High Voltage Circuit Breakers
BESCOM
CONTENTS:
2
 Introduction
 Operating Mechanism
 Types of Circuit Breakers:
 Air Blast Circuit Breaker
 Oil Circuit Breaker
 SF6 Circuit Breaker
 Vacuum Circuit Breaker
 Conclusion
Introduction:
3
 A circuit breaker is a mechanical switching
device, capable of making, carrying & breaking current
under normal circuit conditions. It is also capable of
making and carrying currents for a specified time and
breaking current under specified abnormal conditions,
Such as those of a short circuit.
OPERTING MECHANISM:
4
FIXED CONTACT
MOVING CONTACT
FIXED CONTACT
ARC IS QUENTCHED
BY MEDIUM
MOVING CONTACT
OPERTING MECHANISM:
 Circuit Breaker consists of two contacts:
Fixed Contact
Moving Contact
 Moving contact is used to make and break the circuit using stored energies in the
form of spring and compressed air.
 Spring, pneumatic or oil damping is used to arrest the spped of moving contact while
closing.
 Fixed contact contains a spring which holds the moving contact after closing.
5
6
 Circuit Breaker consists of two coils:
Closing Coil : Used to close the circuit
Tripping Coil : Used to trip the circuit.
 These coils activate the stored energy and directs the moving contact to open or
close.
 DC batteries are used to energies these coils.
 Solenoid are used to close or trip it.
 Circuit Breakers are usually arranged with pilot devices to sense a fault current and
to operate the trip opening mechanism.
ELECTRIC ARC:
7
During the separation of contacts, due to large fault current and high current density at
the contact region the surrounding medium ionizes and thus a conducting medium is
formed is called “ARC”.
Factor Responsible for ARC:
 Potential difference between the contacts
 Ionized particle between the contacts.
PRINCIPLES OF ARC EXTINSION
8
Arc Quenching is achieved by:
 Greater Dielectric strength than restriking voltage.
 Faster rate of heat removal than rate of heat of generation.
Arc Extinction methods are:
 By lengthening the gap.
 Cooling the arc.
 Inserting medium of high dielectric strength.
TYPES OF CIRCUIT BREAKER
9
CIRCUIT BREAKER
OIL CIRCUIT
BREAKER
BREAKER
AIR BLAST
CIRCUIT
BREAKER
VACUUM
CIRCUIT
BREAKER
SF6 CIRCUIT
BREAKER
OIL CIRCUIT BREAKER:
10
 It is designed for 11kV-765kV.
 There are of two types:
BOCB - Break oil circuit breaker.
MOCB- Minimum oil circuit breaker.
 The contacts are immersed in oil bath.
 Oil provides cooling by hydrogen created by
arc.
 It acts as a good dielectric medium and
quenches the arc.
OIL CIRCUIT BREAKER
11
 Advantage:
I. Oil has good dielectric strength.
II. Low cost
III. Oil is easily available
IV. It has wide range of breaking capability.
 Disadvantage:
I. Slower operation. Takes 20 cycles for arc
quenching.
II. It is highly infalamable, so high risk of fire.
III. High maintenance cost.
VACCUM CIRCUIT BREAKER:
12
 It is designed for medium voltage
range(3.3kV-33kV).
 It consists of vacuum of pressure
1*10−6 inside arc extension chamber.
 The arc burns in metal vapour when
the contacts are disconnected.
 At high voltage, Its rate of dielectric
recovery strength is very high.
 Due to vacuum, arc extinction is very
fast.
 The contacts loose metal gradually
due to formation of metal vapours.
VACCUM CIRCUIT BREAKER:
13
 Advantage:
I. Free from arc and fire hazards.
II. Low cost for maintenance and simpler
mechanism.
III. Low arcing time and high contact life.
IV. Silent and less vibrational operation.
V. Due to vacuum contacts remain free from
corrosion.
VI. No byproducts formed.
 Disadvantage:
I. High initial cost due to creation of vaccum.
II. Surface of contacts are depleted due to
metal vapours.
III. High cost and size required for high voltage
breakers.
AIR BLAST CIRCUIT BREAKER:
14
 This operates high velocity blast of air which
quenches the arc.
 It consists of blast valve, blast tube &
contacts.
