2
Subpart S - Electrical
(1910.301 - 399)
515
457
396
347
290
303(g)(2)(i)
305(b)(1)
304(f)(4)
305(b)(2)
305(g)(1)(iii)
Live parts
Grounding path
Electrical box covers
Conductors entering cabinets/boxes/fittings protected from abrasion
Standard:1910.
Use of flexible cords and cables
*
*
*
*
*
*Average number of Federal OSHA citations issued
between 2000 and 2003
DEFINITION
A physical agency caused by the
motion of electrons, protons, and other
charged particles, manifesting itself as
an attraction, repulsion, magnetic,
luminous, and heating effects, etc.
ELEMENTS & ATOMS
Every known substance – solid, liquid or
gas is composed of elements
An atom is the smallest particle of an
element that retains all the properties of
that element
Each element has it’s own kind of atom
ATOMS
Inner part composed of protons & neutrons
Outer part composed of electrons
Protons = positive charge
Neutrons = no charge
Electrons = negative charge
ATOMS
Each element has a definite number of
electrons ----and the same number of
protons
They are oppositely charged and
therefore attract each other. This tends
to hold the electrons in orbit around the
atom.
ELECTRICALLY BALANCED
ATOM
FREE ELECTRONS
Some atoms are easily moved out of orbit
The ability to move or flow is the basis of
current electricity
If channeled in a given direction, a flow of
electrons occurs --- when flowed through a
conductor it is dynamic electricity
ELECTICAL MATERIALS
CONDUCTOR – contains many free
electrons --- gold, copper, silver,
aluminum
INSULATOR – contains few free
electrons-Usually non-metallic such as
wood, rubber, glass, etc
GENERATING ELECTRICITY
Friction, pressure, heat, light, chemical
reaction, and magnetism
Magnetism is most practical & inexpensive
method
Electricity is produced when a magnet is
moved past a piece of wire, or wire is
moved through a magnetic field
VOLTAGE, CURRENT, &
RESISTANCE
VOLTAGE – unit of measurement of electromotive
force (EMF)
CURRENT - Continuous movement of electrons past
a given point. (measured in amperes)
RESISTANCE – Opposition to movement of electrons.
Makes it possible to generate heat, control current
flow, & supply correct voltage to devices
OHM’S LAW
George Simon Ohm
 Formulated a mathematical relationship between:
 Current
 Voltage
 Resistance
 Resistance = Impedance
 Resistance = DC
 Impedance = AC
 Interchangeable – Most Branch circuits
DIRECT CURRENT
Always flows in one direction
Used to charge batteries, run some
motors, operate magnetic lifting devices
and welding equipment.
ALTERNATING CURRRENT
More common in electrical work
Changes rapidly in both direction and
value
Power companies produce power
cheaper with alternating current
ELECTRICAL HAZARDS
SHOCK. Electric shock occurs
when the human body becomes
part of the path through which
current flows.
The direct result can be
electrocution.
The indirect result can be injury
resulting from a fall or movement
into machinery because of a
shock
ELECTRICAL HAZARDS
BURNS. Burns can result when a
person touches electrical wiring or
equipment that is energized.
ARC-BLAST. Arc-blasts occur from
high- amperage currents arcing
through the air. This can be caused
by accidental contact with energized
components or equipment failure.
Arc Flash and Arc Blasts
Arc Flash:
 80%-Burns due to
ignition of clothing
 Temperature-35,000
F
 Fatal Burns-10 ft.
 2000 people
hospitalized with
burns
 Molten metal
Arc Blast:
 Pressure Wave
 Heat
 Molten metal
 Destruction of
structures and life
Arc Blast
Cause
 Short Circuit caused by working on
energized equipment
 Dropped Tool
 Occurs in milliseconds
 Temp: 30,000 degrees
 Air expands very violently
 15 tons of pressure
ELECTRICAL HAZARDS
ARC-BLAST. The three primary
hazards associated with an arc-
blast are:
Thermal radiation.
Pressure Wave.
Projectiles.
ELECTRICAL HAZARDS
EXPLOSIONS. Explosions occur
when electricity provides a
source of ignition for an explosive
mixture in the atmosphere.
ELECTRICAL HAZARDS
FIRES. Electricity is one of the
most common causes of fires
both in the home and in the
workplace. Defective or misused
electrical equipment is a major
cause.
EFFECTS ON THE
HUMAN BODY
Depends on:
Current and Voltage
Resistance
Path through body
Duration of shock
Effects of AC Electricity
More than 3 mA- Painful shock- cause
indirect accident
More than 10 mA- Muscle contraction –
“No Let Go” danger
More than 30 mA- Lung paralysis,
usually temporary
Effects of AC Electricity
More than 50 mA- Ventricular
fibrillation, usually fatal
100 mA to 4 A- Certain ventricular
fibrillation, fatal
Over 4 A- Heart paralysis, severe burns
Effects
Protection
 Circuit Breakers
 Fuses
 15 or 20 amps
 Property/equipment protection
Conductors
American Wire Gauge
 12 gauge – 20 amps (Safely)
 14 gauge – 15 amps
 10 gauge – 30 amps
What determines amount of amps
through a circuit?
 How much the equipment draws
 How much “stuff” plugged in
Protective Devices
Fuses
Circuit Breakers
 Trip or break circuit breakers if conductors
exceed their ampacity
Summary
Current (I)
Voltage (E or v)
Resistance (R) (Ohms)
Electrocution Triangle
Electricity (levels)
Time
Path
Wires
Black = hot = Ungrounded Conductor
White = neutral = Grounded Conductor
(connected to grounding
electrode/Grounding rod)
How to check
Wiring Checks
 Testers
 Different types
Instruments
Normal 3 light Tester
 Won’t check resistance to ground
Others - Check what the 3 light tester
will
 Also checks resistance for ground
Double Insulated
Indicators
 No ground pin
 Plastic tool case
 Listed by NTL
 Marked as double insulated
 Square in a square
 Marked “double insulated”
1910.302 Electrical
Utilization Systems
Scope:
 (a) Covers electrical installations and
utilization equipment installed or used within
or on buildings, structures, and other
premises
(a) Approval. The conductors and equipment
required or permitted by this subpart shall be
acceptable only if approved
1910.303 General
Requirements
1910.303 (b) Examination,
installation and use
Employer Obligation:
 (1) Electrical equipment shall be free from
recognized hazards that are likely to cause
death or serious physical harm to employees
(1) Examination. Safety of equipment shall
determined using the following
considerations:
 (i) Suitability of equipment for an identified
purpose may be evidenced by listing or labeling for
that identified purpose
1910.303 (b)
Examination, installation,
and use
5
• 1910.303(a) Approval
– All electrical conductors and equipment
shall be approved.
UNDERWRITERS
LABORATORIES
ENCLOSED SWITCH
Issue AK 3225
LISTED
1910.303(a)
NEC Article 110-2
6
1910.303 (f) Identification
of Disconnecting
Means and Circuits
Each disconnecting means legibly
marked to indicate its purpose
 (Unless so arranged so the purpose is
evident)
Disconnect switch for
motor number 3
1910.303 (f) ID of
Disconnecting Means
Each service, feeder, and branch circuit, at its
overcurrent device, legibly and durably marked
to indicate its purpose
Switches and circuit breakers must be clearly
labeled to indicate its circuit’s function
Circuit breaker for motors
1,2,3, and 4
1910.303(g) Working
Space
(1) Sufficient access and working space around
all electrical equipment, provided & maintained
to provide ready and safe operation and
maintenance
(ii) Not used
for storage
(ii) If located in aisle or general open area,
working space shall be suitably guarded
1910.303(g)(1)(v)
Illumination
Illumination provided for
all working spaces about
service equipment,
switchboards, panel-
boards, and motor control
centers installed indoors.
1910.303(g)(1)(vi)
Headroom
The minimum
headroom of working
spaces about service
equipment,
switchboards, panel-
boards, or motor
control centers shall
be 6 feet 3 inches
6'3"
(2)(i) Live parts of electric equipment
operating at 50 volts or more guarded against
accidental contact by approved cabinets
1910.303(g) Guarding of
live parts
(g)(2)(i) or other forms of approved enclosures,
or by any of the following means:
 (A) By location in a room, vault, accessible only to
qualified persons
 (B) By permanent, substantial partitions or screens
 (C) By location on a suitable
balcony or platform as to exclude
unqualified persons
 (D) By elevation of 8 feet or more
above the floor or other
working surface
Guarding live parts – 1910.303
1910. 303(g) Guarding live parts
(2)(iii) Entrances to rooms
and other guarded
locations containing
exposed live parts shall be
marked with conspicuous
warning signs forbidding
unqualified persons to enter
1910.303(h)(3)(ii) Illumination
Adequate illumination for all
working spaces about
electric equipment
The lighting outlets arranged
that persons changing lamps
or making repairs on the
lighting system will not be
endangered by live parts or
other equipment
1910.304(a)(1) Identification of
Conductors
A conductor used as a
grounded conductor shall be
identifiable and distinguishable
from all other conductors.
A conductor used as an
equipment grounding conductor
shall be identifiable and
distinguishable from all other
conductors
Identification of Conductors
Grounded conductor and equipment grounding
conductors marked or color coated
So that employees can i.d. and tell apart
Grounded conductor is an energized circuit
(conductor that is connected to earth through
the system ground) Commonly referred to as
the neutral
Grounding Conductors
Equipment grounding conductor acts as a
safeguard against insulation failure or faults in
the other circuit conductors
Not an energized conductor under normal
conditions.
Energized if a leak or fault in the normal
current path
Directs current back to the source
Enabling fuses or circuit breakers to operate
Identification of Conductors
Grounded conductor i.d. and distinguished
from other conductors w/ white or gray
Equipment grounding conductor i.d. and
distinguished w/ green, green w/ yellow stripes,
or bare
1910.304(a) Use and identification
of grounded and grounding
conductors
(2) No grounded conductor may be attached to
any terminal or lead so as to reverse polarity
(3) A grounding terminal on a receptacle, cord
connector, or plug may not be used for
purposes other than grounding
Polarity of
connections
Improper connection of
these conductors (‘hot
and neutral’) is most
prevalent on smaller
branch circuits:
 Standard 120 volt
receptacle outlets
 Cord-and plug-
connected equipment
Reversed Polarity
Reversed polarity is a condition when the
grounded conductor (neutral) is incorrectly
connected to the ungrounded (hot) terminal of a
plug, receptacle, or other type of conductor
Neutral
Hot
1910.304(a)(2)1910.304(a)(2)
Reverse PolarityReverse Polarity
1910.304(a)(2)
NEC Article 200-11
Normal Wiring
Hot
Neutral
1910. 304(b) Branch circuits
1. Reserved
2. Outlet devices. Outlet devices shall have
an ampere rating not less than the load
to be served
1910. 304 (d)(1) Disconnecting
means
1000kV
General. Means shall be provided to disconnect
all conductors in a building or other structure
from the service-entrance conductors.
The disconnecting means shall plainly indicate
whether it is in the open or closed position and
shall be installed at a readily accessible
location nearest the point of entrance of the
service-entrance conductors.
1910. 304 (d)(2) Services
over 600 volts, nominal
Danger
(i) Guarded to make them accessible only to
qualified persons
(ii) Signs warning of high voltage shall be
posted where other than qualified employees
might come in contact with live parts
1910. 304 (e)(1)(vi) Circuit
breakers
1000kV
Danger
Circuit breakers shall clearly indicate whether
they are in the open (off) or closed (on) position
(4) The path to ground from circuits,
equipment, and enclosures shall be
permanent and continuous
1910. 304 (f) Grounding
Grounding
There are two kinds of grounding:
 1. Electrical circuit or system grounding
