SlideShare a Scribd company logo
Axios Bridge – Section Athens to Thessaloniki
Dr. Chris A Rodopoulos, Dr. P. Panetsos and Mr. I. Koropoulis
Application of galvanic cathodic protection using Zink Sheet Anodes according to ΕΝ 12696
Axios bridge consists of two sections. The section Athens to Thessaloniki was given to traffic in
1973. The section Thessaloniki to Athens was inaugurated in 1988. The bridge is part of E75
motorway.
Axios Bridge – Historical Data
Axios Bridge – Historical Data
The bridge is made of 29 spans of 30 m each resulting in overall length of 870m. Due to river
crossing the bridge is founded on R/C piles.
Axios Bridge – Historical Data
The superstructure is made of longitudinal and transverse prestressed beams.
Axios Bridge – Historical Data
Prestressed cross beam detailing
Axios Bridge – Historical Data
Typical reinforcement detailing. Concrete has been classified as C30/37 after coring.
Axios Bridge – Historical Data
A CuSO4 reference electrode has been used. All values in mV.
Measurements and Pathology – Half Cell Measurements of External Beam
Measurements and Pathology – Half Cell Measurements of External Beam
– Projection of values on beam
The high negative values at area A indicate waterproofing failure of the expansion joint. The high
corrosion propensity at areas B and C, indicate potential local failure of the deck waterproofing
layer.
Area Α
Area Β Area C
Measurements and Pathology – Half Cell Measurements of External Beam
– Projection of values on tendon tracks
Note that the anchors of tendons 3-8, exhibit high corrosion potential. Similar problem is
identified at the location of tendons 9, 11 and 12.
Measurements and Pathology – Concrete Electrical Resistivity Measurements
All values in KOhm cm.
Measurements and Pathology – Concrete Electrical Resistivity Measurements– Projection of
values on beam
Electrical resistivity is an indirect way of evaluating concrete’s build in moisture and hence the
susceptibility to ionic current movement (controls the cathodic / oxygen reaction). To
acknowledge the importance of the measurements, it is worth noting that the electrical
resistivity of C30/37 concrete, having build in (hygroscopic) moisture of 2% w. t., is around 70
KOhm cm.
Measurements and Pathology– Linear Polarisation Measurements (LPR)
All values in μΑ/cm2. The measured values classified corrosion belonging into the low to
medium rate according to the above Table. Certain areas in purple are classified as passive.
Measurements and Pathology– Linear Polarisation Measurements (LPR) – Projection of values
on beam
It is important to consider that low values of corrosion current density are most likely to
increase with time compared to high values which are bounded by the nature of concrete’s
pathology. It is also worth noting that values above 0.5 μΑ/cm2 can lead to complete loss of
bond strength within 2-10 years.
Measurements and Pathology– Linear Polarisation Measurements (LPR) – Projection of values
on tendon tracks
Projection of the measured values over the design and especially over tendon tracks is perhaps
the most crucial action when evaluating corrosion in prestressed elements. The generated
image help us identify critical locations while at the same time provides information regarding
potential causes. Herein, we can easily identify that tendons No. 8, 9, 11, 12, are within the area
demonstrating the highest corrosion rate of the sample. It is important to note that the
transverse beam is also critically corroding. The surface tendon 11 appears to experience
significant corrosion rate due to overhead failure of waterproofing.
Measurements and Pathology – Concrete Pathology
Axios Bridge is located in a semi-urban environment experiencing high humidity due to river. The distance
from the sea is over 5 Km and therefore the potential of airborne chlorides diffusing into concrete is
considered as negligible. The bridge is rarely subjected to de-icing salts. Even though vehicular traffic is
substantial, the location experiences CO2 concentration below 300 ppm. In conjunction with the high
humidity of the area, concrete experiences a rather low carbonation rate.
The bridge is suffering from poor storm water drainage, non sealed expansion joints and damaged deck
waterproofing layer.
Accessibility is the most crucial issue in the assessment of concrete's pathology in large structures and
especially prestressed bridges. Herein, it is imperative to collect samples from locations, a) being critical to
the load bearing capacity, b) being indicative to the actual problem both in terms of chemistry and
concentration and c) providing a sound basis for damage classification. The later, is mostly governed by
sample population and the type of pathology being initially identified. The level of carbonation and chloride
attack, coming from airborne chlorides, is perhaps the easiest of all since they rarely demonstrate significant
position variations.
Tendon anchors and tendons are critical items which require particular attention. Surface tendons are
notoriously difficult to locate and approach even though is widely known of being liable to corrosion.
Similarly, tendon anchors in old bridges are usually located in tight spaces with poor access.
Due to accessibility issues, samples were collected from areas being close to the expansion joints and
experiencing spalling. Indicative results are shown in the Table below.
Samples Concentration of Total Chlorides
Cement (% w.t) - ASTM C1152
Concrete Alkalinity
Sample 1 0.19 8.2
Sample 2 0.25 6.9
Sample 3 0.27 7.7
Sample 4 0.21 7.8
Sample 5 0.27 7.6
According to EN 8110, a total chloride concentration of 0.1% is considered as threshold value for
critical corrosion in prestressed elements. The above limit however refers to concrete alkalinity,
pH, being >11. In the samples, concrete alkalinity has dropped as low as 7.6 indicating that
critical chloride levels are several orders below 0.1%. In addition, alkalinity values are significant
below the lower limit value indicating carbonation, i.e. pH=8.4. The phenomenon of low
alkalinity is attributed to water soluble chemicals from tyre wear, brake wear particle emission,
and exhaust discharges (traffic dust).
Measurements and Pathology – Concrete Pathology
All samples have been collected at depth equal to concrete cover thickness (30mm).
Traffic dust’s most common chemicals and their typical concentration
Measurements and Pathology – Concrete Pathology
Most of these chemical are known to disintegrate both concrete and steel (ACI 515.1R).
Measurements and Pathology – Concrete Pathology
Axios Bridge experiences the simultaneous effect of chlorides due to de-icing salts along with chemical
attack due to traffic dust. Both, in their soluble form shall be considered as the main cause of corrosion.
Herein, once again accessibility is vital in order to collect samples that can be analysed in order to provide
secure information regarding concentration of the hazardous chemicals and their reactions with cement
constituents. Indirectly we can overcome the problem by comparing our LPR measurements with the limits
of certain exposure conditions as depicted in the Table below.
Exposure Class per EN 206-1 LPR Values ( μΑ/cm2)
Average Standard Deviation
XC1 0 -
XC2 0.35 0.26
XC3 0.17 0.08
XC4 0.43 0.26
XD1 0.35 0.26
XD2 2.60 1.70
XS1 2.60 1.70
XS2 - -
XS3 6.00 3.50
Axios bridge belongs into classes XD2 and XD3 (de-icing salts). The reader can easily compared the
previously reported values and acknowledge their deviation form the above limits. Such difference indicates
the supplementary effect provide by traffic dust residues.
Basic Principles of Galvanic Protection
Corrosion is based on two reactions
1st Half Cell Reaction Anodic reaction – Oxidation of iron, Iron is oxidized from Fe (oxidation state
0) to Fe 2+ (oxidation state +2).
2nd Half Cell Reaction Cathodic reaction– Reduction of oxygen, the liberated electrons from the
oxidation of iron are consumed by oxygen in the presence of water to form hydroxyl (OH−).
In this reaction oxygen is electrochemically reduced from O2 (oxidation state 0) to OH− (oxidation
state −2).
Basic Principles of Galvanic Protection
If there is no external electric source of electrons, the anodic reaction must generate electrons
at exactly the same rate as the cathodic reaction consumes them.
If electrons were withdrawn from the metal surface, it might be anticipated that the anodic
reaction would speed up (to replace the lost electrons) and the cathodic reaction would slow
down, because of the existing shortfall of electrons. It follows that the rate of metal
consumption would increase.
If however additional electrons were introduced at the metal surface, the cathodic reaction
would speed up (to consume the electrons) and the anodic reaction would be inhibited; metal
dissolution would be slowed down.
Basic Principles of Galvanic Protection
Inhibiting corrosion via external source of electrons is the basic principle of cathodic protection.
In the case of electrons being provide by an electric source, cathodic protection refers to
Induced Current Cathodic Protection (ICCP). If the source of electrons is provided by a sacrificial
metal, being more electronegative, cathodic protection refers to Galvanic Cathodic Protection.
This fundamental principle can be appreciated via the Poubraix diagram for Iron.
The grey area in the diagram on the left
encapsulates the limits of cathodic
protection.
Basic Principles of Galvanic Protection
Schematically, the excess electrons provide by galvanic cathodic protection (leading to corrosion
inhibition) is shown below.
Basic Principles of Galvanic Protection
The availability and the potential of metals able to provide excess electrons is governed by the
Standard Reduction Potential Table. We can easily identify that, Zn, Al and Li are more
electronegative than Fe and therefore can provide excess electrons.
Since the excess electrons are generated by the corrosion of the more electronegative metal,
the term sacrificial metal is widely used.
Basic Principles of Galvanic Protection
In Galvanic Cathodic Protection, the potential difference alone is not enough as to proceed with the
selection of the anode metal. Generated anode (sacrificial metal) current density and electrochemical
capacity (Amp-h/Kg) are also important parameters .
The “Potential volts” refer also referred as polarisation potential. For steel in concrete, a polarized
potential more negative than –800 mV measured with respect to silver/silver chloride reference electrode is
required by EN 12696. The reader shall not confused potential values given by different reference
electrodes. In this case, the -1100 mV of the Cu/CuSO4 are equal to -1044 mV of Ag/AgCl 0.05M KCl.
Simplistically, electrochemical capacity is the result of Faraday's law. For example, pure zinc has a theoretical
