BLT 122
BUILDING TECHNOLOGY II
AR. RONNEL CARLOS T. RAMOS
Course Facilitator
UNIVERSITY OF NORTHERN PHILIPPINES
College of Architecture
COURSE OUTLINE
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
MODULE 01 – BASIC WORKING DRAWINGS AND
GRAPHICAL PRESENTATION TECHNIQUES
MODULE 02 – REFLECTED CEILING PLANS AND DETAILS
MODULE 03 – SCHEDULE OF DOORS AND WINDOWS
MODULE 04 – SCHEDULE OF FINISHES
MODULE 05 – KITCHEN AND T&B DETAILS
MODULE 06 – STAIR DETAILS
MODULE 07 – STRUCTURAL AND CIVIL WORK
DRAWINGS
MODULE 08 – PLUMBING AND SANITARY DRAWINGS
MODULE 09 – ELECTRICAL AND AUXILIARY DRAWINGS
MODULE 09
ELECTRICAL AND
AUXILIARY DRAWINGS
7.A. ELECTRICAL NOTES, LEGENDS & SYMBOLS,
ELECTRICAL WIRING, CONDUIT AND ACCESSORIES
7.B. ELECTRICAL, POWER AND AUXILIARY LAYOUTS
7.C. LOAD COMPUTATION AND SCHEDULE, SINGLE
LINE DIAGRAM AND RISER DIAGRAM
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
What is an ELECTRICAL PLAN?
It is a type of technical drawing that delivers visual
representation and describes circuits
and electrical systems. It consists of symbols and lines that
showcase the engineer's electrical design to its clients.
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
Also referred as “Electrical Drawing” or
“Wiring Diagram”.
Composed of Lighting and Power Layouts and other
electrical specifications.
What is an AUXILIARY PLAN?
These are components related with Security Systems,
Comfort Systems, Lighting Systems and Information
Systems witch are very important to help the main system
to perform according the specifications.
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
Provides supplementary or additional help and support to
the basic systems of a building
Composed of Electronic and Communications systems.
PABX – Private Automatic Branch Exchange
Also referred as “telephone system”, these are switchboards
that connect to several devices.
ELECTRICAL NOTES
REFERENCE:
PHILIPPINE ELECTRICAL CODE (PEC) Parts 1 &
2, 2017 Edition
• Based from the 2017 National Electrical
Code of USA. (NFPA 70, NEC)
• Regularly revised every three(3) years to
reflect the evolution of products, materials,
and installation techniques.
• The primary objective of the code is to
establish basic materials quality and electrical
works standards for the safe use of electricity
for light, heat, power, communications,
signaling and for other purposes.
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
LEGEND AND SYMBOLS
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
POWER SERVICE
ENTRANCE
Also referred to as “service drop”
It is where the wires connected to the load side
of the meter enter the house or building.
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
KILOWATT HOUR (Kwh)
METER
These are compact electronic monitoring devices
that measure the consumed energy flowing
through a circuit such as a standard 120V or
240V
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
ELECTRICAL PANELBOARD
Also called, “distribution board”, “breaker
panel” or “electric panel”.
It is a component of an electricity supply
system that divides an electrical power feed into
subsidiary circuits while providing a
protective fuse or circuit breaker for each circuit
in a common enclosure.
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
CIRCUIT BREAKER
It is an automatically operated electrical switch
designed to protect an electrical circuit from
damage caused by excess current from an
overload or short circuit. Its basic function is to
interrupt current flow after a fault is detected.
CIRCUIT HOMERUN
A home run is a wire that graphically represents
the wiring of a circuit to a central location that
acts as the distribution point for the power,
typically, a panel.
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
GROUND ROD /
GROUND CLAMP
Also known as grounding electrodes.
Used to connect the grounding system of
electrical systems to earth ground.
They are very good conductors of electricity and
allow any dangerous electricity to flow to
ground, taking the danger away from you and
the electrical panel.
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
PULL BOX FOR TELEPHONE
AND CATV
They are used along with conduit to simplify
wiring installation.
