SWITCHGEAR AND PROTECTION
ENGINEERING
EEB 4204
Lecture 02
SWITCHGEAR
Introduction to Switchgear
•The importance of electric energy in everyday
life has reached a stage that it is desirable to
protect the power system from harm during
fault condition and to ensure maximum
continuity of supply
•For this purpose, means must be provided to
switch on and off generators, transmission
lines, distributors and other equipment under
both normal and abnormal conditions.
Introduction to Switchgear
•This is achieved by apparatus called
switchgear
•A switchgear essentially consists of switching
and protecting devices such as switches, fuses,
circuit breaker, relays, isolators, auto-recloser
etc.
•The apparatus used for switching, controlling,
and protecting the electrical circuits and
equipments is called switchgear
Essentials Features of Switchgear
1.Complete reliability - when fault occurs on
any part of the system, the switchgear must
operate to isolate the faulty section from the
reminder circuit.
2.Absolute certain discrimination – it should
be able to discriminate between the fault
section and the health section. Also, to
isolate the fault section from the system in
case of fault. This will ensure continuity of
supply.
Essentials Features of Switchgear
3. Quick Operation- must operates quickly so
that no damage is done in any equipment in
case of fault.
4. Provision for control manual– in case the
electrical or electronics control fails, the
necessary operation can be carried out through
manual control.
Essentials Features of Switchgear
5. Provision for instruments – may be in form
of ammeter or voltmeter on the unit itself or the
necessary current and voltage transformers for
connecting to the main switchboard or a
separate instrument panel.
Classification of Switchgear
Isolating Switch (Isolator)
•Isolating switch is an apparatus which makes
a visible break in the circuit.
•Isolator is used to open (or close) a circuit
either when negligible current is interrupted
(or established) or
•When no significant change in the voltage
across the terminals of each pole of the
isolator will result from the operation.
Isolating Switch (Isolator)
•According to number of poles isolators may be
classified as single pole, double poles isolators
and three pole isolators.
•According to type of service, isolators may be
classified as indoor type or outdoor type
Isolating Switch (Isolator)
Air BreakerType
•This switch is also known as air breaker type
circuit breaker. In this type, air at
atmospheric pressure is used as
extinguishing medium.
•In air-breakers, the principle of high
resistance is employed for arc interruption.
•The arc resistance is increased by
lengthening, splitting and cooling arc.
Air BreakerType
•AC air breaker are available in the range 400V
to 12kV. Also, used in DC circuit up to 12kV.
They are extensively used;
With electric furnaces,
With large motors requiring frequent starting,
 In a place where chances of fire hazard exist.
Lightning Arresters
•Lightning arresters a re also known as surge
diverter or surge arresters.
•They connected between the line and
ground at the substation and always acts as
in shunt (parallel) with the equipment to be
protected.
•Perform their protective function by
providing a low impedance path for the
surge currents
Lightning Arresters
• So that the surge arrester’s protective level is
less than the surge voltage withstanding
capacity of the insulation of equipment to be
protected.
Bus-Bar Arrangements
•When a number of generators and feeders
operating at the same voltage have to be
directly connected electrically
•Bus-bars are used as common electrical
components.
•Bus-bars are copper rod or thin walled tubes
and operate at constant voltage.
Bus-Bar Arrangements
Bus-Bar Arrangements
Bus-Bar Arrangements
1. Single bus-bar system
2.Single bus-bar system with sectionalization
3. Duplicated bus-bar system
Single Bus-bar System
•It is the simplest design of bus-bar systems
•It is used in small outdoor stations having
relatively few outgoing and incoming feeders
and lines.
•In single bus-bar system, each generator and
feeder is controlled by circuit breaker.
•The isolators permit to isolate generators,
feeders and circuit breaker from the bus-bar
for maintenance.
Single Bus-bar System
Single Bus-bar System
1. It has low initial cost
2.Less maintenance
3. Simple operation
Advantages
Single Bus-bar System
1. The bus-bar cannot be cleaned, tested or
repaired without de-energising the whole
system.
2. If a fault occurs on the bus bar itself, there is
complete interruption of supply.
3. Any fault on then system is fed by all the
generating capacity, resulting in very large
fault currents.
Disadvantages
Single Bus-bar System with
Sectionalisation
•In large generating stations where several
units are installed.
•It is common to sectionalize the bus so that
fault on any section of then bus-bar will not
cause complete shutdown.
•The bus-bar divided into two section
connected by circuit breaker and isolators.
Single Bus-bar System with
Sectionalisation
Single Bus-bar System with
Sectionalisation
1. If a fault occurs on any section of the bus-bar,
that section can be isolated without
affecting the supply of other section.