maximum capacity of 820 Ah per kilogram. This means that if a zinc anode were to discharge one ampere
continuously, one kilogram would be consumed in 820 hours. If this kilogram was discharging one tenth of
an ampere, it would be totally consumed in 8200 hours or 48 weeks. Actually, zinc anodes operate, typically,
at about 95 % efficiency. This means that the energy content available for useful current output would be
820 x 0.95, or 779 Ah per kg.
Basic Principles of Galvanic Protection
Cathodic protection current density is currently defined by regulation. Even though differences can be easily
identified, the minimum requirements remain approximately fixed.
Basic Principles of Galvanic Protection
Variations in the range of cathodic protection current density are mostly acknowledged by the diagram
below.
Here the reader can study, different cathodic protection current density requirements as per chloride ions
concentration in concrete. SCE refers to Saturated Calomel Electrode.
Basic Principles of Galvanic Protection
Variations in cathodic protection current densities throughout the years have been classified in order to
provide a sound basis over which repair cost can be realistically estimated.
Current density requirements along with the surface area of steel to be protected (demand), define among
others parameters, whether ICCP or galvanic protection is to be used. It is clear that high current demand
for a large period of time consumes faster the sacrificial anode while at the same time might not be able to
generate the required potential.
The reader can easily relate the above table to that of slide no. 19 .
Axios Bridge Galvanic Protection
Tendon tracks, tendon anchors and non sealed joints create a rather complex scenario for uniform
polarisation potential distribution. In the case of existing bridges offering limited accessibility, the problem
exponentially increases leading to over-polarisation issues and potential hydrogen gas generation . The use
of control sensors and complex programming of the cathodic protection control unit can sometimes only
provide limited solution. In addition to the above, a cathodic protection control unit is usually unprotected
from actions of vandalism and theft.
For the above reasons, the use of Galvanic protection was chosen. Due to the large surface area and the
difficulty in boring to encase embedded anodes, the use of Zinc / Hydrogel Anode or known as Zinc layer
Adhesive Anode or ZLA. This anode consisted of a zinc foil, which measured 0.25 mm thick by 0.25 m wide ,
a conductive adhesive gel (3M Company’s Hydrogel™) bonded to one side of the foil, and a release paper
sticking to the other side of the adhesive gel. In this application, ZLA provided by Mapei under the
commercial name of Mapeshield E25 was used.
Mapeshield E25 provides 455 grams of Zinc per running
meter and is certified according to EN 12696.
Axios Bridge Galvanic Protection
Calculations and the subsequent plans were based on an initial protection current density of 5mΑ/m2 for
the first 12 months followed by a value of 1.5mΑ/m2 for the remaining protection period. A 10 year overall
protection period was considered. A safety factor of 1.1 was implemented. Two reference electrodes were
positioned to monitor the tendons. The overall anode performance level was set at 80%.
Application of Galvanic Protection - Step A - Hydro blasting 500 Bar
Rigorous cleaning of the surface is imperative for Hydrogel to maintain a uniform and maximum
ion current flow. The pressure refers to nozzle output.
It is important to note that the nozzle to surface distance was kept between 5-10 cm. It is a
common mistake of contractors performing hydro blasting to operate at longer distances. A
practical tip identifying correct distance (depends on concrete strength, pressure and flow rate
of the unit) is to achieve concrete skin (2-4mm) removal at a rate of > 0.1 m2/min.
Application of Galvanic Protection - Step A - Hydro blasting 500 Bar
Hydro-blasting at 500 bars, is usually enough to remove loose concrete due to spalling.
Application of Galvanic Protection - Step A - Hydro blasting 500 Bar
Prior to any patch repair it is important to check for electrical continuity. In the case where
electrical continuity (a value <0.1V at DC setting indicatives continuity) is not obtained, the
contractor shall proceed with artificial connection using the fixings and a piece of the
recommended cathodic protection cable. The photograph shows a “bridge” used to achieve
electrical continuity between two stirrups. Connections and fixings are protected using a
conductive sealant.
Application of Galvanic Protection – Step B – Local Patch Repairs
Fixing to steel reinforcement is made using a low voltage cable. Usually type FG7R-0.6/1KV 1 Χ
8. In this particular application connection was made using stainless steel rivets and ring eye
terminals.
Application of Galvanic Protection – Step B – Local Patch Repairs
Patch repair grout should be according to ΕΝ 1504 parts 2,3 while is mandatory to have an
electrical resistivity < 10 KOhm cm (ΕΝ 12696). This is because the grout should allow the
unrestricted row of ions generated by the Zinc / Hydrogel Anode.
Application of Galvanic Protection – Step B – Local Patch Repairs
Sufficient time shall be allowed prior to the application of the ZLA over the patched area. In such
applications, grout strength is not an indicative parameter. The contractor shall measure the
electrical resistivity using a Wenner Probe. Once the reading is within its declared value by the
manufacturer, the contractor can proceed to the next step.
Application of Galvanic Protection – Step B – Local Patch Repairs
After removing the releasing sheet protecting Hydrogel from air, ZLA can be applied on concrete
surface. A rubber mallet is usually used to secure one edge of the anode sheet. A rubber roller is
finally used for final placement and straightening. The stiffness of ZLA and the usually uneven
surface of concrete, usually prevent air being trapped underneath.
Application of Galvanic Protection – Step C – Placing the ZLA
A covermeter is used to identify the location and cover thickness of reinforcement intending to
receive connection to the anode. The action should be performed prior to the placement of ZLA
since measurement over zinc cancels the operation of the covermeter.
Application of Galvanic Protection – Step C – Placing the ZLA
A wedge anchor is used to connect reinforcement to ZLA. The location has been previously
identified by covermeter (reinforcement free zone) and indicated on the ZLA using a marker.
Correct connection once again requires electrical continuity measurement.
Application of Galvanic Protection – Step C – Placing the ZLA
The process is repeated until all ZLA sheets have been placed. Note that all required connections to
reinforcement are established. That allows the contractor to continuously check and recheck electrical
continuity. A valid order is to start the check between the first ZLA and the last reinforcement connection
and continue the process inwards, i.e. the second ZLA or reinforcement connection with the N-1
reinforcement connection (N is the total number of connections), the third ZLA or reinforcement connection
with the N-2 reinforcement connection, etc.
Connection to steel was made using the following steps,
a) Detection of location and depth of steel using covermeter,
b) Drilling of concrete using a Ø40 bit until reaching cover thickness,
c) Drilling steel reinforcement using a Ø4 Cobalt bit.
d) Placement of eye terminal on rivet and fixing using a pop rivet gun
e) Checking of electrical continuity with a multimeter
f) Placement of conductive sealant over the connection.
Application of Galvanic Protection – Step C – Placing the ZLA
Once all ZLAs have been placed and checked for electrical continuity, their edges shall be
protected by moisture attacking the Hydrogel. In this application Mapeflex PU40 was used. A
layer of width around 30mm and thickness 2-3mm is enough.
Application of Galvanic Protection – Step C – Placing the ZLA
Sealing of ZLAs with Mapeflex PU40.
Application of Galvanic Protection – Step C – Placing the ZLA
Application of Galvanic Protection – Step D – Placement of Reference Anodes
Placement of two reference electrodes type Ag/AgCl/KCl (Castle Electrodes Ltd, LD10) according
to plans. Reference electrodes allows us to perform depolarisation testing according to EN
12696.
It is imperative to do an initial potential measurement to safeguard initialisation and uniform
voltage distribution of the circuit. In this case, values of -417 mV και -380 mV (Ag/AgCl) were
measured from the two reference electrodes.
Εφαρμογή Καθοδικής Προστασίας – Στάδιο Ε – Τοποθέτηση Κυτίων ΕλέγχουApplication of Galvanic Protection – Step E – Junction Boxes and Cable Conduits
Complete sealing of ZLA using Mapelastic Smart. Bond strength on ZLA has a declared value of
>1,6 MPa. Sealing protects the anode from consumption due to air oxidation.
Application of Galvanic Protection – Step F – Sealing the Circuit
Final form of ZLA application
Application of Galvanic Protection
Depolarisation values 7 days after initialisation.
All three EN 12696 requirements
are met.
Instant Off Value R1=-793 mV
Instant Off Value R2=-761 mV
Application of Galvanic Protection – Depolarisation Values - 7 days
Instant Off Value R1=-835 mV
Instant Off Value R2=-856 mV
Application of Galvanic Protection – Depolarisation Values - 30 days
Depolarisation values 30 days after initialisation.
All three EN 12696 requirements
are met.
Advantages and Disadvantages of ZLAs compared to ICCP
Advantages
Low initial investment cost,
The application does not require specialised equipment and personnel,
Significantly reduces damage due to concrete boring required for ICCP anodes,
Protection can last over 25 years as in the case of carbonation,
Relatively easy calculations based Faraday’s equation,
The anode can be easily replaced,
The potential for hydrogen gas generation is negligible,
It does not require control unit,
Certified according to ΕΝ 12696, BS 7361 and AS 2382.5.
Disadvantages
High cost per year when protection over 40 years is needed.
Limited performance and protection when high current density is required,
It is highly unlikely to cause chloride ions extraction,
It is sensitive to temperature and moisture changes.
Characteristic Applications of ZLAs
Bridges
Balconies
Local repairs
Facades
Slabs
Beams
Characteristic Applications of ZLAs
Final sealing can be painted or plastered. In the
case of plastering, surface treatment of the
sealant using quartz sand 0.85-1.2 mm is
recommended.
Characteristic Applications of ZLAs on bridges from around the World
List of key materials used in the application
More information can be found in
http://www.mapei.com/GR-EL/
and
http://www.mapei.com/public/GB/linedocument/Cathodic_Protection_GB.pdf
Application of Galvanic Protection – Project Partners

