Overview of Grounding for Industrial
and Commercial Power Systems
Presented By
Robert Schuerger, P.E.
HP Critical Facility Services delivered by EYP MCF
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
What is VOLTAGE?
• Difference of Electric Potential
• Electromotive Force (EMF)
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Electromotive Force (EMF)
Opposite charges attract
Like charges repel
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Electric Fields
• Exist whenever there is an electrically charged particle
• Exist whenever there is a voltage
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
CAPACITANCE is the ratio of the
total charge on two surfaces to the
potential difference between them.
C = Q / V
C = capacitance, in Farads
Q = charge, in Coulombs
V = voltage, in Volts
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
What is CURRENT?
• The flow of electrons.
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Magnetic Fields
• Exist naturally in the earth’s core
(North and South Poles)
• Exist naturally due to permanent magnets
• Exist around the wire when a current flows (Electromagnetism)
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Transformers
• Energy is transferred from the
primary winding to the
secondary winding by the
magnetic flux Øm.
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
What does any of this have to do
with grounding?
• There are two distinctly different functions the
“ground” can perform:
– The first is the safety/protection function of
connecting a specific part of the electrical
generation, transmission or distribution system,
or the utilization equipment to the earth.
– The second function is to provide a “common”
or “reference” or “point of zero volts,” which is
usually thought of as a system operation
requirement.
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Understanding Grounding
• Voltage is a difference of potential, requiring a minimum
of two points
– Ground is often one of the two (or more) points
– Ground is used as a “reference” or “point of zero potential”
– People stand on it, which makes it part of electrical safety
• The secondary of a transformer is electrically isolated
from the primary, since it moves the energy magnetically
– Regardless of how the primary is connected relative to ground, the
secondary is isolated from ground until connected externally
– “You cannot transform ground.” Professor Grumbach
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Solidly Grounded Primary
• With AC voltage, one terminal is often intentionally
grounded; ground is used as “zero volts”
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Solidly Grounded Primary
• If V1 = 480 V and V2 = 120 V, what will a voltmeter (V)
most likely read and why?
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Solidly Grounded Primary –
Capacitively Grounded Secondary
• The voltmeter (V) will read approximately 60 V, assuming
the capacitive coupling between each set of wires and
ground is about the same
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
What are the keys to understanding
Grounding?
• Understanding basic electricity
– What is voltage
– What is capacitance
– What is inductance
– How does a transformer work
(magnetic coupling of windings)
• Understanding when “ground” is
in the circuit, directly or indirectly
• The earth is not an “electrical
sewer” that magically eliminates
interference! Picture from Wikipedia
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
When is ground in the circuit?
Lightning
Picture from www.insidesocal.com
Electrical Faults
Picture from Wikipedia
When supply
transformer or
generator are
solidly grounded
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Minimizing Shock Hazard –
a primary reason for grounding
OSHA ODE-1070 sign
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
The requirements for equipment
grounding are expressly specified in
NFPA 70:
1. Conductive materials enclosing electrical conductors or
equipment, or forming part of such equipment, shall be
connected to earth so as to limit the voltage to ground on
these materials. Where the electrical system is required to
be grounded, these materials shall be connected together
and to the supply system grounded conductor.
2. Where the electrical system is not solidly grounded, these
materials shall be connected together in a manner that
establishes an effective path for fault current.
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
The requirements for equipment
grounding are expressly specified in
NFPA 70:
3. Electrically conductive materials that are likely to become
energized shall be bonded to the supply system grounded
conductor or, in the case of an ungrounded electrical
system, to the electrical system grounded equipment, in a
manner that establishes an effective path for fault current.
4. The earth shall not be used as the sole equipment
grounding conductor or fault current path.
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Basic objectives of an equipment
grounding system:
1. To reduce electric shock hazard to personnel.
2. To provide adequate current carrying capability, both in
magnitude and duration, to accept the ground-fault current
permitted by the overcurrent protection system without
creating a fire or explosive hazard to building or contents.
3. To provide a low impedance return path for ground-fault
current necessary for the timely operation of the
overcurrent protection system.
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Three phase Motor - Shock hazard
• If the insulation fails in a three phase motor, the case becomes
energized at phase to ground voltage
• With no ground on the case, it would remain energized
indefinitely exposing anyone who passed by to a shock hazard
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Three phase Motor –
Effectively Grounded
• By having an equipment grounding conductor connected
to the case, the shock hazard is quickly eliminated – the
circuit breaker trips, often by the instantaneous unit
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
NEC “Grounding” Terminology
• “Grounding” has to do with connecting to the earth (outside
the US this is often referred to as “earthing”)
• “Bonding” is providing a low impedance path to clear faults
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
NEC “Grounding” Terminology
• Grounded - Connected to
earth or to an extended
conducting body that
serves instead of the earth,
whether the connection is
intentional or accidental.
• Examples of grounding
electrodes
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
NEC “Grounding” Terminology
• Grounded conductor
(neutral).
• Equipment
grounding conductor
(green or bare wire)
• Grounding electrode
conductor (ground
wire to ground rod,
usually bare)
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
NEC “Grounding” Terminology
• Most of the “grounding”
in a facility is actually
bonding per the NEC
• The equipment
grounding conductor
(green or bare wire) is
part of the bonding
system
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Grounding of separately
derived system
• separately derived system - A
wiring system whose power is
derived from a generator,
transformer, or converter
windings and has no direct
electrical connection, including a
solidly connected grounded
circuit conductor, to supply
conductors originating in another
system.
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Solidly grounded
transformer secondary
• For AC systems over 50 V, the NEC requires a “separately
derived system” to be grounded [250.20(D)] in accordance
with 250.30(A)
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
What about the electronic equipment
– is “ground” in the circuit?
• Most electronic equipment uses
the frame as “reference”
• The frame is usually grounded,
either intentionally to the raised
floor or by means of the
equipment grounding conductor
• Even though the equipment
grounding conductor will
ultimately connect to ground, the
operation of the equipment does
not depend on a low impedance
to ground (earth)
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Overcurrent Protection Operation
• The equipment-ground system is an essential part of the
overcurrent protection system. The overcurrent protection
system requires a low-impedance ground return path in
order to operate promptly and properly.
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Total impedance (R + jX) of
conductive path
• In 60 Hz circuits rated 40 A or less, the circuit reactance
(jX) is an insignificant part of the circuit impedance.
• Because reactance increases significantly with conductor
separation, reactance is the predominant element of
impedance for open wire and tray systems for circuits rated
above 200 A.
• The reactance of an ac circuit is determined mainly by the
spacing between outgoing and return conductors and is
only slightly affected by conductor size.
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Variation of R and X with Conductor
Size and Spacing
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Fig 2-2 -- Single Wire as
Grounding Conductor
• Imagine the circuit to be
of 350 ampere capacity,
employing 500 KCMil
phase conductors and a
# 4/0 grounding
conductor (copper).
• It is assumed that the
line-to-ground fault
current at the outer
terminal is 5500 A.
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Table 2-1
Impedance as a Function of
Conductor Spacing
0.0260.02330.011530762
0.02070.01720.01158203
0.01580.01080.0115251
Grounding
Conductor
G
0.02160.0210.004930762
0.01570.01490.00498203
0.00980.00850.0049251
