SlideShare a Scribd company logo
1 of 49
Download to read offline
VLF Testing of Cables Using IEEE 400.2™
John Densley
ArborLec Solutions Inc.
Outline
• Aging/diagnostics basics
• Diagnostic testing of MV cables
• IEEE 400.2 – 2013
• Future trends
• Conclusions
Aging
• Changes in properties that occur with time
due to the applied stresses, electrical,
thermal, mechanical and environmental
(chemical). Can act singly or synergistically
• Changes may cause permanent damage that
may affect ability to perform specified
functions. This is sometimes referred to as
degradation
• Changes can lead to failure
Polymer cable insulation aging & failure
mechanisms
• Insulation aging usually at defects (voids, contaminants
or protrusions) → partial discharge (PD), water treeing
(WT), thermal aging
• Failure mechanism → Electrical treeing (ET), thermal
runaway
Aging, e.g. PD, can take a long time initiate failure →
possible to detect with diagnostic test
Failure, e.g. ET, usually takes place quickly → not easy to
pick up with diagnostic test
• Other types of failure:
– voltage transients → intrinsic BD
– abnormal high temperature → mechanical or electrical failure
– Mechanical damage (dig-in, thermomechanical)
Partial discharges
• Local BD of gas in voids,
delaminations at interfaces
or protrusions (electrical
trees)
• A partial discharge is a
current pulse of some
nanoseconds duration that
causes minute high
frequency currents to flow
in the circuit (100’s of MHz)
Simplified PD sequence
Initial
Discharge
Return
Discharge Second
Discharge
Electrical Field Conditions
-20
-15
-10
-5
0
5
10
15
20
0 45 90 135 180 225 270 315 360
Phase Angle
Voltage/ElectricField
Appl. Voltage [kV]
Applied Field in Void [kV/mm]
Void Breakdown Strength
Void Field [kV/mm]
7
-1.5
-1
-0.5
0
0.5
1
1.5
-15
-10
-5
0
5
10
15
0 45 90 135 180 225 270 315 360
ReferenceVoltage[kV]
PDMagnitude[mV]
Phase Angle
Partial discharge pulse sequence
PD Signal Reference Voltage
Electrical treeing
• Localized breakdown of
insulation from voids,
sharp protrusions or
water trees that increase
the local electrical stress
• Local stress at tip at tree
initiation can be >100
kV/mm
• Once tree has initiated its
growth is caused by PD in
the channels (<20 μm
dia.)
Electrical
tree
Water
tree
Electrical treeing
Growth
• The PD leave charges on the
walls of the channels → stress
that can be > applied stress
• ET shape changes with
applied field/frequency in
insulation → non-linear
growth with time, e.g., rate at
60 Hz less than at 0.1 Hz and
rate at 0.1 Hz is less than 0.01
Hz
Breakdown through electrical
tree
9
Water treeing
 Occurs at stress enhancements such as
protrusions, contaminants or voids
 Moisture always present
 Soluble contaminants such as salts are
particularly harmful
 Degradation is slow taking several years
 Final failure due to electrical tree (PD) from
the water tree or thermal runaway for
bridging trees
 Vented tree from semicon surface or bow-tie
tree from contaminant or void
 Responsible for failures of many older
vintage cables (extruded insulation)
 No PD during initiation or growth
Other stresses
• PD and WT are the main aging mechanisms of
extruded MV cables
Therefore:
• Will not consider aging due to mechanical (M)
and thermal (T) stresses
• M and T accelerate electrical aging
We can now look at diagnostic testing
Diagnostic tests
• A diagnostic test is a field test made during the
operating life of a cable system that is intended to
determine and locate aging or degradation that may
cause failure of cable system - Defined in CIGRE WG21-
05 Report, 1994
• May be on-line or off-line
• Tests may be one-time only or periodic to establish
trends
• Can look at metallic and/or insulating parts
The main purposes of a diagnostic test are to reduce the
number of failures in service and provide information
on the serviceability of the cable system
How can we do diagnostics on cables?
Must know details of the cable system to be tested
• Need to know probable aging and failure mechanisms
• Need to measure properties or characteristics that give
an indication of how much aging has occurred
• Would like to know rate of aging
• Need to interpret data to assess circuit condition and
give an indication of serviceability
One of the most important diagnostic tests is a periodic
visual inspection to establish trends
Let’s look at water treeing
Properties of water treed insulation
1. Lower AC Breakdown Voltage
2. Small increase in capacitance (C) with voltage
3. Increase in Tan Delta (dissipation factor (DF))
4. Tan Delta (TD) increases with voltage
5. Tan Delta changes with time at constant V
6. Decrease in insulation resistance (IR)
7. Loss Current Waveform distorted
8. Increased DC leakage current
9. Space charge/polar species in trees
10. No PD until just prior to failure
Numbers 2 to 8 are bulk measurements
IEEE Std 400™-2012
(Revision of IEEE Std 400-2001)
IEEE Guide for Field Testing and
Evaluation of the Insulation of
Shielded Power Cable Systems
Rated 5 kV and Above
IEEE Std 400™-2012
The guide lists the various field test methods that are
currently available, or under development, to evaluate
the insulation of shielded power cable systems.
The guide:
• Rated 5 kV and above
• Describes the tests, gives advantages and
disadvantages, suggested applications, and typical
results
• Does not give test voltage levels or test durations
Guides covering particular test methods are available in
the form of IEEE 400 “point” documents. These Guides
give voltage levels and durations.
Field test categories (1)
Installation tests
• Conducted after cable installation but before jointing
(splicing) or terminating or energizing
• Intended to detect shipping, storage or installation damage
Acceptance tests
• Made after cable system installation, including terminations
and joints, but before the cable system is placed in normal
service
• Intended to detect installation damage and to show any gross
defects or errors in installation of other system components
Field test categories (2)
Maintenance tests
• Performed on cable systems that have been aged in service
for an extended period of time
• Intended to detect deterioration and to check the
serviceability of the system
• Need to consider failure history, testing and installation
history, cable system component makeup, importance of
cable in system
Voltage Sources
• 60 Hz AC (used for transmission class)
• VLF (used for MV and lower voltage
transmission class) – IEEE 400.2
• Damped ac (DAC) – IEEE 400.4 (in prep.)
• DC – IEEE 400.1
These sources may be used in one of two
modes: diagnostic (Tan δ, PD, etc.) or
withstand (Simple and Monitored)
400 “Point” documents (1)
IEEE Std 400.1 ™ – 2007: IEEE Guide for Field
Testing of Laminated Dielectric, Shielded Power
Cable Systems Rated 5 kV and Above with High
Direct Current Voltage
• Oil/paper cables only, not to be used for extruded dielectric
cables
• Includes a table of withstand HVDC test voltages (acceptance
and maintenance) for cables rated 5 kV to 500 kV
