SlideShare a Scribd company logo
1 of 70
BLACKOUT
AVOIDANCE
&
UNDER VOLTAGE
LOAD
SHEDDING
Blackout Avoidance
BLACKOUTS
 How and why they occur
 Why voltage rather than frequency is the
leading edge indicator of system collapse
 How blackout conditions effect generators
and generator protection
 Undervoltage load shedding
Blackout Avoidance
RECENT BLACKOUTS
2003 - East Coast Blackout
2003 - Italian Blackout
2002 - Swedish Blackout
1997 - PJM Disturbance
1996 - West Coast Blackout
1995 - PECO Disturbance
1987 - City of Memphis
Blackout Avoidance
Root Cause of Recent Blackouts
VOLTAGE COLLAPSE – WHY?
 Today, major generation sources are remote from
load centers. This was NOT the case 35 years
ago.
 This makes the power system very reliant on
transmission system to transport power to load
centers.
Blackout Avoidance
Root Cause of Recent Blackouts
VOLTAGE COLLAPSE – WHY?
 Purchase power from remote sources to save
$$$.
 New generation built remotely from load
centers.
 Little new transmission being built.
 Utility loads are increasingly made up of air
conditioning motors susceptible to stall
conditions due to transmission system faults.
Blackout Avoidance
 As lines trip between remote generation and load
center, the reactance increases.
 This increases the reactive (VAR) losses-reducing
the voltage at the load center.
 The voltage phase angle between the
generators at the load center and
remote generators also increase.
REM OTE
GENERATION LOCAL LOAD
CENTER
LINE 1
LINE 2
LINE 3
LINE 4
LINE 5
LINE 6
How Voltage Collapses Occur
Blackout Avoidance
POWER TRANSFER
EXAMPLE
Blackout Avoidance
Real Power (MW) Flow Example
SYSTEM
A
SYSTEM
B SYSTEM
C
Eg O
Es O
POWER
FLOW
Blackout Avoidance
Pe = Eg Es Sin ( 0g- 0s )
X
Where: Eg = Voltage at the Load Center
Generation
Es = Voltage at the Remote Generation
Pe = Electrical Real Power Transfer
X = Reactance Between Local and
Remote Generation
0g = Votage Angle and Local Generation
0s = Voltage Angle at Remote Generation
POWER TRANSFER EQUATION
Where: Es = Voltage at the Load Center
Eg = Voltage at the Remote Generation
Pe = Electrical Real Power Transfer
X = Reactance Between Local and Remote Generation
0s = Voltage Angle and Local Generation
0g = Voltage Angle at Remote Generation
Pe = Eg Es Sin ( 0g- 0s )
X
Where: Eg = Voltage at the Load Center
Generation
Es = Voltage at the Remote Generation
Pe = Electrical Real Power Transfer
X = Reactance Between Local and
Remote Generation
0g = Voltage Angle and Local Generation
0s = Voltage Angle at Remote Generation
POWER TRANSFER EQUATION
SYSTEM
A
Load = 5000MW
GEN. =5000 MW
SYSTEM
B
Load = 5000MW
Gen. = 5000MW
SYSTEM
C
Load = 5000MW
Gen. = 5000MW
Eg O
Es O
POWER
FLOW - 0MW
TRANSFER
Real Power (MW) Flow Example
Blackout Avoidance
Where: Es = Voltage at the Load Center
Eg = Voltage at the Remote Generation
Pe = Electrical Real Power Transfer
X = Reactance Between Local and Remote Generation
0s = Voltage Angle and Local Generation
0g = Voltage Angle at Remote Generation
Where: Eg = Voltage at the Load Center
Generation
Es = Voltage at the Remote Generation
Pe = Electrical Real Power Transfer
X = Reactance Between Local and
Remote Generation
0g = Voltage Angle and Local Generation
0s = Voltage Angle at Remote Generation
POWER TRANSFER EQUATION
Pe = Eg Es Sin ( 0g- 0s )
X
Real Power (MW) Flow Example
SYSTEM
A
Load = 5000 MW
GEN. = 7000 MW
SYSTEM
B
Load = 5000 MW
Gen. = 5000 MW
SYSTEM
C
Load = 5000 MW
Gen. = 3000 MW
Eg O
Es O
POWER
FLOW - 2000 MW
TRANSFER
Blackout Avoidance
Where: Es = Voltage at the Load Center
Eg = Voltage at the Remote Generation
Pe = Electrical Real Power Transfer
X = Reactance Between Local and Remote Generation
0s = Voltage Angle and Local Generation
0g = Voltage Angle at Remote Generation
SYSTEM
A
SYSTEM
B
SYSTEM
C
Eg O
Es O
REACTIVE
POWER
FLOWSMALL
1. T o m a k e reactive p o w e r f l o w
y o u n e e d to h a v e a d i f f e r e n ce
in v o l t a g e m a g n i t u d e b e t w e e n
E g a n d E s .
2. V o l t a g e o n a p o w e r s y s t e m
c a n o n l y b e va r i e d +/- 5 %
w h i c h is n o t e n o u g h d i f f e r e n ce
to result in a significant V A R S
flow .
3. T h u s V A R S c a n n o t b e
t r a n s m i t t e d o v e r l o n g
d i s t a n c e s a n d m u s t b e
g e n e r a t e d locally n e a r t h e
l o a d .
Reactive Power (Mvars) Flow
Blackout Avoidance
Sources of Reactive (Var) Support
 VAr Support must be provided at the load
center.
 Two major sources of VAr support:
Capacitor Banks – Double-Edge Sword.
Vars go down with the square of voltage.
Generators/ Synch. Condensers – A
dynamic source of Vars. Can adjust VAr
output rapidly during contingencies.
Blackout Avoidance
LOAD RESPONSE
TO
LOW VOLTAGE
Blackout Avoidance
How Load Responds to Low Voltage
Basic Power System
Remote
Generation
TransmissionSystem LoadCenter
Resistive
Load
Motor
Load
VAR
Support
Local
Generation
Ps PL
QLVL
Blackout Avoidance
How Load Responds to Low Voltage
 Resistive load current decreases as voltage
goes down Helping the system.
 Motor loads are constant KVA devices and
increase their load current as voltage decreases-
Hurts the system.
 During “Heat Storm” conditions, most load is
motor load making blackout more likely.
Blackout Avoidance
Example of Voltage Recovery From a
Transmission Fault- Rapid Voltage Collapse
R e sid e ntia l V o ltag e R e cove ry fo r P hoe n ix A rea In cide nt on July 2 9 , 19 95
Blackout Avoidance
RECENT BLACKOUTS REVISITED
2003 - East Coast Blackout
2003 - Italian Blackout
2002 - Swedish Blackout
1997 - PJM Disturbance*
1996 - West Coast Blackout
1995 - PECO Disturbance*
1987 - City of Memphis*
* Rapid Voltage Collapse
Blackout Avoidance
POWER SYSTEM
INSTABILITY
Blackout Avoidance
POWER SYSTEM INSTABILITIES
Four Types of Instability:
 Voltage*
 Steady State *
 Transient
 Dynamic
*Involved in Recent Blackouts
Blackout Avoidance
REMOTE
GENERATION LOCAL LOAD
CENTER
LINE 1
LINE 2
LINE 3
LINE 4
LINE 5
LINE 6
Eg O Es O
POWER FLOW
Voltage Collapse Scenario
Blackout Avoidance
REMOTE
GENERATION LOCAL LOAD
CENTER
LINE 1
LINE 2
LINE 3
LINE 4
LINE 5
LINE 6
Eg O Es O
POWER FLOW
Voltage Collapse Scenario
Blackout Avoidance
Pmax = Eg Es
Max. X
Power All Lines in Service