They provide a way to pull conductors at long
distances without placing excessive strain on
the wire or insulation.
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
SWITCHES
They are used to turn electrical current on or off for nearly any electrical device.
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
CONVENIENCE OUTLETS
A receptacle in a wall or baseboard for connection to lamps or other electrical appliances.
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
ELECTRICAL WIRING
1. THHN AND THWN
2. THW
3. TW
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
THERMOPLASTIC HIGH
HEAT-RESISTANT NYLON COATED
(THHN) &
THERMOPLASTIC
WATER-RESISTANT NYLON COATED
(THWN)
Suitable for wet or dry locations at temperatures
not to exceed 90 degrees Celsius or at 75
degrees Celsius when exposed to oil and
gasoline
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
THERMOPLASTIC HEAT AND WATER
RESISTANT INSULATED WIRE (THW)
It is a solid or stranded, soft annealed copper
conductor insulated with Polyvinylchloride (PVC).
Maximum conductor temperature does not
exceed 75 degrees Celsius, 600V
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
THERMOPLASTIC HEAT AND WATER
RESISTANT INSULATED WIRE (TW)
It is a solid or stranded, soft annealed copper
conductor insulated with Polyvinylchloride (PVC).
Maximum conductor temperature does not
exceed 60 degrees Celsius, 600V
BASIC ELECTRICAL CONDUITS
1. RIGID METAL CONDUIT (RMC)
2. RIGID POLYVINYL CHLORIDE (PVC)
3. FLEXIBLE POLYVINYL CHLORIDE (PVC)
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
RIGID METAL CONDUIT (RMC)
For outdoor applications
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
RIGID POLYVINYL CHLORIDE (PVC)
Used in corrosive environments
For outdoor and indoor uses, typically in walls
and slabs
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
FLEXIBLE POLYVINYL CHLORIDE
(PVC)
Used in corrosive environments
For indoor uses, typically in ceilings and slabs
ELECTRICAL FITTINGS
REFER TO ATTACHED PDF
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
LIGHTING LAYOUT
 SCALE 1:100M
 GRIDLINES
 DIMENSIONS (General and Grid to Grid)
 REFER TO RCP FOR CEILING DESIGN AND LIGHTING FIXTURE ARRANGEMENT
 WITH FIXTURE AND FURNITURE (hidden lines)
 LIGHTS AND SWITCH CONNECTIONS
 CIRCUIT HOMERUNS
 LIGHTING FIXTURE LABELS (alphabets-small caps, same letter for lights with one switch)
 SWITCH LABELS
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
LIGHTING LAYOUT
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
POWER LAYOUT
 SCALE 1:100M
 GRIDLINES
 DIMENSIONS (General and Grid to Grid)
 WITH FIXTURE AND FURNITURE (hidden lines)
 CONVENIENCE OUTLETS WITH PROPER DESIGNATIONS
 SERVICE ENTRANCE, KILOWATT HOUR METER AND PANEL BOARD LOCATIONS
 CONVENIENCE OUTLET CONNECTIONS
 CIRCUIT HOMERUNS (single circuit for REFRIGERATOR and AIRCONDITIONING UNITS)
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
POWER LAYOUT
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
AUXILIARY LAYOUT
 SCALE 1:100M
 GRIDLINES
 DIMENSIONS (General and Grid to Grid)
 WITH FIXTURE AND FURNITURE (hidden lines)
 TELEPHONE and CATV OUTLETS
 CCTV (if any)
 PULL BOX (TELEPHONE and CATV) and DVR LOCATIONS
 DOORBELL AND BUZZER LOCATIONS
 OUTLET CONNECTIONS
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
AUXILIARY LAYOUT
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
LOAD COMPUTATION AND SCHEDULE
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
LOAD COMPUTATION AND SCHEDULE
WATTS PER OUTLET:
• LIGHTING OUTLET = 100W
• CONVENIENCE OUTLET = 180W
• CONVENIENCE OUTLET (REF) = 1000W
• CONVENIENCE OUTLET (1hp, ACU) = 1840W
Note: 1hp = 18 to 22sqm
FORMULAS:
• NO. OF OUTLETS PER CIRCUIT X WATTS PER OUTLET = WATTS PER CIRCUIT
• WATTS PER CIRCUIT / 230V = AMPERE LOAD
• TOTAL AMPERE LOAD X 0.80 = DEMAND FACTOR @ 80%
• DEMAND FACTOR X 1.20 = LOAD GROWTH @ 20%
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
ELECTRICIAN’S GUIDE TABLE
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
SINGLE LINE DIAGRAM
Shows a correct power distribution path from the
incoming power source to each downstream load
– including the ratings and sizes of each piece
of electrical equipment, their circuit conductors,
and their protective devices.