More Related Content

What's hot

Lithium-Seawater Battery for Undersea Sensors and Vehicles
Lithium-Seawater Battery for Undersea Sensors and VehiclesLithium-Seawater Battery for Undersea Sensors and Vehicles
Lithium-Seawater Battery for Undersea Sensors and Vehicles
chrisrobschu
 
3 cp corrosion control
3 cp corrosion control3 cp corrosion control
3 cp corrosion control
himanshu jain
 
Presentation Power Sources Lithium Seawater Battery (LiSWB)
Presentation Power Sources Lithium Seawater Battery (LiSWB)Presentation Power Sources Lithium Seawater Battery (LiSWB)
Presentation Power Sources Lithium Seawater Battery (LiSWB)
chrisrobschu
 
FAC_Akshay Murkute
FAC_Akshay MurkuteFAC_Akshay Murkute
FAC_Akshay Murkute
Akshay Murkute
 
Heavy Metals Assessment in Water Reservoirs Reinforced By Służewiecki Stream
Heavy Metals Assessment in Water Reservoirs Reinforced By Służewiecki Stream Heavy Metals Assessment in Water Reservoirs Reinforced By Służewiecki Stream
Heavy Metals Assessment in Water Reservoirs Reinforced By Służewiecki Stream
IJERA Editor
 
Poster Final SETAC 2016 2
Poster Final SETAC 2016 2Poster Final SETAC 2016 2
Poster Final SETAC 2016 2
Aldous Rees
 
Electrochemical Extraction (ECE)
Electrochemical Extraction (ECE)Electrochemical Extraction (ECE)
Electrochemical Extraction (ECE)
Ehab Hasuna
 
Integrated Electrodialysis Membrane Stability Results for Cost-Effective CBM ...
Integrated Electrodialysis Membrane Stability Results for Cost-Effective CBM ...Integrated Electrodialysis Membrane Stability Results for Cost-Effective CBM ...
Integrated Electrodialysis Membrane Stability Results for Cost-Effective CBM ...
Paula Moon, Ph.D.
 
Electrodialysis1
Electrodialysis1Electrodialysis1
Reinforcement corrosion part2
Reinforcement corrosion part2Reinforcement corrosion part2
Reinforcement corrosion part2
Adriana de Araujo
 
Electrical characterization of semiconductor-insulator interfaces in VLSI:ULS...
Electrical characterization of semiconductor-insulator interfaces in VLSI:ULS...Electrical characterization of semiconductor-insulator interfaces in VLSI:ULS...
Electrical characterization of semiconductor-insulator interfaces in VLSI:ULS...
Dang Trang
 
D0281017024
D0281017024D0281017024
D0281017024
inventionjournals
 
Cathodic and anodic protection
Cathodic and anodic protectionCathodic and anodic protection
Cathodic and anodic protection
THOMAS THANGADURAI K
 
Yutong Liu - Final Report - Anodized Aluminium Oxide (AAO)
Yutong Liu - Final Report - Anodized Aluminium Oxide (AAO)Yutong Liu - Final Report - Anodized Aluminium Oxide (AAO)
Yutong Liu - Final Report - Anodized Aluminium Oxide (AAO)
Yutong Liu
 
Cathodic protection of reinforced concrete structures
Cathodic protection of reinforced concrete structuresCathodic protection of reinforced concrete structures
Cathodic protection of reinforced concrete structures
Ravi Kumar
 
Corrosion Inhibition of Carbon Steel In Sulfuric Acid by Sodium Caprylate
Corrosion Inhibition of Carbon Steel In Sulfuric Acid by Sodium CaprylateCorrosion Inhibition of Carbon Steel In Sulfuric Acid by Sodium Caprylate
Corrosion Inhibition of Carbon Steel In Sulfuric Acid by Sodium Caprylate
IJERA Editor
 
EvolutionEDI_AWT06
EvolutionEDI_AWT06EvolutionEDI_AWT06
EvolutionEDI_AWT06
Chris Gallagher
 
F041033947
F041033947F041033947
F041033947
IOSR-JEN
 
Soprovich, 2014
Soprovich, 2014Soprovich, 2014
Soprovich, 2014
Michel Duteau
 
Pidaparthy 2021 j._electrochem._soc._168_100509
Pidaparthy 2021 j._electrochem._soc._168_100509Pidaparthy 2021 j._electrochem._soc._168_100509
Pidaparthy 2021 j._electrochem._soc._168_100509
Ary Assuncao
 

What's hot (20)

Lithium-Seawater Battery for Undersea Sensors and Vehicles
Lithium-Seawater Battery for Undersea Sensors and VehiclesLithium-Seawater Battery for Undersea Sensors and Vehicles
Lithium-Seawater Battery for Undersea Sensors and Vehicles
 
3 cp corrosion control
3 cp corrosion control3 cp corrosion control
3 cp corrosion control
 
Presentation Power Sources Lithium Seawater Battery (LiSWB)
Presentation Power Sources Lithium Seawater Battery (LiSWB)Presentation Power Sources Lithium Seawater Battery (LiSWB)
Presentation Power Sources Lithium Seawater Battery (LiSWB)
 
FAC_Akshay Murkute
FAC_Akshay MurkuteFAC_Akshay Murkute
FAC_Akshay Murkute
 
Heavy Metals Assessment in Water Reservoirs Reinforced By Służewiecki Stream
Heavy Metals Assessment in Water Reservoirs Reinforced By Służewiecki Stream Heavy Metals Assessment in Water Reservoirs Reinforced By Służewiecki Stream
Heavy Metals Assessment in Water Reservoirs Reinforced By Służewiecki Stream
 
Poster Final SETAC 2016 2
Poster Final SETAC 2016 2Poster Final SETAC 2016 2
Poster Final SETAC 2016 2
 
Electrochemical Extraction (ECE)
Electrochemical Extraction (ECE)Electrochemical Extraction (ECE)
Electrochemical Extraction (ECE)
 
Integrated Electrodialysis Membrane Stability Results for Cost-Effective CBM ...
Integrated Electrodialysis Membrane Stability Results for Cost-Effective CBM ...Integrated Electrodialysis Membrane Stability Results for Cost-Effective CBM ...
Integrated Electrodialysis Membrane Stability Results for Cost-Effective CBM ...
 
