SlideShare a Scribd company logo
1 of 15
Download to read offline
TRANSFORMER DIFFERENTIAL
RELAY- RET670
SITE TEST REPORT
Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00
Customer Name: National Grid-SA Page 1 of 15
Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.:
DATE:
TESTING ENGINEER-JAL CSD- ENGINEER
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
Note:
− The approved updated final settings should be applied and printed out from the relay by using the software of the
relay.
− The approved final setting and the printout final setting should be attached with this test format.
− The print out final setting should be signed by NG and Contractor.
− The following test format contains minimum required tests and some of settings are mentioned as an example and
not as limitation.
1. General Data & Information
2. Mechanical Checks and Visual Inspection
As per TCS –P–105 Rev -1, Item no 4.1& 4.12.1.1
ITEM DESCRIPTION REMARKS
1. Inspect for any physical damage or defects. Yes N/A
2. Verify connections and ferrules as per approved drawings Yes N/A
3. Check tightness of all the connections. Yes N/A
4. Check Apparatus List Yes N/A
5. Check relay version and switching elements on printed circuit board Yes N/A
3. Electrical Tests
As per TCS –P–105 Rev -1, Item no 4.2& 4.12.1.2
3.1. Function Test
ITEM DESCRIPTION REMARKS
1. Human Machine Interface (HMI) Checked. Yes N/A
2. Case Earthing checked. Yes N/A
3. LED’s Function Checked. Yes N/A
4. Trip Contacts Checked. Yes N/A
5. Reset Function Checked Yes N/A
6. Group active Functions Checked Yes N/A
7. Binary inputs checked. Yes N/A
8. Output Relays Checked Yes N/A
9. Event Display on HMI Screen Checked Yes N/A
10. Test switch / plug checked for correct function. Yes N/A
Panel No. CT Ratio of HV Side
Relay Type CT Ratio of LV Side
Manufacturer No. of contacts:
SERIAL NO Draw. & Sh No. :
Order - No. Conn.Diag.No.
Software Version DC. Auxiliary. Voltage
pto-coupler supply: Frequency Fn 60 Hz
TRANSFORMER DIFFERENTIAL
RELAY- RET670
SITE TEST REPORT
Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00
Customer Name: National Grid-SA Page 2 of 15
Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.:
DATE:
TESTING ENGINEER-JAL CSD- ENGINEER
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
11. Watchdog contacts checked Yes N/A
12. Current shorting facility. Yes N/A
3.2. Operating DC supply current
DC voltage (V) DC current w/o fault (mA) DC current with
fault(mA)
Max. calculated watt (W)
+
-
Limit: DC burden 50 watts. (Refer to the reference technical manual page 391).
3.3. Watch Dog Check
A. Supply OFF
TERMINALS (CLOSED) - :(X11:2,X11:3) :
TERMINALS (OPEN) - :( X11:2 X11:1) :
B. SUPPLY ON
TERMINALS (CLOSED) - :( X11:1, X11:2) :
TERMINALS (OPEN) - :(X11:3, X11:2) :
3.4. Time and Date Check:-
To check time &date go to main menu on the display for RET670 then system time and adjust time &date.
To test this, remove the auxiliary supply from the relay for approximately 30 seconds, then restoring the auxiliary
supply, the time and date should be correct.
Result: ____________
3.5. Setting Adopted:
Transformer Data: (All Values as an example)
Winding 1 ( HV ) Winding 2 ( LV ) Winding 3 (Tertiary.)
Connection Type Y0 y0 d1
Capacity ( MVA ) 60 60
Rated Voltage ( KV ) 132 13.8
Rated Current ( A ) 262 2510
CT Data:
CT 1 ( HV ) CT 2 ( LV ) CT 3 (Tertiary.)
Connection Type Y y
Primary Current ( A ) 300 3000
Secondary Current (A ) 1 1
Calculated Amplitude Matching Factor (K):
KX = CTX / Rated_Current_Of_Ref.Wdg
Where Ref.Wdg is First Wdg with Y connection. if no Y connection then HV side selected automatically
TRANSFORMER DIFFERENTIAL
RELAY- RET670
SITE TEST REPORT
Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00
Customer Name: National Grid-SA Page 3 of 15
Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.:
DATE:
TESTING ENGINEER-JAL CSD- ENGINEER
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
KHV = 1.14
KLV = 1.19
KTerit. =
General Differential Equation:
Where
1. is Differential Current
2. is Differential Current Contribution from W1 side
3. is Differential Current Contribution from W2 side
4. is Differential Current Contribution from W3 side
A, B, C is a coefficients depended on vector group; refer to Manual to get exact value.
3.6. Secondary Injection Tests: (All Values as an example)
3.6.1. Measurements (HV side):
TRM P40 - 9I+3U
Channel DUTY CTR
Injected
Values
Measured Values
REMARKS
Primary Sec
CH 1-I W1 CT IL1
CH 2-I W1 CT IL2
CH 3-I W1 CT IL3
CH 4-I W1 CT IN
CH 5-I W2 CT IN
CH 6-I W2 CT IL1
CH 7-I W2 CT IL2
CH 8-I W2 CT IL3
CH 9-I Spare
CH 10-U W1 VT Ph-R
CH 11-U W1 VT Ph-R
CH 12-U W1 VT Ph-R
TRM P41 – 6I+6U
CH 1-I Spare
CH 2-I Spare
CH 3-I Spare
CH 4-I Spare
CH 5-I Spare
TRANSFORMER DIFFERENTIAL
RELAY- RET670
SITE TEST REPORT
Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00
Customer Name: National Grid-SA Page 4 of 15
Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.:
DATE:
TESTING ENGINEER-JAL CSD- ENGINEER
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
CH 6-I Spare
CH 7-U Spare
CH 8-U Spare
CH 9-U Spare
CH 10-U Spare
CH 11-U Spare
CH 12-U Spare
Limits: Amplitude Accuracy; ± 0.5 % Ir
According to the Catalogue for Technical Data Page: 32
3.6.2. Pick- up & Drop- off Test For Differential Current (Id):
• This is single phase injection test.
• Disable SOTF facility.
Disable any Negative Sequence facility
• Disable zero Sequence removing facility.
Apply equation at page 3 the Diff. Eq. for single phase injection, 2 winding will be:
IDLx = A . KHV . Iw1Lx + B .( U2/U1) . KLV. Iw2L
Where x represents the concerted phase
HV Winding
Phase
Id min.
Set Value
Calculated
value (A)
Measured Value
( A )
Drop Out
PickUp
Ratio
Operating Time @ 2X
I pickup (ms)
Pick up Drop out
R
0.1 0.087
0.3 0.262
0.5 0.437
Y
0.1 0.087
0.3 0.262
0.5 0.437
B
0.1 0.087
0.3 0.262
0.5 0.437
TRANSFORMER DIFFERENTIAL
RELAY- RET670
SITE TEST REPORT
Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00
Customer Name: National Grid-SA Page 5 of 15
Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.:
DATE:
TESTING ENGINEER-JAL CSD- ENGINEER
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
LV Winding
Phase
Id min.
Set Value
Calculated
value ( A )
Measured Value
( A )
Drop Out
Pickup
Ratio
Operating Time @ 2X
I pickup (ms)
Pick up Drop out
R
0.1 0.084
0.3 0.251
0.5 0.418
Y
0.1 0.084
0.3 0.251
0.5 0.418
B
0.1 0.084
0.3 0.251
0.5 0.418
Limits: Pick up & Drop Out ±2% of Ir for I < Ir or ±2% of I for I > Ir, Reset Ratio > 95%,
Timing tolerance Typically 25 ms for 2 Id, and 12 ms for 5 Id for unrestrained function ,
According to the Catalogue for Technical Data Page: 143
3.6.3. Pick-up & Drop-off Test for Unrestrained Differential Current (id):
