NEMA BU 1.1
GENERAL INSTRUCTIONS
FOR HANDLING,
INSTALLATION,
OPERATION, AND
MAINTENANCE OF
BUSWAY
RATED 600 VOLTS
OR LESS
NEMA Standards Publication BU 1.1-2010
General Instructions for Handling, Installation, Operation, and Maintenance
of Busway Rated 600 Volts or Less
Published by:
National Electrical Manufacturers Association
1300 North 17th Street, Suite 1752
Rosslyn, Virginia 22209
www.nema.org
© Copyright 2010 by the National Electrical Manufacturers Association. All rights including translation into
other languages, reserved under the Universal Copyright Convention, the Berne Convention for the
Protection of Literary and Artistic Works, and the International and Pan American Copyright Conventions.
NOTICE AND DISCLAIMER
The information in this publication was considered technically sound by the consensus of persons
engaged in the development and approval of the document at the time it was developed. Consensus
does not necessarily mean that there is unanimous agreement among every person participating in the
development of this document.
The National Electrical Manufacturers Association (NEMA) standards and guideline publications, of which
the document contained herein is one, are developed through a voluntary consensus standards
development process. This process brings together volunteers and/or seeks out the views of persons
who have an interest in the topic covered by this publication. While NEMA administers the process and
establishes rules to promote fairness in the development of consensus, it does not write the document
and it does not independently test, evaluate, or verify the accuracy or completeness of any information or
the soundness of any judgments contained in its standards and guideline publications.
NEMA disclaims liability for any personal injury, property, or other damages of any nature whatsoever,
whether special, indirect, consequential, or compensatory, directly or indirectly resulting from the
publication, use of, application, or reliance on this document. NEMA disclaims and makes no guaranty or
warranty, express or implied, as to the accuracy or completeness of any information published herein,
and disclaims and makes no warranty that the information in this document will fulfill any of your particular
purposes or needs. NEMA does not undertake to guarantee the performance of any individual
manufacturer or seller’s products or services by virtue of this standard or guide.
In publishing and making this document available, NEMA is not undertaking to render professional or
other services for or on behalf of any person or entity, nor is NEMA undertaking to perform any duty owed
by any person or entity to someone else. Anyone using this document should rely on his or her own
independent judgment or, as appropriate, seek the advice of a competent professional in determining the
exercise of reasonable care in any given circumstances. Information and other standards on the topic
covered by this publication may be available from other sources, which the user may wish to consult for
additional views or information not covered by this publication.
NEMA has no power, nor does it undertake to police or enforce compliance with the contents of this
document. NEMA does not certify, test, or inspect products, designs, or installations for safety or health
purposes. Any certification or other statement of compliance with any health or safety–related information
in this document shall not be attributable to NEMA and is solely the responsibility of the certifier or maker
of the statement.
BU 1.1-2010
Page i
CONTENTS
Foreword........................................................................................................................................................ ii
Section 1 SCOPE.................................................................................................................................................1
Section 2 REFERENCED STANDARDS............................................................................................................2
Section 3 GENERAL............................................................................................................................................3
Section 4 HANDLING...........................................................................................................................................4
Section 5 STORAGE............................................................................................................................................5
Section 6 INSTALLATION ...................................................................................................................................6
6.1 General.................................................................................................................................................6
6.2 Unpacking ............................................................................................................................................6
6.3 Hoisting and Handling (See Also Section 4).......................................................................................6
6.4 Hanging or Supporting.........................................................................................................................6
6.5 Joint Assembly.....................................................................................................................................7
6.6 Grounding.............................................................................................................................................7
6.7 Mounting Plug-In Devices....................................................................................................................8
6.8 Protection from Liquids, Moisture, and Other Contaminants..............................................................8
6.9 Summary..............................................................................................................................................9
Section 7 STEPS TO BE TAKEN BEFORE ENERGIZING..............................................................................10
Section 8 ENERGIZING EQUIPMENT..............................................................................................................11
Section 9 CARE AND MAINTENANCE ............................................................................................................12
9.1 Outdoor Busway ................................................................................................................................12
9.2 Indoor Busway ...................................................................................................................................12
9.3 Busway Plugs and Cubicles with Protective Devices.......................................................................13
9.4 Final Test............................................................................................................................................15
Section 10 PERMISSIBLE LOADING OF BUSWAYS .....................................................................................16
10.1 Busways—With or Without Overcurrent Protection..........................................................................16
10.2 Busway Plugs.....................................................................................................................................16
Section 11 OPERATING CONDITIONS ...........................................................................................................17
© Copyright 2010 by the National Electrical Manufacturers Association.
BU 1.1-2010
Page ii
FOREWORD
This publication is a guide of practical information containing instructions for the proper handling,
installation, operation, and maintenance of busway and associated fittings rated 600 volts or less.
These instructions do not purport to cover all details or variations in equipment, nor to provide for every
possible contingency regarding handling, installation, operation, or maintenance.
It is recommended that work described in this set of instructions be performed only by qualified personnel
familiar with the construction and operation of busway and associated fittings and that such work be
performed only after reading this complete set of instructions. For specific information not covered by
these instructions, you are urged to contact the manufacturer of the busway directly.
These recommendations of the Busway Section of the National Electrical Manufacturers Association will
be found useful by architects, electrical engineers, electrical contractors, electricians, maintenance
engineers, and others. These recommendations will be reviewed periodically by the section and updated
as necessary. Please address any comments or questions you may have on the text to:
Vice President, Technical Services
National Electrical Manufacturers Association
1300 N. 17th Street, Suite 1752
Rosslyn, VA 22209
This Standards Publication was developed by the Busway Section. At the time it was approved, the
Group/Section was composed of the following members:
Eaton Electrical, Inc.—Pittsburgh, PA
GE Consumer & Industrial—Plainville, CT
Schneider Electric/Square D—Smyrna, TN
Siemens Industry, Inc.—Norcross, GA
Publication No. BU 1.1-2010 revises and supersedes BU 1.1-2005.
© Copyright 2010 by the National Electrical Manufacturers Association.
BU 1.1-2010
Page 1
Section 1
SCOPE
This Standards Publication covers products for distribution of electric power at 600 volts or less,
consisting of enclosed sectionalized prefabricated busbars rated at 100 amperes or more, and associated
structures and fittings, classified as follows:
a. Feeder busways (indoor or outdoor)
b. Plug-in busways (indoor only)
c. Accessories required to complete the busway system
It does not pertain to metal-enclosed busways as described in the ANSI/IEEE C37.23 standard.
© Copyright 2010 by the National Electrical Manufacturers Association.
BU 1.1-2010
Page 2
Section 2
REFERENCED STANDARDS
National Electrical Manufacturers Association
1300 N. 17th Street, Suite 1752
Rosslyn, VA 22209
NEMA AB 4 Guidelines for Inspection and Preventive Maintenance of Molded Case Circuit Breakers
Used in Commercial and Industrial Applications
NEMA KS 3 Guidelines for Inspection and Preventive Maintenance of Switches Used in Commercial
and Industrial Applications
National Fire Protection Association
Batterymarch Park
Quincy, MA 02269
NFPA 70 National Electrical Code®
NFPA 70E Standard for Electrical Safety Requirements for Employee Workplace
Institute of Electrical and Electronics Engineers
445 Hoes Lane
Piscataway, NJ 08855-1331
IEEE C37.23 IEEE Standard for Metal-Enclosed Bus
© Copyright 2010 by the National Electrical Manufacturers Association.
BU 1.1-2010
Page 3
Section 3
GENERAL
3.1 Proper planning and coordination between trades, heating contractors, and plumbing contractors
are important for a good busway layout.
3.2 The successful operation of busway is dependent upon proper handling, installation, operation, and
maintenance, as well as upon proper design and manufacture. Neglecting certain fundamental
installation and maintenance requirements may lead to personal injury and damage to electrical
equipment or other property.
3.3 Installation, operation, and maintenance of busway should be conducted only by qualified
personnel.
3.4 For purposes of these guidelines, a qualified person is one who is familiar with the installation,
construction, and operation of the equipment and the hazards involved. In addition, the person
should be:
a. Knowledgeable of the requirements of the National Electrical Code and of all other applicable
codes, laws, and standards.
b. Trained and authorized to test, energize, clear, ground, tag, and lockout circuits and equipment in
accordance with established safety practices.
c. Trained in the proper care and use of personal protective equipment such as rubber gloves, hard
hats, safety glasses or face shields, and flash resistant clothing in accordance with established
safety practices and potential level of the hazard.
d. Trained in rendering first aid.
WARNING: HAZARDOUS VOLTAGES IN ELECTRICAL EQUIPMENT CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. UNLESS OTHERWISE SPECIFIED, INSTALLATION, INSPECTION,
AND MAINTENANCE SHOULD ONLY BE PERFORMED ON BUSWAY AND EQUIPMENT TO WHICH
POWER HAS BEEN TURNED OFF, DISCONNECTED, AND ELECTRICALLY ISOLATED SO THAT NO
ACCIDENTAL CONTACT CAN BE MADE WITH ENERGIZED PARTS. FOLLOW ALL
MANUFACTURER’S WARNINGS AND INSTRUCTIONS.
WARNING: OPERATION OF BUSWAY THAT HAS BEEN WATER OR MOISTURE DAMAGED CAN
CAUSE PROPERTY DAMAGE, SEVERE PERSONAL INJURY, OR DEATH. OBSERVE THE
PRECAUTIONS IN SECTIONS 6.8 AND 6.9 TO ENSURE ADEQUATE INSULATION RESISTANCE
AND THAT SOURCES OF MOISTURE ARE ELIMINATED.
SAFETY RELATED WORK PRACTICES, AS DESCRIBED IN NFPA 70E, SHOULD BE FOLLOWED AT
ALL TIMES.
CAUTION: Hydrocarbon spray propellants and hydrocarbon based sprays or compounds will cause
degradation of certain plastics and elastomers. Contact the busway manufacturer before using these
products to clean, dry, or lubricate compounds during installation or maintenance.
© Copyright 2010 by the National Electrical Manufacturers Association.
BU 1.1-2010
Page 4
Section 4
HANDLING
These guidelines are provided to help avoid personal injury and equipment damage during handling, and
to facilitate moving the busway sections and fittings at the job site.
4.1 Follow the manufacturer's handling instructions for the specific equipment, if available.
4.2 Handle busway with care to avoid damage to internal components and the enclosure or its finish.
Avoid subjecting busway to twisting, denting, impact, and, in general, rough handling.
4.3 Do not use busbar ends for lifting busway sections or fittings.
4.4 When the busway is received, unpack it sufficiently to inspect it for concealed damage and to
determine that the shipment is complete and correct.