2.If a fault occurs on any feeder, the fault
current is much lower than unsectionalise
bus-bar.
3. Eliminate the possibility of complete shut
down during repair or maintenance of any
section on bus-bar.
Advantages
Single Bus-bar System with
Sectionalization
1. A circuit breaker should be used as
sectionalizing switch. So that uncoupling of
the bus-bars may be carried out safely during
load transfer.
2. Moreover, the circuit breaker itself should be
provided with isolators on both sides so that
its maintenance can be done while the bus-
bars are live.
Points to note
Duplicated Bus-bar System
•In large stations, it is important that
breakdown and maintenance should interfere
as little ae possible with continuity of supply.
•In to achieve this objective, duplicate bus-bar
system is used in important substations.
•Such a system consists of two bus-bar, a main
bus-bar and spare bus-bar.
•Each generator ad feeder may be connected to
either bus-bar with the help of bus coupler
which consists of circuit breaker and isolators.
Duplicated Bus-bar System
•Service is interrupted during switch from one
bus-bar to another.
•However, if it were desired to switch a circuit
from one to another without interruption n
there would have two circuit breakers per
circuit.
•Such a arrangement will be to expensive.
Duplicated Bus-bar System
1. If repair ad maintenance are to be carried on
main bus bar, the supply need not be
interrupted as the entire load can be
transferred to the spare bus-bar.
2.The testing of feeder circuit breaker can be
done by putting them on spare bus bar, thus
keeping main bus bar undisturbed
3. If a fault occurs on the bus bar, the continuity
of the supply to the circuit can be maintained
by transferring it to the other bus bar.
Advantages
Duplicated Bus-bar System
Switchgear Accommodation
•Depending upon the voltage to be handled,
switchgear may be broadly classified into
1) Outdoor type
2) Indoor type
•For voltage beyond 66kV, switchgear
equipment is installed outdoor.
Switchgear Accommodation
•It is because for such voltages, the clearance
between conductors and space required for
switches, circuit breaker, transformer and
other equipment become so great that it is not
economical to install all such equipment
indoor.
•For voltage below 66kV, switchgear is
generally installed indoor because of
economical considerations.
Fault in Power System
•The normal path of the electric current is from
the power source through copper (or
aluminum) conductors in generators,
transformers and transmission lines to the
load
• It is confined to this path by insulation. The
insulation, however, may break down, either
by the effect of temperature and age or by a
physical accident,
Fault in Power System
•So that the current then follows an abnormal
path generally known as Short Circuit or Fault
•Any abnormal operating state of a power
system is known as FAULT.
•Faults in general consist of short circuits as
well as open circuits.
•Open circuit faults are less frequent than
short circuit faults, and often they are
transformed in to short circuits by subsequent
events.
Fault in Power System
•A fault occurs when two or more conductors
that are normally operate with potential
difference come in contact with each other.
•This fault may be caused by:
1. Sudden failure of a piece of equipment
2. Accidental damage or short circuit of overhead
lines
3. Insulation failure resulting from lighting surges.
Fault in Power System
•The short circuited fault in three phase system
can be classified into two categories;
1. Symmetrical faults
2. Unsymmetrical faults
•Symmetrical faults gives rise to fault current.
Equal fault current with 120o displacement.
•Example of symmetrical fault is when all three
conductors of a three phase lie brought
together simultaneously into short circuit.
Fault in Power System
•Unsymmetrical faults give rise to
unsymmetrical current. Unequal line currents
with unequal displacement.
•The unsymmetrical faults may take the
following form;
1. Single line to ground fault
2. Line to line fault
3. Double line to ground fault
Fault in Power System
•The great majority faults on the power system
are of unsymmetrical nature, the most
common type being a short circuit from one
line to ground.
Fault in Power System
•The open circuited fault in three phase system
can be classified into two categories;
1. Single phase open circuit
2. Two phases open circuit
3. Three phase open circuit
Fault in Power System
•In terms of seriousness of consequences of a
fault, short circuits are of far greater concern
than open circuits, although some open
circuits present some potential hazards to
personnel
Consequences of occurrence of fault
1. Damage to the equipment due to abnormally
large and unbalanced currents and low
voltages produced by the short circuit
2.Explosions may occur in the equipments
which have insulating oil, particularly during
short circuits.This may result in fire and
hazardous conditions to personnel and
equipments
Consequences of occurrence of fault
3. Individual generators with reduced voltage in
a power station or a group of generators
operating at low voltage may lead to loss of
synchronism, subsequently resulting in
islanding.
THE END OFTHE
TOPIC

