SlideShare a Scribd company logo
500. 2 Definitions
Combustible Dust. Dust particles that are 500 microns
or smaller (material passing a U.S. No. 35 Standard Sieve
as defined in ASTM E 11-09, Standard Specification for Wire
Cloth and Sieves for Testing Purposes) and present a fire or
explosion hazard when dispersed and ignited in air.
Informational Note: See ASTM E 1226–12a, Standard Test
Method for Explosibility of Dust Clouds, or ISO 6184-1,
Explosion protection systems — Part 1: Determination of explosion
indices of combustible dusts in air, for procedures for
determining the explosibility of dusts.
Class 1 Locations
501.10 Wiring Methods
(A) Class I, Division 1.
 (1) General. In Class I, Division 1 locations, the
wiring methods in (a) through ( e) shall be
permitted.
(e) Optical fiber cable Types OFNP, OFCP, OFNR,
OFCR, OFNG, OFCG, OFN, and OFC shall be
permitted to be installed in raceways in accordance
with 501.10(A). These optical fiber cables shall be
sealed in accordance with 501.15.
Class 1 Locations
501.10 Wiring Methods
(A) Class I, Division 1.
 (2) Flexible Connections. Where necessary to
employ flexible connections, as at motor
terminals, the following shall be permitted:
 (1) Flexible fittings listed for the location, or
 (2) Flexible cord in accordance with the
provisions of 501.140, terminated with cord
connectors listed for the location, or
Class 1 Locations
501.10 Wiring Methods
(A) Class I, Division 1.
 (2) Flexible Connections – (cont.)
 (3) In industrial establishments with restricted public
access, where the conditions of maintenance and
supervision ensure that only qualified persons service
the installation, for applications limited to 600 volts,
nominal, or less, and where protected from damage by
location or a suitable guard, listed Type TC-ER-HL
cable with an overall jacket and a separate equipment
grounding conductor(s) in accordance with 250.122
that is terminated with fittings listed for the location
Class 1 Locations
501.15 Sealing and Drainage
 (C) Class I, Divisions 1 and 2.
 (6) Conductor or Optical Fiber Fill. The
cross-sectional area of the conductors or optical
fiber tubes (metallic or nonmetallic) permitted in
a seal shall not exceed 25 percent of the cross-
sectional area of a rigid metal conduit of the
same trade size unless the seal is specifically
identified for a higher percentage of fill.
Class 1 Locations
 501.30 Grounding and Bonding, Class I,
Divisions 1 and 2
Regardless of the voltage of the electrical system,
wiring and equipment in Class I, Division 1 and 2
locations shall be grounded as specified in Article
250 and in accordance with the requirements of
501.30(A) and (B).
Class II Locations
 502.10 Wiring Methods
 (A) Class II, Division 1.
 (1) General. In Class II, Division 1 locations, the
wiring methods in (1) through (4) shall be permitted
 (4) Optical fiber cables Types OFNP, OFCP, OFNR,
OFCR, OFNG, OFCG, OFN, and OFC shall be
permitted to be installed in raceways in accordance with
502.10(A). Optical fiber cables shall be sealed in
accordance with 502.15.d:
Class II Locations
 502.30 Grounding and Bonding, Class II,
Divisions 1 and 2
Regardless of the voltage of the electrical system,
wiring and equipment in Class II, Division 1 and 2
locations shall be grounded as specified in Article
250 and in accordance with the requirements of
502.30(A) and (B).
Intrinsically Safe Systems
 504.10 Equipment Installation
 (C) Enclosures. General-purpose enclosures
shall be permitted for intrinsically safe apparatus
and associated apparatus unless otherwise
specified in the manufacturer’s documentation.
Motor Fuel Dispensing Facilities
514.3 Classification of Locations
 (C) Motor Fuel Dispensing Stations in Boatyards
and Marinas.
 (1) General. Electrical wiring and equipment located at
or serving motor fuel dispensing locations shall be
installed on the side of the wharf, pier, or dock
opposite from the liquid piping system.
Informational Note: For additional information, see
NFPA 303-2011, Fire Protection Standard for Marinas and
Boatyards, and NFPA 30A-2012, Motor Fuel Dispensing
Facilities and Repair Garages.
Motor Fuel Dispensing Facilities
514.3 Classification of Locations
 (C) Motor Fuel Dispensing Stations in Boatyards
and Marinas – (cont.)
 (2) Classification of Class I, Division 1 and 2 Areas.
The following criteria shall be used for the purposes of
applying Table 514.3(B)(1) and Table 514.3(B)(2) to
motor fuel dispensing equipment on floating or fixed
piers, wharfs, or docks.
Motor Fuel Dispensing Facilities
514.3 Classification of Locations
 (D) Closed Construction. Where the construction of
floating docks, piers, or wharfs is closed so that there is
no space between the bottom of the dock, pier, or
wharf and the water, as in the case of concrete-enclosed
expanded foam or similar construction, and the
construction includes integral service boxes with supply
chases, the following shall apply:
Motor Fuel Dispensing Facilities
514.3 Classification of Locations
 (1) The space above the surface of the floating dock,
pier, or wharf shall be a Class I, Division 2 location
with distances as specified in Table 514.3(B)(1)(1) for
dispenser and outdoor locations.
 (2) Spaces below the surface of the floating dock, pier,
or wharf that have areas or enclosures, such as tubs,
voids, pits, vaults, boxes, depressions, fuel piping
chases, or similar spaces, where flammable liquid or
vapor can accumulate shall be a Class I, Division 1
location.
Motor Fuel Dispensing Facilities
514.3 Classification of Locations
 Exception No. 1: Dock, pier, or wharf sections that do not support fuel
dispensers and abut, but are located 6.0 m (20 ft) or more from, dock
sections that support a fuel dispenser(s) shall be permitted to be Class I,
Division 2 locations where documented air space is provided between dock
sections to allow flammable liquids or vapors to dissipate without traveling to
such dock sections. The documentation shall comply with 500.4(A).
 Exception No. 2: Dock, pier, or wharf sections that do not support fuel
dispensers and do not directly abut sections that support fuel dispensers shall
be permitted to be unclassified where documented air space is provided and
where flammable liquids or vapors cannot travel to such dock sections. The
documentation shall comply with 500.4(A).
Motor Fuel Dispensing Facilities
514.3 Classification of Locations
 (E) Open Construction. Where the construction of piers,
wharfs, or docks is open, as in the case of decks built on
stringers supported by pilings, floats, pontoons, or similar
construct ion, the following shall apply:
 (1) The area 450 mm (18 in.) above the surface of the dock, pier,
or wharf and extending 6.0 m (20 ft) horizontally in all directions
from the outside edge of the dispenser and down to the water
level shall be a Class 1, Division 2 location.
 (2) Enclosures such as tubs, voids, pits, vaults, boxes,
depressions, piping chases, or similar spaces where flammable
liquids or vapors can accumulate within 6.0 m (20 ft) of the
dispenser shall be a Class I, Division 1 location.
ARTICLE 516 Spray Application, Dipping,
Coating, and Printing Processes Using
Flammable or Combustible Materials
 516.2 Definitions
 Flash-Off Area. An open or enclosed area after a spray
application process where vapors are released due to exposure to
ambient air or a heated atmosphere. [33:3.3.1.1]
 Limited Finishing Workstation. An apparatus that is capable of
confining the vapors, mists, residues, dusts, or deposits that are
generated by a spray application process and that meets the
requirements of Section 14.3 of NFPA 33, Standard for Spray
Application Using Flammable or Combustible Materials, but
does not meet the requirements of a spray booth or spray room,
as herein defined. [33:3.3.15.1]
ARTICLE 516 Spray Application, Dipping,
Coating, and Printing Processes Using
Flammable or Combustible Materials
 516.2 Definitions – (cont.)
 Resin Application Area. Any area in which polyester resins or
gelcoats are spray applied. [33:3.3.1.2]
 Spray Area. Any fully enclosed, partly enclosed, or unenclosed
area in which ignitible quantities of flammable or combustible
vapors, mists, residues, dusts, or deposits are present due to the
operation of spray processes, including (1) any area in the direct
path of a spray application process; (2) the interior of a spray
booth or spray room or limited finishing workstation, as herein
defined; (3) the interior of any exhaust plenum, eliminator
section, or scrubber section; (4) the interior of any exhaust duct
or exhaust stack leading from a spray application process;
ARTICLE 516 Spray Application, Dipping,
Coating, and Printing Processes Using
Flammable or Combustible Materials
 516.2 Definitions – (cont.)
 (5) the interior of any air recirculation filter house or
enclosure, including secondary recirculation particulate
filters; (6) any solvent concentrator (pollution
abatement) unit or solvent recovery (distillation) unit.
The following are not considered to be a part of the
spray area: (1) fresh air make-up units; (2) air supply
ducts and air supply plenums; (3) recirculation air
supply ducts downstream of secondary filters; (4)
exhaust ducts from solvent concentrateur (pollution
abattement) units. [33:3.3.2.3]
ARTICLE 516 Spray Application, Dipping,
Coating, and Printing Processes Using
Flammable or Combustible Materials
 516.2 Definitions – (cont.)
 Spray Area – (cont.)
(5) the interior of any air recirculation filter house or enclosure,
including secondary recirculation particulate filters; (6) any solvent
concentrator (pollution abatement) unit or solvent recovery
(distillation) unit. The following are not considered to be a part of
the spray area: (1) fresh air make-up units; (2) air supply ducts and
air supply plenums; (3) recirculation air supply ducts downstream of
secondary filters; (4) exhaust ducts from solvent concentrator
(pollution abatement) units. [33:3.3.2.3]
ARTICLE 516 Spray Application, Dipping,
Coating, and Printing Processes Using
Flammable or Combustible Materials
 516.2 Definitions
 Spray Booth. A power-ventilated enclosure for a spray
application operation or process that confines and
limits the escape of the material being sprayed,
including vapors, mists, dusts, and residues that are
produced by the spraying operation and conducts or
directs these materials to an exhaust system. [33:3.3.14]
ARTICLE 516 Spray Application, Dipping,
Coating, and Printing Processes Using
Flammable or Combustible Materials
 516.2 Definitions
 Spray Room. A power-ventilated fully enclosed room
used exclusively for open spraying of flammable or
combustible materials. A spray room is a purposefully
enclosed room built for spray/coating/dipping
applications provided with dedicated ventilation supply
and exhaust. Normally the room is configured to house
the item to be painted, providing reasonable access
around the item/process. Depending on the size of the
item being painted, such rooms may actually be the
entire building or the major portion thereof. [33:3.3.15]
ARTICLE 516 Spray Application, Dipping,
Coating, and Printing Processes Using
Flammable or Combustible Materials
 516.2 Definitions
 Unenclosed Spray Area. Any spray area that is
not confined by a limited finishing workstation,
spray booth, or spray room, as herein defined.
[33:3.3.2.3.2]
516. 3 Classification of Locations
 (A) Zone Classification of Locations.
(1) For the purposes of this article, the zone system of electrical
area classification shall be applied as follows:
a. The inside of open or closed containers or vessels shall be
considered a Class I, Zone 0 location.
b. A Class I, Division 1 location shall be permitted to be
alternatively classified as a Class I, Zone 1 location.
c. A Class I, Division 2 location shall be permitted to be
alternatively classified as a Class I, Zone 2 location.
d. A Class II, Division 1 location shall be permitted to be
alternatively classified as a Zone 21 location.
e. A Class II, Division 2 location shall be permitted to be
alternatively classified as a Zone 22 location. [33:6.2.2]
