This document defines terms related to combustible dust, wiring methods in hazardous locations, grounding requirements, and spray application processes using flammable materials. It provides definitions for combustible dust, various wiring methods permitted in Class I and Class II hazardous locations, sealing and drainage requirements, and definitions for terms like flash-off area, limited finishing workstation, resin application area, and spray area as they relate to spray application processes using flammable materials. It specifies grounding requirements for wiring in hazardous locations and classification of locations for motor fuel dispensing facilities.
The document discusses requirements for flexible cords and cables, receptacles, lighting systems operating at low voltages, appliances, and storage batteries. Some key points include:
- Flexible cords and cables must conform to descriptions in Table 400.4 and can only be used for certain applications.
- Receptacles must be securely mounted and tamper-resistant receptacles are required in certain areas like dwellings and child care facilities.
- Lighting systems operating at 30V or less must use isolating power supplies and listed low-voltage luminaires.
- Appliances like vending machines and inflators must be protected by GFCIs.
- Storage batteries must have sufficient ventilation and space, and terminals cannot
This document lists approvals for various electrical apparatus and cables for use in hazardous areas of oil mines. It provides details of 14 equipment approved by Flexpro Electricals Pvt Ltd such as hand lamp fittings, well glass fittings, control gear boxes, junction boxes, switches, and portable transformers. The approvals specify the equipment type number, construction material, electrical ratings, and expiry dates of the approval, which is valid for use in Zone 1 and Zone 2 hazardous areas of oil mines.
This document provides a list of materials and specifications for an electrical installation project. It includes 14 items with descriptions of materials like service entrance caps, feeder conduit, conductors, emergency circuit breakers, distribution panels, switches and more. Specifications are provided for proper installation and sizing according to standards like the Philippine Electrical Code (PEC) 2017. Total estimated cost is provided for each item and annexes provide additional details for specifications referenced.
This document provides guidance on calculating loading for devices connected to an MX Digital Loop installation. It specifies the loading parameters for each device in terms of DC and AC units. The maximum number of devices per loop is 250. The document provides limits for DC and AC loading and guidance on using short-circuit isolators. It also provides a table of loading values for each device type to allow calculation of total loop loading.
The document discusses specifications for the 158LR separable connector, which meets CENELEC HD 629.1 requirements for up to 24 kV and 250 A. It has an insulating EPDM layer between conductive inner and outer jackets. The connector is designed to connect polymeric cable to equipment safely. Ordering information is provided for selecting the proper connector kit based on cable type, size, and voltage rating.
The document provides information on the 152SR straight connector for connecting polymeric insulated cable to equipment up to 24 kV and 250 A. The connector consists of a conductive EPDM insert, jacket and insulating layer, along with interface, conductor connector, and test point. It meets CENELEC HD 629.1 standards and is tested for AC withstand and partial discharge prior to shipping. Installation instructions and part number ordering information is also provided based on cable type, size, and insulation diameter.
This document provides information on SOCOMEC's ATyS 3 motorised changeover switches, including:
1. The ATyS 3 products are 3 and 4-pole remotely controlled switches that provide switching, source inversion, or changeover of two low voltage power circuits as well as safety isolation.
2. The document lists specifications, characteristics, references, accessories, and dimensions for ATyS 3 switches ranging from 125A to 1800A.
3. Accessories include terminal shrouds, auxiliary contacts, control voltage transformers, and padlocking options that can be factory fitted.
This document provides specifications for cable reeling drums used in steel plants. It outlines three types of cable reeling drums: 1) drums driven by rope drums through chain sprockets or gearboxes, 2) spring loaded reeling drums, and 3) drums driven by torque motors. It specifies design and construction requirements for components like slipring assemblies, drums, cassettes, and limit switches. Site conditions and material standards are also defined. The document aims to achieve standardization of cable reeling drums across steel plants.
The document discusses requirements for flexible cords and cables, receptacles, lighting systems operating at low voltages, appliances, and storage batteries. Some key points include:
- Flexible cords and cables must conform to descriptions in Table 400.4 and can only be used for certain applications.
- Receptacles must be securely mounted and tamper-resistant receptacles are required in certain areas like dwellings and child care facilities.
- Lighting systems operating at 30V or less must use isolating power supplies and listed low-voltage luminaires.
- Appliances like vending machines and inflators must be protected by GFCIs.
- Storage batteries must have sufficient ventilation and space, and terminals cannot
This document lists approvals for various electrical apparatus and cables for use in hazardous areas of oil mines. It provides details of 14 equipment approved by Flexpro Electricals Pvt Ltd such as hand lamp fittings, well glass fittings, control gear boxes, junction boxes, switches, and portable transformers. The approvals specify the equipment type number, construction material, electrical ratings, and expiry dates of the approval, which is valid for use in Zone 1 and Zone 2 hazardous areas of oil mines.
This document provides a list of materials and specifications for an electrical installation project. It includes 14 items with descriptions of materials like service entrance caps, feeder conduit, conductors, emergency circuit breakers, distribution panels, switches and more. Specifications are provided for proper installation and sizing according to standards like the Philippine Electrical Code (PEC) 2017. Total estimated cost is provided for each item and annexes provide additional details for specifications referenced.
This document provides guidance on calculating loading for devices connected to an MX Digital Loop installation. It specifies the loading parameters for each device in terms of DC and AC units. The maximum number of devices per loop is 250. The document provides limits for DC and AC loading and guidance on using short-circuit isolators. It also provides a table of loading values for each device type to allow calculation of total loop loading.
The document discusses specifications for the 158LR separable connector, which meets CENELEC HD 629.1 requirements for up to 24 kV and 250 A. It has an insulating EPDM layer between conductive inner and outer jackets. The connector is designed to connect polymeric cable to equipment safely. Ordering information is provided for selecting the proper connector kit based on cable type, size, and voltage rating.
The document provides information on the 152SR straight connector for connecting polymeric insulated cable to equipment up to 24 kV and 250 A. The connector consists of a conductive EPDM insert, jacket and insulating layer, along with interface, conductor connector, and test point. It meets CENELEC HD 629.1 standards and is tested for AC withstand and partial discharge prior to shipping. Installation instructions and part number ordering information is also provided based on cable type, size, and insulation diameter.
This document provides information on SOCOMEC's ATyS 3 motorised changeover switches, including:
1. The ATyS 3 products are 3 and 4-pole remotely controlled switches that provide switching, source inversion, or changeover of two low voltage power circuits as well as safety isolation.
2. The document lists specifications, characteristics, references, accessories, and dimensions for ATyS 3 switches ranging from 125A to 1800A.
3. Accessories include terminal shrouds, auxiliary contacts, control voltage transformers, and padlocking options that can be factory fitted.
This document provides specifications for cable reeling drums used in steel plants. It outlines three types of cable reeling drums: 1) drums driven by rope drums through chain sprockets or gearboxes, 2) spring loaded reeling drums, and 3) drums driven by torque motors. It specifies design and construction requirements for components like slipring assemblies, drums, cassettes, and limit switches. Site conditions and material standards are also defined. The document aims to achieve standardization of cable reeling drums across steel plants.
Ever wonder if the emerging technologies you hear about will affect nonprofits? Chances are they already have. Let’s recap 2015 breakthroughs and look ahead to learn how things such as wearables, artificial intelligence, drones and 3D printing may directly affect your organization. The Powertools for Nonprofits conference provides an educational forum for nonprofit professionals, volunteers and board members, offering ideas on how to leverage resources, strengthen organizational effectiveness and improve the quality of life for all.
This document outlines a plan to perform a denial-of-service (DoS) attack against the website "Bloggingtheboys.com" in retaliation for the site's Dallas Cowboys fan base. It describes downloading tools to hide the attacker's IP address, scan open ports on the target site, and perform the DoS attack. The goal is to crash the site and disrupt access for Cowboys fans, if only temporarily. References are provided for the various hacking tools and techniques discussed.
