NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 6, JUNE-2015
1 | P a g e
Miss. R.S.Firke
P. G. Student
Prof. G.K.Mahajan
Asso. Prof. Electrical Engg Dept.
Prof. A.P.Chaudhari
Assi.Prof.Electrical Engg Dept.
S.S.G.B.C.O.E.T. Bhusawal , India
Abstract
Module integrated converters (MICs) in single phase have witnessed recent market success due to unique
features such as improved energy harvest, improved system efficiency, lower installation costs, plug-and-
play operation, and enhanced flexibility and modularity. The MIC sector has grown from a niche market
to mainstream, especially in the United States. Assuming further expansion of the MIC market, this paper
presents the micro inverter concept incorporated in large size photovoltaic (PV) installations such as
megawatts (MW)-class solar farms where a three-phase ac connection is employed. A high-efficiency
three-phase MIC with two-stage zero voltage switching (ZVS) operation for the grid-tied PV system is
proposed which will reduce cost per watt, improve re-liability, and increase scalability of MW-class solar
farms through the development of new solar farm system architectures. The first stage consists of a high-
efficiency full-bridge LLC resonant dc–dc converter which interfaces to the PV panel and produces a dc-
link voltage. A center points iteration algorithm developed specifically for LLC resonant topologies is
used to track the maximum power point of the PV panel. The second stage is comprised of a three-phase
dc–ac inverter circuit which employs a simple soft-switching scheme without adding auxiliary
components. The modeling and control strategy of this three-phase dc–ac inverter is described. Because
the dc-link capacitor plays such an important role for dual-stage MIC, the capacitance calculation is given
under type D voltage dip conditions.
Keywords: Center points iteration (CPI), maximum power point tracking (MPPT), module integrated
converter (MIC), three phase, two stage.
Introduction
With ever dwindling natural resources and increasing demands for power, the need to seek out viable
alter-native sources of renewable energy is not just acute but urgent. Due to the fact that solar energy
offers extraordinary merits including environmentally neutral, unlimited availability and low cost capable
of competing with conventional sources with technology advances and mass production in the coming few
years. The photovoltaic (PV) industry has seen over 25% growth on an average over the last 10 years.
Other than the PV panel itself, the inverter is the most critical device in a PV system both for off-grid or
grid-connection applications. Currently, the PV system architectures can be categorized into three basic
classes with respect to the types of grid-tied inverter: central inverter, string or multistring inverter, and
module integrated converter (MIC) (also called micro inverter). Although the central inverter can operate
at high efficiency with only one dc/ac power conversion stage, this structure has some disadvantages: 1)
A REVIEW ON IMPLEMENTATION OF THREE-PHASE
TWO-STAGE GRID-CONNECTED MIC
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 6, JUNE-2015
2 | P a g e
each PV module may not operate at its maximum power point which results in less energy harvested; 2)
additional losses are introduced by string diodes and junction box; and 3) single point of failure and
mismatch of each string or PV panel affects the PV array efficiency greatly. The string inverter is a
modified version of the central inverter. It partially overcomes the issues arising in central inverters;
however, it still suffers some of the disadvantages of the central inverter. In an effort to maximize the
power from each PV panel, a new approach was recently proposed which can be applied to either central
or string inverter architectures. A power maximize (usually in the form of a dc/dc converter) is attached to
each PV panel to implement maximum power tracking. Although the architecture maximizes power from
each PV panel at the cost of additional dc/dc module, it still suffers from drawbacks such as high-voltage
hazard, single-point failure, and difficulty in maintenance. The MIC typically used in distributed PV
systems is a small grid-tie inverter of 150–400 W that converts the output of a single PV panel to ac. The
MIC ac outputs are connected in parallel and routed to a common ac coupling point. No series or parallel
dc connections are made leaving all dc wiring at a relatively low voltage level of a single panel. The MIC
can be further integrated into PV modules to realize a true plug-and-play solar ac PV generation system.