Phase
Conductor
A
ΩΩΩ(in)(mm)
ZXRSpacing
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Shock Voltage as a Function of
Conductor Spacing
14376230
113.92038
86.9512
(V)(mm)(in)
EGSpacing
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Fig 2-3 -- Magnetic Field of Wire as
Grounding Conductor
• Throughout the space between the two conductors [8 in
wide and 200 ft long] exists a powerful 60 Hz magnetic
field with a driving magnetomotive force of 5500 A turns.
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Fig 2.4 -- Electromagnetic Induction
of Wire as Grounding Conductor
• Any loop of conducting
material (wire, pipe,
messenger cable, steel
structure, etc.) through which
some portion of this magnetic
field passes will have induced
in it a corresponding 60 Hz
voltage.
• If the loop in which the
voltage is mutually coupled is
closed, then instead of a
voltage, a circulating current
will exist.
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
What is the correct circuit?
• For electrical distribution, we tend to think in terms of the
circuit as shown below
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
What is the correct circuit?
In terms of the Electric Field, the circuit looks more like this
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
What is the correct circuit?
• In terms of impedance, particularly for high frequency issues
like interference, the actual circuit looks more like this
• When do we need to consider the distributed aspect of the
capacitance and inductance?
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Electrically “small” circuits
• ES drives current Ia in closed loop to the load ZL, along path
length Lm, all current and voltage around the loop will be
considered as occurring instantaneously and continuously
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Electrically “large” circuits
• When length Lm is large relative to the frequency of ES circuit
analysis with lumped parameter no longer applies and
transmission line theory addressing wave propagation is necessary
Lm ≥
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Large Circuits - Examples of
wavelength (Îť) vs frequency (f)
• For copper, the velocity of propagation (v) is
983,576,337 feet per second
1. f = 60 Hz, Îť = 3,104.7 miles, (1/20)Îť = 155.2 miles
2. f = 1 kHz, Îť = 186.3 miles, (1/20)Îť = 9.3 miles
3. f = 1 MHz, Îť = 983.6 feet, (1/20)Îť = 49.2 feet
4. f = 60 MHz, Îť = 16.4 feet, (1/20)Îť = 9.84 inches
• Power transmission lines were the first “large
circuits” to be addressed, hence the name
“transmission line theory”
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
What grounding issues require
“transmission line theory”?
• Lightning has both high and low frequency aspects to
address:
– The leading edge has high frequency aspects
– The major energy of the discharge has low frequency aspects
• Communications/Interference:
– IT equipment operate in the MegaHertz range, where the
wavelength of the signal can measure in feet
– Interference can occur across a relatively large frequency band
• Most data transfer is now done with
“differential voltage” in which neither the
“1” nor “0” is actually zero volts
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Fig 3-8 Cumulative Frequency Distribution
of Maximum Rates of Rise of Lightning
Currents 1. Negative First Strokes
2. Negative Subsequent Strokes
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Fig 3-11--Contour Map of Mean
Annual Lightning Strike Density
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Fig 3-12 Lightning Protection for
Structures
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Lightning Protection
• NFPA 780 provides
specific direction on
how to protect a
building from
lightning
• When the building
has structural steel,
the steel is an
important part of the
“lightning protection
system”
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Grounding Connections Associated
with Steep Wave Front Voltage
Protection Equipment
• The function of the
grounding conductor is to
provide a conducting path
over which the surge
current can be diverted
around the apparatus
being protected, without
developing a dangerous
voltage magnitude.
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Steep Wave Front Voltage
• Actual values of di/dt range over wide limits, but a value
of 10 kA/Âľs is representative. With such a rate of rise of
current, even 1 ÂľH of inductance can be significant.
E = L¡di/dt
= 10-6¡10,000¡106
= 10,000 V
• It would take only a 3 ft length of No. 4/0 AWG conductor
spaced 5 ft away from the transformer in Fig 2-7 to add
10,000 V to the arrester voltage.
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Fig 2-7--Surge Arrester Location on
Transformer
• To take full advantage of
the protective properties
of the surge arrester in Fig
2-7, the arrester should be
mounted so as to be in
direct shunt relationship to
the terminal bushings.
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Fig 2-12: Outdoor Unit Substation
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Grounding techniques to minimize
interference problems
• There are two major strategies that have been used with
grounding to minimize interference issues:
– Single point grounding
– Signal reference grid
• Single point grounding
uses a radial approach in
which all the pieces
connect to a single place
with no “ground loops”
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Single point grounding - theory
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Single point grounding - practice
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Multi-point grounding using a
signal reference grid
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Signal Reference Grid
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Bolted stringer
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Bonding to the pedestal
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Signal Reference Grid
• Signal reference grid
takes advantage of many
resistances in parallel, so
that the overall resistance
is low over a broad
frequency range
• The impedance of an
individual path is much
less significant, since there
are many in parallel
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Telecommunications world
(Bell Standards) have
different grounding
terminology
Isolated Bonding Network:
is the equivalent
grounding scheme as
single point grounding
for an AC distribution
system
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Telecommunications grounding
terminology
Common Bonding Network:
is the equivalent
grounding scheme as
multi-point grounding for
an AC distribution system
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Telecommunications grounding
terminology
TBB –
telecommunications
bonding backbone
TGB -
telecommunications
grounding busbar
TMGB -
telecommunications
main grounding
busbar
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Telecommunications
grounding -Isolated bonding
network
CDCPS – centralized DC power
system
DCG – DC ground
DCEG – DC equipment ground
dc-I – DC return conductor that
is insulated from the DCEG
ITE – Information technology
equipment
SPCB – Single point connection
bar
TBB – telecommunications
bonding backbone
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Telecommunications
grounding -Common bonding
network
CDCPS – centralized DC power
system
DCG – DC ground
DCEG – DC equipment ground
dc-I – DC return conductor that
is insulated from the DCEG
ITE – Information technology
equipment
TBB – telecommunications
bonding backbone
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Grounding to deal with interference
• Interference current does not simply drain into “ground” and disappear
• Interference has a source and follows a closed loop (circuit) back to the
source
• Part of the “circuit” is often a or several capacitors
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Normal mode and Common
mode interference
• Part of dealing with the interference is determining the circuit for the
interference and whether or not it is referenced to ground
NormV VCom
VCom
Normal Mode Common Mode
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
• Unbalanced circuits are much more susceptible to interference from
ground based signals than balanced circuits
• For this reason most IT equipment now uses balanced circuits to send
digital signals
Balanced Circuit Unbalanced Circuit
Grounding to deal with interference
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Shield Capacitances,
ground voltages
Figure 10.3 Model for analyzing shield effectiveness.
C1
C2
C3
C4
A
B
D
C
G3V VG2
G1V
1
2
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Shield equivalent circuit
Figure 10.4 Equivalent circuit for model in Figure 10.3
G2VVG3
VG1
4C
C1
C2
3C
C
1
2
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Ground plane for
industrial machine
Figure 10.6 Panel ground plane extended to the machine structure
Panel ground plane
bonded to structure
ground plane by
Clean and Dirty
wireways
Machine structure used as
ground plane
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
References
IEEE Standard 142-2007, Recommended Practice
for Grounding of Industrial and Commercial Power
Systems
IEEE Standard 1100-2005, IEEE Recommended
Practice for Powering and Grounding Electronic
Equipment
NFPA 70-2008, National Electrical Code
NFPA 780-1995, Lightning Protection Code
March 26, 2010 San Francisco IEEE/IAS Chapter Seminar
Questions?
• Robert Schuerger, PE
• Principal Reliability Analysis
Corporate Lead
• HP Critical Facilities Services
delivered by EYP MCF
• 310-297-4693
• bschuerger@hp.com