4.5 If busway is to be stored prior to installation, restore the packing for protection during that period
(See Section 5). When conditions permit, leave the packing intact until the sections or fittings are
at their final installation location.
4.6 Verify that the weight of any busway sections or fittings are within the rated capacity of the
handling equipment to be used.
4.7 Platform dollies provide a simple method of moving busway on one floor level if there is little or no
incline. Balance the load carefully.
4.8 A forklift truck may offer a more convenient method of handling busway and has the added
advantage of permitting it to be hoisted between levels. Balance the load carefully.
4.9 Platform lifts or elevators, either manually or power operated, can be used advantageously in
moving loads of busway between elevations.
© Copyright 2010 by the National Electrical Manufacturers Association.
BU 1.1-2010
Page 5
Section 5
STORAGE
5.1 Busway sections and fittings that are not to be installed and energized immediately should be
stored in a clean, dry space having a uniform temperature to prevent condensation. Preferably,
they should be stored in a heated building having adequate air circulation and protected from dirt,
fumes, water, and physical damage.
5.2 It is recommended that busway should not be stored outdoors. However, if it must be stored
outdoors, cover it securely to provide protection from weather and dirt. Temporary electrical
heating should be installed beneath the cover to prevent condensation. At least 3 watts per cubic
foot is adequate for the average environment.
5.3 Outdoor busway is not weather resistant until completely and properly installed and should be
treated exactly the same as indoor busway until after it is installed.
© Copyright 2010 by the National Electrical Manufacturers Association.
BU 1.1-2010
Page 6
Section 6
INSTALLATION
6.1 GENERAL
6.1.1 Provide sufficient horizontal and vertical clearance from walls and ceilings to provide easy access
to joints, both for the original installation and possible removal of a section when required.
Busways may be installed behind panels if means of access are provided and if all the conditions
of Article 368 of the National Electrical Code are met.
6.1.2 Follow the manufacturer's installation instructions and the current edition of the National Electrical
Code.
6.1.3 Conduct an insulation resistance test on each busway device with an insulation resistance tester
rated 1000 volts to ensure that the system is free from short circuits and grounds (phase-to-
ground, phase-to-neutral, and phase-to-phase). Record and maintain records of the testing
results. Turn the test results over to the general contractor or owner at completion of the project.
It should be noted that readings vary inversely with the length of run and width or number of bars
per phase. Readings will vary with humidity. If readings of less than 1 megohm for a 100-foot run
(MEGOHMS = 100 / length of busway in feet) are obtained, contact the manufacturer.
6.2 UNPACKING
6.2.1 Care must be used in unpacking. Band cutters should be used on all banding securing the
package.
6.2.2 Nail pullers should be used for unpacking wooden crates to avoid damage.
6.2.3 Remove any support blocks that may have been used for shipping.
6.3 HOISTING AND HANDLING (SEE ALSO SECTION 4)
6.3.1 If a crane is used to install busway, use nylon straps and distribute or balance the weight of each
lift. If cables are used, spreaders should be used to avoid damage to the busway's metal housing.
6.3.2 If a forklift truck or similar hoist is used, properly position the busway on the fork to distribute its
weight. Careful approach is a must to avoid any damage to the metal housing that could pinch
the bus bar insulation and result in a failure.
6.3.3 Do not drag the busway across the floor.
6.3.4 When installing vertical sections, it is easier to lower the busway from the floor above where it will
be installed. Vertical sections are often stored on the floor above their final location to facilitate
lowering them into position.
6.4 HANGING OR SUPPORTING
6.4.1 Use the hangers or the hanging recommendations supplied by the manufacturer in the manner
prescribed to afford a secure installation and proper spacing.
© Copyright 2010 by the National Electrical Manufacturers Association.
BU 1.1-2010
Page 7
6.4.2 Horizontal Mounting
A busway that is mounted horizontally should be supported at a maximum of 5-foot intervals and in no
case at more than 10-foot intervals if it is marked as being suitable for such intervals.
The supports and/or the busway should be braced to minimize swaying. Align busway runs vertically and
horizontally to minimize sags and twists.
Bus plugs or cubicles that have considerable weight and that are mounted with a horizontal run of
busway should be separately supported by the building structure to prevent twisting or deformation of the
busway. Exercise caution when plugs are used on one side of a busway or when there are more plugs on
one side than on the other.
6.4.3 Vertical Mounting
A busway that is to be mounted vertically should be marked to indicate that it is suitable for that service.
When the distance between floor supports is more than the busway is marked as suitable for, the
manufacturer's recommendation regarding intermediate supports should be followed, but in no case
should support intervals exceed 16 feet. Heavy cubicles, panelboards, and bus plugs should be
separately supported by the building structure when so recommended by the manufacturer.
Align busway runs vertically and horizontally to minimize sags and twists.
During installation, protect vertical busways from moisture infiltration from unfinished roofs, walls, etc.
6.4.4 Expansion Joints
A busway section that spans a building expansion joint should be provided with suitable expansion
means for both the busbars and the busway housing unless the length of busway beyond the building
expansion joint is sufficiently short so that the supporting means can be designed to withstand the
expected building motion. Expansion joints may also be required on unusually long, straight runs or
vertical risers. Consult the busway manufacturer for recommendations on specific layouts.
6.4.5 Level and plumb busway (align horizontally and vertically) before the final tightening of all joints.
6.5 JOINT ASSEMBLY
6.5.1 Ensure that all contact surfaces are clean and free of contaminants.
6.5.2 Align the busbar ends of adjoining sections, verifying proper phase alignment, and slide the
sections together.
6.5.3 Use joint pullers, if available.
6.5.4 Follow the manufacturer's instructions for proper completion of joint assemblies and torquing of
joint bolts.
6.5.5 Busway should be properly covered during installation to protect it from moisture or other types of
contaminants.
6.6 GROUNDING
6.6.1 The enclosure of a UL listed busway marked with a short-circuit current rating is recognized as
an equipment grounding conductor. However, the enclosure must be properly bonded to other
equipment grounding conductors in the system, and all of these conductors must be properly
© Copyright 2010 by the National Electrical Manufacturers Association.
BU 1.1-2010
Page 8
connected to a suitable system ground. Consult the National Electrical Code for proper system
grounding procedures.
6.7 MOUNTING PLUG-IN DEVICES
6.7.1 Follow the manufacturer's instructions for the proper mounting of plug-in devices.
6.7.2 Allow sufficient clearances to install, operate, and remove devices and open covers when
necessary.
6.7.3 All plug-in openings that are not in use should be covered when such covers are provided.
6.7.4 All tap-off or plug-in devices should be in the “OFF” position during installation and removal.
6.8 PROTECTION FROM LIQUIDS, MOISTURE, AND OTHER CONTAMINANTS
6.8.1 Busway should be protected from liquids, moisture, and other contaminants to prevent electrical
failure.
6.8.2 Some common sources of such contaminants are described below.
6.8.2.1 During construction—Indoor busways must be protected from moisture during and after
installation. Protective measures should be taken to prevent condensation formation inside the
busway when installed in unheated buildings. Special attention should be given to riser busways
during construction to protect them from moisture from uncompleted roofs, walls, etc. Outdoor
busway is not weather resistant until completely and properly installed. It should be treated
exactly the same as indoor busway until after it is installed. Always verify that the insulation
resistance test of 7.4 has been conducted before energizing any busway for the first time.
6.8.2.2 Floor level liquids—Four-inch minimum curbs should be installed around all floor openings for
riser busways to prevent floor level liquids from entering the opening.
6.8.2.3 Leaking Roof—Protect indoor busway with a temporary sheet metal shield or other protective
cover to prevent water from falling onto the busway until the roof is repaired.
6.8.2.4 Pipes—Protect indoor busway with a temporary sheet metal shield or other protective cover to
prevent water from falling onto the busway until leaking pipes are repaired. Where pipes
(especially cold water pipes) pass directly above indoor busway, the busway should be protected
from dripping condensate by insulating the pipe or permanently shielding the busway with sheet
metal or plastic.
6.8.2.5 Sprinklers—Protect indoor busway from direct spray of sprinklers.
6.8.2.6 Snow—Outdoor busway should be mounted sufficiently above the ground or roof so that snow
build-up does not surround the busway and result in water being forced into the busway through
weep holes.
6.8.2.7 Rain—Outdoor busway should be mounted sufficiently above the ground or roof so that a driving
rain will not result in water being forced into the busway through the weep holes.
6.8.2.8 Transverse Barriers
Where a busway extends through a floor or inside wall and where temperature differences could result in
condensation, an internal transverse barrier, which is designed to restrict the free flow of air, should be
provided.
© Copyright 2010 by the National Electrical Manufacturers Association.
BU 1.1-2010
Page 9
Where a busway extends through a roof or outside wall, a suitable weather barrier should be installed in
accordance with the manufacturer's instructions.
6.9 SUMMARY
6.9.1 Review erection drawings very carefully.
6.9.2 Check the bill of material.
6.9.3 Check the description and identification of each piece before installing it.
6.9.4 Follow instructions on each piece for torque requirements.
6.9.5 Follow the manufacturer's joint assembly instruction drawing for both indoor and outdoor
procedures.
6.9.6 Conduct an insulation resistance test on each section of busway before it is installed.
6.9.7 Conduct an insulation resistance test on the portion of each run already installed on a daily basis.
6.9.8 Check for possible sources of water that may fall on indoor busway, and take corrective action to
prevent this.
© Copyright 2010 by the National Electrical Manufacturers Association.
BU 1.1-2010
Page 10
Section 7
STEPS TO BE TAKEN BEFORE ENERGIZING
WARNING: HAZARDOUS VOLTAGES IN ELECTRICAL EQUIPMENT CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. UNLESS OTHERWISE SPECIFIED, INSTALLATION, INSPECTION,
AND MAINTENANCE SHOULD ONLY BE PERFORMED ON BUSWAY AND EQUIPMENT TO WHICH
POWER HAS BEEN TURNED OFF, DISCONNECTED, AND ELECTRICALLY ISOLATED SO THAT NO
ACCIDENTAL CONTACT CAN BE MADE WITH ENERGIZED PARTS. FOLLOW ALL
MANUFACTURER’S WARNINGS AND INSTRUCTIONS.
7.1 Recheck all joint connections for tightness. Follow the manufacturer's torquing recommendations.
7.2 Ensure that all tap-off or plug-in devices are in the “OFF” position. Tap-off or plug-in devices
without integral disconnects should be removed from busway if they cannot be isolated by an
auxiliary disconnect
7.3 Isolate the busway run by disconnecting all connections to transformers, switchboards, meters,
and so forth.
7.4 Conduct an insulation resistance test with an insulation resistance tester rated 1000 volts to
ensure that the system is free from short circuits and grounds (phase-to-ground, phase-to-
neutral, and phase-to-phase). Record and maintain records of the testing results. Turn the test
results over to the general contractor or owner at completion of the project. It should be noted
that readings vary inversely with the length of run and width or number of bars per phase.
Readings will vary with humidity. If readings of less than 1 megohm for a 100-foot run
(MEGOHMS = 100 / length of busway in feet) are obtained, contact the manufacturer.
7.5.1 Verify that the system phasing matches the busway phasing before reconnecting all connections
to transformers, switchboards, meters, and so forth.
7.5.2 Ensure that ventilation openings and drain holes are clear. On outdoor busway, verify that weep-
hole screws or plugs have been removed in accordance with manufacturer recommendations.
© Copyright 2010 by the National Electrical Manufacturers Association.
BU 1.1-2010
Page 11
Section 8
ENERGIZING EQUIPMENT
WARNING: HAZARDOUS VOLTAGES IN ELECTRICAL EQUIPMENT CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. UNLESS OTHERWISE SPECIFIED, INSTALLATION, INSPECTION,
AND MAINTENANCE SHOULD ONLY BE PERFORMED ON BUSWAY AND EQUIPMENT TO WHICH
POWER HAS BEEN TURNED OFF, DISCONNECTED, AND ELECTRICALLY ISOLATED SO THAT NO
ACCIDENTAL CONTACT CAN BE MADE WITH ENERGIZED PARTS. FOLLOW ALL
MANUFACTURER’S WARNINGS AND INSTRUCTIONS.
8.1 It is not recommended that any busway be energized unless the insulation resistance test
described in Section 7.4 has been successfully completed.
8.2 When the equipment is energized for the first time, qualified electrical personnel should be
present. If short circuits and ground faults caused by damage or poor installation practices have