 2. Electrical equipment grounding
Electrical System Grounding
One conductor of the circuit is
intentionally grounded to earth
Protects circuit from lightning, or other
high voltage contact
Equipment Grounding
All metal frames & enclosures of equipment are
grounded by a permanent connection or bond
The equipment grounding conductor provides a
path for dangerous fault current to return to the
system ground at the supply source should a
fault occur
Grounding Equipment
Connected by Cord and Plug
Exposed non-current carrying metal parts of
cord and plug connected equipment which
may become energized shall be grounded
If in a hazardous location
If operated at over 150 volts
Note that properly bonded conduit and associated
metal enclosures can also serve as a grounding
conductor.
Ground fault circuit
interrupters (GFCI’s)
A GFCI is not an overcurrent device like a fuse
or circuit breaker
GFCI’s are designed to sense an imbalance in
current flow over the normal path
Ground fault circuit
interrupters (GFCI’s)
GFCI contains a special
sensor that monitors the
strength of the magnetic
field around each wire in
the circuit when current is
flowing
The field is proportional to
the amount of current flow
T
If the current flowing in the black (ungrounded)
wire is within 5 milliampers of the current
flowing in the white (grounded) all the current
will flow in the normal path
If the current flow differs by more than 5mA +/-
1mA, the GFCI will quickly open the circuit
Ground fault circuit
interrupters (GFCI’s)
Testing GFCI’s
GFCI’s are complex mechanisms, they must be tested
on a regular basis
Installation must be correct according to the
listing & labeling requirements or the GFCI will not
protect as designed
For permanently mounted types, once a month testing
is recommended
Portable GFCI’s should be tested before each use!
GFCI’s have a test-circuit which imposes an artificial
ground fault when the test button is pushed
Wiring methods, components,
and
equipment
for general use
1910.305(a)(1)(ii) Wiring in ducts
No wiring systems of any type shall be
installed in ducts used to transport
dust, loose stock or flammable vapors
1910.305(a)(2) Temporary wiring
(iii)(F) Lamps for general illumination shall be
protected from accidental contact or breakage
Protection shall be provided by elevation of at
least 7 feet from normal working surface or by a
suitable fixture or lampholder with a guard
1910.305(a)(2) Temporary wiring
(iii)(G) Flexible cords and cables shall be
protected from accidental damage
Sharp corners and projections shall be avoided.
Where passing through doorways or other
pinch points, flexible cords and cables shall be
provided with protection to avoid damage
1910.305(a)(2)(iii)(G) Flexible
Cords
Where passing through doorways or other
pinch points, flexible cords and cables shall be
provided with protection to avoid damage
1910.305 (b) Conductors Entering
Boxes, Cabinets or Fittings
Conductors can be damaged if
they rub against the sharp edges
of cabinets, boxes, or fittings
Where they enter they must be
protected by some type of clamp
or rubber grommet
The device used must close the
hole through which the conductor
passes as well as provide
protection from abrasion
If the conductor is in a conduit
and the conduit fits tightly in the
opening, additional sealing is
not required
The knockouts in cabinets,
boxes, and fittings should be
removed only if conductors are
to be run through them
Open knockouts and other
holes must be closed
1910.305 (b) Conductors Entering
Boxes, Cabinets or Fittings
Conductors Entering Boxes,
Cabinets or Fittings
All pull boxes, junction boxes and fittings must
be provided with approved covers
If covers are metal they must be grounded.
Each outlet box must have a cover, faceplate
or fixture canopy
1910.305(e) Enclosures for
damp or wet locations
Cabinets, cutouts
boxes, fittings, and
panelboards shall be
weatherproof
Switches, circuit
breakers, and
switchboards shall be
in weather proof
enclosures
1910.305 (g)(1) Use of Flexible
Cords & Cables
Flexible cords and shall be approved and
suitable for conditions of use and location*
* The OSHA electric standard
(1910.305) lists specific situations in
which flexible cords may be used
Except for the previously listed exemptions,
flexible cords may not be used for:
 (A) As a substitute for fixed wiring of the structure;
 (B) Where run through holes in walls, ceilings, or
floors;
 (C) Where run through doorways, windows, etc..
1910.305 (g)(1)(iii) Prohibited
uses of flexible cords
There are usually citations when the usage is
obviously not temporary; and,
When the cord is extended to some distant
outlet in order to avoid providing a fixed outlet
where needed
Judgment of application
Identification, Splices and
Terminations
Flexible cords shall only be used in
continuous lengths, no taps or splices
Damaged cord
improperly repaired
Flexible cords shall be connected to devices
and fittings so that strain relief is provided
which will prevent pull from being directly
transmitted to joints or terminal screws
Identification, Splices and
Terminations
1910.305 (g)(2)(ii)
Flexible cords shall be used only in continuous
lengths without splice or tap.
Hard service flexible cords No. 12 or larger may
be repaired if spliced so that the splice retains
the insulation, outer sheath properties, and
usage characteristics of the cord being spliced.
Note: The National Electric Code allows
splice in 14 gauge or greater wire
1910.331 Scope
Covers:
 Qualified persons (those who have training in
avoiding the electrical hazards
 Unqualified persons (those with little or no such
training)
Working on or near the following:
 Premises wiring
 Wiring for connection to supply
 Other wiring
1910.332 Training
Scope:
 The training requirements contained in this section
apply to employees who face a risk of electric shock
that is not reduced to a safe level by the electrical
installation requirements of 1910.303 through
1910.308
 Employees shall be trained in and familiar with the
safety-related work practices required by 1910.331
through 1910.335 that pertain to their respective job
assignments
Footnote to Table S-4
(1) Workers in these groups do not need to be
trained if their work or the work of those they
supervise does not bring them or their
employees close enough to exposed parts of
electric circuits operating at 50 volts or more to
ground for a hazard to exist.
(b)(3) Qualified persons: (i.e. those permitted
to work on or near exposed energized parts)
shall, at a minimum, be trained in and familiar
with the following:
 (i) The skills and techniques necessary to
distinguish exposed live parts from other parts of
electric equipment
 (ii) The skills and techniques necessary to
determine the nominal voltage of exposed live
parts
 (iii) The clearance distances specified in
1910.333(c)
1910.332 Training
1910.333 (a)(1)
Deenergized parts
Live parts to which an employee may be
exposed shall be deenergized before
the employee works on or near them:
 Unless the employer can demonstrate that
deenergizing introduces additional or
increased hazards or is infeasible
 Live parts that operate at less than 50 volts
to ground need not be deenergized if there
will be no increased exposure to electrical
burns or to explosion due to electric arcs
1910.333(b) Working on or
near exposed deenergized
parts
(1) Conductors and parts of electric equipment
that have been deenergized but have not been
locked out or tagged in accordance with
paragraph (b) of this section shall be treated as
energized parts
1910.333(c)(4) Illumination
Employees may not enter spaces containing
exposed energized parts, unless illumination is
provided that enables the employees to
perform the work safely
1910.333(c)(4) Illumination
Employees may not
reach blindly into
areas which may
contain energized
parts.
1910.333(c)(7) Portable
ladders
Portable ladders shall have nonconductive
siderails if they are used where the employee
or the ladder could contact exposed
energized parts
1910.333(c)(8) Conductive
apparel
Conductive articles of jewelry and clothing
(such a watch bands, bracelets, rings, key
chains, necklaces, etc...) may not be worn if
they might contact exposed energized parts
1910.334 Use of equipment
Portable equipment shall be handled in
a manner which will not cause damage
Flexible electric cords connected to
equipment may not be used for raising
or lowering the equipment
Flexible cords may not be fastened with
staples or otherwise hung in such a
fashion as could damage the outer
jacket or insulation
1910.334 (a)(2)(i) Use of equipment
Portable cord and plug connected equipment
and flexible cord sets (extension cords)
visually inspected before use for external
defects (such as loose parts, or damage to
outer jacket or insulation) and for evidence of
possible internal damage (pinched or crushed
outer jacket)
Extension cords which remain connected once
they are put in place and are not exposed to
damage need not be visually inspected until
they are relocated
1910.334 Use of equipment
A flexible cord used with grounding type equipment
shall contain an equipment grounding conductor
Attachment plugs and receptacles may not be
connected or altered in a manner which would
prevent proper continuity of the equipment grounding
conductor at the point where plugs are attached to
receptacles
1910.334 (c)(1) Use
Only qualified persons may perform testing
work on electric circuits or equipment
1910.334 Use of equipment
(c)(2)"Visual inspection." Test instruments and
equipment and all associated test leads,
cables, power cords, probes, and connectors
shall be visually inspected for external defects
and damage before the equipment is used.
If there is a defect or evidence of damage that
might expose an employee to injury, the
defective or damaged item shall be removed
from service, and no employee may use it until
repairs and tests necessary to render the
equipment safe have been made.
1910.335 Safeguards for
personnel protection
(a)(1)Employees working in areas where there
are potential electrical hazards shall be
provided with, and shall use, electrical
protective equipment that is appropriate for the
specific parts of the body to be protected and
for the work to be performed
1910.335 Safeguards for
personnel protection
(a)(1)(ii)Protective equipment shall be
maintained in a safe, reliable condition and
shall be periodically inspected or tested, as
required by 1910.137 *
*1910.137 Electrical protective equipment
1910.335 Safeguards for
personnel protection
(a)(2)(i)When working near exposed energized
conductors or circuit parts, each employee
shall use insulated tools or handling equipment
if the tools or handling equipment might make
contact with such conductors or parts
1910.335 Safeguards for
personnel protection
(b)The following alerting techniques shall be
used to warn and protect employees from
hazards which could cause injury due to
electric shock, burns, or failure of electric
equipment parts:
 Safety signs and tags
 Barricades
 Attendants
1910.335 Safeguards for
personnel protection
(b)(1)Safety signs, safety
symbols, or accident
prevention tags shall be
used where necessary to
warn employees about
electrical hazards which
may endanger them, as
required by 1910.145
1910.335 Safeguards for
personnel protection
(b)(2)Barricades shall be used in conjunction
with safety signs where it is necessary to
prevent or limit employee access to work areas
exposing employees to uninsulated energized
conductors or circuit parts
1910.335 Safeguards for
personnel protection
If signs and barricades do not provide
sufficient warning and protection from electrical
hazards, an attendant shall be stationed to
warn and protect employees
Electrical Safety by OSHA

