What to include in Installation
Qualification
Installation Qualification provides documented evidence
that the process equipment is installed according to the
equipment’s design requirements and manufacturer’s
recommendation. Let’s discuss what to include in an
Installation Qualification.
Installation Qualification is part of equipment validation activity, performed
after the equipment is installed.
It provides documented evidence that the pharmaceutical equipment is
installed according to the equipment’s design requirements and the
manufacturer’s recommendation. Additionally, after installation, the equipment
will operate and perform as per the buyer’s requirements.
These requirements and recommendations are thoroughly discussed during
the design qualification phase.
Installation Qualification Format
There are no strict rules and regulations for designing a format, and mainly
depends on the manufacturer and the buyer’s decision. However, a typical
format consists of a test description, its acceptance criteria, and the actual
result.
Tests are written in tabular form, with their corresponding acceptance criteria,
actual value, and result, i.e., Pass or Fail.
When a particular set of tests have been conducted, the person conducting
the IQ signs it, and the quality person approves the test by its signature.
Common Installation Qualification format is mentioned blow
S.No Test Acceptance Criteria Result PASS / FAIL
In the above table, below is the explanation of each column
● Test: it is parameter under test during the IQ activity
● Acceptance Criteria: The recommended result of the test, on which the
IQ test is considered satisfactory.
● Result: The actual outcome of the test being conducted
● Pass/ Fail: Whether the test is fail or pass, depending upon the test
outcome
Installation Qualification Checklist
Installation Qualification is a series of tests performed related to equipment
installation. Before conducting Installation Qualification, the manufacturer
prepares the desired IQ tests in an approved format. These tests are then
sent to the buyer for their review and approval. When both manufacturer and
buyer approve the test format, the Installation Qualification protocol becomes
official.
Let’s look at common tests routinely performed in an Installation Qualification
activity.
Design Characteristics
It includes tests related to the design attributes of the equipment being
installed. It ensures that all the attached components are installed according
to the agreed characteristics.
Let’s look at some design characteristics tests and their acceptance criteria.
S.No Test Acceptance Criteria Result PASS / FAIL
1 Material of construction of
associated components
Piping
Exhaust
Electrical Conduit
Pneumatic Conduit
Duct
SS / MS / Insulation
MS
SS / MS
SS / MS
SS / MS
2 Area of Installation The area must be free
from dust and particle
3 Ventilation There must be
adequate
arrangements of
ventilation in area
4 Foundation The equipment
foundation must be
solid and rigid
5 Space for person movement Adequate space for
operator and other
personnel movement
must be provided
6 Space for material Adequate space for
placing different
material must be
provided
7 Electrical safety The electrical supply
must be properly
provided with relevant
safety system
8 Compressed Air The compressed air
must be supplied with
adequate pneumatic
components and
safety system
9 Steam Line The steam line must
be proper with
adequate components
and safety system
Utility Requirements
This section verifies that the utilities provided are according to the equipment
requirements, as agreed during the design qualification phase.
Every pharma equipment requires standard utility supplies for its satisfactory
performance. The equipment will not operate according to design
specifications if these are not provided.
Some tests common in this section are mentioned below.
S.No Test Acceptance Criteria Result PASS / FAIL
1 Electricity The electrical supply must
· 380V/220 VAC
· 3 phase / single phase
2 Steam The steam pressure must be
_____ bar / psi
3 Compressed Air The compressed air must be
___bar / psi.
The compressed air must be
dry, free from water.
4 Natural gas The natural gas pressure must
be-------- bar / psi.
5 Chilled Water The chilled water supply must
be -------- bar / psi, at --------⁰C
6 Purified Water The purified water supply must
be -------- bar / psi.
7 Water for Injection The water for injection supply
must be -------- bar / psi.
Documentation
During the design qualification phase, the buyer mentions the documentation
they require, which becomes mandatory for the manufacturer to supply with
equipment.
In this test, the buyer checks and verifies all the required documentation that
the manufacturer has supplied with the equipment.
Some common tests performed in this section include the following.
