Engineering Final Year Project Report on "Electrical Safety and Protection of...Pratap Bhunia
Substation Network and Load Distribution
Substation Network Design
Civil Works Specification
Various Subsystems in Substation and Their Functions
Substation Equipment and Their Functions
Design of Capacity of Transmission Lines
Calculation of Line Constants and SIL
Bus Bar Arrangement
Power Transformer
Substation Earthing
Circuit Breaker
Isolator
Current Transformer
Capacitor Voltage Transformer
Lightning Surge
Switching Surge
Lightning Arrester
Surge Absorber
About
Indigenized remote control interface card suitable for MAFI system CCR equipment. Compatible for IDM8000 CCR. Backplane mounted serial and TCP/Ethernet communication module for CCR remote access. IDM 8000 CCR remote control on serial and TCP protocol.
• Remote control: Parallel or serial interface.
• Compatible with MAFI CCR system.
• Compatible with IDM8000 CCR.
• Compatible with Backplane mount serial communication.
• Compatible with commercial and Defence aviation CCR system.
• Remote control system for accessing CCR and allied system over serial or TCP.
• Indigenized local Support/presence in India.
• Easy in configuration using DIP switches.
Technical Specifications
Indigenized remote control interface card suitable for MAFI system CCR equipment. Compatible for IDM8000 CCR. Backplane mounted serial and TCP/Ethernet communication module for CCR remote access. IDM 8000 CCR remote control on serial and TCP protocol.
Key Features
Indigenized remote control interface card suitable for MAFI system CCR equipment. Compatible for IDM8000 CCR. Backplane mounted serial and TCP/Ethernet communication module for CCR remote access. IDM 8000 CCR remote control on serial and TCP protocol.
• Remote control: Parallel or serial interface
• Compatible with MAFI CCR system
• Copatiable with IDM8000 CCR
• Compatible with Backplane mount serial communication.
• Compatible with commercial and Defence aviation CCR system.
• Remote control system for accessing CCR and allied system over serial or TCP.
• Indigenized local Support/presence in India.
Application
• Remote control: Parallel or serial interface.
• Compatible with MAFI CCR system.
• Compatible with IDM8000 CCR.
• Compatible with Backplane mount serial communication.
• Compatible with commercial and Defence aviation CCR system.
• Remote control system for accessing CCR and allied system over serial or TCP.
• Indigenized local Support/presence in India.
• Easy in configuration using DIP switches.
Engineering Final Year Project Report on "Electrical Safety and Protection of...Pratap Bhunia
Substation Network and Load Distribution
Substation Network Design
Civil Works Specification
Various Subsystems in Substation and Their Functions
Substation Equipment and Their Functions
Design of Capacity of Transmission Lines
Calculation of Line Constants and SIL
Bus Bar Arrangement
Power Transformer
Substation Earthing
Circuit Breaker
Isolator
Current Transformer
Capacitor Voltage Transformer
Lightning Surge
Switching Surge
Lightning Arrester
Surge Absorber
About
Indigenized remote control interface card suitable for MAFI system CCR equipment. Compatible for IDM8000 CCR. Backplane mounted serial and TCP/Ethernet communication module for CCR remote access. IDM 8000 CCR remote control on serial and TCP protocol.
• Remote control: Parallel or serial interface.
• Compatible with MAFI CCR system.
• Compatible with IDM8000 CCR.
• Compatible with Backplane mount serial communication.
• Compatible with commercial and Defence aviation CCR system.
• Remote control system for accessing CCR and allied system over serial or TCP.
• Indigenized local Support/presence in India.
• Easy in configuration using DIP switches.
Technical Specifications
Indigenized remote control interface card suitable for MAFI system CCR equipment. Compatible for IDM8000 CCR. Backplane mounted serial and TCP/Ethernet communication module for CCR remote access. IDM 8000 CCR remote control on serial and TCP protocol.
Key Features
Indigenized remote control interface card suitable for MAFI system CCR equipment. Compatible for IDM8000 CCR. Backplane mounted serial and TCP/Ethernet communication module for CCR remote access. IDM 8000 CCR remote control on serial and TCP protocol.
• Remote control: Parallel or serial interface
• Compatible with MAFI CCR system
• Copatiable with IDM8000 CCR
• Compatible with Backplane mount serial communication.
• Compatible with commercial and Defence aviation CCR system.
• Remote control system for accessing CCR and allied system over serial or TCP.
• Indigenized local Support/presence in India.
Application
• Remote control: Parallel or serial interface.
• Compatible with MAFI CCR system.
• Compatible with IDM8000 CCR.
• Compatible with Backplane mount serial communication.
• Compatible with commercial and Defence aviation CCR system.
• Remote control system for accessing CCR and allied system over serial or TCP.
• Indigenized local Support/presence in India.