H.V Winding
Phase Set Value Calculated
value ( A )
Measured Value
( A ) Drop Out
Pickup
Ratio
Operating Time @ 5X
I pickup (ms)
Pick up Drop out
R
2.00 1.754
3.00 2.631
5.00 4.385
Y
2.00 1.754
3.00 2.631
5.00 4.385
B
2.00 1.754
3.00 2.631
5.00 4.385
TRANSFORMER DIFFERENTIAL
RELAY- RET670
SITE TEST REPORT
Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00
Customer Name: National Grid-SA Page 6 of 15
Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.:
DATE:
TESTING ENGINEER-JAL CSD- ENGINEER
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
L.V Winding
Phase Set Value
Calculated
value ( A )
Measured Value
( A ) Drop Out
Pickup
Ratio
Operating Time @ 5X
I pickup (ms)
Pick up Drop out
R
2.00 1.678
3.00 2.517
5.00 4.195
Y
2.00 1.678
3.00 2.517
5.00 4.195
B
2.00 1.678
3.00 2.517
5.00 4.195
3.6.4. BIAS CHARACTERISTIC TESTING
Inject H.V and L.V phase with equal current on each, and angle 0 for H.V and 180 for L.V, then decrease L.V
Phase until trip, while leave H.V with fixed current which will be the bias current, and record values and check
that corresponds to following equation.
TRANSFORMER DIFFERENTIAL
RELAY- RET670
SITE TEST REPORT
Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00
Customer Name: National Grid-SA Page 7 of 15
Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.:
DATE:
TESTING ENGINEER-JAL CSD- ENGINEER
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
a. Section 1 (All Values as an example)
Where bias current is between:
0 ≤ Ibias ≤ Endsection1
Idmin = 0.3 ,
Set End section1 = 1.25
Slope
section1
I bias
(A)
IH.V
(A)
Expected
IL.V (A)
Id calculated Measured IL.V (A) Errors %
R Y B R Y B
Idmin
0.3 0.262 0 0.3
0.4 0.350 0.084 0.3
1.00 0.875 0.586 0.3
Limits; ± 2 %Ir According to the Technical Reference Catalogue – Page24
b. SLOPE Section 2 (All Values as an example)
When bias current is between:
Endsection1 ≤ Ibias ≤ Endsection2
Trip Id = (Idmin + slope section2/100 *(Ibias - End section1) A
Where; Idmin ; The Basic Diff Current Setting.
To check more than one point at the same slope, Change the bias current value and the equation above can be
used, and also for other differential settings '' Different slopes, Is1 ''.
Apply the above procedure for each phase.
Set Idmin = 0.3
End section1 = 1.25
End section2 =3.0
Slope section 2 = 40%
Ibias
A
IH.V = Ibias /
kHV A
Expected IL.V
= (Ibias – Id) /
kLV (A)
Id calculated Measured IL.V (A) Errors %
R Y B R Y B
1.25 1.093 0.795 0.300
1.50 1.312 0.920 0.400
1.75 1.531 1.046 0.500
2.00 1.750 1.171 0.600
2.25 1.968 1.297 0.700
2.50 2.187 1.422 0.800
Limits; ± 2 %Ir According to the Technical Reference Catalogue – Page24
TRANSFORMER DIFFERENTIAL
RELAY- RET670
SITE TEST REPORT
Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00
Customer Name: National Grid-SA Page 8 of 15
Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.:
DATE:
TESTING ENGINEER-JAL CSD- ENGINEER
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
c. SLOPE Section3 (All Values as an example)
Repeat the test and check the result with the following equation;
When bias current is more than:
Ibias ≥ End section2
Trip Id = (Idmin + slope section2/100*(End section2 - End section1)) +
(Slope section3/100 * (Ibias- End section2)) A
Set End section1 = 1.25
End section2 =3.0
Slope section1 = 40%
Slope section2 = 80%
Idmin = 0.3
I bias
A
IH.V = Ibias /
kHV A
Expected IL.V = (Ibias
– Id) / kLV (A)
Id calculated Measured IL.V (A) Errors %
R Y B R Y B
3.0 2.624 1.673 1.000
3.5 3.062 1.757 1.400
4.0 3.499 1.841 1.800
4.5 3.936 1.925 2.200
5.0 4.374 2.008 2.600
6.0 5.249 2.176 3.4
Limits; ± 2 %Ir According to the Technical Reference Catalogue – Page24
3.6.5. Test of 2nd
Harmonics (All Values as an example)
Idmin = 0.3 Ib
Phase I2 / I1 ratio %
I1 ( F =60 Hz )
(Pickup Value)
I2 ( F = 120 Hz )
Expected Blocking Measured
R 10 0.300 0.030
Y 50 0.300 0.150
B 100 0.300 0.300
3.6.6. Test of 5th Harmonics
Phase I5 / I1 ratio % I1 ( F =60 Hz )
I5 ( F = 300 Hz )
Expected Blocking Measured
R 15 0.300 0.045
Y 30 0.300 0.090
B 50 0.300 0.150
TRANSFORMER DIFFERENTIAL
RELAY- RET670
SITE TEST REPORT
Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00
Customer Name: National Grid-SA Page 9 of 15
Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.:
DATE:
TESTING ENGINEER-JAL CSD- ENGINEER
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
3.6.7. Cross Block test
Winding IR IY IB
Cross Block
on
Cross Block
Off
HV
I > pickup with 2nd
harmonic
I > pickup without 2nd
harmonic
I > pickup with 2nd
harmonic
I > pickup without
2nd
harmonic
I > pickup without 2nd
harmonic
I > pickup with 2nd
harmonic
l.V
I > pickup with 2nd
harmonic
I > pickup without 2nd
harmonic
I > pickup with 2nd
harmonic
I > pickup without
2nd
harmonic
I > pickup without 2nd
harmonic
I > pickup with 2nd
harmonic
Test done at I2/I1= 15%, I5/I1 = 25 %
3.6.8. SOTF test:
This function used when energized the transformer with internal fault. where it use current gap principle to
overridden all harmonic and waveform block and trip quickly.
To test it , enable SOTF function and inject phase with harmonic and current over pickup value …. at two
condition :
a) Direct injection expected : Trip Status ___________
b) 2 stage , 1st
state normal load without trip ( note : inject current from both side H.V and L.V to
simulate the normal load ) and 2nd
state with value over pickup and have a 2nd
harmonic over I2/I1 setting .
Expected: Block Status ___________
3.6.9. Negative Sequence test: (All Values as an example)
a. IminNegSeq test :
INegSeq. =1/3 { IR + a2
IY + a IB } , where a = °∠1201
Irelay = Iinject * K
And we at test inject single phase then :
Irelaynegseq = 1/3 Iinject * K
IMinNegSeq setting IH.V ( > IMinNegSeq setting ) (A) Expected IL..V (A) Measured IL..V (A)
0.04 0.11 0.100
0.08 0.22 0.201
0.10 0.27 0.252
TRANSFORMER DIFFERENTIAL
RELAY- RET670
SITE TEST REPORT
Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00
Customer Name: National Grid-SA Page 10 of 15
Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.:
DATE:
TESTING ENGINEER-JAL CSD- ENGINEER
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
b. Negative sequence Relay Operating Angle (NegSeqROA ) test :
Inject H.V & L.V > IMinNegSeq
Inject H.V with angle zero degree and change the L.V to get the operating zone.
Neg.Seq.ROA setting Expected IL..V angle for operating zone (Deg)
Measured IL..V angle for operating
zone (Deg)
30 330 – 30
40 320 – 40
80 280 – 80
c. Sensitive negative sequence (turn-to-turn falut ) test:
This function based on Negative sequence discriminator. where if there is no start signal ( independent on