 NOT TO SCALE
 REPLICATE DRAWING but indicate correct
ampere trip, wire and conduit sizes as per the
LOAD COMPUTATION AND SCHEDULE
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
RISER DIAGRAM
Two-dimensional representation in a vertical
plane the distribution components of an
electrical system such as bus risers, bus plugs,
panel boards, and transformers from the point
of entry up to the small branch circuits
on each level.
 NOT TO SCALE
 REPLICATE DRAWING but indicate correct
ampere trip and circuit loads as per the
LOAD COMPUTATION AND SCHEDULE
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
VICINITY MAP
For reference of the concerned electric company
on the exact location of electrical tapping points.
 NOT TO SCALE
 REPLICATE VICINITY MAP in the FRONT PAGE
END OF MODULE 09
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS

MODULE-09-ELECTRICAL-AUXILIARY-DRAWINGS.pptx

  • 1.
    BLT 122 BUILDING TECHNOLOGYII AR. RONNEL CARLOS T. RAMOS Course Facilitator UNIVERSITY OF NORTHERN PHILIPPINES College of Architecture
  • 2.
    COURSE OUTLINE BLT -BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS MODULE 01 – BASIC WORKING DRAWINGS AND GRAPHICAL PRESENTATION TECHNIQUES MODULE 02 – REFLECTED CEILING PLANS AND DETAILS MODULE 03 – SCHEDULE OF DOORS AND WINDOWS MODULE 04 – SCHEDULE OF FINISHES MODULE 05 – KITCHEN AND T&B DETAILS MODULE 06 – STAIR DETAILS MODULE 07 – STRUCTURAL AND CIVIL WORK DRAWINGS MODULE 08 – PLUMBING AND SANITARY DRAWINGS MODULE 09 – ELECTRICAL AND AUXILIARY DRAWINGS
  • 3.
    MODULE 09 ELECTRICAL AND AUXILIARYDRAWINGS 7.A. ELECTRICAL NOTES, LEGENDS & SYMBOLS, ELECTRICAL WIRING, CONDUIT AND ACCESSORIES 7.B. ELECTRICAL, POWER AND AUXILIARY LAYOUTS 7.C. LOAD COMPUTATION AND SCHEDULE, SINGLE LINE DIAGRAM AND RISER DIAGRAM BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
  • 4.
    What is anELECTRICAL PLAN? It is a type of technical drawing that delivers visual representation and describes circuits and electrical systems. It consists of symbols and lines that showcase the engineer's electrical design to its clients. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS Also referred as “Electrical Drawing” or “Wiring Diagram”. Composed of Lighting and Power Layouts and other electrical specifications.
  • 5.
    What is anAUXILIARY PLAN? These are components related with Security Systems, Comfort Systems, Lighting Systems and Information Systems witch are very important to help the main system to perform according the specifications. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS Provides supplementary or additional help and support to the basic systems of a building Composed of Electronic and Communications systems. PABX – Private Automatic Branch Exchange Also referred as “telephone system”, these are switchboards that connect to several devices.
  • 6.