The Synthesis Program offers an affordable online ordering solution for small restaurants with customizable package options. It allows restaurants to choose solutions that meet their unique needs at industry low transaction costs, starting at $0.21 per order. Synthesis emphasizes each restaurant's brand identity by redirecting customers to the restaurant's website rather than acting as a central platform, gaining more brand loyalty. It aims to reconnect restaurants with customers through a full-scale marketing initiative at lower monthly costs than competitors.
This document is a curriculum vitae for Mashapa Thabo that includes personal details, educational qualifications, and work experience. It summarizes that Thabo graduated high school in 2010 and obtained a diploma in information technology in 2012 from PC Training and Business College. He then worked as a junior IT technician from 2013-2014 at Edusa College where his duties included technical support, repairs, and network administration. Currently, he works as a sales executive at MTNSP Pedipalp Trading Store where he assists customers with smartphone and laptop set up and use. References are provided from his previous employers.
Wk 7 Case Study Summary Paper_ISSC331_IntindoloJohn Intindolo
- Premier College received notice of a lawsuit and issued a litigation hold and document retention policy to employees to preserve any potentially relevant electronic documents and ensure compliance.
- The document retention policy detailed what types of documents and electronic data must be preserved, including emails, documents, databases, and computer logs. It applied to data on workstations, servers, phones, backups, and removable devices.
- Employees were instructed to suspend deleting or altering any relevant electronic materials and provided contact for questions to ensure all procedures were followed.
This document provides an overview of a business opportunity with a revenue sharing advertising company. It states that members can earn $1 per day per active ad pack by clicking a minimum of 10 ads daily, though actual earnings may vary. It describes how members can watch ads and get paid, buy advertising packs for $50-55, earn affiliate commissions of 10% for referrals, and attend informational seminars. The document is not a guarantee of income and presents figures for illustration only.
The document discusses post-election cooperation in parliament following Canadian elections. It suggests that minority or coalition governments may have advantages over majority governments as they emphasize cooperation between parties rather than polarization. Historically, important Canadian policies like healthcare and pension plans emerged from cross-party cooperation. The effectiveness of minority or coalition governments depends on leaders acting in a spirit of cooperation for the common good.
O documento descreve o novo alto-falante sem fio Samsung Wireless Audio 360, destacando suas características principais de áudio 360, design compacto e funcionalidade de aplicativo multi-room que permite controlar vários dispositivos de áudio da casa pelo smartphone.
Synergy Trucking Ltd. is a global logistics provider that operates through a network of branch offices in North America. They specialize in over-the-road, intermodal, and expedited shipping services between Canada and the USA. Synergy ensures fast and safe delivery to thousands of destinations using teamed drivers. They are a customs-bonded carrier with expertise in cross-border shipping. The company has yards in BC, AB, CA, and ON, and their branch network provides local market knowledge and relationships.
This document discusses various methods and approaches to language education and second language pedagogy. It begins with an introduction describing language education and its importance in an increasingly globalized world. It then provides an overview of different structural, functional, and interactive methods used historically and currently, such as the grammar-translation method, audio-lingual method, direct method, and communicative language teaching. The document concludes that while some methods have fallen out of use, others remain widely practiced, and evaluating various approaches can provide useful insights for language instruction.
The document discusses the mastery approach to teaching mathematics commonly followed in high-performing East and Southeast Asian countries. It outlines key principles of the mastery approach, including high expectations for all students, keeping most students progressing at the same pace, and using precise questioning and regular assessment to identify and support students needing intervention. The 2014 UK national curriculum reflects this mastery approach, aiming for most students to achieve mastery of mathematics. Teachers require in-depth subject and pedagogical knowledge to effectively implement this approach.
The document discusses three main topics: social justice and digital divides, trust issues related to technology, and metaphors related to the Internet of Things (IoT). For each topic, it identifies an ethical issue, provides an example, and notes a related policy objective. The document includes references for further information.
This document discusses building a SaaS startup using the Django and Angular frameworks. It describes the architecture as having a client-side web interface built with Angular that communicates with the backend built using Django. The backend includes components like a task queue using Celery, app monitoring with New Relic, code versioning with BitBucket, and error tracking with Sentry. The document advocates this technical stack can be used to develop a complete product by a single developer within 3 months.
This document provides a summary of Robin L. O'Brien's qualifications and experience. It outlines their background in accounting, finance, and project management. Their most recent role was as Manager of Project Finance at Beacon Power, LLC, where they were responsible for developing budgets, analyzing finances, and ensuring compliance for a portfolio of energy storage projects.
2009 Sfpe Technical Changes To The Part 4 Fire Codeandrewwcwong
- The document summarizes technical changes made to Division B, Part 4 of the Ontario Fire Code regarding storage and handling of flammable and combustible liquids. Key changes include new requirements for spill containment, drainage systems, ventilation systems, underground storage tanks, and documentation of piping systems.
- It also discusses the application of alternative solutions and how objectives and functional statements from the fire code supplement can be used to evaluate alternative designs that achieve an equivalent level of performance. Proposals for alternative solutions must include detailed engineering justification.
This document summarizes ventilation requirements for occupied spaces in buildings. It requires that all occupied spaces be ventilated either through natural means according to Section 402 or mechanical means according to Section 403. Section 403 specifies minimum outdoor air ventilation rates for various occupancies based on estimated maximum occupant loads. It also restricts recirculation of air from certain spaces and allows transfer air to be used as makeup air. Requirements for outdoor air intake and exhaust openings include minimum distances from contaminant sources and protection with screens or louvers.
This document provides an overview of electrical area classification training. It will cover introduction to area classification terminology and standards, identifying electrical equipment for different hazardous areas, and notable area classification standards. The training will also discuss National Electric Code articles related to hazardous locations, class locations for gases, dusts and fibers, division 1 and 2 locations, and groups A-D for gases and E-G for dusts which indicate the degree of hazard.
Ever wonder if the emerging technologies you hear about will affect nonprofits? Chances are they already have. Let’s recap 2015 breakthroughs and look ahead to learn how things such as wearables, artificial intelligence, drones and 3D printing may directly affect your organization. The Powertools for Nonprofits conference provides an educational forum for nonprofit professionals, volunteers and board members, offering ideas on how to leverage resources, strengthen organizational effectiveness and improve the quality of life for all.
This document outlines a plan to perform a denial-of-service (DoS) attack against the website "Bloggingtheboys.com" in retaliation for the site's Dallas Cowboys fan base. It describes downloading tools to hide the attacker's IP address, scan open ports on the target site, and perform the DoS attack. The goal is to crash the site and disrupt access for Cowboys fans, if only temporarily. References are provided for the various hacking tools and techniques discussed.
The Synthesis Program offers an affordable online ordering solution for small restaurants with customizable package options. It allows restaurants to choose solutions that meet their unique needs at industry low transaction costs, starting at $0.21 per order. Synthesis emphasizes each restaurant's brand identity by redirecting customers to the restaurant's website rather than acting as a central platform, gaining more brand loyalty. It aims to reconnect restaurants with customers through a full-scale marketing initiative at lower monthly costs than competitors.
This document is a curriculum vitae for Mashapa Thabo that includes personal details, educational qualifications, and work experience. It summarizes that Thabo graduated high school in 2010 and obtained a diploma in information technology in 2012 from PC Training and Business College. He then worked as a junior IT technician from 2013-2014 at Edusa College where his duties included technical support, repairs, and network administration. Currently, he works as a sales executive at MTNSP Pedipalp Trading Store where he assists customers with smartphone and laptop set up and use. References are provided from his previous employers.
Wk 7 Case Study Summary Paper_ISSC331_IntindoloJohn Intindolo
- Premier College received notice of a lawsuit and issued a litigation hold and document retention policy to employees to preserve any potentially relevant electronic documents and ensure compliance.