 Blast valve contains air at high pressure.
 Blast tube carries air at high pressure and
opens the moving contact attached to spring.
 There is no carbonization of surface as in
VCB
 Air should be kept clean and dry to operate it
properly.
AIR BLAST CIRCUIT BREAKER:
15
 Advantage:
I. High speed operation as compared to OCB.
II. Ability to withstand frequent switching.
III. Facility for high speed closure.
IV. Less maintenance as compared to OCB.
 Disadvantage:
I. Little moisture content prolongs arcing time
II. Pressure should be checked frequently for
frequent operation.
III. Risk of fire hazards due to over voltage.
IV. It can not be used for high voltage
operation due to prolonged arc quenching.
SF6 CIRCUIT BREAKER:
16
 It contains an arc extension chamber containing SF6 gas.
 In closed position the contact remain surrounded by SF6 gas at a pressure of 2.8
Kg/cm2
.
 During opening high pressure SF6 gas at 14Kg/cm2 from its reservoir flows towards
the chamber by valve mechanism.
 SF6 rapidally absorbs the free electrons in the arc path to form immobile negative ions
to build up high dielectric strength.
 It also cools the arc and extinguishes it.
 After operation the valve is closed by the action of a set of springs.
 Absorbent material are used to absorb the byproducts and moisture.
SF6 CIRCUIT BREAKER:
17
SF6 CIRCUIT BREAKER:
18
 Advantage:
I. Very short arcing period due to to superior arc quenching property of
SF6.
II. Can interrupt much larger current as compared to the other breakers.
III. No risk of fire.
IV. Low maintenance, light foundation.
V. No overvoltage problem.
VI. There are no carbon deposits.
 Disadvantage:
I. It is costly due to high cost of SF6 gas.
II. SF6 gas can be reconditioned after every operation of the breaker,
additional equipment is required for this purpose.
CONCLUSION:
19
Therefor we conclude that circuit breaker is the most essential
part of the electrical network as it protects every device from
damage. It help us to detect the fault and area affected by it.
Nowadays vacuum and SF6 circuit breakers are widely used
due to their reliable and fast operations.
Thank You

High voltage circuit breakers

  • 1.
    High Voltage CircuitBreakers BESCOM
  • 2.
    CONTENTS: 2  Introduction  OperatingMechanism  Types of Circuit Breakers:  Air Blast Circuit Breaker  Oil Circuit Breaker  SF6 Circuit Breaker  Vacuum Circuit Breaker  Conclusion
  • 3.
    Introduction: 3  A circuitbreaker is a mechanical switching device, capable of making, carrying & breaking current under normal circuit conditions. It is also capable of making and carrying currents for a specified time and breaking current under specified abnormal conditions, Such as those of a short circuit.
  • 4.
    OPERTING MECHANISM: 4 FIXED CONTACT MOVINGCONTACT FIXED CONTACT ARC IS QUENTCHED BY MEDIUM MOVING CONTACT
  • 5.
    OPERTING MECHANISM:  CircuitBreaker consists of two contacts: Fixed Contact Moving Contact  Moving contact is used to make and break the circuit using stored energies in the form of spring and compressed air.  Spring, pneumatic or oil damping is used to arrest the spped of moving contact while closing.  Fixed contact contains a spring which holds the moving contact after closing. 5
  • 6.
    6  Circuit Breakerconsists of two coils: Closing Coil : Used to close the circuit Tripping Coil : Used to trip the circuit.  These coils activate the stored energy and directs the moving contact to open or close.  DC batteries are used to energies these coils.  Solenoid are used to close or trip it.  Circuit Breakers are usually arranged with pilot devices to sense a fault current and to operate the trip opening mechanism.
  • 7.
    ELECTRIC ARC: 7 During theseparation of contacts, due to large fault current and high current density at the contact region the surrounding medium ionizes and thus a conducting medium is formed is called “ARC”. Factor Responsible for ARC:  Potential difference between the contacts  Ionized particle between the contacts.
  • 8.
    PRINCIPLES OF ARCEXTINSION 8 Arc Quenching is achieved by:  Greater Dielectric strength than restriking voltage.  Faster rate of heat removal than rate of heat of generation. Arc Extinction methods are:  By lengthening the gap.  Cooling the arc.  Inserting medium of high dielectric strength.