More Related Content

What's hot

Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePower System Operation
 
Infinite bus bar in power system
Infinite bus bar in power systemInfinite bus bar in power system
Infinite bus bar in power systemEklavya Sharma
 
ETAP - Transformer sizing using etap
ETAP - Transformer sizing using etapETAP - Transformer sizing using etap
ETAP - Transformer sizing using etapHimmelstern
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgearmichaeljmack
 
Breakdown theory
Breakdown theoryBreakdown theory
Breakdown theorydahir osman
 
Substation Maintenance
Substation MaintenanceSubstation Maintenance
Substation Maintenancekarikalan123
 
Types Of Substations
Types Of SubstationsTypes Of Substations
Types Of Substationssapna186
 
Generator grounding
Generator groundingGenerator grounding
Generator groundingmichaeljmack
 
Power surge protection devices
Power surge protection devices Power surge protection devices
Power surge protection devices Pratik Rasam
 
Presentation on substations
Presentation on substationsPresentation on substations
Presentation on substationsvishalgohel12195
 
Substations
SubstationsSubstations
Substationsitfakash
 
Lightning arrester
Lightning arresterLightning arrester
Lightning arrestergajendra singh
 
Fault Level Calculation
Fault Level CalculationFault Level Calculation
Fault Level CalculationDinesh Sarda
 