- The document retention policy detailed what types of documents and electronic data must be preserved, including emails, documents, databases, and computer logs. It applied to data on workstations, servers, phones, backups, and removable devices.
- Employees were instructed to suspend deleting or altering any relevant electronic materials and provided contact for questions to ensure all procedures were followed.
This document provides an overview of a business opportunity with a revenue sharing advertising company. It states that members can earn $1 per day per active ad pack by clicking a minimum of 10 ads daily, though actual earnings may vary. It describes how members can watch ads and get paid, buy advertising packs for $50-55, earn affiliate commissions of 10% for referrals, and attend informational seminars. The document is not a guarantee of income and presents figures for illustration only.
The document discusses post-election cooperation in parliament following Canadian elections. It suggests that minority or coalition governments may have advantages over majority governments as they emphasize cooperation between parties rather than polarization. Historically, important Canadian policies like healthcare and pension plans emerged from cross-party cooperation. The effectiveness of minority or coalition governments depends on leaders acting in a spirit of cooperation for the common good.
O documento descreve o novo alto-falante sem fio Samsung Wireless Audio 360, destacando suas características principais de áudio 360, design compacto e funcionalidade de aplicativo multi-room que permite controlar vários dispositivos de áudio da casa pelo smartphone.
Synergy Trucking Ltd. is a global logistics provider that operates through a network of branch offices in North America. They specialize in over-the-road, intermodal, and expedited shipping services between Canada and the USA. Synergy ensures fast and safe delivery to thousands of destinations using teamed drivers. They are a customs-bonded carrier with expertise in cross-border shipping. The company has yards in BC, AB, CA, and ON, and their branch network provides local market knowledge and relationships.
This document discusses various methods and approaches to language education and second language pedagogy. It begins with an introduction describing language education and its importance in an increasingly globalized world. It then provides an overview of different structural, functional, and interactive methods used historically and currently, such as the grammar-translation method, audio-lingual method, direct method, and communicative language teaching. The document concludes that while some methods have fallen out of use, others remain widely practiced, and evaluating various approaches can provide useful insights for language instruction.
The document discusses the mastery approach to teaching mathematics commonly followed in high-performing East and Southeast Asian countries. It outlines key principles of the mastery approach, including high expectations for all students, keeping most students progressing at the same pace, and using precise questioning and regular assessment to identify and support students needing intervention. The 2014 UK national curriculum reflects this mastery approach, aiming for most students to achieve mastery of mathematics. Teachers require in-depth subject and pedagogical knowledge to effectively implement this approach.
The document discusses three main topics: social justice and digital divides, trust issues related to technology, and metaphors related to the Internet of Things (IoT). For each topic, it identifies an ethical issue, provides an example, and notes a related policy objective. The document includes references for further information.
This document discusses building a SaaS startup using the Django and Angular frameworks. It describes the architecture as having a client-side web interface built with Angular that communicates with the backend built using Django. The backend includes components like a task queue using Celery, app monitoring with New Relic, code versioning with BitBucket, and error tracking with Sentry. The document advocates this technical stack can be used to develop a complete product by a single developer within 3 months.
This document provides a summary of Robin L. O'Brien's qualifications and experience. It outlines their background in accounting, finance, and project management. Their most recent role was as Manager of Project Finance at Beacon Power, LLC, where they were responsible for developing budgets, analyzing finances, and ensuring compliance for a portfolio of energy storage projects.
2009 Sfpe Technical Changes To The Part 4 Fire Codeandrewwcwong
- The document summarizes technical changes made to Division B, Part 4 of the Ontario Fire Code regarding storage and handling of flammable and combustible liquids. Key changes include new requirements for spill containment, drainage systems, ventilation systems, underground storage tanks, and documentation of piping systems.
- It also discusses the application of alternative solutions and how objectives and functional statements from the fire code supplement can be used to evaluate alternative designs that achieve an equivalent level of performance. Proposals for alternative solutions must include detailed engineering justification.
This document summarizes ventilation requirements for occupied spaces in buildings. It requires that all occupied spaces be ventilated either through natural means according to Section 402 or mechanical means according to Section 403. Section 403 specifies minimum outdoor air ventilation rates for various occupancies based on estimated maximum occupant loads. It also restricts recirculation of air from certain spaces and allows transfer air to be used as makeup air. Requirements for outdoor air intake and exhaust openings include minimum distances from contaminant sources and protection with screens or louvers.
This document provides an overview of electrical area classification training. It will cover introduction to area classification terminology and standards, identifying electrical equipment for different hazardous areas, and notable area classification standards. The training will also discuss National Electric Code articles related to hazardous locations, class locations for gases, dusts and fibers, division 1 and 2 locations, and groups A-D for gases and E-G for dusts which indicate the degree of hazard.
This document summarizes the National Electrical Code (NEC) requirements for various emergency, standby, and remote control power systems. It defines key terms like automatic load control relays and multimode inverters. It specifies that emergency systems must have overcurrent protection and selective coordination. Standby systems also require selective coordination. Outdoor generator sets and portable generators below 15 kW only need disconnecting means if conductors pass into a building. Wiring methods and cable types permitted in different areas like risers, cable trays, and industrial establishments are also defined.
This document outlines requirements for electrical facilities in housing and small buildings. It covers general requirements including conforming to electrical safety regulations. It requires electrical facilities be provided where electrical services are available. Equipment must not be located in public areas without precautions. Recessed lighting fixtures must be designed for insulated ceilings. Wiring and cables must meet certain flame spread and smoke development standards. It also outlines specific requirements for lighting outlets in various areas like entrances, dwelling units, stairways, basements, storage rooms, garages and public areas. Emergency lighting requirements are also referenced.
The document discusses requirements for various types of wiring methods and raceways. It covers corrosion protection for ferrous metal equipment, acceptable wiring methods for spaces used for environmental air like plenums, raceway installation in wet locations above grade, construction requirements for rigid metal conduit, couplings and connectors for liquidtight flexible metal conduit, grounding requirements for liquidtight flexible nonmetallic conduit, and marking requirements for surface nonmetallic raceways.
The document provides guidance on external corrosion control for buried or submerged pipelines, specifically regarding electrical isolation. It states that pipelines must be electrically isolated from other underground structures unless they are interconnected and cathodically protected as a single unit. Insulating devices can be installed where needed to facilitate corrosion control. Pipelines must also be isolated from metallic casings, with some exceptions. Inspection and testing is needed to ensure adequate isolation. Precautions must be taken if insulating devices are installed in areas with combustible atmospheres. Pipelines near electrical transmission towers also require protection from fault currents or lightning.
The document provides guidance on external corrosion control for buried or submerged pipelines, specifically regarding electrical isolation. It states that pipelines must be electrically isolated from other underground structures unless they are interconnected and cathodically protected as a single unit. Insulating devices can be installed where needed to facilitate corrosion control. Pipelines must also be isolated from metallic casings, with some exceptions. Inspection and testing is needed to ensure adequate isolation. Precautions must be taken if insulating devices are installed in areas with combustible atmospheres. Pipelines near electrical transmission towers also require protection from fault currents or lightning.
This document discusses fire safety standards and regulations for metro rail systems. It provides information on various international standards like EN 45545, NFPA 130, and standards from countries like the UK, Germany, and France. It explains concepts like operational categories, hazard levels, fire resistance of materials, requirements for electrical equipment, fire detection and suppression systems, and trends in metro design for improved safety like emergency evacuation and ventilation. The document emphasizes the importance of preventing fires, limiting their spread, minimizing harm through proper material selection, and controlling fires using detection and suppression.
This document provides specifications for renovating and upgrading two dust extraction systems. Key points include:
- The systems will include bag filters, cyclones, centrifugal fans, ducting, and other components to collect dust from machinery and exhaust clean air.
