltage Problems The effects of steady-state voltage problems are divided into two categories as follows: Sustained Over-voltage  Lights globes reduced life span  Electronic equipment life reduction  Equipment destruction - high voltages  Increased motor losses  Overvoltage protection operation Sustained Under-voltage  Slowness with cooking  Dullness in incandescent lighting  Discharge lighting drop outs  Contactor chatter and heating  Increased motor losses Required Standard The required level of voltage to be supplied by a distributor in Australia is either set by the National ElectricityRules,AS60038 and/orstate basedlegislation.Atlow voltage,the distributor should supply a nominal voltage of 230 volts, plus 10% and minus 6% at the point of supply. A voltage transformerwillbe requiredtomeasure voltagesathighvoltage anda GridSense PowerMonic substationconverterkittoconnectto substation CTs(ApplicationNote –MonitoringZone Substations). Case Study A motherishavingproblemswithcookingthe eveningmeal andwithdull lights.A PM45 was installedat the point of supply to determine if the incoming supply was up to standard. Figure 2 showsthe resultsof the loggingwiththe voltage below the requiredstandard for unacceptable periodsof time.The graphwas suppliedto the distribution company, who investigated and found that the user had increased their load and overloaded the low voltage supply network.
  • 15. CHK Power QualityPtyLtd Page 15 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Figure 2 - Graph showing long duration under voltage problem in the evening Conclusions The PM45 can be an extremely valuable tool in determining the cause of long duration under and/or over voltage problems. The logger will need to be set to log for 10 minute averages if there is dispute and maybe setat intervalsmuch less than 10 minutes to assist in locating the source of problems. The PM45 can also be useful with other steady-state problems such as voltage unbalance and harmonics.
  • 16. CHK Power QualityPtyLtd Page 16 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Voltage and Current Unbalance Introduction Voltage unbalance occurs in a three-phase system where there is a difference in the values of voltages or where the phase separation is not 120 degrees. Current unbalance is similar except the values are for current instead of voltage. Large levels of current unbalance generally cause voltage unbalance. Voltage unbalance is normally calculated using two methods.The firstiswhere the negative sequence voltage is expressedasapercentage of the positive sequence voltage (the method used in the PowerMonic). The second method usesthe maximumdeviationfromthe meanof the three line values expressed as a percentage of the mean of the three line voltages. The values for this method can be obtained from a PowerMonic using an export of the voltage data to a spreadsheet and then calculated. Current unbalanced is calculated simile using values for current. The PowerMonicisan excellentinstrumentforloggingvoltage and current unbalance. Figure 1 shows a PM45 being installed where a motor is becoming overheated. Causes of Voltage and Current Unbalance Currentunbalance isthe primarycause of voltage unbalance, as described in the introduction. Current unbalance may be caused by the following: • Large and/or unequal distribution of single-phase load – this often occurs with overhead networkswhere the linespersonconnectslow voltage single-phaseservicestothe closest phase to the neutral (nicknamed“short-armedlinesman’ssyndrome”).The same problem can occur at medium voltage levels where single-phase distribution transformers are all connected to the easiest to reach conductors. • Phase to phase loads – thisoccurs withsome equipmentthatsimplyrequiressingle phasebutat line-to-line voltage e.g. 415 volt welder. • Unbalancedthree phase loads –some three phase loadsare made up of single and three phase equipment. It is important that these loads are balanced to meet the power company’s requirements. Figure 1 – A PM45, configured for voltage unbalance, is being installed at a motor to determine the cause of over heating - voltage unbalance is suspected.
  • 17. CHK Power QualityPtyLtd Page 17 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Unequal impedances of a three-phase transmission and distribution networks also causes voltage unbalance – this occurs where the overhead transmission or distribution system does not have adequate and regular transposition of the phases to balance the system impedance. Effects of Voltage Unbalance Resistive loadsare relativelyunaffected by voltage unbalance. However, the major problem with voltage unbalance is that it causes additional heating/losses with three-phase motors. Motors may also be noisy due to torque and speed variations caused by the voltage unbalance and will have less effective torque and speed than normal. The voltage unbalance also causesan increase incurrent unbalance well in excess of the voltage unbalance percentage. Figure 2 shows a standard that allows for de-rating motors based on the percentage of voltage unbalance. Variable speeddrives(VSD) maytripoff due toan increase inac line currentscausedby a compensation for the voltage unbalance.Increasedthermalstress of VSD diodes and dc link capacitors and additional triplen harmonics can also occur. Required Standard The National Electricity Rules sets the limits for voltage unbalance as per Figure 3. Figure 3: Voltage Unbalance Limits Nominal Supply Voltage Negative Sequence Voltage(% of Nominal Voltage) Column 1 Column 2 Column 3 Column 4 Column 5 no contingency event credible contingency event General Once per hour 30 minute average 30 minute average 10 minute average 1 minute average >100kV 0.5% 0.7% 1.0% 2.0% Figure 2 – De-rating Curve for Motors