516. 3 Classification of Locations
(cont.)
(2) For the purposes of electrical area classification, the
division system and the zone system shall not be
intermixed for any given source of release. [33:6.2.3]
(3) In instances of areas within the same facility classified
separately, Class I, Zone 2 locations shall be permitted to
abut, but not overlap, Class I, Division 2 locations. Class
I, Zone 0 or Zone 1 locations shall not abut Class I,
Division 1 or Division 2 locations. [33:6.2.4]
516. 3 Classification of Locations
(cont.)
(4) Open flames, spark-producing equipment or
processes, and equipment whose exposed surfaces exceed
the autoignition temperature of the material being sprayed
shall not be located in a spray area or in any surrounding
area that is classified as Division 2, Zone 2, or Zone 22.
Exception: This requirement shall not apply to drying, curing, or
fusing apparatus. [33:6.2.5]
516. 3 Classification of Locations
(cont.)
(5) Any utilization equipment or apparatus that is capable
of producing sparks or particles of hot metal and that is
located above or adjacent to either the spray area or the
surrounding Division 2, Zone 2, or Zone 22 areas shall be
of the totally enclosed type or shall be constructed to
prevent the escape of sparks or particles of hot metal.
[33:6.2.6]
Health Care Facilities
517.2 Definitions
 Life Safety Branch. A system of feeders and branch
circuits supplying power for lighting, receptacles, and
equipment essential for life safety that is automatically
connected to alternate power sources by one or more
transfer switches during interruption of the normal
power source. [99:3.3.94]
Health Care Facilities
517.2 Definitions – (cont.)
 Patient Care Space. Space within a health care facility wherein
patients are intended to be examined or treated.
 Basic Care Space. Space in which failure of equipment or a system
is not likely t o cause injury to the patients or caregivers but may
cause patient discomfort.
 General Care Space. Space in which failure of equipment or a
system is likely to cause minor injury to patients or caregivers.
 Critical Care Space. Space in which failure of equipment or a
system is likely to cause major injury or death to patients or
caregivers.
Health Care Facilities
517.2 Definitions – (cont.)
 Support Space. Space in which failure of equipment or a system is
not likely to have a physical impact on patients or caregivers.
Informational Note No. 1: The governing body of the facility
designates patient care space in accordance with the type of patient
care anticipated and with the definitions of the area classification.
Business offices, corridors, lounges, day rooms, dining rooms, or
similar areas typically are not classified as patient care space.
Informational Note No. 2: Basic care space is typically a location
where basic medical or dental care, treatment, or examinations are
performed. Examples include, but are not limited to, examination
or treatment rooms in clinics, medical and dental offices, nursing
homes, and limited care facilities.
Health Care Facilities
517.2 Definitions – (cont.)
 Informational Note No. 3: General care space includes areas such as patient
bedrooms, examining rooms, treatment rooms, clinics, and similar areas
where the patient may come into contact with electromedical devices or
ordinary appliances such as a nurse call system, electric beds, examining
lamps, telephones, and entertainment devices.
 Informational Note No. 4: Critical care space includes special care units,
intensive care units, coronary care units, angiography laboratories, cardiac
catheterization laboratories, delivery rooms, operating rooms, and similar
areas in which are patients are intended to be subjected to invasive procedures
and are connected to line-operated, electromedical devices.
 Informational Note No. 5: Spaces where a procedure is performed that
subjects patients or staff to wet conditions are considered as wet procedure
areas. Wet conditions include standing fluids on the floor or drenching of the
work area. Routine housekeeping procedures and incidental spillage of liquids
do not define wet procedure areas. It is the responsibility of the governing
body of the health care facility to designate the wet procedure areas.
Health Care Facilities
517.2 Definitions – (cont.)
 Patient Care Vicinity. A space, within a
location intended for the examination and
treatment of patients, extending 1.8 m (6 ft)
beyond the normal location of the patient bed,
chair, table, treadmill, or other device that
supports the patient during examination and
treatment and extending vertically to 2.3 m (7 ft
6 in.) above the floor. [99:3.3.139]
Health Care Facilities
517.2 Definitions – (cont.)
 Wet Procedure Location. The area in a patient care
space where a procedure is performed that is normally
subject to wet conditions while patients are present,
including standing fluids on the floor or drenching of
the work area, where either such condition is intimate
to the patient or staff.
 Informational Note: Routine housekeeping procedures
and incidental spillage of liquids do not define a wet
procedure location.
Further Information
 Wet procedure locations may also include such areas as
hydrotherapy areas, dialysis laboratories, and certain
wet laboratories at the discretion of the governing body
of the facility. The definition excludes areas such as
lavatories or bathrooms within a health care facility. For
infection control purposes, many patient and treatment
areas have a sink for hand washing, which also is not a
wet procedure location.
Health Care Facilities
517.19(C) Operating Room Receptacles
 (1) Minimum Number and Supply. Each operating
room shall be provided with a minimum of 36
receptacles, at least 12 of which shall be connected to
eit her of the following:
 (1) The normal system branch circuit required in
517.19(A)
 (2) A critical branch circuit supplied by a different
transfer switch than the other receptacles at the same
location
Health Care Facilities
517.19(C) Operating Room Receptacles
 (2) Receptacle Requirements. The receptacles
required in (517.19)(C)(1) shall be permitted to be of
the single or duplex types or a combination of both. All
receptacles shall be listed hospital grade and so
identified. The grounding terminal of each receptacle
shall be connected to the reference grounding point by
means of an insulated copper equipment grounding
conductor.
ARTICLE 520
Theaters, Audience Areas of Motion Picture
and Television Studios, Performance Areas,
and Similar Locations
520.2 Definitions
 Stage Equipment. Equipment at any location on the
premises integral to the stage production including, but
not limited to, equipment for lighting, audio, special
effects, rigging, motion control, projection, or video.
520.2 Definitions – (cont.)
 Stage Lighting Hoist. A motorized lifting
device that contains a mounting position for one or more
luminaires, with wiring devices for connection of
luminaires to branch
circuits, and integral flexible cables
to allow the luminaires
to travel over the
lifting range of the
hoist while energized.
520.2 Definitions – (cont.)
 Stage Switchboard. A switchboard, panelboard, or
rack containing dimmers or relays with associated
overcurrent protective devices, or overcurrent
protective devices alone, used primarily to feed stage
equipment.
II. Fixed Stage Switchboards
520.21 General
 Fixed stage switchboards shall comply with 520.21(1) through
(4):
 (1) Fixed stage switchboards shall be listed.
 (2) Fixed stage switchboards shall be readily accessible but shall
not be required to be located on or adjacent to the stage.
Multiple fixed stage switchboards shall be permitted at different
locations.
 (3) A fixed stage switchboard shall contain overcurrent
protective devices for all branch circuits supplied by that
switchboard.
 (4) A fixed stage switchboard shall be permitted to supply both
stage and non-stage equipment.
III. Fixed Stage Equipment
Other Than Switchboards
 520.40 Stage Lighting Hoists
Where a stage lighting hoist is listed as a complete
assembly and contains an integral cable-handling
system and cable to connect a moving wiring
device to a fixed junction box for connection to
permanent wiring, the extra-hard usage
requirement of 520.44(C)(1) shall not apply.
ARTICLE 640
Audio Signal Processing,
Amplification, and Reproduction
Equipment
640.1 Scope
 (B) Not Covered. This article does not cover the
installation and wiring of fire and burglary alarm
signaling devices.
680.22 Lighting, Receptacles, and Equipment
(B) Luminaires, Lighting Outlets, and
Ceiling-Suspended (Paddle) Fans.
 (6) Low-Voltage Luminaires.
Listed low-voltage luminaires
not requiring grounding, not
exceeding the low-voltage
contact limit, and supplied by
listed transformers or power
supplies that comply with
680.23(A)(2) shall be permitted
to be located less than 1.5 m (5
ft) from the inside walls of the
pool.
680.26 Equipotential Bonding
 (C) Pool Water.
Where none of the bonded parts is in direct connection
with the pool water, the pool water shall be in direct
contact with an approved corrosion-resistant conductive
surface that exposes not less than 5800 mm2 (9 in.2) of
surface area to the pool water at all times. The conductive
surface shall be located where it is not exposed to physical
damage or dislodgement during usual pool activities, and
it shall be bonded in accordance with 680.26(B).
Solar Photovoltaic (PV ) Systems
690.2 Definitions
 DC-to-DC Converter. A device installed in the PV
source circuit or PV output circuit that can provide an
output dc voltage and current at a higher or lower value
than the input dc voltage and current.
Solar Photovoltaic (PV ) Systems
690.2 Definitions
 Direct-Current (dc)
Combiner. A device
used in the PV source
and PV output circuits
to combine two or
more dc circuit inputs
and provide one dc
circuit output.
Solar Photovoltaic (PV ) Systems
690.2 Definitions
 Multimode Inverter.
Equipment having the
capabilities of both the
utility-interactive inverter
and the stand-alone
inverter.
IV. Wiring Methods
690.31 Methods Permitted
 (B) Identification and Grouping. PV source circuits
and PV output circuits shall not be contained in the
same raceway, cable tray, cable, outlet box, junction
box, or similar fitting as conductors, feeders, branch
circuits of other non-PV systems, or inverter output
circuits, unless the conductors of the different systems
are separated by a partition. PV system conductors shall
be identified and grouped as required by 690.31(B)(1)
through (4). The means of identification shall be
permitted by separate color coding, marking tape,
tagging, or other approved means.
IV. Wiring Methods
690.31 Methods Permitted
 (B) Identification and Grouping (cont.)
 (1) PV Source Circuits. PV source circuits shall be
identified at all points of termination, connection, and
splices.
 (2) PV Output and Inverter Circuits. The
conductors of PV output circuits and inverter input and
output circuits shall be identified at all points of
termination, connection, and splices.
IV. Wiring Methods
690.31 Methods Permitted
 (B) Identification and Grouping (cont.)
 (3) Conductors of Multiple Systems. Where the
conductors of more than one PV system occupy the
same junction box, raceway, or equipment, the
conductors of each system shall be identified at all
termination, connection, and splice points.
Exception: Where the identification of the conductors is evident by
spacing or arrangement, further identification shall not be required.
IV. Wiring Methods
690.31 Methods Permitted
 (B) Identification and Grouping (cont.)
 (4) Grouping. Where the conductors of more than one
PV system occupy the same junction box or raceway
with a removable cover(s), the ac and dc conductors of
each system shall be grouped separately by cable ties or
similar means at least once and shall then be grouped at
intervals not to exceed 1.8 m (6 ft).
Exception: The requirement for grouping shall not apply if the
circuit enters from a cable or raceway unique to the circuit that
makes the grouping obvious.