existence or not for start signal ) and the fault is classified as internal fault and at same time for H.V and L.V sides
the negative sequence current is greater than IminNegSeq .. then trip transformer
To test it , inject single phase from 2 winding in phase and increase them at same time until trip , ( must happen by
ssneg only not restrain function ) .
Status ____________________
3.6.10. Unrestrained negative sequence test:
Any start signal activate that function (i.e function independent on start signal ), where if the fault discriminate as
internal fault then remove any harmonic which block relay and trip quickly , And if fault discriminate as external
fault. Then if the signal is polluted with harmonics this will block relay else request trip.
Internal fault action (Expected: Trip): _____________
External fault (with harmonics) action (Expected: Block) :
External fault (without harmonics) action (Expected: Trip):
3.7. FINAL SETTING: (All values as an example)
Power Transformer Configuration
Rated Voltage W1
Rated Voltage W2
Rated Current W1
Rated Current W2
W1 Connection Type
W2 Connection Type
W2 Clock Number
ZS CurrSubtr W1
ZS CurrSubtr W2
ZS CurrSubtr W3
T configuration of W1
CT1 Rating W1
CT2 Rating W1
T configuration of W2
CT1 Rating W2
CT2 Rating W2
TRANSFORMER DIFFERENTIAL
RELAY- RET670
SITE TEST REPORT
Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00
Customer Name: National Grid-SA Page 11 of 15
Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.:
DATE:
TESTING ENGINEER-JAL CSD- ENGINEER
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
Differential Characteristics Configuration
Idmin:
End section1:
End section2:
Slope section2:
Slope section3:
Id Unre:
I2/I1 Ratio:
I5/I1 Ratio:
Idiff Alarm:
tAlarm delay:
Op Neg. Seq. Diff
I min Neg. Seq.
Neg Sequence ROA
SOTF
Cross Blocking
3.7.1. PICK UP & DROP OFF TEST FOR DIFFERENTIAL CURRENT (Id):
From eq. at page 2 the Diff. Eq. for single phase injection, 2 windge will be:
IDLx = A * Iw1Lx + (U2/U1) * B * Iw2Lx
And after applying zero sequence removing facility then
- H.V side:
I relay = I inject * (2 / 3) * KH.v .
Where KH.v =
- L.V side:
I relay = I inject * (2 / 3) * KL.v
where KL.v =
Where x represent the concerted phase
HV Winding
Phase
Id min.
Set Value
Calculated
value
Measured Value
Drop Out
PickUp
Ratio
Operating Time @ 2X
I pickup (ms)
Pick up Drop out
R
Y
B
TRANSFORMER DIFFERENTIAL
RELAY- RET670
SITE TEST REPORT
Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00
Customer Name: National Grid-SA Page 12 of 15
Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.:
DATE:
TESTING ENGINEER-JAL CSD- ENGINEER
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
LV Winding
Phase
Id min.
Set Value
Calculated value
Measured Value
Drop Out
PickUp
Ratio
Operating Time @ 2X
I pickup (ms)
Pick up Drop out
R
Y
B
Limits: Pick up & Drop Out ±2% of Ir for I < Ir or ±2% of I for I > Ir, Reset Ratio > 95%,
Timing tolerance Typically 25 ms, According to the Catalogue for Technical Data Page: 143
Pick-up & Drop-off Test for Unrestrained Differential Current (Id):
HV winding
Phase
Iunrest.
Set Value
Calculated value
Measured Value
Drop Out
PickUp
Ratio
Operating Time @ 2X
I pickup (ms)
Pick up Drop out
R
Y
B
LV Winding
Phase
Iunrest.
Set Value
Calculated value
Measured Value
Drop Out
PickUp
Ratio
Operating Time
@ 2X
I pickup (ms)
Pick up Drop out
R
Y
B
Limits: Pick up & Drop Out ±2% of Ir for I < Ir or ±2% of I for I > Ir, Reset Ratio > 95%,
Timing tolerance Typically 25 ms, According to the Catalogue for Technical Data Page: 143
3.7.2. BIAS CHARACTERISTIC TESTING
Section 1
When bias current is between:
0 ≤ Ibias ≤ Endsection1
Slope
section1
I bias
A
IH.V
A
Expected IL.V
(A)
Id calculated Measured IL.V (A) Errors %
R Y B R Y B
Idmin
TRANSFORMER DIFFERENTIAL
RELAY- RET670
SITE TEST REPORT
Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00
Customer Name: National Grid-SA Page 13 of 15
Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.:
DATE:
TESTING ENGINEER-JAL CSD- ENGINEER
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
Limits; ± 2 %Ir According to the Technical Reference Catalogue – Page24
SLOPE Section 2
When bias current is between:
Endsection1 ≤ Ibias ≤ Endsection2
Trip = (Idmin + slope section2/100 *(Ibias - End section1) A
I bias
A
IH.V
A
Expected
IL.V (A)
Id calculated Measured IL.V (A) Errors %
R Y B R Y B
Limits; ± 2 %Ir According to the Technical Reference Catalogue – Page24
SLOPE Section3
When bias current is more than:
Ibias ≥ End section2
Trip = (Idmin + slope section2/100*(End section2 - End section1)) +
(Slope section3/100 * (Ibias- End section2) A
I bias
A
IH.V
A
Expected
IL.V (A)
Id
calculated
Measured IL.V (A) Errors %
R Y B R Y B
Limits; ± 2 %Ir According to the Technical Reference Catalogue – Page24
3.7.3. Test of 2nd
Harmonics
Phase I2 / I1 ratio %
I1 ( F =60 Hz )
(Pickup Value)
I2 ( F = 120 Hz )
Expected Blocking Measured
R
Y
B
TRANSFORMER DIFFERENTIAL
RELAY- RET670
SITE TEST REPORT
Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00
Customer Name: National Grid-SA Page 14 of 15
Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.:
DATE:
TESTING ENGINEER-JAL CSD- ENGINEER
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
3.7.4. Test of 5th Harmonics
Phase I5 / I1 ratio % I1 ( F =60 Hz )
I5 ( F = 300 Hz )
Expected Blocking Measured
R
Y
B
3.7.5. Negative Sequence test:
IminNegSeq test:
IMinNegSeq setting
Expected
IH.V (A)
Expected
IL.V (A)
Measured
IL.V (A)
Measured
IH.V (A)
Negative sequence Relay Operating Angle (NegSeqROA ) test :
Inject H.V & L.V > IMinNegSeq
Inject H.V with angle zero degree and change the L.V to get the operating zone.
NegSeqROA setting
Expected IL..V angle for operating zone
(Deg)
Measured IL..V angle for operating zone (Deg)
3.7.6. Sensitive negative sequence (turn-to-turn falut) test:
Status ____________________
3.7.7. Unrestrained negative sequence test:
Internal fault action (Expected: Trip): _____________
External fault (with harmonics) action (Expected: Block) :
External fault (without harmonics) action (Expected: Trip): ____Trip indication test: ____
No. Type of fault Led Color Check
TRANSFORMER DIFFERENTIAL
RELAY- RET670
SITE TEST REPORT
Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00
Customer Name: National Grid-SA Page 15 of 15
Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.:
DATE:
TESTING ENGINEER-JAL CSD- ENGINEER
Signature: ________________ Signature: ________________
Name : ________________ Name : ________________
3.7.8.Disturbance recorder checked [ ].
3.7.9.Binary outputs and inputs checked [ ].
3.7.10. Attach the Final setting print out of relay:
3.8. Test Equipment Used
Sl. No Description Make Equipment Sl. No Calibration
Date
Calibration
Due Date
1
2
3