    ELECTRICAL NOTES REFERENCE: PHILIPPINE ELECTRICALCODE (PEC) Parts 1 & 2, 2017 Edition • Based from the 2017 National Electrical Code of USA. (NFPA 70, NEC) • Regularly revised every three(3) years to reflect the evolution of products, materials, and installation techniques. • The primary objective of the code is to establish basic materials quality and electrical works standards for the safe use of electricity for light, heat, power, communications, signaling and for other purposes. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
  • 7.
    LEGEND AND SYMBOLS BLT- BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
  • 8.
    POWER SERVICE ENTRANCE Also referredto as “service drop” It is where the wires connected to the load side of the meter enter the house or building. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
  • 9.
    KILOWATT HOUR (Kwh) METER Theseare compact electronic monitoring devices that measure the consumed energy flowing through a circuit such as a standard 120V or 240V BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
  • 10.
    ELECTRICAL PANELBOARD Also called,“distribution board”, “breaker panel” or “electric panel”. It is a component of an electricity supply system that divides an electrical power feed into subsidiary circuits while providing a protective fuse or circuit breaker for each circuit in a common enclosure. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
  • 11.
    CIRCUIT BREAKER It isan automatically operated electrical switch designed to protect an electrical circuit from damage caused by excess current from an overload or short circuit. Its basic function is to interrupt current flow after a fault is detected. CIRCUIT HOMERUN A home run is a wire that graphically represents the wiring of a circuit to a central location that acts as the distribution point for the power, typically, a panel. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
  • 12.
    GROUND ROD / GROUNDCLAMP Also known as grounding electrodes. Used to connect the grounding system of electrical systems to earth ground. They are very good conductors of electricity and allow any dangerous electricity to flow to ground, taking the danger away from you and the electrical panel. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
  • 13.
    PULL BOX FORTELEPHONE AND CATV They are used along with conduit to simplify wiring installation. They provide a way to pull conductors at long distances without placing excessive strain on the wire or insulation. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
  • 14.
    SWITCHES They are usedto turn electrical current on or off for nearly any electrical device. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
  • 15.
    CONVENIENCE OUTLETS A receptaclein a wall or baseboard for connection to lamps or other electrical appliances. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
  • 16.
    ELECTRICAL WIRING 1. THHNAND THWN 2. THW 3. TW BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
  • 17.
    BLT - BUILDINGTECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS THERMOPLASTIC HIGH HEAT-RESISTANT NYLON COATED (THHN) & THERMOPLASTIC WATER-RESISTANT NYLON COATED (THWN) Suitable for wet or dry locations at temperatures not to exceed 90 degrees Celsius or at 75 degrees Celsius when exposed to oil and gasoline
  • 18.
    BLT - BUILDINGTECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS THERMOPLASTIC HEAT AND WATER RESISTANT INSULATED WIRE (THW) It is a solid or stranded, soft annealed copper conductor insulated with Polyvinylchloride (PVC). Maximum conductor temperature does not exceed 75 degrees Celsius, 600V
  • 19.
    BLT - BUILDINGTECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS THERMOPLASTIC HEAT AND WATER RESISTANT INSULATED WIRE (TW) It is a solid or stranded, soft annealed copper conductor insulated with Polyvinylchloride (PVC). Maximum conductor temperature does not exceed 60 degrees Celsius, 600V
  • 20.
    BASIC ELECTRICAL CONDUITS 1.RIGID METAL CONDUIT (RMC) 2. RIGID POLYVINYL CHLORIDE (PVC) 3. FLEXIBLE POLYVINYL CHLORIDE (PVC) BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
  • 21.
    BLT - BUILDINGTECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS RIGID METAL CONDUIT (RMC) For outdoor applications
  • 22.
    BLT - BUILDINGTECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS RIGID POLYVINYL CHLORIDE (PVC) Used in corrosive environments For outdoor and indoor uses, typically in walls and slabs
  • 23.
    BLT - BUILDINGTECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS FLEXIBLE POLYVINYL CHLORIDE (PVC) Used in corrosive environments For indoor uses, typically in ceilings and slabs
  • 24.
    ELECTRICAL FITTINGS REFER TOATTACHED PDF BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
  • 25.