MCB And Earth Leakage Circuit
MCB And Earth Leakage CircuitMCB And Earth Leakage Circuit
MCB And Earth Leakage CircuitNavin Patle
 
Distribution boards and Protection devices ppt
Distribution boards and Protection devices  pptDistribution boards and Protection devices  ppt
Distribution boards and Protection devices pptZuhairQadri
 
Circuit breakers
Circuit breakersCircuit breakers
Circuit breakersali raza
 
TOWNSEND'S CRITERION & LIMITATIONS|BREAKDOWN IN GAS|HIGH VOLTAGE ENGINEERING
TOWNSEND'S CRITERION & LIMITATIONS|BREAKDOWN IN GAS|HIGH VOLTAGE ENGINEERINGTOWNSEND'S CRITERION & LIMITATIONS|BREAKDOWN IN GAS|HIGH VOLTAGE ENGINEERING
TOWNSEND'S CRITERION & LIMITATIONS|BREAKDOWN IN GAS|HIGH VOLTAGE ENGINEERINGPrasant Kumar
 
Voltage Drop Calculation.pdf
Voltage Drop Calculation.pdfVoltage Drop Calculation.pdf
Voltage Drop Calculation.pdfMesiasJohnFederico
 
PPT ON 220KV GSS
PPT ON 220KV GSSPPT ON 220KV GSS
PPT ON 220KV GSSMohitkalal4
 

What's hot (20)

IEEE substation design
IEEE substation designIEEE substation design
IEEE substation design
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground Resistance
 
Infinite bus bar in power system
Infinite bus bar in power systemInfinite bus bar in power system
Infinite bus bar in power system
 
ETAP - Transformer sizing using etap
ETAP - Transformer sizing using etapETAP - Transformer sizing using etap
ETAP - Transformer sizing using etap
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgear
 
Breakdown theory
Breakdown theoryBreakdown theory
Breakdown theory
 
Substation Maintenance
Substation MaintenanceSubstation Maintenance
Substation Maintenance
 
Types Of Substations
Types Of SubstationsTypes Of Substations
Types Of Substations
 
Generator grounding
Generator groundingGenerator grounding
Generator grounding
 
Power surge protection devices
Power surge protection devices Power surge protection devices
Power surge protection devices
 
Presentation on substations
Presentation on substationsPresentation on substations
Presentation on substations
 
Substations
SubstationsSubstations
Substations
 
Lightning arrester
Lightning arresterLightning arrester
Lightning arrester
 
Fault Level Calculation
Fault Level CalculationFault Level Calculation
Fault Level Calculation
 
MCB And Earth Leakage Circuit
MCB And Earth Leakage CircuitMCB And Earth Leakage Circuit
MCB And Earth Leakage Circuit
 
Distribution boards and Protection devices ppt
Distribution boards and Protection devices  pptDistribution boards and Protection devices  ppt
Distribution boards and Protection devices ppt
 
Circuit breakers
Circuit breakersCircuit breakers
Circuit breakers
 
TOWNSEND'S CRITERION & LIMITATIONS|BREAKDOWN IN GAS|HIGH VOLTAGE ENGINEERING
TOWNSEND'S CRITERION & LIMITATIONS|BREAKDOWN IN GAS|HIGH VOLTAGE ENGINEERINGTOWNSEND'S CRITERION & LIMITATIONS|BREAKDOWN IN GAS|HIGH VOLTAGE ENGINEERING
TOWNSEND'S CRITERION & LIMITATIONS|BREAKDOWN IN GAS|HIGH VOLTAGE ENGINEERING
 
Voltage Drop Calculation.pdf
Voltage Drop Calculation.pdfVoltage Drop Calculation.pdf
Voltage Drop Calculation.pdf
 
PPT ON 220KV GSS
PPT ON 220KV GSSPPT ON 220KV GSS
PPT ON 220KV GSS
 

Similar to Overview of Grounding for Industrial and Commercial Power Systems

Importance of Earth Mat in Substation.docx
Importance of Earth Mat in Substation.docxImportance of Earth Mat in Substation.docx
Importance of Earth Mat in Substation.docxvikram desai
 
Short-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.pptShort-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.pptJatmylHarnero1
 
Protection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdfProtection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdfwhmonkey
 
Aterramento ground 1 - dimensionamento
Aterramento ground 1 - dimensionamento Aterramento ground 1 - dimensionamento
Aterramento ground 1 - dimensionamento Ragamurf
 
Electrical Grounding Practices- Part 1 of 3
Electrical Grounding Practices- Part 1 of 3Electrical Grounding Practices- Part 1 of 3
Electrical Grounding Practices- Part 1 of 3M.S. Jacobs & Associates
 
The Complete Acromag Guide to Industrial Electrical Grounding
The Complete Acromag Guide to Industrial Electrical GroundingThe Complete Acromag Guide to Industrial Electrical Grounding
The Complete Acromag Guide to Industrial Electrical GroundingInstrument Specialties, Inc.
 
Earthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspectsEarthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspectsBruno De Wachter
 
120A- WOBC H05 Electrical safety day 3
120A- WOBC H05 Electrical safety day 3120A- WOBC H05 Electrical safety day 3
120A- WOBC H05 Electrical safety day 3phase3-120A
 
Design of Grounding System for Substation
Design of Grounding System for SubstationDesign of Grounding System for Substation
Design of Grounding System for Substationijtsrd
 
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINECOMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINEIRJET Journal
 
Earthing & Grounding (Easily Explained)
Earthing & Grounding (Easily Explained)Earthing & Grounding (Easily Explained)
Earthing & Grounding (Easily Explained)Muhammad Zaeem Sarfraz
 
Presentation2.pptx
Presentation2.pptxPresentation2.pptx
Presentation2.pptxabdullah75131
 
Report earthing grounding pv with shielded, armoured dc cabling (worldwide)
Report earthing grounding pv with shielded, armoured dc cabling (worldwide)Report earthing grounding pv with shielded, armoured dc cabling (worldwide)
Report earthing grounding pv with shielded, armoured dc cabling (worldwide)Andreas ILIOU - Elektro- Solar
 
Design and Implementation of a Single Phase Earth Fault Relay
Design and Implementation of a Single  Phase Earth Fault RelayDesign and Implementation of a Single  Phase Earth Fault Relay
Design and Implementation of a Single Phase Earth Fault RelayIJSRED
 
DC Electrical Safety Standards presentation
DC Electrical Safety Standards presentationDC Electrical Safety Standards presentation
DC Electrical Safety Standards presentationakhilesh682519
 
EC73_-RF_AND_MICROWAVE_ENGINEERING.pdf
EC73_-RF_AND_MICROWAVE_ENGINEERING.pdfEC73_-RF_AND_MICROWAVE_ENGINEERING.pdf
EC73_-RF_AND_MICROWAVE_ENGINEERING.pdfEmmanuelMukubwa2
 
witricity WPT
witricity WPTwitricity WPT
witricity WPTSuriya Naidu
 
Experiment no. 2
Experiment no. 2Experiment no. 2
Experiment no. 2Suhas Chate
 
Wireless power transmission
Wireless power transmissionWireless power transmission
Wireless power transmissionrakeshkk
 

Similar to Overview of Grounding for Industrial and Commercial Power Systems (20)

Earthing
EarthingEarthing
Earthing
 
Importance of Earth Mat in Substation.docx
Importance of Earth Mat in Substation.docxImportance of Earth Mat in Substation.docx
Importance of Earth Mat in Substation.docx
 
Short-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.pptShort-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.ppt
 
Protection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdfProtection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdf
 
Aterramento ground 1 - dimensionamento
Aterramento ground 1 - dimensionamento Aterramento ground 1 - dimensionamento
Aterramento ground 1 - dimensionamento
 
Electrical Grounding Practices- Part 1 of 3
Electrical Grounding Practices- Part 1 of 3Electrical Grounding Practices- Part 1 of 3
Electrical Grounding Practices- Part 1 of 3
 
The Complete Acromag Guide to Industrial Electrical Grounding
The Complete Acromag Guide to Industrial Electrical GroundingThe Complete Acromag Guide to Industrial Electrical Grounding
The Complete Acromag Guide to Industrial Electrical Grounding
 
Earthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspectsEarthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspects
 
120A- WOBC H05 Electrical safety day 3
120A- WOBC H05 Electrical safety day 3120A- WOBC H05 Electrical safety day 3
120A- WOBC H05 Electrical safety day 3
 
Design of Grounding System for Substation
Design of Grounding System for SubstationDesign of Grounding System for Substation
Design of Grounding System for Substation
 
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINECOMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
 
Earthing & Grounding (Easily Explained)
Earthing & Grounding (Easily Explained)Earthing & Grounding (Easily Explained)
Earthing & Grounding (Easily Explained)
 
Presentation2.pptx
Presentation2.pptxPresentation2.pptx
Presentation2.pptx
 
Report earthing grounding pv with shielded, armoured dc cabling (worldwide)
Report earthing grounding pv with shielded, armoured dc cabling (worldwide)Report earthing grounding pv with shielded, armoured dc cabling (worldwide)
Report earthing grounding pv with shielded, armoured dc cabling (worldwide)
 
Design and Implementation of a Single Phase Earth Fault Relay
Design and Implementation of a Single  Phase Earth Fault RelayDesign and Implementation of a Single  Phase Earth Fault Relay
Design and Implementation of a Single Phase Earth Fault Relay
 
DC Electrical Safety Standards presentation
DC Electrical Safety Standards presentationDC Electrical Safety Standards presentation
DC Electrical Safety Standards presentation
 
EC73_-RF_AND_MICROWAVE_ENGINEERING.pdf
EC73_-RF_AND_MICROWAVE_ENGINEERING.pdfEC73_-RF_AND_MICROWAVE_ENGINEERING.pdf
EC73_-RF_AND_MICROWAVE_ENGINEERING.pdf
 
witricity WPT
witricity WPTwitricity WPT
witricity WPT
 
Experiment no. 2
Experiment no. 2Experiment no. 2
Experiment no. 2
 
Wireless power transmission
Wireless power transmissionWireless power transmission
Wireless power transmission
 

More from michaeljmack

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993michaeljmack
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbookmichaeljmack
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbookmichaeljmack
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protectionmichaeljmack
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systemsmichaeljmack
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flashmichaeljmack
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrushmichaeljmack
 
Building information modeling
Building information modelingBuilding information modeling
Building information modelingmichaeljmack
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protectionmichaeljmack
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systemsmichaeljmack
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spacesmichaeljmack
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708michaeljmack
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distributionmichaeljmack
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performancemichaeljmack
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulatormichaeljmack
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plantsmichaeljmack
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Storiesmichaeljmack
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Sheddingmichaeljmack
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentalsmichaeljmack
 

More from michaeljmack (20)