Transfer
Line 1
Tripped
Pe
Line 2
Tripped
0 90o 1800
0g - 0s
Pmax = Eg Es
Max. X
Power All Lines in Service
Transfer
Line 1
Tripped
Pe
Line 2
Tripped
0 90o 1800
0g - 0s
Pe = Eg Es Sin ( 0g- 0s )
X
POWER TRANSFER EQUATION
Eg Og Es Os
POWER FLOW
REMOTE
GENERATION LOCAL LOAD
CENTER
LINE 1
LINE 2
LINE 3
LINE 4
LINE 5
LINE 6
0 1800
Max.
Power
Transfer
All Lines in Service
Line 1
Tripped
Line 2
Tripped
Pe
Pmax = Eg Es
X
90o
0g - 0s
Steady State Instability
Blackout Avoidance
Generator
G
GSU
System
Reactance
V
Xd XT
XS
V2
__ 1____ + 1
2 XT + XS Xd
Per Unit MW
Per Unit
MVAR
___1___ 1V2
2 XT + XS Xd
a) MW - MVAR PER UNIT PLOT
X
R
Xd + XT + XS
2
XT + XS
Xd - XT + XS
2
Xd
b) R-X DIAGRAM PLOT
Steady State Instability
Blackout Avoidance
GENERATOR RESPONDS
TO BLACKOUT
CONDITIONS
Blackout Avoidance
Gen.
AVR
Excitation
Transformer
CT VTField
Static
Exciter
Generator Excitation & AVR Control
Generator Step-up
Transformer
Generator
Blackout Avoidance
Reactive Power
into System
Reactive Power
into Generator
Real Power
into System
+
MVAR
Overexcited
Underexcited
0
-
MVAR
Under
Excitation
Limiter
(URL)
+ MW
MW
G
MVARS
Overexcitation
Limiter (OEL)
Winding
Limited
Stator
Winding
Limited
Stator End
Iron Limited
MW
G
MVAR
System
Normal Overexcited
Operation
Underexcited
Operation
System
How Generators Provide Vars to the
System
 The Generator AVR (Automatic Voltage Regulator)
Controls Field Current into the Rotor Which in Turn
Controls Terminal Voltage and VAr Output/Input.
Rotor
Blackout Avoidance
AVR Limiters Response During Low Voltage
DEPENDS ON THE MANUFACTURER:
 Some Limiters Change as the Square of the
Voltage – 90% Voltage Results in 81% of Setting
 Some Proportional to Voltage – 90% Voltage
result in 90% Setting
 Some Do Not Change with Voltage at all
Blackout Avoidance
0 1800
Max.
Power
Transfer
All Lines in Service
Breakers 1 and 2
Tripped
PM = Pe
Pmax = Eg Es
X
90o
0g - 0s
A2
0C
A1
Transient Instability
Blackout Avoidance
Typical Out-of-Step Impedance LOCI
Blackout Avoidance
 Required by WECC in the Western USA for
generators larger than 30 MVA
Dynamic Instability
 Occurs when fast acting AVR control amplifies
rather than damps small MW oscillations.
 Occurs when generators are remote from load
 Solution is AVR Power System Stabilizers
(PSS) – Low Freq. Filter
Blackout Avoidance
GENERATOR PROTECTION
RESPOND TO BLACKOUT
CONDITIONS
Blackout Avoidance
Key Generator Protection Functions
Effected by Major System Disturbances
 Loss of Field (40)
 Overexcitation (24)
 Overexcitation (24) System Backup (21 & 51V)
 Under Frequency (81)
 Out of Step Protection (78)
Blackout Avoidance
Generator Protection Effected by Major
System Disturbances
 Loss of Field (40) – Must be Coordinated with
AVR Control, Steady State Stability Limit and
Secure Under Low Voltage.
 Overexcitation (24) - Coordinated with AVR
Control.
 System Backup (21 & 51V) – Secure on Stable
Power Swings and System Low Voltage. Must
be Coordinated with Transmission
Protection.
Blackout Avoidance
Generator Protection Effected by Major
System Disturbances
 Under Frequency (81) – Coordinated with
System Load Shedding.
 Out of Step Protection (78) – Set to trip the
Generator if it Losses Synchronism.
Blackout Avoidance
-X
+R-R
- Xd’
2
Xd
Generator
Capability
Under Excitation
Limiter (UEL)
Heavy Load Light Load
Impedance Locus
During Loss of Field
1.0 pu
Steady State
Stability Limit
Zone 1
Zone 2
Loss of Field (40) – Must be Coordinated with
AVR Control, Steady State Stability Limit and
Secure Under Low Voltage.
+X
Blackout Avoidance
Transformation From Mw-Mvar to R-X Plot
Blackout Avoidance
G
Reactive Power
into System
Reactive Power
into Generator
Real Power
into System
+
MVAR
Overexcited
Underexcited
0
-
MVAR
Under
Excitation
Limiter
(URL)
+ MW
MW
G
MVARS
Overexcitation
Limiter (OEL)
Rotor
Winding
Limited
Stator
Winding
Limited
Stator End
Iron Limited
Steady State
Stability Limit
MW
MVAR
System
Normal Overexcited
Operation
Underexcited
Operation
System
Overexcitation (24)-Coordinated with AVR Control
Blackout Avoidance
Overexcitation Gen./Trans. Capability
 Generator (IEEE/ANSI C-50.12 &13)
1.05pu V/Hz on Gen. Base
 Transformers (IEEE/ANSI C-57.12 )
1.05pu V/Hz loaded at output
1.10pu V/Hz unloaded
Blackout Avoidance
Figure #4C
Overexcitation Operating Limits
Blackout Avoidance
Typical V/Hz 24 Relay Settings
 Dual Set-point Definite Time
1.18pu V/Hz – 2-6 Sec. Delay
1.10 pu V/Hz – 45-60 Sec. Delay
 Inverse Time Curve
1.10pu V/Hz Pickup with Curve
Selection to Match Gen./Trans
V/Hz Capability Curve
Blackout Avoidance
J X
R
Z2
RPFA
Max.
Torque
Angle
Z1
Generator
Capability
Curve
Z2 Reach at 50 to 67% of
Generator Capability Curve
Z2 Reach 120% of Longest Line but
Must be Less than 80 to 90%
of Capability Curve
System Backup (21 & 51V) – Secure on Stable
Power Swings and System Low Voltage. Must be
Coordinated with Transmission Protection.
Blackout Avoidance
J X
Z2
Z1
Max.
Torque
Angle
Generator
Capability
Curve
Z2 Reach at 50 to 67% of
Generator Capability Curve
Z2 Reach 120% of Longest Line but
Must be Less than 80 to 90%
of Capability Curve
Z3 out of step blocking
Load Encroachment
Blocking
RPFA
R
Z3
Security Enhancements for Generator
Distance Backup Protection
Blackout Avoidance
Generator Voltage Overcurrent (51V)
Backup
 Voltage Controlled Overcurrent Relays
- Voltage control set below emergency system
operating voltage.
- Current pickup set at 30-40% of full load (Xd).
- Time delay set to coordinate with transmission
backup.
 Voltage Restrained Overcurrent Relays
- Current pickup varies proportional to voltage and set
150% of gen. Rating at gen. Rated voltage.
- Time delay set to coordinate with transmission
backup.
Blackout Avoidance
Under Frequency (81) – Coordinated with
System Load Shedding
 Coordinate Under Frequency Tripping of Generator
With North American Electric Reliability Council
(NERC) System Load Shedding Regions – WECC,
ECAR, ERCOT, PJM, Others.
 Hydro Generators not affected by Under Frequency
 Gas Turbines Controls Run Back Mw Output When
Frequency Drops
Blackout Avoidance
Out of Step Protection (78) – Set to trip the
Generator if it Losses Synchronism
Blackout Avoidance
 Undervoltage Condition Not Itself Harmful To