• Easy in configuration using DIP switches.
Water scarcity is the lack of fresh water resources to meet the standard water demand. There are two type of water scarcity. One is physical. The other is economic water scarcity.
Student information management system project report ii.pdfKamal Acharya
Our project explains about the student management. This project mainly explains the various actions related to student details. This project shows some ease in adding, editing and deleting the student details. It also provides a less time consuming process for viewing, adding, editing and deleting the marks of the students.
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Dr.Costas Sachpazis
Terzaghi's soil bearing capacity theory, developed by Karl Terzaghi, is a fundamental principle in geotechnical engineering used to determine the bearing capacity of shallow foundations. This theory provides a method to calculate the ultimate bearing capacity of soil, which is the maximum load per unit area that the soil can support without undergoing shear failure. The Calculation HTML Code included.
Hall booking system project report .pdfKamal Acharya
PHP and MySQL project on Hall Booking System is a web based project and it has been developed in PHP and MySQL and we can manage Payment, Booking, Inventory, Booking Dates, Customers and Hall from this project.
The main objective to develop Hall Booking System PHP, MySQL, JAVA SCRIPT and BOOTSRAP Project is to overcome the manual errors and make a computerized system.
In this project, there are various type of modules available to manage Customers, Booking, Payment. We can also generate reports for Booking, Payment, Booking Dates, Hall. Here the Payment module manage all the operations of Payment, Booking module can manage Booking, Inventory module is normally developed for managing Inventory, Booking Dates module manages Booking Dates operations, Customers module has been implemented to manage Customers.
In this project all the modules like Payment, Booking Dates, Booking are tightly coupled and we can track the information easily. Ifyou are looking for Free Hall Booking System Project in PHP and MySQL then you can visit our free projects section.
We can easily get the list of wedding halls & lawns in Nagpur. Also we have detailed contact information for some particular hall. But we cannot get the availability about hall. So background behind this web portal is that it gives the area wise listing of wedding halls & lawns with the detailed information of individual and also display for particular date the hall is available or not. Just dial is the system in which we can only find the name of Hall and Lawns in city. In just dial we cannot find Halls in specific area. This system cannot show all information about any Hall. This system is not able to book the Halls online.
The A Web Based Hall Booking Management System is designed to overcome the disadvantage of previous system.We can easily get the list of Wedding Halls. But we cannot get the availability about Hall. So background behind this web portal is that it gives the area wise listing of Wedding Halls with the detailed information of individual and also display for particular date the Hall is available or not. This is a special type of web portal to easily get the information of all Wedding Halls in Nagpur which display separate calendar for separate Hall. For particular date the Hall. We can availability of Hall as well as Lawns detailed information about individuals Hall in our web portal . It provides all facilities to clients with lowest cost and lowest maintenance problems.
This is a assigned group presentation given by my Computer Science course teacher at Green University of Bangladesh, Bangladesh.
My Presentation Topic was - Cloud Computing
This group presentation includes the work Md. Shahidul Islam Prodhan, pages no 10 - 15.
www.facebook.com/TheShahidul
www.twitter.com/TheShahidul
www.linkedin.com/TheShahidul
Democratizing Fuzzing at Scale by Abhishek Aryaabh.arya
Presented at NUS: Fuzzing and Software Security Summer School 2024
This keynote talks about the democratization of fuzzing at scale, highlighting the collaboration between open source communities, academia, and industry to advance the field of fuzzing. It delves into the history of fuzzing, the development of scalable fuzzing platforms, and the empowerment of community-driven research. The talk will further discuss recent advancements leveraging AI/ML and offer insights into the future evolution of the fuzzing landscape.
A CASE STUDY ON ONLINE TICKET BOOKING SYSTEM PROJECT.pdfKamal Acharya
Online movie ticket booking system for movies is a web-based program. This application allows users to purchase cinema tickets over the portal. To buy tickets, people must first register or log in. This website's backend is PHP and JavaScript, and the front end is HTML and CSS. All phases of the software development life cycle are efficiently managed in order to design and implement software. On the website, there are two panels: one for administrators and one for customers/users. The admin has the ability to add cinemas, movies, delete, halt execution, and add screens, among other things. The website is simple to navigate and appealing, saving the end user time.
Construction method of steel structure space frame .pptxwendy cai
High-altitude bulk installation refers to the method of total assembling of small assembled units or loose parts directly in the design position, applicable to the installation of space structure such as space frame and reticulated shell.
Top 13 Famous Civil Engineering Scientistgettygaming1
List of Best Scientist Who Gives Big Contribution in Civil Engineering Filed, in this we provide how they Contribute in Civil Engineering filed, For Data Collection civilthings.com helps us a lot.