not been detected in the check-out procedure, serious damage can result when the power is
turned on.
8.3 There should be no electrical load on the busway when it is energized. Since busway typically
extends through several rooms and floor levels, care should be taken to see that all devices fed
from the busway are in the "OFF" position.
8.4 The equipment should be energized in sequence by starting at the source end of the system and
working toward the load end. In other words, energize the main devices, then the feeder devices,
and then the branch-circuit devices. Turn the devices to the "ON" position with a firm positive
motion.
8.5 After all overcurrent devices have been turned on, loads such as lighting circuits, contactors,
heaters, and motors may be turned "ON."
8.6 Busway, when operating properly, will have a moderate hum. Excessive noise may be an
indication of hardware that has not been tightened or of metal parts that have been improperly
assembled.
8.7 Occurrence of sparking at any point along the busway is not a normal condition. The busway
must be de-energized immediately, and remain de-energized until the sparking condition has
been corrected.
© Copyright 2010 by the National Electrical Manufacturers Association.
BU 1.1-2010
Page 12
Section 9
CARE AND MAINTENANCE
9.1 OUTDOOR BUSWAY
9.1.1 Inspect busway once each year or after any severe electrical short circuit or ground fault.
9.1.2 Perform an infrared temperature scan on all electrical connections and busway enclosures while
busway is energized and operating under maximum load conditions. A permanent record should
be kept. If readings change with time, deterioration may be taking place and must be corrected.
WARNING: HAZARDOUS VOLTAGES IN ELECTRICAL EQUIPMENT CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. UNLESS OTHERWISE SPECIFIED, INSTALLATION, INSPECTION,
AND MAINTENANCE SHOULD ONLY BE PERFORMED ON BUSWAY AND EQUIPMENT TO WHICH
POWER HAS BEEN TURNED OFF, DISCONNECTED, AND ELECTRICALLY ISOLATED SO THAT NO
ACCIDENTAL CONTACT CAN BE MADE WITH ENERGIZED PARTS. FOLLOW ALL
MANUFACTURER’S WARNINGS AND INSTRUCTIONS.
WARNING: OPERATION OF BUSWAY THAT HAS BEEN WATER OR MOISTURE DAMAGED CAN
CAUSE PROPERTY DAMAGE, SEVERE PERSONAL INJURY, OR DEATH. OBSERVE THE
PRECAUTIONS IN SECTIONS 6.8 AND 6.9 TO ENSURE ADEQUATE INSULATION RESISTANCE
AND THAT SOURCES OF MOISTURE ARE ELIMINATED.
SAFETY RELATED WORK PRACTICES, AS DESCRIBED IN NFPA 70E, SHOULD BE FOLLOWED AT
ALL TIMES.
CAUTION: Hydrocarbon spray propellants and hydrocarbon based sprays or compounds will cause
degradation of certain plastics and elastomers. Contact the busway manufacturer before using these
products to clean, dry, or lubricate compounds during installation or maintenance.
9.1.3 Turn off power to the busway.
9.1.4 If there is appreciable accumulation of dust and dirt, clean it off by using a brush, vacuum
cleaner, or clean lint-free rags. In order to avoid blowing dust into busway joints, circuit breakers,
or other equipment, do not use a blower or compressed air. Ensure that all drain holes are
operating properly.
9.1.5 Check the insulation resistance prior to re-energizing the busway. A permanent record should be
kept of resistance readings. If readings decrease appreciably with time, deterioration is taking
place and must be corrected. (Contact the manufacturer.) Also, refer to Section 7.4.
9.2 INDOOR BUSWAY
9.2.1 Inspect busway once each year or after any severe electrical short circuit or ground fault or if the
busway has been subjected to a liquid spill.
9.2.2 Perform an infrared temperature scan on all electrical connections and busway enclosure while
busway is energized and operating under maximum load conditions. A permanent record should
be kept. If readings change with time, deterioration may be taking place and must be corrected.
© Copyright 2010 by the National Electrical Manufacturers Association.
BU 1.1-2010
Page 13
WARNING: HAZARDOUS VOLTAGES IN ELECTRICAL EQUIPMENT CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. UNLESS OTHERWISE SPECIFIED, INSTALLATION, INSPECTION,
AND MAINTENANCE SHOULD ONLY BE PERFORMED ON BUSWAY AND EQUIPMENT TO WHICH
POWER HAS BEEN TURNED OFF, DISCONNECTED, AND ELECTRICALLY ISOLATED SO THAT NO
ACCIDENTAL CONTACT CAN BE MADE WITH ENERGIZED PARTS. FOLLOW ALL
MANUFACTURER’S WARNINGS AND INSTRUCTIONS.
CAUTION: Hydrocarbon spray propellants and hydrocarbon based sprays or compounds will cause
degradation of certain plastics and elastomers. Contact the busway manufacturer before using these
products to clean, dry, or lubricate compounds during installation or maintenance.
9.2.3 Turn off power to busway.
9.2.4 Look for any moisture or signs of previous wetness or dripping onto the busway or onto
connection boxes from leaky roofs, pipes, sprinklers, or other sources of moisture. Look for any
recent changes in sprinklers or other plumbing that might now be a source of trouble to busway.
9.2.4.1 Seal off any cracks or openings that have allowed moisture to enter the busway or its connection
boxes. Eliminate source of any dripping onto the busway and any other source of moisture. See
Section 6.8 for more specific details on preventing liquid from getting onto the busway.
9.2.4.2 Replace or thoroughly dry and clean any insulating material that is damp or wet or shows
accumulation of deposited material from previous wettings. Consult the manufacturer for proper
procedures.
9.2.5 If there is appreciable accumulation of dust, clean it off by using a brush, vacuum cleaner, or
clean lint-free rags. In order to avoid blowing dust into busway joints, circuit breakers, or other
equipment, do not use a blower or compressed air.
9.2.6 Carefully inspect all visible electrical joints and terminals.
9.2.7 Visually check connections to be certain that they are clean and secure. Loose and/or
contaminated connections increase electrical resistance which can cause overheating. Such
overheating is indicated by discoloration or flaking of insulation and/or metal parts. Pitting or
melting of connecting surfaces is a sign of arcing due to a loose or otherwise poor connection.
Parts that show evidence of overheating or looseness should be cleaned or replaced if damaged;
contact manufacturer before re-torquing joint bolts.
CAUTION: Do not remove plating from aluminum parts in joints or terminations. Removal of plating can
result in overheating. Replace damaged aluminum parts.
9.2.8 Check the insulation resistance prior to re-energizing the busway. A permanent record should be
kept of resistance readings. If readings decrease appreciably with time, deterioration is taking
place and must be corrected. (Contact the manufacturer.) Also, refer to Section 7.4.
9.3 BUSWAY PLUGS AND CUBICLES WITH PROTECTIVE DEVICES
WARNING: HAZARDOUS VOLTAGES IN ELECTRICAL EQUIPMENT CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. UNLESS OTHERWISE SPECIFIED, INSTALLATION, INSPECTION,
AND MAINTENANCE SHOULD ONLY BE PERFORMED ON BUSWAY AND EQUIPMENT TO WHICH
POWER HAS BEEN TURNED OFF, DISCONNECTED, AND ELECTRICALLY ISOLATED SO THAT NO
ACCIDENTAL CONTACT CAN BE MADE WITH ENERGIZED PARTS. FOLLOW ALL
MANUFACTURER’S WARNINGS AND INSTRUCTIONS.
© Copyright 2010 by the National Electrical Manufacturers Association.
BU 1.1-2010
Page 14
CAUTION: Hydrocarbon spray propellants and hydrocarbon based sprays or compounds will cause
degradation of certain plastics and elastomers. Contact the busway manufacturer before using these
products to clean, dry, or lubricate compounds during installation or maintenance.
9.3.1 Additional guidance on the care and maintenance of protective devices can be found in NEMA
AB 4 for molded case circuit breakers and NEMA KS 3 for switches.
9.3.2 Turn off power to busway.
9.3.3 Examine fuse clip contact pressure and contact means. If there is any sign of overheating or
looseness, follow the manufacturer's maintenance instructions or replace the fuse clips. Loose
fuse clips can result in overheating.
9.3.4 Look for any signs of deterioration in insulating material or melting of the sealing compound.
Replace such insulating parts and assemblies where the sealing compound has melted.
9.3.5 BE SURE THAT ALL CONDITIONS WHICH CAUSED THE OVERHEATING HAVE BEEN
CORRECTED.
9.3.6 Check the operation of all mechanical components.
9.3.6.1 Exercise switch operating mechanisms and external operators for circuit breakers to determine
that they operate freely to their full on and off positions.
9.3.6.2 Check the mechanisms of all electrical and mechanical interlocks and padlocking means.
9.3.6.3 Check for missing or broken parts, proper spring tension, free movement, rusting or corrosion,
dirt, and excessive wear.
9.3.6.4 Examine all readily accessible arc chutes and insulating parts for cracks or breakage and for arc
spatter, sooty deposits, oil, or tracking.
9.3.6.5 Clean off arc spatter, oil, and sooty deposits. Replace the device if appreciable material has
burned away or if parts are charred or cracked.
9.3.7 Lubricate the operating parts of switch mechanisms, and other moving parts, according to the
manufacturer's instructions. Use only manufacturer approved cleaners and lubricates.
CAUTION: Hydrocarbon spray propellants and hydrocarbon based sprays or compounds will cause
degradation of certain plastics and elastomers. Contact the busway manufacturer before using these
products to clean, dry, or lubricate compounds during installation or maintenance.
9.3.7.1 Use clean, nonmetallic, light grease or oil as instructed.
9.3.7.2 Do not oil or grease parts of molded case circuit breakers.
9.3.7.3 If no instructions are given on the devices, sliding copper contacts, operating mechanisms, and
interlocks may be lubricated with clean, light grease.
9.3.7.4 Wipe off excess lubrication to avoid accumulation of foreign material.
9.3.8 Operate each switch or circuit breaker several times to ensure that all mechanisms are free and
in proper working order. Ensure all interlocking mechanisms function properly.
© Copyright 2010 by the National Electrical Manufacturers Association.
BU 1.1-2010
Page 15
9.3.9 Re-tighten all wire connections according to the manufacturer’s instructions.
9.3.10 Check circuit breakers and fuses to ensure they have the proper ampere, voltage, and
interrupting ratings. Ensure that non–current-limiting devices are not used as replacements for
current-limiting devices. Never attempt to defeat rejection mechanisms, which are provided to
prevent the installation of the incorrect class of fuse.
9.3.11 Check the insulation resistance of devices prior to their reinstallation on the busway.
9.4 FINAL TEST
9.4.1 After performing all of the above inspections and necessary repairs, it may be desirable to
perform another infrared temperature scan on all electrical connections after busway is re-
energized and reaches a stabilized operating temperature. A permanent record should be kept. If
readings change with time, deterioration may be taking place and must be corrected.
© Copyright 2010 by the National Electrical Manufacturers Association.
BU 1.1-2010
Page 16
Section 10
PERMISSIBLE LOADING OF BUSWAYS
10.1 BUSWAYS—WITH OR WITHOUT OVERCURRENT PROTECTION
10.1.1 The total continuous load current should not exceed the current rating on the busway nameplate.
For outdoor busway, the radiant heat from the sun in the installation location must be considered
when busway system is sized for ampacity. Consult the manufacturer for appropriate derating.
10.2 BUSWAY PLUGS
10.2.1 The total continuous load current on a busway fusible plug should not exceed 80 percent of the
ampere rating of the fuses. The total continuous load current on other types of plugs should not
exceed 80 percent of the ampere rating of the plug unless the device is rated to carry 100
percent of its ampere rating. Cycling loads with high inrush currents may require additional
consideration when sizing plug-in units. Consult the manufacturer’s literature for proper sizing
under these conditions.
© Copyright 2010 by the National Electrical Manufacturers Association.
BU 1.1-2010
Page 17
Section 11
OPERATING CONDITIONS
11.1 NORMAL OPERATING CONDITIONS
11.1.1 Busways shall be suitable for operation:
a. When and where the ambient temperature is within the limits -30°C through +40°C for
busway and busway plug-in-units incorporating enclosed switches.
b. When and where the ambient temperature is within the limits 0°C through +40°C for busway
plug-in-units incorporating molded case circuit breakers or electromagnetic and manual
motor controls.
c. Where the altitude does not exceed 6600 feet (2000 meters).
11.1.2 Voltage Drop (General)
Good practice indicates that the voltage drop in feeder circuits up to the final distribution point
where the load is divided into individual branch circuits should not exceed 3 percent for power,
heating, or lighting loads or combination thereof. Total voltage drop for feeders and individual
branch circuits up to the final utilization point should not exceed 5 percent overall.
11.2 UNUSUAL OPERATING CONDITIONS
11.2.1 When busways are installed in locations that have a continuous ambient temperature above 40°C
(104°F), the busways should be de-rated in accordance with the manufacturer’s
recommendations, if furnished, or the following table:
AMBIENT
TEMPERATURE
MULTIPLIER
40°C (104°F) 1.00
45°C (113°F) 0.95
50°C (122°F) 0.90
55°C (131°F) 0.85
60°C (140°F) 0.80
65°C (149°F) 0.74
70°C (158°F) 0.67
11.2.2 For applications where the ambient temperature is lower than the minimum limits per 11.1.1a and
11.1.1b or at altitudes greater than 6600 feet (2000 meters), consult the manufacturer.
11.2.3 Unless specifically designed for such use, do not locate busway so that it is exposed to dust,
vapors, abnormal vibration, shock, or other such unusual operating conditions. A busway should
not be installed in wet locations or outdoors unless specifically identified as an outdoor busway.
§
© Copyright 2010 by the National Electrical Manufacturers Association.

