SlideShare a Scribd company logo
1 of 71
Schedule
Ref. Date Topic
A07 27 Oct 2005 Introduction and Load Assessment
A08 3 Nov 2005 Standards and Basic Equipment
A09 10 Nov 2005 Power Distribution & Final Circuit
A10 17 Nov 2005 Protection & Earthing
A11 24 Nov 2005 Cable & Wiring
A12 1 Dec 2005 Standby Generator and Power
Supplies
Introduction
Load Estimation
Terminology
Basic Equipment Codes and Standards
Power Distribution & Final Circuit
Protection & Cable Wiring
Earthing
Design of Electricity Distribution
Standby Generator
and Power Supplies
Earthing and Design of
Electricity Distribution
Date : 24 November 2005
Module Code : A11
Ir. KF Cheung
Earthed Equipotential Bonding and
Automatic Disconnection
C) Determination of Disconnection Time
1) Maximum values of earth loop impedance for various
overcurrent protective devices are shown in table 41B1,
Table 41B2 & Table 41D
2) Actual earth loop impedance can be calculated as follows:
Zs = Ze + Z1 + Z2
Ze : Earth loop impedance at the source
Z1 : Impedance of phase conductor
Z2 : Impedance of circuit protective conductor (cpc)
Earthed Equipotential Bonding and
Automatic Disconnection
C) Determination of Disconnection Time
3) Compare the actual Zs with the tabulated Zs(max):
 The actual Zs value measured from the installation should be
smaller than the Zs(max) value from IEE Tables in order to achieve
safe disconnection time. Attention is drawn on that the Zs (max)
form IEE Tables shall be converted to nominal supply voltage
system in Hong Kong before comparison.
Zs (max :220) = Zs (max : 240) in IEE Tables X 220/240
Earthed Equipotential Bonding and
Automatic Disconnection
C) Determination of Disconnection Time
4) The earth fault current can be calculated using the
following formula:
If = Uo /Zs
Uo = Phase to earth voltage
If = earth fault current
5) By putting the calculated fault current against the
characteristic curves of the protective device given in IEE,
the actual disconnection time can be found.
Example
 A 220V circuit is protected by a 30A Type 2 MCB, the
cable used is 2.5/1.5 twin with cpc PVC copper conductor,
if the circuit length is 15m and Ze up to the MCB board
is 0.5Ω, what is the actual disconnection time?
 From table 17, R1+R2 /m = 19.51mΩ x 1.38
= 0.269 Ω/m
Time
(s)
Current (A)
A) Cable Selection
 Factors to be considered in sizing of cable conductors
 Conductor material
 Insulating material
 Method of installation
 Installed environment
 Ambient temperature
 Thermal insulating enclosure
 Adjacent cables
 Type of protective device
 Voltage drop
 Minimum cross-sectional area
Comparison between Copper
Conductor and Aluminum Conductor
 A) Copper Conductor
 High degree of electrical conductivity
 Tough, slow to tarnish
 Can be jointed without any special provision to prevent electrolytic
action
 B) Aluminum Conductor
 Lower price & light in weight
 Pliable, it can be used in solid-core cables
 Excellent resistance to corrosion
Insulating Materials
Bends of Non-flexible Cable
 The minimum internal radius bend in cables for fixing
wiring are shown in the following table
Correction Factor for Conductors
 Factors which affect the ability of a cable to lose heat are:
 Grouping (Cg or C1)
 Ambient temperature (Ca or C2)
 Thermal insulation (Ci or C3)
 Semi-enclosed fuse to BS 3036 (0.725 or C4)
 Type of installation (Table 4A)
Correction Factor for Conductors
 A) Grouping factor (Cg) - 1
 IEE Table 4B1 gives correction factors to be applied to te tabulated
current-carrying capacities where cables or circuits are grouped.
 Where the horizontal clearance s between adjacent cables exceed
two cable diameter (2D2), no correction factor need be applied.
Correction Factor for Conductors
 A) Grouping factor (Cg) - 2
 If a cable is expected to carry not more than 30% of its grouped
rating, it may be ignored from the rest of the group.
Correction Factor for Conductors
 B) Correction Factor for Ambient Temperature (Ca)
 Correction factor for ambient temperature is shown in IEE Table
4C1. Where for semi-enclosed fuses are being used, see IEE Table
4C2.
It ≥ In / Ca
 Typical data are shown in the following table for quick reference.
Correction Factor for Conductors
 C) Correction Factor for thermal Insulation (Ci)
 The value of current-carrying-capacity for various sizes of
conductors shown in Tables of Appendix 4 have been taken into
account of cables installed in a thermally insulated wall or ceiling
where one side of the cable is in contact with a thermally
conductive surface.
 Where the cable is totally enclosed in thermal insulation, Ci=0.5
shall be used in absence of more precise information.
It ≥ In / Ci
 Ci shall only be applied to the ‘open and clipped direct’ column of
respective IEE Tables.
Correction Factor for Conductors
 D) factor for Semi-enlosed fuse to BS3036 (C4)
 When semi-enclosed fuse is used for protecting the conductor, a
derating factor of 0.726 shall be applied.
Correction Factor for Conductors
 E) General Formula for Correction Factors Applied to Cable
Sizing
 It ≥ In / Cg x Ca x Ci x C4
Example
Example
 Protective device : BS 3036 fuses
 Ambient temperature: 30oC
 Cable use :PVC twin with cpc cable
 Cabling conditions at:
 1) Bunched and clipped direct
 2) Passed through totally enclosed thermal insulation area
 3) One side in contact with thermally insulated ceiling
 4) Passed through a boiler house where ambient temperature of
45oC
 5) Clipped direct
 Ignore voltage drop
 What cable sizes are required?
Voltage Drop
 The overall voltage drop shall not exceed the value
appropriate to the safe functioning of the equipment in
normal service.
 The voltage drop in any circuit from the origin of
installation to the current-using equipment should not
exceed 4% of the nominal voltage.
 Volt drop pre unit value in from of mv/A/m are shown on
IEE tables of Appendix 4. The values are based on the
circuit conductor working at the maximum permitted
operating temperature and at unity power factor.
Voltage Drop
Voltage Drop
Voltage Drop
Voltage Drop
 Voltage drop (V.D.) can be calculated as follows:
V.D. = design current (Ib) x circuit length (L) x volt drop
per unit (mv/A/m)
Example
 A PVC/SWA/PVC armoured cable is to be installed from an
HRC 100A fuse in a distribution board to a 3-phase 380V
motor, along with 5 other cables fixed to a perforated
metal cable tray where the cable sheaths will be touching,