Final project report on grocery store management system..pdfKamal Acharya
In today’s fast-changing business environment, it’s extremely important to be able to respond to client needs in the most effective and timely manner. If your customers wish to see your business online and have instant access to your products or services.
Online Grocery Store is an e-commerce website, which retails various grocery products. This project allows viewing various products available enables registered users to purchase desired products instantly using Paytm, UPI payment processor (Instant Pay) and also can place order by using Cash on Delivery (Pay Later) option. This project provides an easy access to Administrators and Managers to view orders placed using Pay Later and Instant Pay options.
In order to develop an e-commerce website, a number of Technologies must be studied and understood. These include multi-tiered architecture, server and client-side scripting techniques, implementation technologies, programming language (such as PHP, HTML, CSS, JavaScript) and MySQL relational databases. This is a project with the objective to develop a basic website where a consumer is provided with a shopping cart website and also to know about the technologies used to develop such a website.
This document will discuss each of the underlying technologies to create and implement an e- commerce website.
Courier management system project report.pdfKamal Acharya
It is now-a-days very important for the people to send or receive articles like imported furniture, electronic items, gifts, business goods and the like. People depend vastly on different transport systems which mostly use the manual way of receiving and delivering the articles. There is no way to track the articles till they are received and there is no way to let the customer know what happened in transit, once he booked some articles. In such a situation, we need a system which completely computerizes the cargo activities including time to time tracking of the articles sent. This need is fulfilled by Courier Management System software which is online software for the cargo management people that enables them to receive the goods from a source and send them to a required destination and track their status from time to time.
Introduction to Casting Processes in Manufacturing
electrical regulation ppt 0123321123333333
1. ELECTRICAL REGULATIONS
BY PD 1096
1. General Locational Requirements in Towns,
Subdivisions, Human Settlements, Industrial Estates
and the like.
Overhead transmission and/or distribution
lines/systems including transformers, poles, towers and
the like shall be located and installed following the
latest standards of design, construction and
maintenance but so as not to cause visual pollution and
in the interest of public safety, convenience, good
viewing and aesthetics, these may be located along
alleys or back streets.
2. 2. Location of Poles and Clearances of Power Lines along Public Roads.
2.1 All poles erected on public roads shall be covered by Approved Pole
Location (APL) plan from the Municipal Engineer.
2.2 Poles and transformer supports shall be located not more than
500mm inside from the road right-of-way or property line, and
shall not obstruct the sidewalk, pedestrian path and/or the road
drainage canal or structure, existing or proposed.
≤ 500 mm
Property line
Pole
3. 2.3 Primary lines shall have a minimum vertical clearance of 10 m
from the crown of the pavement when crossing the highway
and 7.5 m from the top of the shoulder or sidewalk when installed
along the side of the highway or street in a highly urbanized area.
≥10 m
≥7.5 m
2.4 Secondary, neutral and service lines shall have a minimum vertical
clearance of 7.5 m from the crown of the road pavement when
crossing the highway and from the top of the shoulder or sidewalk
when installed along the side of the highway or street in highly
urbanized area.
4. 2.5 Clearances of Supporting Structures such as Poles, Towers and
others and their guys and braces measured from the nearest
parts of the objects concerned:
A. From Fire Hydrants, not less than 5 m.
B. From the Street Corners, where hydrants are
located at street corners, poles and towers shall
not be set so far from the corners as to make
necessary the use of flying taps which are
inaccessible from the poles.
C. From Curbs, not less than 150 mm measured from
the curb away from the roadway.
≥5 m
≥150 mm
5. 3. Attachments on and Clearances from Buildings
3.1 Attachments for support of power lines and cables, transformers and other
equipment and/or communications lines installed on buildings shall be
covered by an Approved Attachment Plan from the local Building Official.
3.2 Where buildings exceed 15 m in height, overhead lines shall be arranged
where practicable so that a clear space or zone at least 2 m wide will be
left, either adjacent to the building or beginning not over 2.5 m from the
building, to facilitate the raising of ladders where necessary for fire
fighting.
2 - 2.5 m
Pole
≥ 15 m
6. 4. Open Supply Conductors Attached to Buildings
Where the permanent attachment of open supply conductors of any class to
buildings is necessary for an entrance such conductors shall meet the following
requirements:
4.1 Conductors of more than 300 volts to ground shall not be carried along or
near the surface of the buildings unless they are guarded or made
inaccessible.
4.2 To promote safety to the general public and to employees not authorized
to approach conductors and other current-carrying parts of electric supply
lines, such parts shall be arranged so as to provide adequate clearance
from the ground or other space generally accessible, or shall be provided
with guards so as to isolate them effectively from accidental contact by
such persons.