More Related Content

What's hot

132kV GSS ppt
132kV GSS ppt132kV GSS ppt
132kV GSS ppt
Abhishek Dosaya
 
Fundamentals of power system
Fundamentals of power systemFundamentals of power system
Fundamentals of power system
Balaram Das
 
66 kv substation
66 kv substation66 kv substation
66 kv substation
lovish virmani
 
Pptonconsumersrights 160126053652
Pptonconsumersrights 160126053652Pptonconsumersrights 160126053652
Pptonconsumersrights 160126053652
NIRAVJINJALA
 
Nema standards publication mg 2 2001
Nema standards publication mg 2 2001Nema standards publication mg 2 2001
Nema standards publication mg 2 2001
Danilo Poma Muñoz
 
Snapfit design
Snapfit designSnapfit design
Snapfit design
Ramirez Bernuy
 
Fluke 435-ii user training
Fluke 435-ii user trainingFluke 435-ii user training
Fluke 435-ii user trainingHaris Ahmad
 
Dampers used in electrical transmission lines
Dampers used in electrical transmission linesDampers used in electrical transmission lines
Dampers used in electrical transmission lines
adeelshafiq
 
Power Flow in a Transmission line
Power Flow in a Transmission linePower Flow in a Transmission line
Power Flow in a Transmission lineAyyarao T S L V
 
Catu Electrical - Low & High Voltage Electrical Safety Equipment For Undergro...
Catu Electrical - Low & High Voltage Electrical Safety Equipment For Undergro...Catu Electrical - Low & High Voltage Electrical Safety Equipment For Undergro...
Catu Electrical - Low & High Voltage Electrical Safety Equipment For Undergro...
Thorne & Derrick International
 
Power system in pakistan
Power system in pakistan Power system in pakistan
Power system in pakistan
rana622987
 
Busbar configuarations
Busbar configuarationsBusbar configuarations
Busbar configuarations
Boopathi Thambusamy
 
classification of substation & busbar arrangement
classification of substation & busbar arrangementclassification of substation & busbar arrangement
classification of substation & busbar arrangement
Rahul Ghayal
 
Benefits of power flow control
Benefits of power flow controlBenefits of power flow control
Benefits of power flow control
jgould03
 
Distribution Transformers
Distribution TransformersDistribution Transformers
Distribution TransformersRao Saim Zafar
 
Integrated earthing systems
Integrated earthing systemsIntegrated earthing systems
Integrated earthing systems
Leonardo ENERGY
 
Resistance potential divider
Resistance potential dividerResistance potential divider
Resistance potential divider
120101eer001
 
Okonite - Cable Engineering Handbook (Copper & Aluminium Cables)
Okonite - Cable Engineering Handbook (Copper & Aluminium Cables)Okonite - Cable Engineering Handbook (Copper & Aluminium Cables)
Okonite - Cable Engineering Handbook (Copper & Aluminium Cables)
Thorne & Derrick International
 
Wind Farm Earthing, Lightning & Overvoltage Protection - Wind Turbines Earthi...
Wind Farm Earthing, Lightning & Overvoltage Protection - Wind Turbines Earthi...Wind Farm Earthing, Lightning & Overvoltage Protection - Wind Turbines Earthi...
Wind Farm Earthing, Lightning & Overvoltage Protection - Wind Turbines Earthi...
Thorne & Derrick International
 

What's hot (20)

132kV GSS ppt
132kV GSS ppt132kV GSS ppt
132kV GSS ppt
 
Fundamentals of power system
Fundamentals of power systemFundamentals of power system
Fundamentals of power system
 
66 kv substation
66 kv substation66 kv substation
66 kv substation
 
Pptonconsumersrights 160126053652
Pptonconsumersrights 160126053652Pptonconsumersrights 160126053652
Pptonconsumersrights 160126053652
 
Nema standards publication mg 2 2001
Nema standards publication mg 2 2001Nema standards publication mg 2 2001
Nema standards publication mg 2 2001
 
Snapfit design
Snapfit designSnapfit design
Snapfit design
 
Fluke 435-ii user training
Fluke 435-ii user trainingFluke 435-ii user training
Fluke 435-ii user training
 
Dampers used in electrical transmission lines
Dampers used in electrical transmission linesDampers used in electrical transmission lines
Dampers used in electrical transmission lines
 
Power Flow in a Transmission line
Power Flow in a Transmission linePower Flow in a Transmission line
Power Flow in a Transmission line
 
Catu Electrical - Low & High Voltage Electrical Safety Equipment For Undergro...
Catu Electrical - Low & High Voltage Electrical Safety Equipment For Undergro...Catu Electrical - Low & High Voltage Electrical Safety Equipment For Undergro...
Catu Electrical - Low & High Voltage Electrical Safety Equipment For Undergro...
 
Power system in pakistan
Power system in pakistan Power system in pakistan
Power system in pakistan
 
Busbar configuarations
Busbar configuarationsBusbar configuarations
Busbar configuarations
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
classification of substation & busbar arrangement
classification of substation & busbar arrangementclassification of substation & busbar arrangement
classification of substation & busbar arrangement
 
Benefits of power flow control
Benefits of power flow controlBenefits of power flow control
Benefits of power flow control
 
Distribution Transformers
Distribution TransformersDistribution Transformers
Distribution Transformers
 
Integrated earthing systems
Integrated earthing systemsIntegrated earthing systems
Integrated earthing systems
 
Resistance potential divider
Resistance potential dividerResistance potential divider
Resistance potential divider
 
Okonite - Cable Engineering Handbook (Copper & Aluminium Cables)
Okonite - Cable Engineering Handbook (Copper & Aluminium Cables)Okonite - Cable Engineering Handbook (Copper & Aluminium Cables)
Okonite - Cable Engineering Handbook (Copper & Aluminium Cables)
 
Wind Farm Earthing, Lightning & Overvoltage Protection - Wind Turbines Earthi...
Wind Farm Earthing, Lightning & Overvoltage Protection - Wind Turbines Earthi...Wind Farm Earthing, Lightning & Overvoltage Protection - Wind Turbines Earthi...
Wind Farm Earthing, Lightning & Overvoltage Protection - Wind Turbines Earthi...
 

Similar to Bu 1-1-2010

Nema symbols
Nema symbolsNema symbols
Ansi z535.3 2011 criteria for safety symbols
Ansi z535.3 2011 criteria for safety symbolsAnsi z535.3 2011 criteria for safety symbols
Ansi z535.3 2011 criteria for safety symbols
Arturo Puentes
 
NEETRAC (Chapter 11: Metallic Shield Assessment)
NEETRAC (Chapter 11: Metallic Shield Assessment)NEETRAC (Chapter 11: Metallic Shield Assessment)
NEETRAC (Chapter 11: Metallic Shield Assessment)
AHMED MOHAMED HEGAB
 
NEMA VE-2 cable tray (2006).pdf
NEMA VE-2 cable tray (2006).pdfNEMA VE-2 cable tray (2006).pdf
NEMA VE-2 cable tray (2006).pdf
Ansar14
 
NEETRAC (Chapter 9: Simple Dielectric Withstand)
NEETRAC (Chapter 9: Simple Dielectric Withstand)NEETRAC (Chapter 9: Simple Dielectric Withstand)
NEETRAC (Chapter 9: Simple Dielectric Withstand)
AHMED MOHAMED HEGAB
 
NEETRAC (Chapter 8: Partial Discharge for HV and EHV Cable Systems)
NEETRAC (Chapter 8: Partial Discharge for HV and EHV Cable Systems)NEETRAC (Chapter 8: Partial Discharge for HV and EHV Cable Systems)
NEETRAC (Chapter 8: Partial Discharge for HV and EHV Cable Systems)
AHMED MOHAMED HEGAB
 
Nfpa 70 b, 1998 edition
Nfpa 70 b, 1998 editionNfpa 70 b, 1998 edition
Nfpa 70 b, 1998 edition
Argenis Veramendi
 
Insulated siding as_home_insulation_guide
Insulated siding as_home_insulation_guideInsulated siding as_home_insulation_guide
Insulated siding as_home_insulation_guide
donnie harold harris
 
NEETRAC (Chapter 7: Medium Voltage Cable System Partial Discharge) )
NEETRAC (Chapter 7: Medium Voltage Cable System Partial Discharge) )NEETRAC (Chapter 7: Medium Voltage Cable System Partial Discharge) )
NEETRAC (Chapter 7: Medium Voltage Cable System Partial Discharge) )
AHMED MOHAMED HEGAB
 
Tia eia-568-b.3
Tia eia-568-b.3Tia eia-568-b.3
Tia eia-568-b.3Isidro Ska
 
NEETRAC (Chapter 2: MV Cable System Issues)
NEETRAC (Chapter 2: MV Cable System Issues)NEETRAC (Chapter 2: MV Cable System Issues)
NEETRAC (Chapter 2: MV Cable System Issues)
AHMED MOHAMED HEGAB
 
Cambium network ptp 810 series 01 00 user guide
Cambium network ptp 810 series 01 00 user guideCambium network ptp 810 series 01 00 user guide
Cambium network ptp 810 series 01 00 user guideAdvantec Distribution
 
WR-TR-PNM-WCCF-V01-171010.pdf
WR-TR-PNM-WCCF-V01-171010.pdfWR-TR-PNM-WCCF-V01-171010.pdf
WR-TR-PNM-WCCF-V01-171010.pdf
LenCarrusel
 
NEETRAC (Chapter 3: HV and EHV Cable System Aging and Testing Issues)
NEETRAC (Chapter 3: HV and EHV Cable System Aging and Testing Issues)NEETRAC (Chapter 3: HV and EHV Cable System Aging and Testing Issues)
NEETRAC (Chapter 3: HV and EHV Cable System Aging and Testing Issues)
AHMED MOHAMED HEGAB
 
Natural Gas for Transportation Vehicle Repair Garage Guidelines
Natural Gas for Transportation Vehicle Repair Garage GuidelinesNatural Gas for Transportation Vehicle Repair Garage Guidelines
Natural Gas for Transportation Vehicle Repair Garage Guidelines
Wisconsin Clean Cities
 
Beetle fusion modular operating manual (english)
Beetle fusion modular operating manual (english)Beetle fusion modular operating manual (english)
Beetle fusion modular operating manual (english)
Nguyễn Việt Hồng (wincor.com.vn)
 
Nec handbook versión 2005 compacta
Nec handbook versión 2005 compactaNec handbook versión 2005 compacta
Nec handbook versión 2005 compacta
venenox1984
 
Written Programs.pdf
Written Programs.pdfWritten Programs.pdf
Written Programs.pdf
John Gibso
 
M_SERIES_621x.pdfeiefwqifuiewqfbhiqufhua
M_SERIES_621x.pdfeiefwqifuiewqfbhiqufhuaM_SERIES_621x.pdfeiefwqifuiewqfbhiqufhua
M_SERIES_621x.pdfeiefwqifuiewqfbhiqufhua
tungduong17062003
 
1388-2000.pdf
1388-2000.pdf1388-2000.pdf
1388-2000.pdf
MuhammadHanif91995
 

Similar to Bu 1-1-2010 (20)

Nema symbols
Nema symbolsNema symbols
Nema symbols
 
Ansi z535.3 2011 criteria for safety symbols
Ansi z535.3 2011 criteria for safety symbolsAnsi z535.3 2011 criteria for safety symbols
Ansi z535.3 2011 criteria for safety symbols
 
NEETRAC (Chapter 11: Metallic Shield Assessment)
NEETRAC (Chapter 11: Metallic Shield Assessment)NEETRAC (Chapter 11: Metallic Shield Assessment)
NEETRAC (Chapter 11: Metallic Shield Assessment)
 
NEMA VE-2 cable tray (2006).pdf
NEMA VE-2 cable tray (2006).pdfNEMA VE-2 cable tray (2006).pdf
NEMA VE-2 cable tray (2006).pdf
 
NEETRAC (Chapter 9: Simple Dielectric Withstand)
NEETRAC (Chapter 9: Simple Dielectric Withstand)NEETRAC (Chapter 9: Simple Dielectric Withstand)
NEETRAC (Chapter 9: Simple Dielectric Withstand)
 