Synchronous Generators – V/Hz is a Low Limit.
 Auxiliary System is Effected By Low Voltage –
Auxiliary Motor Tripping Can Shut Down Gens.
 U.S. Nuclear Plants Have Second Level Voltage
Separation Relays on Auxiliary System.
 Automatic Generator Control (AGC) can Cause
Problems when the Power System Breaks-up into
Islands.
Undervoltage Power Plant Trippings
Brought About By System Var Deficits
Blackout Avoidance
SYSTEM UNDERVOLTAGE
LOAD SHEDDING
(UVLS)
Blackout Avoidance
Utility Undervoltage Load Shedding (UVLS)
 ATTEMPT TO BALANCE MVAR LOAD WITH MVAR
SOURCES BY SHEDDING LOAD.
 TWO TYPES OF UVLS SCHEMES:
Decentralized - Relays Measure Voltage at load to be
shed.
Centralized – Relays Measure Voltage at Key
locations. Voltage transmitted to Central Location and
combined with other System Information. Schemes
Called SPS or Wide Area Protection.
Blackout Avoidance
Status Of Utility Undervoltage Load Shedding
(UVLS)
 NERC
- UVLS Not Mandatory
- Recognized as a Cost-effective Method to Address
Voltage Collapse.
- Allowed Region to Establish Policy
 WECC
- Most Aggressive in UVLS
- Established UVLS Guidelines
Blackout Avoidance
North American Electric Reliability Council
(NERC) Regional Areas
Blackout Avoidance
Decentralized
- Puget Sound
- First Energy
- TXU
UVLS AT Utilities
Centralized
- BC Hydro
- Hydro Quebec
- Entergy
- Public Service of New
Mexico
- PG&E
Blackout Avoidance
Blackout Avoidance
DESIGNING A SECURE
UVLS
SCHEME
Selection of Voltage Relays for UVLS
 Measure all Three Voltage or Positive
Sequence Voltage.
 Use Low Voltage Cutoff.
 Consider Negative Sequence Blocking.
 Start Timer only if Voltage is Within Window.
 Use Relay with High Reset Ratio.
 Digital Voltage Relays are ideal for This
Application.
Blackout Avoidance
Three-Phase UVLS Logic
27
27B
UNDERVOLTAGE
BOCK
47B
NEGATIVE
SEQUENCE
OVERVOLTAGE
BLOCK
Vc 
Va Setpoint #1
Vb Setpoint #1
Setpoint #1
AND
Adjustable
Timer
Undervoltage
Trip
AND
SINGLE PHASE
UNDERVOLTAGE
Va Setpoint #2
Vb Setpoint #2
Vc Setpoint #2
OR x
Setpoint #3V2  x
Blackout Avoidance
Blackout Avoidance
Positive Sequence UVLS Logic
V1 = 1/3 ( Va + aVb +a2Vc)
Where: Va,Vb,Vc are line-to-
neutral voltages
a = 1l120o
a2 = 1l240o
Balanced Conditions:
1V =Va=Vb=Vc.
27
47B
NEGATIVE
SEQUENCE
OVERVOLTAGE
BLOCK
1
V Setpoint #1
Adjustable
Timer
Undervoltage
Trip
AND
POSITIVE
SEQUENCE
UNDERVOLTAGE
Va Setpoint #2
Vb Setpoint #2
VcSetpoint #2
OR x
27B
UNDERVOLTAGE
BOCK
Setpoint#3V2  x
Point of Voltage Measurement
UTILITY TRANSMISSION
SYSTEM
27
81
A C
Trip Selected Circuits
(A-D)
Typical Distribution
Substation Transformer with
LTC
B D
27 = Undervoltage Relay
81= Underfrequency Relay
Blackout Avoidance
UVLS SETTING
CONSIDERATIONS
Blackout Avoidance
UVLS Setting Considerations
 Relay Engineers Must Work Closely With System
Planning Engineers to Design UVLS.
 Planning Engineers Have the Load Flow Data Required
to Determine the Voltage Measurement Locations and
Amount of Load to Shed.
 They also develop the P-V (Nose Curve) that will
determine the Voltage Relay Pickup Setting.
 Time Delay for UVLS are Typically in the 2-10 Sec.
Range – not in Cycles Range for UFLS.
Blackout Avoidance
Undervoltage Relay Pickup
MW LOAD
VOLTAGE
Relay and VT Accuracy Band
Setting Margin
Vcollapse
V setting
Allowable
Operating Area
Operating Margin
Blackout Avoidance
Coordinating UVLS Relay Pickup
Blackout Avoidance
NEW M-3401
BECKWITH LOAD
SHEDDING RELAY
Blackout Avoidance
NEW M-3401 RELAY
Blackout Avoidance
Blackout Avoidance
NEW M-3401 RELAY
M-3401 Protective Functions
 4-Step Phase Undervoltage (27) Protection, single-phase and
positive sequence
Blackout Avoidance
 4-Step Phase Undervoltage, selectable as single phase or
positive sequence responding, with Negative
overvoltage and single phase undervoltage supervision
sequence
 Phase Overvoltage (59) Protection
 Four-Step Over/Under Frequency (81) protection
 Rate of Change of Frequency (81R) protection
 IPSlogicTM takes the contact INPUT status and function status
and generates OUTPUTS by employing (OR, AND, and NOT)
boolean Logic and a timer
Three-Phase UVLS Logic
27
27B
UNDERVOLTAGE
BOCK
47B
NEGATIVE
SEQUENCE
OVERVOLTAGE
BLOCK
Vc 
Va Setpoint #1
Vb Setpoint #1
Setpoint #1
AND
Adjustable
Timer
Undervoltage
Trip
AND
SINGLE PHASE
UNDERVOLTAGE
Va Setpoint #2
Vb Setpoint #2
Vc Setpoint #2
OR x
Setpoint #3V2  x
Blackout Avoidance
V1 = 1/3 ( Va + aVb +a2Vc)
Blackout Avoidance
Positive Sequence UVLS Logic
Where: Va,Vb,Vc are line-to-
neutral voltages
a = 1l120o
a2 = 1l240o
Balanced Conditions:
V1=Va=Vb=Vc.
27
47B
NEGATIVE
SEQUENCE
OVERVOLTAGE
BLOCK
1
V Setpoint #1
Adjustable
Timer
Undervoltage
Trip
AND
POSITIVE
SEQUENCE
UNDERVOLTAGE
Va Setpoint #2
Vb Setpoint #2
VcSetpoint #2
OR x
27B
UNDERVOLTAGE
BOCK
Setpoint#3V2  x
Blackout Avoidance
M-3401 Standard Features
 5 Programmable Outputs, 2 programmable inputs, and 1 self-test
output
 Oscillographic Recording (COMTRADE file format)
 Time-Stamped Sequence of Events (SOE) recording for 32 events
 Metering of Voltage and Frequency
 Ports – one RS-232 port (COM1) on front and one RS-232 and 485
port (COM2) on rear
 Setting Software – M-3812 IPScom® For WindowsTM Communica-
tions Software
 Modbus Protocol
 Relay Voltage Inputs Can Be Directly Connected (no VT required)
for voltages < 480 V ac
 Continuous Self-Diagnostics
CONCLUSIONS
 Voltage Collapse is the Major Cause of Blackouts in US
Power Systems.
 UVLS is a Viable Method of Providing Protection to
Avoid Slow Voltage Collapse Situations.
 UVLS May be too Slow to respond to Rapid Fault
Induced Voltage Collapses.
 UVLS Requires close Cooperation Between Planners
and Relay Engs.
 UVLS Schemes are More Difficult to Design and Set
than UFLS.
Blackout Avoidance
CONCLUSIONS
 Generator Protection Needs to be Made More Secure
During Low Voltage Conditions and be Coordinated with
Generator Controls.
 Methods to do this are Scattered in Various Text Books
and Manufactures Literature.
 My Paper Provides a Single Document with this
Information.
 My Paper Highlights the Important Role the AVR Plays
During Major Disturbances.
Blackout Avoidance
BLACKOUT AVOIDANCE
&
UNDERVOLTAGE LOAD SHEDDING
THE END
Questions ?
Blackout Avoidance
©2008 Beckwith Electric Co., Inc.