4.3 Undergrounded metal-sheathed service cables, service conduits, metal
fixtures and similar noncurrent-carrying parts, if located in urban districts
and where liable to become charged to more than 300 volts to ground,
shall be isolated or guarded so as not to be exposed to accidental contact
by unauthorized persons. As an alternative to isolation or guarding,
noncurrent-carrying parts shall be solidly or effectively grounded.
7. 4.4 Clearance of wires from building surface shall be not less than
those required Table II.
4.5 Supports over buildings. Service-drop conductors passing over a
roof shall be securely supported by substantial structures.
Where practicable, such supports shall be independent of the
building.
Voltage of Supply
Conductors
Horizontal
Clearance in
Meters
Vertical Clearance
in Meters
300 to 8,700 volts 1.0 2.5
8,700 to 15,000
volts
2.5 2.5
15,000 to 50,000
volts
3.0 3.0
> 50,000 volts 3.0 + 10 mm per Kv
in excess
3.0 + 10 mm per Kv
in excess
8. 5. Conductors Passing By or Over Buildings
5.1 Minimum Clearances. Unguarded or accessible supply conductors
carrying voltages in excess of 300 volts may be run either beside
or over buildings. The vertical or horizontal clearance to any
building or its attachments (balconies, platforms, etc.) shall be as
listed below. The horizontal clearance governs above the roof
level to the point where the diagonal equals the vertical clearance
requirement. This rule should not be interpreted as restricting the
installation of a trolley contact conductor over the approximate
center line of the track it serves.
5.2 Guarding of Supply Conductors/Supply of Conductors of 300 volts
or more shall be properly guarded by grounded conduit, barriers,
or otherwise, under the following conditions:
1. Where the clearances set forth in Table II above cannot
be obtained.
2. Where such supply conductors are placed near enough to
windows, verandas, fire escapes, or other ordinarily
accessible places within the reach of persons.
9. 5.3 Where the required clearances cannot be obtained, supply
conductors shall be of Grounded Metallic Shield, Jacketed Primary
Cables grouped or bundled and supported by grounded messenger
wires.
V-
≥V
10. Clearance of line
conductors from -
Communication LInes Supply LInes
In general On jointly used
poles
In general (0 to
8700 volts)
On jointly used
poles (0 to 8700
volts)
Exceeding 8700
volts, add for each
1000 volts of excess
Vertical and lateral
conductors of the
same circuit
75 mm 75 mm 75 mm 75 mm 6.25 mm
Vertical and lateral
conductors of other
circuits
75 mm 75 mm 150 mm 150 mm 10 mm
Span and guy wires
attached to same
pole: general
75 mm 150 mm 150 mm 150 mm 10 mm
Span and guy wires
attached to same
pole: when parallel
to line
75 mm 150 mm 300 mm 300 mm 10 mm
Lightning protection
wires parallel to line:
surfaces of cross
arms
75 mm 75 mm 75 mm 75 mm 5 mm
Lightning protection
wires parallel to line:
surfaces of poles
75 mm 125 mm 75 mm 125 mm 5 mm
11. 6. Clearance of Service Drops
6.1 Service drop conductors shall not be readily accessible and when not in
excess of 600 volts, shall conform to the following:
a. Clearances over roof. Conductors shall have a clearance of not less
than 2.5m from the highest point of roofs over which they pass with
the following exceptions:
≥ 2.5 m
Highest point
Service Drop Conductor
< 600 volts
12. Exception No. 1. Where the voltage between conductors does not exceed 300
volts and the roof has a slope of not less than 100mm in 300mm, the
clearance may not be less than 1m.
≥1 m
Highest point
Service Drop Conductor
≤300 volts
Slope ≥ 1:3
13. Exception No. 2. Service drop conductors of 300 volts or less which do not pass
over other than a maximum of 1.2m of the overhang portion of the roof for the
purpose of terminating at a through-the-roof service raceway or approved
support may be maintained at a minimum of 500mm from any portion of the
roof over which they pass.
≤ 1.2 m
Highest point
Service Drop Conductor
≤ 300 volts
≥500mm
14. 6.2 Clearance from the Ground. Conductors shall have a clearance of not less
than 3m from the ground or from any platform or projection from which they
might be reached.
conductor
platform
≥ 3 m
6.3 Clearance from Building Openings. Conductors shall have a horizontal
clearance of not less than 1m from windows, doors, porches, fire escapes, or
similar locations and shall be run at least 500mm above the top level of a
window or opening.
window
≥ 500mm
≥ 1 m
15. 6.4 Service Drop of communication lines, when crossing a street, shall have a
clearance of not less than 5.5 m from the crown of the street or sidewalk
over which it passes.
≥ 5.50 m ≥5.50 m
Service drop of communication line
Service Drop of communication lines shall have a minimum clearance of 3m
above ground at its point of attachment to the building or pedestal.