More Related Content

What's hot

Health & safety training
Health & safety trainingHealth & safety training
Health & safety trainingHarvey Allen
 
Trapping and Crushing in MEWPS - Guidance from Strategic Forum Plant Safety ...
Trapping and Crushing in MEWPS -  Guidance from Strategic Forum Plant Safety ...Trapping and Crushing in MEWPS -  Guidance from Strategic Forum Plant Safety ...
Trapping and Crushing in MEWPS - Guidance from Strategic Forum Plant Safety ...
Alan Bassett
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
Muhammad Izaz
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
Raj Patel
 
Electrical safety slideshare
Electrical safety slideshareElectrical safety slideshare
Electrical safety slideshare
YokeshDhanabal
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
Dabbroto Binoy Bhadra
 
Electrical Safety, Personal Protective Equipment, & Z462 Compliance
Electrical Safety, Personal Protective Equipment, & Z462 ComplianceElectrical Safety, Personal Protective Equipment, & Z462 Compliance
Electrical Safety, Personal Protective Equipment, & Z462 Compliance
CCOHS
 
17. ppe
17. ppe17. ppe
17. ppe
Alan Bassett
 
FIRE & SAFETY Questions
FIRE & SAFETY QuestionsFIRE & SAFETY Questions
FIRE & SAFETY QuestionsSELVAN J
 
Electrical Safety by OSHA
Electrical Safety by OSHAElectrical Safety by OSHA
Electrical Safety by OSHA
Atlantic Training, LLC.
 
Emergency Action Plans By OSHA
Emergency Action Plans By OSHAEmergency Action Plans By OSHA
Emergency Action Plans By OSHA
Atlantic Training, LLC.
 
Safety At Workplace
Safety At WorkplaceSafety At Workplace
Safety At Workplace
Dhara Madhwani
 
New Electrical Safety Present2009
New Electrical Safety Present2009New Electrical Safety Present2009
New Electrical Safety Present2009Nestor Fraga
 
Electrical Safety Audit - FM Pvt ltd.pptx
Electrical Safety Audit - FM Pvt ltd.pptxElectrical Safety Audit - FM Pvt ltd.pptx
Electrical Safety Audit - FM Pvt ltd.pptx
Syed Atif Naseem
 
fire extinguisher types and usage.
fire extinguisher types and usage. fire extinguisher types and usage.
fire extinguisher types and usage. Arabinda Das
 
Incident Report Training
Incident Report TrainingIncident Report Training
Incident Report Training
Hatch Compliance, Inc.
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
prabakaran G
 
LIST OF TRAINING TOPICS
LIST OF TRAINING TOPICSLIST OF TRAINING TOPICS
LIST OF TRAINING TOPICSJohn Cariglio
 
Electrical safety training based on osha 1910 standards sw
Electrical safety training based on osha 1910 standards swElectrical safety training based on osha 1910 standards sw
Electrical safety training based on osha 1910 standards sw
Aniruddha Kulkarni
 

What's hot (20)

Health & safety training
Health & safety trainingHealth & safety training
Health & safety training
 
Trapping and Crushing in MEWPS - Guidance from Strategic Forum Plant Safety ...
Trapping and Crushing in MEWPS -  Guidance from Strategic Forum Plant Safety ...Trapping and Crushing in MEWPS -  Guidance from Strategic Forum Plant Safety ...
Trapping and Crushing in MEWPS - Guidance from Strategic Forum Plant Safety ...
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Electrical safety slideshare
Electrical safety slideshareElectrical safety slideshare
Electrical safety slideshare
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Electrical Safety, Personal Protective Equipment, & Z462 Compliance
Electrical Safety, Personal Protective Equipment, & Z462 ComplianceElectrical Safety, Personal Protective Equipment, & Z462 Compliance
Electrical Safety, Personal Protective Equipment, & Z462 Compliance
 
EHS Presentation
EHS PresentationEHS Presentation
EHS Presentation
 
17. ppe
17. ppe17. ppe
17. ppe
 
FIRE & SAFETY Questions
FIRE & SAFETY QuestionsFIRE & SAFETY Questions
FIRE & SAFETY Questions
 
Electrical Safety by OSHA
Electrical Safety by OSHAElectrical Safety by OSHA
Electrical Safety by OSHA
 
Emergency Action Plans By OSHA
Emergency Action Plans By OSHAEmergency Action Plans By OSHA
Emergency Action Plans By OSHA
 
Safety At Workplace
Safety At WorkplaceSafety At Workplace
Safety At Workplace
 
New Electrical Safety Present2009
New Electrical Safety Present2009New Electrical Safety Present2009
New Electrical Safety Present2009
 
Electrical Safety Audit - FM Pvt ltd.pptx
Electrical Safety Audit - FM Pvt ltd.pptxElectrical Safety Audit - FM Pvt ltd.pptx
Electrical Safety Audit - FM Pvt ltd.pptx
 
fire extinguisher types and usage.
fire extinguisher types and usage. fire extinguisher types and usage.
fire extinguisher types and usage.
 
Incident Report Training
Incident Report TrainingIncident Report Training
Incident Report Training
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
LIST OF TRAINING TOPICS
LIST OF TRAINING TOPICSLIST OF TRAINING TOPICS
LIST OF TRAINING TOPICS
 
Electrical safety training based on osha 1910 standards sw
Electrical safety training based on osha 1910 standards swElectrical safety training based on osha 1910 standards sw
Electrical safety training based on osha 1910 standards sw
 

Similar to Electrical Safety by OSHA

Electrical Safety Training by Georgia Tech
Electrical Safety Training by Georgia TechElectrical Safety Training by Georgia Tech
Electrical Safety Training by Georgia TechAtlantic Training, LLC.
 