More Related Content

What's hot

Machines dc motors
Machines   dc motorsMachines   dc motors
Machines dc motors
sld1950
 
Elect principles 2 ac circuits series resonance
Elect principles 2   ac circuits series resonanceElect principles 2   ac circuits series resonance
Elect principles 2 ac circuits series resonance
sdacey
 
Automatic synch of gen
Automatic synch of genAutomatic synch of gen
Automatic synch of gen
michaeljmack
 
New microsoft word document
New microsoft word documentNew microsoft word document
New microsoft word document
jeevan_raju
 
FAULT Analysis presentation Armstrong
FAULT Analysis presentation ArmstrongFAULT Analysis presentation Armstrong
FAULT Analysis presentation Armstrong
Armstrong Okai Ababio
 

What's hot (20)

Transformer Seminar - Buck-Boost
Transformer Seminar - Buck-BoostTransformer Seminar - Buck-Boost
Transformer Seminar - Buck-Boost
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentals
 
Machines dc motors
Machines   dc motorsMachines   dc motors
Machines dc motors
 
Elect principles 2 ac circuits series resonance
Elect principles 2   ac circuits series resonanceElect principles 2   ac circuits series resonance
Elect principles 2 ac circuits series resonance
 
AC electricity
AC electricityAC electricity
AC electricity
 
Analysis of unsymmetrical faults using bus impedence matrix
Analysis of unsymmetrical faults using bus impedence matrixAnalysis of unsymmetrical faults using bus impedence matrix
Analysis of unsymmetrical faults using bus impedence matrix
 
Automatic synch of gen
Automatic synch of genAutomatic synch of gen
Automatic synch of gen
 
New microsoft word document
New microsoft word documentNew microsoft word document
New microsoft word document
 
Voltage Regulation
Voltage RegulationVoltage Regulation
Voltage Regulation
 
TRANSIENT IN POWER SYSTEM
TRANSIENT IN POWER SYSTEMTRANSIENT IN POWER SYSTEM
TRANSIENT IN POWER SYSTEM
 
Fault Calculations
Fault CalculationsFault Calculations
Fault Calculations
 
Motor & generator protection example settings
Motor & generator protection example settingsMotor & generator protection example settings
Motor & generator protection example settings
 
ECNG 3015 Industrial and Commercial Electrical Systems
ECNG 3015   Industrial and Commercial Electrical SystemsECNG 3015   Industrial and Commercial Electrical Systems
ECNG 3015 Industrial and Commercial Electrical Systems
 
Power system fault analysis ppt
Power system fault analysis pptPower system fault analysis ppt
Power system fault analysis ppt
 
Three phase balanced load circuits and synchronous generators
Three phase balanced load circuits and synchronous generatorsThree phase balanced load circuits and synchronous generators
Three phase balanced load circuits and synchronous generators
 