≥3m
protector
≥3m
16. 6.5 No parts of swimming and wading pools shall be placed under existing service
drop conductors or any other over-head wiring; nor shall such wiring be
installed above the following:
a. Swimming and wading pools and the area extending 3m
outward horizontally from the inside of the walls of the pool.
b. Diving Structures
c. Observation stands, towers or platforms
Swimming pool
Service
drop
conductor
≥ 3 m
17. 7. Wiring Methods
Service entrance conductors extending along the exterior or entering
buildings or other structures shall be installed in rigid steel conduit or
asbestos cement conduit or concrete encased plastic conduit from point of
service drop to meter socket and from meter socket to the disconnecting
equipment. However, where the service entrance conductors are protected
by approved fuses or breakers at their outer ends (immediately after the
service drop or lateral) they may be installed in any of the recognized wiring
methods.
7.1 Abandoned Lines and/or portions of lines no longer required to provide
shall be removed.
7.2 Power or communication poles, lines, service drops and other line
equipment shall be free from any attachment for antennas, signs,
streamers and the like.
7.3 Metallic sheaths or jackets of overhead power or communication cables
shall be grounded at a point as close as possible to ground level
whenever such cables change from overhead to underground
installations.
18. 8. Transformers
8.1 Oil-insulated Transformers Installed Outdoors. Combustible material,
combustible buildings and parts of buildings, fire escapes, door and
window openings shall be safeguarded from fires originating in oil-
insulated transformers installed on, attached to, or adjacent to a building
or combustible material. Space separations, fire-resistant barriers and
enclosures which confine the oil of a ruptured transformer tank are
recognized safeguards. One or more of these safeguards shall be applied
according to the degree of hazard involved in cases where the transformer
installation presents a fire hazard. Oil enclosures may consist of fire-
resistant dikes, curbed areas or basins, or trenches filled with coarse,
crushed stone. Oil enclosures shall be provided with trapped drains in
cases where the exposure and the quantity of oil involved are such that
removal of oil is important.
Trench all
around
Exterior Oil-insulated
Transformer
19. 8.2 Dry-Type Transformers Installed Indoors. Transformers rated 112-1/2 KVA
or less shall have separation of at least 300mm from combustible material
unless separated there from by a fire-resistant heat-insulating barrier or
unless of a rating not exceeding 600 volts and completely enclosed except for
ventilating openings.
Dry-type transformer
112-1/2 Kva or less
≥ 300mm
Combustible Wall
20. 8.3 Askarel-Insulated Transformers Installed Indoors. Askarel-insulated
transformers rated in excess of 25 KVA shall be furnished with a pressure
relief vent. Where installed in a poorly ventilated place they shall be
furnished with a means for absorbing any gases generated by arcing inside
the case, or the pressure relief vent shall be connected to a chimney or flue
which will carry such gases outside the building. Askarel-insulated
transformers rated more than 35,000 volts shall be installed in a vault.
Transformers of more than 112-1/2 KVA rating shall be installed in a transformer
room of fire-resistant construction unless they are constructed with Class B (80ºC
rise) or Class H (150ºC rise) insulation, and are separated from combustible
material not less than 1.85m horizontally and 3.7m vertically or are separated
there from by a fire-resistant heat-insulating barrier.
Transformers rated more than 35,000 volts shall be installed in a vault.
Dry-type transformer
112-1/2 Kva or less
≥ 1.85 m
Combustible
Wall
Combustible ceiling
≥ 3.70 m
vault
Transformer more
than 35,000 volts
21. 8.4 Oil-Insulated Transformers Installed Indoors. Oil-insulated transformers shall
be installed in a vault constructed as specified in this Section except as follows:
1. NOT OVER 112-1/2KVA TOTAL CAPACITY. The provisions for transformer
vaults specified in Section 9.3 of this Rule apply except that the vault may
be constructed of reinforced concrete not less than 100mm thick.
2. NOT OVER 600 VOLTS. A vault is not required provided suitable
arrangements are made where necessary to prevent a transformer oil fire
igniting other materials, and the total transformer capacity in one location
does not exceed 10 KVA in a section of the building classified as
combustible, or 75 KVA where the surrounding structures is classified as
fire-resistant construction.
> 100mm thick reinforced
concrete vault
oil insulated transformer
< 112-1/2 KVa
22. 8.5 Guarding. Transformers shall be guarded as follows:
1. MECHANICAL PROTECTION. Appropriate provisions shall be made
to minimize the possibility of damage to transformers from external
causes where the transformers are located exposed to physical
damage.
2. CASE OR ENCLOSURE. Dry-type transformers shall be provided with
a non-combustible moisture resistant case or enclosure which will
provide reasonable protection against accidental insertion of foreign
objects.
3. EXPOSED LIVE PARTS. The transformer installation shall conform
with the provisions for guarding of live parts in PEC Rule 1056.