    BLT - BUILDINGTECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS LIGHTING LAYOUT  SCALE 1:100M  GRIDLINES  DIMENSIONS (General and Grid to Grid)  REFER TO RCP FOR CEILING DESIGN AND LIGHTING FIXTURE ARRANGEMENT  WITH FIXTURE AND FURNITURE (hidden lines)  LIGHTS AND SWITCH CONNECTIONS  CIRCUIT HOMERUNS  LIGHTING FIXTURE LABELS (alphabets-small caps, same letter for lights with one switch)  SWITCH LABELS
  • 26.
    BLT - BUILDINGTECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS LIGHTING LAYOUT
  • 27.
    BLT - BUILDINGTECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS POWER LAYOUT  SCALE 1:100M  GRIDLINES  DIMENSIONS (General and Grid to Grid)  WITH FIXTURE AND FURNITURE (hidden lines)  CONVENIENCE OUTLETS WITH PROPER DESIGNATIONS  SERVICE ENTRANCE, KILOWATT HOUR METER AND PANEL BOARD LOCATIONS  CONVENIENCE OUTLET CONNECTIONS  CIRCUIT HOMERUNS (single circuit for REFRIGERATOR and AIRCONDITIONING UNITS)
  • 28.
    BLT - BUILDINGTECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS POWER LAYOUT
  • 29.
    BLT - BUILDINGTECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS AUXILIARY LAYOUT  SCALE 1:100M  GRIDLINES  DIMENSIONS (General and Grid to Grid)  WITH FIXTURE AND FURNITURE (hidden lines)  TELEPHONE and CATV OUTLETS  CCTV (if any)  PULL BOX (TELEPHONE and CATV) and DVR LOCATIONS  DOORBELL AND BUZZER LOCATIONS  OUTLET CONNECTIONS
  • 30.
    BLT - BUILDINGTECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS AUXILIARY LAYOUT
  • 31.
    BLT - BUILDINGTECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS LOAD COMPUTATION AND SCHEDULE
  • 32.
    BLT - BUILDINGTECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS LOAD COMPUTATION AND SCHEDULE WATTS PER OUTLET: • LIGHTING OUTLET = 100W • CONVENIENCE OUTLET = 180W • CONVENIENCE OUTLET (REF) = 1000W • CONVENIENCE OUTLET (1hp, ACU) = 1840W Note: 1hp = 18 to 22sqm FORMULAS: • NO. OF OUTLETS PER CIRCUIT X WATTS PER OUTLET = WATTS PER CIRCUIT • WATTS PER CIRCUIT / 230V = AMPERE LOAD • TOTAL AMPERE LOAD X 0.80 = DEMAND FACTOR @ 80% • DEMAND FACTOR X 1.20 = LOAD GROWTH @ 20%
  • 33.
    BLT - BUILDINGTECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS ELECTRICIAN’S GUIDE TABLE
  • 34.
    BLT - BUILDINGTECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS SINGLE LINE DIAGRAM Shows a correct power distribution path from the incoming power source to each downstream load – including the ratings and sizes of each piece of electrical equipment, their circuit conductors, and their protective devices.  NOT TO SCALE  REPLICATE DRAWING but indicate correct ampere trip, wire and conduit sizes as per the LOAD COMPUTATION AND SCHEDULE
  • 35.
    BLT - BUILDINGTECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS RISER DIAGRAM Two-dimensional representation in a vertical plane the distribution components of an electrical system such as bus risers, bus plugs, panel boards, and transformers from the point of entry up to the small branch circuits on each level.  NOT TO SCALE  REPLICATE DRAWING but indicate correct ampere trip and circuit loads as per the LOAD COMPUTATION AND SCHEDULE
  • 36.
    BLT - BUILDINGTECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS VICINITY MAP For reference of the concerned electric company on the exact location of electrical tapping points.  NOT TO SCALE  REPLICATE VICINITY MAP in the FRONT PAGE
  • 37.
    END OF MODULE09 BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS