SlideShare a Scribd company logo
1 of 29
Download to read offline
© 2017 Cummins All Rights Reserved
Grounding Recommendations for
On Site Power Systems
Revised: February 23, 2017
Course Objectives
Participants will be able to:
 Explain grounding best practices and code requirements for system and equipment grounding
methods.
 Define requirements for proper ground fault sensing to help design and install ground fault
systems that work correctly.
 Define when a 3 pole vs 4 pole transfer switch should be used so that neutral and ground
current loops are eliminated and ground fault detection systems work correctly.
 Identify key factors of paralleled systems that need to be considered so that ground fault
detection systems will work properly.
Equipment Grounding vs System Grounding
 Equipment grounding
– Establish (connect) a conductive path between
normally non-current carrying metal parts of
equipment AND between these parts and the
grounding electrode
 System grounding
– Deliberate connection between a circuit conductor
of a power source and ground (earth)
 Both are part of the path for ground fault
current to return to the source
Neutral
Metal Enclosures
Grounding
Electrode
System
Ground
Equipment
Ground
Equipment Grounding
 Equipment Grounding Conductor (EGC)
– Connects normally non–current-carrying metal parts of
equipment together and to the
• System grounded conductor (neutral) or
• Grounding electrode conductor (GEC)
– Provides path for ground fault current
 Grounding electrode: a conducting object through
which a direct connection to earth is established
such as building steel or a ground rod
ATS Generator Set
GEC
EGC
Neutral
Grounding
Electrode
Why Ground Equipment?
 Safety
 Minimizes hazards of touching live equipment
 Minimizes voltages on equipment during fault conditions
 Provide a path for fault current to return to the source
– Earth is not an acceptable path for fault current to return to the source
Impediments to Effective Equipment Grounding
 Painted surfaces
– Use ground braid or cable across anti-vibration mounts or painted
metal surfaces
 Corroded or damaged ground connections, wires or cables
 Loose ground connections
 Missing star type washers
IEEE Std 142-2007 (Green Book)
System grounding is the intentional connection to ground of a phase or neutral conductor for the purpose of:
a) Controlling the voltage with respect to earth or ground within predictable limits and
b) Providing for a flow of current that will allow detection of an unwanted connection between system
conductors and ground…
… the control of voltage to ground limits the voltage stress on the insulation of conductors…
… the control of voltage also allows reduction of shock hazards
System Grounding
VA-G = 277 V
VB-G = 277 V
VC-G = 277 V
VN-G = 0 V
C A
B
G
N
VA-G = 480 V
VB-G = 0 V
VC-G = 480 V
VN-G = 277 V
C A
B
N
Full Ground Fault on Phase B
Solidly Grounded System
 Most common grounding method for low voltage generator sets
 Enables ground fault detection and thus activation of ground fault
protection equipment
 High level of ground fault current
 Limits excess voltage on ungrounded phases during ground fault
Resistance Grounded System
 Commonly used with medium voltage generator sets
 Limits ground fault current level
 Two types of resistance grounded system:
– Low Resistance Grounding
• Fault current usually limited to 300-500 amps
• Easily detectable with conventional CT’s
• Sufficient to trip circuit breakers
– High Resistance Grounding
• Fault current usually limited to 5-10 amps
• Maintain continuity of power during a fault allowing controlled shutdown
Z
Establishing a Neutral on an Ungrounded System
 Zigzag or wye-delta transformers may be used to obtain a neutral for ungrounded
systems
 Either solidly grounded or resistance grounded
 High impedance to balanced normal phase currents
 Low impedance to zero sequence (fault) currents
Z
M
Z
M
Separately Derived Systems
 NEC Definition - “A premises wiring system
whose power is derived from a source of
electric energy or equipment other than a
service. Such systems have no direct electrical
connection including a solidly connected
grounded circuit conductor, to supply
conductors originating in another system.”
 NEC Section 250.30(A)(1) requires separately
derived systems to have a system bonding
jumper connected between the generator frame
and the grounded circuit conductor (neutral)
Neutral
Ground
Bonding Jumper
Separately Derived System
 No direct electrical connection between sources
 3 Phase, 4 Wire System
 4 Pole Transfer Switch
 Generator neutral is solidly grounded and bonded
4P ATS
To Loads (3-phase/4W with GND)
GEC
Generator Set
GEC
EGC
Service Entrance
Non-Separately Derived System
 Common neutral for entire system
 3-phase, 4 wire system
 3 Pole Transfer Switch
 Neutral is not grounded at the generator
3P ATS Generator Set
To Loads (3-phase/4W with GND)
Service Entrance
Ground Fault Protection and Indication
 NEC 230.95 (CEC 14-102) requires Ground Fault Protection (GFP) at the service
disconnect (utility breaker) for systems with:
– Solidly grounded wye
– More than 150 volts to ground (277/480 or 347/600VAC)
– Over current device rating of 1000A or More (CEC 120/208VAC & 2000A)
 Ground Fault Indication (GFI), not protection, is required at the emergency source
(NEC 700.6 (D))
How Do We Sense Ground Fault?
 Residual
– Most common method for breakers
– CTs on each phase and neutral
– Vector sum of current through all CT’s must be 0 (< threshold)
 Zero sequence
– Single CT around all three phases and neutral
– Same concept as residual method
 Source ground return
– Single CT in the neutral to ground bond
– Method used by our genset control
L1
L2
L3
N
GFR
L1
L2
L3
N
GFR
L1
L2
L3
N
GFR
GFR: Ground Fault Relay
Ground Fault Sensing in LV Emergency Standby Systems
 Most common method is to use GFP in breaker at the service disconnect
 Two rules for proper GF sensing:
– Rule #1: There must be only one neutral/ground connection on any neutral bus at one time
– Rule #2: Ground fault sensors must be downstream from the bonding connection
– These two rules drive the requirement that 4 pole transfer switches must be used when ground fault
sensing is required or may be required in the future.
IEEE Std 446-1995 (Orange Book)
7.9.1 “for most emergency and standby power systems with ground-fault systems, switching of the grounded
circuit conductor by the transfer switch is the recommended practice.”
Sensing a Ground Fault
ATS Generator Set
To Loads (3-phase/4W with GND)
Service Entrance
Two Bonding Jumpers
 Parallel path for ground fault current on the neutral
 GFP does not sense all fault current
 Solution: remove the bond on the generator set
ATS Generator Set
To Loads (3-phase/4W with GND)
Service Entrance
Single Bonding Jumper
 Removing the generator set neutral bond solves the problem in the previous slide
 There is only one path for earth fault current to return to the source
ATS Generator Set
To Loads (3-phase/4W with GND)
3-Pole ATS Connected to Emergency Side
 Ground fault returns on neutral
 Possible nuisance trip during exercise
 Solution: ground the neutral on the source side of sensor
ATS Generator Set
To Loads (3-phase/4W with GND)
Service Entrance
Function of 4-Pole Transfer Switches
 Fourth pole opens the path on neutral
 Allows accurate GFP sensing on both sides
 The neutral is grounded in only one place at a time
 Ground fault sensor is downstream of the bonding connection
ATS Generator Set
Service Entrance
Grounding Case Study
 Nine containerized generator sets on metal platform
 Containers bonded to platform
 Platform connected to underground ground ring
 Each generator is grounded through an NGR located
inside the container
Grounding Case Study
Load
Bank
… …
Underground Ground Ring
Gen 9
Z
Metal Platform
Platform is the fault
current return path
Gen 1
Z
 Should the NGR be bonded to the platform? (Yes/No)
Grounding Case Study
Load
Bank
… …
Underground Ground Ring
Gen 9
Z
Metal Platform
Ground ring is the fault
current return path
Gen 1
Z
Grounding Case Study
 System ground consists of neutral conductors, NGRs and ground ring
– System ground is intended to carry current – don’t rely on metal structures
 Equipment ground consists of containers, platform, cabinets, etc. and ground ring
– Ground ring is common to both equipment and system ground
 Establish a low impedance path for fault current to return to the source
– Path should be through ground ring, not across platform, cabinet, railing
 Minimize touch potential
Grounding of Paralleled Generator Sets
 4 wire systems typically have a
single ground in the switchgear
 Generators in 3 wire systems are typically
separately grounded
 Medium or high voltage generators are
often resistance grounded
G1 G2
GFR
GFR GFR
G1 G2
Z Z
Ground Fault Sensing with Paralleled Systems
G1 G2 G3
:Y
Utility
Neutral
To Loads (3-phase/4W)
4-Pole Breaker
Recommendations
 All equipment that can be energized must be grounded
 Ground fault current must have a defined path to return to the sources
 Remember the two big rules for ground fault sensing in emergency standby systems:
– There can be only one neutral-to-ground bond in the system
– The sensor for the ground-fault signal devices shall be located downstream of the neutral bonding
point
 Specify 4-Pole ATS if:
– GFP on Normal/GF indication on emergency is required
– Any 3-phase 4-wire with line-to-ground voltage above150V when future expansion to the facility is
expected
 Paralleled sources may require complex ground fault schemes
– Modified Differential GFP can differentiate between fault current and normal neutral current in systems
with multiple sources and grounds
– Multiple grounds, 4 wire solid neutral systems and utility paralleling applications may require MDGFP
© 2017 Cummins All Rights Reserved
Thank You!
Please share your feedback by completing the
Power Seminar evaluation form.