• Usual to measure current after 2 and 15 minutes
400 “Point” documents (2)
• IEEE Std 400.3™-2006: IEEE Guide for Partial Discharge Testing of
Shielded Power Cable Systems in a Field Environment
• No tables of test voltages or maximum allowable discharge
magnitudes for cables with different ratings, unlike factory/routine
tests
• Describes principles of methods capable of detecting, measuring
and locating partial discharges from defects and damage in installed
shielded power cable systems
• Usually cannot assume lumped capacitance as for factory tests as
long cable lengths have to be treated as transmission lines
Guide is presently under revision – more comprehensive than original
version and will probably contain test voltages for both distribution
and transmission class cables
400 “Point” documents (3)
• P400.4™/D8: Draft Guide for Guide for Field-
Testing of Shielded Power Cable Systems
Rated 5 kV and Above with Damped
Alternating Current Voltage (DAC)
• Presently out for ballot
• Recommended test values are included in an Annex for
engineering information as not enough practical data are
available
• A number of damped oscillations between 20 Hz and 500 Hz
applied at each test level
400 “Point” documents (4)
IEEE Std 400.2™-2013: IEEE Guide for Field
Testing of Shielded Power Cable Systems Using
Very Low Frequency (VLF) (less than 1 Hz)
• Cables rated 5 kV to 69 kV
• Guide valid for extruded & oil/paper cables
• Includes tables of withstand (installation, acceptance and
maintenance) tests
• Includes tables of tangent delta (dissipation factor) criteria –
“no action required”, “further study required” & “action
required”
VLF testing
• Mostly used at distribution voltage levels
• Can be a simple or monitored (tan δ and/or PD) withstand
test
• VLF defined as < 1 Hz but most common frequency is 0.1 Hz.
Very long lengths tested at 0.05 Hz or 0.02 Hz.
• Must be careful when interpreting partial discharge data
acquired at VLF conditions since the physics of PD has a
complex relationship with frequency
• Maintenance testing of medium voltage cables with VLF is
popular in North America (IEEE 400.2™), Asia and Europe
(Cenelec Standard)
• Present voltage sources limited to cables rated 138 kV and
lower (200 kV peak)
• Two waveforms – sinusoidal and cosine-rectangular
24
VLF waveforms
Sinusoidal waveform
HVA30 @5kV RMS with 280feet XLPE Load
-8000
-6000
-4000
-2000
0
2000
4000
6000
8000
Voltage(kV)
Cosine rectangular waveform
SEBAKMT VLF40 @5kv RMS with 280feet XLPE Load
-8000
-6000
-4000
-2000
0
2000
4000
6000
Voltage(kV)
25
Examples of commercially available VLF Sources
- courtesy of NEETRAC
VLF withstand testing (1)
• Test integrity of circuit
• Test frequency is between 0.01 Hz and 1 Hz (0.1 most
common). <0.1 Hz used for longer length circuits
• As electrical tree grows faster at 0.1 Hz than at 50/60
Hz, more likely to cause failure during test
• Test values based on most used practices
• Recommended test duration is 30 minutes with 60
minutes allowed for critical circuits. European standard
is 60 minutes
• A test time within the range 15 – 30 minutes may be
considered if the monitored characteristic remains
stable for at least 15 minutes and no failure occurs
VLF withstand testing (2)
• IEEE 400.2 -2013 test voltages are based on peak to
peak voltages being equal for sinusoidal and cosine-
rectangular voltage waveforms (based on breakdown
tests on aged XLPE cables)
• European standard test voltages based on rms values
being equal for the two waveforms (based on electrical
tree growth data)
• If a circuit fails during test → repaired or replaced →
re-tested using a complete 30 minute test, preferably
monitored withstand test. It is recommended to retest
each section with VLF-TD, VLF-DTD, VLF-TDTS or VLF-
PD
VLF withstand test voltages for sinusoidal
waveform1 IEEE 400.2 - 2013
• Note 1: If the operating voltage is a voltage less than rated voltage, it is recommended that the
maintenance test voltages should be those corresponding to the operating voltage class.
• Note 2: The maintenance voltage is about 75% of the acceptance test voltage magnitude.
• Note 3: Some existing test sets have a maximum voltage that is up to 5% below the values listed
in the Table. These test sets are acceptable to be used. However, there is a risk that the cable
may be "undertested" due to a combination of lower test voltage and allowed uncertainty of the
measuring circuit.
Cable System
Rating
(Phase to Phase)
[kV]
Installation
(Phase to Ground)
Acceptance
(Phase to Ground)
Maintenance2
(Phase to Ground)
[kV rms] [kV peak] [kV rms] [kV peak] [kV rms] [kV peak]
5 9 13 10 14 7 10
8 11 16 13 18 10 14
15 19 27 21 30 16 22
20 243 343 26 37 20 28
25 293 413 32 45 243 343
28 32 45 363 513 27 38
30 34 48 38 54 293 413
35 39 55 44 62 33 47
46 51 72 57 81 43 61
69 75 106 84 119 63 89
VLF withstand test voltages for cosine-
rectangular waveform1 IEEE 400.2 - 2013
• Note 1: If the operating voltage is a voltage class lower than the rated voltage of the
cable, it s recommended that the maintenance test voltages should be those
corresponding to the operating voltage class.
Cable System
Rating
(Phase to Phase)
[kV]
Installation
(Phase to Ground)
Acceptance
(Phase to Ground)
Maintenance2
(Phase to Ground)
[kV
rms]
[kV peak] [kV rms] [kV peak] [kV rms] [kV peak]
5 13 13 14 14 10 10
8 16 16 18 18 14 14
15 27 27 30 30 22 22
20 34 34 37 37 28 28
25 41 41 45 45 34 34
28 45 45 51 51 38 38
30 48 48 54 54 41 41
35 55 55 62 62 47 47
46 72 72 81 81 61 61
69 106 106 119 119 89 89
Note on dissipation factor
Tan , Dissipation Factor, or Loss
Factor  Power Factor
Tan  = Ir/Ic = / = 1/[2CR]
• Tan  is a measure of polar
and dipolar movement
• Polar/dipolar species  bulk
test  sensitive to water,
high density of WT), ageing
• Tan  /dielectric
spectroscopy are bulk
measurements. The average
of the whole length of the
cable and its accessories is
measured.
31
• Careful interpretation of tan
 may be needed:
– Short sections of high Tan 
in a long cable may not
significantly increase the
overall Tan 
– In field measurements,
certain types of accessories
can give high tan  values
Voltage dependence of 0.1 Hz dissipation factor
of new and service-aged XLPE-insulated
medium voltage cables - Baur (1995 JICABLE),
tan  . 10-3
0
1
2
3
4
5
6
7
0 0.5 1 1.5 2 2.5 3
U / U 0
0,1Hzdissipationfactor
reference cable (new)
slightly service-aged (1)
moderately service-aged (2)
moderately service-aged (3)
strongly service-aged (4)
.
32
VLF tan δ – aged cables
IEEE 400.2 - 2013 gives:
• Criteria for aged (WT) XLPE and EPR cables
– No action required
– Further study recommended
– Action required
• Criteria based on tan  time stability (TDTS),
voltage tip-up (DTD) and mean value of tan 
(TDM)
33
Criteria
• no action required
– Cable system can be returned to service, but may be
retested at some later date to observe the trend in tan
delta
• action required
– Unusually high set of tan delta characteristics which may
indicate poor insulation condition and should be considered for
further testing or replacement or repair immediately
• further study advised
– Additional information is needed to make an assessment
→ failure history, additional testing
Parameters used to establish criteria
• Time stability of tan delta at Uo (TDTS)
– At least six single TD measurements at intervals of 10
seconds between each measurement at 0.1 Hz
– Measure mean and standard deviation
• Voltage tip-up of tan delta between 0.5 Uo
and 1.5 Uo (DTD)
• Mean value of tan delta at Uo (TDM)
TDTS most sensitive to degradation, then DTD
which is more sensitive than TDM
How numerical values of criteria derived
• Derived from cumulative distribution function
of the maintenance measurement data of tan δ
(time stability (TDTS) voltage tip-up (DTD) and
mean value (TDM)) obtained for aged cable
systems, mainly in North America
• Tables use the probability criteria of 80% based
on the Pareto principle (best ranked 80%
account for only 20% of the problems) and 95%
probability
36
Cumulative distribution of all cable system TDTS
values at U0 from IEEE 400.2-2013
Cumulative distribution of all cable system DTD
Criteria from 400.2 - 2013
Cumulative distribution of all cable systems
TDM values from IEEE 400.2 - 2013
• Criteria for PE, filled
polymer and PILC are
values at 80% and 95%
probabilities
• Utilities are encouraged
to develop their own
data plots
39
Assessment criteria for PE based insulations - IEEE
400.2 - 2013
Historical figures of merit for condition assessment of service-
aged PE-based insulations (i.e. PE, XLPE, and TRXLPE) using 0.1 Hz
40
Condition
Assessment
VLF-TD Time
Stability (VLF-TDTS
measured by
standard deviation
at Uo
[10-3]
Differential VLF-TD
(VLF-DTD)
(difference in mean
VLF-TD) between
0.5 Uo and 1.5 Uo
[10-3]
Mean VLF-TD at
Uo
[10-3]
No Action
Required
<0.1 and <5 and <4
Further Study
Advised 0.1 to 0.5 or 5 to 80 or 4 to 50
Action
Required >0.5 or >80 or >50
Assessment of service-aged OIP insulations
Condition
Assessment
VLF-TD Time Stability
(VLF-TDTS measured
by standard deviation
at Uo
[10-3]
Differential VLF-TD
(VLF-DTD) (difference
in mean VLF-TD)
between 0.5 Uo and
1.5 Uo
[10-3]
Mean VLF-
TD at Uo
[10-3]
No Action
Required
<0.1 and -35 to 10 and <85
Further Study
Advised
0.1 to 0.4 or -35 to -50
or
10 to 100
or 85 to 200
Action
Required
>0.4 or <-50
or
>100
or >200
No action required criteria for service-aged
filled insulations - IEEE 400.2 - 2013
Condition
Assessment
Filled Insulation
System
VLF-TD Time
Stability (VLF-
TDTS measure
d by standard
deviation
at Uo
[10-3]
Differential
VLF-TD (VLF-
DTD)
(difference in
mean VLF-TD)
between 0.5
Uo and 1.5 Uo
[10-3]
Mean VLF-
TD at Uo
[10-3]
No Action Required
* If it is not possible
to definitively identify
a Filled Insulation
<0.1
a
n
d
<5
a
n
d
<35
Carbon-filled (Black)
EPR
<0.1 <2 <20
Mineral-filled (Pink)
EPR
<0.1 <4 <20
** Discharge resistant
EPR
<0.1 <6 <100
** Mineral-filled XLPE - - <100
Further study and action required criteria for
service-aged filled insulations - IEEE 400.2 - 2013
Condition
Assessment
Filled Insulation System VLF-TD Time
Stability (VLF-
TDTS measured
by standard
deviation
at Uo
[10-3]
Differential VLF-
TD (VLF-DTD)
(difference in
mean VLF-TD)
between 0.5 Uo
and 1.5 Uo
[10-3]
Mean VLF-TD at
Uo
[10-3]
Further Study
Advised
* If it is not possible to
definitively identify a Filled
Insulation
0.1 to 1.3
o
r
5 to 100
or
35 to 120
Carbon-filled (Black) EPR 0.1 to 2.7 2 to 120 20 to 100
Mineral-filled (Pink) EPR 0.1 to 1 4 to 120 20 to 100
** Discharge resistant EPR 0.1 to 1 6 to 10 100 to 350
** Mineral-filled XLPE - - 100 to 350
Action
Required
* If it is not possible to
definitively identify a Filled
Insulation
>1.3
o
r
>100
or
>120
Carbon-filled (Black) EPR >2.7 >120 >100
Mineral-filled (Pink) EPR >1 >120 >100
** Discharge resistant EPR >1 >10 >350
** Mineral-filled XLPE - - >350
If high values of TDTS, DTD and or TDM
• 1. Can compare results between different phases of the same
segment or sequential sections to better place the result in context
• 2. Can divide circuits into sub sections and retest, perform a visual
inspection of circuit components where accessible and replace
suspect parts, or replace the accessories, especially if they appear
to be old, and re-measure
• 3. Can perform additional testing in the form of a monitored
withstand, non-monitored withstand, or partial discharge test
should they wish to identify a localized problem
• 4. Can separate the response of terminations and other
components if connected from cables plus splices, by, if practical,
adding guard circuits at the terminations
VLF testing - advantages
• Inexpensive compared to AC HiPot testing
• Power supply light in weight
• Simple withstand test easy to perform
• Non-expert test
• IEEE Std 400.2™ gives test voltages
• Effective to measure water tree degradation
• Used for PE and EPR based, and OIP cables
• Monitored withstand testing can measure
tangent delta, insulation resistance and partial
discharge characteristics → better assessment of
cable insulation by picking out defects that do not
fail during the test
•
VLF testing - disadvantages
• Cable systems must be taken out of service for
testing
• Possible issues with charge injection and trapped
charge when testing at frequencies less than 0.1 Hz
• Two voltage waveforms available, sinusoidal and
cosine - rectangular
• Not straight forward to interpret PD data acquired
during VLF conditions
• When testing cables with extensive insulation
degradation, simple VLF withstand testing can result
in repeated failures, although this rarely occurs in
practice
• Simple withstand testing does not monitor the effect
of the test on the cable during the voltage
application and can fail to detect a potentially
destructive defect
Recent work - effect of test frequency
• Long lengths tested at <0.1 Hz due to power
limitation
• Should lower frequency be tested longer?
• NEETRAC grew WT in PE & EPR and subjected
samples to BD tests at 0.1 Hz and 0.05 Hz
• BD strength was lower at 0.05 Hz (6.7 kV/mm)
than at 0.1 Hz (8.5 kV/mm) – tree growth rate?
• Conclusion – no need to test for longer time at
0.05 Hz
Future work
• Encourage utilities to do diagnostic tests
• Encourage utilities to develop and use their own
cumulative distributions for VLF
• Retest cables to verify performance (trends)
• Re-establish Discussion Group FD03 to discuss
data
• Develop other criteria, e.g., Delta tip-up
(TD(1.5Uo) - TD(Uo)) - (TD(Uo) - TD(0.5Uo))
• Prepare standard for continuous AC test for MV
Conclusions
• VLF simple withstand and monitored withstand are
most commonly used diagnostic tests on MV cables
• Larger utilities have a cable diagnostic program (why?)
• The majority of utilities do not do diagnostic tests on
their MV cable systems
• Testing at less than 0.1 Hz does not require a longer
test time
• Refinements to the tan delta criteria are under study
and should be incorporated in the next revision of
400.2

More Related Content

What's hot

ETAP - Arc flash analysis done Right
ETAP - Arc flash analysis done RightETAP - Arc flash analysis done Right
ETAP - Arc flash analysis done RightHimmelstern
 
Cable fault location methods (Megger)
Cable fault location methods (Megger)Cable fault location methods (Megger)
Cable fault location methods (Megger)AHMED MOHAMED HEGAB
 
cable ampacity calculations- IEC
cable ampacity calculations- IECcable ampacity calculations- IEC
cable ampacity calculations- IECJoe Khan
 
Bts-site-installation
 Bts-site-installation Bts-site-installation
Bts-site-installationAli Usman
 
High Voltage On-Site Testing with Partial Discharge Measurement (Cigre 502)
High Voltage On-Site Testing with Partial Discharge Measurement (Cigre 502)High Voltage On-Site Testing with Partial Discharge Measurement (Cigre 502)
High Voltage On-Site Testing with Partial Discharge Measurement (Cigre 502)AHMED MOHAMED HEGAB
 
Installation & maintenance of power cable
Installation & maintenance of power cableInstallation & maintenance of power cable
Installation & maintenance of power cableAmbuj Mishra
 
- IEEE Std C57.91-1995
 - IEEE Std C57.91-1995 - IEEE Std C57.91-1995
- IEEE Std C57.91-1995ShroukHamdy5
 
Vocation Training Program 50MW solar PPT By Hari Singh Rathore
Vocation Training  Program 50MW solar PPT By Hari Singh RathoreVocation Training  Program 50MW solar PPT By Hari Singh Rathore
Vocation Training Program 50MW solar PPT By Hari Singh RathoreHari Singh Rathore
 
Interrupteurs iacm INES MAX
Interrupteurs iacm INES MAX Interrupteurs iacm INES MAX
Interrupteurs iacm INES MAX Amzil Yassine
 
Electrical Engineering (EE) presentation on POWER CABLES
Electrical Engineering (EE) presentation on POWER CABLESElectrical Engineering (EE) presentation on POWER CABLES
Electrical Engineering (EE) presentation on POWER CABLESPritish Parihar
 
Design and construction of underground cable transmission line
Design and construction of underground cable transmission lineDesign and construction of underground cable transmission line
Design and construction of underground cable transmission lineFazlur Rahman
 
Current carrying capacities & other technical tables
Current carrying capacities & other technical tablesCurrent carrying capacities & other technical tables
Current carrying capacities & other technical tablesasif raza
 
ETAP - Harmonics Analysis
ETAP - Harmonics AnalysisETAP - Harmonics Analysis
ETAP - Harmonics AnalysisHimmelstern
 

What's hot (20)

ETAP - Arc flash analysis done Right
ETAP - Arc flash analysis done RightETAP - Arc flash analysis done Right
ETAP - Arc flash analysis done Right
 
Cable fault location methods (Megger)
Cable fault location methods (Megger)Cable fault location methods (Megger)
Cable fault location methods (Megger)
 
IEEE-std80.pdf
IEEE-std80.pdfIEEE-std80.pdf
IEEE-std80.pdf
 
cable ampacity calculations- IEC
cable ampacity calculations- IECcable ampacity calculations- IEC
cable ampacity calculations- IEC
 
Bts-site-installation
 Bts-site-installation Bts-site-installation
Bts-site-installation
 
Iec 60364 4-442
Iec 60364 4-442Iec 60364 4-442
Iec 60364 4-442
 
High Voltage On-Site Testing with Partial Discharge Measurement (Cigre 502)
High Voltage On-Site Testing with Partial Discharge Measurement (Cigre 502)High Voltage On-Site Testing with Partial Discharge Measurement (Cigre 502)
High Voltage On-Site Testing with Partial Discharge Measurement (Cigre 502)
 
Ieee 80 informe
Ieee 80 informeIeee 80 informe
Ieee 80 informe
 
Installation & maintenance of power cable
Installation & maintenance of power cableInstallation & maintenance of power cable
Installation & maintenance of power cable
 
- IEEE Std C57.91-1995
 - IEEE Std C57.91-1995 - IEEE Std C57.91-1995
- IEEE Std C57.91-1995
 
Electrical Heat Tracing
Electrical Heat TracingElectrical Heat Tracing
Electrical Heat Tracing
 
Vocation Training Program 50MW solar PPT By Hari Singh Rathore
Vocation Training  Program 50MW solar PPT By Hari Singh RathoreVocation Training  Program 50MW solar PPT By Hari Singh Rathore
Vocation Training Program 50MW solar PPT By Hari Singh Rathore
 
Interrupteurs iacm INES MAX
Interrupteurs iacm INES MAX Interrupteurs iacm INES MAX
Interrupteurs iacm INES MAX
 
Electrical Engineering (EE) presentation on POWER CABLES
Electrical Engineering (EE) presentation on POWER CABLESElectrical Engineering (EE) presentation on POWER CABLES
Electrical Engineering (EE) presentation on POWER CABLES
 
Design and construction of underground cable transmission line
Design and construction of underground cable transmission lineDesign and construction of underground cable transmission line
Design and construction of underground cable transmission line
 
TRANSFORMERS
TRANSFORMERSTRANSFORMERS
TRANSFORMERS
 
Current carrying capacities & other technical tables
Current carrying capacities & other technical tablesCurrent carrying capacities & other technical tables
Current carrying capacities & other technical tables
 
ETAP - Harmonics Analysis
ETAP - Harmonics AnalysisETAP - Harmonics Analysis
ETAP - Harmonics Analysis
 
Busduct catalogue
Busduct catalogueBusduct catalogue
Busduct catalogue
 
Subestacion mtbt
Subestacion mtbtSubestacion mtbt
Subestacion mtbt
 

Viewers also liked

Seminar on Partial Discharge detection methods
Seminar on Partial Discharge detection methodsSeminar on Partial Discharge detection methods
Seminar on Partial Discharge detection methodsHarshit Bhandari
 
Partial Discharge Detection Products by EA Technology
Partial Discharge Detection Products by EA TechnologyPartial Discharge Detection Products by EA Technology
Partial Discharge Detection Products by EA TechnologyRyan McFallo
 
Self-healing high voltage electrical insulation materials
Self-healing high voltage electrical insulation materialsSelf-healing high voltage electrical insulation materials
Self-healing high voltage electrical insulation materialsAnand Parakkat Parambil
 
Results of 10 years after installation tests with partial discharge detection...
Results of 10 years after installation tests with partial discharge detection...Results of 10 years after installation tests with partial discharge detection...
Results of 10 years after installation tests with partial discharge detection...HighVoltageDUT
 
High Voltage, Inc. Products Presentation Short Version
High Voltage, Inc. Products Presentation Short VersionHigh Voltage, Inc. Products Presentation Short Version
High Voltage, Inc. Products Presentation Short VersionMichael T. Peschel
 
Heinputter 2
Heinputter 2Heinputter 2
Heinputter 2Thang Nd
 
Insulation testing of power cable
Insulation testing of power cableInsulation testing of power cable
Insulation testing of power cableSyed Atif Naseem
 
Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...
Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...
Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...Thorne & Derrick International
 
High voltage transmission
High voltage transmissionHigh voltage transmission
High voltage transmissionSHIVLAL MOHAL
 
MS Thesis Lakshya MIttal
MS Thesis Lakshya MIttalMS Thesis Lakshya MIttal
MS Thesis Lakshya MIttalLakshya Mittal
 
Tan delta test for power transformers
Tan delta test for power transformersTan delta test for power transformers
Tan delta test for power transformersjibinjoy1988
 
IEEE 848 Standard Procedure For The Determination Of Tthe Ampacity Derating o...
IEEE 848 Standard Procedure For The Determination Of Tthe Ampacity Derating o...IEEE 848 Standard Procedure For The Determination Of Tthe Ampacity Derating o...
IEEE 848 Standard Procedure For The Determination Of Tthe Ampacity Derating o...Thorne & Derrick International
 
High voltage cable insulation systems
High voltage cable insulation systemsHigh voltage cable insulation systems
High voltage cable insulation systemsSanket Tambakhe
 
EE-55 Power Cables Testing & Fault Location
EE-55 Power Cables Testing & Fault LocationEE-55 Power Cables Testing & Fault Location
EE-55 Power Cables Testing & Fault LocationRina Florentes
 

Viewers also liked (20)

Basic Partial Discharge
Basic Partial DischargeBasic Partial Discharge
Basic Partial Discharge
 
Seminar on Partial Discharge detection methods
Seminar on Partial Discharge detection methodsSeminar on Partial Discharge detection methods
Seminar on Partial Discharge detection methods
 
Partial Discharge Detection Products by EA Technology
Partial Discharge Detection Products by EA TechnologyPartial Discharge Detection Products by EA Technology
Partial Discharge Detection Products by EA Technology
 
Self-healing high voltage electrical insulation materials
Self-healing high voltage electrical insulation materialsSelf-healing high voltage electrical insulation materials
Self-healing high voltage electrical insulation materials
 
Results of 10 years after installation tests with partial discharge detection...
Results of 10 years after installation tests with partial discharge detection...Results of 10 years after installation tests with partial discharge detection...
Results of 10 years after installation tests with partial discharge detection...
 