if the cable length is 100 meters and the power factor of
the load is 0.866, what size of cable would be required to
satisfy voltage drop if the ambient temperature is 30oC
and the voltage drop in the 3 phase feeder cable up to the
distribution board is 7.7V and the total voltage drop
allowed is 4%?
Sizing Circuit Protective Conductors
 If the conductor ≤ 35mm2 : Zs = Ze + R1 + R2
>35mm2 : Zs = Ze + Z1 + Z2
 Use the formula : S ≥ √{(I2t)} / K
 Value of K : from IEE Tables 54B to 54F
 If = Uo / Zs
 Value of t from IEE Fig. 1 to 8 of Appendix 3
 Use Table 54G to size the minimum size of protective
conductors.
Thermal Constraint
 To protect conductor insulation against thermal damage
during short circuit conditions.
I2 t = K2 S2
t = K2 S2/ I2
t = duration in second
S = cross-sectional area in mm2
I = effective short-circuit current in A
K = 115 for copper conductor insulated with PVC
Thermal Constraint
Procedure
 To check the prospective short-circuit current at the
farthest point of the circuit from the point where the
device is installed
 To check the operation time of the device according to the
short-circuit current from the time/ current characteristic
of the device
 To check the adiabatic line of the conductor by
superimposing onto the characteristics of protective
devices.
Cable Selection Procedure
 Select wiring system to be installed and type of cable
 Calculate the equipment current demand using Table 4A
(15 Edition)
Calculate the circuit design current (Ib) and using diversity
allowance.
 Determine the overcueent protective device (In) : type;
rating
Check Ib ≤ In
 Determine correction factors for installation
 Grouping (Cg)
 Ambient temperature (Ca)
 Thermal insulation (Ci)
 Semi-enclosed fuse (C4)
Cable Selection Procedure
 Calculate the tabulated current carrying capacity of
conductor:
It (min) ≥ In x (1/ Cg) x (1/ Ca) x (1/ Ci) x (1/ C4)
 Select cable size from Appendix 4
Check Ib ≤ In ≤ Iz
 Calculate volt drop at the farthest point of circuit
Cable Selection Procedure
 Dose device offer shock protection in accordance with
table 41B1, 41B2 & 41D for Zs (max)?
Check Zs ≤ Zs (max) from the tables
If No :
 Re-select device or re-select phase conductor size
 Re-select cpc size
 Use alternative method as stated in Reg. 413-02-12
Checked by calculation
 Obtain Ze form supply authority
 Calculate R1 + R2 using Table 17A & B
 Determine actual Zs = Ze + (R1 + R2)
Cable Selection Procedure
 Dose the type and size of cpc offer protection?
Check : S ≥ √{(I2t)} / K
If No : re-select type and/ or size of cpc
 Check the adiabatic line of conductor against the
characteristic of overcurrent protective device.
B1) Type of Conduit
B2) Sizing of Conduit
B3) Type of Trunking
B4) Sizing of Trunking
B5) Ducting
B6) Segregation of Circuit
B) Conduit & Trunking
Steel Conduit to BS 4568 : Part 1
 A) Light duty type: plain and conduits
 Limited to use in dry situation;
 Unsuitable for bending
 Low degree of mechanical protection
 B) Heavy duty type: screwed-end conduits
 Back enamel for internal use in dry situation;
 Hot-dip galvanized for external use in situation
subject to dampness or water condensation;
 Good mechanical strength and electrical continuity.
B1) Type of Conduit
B1) Type of Conduit
Steel Conduit to BS 4568 : Part 1
 C) Classification for protection:
Class Protection Applied Example
1 Light protection both inside & outside Priming paint
2 Medium protection both inside &
outside
Stoved enamel;
Air-drying paint
3 Medium heavy protection : inside as
Class 2;
Outside as Class 4
Stoved enamel inside;
Sherardized outside
4 Heavy protection both inside &
outside
Hot-dip zinc coating,
sherardizing
Steel Conduit to BS 4568 : Part 1
 D) Heavy duty hot-dip galvanized steel
conduit system is the most common use
system for surface conduit wiring and
concealed conduit wiring. Conduit is
supplied in standard lengths of 4 meters
and is manufactured in accordance with
BS4568.
B1) Type of Conduit
Plastic conduits
 To BS4607 Part 1 and 2;
 Characteristics : light, easily bend, less
installation time, no water condensation,
lower cost;
 Heavy duty PVC conduits can be
concealed but CPC are required.
B1) Type of Conduit
Copper Conduits
 High resistance to corrosion;
 Last for long time;
 Higher cost;
 Act as excellent circuit protective
conductor (CPC)
B1) Type of Conduit
Aluminum Conduits
 Light weight and lower cost;
 Not so good in mechanical protection
Flexible Conduits
 To BS731 : Part 1
 Used for final connection to machinery;
 CPC are required.
B1) Type of Conduit
B2) Sizing of Conduit
 IEE Regulation (15th Edition) provide the
following tables for ease of conduit sizing:
 Table A, B for 1/C PVC cables in a straight run ≤ 3m;
 Table C, D for 1/C PVC cable in conduit run > 3m.
 The conduit size is considered satisfactory if the
conduit factor is equal to or exceeds the sum of
the cable factors
B2) Sizing of Conduit
Type of Conductor C.S.A. of Conductor (mm2) Factor
Solid 1
1.5
2.5
22
27
39
Stranded 1.5
2.5
4
6
10
31
43
58
68
146
Table A – Cable factors for short straight runs
B2) Sizing of Conduit
Conduit Diameter (mm) Factor
16 290
20 460
25 800
32 1400
Table B – Conduit factors for short straight runs
B2) Sizing of Conduit
Type of Conductor C.S.A. of Conductor
(mm2)
Factor
Solid or Stranded 1 16
1.5 22
2.5 30
4 41
6 58
10 105
Table C – Cable factors for long straight runs, or runs incorporating bends
B2) Sizing of Conduit
Table D – Conduit factors for runs incorporating bends
Refer to
Table A and B
B2)Sizing of Conduit
Example
 In a conduit installation the length of run is 10m,
assuming 2 right-angle bend. What is the
conduit size to enclose four 2.5 mm2 PVC cables?
 From Table C, factor for one 2.5mm2 cable = 30
 Therefore, four 2.5mm2 cables = 4 x 30 = 120
 From Table D, suitable conduit size with a factor of
141(>120) is 20mm.
[10m Vs 2 bends, cable factor : 141]
B3)Type of Trunking
 Use in conditions where a considerable no. of
cables are required in an installation or where
cables are too large for drawing into conduits.
 Erection time is reduced (wiring is easier and
quicker)
 Multi-compartment trunking provides circuit
segregation.
B3)Type of Trunking
Typical types of trunking
 A) Steel trunking for busbar rising mains.
 B) PVC skirting 3-compartment trunking for fitting-out
wiring works where different category circuits such as