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbook
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbook
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protection
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systems
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
Building information modeling
Building information modelingBuilding information modeling
Building information modeling
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systems
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spaces
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distribution
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performance
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulator
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plants
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Stories
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Shedding
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentals
 
Arc Flash
Arc FlashArc Flash
Arc Flash
 

Recently uploaded

Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...asadnawaz62
 
Effects of rheological properties on mixing
Effects of rheological properties on mixingEffects of rheological properties on mixing
Effects of rheological properties on mixingviprabot1
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)Dr SOUNDIRARAJ N
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoĂŁo Esperancinha
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
EduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AIEduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AIkoyaldeepu123
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfROCENODodongVILLACER
 
pipeline in computer architecture design
pipeline in computer architecture  designpipeline in computer architecture  design
pipeline in computer architecture designssuser87fa0c1
 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfme23b1001
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEroselinkalist12
 
DATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage exampleDATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage examplePragyanshuParadkar1
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 

Recently uploaded (20)

Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...
 
Effects of rheological properties on mixing
Effects of rheological properties on mixingEffects of rheological properties on mixing
Effects of rheological properties on mixing
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
young call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Serviceyoung call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Service
 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
EduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AIEduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AI
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdf
 
pipeline in computer architecture design
pipeline in computer architecture  designpipeline in computer architecture  design
pipeline in computer architecture design
 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdf
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
 
DATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage exampleDATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage example
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 