Electrodialysis1
Electrodialysis1Electrodialysis1
Electrodialysis1
 
Reinforcement corrosion part2
Reinforcement corrosion part2Reinforcement corrosion part2
Reinforcement corrosion part2
 
Electrical characterization of semiconductor-insulator interfaces in VLSI:ULS...
Electrical characterization of semiconductor-insulator interfaces in VLSI:ULS...Electrical characterization of semiconductor-insulator interfaces in VLSI:ULS...
Electrical characterization of semiconductor-insulator interfaces in VLSI:ULS...
 
D0281017024
D0281017024D0281017024
D0281017024
 
Cathodic and anodic protection
Cathodic and anodic protectionCathodic and anodic protection
Cathodic and anodic protection
 
Yutong Liu - Final Report - Anodized Aluminium Oxide (AAO)
Yutong Liu - Final Report - Anodized Aluminium Oxide (AAO)Yutong Liu - Final Report - Anodized Aluminium Oxide (AAO)
Yutong Liu - Final Report - Anodized Aluminium Oxide (AAO)
 
Cathodic protection of reinforced concrete structures
Cathodic protection of reinforced concrete structuresCathodic protection of reinforced concrete structures
Cathodic protection of reinforced concrete structures
 
Corrosion Inhibition of Carbon Steel In Sulfuric Acid by Sodium Caprylate
Corrosion Inhibition of Carbon Steel In Sulfuric Acid by Sodium CaprylateCorrosion Inhibition of Carbon Steel In Sulfuric Acid by Sodium Caprylate
Corrosion Inhibition of Carbon Steel In Sulfuric Acid by Sodium Caprylate
 
EvolutionEDI_AWT06
EvolutionEDI_AWT06EvolutionEDI_AWT06
EvolutionEDI_AWT06
 
F041033947
F041033947F041033947
F041033947
 
Soprovich, 2014
Soprovich, 2014Soprovich, 2014
Soprovich, 2014
 
Pidaparthy 2021 j._electrochem._soc._168_100509
Pidaparthy 2021 j._electrochem._soc._168_100509Pidaparthy 2021 j._electrochem._soc._168_100509
Pidaparthy 2021 j._electrochem._soc._168_100509
 

Similar to Axios bridge final-english

Cathodic protection in_practise
Cathodic protection in_practiseCathodic protection in_practise
Cathodic protection in_practise
abdallahbeca
 
(cathodic protection)
(cathodic protection) (cathodic protection)
(cathodic protection)
Mohamed Safwat
 
Corrosion Assessment – Half-Cell Potential Method for reinforced concrete
Corrosion Assessment – Half-Cell Potential Method for reinforced concreteCorrosion Assessment – Half-Cell Potential Method for reinforced concrete
Corrosion Assessment – Half-Cell Potential Method for reinforced concrete
Yash Shah
 
Corrosion and Degradation of Materials-chapter 16
Corrosion and Degradation of Materials-chapter 16Corrosion and Degradation of Materials-chapter 16
Corrosion and Degradation of Materials-chapter 16
ssuser2fec01
 
Literature review of recent best practices of downhole corrosion system , mod...
Literature review of recent best practices of downhole corrosion system , mod...Literature review of recent best practices of downhole corrosion system , mod...
Literature review of recent best practices of downhole corrosion system , mod...
Muzammal Arif
 
Behavior of carbon steel in simulated concrete pore solutions of air-entraine...
Behavior of carbon steel in simulated concrete pore solutions of air-entraine...Behavior of carbon steel in simulated concrete pore solutions of air-entraine...
Behavior of carbon steel in simulated concrete pore solutions of air-entraine...
Adriana de Araujo
 
Characterization of corrosion of x70 pipeline steel in thin electrolyte layer
Characterization of corrosion of x70 pipeline steel in thin electrolyte layerCharacterization of corrosion of x70 pipeline steel in thin electrolyte layer
Characterization of corrosion of x70 pipeline steel in thin electrolyte layer
A X.S
 
Design of a Cathodic Protection System for Corrosion Prevention of a Pipeline...
Design of a Cathodic Protection System for Corrosion Prevention of a Pipeline...Design of a Cathodic Protection System for Corrosion Prevention of a Pipeline...
Design of a Cathodic Protection System for Corrosion Prevention of a Pipeline...
Onyedikachi Martins
 
Crain, Alexis Poster
Crain, Alexis PosterCrain, Alexis Poster
Crain, Alexis Poster
Alexis Crain
 
20140801-JCIS-AZ-RH
20140801-JCIS-AZ-RH20140801-JCIS-AZ-RH
20140801-JCIS-AZ-RH
Rossen Hristov
 
2010 cu c fiber hybrids carbon 2106
2010 cu c fiber hybrids carbon 21062010 cu c fiber hybrids carbon 2106
2010 cu c fiber hybrids carbon 2106
Nourre
 
Advanced Cathodic Protection - CP Series - Eric Langelund
Advanced Cathodic Protection - CP Series - Eric LangelundAdvanced Cathodic Protection - CP Series - Eric Langelund
Advanced Cathodic Protection - CP Series - Eric Langelund
nacetwincities
 
Corrosion control of underwater piles
Corrosion control of underwater pilesCorrosion control of underwater piles
Corrosion control of underwater piles
Aglaia Connect
 
Some problems with prestressed concrete sleepers durability
Some problems with prestressed concrete sleepers durabilitySome problems with prestressed concrete sleepers durability
Some problems with prestressed concrete sleepers durability
eSAT Publishing House
 
1 s2.0-0040609083905771-main contact resistance and methods for its determina...
1 s2.0-0040609083905771-main contact resistance and methods for its determina...1 s2.0-0040609083905771-main contact resistance and methods for its determina...
1 s2.0-0040609083905771-main contact resistance and methods for its determina...
Kadu Brito
 
Corrosion
CorrosionCorrosion
Corrosion
Ahtisham Arshad
 
Presentation of iqra malik
Presentation of iqra malikPresentation of iqra malik
Presentation of iqra malik
Iqra malik
 
Paul Ahern - Copper/ low-K Interconnect Technology
Paul Ahern - Copper/ low-K Interconnect TechnologyPaul Ahern - Copper/ low-K Interconnect Technology
Paul Ahern - Copper/ low-K Interconnect Technology
Paul Ahern
 
CorrosionCathProtBasicDesignSATX
CorrosionCathProtBasicDesignSATXCorrosionCathProtBasicDesignSATX
CorrosionCathProtBasicDesignSATX
Stanley Worcester
 
Pvc cmos finale
Pvc cmos finale Pvc cmos finale
Pvc cmos finale
Roslina Shariff
 

Similar to Axios bridge final-english (20)

Cathodic protection in_practise
Cathodic protection in_practiseCathodic protection in_practise
Cathodic protection in_practise
 
(cathodic protection)
(cathodic protection) (cathodic protection)
(cathodic protection)
 
Corrosion Assessment – Half-Cell Potential Method for reinforced concrete
Corrosion Assessment – Half-Cell Potential Method for reinforced concreteCorrosion Assessment – Half-Cell Potential Method for reinforced concrete
Corrosion Assessment – Half-Cell Potential Method for reinforced concrete
 
Corrosion and Degradation of Materials-chapter 16
Corrosion and Degradation of Materials-chapter 16Corrosion and Degradation of Materials-chapter 16
Corrosion and Degradation of Materials-chapter 16
 
Literature review of recent best practices of downhole corrosion system , mod...
Literature review of recent best practices of downhole corrosion system , mod...Literature review of recent best practices of downhole corrosion system , mod...
Literature review of recent best practices of downhole corrosion system , mod...
 
Behavior of carbon steel in simulated concrete pore solutions of air-entraine...
Behavior of carbon steel in simulated concrete pore solutions of air-entraine...Behavior of carbon steel in simulated concrete pore solutions of air-entraine...
Behavior of carbon steel in simulated concrete pore solutions of air-entraine...
 
Characterization of corrosion of x70 pipeline steel in thin electrolyte layer
Characterization of corrosion of x70 pipeline steel in thin electrolyte layerCharacterization of corrosion of x70 pipeline steel in thin electrolyte layer
Characterization of corrosion of x70 pipeline steel in thin electrolyte layer
 
Design of a Cathodic Protection System for Corrosion Prevention of a Pipeline...
Design of a Cathodic Protection System for Corrosion Prevention of a Pipeline...Design of a Cathodic Protection System for Corrosion Prevention of a Pipeline...
Design of a Cathodic Protection System for Corrosion Prevention of a Pipeline...
 
Crain, Alexis Poster
Crain, Alexis PosterCrain, Alexis Poster
Crain, Alexis Poster
 
20140801-JCIS-AZ-RH
20140801-JCIS-AZ-RH20140801-JCIS-AZ-RH
20140801-JCIS-AZ-RH
 
2010 cu c fiber hybrids carbon 2106
2010 cu c fiber hybrids carbon 21062010 cu c fiber hybrids carbon 2106
2010 cu c fiber hybrids carbon 2106
 
Advanced Cathodic Protection - CP Series - Eric Langelund
Advanced Cathodic Protection - CP Series - Eric LangelundAdvanced Cathodic Protection - CP Series - Eric Langelund
Advanced Cathodic Protection - CP Series - Eric Langelund
 
Corrosion control of underwater piles
Corrosion control of underwater pilesCorrosion control of underwater piles
Corrosion control of underwater piles
 
Some problems with prestressed concrete sleepers durability
Some problems with prestressed concrete sleepers durabilitySome problems with prestressed concrete sleepers durability
Some problems with prestressed concrete sleepers durability
 
1 s2.0-0040609083905771-main contact resistance and methods for its determina...
1 s2.0-0040609083905771-main contact resistance and methods for its determina...1 s2.0-0040609083905771-main contact resistance and methods for its determina...
1 s2.0-0040609083905771-main contact resistance and methods for its determina...
 
Corrosion
CorrosionCorrosion
Corrosion
 
Presentation of iqra malik
Presentation of iqra malikPresentation of iqra malik
Presentation of iqra malik
 
Paul Ahern - Copper/ low-K Interconnect Technology
Paul Ahern - Copper/ low-K Interconnect TechnologyPaul Ahern - Copper/ low-K Interconnect Technology
Paul Ahern - Copper/ low-K Interconnect Technology
 
CorrosionCathProtBasicDesignSATX
CorrosionCathProtBasicDesignSATXCorrosionCathProtBasicDesignSATX
CorrosionCathProtBasicDesignSATX
 
Pvc cmos finale
Pvc cmos finale Pvc cmos finale
Pvc cmos finale
 

Recently uploaded

Call For Paper -3rd International Conference on Artificial Intelligence Advan...
Call For Paper -3rd International Conference on Artificial Intelligence Advan...Call For Paper -3rd International Conference on Artificial Intelligence Advan...
Call For Paper -3rd International Conference on Artificial Intelligence Advan...
ijseajournal
 
Properties of Fluids, Fluid Statics, Pressure Measurement
Properties of Fluids, Fluid Statics, Pressure MeasurementProperties of Fluids, Fluid Statics, Pressure Measurement
Properties of Fluids, Fluid Statics, Pressure Measurement
Indrajeet sahu
 
Supermarket Management System Project Report.pdf
Supermarket Management System Project Report.pdfSupermarket Management System Project Report.pdf
Supermarket Management System Project Report.pdf
Kamal Acharya
 
Call Girls Chennai +91-8824825030 Vip Call Girls Chennai
Call Girls Chennai +91-8824825030 Vip Call Girls ChennaiCall Girls Chennai +91-8824825030 Vip Call Girls Chennai
Call Girls Chennai +91-8824825030 Vip Call Girls Chennai
paraasingh12 #V08
 
一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理
一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理
一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理
upoux
 
Open Channel Flow: fluid flow with a free surface
Open Channel Flow: fluid flow with a free surfaceOpen Channel Flow: fluid flow with a free surface
Open Channel Flow: fluid flow with a free surface
Indrajeet sahu
 
Particle Swarm Optimization–Long Short-Term Memory based Channel Estimation w...
Particle Swarm Optimization–Long Short-Term Memory based Channel Estimation w...Particle Swarm Optimization–Long Short-Term Memory based Channel Estimation w...
Particle Swarm Optimization–Long Short-Term Memory based Channel Estimation w...
IJCNCJournal
 
Unit -II Spectroscopy - EC I B.Tech.pdf
Unit -II Spectroscopy - EC  I B.Tech.pdfUnit -II Spectroscopy - EC  I B.Tech.pdf
Unit -II Spectroscopy - EC I B.Tech.pdf
TeluguBadi
 
309475979-Creativity-Innovation-notes-IV-Sem-2016-pdf.pdf
309475979-Creativity-Innovation-notes-IV-Sem-2016-pdf.pdf309475979-Creativity-Innovation-notes-IV-Sem-2016-pdf.pdf
309475979-Creativity-Innovation-notes-IV-Sem-2016-pdf.pdf
Sou Tibon
 
Digital Twins Computer Networking Paper Presentation.pptx
Digital Twins Computer Networking Paper Presentation.pptxDigital Twins Computer Networking Paper Presentation.pptx
Digital Twins Computer Networking Paper Presentation.pptx
aryanpankaj78
 
FULL STACK PROGRAMMING - Both Front End and Back End
FULL STACK PROGRAMMING - Both Front End and Back EndFULL STACK PROGRAMMING - Both Front End and Back End
FULL STACK PROGRAMMING - Both Front End and Back End
PreethaV16
 
AN INTRODUCTION OF AI & SEARCHING TECHIQUES
AN INTRODUCTION OF AI & SEARCHING TECHIQUESAN INTRODUCTION OF AI & SEARCHING TECHIQUES
AN INTRODUCTION OF AI & SEARCHING TECHIQUES
drshikhapandey2022
 
Object Oriented Analysis and Design - OOAD
Object Oriented Analysis and Design - OOADObject Oriented Analysis and Design - OOAD
Object Oriented Analysis and Design - OOAD
PreethaV16
 
UNIT 4 LINEAR INTEGRATED CIRCUITS-DIGITAL ICS
UNIT 4 LINEAR INTEGRATED CIRCUITS-DIGITAL ICSUNIT 4 LINEAR INTEGRATED CIRCUITS-DIGITAL ICS
UNIT 4 LINEAR INTEGRATED CIRCUITS-DIGITAL ICS
vmspraneeth
 
UNIT-III- DATA CONVERTERS ANALOG TO DIGITAL CONVERTER
UNIT-III- DATA CONVERTERS ANALOG TO DIGITAL CONVERTERUNIT-III- DATA CONVERTERS ANALOG TO DIGITAL CONVERTER
UNIT-III- DATA CONVERTERS ANALOG TO DIGITAL CONVERTER
vmspraneeth
 
Tools & Techniques for Commissioning and Maintaining PV Systems W-Animations ...
Tools & Techniques for Commissioning and Maintaining PV Systems W-Animations ...Tools & Techniques for Commissioning and Maintaining PV Systems W-Animations ...
Tools & Techniques for Commissioning and Maintaining PV Systems W-Animations ...
Transcat
 
Butterfly Valves Manufacturer (LBF Series).pdf
Butterfly Valves Manufacturer (LBF Series).pdfButterfly Valves Manufacturer (LBF Series).pdf
Butterfly Valves Manufacturer (LBF Series).pdf
Lubi Valves
 
FUNDAMENTALS OF MECHANICAL ENGINEERING.pdf
FUNDAMENTALS OF MECHANICAL ENGINEERING.pdfFUNDAMENTALS OF MECHANICAL ENGINEERING.pdf
FUNDAMENTALS OF MECHANICAL ENGINEERING.pdf
EMERSON EDUARDO RODRIGUES
 
openshift technical overview - Flow of openshift containerisatoin
openshift technical overview - Flow of openshift containerisatoinopenshift technical overview - Flow of openshift containerisatoin
openshift technical overview - Flow of openshift containerisatoin
snaprevwdev
 
comptia-security-sy0-701-exam-objectives-(5-0).pdf
comptia-security-sy0-701-exam-objectives-(5-0).pdfcomptia-security-sy0-701-exam-objectives-(5-0).pdf
comptia-security-sy0-701-exam-objectives-(5-0).pdf
foxlyon
 

Recently uploaded (20)

Call For Paper -3rd International Conference on Artificial Intelligence Advan...
Call For Paper -3rd International Conference on Artificial Intelligence Advan...Call For Paper -3rd International Conference on Artificial Intelligence Advan...
Call For Paper -3rd International Conference on Artificial Intelligence Advan...
 