High Voltage, Inc. Products Presentation Short Version
High Voltage, Inc. Products Presentation Short VersionHigh Voltage, Inc. Products Presentation Short Version
High Voltage, Inc. Products Presentation Short Version
 
Heinputter 2
Heinputter 2Heinputter 2
Heinputter 2
 
C&I Cables Tests
C&I Cables TestsC&I Cables Tests
C&I Cables Tests
 
Insulation testing of power cable
Insulation testing of power cableInsulation testing of power cable
Insulation testing of power cable
 
Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...
Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...
Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...
 
High voltage transmission
High voltage transmissionHigh voltage transmission
High voltage transmission
 
MS Thesis Lakshya MIttal
MS Thesis Lakshya MIttalMS Thesis Lakshya MIttal
MS Thesis Lakshya MIttal
 
Tan delta test for power transformers
Tan delta test for power transformersTan delta test for power transformers
Tan delta test for power transformers
 
IEEE 848 Standard Procedure For The Determination Of Tthe Ampacity Derating o...
IEEE 848 Standard Procedure For The Determination Of Tthe Ampacity Derating o...IEEE 848 Standard Procedure For The Determination Of Tthe Ampacity Derating o...
IEEE 848 Standard Procedure For The Determination Of Tthe Ampacity Derating o...
 
LT XLPE Cable & HT ABC Redesign
LT XLPE Cable & HT ABC RedesignLT XLPE Cable & HT ABC Redesign
LT XLPE Cable & HT ABC Redesign
 
High voltage cable insulation systems
High voltage cable insulation systemsHigh voltage cable insulation systems
High voltage cable insulation systems
 
Power cables
Power cablesPower cables
Power cables
 
EE-55 Power Cables Testing & Fault Location
EE-55 Power Cables Testing & Fault LocationEE-55 Power Cables Testing & Fault Location
EE-55 Power Cables Testing & Fault Location
 
Hv Cable Testing
Hv Cable TestingHv Cable Testing
Hv Cable Testing
 
Xlpe insulated cables
Xlpe insulated cablesXlpe insulated cables
Xlpe insulated cables
 

Similar to Deis talk-nov-2014-revised

Adoption of Best Practices for Cable Testing and Condition Monitoring In The ...
Adoption of Best Practices for Cable Testing and Condition Monitoring In The ...Adoption of Best Practices for Cable Testing and Condition Monitoring In The ...
Adoption of Best Practices for Cable Testing and Condition Monitoring In The ...Thorne & Derrick International
 
Design of Electrical Installation of Buildings.ppt
Design of Electrical Installation of Buildings.pptDesign of Electrical Installation of Buildings.ppt
Design of Electrical Installation of Buildings.pptSameeraShaman
 
Lightning and Surge Protection Strategy for Instrumentation
Lightning and Surge Protection Strategy for InstrumentationLightning and Surge Protection Strategy for Instrumentation
Lightning and Surge Protection Strategy for InstrumentationRekaNext Capital
 
A Comparison of Contemporary Electrical Distribution Equipment Standards
A Comparison of Contemporary Electrical Distribution Equipment StandardsA Comparison of Contemporary Electrical Distribution Equipment Standards
A Comparison of Contemporary Electrical Distribution Equipment Standardsmichaeljmack
 
Relay testing.............................
Relay testing.............................Relay testing.............................
Relay testing.............................hiiarindam
 
Assuring Reliability of Critical Power Cable Systems
Assuring Reliability of Critical Power Cable SystemsAssuring Reliability of Critical Power Cable Systems
Assuring Reliability of Critical Power Cable Systemsmichaeljmack
 
Power quality disturbances
Power quality disturbancesPower quality disturbances
Power quality disturbancesManasKumarPatro
 
Transformer Diagnostics | Sweep Frequency Response Analysis
Transformer Diagnostics | Sweep Frequency Response AnalysisTransformer Diagnostics | Sweep Frequency Response Analysis
Transformer Diagnostics | Sweep Frequency Response AnalysisHamedPasha1
 
switchgear and protection.pdf
switchgear and protection.pdfswitchgear and protection.pdf
switchgear and protection.pdfbhaskarbhalerao
 
DC Electrical Safety Standards presentation
DC Electrical Safety Standards presentationDC Electrical Safety Standards presentation
DC Electrical Safety Standards presentationakhilesh682519
 
Switchgear and protection engineering Lecture 02.pptx
Switchgear and protection engineering Lecture 02.pptxSwitchgear and protection engineering Lecture 02.pptx
Switchgear and protection engineering Lecture 02.pptxLoitaFredy
 
Shorted Casing Study - Tim Sievert
Shorted Casing Study - Tim SievertShorted Casing Study - Tim Sievert
Shorted Casing Study - Tim Sievertnacetwincities
 

Similar to Deis talk-nov-2014-revised (20)

Adoption of Best Practices for Cable Testing and Condition Monitoring In The ...
Adoption of Best Practices for Cable Testing and Condition Monitoring In The ...Adoption of Best Practices for Cable Testing and Condition Monitoring In The ...
Adoption of Best Practices for Cable Testing and Condition Monitoring In The ...
 
Tan Delta on MV Cables (Megger)
Tan Delta on MV Cables (Megger)Tan Delta on MV Cables (Megger)
Tan Delta on MV Cables (Megger)
 
Protection and Switchgear
Protection and SwitchgearProtection and Switchgear
Protection and Switchgear
 
Design of Electrical Installation of Buildings.ppt
Design of Electrical Installation of Buildings.pptDesign of Electrical Installation of Buildings.ppt
Design of Electrical Installation of Buildings.ppt
 
Lightning and Surge Protection Strategy for Instrumentation
Lightning and Surge Protection Strategy for InstrumentationLightning and Surge Protection Strategy for Instrumentation
Lightning and Surge Protection Strategy for Instrumentation
 
Procedure cable testing
Procedure cable testingProcedure cable testing
Procedure cable testing
 
A Comparison of Contemporary Electrical Distribution Equipment Standards
A Comparison of Contemporary Electrical Distribution Equipment StandardsA Comparison of Contemporary Electrical Distribution Equipment Standards
A Comparison of Contemporary Electrical Distribution Equipment Standards
 
Relay testing.............................
Relay testing.............................Relay testing.............................
Relay testing.............................
 