NEETRAC (Chapter 8: Partial Discharge for HV and EHV Cable Systems)
NEETRAC (Chapter 8: Partial Discharge for HV and EHV Cable Systems)NEETRAC (Chapter 8: Partial Discharge for HV and EHV Cable Systems)
NEETRAC (Chapter 8: Partial Discharge for HV and EHV Cable Systems)
 
Nfpa 70 b, 1998 edition
Nfpa 70 b, 1998 editionNfpa 70 b, 1998 edition
Nfpa 70 b, 1998 edition
 
Insulated siding as_home_insulation_guide
Insulated siding as_home_insulation_guideInsulated siding as_home_insulation_guide
Insulated siding as_home_insulation_guide
 
NEETRAC (Chapter 7: Medium Voltage Cable System Partial Discharge) )
NEETRAC (Chapter 7: Medium Voltage Cable System Partial Discharge) )NEETRAC (Chapter 7: Medium Voltage Cable System Partial Discharge) )
NEETRAC (Chapter 7: Medium Voltage Cable System Partial Discharge) )
 
Tia eia-568-b.3
Tia eia-568-b.3Tia eia-568-b.3
Tia eia-568-b.3
 
NEETRAC (Chapter 2: MV Cable System Issues)
NEETRAC (Chapter 2: MV Cable System Issues)NEETRAC (Chapter 2: MV Cable System Issues)
NEETRAC (Chapter 2: MV Cable System Issues)
 
Cambium network ptp 810 series 01 00 user guide
Cambium network ptp 810 series 01 00 user guideCambium network ptp 810 series 01 00 user guide
Cambium network ptp 810 series 01 00 user guide
 
WR-TR-PNM-WCCF-V01-171010.pdf
WR-TR-PNM-WCCF-V01-171010.pdfWR-TR-PNM-WCCF-V01-171010.pdf
WR-TR-PNM-WCCF-V01-171010.pdf
 
NEETRAC (Chapter 3: HV and EHV Cable System Aging and Testing Issues)
NEETRAC (Chapter 3: HV and EHV Cable System Aging and Testing Issues)NEETRAC (Chapter 3: HV and EHV Cable System Aging and Testing Issues)
NEETRAC (Chapter 3: HV and EHV Cable System Aging and Testing Issues)
 
Natural Gas for Transportation Vehicle Repair Garage Guidelines
Natural Gas for Transportation Vehicle Repair Garage GuidelinesNatural Gas for Transportation Vehicle Repair Garage Guidelines
Natural Gas for Transportation Vehicle Repair Garage Guidelines
 
Beetle fusion modular operating manual (english)
Beetle fusion modular operating manual (english)Beetle fusion modular operating manual (english)
Beetle fusion modular operating manual (english)
 
Nec handbook versión 2005 compacta
Nec handbook versión 2005 compactaNec handbook versión 2005 compacta
Nec handbook versión 2005 compacta
 
Written Programs.pdf
Written Programs.pdfWritten Programs.pdf
Written Programs.pdf
 
M_SERIES_621x.pdfeiefwqifuiewqfbhiqufhua
M_SERIES_621x.pdfeiefwqifuiewqfbhiqufhuaM_SERIES_621x.pdfeiefwqifuiewqfbhiqufhua
M_SERIES_621x.pdfeiefwqifuiewqfbhiqufhua
 
1388-2000.pdf
1388-2000.pdf1388-2000.pdf
1388-2000.pdf
 

Recently uploaded

Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)
Lviv Startup Club
 
Buy Verified PayPal Account | Buy Google 5 Star Reviews
Buy Verified PayPal Account | Buy Google 5 Star ReviewsBuy Verified PayPal Account | Buy Google 5 Star Reviews
Buy Verified PayPal Account | Buy Google 5 Star Reviews
usawebmarket
 
India Orthopedic Devices Market: Unlocking Growth Secrets, Trends and Develop...
India Orthopedic Devices Market: Unlocking Growth Secrets, Trends and Develop...India Orthopedic Devices Market: Unlocking Growth Secrets, Trends and Develop...
India Orthopedic Devices Market: Unlocking Growth Secrets, Trends and Develop...
Kumar Satyam
 
anas about venice for grade 6f about venice
anas about venice for grade 6f about veniceanas about venice for grade 6f about venice
anas about venice for grade 6f about venice
anasabutalha2013
 
What are the main advantages of using HR recruiter services.pdf
What are the main advantages of using HR recruiter services.pdfWhat are the main advantages of using HR recruiter services.pdf
What are the main advantages of using HR recruiter services.pdf
HumanResourceDimensi1
 
Filing Your Delaware Franchise Tax A Detailed Guide
Filing Your Delaware Franchise Tax A Detailed GuideFiling Your Delaware Franchise Tax A Detailed Guide
Filing Your Delaware Franchise Tax A Detailed Guide
YourLegal Accounting
 
The Parable of the Pipeline a book every new businessman or business student ...
The Parable of the Pipeline a book every new businessman or business student ...The Parable of the Pipeline a book every new businessman or business student ...
The Parable of the Pipeline a book every new businessman or business student ...
awaisafdar
 
Lookback Analysis
Lookback AnalysisLookback Analysis
Lookback Analysis
Safe PaaS
 
Brand Analysis for an artist named Struan
Brand Analysis for an artist named StruanBrand Analysis for an artist named Struan
Brand Analysis for an artist named Struan
sarahvanessa51503
 
Memorandum Of Association Constitution of Company.ppt
Memorandum Of Association Constitution of Company.pptMemorandum Of Association Constitution of Company.ppt
Memorandum Of Association Constitution of Company.ppt
seri bangash
 
chapter 10 - excise tax of transfer and business taxation
chapter 10 - excise tax of transfer and business taxationchapter 10 - excise tax of transfer and business taxation
chapter 10 - excise tax of transfer and business taxation
AUDIJEAngelo
 
Accpac to QuickBooks Conversion Navigating the Transition with Online Account...
Accpac to QuickBooks Conversion Navigating the Transition with Online Account...Accpac to QuickBooks Conversion Navigating the Transition with Online Account...
Accpac to QuickBooks Conversion Navigating the Transition with Online Account...
PaulBryant58
 
3.0 Project 2_ Developing My Brand Identity Kit.pptx
3.0 Project 2_ Developing My Brand Identity Kit.pptx3.0 Project 2_ Developing My Brand Identity Kit.pptx
3.0 Project 2_ Developing My Brand Identity Kit.pptx
tanyjahb
 
20240425_ TJ Communications Credentials_compressed.pdf
20240425_ TJ Communications Credentials_compressed.pdf20240425_ TJ Communications Credentials_compressed.pdf
20240425_ TJ Communications Credentials_compressed.pdf
tjcomstrang
 
April 2024 Nostalgia Products Newsletter
April 2024 Nostalgia Products NewsletterApril 2024 Nostalgia Products Newsletter
April 2024 Nostalgia Products Newsletter
NathanBaughman3
 
Enterprise Excellence is Inclusive Excellence.pdf
Enterprise Excellence is Inclusive Excellence.pdfEnterprise Excellence is Inclusive Excellence.pdf
Enterprise Excellence is Inclusive Excellence.pdf
KaiNexus
 
Cree_Rey_BrandIdentityKit.PDF_PersonalBd
Cree_Rey_BrandIdentityKit.PDF_PersonalBdCree_Rey_BrandIdentityKit.PDF_PersonalBd
Cree_Rey_BrandIdentityKit.PDF_PersonalBd
creerey
 
Global Interconnection Group Joint Venture[960] (1).pdf
Global Interconnection Group Joint Venture[960] (1).pdfGlobal Interconnection Group Joint Venture[960] (1).pdf
Global Interconnection Group Joint Venture[960] (1).pdf
Henry Tapper
 
Exploring Patterns of Connection with Social Dreaming
Exploring Patterns of Connection with Social DreamingExploring Patterns of Connection with Social Dreaming
Exploring Patterns of Connection with Social Dreaming
Nicola Wreford-Howard
 
Sustainability: Balancing the Environment, Equity & Economy
Sustainability: Balancing the Environment, Equity & EconomySustainability: Balancing the Environment, Equity & Economy
Sustainability: Balancing the Environment, Equity & Economy
Operational Excellence Consulting
 

Recently uploaded (20)

Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)
 
Buy Verified PayPal Account | Buy Google 5 Star Reviews
Buy Verified PayPal Account | Buy Google 5 Star ReviewsBuy Verified PayPal Account | Buy Google 5 Star Reviews
Buy Verified PayPal Account | Buy Google 5 Star Reviews
 
India Orthopedic Devices Market: Unlocking Growth Secrets, Trends and Develop...
India Orthopedic Devices Market: Unlocking Growth Secrets, Trends and Develop...India Orthopedic Devices Market: Unlocking Growth Secrets, Trends and Develop...
India Orthopedic Devices Market: Unlocking Growth Secrets, Trends and Develop...
 
anas about venice for grade 6f about venice
anas about venice for grade 6f about veniceanas about venice for grade 6f about venice
anas about venice for grade 6f about venice
 
What are the main advantages of using HR recruiter services.pdf
What are the main advantages of using HR recruiter services.pdfWhat are the main advantages of using HR recruiter services.pdf
What are the main advantages of using HR recruiter services.pdf
 
Filing Your Delaware Franchise Tax A Detailed Guide
Filing Your Delaware Franchise Tax A Detailed GuideFiling Your Delaware Franchise Tax A Detailed Guide
Filing Your Delaware Franchise Tax A Detailed Guide
 
The Parable of the Pipeline a book every new businessman or business student ...
The Parable of the Pipeline a book every new businessman or business student ...The Parable of the Pipeline a book every new businessman or business student ...
The Parable of the Pipeline a book every new businessman or business student ...
 
Lookback Analysis
Lookback AnalysisLookback Analysis
Lookback Analysis
 
Brand Analysis for an artist named Struan
Brand Analysis for an artist named StruanBrand Analysis for an artist named Struan
Brand Analysis for an artist named Struan
 
Memorandum Of Association Constitution of Company.ppt
Memorandum Of Association Constitution of Company.pptMemorandum Of Association Constitution of Company.ppt
Memorandum Of Association Constitution of Company.ppt
 
chapter 10 - excise tax of transfer and business taxation
chapter 10 - excise tax of transfer and business taxationchapter 10 - excise tax of transfer and business taxation
chapter 10 - excise tax of transfer and business taxation
 
Accpac to QuickBooks Conversion Navigating the Transition with Online Account...
Accpac to QuickBooks Conversion Navigating the Transition with Online Account...Accpac to QuickBooks Conversion Navigating the Transition with Online Account...
Accpac to QuickBooks Conversion Navigating the Transition with Online Account...
 