Telephone cable, CABDS cable & power supply cable are
to be installed in same run.
 C) Floor trunking to BS 4678 : Part 2 provides cabling to
service boxes flushed with floor level (e.g. in open-plan
office or dental room)
 D) Tap-on trunking in factory for internal power supply
to machinery by plugging into the overhead trunking.
 E) Steel surface trunking for cable to BS 4678 : Part 1
B3)Type of Trunking
 Classification for protection against corrosion:
Class 1 Electroplated zinc having a minimum thickness
of zinc coating of 0.0012mm, inside and outside.
Class 2 As Class 1 but additional coating of stoved or air
drying paint, applied at least to the external
surface.
Class 3 Hot dip zinc coated steel.
B4) Sizing of Trunking
Type of Conductor C.S.A of Conductor (mm2) Factor
Solid 1.5
2.5
7.1
10.2
Stranded 1.5
2.5
4
6
10
8.1
11.4
15.2
22.9
36.3
Table E – Cable factors for trunking
B4) Sizing of Trunking
Dimension of Trunking (mm x mm) Factor
50 x 37.5 767
50 x 50 1037
75 x 25 738
75 x 37.5 1145
75 x 50 1555
75 x 75 2371
100 x 25 993
100 x 37.5 1542
100 x 50 2091
100 x 75 3189
100 x 100 4252
Table F –Factors for trunking
B4) Sizing of Trunking
Example
 What is the maximum no. of 10mm2 PVC cables
permitted in 50mm x 50mm trunking?
 From Table E, factor of 10mm2 conductor = 36.3
 From Table F, factor of 50 x 50mm trunking = 1037
 Maximum no. of cable= 1037 ÷ 36.3
= 28.56 (say 28)
B5) Ducting
 It provided mechanical protection for cable run
in the ground or under concreted floor.
 Types of ducting:
 Concrete ducts
 Steel underfloor ducts
 Fibre underfloor ducts
 Maximum spacing factor is 35%.
 It should be securely fixed and protected against
corrosion and mechanical damage.
B5) Ducting
 Entries to duct must be protected against the
inflow of water.
 Cables installed in underground ducts shall have
a metal sheath.
 Underfloor trunking should be fabricated with
sheet steel of not less than 12mm thickness for
compartment width up to 100mm, but at least
1.6mm thickness for compartment width over
100mm. The minimum thickness of 1mm shall
be used for the partitions and connector
material.
B6) Segregation of Circuits
 1) Suitable segregation between enclosed circuits with different
categories shall be provided in wiring. For example, a low voltage
circuit shall be separated from an extra-low voltage circuit.
 2) Types of Circuit:
Category 1 Circuit A circuit (other than a fire alarm or emergency
lighting circuit) operation at low voltage and
supplied directly from a main supply system
Category 2 Circuit With the exception of firm alarm and emergency
lighting circuits, ant circuit for telecommunication
(e.g. radio, telephone…) which is supplied form a
safety source.
Category 3 Circuit A fire alarm circuit or an emergency lighting
circuit.
Category 4 Circuit A high voltage circuit.
B6) Segregation of Circuits
 3) Low Voltage circuit shall be segregated form extra-low voltage
circuit. Extra-low voltage cables shall not be drawn into the same
conduit or duct, or terminated in the same box or block as low
voltage cables unless the former are insulated for the highest
voltage present in the low voltage circuit.
 4) Cables of fire alarm and emergency lighting circuits shall not in
any circumstances be drawn into the same conduit duct or ducting
of other cables.
B6) Segregation of Circuits
 5) Electrical services shall not be installed with pipes or tubes of
non-electrical services (e.g. air, gas, oil, or water) in the same
conduit, ducting or trunking. This requirement does not apply where
the various services are under common supervision and it is
confirmed that no mutual detrimental influence can occur.
 6) For cables of category 1,2,3 circuits that are installed without
enclosure or underground, a minimum separation of 50mm should
be provided between different category circuits or alternatively at
least 25mm separation with slabs of concrete inserted between the
circuits and the shortest path round the concrete should exceed
75mm.
B6) Segregation of Circuits
 7) Insulated bridge of at least 6mm thick should be used for
separation of surface wiring of Category 1,2,3 circuit running across
each other. The bridge should overlap the cables by at least 25mm
on either side of point of crossing.
 8) For cables of Category 4 circuit that are installed without
enclosure or underground, a minimum separation of 300mm should
be provided between Categories or alternatively a reduced
separation with 50mm thick slabs of concrete inserted between the
circuits and the shortest path round the concrete should exceed
180mm.
Example
 Descriptions:
 A flat of about 90m2 (useable area), with three bedrooms, (the master
bedroom with en-suite bathroom), a guest bathroom, a kitchen, a
dining room, lounge (living room) and a store room.
 An air-conditioner (<1.5 h.p., i.e. < 15A input current) is expected to be
in each bedroom.
 An large air-conditioner (may be >2 h.p., i.e. >=15A input current) is
expected to be in the dining room, and it also for the lounge.
 An electric cooker of about 14A rating is expected to be installed in the
kitchen.
 Hot water is provided by gas heaters in bathrooms and the kitchen
 Battery operated door bell and clocks are expected.
Example
Example
Example
 To provision here is more than that of the
minimum recommended requirements in the CP
for WR.
 No socket outlet is provided in the bathrooms,
and the switches for lighting and the ventilation
fan should be installed outside the bathrooms.
Example
Example
Typical Earthing Systems - 1
 TT system
 A system having one point of the source of energy
directly earthed, the exposed-conductive parts of the
installation being connected to earth electrodes
electrically independent of the earth electrodes of the
source.
Typical Earthing Systems - 2
 TN-S system
 A system having one point of the source of energy directly
earthed and having separate neutral and protective conductors
throughout the system.
Typical Earthing Systems - 3
 TNC-S system
 A system having one point of the source of energy directly
earthed, the neutral and protective functions are combined in a
single conductor in part of the system.
Type of Earth Electrode
 The following Earth Electrode
 Deep driven earth rods and/ or parallel driven earth
rods
 Buried tapes/ plated
 Welded metal reinforcement of concrete
Q & A
The End