More Related Content

What's hot

RELAY ETTING CALCULATION REV-A (DG-298).pdf
RELAY ETTING CALCULATION REV-A (DG-298).pdfRELAY ETTING CALCULATION REV-A (DG-298).pdf
RELAY ETTING CALCULATION REV-A (DG-298).pdfJayWin2
 
Differential protection
Differential protectionDifferential protection
Differential protectionRishi Tandon
 
Stability test of transformer
Stability test of transformerStability test of transformer
Stability test of transformerSantu Mondal
 
Digital transformer protection systems
Digital transformer protection systemsDigital transformer protection systems
Digital transformer protection systemsmichaeljmack
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settingsmichaeljmack
 
RELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATIONRELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATIONMd Sarowar Alam
 
CT design aspects - Nageswar-6
CT design aspects - Nageswar-6CT design aspects - Nageswar-6
CT design aspects - Nageswar-6Nageswar Rao
 
Basics of overcurrent protection
Basics of overcurrent protectionBasics of overcurrent protection
Basics of overcurrent protectionSalim Palayi
 
Transformer vector group_test_conditions
Transformer vector group_test_conditionsTransformer vector group_test_conditions
Transformer vector group_test_conditionsSARAVANAN A
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsPower System Operation
 
Understanding and testing_the_abb_red670
Understanding and testing_the_abb_red670Understanding and testing_the_abb_red670
Understanding and testing_the_abb_red670طه محمد
 
Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrentmichaeljmack
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introductionH. Kheir
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 
Power Transformer Differential protection
Power Transformer Differential protectionPower Transformer Differential protection
Power Transformer Differential protectionRishi Tandon
 
Transformer testing
Transformer testingTransformer testing
Transformer testingajayknows
 
Power transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines rPower transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines rAshish Patel
 
Testing of power_transformers_kt_80_gb_2
Testing of power_transformers_kt_80_gb_2Testing of power_transformers_kt_80_gb_2
Testing of power_transformers_kt_80_gb_2koperundeviG
 

What's hot (20)

RELAY ETTING CALCULATION REV-A (DG-298).pdf
RELAY ETTING CALCULATION REV-A (DG-298).pdfRELAY ETTING CALCULATION REV-A (DG-298).pdf
RELAY ETTING CALCULATION REV-A (DG-298).pdf
 
Differential protection
Differential protectionDifferential protection
Differential protection
 
Stability test of transformer
Stability test of transformerStability test of transformer
Stability test of transformer
 
Digital transformer protection systems
Digital transformer protection systemsDigital transformer protection systems
Digital transformer protection systems
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settings
 
Transformers Protection
Transformers ProtectionTransformers Protection
Transformers Protection
 
RELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATIONRELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATION
 
CT design aspects - Nageswar-6
CT design aspects - Nageswar-6CT design aspects - Nageswar-6
CT design aspects - Nageswar-6
 
Basics of overcurrent protection
Basics of overcurrent protectionBasics of overcurrent protection
Basics of overcurrent protection
 
Transformer vector group_test_conditions
Transformer vector group_test_conditionsTransformer vector group_test_conditions
Transformer vector group_test_conditions
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
 
Understanding and testing_the_abb_red670
Understanding and testing_the_abb_red670Understanding and testing_the_abb_red670
Understanding and testing_the_abb_red670
 
Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrent
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introduction
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Power Transformer Differential protection
Power Transformer Differential protectionPower Transformer Differential protection
Power Transformer Differential protection
 
Transformer testing
Transformer testingTransformer testing
Transformer testing
 
Insulation Resistance Test
Insulation Resistance TestInsulation Resistance Test
Insulation Resistance Test
 
Power transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines rPower transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines r
 
Testing of power_transformers_kt_80_gb_2
Testing of power_transformers_kt_80_gb_2Testing of power_transformers_kt_80_gb_2
Testing of power_transformers_kt_80_gb_2
 

Similar to 04 ret670 test report

AVR_GENERAL KOSTI.ppt
AVR_GENERAL KOSTI.pptAVR_GENERAL KOSTI.ppt
AVR_GENERAL KOSTI.pptprasadkappala
 
Advanced motion controls b12a6
Advanced motion controls b12a6Advanced motion controls b12a6
Advanced motion controls b12a6Electromate
 
Advanced motion controls avb100c200
Advanced motion controls avb100c200Advanced motion controls avb100c200
Advanced motion controls avb100c200Electromate
 
Advanced motion controls b100a20
Advanced motion controls b100a20Advanced motion controls b100a20
Advanced motion controls b100a20Electromate
 
Uniohm resistors datasheet for car -anti-sulfurized thick film chip resistors...
Uniohm resistors datasheet for car -anti-sulfurized thick film chip resistors...Uniohm resistors datasheet for car -anti-sulfurized thick film chip resistors...
Uniohm resistors datasheet for car -anti-sulfurized thick film chip resistors...Felix Law
 
Advanced motion controls b60a40ac
Advanced motion controls b60a40acAdvanced motion controls b60a40ac
Advanced motion controls b60a40acElectromate
 
Advanced motion controls avb250a060
Advanced motion controls avb250a060Advanced motion controls avb250a060
Advanced motion controls avb250a060Electromate
 