More Related Content

What's hot

Maintenance of Substation Equipment | Operation And Maintenance Of Substation
Maintenance of Substation Equipment | Operation And Maintenance Of SubstationMaintenance of Substation Equipment | Operation And Maintenance Of Substation
Maintenance of Substation Equipment | Operation And Maintenance Of SubstationSystem Protection
 
Types of relay
Types of relayTypes of relay
Types of relayAbdur rehman
 
Under ground cables presention
Under ground cables presentionUnder ground cables presention
Under ground cables presentionRazu Khan
 
Transformer failure case study
Transformer failure case studyTransformer failure case study
Transformer failure case studyLeonardo ENERGY
 
Tap changer
Tap changerTap changer
Tap changervivek1292
 
Function relay types
Function relay typesFunction relay types
Function relay typesjawaharramaya
 
substation internship report
substation internship report substation internship report
substation internship report Arun Thapa
 
PPT on 33/11 sub-station uppcl
PPT on 33/11 sub-station uppclPPT on 33/11 sub-station uppcl
PPT on 33/11 sub-station uppclVISHAL VERMA
 
Introduction to switchgear
Introduction to switchgearIntroduction to switchgear
Introduction to switchgearAdnan Sayed
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)J. FR
 
Instrument transformer CT & PT
Instrument transformer CT & PTInstrument transformer CT & PT
Instrument transformer CT & PTChandan Singh
 
HT and LT SWITCHGEAR
HT and LT SWITCHGEARHT and LT SWITCHGEAR
HT and LT SWITCHGEARRavindra Kumar
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relaysPremanandDesai
 
Three phase transformer ( vector groups)
Three phase  transformer ( vector groups)Three phase  transformer ( vector groups)
Three phase transformer ( vector groups)Dr.Raja Masood Larik
 
Isolator and bushing
Isolator and bushingIsolator and bushing
Isolator and bushingNovia Putri
 
Distribution Transformer testing, West Bengal, India
Distribution Transformer testing,  West Bengal, IndiaDistribution Transformer testing,  West Bengal, India
Distribution Transformer testing, West Bengal, IndiaRajuMondal18
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devicesRahul Aman
 
Electrical 132kv substation project .. shakir
Electrical 132kv substation project .. shakirElectrical 132kv substation project .. shakir
Electrical 132kv substation project .. shakirSheikh Shakir
 

What's hot (20)

Maintenance of Substation Equipment | Operation And Maintenance Of Substation
Maintenance of Substation Equipment | Operation And Maintenance Of SubstationMaintenance of Substation Equipment | Operation And Maintenance Of Substation
Maintenance of Substation Equipment | Operation And Maintenance Of Substation
 
Types of relay
Types of relayTypes of relay
Types of relay
 
Under ground cables presention
Under ground cables presentionUnder ground cables presention
Under ground cables presention
 
Transformer failure case study
Transformer failure case studyTransformer failure case study
Transformer failure case study
 
Tap changer
Tap changerTap changer
Tap changer
 
Function relay types
Function relay typesFunction relay types
Function relay types
 
substation internship report
substation internship report substation internship report
substation internship report
 
PPT on 33/11 sub-station uppcl
PPT on 33/11 sub-station uppclPPT on 33/11 sub-station uppcl
PPT on 33/11 sub-station uppcl
 