3.0 Project 2_ Developing My Brand Identity Kit.pptx
3.0 Project 2_ Developing My Brand Identity Kit.pptx3.0 Project 2_ Developing My Brand Identity Kit.pptx
3.0 Project 2_ Developing My Brand Identity Kit.pptx
 
20240425_ TJ Communications Credentials_compressed.pdf
20240425_ TJ Communications Credentials_compressed.pdf20240425_ TJ Communications Credentials_compressed.pdf
20240425_ TJ Communications Credentials_compressed.pdf
 
April 2024 Nostalgia Products Newsletter
April 2024 Nostalgia Products NewsletterApril 2024 Nostalgia Products Newsletter
April 2024 Nostalgia Products Newsletter
 
Enterprise Excellence is Inclusive Excellence.pdf
Enterprise Excellence is Inclusive Excellence.pdfEnterprise Excellence is Inclusive Excellence.pdf
Enterprise Excellence is Inclusive Excellence.pdf
 
Cree_Rey_BrandIdentityKit.PDF_PersonalBd
Cree_Rey_BrandIdentityKit.PDF_PersonalBdCree_Rey_BrandIdentityKit.PDF_PersonalBd
Cree_Rey_BrandIdentityKit.PDF_PersonalBd
 
Global Interconnection Group Joint Venture[960] (1).pdf
Global Interconnection Group Joint Venture[960] (1).pdfGlobal Interconnection Group Joint Venture[960] (1).pdf
Global Interconnection Group Joint Venture[960] (1).pdf
 
Exploring Patterns of Connection with Social Dreaming
Exploring Patterns of Connection with Social DreamingExploring Patterns of Connection with Social Dreaming
Exploring Patterns of Connection with Social Dreaming
 
Sustainability: Balancing the Environment, Equity & Economy
Sustainability: Balancing the Environment, Equity & EconomySustainability: Balancing the Environment, Equity & Economy
Sustainability: Balancing the Environment, Equity & Economy
 