- The bag filters must be capable of handling 20,000 cubic meters per hour and have components like filter bags, manifolds, and pulse valves.
- The ducting design must meet standards for materials, supports, and velocities to efficiently convey dust to the filtration equipment.
- The upgraded systems must limit worker exposure to respirable dust and ensure stack emissions do not exceed regulatory limits.
The document discusses hazardous areas and explosion-proof equipment. It defines hazardous areas as places where potentially explosive atmospheres may occur due to gases, vapors, mists or combustible dusts. It classifies hazardous areas into zones based on the likelihood and duration of an explosive atmosphere. The document also describes the various types of protection for electrical equipment used in explosive atmospheres, including flameproof enclosures, increased safety, intrinsic safety, encapsulation, and others. It provides examples of how ATEX approved equipment is identified through markings.
This document outlines requirements for fuel-oil piping and storage systems in New York City. It covers general provisions, material standards, joints/connections, piping supports, and fuel-oil system installation. Key points include:
- Systems must comply with chapter requirements and NFPA 31. Storage over 1,100 gallons also requires compliance with NY environmental regulations.
- Appliances must be designed for the type of fuel connected. Conversions require approval.
- Piping material standards include brass, copper, steel, and listed nonmetallic pipe. Joints must be approved for the application.
- Installation must include provisions for expansion/contraction, protection of piping/equipment, and requirements for supply/
2011 12-33kv tech.spec for v c b type- m2-c1-revisedBasudev patra
This document provides the technical specifications for 33kV outdoor type vacuum circuit breakers. Key details include:
- Scope covers design, manufacturing, assembly and testing of 33kV, 1250A, 25kA circuit breakers.
- Circuit breakers must meet Indian and international standards. They will be installed in West Bengal with ambient temperatures up to 50°C.
- Design criteria includes interrupting fault levels of 20kA, continuous current rating of 1250A, and operating duty of 0-0.3 sec-CO-3 min-CO.
This document outlines requirements for business occupancies. It discusses classification of occupancy and hazard contents, exit details like types of exits permitted and capacity requirements, protection requirements like vertical opening enclosure and interior finishes, and fire protection systems like sprinklers, alarms and hazard separation. It provides specific requirements for means of egress, travel distances, number and arrangement of exits, signage and evacuation plans that must be followed for business occupancy buildings.
Hazardous area classification and control of ignition sourceseldhoev
This document discusses hazardous area classification and control of ignition sources. It defines hazardous areas as any place where an explosive atmosphere may occur, and outlines the process to classify these areas into zones based on the likelihood and duration of an explosive atmosphere. The document provides guidance on identifying potential ignition sources and selecting appropriate equipment for use in the classified zones to ensure safety. It emphasizes the need to control ignition sources through design measures, work procedures, and proper equipment selection according to the zone classification.
This document provides rules and guidelines for high velocity water spray systems used to extinguish fires involving liquids with flash points of 650°C or higher. It focuses on protections for transformers, discussing general layout and design, including requirements for projectors, detectors, piping, and water supplies. Detailed information is required to be submitted for approval of individual transformer protection systems, including dimensions, equipment locations, and sprinkler/piping details. Medium velocity spray systems used for lower flash point liquids are also addressed.
This document discusses hazardous areas and explosion-proof solenoids. It begins with some history on how hazardous areas have been classified into zones based on the level of explosion risk from gas or dust atmospheres. It then defines hazardous places as areas where a potentially explosive atmosphere may occur. The document outlines the gas and dust groups, as well as the zones and categories used to classify hazardous areas based on the likelihood of an explosive atmosphere. It also discusses equipment protection levels and provides examples of how ATEX, IEC 60079, and IEC 61241 approved equipment is identified.
The document is a technical approval certificate from the British Board of Agrément for the Terrabound resin bound aggregate surfacing system. It provides details on the product's certification, key factors assessed including strength and stability, surface characteristics, rainwater drainage and durability. It also addresses use, practicability of installation and resistance to permanent deformation. The certificate indicates the system is suitable for use in domestic driveways, patios and lightly trafficked areas when installed and maintained as specified.
General Specification for Thermofoil Heater, All-Polyimide, Space ApplicationsBelilove Company-Engineers
Purpose. This specification establishes the requirements for thermofoil heaters of an all- polyimide (adhesive-less) construction for high reliability space applications. It defines the process, test verification, and inspections required by product used in space flight applications.
This document provides guidelines for cleaning, descaling, and passivating stainless steel parts, equipment, and systems. It discusses:
1) The scope, which includes recommendations for removing surface contaminants that could impair corrosion resistance or cause contamination.
2) Design considerations to facilitate effective cleaning by minimizing crevices and allowing for drainage, ventilation, and inspection.
3) Precleaning to remove gross contamination before high-temperature processes or final cleaning using methods like degreasing or alkaline cleaners.
4) Descaling to remove heavy oxide films from hot-forming, heat treatment, or welding using methods like mechanical removal or chemical dissolution in acid solutions.
Fire alarm 3-f-single_and_multiple-station_alarms_and_household_fire_alarm_sy...grantlerc
This document summarizes NFPA 72 chapter 29 regarding single and multiple station alarms and household fire alarm systems. It outlines requirements for detection, notification, power supplies, equipment performance, installation, maintenance and testing. Key points include smoke alarms being required in all sleeping rooms, outside sleeping areas, and on every level. Alarms must be interconnected to sound together when one activates. Primary power sources must be monitored and provide trouble signals. Installation locations have restrictions near cooking appliances, bathrooms and HVAC supplies.
Fire alarm 3-e-public_emergency_alarm_reporting_systemsgrantlerc
This document discusses Chapter 27 of NFPA 72, which covers public emergency alarm reporting systems. It outlines the general requirements and fundamentals, including management and maintenance, communication methods, alarm processing equipment, and alarm boxes. Wireless boxes must provide at least three identifiable functions to the communications center: test, tamper, and fire. The primary power source for wireless boxes can include a utility distribution system, solar photovoltaic power, user power, or an internal battery.
Fire alarm 3-d-supervising_station_alarm_systemgrantlerc
This document discusses the requirements for supervising station alarm systems in Chapter 26 of NFPA 72. It provides an overview of the requirements for central station alarm systems, proprietary supervising station systems, and remote supervising station alarm systems. The key requirements addressed include equipment and facility standards, operator qualifications and duties, signal handling and retransmission procedures, testing and inspection standards, and record keeping requirements.
Fire alarm 3-b-protected_premises_fire_alarm_systemgrantlerc
This document summarizes NFPA 72 Chapter 23 on protected premises fire alarm systems. It outlines the requirements for system features, performance, circuits, control units, initiating devices, and notification appliances. Key points include classifications for initiating device circuits, signaling line circuits, and notification appliance circuits based on their performance during faults. It also specifies requirements for actuation time, positive alarm sequence operation, annunciation of signals, and sharing of components between fire and non-fire systems.
Fire alarm 3-a-emergency_control_functionsgrantlerc
This document summarizes NFPA 72 Chapter 21 on emergency control functions and interfaces that can be connected to a fire alarm system. It discusses requirements for functions like elevator recall, shutdown, HVAC control, door release, and exit marking notification. Key requirements include that initiating devices used for elevator recall must connect to the building fire alarm system, lobby smoke detectors must be within 21 feet of elevator doors, and electrically locked doors must release upon fire alarm and remain unlocked until reset.
The document summarizes key sections from NFPA 72 regarding fire alarm systems. It outlines chapters that cover fundamentals, circuits, inspection/testing, initiating devices, and notification devices. For chapter 10 on fundamentals, it provides details on signal priority, distinctive signals for different alarm types, equipment performance requirements, annunciation zoning, integrity monitoring of components, and documentation requirements. Installation and equipment must comply with NFPA 70 and 72 standards unless otherwise indicated.