Introduction to switchgear
Introduction to switchgearIntroduction to switchgear
Introduction to switchgear
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
 
Instrument transformer CT & PT
Instrument transformer CT & PTInstrument transformer CT & PT
Instrument transformer CT & PT
 
SWITCHGEAR
SWITCHGEARSWITCHGEAR
SWITCHGEAR
 
HT and LT SWITCHGEAR
HT and LT SWITCHGEARHT and LT SWITCHGEAR
HT and LT SWITCHGEAR
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Three phase transformer ( vector groups)
Three phase  transformer ( vector groups)Three phase  transformer ( vector groups)
Three phase transformer ( vector groups)
 
Isolator and bushing
Isolator and bushingIsolator and bushing
Isolator and bushing
 
Distribution Transformer testing, West Bengal, India
Distribution Transformer testing,  West Bengal, IndiaDistribution Transformer testing,  West Bengal, India
Distribution Transformer testing, West Bengal, India
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devices
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Electrical 132kv substation project .. shakir
Electrical 132kv substation project .. shakirElectrical 132kv substation project .. shakir
Electrical 132kv substation project .. shakir
 

Similar to Switchgear and protection engineering Lecture 02.pptx

DISTRIBUTION SYSTEM OPERATION AND CONTROL
DISTRIBUTION SYSTEM OPERATION AND CONTROLDISTRIBUTION SYSTEM OPERATION AND CONTROL
DISTRIBUTION SYSTEM OPERATION AND CONTROLyohannes feleke
 
Switchgear and protection lecture 1
Switchgear and protection lecture 1Switchgear and protection lecture 1
Switchgear and protection lecture 1anuphowlader1
 
Switchgears and protection devices
Switchgears and protection devicesSwitchgears and protection devices
Switchgears and protection devicesManojkarader
 
Electrical power distribution and utilization
Electrical power distribution and utilizationElectrical power distribution and utilization
Electrical power distribution and utilizationMuhammadAliImran11
 
Unit IV.pptx
Unit IV.pptxUnit IV.pptx
Unit IV.pptxpmaheshh
 
PPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptxPPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptxayazkhan261
 
PPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptxPPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptxayazkhan261
 
Module 1 Power System Protection(18EE72).pptx
Module 1 Power System Protection(18EE72).pptxModule 1 Power System Protection(18EE72).pptx
Module 1 Power System Protection(18EE72).pptxssuser139a56
 
presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.Hemendra Kumar Rajput
 
newswitchgearandprotection-130925105559-phpapp02.pptx
newswitchgearandprotection-130925105559-phpapp02.pptxnewswitchgearandprotection-130925105559-phpapp02.pptx
newswitchgearandprotection-130925105559-phpapp02.pptxDrNiveditaSingh3
 
Electrical Basics-VBR
Electrical Basics-VBRElectrical Basics-VBR
Electrical Basics-VBRVijay Raskar
 
400 kv Heerapura gss ppt by ishan pdf
400 kv Heerapura gss ppt by ishan pdf 400 kv Heerapura gss ppt by ishan pdf
400 kv Heerapura gss ppt by ishan pdf Ishan Khandelwal
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear johny renoald
 
Surge arrester ppt
Surge arrester pptSurge arrester ppt
Surge arrester pptIrinElsa
 
Presentation on 132/33KV BSPTCL(Bodhgaya Substation)
Presentation on 132/33KV BSPTCL(Bodhgaya Substation)Presentation on 132/33KV BSPTCL(Bodhgaya Substation)
Presentation on 132/33KV BSPTCL(Bodhgaya Substation)Rahul Prajapati
 
SGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSHIVANICHAUUHAN1
 
Ppt on 400 kv gss raiser Bikaner- Yatendra Parashar
Ppt on 400 kv gss raiser Bikaner- Yatendra ParasharPpt on 400 kv gss raiser Bikaner- Yatendra Parashar
Ppt on 400 kv gss raiser Bikaner- Yatendra ParasharYatendra Parashar
 
lecture1423723756.pdf
lecture1423723756.pdflecture1423723756.pdf
lecture1423723756.pdfssuser564db8
 