Electrical_Safety_for_General_Industry_GA_Tech.ppt
Electrical_Safety_for_General_Industry_GA_Tech.pptElectrical_Safety_for_General_Industry_GA_Tech.ppt
Electrical_Safety_for_General_Industry_GA_Tech.ppt
ROWELTREYES
 
Electronics Mechanics And Machines tools .ppt
Electronics Mechanics And Machines tools .pptElectronics Mechanics And Machines tools .ppt
Electronics Mechanics And Machines tools .ppt
bharathshobhads
 
Electrical_Hazards Electrical Safety.ppt
Electrical_Hazards Electrical Safety.pptElectrical_Hazards Electrical Safety.ppt
Electrical_Hazards Electrical Safety.ppt
SamiranSaha9
 
Electrical hazards2 (1)
 Electrical hazards2 (1) Electrical hazards2 (1)
Electrical hazards2 (1)
jcpdrz
 
Electrical safety.pptx
Electrical safety.pptxElectrical safety.pptx
Electrical safety.pptx
NarayanaMurthy79
 
Electrical Hazards in the Workplace
Electrical Hazards in the WorkplaceElectrical Hazards in the Workplace
Electrical Hazards in the Workplace
Atlantic Training, LLC.
 
Electrical Safety.ppt
Electrical Safety.pptElectrical Safety.ppt
Electrical Safety.ppt
Somasundaram Kailasam
 
10.Electrical and Equipment Safety (1).ppt
10.Electrical and Equipment Safety (1).ppt10.Electrical and Equipment Safety (1).ppt
10.Electrical and Equipment Safety (1).ppt
azmatdbg3
 
10.Electrical and Equipment Safety.ppt
10.Electrical and Equipment Safety.ppt10.Electrical and Equipment Safety.ppt
10.Electrical and Equipment Safety.ppt
anu200770
 
10.Electrical and Equipment Safety.ppt
10.Electrical and Equipment Safety.ppt10.Electrical and Equipment Safety.ppt
10.Electrical and Equipment Safety.ppt
RajaMannar6
 
She training module electrical safety
She training module electrical safetyShe training module electrical safety
She training module electrical safety
sunilkumarkushwaha12
 
Elect. presentation (04).ppt
Elect. presentation (04).pptElect. presentation (04).ppt
Elect. presentation (04).ppt
BgrenergyTarapurreps
 
MU Electrical safety
MU Electrical safetyMU Electrical safety
MU Electrical safetytblackley
 
General Industry 2015 Electric Safety
General Industry 2015 Electric SafetyGeneral Industry 2015 Electric Safety
General Industry 2015 Electric Safety
John Newquist
 
Basic Principles of Electrical Safety.ppt
Basic Principles of Electrical Safety.pptBasic Principles of Electrical Safety.ppt
Basic Principles of Electrical Safety.ppt
Abdulmajeed70384
 
Safety and Security-1.pptx
Safety and Security-1.pptxSafety and Security-1.pptx
Safety and Security-1.pptx
AbdulRahmanPuasa1
 
Lightning and surge transfer to systems presentation by jmv lps
Lightning and surge  transfer to systems presentation by jmv lpsLightning and surge  transfer to systems presentation by jmv lps
Lightning and surge transfer to systems presentation by jmv lps
Mahesh Chandra Manav
 

Similar to Electrical Safety by OSHA (20)

Electrical Safety Training by Georgia Tech
Electrical Safety Training by Georgia TechElectrical Safety Training by Georgia Tech
Electrical Safety Training by Georgia Tech
 
Electrical_Safety_for_General_Industry_GA_Tech.ppt
Electrical_Safety_for_General_Industry_GA_Tech.pptElectrical_Safety_for_General_Industry_GA_Tech.ppt
Electrical_Safety_for_General_Industry_GA_Tech.ppt
 
Electronics Mechanics And Machines tools .ppt
Electronics Mechanics And Machines tools .pptElectronics Mechanics And Machines tools .ppt
Electronics Mechanics And Machines tools .ppt
 
Electrical_Hazards Electrical Safety.ppt
Electrical_Hazards Electrical Safety.pptElectrical_Hazards Electrical Safety.ppt
Electrical_Hazards Electrical Safety.ppt
 
Electrical hazards2 (1)
 Electrical hazards2 (1) Electrical hazards2 (1)
Electrical hazards2 (1)
 
Electrical safety.pptx
Electrical safety.pptxElectrical safety.pptx
Electrical safety.pptx
 
Fire and electrical hazards
Fire and electrical hazardsFire and electrical hazards
Fire and electrical hazards
 
Electrical Hazards in the Workplace
Electrical Hazards in the WorkplaceElectrical Hazards in the Workplace
Electrical Hazards in the Workplace
 
Electrical Safety.ppt
Electrical Safety.pptElectrical Safety.ppt
Electrical Safety.ppt
 
10.Electrical and Equipment Safety (1).ppt
10.Electrical and Equipment Safety (1).ppt10.Electrical and Equipment Safety (1).ppt
10.Electrical and Equipment Safety (1).ppt
 
10.Electrical and Equipment Safety.ppt
10.Electrical and Equipment Safety.ppt10.Electrical and Equipment Safety.ppt
10.Electrical and Equipment Safety.ppt
 
10.Electrical and Equipment Safety.ppt
10.Electrical and Equipment Safety.ppt10.Electrical and Equipment Safety.ppt
10.Electrical and Equipment Safety.ppt
 
She training module electrical safety
She training module electrical safetyShe training module electrical safety
She training module electrical safety
 
1910electric rev0
1910electric rev01910electric rev0
1910electric rev0
 
Elect. presentation (04).ppt
Elect. presentation (04).pptElect. presentation (04).ppt
Elect. presentation (04).ppt
 
MU Electrical safety
MU Electrical safetyMU Electrical safety
MU Electrical safety
 
General Industry 2015 Electric Safety
General Industry 2015 Electric SafetyGeneral Industry 2015 Electric Safety
General Industry 2015 Electric Safety
 
Basic Principles of Electrical Safety.ppt
Basic Principles of Electrical Safety.pptBasic Principles of Electrical Safety.ppt
Basic Principles of Electrical Safety.ppt
 
Safety and Security-1.pptx
Safety and Security-1.pptxSafety and Security-1.pptx
Safety and Security-1.pptx
 
Lightning and surge transfer to systems presentation by jmv lps
Lightning and surge  transfer to systems presentation by jmv lpsLightning and surge  transfer to systems presentation by jmv lps
Lightning and surge transfer to systems presentation by jmv lps
 

More from Atlantic Training, LLC.

Wellness for Supervisors by SWOSU
Wellness for Supervisors by SWOSUWellness for Supervisors by SWOSU
Wellness for Supervisors by SWOSU
Atlantic Training, LLC.
 
Workplace Wellness by PHA
Workplace Wellness by PHAWorkplace Wellness by PHA
Workplace Wellness by PHA
Atlantic Training, LLC.
 
Stress Management Training by SG
Stress Management Training by  SGStress Management Training by  SG
Stress Management Training by SG
Atlantic Training, LLC.
 
Stress Management Training by SW
Stress Management Training by SWStress Management Training by SW
Stress Management Training by SW
Atlantic Training, LLC.
 
Stress and Worker Safety by Pennsylvania L&I
Stress and Worker Safety by Pennsylvania L&IStress and Worker Safety by Pennsylvania L&I
Stress and Worker Safety by Pennsylvania L&I
Atlantic Training, LLC.
 
Respectful Workplace by RDTC
Respectful Workplace by RDTCRespectful Workplace by RDTC
Respectful Workplace by RDTC
Atlantic Training, LLC.
 
Workplace Harassment by CLGW
Workplace Harassment by CLGWWorkplace Harassment by CLGW
Workplace Harassment by CLGW
Atlantic Training, LLC.
 
Workplace Harassment Prevention by UT EAP
Workplace Harassment Prevention by  UT EAPWorkplace Harassment Prevention by  UT EAP
Workplace Harassment Prevention by UT EAP
Atlantic Training, LLC.
 
Welding Safety by Pennsylvania L&I
Welding Safety by Pennsylvania L&IWelding Safety by Pennsylvania L&I
Welding Safety by Pennsylvania L&I
Atlantic Training, LLC.
 
Slips Trips & Falls Training by Signal
Slips Trips & Falls Training by SignalSlips Trips & Falls Training by Signal
Slips Trips & Falls Training by Signal
Atlantic Training, LLC.
 
Preventing Falls, Slips and Trips by MGSU
Preventing Falls, Slips and Trips by MGSUPreventing Falls, Slips and Trips by MGSU
Preventing Falls, Slips and Trips by MGSU
Atlantic Training, LLC.
 
Preventing Workplace Harassment by Pennsylvania L&I
Preventing Workplace Harassment by Pennsylvania L&IPreventing Workplace Harassment by Pennsylvania L&I
Preventing Workplace Harassment by Pennsylvania L&I
Atlantic Training, LLC.
 