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdfChadWood16
 
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdfAhmadHamouda3
 
Advanced motion controls b30a40ac
Advanced motion controls b30a40acAdvanced motion controls b30a40ac
Advanced motion controls b30a40acElectromate
 
Advanced motion controls ab200a100
Advanced motion controls ab200a100Advanced motion controls ab200a100
Advanced motion controls ab200a100Electromate
 
Advanced motion controls b100a40ac
Advanced motion controls b100a40acAdvanced motion controls b100a40ac
Advanced motion controls b100a40acElectromate
 
Bta08 600 bw3-d tiristor bidireccional
Bta08 600 bw3-d  tiristor bidireccionalBta08 600 bw3-d  tiristor bidireccional
Bta08 600 bw3-d tiristor bidireccional8525
 
Uniohm resistors datasheet high quality anti-sulfurized thick film chip resis...
Uniohm resistors datasheet high quality anti-sulfurized thick film chip resis...Uniohm resistors datasheet high quality anti-sulfurized thick film chip resis...
Uniohm resistors datasheet high quality anti-sulfurized thick film chip resis...Felix Law
 
Advanced motion controls sx30a8
Advanced motion controls sx30a8Advanced motion controls sx30a8
Advanced motion controls sx30a8Electromate
 
Advanced motion controls b15a8
Advanced motion controls b15a8Advanced motion controls b15a8
Advanced motion controls b15a8Electromate
 
Advanced motion controls 10a8dd
Advanced motion controls 10a8ddAdvanced motion controls 10a8dd
Advanced motion controls 10a8ddElectromate
 

Similar to 04 ret670 test report (20)

AVR_GENERAL KOSTI.ppt
AVR_GENERAL KOSTI.pptAVR_GENERAL KOSTI.ppt
AVR_GENERAL KOSTI.ppt
 
Advanced motion controls b12a6
Advanced motion controls b12a6Advanced motion controls b12a6
Advanced motion controls b12a6
 
Advanced motion controls avb100c200
Advanced motion controls avb100c200Advanced motion controls avb100c200
Advanced motion controls avb100c200
 
Advanced motion controls b100a20
Advanced motion controls b100a20Advanced motion controls b100a20
Advanced motion controls b100a20
 
Uniohm resistors datasheet for car -anti-sulfurized thick film chip resistors...
Uniohm resistors datasheet for car -anti-sulfurized thick film chip resistors...Uniohm resistors datasheet for car -anti-sulfurized thick film chip resistors...
Uniohm resistors datasheet for car -anti-sulfurized thick film chip resistors...
 
Advanced motion controls b60a40ac
Advanced motion controls b60a40acAdvanced motion controls b60a40ac
Advanced motion controls b60a40ac
 
1.3 ron 3
1.3 ron 31.3 ron 3
1.3 ron 3
 
Advanced motion controls avb250a060
Advanced motion controls avb250a060Advanced motion controls avb250a060
Advanced motion controls avb250a060
 
1.2 ron 2
1.2 ron 21.2 ron 2
1.2 ron 2
 
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
 
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
187787508-Over-Current-Earth-Fault-Setting-Calculations.pdf
 
Advanced motion controls b30a40ac
Advanced motion controls b30a40acAdvanced motion controls b30a40ac
Advanced motion controls b30a40ac
 
Advanced motion controls ab200a100
Advanced motion controls ab200a100Advanced motion controls ab200a100
Advanced motion controls ab200a100
 
Advanced motion controls b100a40ac
Advanced motion controls b100a40acAdvanced motion controls b100a40ac
Advanced motion controls b100a40ac
 
Bta08 600 bw3-d tiristor bidireccional
Bta08 600 bw3-d  tiristor bidireccionalBta08 600 bw3-d  tiristor bidireccional
Bta08 600 bw3-d tiristor bidireccional
 
Uniohm resistors datasheet high quality anti-sulfurized thick film chip resis...
Uniohm resistors datasheet high quality anti-sulfurized thick film chip resis...Uniohm resistors datasheet high quality anti-sulfurized thick film chip resis...
Uniohm resistors datasheet high quality anti-sulfurized thick film chip resis...
 
Advanced motion controls sx30a8
Advanced motion controls sx30a8Advanced motion controls sx30a8
Advanced motion controls sx30a8
 
Advanced motion controls b15a8
Advanced motion controls b15a8Advanced motion controls b15a8
Advanced motion controls b15a8
 
EAPL TIMER & CONTROLLER PRICE LIST wef 01-08-2022.pdf
EAPL TIMER & CONTROLLER PRICE LIST wef 01-08-2022.pdfEAPL TIMER & CONTROLLER PRICE LIST wef 01-08-2022.pdf
EAPL TIMER & CONTROLLER PRICE LIST wef 01-08-2022.pdf
 
Advanced motion controls 10a8dd
Advanced motion controls 10a8ddAdvanced motion controls 10a8dd
Advanced motion controls 10a8dd
 

Recently uploaded

APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 

Recently uploaded (20)

APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 

04 ret670 test report

  • 1. TRANSFORMER DIFFERENTIAL RELAY- RET670 SITE TEST REPORT Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00 Customer Name: National Grid-SA Page 1 of 15 Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.: DATE: TESTING ENGINEER-JAL CSD- ENGINEER Signature: ________________ Signature: ________________ Name : ________________ Name : ________________ Note: − The approved updated final settings should be applied and printed out from the relay by using the software of the relay. − The approved final setting and the printout final setting should be attached with this test format. − The print out final setting should be signed by NG and Contractor. − The following test format contains minimum required tests and some of settings are mentioned as an example and not as limitation. 1. General Data & Information 2. Mechanical Checks and Visual Inspection As per TCS –P–105 Rev -1, Item no 4.1& 4.12.1.1 ITEM DESCRIPTION REMARKS 1. Inspect for any physical damage or defects. Yes N/A 2. Verify connections and ferrules as per approved drawings Yes N/A 3. Check tightness of all the connections. Yes N/A 4. Check Apparatus List Yes N/A 5. Check relay version and switching elements on printed circuit board Yes N/A 3. Electrical Tests As per TCS –P–105 Rev -1, Item no 4.2& 4.12.1.2 3.1. Function Test ITEM DESCRIPTION REMARKS 1. Human Machine Interface (HMI) Checked. Yes N/A 2. Case Earthing checked. Yes N/A 3. LED’s Function Checked. Yes N/A 4. Trip Contacts Checked. Yes N/A 5. Reset Function Checked Yes N/A 6. Group active Functions Checked Yes N/A 7. Binary inputs checked. Yes N/A 8. Output Relays Checked Yes N/A 9. Event Display on HMI Screen Checked Yes N/A 10. Test switch / plug checked for correct function. Yes N/A Panel No. CT Ratio of HV Side Relay Type CT Ratio of LV Side Manufacturer No. of contacts: SERIAL NO Draw. & Sh No. : Order - No. Conn.Diag.No. Software Version DC. Auxiliary. Voltage pto-coupler supply: Frequency Fn 60 Hz
  • 2. TRANSFORMER DIFFERENTIAL RELAY- RET670 SITE TEST REPORT Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00 Customer Name: National Grid-SA Page 2 of 15 Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.: DATE: TESTING ENGINEER-JAL CSD- ENGINEER Signature: ________________ Signature: ________________ Name : ________________ Name : ________________ 11. Watchdog contacts checked Yes N/A 12. Current shorting facility. Yes N/A 3.2. Operating DC supply current DC voltage (V) DC current w/o fault (mA) DC current with fault(mA) Max. calculated watt (W) + - Limit: DC burden 50 watts. (Refer to the reference technical manual page 391). 3.3. Watch Dog Check A. Supply OFF TERMINALS (CLOSED) - :(X11:2,X11:3) : TERMINALS (OPEN) - :( X11:2 X11:1) : B. SUPPLY ON TERMINALS (CLOSED) - :( X11:1, X11:2) : TERMINALS (OPEN) - :(X11:3, X11:2) : 3.4. Time and Date Check:- To check time &date go to main menu on the display for RET670 then system time and adjust time &date. To test this, remove the auxiliary supply from the relay for approximately 30 seconds, then restoring the auxiliary supply, the time and date should be correct. Result: ____________ 3.5. Setting Adopted: Transformer Data: (All Values as an example) Winding 1 ( HV ) Winding 2 ( LV ) Winding 3 (Tertiary.) Connection Type Y0 y0 d1 Capacity ( MVA ) 60 60 Rated Voltage ( KV ) 132 13.8 Rated Current ( A ) 262 2510 CT Data: CT 1 ( HV ) CT 2 ( LV ) CT 3 (Tertiary.) Connection Type Y y Primary Current ( A ) 300 3000 Secondary Current (A ) 1 1 Calculated Amplitude Matching Factor (K): KX = CTX / Rated_Current_Of_Ref.Wdg Where Ref.Wdg is First Wdg with Y connection. if no Y connection then HV side selected automatically
  • 3. TRANSFORMER DIFFERENTIAL RELAY- RET670 SITE TEST REPORT Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00 Customer Name: National Grid-SA Page 3 of 15 Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.: DATE: TESTING ENGINEER-JAL CSD- ENGINEER Signature: ________________ Signature: ________________ Name : ________________ Name : ________________ KHV = 1.14 KLV = 1.19 KTerit. = General Differential Equation: Where 1. is Differential Current 2. is Differential Current Contribution from W1 side 3. is Differential Current Contribution from W2 side 4. is Differential Current Contribution from W3 side A, B, C is a coefficients depended on vector group; refer to Manual to get exact value. 3.6. Secondary Injection Tests: (All Values as an example) 3.6.1. Measurements (HV side): TRM P40 - 9I+3U Channel DUTY CTR Injected Values Measured Values REMARKS Primary Sec CH 1-I W1 CT IL1 CH 2-I W1 CT IL2 CH 3-I W1 CT IL3 CH 4-I W1 CT IN CH 5-I W2 CT IN CH 6-I W2 CT IL1 CH 7-I W2 CT IL2 CH 8-I W2 CT IL3 CH 9-I Spare CH 10-U W1 VT Ph-R CH 11-U W1 VT Ph-R CH 12-U W1 VT Ph-R TRM P41 – 6I+6U CH 1-I Spare CH 2-I Spare CH 3-I Spare CH 4-I Spare CH 5-I Spare
  • 4. TRANSFORMER DIFFERENTIAL RELAY- RET670 SITE TEST REPORT Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00 Customer Name: National Grid-SA Page 4 of 15 Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.: DATE: TESTING ENGINEER-JAL CSD- ENGINEER Signature: ________________ Signature: ________________ Name : ________________ Name : ________________ CH 6-I Spare CH 7-U Spare CH 8-U Spare CH 9-U Spare CH 10-U Spare CH 11-U Spare CH 12-U Spare Limits: Amplitude Accuracy; ± 0.5 % Ir According to the Catalogue for Technical Data Page: 32 3.6.2. Pick- up & Drop- off Test For Differential Current (Id): • This is single phase injection test. • Disable SOTF facility. Disable any Negative Sequence facility • Disable zero Sequence removing facility. Apply equation at page 3 the Diff. Eq. for single phase injection, 2 winding will be: IDLx = A . KHV . Iw1Lx + B .( U2/U1) . KLV. Iw2L Where x represents the concerted phase HV Winding Phase Id min. Set Value Calculated value (A) Measured Value ( A ) Drop Out PickUp Ratio Operating Time @ 2X I pickup (ms) Pick up Drop out R 0.1 0.087 0.3 0.262 0.5 0.437 Y 0.1 0.087 0.3 0.262 0.5 0.437 B 0.1 0.087 0.3 0.262 0.5 0.437
  • 5. TRANSFORMER DIFFERENTIAL RELAY- RET670 SITE TEST REPORT Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00 Customer Name: National Grid-SA Page 5 of 15 Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.: DATE: TESTING ENGINEER-JAL CSD- ENGINEER Signature: ________________ Signature: ________________ Name : ________________ Name : ________________ LV Winding Phase Id min. Set Value Calculated value ( A ) Measured Value ( A ) Drop Out Pickup Ratio Operating Time @ 2X I pickup (ms) Pick up Drop out R 0.1 0.084 0.3 0.251 0.5 0.418 Y 0.1 0.084 0.3 0.251 0.5 0.418 B 0.1 0.084 0.3 0.251 0.5 0.418 Limits: Pick up & Drop Out ±2% of Ir for I < Ir or ±2% of I for I > Ir, Reset Ratio > 95%, Timing tolerance Typically 25 ms for 2 Id, and 12 ms for 5 Id for unrestrained function , According to the Catalogue for Technical Data Page: 143 3.6.3. Pick-up & Drop-off Test for Unrestrained Differential Current (id): H.V Winding Phase Set Value Calculated value ( A ) Measured Value ( A ) Drop Out Pickup Ratio Operating Time @ 5X I pickup (ms) Pick up Drop out R 2.00 1.754 3.00 2.631 5.00 4.385 Y 2.00 1.754 3.00 2.631 5.00 4.385 B 2.00 1.754 3.00 2.631 5.00 4.385