Similar to Switchgear and protection engineering Lecture 02.pptx (20)

DISTRIBUTION SYSTEM OPERATION AND CONTROL
DISTRIBUTION SYSTEM OPERATION AND CONTROLDISTRIBUTION SYSTEM OPERATION AND CONTROL
DISTRIBUTION SYSTEM OPERATION AND CONTROL
 
Switchgear and protection lecture 1
Switchgear and protection lecture 1Switchgear and protection lecture 1
Switchgear and protection lecture 1
 
Switchgears and protection devices
Switchgears and protection devicesSwitchgears and protection devices
Switchgears and protection devices
 
Gss report
Gss reportGss report
Gss report
 
Electrical power distribution and utilization
Electrical power distribution and utilizationElectrical power distribution and utilization
Electrical power distribution and utilization
 
Ashwani kumar
Ashwani kumarAshwani kumar
Ashwani kumar
 
Unit IV.pptx
Unit IV.pptxUnit IV.pptx
Unit IV.pptx
 
PPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptxPPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptx
 
PPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptxPPT_1_Electrical services_By group no. 1.pptx
PPT_1_Electrical services_By group no. 1.pptx
 
Module 1 Power System Protection(18EE72).pptx
Module 1 Power System Protection(18EE72).pptxModule 1 Power System Protection(18EE72).pptx
Module 1 Power System Protection(18EE72).pptx
 
presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.
 
newswitchgearandprotection-130925105559-phpapp02.pptx
newswitchgearandprotection-130925105559-phpapp02.pptxnewswitchgearandprotection-130925105559-phpapp02.pptx
newswitchgearandprotection-130925105559-phpapp02.pptx
 
Electrical Basics-VBR
Electrical Basics-VBRElectrical Basics-VBR
Electrical Basics-VBR
 
400 kv Heerapura gss ppt by ishan pdf
400 kv Heerapura gss ppt by ishan pdf 400 kv Heerapura gss ppt by ishan pdf
400 kv Heerapura gss ppt by ishan pdf
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear
 
Surge arrester ppt
Surge arrester pptSurge arrester ppt
Surge arrester ppt
 
Presentation on 132/33KV BSPTCL(Bodhgaya Substation)
Presentation on 132/33KV BSPTCL(Bodhgaya Substation)Presentation on 132/33KV BSPTCL(Bodhgaya Substation)
Presentation on 132/33KV BSPTCL(Bodhgaya Substation)
 
SGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptx
 
Ppt on 400 kv gss raiser Bikaner- Yatendra Parashar
Ppt on 400 kv gss raiser Bikaner- Yatendra ParasharPpt on 400 kv gss raiser Bikaner- Yatendra Parashar
Ppt on 400 kv gss raiser Bikaner- Yatendra Parashar
 
lecture1423723756.pdf
lecture1423723756.pdflecture1423723756.pdf
lecture1423723756.pdf
 

Recently uploaded

Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .Satyam Kumar
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Study on Air-Water & Water-Water Heat Exchange in a Finned ďťżTube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned ďťżTube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned ďťżTube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned ďťżTube ExchangerAnamika Sarkar
 
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)dollysharma2066
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxvipinkmenon1
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 

Recently uploaded (20)

Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
POWER SYSTEMS-1 Complete notes examples
POWER SYSTEMS-1 Complete notes  examplesPOWER SYSTEMS-1 Complete notes  examples
POWER SYSTEMS-1 Complete notes examples
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
Study on Air-Water & Water-Water Heat Exchange in a Finned ďťżTube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned ďťżTube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned ďťżTube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned ďťżTube Exchanger
 
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptx
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Design and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdfDesign and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdf
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 