This document provides an overview and summary of key chapters and sections from NFPA 72 and NFPA 110 regarding fire alarm systems. It discusses fundamentals such as equipment qualifications, personnel qualifications for system designers, installers and maintenance, power supplies including primary and secondary sources, storage batteries, and engine-driven generators. Specific requirements are referenced from NFPA publications regarding circuits, equipment listing, power source configuration, capacity, location, and charging of batteries and generator installation.
This document discusses various types of initiating devices as defined in NFPA 72 Chapter 17 including: manually actuated alarm initiating devices (17.14), fire extinguisher monitoring devices (17.15), and supervisory signal initiating devices (17.16). Supervisory signal initiating devices provide signals for conditions involving control valves, pressure, water levels, temperatures of water storage containers, and room temperatures. Specific requirements are defined for the different device types and conditions they monitor.
This document discusses various types of initiating devices for fire alarm systems as outlined in NFPA 72 Chapter 17, including radiant energy fire detectors, combination detectors, gas detectors, other fire detectors, sprinkler waterflow alarm devices, and detectors for other automatic extinguishing systems. It provides requirements for listing, installation, location, and operation of these different initiating device types.
This document discusses standards for installing radiant energy-sensing fire detectors. It covers considerations for detector selection and spacing based on fire characteristics and the environment. Detector location and spacing must account for factors like fire size, fuel type, detector sensitivity and field of view, atmosphere, and response time needed. The detector must have an unobstructed field of view and be protected and maintained per its listing.
This document outlines requirements for smoke-sensing fire detectors as specified in NFPA 72 Chapter 17. It addresses general requirements, sensitivity, location and spacing, considerations for HVAC systems, special applications like high-rack storage and high air movement areas, and the use of video image smoke detection systems. Performance-based and prescriptive design approaches are both addressed.
This document discusses heat-sensing fire detectors in accordance with NFPA 72 Chapter 17. It covers requirements for installation, temperature classification, color coding, location, spacing for different ceiling types including smooth ceilings, solid joist construction, beam construction, sloping ceilings, and high ceilings. Detectors must be installed in all areas required by codes or the authority having jurisdiction.
This document outlines an agenda for a course on fire alarm systems. It discusses initiating devices and protected premises fire alarm systems. The document reviews NFPA 72 chapter 17 which covers performance, selection, use and location of detectors. It provides requirements for smoke and heat detectors including total coverage, partial coverage, and non-required coverage. General requirements are also outlined such as not installing devices in inaccessible areas and supporting them independently of their circuit.
Fire basics 1-4-risers_thru_power_supplies_08grantlerc
Fire alarm systems are installed to detect and notify people of emergencies to allow safe evacuation. NFPA 72 provides standards for fire alarm system components, functions, and performance. It classifies systems and defines key terms. Fire alarm systems have initiating devices, notification appliances, a control panel, and they transmit signals to a supervising station in some cases. Systems must be designed according to occupancy requirements and approved by the AHJ. They require both primary and secondary power supplies, and the secondary battery must be capable of powering the system for 24 hours plus additional time.
The document discusses fire alarm system fundamentals and requirements based on NFPA 70 and NFPA 72 standards. Key points include requirements for initiating devices to be compatible with listed control units, emergency functions not interfering with alarm operations, alarm activation within 10 seconds of detection, and zoning, annunciation, monitoring, and limitations of fire alarm systems and components.
This document provides an overview of fire alarm system fundamentals and electrical requirements according to NFPA 70 Article 760. It discusses why fire alarm systems are installed, their components and classifications. NFPA 70 Article 760 divides fire alarm systems into non-power limited and power limited circuits. It outlines the power sources, wiring methods, and installation requirements for both non-power limited and power limited fire alarm circuits according to the National Electrical Code.
This document provides an overview of fire alarm system fundamentals based on current NFPA codes. It defines key components of fire alarm systems including the fire alarm control panel, initiating devices, notification appliances, transmitters and receivers, and control functions. It also outlines the classification of fire alarm systems, why they are installed, and what topics will be covered, including a review of NFPA 72.
Fiber optic cables, connectors, and splices can be tested in three main ways: continuity testing using a visible light source, insertion loss testing to simulate system use, and OTDR testing which uses backscatter to locate faults. Continuity testing uses a fiber tracer or visual fault locator with an LED or laser to check for breaks. Insertion loss testing measures loss by comparing output levels with and without the cable under test. OTDR testing indirectly measures loss by analyzing backscattered light to create a display showing loss over distance.
There are two types of fiber optic splices: fusion and mechanical. Fusion splicing permanently fuses two fibers together using an electrical arc welder for low loss and high reliability. Mechanical splices use alignment fixtures and epoxy or gel to connect fibers, having higher loss but also being cheaper. Proper cleaving of fibers is important for low loss splices and connectors, done using a cleaver to score and break the fiber smoothly. Sources of loss include end gaps, dirt, numerical aperture and core diameter mismatches between spliced fibers.
Most fiber optic connectors work by aligning the two fiber ends and securing them in a way that is resistant to environmental factors. The most common method uses a cylindrical ferrule with a fiber-sized hole to secure the fiber with adhesive. Connector ferrules are often made of ceramic because it is environmentally stable and easy to polish. Proper termination involves stripping the fiber, applying adhesive to the ferrule, inserting and cleaving the fiber, and polishing the end to minimize back reflection.
Prediction of Electrical Energy Efficiency Using Information on Consumer's Ac...PriyankaKilaniya
Energy efficiency has been important since the latter part of the last century. The main object of this survey is to determine the energy efficiency knowledge among consumers. Two separate districts in Bangladesh are selected to conduct the survey on households and showrooms about the energy and seller also. The survey uses the data to find some regression equations from which it is easy to predict energy efficiency knowledge. The data is analyzed and calculated based on five important criteria. The initial target was to find some factors that help predict a person's energy efficiency knowledge. From the survey, it is found that the energy efficiency awareness among the people of our country is very low. Relationships between household energy use behaviors are estimated using a unique dataset of about 40 households and 20 showrooms in Bangladesh's Chapainawabganj and Bagerhat districts. Knowledge of energy consumption and energy efficiency technology options is found to be associated with household use of energy conservation practices. Household characteristics also influence household energy use behavior. Younger household cohorts are more likely to adopt energy-efficient technologies and energy conservation practices and place primary importance on energy saving for environmental reasons. Education also influences attitudes toward energy conservation in Bangladesh. Low-education households indicate they primarily save electricity for the environment while high-education households indicate they are motivated by environmental concerns.
Supermarket Management System Project Report.pdfKamal Acharya
Supermarket management is a stand-alone J2EE using Eclipse Juno program.
This project contains all the necessary required information about maintaining
the supermarket billing system.
The core idea of this project to minimize the paper work and centralize the
data. Here all the communication is taken in secure manner. That is, in this
application the information will be stored in client itself. For further security the
data base is stored in the back-end oracle and so no intruders can access it.
Levelised Cost of Hydrogen (LCOH) Calculator ManualMassimo Talia
The aim of this manual is to explain the
methodology behind the Levelized Cost of
Hydrogen (LCOH) calculator. Moreover, this
manual also demonstrates how the calculator
can be used for estimating the expenses associated with hydrogen production in Europe
using low-temperature electrolysis considering different sources of electricity
Applications of artificial Intelligence in Mechanical Engineering.pdfAtif Razi
Historically, mechanical engineering has relied heavily on human expertise and empirical methods to solve complex problems. With the introduction of computer-aided design (CAD) and finite element analysis (FEA), the field took its first steps towards digitization. These tools allowed engineers to simulate and analyze mechanical systems with greater accuracy and efficiency. However, the sheer volume of data generated by modern engineering systems and the increasing complexity of these systems have necessitated more advanced analytical tools, paving the way for AI.