Warehouses In Emergencies by WFP Logistics
Warehouses In Emergencies by WFP LogisticsWarehouses In Emergencies by WFP Logistics
Warehouses In Emergencies by WFP Logistics
Atlantic Training, LLC.
 
Prevention of Sexual Harassment by USMC
Prevention of Sexual Harassment by USMCPrevention of Sexual Harassment by USMC
Prevention of Sexual Harassment by USMC
Atlantic Training, LLC.
 
Sexual Harassment by DEOMI
Sexual Harassment by DEOMISexual Harassment by DEOMI
Sexual Harassment by DEOMI
Atlantic Training, LLC.
 
Sexual Harassment in the Workplace Training by Shumaker
Sexual Harassment in the Workplace Training by ShumakerSexual Harassment in the Workplace Training by Shumaker
Sexual Harassment in the Workplace Training by Shumaker
Atlantic Training, LLC.
 
Sexual Harassment Training by NAP
Sexual Harassment Training by NAPSexual Harassment Training by NAP
Sexual Harassment Training by NAP
Atlantic Training, LLC.
 
Scaffolds Training by Pennsylvania L&I
Scaffolds Training by Pennsylvania L&IScaffolds Training by Pennsylvania L&I
Scaffolds Training by Pennsylvania L&I
Atlantic Training, LLC.
 
Supervision
SupervisionSupervision
New Employee Safety Orientation by Oregon State University
New Employee Safety Orientation by Oregon State UniversityNew Employee Safety Orientation by Oregon State University
New Employee Safety Orientation by Oregon State University
Atlantic Training, LLC.
 

More from Atlantic Training, LLC. (20)

Wellness for Supervisors by SWOSU
Wellness for Supervisors by SWOSUWellness for Supervisors by SWOSU
Wellness for Supervisors by SWOSU
 
Workplace Wellness by PHA
Workplace Wellness by PHAWorkplace Wellness by PHA
Workplace Wellness by PHA
 
Stress Management Training by SG
Stress Management Training by  SGStress Management Training by  SG
Stress Management Training by SG
 
Stress Management Training by SW
Stress Management Training by SWStress Management Training by SW
Stress Management Training by SW
 
Stress and Worker Safety by Pennsylvania L&I
Stress and Worker Safety by Pennsylvania L&IStress and Worker Safety by Pennsylvania L&I
Stress and Worker Safety by Pennsylvania L&I
 
Respectful Workplace by RDTC
Respectful Workplace by RDTCRespectful Workplace by RDTC
Respectful Workplace by RDTC
 
Workplace Harassment by CLGW
Workplace Harassment by CLGWWorkplace Harassment by CLGW
Workplace Harassment by CLGW
 
Workplace Harassment Prevention by UT EAP
Workplace Harassment Prevention by  UT EAPWorkplace Harassment Prevention by  UT EAP
Workplace Harassment Prevention by UT EAP
 
Welding Safety by Pennsylvania L&I
Welding Safety by Pennsylvania L&IWelding Safety by Pennsylvania L&I
Welding Safety by Pennsylvania L&I
 
Slips Trips & Falls Training by Signal
Slips Trips & Falls Training by SignalSlips Trips & Falls Training by Signal
Slips Trips & Falls Training by Signal
 
Preventing Falls, Slips and Trips by MGSU
Preventing Falls, Slips and Trips by MGSUPreventing Falls, Slips and Trips by MGSU
Preventing Falls, Slips and Trips by MGSU
 
Preventing Workplace Harassment by Pennsylvania L&I
Preventing Workplace Harassment by Pennsylvania L&IPreventing Workplace Harassment by Pennsylvania L&I
Preventing Workplace Harassment by Pennsylvania L&I
 
Warehouses In Emergencies by WFP Logistics
Warehouses In Emergencies by WFP LogisticsWarehouses In Emergencies by WFP Logistics
Warehouses In Emergencies by WFP Logistics
 
Prevention of Sexual Harassment by USMC
Prevention of Sexual Harassment by USMCPrevention of Sexual Harassment by USMC
Prevention of Sexual Harassment by USMC
 
Sexual Harassment by DEOMI
Sexual Harassment by DEOMISexual Harassment by DEOMI
Sexual Harassment by DEOMI
 
Sexual Harassment in the Workplace Training by Shumaker
Sexual Harassment in the Workplace Training by ShumakerSexual Harassment in the Workplace Training by Shumaker
Sexual Harassment in the Workplace Training by Shumaker
 
Sexual Harassment Training by NAP
Sexual Harassment Training by NAPSexual Harassment Training by NAP
Sexual Harassment Training by NAP
 
Scaffolds Training by Pennsylvania L&I
Scaffolds Training by Pennsylvania L&IScaffolds Training by Pennsylvania L&I
Scaffolds Training by Pennsylvania L&I
 
Supervision
SupervisionSupervision
Supervision
 
New Employee Safety Orientation by Oregon State University
New Employee Safety Orientation by Oregon State UniversityNew Employee Safety Orientation by Oregon State University
New Employee Safety Orientation by Oregon State University
 

Recently uploaded

In the Adani-Hindenburg case, what is SEBI investigating.pptx
In the Adani-Hindenburg case, what is SEBI investigating.pptxIn the Adani-Hindenburg case, what is SEBI investigating.pptx
In the Adani-Hindenburg case, what is SEBI investigating.pptx
Adani case
 
3.0 Project 2_ Developing My Brand Identity Kit.pptx
3.0 Project 2_ Developing My Brand Identity Kit.pptx3.0 Project 2_ Developing My Brand Identity Kit.pptx
3.0 Project 2_ Developing My Brand Identity Kit.pptx
tanyjahb
 
Auditing study material for b.com final year students
Auditing study material for b.com final year  studentsAuditing study material for b.com final year  students
Auditing study material for b.com final year students
narasimhamurthyh4
 
Creative Web Design Company in Singapore
Creative Web Design Company in SingaporeCreative Web Design Company in Singapore
Creative Web Design Company in Singapore
techboxsqauremedia
 
Agency Managed Advisory Board As a Solution To Career Path Defining Business ...
Agency Managed Advisory Board As a Solution To Career Path Defining Business ...Agency Managed Advisory Board As a Solution To Career Path Defining Business ...
Agency Managed Advisory Board As a Solution To Career Path Defining Business ...
Boris Ziegler
 
Evgen Osmak: Methods of key project parameters estimation: from the shaman-in...
Evgen Osmak: Methods of key project parameters estimation: from the shaman-in...Evgen Osmak: Methods of key project parameters estimation: from the shaman-in...
Evgen Osmak: Methods of key project parameters estimation: from the shaman-in...
Lviv Startup Club
 
一比一原版加拿大渥太华大学毕业证(uottawa毕业证书)如何办理
一比一原版加拿大渥太华大学毕业证(uottawa毕业证书)如何办理一比一原版加拿大渥太华大学毕业证(uottawa毕业证书)如何办理
一比一原版加拿大渥太华大学毕业证(uottawa毕业证书)如何办理
taqyed
 
Exploring Patterns of Connection with Social Dreaming
Exploring Patterns of Connection with Social DreamingExploring Patterns of Connection with Social Dreaming
Exploring Patterns of Connection with Social Dreaming
Nicola Wreford-Howard
 
Helen Lubchak: Тренди в управлінні проєктами та miltech (UA)
Helen Lubchak: Тренди в управлінні проєктами та miltech (UA)Helen Lubchak: Тренди в управлінні проєктами та miltech (UA)
Helen Lubchak: Тренди в управлінні проєктами та miltech (UA)
Lviv Startup Club
 
amptalk_RecruitingDeck_english_2024.06.05
amptalk_RecruitingDeck_english_2024.06.05amptalk_RecruitingDeck_english_2024.06.05
amptalk_RecruitingDeck_english_2024.06.05
marketing317746
 
The Influence of Marketing Strategy and Market Competition on Business Perfor...
The Influence of Marketing Strategy and Market Competition on Business Perfor...The Influence of Marketing Strategy and Market Competition on Business Perfor...
The Influence of Marketing Strategy and Market Competition on Business Perfor...
Adam Smith
 
Mastering B2B Payments Webinar from BlueSnap
Mastering B2B Payments Webinar from BlueSnapMastering B2B Payments Webinar from BlueSnap
Mastering B2B Payments Webinar from BlueSnap
Norma Mushkat Gaffin
 
Creative Web Design Company in Singapore
Creative Web Design Company in SingaporeCreative Web Design Company in Singapore
Creative Web Design Company in Singapore
techboxsqauremedia
 
The Influence of Marketing Strategy and Market Competition on Business Perfor...
The Influence of Marketing Strategy and Market Competition on Business Perfor...The Influence of Marketing Strategy and Market Competition on Business Perfor...
The Influence of Marketing Strategy and Market Competition on Business Perfor...
Adam Smith
 
Anny Serafina Love - Letter of Recommendation by Kellen Harkins, MS.
Anny Serafina Love - Letter of Recommendation by Kellen Harkins, MS.Anny Serafina Love - Letter of Recommendation by Kellen Harkins, MS.
Anny Serafina Love - Letter of Recommendation by Kellen Harkins, MS.
AnnySerafinaLove
 
Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)
Lviv Startup Club
 
An introduction to the cryptocurrency investment platform Binance Savings.
An introduction to the cryptocurrency investment platform Binance Savings.An introduction to the cryptocurrency investment platform Binance Savings.
An introduction to the cryptocurrency investment platform Binance Savings.
Any kyc Account
 
Event Report - SAP Sapphire 2024 Orlando - lots of innovation and old challenges
Event Report - SAP Sapphire 2024 Orlando - lots of innovation and old challengesEvent Report - SAP Sapphire 2024 Orlando - lots of innovation and old challenges
Event Report - SAP Sapphire 2024 Orlando - lots of innovation and old challenges
Holger Mueller
 
ikea_woodgreen_petscharity_cat-alogue_digital.pdf
ikea_woodgreen_petscharity_cat-alogue_digital.pdfikea_woodgreen_petscharity_cat-alogue_digital.pdf
ikea_woodgreen_petscharity_cat-alogue_digital.pdf
agatadrynko
 
Premium MEAN Stack Development Solutions for Modern Businesses
Premium MEAN Stack Development Solutions for Modern BusinessesPremium MEAN Stack Development Solutions for Modern Businesses
Premium MEAN Stack Development Solutions for Modern Businesses
SynapseIndia
 

Recently uploaded (20)

In the Adani-Hindenburg case, what is SEBI investigating.pptx
In the Adani-Hindenburg case, what is SEBI investigating.pptxIn the Adani-Hindenburg case, what is SEBI investigating.pptx
In the Adani-Hindenburg case, what is SEBI investigating.pptx
 
3.0 Project 2_ Developing My Brand Identity Kit.pptx
3.0 Project 2_ Developing My Brand Identity Kit.pptx3.0 Project 2_ Developing My Brand Identity Kit.pptx
3.0 Project 2_ Developing My Brand Identity Kit.pptx
 
Auditing study material for b.com final year students
Auditing study material for b.com final year  studentsAuditing study material for b.com final year  students
Auditing study material for b.com final year students
 
Creative Web Design Company in Singapore
Creative Web Design Company in SingaporeCreative Web Design Company in Singapore
Creative Web Design Company in Singapore
 
Agency Managed Advisory Board As a Solution To Career Path Defining Business ...
Agency Managed Advisory Board As a Solution To Career Path Defining Business ...Agency Managed Advisory Board As a Solution To Career Path Defining Business ...
Agency Managed Advisory Board As a Solution To Career Path Defining Business ...
 
Evgen Osmak: Methods of key project parameters estimation: from the shaman-in...
Evgen Osmak: Methods of key project parameters estimation: from the shaman-in...Evgen Osmak: Methods of key project parameters estimation: from the shaman-in...
Evgen Osmak: Methods of key project parameters estimation: from the shaman-in...
 
一比一原版加拿大渥太华大学毕业证(uottawa毕业证书)如何办理
一比一原版加拿大渥太华大学毕业证(uottawa毕业证书)如何办理一比一原版加拿大渥太华大学毕业证(uottawa毕业证书)如何办理
一比一原版加拿大渥太华大学毕业证(uottawa毕业证书)如何办理
 
Exploring Patterns of Connection with Social Dreaming
Exploring Patterns of Connection with Social DreamingExploring Patterns of Connection with Social Dreaming
Exploring Patterns of Connection with Social Dreaming
 
Helen Lubchak: Тренди в управлінні проєктами та miltech (UA)
Helen Lubchak: Тренди в управлінні проєктами та miltech (UA)Helen Lubchak: Тренди в управлінні проєктами та miltech (UA)
Helen Lubchak: Тренди в управлінні проєктами та miltech (UA)
 
amptalk_RecruitingDeck_english_2024.06.05
amptalk_RecruitingDeck_english_2024.06.05amptalk_RecruitingDeck_english_2024.06.05
amptalk_RecruitingDeck_english_2024.06.05
 
The Influence of Marketing Strategy and Market Competition on Business Perfor...
The Influence of Marketing Strategy and Market Competition on Business Perfor...The Influence of Marketing Strategy and Market Competition on Business Perfor...
The Influence of Marketing Strategy and Market Competition on Business Perfor...
 
Mastering B2B Payments Webinar from BlueSnap
Mastering B2B Payments Webinar from BlueSnapMastering B2B Payments Webinar from BlueSnap
Mastering B2B Payments Webinar from BlueSnap
 
Creative Web Design Company in Singapore
Creative Web Design Company in SingaporeCreative Web Design Company in Singapore
Creative Web Design Company in Singapore
 
The Influence of Marketing Strategy and Market Competition on Business Perfor...
The Influence of Marketing Strategy and Market Competition on Business Perfor...The Influence of Marketing Strategy and Market Competition on Business Perfor...
The Influence of Marketing Strategy and Market Competition on Business Perfor...
 
Anny Serafina Love - Letter of Recommendation by Kellen Harkins, MS.
Anny Serafina Love - Letter of Recommendation by Kellen Harkins, MS.Anny Serafina Love - Letter of Recommendation by Kellen Harkins, MS.
Anny Serafina Love - Letter of Recommendation by Kellen Harkins, MS.
 
Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)
 
An introduction to the cryptocurrency investment platform Binance Savings.
An introduction to the cryptocurrency investment platform Binance Savings.An introduction to the cryptocurrency investment platform Binance Savings.
An introduction to the cryptocurrency investment platform Binance Savings.
 
Event Report - SAP Sapphire 2024 Orlando - lots of innovation and old challenges
Event Report - SAP Sapphire 2024 Orlando - lots of innovation and old challengesEvent Report - SAP Sapphire 2024 Orlando - lots of innovation and old challenges
Event Report - SAP Sapphire 2024 Orlando - lots of innovation and old challenges
 
ikea_woodgreen_petscharity_cat-alogue_digital.pdf
ikea_woodgreen_petscharity_cat-alogue_digital.pdfikea_woodgreen_petscharity_cat-alogue_digital.pdf
ikea_woodgreen_petscharity_cat-alogue_digital.pdf
 
Premium MEAN Stack Development Solutions for Modern Businesses
Premium MEAN Stack Development Solutions for Modern BusinessesPremium MEAN Stack Development Solutions for Modern Businesses
Premium MEAN Stack Development Solutions for Modern Businesses
 