More Related Content

Viewers also liked

Powertools2015
Powertools2015Powertools2015
Powertools2015
Jeff Frey
 
Attack_Project_Presentation_ISSC461_Intindolo
Attack_Project_Presentation_ISSC461_IntindoloAttack_Project_Presentation_ISSC461_Intindolo
Attack_Project_Presentation_ISSC461_Intindolo
John Intindolo
 
The Pitch Final For Public
The Pitch Final For PublicThe Pitch Final For Public
The Pitch Final For Public
Alexander Fattell
 
Thabo_Mashapa_Resume[1]_(1)[1]
Thabo_Mashapa_Resume[1]_(1)[1]Thabo_Mashapa_Resume[1]_(1)[1]
Thabo_Mashapa_Resume[1]_(1)[1]
Thabo Mashapa
 
Wk 7 Case Study Summary Paper_ISSC331_Intindolo
Wk 7 Case Study Summary Paper_ISSC331_IntindoloWk 7 Case Study Summary Paper_ISSC331_Intindolo
Wk 7 Case Study Summary Paper_ISSC331_Intindolo
John Intindolo
 
TM Business Opportunity Overview
TM Business Opportunity OverviewTM Business Opportunity Overview
TM Business Opportunity Overview
Gerald Ballantyne
 
01a-MASTER TRASCRIPT
01a-MASTER TRASCRIPT01a-MASTER TRASCRIPT
01a-MASTER TRASCRIPTHatem Mehilab
 
trust-and-confidence
trust-and-confidencetrust-and-confidence
trust-and-confidence
Tovah Paglaro
 
Wireless Audio 360 Samsung
Wireless Audio 360 SamsungWireless Audio 360 Samsung
Wireless Audio 360 Samsung
FFM_Training
 
Synergy Booklet
Synergy BookletSynergy Booklet
Synergy Booklet
PAUL NAHAL
 
Methodology fair
Methodology fairMethodology fair
Methodology fair
bindujakrishnan
 
Developing_mastery_in_mathematics_october_2014.pd
Developing_mastery_in_mathematics_october_2014.pdDeveloping_mastery_in_mathematics_october_2014.pd
Developing_mastery_in_mathematics_october_2014.pd
Dare Akindele
 
Если хочешь быть здоров
Если хочешь быть здоровЕсли хочешь быть здоров
Если хочешь быть здоров
helen_2015
 
IoT_Ethics
IoT_EthicsIoT_Ethics
IoT_Ethics
Brandon Walston
 
Armas de los piratas
Armas de los piratasArmas de los piratas
Armas de los piratas
blogmonre
 
Построение Saas-стартапа на django и angular
Построение Saas-стартапа на django и angularПостроение Saas-стартапа на django и angular
Построение Saas-стартапа на django и angular
Alexander Lifanov
 
OBrienR_Resume_2016
OBrienR_Resume_2016OBrienR_Resume_2016
OBrienR_Resume_2016
Robin O'Brien
 

Viewers also liked (19)

Powertools2015
Powertools2015Powertools2015
Powertools2015
 
Attack_Project_Presentation_ISSC461_Intindolo
Attack_Project_Presentation_ISSC461_IntindoloAttack_Project_Presentation_ISSC461_Intindolo
Attack_Project_Presentation_ISSC461_Intindolo
 
The Pitch Final For Public
The Pitch Final For PublicThe Pitch Final For Public
The Pitch Final For Public
 
Thabo_Mashapa_Resume[1]_(1)[1]
Thabo_Mashapa_Resume[1]_(1)[1]Thabo_Mashapa_Resume[1]_(1)[1]
Thabo_Mashapa_Resume[1]_(1)[1]
 
Wk 7 Case Study Summary Paper_ISSC331_Intindolo
Wk 7 Case Study Summary Paper_ISSC331_IntindoloWk 7 Case Study Summary Paper_ISSC331_Intindolo
Wk 7 Case Study Summary Paper_ISSC331_Intindolo
 
TM Business Opportunity Overview
TM Business Opportunity OverviewTM Business Opportunity Overview
TM Business Opportunity Overview
 
01a-MASTER TRASCRIPT
01a-MASTER TRASCRIPT01a-MASTER TRASCRIPT
01a-MASTER TRASCRIPT
 
trust-and-confidence
trust-and-confidencetrust-and-confidence
trust-and-confidence
 
Wireless Audio 360 Samsung
Wireless Audio 360 SamsungWireless Audio 360 Samsung
Wireless Audio 360 Samsung
 
Synergy Booklet
Synergy BookletSynergy Booklet
Synergy Booklet
 
Methodology fair
Methodology fairMethodology fair
Methodology fair
 
Developing_mastery_in_mathematics_october_2014.pd
Developing_mastery_in_mathematics_october_2014.pdDeveloping_mastery_in_mathematics_october_2014.pd
Developing_mastery_in_mathematics_october_2014.pd
 
Если хочешь быть здоров
Если хочешь быть здоровЕсли хочешь быть здоров
Если хочешь быть здоров
 
IoT_Ethics
IoT_EthicsIoT_Ethics
IoT_Ethics
 
Usama_Amer
Usama_AmerUsama_Amer
Usama_Amer
 
Armas de los piratas
Armas de los piratasArmas de los piratas
Armas de los piratas
 
Построение Saas-стартапа на django и angular
Построение Saas-стартапа на django и angularПостроение Saas-стартапа на django и angular
Построение Saas-стартапа на django и angular
 
OBrienR_Resume_2016
OBrienR_Resume_2016OBrienR_Resume_2016
OBrienR_Resume_2016
 
第十三课 – 旅游
第十三课 – 旅游第十三课 – 旅游
第十三课 – 旅游
 

Similar to Nec and oesc-5

2009 Sfpe Technical Changes To The Part 4 Fire Code
2009 Sfpe Technical Changes To The Part 4 Fire Code2009 Sfpe Technical Changes To The Part 4 Fire Code
2009 Sfpe Technical Changes To The Part 4 Fire Code
andrewwcwong
 