Overview of Grounding for Industrial and Commercial Power Systems

  • 1. Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. HP Critical Facility Services delivered by EYP MCF
  • 2. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar What is VOLTAGE? • Difference of Electric Potential • Electromotive Force (EMF)
  • 3. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Electromotive Force (EMF) Opposite charges attract Like charges repel
  • 4. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Electric Fields • Exist whenever there is an electrically charged particle • Exist whenever there is a voltage
  • 5. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar CAPACITANCE is the ratio of the total charge on two surfaces to the potential difference between them. C = Q / V C = capacitance, in Farads Q = charge, in Coulombs V = voltage, in Volts
  • 6. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar What is CURRENT? • The flow of electrons.
  • 7. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Magnetic Fields • Exist naturally in the earth’s core (North and South Poles) • Exist naturally due to permanent magnets • Exist around the wire when a current flows (Electromagnetism)
  • 8. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Transformers • Energy is transferred from the primary winding to the secondary winding by the magnetic flux Øm.
  • 9. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar What does any of this have to do with grounding? • There are two distinctly different functions the “ground” can perform: – The first is the safety/protection function of connecting a specific part of the electrical generation, transmission or distribution system, or the utilization equipment to the earth. – The second function is to provide a “common” or “reference” or “point of zero volts,” which is usually thought of as a system operation requirement.
  • 10. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Understanding Grounding • Voltage is a difference of potential, requiring a minimum of two points – Ground is often one of the two (or more) points – Ground is used as a “reference” or “point of zero potential” – People stand on it, which makes it part of electrical safety • The secondary of a transformer is electrically isolated from the primary, since it moves the energy magnetically – Regardless of how the primary is connected relative to ground, the secondary is isolated from ground until connected externally – “You cannot transform ground.” Professor Grumbach
  • 11. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Solidly Grounded Primary • With AC voltage, one terminal is often intentionally grounded; ground is used as “zero volts”
  • 12. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Solidly Grounded Primary • If V1 = 480 V and V2 = 120 V, what will a voltmeter (V) most likely read and why?
  • 13. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Solidly Grounded Primary – Capacitively Grounded Secondary • The voltmeter (V) will read approximately 60 V, assuming the capacitive coupling between each set of wires and ground is about the same
  • 14. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar What are the keys to understanding Grounding? • Understanding basic electricity – What is voltage – What is capacitance – What is inductance – How does a transformer work (magnetic coupling of windings) • Understanding when “ground” is in the circuit, directly or indirectly • The earth is not an “electrical sewer” that magically eliminates interference! Picture from Wikipedia
  • 15. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar When is ground in the circuit? Lightning Picture from www.insidesocal.com Electrical Faults Picture from Wikipedia When supply transformer or generator are solidly grounded
  • 16. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Minimizing Shock Hazard – a primary reason for grounding OSHA ODE-1070 sign
  • 17. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar The requirements for equipment grounding are expressly specified in NFPA 70: 1. Conductive materials enclosing electrical conductors or equipment, or forming part of such equipment, shall be connected to earth so as to limit the voltage to ground on these materials. Where the electrical system is required to be grounded, these materials shall be connected together and to the supply system grounded conductor. 2. Where the electrical system is not solidly grounded, these materials shall be connected together in a manner that establishes an effective path for fault current.
  • 18. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar The requirements for equipment grounding are expressly specified in NFPA 70: 3. Electrically conductive materials that are likely to become energized shall be bonded to the supply system grounded conductor or, in the case of an ungrounded electrical system, to the electrical system grounded equipment, in a manner that establishes an effective path for fault current. 4. The earth shall not be used as the sole equipment grounding conductor or fault current path.
  • 19. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Basic objectives of an equipment grounding system: 1. To reduce electric shock hazard to personnel. 2. To provide adequate current carrying capability, both in magnitude and duration, to accept the ground-fault current permitted by the overcurrent protection system without creating a fire or explosive hazard to building or contents. 3. To provide a low impedance return path for ground-fault current necessary for the timely operation of the overcurrent protection system.
  • 20. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Three phase Motor - Shock hazard • If the insulation fails in a three phase motor, the case becomes energized at phase to ground voltage • With no ground on the case, it would remain energized indefinitely exposing anyone who passed by to a shock hazard
  • 21. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Three phase Motor – Effectively Grounded • By having an equipment grounding conductor connected to the case, the shock hazard is quickly eliminated – the circuit breaker trips, often by the instantaneous unit
  • 22. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar NEC “Grounding” Terminology • “Grounding” has to do with connecting to the earth (outside the US this is often referred to as “earthing”) • “Bonding” is providing a low impedance path to clear faults
  • 23. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar NEC “Grounding” Terminology • Grounded - Connected to earth or to an extended conducting body that serves instead of the earth, whether the connection is intentional or accidental. • Examples of grounding electrodes
  • 24. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar NEC “Grounding” Terminology • Grounded conductor (neutral). • Equipment grounding conductor (green or bare wire) • Grounding electrode conductor (ground wire to ground rod, usually bare)
  • 25. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar NEC “Grounding” Terminology • Most of the “grounding” in a facility is actually bonding per the NEC • The equipment grounding conductor (green or bare wire) is part of the bonding system
  • 26. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Grounding of separately derived system • separately derived system - A wiring system whose power is derived from a generator, transformer, or converter windings and has no direct electrical connection, including a solidly connected grounded circuit conductor, to supply conductors originating in another system.
  • 27. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Solidly grounded transformer secondary • For AC systems over 50 V, the NEC requires a “separately derived system” to be grounded [250.20(D)] in accordance with 250.30(A)
  • 28. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar What about the electronic equipment – is “ground” in the circuit? • Most electronic equipment uses the frame as “reference” • The frame is usually grounded, either intentionally to the raised floor or by means of the equipment grounding conductor • Even though the equipment grounding conductor will ultimately connect to ground, the operation of the equipment does not depend on a low impedance to ground (earth)
  • 29. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Overcurrent Protection Operation • The equipment-ground system is an essential part of the overcurrent protection system. The overcurrent protection system requires a low-impedance ground return path in order to operate promptly and properly.
  • 30. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Total impedance (R + jX) of conductive path • In 60 Hz circuits rated 40 A or less, the circuit reactance (jX) is an insignificant part of the circuit impedance. • Because reactance increases significantly with conductor separation, reactance is the predominant element of impedance for open wire and tray systems for circuits rated above 200 A. • The reactance of an ac circuit is determined mainly by the spacing between outgoing and return conductors and is only slightly affected by conductor size.
  • 31. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Variation of R and X with Conductor Size and Spacing
  • 32. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Fig 2-2 -- Single Wire as Grounding Conductor • Imagine the circuit to be of 350 ampere capacity, employing 500 KCMil phase conductors and a # 4/0 grounding conductor (copper). • It is assumed that the line-to-ground fault current at the outer terminal is 5500 A.
  • 33. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Table 2-1 Impedance as a Function of Conductor Spacing 0.0260.02330.011530762 0.02070.01720.01158203 0.01580.01080.0115251 Grounding Conductor G 0.02160.0210.004930762 0.01570.01490.00498203 0.00980.00850.0049251 Phase Conductor A ΩΩΩ(in)(mm) ZXRSpacing