More Related Content

What's hot

Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601SARAVANAN A
 
Norma EDP-Escelsa Instalações Individuais
Norma EDP-Escelsa Instalações IndividuaisNorma EDP-Escelsa Instalações Individuais
Norma EDP-Escelsa Instalações Individuaisjacksoow Sobrenome
 
Lv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizingLv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizingAsif Eqbal
 
ETAP - Coordinación de protecciones y arco eléctrico
ETAP - Coordinación de protecciones y arco eléctricoETAP - Coordinación de protecciones y arco eléctrico
ETAP - Coordinación de protecciones y arco eléctricoHimmelstern
 
Electrical Lessons learned
Electrical Lessons learnedElectrical Lessons learned
Electrical Lessons learnedmichaeljmack
 
13924257 calculo-de-las-corrientes-de-cortocircuito-121204141733-phpapp02
13924257 calculo-de-las-corrientes-de-cortocircuito-121204141733-phpapp0213924257 calculo-de-las-corrientes-de-cortocircuito-121204141733-phpapp02
13924257 calculo-de-las-corrientes-de-cortocircuito-121204141733-phpapp02Ivan Huamani
 
Weg fusibles-ultra-rapidos-tipo-nh-ar-50030486-catalogo-espanol
Weg fusibles-ultra-rapidos-tipo-nh-ar-50030486-catalogo-espanolWeg fusibles-ultra-rapidos-tipo-nh-ar-50030486-catalogo-espanol
Weg fusibles-ultra-rapidos-tipo-nh-ar-50030486-catalogo-espanolEdward S. Vidal Mendoza
 
Guia de interpretación de las curvas de disparo bt
Guia de interpretación de las curvas de disparo btGuia de interpretación de las curvas de disparo bt
Guia de interpretación de las curvas de disparo btSebastian Toloza
 
Instalaciones electricas-domiciliarias actividades inacap
Instalaciones electricas-domiciliarias actividades inacapInstalaciones electricas-domiciliarias actividades inacap
Instalaciones electricas-domiciliarias actividades inacapgabrielvenegas14
 
Catalogo de transformadores de medida y protección
Catalogo de transformadores de medida y protecciónCatalogo de transformadores de medida y protección
Catalogo de transformadores de medida y protecciónNestor Paco Choquecallata
 
Over current Relays
Over current RelaysOver current Relays
Over current RelaysASWANTH6270
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)Power System Operation
 
Electrical fuse power point presentation
Electrical fuse power point presentation Electrical fuse power point presentation
Electrical fuse power point presentation prasantakcs
 
Rated diversity factor of a switchboard
Rated diversity factor of a switchboardRated diversity factor of a switchboard
Rated diversity factor of a switchboardSayandeep Dasgupta
 
Calculo de corto circuito
Calculo de corto circuitoCalculo de corto circuito
Calculo de corto circuitoEduardo Raya
 

What's hot (20)

Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601
 
Ehv substation
Ehv substationEhv substation
Ehv substation
 
Norma EDP-Escelsa Instalações Individuais
Norma EDP-Escelsa Instalações IndividuaisNorma EDP-Escelsa Instalações Individuais
Norma EDP-Escelsa Instalações Individuais
 
Lv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizingLv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizing
 
IEEE 242-2001 Proteccion y Coordinacion.pdf
IEEE 242-2001 Proteccion y Coordinacion.pdfIEEE 242-2001 Proteccion y Coordinacion.pdf
IEEE 242-2001 Proteccion y Coordinacion.pdf
 
ETAP - Coordinación de protecciones y arco eléctrico
ETAP - Coordinación de protecciones y arco eléctricoETAP - Coordinación de protecciones y arco eléctrico
ETAP - Coordinación de protecciones y arco eléctrico
 
Mcb Breaker
Mcb Breaker Mcb Breaker
Mcb Breaker
 
Electrical Lessons learned
Electrical Lessons learnedElectrical Lessons learned
Electrical Lessons learned
 
13924257 calculo-de-las-corrientes-de-cortocircuito-121204141733-phpapp02
13924257 calculo-de-las-corrientes-de-cortocircuito-121204141733-phpapp0213924257 calculo-de-las-corrientes-de-cortocircuito-121204141733-phpapp02
13924257 calculo-de-las-corrientes-de-cortocircuito-121204141733-phpapp02
 
Weg fusibles-ultra-rapidos-tipo-nh-ar-50030486-catalogo-espanol
Weg fusibles-ultra-rapidos-tipo-nh-ar-50030486-catalogo-espanolWeg fusibles-ultra-rapidos-tipo-nh-ar-50030486-catalogo-espanol
Weg fusibles-ultra-rapidos-tipo-nh-ar-50030486-catalogo-espanol
 
Guia de interpretación de las curvas de disparo bt
Guia de interpretación de las curvas de disparo btGuia de interpretación de las curvas de disparo bt
Guia de interpretación de las curvas de disparo bt
 
Instalaciones electricas-domiciliarias actividades inacap
Instalaciones electricas-domiciliarias actividades inacapInstalaciones electricas-domiciliarias actividades inacap
Instalaciones electricas-domiciliarias actividades inacap
 
Catalogo de transformadores de medida y protección
Catalogo de transformadores de medida y protecciónCatalogo de transformadores de medida y protección
Catalogo de transformadores de medida y protección
 
ABB Transformers MV Medium Voltage Transformers Guide
ABB Transformers MV Medium Voltage Transformers GuideABB Transformers MV Medium Voltage Transformers Guide
ABB Transformers MV Medium Voltage Transformers Guide
 
Over current Relays
Over current RelaysOver current Relays
Over current Relays
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
 
Electrical fuse power point presentation
Electrical fuse power point presentation Electrical fuse power point presentation
Electrical fuse power point presentation
 
Rated diversity factor of a switchboard
Rated diversity factor of a switchboardRated diversity factor of a switchboard
Rated diversity factor of a switchboard
 
Calculo de corto circuito
Calculo de corto circuitoCalculo de corto circuito
Calculo de corto circuito
 

Similar to cable sizing.ppt

Cable ampacity calculations iec
Cable ampacity calculations  iecCable ampacity calculations  iec
Cable ampacity calculations iecJoe Khan
 
cable ampacity calculations- IEC
cable ampacity calculations- IECcable ampacity calculations- IEC
cable ampacity calculations- IECJoe Khan
 
Electrical component at airport for airfield lighting circuit
Electrical component at airport for airfield lighting circuitElectrical component at airport for airfield lighting circuit
Electrical component at airport for airfield lighting circuitRLarivee
 
Earthing and bonding - Power cables
Earthing and bonding - Power cablesEarthing and bonding - Power cables
Earthing and bonding - Power cablesLeonardo ENERGY
 
Dienhathe.com 3 red-line_technical_catalogue
Dienhathe.com 3 red-line_technical_catalogueDienhathe.com 3 red-line_technical_catalogue
Dienhathe.com 3 red-line_technical_catalogueDien Ha The
 
ABB CLMD Low Voltage Capacitors - ABB LV Capacitors CLMD03
ABB CLMD Low Voltage Capacitors - ABB LV Capacitors CLMD03ABB CLMD Low Voltage Capacitors - ABB LV Capacitors CLMD03
ABB CLMD Low Voltage Capacitors - ABB LV Capacitors CLMD03Thorne & Derrick International
 