  • 18. CHK Power QualityPtyLtd Page 18 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Current balance requirements are also set by the National Electricity Rules, distributor or state based Service Rules and in state based legislation. Check the requirements for the location being logged. Measurement of Voltage Unbalance Voltage unbalance shouldbe measuredwithline toline valuesof voltage.Gridsense’s 6-wire lead is the only way of measuring this when using PowerMonics. The logger should be set to 10-minute averages in case logs need to be compared with standards e.g. where there isa dispute. Voltage unbalance is more a steady-state issue and so 10-minute averages is oftensuffice.However, voltage or current unbalance protection may be tripping and shorter averages may be better suited to assist in determining the cause. Case Study The motor inFigure 1 wasoverheatingandvoltage unbalance was suspected as the cause. A PM45 was installedandthe graphinFigure 4 obtained.Itshowsexcessive voltage unbalance andthe likelycause of the overheating. Figure 4 - Graph showing excessive voltage unbalance to a motor Conclusions The major cause of currentunbalance isthe “short-armedlinesmen’s syndrome” that results in voltage unbalance.The majoreffectof voltage unbalance isadditional heatingandlossesinthree-phasemotors. Voltage and current unbalance can be easily tracked down using a PM45. 10kV to100kV 1.3% 1.3% 2.0% 2.5% <10kV 2.0% 2.0% 2.5% 3.0%
  • 19. CHK Power QualityPtyLtd Page 19 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Voltage Flicker Introduction Voltage fluctuations and flicker can be a real nuisance with the source of the problem often difficult to locate. The PM45 is arguably the best logger for locating the source of voltage fluctuations, particularly where motor starting is a problem. Figure 1 showsa PM45 beinginstalledtotrackdownthe source of voltage fluctuations caused by a motor. The PM 45 has shortand longterm flickermonitoringcapabilityas well as event recording for rolling average voltage variations or threshold settings. The eventrecordingcomesintoits own when trying to locate the motor that is causing voltage fluctuations or when determining the best time to swap a motor from the start to run sequence. The PM45 has memory allocated for events that is independent of steady state logging, or profiling as it is sometimes called, assuring that profiling is not disrupted should significant numbers of events occur. Causes of Voltage Fluctuations and Flicker Motor Starting Motor startingis a major source of complaintsregardingvoltage variations. A motor can draw up to ten timesitsrunningcurrenton start up. This huge increase in current causes the voltage to sag due to the source impedance. Reduced voltage starting seeks to limit the start-up current and hence limit the voltage fluctuation during the start-up process. Swappingamotor to run before ithasgottenup to full speedwill cause the currenttopeakmuchhigher than it would if started when up to speed. The PM45 can capture the start up sequence if set appropriately.Analysisof the eventrecordedfromthe startupsequence willshow whether the voltage fluctuation complies with the required standard and if the controller, that swaps the motor to run, is appropriately set. Generally a simple timer is used for the swap over process and it may be that this timer needs to be more appropriately set (tweaked) to prevent the excessive voltage fluctuation. Heavy Industry Heavy industry is most often the cause of flicker. Electric arc furnaces, induction furnaces, static frequency converters and cyclo-converters are some of the more common offending equipment. Figure 1 - A PM45 being installed to help locate a motor start issue. It is arguably the best test instrument for this task.
  • 20. CHK Power QualityPtyLtd Page 20 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Loose Connections Loose connectionscanalsocause voltage fluctuationsorflicker whether on the low or medium voltage network.Heavilyloadedconnectionstendtoburnoutquickerbutlightlyloadedconnections may cause fluctuations or flicker for long periods. Effects of Voltage Fluctuations and Flicker The most common effect of voltage fluctuations and flicker is to do with lighting and the human eye. The incandescentlight globe is sensitive to voltage fluctuations and flicker. Fluorescent lighting is not immune from such problems but is less prone to problems and tends to dampen voltage variations. Required Standard The flickercompatibilitylevel forLV andMV powersystemsisset by AS/NZS61000.3.7 at 1.0 for P-st and 0.8 for P-lt. AS/NZS61000.3.3, AS/NZS61000.3.5 and AS/NZS61000.3.7 set the limits for fluctuations. Case Study A customerina semi-rural situationwascomplainingtothe distribution company that their lights were flickeringall day.A technicianwassentouttoinvestigate.The loggerwassettorecord flickerandrolling voltage events set at 5%. The logger was down loaded a few days later and the Pst was continually above the 1.0 limit. The logger failed to record any events outside the 5% rolling level. The loggerwas reprogrammedwitha3% rollingvoltage setting.The resultsclearlyshowed that a motor was startingapproximatelyeveryminuteandthe motorwasnot at the complainingcustomer’spremise (Figure 2).There were twoneighbors,bothwithsingle phase supply, supplied from a common point of supplyonpowerpole.One logger was installed with A phase C/T clipped over the active to one house and B phase to the other house. The results from this logging clearly showed that one house had a motor causing the problems. Discussionswiththe customer revealed that the motor was on a pressure pump and the pressure tank had lostitspressure.The customeralsohad a very leaky tap that was causing the pressure pump to cut inand out, all day long. The customer replaced the valve in the pressure tank, and fixed the leaky tap.