  • 6. TRANSFORMER DIFFERENTIAL RELAY- RET670 SITE TEST REPORT Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00 Customer Name: National Grid-SA Page 6 of 15 Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.: DATE: TESTING ENGINEER-JAL CSD- ENGINEER Signature: ________________ Signature: ________________ Name : ________________ Name : ________________ L.V Winding Phase Set Value Calculated value ( A ) Measured Value ( A ) Drop Out Pickup Ratio Operating Time @ 5X I pickup (ms) Pick up Drop out R 2.00 1.678 3.00 2.517 5.00 4.195 Y 2.00 1.678 3.00 2.517 5.00 4.195 B 2.00 1.678 3.00 2.517 5.00 4.195 3.6.4. BIAS CHARACTERISTIC TESTING Inject H.V and L.V phase with equal current on each, and angle 0 for H.V and 180 for L.V, then decrease L.V Phase until trip, while leave H.V with fixed current which will be the bias current, and record values and check that corresponds to following equation.
  • 7. TRANSFORMER DIFFERENTIAL RELAY- RET670 SITE TEST REPORT Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00 Customer Name: National Grid-SA Page 7 of 15 Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.: DATE: TESTING ENGINEER-JAL CSD- ENGINEER Signature: ________________ Signature: ________________ Name : ________________ Name : ________________ a. Section 1 (All Values as an example) Where bias current is between: 0 ≤ Ibias ≤ Endsection1 Idmin = 0.3 , Set End section1 = 1.25 Slope section1 I bias (A) IH.V (A) Expected IL.V (A) Id calculated Measured IL.V (A) Errors % R Y B R Y B Idmin 0.3 0.262 0 0.3 0.4 0.350 0.084 0.3 1.00 0.875 0.586 0.3 Limits; ± 2 %Ir According to the Technical Reference Catalogue – Page24 b. SLOPE Section 2 (All Values as an example) When bias current is between: Endsection1 ≤ Ibias ≤ Endsection2 Trip Id = (Idmin + slope section2/100 *(Ibias - End section1) A Where; Idmin ; The Basic Diff Current Setting. To check more than one point at the same slope, Change the bias current value and the equation above can be used, and also for other differential settings '' Different slopes, Is1 ''. Apply the above procedure for each phase. Set Idmin = 0.3 End section1 = 1.25 End section2 =3.0 Slope section 2 = 40% Ibias A IH.V = Ibias / kHV A Expected IL.V = (Ibias – Id) / kLV (A) Id calculated Measured IL.V (A) Errors % R Y B R Y B 1.25 1.093 0.795 0.300 1.50 1.312 0.920 0.400 1.75 1.531 1.046 0.500 2.00 1.750 1.171 0.600 2.25 1.968 1.297 0.700 2.50 2.187 1.422 0.800 Limits; ± 2 %Ir According to the Technical Reference Catalogue – Page24
  • 8. TRANSFORMER DIFFERENTIAL RELAY- RET670 SITE TEST REPORT Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00 Customer Name: National Grid-SA Page 8 of 15 Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.: DATE: TESTING ENGINEER-JAL CSD- ENGINEER Signature: ________________ Signature: ________________ Name : ________________ Name : ________________ c. SLOPE Section3 (All Values as an example) Repeat the test and check the result with the following equation; When bias current is more than: Ibias ≥ End section2 Trip Id = (Idmin + slope section2/100*(End section2 - End section1)) + (Slope section3/100 * (Ibias- End section2)) A Set End section1 = 1.25 End section2 =3.0 Slope section1 = 40% Slope section2 = 80% Idmin = 0.3 I bias A IH.V = Ibias / kHV A Expected IL.V = (Ibias – Id) / kLV (A) Id calculated Measured IL.V (A) Errors % R Y B R Y B 3.0 2.624 1.673 1.000 3.5 3.062 1.757 1.400 4.0 3.499 1.841 1.800 4.5 3.936 1.925 2.200 5.0 4.374 2.008 2.600 6.0 5.249 2.176 3.4 Limits; ± 2 %Ir According to the Technical Reference Catalogue – Page24 3.6.5. Test of 2nd Harmonics (All Values as an example) Idmin = 0.3 Ib Phase I2 / I1 ratio % I1 ( F =60 Hz ) (Pickup Value) I2 ( F = 120 Hz ) Expected Blocking Measured R 10 0.300 0.030 Y 50 0.300 0.150 B 100 0.300 0.300 3.6.6. Test of 5th Harmonics Phase I5 / I1 ratio % I1 ( F =60 Hz ) I5 ( F = 300 Hz ) Expected Blocking Measured R 15 0.300 0.045 Y 30 0.300 0.090 B 50 0.300 0.150
  • 9. TRANSFORMER DIFFERENTIAL RELAY- RET670 SITE TEST REPORT Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00 Customer Name: National Grid-SA Page 9 of 15 Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.: DATE: TESTING ENGINEER-JAL CSD- ENGINEER Signature: ________________ Signature: ________________ Name : ________________ Name : ________________ 3.6.7. Cross Block test Winding IR IY IB Cross Block on Cross Block Off HV I > pickup with 2nd harmonic I > pickup without 2nd harmonic I > pickup with 2nd harmonic I > pickup without 2nd harmonic I > pickup without 2nd harmonic I > pickup with 2nd harmonic l.V I > pickup with 2nd harmonic I > pickup without 2nd harmonic I > pickup with 2nd harmonic I > pickup without 2nd harmonic I > pickup without 2nd harmonic I > pickup with 2nd harmonic Test done at I2/I1= 15%, I5/I1 = 25 % 3.6.8. SOTF test: This function used when energized the transformer with internal fault. where it use current gap principle to overridden all harmonic and waveform block and trip quickly. To test it , enable SOTF function and inject phase with harmonic and current over pickup value …. at two condition : a) Direct injection expected : Trip Status ___________ b) 2 stage , 1st state normal load without trip ( note : inject current from both side H.V and L.V to simulate the normal load ) and 2nd state with value over pickup and have a 2nd harmonic over I2/I1 setting . Expected: Block Status ___________ 3.6.9. Negative Sequence test: (All Values as an example) a. IminNegSeq test : INegSeq. =1/3 { IR + a2 IY + a IB } , where a = °∠1201 Irelay = Iinject * K And we at test inject single phase then : Irelaynegseq = 1/3 Iinject * K IMinNegSeq setting IH.V ( > IMinNegSeq setting ) (A) Expected IL..V (A) Measured IL..V (A) 0.04 0.11 0.100 0.08 0.22 0.201 0.10 0.27 0.252