AI offers the capability to process vast amounts of data, identify patterns, and make predictions with a level of speed and accuracy unattainable by traditional methods. This has profound implications for mechanical engineering, enabling more efficient design processes, predictive maintenance strategies, and optimized manufacturing operations. AI-driven tools can learn from historical data, adapt to new information, and continuously improve their performance, making them invaluable in tackling the multifaceted challenges of modern mechanical engineering.
Open Channel Flow: fluid flow with a free surfaceIndrajeet sahu
Open Channel Flow: This topic focuses on fluid flow with a free surface, such as in rivers, canals, and drainage ditches. Key concepts include the classification of flow types (steady vs. unsteady, uniform vs. non-uniform), hydraulic radius, flow resistance, Manning's equation, critical flow conditions, and energy and momentum principles. It also covers flow measurement techniques, gradually varied flow analysis, and the design of open channels. Understanding these principles is vital for effective water resource management and engineering applications.
Zener Diode and its V-I Characteristics and Applications
Nec and oesc-5
1. 500. 2 Definitions
Combustible Dust. Dust particles that are 500 microns
or smaller (material passing a U.S. No. 35 Standard Sieve
as defined in ASTM E 11-09, Standard Specification for Wire
Cloth and Sieves for Testing Purposes) and present a fire or
explosion hazard when dispersed and ignited in air.
Informational Note: See ASTM E 1226–12a, Standard Test
Method for Explosibility of Dust Clouds, or ISO 6184-1,
Explosion protection systems — Part 1: Determination of explosion
indices of combustible dusts in air, for procedures for
determining the explosibility of dusts.
2. Class 1 Locations
501.10 Wiring Methods
(A) Class I, Division 1.
(1) General. In Class I, Division 1 locations, the
wiring methods in (a) through ( e) shall be
permitted.
(e) Optical fiber cable Types OFNP, OFCP, OFNR,
OFCR, OFNG, OFCG, OFN, and OFC shall be
permitted to be installed in raceways in accordance
with 501.10(A). These optical fiber cables shall be
sealed in accordance with 501.15.
3. Class 1 Locations
501.10 Wiring Methods
(A) Class I, Division 1.
(2) Flexible Connections. Where necessary to
employ flexible connections, as at motor
terminals, the following shall be permitted:
(1) Flexible fittings listed for the location, or
(2) Flexible cord in accordance with the
provisions of 501.140, terminated with cord
connectors listed for the location, or
4. Class 1 Locations
501.10 Wiring Methods
(A) Class I, Division 1.
(2) Flexible Connections – (cont.)
(3) In industrial establishments with restricted public
access, where the conditions of maintenance and
supervision ensure that only qualified persons service
the installation, for applications limited to 600 volts,
nominal, or less, and where protected from damage by
location or a suitable guard, listed Type TC-ER-HL
cable with an overall jacket and a separate equipment
grounding conductor(s) in accordance with 250.122
that is terminated with fittings listed for the location
5. Class 1 Locations
501.15 Sealing and Drainage
(C) Class I, Divisions 1 and 2.
(6) Conductor or Optical Fiber Fill. The
cross-sectional area of the conductors or optical
fiber tubes (metallic or nonmetallic) permitted in
a seal shall not exceed 25 percent of the cross-
sectional area of a rigid metal conduit of the
same trade size unless the seal is specifically
identified for a higher percentage of fill.
6. Class 1 Locations
501.30 Grounding and Bonding, Class I,
Divisions 1 and 2
Regardless of the voltage of the electrical system,
wiring and equipment in Class I, Division 1 and 2
locations shall be grounded as specified in Article
250 and in accordance with the requirements of
501.30(A) and (B).
7. Class II Locations
502.10 Wiring Methods
(A) Class II, Division 1.
(1) General. In Class II, Division 1 locations, the
wiring methods in (1) through (4) shall be permitted
(4) Optical fiber cables Types OFNP, OFCP, OFNR,
OFCR, OFNG, OFCG, OFN, and OFC shall be
permitted to be installed in raceways in accordance with
502.10(A). Optical fiber cables shall be sealed in
accordance with 502.15.d:
8. Class II Locations
502.30 Grounding and Bonding, Class II,
Divisions 1 and 2
Regardless of the voltage of the electrical system,
wiring and equipment in Class II, Division 1 and 2
locations shall be grounded as specified in Article
250 and in accordance with the requirements of
502.30(A) and (B).
9. Intrinsically Safe Systems
504.10 Equipment Installation
(C) Enclosures. General-purpose enclosures
shall be permitted for intrinsically safe apparatus
and associated apparatus unless otherwise
specified in the manufacturer’s documentation.
10. Motor Fuel Dispensing Facilities
514.3 Classification of Locations
(C) Motor Fuel Dispensing Stations in Boatyards
and Marinas.
(1) General. Electrical wiring and equipment located at
or serving motor fuel dispensing locations shall be
installed on the side of the wharf, pier, or dock
opposite from the liquid piping system.
Informational Note: For additional information, see
NFPA 303-2011, Fire Protection Standard for Marinas and
Boatyards, and NFPA 30A-2012, Motor Fuel Dispensing
Facilities and Repair Garages.
11. Motor Fuel Dispensing Facilities
514.3 Classification of Locations
(C) Motor Fuel Dispensing Stations in Boatyards
and Marinas – (cont.)
(2) Classification of Class I, Division 1 and 2 Areas.
The following criteria shall be used for the purposes of
applying Table 514.3(B)(1) and Table 514.3(B)(2) to
motor fuel dispensing equipment on floating or fixed
piers, wharfs, or docks.
12. Motor Fuel Dispensing Facilities
514.3 Classification of Locations
(D) Closed Construction. Where the construction of
floating docks, piers, or wharfs is closed so that there is
no space between the bottom of the dock, pier, or
wharf and the water, as in the case of concrete-enclosed
expanded foam or similar construction, and the
construction includes integral service boxes with supply
chases, the following shall apply:
13. Motor Fuel Dispensing Facilities
514.3 Classification of Locations
(1) The space above the surface of the floating dock,
pier, or wharf shall be a Class I, Division 2 location
with distances as specified in Table 514.3(B)(1)(1) for
dispenser and outdoor locations.
(2) Spaces below the surface of the floating dock, pier,
or wharf that have areas or enclosures, such as tubs,
voids, pits, vaults, boxes, depressions, fuel piping
chases, or similar spaces, where flammable liquid or
vapor can accumulate shall be a Class I, Division 1
location.
14. Motor Fuel Dispensing Facilities
514.3 Classification of Locations
Exception No. 1: Dock, pier, or wharf sections that do not support fuel
dispensers and abut, but are located 6.0 m (20 ft) or more from, dock
sections that support a fuel dispenser(s) shall be permitted to be Class I,
Division 2 locations where documented air space is provided between dock
sections to allow flammable liquids or vapors to dissipate without traveling to
such dock sections. The documentation shall comply with 500.4(A).
Exception No. 2: Dock, pier, or wharf sections that do not support fuel
dispensers and do not directly abut sections that support fuel dispensers shall
be permitted to be unclassified where documented air space is provided and
where flammable liquids or vapors cannot travel to such dock sections. The
documentation shall comply with 500.4(A).
15. Motor Fuel Dispensing Facilities
514.3 Classification of Locations
(E) Open Construction. Where the construction of piers,
wharfs, or docks is open, as in the case of decks built on
stringers supported by pilings, floats, pontoons, or similar
construct ion, the following shall apply:
(1) The area 450 mm (18 in.) above the surface of the dock, pier,
or wharf and extending 6.0 m (20 ft) horizontally in all directions
from the outside edge of the dispenser and down to the water
level shall be a Class 1, Division 2 location.