4. VOLTAGE WARNING. The operating voltage of exposed live parts of
transformer installations shall be indicated by signs or visible
markings on the equipment or structures.
3. FURNACE TRANSFORMERS. Electric furnace transformers of a total rating
not exceeding 75 KVA may be installed without a vault in a building or room
of fire-resistant construction provided suitable arrangements are made to
prevent a transformer oil fire spreading to other combustible material.
4. DETACHED BUILDING. Transformers may be installed in a building which
does not conform with the provisions specified in this Code for transformer
vault, provided neither the building nor its contents present fire hazard to
any other building or property, and provided the building is used only in
supplying electric service and the interior is accessible only to qualified
persons.
23. 9. Provisions for Transformer Vaults
9.1 New Building. New buildings requiring an expected load demand of
200KVA or above shall be provided with a transformer vault, except that
transformers may be mounted on poles or structures within the property if
enough space is available, provided that all clearances required can be
obtained and no troublesome contamination on insulators, bushings, etc.
can cause hazards and malfunctioning of the equipment.
150 mm for R.C
200 mm for Brick
300 mm for Load bearing CHB
200 Kva or more
Wall:
20 mm thick plaster
2-1/2 hours fire rating
Floor:
100mm thick
2-1/2 hours fire rating
24. 9.2 Location. Transformer and transformer vaults shall be readily accessible to
qualified personnel for inspection and maintenance. Vaults shall be located
where they can be ventilated to the outside air without using flues or ducts
wherever such an arrangement is practicable.
9.3 Walls, Roof and Floor. The walls and roofs of vaults shall consist of reinforced
concrete not less than 150mm thick, masonry or brick not less than 200mm
thick, or 300mm load bearing hollow concrete blocks. The inside wall and roof
surface of vaults constructed of hollow concrete blocks shall have a coating of
cement or gypsum plaster not less than 20mm thick. The vault shall have a
concrete floor not less than 100mm thick. Building walls and floor which meet
these requirements may serve for the floor, roof and one or more walls of the
vaults. Other forms of fire-resistive construction are also acceptable provided
they have adequate structural strength for the conditions and a minimum fire
resistance of two and one half hours according to the approved Fire Test
Standard. The quality of the material used in the construction of the vault shall
be of the grade approved by the Building Official having jurisdiction.
25. 9.4 Doorways. Any doorway leading from the vault into the building shall be
protected as follows:
1. TYPE OF DOOR. Each doorway shall be provided with a tight-fitting
door of a type approved for openings in such locations by the authority
enforcing this Code.
2. SILLS. A door sill or curb of sufficient height to confine within the
vault, the oil from the largest transformer shall be provided and in no
case shall the height be less than 100mm.
3. LOCKS. Entrance doors shall be equipped with locks, and doors shall
be kept locked, access being allowed only to qualified persons. Locks
and latches shall be so arranged that the door may be readily and
quickly opened from the inside.
10.Ventilation. Ventilation shall be adequate to prevent a transformer temperature
in excess of the prescribed values.
1. LOCATION. Ventilation openings shall be located as far away as
possible from doors, windows, fire escapes and combustible material.
26. 2. ARRANGEMENT. Vaults ventilated by natural circulation of air may have
roughly half of the total area of openings required or ventilation in one or more
openings near the floor and the remainder in one or more openings in the roof
or in the sidewalls near the roof; or all of the area required for ventilation may
be provided in one or more openings in or near the roof.
3. SIZE. In the case of vaults ventilated to an outdoor area without using ducts or
flues the combined net area of all ventilating openings after deducting the area
occupied by screens, grating, or louvers, shall be not less than 0.006 sqmm per
KVA of transformer capacity in service, except that the net area shall be not
less than 0.1 sqm for any capacity under 50 KVA.
4. COVERING. Ventilation openings shall be covered with durable gratings,
screens, or louvers, according to the treatment requirement required in order to
avoid unsafe conditions.
5. DAMPERS. Where automatic dampers are used in the ventilation openings of
vaults containing oil-insulated transformers, the actuating device should be
made to function at a temperature resulting from fire and not a temperature
which might prevail as a result of an overheated transformer or bank of
transformers. Automatic dampers should be designed and constructed to
minimize the possibility of accidental closing.
27. 6. DUCTS. Ventilating ducts shall be constructed of fire resistant material.
7. DRAINAGE. Where practicable, vaults containing more than 100KVA
transformer capacity shall be provided with a drain or other means which will
carry off any accumulation of oil or water in the vaults unless local conditions
make this impracticable.
8. WATER PIPES AND ACCESSORIES. Any pipe or duct system foreign to the
electrical installation should not enter or pass through a transformer vault.