Switchgear and protection engineering Lecture 02.pptx

  • 3. Introduction to Switchgear •The importance of electric energy in everyday life has reached a stage that it is desirable to protect the power system from harm during fault condition and to ensure maximum continuity of supply •For this purpose, means must be provided to switch on and off generators, transmission lines, distributors and other equipment under both normal and abnormal conditions.
  • 4. Introduction to Switchgear •This is achieved by apparatus called switchgear •A switchgear essentially consists of switching and protecting devices such as switches, fuses, circuit breaker, relays, isolators, auto-recloser etc. •The apparatus used for switching, controlling, and protecting the electrical circuits and equipments is called switchgear
  • 5. Essentials Features of Switchgear 1.Complete reliability - when fault occurs on any part of the system, the switchgear must operate to isolate the faulty section from the reminder circuit. 2.Absolute certain discrimination – it should be able to discriminate between the fault section and the health section. Also, to isolate the fault section from the system in case of fault. This will ensure continuity of supply.
  • 6. Essentials Features of Switchgear 3. Quick Operation- must operates quickly so that no damage is done in any equipment in case of fault. 4. Provision for control manual– in case the electrical or electronics control fails, the necessary operation can be carried out through manual control.
  • 7. Essentials Features of Switchgear 5. Provision for instruments – may be in form of ammeter or voltmeter on the unit itself or the necessary current and voltage transformers for connecting to the main switchboard or a separate instrument panel.
  • 9. Isolating Switch (Isolator) •Isolating switch is an apparatus which makes a visible break in the circuit. •Isolator is used to open (or close) a circuit either when negligible current is interrupted (or established) or •When no significant change in the voltage across the terminals of each pole of the isolator will result from the operation.
  • 10. Isolating Switch (Isolator) •According to number of poles isolators may be classified as single pole, double poles isolators and three pole isolators. •According to type of service, isolators may be classified as indoor type or outdoor type
  • 12. Air BreakerType •This switch is also known as air breaker type circuit breaker. In this type, air at atmospheric pressure is used as extinguishing medium. •In air-breakers, the principle of high resistance is employed for arc interruption. •The arc resistance is increased by lengthening, splitting and cooling arc.
  • 13. Air BreakerType •AC air breaker are available in the range 400V to 12kV. Also, used in DC circuit up to 12kV. They are extensively used; With electric furnaces, With large motors requiring frequent starting,  In a place where chances of fire hazard exist.
  • 14. Lightning Arresters •Lightning arresters a re also known as surge diverter or surge arresters. •They connected between the line and ground at the substation and always acts as in shunt (parallel) with the equipment to be protected. •Perform their protective function by providing a low impedance path for the surge currents
  • 15. Lightning Arresters • So that the surge arrester’s protective level is less than the surge voltage withstanding capacity of the insulation of equipment to be protected.
  • 16. Bus-Bar Arrangements •When a number of generators and feeders operating at the same voltage have to be directly connected electrically •Bus-bars are used as common electrical components. •Bus-bars are copper rod or thin walled tubes and operate at constant voltage.
  • 19. Bus-Bar Arrangements 1. Single bus-bar system 2.Single bus-bar system with sectionalization 3. Duplicated bus-bar system
  • 20. Single Bus-bar System •It is the simplest design of bus-bar systems •It is used in small outdoor stations having relatively few outgoing and incoming feeders and lines. •In single bus-bar system, each generator and feeder is controlled by circuit breaker. •The isolators permit to isolate generators, feeders and circuit breaker from the bus-bar for maintenance.
  • 22. Single Bus-bar System 1. It has low initial cost 2.Less maintenance 3. Simple operation Advantages
  • 23. Single Bus-bar System 1. The bus-bar cannot be cleaned, tested or repaired without de-energising the whole system. 2. If a fault occurs on the bus bar itself, there is complete interruption of supply. 3. Any fault on then system is fed by all the generating capacity, resulting in very large fault currents. Disadvantages
  • 24. Single Bus-bar System with Sectionalisation •In large generating stations where several units are installed. •It is common to sectionalize the bus so that fault on any section of then bus-bar will not cause complete shutdown. •The bus-bar divided into two section connected by circuit breaker and isolators.
  • 25. Single Bus-bar System with Sectionalisation
  • 26. Single Bus-bar System with Sectionalisation 1. If a fault occurs on any section of the bus-bar, that section can be isolated without affecting the supply of other section. 2.If a fault occurs on any feeder, the fault current is much lower than unsectionalise bus-bar. 3. Eliminate the possibility of complete shut down during repair or maintenance of any section on bus-bar. Advantages