(2) Enclosures such as tubs, voids, pits, vaults, boxes,
depressions, piping chases, or similar spaces where flammable
liquids or vapors can accumulate within 6.0 m (20 ft) of the
dispenser shall be a Class I, Division 1 location.
16. ARTICLE 516 Spray Application, Dipping,
Coating, and Printing Processes Using
Flammable or Combustible Materials
516.2 Definitions
Flash-Off Area. An open or enclosed area after a spray
application process where vapors are released due to exposure to
ambient air or a heated atmosphere. [33:3.3.1.1]
Limited Finishing Workstation. An apparatus that is capable of
confining the vapors, mists, residues, dusts, or deposits that are
generated by a spray application process and that meets the
requirements of Section 14.3 of NFPA 33, Standard for Spray
Application Using Flammable or Combustible Materials, but
does not meet the requirements of a spray booth or spray room,
as herein defined. [33:3.3.15.1]
17. ARTICLE 516 Spray Application, Dipping,
Coating, and Printing Processes Using
Flammable or Combustible Materials
516.2 Definitions – (cont.)
Resin Application Area. Any area in which polyester resins or
gelcoats are spray applied. [33:3.3.1.2]
Spray Area. Any fully enclosed, partly enclosed, or unenclosed
area in which ignitible quantities of flammable or combustible
vapors, mists, residues, dusts, or deposits are present due to the
operation of spray processes, including (1) any area in the direct
path of a spray application process; (2) the interior of a spray
booth or spray room or limited finishing workstation, as herein
defined; (3) the interior of any exhaust plenum, eliminator
section, or scrubber section; (4) the interior of any exhaust duct
or exhaust stack leading from a spray application process;
18. ARTICLE 516 Spray Application, Dipping,
Coating, and Printing Processes Using
Flammable or Combustible Materials
516.2 Definitions – (cont.)
(5) the interior of any air recirculation filter house or
enclosure, including secondary recirculation particulate
filters; (6) any solvent concentrator (pollution
abatement) unit or solvent recovery (distillation) unit.
The following are not considered to be a part of the
spray area: (1) fresh air make-up units; (2) air supply
ducts and air supply plenums; (3) recirculation air
supply ducts downstream of secondary filters; (4)
exhaust ducts from solvent concentrateur (pollution
abattement) units. [33:3.3.2.3]
19. ARTICLE 516 Spray Application, Dipping,
Coating, and Printing Processes Using
Flammable or Combustible Materials
516.2 Definitions – (cont.)
Spray Area – (cont.)
(5) the interior of any air recirculation filter house or enclosure,
including secondary recirculation particulate filters; (6) any solvent
concentrator (pollution abatement) unit or solvent recovery
(distillation) unit. The following are not considered to be a part of
the spray area: (1) fresh air make-up units; (2) air supply ducts and
air supply plenums; (3) recirculation air supply ducts downstream of
secondary filters; (4) exhaust ducts from solvent concentrator
(pollution abatement) units. [33:3.3.2.3]
20. ARTICLE 516 Spray Application, Dipping,
Coating, and Printing Processes Using
Flammable or Combustible Materials
516.2 Definitions
Spray Booth. A power-ventilated enclosure for a spray
application operation or process that confines and
limits the escape of the material being sprayed,
including vapors, mists, dusts, and residues that are
produced by the spraying operation and conducts or
directs these materials to an exhaust system. [33:3.3.14]
21. ARTICLE 516 Spray Application, Dipping,
Coating, and Printing Processes Using
Flammable or Combustible Materials
516.2 Definitions
Spray Room. A power-ventilated fully enclosed room
used exclusively for open spraying of flammable or
combustible materials. A spray room is a purposefully
enclosed room built for spray/coating/dipping
applications provided with dedicated ventilation supply
and exhaust. Normally the room is configured to house
the item to be painted, providing reasonable access
around the item/process. Depending on the size of the
item being painted, such rooms may actually be the
entire building or the major portion thereof. [33:3.3.15]
22. ARTICLE 516 Spray Application, Dipping,
Coating, and Printing Processes Using
Flammable or Combustible Materials
516.2 Definitions
Unenclosed Spray Area. Any spray area that is
not confined by a limited finishing workstation,
spray booth, or spray room, as herein defined.
[33:3.3.2.3.2]
23. 516. 3 Classification of Locations
(A) Zone Classification of Locations.
(1) For the purposes of this article, the zone system of electrical
area classification shall be applied as follows:
a. The inside of open or closed containers or vessels shall be
considered a Class I, Zone 0 location.
b. A Class I, Division 1 location shall be permitted to be
alternatively classified as a Class I, Zone 1 location.
c. A Class I, Division 2 location shall be permitted to be
alternatively classified as a Class I, Zone 2 location.
d. A Class II, Division 1 location shall be permitted to be
alternatively classified as a Zone 21 location.
e. A Class II, Division 2 location shall be permitted to be
alternatively classified as a Zone 22 location. [33:6.2.2]
24. 516. 3 Classification of Locations
(cont.)
(2) For the purposes of electrical area classification, the
division system and the zone system shall not be
intermixed for any given source of release. [33:6.2.3]
(3) In instances of areas within the same facility classified
separately, Class I, Zone 2 locations shall be permitted to
abut, but not overlap, Class I, Division 2 locations. Class
I, Zone 0 or Zone 1 locations shall not abut Class I,
Division 1 or Division 2 locations. [33:6.2.4]
25. 516. 3 Classification of Locations
(cont.)
(4) Open flames, spark-producing equipment or
processes, and equipment whose exposed surfaces exceed
the autoignition temperature of the material being sprayed
shall not be located in a spray area or in any surrounding
area that is classified as Division 2, Zone 2, or Zone 22.
Exception: This requirement shall not apply to drying, curing, or
fusing apparatus. [33:6.2.5]
26. 516. 3 Classification of Locations
(cont.)
(5) Any utilization equipment or apparatus that is capable
of producing sparks or particles of hot metal and that is
located above or adjacent to either the spray area or the
surrounding Division 2, Zone 2, or Zone 22 areas shall be
of the totally enclosed type or shall be constructed to
prevent the escape of sparks or particles of hot metal.
[33:6.2.6]
27. Health Care Facilities
517.2 Definitions
Life Safety Branch. A system of feeders and branch
circuits supplying power for lighting, receptacles, and
equipment essential for life safety that is automatically
connected to alternate power sources by one or more
transfer switches during interruption of the normal
power source. [99:3.3.94]
28. Health Care Facilities
517.2 Definitions – (cont.)
Patient Care Space. Space within a health care facility wherein
patients are intended to be examined or treated.
Basic Care Space. Space in which failure of equipment or a system
is not likely t o cause injury to the patients or caregivers but may
cause patient discomfort.
General Care Space. Space in which failure of equipment or a
system is likely to cause minor injury to patients or caregivers.
Critical Care Space. Space in which failure of equipment or a
system is likely to cause major injury or death to patients or
caregivers.
29. Health Care Facilities
517.2 Definitions – (cont.)
Support Space. Space in which failure of equipment or a system is
not likely to have a physical impact on patients or caregivers.
Informational Note No. 1: The governing body of the facility
designates patient care space in accordance with the type of patient
care anticipated and with the definitions of the area classification.
Business offices, corridors, lounges, day rooms, dining rooms, or
similar areas typically are not classified as patient care space.
Informational Note No. 2: Basic care space is typically a location
where basic medical or dental care, treatment, or examinations are
performed. Examples include, but are not limited to, examination
or treatment rooms in clinics, medical and dental offices, nursing
homes, and limited care facilities.
30. Health Care Facilities
517.2 Definitions – (cont.)
Informational Note No. 3: General care space includes areas such as patient
bedrooms, examining rooms, treatment rooms, clinics, and similar areas
where the patient may come into contact with electromedical devices or
ordinary appliances such as a nurse call system, electric beds, examining
lamps, telephones, and entertainment devices.