Properties of Fluids, Fluid Statics, Pressure Measurement
Properties of Fluids, Fluid Statics, Pressure MeasurementProperties of Fluids, Fluid Statics, Pressure Measurement
Properties of Fluids, Fluid Statics, Pressure Measurement
 
Supermarket Management System Project Report.pdf
Supermarket Management System Project Report.pdfSupermarket Management System Project Report.pdf
Supermarket Management System Project Report.pdf
 
Call Girls Chennai +91-8824825030 Vip Call Girls Chennai
Call Girls Chennai +91-8824825030 Vip Call Girls ChennaiCall Girls Chennai +91-8824825030 Vip Call Girls Chennai
Call Girls Chennai +91-8824825030 Vip Call Girls Chennai
 
一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理
一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理
一比一原版(uofo毕业证书)美国俄勒冈大学毕业证如何办理
 
Open Channel Flow: fluid flow with a free surface
Open Channel Flow: fluid flow with a free surfaceOpen Channel Flow: fluid flow with a free surface
Open Channel Flow: fluid flow with a free surface
 
Particle Swarm Optimization–Long Short-Term Memory based Channel Estimation w...
Particle Swarm Optimization–Long Short-Term Memory based Channel Estimation w...Particle Swarm Optimization–Long Short-Term Memory based Channel Estimation w...
Particle Swarm Optimization–Long Short-Term Memory based Channel Estimation w...
 
Unit -II Spectroscopy - EC I B.Tech.pdf
Unit -II Spectroscopy - EC  I B.Tech.pdfUnit -II Spectroscopy - EC  I B.Tech.pdf
Unit -II Spectroscopy - EC I B.Tech.pdf
 
309475979-Creativity-Innovation-notes-IV-Sem-2016-pdf.pdf
309475979-Creativity-Innovation-notes-IV-Sem-2016-pdf.pdf309475979-Creativity-Innovation-notes-IV-Sem-2016-pdf.pdf
309475979-Creativity-Innovation-notes-IV-Sem-2016-pdf.pdf
 
Digital Twins Computer Networking Paper Presentation.pptx
Digital Twins Computer Networking Paper Presentation.pptxDigital Twins Computer Networking Paper Presentation.pptx
Digital Twins Computer Networking Paper Presentation.pptx
 
FULL STACK PROGRAMMING - Both Front End and Back End
FULL STACK PROGRAMMING - Both Front End and Back EndFULL STACK PROGRAMMING - Both Front End and Back End
FULL STACK PROGRAMMING - Both Front End and Back End
 
AN INTRODUCTION OF AI & SEARCHING TECHIQUES
AN INTRODUCTION OF AI & SEARCHING TECHIQUESAN INTRODUCTION OF AI & SEARCHING TECHIQUES
AN INTRODUCTION OF AI & SEARCHING TECHIQUES
 
Object Oriented Analysis and Design - OOAD
Object Oriented Analysis and Design - OOADObject Oriented Analysis and Design - OOAD
Object Oriented Analysis and Design - OOAD
 
UNIT 4 LINEAR INTEGRATED CIRCUITS-DIGITAL ICS
UNIT 4 LINEAR INTEGRATED CIRCUITS-DIGITAL ICSUNIT 4 LINEAR INTEGRATED CIRCUITS-DIGITAL ICS
UNIT 4 LINEAR INTEGRATED CIRCUITS-DIGITAL ICS
 
UNIT-III- DATA CONVERTERS ANALOG TO DIGITAL CONVERTER
UNIT-III- DATA CONVERTERS ANALOG TO DIGITAL CONVERTERUNIT-III- DATA CONVERTERS ANALOG TO DIGITAL CONVERTER
UNIT-III- DATA CONVERTERS ANALOG TO DIGITAL CONVERTER
 
Tools & Techniques for Commissioning and Maintaining PV Systems W-Animations ...
Tools & Techniques for Commissioning and Maintaining PV Systems W-Animations ...Tools & Techniques for Commissioning and Maintaining PV Systems W-Animations ...
Tools & Techniques for Commissioning and Maintaining PV Systems W-Animations ...
 
Butterfly Valves Manufacturer (LBF Series).pdf
Butterfly Valves Manufacturer (LBF Series).pdfButterfly Valves Manufacturer (LBF Series).pdf
Butterfly Valves Manufacturer (LBF Series).pdf
 
FUNDAMENTALS OF MECHANICAL ENGINEERING.pdf
FUNDAMENTALS OF MECHANICAL ENGINEERING.pdfFUNDAMENTALS OF MECHANICAL ENGINEERING.pdf
FUNDAMENTALS OF MECHANICAL ENGINEERING.pdf
 
openshift technical overview - Flow of openshift containerisatoin
openshift technical overview - Flow of openshift containerisatoinopenshift technical overview - Flow of openshift containerisatoin
openshift technical overview - Flow of openshift containerisatoin
 
comptia-security-sy0-701-exam-objectives-(5-0).pdf
comptia-security-sy0-701-exam-objectives-(5-0).pdfcomptia-security-sy0-701-exam-objectives-(5-0).pdf
comptia-security-sy0-701-exam-objectives-(5-0).pdf
 