Technical presentation on modern earthing
Technical presentation on modern earthingTechnical presentation on modern earthing
Technical presentation on modern earthingPankaj Chakraborty
 
Radio Interference Suppression Capacitors and Filters
Radio Interference Suppression Capacitors and FiltersRadio Interference Suppression Capacitors and Filters
Radio Interference Suppression Capacitors and FiltersMinka Grdesic
 
17 mse010 loss in pv plant
17 mse010 loss in pv plant17 mse010 loss in pv plant
17 mse010 loss in pv plantpaneliya sagar
 
IRJET- Design and Fabrication of a Single-Phase 1KVA Transformer with Aut...
IRJET-  	  Design and Fabrication of a Single-Phase 1KVA Transformer with Aut...IRJET-  	  Design and Fabrication of a Single-Phase 1KVA Transformer with Aut...
IRJET- Design and Fabrication of a Single-Phase 1KVA Transformer with Aut...IRJET Journal
 
ETAP - Ugs Underground Raceway Systems
ETAP - Ugs Underground Raceway SystemsETAP - Ugs Underground Raceway Systems
ETAP - Ugs Underground Raceway SystemsHimmelstern
 
Concept of energy transmission & distribution
Concept of energy transmission & distribution Concept of energy transmission & distribution
Concept of energy transmission & distribution ZunAib Ali
 
Simple 100 w inverter circuit
Simple 100 w inverter circuitSimple 100 w inverter circuit
Simple 100 w inverter circuitNarasimha Reddy
 
Grounding System Analysis
Grounding System AnalysisGrounding System Analysis
Grounding System Analysisijtsrd
 

Similar to cable sizing.ppt (20)

Cable ampacity calculations iec
Cable ampacity calculations  iecCable ampacity calculations  iec
Cable ampacity calculations iec
 
cable ampacity calculations- IEC
cable ampacity calculations- IECcable ampacity calculations- IEC
cable ampacity calculations- IEC
 
Electrical component at airport for airfield lighting circuit
Electrical component at airport for airfield lighting circuitElectrical component at airport for airfield lighting circuit
Electrical component at airport for airfield lighting circuit
 
Earthing and bonding - Power cables
Earthing and bonding - Power cablesEarthing and bonding - Power cables
Earthing and bonding - Power cables
 
Dienhathe.com 3 red-line_technical_catalogue
Dienhathe.com 3 red-line_technical_catalogueDienhathe.com 3 red-line_technical_catalogue
Dienhathe.com 3 red-line_technical_catalogue
 
H046044147
H046044147H046044147
H046044147
 
ABB CLMD Low Voltage Capacitors - ABB LV Capacitors CLMD03
ABB CLMD Low Voltage Capacitors - ABB LV Capacitors CLMD03ABB CLMD Low Voltage Capacitors - ABB LV Capacitors CLMD03
ABB CLMD Low Voltage Capacitors - ABB LV Capacitors CLMD03
 
Technical presentation on modern earthing
Technical presentation on modern earthingTechnical presentation on modern earthing
Technical presentation on modern earthing
 
Radio Interference Suppression Capacitors and Filters
Radio Interference Suppression Capacitors and FiltersRadio Interference Suppression Capacitors and Filters
Radio Interference Suppression Capacitors and Filters
 
Eat 105 Chapter 3
Eat 105  Chapter 3Eat 105  Chapter 3
Eat 105 Chapter 3
 
Specifications
SpecificationsSpecifications
Specifications
 
Heat sink
Heat sinkHeat sink
Heat sink
 
17 mse010 loss in pv plant
17 mse010 loss in pv plant17 mse010 loss in pv plant
17 mse010 loss in pv plant
 
IRJET- Design and Fabrication of a Single-Phase 1KVA Transformer with Aut...
IRJET-  	  Design and Fabrication of a Single-Phase 1KVA Transformer with Aut...IRJET-  	  Design and Fabrication of a Single-Phase 1KVA Transformer with Aut...
IRJET- Design and Fabrication of a Single-Phase 1KVA Transformer with Aut...
 
K2917.pptx
K2917.pptxK2917.pptx
K2917.pptx
 
ETAP - Ugs Underground Raceway Systems
ETAP - Ugs Underground Raceway SystemsETAP - Ugs Underground Raceway Systems
ETAP - Ugs Underground Raceway Systems
 
Concept of energy transmission & distribution
Concept of energy transmission & distribution Concept of energy transmission & distribution
Concept of energy transmission & distribution
 
Sistem breaker pro abb
Sistem breaker pro abbSistem breaker pro abb
Sistem breaker pro abb
 
Simple 100 w inverter circuit
Simple 100 w inverter circuitSimple 100 w inverter circuit
Simple 100 w inverter circuit
 
Grounding System Analysis
Grounding System AnalysisGrounding System Analysis
Grounding System Analysis
 

More from ChadWood16

17thEdition.ppt
17thEdition.ppt17thEdition.ppt
17thEdition.pptChadWood16
 
Electrical and Magnetic force fileds.pdf
Electrical and Magnetic force fileds.pdfElectrical and Magnetic force fileds.pdf
Electrical and Magnetic force fileds.pdfChadWood16
 
OverCurrent(1).pdf
OverCurrent(1).pdfOverCurrent(1).pdf
OverCurrent(1).pdfChadWood16
 
Lecture 12 Overcurrent Protection.pdf
Lecture 12 Overcurrent Protection.pdfLecture 12 Overcurrent Protection.pdf
Lecture 12 Overcurrent Protection.pdfChadWood16
 
Line Protection.pdf
Line Protection.pdfLine Protection.pdf
Line Protection.pdfChadWood16
 
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdfChadWood16
 
CH4_Transfo_Mesure(SP).pdf
CH4_Transfo_Mesure(SP).pdfCH4_Transfo_Mesure(SP).pdf
CH4_Transfo_Mesure(SP).pdfChadWood16
 
CH3_MALT_Reseaux(2016-01-20).pdf
CH3_MALT_Reseaux(2016-01-20).pdfCH3_MALT_Reseaux(2016-01-20).pdf
CH3_MALT_Reseaux(2016-01-20).pdfChadWood16
 

More from ChadWood16 (9)

17thEdition.ppt
17thEdition.ppt17thEdition.ppt
17thEdition.ppt
 
Electrical and Magnetic force fileds.pdf
Electrical and Magnetic force fileds.pdfElectrical and Magnetic force fileds.pdf
Electrical and Magnetic force fileds.pdf
 