Informational Note No. 4: Critical care space includes special care units,
intensive care units, coronary care units, angiography laboratories, cardiac
catheterization laboratories, delivery rooms, operating rooms, and similar
areas in which are patients are intended to be subjected to invasive procedures
and are connected to line-operated, electromedical devices.
Informational Note No. 5: Spaces where a procedure is performed that
subjects patients or staff to wet conditions are considered as wet procedure
areas. Wet conditions include standing fluids on the floor or drenching of the
work area. Routine housekeeping procedures and incidental spillage of liquids
do not define wet procedure areas. It is the responsibility of the governing
body of the health care facility to designate the wet procedure areas.
31. Health Care Facilities
517.2 Definitions – (cont.)
Patient Care Vicinity. A space, within a
location intended for the examination and
treatment of patients, extending 1.8 m (6 ft)
beyond the normal location of the patient bed,
chair, table, treadmill, or other device that
supports the patient during examination and
treatment and extending vertically to 2.3 m (7 ft
6 in.) above the floor. [99:3.3.139]
32. Health Care Facilities
517.2 Definitions – (cont.)
Wet Procedure Location. The area in a patient care
space where a procedure is performed that is normally
subject to wet conditions while patients are present,
including standing fluids on the floor or drenching of
the work area, where either such condition is intimate
to the patient or staff.
Informational Note: Routine housekeeping procedures
and incidental spillage of liquids do not define a wet
procedure location.
33. Further Information
Wet procedure locations may also include such areas as
hydrotherapy areas, dialysis laboratories, and certain
wet laboratories at the discretion of the governing body
of the facility. The definition excludes areas such as
lavatories or bathrooms within a health care facility. For
infection control purposes, many patient and treatment
areas have a sink for hand washing, which also is not a
wet procedure location.
34. Health Care Facilities
517.19(C) Operating Room Receptacles
(1) Minimum Number and Supply. Each operating
room shall be provided with a minimum of 36
receptacles, at least 12 of which shall be connected to
eit her of the following:
(1) The normal system branch circuit required in
517.19(A)
(2) A critical branch circuit supplied by a different
transfer switch than the other receptacles at the same
location
35. Health Care Facilities
517.19(C) Operating Room Receptacles
(2) Receptacle Requirements. The receptacles
required in (517.19)(C)(1) shall be permitted to be of
the single or duplex types or a combination of both. All
receptacles shall be listed hospital grade and so
identified. The grounding terminal of each receptacle
shall be connected to the reference grounding point by
means of an insulated copper equipment grounding
conductor.
37. 520.2 Definitions
Stage Equipment. Equipment at any location on the
premises integral to the stage production including, but
not limited to, equipment for lighting, audio, special
effects, rigging, motion control, projection, or video.
38. 520.2 Definitions – (cont.)
Stage Lighting Hoist. A motorized lifting
device that contains a mounting position for one or more
luminaires, with wiring devices for connection of
luminaires to branch
circuits, and integral flexible cables
to allow the luminaires
to travel over the
lifting range of the
hoist while energized.
39. 520.2 Definitions – (cont.)
Stage Switchboard. A switchboard, panelboard, or
rack containing dimmers or relays with associated
overcurrent protective devices, or overcurrent
protective devices alone, used primarily to feed stage
equipment.
40. II. Fixed Stage Switchboards
520.21 General
Fixed stage switchboards shall comply with 520.21(1) through
(4):
(1) Fixed stage switchboards shall be listed.
(2) Fixed stage switchboards shall be readily accessible but shall
not be required to be located on or adjacent to the stage.
Multiple fixed stage switchboards shall be permitted at different
locations.
(3) A fixed stage switchboard shall contain overcurrent
protective devices for all branch circuits supplied by that
switchboard.
(4) A fixed stage switchboard shall be permitted to supply both
stage and non-stage equipment.
41. III. Fixed Stage Equipment
Other Than Switchboards
520.40 Stage Lighting Hoists
Where a stage lighting hoist is listed as a complete
assembly and contains an integral cable-handling
system and cable to connect a moving wiring
device to a fixed junction box for connection to
permanent wiring, the extra-hard usage
requirement of 520.44(C)(1) shall not apply.
42. ARTICLE 640
Audio Signal Processing,
Amplification, and Reproduction
Equipment
640.1 Scope
(B) Not Covered. This article does not cover the
installation and wiring of fire and burglary alarm
signaling devices.
43. 680.22 Lighting, Receptacles, and Equipment
(B) Luminaires, Lighting Outlets, and
Ceiling-Suspended (Paddle) Fans.
(6) Low-Voltage Luminaires.
Listed low-voltage luminaires
not requiring grounding, not
exceeding the low-voltage
contact limit, and supplied by
listed transformers or power
supplies that comply with
680.23(A)(2) shall be permitted
to be located less than 1.5 m (5
ft) from the inside walls of the
pool.
44. 680.26 Equipotential Bonding
(C) Pool Water.
Where none of the bonded parts is in direct connection
with the pool water, the pool water shall be in direct
contact with an approved corrosion-resistant conductive
surface that exposes not less than 5800 mm2 (9 in.2) of
surface area to the pool water at all times. The conductive
surface shall be located where it is not exposed to physical
damage or dislodgement during usual pool activities, and
it shall be bonded in accordance with 680.26(B).
45. Solar Photovoltaic (PV ) Systems
690.2 Definitions
DC-to-DC Converter. A device installed in the PV
source circuit or PV output circuit that can provide an
output dc voltage and current at a higher or lower value
than the input dc voltage and current.
46. Solar Photovoltaic (PV ) Systems
690.2 Definitions
Direct-Current (dc)
Combiner. A device
used in the PV source
and PV output circuits
to combine two or
more dc circuit inputs
and provide one dc
circuit output.
47. Solar Photovoltaic (PV ) Systems
690.2 Definitions
Multimode Inverter.
Equipment having the
capabilities of both the
utility-interactive inverter
and the stand-alone
inverter.
48. IV. Wiring Methods
690.31 Methods Permitted
(B) Identification and Grouping. PV source circuits
and PV output circuits shall not be contained in the
same raceway, cable tray, cable, outlet box, junction
box, or similar fitting as conductors, feeders, branch
circuits of other non-PV systems, or inverter output
circuits, unless the conductors of the different systems
are separated by a partition. PV system conductors shall
be identified and grouped as required by 690.31(B)(1)
through (4). The means of identification shall be
permitted by separate color coding, marking tape,
tagging, or other approved means.
49. IV. Wiring Methods
690.31 Methods Permitted
(B) Identification and Grouping (cont.)
(1) PV Source Circuits. PV source circuits shall be
identified at all points of termination, connection, and
splices.
(2) PV Output and Inverter Circuits. The
conductors of PV output circuits and inverter input and
output circuits shall be identified at all points of
termination, connection, and splices.
50. IV. Wiring Methods
690.31 Methods Permitted
(B) Identification and Grouping (cont.)
(3) Conductors of Multiple Systems. Where the
conductors of more than one PV system occupy the
same junction box, raceway, or equipment, the
conductors of each system shall be identified at all
termination, connection, and splice points.
Exception: Where the identification of the conductors is evident by
spacing or arrangement, further identification shall not be required.
51. IV. Wiring Methods
690.31 Methods Permitted
(B) Identification and Grouping (cont.)
(4) Grouping. Where the conductors of more than one
PV system occupy the same junction box or raceway
with a removable cover(s), the ac and dc conductors of
each system shall be grouped separately by cable ties or
similar means at least once and shall then be grouped at
intervals not to exceed 1.8 m (6 ft).
Exception: The requirement for grouping shall not apply if the
circuit enters from a cable or raceway unique to the circuit that
makes the grouping obvious.