Axios bridge final-english

  • 1. Axios Bridge – Section Athens to Thessaloniki Dr. Chris A Rodopoulos, Dr. P. Panetsos and Mr. I. Koropoulis Application of galvanic cathodic protection using Zink Sheet Anodes according to ΕΝ 12696
  • 2. Axios bridge consists of two sections. The section Athens to Thessaloniki was given to traffic in 1973. The section Thessaloniki to Athens was inaugurated in 1988. The bridge is part of E75 motorway. Axios Bridge – Historical Data
  • 3. Axios Bridge – Historical Data
  • 4. The bridge is made of 29 spans of 30 m each resulting in overall length of 870m. Due to river crossing the bridge is founded on R/C piles. Axios Bridge – Historical Data
  • 5. The superstructure is made of longitudinal and transverse prestressed beams. Axios Bridge – Historical Data
  • 6. Prestressed cross beam detailing Axios Bridge – Historical Data
  • 7. Typical reinforcement detailing. Concrete has been classified as C30/37 after coring. Axios Bridge – Historical Data
  • 8. A CuSO4 reference electrode has been used. All values in mV. Measurements and Pathology – Half Cell Measurements of External Beam
  • 9. Measurements and Pathology – Half Cell Measurements of External Beam – Projection of values on beam The high negative values at area A indicate waterproofing failure of the expansion joint. The high corrosion propensity at areas B and C, indicate potential local failure of the deck waterproofing layer. Area Α Area Β Area C
  • 10. Measurements and Pathology – Half Cell Measurements of External Beam – Projection of values on tendon tracks Note that the anchors of tendons 3-8, exhibit high corrosion potential. Similar problem is identified at the location of tendons 9, 11 and 12.
  • 11. Measurements and Pathology – Concrete Electrical Resistivity Measurements All values in KOhm cm.
  • 12. Measurements and Pathology – Concrete Electrical Resistivity Measurements– Projection of values on beam Electrical resistivity is an indirect way of evaluating concrete’s build in moisture and hence the susceptibility to ionic current movement (controls the cathodic / oxygen reaction). To acknowledge the importance of the measurements, it is worth noting that the electrical resistivity of C30/37 concrete, having build in (hygroscopic) moisture of 2% w. t., is around 70 KOhm cm.
  • 13. Measurements and Pathology– Linear Polarisation Measurements (LPR) All values in μΑ/cm2. The measured values classified corrosion belonging into the low to medium rate according to the above Table. Certain areas in purple are classified as passive.
  • 14. Measurements and Pathology– Linear Polarisation Measurements (LPR) – Projection of values on beam It is important to consider that low values of corrosion current density are most likely to increase with time compared to high values which are bounded by the nature of concrete’s pathology. It is also worth noting that values above 0.5 μΑ/cm2 can lead to complete loss of bond strength within 2-10 years.
  • 15. Measurements and Pathology– Linear Polarisation Measurements (LPR) – Projection of values on tendon tracks Projection of the measured values over the design and especially over tendon tracks is perhaps the most crucial action when evaluating corrosion in prestressed elements. The generated image help us identify critical locations while at the same time provides information regarding potential causes. Herein, we can easily identify that tendons No. 8, 9, 11, 12, are within the area demonstrating the highest corrosion rate of the sample. It is important to note that the transverse beam is also critically corroding. The surface tendon 11 appears to experience significant corrosion rate due to overhead failure of waterproofing.
  • 16. Measurements and Pathology – Concrete Pathology Axios Bridge is located in a semi-urban environment experiencing high humidity due to river. The distance from the sea is over 5 Km and therefore the potential of airborne chlorides diffusing into concrete is considered as negligible. The bridge is rarely subjected to de-icing salts. Even though vehicular traffic is substantial, the location experiences CO2 concentration below 300 ppm. In conjunction with the high humidity of the area, concrete experiences a rather low carbonation rate. The bridge is suffering from poor storm water drainage, non sealed expansion joints and damaged deck waterproofing layer. Accessibility is the most crucial issue in the assessment of concrete's pathology in large structures and especially prestressed bridges. Herein, it is imperative to collect samples from locations, a) being critical to the load bearing capacity, b) being indicative to the actual problem both in terms of chemistry and concentration and c) providing a sound basis for damage classification. The later, is mostly governed by sample population and the type of pathology being initially identified. The level of carbonation and chloride attack, coming from airborne chlorides, is perhaps the easiest of all since they rarely demonstrate significant position variations. Tendon anchors and tendons are critical items which require particular attention. Surface tendons are notoriously difficult to locate and approach even though is widely known of being liable to corrosion. Similarly, tendon anchors in old bridges are usually located in tight spaces with poor access.
  • 17. Due to accessibility issues, samples were collected from areas being close to the expansion joints and experiencing spalling. Indicative results are shown in the Table below. Samples Concentration of Total Chlorides Cement (% w.t) - ASTM C1152 Concrete Alkalinity Sample 1 0.19 8.2 Sample 2 0.25 6.9 Sample 3 0.27 7.7 Sample 4 0.21 7.8 Sample 5 0.27 7.6 According to EN 8110, a total chloride concentration of 0.1% is considered as threshold value for critical corrosion in prestressed elements. The above limit however refers to concrete alkalinity, pH, being >11. In the samples, concrete alkalinity has dropped as low as 7.6 indicating that critical chloride levels are several orders below 0.1%. In addition, alkalinity values are significant below the lower limit value indicating carbonation, i.e. pH=8.4. The phenomenon of low alkalinity is attributed to water soluble chemicals from tyre wear, brake wear particle emission, and exhaust discharges (traffic dust). Measurements and Pathology – Concrete Pathology All samples have been collected at depth equal to concrete cover thickness (30mm).
  • 18. Traffic dust’s most common chemicals and their typical concentration Measurements and Pathology – Concrete Pathology Most of these chemical are known to disintegrate both concrete and steel (ACI 515.1R).
  • 19. Measurements and Pathology – Concrete Pathology Axios Bridge experiences the simultaneous effect of chlorides due to de-icing salts along with chemical attack due to traffic dust. Both, in their soluble form shall be considered as the main cause of corrosion. Herein, once again accessibility is vital in order to collect samples that can be analysed in order to provide secure information regarding concentration of the hazardous chemicals and their reactions with cement constituents. Indirectly we can overcome the problem by comparing our LPR measurements with the limits of certain exposure conditions as depicted in the Table below. Exposure Class per EN 206-1 LPR Values ( μΑ/cm2) Average Standard Deviation XC1 0 - XC2 0.35 0.26 XC3 0.17 0.08 XC4 0.43 0.26 XD1 0.35 0.26 XD2 2.60 1.70 XS1 2.60 1.70 XS2 - - XS3 6.00 3.50 Axios bridge belongs into classes XD2 and XD3 (de-icing salts). The reader can easily compared the previously reported values and acknowledge their deviation form the above limits. Such difference indicates the supplementary effect provide by traffic dust residues.
  • 20. Basic Principles of Galvanic Protection Corrosion is based on two reactions 1st Half Cell Reaction Anodic reaction – Oxidation of iron, Iron is oxidized from Fe (oxidation state 0) to Fe 2+ (oxidation state +2). 2nd Half Cell Reaction Cathodic reaction– Reduction of oxygen, the liberated electrons from the oxidation of iron are consumed by oxygen in the presence of water to form hydroxyl (OH−). In this reaction oxygen is electrochemically reduced from O2 (oxidation state 0) to OH− (oxidation state −2).
  • 21. Basic Principles of Galvanic Protection If there is no external electric source of electrons, the anodic reaction must generate electrons at exactly the same rate as the cathodic reaction consumes them. If electrons were withdrawn from the metal surface, it might be anticipated that the anodic reaction would speed up (to replace the lost electrons) and the cathodic reaction would slow down, because of the existing shortfall of electrons. It follows that the rate of metal consumption would increase. If however additional electrons were introduced at the metal surface, the cathodic reaction would speed up (to consume the electrons) and the anodic reaction would be inhibited; metal dissolution would be slowed down.
  • 22. Basic Principles of Galvanic Protection Inhibiting corrosion via external source of electrons is the basic principle of cathodic protection. In the case of electrons being provide by an electric source, cathodic protection refers to Induced Current Cathodic Protection (ICCP). If the source of electrons is provided by a sacrificial metal, being more electronegative, cathodic protection refers to Galvanic Cathodic Protection. This fundamental principle can be appreciated via the Poubraix diagram for Iron. The grey area in the diagram on the left encapsulates the limits of cathodic protection.
  • 23. Basic Principles of Galvanic Protection Schematically, the excess electrons provide by galvanic cathodic protection (leading to corrosion inhibition) is shown below.
  • 24. Basic Principles of Galvanic Protection The availability and the potential of metals able to provide excess electrons is governed by the Standard Reduction Potential Table. We can easily identify that, Zn, Al and Li are more electronegative than Fe and therefore can provide excess electrons. Since the excess electrons are generated by the corrosion of the more electronegative metal, the term sacrificial metal is widely used.
  • 25. Basic Principles of Galvanic Protection In Galvanic Cathodic Protection, the potential difference alone is not enough as to proceed with the selection of the anode metal. Generated anode (sacrificial metal) current density and electrochemical capacity (Amp-h/Kg) are also important parameters . The “Potential volts” refer also referred as polarisation potential. For steel in concrete, a polarized potential more negative than –800 mV measured with respect to silver/silver chloride reference electrode is required by EN 12696. The reader shall not confused potential values given by different reference electrodes. In this case, the -1100 mV of the Cu/CuSO4 are equal to -1044 mV of Ag/AgCl 0.05M KCl. Simplistically, electrochemical capacity is the result of Faraday's law. For example, pure zinc has a theoretical maximum capacity of 820 Ah per kilogram. This means that if a zinc anode were to discharge one ampere continuously, one kilogram would be consumed in 820 hours. If this kilogram was discharging one tenth of an ampere, it would be totally consumed in 8200 hours or 48 weeks. Actually, zinc anodes operate, typically, at about 95 % efficiency. This means that the energy content available for useful current output would be 820 x 0.95, or 779 Ah per kg.