Bu 1-1-2010

  • 1. NEMA BU 1.1 GENERAL INSTRUCTIONS FOR HANDLING, INSTALLATION, OPERATION, AND MAINTENANCE OF BUSWAY RATED 600 VOLTS OR LESS
  • 2.
  • 3. NEMA Standards Publication BU 1.1-2010 General Instructions for Handling, Installation, Operation, and Maintenance of Busway Rated 600 Volts or Less Published by: National Electrical Manufacturers Association 1300 North 17th Street, Suite 1752 Rosslyn, Virginia 22209 www.nema.org © Copyright 2010 by the National Electrical Manufacturers Association. All rights including translation into other languages, reserved under the Universal Copyright Convention, the Berne Convention for the Protection of Literary and Artistic Works, and the International and Pan American Copyright Conventions.
  • 4. NOTICE AND DISCLAIMER The information in this publication was considered technically sound by the consensus of persons engaged in the development and approval of the document at the time it was developed. Consensus does not necessarily mean that there is unanimous agreement among every person participating in the development of this document. The National Electrical Manufacturers Association (NEMA) standards and guideline publications, of which the document contained herein is one, are developed through a voluntary consensus standards development process. This process brings together volunteers and/or seeks out the views of persons who have an interest in the topic covered by this publication. While NEMA administers the process and establishes rules to promote fairness in the development of consensus, it does not write the document and it does not independently test, evaluate, or verify the accuracy or completeness of any information or the soundness of any judgments contained in its standards and guideline publications. NEMA disclaims liability for any personal injury, property, or other damages of any nature whatsoever, whether special, indirect, consequential, or compensatory, directly or indirectly resulting from the publication, use of, application, or reliance on this document. NEMA disclaims and makes no guaranty or warranty, express or implied, as to the accuracy or completeness of any information published herein, and disclaims and makes no warranty that the information in this document will fulfill any of your particular purposes or needs. NEMA does not undertake to guarantee the performance of any individual manufacturer or seller’s products or services by virtue of this standard or guide. In publishing and making this document available, NEMA is not undertaking to render professional or other services for or on behalf of any person or entity, nor is NEMA undertaking to perform any duty owed by any person or entity to someone else. Anyone using this document should rely on his or her own independent judgment or, as appropriate, seek the advice of a competent professional in determining the exercise of reasonable care in any given circumstances. Information and other standards on the topic covered by this publication may be available from other sources, which the user may wish to consult for additional views or information not covered by this publication. NEMA has no power, nor does it undertake to police or enforce compliance with the contents of this document. NEMA does not certify, test, or inspect products, designs, or installations for safety or health purposes. Any certification or other statement of compliance with any health or safety–related information in this document shall not be attributable to NEMA and is solely the responsibility of the certifier or maker of the statement.
  • 5. BU 1.1-2010 Page i CONTENTS Foreword........................................................................................................................................................ ii Section 1 SCOPE.................................................................................................................................................1 Section 2 REFERENCED STANDARDS............................................................................................................2 Section 3 GENERAL............................................................................................................................................3 Section 4 HANDLING...........................................................................................................................................4 Section 5 STORAGE............................................................................................................................................5 Section 6 INSTALLATION ...................................................................................................................................6 6.1 General.................................................................................................................................................6 6.2 Unpacking ............................................................................................................................................6 6.3 Hoisting and Handling (See Also Section 4).......................................................................................6 6.4 Hanging or Supporting.........................................................................................................................6 6.5 Joint Assembly.....................................................................................................................................7 6.6 Grounding.............................................................................................................................................7 6.7 Mounting Plug-In Devices....................................................................................................................8 6.8 Protection from Liquids, Moisture, and Other Contaminants..............................................................8 6.9 Summary..............................................................................................................................................9 Section 7 STEPS TO BE TAKEN BEFORE ENERGIZING..............................................................................10 Section 8 ENERGIZING EQUIPMENT..............................................................................................................11 Section 9 CARE AND MAINTENANCE ............................................................................................................12 9.1 Outdoor Busway ................................................................................................................................12 9.2 Indoor Busway ...................................................................................................................................12 9.3 Busway Plugs and Cubicles with Protective Devices.......................................................................13 9.4 Final Test............................................................................................................................................15 Section 10 PERMISSIBLE LOADING OF BUSWAYS .....................................................................................16 10.1 Busways—With or Without Overcurrent Protection..........................................................................16 10.2 Busway Plugs.....................................................................................................................................16 Section 11 OPERATING CONDITIONS ...........................................................................................................17 © Copyright 2010 by the National Electrical Manufacturers Association.
  • 6. BU 1.1-2010 Page ii FOREWORD This publication is a guide of practical information containing instructions for the proper handling, installation, operation, and maintenance of busway and associated fittings rated 600 volts or less. These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency regarding handling, installation, operation, or maintenance. It is recommended that work described in this set of instructions be performed only by qualified personnel familiar with the construction and operation of busway and associated fittings and that such work be performed only after reading this complete set of instructions. For specific information not covered by these instructions, you are urged to contact the manufacturer of the busway directly. These recommendations of the Busway Section of the National Electrical Manufacturers Association will be found useful by architects, electrical engineers, electrical contractors, electricians, maintenance engineers, and others. These recommendations will be reviewed periodically by the section and updated as necessary. Please address any comments or questions you may have on the text to: Vice President, Technical Services National Electrical Manufacturers Association 1300 N. 17th Street, Suite 1752 Rosslyn, VA 22209 This Standards Publication was developed by the Busway Section. At the time it was approved, the Group/Section was composed of the following members: Eaton Electrical, Inc.—Pittsburgh, PA GE Consumer & Industrial—Plainville, CT Schneider Electric/Square D—Smyrna, TN Siemens Industry, Inc.—Norcross, GA Publication No. BU 1.1-2010 revises and supersedes BU 1.1-2005. © Copyright 2010 by the National Electrical Manufacturers Association.
  • 7. BU 1.1-2010 Page 1 Section 1 SCOPE This Standards Publication covers products for distribution of electric power at 600 volts or less, consisting of enclosed sectionalized prefabricated busbars rated at 100 amperes or more, and associated structures and fittings, classified as follows: a. Feeder busways (indoor or outdoor) b. Plug-in busways (indoor only) c. Accessories required to complete the busway system It does not pertain to metal-enclosed busways as described in the ANSI/IEEE C37.23 standard. © Copyright 2010 by the National Electrical Manufacturers Association.
  • 8. BU 1.1-2010 Page 2 Section 2 REFERENCED STANDARDS National Electrical Manufacturers Association 1300 N. 17th Street, Suite 1752 Rosslyn, VA 22209 NEMA AB 4 Guidelines for Inspection and Preventive Maintenance of Molded Case Circuit Breakers Used in Commercial and Industrial Applications NEMA KS 3 Guidelines for Inspection and Preventive Maintenance of Switches Used in Commercial and Industrial Applications National Fire Protection Association Batterymarch Park Quincy, MA 02269 NFPA 70 National Electrical Code® NFPA 70E Standard for Electrical Safety Requirements for Employee Workplace Institute of Electrical and Electronics Engineers 445 Hoes Lane Piscataway, NJ 08855-1331 IEEE C37.23 IEEE Standard for Metal-Enclosed Bus © Copyright 2010 by the National Electrical Manufacturers Association.
  • 9. BU 1.1-2010 Page 3 Section 3 GENERAL 3.1 Proper planning and coordination between trades, heating contractors, and plumbing contractors are important for a good busway layout. 3.2 The successful operation of busway is dependent upon proper handling, installation, operation, and maintenance, as well as upon proper design and manufacture. Neglecting certain fundamental installation and maintenance requirements may lead to personal injury and damage to electrical equipment or other property. 3.3 Installation, operation, and maintenance of busway should be conducted only by qualified personnel. 3.4 For purposes of these guidelines, a qualified person is one who is familiar with the installation, construction, and operation of the equipment and the hazards involved. In addition, the person should be: a. Knowledgeable of the requirements of the National Electrical Code and of all other applicable codes, laws, and standards. b. Trained and authorized to test, energize, clear, ground, tag, and lockout circuits and equipment in accordance with established safety practices. c. Trained in the proper care and use of personal protective equipment such as rubber gloves, hard hats, safety glasses or face shields, and flash resistant clothing in accordance with established safety practices and potential level of the hazard. d. Trained in rendering first aid. WARNING: HAZARDOUS VOLTAGES IN ELECTRICAL EQUIPMENT CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. UNLESS OTHERWISE SPECIFIED, INSTALLATION, INSPECTION, AND MAINTENANCE SHOULD ONLY BE PERFORMED ON BUSWAY AND EQUIPMENT TO WHICH POWER HAS BEEN TURNED OFF, DISCONNECTED, AND ELECTRICALLY ISOLATED SO THAT NO ACCIDENTAL CONTACT CAN BE MADE WITH ENERGIZED PARTS. FOLLOW ALL MANUFACTURER’S WARNINGS AND INSTRUCTIONS. WARNING: OPERATION OF BUSWAY THAT HAS BEEN WATER OR MOISTURE DAMAGED CAN CAUSE PROPERTY DAMAGE, SEVERE PERSONAL INJURY, OR DEATH. OBSERVE THE PRECAUTIONS IN SECTIONS 6.8 AND 6.9 TO ENSURE ADEQUATE INSULATION RESISTANCE AND THAT SOURCES OF MOISTURE ARE ELIMINATED. SAFETY RELATED WORK PRACTICES, AS DESCRIBED IN NFPA 70E, SHOULD BE FOLLOWED AT ALL TIMES. CAUTION: Hydrocarbon spray propellants and hydrocarbon based sprays or compounds will cause degradation of certain plastics and elastomers. Contact the busway manufacturer before using these products to clean, dry, or lubricate compounds during installation or maintenance. © Copyright 2010 by the National Electrical Manufacturers Association.
  • 10. BU 1.1-2010 Page 4 Section 4 HANDLING These guidelines are provided to help avoid personal injury and equipment damage during handling, and to facilitate moving the busway sections and fittings at the job site. 4.1 Follow the manufacturer's handling instructions for the specific equipment, if available. 4.2 Handle busway with care to avoid damage to internal components and the enclosure or its finish. Avoid subjecting busway to twisting, denting, impact, and, in general, rough handling. 4.3 Do not use busbar ends for lifting busway sections or fittings. 4.4 When the busway is received, unpack it sufficiently to inspect it for concealed damage and to determine that the shipment is complete and correct. 4.5 If busway is to be stored prior to installation, restore the packing for protection during that period (See Section 5). When conditions permit, leave the packing intact until the sections or fittings are at their final installation location. 4.6 Verify that the weight of any busway sections or fittings are within the rated capacity of the handling equipment to be used. 4.7 Platform dollies provide a simple method of moving busway on one floor level if there is little or no incline. Balance the load carefully. 4.8 A forklift truck may offer a more convenient method of handling busway and has the added advantage of permitting it to be hoisted between levels. Balance the load carefully. 4.9 Platform lifts or elevators, either manually or power operated, can be used advantageously in moving loads of busway between elevations. © Copyright 2010 by the National Electrical Manufacturers Association.
  • 11. BU 1.1-2010 Page 5 Section 5 STORAGE 5.1 Busway sections and fittings that are not to be installed and energized immediately should be stored in a clean, dry space having a uniform temperature to prevent condensation. Preferably, they should be stored in a heated building having adequate air circulation and protected from dirt, fumes, water, and physical damage. 5.2 It is recommended that busway should not be stored outdoors. However, if it must be stored outdoors, cover it securely to provide protection from weather and dirt. Temporary electrical heating should be installed beneath the cover to prevent condensation. At least 3 watts per cubic foot is adequate for the average environment. 5.3 Outdoor busway is not weather resistant until completely and properly installed and should be treated exactly the same as indoor busway until after it is installed. © Copyright 2010 by the National Electrical Manufacturers Association.
  • 12. BU 1.1-2010 Page 6 Section 6 INSTALLATION 6.1 GENERAL 6.1.1 Provide sufficient horizontal and vertical clearance from walls and ceilings to provide easy access to joints, both for the original installation and possible removal of a section when required. Busways may be installed behind panels if means of access are provided and if all the conditions of Article 368 of the National Electrical Code are met. 6.1.2 Follow the manufacturer's installation instructions and the current edition of the National Electrical Code. 6.1.3 Conduct an insulation resistance test on each busway device with an insulation resistance tester rated 1000 volts to ensure that the system is free from short circuits and grounds (phase-to- ground, phase-to-neutral, and phase-to-phase). Record and maintain records of the testing results. Turn the test results over to the general contractor or owner at completion of the project. It should be noted that readings vary inversely with the length of run and width or number of bars per phase. Readings will vary with humidity. If readings of less than 1 megohm for a 100-foot run (MEGOHMS = 100 / length of busway in feet) are obtained, contact the manufacturer. 6.2 UNPACKING 6.2.1 Care must be used in unpacking. Band cutters should be used on all banding securing the package. 6.2.2 Nail pullers should be used for unpacking wooden crates to avoid damage. 6.2.3 Remove any support blocks that may have been used for shipping. 6.3 HOISTING AND HANDLING (SEE ALSO SECTION 4) 6.3.1 If a crane is used to install busway, use nylon straps and distribute or balance the weight of each lift. If cables are used, spreaders should be used to avoid damage to the busway's metal housing. 6.3.2 If a forklift truck or similar hoist is used, properly position the busway on the fork to distribute its weight. Careful approach is a must to avoid any damage to the metal housing that could pinch the bus bar insulation and result in a failure. 6.3.3 Do not drag the busway across the floor. 6.3.4 When installing vertical sections, it is easier to lower the busway from the floor above where it will be installed. Vertical sections are often stored on the floor above their final location to facilitate lowering them into position. 6.4 HANGING OR SUPPORTING 6.4.1 Use the hangers or the hanging recommendations supplied by the manufacturer in the manner prescribed to afford a secure installation and proper spacing. © Copyright 2010 by the National Electrical Manufacturers Association.
  • 13. BU 1.1-2010 Page 7 6.4.2 Horizontal Mounting A busway that is mounted horizontally should be supported at a maximum of 5-foot intervals and in no case at more than 10-foot intervals if it is marked as being suitable for such intervals. The supports and/or the busway should be braced to minimize swaying. Align busway runs vertically and horizontally to minimize sags and twists. Bus plugs or cubicles that have considerable weight and that are mounted with a horizontal run of busway should be separately supported by the building structure to prevent twisting or deformation of the busway. Exercise caution when plugs are used on one side of a busway or when there are more plugs on one side than on the other. 6.4.3 Vertical Mounting A busway that is to be mounted vertically should be marked to indicate that it is suitable for that service. When the distance between floor supports is more than the busway is marked as suitable for, the manufacturer's recommendation regarding intermediate supports should be followed, but in no case should support intervals exceed 16 feet. Heavy cubicles, panelboards, and bus plugs should be separately supported by the building structure when so recommended by the manufacturer. Align busway runs vertically and horizontally to minimize sags and twists. During installation, protect vertical busways from moisture infiltration from unfinished roofs, walls, etc. 6.4.4 Expansion Joints A busway section that spans a building expansion joint should be provided with suitable expansion means for both the busbars and the busway housing unless the length of busway beyond the building expansion joint is sufficiently short so that the supporting means can be designed to withstand the expected building motion. Expansion joints may also be required on unusually long, straight runs or vertical risers. Consult the busway manufacturer for recommendations on specific layouts. 6.4.5 Level and plumb busway (align horizontally and vertically) before the final tightening of all joints. 6.5 JOINT ASSEMBLY 6.5.1 Ensure that all contact surfaces are clean and free of contaminants. 6.5.2 Align the busbar ends of adjoining sections, verifying proper phase alignment, and slide the sections together. 6.5.3 Use joint pullers, if available. 6.5.4 Follow the manufacturer's instructions for proper completion of joint assemblies and torquing of joint bolts. 6.5.5 Busway should be properly covered during installation to protect it from moisture or other types of contaminants. 6.6 GROUNDING 6.6.1 The enclosure of a UL listed busway marked with a short-circuit current rating is recognized as an equipment grounding conductor. However, the enclosure must be properly bonded to other equipment grounding conductors in the system, and all of these conductors must be properly © Copyright 2010 by the National Electrical Manufacturers Association.