FAULT Analysis presentation Armstrong
FAULT Analysis presentation ArmstrongFAULT Analysis presentation Armstrong
FAULT Analysis presentation Armstrong
 
Transmission line zero seq reactance
Transmission line zero seq reactanceTransmission line zero seq reactance
Transmission line zero seq reactance
 
Output power meter
Output power meterOutput power meter
Output power meter
 
dc to dc-converter
dc to dc-converterdc to dc-converter
dc to dc-converter
 
Mag ch of dc shunt generator
Mag ch of dc shunt generatorMag ch of dc shunt generator
Mag ch of dc shunt generator
 

Similar to Blackout avoidance & under voltage loadshedding

Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Shedding
michaeljmack
 
New Microsoft Word Document
New Microsoft Word DocumentNew Microsoft Word Document
New Microsoft Word Document
Barunava Sikdar
 
INDUSTRIAL TRAINING REPORT.pptx
INDUSTRIAL TRAINING REPORT.pptxINDUSTRIAL TRAINING REPORT.pptx
INDUSTRIAL TRAINING REPORT.pptx
SanatKumar66
 

Similar to Blackout avoidance & under voltage loadshedding (20)

Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Shedding
 
Short circuit test in brief
Short circuit test in briefShort circuit test in brief
Short circuit test in brief
 
97
9797
97
 
Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear
 
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
 
protection against overvoltages in power system
protection against overvoltages in power systemprotection against overvoltages in power system
protection against overvoltages in power system
 
HVE.ppt
HVE.pptHVE.ppt
HVE.ppt
 
lightning.ppt
lightning.pptlightning.ppt
lightning.ppt
 
EMEC-II, unit 1
EMEC-II, unit 1EMEC-II, unit 1
EMEC-II, unit 1
 
High Voltage Engineering- OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS
High Voltage Engineering- OVER VOLTAGES IN ELECTRICAL POWER SYSTEMSHigh Voltage Engineering- OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS
High Voltage Engineering- OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS
 
New Microsoft Word Document
New Microsoft Word DocumentNew Microsoft Word Document
New Microsoft Word Document
 
INDUSTRIAL TRAINING REPORT.pptx
INDUSTRIAL TRAINING REPORT.pptxINDUSTRIAL TRAINING REPORT.pptx
INDUSTRIAL TRAINING REPORT.pptx
 
project report on plc based load sharing
project report on plc based load sharingproject report on plc based load sharing
project report on plc based load sharing
 
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarGenerator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkar
 
Voltage magnitude variation and stability
Voltage magnitude variation and stabilityVoltage magnitude variation and stability
Voltage magnitude variation and stability
 
Lecture no 1 switchgears bt255 converted
Lecture no 1 switchgears bt255 convertedLecture no 1 switchgears bt255 converted
Lecture no 1 switchgears bt255 converted
 
Lecture1
Lecture1Lecture1
Lecture1
 
Power system Analysis By Sharif Kakar
Power system Analysis   By Sharif KakarPower system Analysis   By Sharif Kakar
Power system Analysis By Sharif Kakar
 
vol_stability_slides.ppt
vol_stability_slides.pptvol_stability_slides.ppt
vol_stability_slides.ppt
 
post_glover_resistance_grounding_2012.ppt
post_glover_resistance_grounding_2012.pptpost_glover_resistance_grounding_2012.ppt
post_glover_resistance_grounding_2012.ppt
 

More from Power System Operation

SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action Scheme
Power System Operation
 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
Power System Operation
 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
Power System Operation
 

More from Power System Operation (20)

ENERGY TRANSITION OUTLOOK 2021
ENERGY TRANSITION OUTLOOK  2021ENERGY TRANSITION OUTLOOK  2021
ENERGY TRANSITION OUTLOOK 2021
 
Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panels
 
What does peak shaving mean
What does peak shaving meanWhat does peak shaving mean
What does peak shaving mean
 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
 
Power System Restoration Guide
Power System Restoration Guide  Power System Restoration Guide
Power System Restoration Guide
 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid Operations
 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action Scheme
 
Substation Neutral Earthing
Substation Neutral EarthingSubstation Neutral Earthing
Substation Neutral Earthing
 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground Resistance
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & Parts
 
What is load management
What is load managementWhat is load management
What is load management
 
What does merit order mean
What does merit order meanWhat does merit order mean
What does merit order mean
 
What are Balancing Services ?
What are  Balancing Services ?What are  Balancing Services ?
What are Balancing Services ?
 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
 
Power Purchase Agreement PPA
Power Purchase Agreement PPA Power Purchase Agreement PPA
Power Purchase Agreement PPA
 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
 

Recently uploaded

Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 

Recently uploaded (20)

Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 

Blackout avoidance & under voltage loadshedding

  • 2. BLACKOUTS  How and why they occur  Why voltage rather than frequency is the leading edge indicator of system collapse  How blackout conditions effect generators and generator protection  Undervoltage load shedding Blackout Avoidance
  • 3. RECENT BLACKOUTS 2003 - East Coast Blackout 2003 - Italian Blackout 2002 - Swedish Blackout 1997 - PJM Disturbance 1996 - West Coast Blackout 1995 - PECO Disturbance 1987 - City of Memphis Blackout Avoidance
  • 4. Root Cause of Recent Blackouts VOLTAGE COLLAPSE – WHY?  Today, major generation sources are remote from load centers. This was NOT the case 35 years ago.  This makes the power system very reliant on transmission system to transport power to load centers. Blackout Avoidance
  • 5. Root Cause of Recent Blackouts VOLTAGE COLLAPSE – WHY?  Purchase power from remote sources to save $$$.  New generation built remotely from load centers.  Little new transmission being built.  Utility loads are increasingly made up of air conditioning motors susceptible to stall conditions due to transmission system faults. Blackout Avoidance
  • 6.  As lines trip between remote generation and load center, the reactance increases.  This increases the reactive (VAR) losses-reducing the voltage at the load center.  The voltage phase angle between the generators at the load center and remote generators also increase. REM OTE GENERATION LOCAL LOAD CENTER LINE 1 LINE 2 LINE 3 LINE 4 LINE 5 LINE 6 How Voltage Collapses Occur Blackout Avoidance
  • 8. Real Power (MW) Flow Example SYSTEM A SYSTEM B SYSTEM C Eg O Es O POWER FLOW Blackout Avoidance Pe = Eg Es Sin ( 0g- 0s ) X Where: Eg = Voltage at the Load Center Generation Es = Voltage at the Remote Generation Pe = Electrical Real Power Transfer X = Reactance Between Local and Remote Generation 0g = Votage Angle and Local Generation 0s = Voltage Angle at Remote Generation POWER TRANSFER EQUATION Where: Es = Voltage at the Load Center Eg = Voltage at the Remote Generation Pe = Electrical Real Power Transfer X = Reactance Between Local and Remote Generation 0s = Voltage Angle and Local Generation 0g = Voltage Angle at Remote Generation
  • 9. Pe = Eg Es Sin ( 0g- 0s ) X Where: Eg = Voltage at the Load Center Generation Es = Voltage at the Remote Generation Pe = Electrical Real Power Transfer X = Reactance Between Local and Remote Generation 0g = Voltage Angle and Local Generation 0s = Voltage Angle at Remote Generation POWER TRANSFER EQUATION SYSTEM A Load = 5000MW GEN. =5000 MW SYSTEM B Load = 5000MW Gen. = 5000MW SYSTEM C Load = 5000MW Gen. = 5000MW Eg O Es O POWER FLOW - 0MW TRANSFER Real Power (MW) Flow Example Blackout Avoidance Where: Es = Voltage at the Load Center Eg = Voltage at the Remote Generation Pe = Electrical Real Power Transfer X = Reactance Between Local and Remote Generation 0s = Voltage Angle and Local Generation 0g = Voltage Angle at Remote Generation
  • 10. Where: Eg = Voltage at the Load Center Generation Es = Voltage at the Remote Generation Pe = Electrical Real Power Transfer X = Reactance Between Local and Remote Generation 0g = Voltage Angle and Local Generation 0s = Voltage Angle at Remote Generation POWER TRANSFER EQUATION Pe = Eg Es Sin ( 0g- 0s ) X Real Power (MW) Flow Example SYSTEM A Load = 5000 MW GEN. = 7000 MW SYSTEM B Load = 5000 MW Gen. = 5000 MW SYSTEM C Load = 5000 MW Gen. = 3000 MW Eg O Es O POWER FLOW - 2000 MW TRANSFER Blackout Avoidance Where: Es = Voltage at the Load Center Eg = Voltage at the Remote Generation Pe = Electrical Real Power Transfer X = Reactance Between Local and Remote Generation 0s = Voltage Angle and Local Generation 0g = Voltage Angle at Remote Generation
  • 11. SYSTEM A SYSTEM B SYSTEM C Eg O Es O REACTIVE POWER FLOWSMALL 1. T o m a k e reactive p o w e r f l o w y o u n e e d to h a v e a d i f f e r e n ce in v o l t a g e m a g n i t u d e b e t w e e n E g a n d E s . 2. V o l t a g e o n a p o w e r s y s t e m c a n o n l y b e va r i e d +/- 5 % w h i c h is n o t e n o u g h d i f f e r e n ce to result in a significant V A R S flow . 3. T h u s V A R S c a n n o t b e t r a n s m i t t e d o v e r l o n g d i s t a n c e s a n d m u s t b e g e n e r a t e d locally n e a r t h e l o a d . Reactive Power (Mvars) Flow Blackout Avoidance
  • 12. Sources of Reactive (Var) Support  VAr Support must be provided at the load center.  Two major sources of VAr support: Capacitor Banks – Double-Edge Sword. Vars go down with the square of voltage. Generators/ Synch. Condensers – A dynamic source of Vars. Can adjust VAr output rapidly during contingencies. Blackout Avoidance
  • 14. How Load Responds to Low Voltage Basic Power System Remote Generation TransmissionSystem LoadCenter Resistive Load Motor Load VAR Support Local Generation Ps PL QLVL Blackout Avoidance
  • 15. How Load Responds to Low Voltage  Resistive load current decreases as voltage goes down Helping the system.  Motor loads are constant KVA devices and increase their load current as voltage decreases- Hurts the system.  During “Heat Storm” conditions, most load is motor load making blackout more likely. Blackout Avoidance
  • 16. Example of Voltage Recovery From a Transmission Fault- Rapid Voltage Collapse R e sid e ntia l V o ltag e R e cove ry fo r P hoe n ix A rea In cide nt on July 2 9 , 19 95 Blackout Avoidance
  • 17. RECENT BLACKOUTS REVISITED 2003 - East Coast Blackout 2003 - Italian Blackout 2002 - Swedish Blackout 1997 - PJM Disturbance* 1996 - West Coast Blackout 1995 - PECO Disturbance* 1987 - City of Memphis* * Rapid Voltage Collapse Blackout Avoidance
  • 19. POWER SYSTEM INSTABILITIES Four Types of Instability:  Voltage*  Steady State *  Transient  Dynamic *Involved in Recent Blackouts Blackout Avoidance
  • 20. REMOTE GENERATION LOCAL LOAD CENTER LINE 1 LINE 2 LINE 3 LINE 4 LINE 5 LINE 6 Eg O Es O POWER FLOW Voltage Collapse Scenario Blackout Avoidance
  • 21. REMOTE GENERATION LOCAL LOAD CENTER LINE 1 LINE 2 LINE 3 LINE 4 LINE 5 LINE 6 Eg O Es O POWER FLOW Voltage Collapse Scenario Blackout Avoidance