  • 34. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Shock Voltage as a Function of Conductor Spacing 14376230 113.92038 86.9512 (V)(mm)(in) EGSpacing
  • 35. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Fig 2-3 -- Magnetic Field of Wire as Grounding Conductor • Throughout the space between the two conductors [8 in wide and 200 ft long] exists a powerful 60 Hz magnetic field with a driving magnetomotive force of 5500 A turns.
  • 36. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Fig 2.4 -- Electromagnetic Induction of Wire as Grounding Conductor • Any loop of conducting material (wire, pipe, messenger cable, steel structure, etc.) through which some portion of this magnetic field passes will have induced in it a corresponding 60 Hz voltage. • If the loop in which the voltage is mutually coupled is closed, then instead of a voltage, a circulating current will exist.
  • 37. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar What is the correct circuit? • For electrical distribution, we tend to think in terms of the circuit as shown below
  • 38. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar What is the correct circuit? In terms of the Electric Field, the circuit looks more like this
  • 39. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar What is the correct circuit? • In terms of impedance, particularly for high frequency issues like interference, the actual circuit looks more like this • When do we need to consider the distributed aspect of the capacitance and inductance?
  • 40. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Electrically “small” circuits • ES drives current Ia in closed loop to the load ZL, along path length Lm, all current and voltage around the loop will be considered as occurring instantaneously and continuously
  • 41. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Electrically “large” circuits • When length Lm is large relative to the frequency of ES circuit analysis with lumped parameter no longer applies and transmission line theory addressing wave propagation is necessary Lm ≥
  • 42. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Large Circuits - Examples of wavelength (Îť) vs frequency (f) • For copper, the velocity of propagation (v) is 983,576,337 feet per second 1. f = 60 Hz, Îť = 3,104.7 miles, (1/20)Îť = 155.2 miles 2. f = 1 kHz, Îť = 186.3 miles, (1/20)Îť = 9.3 miles 3. f = 1 MHz, Îť = 983.6 feet, (1/20)Îť = 49.2 feet 4. f = 60 MHz, Îť = 16.4 feet, (1/20)Îť = 9.84 inches • Power transmission lines were the first “large circuits” to be addressed, hence the name “transmission line theory”
  • 43. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar What grounding issues require “transmission line theory”? • Lightning has both high and low frequency aspects to address: – The leading edge has high frequency aspects – The major energy of the discharge has low frequency aspects • Communications/Interference: – IT equipment operate in the MegaHertz range, where the wavelength of the signal can measure in feet – Interference can occur across a relatively large frequency band • Most data transfer is now done with “differential voltage” in which neither the “1” nor “0” is actually zero volts
  • 44. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Fig 3-8 Cumulative Frequency Distribution of Maximum Rates of Rise of Lightning Currents 1. Negative First Strokes 2. Negative Subsequent Strokes
  • 45. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Fig 3-11--Contour Map of Mean Annual Lightning Strike Density
  • 46. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Fig 3-12 Lightning Protection for Structures
  • 47. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Lightning Protection • NFPA 780 provides specific direction on how to protect a building from lightning • When the building has structural steel, the steel is an important part of the “lightning protection system”
  • 48. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Grounding Connections Associated with Steep Wave Front Voltage Protection Equipment • The function of the grounding conductor is to provide a conducting path over which the surge current can be diverted around the apparatus being protected, without developing a dangerous voltage magnitude.
  • 49. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Steep Wave Front Voltage • Actual values of di/dt range over wide limits, but a value of 10 kA/Âľs is representative. With such a rate of rise of current, even 1 ÂľH of inductance can be significant. E = L¡di/dt = 10-6¡10,000¡106 = 10,000 V • It would take only a 3 ft length of No. 4/0 AWG conductor spaced 5 ft away from the transformer in Fig 2-7 to add 10,000 V to the arrester voltage.
  • 50. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Fig 2-7--Surge Arrester Location on Transformer • To take full advantage of the protective properties of the surge arrester in Fig 2-7, the arrester should be mounted so as to be in direct shunt relationship to the terminal bushings.
  • 51. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Fig 2-12: Outdoor Unit Substation
  • 52. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Grounding techniques to minimize interference problems • There are two major strategies that have been used with grounding to minimize interference issues: – Single point grounding – Signal reference grid • Single point grounding uses a radial approach in which all the pieces connect to a single place with no “ground loops”
  • 53. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Single point grounding - theory
  • 54. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Single point grounding - practice
  • 55. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Multi-point grounding using a signal reference grid
  • 56. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Signal Reference Grid
  • 57. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Bolted stringer
  • 58. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Bonding to the pedestal
  • 59. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Signal Reference Grid • Signal reference grid takes advantage of many resistances in parallel, so that the overall resistance is low over a broad frequency range • The impedance of an individual path is much less significant, since there are many in parallel
  • 60. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Telecommunications world (Bell Standards) have different grounding terminology Isolated Bonding Network: is the equivalent grounding scheme as single point grounding for an AC distribution system
  • 61. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Telecommunications grounding terminology Common Bonding Network: is the equivalent grounding scheme as multi-point grounding for an AC distribution system
  • 62. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Telecommunications grounding terminology TBB – telecommunications bonding backbone TGB - telecommunications grounding busbar TMGB - telecommunications main grounding busbar
  • 63. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Telecommunications grounding -Isolated bonding network CDCPS – centralized DC power system DCG – DC ground DCEG – DC equipment ground dc-I – DC return conductor that is insulated from the DCEG ITE – Information technology equipment SPCB – Single point connection bar TBB – telecommunications bonding backbone
  • 64. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Telecommunications grounding -Common bonding network CDCPS – centralized DC power system DCG – DC ground DCEG – DC equipment ground dc-I – DC return conductor that is insulated from the DCEG ITE – Information technology equipment TBB – telecommunications bonding backbone
  • 65. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Grounding to deal with interference • Interference current does not simply drain into “ground” and disappear • Interference has a source and follows a closed loop (circuit) back to the source • Part of the “circuit” is often a or several capacitors
  • 66. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Normal mode and Common mode interference • Part of dealing with the interference is determining the circuit for the interference and whether or not it is referenced to ground NormV VCom VCom Normal Mode Common Mode
  • 67. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar • Unbalanced circuits are much more susceptible to interference from ground based signals than balanced circuits • For this reason most IT equipment now uses balanced circuits to send digital signals Balanced Circuit Unbalanced Circuit Grounding to deal with interference
  • 68. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Shield Capacitances, ground voltages Figure 10.3 Model for analyzing shield effectiveness. C1 C2 C3 C4 A B D C G3V VG2 G1V 1 2
  • 69. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Shield equivalent circuit Figure 10.4 Equivalent circuit for model in Figure 10.3 G2VVG3 VG1 4C C1 C2 3C C 1 2
  • 70. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Ground plane for industrial machine Figure 10.6 Panel ground plane extended to the machine structure Panel ground plane bonded to structure ground plane by Clean and Dirty wireways Machine structure used as ground plane
  • 71. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar References IEEE Standard 142-2007, Recommended Practice for Grounding of Industrial and Commercial Power Systems IEEE Standard 1100-2005, IEEE Recommended Practice for Powering and Grounding Electronic Equipment NFPA 70-2008, National Electrical Code NFPA 780-1995, Lightning Protection Code
  • 72. March 26, 2010 San Francisco IEEE/IAS Chapter Seminar Questions? • Robert Schuerger, PE • Principal Reliability Analysis Corporate Lead • HP Critical Facilities Services delivered by EYP MCF • 310-297-4693 • bschuerger@hp.com