This document discusses fireball formation and combustion optimization in boilers. It covers topics such as:
- Types of combustion (complete vs incomplete) and factors affecting combustion
- Temperature, turbulence, and time requirements for combustion
- Technologies for measuring fireball temperature distribution like acoustic and laser methods
- Software systems for advanced combustion control using modeling and CFD simulations
- An integrated solution combining acoustic temperature measurement and an online optimization system
- Process parameters related to boiler efficiency and deciding fireball shape/size
- An algorithm for optimizing burner setpoints to control the fireball shape based on temperature measurements
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
FIREBALL FORMATION AND COMBUSTION OPTIMIZATION IN A BOILER
1. FIREBALL FORMATION AND COMBUSTION
OPTIMIZATION IN A BOILER
KUMARASWAMY HIREMATH
Senior Research Fellow, MTD
CPRI- Bangalore
2. C O M B U S T I O N C O M B U S T I O N I S A C H E M I C A L P R O C E S S I N
W H I C H A S U B S TA N C E R E AC T S R A P I D LY W I T H O XY G E N A N D
G I V E S O F F H E AT.
C+ O2 = CO2 + 8084 KCALS/KG OF CARBON
2C + O2 = 2CO + 2430 KCALS/KG OF CARBON
2H2 + O2 = 2H2O + 28,922 KCALS/KG OF HYDROGEN
S + O2 = SO + 2,224 KCALS/KG OF SULPHUR
FIREBALL FORMATION AND
COMBUSTION OF COAL IN A BOILER
3. Complete Combustion Incomplete Combustion
Involves complete burning of
fuel.
It takes place when there is
constant and enough oxygen
supply as well as sufficient
temperature.
In complete combustion limited
number of products are formed
in contrast to incomplete
combustion. If case of
hydrocarbon, only carbon
dioxide and water is produced.
Results in more energy
Involves partial burning of fuel
It takes place when there is
insufficient oxygen supply or
temperature.
In case of hydrocarbons ,
monoxides and carbon particles
are also produced other than
carbon dioxide and water
Results in less energy
COMPLETE VS INCOMPLETE
COMBUSTION
5. 3T’S OF COMBUSTION
Temperature high enough to ignite the fuel
Turbulence vigorous enough for the fuel constituents to be
exposed to the oxygen of the air
Time long enough to assure complete combustion.
The three requirements are best met by pulverized coal,
which is forced into the furnace by an air stream under
high pressure and is ignited as it enters through a nozzle.
6. fireball & Optimization
Contactless temperature measurement technologies, which are
used in coal fired boilers to measure temperature distribution
Acoustic technology
Laser technology
Regarding software optimization systems for advanced
combustion control there is number of different solutions
Coal combustion modelling Using CFD & Empirical models
CFD models are very complex and are used for deep
investigation of the process. Information provided from CFD
analysis could be used for manual tuning of a boiler.
7. Cont..
Acoustic temperature measurement system – AGAM
C= 𝑠𝑞𝑡
𝑘𝐵
𝑀
𝑇
the system consists of transmitters and receivers placed at the
same level of the furnace. A distance between transmitter and
receiver is a single measuring path. Set of transmitters and
receivers creates a measuring mesh (combination of multiple
paths)
SILO – System for on-line optimization of the combustion
process
9. The fireball control algorithm
Fuel and air supply system in boiler, where A1, A2, A3 and A4 are the burners supplied from
pulverizer 1, B1, B2, B3 and B4 are the burners supplied
from pulverizer 2, C1, C2, C3 and C4 are the burners supplied from pulverizer 3, D1, D2, D3
and D4 are the burners supplied from pulverizer 4, E1, E2, E3 and E4 are the
burners supplied from pulverizer 5, F1, F2, F3 and F4 are the burners supplied from
pulverizer 6
10. Efficiency component Process parameters
Useful heat output
Heat loss in dry flue gas
Heat loss from H2O in
combustion air, fuel and
combustion products
Heat loss from unburned
carbon in the refuse
Heat loss from unburned
combustible gas in flue
gases
Superheated steam
temperature, reheated steam
temperature, reheated spray
flow
Mass of dry flue gas, flue gas
temperature
flue gas temperature
Mass of unburned carbon in
fly and bottom ash
Mass of combustible gases in
flue gases
BOILER PARAMETERS DIRECTLY RELATED TO
BOILER’S EFFICIENCY.
11. DECIDING PARAMETERS OF FIREBALL SHAPE
AND SIZE
Left-right hot spot position,
Intensity,
Dispersion
The fire-ball shape is calculated on a basis of twelve AGAM
temperatures.
Position of temperatures hot spot indicates, wheather the fire-ball is
shifted to left or right side of the furnace.
Intensity is calculated as average temperature for a given
temperature profile
Dispersion is a parameter calculated as standard deviation of
AGAM temperatures.
12. Contd..
This algorithm monitors difference between current and
reference shape and calculate optimal set points for twelve
AGAM temperatures to minimize this difference.
Penalty function for single AGAM temperature –
standard approach
Penalty function for single AGAM temperature
- dynamically calculated.