Where the presence of such foreign system cannot be avoided, appurtenances
thereto which require maintenance at regular intervals shall not be located
inside the vault. Arrangements shall be made where necessary to avoid
possible trouble from compensation, leaks and breaks in such foreign system.
Piping or other facilities provided for fire protection or for water-cooled
transformers are not deemed to be foreign to the electrical installation.
28. 11.Capacitors.
1. Application. This section applies to installation of capacitors on electric
circuits in or on buildings.
Exception No. 1. Capacitors that are components of other apparatus shall
conform to the requirements for such apparatus.
Exception No. 2. Capacitors in hazardous locations shall comply with
additional requirements in PEC Section 400-415.
2. Location. An installation of capacitors in which any single unit contains
more than three gallons of combustible liquid shall be in a vault conforming
to part C of PEC Section 319.
3. Mechanical Protection. Capacitors shall be protected from physical damage
by location or by suitable fences, barriers or other enclosures.
4. Cases and Supports. Capacitors shall be protected from physical damage by
location or by suitable fences, barriers or other enclosures.
5. Transformers Used with Capacitors. Transformers which are components of
capacitor installations and are used for the purpose of connecting the
capacitor to a power circuit shall be installed in accordance with PEC Section
319. The KVA rating shall not be less than 135 per cent of the capacitor
rating in Kva.
29. 12.Emergency Systems
1. The provisions of this Section shall apply to the installation, operation and
maintenance of circuits, systems and equipment intended to supply
illumination and power in the event of failure of the normal supply or in the
event of accident to elements of a system supplying power and illumination
essential for safety to life and proper where such systems or circuits are
required by the Fire Code, or by any government agency having jurisdiction.
Emergency systems are generally installed in places of assembly where
artificial illumination is required, such as buildings subject to occupancy by
large numbers of persons, hotels, theaters, sports arenas, hospitals and similar
institutions. Emergency systems provide power for such functions as
refrigeration, operation of mechanical breathing apparatus, ventilation
essential to maintain life, illumination and power for hospital room, fire alarm
systems, fire pumps, industrial processes where current interruption would
produce serious hazards, public address systems and other similar functions.
2. All requirements of this Section shall apply to emergency systems.
3. All equipment for use on emergency systems shall be properly approved.
30. 4. Tests and Maintenance
a. The authority having jurisdiction shall conduct or witness a test on the
complete system upon completion of installation, and periodically afterwards.
b. Systems shall be tested periodically in accordance with a schedule acceptable
to the authority having jurisdiction to assure that they are maintained in proper
operating condition.
c. Where the battery systems or unit equipment are involved, including
batteries used for starting or ignition in auxiliary engines, the authority having
jurisdiction shall require periodic maintenance.
d. A written record shall be kept of such tests and maintenance.
5. Emergency systems shall have adequate capacity and rating for the emergency
operation of all equipment connected to the system.
31. 6. Current supply shall be such that in the event of failure of the normal supply to
or within the building or group of buildings concerned, emergency lighting or
emergency power, will be immediately available. The supply system for
emergency purposes may be composed one or more of the types of systems
covered in Section 12.7 to Section 12.10 of this Rule. Unit equipment in
accordance with Section 12.21 shall satisfy the applicable requirements of this
Section.
Consideration must be given to the type of service to be rendered; whether for
short duration, as for exit lights of a theater, or for long duration, as for
supplying emergency power and lighting during long periods of current failure
from trouble either inside or outside the buildings, as in the case of a hospital.
Assignment of degree of reliability of the recognized emergency supply system
depends upon the careful evaluation of the variables of each particular
installation.
7. A storage battery of suitable rating and capacity shall supply, by means of a
service installed according to Section 200 of the PEC and maintained at not
more than 90 per cent of system voltage, the total load of the circuits supplying
emergency lighting and emergency power for a period of at least ½ hour.
32. 8. A generator set driven by some form of prime mover, with sufficient capacity
and proper rating to supply circuits carrying emergency lighting or lighting and
power, equipped with suitable means for automatically starting the prime mover
on failure of the normal service shall be provided. For hospitals, the transition-
time from instant of failure of the normal power source to the emergency
generator source shall not exceed ten seconds. (See Section 12.4)
9. There shall be two services, each in accordance with Section 200 of the PEC,
widely separated electrically and physically to minimize the possibility of
simultaneous interruption of power supply arising from an occurrence within
the building or group of buildings served.
10.Connections on the line side of the main service shall be sufficiently separated
from said main service to prevent simultaneous interruption of supply through
an occurrence within the building or group of buildings served.
11. The requirements of Section 12.5 and Section 12.6 also apply to installations
where the entire electrical load on a service or sub-service is arranged to be
supplied from a second source. Current supply from a standby power plant
shall satisfy the requirements of availability in Section 12.6.