OverCurrent(1).pdf
OverCurrent(1).pdfOverCurrent(1).pdf
OverCurrent(1).pdf
 
Lecture 12 Overcurrent Protection.pdf
Lecture 12 Overcurrent Protection.pdfLecture 12 Overcurrent Protection.pdf
Lecture 12 Overcurrent Protection.pdf
 
Line Protection.pdf
Line Protection.pdfLine Protection.pdf
Line Protection.pdf
 
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
 
CH4_Transfo_Mesure(SP).pdf
CH4_Transfo_Mesure(SP).pdfCH4_Transfo_Mesure(SP).pdf
CH4_Transfo_Mesure(SP).pdf
 
CH3_MALT_Reseaux(2016-01-20).pdf
CH3_MALT_Reseaux(2016-01-20).pdfCH3_MALT_Reseaux(2016-01-20).pdf
CH3_MALT_Reseaux(2016-01-20).pdf
 
CH2_.pdf
CH2_.pdfCH2_.pdf
CH2_.pdf
 

Recently uploaded

MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...Call Girls in Nagpur High Profile
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 

Recently uploaded (20)

MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 

cable sizing.ppt

  • 1. Schedule Ref. Date Topic A07 27 Oct 2005 Introduction and Load Assessment A08 3 Nov 2005 Standards and Basic Equipment A09 10 Nov 2005 Power Distribution & Final Circuit A10 17 Nov 2005 Protection & Earthing A11 24 Nov 2005 Cable & Wiring A12 1 Dec 2005 Standby Generator and Power Supplies
  • 2. Introduction Load Estimation Terminology Basic Equipment Codes and Standards Power Distribution & Final Circuit Protection & Cable Wiring Earthing Design of Electricity Distribution Standby Generator and Power Supplies
  • 3. Earthing and Design of Electricity Distribution Date : 24 November 2005 Module Code : A11 Ir. KF Cheung
  • 4. Earthed Equipotential Bonding and Automatic Disconnection C) Determination of Disconnection Time 1) Maximum values of earth loop impedance for various overcurrent protective devices are shown in table 41B1, Table 41B2 & Table 41D 2) Actual earth loop impedance can be calculated as follows: Zs = Ze + Z1 + Z2 Ze : Earth loop impedance at the source Z1 : Impedance of phase conductor Z2 : Impedance of circuit protective conductor (cpc)
  • 5. Earthed Equipotential Bonding and Automatic Disconnection C) Determination of Disconnection Time 3) Compare the actual Zs with the tabulated Zs(max):  The actual Zs value measured from the installation should be smaller than the Zs(max) value from IEE Tables in order to achieve safe disconnection time. Attention is drawn on that the Zs (max) form IEE Tables shall be converted to nominal supply voltage system in Hong Kong before comparison. Zs (max :220) = Zs (max : 240) in IEE Tables X 220/240
  • 6. Earthed Equipotential Bonding and Automatic Disconnection C) Determination of Disconnection Time 4) The earth fault current can be calculated using the following formula: If = Uo /Zs Uo = Phase to earth voltage If = earth fault current 5) By putting the calculated fault current against the characteristic curves of the protective device given in IEE, the actual disconnection time can be found.
  • 7. Example  A 220V circuit is protected by a 30A Type 2 MCB, the cable used is 2.5/1.5 twin with cpc PVC copper conductor, if the circuit length is 15m and Ze up to the MCB board is 0.5Ω, what is the actual disconnection time?  From table 17, R1+R2 /m = 19.51mΩ x 1.38 = 0.269 Ω/m
  • 9. A) Cable Selection  Factors to be considered in sizing of cable conductors  Conductor material  Insulating material  Method of installation  Installed environment  Ambient temperature  Thermal insulating enclosure  Adjacent cables  Type of protective device  Voltage drop  Minimum cross-sectional area
  • 10. Comparison between Copper Conductor and Aluminum Conductor  A) Copper Conductor  High degree of electrical conductivity  Tough, slow to tarnish  Can be jointed without any special provision to prevent electrolytic action  B) Aluminum Conductor  Lower price & light in weight  Pliable, it can be used in solid-core cables  Excellent resistance to corrosion
  • 12. Bends of Non-flexible Cable  The minimum internal radius bend in cables for fixing wiring are shown in the following table
  • 13. Correction Factor for Conductors  Factors which affect the ability of a cable to lose heat are:  Grouping (Cg or C1)  Ambient temperature (Ca or C2)  Thermal insulation (Ci or C3)  Semi-enclosed fuse to BS 3036 (0.725 or C4)  Type of installation (Table 4A)
  • 14. Correction Factor for Conductors  A) Grouping factor (Cg) - 1  IEE Table 4B1 gives correction factors to be applied to te tabulated current-carrying capacities where cables or circuits are grouped.  Where the horizontal clearance s between adjacent cables exceed two cable diameter (2D2), no correction factor need be applied.
  • 15. Correction Factor for Conductors  A) Grouping factor (Cg) - 2  If a cable is expected to carry not more than 30% of its grouped rating, it may be ignored from the rest of the group.
  • 16. Correction Factor for Conductors  B) Correction Factor for Ambient Temperature (Ca)  Correction factor for ambient temperature is shown in IEE Table 4C1. Where for semi-enclosed fuses are being used, see IEE Table 4C2. It ≥ In / Ca  Typical data are shown in the following table for quick reference.
  • 17. Correction Factor for Conductors  C) Correction Factor for thermal Insulation (Ci)  The value of current-carrying-capacity for various sizes of conductors shown in Tables of Appendix 4 have been taken into account of cables installed in a thermally insulated wall or ceiling where one side of the cable is in contact with a thermally conductive surface.  Where the cable is totally enclosed in thermal insulation, Ci=0.5 shall be used in absence of more precise information. It ≥ In / Ci  Ci shall only be applied to the ‘open and clipped direct’ column of respective IEE Tables.
  • 18. Correction Factor for Conductors  D) factor for Semi-enlosed fuse to BS3036 (C4)  When semi-enclosed fuse is used for protecting the conductor, a derating factor of 0.726 shall be applied.
  • 19. Correction Factor for Conductors  E) General Formula for Correction Factors Applied to Cable Sizing  It ≥ In / Cg x Ca x Ci x C4
  • 21. Example  Protective device : BS 3036 fuses  Ambient temperature: 30oC  Cable use :PVC twin with cpc cable  Cabling conditions at:  1) Bunched and clipped direct  2) Passed through totally enclosed thermal insulation area  3) One side in contact with thermally insulated ceiling  4) Passed through a boiler house where ambient temperature of 45oC  5) Clipped direct  Ignore voltage drop  What cable sizes are required?
  • 22. Voltage Drop  The overall voltage drop shall not exceed the value appropriate to the safe functioning of the equipment in normal service.  The voltage drop in any circuit from the origin of installation to the current-using equipment should not exceed 4% of the nominal voltage.  Volt drop pre unit value in from of mv/A/m are shown on IEE tables of Appendix 4. The values are based on the circuit conductor working at the maximum permitted operating temperature and at unity power factor.