Fusing Metering Voltages for High Capacity Circuits
Fusing Metering Voltages for High Capacity CircuitsFusing Metering Voltages for High Capacity Circuits
Fusing Metering Voltages for High Capacity Circuits
 
PD_Presentation_1.pdf
PD_Presentation_1.pdfPD_Presentation_1.pdf
PD_Presentation_1.pdf
 
Assuring Reliability of Critical Power Cable Systems
Assuring Reliability of Critical Power Cable SystemsAssuring Reliability of Critical Power Cable Systems
Assuring Reliability of Critical Power Cable Systems
 
Power quality disturbances
Power quality disturbancesPower quality disturbances
Power quality disturbances
 
ET 5 LESSON 2 TEST EQUIPMENT.pptx
ET 5 LESSON 2 TEST EQUIPMENT.pptxET 5 LESSON 2 TEST EQUIPMENT.pptx
ET 5 LESSON 2 TEST EQUIPMENT.pptx
 
Transformer Diagnostics | Sweep Frequency Response Analysis
Transformer Diagnostics | Sweep Frequency Response AnalysisTransformer Diagnostics | Sweep Frequency Response Analysis
Transformer Diagnostics | Sweep Frequency Response Analysis
 
switchgear and protection.pdf
switchgear and protection.pdfswitchgear and protection.pdf
switchgear and protection.pdf
 
DC Electrical Safety Standards presentation
DC Electrical Safety Standards presentationDC Electrical Safety Standards presentation
DC Electrical Safety Standards presentation
 
Switchgear and protection engineering Lecture 02.pptx
Switchgear and protection engineering Lecture 02.pptxSwitchgear and protection engineering Lecture 02.pptx
Switchgear and protection engineering Lecture 02.pptx
 
Shorted Casing Study - Tim Sievert
Shorted Casing Study - Tim SievertShorted Casing Study - Tim Sievert
Shorted Casing Study - Tim Sievert
 
Distribution systems
Distribution systemsDistribution systems
Distribution systems
 
63-pq.ppt
63-pq.ppt63-pq.ppt
63-pq.ppt
 

Recently uploaded

What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 

Recently uploaded (20)