  • 22. Pmax = Eg Es Max. X Power All Lines in Service Transfer Line 1 Tripped Pe Line 2 Tripped 0 90o 1800 0g - 0s Pmax = Eg Es Max. X Power All Lines in Service Transfer Line 1 Tripped Pe Line 2 Tripped 0 90o 1800 0g - 0s Pe = Eg Es Sin ( 0g- 0s ) X POWER TRANSFER EQUATION Eg Og Es Os POWER FLOW REMOTE GENERATION LOCAL LOAD CENTER LINE 1 LINE 2 LINE 3 LINE 4 LINE 5 LINE 6 0 1800 Max. Power Transfer All Lines in Service Line 1 Tripped Line 2 Tripped Pe Pmax = Eg Es X 90o 0g - 0s Steady State Instability Blackout Avoidance
  • 23. Generator G GSU System Reactance V Xd XT XS V2 __ 1____ + 1 2 XT + XS Xd Per Unit MW Per Unit MVAR ___1___ 1V2 2 XT + XS Xd a) MW - MVAR PER UNIT PLOT X R Xd + XT + XS 2 XT + XS Xd - XT + XS 2 Xd b) R-X DIAGRAM PLOT Steady State Instability Blackout Avoidance
  • 25. Gen. AVR Excitation Transformer CT VTField Static Exciter Generator Excitation & AVR Control Generator Step-up Transformer Generator Blackout Avoidance
  • 26. Reactive Power into System Reactive Power into Generator Real Power into System + MVAR Overexcited Underexcited 0 - MVAR Under Excitation Limiter (URL) + MW MW G MVARS Overexcitation Limiter (OEL) Winding Limited Stator Winding Limited Stator End Iron Limited MW G MVAR System Normal Overexcited Operation Underexcited Operation System How Generators Provide Vars to the System  The Generator AVR (Automatic Voltage Regulator) Controls Field Current into the Rotor Which in Turn Controls Terminal Voltage and VAr Output/Input. Rotor Blackout Avoidance
  • 27. AVR Limiters Response During Low Voltage DEPENDS ON THE MANUFACTURER:  Some Limiters Change as the Square of the Voltage – 90% Voltage Results in 81% of Setting  Some Proportional to Voltage – 90% Voltage result in 90% Setting  Some Do Not Change with Voltage at all Blackout Avoidance
  • 28. 0 1800 Max. Power Transfer All Lines in Service Breakers 1 and 2 Tripped PM = Pe Pmax = Eg Es X 90o 0g - 0s A2 0C A1 Transient Instability Blackout Avoidance
  • 29. Typical Out-of-Step Impedance LOCI Blackout Avoidance
  • 30.  Required by WECC in the Western USA for generators larger than 30 MVA Dynamic Instability  Occurs when fast acting AVR control amplifies rather than damps small MW oscillations.  Occurs when generators are remote from load  Solution is AVR Power System Stabilizers (PSS) – Low Freq. Filter Blackout Avoidance
  • 31. GENERATOR PROTECTION RESPOND TO BLACKOUT CONDITIONS Blackout Avoidance
  • 32. Key Generator Protection Functions Effected by Major System Disturbances  Loss of Field (40)  Overexcitation (24)  Overexcitation (24) System Backup (21 & 51V)  Under Frequency (81)  Out of Step Protection (78) Blackout Avoidance
  • 33. Generator Protection Effected by Major System Disturbances  Loss of Field (40) – Must be Coordinated with AVR Control, Steady State Stability Limit and Secure Under Low Voltage.  Overexcitation (24) - Coordinated with AVR Control.  System Backup (21 & 51V) – Secure on Stable Power Swings and System Low Voltage. Must be Coordinated with Transmission Protection. Blackout Avoidance
  • 34. Generator Protection Effected by Major System Disturbances  Under Frequency (81) – Coordinated with System Load Shedding.  Out of Step Protection (78) – Set to trip the Generator if it Losses Synchronism. Blackout Avoidance
  • 35. -X +R-R - Xd’ 2 Xd Generator Capability Under Excitation Limiter (UEL) Heavy Load Light Load Impedance Locus During Loss of Field 1.0 pu Steady State Stability Limit Zone 1 Zone 2 Loss of Field (40) – Must be Coordinated with AVR Control, Steady State Stability Limit and Secure Under Low Voltage. +X Blackout Avoidance
  • 36. Transformation From Mw-Mvar to R-X Plot Blackout Avoidance
  • 37. G Reactive Power into System Reactive Power into Generator Real Power into System + MVAR Overexcited Underexcited 0 - MVAR Under Excitation Limiter (URL) + MW MW G MVARS Overexcitation Limiter (OEL) Rotor Winding Limited Stator Winding Limited Stator End Iron Limited Steady State Stability Limit MW MVAR System Normal Overexcited Operation Underexcited Operation System Overexcitation (24)-Coordinated with AVR Control Blackout Avoidance
  • 38. Overexcitation Gen./Trans. Capability  Generator (IEEE/ANSI C-50.12 &13) 1.05pu V/Hz on Gen. Base  Transformers (IEEE/ANSI C-57.12 ) 1.05pu V/Hz loaded at output 1.10pu V/Hz unloaded Blackout Avoidance
  • 39. Figure #4C Overexcitation Operating Limits Blackout Avoidance
  • 40. Typical V/Hz 24 Relay Settings  Dual Set-point Definite Time 1.18pu V/Hz – 2-6 Sec. Delay 1.10 pu V/Hz – 45-60 Sec. Delay  Inverse Time Curve 1.10pu V/Hz Pickup with Curve Selection to Match Gen./Trans V/Hz Capability Curve Blackout Avoidance
  • 41. J X R Z2 RPFA Max. Torque Angle Z1 Generator Capability Curve Z2 Reach at 50 to 67% of Generator Capability Curve Z2 Reach 120% of Longest Line but Must be Less than 80 to 90% of Capability Curve System Backup (21 & 51V) – Secure on Stable Power Swings and System Low Voltage. Must be Coordinated with Transmission Protection. Blackout Avoidance
  • 42. J X Z2 Z1 Max. Torque Angle Generator Capability Curve Z2 Reach at 50 to 67% of Generator Capability Curve Z2 Reach 120% of Longest Line but Must be Less than 80 to 90% of Capability Curve Z3 out of step blocking Load Encroachment Blocking RPFA R Z3 Security Enhancements for Generator Distance Backup Protection Blackout Avoidance
  • 43. Generator Voltage Overcurrent (51V) Backup  Voltage Controlled Overcurrent Relays - Voltage control set below emergency system operating voltage. - Current pickup set at 30-40% of full load (Xd). - Time delay set to coordinate with transmission backup.  Voltage Restrained Overcurrent Relays - Current pickup varies proportional to voltage and set 150% of gen. Rating at gen. Rated voltage. - Time delay set to coordinate with transmission backup. Blackout Avoidance
  • 44. Under Frequency (81) – Coordinated with System Load Shedding  Coordinate Under Frequency Tripping of Generator With North American Electric Reliability Council (NERC) System Load Shedding Regions – WECC, ECAR, ERCOT, PJM, Others.  Hydro Generators not affected by Under Frequency  Gas Turbines Controls Run Back Mw Output When Frequency Drops Blackout Avoidance
  • 45. Out of Step Protection (78) – Set to trip the Generator if it Losses Synchronism Blackout Avoidance