More Related Content

What's hot

Representação de Sistemas Elétricos de Potência.ppt
Representação de Sistemas Elétricos de Potência.pptRepresentação de Sistemas Elétricos de Potência.ppt
Representação de Sistemas Elétricos de Potência.ppt
RodrigoPBaziuk
 
EE2353 / High Voltage Engineering - Testing of Cables
EE2353 / High Voltage Engineering - Testing of CablesEE2353 / High Voltage Engineering - Testing of Cables
EE2353 / High Voltage Engineering - Testing of Cables
Rajesh Ramesh
 
Commissioning of Electrical Equipment or systems.ppt
Commissioning of Electrical Equipment or systems.pptCommissioning of Electrical Equipment or systems.ppt
Commissioning of Electrical Equipment or systems.ppt
AlemayehuAsmare
 

What's hot (20)

INSPECTION AND TEST PROCEDURES FOR SWITCHGEAR AND SWITCHBOARD
INSPECTION AND TEST PROCEDURES FOR SWITCHGEAR AND SWITCHBOARDINSPECTION AND TEST PROCEDURES FOR SWITCHGEAR AND SWITCHBOARD
INSPECTION AND TEST PROCEDURES FOR SWITCHGEAR AND SWITCHBOARD
 
Hv grounding final
Hv grounding finalHv grounding final
Hv grounding final
 
Motor Control Centre
Motor Control CentreMotor Control Centre
Motor Control Centre
 
Differential protection
Differential protectionDifferential protection
Differential protection
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Cable Sizing Calculations
Cable Sizing CalculationsCable Sizing Calculations
Cable Sizing Calculations
 
RTCC & AVR
RTCC & AVRRTCC & AVR
RTCC & AVR
 
Representação de Sistemas Elétricos de Potência.ppt
Representação de Sistemas Elétricos de Potência.pptRepresentação de Sistemas Elétricos de Potência.ppt
Representação de Sistemas Elétricos de Potência.ppt
 
Basics of motor control centers
Basics of motor control centersBasics of motor control centers
Basics of motor control centers
 
Cpc 100 user manual
Cpc 100 user manualCpc 100 user manual
Cpc 100 user manual
 
Power System Protection course - Part I
Power System Protection course - Part IPower System Protection course - Part I
Power System Protection course - Part I
 
EE2353 / High Voltage Engineering - Testing of Cables
EE2353 / High Voltage Engineering - Testing of CablesEE2353 / High Voltage Engineering - Testing of Cables
EE2353 / High Voltage Engineering - Testing of Cables
 
High direct current measurement
High direct current measurementHigh direct current measurement
High direct current measurement
 
OMICRON Testing Solutions For Protection & Measurement Systems - OMICRON CMC ...
OMICRON Testing Solutions For Protection & Measurement Systems - OMICRON CMC ...OMICRON Testing Solutions For Protection & Measurement Systems - OMICRON CMC ...
OMICRON Testing Solutions For Protection & Measurement Systems - OMICRON CMC ...
 