  • 26. Basic Principles of Galvanic Protection Cathodic protection current density is currently defined by regulation. Even though differences can be easily identified, the minimum requirements remain approximately fixed.
  • 27. Basic Principles of Galvanic Protection Variations in the range of cathodic protection current density are mostly acknowledged by the diagram below. Here the reader can study, different cathodic protection current density requirements as per chloride ions concentration in concrete. SCE refers to Saturated Calomel Electrode.
  • 28. Basic Principles of Galvanic Protection Variations in cathodic protection current densities throughout the years have been classified in order to provide a sound basis over which repair cost can be realistically estimated. Current density requirements along with the surface area of steel to be protected (demand), define among others parameters, whether ICCP or galvanic protection is to be used. It is clear that high current demand for a large period of time consumes faster the sacrificial anode while at the same time might not be able to generate the required potential. The reader can easily relate the above table to that of slide no. 19 .
  • 29. Axios Bridge Galvanic Protection Tendon tracks, tendon anchors and non sealed joints create a rather complex scenario for uniform polarisation potential distribution. In the case of existing bridges offering limited accessibility, the problem exponentially increases leading to over-polarisation issues and potential hydrogen gas generation . The use of control sensors and complex programming of the cathodic protection control unit can sometimes only provide limited solution. In addition to the above, a cathodic protection control unit is usually unprotected from actions of vandalism and theft. For the above reasons, the use of Galvanic protection was chosen. Due to the large surface area and the difficulty in boring to encase embedded anodes, the use of Zinc / Hydrogel Anode or known as Zinc layer Adhesive Anode or ZLA. This anode consisted of a zinc foil, which measured 0.25 mm thick by 0.25 m wide , a conductive adhesive gel (3M Company’s Hydrogel™) bonded to one side of the foil, and a release paper sticking to the other side of the adhesive gel. In this application, ZLA provided by Mapei under the commercial name of Mapeshield E25 was used. Mapeshield E25 provides 455 grams of Zinc per running meter and is certified according to EN 12696.
  • 30. Axios Bridge Galvanic Protection Calculations and the subsequent plans were based on an initial protection current density of 5mΑ/m2 for the first 12 months followed by a value of 1.5mΑ/m2 for the remaining protection period. A 10 year overall protection period was considered. A safety factor of 1.1 was implemented. Two reference electrodes were positioned to monitor the tendons. The overall anode performance level was set at 80%.
  • 31. Application of Galvanic Protection - Step A - Hydro blasting 500 Bar Rigorous cleaning of the surface is imperative for Hydrogel to maintain a uniform and maximum ion current flow. The pressure refers to nozzle output.
  • 32. It is important to note that the nozzle to surface distance was kept between 5-10 cm. It is a common mistake of contractors performing hydro blasting to operate at longer distances. A practical tip identifying correct distance (depends on concrete strength, pressure and flow rate of the unit) is to achieve concrete skin (2-4mm) removal at a rate of > 0.1 m2/min. Application of Galvanic Protection - Step A - Hydro blasting 500 Bar
  • 33. Hydro-blasting at 500 bars, is usually enough to remove loose concrete due to spalling. Application of Galvanic Protection - Step A - Hydro blasting 500 Bar
  • 34. Prior to any patch repair it is important to check for electrical continuity. In the case where electrical continuity (a value <0.1V at DC setting indicatives continuity) is not obtained, the contractor shall proceed with artificial connection using the fixings and a piece of the recommended cathodic protection cable. The photograph shows a “bridge” used to achieve electrical continuity between two stirrups. Connections and fixings are protected using a conductive sealant. Application of Galvanic Protection – Step B – Local Patch Repairs
  • 35. Fixing to steel reinforcement is made using a low voltage cable. Usually type FG7R-0.6/1KV 1 Χ 8. In this particular application connection was made using stainless steel rivets and ring eye terminals. Application of Galvanic Protection – Step B – Local Patch Repairs
  • 36. Patch repair grout should be according to ΕΝ 1504 parts 2,3 while is mandatory to have an electrical resistivity < 10 KOhm cm (ΕΝ 12696). This is because the grout should allow the unrestricted row of ions generated by the Zinc / Hydrogel Anode. Application of Galvanic Protection – Step B – Local Patch Repairs
  • 37. Sufficient time shall be allowed prior to the application of the ZLA over the patched area. In such applications, grout strength is not an indicative parameter. The contractor shall measure the electrical resistivity using a Wenner Probe. Once the reading is within its declared value by the manufacturer, the contractor can proceed to the next step. Application of Galvanic Protection – Step B – Local Patch Repairs
  • 38. After removing the releasing sheet protecting Hydrogel from air, ZLA can be applied on concrete surface. A rubber mallet is usually used to secure one edge of the anode sheet. A rubber roller is finally used for final placement and straightening. The stiffness of ZLA and the usually uneven surface of concrete, usually prevent air being trapped underneath. Application of Galvanic Protection – Step C – Placing the ZLA
  • 39. A covermeter is used to identify the location and cover thickness of reinforcement intending to receive connection to the anode. The action should be performed prior to the placement of ZLA since measurement over zinc cancels the operation of the covermeter. Application of Galvanic Protection – Step C – Placing the ZLA
  • 40. A wedge anchor is used to connect reinforcement to ZLA. The location has been previously identified by covermeter (reinforcement free zone) and indicated on the ZLA using a marker. Correct connection once again requires electrical continuity measurement. Application of Galvanic Protection – Step C – Placing the ZLA
  • 41. The process is repeated until all ZLA sheets have been placed. Note that all required connections to reinforcement are established. That allows the contractor to continuously check and recheck electrical continuity. A valid order is to start the check between the first ZLA and the last reinforcement connection and continue the process inwards, i.e. the second ZLA or reinforcement connection with the N-1 reinforcement connection (N is the total number of connections), the third ZLA or reinforcement connection with the N-2 reinforcement connection, etc. Connection to steel was made using the following steps, a) Detection of location and depth of steel using covermeter, b) Drilling of concrete using a Ø40 bit until reaching cover thickness, c) Drilling steel reinforcement using a Ø4 Cobalt bit. d) Placement of eye terminal on rivet and fixing using a pop rivet gun e) Checking of electrical continuity with a multimeter f) Placement of conductive sealant over the connection. Application of Galvanic Protection – Step C – Placing the ZLA
  • 42. Once all ZLAs have been placed and checked for electrical continuity, their edges shall be protected by moisture attacking the Hydrogel. In this application Mapeflex PU40 was used. A layer of width around 30mm and thickness 2-3mm is enough. Application of Galvanic Protection – Step C – Placing the ZLA
  • 43. Sealing of ZLAs with Mapeflex PU40. Application of Galvanic Protection – Step C – Placing the ZLA
  • 44. Application of Galvanic Protection – Step D – Placement of Reference Anodes Placement of two reference electrodes type Ag/AgCl/KCl (Castle Electrodes Ltd, LD10) according to plans. Reference electrodes allows us to perform depolarisation testing according to EN 12696.
  • 45. It is imperative to do an initial potential measurement to safeguard initialisation and uniform voltage distribution of the circuit. In this case, values of -417 mV και -380 mV (Ag/AgCl) were measured from the two reference electrodes. Εφαρμογή Καθοδικής Προστασίας – Στάδιο Ε – Τοποθέτηση Κυτίων ΕλέγχουApplication of Galvanic Protection – Step E – Junction Boxes and Cable Conduits
  • 46. Complete sealing of ZLA using Mapelastic Smart. Bond strength on ZLA has a declared value of >1,6 MPa. Sealing protects the anode from consumption due to air oxidation. Application of Galvanic Protection – Step F – Sealing the Circuit
  • 47. Final form of ZLA application Application of Galvanic Protection
  • 48. Depolarisation values 7 days after initialisation. All three EN 12696 requirements are met. Instant Off Value R1=-793 mV Instant Off Value R2=-761 mV Application of Galvanic Protection – Depolarisation Values - 7 days
  • 49. Instant Off Value R1=-835 mV Instant Off Value R2=-856 mV Application of Galvanic Protection – Depolarisation Values - 30 days Depolarisation values 30 days after initialisation. All three EN 12696 requirements are met.
  • 50. Advantages and Disadvantages of ZLAs compared to ICCP Advantages Low initial investment cost, The application does not require specialised equipment and personnel, Significantly reduces damage due to concrete boring required for ICCP anodes, Protection can last over 25 years as in the case of carbonation, Relatively easy calculations based Faraday’s equation, The anode can be easily replaced, The potential for hydrogen gas generation is negligible, It does not require control unit, Certified according to ΕΝ 12696, BS 7361 and AS 2382.5. Disadvantages High cost per year when protection over 40 years is needed. Limited performance and protection when high current density is required, It is highly unlikely to cause chloride ions extraction, It is sensitive to temperature and moisture changes.
  • 51. Characteristic Applications of ZLAs Bridges Balconies Local repairs
  • 52. Facades Slabs Beams Characteristic Applications of ZLAs Final sealing can be painted or plastered. In the case of plastering, surface treatment of the sealant using quartz sand 0.85-1.2 mm is recommended.
  • 53. Characteristic Applications of ZLAs on bridges from around the World
  • 54. List of key materials used in the application More information can be found in http://www.mapei.com/GR-EL/ and http://www.mapei.com/public/GB/linedocument/Cathodic_Protection_GB.pdf
  • 55. Application of Galvanic Protection – Project Partners