  • 14. BU 1.1-2010 Page 8 connected to a suitable system ground. Consult the National Electrical Code for proper system grounding procedures. 6.7 MOUNTING PLUG-IN DEVICES 6.7.1 Follow the manufacturer's instructions for the proper mounting of plug-in devices. 6.7.2 Allow sufficient clearances to install, operate, and remove devices and open covers when necessary. 6.7.3 All plug-in openings that are not in use should be covered when such covers are provided. 6.7.4 All tap-off or plug-in devices should be in the “OFF” position during installation and removal. 6.8 PROTECTION FROM LIQUIDS, MOISTURE, AND OTHER CONTAMINANTS 6.8.1 Busway should be protected from liquids, moisture, and other contaminants to prevent electrical failure. 6.8.2 Some common sources of such contaminants are described below. 6.8.2.1 During construction—Indoor busways must be protected from moisture during and after installation. Protective measures should be taken to prevent condensation formation inside the busway when installed in unheated buildings. Special attention should be given to riser busways during construction to protect them from moisture from uncompleted roofs, walls, etc. Outdoor busway is not weather resistant until completely and properly installed. It should be treated exactly the same as indoor busway until after it is installed. Always verify that the insulation resistance test of 7.4 has been conducted before energizing any busway for the first time. 6.8.2.2 Floor level liquids—Four-inch minimum curbs should be installed around all floor openings for riser busways to prevent floor level liquids from entering the opening. 6.8.2.3 Leaking Roof—Protect indoor busway with a temporary sheet metal shield or other protective cover to prevent water from falling onto the busway until the roof is repaired. 6.8.2.4 Pipes—Protect indoor busway with a temporary sheet metal shield or other protective cover to prevent water from falling onto the busway until leaking pipes are repaired. Where pipes (especially cold water pipes) pass directly above indoor busway, the busway should be protected from dripping condensate by insulating the pipe or permanently shielding the busway with sheet metal or plastic. 6.8.2.5 Sprinklers—Protect indoor busway from direct spray of sprinklers. 6.8.2.6 Snow—Outdoor busway should be mounted sufficiently above the ground or roof so that snow build-up does not surround the busway and result in water being forced into the busway through weep holes. 6.8.2.7 Rain—Outdoor busway should be mounted sufficiently above the ground or roof so that a driving rain will not result in water being forced into the busway through the weep holes. 6.8.2.8 Transverse Barriers Where a busway extends through a floor or inside wall and where temperature differences could result in condensation, an internal transverse barrier, which is designed to restrict the free flow of air, should be provided. © Copyright 2010 by the National Electrical Manufacturers Association.
  • 15. BU 1.1-2010 Page 9 Where a busway extends through a roof or outside wall, a suitable weather barrier should be installed in accordance with the manufacturer's instructions. 6.9 SUMMARY 6.9.1 Review erection drawings very carefully. 6.9.2 Check the bill of material. 6.9.3 Check the description and identification of each piece before installing it. 6.9.4 Follow instructions on each piece for torque requirements. 6.9.5 Follow the manufacturer's joint assembly instruction drawing for both indoor and outdoor procedures. 6.9.6 Conduct an insulation resistance test on each section of busway before it is installed. 6.9.7 Conduct an insulation resistance test on the portion of each run already installed on a daily basis. 6.9.8 Check for possible sources of water that may fall on indoor busway, and take corrective action to prevent this. © Copyright 2010 by the National Electrical Manufacturers Association.
  • 16. BU 1.1-2010 Page 10 Section 7 STEPS TO BE TAKEN BEFORE ENERGIZING WARNING: HAZARDOUS VOLTAGES IN ELECTRICAL EQUIPMENT CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. UNLESS OTHERWISE SPECIFIED, INSTALLATION, INSPECTION, AND MAINTENANCE SHOULD ONLY BE PERFORMED ON BUSWAY AND EQUIPMENT TO WHICH POWER HAS BEEN TURNED OFF, DISCONNECTED, AND ELECTRICALLY ISOLATED SO THAT NO ACCIDENTAL CONTACT CAN BE MADE WITH ENERGIZED PARTS. FOLLOW ALL MANUFACTURER’S WARNINGS AND INSTRUCTIONS. 7.1 Recheck all joint connections for tightness. Follow the manufacturer's torquing recommendations. 7.2 Ensure that all tap-off or plug-in devices are in the “OFF” position. Tap-off or plug-in devices without integral disconnects should be removed from busway if they cannot be isolated by an auxiliary disconnect 7.3 Isolate the busway run by disconnecting all connections to transformers, switchboards, meters, and so forth. 7.4 Conduct an insulation resistance test with an insulation resistance tester rated 1000 volts to ensure that the system is free from short circuits and grounds (phase-to-ground, phase-to- neutral, and phase-to-phase). Record and maintain records of the testing results. Turn the test results over to the general contractor or owner at completion of the project. It should be noted that readings vary inversely with the length of run and width or number of bars per phase. Readings will vary with humidity. If readings of less than 1 megohm for a 100-foot run (MEGOHMS = 100 / length of busway in feet) are obtained, contact the manufacturer. 7.5.1 Verify that the system phasing matches the busway phasing before reconnecting all connections to transformers, switchboards, meters, and so forth. 7.5.2 Ensure that ventilation openings and drain holes are clear. On outdoor busway, verify that weep- hole screws or plugs have been removed in accordance with manufacturer recommendations. © Copyright 2010 by the National Electrical Manufacturers Association.
  • 17. BU 1.1-2010 Page 11 Section 8 ENERGIZING EQUIPMENT WARNING: HAZARDOUS VOLTAGES IN ELECTRICAL EQUIPMENT CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. UNLESS OTHERWISE SPECIFIED, INSTALLATION, INSPECTION, AND MAINTENANCE SHOULD ONLY BE PERFORMED ON BUSWAY AND EQUIPMENT TO WHICH POWER HAS BEEN TURNED OFF, DISCONNECTED, AND ELECTRICALLY ISOLATED SO THAT NO ACCIDENTAL CONTACT CAN BE MADE WITH ENERGIZED PARTS. FOLLOW ALL MANUFACTURER’S WARNINGS AND INSTRUCTIONS. 8.1 It is not recommended that any busway be energized unless the insulation resistance test described in Section 7.4 has been successfully completed. 8.2 When the equipment is energized for the first time, qualified electrical personnel should be present. If short circuits and ground faults caused by damage or poor installation practices have not been detected in the check-out procedure, serious damage can result when the power is turned on. 8.3 There should be no electrical load on the busway when it is energized. Since busway typically extends through several rooms and floor levels, care should be taken to see that all devices fed from the busway are in the "OFF" position. 8.4 The equipment should be energized in sequence by starting at the source end of the system and working toward the load end. In other words, energize the main devices, then the feeder devices, and then the branch-circuit devices. Turn the devices to the "ON" position with a firm positive motion. 8.5 After all overcurrent devices have been turned on, loads such as lighting circuits, contactors, heaters, and motors may be turned "ON." 8.6 Busway, when operating properly, will have a moderate hum. Excessive noise may be an indication of hardware that has not been tightened or of metal parts that have been improperly assembled. 8.7 Occurrence of sparking at any point along the busway is not a normal condition. The busway must be de-energized immediately, and remain de-energized until the sparking condition has been corrected. © Copyright 2010 by the National Electrical Manufacturers Association.
  • 18. BU 1.1-2010 Page 12 Section 9 CARE AND MAINTENANCE 9.1 OUTDOOR BUSWAY 9.1.1 Inspect busway once each year or after any severe electrical short circuit or ground fault. 9.1.2 Perform an infrared temperature scan on all electrical connections and busway enclosures while busway is energized and operating under maximum load conditions. A permanent record should be kept. If readings change with time, deterioration may be taking place and must be corrected. WARNING: HAZARDOUS VOLTAGES IN ELECTRICAL EQUIPMENT CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. UNLESS OTHERWISE SPECIFIED, INSTALLATION, INSPECTION, AND MAINTENANCE SHOULD ONLY BE PERFORMED ON BUSWAY AND EQUIPMENT TO WHICH POWER HAS BEEN TURNED OFF, DISCONNECTED, AND ELECTRICALLY ISOLATED SO THAT NO ACCIDENTAL CONTACT CAN BE MADE WITH ENERGIZED PARTS. FOLLOW ALL MANUFACTURER’S WARNINGS AND INSTRUCTIONS. WARNING: OPERATION OF BUSWAY THAT HAS BEEN WATER OR MOISTURE DAMAGED CAN CAUSE PROPERTY DAMAGE, SEVERE PERSONAL INJURY, OR DEATH. OBSERVE THE PRECAUTIONS IN SECTIONS 6.8 AND 6.9 TO ENSURE ADEQUATE INSULATION RESISTANCE AND THAT SOURCES OF MOISTURE ARE ELIMINATED. SAFETY RELATED WORK PRACTICES, AS DESCRIBED IN NFPA 70E, SHOULD BE FOLLOWED AT ALL TIMES. CAUTION: Hydrocarbon spray propellants and hydrocarbon based sprays or compounds will cause degradation of certain plastics and elastomers. Contact the busway manufacturer before using these products to clean, dry, or lubricate compounds during installation or maintenance. 9.1.3 Turn off power to the busway. 9.1.4 If there is appreciable accumulation of dust and dirt, clean it off by using a brush, vacuum cleaner, or clean lint-free rags. In order to avoid blowing dust into busway joints, circuit breakers, or other equipment, do not use a blower or compressed air. Ensure that all drain holes are operating properly. 9.1.5 Check the insulation resistance prior to re-energizing the busway. A permanent record should be kept of resistance readings. If readings decrease appreciably with time, deterioration is taking place and must be corrected. (Contact the manufacturer.) Also, refer to Section 7.4. 9.2 INDOOR BUSWAY 9.2.1 Inspect busway once each year or after any severe electrical short circuit or ground fault or if the busway has been subjected to a liquid spill. 9.2.2 Perform an infrared temperature scan on all electrical connections and busway enclosure while busway is energized and operating under maximum load conditions. A permanent record should be kept. If readings change with time, deterioration may be taking place and must be corrected. © Copyright 2010 by the National Electrical Manufacturers Association.
  • 19. BU 1.1-2010 Page 13 WARNING: HAZARDOUS VOLTAGES IN ELECTRICAL EQUIPMENT CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. UNLESS OTHERWISE SPECIFIED, INSTALLATION, INSPECTION, AND MAINTENANCE SHOULD ONLY BE PERFORMED ON BUSWAY AND EQUIPMENT TO WHICH POWER HAS BEEN TURNED OFF, DISCONNECTED, AND ELECTRICALLY ISOLATED SO THAT NO ACCIDENTAL CONTACT CAN BE MADE WITH ENERGIZED PARTS. FOLLOW ALL MANUFACTURER’S WARNINGS AND INSTRUCTIONS. CAUTION: Hydrocarbon spray propellants and hydrocarbon based sprays or compounds will cause degradation of certain plastics and elastomers. Contact the busway manufacturer before using these products to clean, dry, or lubricate compounds during installation or maintenance. 9.2.3 Turn off power to busway. 9.2.4 Look for any moisture or signs of previous wetness or dripping onto the busway or onto connection boxes from leaky roofs, pipes, sprinklers, or other sources of moisture. Look for any recent changes in sprinklers or other plumbing that might now be a source of trouble to busway. 9.2.4.1 Seal off any cracks or openings that have allowed moisture to enter the busway or its connection boxes. Eliminate source of any dripping onto the busway and any other source of moisture. See Section 6.8 for more specific details on preventing liquid from getting onto the busway. 9.2.4.2 Replace or thoroughly dry and clean any insulating material that is damp or wet or shows accumulation of deposited material from previous wettings. Consult the manufacturer for proper procedures. 9.2.5 If there is appreciable accumulation of dust, clean it off by using a brush, vacuum cleaner, or clean lint-free rags. In order to avoid blowing dust into busway joints, circuit breakers, or other equipment, do not use a blower or compressed air. 9.2.6 Carefully inspect all visible electrical joints and terminals. 9.2.7 Visually check connections to be certain that they are clean and secure. Loose and/or contaminated connections increase electrical resistance which can cause overheating. Such overheating is indicated by discoloration or flaking of insulation and/or metal parts. Pitting or melting of connecting surfaces is a sign of arcing due to a loose or otherwise poor connection. Parts that show evidence of overheating or looseness should be cleaned or replaced if damaged; contact manufacturer before re-torquing joint bolts. CAUTION: Do not remove plating from aluminum parts in joints or terminations. Removal of plating can result in overheating. Replace damaged aluminum parts. 9.2.8 Check the insulation resistance prior to re-energizing the busway. A permanent record should be kept of resistance readings. If readings decrease appreciably with time, deterioration is taking place and must be corrected. (Contact the manufacturer.) Also, refer to Section 7.4. 9.3 BUSWAY PLUGS AND CUBICLES WITH PROTECTIVE DEVICES WARNING: HAZARDOUS VOLTAGES IN ELECTRICAL EQUIPMENT CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. UNLESS OTHERWISE SPECIFIED, INSTALLATION, INSPECTION, AND MAINTENANCE SHOULD ONLY BE PERFORMED ON BUSWAY AND EQUIPMENT TO WHICH POWER HAS BEEN TURNED OFF, DISCONNECTED, AND ELECTRICALLY ISOLATED SO THAT NO ACCIDENTAL CONTACT CAN BE MADE WITH ENERGIZED PARTS. FOLLOW ALL MANUFACTURER’S WARNINGS AND INSTRUCTIONS. © Copyright 2010 by the National Electrical Manufacturers Association.
  • 20. BU 1.1-2010 Page 14 CAUTION: Hydrocarbon spray propellants and hydrocarbon based sprays or compounds will cause degradation of certain plastics and elastomers. Contact the busway manufacturer before using these products to clean, dry, or lubricate compounds during installation or maintenance. 9.3.1 Additional guidance on the care and maintenance of protective devices can be found in NEMA AB 4 for molded case circuit breakers and NEMA KS 3 for switches. 9.3.2 Turn off power to busway. 9.3.3 Examine fuse clip contact pressure and contact means. If there is any sign of overheating or looseness, follow the manufacturer's maintenance instructions or replace the fuse clips. Loose fuse clips can result in overheating. 9.3.4 Look for any signs of deterioration in insulating material or melting of the sealing compound. Replace such insulating parts and assemblies where the sealing compound has melted. 9.3.5 BE SURE THAT ALL CONDITIONS WHICH CAUSED THE OVERHEATING HAVE BEEN CORRECTED. 9.3.6 Check the operation of all mechanical components. 9.3.6.1 Exercise switch operating mechanisms and external operators for circuit breakers to determine that they operate freely to their full on and off positions. 9.3.6.2 Check the mechanisms of all electrical and mechanical interlocks and padlocking means. 9.3.6.3 Check for missing or broken parts, proper spring tension, free movement, rusting or corrosion, dirt, and excessive wear. 9.3.6.4 Examine all readily accessible arc chutes and insulating parts for cracks or breakage and for arc spatter, sooty deposits, oil, or tracking. 9.3.6.5 Clean off arc spatter, oil, and sooty deposits. Replace the device if appreciable material has burned away or if parts are charred or cracked. 9.3.7 Lubricate the operating parts of switch mechanisms, and other moving parts, according to the manufacturer's instructions. Use only manufacturer approved cleaners and lubricates. CAUTION: Hydrocarbon spray propellants and hydrocarbon based sprays or compounds will cause degradation of certain plastics and elastomers. Contact the busway manufacturer before using these products to clean, dry, or lubricate compounds during installation or maintenance. 9.3.7.1 Use clean, nonmetallic, light grease or oil as instructed. 9.3.7.2 Do not oil or grease parts of molded case circuit breakers. 9.3.7.3 If no instructions are given on the devices, sliding copper contacts, operating mechanisms, and interlocks may be lubricated with clean, light grease. 9.3.7.4 Wipe off excess lubrication to avoid accumulation of foreign material. 9.3.8 Operate each switch or circuit breaker several times to ensure that all mechanisms are free and in proper working order. Ensure all interlocking mechanisms function properly. © Copyright 2010 by the National Electrical Manufacturers Association.
  • 21. BU 1.1-2010 Page 15 9.3.9 Re-tighten all wire connections according to the manufacturer’s instructions. 9.3.10 Check circuit breakers and fuses to ensure they have the proper ampere, voltage, and interrupting ratings. Ensure that non–current-limiting devices are not used as replacements for current-limiting devices. Never attempt to defeat rejection mechanisms, which are provided to prevent the installation of the incorrect class of fuse. 9.3.11 Check the insulation resistance of devices prior to their reinstallation on the busway. 9.4 FINAL TEST 9.4.1 After performing all of the above inspections and necessary repairs, it may be desirable to perform another infrared temperature scan on all electrical connections after busway is re- energized and reaches a stabilized operating temperature. A permanent record should be kept. If readings change with time, deterioration may be taking place and must be corrected. © Copyright 2010 by the National Electrical Manufacturers Association.
  • 22. BU 1.1-2010 Page 16 Section 10 PERMISSIBLE LOADING OF BUSWAYS 10.1 BUSWAYS—WITH OR WITHOUT OVERCURRENT PROTECTION 10.1.1 The total continuous load current should not exceed the current rating on the busway nameplate. For outdoor busway, the radiant heat from the sun in the installation location must be considered when busway system is sized for ampacity. Consult the manufacturer for appropriate derating. 10.2 BUSWAY PLUGS 10.2.1 The total continuous load current on a busway fusible plug should not exceed 80 percent of the ampere rating of the fuses. The total continuous load current on other types of plugs should not exceed 80 percent of the ampere rating of the plug unless the device is rated to carry 100 percent of its ampere rating. Cycling loads with high inrush currents may require additional consideration when sizing plug-in units. Consult the manufacturer’s literature for proper sizing under these conditions. © Copyright 2010 by the National Electrical Manufacturers Association.
  • 23. BU 1.1-2010 Page 17 Section 11 OPERATING CONDITIONS 11.1 NORMAL OPERATING CONDITIONS 11.1.1 Busways shall be suitable for operation: a. When and where the ambient temperature is within the limits -30°C through +40°C for busway and busway plug-in-units incorporating enclosed switches. b. When and where the ambient temperature is within the limits 0°C through +40°C for busway plug-in-units incorporating molded case circuit breakers or electromagnetic and manual motor controls. c. Where the altitude does not exceed 6600 feet (2000 meters). 11.1.2 Voltage Drop (General) Good practice indicates that the voltage drop in feeder circuits up to the final distribution point where the load is divided into individual branch circuits should not exceed 3 percent for power, heating, or lighting loads or combination thereof. Total voltage drop for feeders and individual branch circuits up to the final utilization point should not exceed 5 percent overall. 11.2 UNUSUAL OPERATING CONDITIONS 11.2.1 When busways are installed in locations that have a continuous ambient temperature above 40°C (104°F), the busways should be de-rated in accordance with the manufacturer’s recommendations, if furnished, or the following table: AMBIENT TEMPERATURE MULTIPLIER 40°C (104°F) 1.00 45°C (113°F) 0.95 50°C (122°F) 0.90 55°C (131°F) 0.85 60°C (140°F) 0.80 65°C (149°F) 0.74 70°C (158°F) 0.67 11.2.2 For applications where the ambient temperature is lower than the minimum limits per 11.1.1a and 11.1.1b or at altitudes greater than 6600 feet (2000 meters), consult the manufacturer. 11.2.3 Unless specifically designed for such use, do not locate busway so that it is exposed to dust, vapors, abnormal vibration, shock, or other such unusual operating conditions. A busway should not be installed in wet locations or outdoors unless specifically identified as an outdoor busway. § © Copyright 2010 by the National Electrical Manufacturers Association.