  • 26. Voltage Drop  Voltage drop (V.D.) can be calculated as follows: V.D. = design current (Ib) x circuit length (L) x volt drop per unit (mv/A/m)
  • 27. Example  A PVC/SWA/PVC armoured cable is to be installed from an HRC 100A fuse in a distribution board to a 3-phase 380V motor, along with 5 other cables fixed to a perforated metal cable tray where the cable sheaths will be touching, if the cable length is 100 meters and the power factor of the load is 0.866, what size of cable would be required to satisfy voltage drop if the ambient temperature is 30oC and the voltage drop in the 3 phase feeder cable up to the distribution board is 7.7V and the total voltage drop allowed is 4%?
  • 28. Sizing Circuit Protective Conductors  If the conductor ≤ 35mm2 : Zs = Ze + R1 + R2 >35mm2 : Zs = Ze + Z1 + Z2  Use the formula : S ≥ √{(I2t)} / K  Value of K : from IEE Tables 54B to 54F  If = Uo / Zs  Value of t from IEE Fig. 1 to 8 of Appendix 3  Use Table 54G to size the minimum size of protective conductors.
  • 29. Thermal Constraint  To protect conductor insulation against thermal damage during short circuit conditions. I2 t = K2 S2 t = K2 S2/ I2 t = duration in second S = cross-sectional area in mm2 I = effective short-circuit current in A K = 115 for copper conductor insulated with PVC
  • 30. Thermal Constraint Procedure  To check the prospective short-circuit current at the farthest point of the circuit from the point where the device is installed  To check the operation time of the device according to the short-circuit current from the time/ current characteristic of the device  To check the adiabatic line of the conductor by superimposing onto the characteristics of protective devices.
  • 31. Cable Selection Procedure  Select wiring system to be installed and type of cable  Calculate the equipment current demand using Table 4A (15 Edition) Calculate the circuit design current (Ib) and using diversity allowance.  Determine the overcueent protective device (In) : type; rating Check Ib ≤ In  Determine correction factors for installation  Grouping (Cg)  Ambient temperature (Ca)  Thermal insulation (Ci)  Semi-enclosed fuse (C4)
  • 32. Cable Selection Procedure  Calculate the tabulated current carrying capacity of conductor: It (min) ≥ In x (1/ Cg) x (1/ Ca) x (1/ Ci) x (1/ C4)  Select cable size from Appendix 4 Check Ib ≤ In ≤ Iz  Calculate volt drop at the farthest point of circuit
  • 33. Cable Selection Procedure  Dose device offer shock protection in accordance with table 41B1, 41B2 & 41D for Zs (max)? Check Zs ≤ Zs (max) from the tables If No :  Re-select device or re-select phase conductor size  Re-select cpc size  Use alternative method as stated in Reg. 413-02-12 Checked by calculation  Obtain Ze form supply authority  Calculate R1 + R2 using Table 17A & B  Determine actual Zs = Ze + (R1 + R2)
  • 34. Cable Selection Procedure  Dose the type and size of cpc offer protection? Check : S ≥ √{(I2t)} / K If No : re-select type and/ or size of cpc  Check the adiabatic line of conductor against the characteristic of overcurrent protective device.
  • 35. B1) Type of Conduit B2) Sizing of Conduit B3) Type of Trunking B4) Sizing of Trunking B5) Ducting B6) Segregation of Circuit B) Conduit & Trunking
  • 36. Steel Conduit to BS 4568 : Part 1  A) Light duty type: plain and conduits  Limited to use in dry situation;  Unsuitable for bending  Low degree of mechanical protection  B) Heavy duty type: screwed-end conduits  Back enamel for internal use in dry situation;  Hot-dip galvanized for external use in situation subject to dampness or water condensation;  Good mechanical strength and electrical continuity. B1) Type of Conduit
  • 37. B1) Type of Conduit Steel Conduit to BS 4568 : Part 1  C) Classification for protection: Class Protection Applied Example 1 Light protection both inside & outside Priming paint 2 Medium protection both inside & outside Stoved enamel; Air-drying paint 3 Medium heavy protection : inside as Class 2; Outside as Class 4 Stoved enamel inside; Sherardized outside 4 Heavy protection both inside & outside Hot-dip zinc coating, sherardizing
  • 38. Steel Conduit to BS 4568 : Part 1  D) Heavy duty hot-dip galvanized steel conduit system is the most common use system for surface conduit wiring and concealed conduit wiring. Conduit is supplied in standard lengths of 4 meters and is manufactured in accordance with BS4568. B1) Type of Conduit
  • 39. Plastic conduits  To BS4607 Part 1 and 2;  Characteristics : light, easily bend, less installation time, no water condensation, lower cost;  Heavy duty PVC conduits can be concealed but CPC are required. B1) Type of Conduit
  • 40. Copper Conduits  High resistance to corrosion;  Last for long time;  Higher cost;  Act as excellent circuit protective conductor (CPC) B1) Type of Conduit
  • 41. Aluminum Conduits  Light weight and lower cost;  Not so good in mechanical protection Flexible Conduits  To BS731 : Part 1  Used for final connection to machinery;  CPC are required. B1) Type of Conduit
  • 42. B2) Sizing of Conduit  IEE Regulation (15th Edition) provide the following tables for ease of conduit sizing:  Table A, B for 1/C PVC cables in a straight run ≤ 3m;  Table C, D for 1/C PVC cable in conduit run > 3m.  The conduit size is considered satisfactory if the conduit factor is equal to or exceeds the sum of the cable factors
  • 43. B2) Sizing of Conduit Type of Conductor C.S.A. of Conductor (mm2) Factor Solid 1 1.5 2.5 22 27 39 Stranded 1.5 2.5 4 6 10 31 43 58 68 146 Table A – Cable factors for short straight runs
  • 44. B2) Sizing of Conduit Conduit Diameter (mm) Factor 16 290 20 460 25 800 32 1400 Table B – Conduit factors for short straight runs
  • 45. B2) Sizing of Conduit Type of Conductor C.S.A. of Conductor (mm2) Factor Solid or Stranded 1 16 1.5 22 2.5 30 4 41 6 58 10 105 Table C – Cable factors for long straight runs, or runs incorporating bends
  • 46. B2) Sizing of Conduit Table D – Conduit factors for runs incorporating bends Refer to Table A and B
  • 47. B2)Sizing of Conduit Example  In a conduit installation the length of run is 10m, assuming 2 right-angle bend. What is the conduit size to enclose four 2.5 mm2 PVC cables?  From Table C, factor for one 2.5mm2 cable = 30  Therefore, four 2.5mm2 cables = 4 x 30 = 120  From Table D, suitable conduit size with a factor of 141(>120) is 20mm. [10m Vs 2 bends, cable factor : 141]
  • 48. B3)Type of Trunking  Use in conditions where a considerable no. of cables are required in an installation or where cables are too large for drawing into conduits.  Erection time is reduced (wiring is easier and quicker)  Multi-compartment trunking provides circuit segregation.
