1. TYPE-1 AS NBC 2016
1. Our category moderate Hazard,
based on more then 1000m2 we
need 150m3 O/G tank. Overhead
tank 20m3.
2. Installation of negative suction
arrangement and submersible
pumps shall not be allowed.
2. Interconnecting overflow line
FIRE WATER TANK 1 : 150 KL
Fire Pump
Fire supply
Minimum water level to keep 150 KL
in tank 1.
75 KL
Water should
be always
available for
pump suction.
Overflow
Always feed
Maintain level
every time
b
75 KL
Maintain level
every time
3. 1. MAXIMUM 7NOS OF HYDRANTS WILL
COME IN NEW FACTORY.
2. ORINARY HARAD IN OUR CASE
38LPS(2280LPM) PUMP IS REQUIRED.
3. TANK CAPACITY IN ORDINARY HAZARD
FOR 2HOURS (2280LPMX120MINUTES).
273.6M3 TANK IS REQUIRED.
4. 2NOS OF ELECTRIC 2280LPM, 1NO OF
DIESEL 2280 LPM & 2NOS OF ELECTRIC
PUMP 180LPM JOCKEY IS REQUIRED.
TYPE-2 AS PER IS 12469
4. Interconnecting overflow line
FIRE WATER TANK 1 : 150 KL FIRE WATER TANK 2 : 150 KL
Fire Pump
Fire supply
Minimum water level to keep 150 KL
in tank 2.
150 KL
150 KL
Maintain
Water should
be always
available for
pump suction.
Overflow
Always feed
Maintain level
every time
6. Sr. No. Company Name Executed By Year of
completion
Fire Tank 1
(m3)
Fire Tank 2
(m3)
Remark
1 Mitsui Kinzoku TKIN 2014 (Exp 2020) 150 × U/G RCC
2 FCC Clutch TKIN 2017 100 × U/G RCC
3 Oji Packaging TKIN 2020 200 150 U/G RCC
4 INDIA JAPAN LIGHTING TKIN 2020 175 175 A/G RCC
5 MITSUBISHI AUTO TKIN 2021 175 175 A/G RCC
6 NIFCO INDIA TKIN 2022 150 150 A/G ZIRCONIUM
7 SECURE METER OTHERS 2021 160 × U/G RCC
8 VEGA INDIA OTHERS 2021 175 × U/G RCC
9 MITSUBA OTHERS 2018 120 × U/G RCC
10 HI-LEX OTHERS × 100 × U/G RCC
11 IDEX OTHERS 2021 175 175 O/H MODULAR
12 HI-TEMP FURNACE OTHERS × 100 × U/G RCC
Details Fire tank of Projects at Sanand GIDC
7. Sr. No. Company Name Executed By Year of
completion
Fire Tank 1
(m3)
Fire Tank
2
(m3)
Remark
13 Ball Corporation Others × 150 × OH Modular tank
14 VALEO Others × 200 × OH Modular Tank
15 Pinggao group power Others × 150 × OH RC Tank
Details Fire tank of Projects at Sanand GIDC
Conclusion :-
(i) The projects executed 2014- 2018 duration follow the regulation of providing tank capacity of 100 m3 .
(ii) The recent project after 2018 follow the new NBC 2016 regulation & provide tank capacity of 150 m3 +
(iii) The Provision of Fire tank separation wall / spare tank detail & how they manage not shared by other
organizations as listed.