What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 

Deis talk-nov-2014-revised

  • 1. VLF Testing of Cables Using IEEE 400.2™ John Densley ArborLec Solutions Inc.
  • 2. Outline • Aging/diagnostics basics • Diagnostic testing of MV cables • IEEE 400.2 – 2013 • Future trends • Conclusions
  • 3. Aging • Changes in properties that occur with time due to the applied stresses, electrical, thermal, mechanical and environmental (chemical). Can act singly or synergistically • Changes may cause permanent damage that may affect ability to perform specified functions. This is sometimes referred to as degradation • Changes can lead to failure
  • 4. Polymer cable insulation aging & failure mechanisms • Insulation aging usually at defects (voids, contaminants or protrusions) → partial discharge (PD), water treeing (WT), thermal aging • Failure mechanism → Electrical treeing (ET), thermal runaway Aging, e.g. PD, can take a long time initiate failure → possible to detect with diagnostic test Failure, e.g. ET, usually takes place quickly → not easy to pick up with diagnostic test • Other types of failure: – voltage transients → intrinsic BD – abnormal high temperature → mechanical or electrical failure – Mechanical damage (dig-in, thermomechanical)
  • 5. Partial discharges • Local BD of gas in voids, delaminations at interfaces or protrusions (electrical trees) • A partial discharge is a current pulse of some nanoseconds duration that causes minute high frequency currents to flow in the circuit (100’s of MHz)
  • 6. Simplified PD sequence Initial Discharge Return Discharge Second Discharge Electrical Field Conditions -20 -15 -10 -5 0 5 10 15 20 0 45 90 135 180 225 270 315 360 Phase Angle Voltage/ElectricField Appl. Voltage [kV] Applied Field in Void [kV/mm] Void Breakdown Strength Void Field [kV/mm]
  • 7. 7 -1.5 -1 -0.5 0 0.5 1 1.5 -15 -10 -5 0 5 10 15 0 45 90 135 180 225 270 315 360 ReferenceVoltage[kV] PDMagnitude[mV] Phase Angle Partial discharge pulse sequence PD Signal Reference Voltage
  • 8. Electrical treeing • Localized breakdown of insulation from voids, sharp protrusions or water trees that increase the local electrical stress • Local stress at tip at tree initiation can be >100 kV/mm • Once tree has initiated its growth is caused by PD in the channels (<20 μm dia.) Electrical tree Water tree
  • 9. Electrical treeing Growth • The PD leave charges on the walls of the channels → stress that can be > applied stress • ET shape changes with applied field/frequency in insulation → non-linear growth with time, e.g., rate at 60 Hz less than at 0.1 Hz and rate at 0.1 Hz is less than 0.01 Hz Breakdown through electrical tree 9
  • 10. Water treeing  Occurs at stress enhancements such as protrusions, contaminants or voids  Moisture always present  Soluble contaminants such as salts are particularly harmful  Degradation is slow taking several years  Final failure due to electrical tree (PD) from the water tree or thermal runaway for bridging trees  Vented tree from semicon surface or bow-tie tree from contaminant or void  Responsible for failures of many older vintage cables (extruded insulation)  No PD during initiation or growth
  • 11. Other stresses • PD and WT are the main aging mechanisms of extruded MV cables Therefore: • Will not consider aging due to mechanical (M) and thermal (T) stresses • M and T accelerate electrical aging We can now look at diagnostic testing
  • 12. Diagnostic tests • A diagnostic test is a field test made during the operating life of a cable system that is intended to determine and locate aging or degradation that may cause failure of cable system - Defined in CIGRE WG21- 05 Report, 1994 • May be on-line or off-line • Tests may be one-time only or periodic to establish trends • Can look at metallic and/or insulating parts The main purposes of a diagnostic test are to reduce the number of failures in service and provide information on the serviceability of the cable system
  • 13. How can we do diagnostics on cables? Must know details of the cable system to be tested • Need to know probable aging and failure mechanisms • Need to measure properties or characteristics that give an indication of how much aging has occurred • Would like to know rate of aging • Need to interpret data to assess circuit condition and give an indication of serviceability One of the most important diagnostic tests is a periodic visual inspection to establish trends Let’s look at water treeing
  • 14. Properties of water treed insulation 1. Lower AC Breakdown Voltage 2. Small increase in capacitance (C) with voltage 3. Increase in Tan Delta (dissipation factor (DF)) 4. Tan Delta (TD) increases with voltage 5. Tan Delta changes with time at constant V 6. Decrease in insulation resistance (IR) 7. Loss Current Waveform distorted 8. Increased DC leakage current 9. Space charge/polar species in trees 10. No PD until just prior to failure Numbers 2 to 8 are bulk measurements
  • 15. IEEE Std 400™-2012 (Revision of IEEE Std 400-2001) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above
  • 16. IEEE Std 400™-2012 The guide lists the various field test methods that are currently available, or under development, to evaluate the insulation of shielded power cable systems. The guide: • Rated 5 kV and above • Describes the tests, gives advantages and disadvantages, suggested applications, and typical results • Does not give test voltage levels or test durations Guides covering particular test methods are available in the form of IEEE 400 “point” documents. These Guides give voltage levels and durations.
  • 17. Field test categories (1) Installation tests • Conducted after cable installation but before jointing (splicing) or terminating or energizing • Intended to detect shipping, storage or installation damage Acceptance tests • Made after cable system installation, including terminations and joints, but before the cable system is placed in normal service • Intended to detect installation damage and to show any gross defects or errors in installation of other system components
  • 18. Field test categories (2) Maintenance tests • Performed on cable systems that have been aged in service for an extended period of time • Intended to detect deterioration and to check the serviceability of the system • Need to consider failure history, testing and installation history, cable system component makeup, importance of cable in system
  • 19. Voltage Sources • 60 Hz AC (used for transmission class) • VLF (used for MV and lower voltage transmission class) – IEEE 400.2 • Damped ac (DAC) – IEEE 400.4 (in prep.) • DC – IEEE 400.1 These sources may be used in one of two modes: diagnostic (Tan δ, PD, etc.) or withstand (Simple and Monitored)
  • 20. 400 “Point” documents (1) IEEE Std 400.1 ™ – 2007: IEEE Guide for Field Testing of Laminated Dielectric, Shielded Power Cable Systems Rated 5 kV and Above with High Direct Current Voltage • Oil/paper cables only, not to be used for extruded dielectric cables • Includes a table of withstand HVDC test voltages (acceptance and maintenance) for cables rated 5 kV to 500 kV • Usual to measure current after 2 and 15 minutes
  • 21. 400 “Point” documents (2) • IEEE Std 400.3™-2006: IEEE Guide for Partial Discharge Testing of Shielded Power Cable Systems in a Field Environment • No tables of test voltages or maximum allowable discharge magnitudes for cables with different ratings, unlike factory/routine tests • Describes principles of methods capable of detecting, measuring and locating partial discharges from defects and damage in installed shielded power cable systems • Usually cannot assume lumped capacitance as for factory tests as long cable lengths have to be treated as transmission lines Guide is presently under revision – more comprehensive than original version and will probably contain test voltages for both distribution and transmission class cables
  • 22. 400 “Point” documents (3) • P400.4™/D8: Draft Guide for Guide for Field- Testing of Shielded Power Cable Systems Rated 5 kV and Above with Damped Alternating Current Voltage (DAC) • Presently out for ballot • Recommended test values are included in an Annex for engineering information as not enough practical data are available • A number of damped oscillations between 20 Hz and 500 Hz applied at each test level
  • 23. 400 “Point” documents (4) IEEE Std 400.2™-2013: IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (less than 1 Hz) • Cables rated 5 kV to 69 kV • Guide valid for extruded & oil/paper cables • Includes tables of withstand (installation, acceptance and maintenance) tests • Includes tables of tangent delta (dissipation factor) criteria – “no action required”, “further study required” & “action required”
  • 24. VLF testing • Mostly used at distribution voltage levels • Can be a simple or monitored (tan δ and/or PD) withstand test • VLF defined as < 1 Hz but most common frequency is 0.1 Hz. Very long lengths tested at 0.05 Hz or 0.02 Hz. • Must be careful when interpreting partial discharge data acquired at VLF conditions since the physics of PD has a complex relationship with frequency • Maintenance testing of medium voltage cables with VLF is popular in North America (IEEE 400.2™), Asia and Europe (Cenelec Standard) • Present voltage sources limited to cables rated 138 kV and lower (200 kV peak) • Two waveforms – sinusoidal and cosine-rectangular 24
  • 25. VLF waveforms Sinusoidal waveform HVA30 @5kV RMS with 280feet XLPE Load -8000 -6000 -4000 -2000 0 2000 4000 6000 8000 Voltage(kV) Cosine rectangular waveform SEBAKMT VLF40 @5kv RMS with 280feet XLPE Load -8000 -6000 -4000 -2000 0 2000 4000 6000 Voltage(kV) 25
  • 26. Examples of commercially available VLF Sources - courtesy of NEETRAC
  • 27. VLF withstand testing (1) • Test integrity of circuit • Test frequency is between 0.01 Hz and 1 Hz (0.1 most common). <0.1 Hz used for longer length circuits • As electrical tree grows faster at 0.1 Hz than at 50/60 Hz, more likely to cause failure during test • Test values based on most used practices • Recommended test duration is 30 minutes with 60 minutes allowed for critical circuits. European standard is 60 minutes • A test time within the range 15 – 30 minutes may be considered if the monitored characteristic remains stable for at least 15 minutes and no failure occurs