  • 9.
    TYPES OF CIRCUITBREAKER 9 CIRCUIT BREAKER OIL CIRCUIT BREAKER BREAKER AIR BLAST CIRCUIT BREAKER VACUUM CIRCUIT BREAKER SF6 CIRCUIT BREAKER
  • 10.
    OIL CIRCUIT BREAKER: 10 It is designed for 11kV-765kV.  There are of two types: BOCB - Break oil circuit breaker. MOCB- Minimum oil circuit breaker.  The contacts are immersed in oil bath.  Oil provides cooling by hydrogen created by arc.  It acts as a good dielectric medium and quenches the arc.
  • 11.
    OIL CIRCUIT BREAKER 11 Advantage: I. Oil has good dielectric strength. II. Low cost III. Oil is easily available IV. It has wide range of breaking capability.  Disadvantage: I. Slower operation. Takes 20 cycles for arc quenching. II. It is highly infalamable, so high risk of fire. III. High maintenance cost.
  • 12.
    VACCUM CIRCUIT BREAKER: 12 It is designed for medium voltage range(3.3kV-33kV).  It consists of vacuum of pressure 1*10−6 inside arc extension chamber.  The arc burns in metal vapour when the contacts are disconnected.  At high voltage, Its rate of dielectric recovery strength is very high.  Due to vacuum, arc extinction is very fast.  The contacts loose metal gradually due to formation of metal vapours.
  • 13.
    VACCUM CIRCUIT BREAKER: 13 Advantage: I. Free from arc and fire hazards. II. Low cost for maintenance and simpler mechanism. III. Low arcing time and high contact life. IV. Silent and less vibrational operation. V. Due to vacuum contacts remain free from corrosion. VI. No byproducts formed.  Disadvantage: I. High initial cost due to creation of vaccum. II. Surface of contacts are depleted due to metal vapours. III. High cost and size required for high voltage breakers.
  • 14.
    AIR BLAST CIRCUITBREAKER: 14  This operates high velocity blast of air which quenches the arc.  It consists of blast valve, blast tube & contacts.  Blast valve contains air at high pressure.  Blast tube carries air at high pressure and opens the moving contact attached to spring.  There is no carbonization of surface as in VCB  Air should be kept clean and dry to operate it properly.
  • 15.
    AIR BLAST CIRCUITBREAKER: 15  Advantage: I. High speed operation as compared to OCB. II. Ability to withstand frequent switching. III. Facility for high speed closure. IV. Less maintenance as compared to OCB.  Disadvantage: I. Little moisture content prolongs arcing time II. Pressure should be checked frequently for frequent operation. III. Risk of fire hazards due to over voltage. IV. It can not be used for high voltage operation due to prolonged arc quenching.
  • 16.
    SF6 CIRCUIT BREAKER: 16 It contains an arc extension chamber containing SF6 gas.  In closed position the contact remain surrounded by SF6 gas at a pressure of 2.8 Kg/cm2 .  During opening high pressure SF6 gas at 14Kg/cm2 from its reservoir flows towards the chamber by valve mechanism.  SF6 rapidally absorbs the free electrons in the arc path to form immobile negative ions to build up high dielectric strength.  It also cools the arc and extinguishes it.  After operation the valve is closed by the action of a set of springs.  Absorbent material are used to absorb the byproducts and moisture.
  • 17.
  • 18.
    SF6 CIRCUIT BREAKER: 18 Advantage: I. Very short arcing period due to to superior arc quenching property of SF6. II. Can interrupt much larger current as compared to the other breakers. III. No risk of fire. IV. Low maintenance, light foundation. V. No overvoltage problem. VI. There are no carbon deposits.  Disadvantage: I. It is costly due to high cost of SF6 gas. II. SF6 gas can be reconditioned after every operation of the breaker, additional equipment is required for this purpose.
  • 19.
    CONCLUSION: 19 Therefor we concludethat circuit breaker is the most essential part of the electrical network as it protects every device from damage. It help us to detect the fault and area affected by it. Nowadays vacuum and SF6 circuit breakers are widely used due to their reliable and fast operations.
  • 20.