  • 46.  Undervoltage Condition Not Itself Harmful To Synchronous Generators – V/Hz is a Low Limit.  Auxiliary System is Effected By Low Voltage – Auxiliary Motor Tripping Can Shut Down Gens.  U.S. Nuclear Plants Have Second Level Voltage Separation Relays on Auxiliary System.  Automatic Generator Control (AGC) can Cause Problems when the Power System Breaks-up into Islands. Undervoltage Power Plant Trippings Brought About By System Var Deficits Blackout Avoidance
  • 48. Utility Undervoltage Load Shedding (UVLS)  ATTEMPT TO BALANCE MVAR LOAD WITH MVAR SOURCES BY SHEDDING LOAD.  TWO TYPES OF UVLS SCHEMES: Decentralized - Relays Measure Voltage at load to be shed. Centralized – Relays Measure Voltage at Key locations. Voltage transmitted to Central Location and combined with other System Information. Schemes Called SPS or Wide Area Protection. Blackout Avoidance
  • 49. Status Of Utility Undervoltage Load Shedding (UVLS)  NERC - UVLS Not Mandatory - Recognized as a Cost-effective Method to Address Voltage Collapse. - Allowed Region to Establish Policy  WECC - Most Aggressive in UVLS - Established UVLS Guidelines Blackout Avoidance
  • 50. North American Electric Reliability Council (NERC) Regional Areas Blackout Avoidance
  • 51. Decentralized - Puget Sound - First Energy - TXU UVLS AT Utilities Centralized - BC Hydro - Hydro Quebec - Entergy - Public Service of New Mexico - PG&E Blackout Avoidance
  • 52. Blackout Avoidance DESIGNING A SECURE UVLS SCHEME
  • 53. Selection of Voltage Relays for UVLS  Measure all Three Voltage or Positive Sequence Voltage.  Use Low Voltage Cutoff.  Consider Negative Sequence Blocking.  Start Timer only if Voltage is Within Window.  Use Relay with High Reset Ratio.  Digital Voltage Relays are ideal for This Application. Blackout Avoidance
  • 54. Three-Phase UVLS Logic 27 27B UNDERVOLTAGE BOCK 47B NEGATIVE SEQUENCE OVERVOLTAGE BLOCK Vc  Va Setpoint #1 Vb Setpoint #1 Setpoint #1 AND Adjustable Timer Undervoltage Trip AND SINGLE PHASE UNDERVOLTAGE Va Setpoint #2 Vb Setpoint #2 Vc Setpoint #2 OR x Setpoint #3V2  x Blackout Avoidance
  • 55. Blackout Avoidance Positive Sequence UVLS Logic V1 = 1/3 ( Va + aVb +a2Vc) Where: Va,Vb,Vc are line-to- neutral voltages a = 1l120o a2 = 1l240o Balanced Conditions: 1V =Va=Vb=Vc. 27 47B NEGATIVE SEQUENCE OVERVOLTAGE BLOCK 1 V Setpoint #1 Adjustable Timer Undervoltage Trip AND POSITIVE SEQUENCE UNDERVOLTAGE Va Setpoint #2 Vb Setpoint #2 VcSetpoint #2 OR x 27B UNDERVOLTAGE BOCK Setpoint#3V2  x
  • 56. Point of Voltage Measurement UTILITY TRANSMISSION SYSTEM 27 81 A C Trip Selected Circuits (A-D) Typical Distribution Substation Transformer with LTC B D 27 = Undervoltage Relay 81= Underfrequency Relay Blackout Avoidance
  • 58. UVLS Setting Considerations  Relay Engineers Must Work Closely With System Planning Engineers to Design UVLS.  Planning Engineers Have the Load Flow Data Required to Determine the Voltage Measurement Locations and Amount of Load to Shed.  They also develop the P-V (Nose Curve) that will determine the Voltage Relay Pickup Setting.  Time Delay for UVLS are Typically in the 2-10 Sec. Range – not in Cycles Range for UFLS. Blackout Avoidance
  • 59. Undervoltage Relay Pickup MW LOAD VOLTAGE Relay and VT Accuracy Band Setting Margin Vcollapse V setting Allowable Operating Area Operating Margin Blackout Avoidance
  • 60. Coordinating UVLS Relay Pickup Blackout Avoidance
  • 61. NEW M-3401 BECKWITH LOAD SHEDDING RELAY Blackout Avoidance
  • 64. M-3401 Protective Functions  4-Step Phase Undervoltage (27) Protection, single-phase and positive sequence Blackout Avoidance  4-Step Phase Undervoltage, selectable as single phase or positive sequence responding, with Negative overvoltage and single phase undervoltage supervision sequence  Phase Overvoltage (59) Protection  Four-Step Over/Under Frequency (81) protection  Rate of Change of Frequency (81R) protection  IPSlogicTM takes the contact INPUT status and function status and generates OUTPUTS by employing (OR, AND, and NOT) boolean Logic and a timer
  • 65. Three-Phase UVLS Logic 27 27B UNDERVOLTAGE BOCK 47B NEGATIVE SEQUENCE OVERVOLTAGE BLOCK Vc  Va Setpoint #1 Vb Setpoint #1 Setpoint #1 AND Adjustable Timer Undervoltage Trip AND SINGLE PHASE UNDERVOLTAGE Va Setpoint #2 Vb Setpoint #2 Vc Setpoint #2 OR x Setpoint #3V2  x Blackout Avoidance
  • 66. V1 = 1/3 ( Va + aVb +a2Vc) Blackout Avoidance Positive Sequence UVLS Logic Where: Va,Vb,Vc are line-to- neutral voltages a = 1l120o a2 = 1l240o Balanced Conditions: V1=Va=Vb=Vc. 27 47B NEGATIVE SEQUENCE OVERVOLTAGE BLOCK 1 V Setpoint #1 Adjustable Timer Undervoltage Trip AND POSITIVE SEQUENCE UNDERVOLTAGE Va Setpoint #2 Vb Setpoint #2 VcSetpoint #2 OR x 27B UNDERVOLTAGE BOCK Setpoint#3V2  x
  • 67. Blackout Avoidance M-3401 Standard Features  5 Programmable Outputs, 2 programmable inputs, and 1 self-test output  Oscillographic Recording (COMTRADE file format)  Time-Stamped Sequence of Events (SOE) recording for 32 events  Metering of Voltage and Frequency  Ports – one RS-232 port (COM1) on front and one RS-232 and 485 port (COM2) on rear  Setting Software – M-3812 IPScom® For WindowsTM Communica- tions Software  Modbus Protocol  Relay Voltage Inputs Can Be Directly Connected (no VT required) for voltages < 480 V ac  Continuous Self-Diagnostics
  • 68. CONCLUSIONS  Voltage Collapse is the Major Cause of Blackouts in US Power Systems.  UVLS is a Viable Method of Providing Protection to Avoid Slow Voltage Collapse Situations.  UVLS May be too Slow to respond to Rapid Fault Induced Voltage Collapses.  UVLS Requires close Cooperation Between Planners and Relay Engs.  UVLS Schemes are More Difficult to Design and Set than UFLS. Blackout Avoidance
  • 69. CONCLUSIONS  Generator Protection Needs to be Made More Secure During Low Voltage Conditions and be Coordinated with Generator Controls.  Methods to do this are Scattered in Various Text Books and Manufactures Literature.  My Paper Provides a Single Document with this Information.  My Paper Highlights the Important Role the AVR Plays During Major Disturbances. Blackout Avoidance
  • 70. BLACKOUT AVOIDANCE & UNDERVOLTAGE LOAD SHEDDING THE END Questions ? Blackout Avoidance ©2008 Beckwith Electric Co., Inc.