Electrical Safety by OSHA

  • 1.
  • 2. 2 Subpart S - Electrical (1910.301 - 399) 515 457 396 347 290 303(g)(2)(i) 305(b)(1) 304(f)(4) 305(b)(2) 305(g)(1)(iii) Live parts Grounding path Electrical box covers Conductors entering cabinets/boxes/fittings protected from abrasion Standard:1910. Use of flexible cords and cables * * * * * *Average number of Federal OSHA citations issued between 2000 and 2003
  • 3. DEFINITION A physical agency caused by the motion of electrons, protons, and other charged particles, manifesting itself as an attraction, repulsion, magnetic, luminous, and heating effects, etc.
  • 4. ELEMENTS & ATOMS Every known substance – solid, liquid or gas is composed of elements An atom is the smallest particle of an element that retains all the properties of that element Each element has it’s own kind of atom
  • 5. ATOMS Inner part composed of protons & neutrons Outer part composed of electrons Protons = positive charge Neutrons = no charge Electrons = negative charge
  • 6. ATOMS Each element has a definite number of electrons ----and the same number of protons They are oppositely charged and therefore attract each other. This tends to hold the electrons in orbit around the atom.
  • 8. FREE ELECTRONS Some atoms are easily moved out of orbit The ability to move or flow is the basis of current electricity If channeled in a given direction, a flow of electrons occurs --- when flowed through a conductor it is dynamic electricity
  • 9. ELECTICAL MATERIALS CONDUCTOR – contains many free electrons --- gold, copper, silver, aluminum INSULATOR – contains few free electrons-Usually non-metallic such as wood, rubber, glass, etc
  • 10. GENERATING ELECTRICITY Friction, pressure, heat, light, chemical reaction, and magnetism Magnetism is most practical & inexpensive method Electricity is produced when a magnet is moved past a piece of wire, or wire is moved through a magnetic field
  • 11. VOLTAGE, CURRENT, & RESISTANCE VOLTAGE – unit of measurement of electromotive force (EMF) CURRENT - Continuous movement of electrons past a given point. (measured in amperes) RESISTANCE – Opposition to movement of electrons. Makes it possible to generate heat, control current flow, & supply correct voltage to devices
  • 12. OHM’S LAW George Simon Ohm  Formulated a mathematical relationship between:  Current  Voltage  Resistance  Resistance = Impedance  Resistance = DC  Impedance = AC  Interchangeable – Most Branch circuits
  • 13. DIRECT CURRENT Always flows in one direction Used to charge batteries, run some motors, operate magnetic lifting devices and welding equipment.
  • 14. ALTERNATING CURRRENT More common in electrical work Changes rapidly in both direction and value Power companies produce power cheaper with alternating current
  • 15. ELECTRICAL HAZARDS SHOCK. Electric shock occurs when the human body becomes part of the path through which current flows. The direct result can be electrocution. The indirect result can be injury resulting from a fall or movement into machinery because of a shock
  • 16. ELECTRICAL HAZARDS BURNS. Burns can result when a person touches electrical wiring or equipment that is energized. ARC-BLAST. Arc-blasts occur from high- amperage currents arcing through the air. This can be caused by accidental contact with energized components or equipment failure.
  • 17. Arc Flash and Arc Blasts Arc Flash:  80%-Burns due to ignition of clothing  Temperature-35,000 F  Fatal Burns-10 ft.  2000 people hospitalized with burns  Molten metal Arc Blast:  Pressure Wave  Heat  Molten metal  Destruction of structures and life
  • 18. Arc Blast Cause  Short Circuit caused by working on energized equipment  Dropped Tool  Occurs in milliseconds  Temp: 30,000 degrees  Air expands very violently  15 tons of pressure
  • 19. ELECTRICAL HAZARDS ARC-BLAST. The three primary hazards associated with an arc- blast are: Thermal radiation. Pressure Wave. Projectiles.
  • 20. ELECTRICAL HAZARDS EXPLOSIONS. Explosions occur when electricity provides a source of ignition for an explosive mixture in the atmosphere.
  • 21. ELECTRICAL HAZARDS FIRES. Electricity is one of the most common causes of fires both in the home and in the workplace. Defective or misused electrical equipment is a major cause.
  • 22. EFFECTS ON THE HUMAN BODY Depends on: Current and Voltage Resistance Path through body Duration of shock
  • 23. Effects of AC Electricity More than 3 mA- Painful shock- cause indirect accident More than 10 mA- Muscle contraction – “No Let Go” danger More than 30 mA- Lung paralysis, usually temporary
  • 24. Effects of AC Electricity More than 50 mA- Ventricular fibrillation, usually fatal 100 mA to 4 A- Certain ventricular fibrillation, fatal Over 4 A- Heart paralysis, severe burns
  • 25. Effects Protection  Circuit Breakers  Fuses  15 or 20 amps  Property/equipment protection
  • 26. Conductors American Wire Gauge  12 gauge – 20 amps (Safely)  14 gauge – 15 amps  10 gauge – 30 amps What determines amount of amps through a circuit?  How much the equipment draws  How much “stuff” plugged in
  • 27. Protective Devices Fuses Circuit Breakers  Trip or break circuit breakers if conductors exceed their ampacity
  • 28. Summary Current (I) Voltage (E or v) Resistance (R) (Ohms)
  • 30. Wires Black = hot = Ungrounded Conductor White = neutral = Grounded Conductor (connected to grounding electrode/Grounding rod)
  • 31.
  • 32. How to check Wiring Checks  Testers  Different types
  • 33. Instruments Normal 3 light Tester  Won’t check resistance to ground Others - Check what the 3 light tester will  Also checks resistance for ground
  • 34. Double Insulated Indicators  No ground pin  Plastic tool case  Listed by NTL  Marked as double insulated  Square in a square  Marked “double insulated”
  • 35. 1910.302 Electrical Utilization Systems Scope:  (a) Covers electrical installations and utilization equipment installed or used within or on buildings, structures, and other premises
  • 36. (a) Approval. The conductors and equipment required or permitted by this subpart shall be acceptable only if approved 1910.303 General Requirements
  • 37. 1910.303 (b) Examination, installation and use Employer Obligation:  (1) Electrical equipment shall be free from recognized hazards that are likely to cause death or serious physical harm to employees
  • 38. (1) Examination. Safety of equipment shall determined using the following considerations:  (i) Suitability of equipment for an identified purpose may be evidenced by listing or labeling for that identified purpose 1910.303 (b) Examination, installation, and use
  • 39. 5 • 1910.303(a) Approval – All electrical conductors and equipment shall be approved. UNDERWRITERS LABORATORIES ENCLOSED SWITCH Issue AK 3225 LISTED 1910.303(a) NEC Article 110-2 6
  • 40. 1910.303 (f) Identification of Disconnecting Means and Circuits Each disconnecting means legibly marked to indicate its purpose  (Unless so arranged so the purpose is evident) Disconnect switch for motor number 3
  • 41. 1910.303 (f) ID of Disconnecting Means Each service, feeder, and branch circuit, at its overcurrent device, legibly and durably marked to indicate its purpose Switches and circuit breakers must be clearly labeled to indicate its circuit’s function Circuit breaker for motors 1,2,3, and 4
  • 42. 1910.303(g) Working Space (1) Sufficient access and working space around all electrical equipment, provided & maintained to provide ready and safe operation and maintenance (ii) Not used for storage (ii) If located in aisle or general open area, working space shall be suitably guarded
  • 43. 1910.303(g)(1)(v) Illumination Illumination provided for all working spaces about service equipment, switchboards, panel- boards, and motor control centers installed indoors.
  • 44. 1910.303(g)(1)(vi) Headroom The minimum headroom of working spaces about service equipment, switchboards, panel- boards, or motor control centers shall be 6 feet 3 inches 6'3"
  • 45. (2)(i) Live parts of electric equipment operating at 50 volts or more guarded against accidental contact by approved cabinets 1910.303(g) Guarding of live parts
  • 46. (g)(2)(i) or other forms of approved enclosures, or by any of the following means:  (A) By location in a room, vault, accessible only to qualified persons  (B) By permanent, substantial partitions or screens  (C) By location on a suitable balcony or platform as to exclude unqualified persons  (D) By elevation of 8 feet or more above the floor or other working surface Guarding live parts – 1910.303
  • 47. 1910. 303(g) Guarding live parts (2)(iii) Entrances to rooms and other guarded locations containing exposed live parts shall be marked with conspicuous warning signs forbidding unqualified persons to enter
  • 48. 1910.303(h)(3)(ii) Illumination Adequate illumination for all working spaces about electric equipment The lighting outlets arranged that persons changing lamps or making repairs on the lighting system will not be endangered by live parts or other equipment
  • 49.
  • 50. 1910.304(a)(1) Identification of Conductors A conductor used as a grounded conductor shall be identifiable and distinguishable from all other conductors. A conductor used as an equipment grounding conductor shall be identifiable and distinguishable from all other conductors
  • 51. Identification of Conductors Grounded conductor and equipment grounding conductors marked or color coated So that employees can i.d. and tell apart Grounded conductor is an energized circuit (conductor that is connected to earth through the system ground) Commonly referred to as the neutral
  • 52. Grounding Conductors Equipment grounding conductor acts as a safeguard against insulation failure or faults in the other circuit conductors Not an energized conductor under normal conditions. Energized if a leak or fault in the normal current path Directs current back to the source Enabling fuses or circuit breakers to operate
  • 53. Identification of Conductors Grounded conductor i.d. and distinguished from other conductors w/ white or gray Equipment grounding conductor i.d. and distinguished w/ green, green w/ yellow stripes, or bare
  • 54. 1910.304(a) Use and identification of grounded and grounding conductors (2) No grounded conductor may be attached to any terminal or lead so as to reverse polarity (3) A grounding terminal on a receptacle, cord connector, or plug may not be used for purposes other than grounding
  • 55.
  • 56. Polarity of connections Improper connection of these conductors (‘hot and neutral’) is most prevalent on smaller branch circuits:  Standard 120 volt receptacle outlets  Cord-and plug- connected equipment
  • 57. Reversed Polarity Reversed polarity is a condition when the grounded conductor (neutral) is incorrectly connected to the ungrounded (hot) terminal of a plug, receptacle, or other type of conductor
  • 59. 1910. 304(b) Branch circuits 1. Reserved 2. Outlet devices. Outlet devices shall have an ampere rating not less than the load to be served
  • 60. 1910. 304 (d)(1) Disconnecting means 1000kV General. Means shall be provided to disconnect all conductors in a building or other structure from the service-entrance conductors. The disconnecting means shall plainly indicate whether it is in the open or closed position and shall be installed at a readily accessible location nearest the point of entrance of the service-entrance conductors.
  • 61. 1910. 304 (d)(2) Services over 600 volts, nominal Danger (i) Guarded to make them accessible only to qualified persons (ii) Signs warning of high voltage shall be posted where other than qualified employees might come in contact with live parts
  • 62. 1910. 304 (e)(1)(vi) Circuit breakers 1000kV Danger Circuit breakers shall clearly indicate whether they are in the open (off) or closed (on) position