Chapter 4 ventilation
Chapter 4 ventilationChapter 4 ventilation
Chapter 4 ventilation
Leody Diaz Jr
 
Area classification
Area classification Area classification
Area classification
Vincent Wedelich, PE MBA
 
Nec and oesc-6
Nec and oesc-6Nec and oesc-6
Nec and oesc-6
grantlerc
 
Session 13
Session 13Session 13
Session 13
VancityInstitute
 
Nec and oesc-3
Nec and oesc-3Nec and oesc-3
Nec and oesc-3
grantlerc
 
Ansi Gptc Z380.1 2009 192 467
Ansi Gptc Z380.1   2009 192 467Ansi Gptc Z380.1   2009 192 467
Ansi Gptc Z380.1 2009 192 467
trorro
 
Ansi Gptc Z380.1 2009 192 467
Ansi Gptc Z380.1   2009 192 467Ansi Gptc Z380.1   2009 192 467
Ansi Gptc Z380.1 2009 192 467
trorro
 
FIRE_Safety.pptx
FIRE_Safety.pptxFIRE_Safety.pptx
FIRE_Safety.pptx
Sivakumar599008
 
specif-dust-extraction-system.pdf
specif-dust-extraction-system.pdfspecif-dust-extraction-system.pdf
specif-dust-extraction-system.pdf
SergioPereira229337
 
Asco Solenoid Valves Explosionproof Solenoid Valves - Technical Information
Asco Solenoid Valves Explosionproof Solenoid Valves - Technical InformationAsco Solenoid Valves Explosionproof Solenoid Valves - Technical Information
Asco Solenoid Valves Explosionproof Solenoid Valves - Technical Information
Thorne & Derrick UK
 
Chapter 13 fuel oil piping and storage
Chapter 13 fuel oil piping and storageChapter 13 fuel oil piping and storage
Chapter 13 fuel oil piping and storage
AYM1979
 
2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised
Basudev patra
 
orca_share_media1681902232358_7054409260788301852.pptx
orca_share_media1681902232358_7054409260788301852.pptxorca_share_media1681902232358_7054409260788301852.pptx
orca_share_media1681902232358_7054409260788301852.pptx
NelizaSalcedo
 
Hazardous area classification and control of ignition sources
Hazardous area classification and control of ignition sourcesHazardous area classification and control of ignition sources
Hazardous area classification and control of ignition sources
eldhoev
 
tac spray rules
tac spray rulestac spray rules
tac spray rules
vakil jagdish
 
Explosion Proof Solenoid Valves & Hazardous Areas
Explosion Proof Solenoid Valves & Hazardous AreasExplosion Proof Solenoid Valves & Hazardous Areas
Explosion Proof Solenoid Valves & Hazardous Areas
Thorne & Derrick UK
 
5288PS2i1
5288PS2i15288PS2i1
5288PS2i1
Mark Wilmot
 
General Specification for Thermofoil Heater, All-Polyimide, Space Applications
General Specification for Thermofoil Heater, All-Polyimide, Space ApplicationsGeneral Specification for Thermofoil Heater, All-Polyimide, Space Applications
General Specification for Thermofoil Heater, All-Polyimide, Space Applications
Belilove Company-Engineers
 
Astm a380 ss pickling_passivation
Astm a380 ss pickling_passivationAstm a380 ss pickling_passivation
Astm a380 ss pickling_passivation
JosephFaustinMbe
 

Similar to Nec and oesc-5 (20)

2009 Sfpe Technical Changes To The Part 4 Fire Code
2009 Sfpe Technical Changes To The Part 4 Fire Code2009 Sfpe Technical Changes To The Part 4 Fire Code
2009 Sfpe Technical Changes To The Part 4 Fire Code
 
Chapter 4 ventilation
Chapter 4 ventilationChapter 4 ventilation
Chapter 4 ventilation
 
Area classification
Area classification Area classification
Area classification
 
Nec and oesc-6
Nec and oesc-6Nec and oesc-6
Nec and oesc-6
 
Session 13
Session 13Session 13
Session 13
 
Nec and oesc-3
Nec and oesc-3Nec and oesc-3
Nec and oesc-3
 
Ansi Gptc Z380.1 2009 192 467
Ansi Gptc Z380.1   2009 192 467Ansi Gptc Z380.1   2009 192 467
Ansi Gptc Z380.1 2009 192 467
 
Ansi Gptc Z380.1 2009 192 467
Ansi Gptc Z380.1   2009 192 467Ansi Gptc Z380.1   2009 192 467
Ansi Gptc Z380.1 2009 192 467
 
FIRE_Safety.pptx
FIRE_Safety.pptxFIRE_Safety.pptx
FIRE_Safety.pptx
 
specif-dust-extraction-system.pdf
specif-dust-extraction-system.pdfspecif-dust-extraction-system.pdf
specif-dust-extraction-system.pdf
 
Asco Solenoid Valves Explosionproof Solenoid Valves - Technical Information
Asco Solenoid Valves Explosionproof Solenoid Valves - Technical InformationAsco Solenoid Valves Explosionproof Solenoid Valves - Technical Information
Asco Solenoid Valves Explosionproof Solenoid Valves - Technical Information
 
Chapter 13 fuel oil piping and storage
Chapter 13 fuel oil piping and storageChapter 13 fuel oil piping and storage
Chapter 13 fuel oil piping and storage
 
2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised
 
orca_share_media1681902232358_7054409260788301852.pptx
orca_share_media1681902232358_7054409260788301852.pptxorca_share_media1681902232358_7054409260788301852.pptx
orca_share_media1681902232358_7054409260788301852.pptx
 
Hazardous area classification and control of ignition sources
Hazardous area classification and control of ignition sourcesHazardous area classification and control of ignition sources
Hazardous area classification and control of ignition sources
 
tac spray rules
tac spray rulestac spray rules
tac spray rules
 
Explosion Proof Solenoid Valves & Hazardous Areas
Explosion Proof Solenoid Valves & Hazardous AreasExplosion Proof Solenoid Valves & Hazardous Areas
Explosion Proof Solenoid Valves & Hazardous Areas
 
5288PS2i1
5288PS2i15288PS2i1
5288PS2i1
 
General Specification for Thermofoil Heater, All-Polyimide, Space Applications
General Specification for Thermofoil Heater, All-Polyimide, Space ApplicationsGeneral Specification for Thermofoil Heater, All-Polyimide, Space Applications
General Specification for Thermofoil Heater, All-Polyimide, Space Applications
 
Astm a380 ss pickling_passivation
Astm a380 ss pickling_passivationAstm a380 ss pickling_passivation
Astm a380 ss pickling_passivation
 

More from grantlerc

Fire alarm 3-f-single_and_multiple-station_alarms_and_household_fire_alarm_sy...
Fire alarm 3-f-single_and_multiple-station_alarms_and_household_fire_alarm_sy...Fire alarm 3-f-single_and_multiple-station_alarms_and_household_fire_alarm_sy...
Fire alarm 3-f-single_and_multiple-station_alarms_and_household_fire_alarm_sy...
grantlerc
 
Fire alarm 3-e-public_emergency_alarm_reporting_systems
Fire alarm 3-e-public_emergency_alarm_reporting_systemsFire alarm 3-e-public_emergency_alarm_reporting_systems
Fire alarm 3-e-public_emergency_alarm_reporting_systems
grantlerc
 
Fire alarm 3-d-supervising_station_alarm_system
Fire alarm 3-d-supervising_station_alarm_systemFire alarm 3-d-supervising_station_alarm_system
Fire alarm 3-d-supervising_station_alarm_system
grantlerc
 
Fire alarm 3-b-protected_premises_fire_alarm_system
Fire alarm 3-b-protected_premises_fire_alarm_systemFire alarm 3-b-protected_premises_fire_alarm_system
Fire alarm 3-b-protected_premises_fire_alarm_system
grantlerc
 
Fire alarm 3-a-emergency_control_functions
Fire alarm 3-a-emergency_control_functionsFire alarm 3-a-emergency_control_functions
Fire alarm 3-a-emergency_control_functions
grantlerc
 
Fire alarm basics 1-6
Fire alarm basics 1-6Fire alarm basics 1-6
Fire alarm basics 1-6
grantlerc
 
Fire alarm basics 1-5
Fire alarm basics 1-5Fire alarm basics 1-5
Fire alarm basics 1-5
grantlerc
 
Fire alarm 2_f_manual supervisory
Fire alarm 2_f_manual supervisoryFire alarm 2_f_manual supervisory
Fire alarm 2_f_manual supervisory
grantlerc
 
Fire alarm 2_e_combination
Fire alarm 2_e_combinationFire alarm 2_e_combination
Fire alarm 2_e_combination
grantlerc
 
Fire alarm 2_d_radiant energy detectors
Fire alarm 2_d_radiant energy detectorsFire alarm 2_d_radiant energy detectors
Fire alarm 2_d_radiant energy detectors
grantlerc
 
Fire alarm 2_c_smoke detectors
Fire alarm 2_c_smoke detectorsFire alarm 2_c_smoke detectors
Fire alarm 2_c_smoke detectors
grantlerc
 
Fire alarm 2_b_heat detectors
Fire alarm 2_b_heat detectorsFire alarm 2_b_heat detectors
Fire alarm 2_b_heat detectors
grantlerc
 
Fire alarm 2_a_initiation basics
Fire alarm 2_a_initiation basicsFire alarm 2_a_initiation basics
Fire alarm 2_a_initiation basics
grantlerc
 