Interlocking on switchgear principles
Interlocking on switchgear principlesInterlocking on switchgear principles
Interlocking on switchgear principles
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
 
Commissioning of Electrical Equipment or systems.ppt
Commissioning of Electrical Equipment or systems.pptCommissioning of Electrical Equipment or systems.ppt
Commissioning of Electrical Equipment or systems.ppt
 
ABB High Voltage Fuses - CMF Range, Motor Fuses 3.3kV -11kV
ABB High Voltage Fuses - CMF Range, Motor Fuses 3.3kV -11kVABB High Voltage Fuses - CMF Range, Motor Fuses 3.3kV -11kV
ABB High Voltage Fuses - CMF Range, Motor Fuses 3.3kV -11kV
 
Transformer Diagnostics | Sweep Frequency Response Analysis
Transformer Diagnostics | Sweep Frequency Response AnalysisTransformer Diagnostics | Sweep Frequency Response Analysis
Transformer Diagnostics | Sweep Frequency Response Analysis
 
Motor protection
Motor protectionMotor protection
Motor protection
 

Similar to NEUTRAL TO GROUND BONDING.pdf

Earthing grounding protection Difference between earthing and grounding.pptx
Earthing  grounding protection Difference between earthing and grounding.pptxEarthing  grounding protection Difference between earthing and grounding.pptx
Earthing grounding protection Difference between earthing and grounding.pptx
NANDHAKUMARA10
 
GOOD GROUNDING PRACTICES.ppt
GOOD GROUNDING PRACTICES.pptGOOD GROUNDING PRACTICES.ppt
GOOD GROUNDING PRACTICES.ppt
ganesh2428364
 
ATS, Grounding Issues & Installation Considerations
ATS, Grounding Issues & Installation ConsiderationsATS, Grounding Issues & Installation Considerations
ATS, Grounding Issues & Installation Considerations
michaeljmack
 
Application Considerations for Power System Grounding
Application Considerations for Power System GroundingApplication Considerations for Power System Grounding
Application Considerations for Power System Grounding
michaeljmack
 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
Priten Vasa
 

Similar to NEUTRAL TO GROUND BONDING.pdf (20)

Grounding and Bonding
Grounding and BondingGrounding and Bonding
Grounding and Bonding
 
4th chapter.pptx
4th chapter.pptx4th chapter.pptx
4th chapter.pptx
 
Earthing of epg
Earthing  of epg Earthing  of epg
Earthing of epg
 
Vignettes in Grounding
Vignettes in GroundingVignettes in Grounding
Vignettes in Grounding
 
283481961-POWER-SYSTEM-FAULTS-ppt.ppt
283481961-POWER-SYSTEM-FAULTS-ppt.ppt283481961-POWER-SYSTEM-FAULTS-ppt.ppt
283481961-POWER-SYSTEM-FAULTS-ppt.ppt
 
Earthing grounding protection Difference between earthing and grounding.pptx
Earthing  grounding protection Difference between earthing and grounding.pptxEarthing  grounding protection Difference between earthing and grounding.pptx
Earthing grounding protection Difference between earthing and grounding.pptx
 
System neutral-earthing
System neutral-earthingSystem neutral-earthing
System neutral-earthing
 
GOOD GROUNDING PRACTICES.ppt
GOOD GROUNDING PRACTICES.pptGOOD GROUNDING PRACTICES.ppt
GOOD GROUNDING PRACTICES.ppt
 
GOOD GROUNDING PRACTICES.ppt
GOOD GROUNDING PRACTICES.pptGOOD GROUNDING PRACTICES.ppt
GOOD GROUNDING PRACTICES.ppt
 
High voltage grounding methods
High voltage grounding methods High voltage grounding methods
High voltage grounding methods
 
Effective Methods For Power Systems Grounding
Effective Methods For Power Systems GroundingEffective Methods For Power Systems Grounding
Effective Methods For Power Systems Grounding
 
ATS, Grounding Issues & Installation Considerations
ATS, Grounding Issues & Installation ConsiderationsATS, Grounding Issues & Installation Considerations
ATS, Grounding Issues & Installation Considerations
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDINGPROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
 
Application Considerations for Power System Grounding
Application Considerations for Power System GroundingApplication Considerations for Power System Grounding
Application Considerations for Power System Grounding
 
Equipments in distribution system
Equipments in distribution systemEquipments in distribution system
Equipments in distribution system
 
s.pdf
s.pdfs.pdf
s.pdf
 
Electricity distribution system in india
Electricity distribution system in indiaElectricity distribution system in india
Electricity distribution system in india
 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
 
earthing-system.ppt
earthing-system.pptearthing-system.ppt
earthing-system.ppt
 

Recently uploaded

Recently uploaded (10)

Deciding The Topic of our Magazine.pptx.
Deciding The Topic of our Magazine.pptx.Deciding The Topic of our Magazine.pptx.
Deciding The Topic of our Magazine.pptx.
 
Breathing in New Life_ Part 3 05 22 2024.pptx
Breathing in New Life_ Part 3 05 22 2024.pptxBreathing in New Life_ Part 3 05 22 2024.pptx
Breathing in New Life_ Part 3 05 22 2024.pptx
 
DAY 0 8 A Revelation 05-19-2024 PPT.pptx
DAY 0 8 A Revelation 05-19-2024 PPT.pptxDAY 0 8 A Revelation 05-19-2024 PPT.pptx
DAY 0 8 A Revelation 05-19-2024 PPT.pptx
 
2024-05-15-Surat Meetup-Hyperautomation.pptx
2024-05-15-Surat Meetup-Hyperautomation.pptx2024-05-15-Surat Meetup-Hyperautomation.pptx
2024-05-15-Surat Meetup-Hyperautomation.pptx
 
The Influence and Evolution of Mogul Press in Contemporary Public Relations.docx
The Influence and Evolution of Mogul Press in Contemporary Public Relations.docxThe Influence and Evolution of Mogul Press in Contemporary Public Relations.docx
The Influence and Evolution of Mogul Press in Contemporary Public Relations.docx
 
Understanding Poverty: A Community Questionnaire
Understanding Poverty: A Community QuestionnaireUnderstanding Poverty: A Community Questionnaire
Understanding Poverty: A Community Questionnaire
 
Microsoft Fabric Analytics Engineer (DP-600) Exam Dumps 2024.pdf
Microsoft Fabric Analytics Engineer (DP-600) Exam Dumps 2024.pdfMicrosoft Fabric Analytics Engineer (DP-600) Exam Dumps 2024.pdf
Microsoft Fabric Analytics Engineer (DP-600) Exam Dumps 2024.pdf
 
ACM CHT Best Inspection Practices Kinben Innovation MIC Slideshare.pdf
ACM CHT Best Inspection Practices Kinben Innovation MIC Slideshare.pdfACM CHT Best Inspection Practices Kinben Innovation MIC Slideshare.pdf
ACM CHT Best Inspection Practices Kinben Innovation MIC Slideshare.pdf
 
Databricks Machine Learning Associate Exam Dumps 2024.pdf
Databricks Machine Learning Associate Exam Dumps 2024.pdfDatabricks Machine Learning Associate Exam Dumps 2024.pdf
Databricks Machine Learning Associate Exam Dumps 2024.pdf
 
ServiceNow CIS-Discovery Exam Dumps 2024
ServiceNow CIS-Discovery Exam Dumps 2024ServiceNow CIS-Discovery Exam Dumps 2024
ServiceNow CIS-Discovery Exam Dumps 2024
 

NEUTRAL TO GROUND BONDING.pdf

  • 1. © 2017 Cummins All Rights Reserved Grounding Recommendations for On Site Power Systems Revised: February 23, 2017
  • 2. Course Objectives Participants will be able to:  Explain grounding best practices and code requirements for system and equipment grounding methods.  Define requirements for proper ground fault sensing to help design and install ground fault systems that work correctly.  Define when a 3 pole vs 4 pole transfer switch should be used so that neutral and ground current loops are eliminated and ground fault detection systems work correctly.  Identify key factors of paralleled systems that need to be considered so that ground fault detection systems will work properly.
  • 3. Equipment Grounding vs System Grounding  Equipment grounding – Establish (connect) a conductive path between normally non-current carrying metal parts of equipment AND between these parts and the grounding electrode  System grounding – Deliberate connection between a circuit conductor of a power source and ground (earth)  Both are part of the path for ground fault current to return to the source Neutral Metal Enclosures Grounding Electrode System Ground Equipment Ground
  • 4. Equipment Grounding  Equipment Grounding Conductor (EGC) – Connects normally non–current-carrying metal parts of equipment together and to the • System grounded conductor (neutral) or • Grounding electrode conductor (GEC) – Provides path for ground fault current  Grounding electrode: a conducting object through which a direct connection to earth is established such as building steel or a ground rod ATS Generator Set GEC EGC Neutral Grounding Electrode
  • 5. Why Ground Equipment?  Safety  Minimizes hazards of touching live equipment  Minimizes voltages on equipment during fault conditions  Provide a path for fault current to return to the source – Earth is not an acceptable path for fault current to return to the source
  • 6. Impediments to Effective Equipment Grounding  Painted surfaces – Use ground braid or cable across anti-vibration mounts or painted metal surfaces  Corroded or damaged ground connections, wires or cables  Loose ground connections  Missing star type washers
  • 7. IEEE Std 142-2007 (Green Book) System grounding is the intentional connection to ground of a phase or neutral conductor for the purpose of: a) Controlling the voltage with respect to earth or ground within predictable limits and b) Providing for a flow of current that will allow detection of an unwanted connection between system conductors and ground… … the control of voltage to ground limits the voltage stress on the insulation of conductors… … the control of voltage also allows reduction of shock hazards System Grounding VA-G = 277 V VB-G = 277 V VC-G = 277 V VN-G = 0 V C A B G N VA-G = 480 V VB-G = 0 V VC-G = 480 V VN-G = 277 V C A B N Full Ground Fault on Phase B
  • 8. Solidly Grounded System  Most common grounding method for low voltage generator sets  Enables ground fault detection and thus activation of ground fault protection equipment  High level of ground fault current  Limits excess voltage on ungrounded phases during ground fault
  • 9. Resistance Grounded System  Commonly used with medium voltage generator sets  Limits ground fault current level  Two types of resistance grounded system: – Low Resistance Grounding • Fault current usually limited to 300-500 amps • Easily detectable with conventional CT’s • Sufficient to trip circuit breakers – High Resistance Grounding • Fault current usually limited to 5-10 amps • Maintain continuity of power during a fault allowing controlled shutdown Z
  • 10. Establishing a Neutral on an Ungrounded System  Zigzag or wye-delta transformers may be used to obtain a neutral for ungrounded systems  Either solidly grounded or resistance grounded  High impedance to balanced normal phase currents  Low impedance to zero sequence (fault) currents Z M Z M
  • 11. Separately Derived Systems  NEC Definition - “A premises wiring system whose power is derived from a source of electric energy or equipment other than a service. Such systems have no direct electrical connection including a solidly connected grounded circuit conductor, to supply conductors originating in another system.”  NEC Section 250.30(A)(1) requires separately derived systems to have a system bonding jumper connected between the generator frame and the grounded circuit conductor (neutral) Neutral Ground Bonding Jumper
  • 12. Separately Derived System  No direct electrical connection between sources  3 Phase, 4 Wire System  4 Pole Transfer Switch  Generator neutral is solidly grounded and bonded 4P ATS To Loads (3-phase/4W with GND) GEC Generator Set GEC EGC Service Entrance
  • 13. Non-Separately Derived System  Common neutral for entire system  3-phase, 4 wire system  3 Pole Transfer Switch  Neutral is not grounded at the generator 3P ATS Generator Set To Loads (3-phase/4W with GND) Service Entrance
  • 14. Ground Fault Protection and Indication  NEC 230.95 (CEC 14-102) requires Ground Fault Protection (GFP) at the service disconnect (utility breaker) for systems with: – Solidly grounded wye – More than 150 volts to ground (277/480 or 347/600VAC) – Over current device rating of 1000A or More (CEC 120/208VAC & 2000A)  Ground Fault Indication (GFI), not protection, is required at the emergency source (NEC 700.6 (D))
  • 15. How Do We Sense Ground Fault?  Residual – Most common method for breakers – CTs on each phase and neutral – Vector sum of current through all CT’s must be 0 (< threshold)  Zero sequence – Single CT around all three phases and neutral – Same concept as residual method  Source ground return – Single CT in the neutral to ground bond – Method used by our genset control L1 L2 L3 N GFR L1 L2 L3 N GFR L1 L2 L3 N GFR GFR: Ground Fault Relay
  • 16. Ground Fault Sensing in LV Emergency Standby Systems  Most common method is to use GFP in breaker at the service disconnect  Two rules for proper GF sensing: – Rule #1: There must be only one neutral/ground connection on any neutral bus at one time – Rule #2: Ground fault sensors must be downstream from the bonding connection – These two rules drive the requirement that 4 pole transfer switches must be used when ground fault sensing is required or may be required in the future. IEEE Std 446-1995 (Orange Book) 7.9.1 “for most emergency and standby power systems with ground-fault systems, switching of the grounded circuit conductor by the transfer switch is the recommended practice.”
  • 17. Sensing a Ground Fault ATS Generator Set To Loads (3-phase/4W with GND) Service Entrance
  • 18. Two Bonding Jumpers  Parallel path for ground fault current on the neutral  GFP does not sense all fault current  Solution: remove the bond on the generator set ATS Generator Set To Loads (3-phase/4W with GND) Service Entrance
  • 19. Single Bonding Jumper  Removing the generator set neutral bond solves the problem in the previous slide  There is only one path for earth fault current to return to the source ATS Generator Set To Loads (3-phase/4W with GND)
  • 20. 3-Pole ATS Connected to Emergency Side  Ground fault returns on neutral  Possible nuisance trip during exercise  Solution: ground the neutral on the source side of sensor ATS Generator Set To Loads (3-phase/4W with GND) Service Entrance
  • 21. Function of 4-Pole Transfer Switches  Fourth pole opens the path on neutral  Allows accurate GFP sensing on both sides  The neutral is grounded in only one place at a time  Ground fault sensor is downstream of the bonding connection ATS Generator Set Service Entrance
  • 22. Grounding Case Study  Nine containerized generator sets on metal platform  Containers bonded to platform  Platform connected to underground ground ring  Each generator is grounded through an NGR located inside the container
  • 23. Grounding Case Study Load Bank … … Underground Ground Ring Gen 9 Z Metal Platform Platform is the fault current return path Gen 1 Z  Should the NGR be bonded to the platform? (Yes/No)
  • 24. Grounding Case Study Load Bank … … Underground Ground Ring Gen 9 Z Metal Platform Ground ring is the fault current return path Gen 1 Z
  • 25. Grounding Case Study  System ground consists of neutral conductors, NGRs and ground ring – System ground is intended to carry current – don’t rely on metal structures  Equipment ground consists of containers, platform, cabinets, etc. and ground ring – Ground ring is common to both equipment and system ground  Establish a low impedance path for fault current to return to the source – Path should be through ground ring, not across platform, cabinet, railing  Minimize touch potential
  • 26. Grounding of Paralleled Generator Sets  4 wire systems typically have a single ground in the switchgear  Generators in 3 wire systems are typically separately grounded  Medium or high voltage generators are often resistance grounded G1 G2 GFR GFR GFR G1 G2 Z Z
  • 27. Ground Fault Sensing with Paralleled Systems G1 G2 G3 :Y Utility Neutral To Loads (3-phase/4W) 4-Pole Breaker
  • 28. Recommendations  All equipment that can be energized must be grounded  Ground fault current must have a defined path to return to the sources  Remember the two big rules for ground fault sensing in emergency standby systems: – There can be only one neutral-to-ground bond in the system – The sensor for the ground-fault signal devices shall be located downstream of the neutral bonding point  Specify 4-Pole ATS if: – GFP on Normal/GF indication on emergency is required – Any 3-phase 4-wire with line-to-ground voltage above150V when future expansion to the facility is expected  Paralleled sources may require complex ground fault schemes – Modified Differential GFP can differentiate between fault current and normal neutral current in systems with multiple sources and grounds – Multiple grounds, 4 wire solid neutral systems and utility paralleling applications may require MDGFP
  • 29. © 2017 Cummins All Rights Reserved Thank You! Please share your feedback by completing the Power Seminar evaluation form.