  • 63. (4) The path to ground from circuits, equipment, and enclosures shall be permanent and continuous 1910. 304 (f) Grounding
  • 64. Grounding There are two kinds of grounding:  1. Electrical circuit or system grounding  2. Electrical equipment grounding
  • 65. Electrical System Grounding One conductor of the circuit is intentionally grounded to earth Protects circuit from lightning, or other high voltage contact
  • 66. Equipment Grounding All metal frames & enclosures of equipment are grounded by a permanent connection or bond The equipment grounding conductor provides a path for dangerous fault current to return to the system ground at the supply source should a fault occur
  • 67. Grounding Equipment Connected by Cord and Plug Exposed non-current carrying metal parts of cord and plug connected equipment which may become energized shall be grounded If in a hazardous location If operated at over 150 volts
  • 68.
  • 69. Note that properly bonded conduit and associated metal enclosures can also serve as a grounding conductor.
  • 70. Ground fault circuit interrupters (GFCI’s) A GFCI is not an overcurrent device like a fuse or circuit breaker GFCI’s are designed to sense an imbalance in current flow over the normal path
  • 71. Ground fault circuit interrupters (GFCI’s) GFCI contains a special sensor that monitors the strength of the magnetic field around each wire in the circuit when current is flowing The field is proportional to the amount of current flow T
  • 72. If the current flowing in the black (ungrounded) wire is within 5 milliampers of the current flowing in the white (grounded) all the current will flow in the normal path If the current flow differs by more than 5mA +/- 1mA, the GFCI will quickly open the circuit Ground fault circuit interrupters (GFCI’s)
  • 73.
  • 74. Testing GFCI’s GFCI’s are complex mechanisms, they must be tested on a regular basis Installation must be correct according to the listing & labeling requirements or the GFCI will not protect as designed For permanently mounted types, once a month testing is recommended Portable GFCI’s should be tested before each use! GFCI’s have a test-circuit which imposes an artificial ground fault when the test button is pushed
  • 76. 1910.305(a)(1)(ii) Wiring in ducts No wiring systems of any type shall be installed in ducts used to transport dust, loose stock or flammable vapors
  • 77. 1910.305(a)(2) Temporary wiring (iii)(F) Lamps for general illumination shall be protected from accidental contact or breakage Protection shall be provided by elevation of at least 7 feet from normal working surface or by a suitable fixture or lampholder with a guard
  • 78. 1910.305(a)(2) Temporary wiring (iii)(G) Flexible cords and cables shall be protected from accidental damage Sharp corners and projections shall be avoided. Where passing through doorways or other pinch points, flexible cords and cables shall be provided with protection to avoid damage
  • 79. 1910.305(a)(2)(iii)(G) Flexible Cords Where passing through doorways or other pinch points, flexible cords and cables shall be provided with protection to avoid damage
  • 80. 1910.305 (b) Conductors Entering Boxes, Cabinets or Fittings Conductors can be damaged if they rub against the sharp edges of cabinets, boxes, or fittings Where they enter they must be protected by some type of clamp or rubber grommet The device used must close the hole through which the conductor passes as well as provide protection from abrasion
  • 81. If the conductor is in a conduit and the conduit fits tightly in the opening, additional sealing is not required The knockouts in cabinets, boxes, and fittings should be removed only if conductors are to be run through them Open knockouts and other holes must be closed 1910.305 (b) Conductors Entering Boxes, Cabinets or Fittings
  • 82. Conductors Entering Boxes, Cabinets or Fittings All pull boxes, junction boxes and fittings must be provided with approved covers If covers are metal they must be grounded. Each outlet box must have a cover, faceplate or fixture canopy
  • 83. 1910.305(e) Enclosures for damp or wet locations Cabinets, cutouts boxes, fittings, and panelboards shall be weatherproof Switches, circuit breakers, and switchboards shall be in weather proof enclosures
  • 84. 1910.305 (g)(1) Use of Flexible Cords & Cables Flexible cords and shall be approved and suitable for conditions of use and location* * The OSHA electric standard (1910.305) lists specific situations in which flexible cords may be used
  • 85. Except for the previously listed exemptions, flexible cords may not be used for:  (A) As a substitute for fixed wiring of the structure;  (B) Where run through holes in walls, ceilings, or floors;  (C) Where run through doorways, windows, etc.. 1910.305 (g)(1)(iii) Prohibited uses of flexible cords
  • 86. There are usually citations when the usage is obviously not temporary; and, When the cord is extended to some distant outlet in order to avoid providing a fixed outlet where needed Judgment of application
  • 87. Identification, Splices and Terminations Flexible cords shall only be used in continuous lengths, no taps or splices Damaged cord improperly repaired
  • 88. Flexible cords shall be connected to devices and fittings so that strain relief is provided which will prevent pull from being directly transmitted to joints or terminal screws Identification, Splices and Terminations
  • 89. 1910.305 (g)(2)(ii) Flexible cords shall be used only in continuous lengths without splice or tap. Hard service flexible cords No. 12 or larger may be repaired if spliced so that the splice retains the insulation, outer sheath properties, and usage characteristics of the cord being spliced. Note: The National Electric Code allows splice in 14 gauge or greater wire
  • 90.
  • 91. 1910.331 Scope Covers:  Qualified persons (those who have training in avoiding the electrical hazards  Unqualified persons (those with little or no such training) Working on or near the following:  Premises wiring  Wiring for connection to supply  Other wiring
  • 92. 1910.332 Training Scope:  The training requirements contained in this section apply to employees who face a risk of electric shock that is not reduced to a safe level by the electrical installation requirements of 1910.303 through 1910.308  Employees shall be trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertain to their respective job assignments
  • 93. Footnote to Table S-4 (1) Workers in these groups do not need to be trained if their work or the work of those they supervise does not bring them or their employees close enough to exposed parts of electric circuits operating at 50 volts or more to ground for a hazard to exist.
  • 94. (b)(3) Qualified persons: (i.e. those permitted to work on or near exposed energized parts) shall, at a minimum, be trained in and familiar with the following:  (i) The skills and techniques necessary to distinguish exposed live parts from other parts of electric equipment  (ii) The skills and techniques necessary to determine the nominal voltage of exposed live parts  (iii) The clearance distances specified in 1910.333(c) 1910.332 Training
  • 95. 1910.333 (a)(1) Deenergized parts Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them:  Unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible  Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs
  • 96. 1910.333(b) Working on or near exposed deenergized parts (1) Conductors and parts of electric equipment that have been deenergized but have not been locked out or tagged in accordance with paragraph (b) of this section shall be treated as energized parts
  • 97. 1910.333(c)(4) Illumination Employees may not enter spaces containing exposed energized parts, unless illumination is provided that enables the employees to perform the work safely
  • 98. 1910.333(c)(4) Illumination Employees may not reach blindly into areas which may contain energized parts.
  • 99. 1910.333(c)(7) Portable ladders Portable ladders shall have nonconductive siderails if they are used where the employee or the ladder could contact exposed energized parts
  • 100. 1910.333(c)(8) Conductive apparel Conductive articles of jewelry and clothing (such a watch bands, bracelets, rings, key chains, necklaces, etc...) may not be worn if they might contact exposed energized parts
  • 101. 1910.334 Use of equipment Portable equipment shall be handled in a manner which will not cause damage Flexible electric cords connected to equipment may not be used for raising or lowering the equipment Flexible cords may not be fastened with staples or otherwise hung in such a fashion as could damage the outer jacket or insulation
  • 102. 1910.334 (a)(2)(i) Use of equipment Portable cord and plug connected equipment and flexible cord sets (extension cords) visually inspected before use for external defects (such as loose parts, or damage to outer jacket or insulation) and for evidence of possible internal damage (pinched or crushed outer jacket) Extension cords which remain connected once they are put in place and are not exposed to damage need not be visually inspected until they are relocated
  • 103. 1910.334 Use of equipment A flexible cord used with grounding type equipment shall contain an equipment grounding conductor Attachment plugs and receptacles may not be connected or altered in a manner which would prevent proper continuity of the equipment grounding conductor at the point where plugs are attached to receptacles
  • 104. 1910.334 (c)(1) Use Only qualified persons may perform testing work on electric circuits or equipment
  • 105. 1910.334 Use of equipment (c)(2)"Visual inspection." Test instruments and equipment and all associated test leads, cables, power cords, probes, and connectors shall be visually inspected for external defects and damage before the equipment is used. If there is a defect or evidence of damage that might expose an employee to injury, the defective or damaged item shall be removed from service, and no employee may use it until repairs and tests necessary to render the equipment safe have been made.
  • 106. 1910.335 Safeguards for personnel protection (a)(1)Employees working in areas where there are potential electrical hazards shall be provided with, and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed
  • 107. 1910.335 Safeguards for personnel protection (a)(1)(ii)Protective equipment shall be maintained in a safe, reliable condition and shall be periodically inspected or tested, as required by 1910.137 * *1910.137 Electrical protective equipment
  • 108. 1910.335 Safeguards for personnel protection (a)(2)(i)When working near exposed energized conductors or circuit parts, each employee shall use insulated tools or handling equipment if the tools or handling equipment might make contact with such conductors or parts
  • 109. 1910.335 Safeguards for personnel protection (b)The following alerting techniques shall be used to warn and protect employees from hazards which could cause injury due to electric shock, burns, or failure of electric equipment parts:  Safety signs and tags  Barricades  Attendants
  • 110. 1910.335 Safeguards for personnel protection (b)(1)Safety signs, safety symbols, or accident prevention tags shall be used where necessary to warn employees about electrical hazards which may endanger them, as required by 1910.145
  • 111. 1910.335 Safeguards for personnel protection (b)(2)Barricades shall be used in conjunction with safety signs where it is necessary to prevent or limit employee access to work areas exposing employees to uninsulated energized conductors or circuit parts
  • 112. 1910.335 Safeguards for personnel protection If signs and barricades do not provide sufficient warning and protection from electrical hazards, an attendant shall be stationed to warn and protect employees

Editor's Notes

  1. Subpart S