33. 12.Audible and visual signal devices shall be provided, where practicable, for the
following purposes:
a. To give warning of dearrangement of the emergency or auxiliary source.
b. To indicate that the battery or generator set is carrying a load.
c. To indicate when a battery charger is properly functioning.
13. Only appliances and lamps specified as required for emergency use shall be
supplied by emergency lighting circuits.
14. Emergency illumination shall be provided for all required exit lights and all
other lights specified as necessary for sufficient illumination.
Emergency lighting systems should be so designed and installed that the
failure of any individual lighting element, such as the burning out of a light
bulb, shall not leave any area in total darkness.
34. 15.Branch circuits intended to supply emergency lighting shall be so installed as to
provide service immediately when the normal supply for lighting is interrupted.
Such installations shall provide either one of the following:
a. An emergency lighting supply, independent of the general lighting
system with provisions for automatically transferring to the emergency
lights by means of devices approved for the purpose upon the event of
failure of the general lighting system supply.
b. Two or more separate and complete systems with independent power
supply, each system providing sufficient current for emergency lighting
purposes. Unless both systems are used for regular lighting purposes
and are both lighted, means shall be provided for automatically
energizing either system upon failure of the other. Either or both
systems may be part of the general lighting system of the protected
occupancy if circuits supplying lights for emergency illumination are
installed in accordance with other Section of this Rule.
16. For branch circuits which supply equipment classed as emergency, there shall
be an emergency supply source to which the load will be transferred
automatically and immediately upon the failure of the normal supply.
35. 17. Emergency circuit wiring shall be kept entirely independent of all other wiring and
equipment and shall not enter the same raceway, box or cabinet with other wiring
except:
a. In transfer switches, or
b. In exit or emergency lighting fixtures supplied from two (2) sources.
18. The switches installed in emergency lighting circuits shall be so arranged that only
authorized persons have control of emergency lighting, except:
a. Where two or more single throw switches are connected in parallel to
control a single circuit, at least one of those switches shall be accessible
only to authorized persons.
b. Additional switches which act only to put emergency lights into operation
but not to disconnect them may be permitted.
Switches connected in series and three- and four-way switches shall not be
allowed.
19. All manual switches for controlling emergency circuits shall be located at the most
accessible place to authorized persons responsible for their actuation. In places of
assembly, such as theaters, a switch for controlling emergency lighting systems
shall be located in the lobby or at a place conveniently accessible there from.
In no case shall a control switch for emergency lighting in a theater for motion
picture projection be placed in the projection booth or on the stage. However,
where multiple switches are provided, one such switch may be installed in such
locations and so arranged that it can energize but not disconnect for the circuit.
36. 20. Lights on the exterior of the building which are not required for illumination
when there is sufficient daylight may be controlled by an automatic light
actuated device approved for the purpose.
21. In hospital corridors, switching arrangements to transfer corridor lighting in
patient areas of hospitals from overhead fixtures to fixtures designed to provide
night lighting maybe permitted, provided that the switching system is so
designed that switches can only select between two sets of fixtures but cannot
extinguish both sets at the same time.
22.The branch circuits over current devices in emergency circuits shall be
accessible to authorized persons only.
23. Where permitted by the authority having jurisdiction, in lieu of other methods
specified elsewhere in this Section, individual unit equipment for emergency
illumination shall consist of:
a. Battery
b. Battery charging means, when a storage battery is used
c. One or more lamps, and
d. A relaying device arranged to energize the lamps automatically upon
failure of the normal supply to the building
37. The batteries shall be of suitable rating and capacity to supply and maintain, at not
less than 90 per cent of rated lamp voltage, the total lamp load associated with the
unit for a period of at least ½ hour. Storage batteries, whether of the acid or alkali
type, shall be designed and constructed to meet the requirements of emergency
service. Lead-acid type storage batteries shall have transparent jars.
Unit equipment shall be permanently fixed in place and shall have all wiring to each
unit installed in accordance with the requirements of any of the wiring methods
discussed in Chapter II of the PEC. They shall not be connected by flexible cord. The
supply circuit between the unit equipment and the service, the feeders or the branch
circuit wiring shall be installed as required by Section 12.17. Emergency illumination
fixtures which obtain power from a unit equipment which are not part of the unit
equipment shall be wired to the unit equipment as required by Rule 5257 of the PEC
and in accordance with the one of the wiring methods described in Chapter II of the
PEC.
13. Effectivity
1. All primary and secondary supply lines already existing shall comply with the
provisions of this Rule within two (2) years from the effectivity of this Rule.
2. Transformers to be installed on, attached to, or in buildings shall comply with the
requirements of this Rule. Transformer installations already existing shall comply with
the requirements within two (2) years from the effectivity of this Rule.
3. Non-compliance with the provisions of this Rule shall be subject to the penal
provisions in Section 213 of PD 1096.