S.N
o
Test Acceptance Criteria Result PASS / FAIL
1 Operation Manual Operational manual with detailed
guidelines should be supplied
2 Wiring Diagram Wiring diagram with detailed guidelines
should be supplied
3 Maintenance
manual
Maintenance manual, containing
schedule with detailed guidelines should
be supplied
4 Validation
documents
(including DQ, IQ,
OQ and PQ)
Manufacturer must provide complete
Validation documents
5 Preventive
Maintenance
Manual
Manufacturer must provide Preventive
maintenance procedure with complete
6 Calibration Manufacturer must provide calibration
procedure of all measuring instrument
and devices with proper schedule.
7 Spare parts list Manufacturer must provide spare parts
list of all the critical items and
components.
Certificates
This test includes verification that the desired certificates are provided with the
machine, agreed upon during the design qualification stage.
Certificates are necessary because the pharma process are critical and
requires specialized materials, devices, and instruments. To ensure that the
manufacturer has adequately applied all requirements, the manufacturer
provides certificates as a proof. Additionally, regulatory authorities such as
the United States FDA can also review them during their routine inspection.
Some common tests performed in this section include the following
S.No Test Acceptance Criteria Result PASS / FAIL
1 Calibration certificates Calibration certificates for all
the recording and measuring
devices must be provided
The certificates must not be
expired
2 Material of
construction
Product contact parts
Non – Product contact
parts
Certificates for material of
construction of specific
machine parts must be
SS 316L
SS 304
Environmental Conditions
In this section, environmental condition equipment is checked and verified.
Pharmaceutical equipment require specific conditions for their satisfactory
performance. If the desired environmental conditions are not provided, it will
negatively impact the output product and equipment performance.
Some common tests performed in this section include the following.
S.No Test Acceptance Criteria Result PASS / FAIL
1 Area Temperature The temperature must be-----
⁰C
2 Area Humidity The humidity must be --------
4 Laminar Flow Laminar air flow with ----- air
speed must be installed
5 Air Changes Air changes in the area must
be ----
6 Differential Pressure Differential pressure of the
area must be-------
The pressure in the areas
must be negative / positive
Area Classification The area for production must
be ___ (Class A , B , C , D)

Installation Qualification.pdf

  • 1.
    What to includein Installation Qualification Installation Qualification provides documented evidence that the process equipment is installed according to the equipment’s design requirements and manufacturer’s recommendation. Let’s discuss what to include in an Installation Qualification. Installation Qualification is part of equipment validation activity, performed after the equipment is installed. It provides documented evidence that the pharmaceutical equipment is installed according to the equipment’s design requirements and the manufacturer’s recommendation. Additionally, after installation, the equipment will operate and perform as per the buyer’s requirements. These requirements and recommendations are thoroughly discussed during the design qualification phase. Installation Qualification Format There are no strict rules and regulations for designing a format, and mainly depends on the manufacturer and the buyer’s decision. However, a typical format consists of a test description, its acceptance criteria, and the actual result.
  • 2.
    Tests are writtenin tabular form, with their corresponding acceptance criteria, actual value, and result, i.e., Pass or Fail. When a particular set of tests have been conducted, the person conducting the IQ signs it, and the quality person approves the test by its signature. Common Installation Qualification format is mentioned blow S.No Test Acceptance Criteria Result PASS / FAIL
  • 3.
    In the abovetable, below is the explanation of each column ● Test: it is parameter under test during the IQ activity ● Acceptance Criteria: The recommended result of the test, on which the IQ test is considered satisfactory. ● Result: The actual outcome of the test being conducted ● Pass/ Fail: Whether the test is fail or pass, depending upon the test outcome Installation Qualification Checklist Installation Qualification is a series of tests performed related to equipment installation. Before conducting Installation Qualification, the manufacturer prepares the desired IQ tests in an approved format. These tests are then sent to the buyer for their review and approval. When both manufacturer and buyer approve the test format, the Installation Qualification protocol becomes official. Let’s look at common tests routinely performed in an Installation Qualification activity. Design Characteristics
  • 4.