  • 27. Single Bus-bar System with Sectionalization 1. A circuit breaker should be used as sectionalizing switch. So that uncoupling of the bus-bars may be carried out safely during load transfer. 2. Moreover, the circuit breaker itself should be provided with isolators on both sides so that its maintenance can be done while the bus- bars are live. Points to note
  • 28. Duplicated Bus-bar System •In large stations, it is important that breakdown and maintenance should interfere as little ae possible with continuity of supply. •In to achieve this objective, duplicate bus-bar system is used in important substations. •Such a system consists of two bus-bar, a main bus-bar and spare bus-bar. •Each generator ad feeder may be connected to either bus-bar with the help of bus coupler which consists of circuit breaker and isolators.
  • 29. Duplicated Bus-bar System •Service is interrupted during switch from one bus-bar to another. •However, if it were desired to switch a circuit from one to another without interruption n there would have two circuit breakers per circuit. •Such a arrangement will be to expensive.
  • 31. 1. If repair ad maintenance are to be carried on main bus bar, the supply need not be interrupted as the entire load can be transferred to the spare bus-bar. 2.The testing of feeder circuit breaker can be done by putting them on spare bus bar, thus keeping main bus bar undisturbed 3. If a fault occurs on the bus bar, the continuity of the supply to the circuit can be maintained by transferring it to the other bus bar. Advantages Duplicated Bus-bar System
  • 32. Switchgear Accommodation •Depending upon the voltage to be handled, switchgear may be broadly classified into 1) Outdoor type 2) Indoor type •For voltage beyond 66kV, switchgear equipment is installed outdoor.
  • 33. Switchgear Accommodation •It is because for such voltages, the clearance between conductors and space required for switches, circuit breaker, transformer and other equipment become so great that it is not economical to install all such equipment indoor. •For voltage below 66kV, switchgear is generally installed indoor because of economical considerations.
  • 34. Fault in Power System •The normal path of the electric current is from the power source through copper (or aluminum) conductors in generators, transformers and transmission lines to the load • It is confined to this path by insulation. The insulation, however, may break down, either by the effect of temperature and age or by a physical accident,
  • 35. Fault in Power System •So that the current then follows an abnormal path generally known as Short Circuit or Fault •Any abnormal operating state of a power system is known as FAULT. •Faults in general consist of short circuits as well as open circuits. •Open circuit faults are less frequent than short circuit faults, and often they are transformed in to short circuits by subsequent events.
  • 36. Fault in Power System •A fault occurs when two or more conductors that are normally operate with potential difference come in contact with each other. •This fault may be caused by: 1. Sudden failure of a piece of equipment 2. Accidental damage or short circuit of overhead lines 3. Insulation failure resulting from lighting surges.
  • 37. Fault in Power System •The short circuited fault in three phase system can be classified into two categories; 1. Symmetrical faults 2. Unsymmetrical faults •Symmetrical faults gives rise to fault current. Equal fault current with 120o displacement. •Example of symmetrical fault is when all three conductors of a three phase lie brought together simultaneously into short circuit.
  • 38. Fault in Power System •Unsymmetrical faults give rise to unsymmetrical current. Unequal line currents with unequal displacement. •The unsymmetrical faults may take the following form; 1. Single line to ground fault 2. Line to line fault 3. Double line to ground fault
  • 39. Fault in Power System •The great majority faults on the power system are of unsymmetrical nature, the most common type being a short circuit from one line to ground.
  • 40. Fault in Power System •The open circuited fault in three phase system can be classified into two categories; 1. Single phase open circuit 2. Two phases open circuit 3. Three phase open circuit
  • 41. Fault in Power System •In terms of seriousness of consequences of a fault, short circuits are of far greater concern than open circuits, although some open circuits present some potential hazards to personnel
  • 42. Consequences of occurrence of fault 1. Damage to the equipment due to abnormally large and unbalanced currents and low voltages produced by the short circuit 2.Explosions may occur in the equipments which have insulating oil, particularly during short circuits.This may result in fire and hazardous conditions to personnel and equipments
  • 43. Consequences of occurrence of fault 3. Individual generators with reduced voltage in a power station or a group of generators operating at low voltage may lead to loss of synchronism, subsequently resulting in islanding.