Fire basics 1-4-risers_thru_power_supplies_08
Fire basics 1-4-risers_thru_power_supplies_08Fire basics 1-4-risers_thru_power_supplies_08
Fire basics 1-4-risers_thru_power_supplies_08
grantlerc
 
Fire basics 1-3-functions_to_docs_08
Fire basics 1-3-functions_to_docs_08Fire basics 1-3-functions_to_docs_08
Fire basics 1-3-functions_to_docs_08
grantlerc
 
Fire basics 1-2-the_nec_11
Fire basics 1-2-the_nec_11Fire basics 1-2-the_nec_11
Fire basics 1-2-the_nec_11
grantlerc
 
Fire basics 1-1-fundamentals
Fire basics 1-1-fundamentalsFire basics 1-1-fundamentals
Fire basics 1-1-fundamentals
grantlerc
 
Fiber optics 2-7
Fiber optics 2-7Fiber optics 2-7
Fiber optics 2-7
grantlerc
 
Fiber optics 2-6
Fiber optics 2-6Fiber optics 2-6
Fiber optics 2-6
grantlerc
 
Fiber optics 2-5
Fiber optics 2-5Fiber optics 2-5
Fiber optics 2-5
grantlerc
 

More from grantlerc (20)

Fire alarm 3-f-single_and_multiple-station_alarms_and_household_fire_alarm_sy...
Fire alarm 3-f-single_and_multiple-station_alarms_and_household_fire_alarm_sy...Fire alarm 3-f-single_and_multiple-station_alarms_and_household_fire_alarm_sy...
Fire alarm 3-f-single_and_multiple-station_alarms_and_household_fire_alarm_sy...
 
Fire alarm 3-e-public_emergency_alarm_reporting_systems
Fire alarm 3-e-public_emergency_alarm_reporting_systemsFire alarm 3-e-public_emergency_alarm_reporting_systems
Fire alarm 3-e-public_emergency_alarm_reporting_systems
 
Fire alarm 3-d-supervising_station_alarm_system
Fire alarm 3-d-supervising_station_alarm_systemFire alarm 3-d-supervising_station_alarm_system
Fire alarm 3-d-supervising_station_alarm_system
 
Fire alarm 3-b-protected_premises_fire_alarm_system
Fire alarm 3-b-protected_premises_fire_alarm_systemFire alarm 3-b-protected_premises_fire_alarm_system
Fire alarm 3-b-protected_premises_fire_alarm_system
 
Fire alarm 3-a-emergency_control_functions
Fire alarm 3-a-emergency_control_functionsFire alarm 3-a-emergency_control_functions
Fire alarm 3-a-emergency_control_functions
 
Fire alarm basics 1-6
Fire alarm basics 1-6Fire alarm basics 1-6
Fire alarm basics 1-6
 
Fire alarm basics 1-5
Fire alarm basics 1-5Fire alarm basics 1-5
Fire alarm basics 1-5
 
Fire alarm 2_f_manual supervisory
Fire alarm 2_f_manual supervisoryFire alarm 2_f_manual supervisory
Fire alarm 2_f_manual supervisory
 
Fire alarm 2_e_combination
Fire alarm 2_e_combinationFire alarm 2_e_combination
Fire alarm 2_e_combination
 
Fire alarm 2_d_radiant energy detectors
Fire alarm 2_d_radiant energy detectorsFire alarm 2_d_radiant energy detectors
Fire alarm 2_d_radiant energy detectors
 
Fire alarm 2_c_smoke detectors
Fire alarm 2_c_smoke detectorsFire alarm 2_c_smoke detectors
Fire alarm 2_c_smoke detectors
 
Fire alarm 2_b_heat detectors
Fire alarm 2_b_heat detectorsFire alarm 2_b_heat detectors
Fire alarm 2_b_heat detectors
 
Fire alarm 2_a_initiation basics
Fire alarm 2_a_initiation basicsFire alarm 2_a_initiation basics
Fire alarm 2_a_initiation basics
 
Fire basics 1-4-risers_thru_power_supplies_08
Fire basics 1-4-risers_thru_power_supplies_08Fire basics 1-4-risers_thru_power_supplies_08
Fire basics 1-4-risers_thru_power_supplies_08
 
Fire basics 1-3-functions_to_docs_08
Fire basics 1-3-functions_to_docs_08Fire basics 1-3-functions_to_docs_08
Fire basics 1-3-functions_to_docs_08
 
Fire basics 1-2-the_nec_11
Fire basics 1-2-the_nec_11Fire basics 1-2-the_nec_11
Fire basics 1-2-the_nec_11
 
Fire basics 1-1-fundamentals
Fire basics 1-1-fundamentalsFire basics 1-1-fundamentals
Fire basics 1-1-fundamentals
 
Fiber optics 2-7
Fiber optics 2-7Fiber optics 2-7
Fiber optics 2-7
 
Fiber optics 2-6
Fiber optics 2-6Fiber optics 2-6
Fiber optics 2-6
 
Fiber optics 2-5
Fiber optics 2-5Fiber optics 2-5
Fiber optics 2-5
 

Recently uploaded

一比一原版(爱大毕业证书)爱荷华大学毕业证如何办理
一比一原版(爱大毕业证书)爱荷华大学毕业证如何办理一比一原版(爱大毕业证书)爱荷华大学毕业证如何办理
一比一原版(爱大毕业证书)爱荷华大学毕业证如何办理
nedcocy
 
Transformers design and coooling methods
Transformers design and coooling methodsTransformers design and coooling methods
Transformers design and coooling methods
Roger Rozario
 
Prediction of Electrical Energy Efficiency Using Information on Consumer's Ac...
Prediction of Electrical Energy Efficiency Using Information on Consumer's Ac...Prediction of Electrical Energy Efficiency Using Information on Consumer's Ac...
Prediction of Electrical Energy Efficiency Using Information on Consumer's Ac...
PriyankaKilaniya
 
DESIGN AND MANUFACTURE OF CEILING BOARD USING SAWDUST AND WASTE CARTON MATERI...
DESIGN AND MANUFACTURE OF CEILING BOARD USING SAWDUST AND WASTE CARTON MATERI...DESIGN AND MANUFACTURE OF CEILING BOARD USING SAWDUST AND WASTE CARTON MATERI...
DESIGN AND MANUFACTURE OF CEILING BOARD USING SAWDUST AND WASTE CARTON MATERI...
OKORIE1
 
Power Electronics- AC -AC Converters.pptx
Power Electronics- AC -AC Converters.pptxPower Electronics- AC -AC Converters.pptx
Power Electronics- AC -AC Converters.pptx
Poornima D
 
Asymmetrical Repulsion Magnet Motor Ratio 6-7.pdf
Asymmetrical Repulsion Magnet Motor Ratio 6-7.pdfAsymmetrical Repulsion Magnet Motor Ratio 6-7.pdf
Asymmetrical Repulsion Magnet Motor Ratio 6-7.pdf
felixwold
 
Supermarket Management System Project Report.pdf
Supermarket Management System Project Report.pdfSupermarket Management System Project Report.pdf
Supermarket Management System Project Report.pdf
Kamal Acharya
 
Levelised Cost of Hydrogen (LCOH) Calculator Manual
Levelised Cost of Hydrogen  (LCOH) Calculator ManualLevelised Cost of Hydrogen  (LCOH) Calculator Manual
Levelised Cost of Hydrogen (LCOH) Calculator Manual
Massimo Talia
 
SENTIMENT ANALYSIS ON PPT AND Project template_.pptx
SENTIMENT ANALYSIS ON PPT AND Project template_.pptxSENTIMENT ANALYSIS ON PPT AND Project template_.pptx
SENTIMENT ANALYSIS ON PPT AND Project template_.pptx
b0754201
 
An Introduction to the Compiler Designss
An Introduction to the Compiler DesignssAn Introduction to the Compiler Designss
An Introduction to the Compiler Designss
ElakkiaU
 
一比一原版(osu毕业证书)美国俄勒冈州立大学毕业证如何办理
一比一原版(osu毕业证书)美国俄勒冈州立大学毕业证如何办理一比一原版(osu毕业证书)美国俄勒冈州立大学毕业证如何办理
一比一原版(osu毕业证书)美国俄勒冈州立大学毕业证如何办理
upoux
 
4. Mosca vol I -Fisica-Tipler-5ta-Edicion-Vol-1.pdf
4. Mosca vol I -Fisica-Tipler-5ta-Edicion-Vol-1.pdf4. Mosca vol I -Fisica-Tipler-5ta-Edicion-Vol-1.pdf
4. Mosca vol I -Fisica-Tipler-5ta-Edicion-Vol-1.pdf
Gino153088
 
Assistant Engineer (Chemical) Interview Questions.pdf
Assistant Engineer (Chemical) Interview Questions.pdfAssistant Engineer (Chemical) Interview Questions.pdf
Assistant Engineer (Chemical) Interview Questions.pdf
Seetal Daas
 
Applications of artificial Intelligence in Mechanical Engineering.pdf
Applications of artificial Intelligence in Mechanical Engineering.pdfApplications of artificial Intelligence in Mechanical Engineering.pdf
Applications of artificial Intelligence in Mechanical Engineering.pdf
Atif Razi
 
Open Channel Flow: fluid flow with a free surface
Open Channel Flow: fluid flow with a free surfaceOpen Channel Flow: fluid flow with a free surface
Open Channel Flow: fluid flow with a free surface
Indrajeet sahu
 
一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理
一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理
一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理
upoux
 
一比一原版(USF毕业证)旧金山大学毕业证如何办理
一比一原版(USF毕业证)旧金山大学毕业证如何办理一比一原版(USF毕业证)旧金山大学毕业证如何办理
一比一原版(USF毕业证)旧金山大学毕业证如何办理
uqyfuc
 
P5 Working Drawings.pdf floor plan, civil
P5 Working Drawings.pdf floor plan, civilP5 Working Drawings.pdf floor plan, civil
P5 Working Drawings.pdf floor plan, civil
AnasAhmadNoor
 
1FIDIC-CONSTRUCTION-CONTRACT-2ND-ED-2017-RED-BOOK.pdf
1FIDIC-CONSTRUCTION-CONTRACT-2ND-ED-2017-RED-BOOK.pdf1FIDIC-CONSTRUCTION-CONTRACT-2ND-ED-2017-RED-BOOK.pdf
1FIDIC-CONSTRUCTION-CONTRACT-2ND-ED-2017-RED-BOOK.pdf
MadhavJungKarki
 
Zener Diode and its V-I Characteristics and Applications
Zener Diode and its V-I Characteristics and ApplicationsZener Diode and its V-I Characteristics and Applications
Zener Diode and its V-I Characteristics and Applications
Shiny Christobel
 

Recently uploaded (20)

一比一原版(爱大毕业证书)爱荷华大学毕业证如何办理
一比一原版(爱大毕业证书)爱荷华大学毕业证如何办理一比一原版(爱大毕业证书)爱荷华大学毕业证如何办理
一比一原版(爱大毕业证书)爱荷华大学毕业证如何办理
 
Transformers design and coooling methods
Transformers design and coooling methodsTransformers design and coooling methods
Transformers design and coooling methods
 
Prediction of Electrical Energy Efficiency Using Information on Consumer's Ac...
Prediction of Electrical Energy Efficiency Using Information on Consumer's Ac...Prediction of Electrical Energy Efficiency Using Information on Consumer's Ac...
Prediction of Electrical Energy Efficiency Using Information on Consumer's Ac...
 
DESIGN AND MANUFACTURE OF CEILING BOARD USING SAWDUST AND WASTE CARTON MATERI...
DESIGN AND MANUFACTURE OF CEILING BOARD USING SAWDUST AND WASTE CARTON MATERI...DESIGN AND MANUFACTURE OF CEILING BOARD USING SAWDUST AND WASTE CARTON MATERI...
DESIGN AND MANUFACTURE OF CEILING BOARD USING SAWDUST AND WASTE CARTON MATERI...
 
Power Electronics- AC -AC Converters.pptx
Power Electronics- AC -AC Converters.pptxPower Electronics- AC -AC Converters.pptx
Power Electronics- AC -AC Converters.pptx
 
Asymmetrical Repulsion Magnet Motor Ratio 6-7.pdf
Asymmetrical Repulsion Magnet Motor Ratio 6-7.pdfAsymmetrical Repulsion Magnet Motor Ratio 6-7.pdf
Asymmetrical Repulsion Magnet Motor Ratio 6-7.pdf
 
Supermarket Management System Project Report.pdf
Supermarket Management System Project Report.pdfSupermarket Management System Project Report.pdf
Supermarket Management System Project Report.pdf
 
Levelised Cost of Hydrogen (LCOH) Calculator Manual
Levelised Cost of Hydrogen  (LCOH) Calculator ManualLevelised Cost of Hydrogen  (LCOH) Calculator Manual
Levelised Cost of Hydrogen (LCOH) Calculator Manual
 
SENTIMENT ANALYSIS ON PPT AND Project template_.pptx
SENTIMENT ANALYSIS ON PPT AND Project template_.pptxSENTIMENT ANALYSIS ON PPT AND Project template_.pptx
SENTIMENT ANALYSIS ON PPT AND Project template_.pptx
 
An Introduction to the Compiler Designss
An Introduction to the Compiler DesignssAn Introduction to the Compiler Designss
An Introduction to the Compiler Designss
 
一比一原版(osu毕业证书)美国俄勒冈州立大学毕业证如何办理
一比一原版(osu毕业证书)美国俄勒冈州立大学毕业证如何办理一比一原版(osu毕业证书)美国俄勒冈州立大学毕业证如何办理
一比一原版(osu毕业证书)美国俄勒冈州立大学毕业证如何办理
 
4. Mosca vol I -Fisica-Tipler-5ta-Edicion-Vol-1.pdf
4. Mosca vol I -Fisica-Tipler-5ta-Edicion-Vol-1.pdf4. Mosca vol I -Fisica-Tipler-5ta-Edicion-Vol-1.pdf
4. Mosca vol I -Fisica-Tipler-5ta-Edicion-Vol-1.pdf
 
Assistant Engineer (Chemical) Interview Questions.pdf
Assistant Engineer (Chemical) Interview Questions.pdfAssistant Engineer (Chemical) Interview Questions.pdf
Assistant Engineer (Chemical) Interview Questions.pdf
 
Applications of artificial Intelligence in Mechanical Engineering.pdf
Applications of artificial Intelligence in Mechanical Engineering.pdfApplications of artificial Intelligence in Mechanical Engineering.pdf
Applications of artificial Intelligence in Mechanical Engineering.pdf
 
Open Channel Flow: fluid flow with a free surface
Open Channel Flow: fluid flow with a free surfaceOpen Channel Flow: fluid flow with a free surface
Open Channel Flow: fluid flow with a free surface
 
一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理
一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理
一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理
 
一比一原版(USF毕业证)旧金山大学毕业证如何办理
一比一原版(USF毕业证)旧金山大学毕业证如何办理一比一原版(USF毕业证)旧金山大学毕业证如何办理
一比一原版(USF毕业证)旧金山大学毕业证如何办理
 
P5 Working Drawings.pdf floor plan, civil
P5 Working Drawings.pdf floor plan, civilP5 Working Drawings.pdf floor plan, civil
P5 Working Drawings.pdf floor plan, civil
 
1FIDIC-CONSTRUCTION-CONTRACT-2ND-ED-2017-RED-BOOK.pdf
1FIDIC-CONSTRUCTION-CONTRACT-2ND-ED-2017-RED-BOOK.pdf1FIDIC-CONSTRUCTION-CONTRACT-2ND-ED-2017-RED-BOOK.pdf
1FIDIC-CONSTRUCTION-CONTRACT-2ND-ED-2017-RED-BOOK.pdf
 
Zener Diode and its V-I Characteristics and Applications
Zener Diode and its V-I Characteristics and ApplicationsZener Diode and its V-I Characteristics and Applications
Zener Diode and its V-I Characteristics and Applications
 

Nec and oesc-5

  • 1. 500. 2 Definitions Combustible Dust. Dust particles that are 500 microns or smaller (material passing a U.S. No. 35 Standard Sieve as defined in ASTM E 11-09, Standard Specification for Wire Cloth and Sieves for Testing Purposes) and present a fire or explosion hazard when dispersed and ignited in air. Informational Note: See ASTM E 1226–12a, Standard Test Method for Explosibility of Dust Clouds, or ISO 6184-1, Explosion protection systems — Part 1: Determination of explosion indices of combustible dusts in air, for procedures for determining the explosibility of dusts.
  • 2. Class 1 Locations 501.10 Wiring Methods (A) Class I, Division 1.  (1) General. In Class I, Division 1 locations, the wiring methods in (a) through ( e) shall be permitted. (e) Optical fiber cable Types OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, and OFC shall be permitted to be installed in raceways in accordance with 501.10(A). These optical fiber cables shall be sealed in accordance with 501.15.
  • 3. Class 1 Locations 501.10 Wiring Methods (A) Class I, Division 1.  (2) Flexible Connections. Where necessary to employ flexible connections, as at motor terminals, the following shall be permitted:  (1) Flexible fittings listed for the location, or  (2) Flexible cord in accordance with the provisions of 501.140, terminated with cord connectors listed for the location, or
  • 4. Class 1 Locations 501.10 Wiring Methods (A) Class I, Division 1.  (2) Flexible Connections – (cont.)  (3) In industrial establishments with restricted public access, where the conditions of maintenance and supervision ensure that only qualified persons service the installation, for applications limited to 600 volts, nominal, or less, and where protected from damage by location or a suitable guard, listed Type TC-ER-HL cable with an overall jacket and a separate equipment grounding conductor(s) in accordance with 250.122 that is terminated with fittings listed for the location
  • 5. Class 1 Locations 501.15 Sealing and Drainage  (C) Class I, Divisions 1 and 2.  (6) Conductor or Optical Fiber Fill. The cross-sectional area of the conductors or optical fiber tubes (metallic or nonmetallic) permitted in a seal shall not exceed 25 percent of the cross- sectional area of a rigid metal conduit of the same trade size unless the seal is specifically identified for a higher percentage of fill.
  • 6. Class 1 Locations  501.30 Grounding and Bonding, Class I, Divisions 1 and 2 Regardless of the voltage of the electrical system, wiring and equipment in Class I, Division 1 and 2 locations shall be grounded as specified in Article 250 and in accordance with the requirements of 501.30(A) and (B).
  • 7. Class II Locations  502.10 Wiring Methods  (A) Class II, Division 1.  (1) General. In Class II, Division 1 locations, the wiring methods in (1) through (4) shall be permitted  (4) Optical fiber cables Types OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, and OFC shall be permitted to be installed in raceways in accordance with 502.10(A). Optical fiber cables shall be sealed in accordance with 502.15.d:
  • 8. Class II Locations  502.30 Grounding and Bonding, Class II, Divisions 1 and 2 Regardless of the voltage of the electrical system, wiring and equipment in Class II, Division 1 and 2 locations shall be grounded as specified in Article 250 and in accordance with the requirements of 502.30(A) and (B).
  • 9. Intrinsically Safe Systems  504.10 Equipment Installation  (C) Enclosures. General-purpose enclosures shall be permitted for intrinsically safe apparatus and associated apparatus unless otherwise specified in the manufacturer’s documentation.
  • 10. Motor Fuel Dispensing Facilities 514.3 Classification of Locations  (C) Motor Fuel Dispensing Stations in Boatyards and Marinas.  (1) General. Electrical wiring and equipment located at or serving motor fuel dispensing locations shall be installed on the side of the wharf, pier, or dock opposite from the liquid piping system. Informational Note: For additional information, see NFPA 303-2011, Fire Protection Standard for Marinas and Boatyards, and NFPA 30A-2012, Motor Fuel Dispensing Facilities and Repair Garages.
  • 11. Motor Fuel Dispensing Facilities 514.3 Classification of Locations  (C) Motor Fuel Dispensing Stations in Boatyards and Marinas – (cont.)  (2) Classification of Class I, Division 1 and 2 Areas. The following criteria shall be used for the purposes of applying Table 514.3(B)(1) and Table 514.3(B)(2) to motor fuel dispensing equipment on floating or fixed piers, wharfs, or docks.
  • 12. Motor Fuel Dispensing Facilities 514.3 Classification of Locations  (D) Closed Construction. Where the construction of floating docks, piers, or wharfs is closed so that there is no space between the bottom of the dock, pier, or wharf and the water, as in the case of concrete-enclosed expanded foam or similar construction, and the construction includes integral service boxes with supply chases, the following shall apply:
  • 13. Motor Fuel Dispensing Facilities 514.3 Classification of Locations  (1) The space above the surface of the floating dock, pier, or wharf shall be a Class I, Division 2 location with distances as specified in Table 514.3(B)(1)(1) for dispenser and outdoor locations.  (2) Spaces below the surface of the floating dock, pier, or wharf that have areas or enclosures, such as tubs, voids, pits, vaults, boxes, depressions, fuel piping chases, or similar spaces, where flammable liquid or vapor can accumulate shall be a Class I, Division 1 location.
  • 14. Motor Fuel Dispensing Facilities 514.3 Classification of Locations  Exception No. 1: Dock, pier, or wharf sections that do not support fuel dispensers and abut, but are located 6.0 m (20 ft) or more from, dock sections that support a fuel dispenser(s) shall be permitted to be Class I, Division 2 locations where documented air space is provided between dock sections to allow flammable liquids or vapors to dissipate without traveling to such dock sections. The documentation shall comply with 500.4(A).  Exception No. 2: Dock, pier, or wharf sections that do not support fuel dispensers and do not directly abut sections that support fuel dispensers shall be permitted to be unclassified where documented air space is provided and where flammable liquids or vapors cannot travel to such dock sections. The documentation shall comply with 500.4(A).
  • 15. Motor Fuel Dispensing Facilities 514.3 Classification of Locations  (E) Open Construction. Where the construction of piers, wharfs, or docks is open, as in the case of decks built on stringers supported by pilings, floats, pontoons, or similar construct ion, the following shall apply:  (1) The area 450 mm (18 in.) above the surface of the dock, pier, or wharf and extending 6.0 m (20 ft) horizontally in all directions from the outside edge of the dispenser and down to the water level shall be a Class 1, Division 2 location.  (2) Enclosures such as tubs, voids, pits, vaults, boxes, depressions, piping chases, or similar spaces where flammable liquids or vapors can accumulate within 6.0 m (20 ft) of the dispenser shall be a Class I, Division 1 location.
  • 16. ARTICLE 516 Spray Application, Dipping, Coating, and Printing Processes Using Flammable or Combustible Materials  516.2 Definitions  Flash-Off Area. An open or enclosed area after a spray application process where vapors are released due to exposure to ambient air or a heated atmosphere. [33:3.3.1.1]  Limited Finishing Workstation. An apparatus that is capable of confining the vapors, mists, residues, dusts, or deposits that are generated by a spray application process and that meets the requirements of Section 14.3 of NFPA 33, Standard for Spray Application Using Flammable or Combustible Materials, but does not meet the requirements of a spray booth or spray room, as herein defined. [33:3.3.15.1]
  • 17. ARTICLE 516 Spray Application, Dipping, Coating, and Printing Processes Using Flammable or Combustible Materials  516.2 Definitions – (cont.)  Resin Application Area. Any area in which polyester resins or gelcoats are spray applied. [33:3.3.1.2]  Spray Area. Any fully enclosed, partly enclosed, or unenclosed area in which ignitible quantities of flammable or combustible vapors, mists, residues, dusts, or deposits are present due to the operation of spray processes, including (1) any area in the direct path of a spray application process; (2) the interior of a spray booth or spray room or limited finishing workstation, as herein defined; (3) the interior of any exhaust plenum, eliminator section, or scrubber section; (4) the interior of any exhaust duct or exhaust stack leading from a spray application process;
  • 18. ARTICLE 516 Spray Application, Dipping, Coating, and Printing Processes Using Flammable or Combustible Materials  516.2 Definitions – (cont.)  (5) the interior of any air recirculation filter house or enclosure, including secondary recirculation particulate filters; (6) any solvent concentrator (pollution abatement) unit or solvent recovery (distillation) unit. The following are not considered to be a part of the spray area: (1) fresh air make-up units; (2) air supply ducts and air supply plenums; (3) recirculation air supply ducts downstream of secondary filters; (4) exhaust ducts from solvent concentrateur (pollution abattement) units. [33:3.3.2.3]
  • 19. ARTICLE 516 Spray Application, Dipping, Coating, and Printing Processes Using Flammable or Combustible Materials  516.2 Definitions – (cont.)  Spray Area – (cont.) (5) the interior of any air recirculation filter house or enclosure, including secondary recirculation particulate filters; (6) any solvent concentrator (pollution abatement) unit or solvent recovery (distillation) unit. The following are not considered to be a part of the spray area: (1) fresh air make-up units; (2) air supply ducts and air supply plenums; (3) recirculation air supply ducts downstream of secondary filters; (4) exhaust ducts from solvent concentrator (pollution abatement) units. [33:3.3.2.3]
  • 20. ARTICLE 516 Spray Application, Dipping, Coating, and Printing Processes Using Flammable or Combustible Materials  516.2 Definitions  Spray Booth. A power-ventilated enclosure for a spray application operation or process that confines and limits the escape of the material being sprayed, including vapors, mists, dusts, and residues that are produced by the spraying operation and conducts or directs these materials to an exhaust system. [33:3.3.14]
  • 21. ARTICLE 516 Spray Application, Dipping, Coating, and Printing Processes Using Flammable or Combustible Materials  516.2 Definitions  Spray Room. A power-ventilated fully enclosed room used exclusively for open spraying of flammable or combustible materials. A spray room is a purposefully enclosed room built for spray/coating/dipping applications provided with dedicated ventilation supply and exhaust. Normally the room is configured to house the item to be painted, providing reasonable access around the item/process. Depending on the size of the item being painted, such rooms may actually be the entire building or the major portion thereof. [33:3.3.15]
  • 22. ARTICLE 516 Spray Application, Dipping, Coating, and Printing Processes Using Flammable or Combustible Materials  516.2 Definitions  Unenclosed Spray Area. Any spray area that is not confined by a limited finishing workstation, spray booth, or spray room, as herein defined. [33:3.3.2.3.2]
  • 23. 516. 3 Classification of Locations  (A) Zone Classification of Locations. (1) For the purposes of this article, the zone system of electrical area classification shall be applied as follows: a. The inside of open or closed containers or vessels shall be considered a Class I, Zone 0 location. b. A Class I, Division 1 location shall be permitted to be alternatively classified as a Class I, Zone 1 location. c. A Class I, Division 2 location shall be permitted to be alternatively classified as a Class I, Zone 2 location. d. A Class II, Division 1 location shall be permitted to be alternatively classified as a Zone 21 location. e. A Class II, Division 2 location shall be permitted to be alternatively classified as a Zone 22 location. [33:6.2.2]