    It includes testsrelated to the design attributes of the equipment being installed. It ensures that all the attached components are installed according to the agreed characteristics. Let’s look at some design characteristics tests and their acceptance criteria. S.No Test Acceptance Criteria Result PASS / FAIL 1 Material of construction of associated components Piping Exhaust Electrical Conduit Pneumatic Conduit Duct SS / MS / Insulation MS SS / MS SS / MS SS / MS 2 Area of Installation The area must be free from dust and particle 3 Ventilation There must be adequate arrangements of ventilation in area 4 Foundation The equipment foundation must be solid and rigid
  • 5.
    5 Space forperson movement Adequate space for operator and other personnel movement must be provided 6 Space for material Adequate space for placing different material must be provided 7 Electrical safety The electrical supply must be properly provided with relevant safety system 8 Compressed Air The compressed air must be supplied with adequate pneumatic components and safety system 9 Steam Line The steam line must be proper with adequate components and safety system Utility Requirements This section verifies that the utilities provided are according to the equipment requirements, as agreed during the design qualification phase. Every pharma equipment requires standard utility supplies for its satisfactory performance. The equipment will not operate according to design specifications if these are not provided. Some tests common in this section are mentioned below.
  • 6.
    S.No Test AcceptanceCriteria Result PASS / FAIL 1 Electricity The electrical supply must · 380V/220 VAC · 3 phase / single phase 2 Steam The steam pressure must be _____ bar / psi 3 Compressed Air The compressed air must be ___bar / psi. The compressed air must be dry, free from water. 4 Natural gas The natural gas pressure must be-------- bar / psi. 5 Chilled Water The chilled water supply must be -------- bar / psi, at --------⁰C 6 Purified Water The purified water supply must be -------- bar / psi. 7 Water for Injection The water for injection supply must be -------- bar / psi.
  • 8.
    Documentation During the designqualification phase, the buyer mentions the documentation they require, which becomes mandatory for the manufacturer to supply with equipment. In this test, the buyer checks and verifies all the required documentation that the manufacturer has supplied with the equipment. Some common tests performed in this section include the following. S.N o Test Acceptance Criteria Result PASS / FAIL 1 Operation Manual Operational manual with detailed guidelines should be supplied 2 Wiring Diagram Wiring diagram with detailed guidelines should be supplied 3 Maintenance manual Maintenance manual, containing schedule with detailed guidelines should be supplied
  • 9.
    4 Validation documents (including DQ,IQ, OQ and PQ) Manufacturer must provide complete Validation documents 5 Preventive Maintenance Manual Manufacturer must provide Preventive maintenance procedure with complete 6 Calibration Manufacturer must provide calibration procedure of all measuring instrument and devices with proper schedule. 7 Spare parts list Manufacturer must provide spare parts list of all the critical items and components. Certificates This test includes verification that the desired certificates are provided with the machine, agreed upon during the design qualification stage. Certificates are necessary because the pharma process are critical and requires specialized materials, devices, and instruments. To ensure that the
  • 10.
    manufacturer has adequatelyapplied all requirements, the manufacturer provides certificates as a proof. Additionally, regulatory authorities such as the United States FDA can also review them during their routine inspection. Some common tests performed in this section include the following S.No Test Acceptance Criteria Result PASS / FAIL 1 Calibration certificates Calibration certificates for all the recording and measuring devices must be provided The certificates must not be expired 2 Material of construction Product contact parts Non – Product contact parts Certificates for material of construction of specific machine parts must be SS 316L SS 304 Environmental Conditions In this section, environmental condition equipment is checked and verified.
  • 11.
    Pharmaceutical equipment requirespecific conditions for their satisfactory performance. If the desired environmental conditions are not provided, it will negatively impact the output product and equipment performance. Some common tests performed in this section include the following. S.No Test Acceptance Criteria Result PASS / FAIL 1 Area Temperature The temperature must be----- ⁰C 2 Area Humidity The humidity must be -------- 4 Laminar Flow Laminar air flow with ----- air speed must be installed 5 Air Changes Air changes in the area must be ---- 6 Differential Pressure Differential pressure of the area must be------- The pressure in the areas must be negative / positive Area Classification The area for production must be ___ (Class A , B , C , D)