  • 21. CHK Power QualityPtyLtd Page 21 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Figure 2 - Graph showing a motor start. The starter was continually cutting in and out and causing a nuisance Conclusions The PM45 can be a valuable tool in determining the source of voltage fluctuations and flicker and is arguably the best instrument on the market for locating motor starting problems and in assisting with the settingof starters. Thisloggeris easyto set,obtainthe loggeddata and then to analyse the results.
  • 22. CHK Power QualityPtyLtd Page 22 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Event Recording Introduction The PM45 notonlyprofiles/logssteady state issues such as voltage and harmonic levels but can also record one off power quality events.The memoryallocatedforeventsisindependentof profiling to ensure thatprofilingisnotdisrupted should significant numbers of events occur. Events are divided into the following classes:  Sag/Swell detection  RMS capture;  Transient capture (dV/dt). Sag/Swell Detection Sag/Swell detection is used where a list of sag and swell events is requiredinatable formator where these eventsare required to be plotted on a curve such as the ITIC curve. Table data includes the time, duration and the maximum or minimum voltage of the event. Powerview automatically graphs the events on the ITIC curve when selected.Plottingtoothercurves or manipulation of the data can be achieved by exporting the data to Excel. RMS Capture RMS capture isideal to capture temporary (3 s – 1 min), momentary (30 cycles – 3 s) and instantaneous (0.5 – 30 cycle) sag, swell and/or interruption events. It is an excellent tool to locate motor start problemsandwhensettingthe changeover timer for motor starters. Voltage or current can be used to setthe RMS capture.Interruptionscanbe clearlyseentodetermineif networkprotection equipment is operating as it should. RMS capture allow comparison with customer logs to determine the cause of equipment malfunctions or plant failures. Up to 30 seconds of 10 ms data points for 50 Hz supplies are captured. Waveformcapture can alsobe selectedwithRMScapture to allow directcorrelation with an RMS event captured at the same time. This can be handy to see what happened at the onset of the RMS event in more detail. 400ms of data points are captured at 98 micro-second intervals. Transient Waveform Capture Transient waveform capture allows the capture of low frequency oscillatory waveforms that would occur as a result of the energisation of a capacitor bank and notching caused by the commutation of electronic devices such as Silicon Controlled Rectifiers. Setting the Logger A detailedexplanationof settingthe loggertocapture eventdataandallocationof memory isprovided inGridsense’sConfigurationGuidesavailable at www.gridsense.net Figure 1 - A PM45 being installed at a plastic plant to determine the cause of plant shutdowns (see Case Study).
  • 23. CHK Power QualityPtyLtd Page 23 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831
  • 24. CHK Power QualityPtyLtd Page 24 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 Required Standard The following provides a summary of the standards that apply to events captured by the PM45:  Sags – no standard applies at this stage other than the input sags have on flicker and voltage fluctuations;  Swells – the National Electricity Rules Figure S5.1a.1;  RMS voltage capture – voltage fluctuations are managed by AS/NZS61000.3.3, AS/NZS61000.3.5 and AS/NZS61000.3.7;  RMS currentcapture – large swingsincurrentcause voltage fluctuations and so current capture isgenerallymanagedthroughthe managementof voltage fluctuations though distributors may have requirements in local service rules;  Transient waveform capture – compatibility limits have not been applied for transients and notchingat thisstage.ObsolescentstandardAS2270.2 providesguidance onthe managementof notching and oscillatory transients should be managed through good industry practice. Case Study A plasticsfactorywashavingproblemswiththe plant’sVariable Speed Drive (VSD) equipment shutting downrandomlyforno apparentreason.Unblockingof equipmentwas timing consuming and damaging client relationships due to delays in the supply of their products. Unseeneventswere suspectedasthe cause andso a PM45 was installedatthe mainswitchboardsetup to logTransientWaveformcapture,aswell aslogging for RMS capture, voltage and harmonics. Figure 2 shows a low frequency oscillatory transient that was captured by the logger. This event related to a major shutdown at the plant. Figure 2 – A Transient Waveform event captured by a PM45 at the plasitcs plant The networkpowercompanywascontactedto see if theywere switchingcapacitorsatthe time thatthe oscillatorytransientoccurred.The powercompanyadmittedthatacapacitor bankhad beenswitchedat the local zone substation at that time and that the bank did not have transient mitigation equipment. The problemsatthe plasticsplantwasexplained and the power company agreed to stop switching the capacitorswhenthe plantwas operatingandthat theywouldintroduce transientmitigation equipment to the capacitor bank as soon as possibe. Conclusions The PM45 can be very useful in detecting event based power quality problems. The instrument will record low frequency oscillatory transients and notching type events. Steady state profiling can be
  • 25. CHK Power QualityPtyLtd Page 25 Address:Unit102, 25 Angas Street Telephone: +61 2 8283 6945 Meadowbank NSW 2114,Sydney Australia Fax: +61 2 8212 8105 Website:www.chkpowerquality.com.au ABN: 53 169 840 831 carried out at the same time as event recording. This profiling will not affect the event logging as the memory is partitioned and separate memory allocated for profiling and events.