  • 10. TRANSFORMER DIFFERENTIAL RELAY- RET670 SITE TEST REPORT Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00 Customer Name: National Grid-SA Page 10 of 15 Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.: DATE: TESTING ENGINEER-JAL CSD- ENGINEER Signature: ________________ Signature: ________________ Name : ________________ Name : ________________ b. Negative sequence Relay Operating Angle (NegSeqROA ) test : Inject H.V & L.V > IMinNegSeq Inject H.V with angle zero degree and change the L.V to get the operating zone. Neg.Seq.ROA setting Expected IL..V angle for operating zone (Deg) Measured IL..V angle for operating zone (Deg) 30 330 – 30 40 320 – 40 80 280 – 80 c. Sensitive negative sequence (turn-to-turn falut ) test: This function based on Negative sequence discriminator. where if there is no start signal ( independent on existence or not for start signal ) and the fault is classified as internal fault and at same time for H.V and L.V sides the negative sequence current is greater than IminNegSeq .. then trip transformer To test it , inject single phase from 2 winding in phase and increase them at same time until trip , ( must happen by ssneg only not restrain function ) . Status ____________________ 3.6.10. Unrestrained negative sequence test: Any start signal activate that function (i.e function independent on start signal ), where if the fault discriminate as internal fault then remove any harmonic which block relay and trip quickly , And if fault discriminate as external fault. Then if the signal is polluted with harmonics this will block relay else request trip. Internal fault action (Expected: Trip): _____________ External fault (with harmonics) action (Expected: Block) : External fault (without harmonics) action (Expected: Trip): 3.7. FINAL SETTING: (All values as an example) Power Transformer Configuration Rated Voltage W1 Rated Voltage W2 Rated Current W1 Rated Current W2 W1 Connection Type W2 Connection Type W2 Clock Number ZS CurrSubtr W1 ZS CurrSubtr W2 ZS CurrSubtr W3 T configuration of W1 CT1 Rating W1 CT2 Rating W1 T configuration of W2 CT1 Rating W2 CT2 Rating W2
  • 11. TRANSFORMER DIFFERENTIAL RELAY- RET670 SITE TEST REPORT Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00 Customer Name: National Grid-SA Page 11 of 15 Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.: DATE: TESTING ENGINEER-JAL CSD- ENGINEER Signature: ________________ Signature: ________________ Name : ________________ Name : ________________ Differential Characteristics Configuration Idmin: End section1: End section2: Slope section2: Slope section3: Id Unre: I2/I1 Ratio: I5/I1 Ratio: Idiff Alarm: tAlarm delay: Op Neg. Seq. Diff I min Neg. Seq. Neg Sequence ROA SOTF Cross Blocking 3.7.1. PICK UP & DROP OFF TEST FOR DIFFERENTIAL CURRENT (Id): From eq. at page 2 the Diff. Eq. for single phase injection, 2 windge will be: IDLx = A * Iw1Lx + (U2/U1) * B * Iw2Lx And after applying zero sequence removing facility then - H.V side: I relay = I inject * (2 / 3) * KH.v . Where KH.v = - L.V side: I relay = I inject * (2 / 3) * KL.v where KL.v = Where x represent the concerted phase HV Winding Phase Id min. Set Value Calculated value Measured Value Drop Out PickUp Ratio Operating Time @ 2X I pickup (ms) Pick up Drop out R Y B
  • 12. TRANSFORMER DIFFERENTIAL RELAY- RET670 SITE TEST REPORT Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00 Customer Name: National Grid-SA Page 12 of 15 Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.: DATE: TESTING ENGINEER-JAL CSD- ENGINEER Signature: ________________ Signature: ________________ Name : ________________ Name : ________________ LV Winding Phase Id min. Set Value Calculated value Measured Value Drop Out PickUp Ratio Operating Time @ 2X I pickup (ms) Pick up Drop out R Y B Limits: Pick up & Drop Out ±2% of Ir for I < Ir or ±2% of I for I > Ir, Reset Ratio > 95%, Timing tolerance Typically 25 ms, According to the Catalogue for Technical Data Page: 143 Pick-up & Drop-off Test for Unrestrained Differential Current (Id): HV winding Phase Iunrest. Set Value Calculated value Measured Value Drop Out PickUp Ratio Operating Time @ 2X I pickup (ms) Pick up Drop out R Y B LV Winding Phase Iunrest. Set Value Calculated value Measured Value Drop Out PickUp Ratio Operating Time @ 2X I pickup (ms) Pick up Drop out R Y B Limits: Pick up & Drop Out ±2% of Ir for I < Ir or ±2% of I for I > Ir, Reset Ratio > 95%, Timing tolerance Typically 25 ms, According to the Catalogue for Technical Data Page: 143 3.7.2. BIAS CHARACTERISTIC TESTING Section 1 When bias current is between: 0 ≤ Ibias ≤ Endsection1 Slope section1 I bias A IH.V A Expected IL.V (A) Id calculated Measured IL.V (A) Errors % R Y B R Y B Idmin
  • 13. TRANSFORMER DIFFERENTIAL RELAY- RET670 SITE TEST REPORT Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00 Customer Name: National Grid-SA Page 13 of 15 Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.: DATE: TESTING ENGINEER-JAL CSD- ENGINEER Signature: ________________ Signature: ________________ Name : ________________ Name : ________________ Limits; ± 2 %Ir According to the Technical Reference Catalogue – Page24 SLOPE Section 2 When bias current is between: Endsection1 ≤ Ibias ≤ Endsection2 Trip = (Idmin + slope section2/100 *(Ibias - End section1) A I bias A IH.V A Expected IL.V (A) Id calculated Measured IL.V (A) Errors % R Y B R Y B Limits; ± 2 %Ir According to the Technical Reference Catalogue – Page24 SLOPE Section3 When bias current is more than: Ibias ≥ End section2 Trip = (Idmin + slope section2/100*(End section2 - End section1)) + (Slope section3/100 * (Ibias- End section2) A I bias A IH.V A Expected IL.V (A) Id calculated Measured IL.V (A) Errors % R Y B R Y B Limits; ± 2 %Ir According to the Technical Reference Catalogue – Page24 3.7.3. Test of 2nd Harmonics Phase I2 / I1 ratio % I1 ( F =60 Hz ) (Pickup Value) I2 ( F = 120 Hz ) Expected Blocking Measured R Y B
  • 14. TRANSFORMER DIFFERENTIAL RELAY- RET670 SITE TEST REPORT Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00 Customer Name: National Grid-SA Page 14 of 15 Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.: DATE: TESTING ENGINEER-JAL CSD- ENGINEER Signature: ________________ Signature: ________________ Name : ________________ Name : ________________ 3.7.4. Test of 5th Harmonics Phase I5 / I1 ratio % I1 ( F =60 Hz ) I5 ( F = 300 Hz ) Expected Blocking Measured R Y B 3.7.5. Negative Sequence test: IminNegSeq test: IMinNegSeq setting Expected IH.V (A) Expected IL.V (A) Measured IL.V (A) Measured IH.V (A) Negative sequence Relay Operating Angle (NegSeqROA ) test : Inject H.V & L.V > IMinNegSeq Inject H.V with angle zero degree and change the L.V to get the operating zone. NegSeqROA setting Expected IL..V angle for operating zone (Deg) Measured IL..V angle for operating zone (Deg) 3.7.6. Sensitive negative sequence (turn-to-turn falut) test: Status ____________________ 3.7.7. Unrestrained negative sequence test: Internal fault action (Expected: Trip): _____________ External fault (with harmonics) action (Expected: Block) : External fault (without harmonics) action (Expected: Trip): ____Trip indication test: ____ No. Type of fault Led Color Check
  • 15. TRANSFORMER DIFFERENTIAL RELAY- RET670 SITE TEST REPORT Name of Substation: AL-GHASSANIYAH 115/13.8kV S/S Contract No. : 31131093/00 Customer Name: National Grid-SA Page 15 of 15 Panel/Bay No.: Equip. No.: Dwg. Ref.: Record No.: DATE: TESTING ENGINEER-JAL CSD- ENGINEER Signature: ________________ Signature: ________________ Name : ________________ Name : ________________ 3.7.8.Disturbance recorder checked [ ]. 3.7.9.Binary outputs and inputs checked [ ]. 3.7.10. Attach the Final setting print out of relay: 3.8. Test Equipment Used Sl. No Description Make Equipment Sl. No Calibration Date Calibration Due Date 1 2 3