  • 24. 516. 3 Classification of Locations (cont.) (2) For the purposes of electrical area classification, the division system and the zone system shall not be intermixed for any given source of release. [33:6.2.3] (3) In instances of areas within the same facility classified separately, Class I, Zone 2 locations shall be permitted to abut, but not overlap, Class I, Division 2 locations. Class I, Zone 0 or Zone 1 locations shall not abut Class I, Division 1 or Division 2 locations. [33:6.2.4]
  • 25. 516. 3 Classification of Locations (cont.) (4) Open flames, spark-producing equipment or processes, and equipment whose exposed surfaces exceed the autoignition temperature of the material being sprayed shall not be located in a spray area or in any surrounding area that is classified as Division 2, Zone 2, or Zone 22. Exception: This requirement shall not apply to drying, curing, or fusing apparatus. [33:6.2.5]
  • 26. 516. 3 Classification of Locations (cont.) (5) Any utilization equipment or apparatus that is capable of producing sparks or particles of hot metal and that is located above or adjacent to either the spray area or the surrounding Division 2, Zone 2, or Zone 22 areas shall be of the totally enclosed type or shall be constructed to prevent the escape of sparks or particles of hot metal. [33:6.2.6]
  • 27. Health Care Facilities 517.2 Definitions  Life Safety Branch. A system of feeders and branch circuits supplying power for lighting, receptacles, and equipment essential for life safety that is automatically connected to alternate power sources by one or more transfer switches during interruption of the normal power source. [99:3.3.94]
  • 28. Health Care Facilities 517.2 Definitions – (cont.)  Patient Care Space. Space within a health care facility wherein patients are intended to be examined or treated.  Basic Care Space. Space in which failure of equipment or a system is not likely t o cause injury to the patients or caregivers but may cause patient discomfort.  General Care Space. Space in which failure of equipment or a system is likely to cause minor injury to patients or caregivers.  Critical Care Space. Space in which failure of equipment or a system is likely to cause major injury or death to patients or caregivers.
  • 29. Health Care Facilities 517.2 Definitions – (cont.)  Support Space. Space in which failure of equipment or a system is not likely to have a physical impact on patients or caregivers. Informational Note No. 1: The governing body of the facility designates patient care space in accordance with the type of patient care anticipated and with the definitions of the area classification. Business offices, corridors, lounges, day rooms, dining rooms, or similar areas typically are not classified as patient care space. Informational Note No. 2: Basic care space is typically a location where basic medical or dental care, treatment, or examinations are performed. Examples include, but are not limited to, examination or treatment rooms in clinics, medical and dental offices, nursing homes, and limited care facilities.
  • 30. Health Care Facilities 517.2 Definitions – (cont.)  Informational Note No. 3: General care space includes areas such as patient bedrooms, examining rooms, treatment rooms, clinics, and similar areas where the patient may come into contact with electromedical devices or ordinary appliances such as a nurse call system, electric beds, examining lamps, telephones, and entertainment devices.  Informational Note No. 4: Critical care space includes special care units, intensive care units, coronary care units, angiography laboratories, cardiac catheterization laboratories, delivery rooms, operating rooms, and similar areas in which are patients are intended to be subjected to invasive procedures and are connected to line-operated, electromedical devices.  Informational Note No. 5: Spaces where a procedure is performed that subjects patients or staff to wet conditions are considered as wet procedure areas. Wet conditions include standing fluids on the floor or drenching of the work area. Routine housekeeping procedures and incidental spillage of liquids do not define wet procedure areas. It is the responsibility of the governing body of the health care facility to designate the wet procedure areas.
  • 31. Health Care Facilities 517.2 Definitions – (cont.)  Patient Care Vicinity. A space, within a location intended for the examination and treatment of patients, extending 1.8 m (6 ft) beyond the normal location of the patient bed, chair, table, treadmill, or other device that supports the patient during examination and treatment and extending vertically to 2.3 m (7 ft 6 in.) above the floor. [99:3.3.139]
  • 32. Health Care Facilities 517.2 Definitions – (cont.)  Wet Procedure Location. The area in a patient care space where a procedure is performed that is normally subject to wet conditions while patients are present, including standing fluids on the floor or drenching of the work area, where either such condition is intimate to the patient or staff.  Informational Note: Routine housekeeping procedures and incidental spillage of liquids do not define a wet procedure location.
  • 33. Further Information  Wet procedure locations may also include such areas as hydrotherapy areas, dialysis laboratories, and certain wet laboratories at the discretion of the governing body of the facility. The definition excludes areas such as lavatories or bathrooms within a health care facility. For infection control purposes, many patient and treatment areas have a sink for hand washing, which also is not a wet procedure location.
  • 34. Health Care Facilities 517.19(C) Operating Room Receptacles  (1) Minimum Number and Supply. Each operating room shall be provided with a minimum of 36 receptacles, at least 12 of which shall be connected to eit her of the following:  (1) The normal system branch circuit required in 517.19(A)  (2) A critical branch circuit supplied by a different transfer switch than the other receptacles at the same location
  • 35. Health Care Facilities 517.19(C) Operating Room Receptacles  (2) Receptacle Requirements. The receptacles required in (517.19)(C)(1) shall be permitted to be of the single or duplex types or a combination of both. All receptacles shall be listed hospital grade and so identified. The grounding terminal of each receptacle shall be connected to the reference grounding point by means of an insulated copper equipment grounding conductor.
  • 36. ARTICLE 520 Theaters, Audience Areas of Motion Picture and Television Studios, Performance Areas, and Similar Locations
  • 37. 520.2 Definitions  Stage Equipment. Equipment at any location on the premises integral to the stage production including, but not limited to, equipment for lighting, audio, special effects, rigging, motion control, projection, or video.
  • 38. 520.2 Definitions – (cont.)  Stage Lighting Hoist. A motorized lifting device that contains a mounting position for one or more luminaires, with wiring devices for connection of luminaires to branch circuits, and integral flexible cables to allow the luminaires to travel over the lifting range of the hoist while energized.
  • 39. 520.2 Definitions – (cont.)  Stage Switchboard. A switchboard, panelboard, or rack containing dimmers or relays with associated overcurrent protective devices, or overcurrent protective devices alone, used primarily to feed stage equipment.
  • 40. II. Fixed Stage Switchboards 520.21 General  Fixed stage switchboards shall comply with 520.21(1) through (4):  (1) Fixed stage switchboards shall be listed.  (2) Fixed stage switchboards shall be readily accessible but shall not be required to be located on or adjacent to the stage. Multiple fixed stage switchboards shall be permitted at different locations.  (3) A fixed stage switchboard shall contain overcurrent protective devices for all branch circuits supplied by that switchboard.  (4) A fixed stage switchboard shall be permitted to supply both stage and non-stage equipment.
  • 41. III. Fixed Stage Equipment Other Than Switchboards  520.40 Stage Lighting Hoists Where a stage lighting hoist is listed as a complete assembly and contains an integral cable-handling system and cable to connect a moving wiring device to a fixed junction box for connection to permanent wiring, the extra-hard usage requirement of 520.44(C)(1) shall not apply.
  • 42. ARTICLE 640 Audio Signal Processing, Amplification, and Reproduction Equipment 640.1 Scope  (B) Not Covered. This article does not cover the installation and wiring of fire and burglary alarm signaling devices.
  • 43. 680.22 Lighting, Receptacles, and Equipment (B) Luminaires, Lighting Outlets, and Ceiling-Suspended (Paddle) Fans.  (6) Low-Voltage Luminaires. Listed low-voltage luminaires not requiring grounding, not exceeding the low-voltage contact limit, and supplied by listed transformers or power supplies that comply with 680.23(A)(2) shall be permitted to be located less than 1.5 m (5 ft) from the inside walls of the pool.
  • 44. 680.26 Equipotential Bonding  (C) Pool Water. Where none of the bonded parts is in direct connection with the pool water, the pool water shall be in direct contact with an approved corrosion-resistant conductive surface that exposes not less than 5800 mm2 (9 in.2) of surface area to the pool water at all times. The conductive surface shall be located where it is not exposed to physical damage or dislodgement during usual pool activities, and it shall be bonded in accordance with 680.26(B).
  • 45. Solar Photovoltaic (PV ) Systems 690.2 Definitions  DC-to-DC Converter. A device installed in the PV source circuit or PV output circuit that can provide an output dc voltage and current at a higher or lower value than the input dc voltage and current.
  • 46. Solar Photovoltaic (PV ) Systems 690.2 Definitions  Direct-Current (dc) Combiner. A device used in the PV source and PV output circuits to combine two or more dc circuit inputs and provide one dc circuit output.
  • 47. Solar Photovoltaic (PV ) Systems 690.2 Definitions  Multimode Inverter. Equipment having the capabilities of both the utility-interactive inverter and the stand-alone inverter.
  • 48. IV. Wiring Methods 690.31 Methods Permitted  (B) Identification and Grouping. PV source circuits and PV output circuits shall not be contained in the same raceway, cable tray, cable, outlet box, junction box, or similar fitting as conductors, feeders, branch circuits of other non-PV systems, or inverter output circuits, unless the conductors of the different systems are separated by a partition. PV system conductors shall be identified and grouped as required by 690.31(B)(1) through (4). The means of identification shall be permitted by separate color coding, marking tape, tagging, or other approved means.
  • 49. IV. Wiring Methods 690.31 Methods Permitted  (B) Identification and Grouping (cont.)  (1) PV Source Circuits. PV source circuits shall be identified at all points of termination, connection, and splices.  (2) PV Output and Inverter Circuits. The conductors of PV output circuits and inverter input and output circuits shall be identified at all points of termination, connection, and splices.
  • 50. IV. Wiring Methods 690.31 Methods Permitted  (B) Identification and Grouping (cont.)  (3) Conductors of Multiple Systems. Where the conductors of more than one PV system occupy the same junction box, raceway, or equipment, the conductors of each system shall be identified at all termination, connection, and splice points. Exception: Where the identification of the conductors is evident by spacing or arrangement, further identification shall not be required.
  • 51. IV. Wiring Methods 690.31 Methods Permitted  (B) Identification and Grouping (cont.)  (4) Grouping. Where the conductors of more than one PV system occupy the same junction box or raceway with a removable cover(s), the ac and dc conductors of each system shall be grouped separately by cable ties or similar means at least once and shall then be grouped at intervals not to exceed 1.8 m (6 ft). Exception: The requirement for grouping shall not apply if the circuit enters from a cable or raceway unique to the circuit that makes the grouping obvious.