  • 28. VLF withstand testing (2) • IEEE 400.2 -2013 test voltages are based on peak to peak voltages being equal for sinusoidal and cosine- rectangular voltage waveforms (based on breakdown tests on aged XLPE cables) • European standard test voltages based on rms values being equal for the two waveforms (based on electrical tree growth data) • If a circuit fails during test → repaired or replaced → re-tested using a complete 30 minute test, preferably monitored withstand test. It is recommended to retest each section with VLF-TD, VLF-DTD, VLF-TDTS or VLF- PD
  • 29. VLF withstand test voltages for sinusoidal waveform1 IEEE 400.2 - 2013 • Note 1: If the operating voltage is a voltage less than rated voltage, it is recommended that the maintenance test voltages should be those corresponding to the operating voltage class. • Note 2: The maintenance voltage is about 75% of the acceptance test voltage magnitude. • Note 3: Some existing test sets have a maximum voltage that is up to 5% below the values listed in the Table. These test sets are acceptable to be used. However, there is a risk that the cable may be "undertested" due to a combination of lower test voltage and allowed uncertainty of the measuring circuit. Cable System Rating (Phase to Phase) [kV] Installation (Phase to Ground) Acceptance (Phase to Ground) Maintenance2 (Phase to Ground) [kV rms] [kV peak] [kV rms] [kV peak] [kV rms] [kV peak] 5 9 13 10 14 7 10 8 11 16 13 18 10 14 15 19 27 21 30 16 22 20 243 343 26 37 20 28 25 293 413 32 45 243 343 28 32 45 363 513 27 38 30 34 48 38 54 293 413 35 39 55 44 62 33 47 46 51 72 57 81 43 61 69 75 106 84 119 63 89
  • 30. VLF withstand test voltages for cosine- rectangular waveform1 IEEE 400.2 - 2013 • Note 1: If the operating voltage is a voltage class lower than the rated voltage of the cable, it s recommended that the maintenance test voltages should be those corresponding to the operating voltage class. Cable System Rating (Phase to Phase) [kV] Installation (Phase to Ground) Acceptance (Phase to Ground) Maintenance2 (Phase to Ground) [kV rms] [kV peak] [kV rms] [kV peak] [kV rms] [kV peak] 5 13 13 14 14 10 10 8 16 16 18 18 14 14 15 27 27 30 30 22 22 20 34 34 37 37 28 28 25 41 41 45 45 34 34 28 45 45 51 51 38 38 30 48 48 54 54 41 41 35 55 55 62 62 47 47 46 72 72 81 81 61 61 69 106 106 119 119 89 89
  • 31. Note on dissipation factor Tan , Dissipation Factor, or Loss Factor  Power Factor Tan  = Ir/Ic = / = 1/[2CR] • Tan  is a measure of polar and dipolar movement • Polar/dipolar species  bulk test  sensitive to water, high density of WT), ageing • Tan  /dielectric spectroscopy are bulk measurements. The average of the whole length of the cable and its accessories is measured. 31 • Careful interpretation of tan  may be needed: – Short sections of high Tan  in a long cable may not significantly increase the overall Tan  – In field measurements, certain types of accessories can give high tan  values
  • 32. Voltage dependence of 0.1 Hz dissipation factor of new and service-aged XLPE-insulated medium voltage cables - Baur (1995 JICABLE), tan  . 10-3 0 1 2 3 4 5 6 7 0 0.5 1 1.5 2 2.5 3 U / U 0 0,1Hzdissipationfactor reference cable (new) slightly service-aged (1) moderately service-aged (2) moderately service-aged (3) strongly service-aged (4) . 32
  • 33. VLF tan δ – aged cables IEEE 400.2 - 2013 gives: • Criteria for aged (WT) XLPE and EPR cables – No action required – Further study recommended – Action required • Criteria based on tan  time stability (TDTS), voltage tip-up (DTD) and mean value of tan  (TDM) 33
  • 34. Criteria • no action required – Cable system can be returned to service, but may be retested at some later date to observe the trend in tan delta • action required – Unusually high set of tan delta characteristics which may indicate poor insulation condition and should be considered for further testing or replacement or repair immediately • further study advised – Additional information is needed to make an assessment → failure history, additional testing
  • 35. Parameters used to establish criteria • Time stability of tan delta at Uo (TDTS) – At least six single TD measurements at intervals of 10 seconds between each measurement at 0.1 Hz – Measure mean and standard deviation • Voltage tip-up of tan delta between 0.5 Uo and 1.5 Uo (DTD) • Mean value of tan delta at Uo (TDM) TDTS most sensitive to degradation, then DTD which is more sensitive than TDM
  • 36. How numerical values of criteria derived • Derived from cumulative distribution function of the maintenance measurement data of tan δ (time stability (TDTS) voltage tip-up (DTD) and mean value (TDM)) obtained for aged cable systems, mainly in North America • Tables use the probability criteria of 80% based on the Pareto principle (best ranked 80% account for only 20% of the problems) and 95% probability 36
  • 37. Cumulative distribution of all cable system TDTS values at U0 from IEEE 400.2-2013
  • 38. Cumulative distribution of all cable system DTD Criteria from 400.2 - 2013
  • 39. Cumulative distribution of all cable systems TDM values from IEEE 400.2 - 2013 • Criteria for PE, filled polymer and PILC are values at 80% and 95% probabilities • Utilities are encouraged to develop their own data plots 39
  • 40. Assessment criteria for PE based insulations - IEEE 400.2 - 2013 Historical figures of merit for condition assessment of service- aged PE-based insulations (i.e. PE, XLPE, and TRXLPE) using 0.1 Hz 40 Condition Assessment VLF-TD Time Stability (VLF-TDTS measured by standard deviation at Uo [10-3] Differential VLF-TD (VLF-DTD) (difference in mean VLF-TD) between 0.5 Uo and 1.5 Uo [10-3] Mean VLF-TD at Uo [10-3] No Action Required <0.1 and <5 and <4 Further Study Advised 0.1 to 0.5 or 5 to 80 or 4 to 50 Action Required >0.5 or >80 or >50
  • 41. Assessment of service-aged OIP insulations Condition Assessment VLF-TD Time Stability (VLF-TDTS measured by standard deviation at Uo [10-3] Differential VLF-TD (VLF-DTD) (difference in mean VLF-TD) between 0.5 Uo and 1.5 Uo [10-3] Mean VLF- TD at Uo [10-3] No Action Required <0.1 and -35 to 10 and <85 Further Study Advised 0.1 to 0.4 or -35 to -50 or 10 to 100 or 85 to 200 Action Required >0.4 or <-50 or >100 or >200
  • 42. No action required criteria for service-aged filled insulations - IEEE 400.2 - 2013 Condition Assessment Filled Insulation System VLF-TD Time Stability (VLF- TDTS measure d by standard deviation at Uo [10-3] Differential VLF-TD (VLF- DTD) (difference in mean VLF-TD) between 0.5 Uo and 1.5 Uo [10-3] Mean VLF- TD at Uo [10-3] No Action Required * If it is not possible to definitively identify a Filled Insulation <0.1 a n d <5 a n d <35 Carbon-filled (Black) EPR <0.1 <2 <20 Mineral-filled (Pink) EPR <0.1 <4 <20 ** Discharge resistant EPR <0.1 <6 <100 ** Mineral-filled XLPE - - <100
  • 43. Further study and action required criteria for service-aged filled insulations - IEEE 400.2 - 2013 Condition Assessment Filled Insulation System VLF-TD Time Stability (VLF- TDTS measured by standard deviation at Uo [10-3] Differential VLF- TD (VLF-DTD) (difference in mean VLF-TD) between 0.5 Uo and 1.5 Uo [10-3] Mean VLF-TD at Uo [10-3] Further Study Advised * If it is not possible to definitively identify a Filled Insulation 0.1 to 1.3 o r 5 to 100 or 35 to 120 Carbon-filled (Black) EPR 0.1 to 2.7 2 to 120 20 to 100 Mineral-filled (Pink) EPR 0.1 to 1 4 to 120 20 to 100 ** Discharge resistant EPR 0.1 to 1 6 to 10 100 to 350 ** Mineral-filled XLPE - - 100 to 350 Action Required * If it is not possible to definitively identify a Filled Insulation >1.3 o r >100 or >120 Carbon-filled (Black) EPR >2.7 >120 >100 Mineral-filled (Pink) EPR >1 >120 >100 ** Discharge resistant EPR >1 >10 >350 ** Mineral-filled XLPE - - >350
  • 44. If high values of TDTS, DTD and or TDM • 1. Can compare results between different phases of the same segment or sequential sections to better place the result in context • 2. Can divide circuits into sub sections and retest, perform a visual inspection of circuit components where accessible and replace suspect parts, or replace the accessories, especially if they appear to be old, and re-measure • 3. Can perform additional testing in the form of a monitored withstand, non-monitored withstand, or partial discharge test should they wish to identify a localized problem • 4. Can separate the response of terminations and other components if connected from cables plus splices, by, if practical, adding guard circuits at the terminations
  • 45. VLF testing - advantages • Inexpensive compared to AC HiPot testing • Power supply light in weight • Simple withstand test easy to perform • Non-expert test • IEEE Std 400.2™ gives test voltages • Effective to measure water tree degradation • Used for PE and EPR based, and OIP cables • Monitored withstand testing can measure tangent delta, insulation resistance and partial discharge characteristics → better assessment of cable insulation by picking out defects that do not fail during the test •
  • 46. VLF testing - disadvantages • Cable systems must be taken out of service for testing • Possible issues with charge injection and trapped charge when testing at frequencies less than 0.1 Hz • Two voltage waveforms available, sinusoidal and cosine - rectangular • Not straight forward to interpret PD data acquired during VLF conditions • When testing cables with extensive insulation degradation, simple VLF withstand testing can result in repeated failures, although this rarely occurs in practice • Simple withstand testing does not monitor the effect of the test on the cable during the voltage application and can fail to detect a potentially destructive defect
  • 47. Recent work - effect of test frequency • Long lengths tested at <0.1 Hz due to power limitation • Should lower frequency be tested longer? • NEETRAC grew WT in PE & EPR and subjected samples to BD tests at 0.1 Hz and 0.05 Hz • BD strength was lower at 0.05 Hz (6.7 kV/mm) than at 0.1 Hz (8.5 kV/mm) – tree growth rate? • Conclusion – no need to test for longer time at 0.05 Hz
  • 48. Future work • Encourage utilities to do diagnostic tests • Encourage utilities to develop and use their own cumulative distributions for VLF • Retest cables to verify performance (trends) • Re-establish Discussion Group FD03 to discuss data • Develop other criteria, e.g., Delta tip-up (TD(1.5Uo) - TD(Uo)) - (TD(Uo) - TD(0.5Uo)) • Prepare standard for continuous AC test for MV
  • 49. Conclusions • VLF simple withstand and monitored withstand are most commonly used diagnostic tests on MV cables • Larger utilities have a cable diagnostic program (why?) • The majority of utilities do not do diagnostic tests on their MV cable systems • Testing at less than 0.1 Hz does not require a longer test time • Refinements to the tan delta criteria are under study and should be incorporated in the next revision of 400.2