  • 49. B3)Type of Trunking Typical types of trunking  A) Steel trunking for busbar rising mains.  B) PVC skirting 3-compartment trunking for fitting-out wiring works where different category circuits such as Telephone cable, CABDS cable & power supply cable are to be installed in same run.  C) Floor trunking to BS 4678 : Part 2 provides cabling to service boxes flushed with floor level (e.g. in open-plan office or dental room)  D) Tap-on trunking in factory for internal power supply to machinery by plugging into the overhead trunking.  E) Steel surface trunking for cable to BS 4678 : Part 1
  • 50. B3)Type of Trunking  Classification for protection against corrosion: Class 1 Electroplated zinc having a minimum thickness of zinc coating of 0.0012mm, inside and outside. Class 2 As Class 1 but additional coating of stoved or air drying paint, applied at least to the external surface. Class 3 Hot dip zinc coated steel.
  • 51. B4) Sizing of Trunking Type of Conductor C.S.A of Conductor (mm2) Factor Solid 1.5 2.5 7.1 10.2 Stranded 1.5 2.5 4 6 10 8.1 11.4 15.2 22.9 36.3 Table E – Cable factors for trunking
  • 52. B4) Sizing of Trunking Dimension of Trunking (mm x mm) Factor 50 x 37.5 767 50 x 50 1037 75 x 25 738 75 x 37.5 1145 75 x 50 1555 75 x 75 2371 100 x 25 993 100 x 37.5 1542 100 x 50 2091 100 x 75 3189 100 x 100 4252 Table F –Factors for trunking
  • 53. B4) Sizing of Trunking Example  What is the maximum no. of 10mm2 PVC cables permitted in 50mm x 50mm trunking?  From Table E, factor of 10mm2 conductor = 36.3  From Table F, factor of 50 x 50mm trunking = 1037  Maximum no. of cable= 1037 ÷ 36.3 = 28.56 (say 28)
  • 54. B5) Ducting  It provided mechanical protection for cable run in the ground or under concreted floor.  Types of ducting:  Concrete ducts  Steel underfloor ducts  Fibre underfloor ducts  Maximum spacing factor is 35%.  It should be securely fixed and protected against corrosion and mechanical damage.
  • 55. B5) Ducting  Entries to duct must be protected against the inflow of water.  Cables installed in underground ducts shall have a metal sheath.  Underfloor trunking should be fabricated with sheet steel of not less than 12mm thickness for compartment width up to 100mm, but at least 1.6mm thickness for compartment width over 100mm. The minimum thickness of 1mm shall be used for the partitions and connector material.
  • 56. B6) Segregation of Circuits  1) Suitable segregation between enclosed circuits with different categories shall be provided in wiring. For example, a low voltage circuit shall be separated from an extra-low voltage circuit.  2) Types of Circuit: Category 1 Circuit A circuit (other than a fire alarm or emergency lighting circuit) operation at low voltage and supplied directly from a main supply system Category 2 Circuit With the exception of firm alarm and emergency lighting circuits, ant circuit for telecommunication (e.g. radio, telephone…) which is supplied form a safety source. Category 3 Circuit A fire alarm circuit or an emergency lighting circuit. Category 4 Circuit A high voltage circuit.
  • 57. B6) Segregation of Circuits  3) Low Voltage circuit shall be segregated form extra-low voltage circuit. Extra-low voltage cables shall not be drawn into the same conduit or duct, or terminated in the same box or block as low voltage cables unless the former are insulated for the highest voltage present in the low voltage circuit.  4) Cables of fire alarm and emergency lighting circuits shall not in any circumstances be drawn into the same conduit duct or ducting of other cables.
  • 58. B6) Segregation of Circuits  5) Electrical services shall not be installed with pipes or tubes of non-electrical services (e.g. air, gas, oil, or water) in the same conduit, ducting or trunking. This requirement does not apply where the various services are under common supervision and it is confirmed that no mutual detrimental influence can occur.  6) For cables of category 1,2,3 circuits that are installed without enclosure or underground, a minimum separation of 50mm should be provided between different category circuits or alternatively at least 25mm separation with slabs of concrete inserted between the circuits and the shortest path round the concrete should exceed 75mm.
  • 59. B6) Segregation of Circuits  7) Insulated bridge of at least 6mm thick should be used for separation of surface wiring of Category 1,2,3 circuit running across each other. The bridge should overlap the cables by at least 25mm on either side of point of crossing.  8) For cables of Category 4 circuit that are installed without enclosure or underground, a minimum separation of 300mm should be provided between Categories or alternatively a reduced separation with 50mm thick slabs of concrete inserted between the circuits and the shortest path round the concrete should exceed 180mm.
  • 60. Example  Descriptions:  A flat of about 90m2 (useable area), with three bedrooms, (the master bedroom with en-suite bathroom), a guest bathroom, a kitchen, a dining room, lounge (living room) and a store room.  An air-conditioner (<1.5 h.p., i.e. < 15A input current) is expected to be in each bedroom.  An large air-conditioner (may be >2 h.p., i.e. >=15A input current) is expected to be in the dining room, and it also for the lounge.  An electric cooker of about 14A rating is expected to be installed in the kitchen.  Hot water is provided by gas heaters in bathrooms and the kitchen  Battery operated door bell and clocks are expected.
  • 63. Example  To provision here is more than that of the minimum recommended requirements in the CP for WR.  No socket outlet is provided in the bathrooms, and the switches for lighting and the ventilation fan should be installed outside the bathrooms.
  • 66. Typical Earthing Systems - 1  TT system  A system having one point of the source of energy directly earthed, the exposed-conductive parts of the installation being connected to earth electrodes electrically independent of the earth electrodes of the source.
  • 67. Typical Earthing Systems - 2  TN-S system  A system having one point of the source of energy directly earthed and having separate neutral and protective conductors throughout the system.
  • 68. Typical Earthing Systems - 3  TNC-S system  A system having one point of the source of energy directly earthed, the neutral and protective functions are combined in a single conductor in part of the system.
  • 69. Type of Earth Electrode  The following Earth Electrode  Deep driven earth rods and/ or parallel driven earth rods  Buried tapes/ plated  Welded metal reinforcement of concrete
  • 70. Q & A