Thus, ac PV modules with integrated MIC have significant advantages over traditional PV systems since
they allow maximum peak power tracking on each solar panel to maximize energy harvesting, and offer
distributed and redundant system architecture. In addition, MIC and ac PV systems greatly simplify
system design, eliminate safety hazards, and reduce installation costs With these advantages, the ac
module has become the trend for future PV system development. Although MIC and ac PV modules have
witnessed recent market success, MIC still has many technical challenges remaining such as high
efficiency, high reliability at module level, low-cost and high-level control issues. To date, research of the
MIC has mainly focused on isolated topologies for the following two reasons: 1) from reported literature,
most topologies with a few exceptions cannot meet the dual grounding requirement without transformer
isolation according to the UL1741 standard; and 2) using transformer is the best way to boost the low
input voltage to high output voltage for ac grid with high efficiency. Since line transformers are bulky and
costly, this architecture is not practical for MIC. This paper mainly focuses on the architecture employing
a high-frequency transformer. The MIC with its high-frequency transformer can be grouped into three
architectures based on the dc-link configurations: dc-link, pseudo-dc-link, and high-frequency ac. Usually
the MIC just pumps the power from PV to ac grid with unidirectional power flow. However, with the
presence of the power decoupling capacitor, MIC can support the ac grid not only as an ac power source,
but as a VAR and possibly a harmonics compensator as well. For the latter two cases, bidirectional power
flow is needed between ac grid and the power decoupling capacitor requiring MIC with bidirectional
power flow capability. For applications with power levels under several kilowatts, the single-phase
connection is commonly used.
Literature Survey
Resonant converters have been confined in the last thirty years to niche applications such as very high-
voltage applications or high fidelity audio systems while much effort was spent in research by industries
and universities because of its attractive features: smooth waveforms, high efficiency and high power
density. In recent times the LLC resonant Converter in particular in its half-bridge implementation, has
been widely and successfully applied to flat panel TV, 80+ ATX and small form factor PC, where the
requirements on efficiency, power density and EMC compliance of their switching mode power supplies
(SMPS) are getting more and more stringent. However future SMPS requirements will have to face one
of the few remaining drawbacks of LLC resonant converter topology that is related to the output filter
capacitors volume that represents the major limit for such applications. The injection of rectified sine
wave currents into the output filter capacitor can be adequately mitigated by the parallel use of multiple
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 6, JUNE-2015
3 | P a g e
modules such as in interleaved buck solutions for voltage regulator modules. This topology has been
presented in for two modules operating with 90 degrees phase shift. One of the drawbacks of this solution
is represented by the inherent current unbalance caused by resonant component mismatch that may cause
one of the two modules to reduce its output power down to zero, thus requiring mandatory workarounds to
overcome the problem Resonant converters are commonly selected for applications which demand for a
high power density and a high energy efficiency. By featuring soft-switching, the switching frequency can
in general be chosen much higher than the switching frequency of a comparable hard-switching converter.
As a consequence, the volume required for the passive components is drastically reduced, enabling high
power densities and high power conversion efficiencies. In this paper, a highly efficient battery charger is
designed, which is capable of bidirectionally charging light electric vehicles (LEVs). The charger will be
connected to a dc micro-grid at Vdc = 450V and will feature an output voltage range from 17Vto56V. To
limit the duty-cycle and/or frequency variation, and to provide galvanic separation from the dc-bus, a
transformer is needed. For this type of application, the LLC resonant converter promises remarkable
unidirectional performance. In, a bidirectional LLC prototype was built, but no optimized modulation
schemes were employed and the converter did not achieve satisfactory power conversion efficiency. In a
symmetric fourth-order resonant converter was built based on an LLC resonant tank, featuring an
additional resonant capacitor. However, the proposed CLLC converter operates in boost-mode in both
directions and is therefore not very suitable for use as a voltage-regulating converter. the LLC resonant
converter has drawn a lot of attention due to its advantages over the conventional series resonant
converter and parallel resonant converter: narrow frequency variation over wide load and input variation
and Zero Voltage Switching (ZVS) of the switches for entire load range. This paper presents an analysis
and reviews practical design considerations for the LLC-type resonant converter. It includes designing the
transformer and selecting the components. The step-by-step design procedure explained with a design
example will help engineers design the LLC resonant converter easily. The effect of resonant component
mismatch will also be explored and a suitable star connection solution will be investigated to overcome
current derating limits by means of intrinsic balancing. Section XIVX will investigate the feasibility of
phase-shedding for the three phase LLC resonant converter with star connection exploring the benefits in
terms of converter efficiency, effects on current ripple reduction and switching frequency design.
Measurements on a prototype will be included in the paper as validation of assertions and proposals. [1]
The Basic requirements of battery chargers with switching regulators are small sized and high
efficiency. High switching frequency is necessary to achieve a small size. However, the switching loss
will increase as the switching frequency is increased. This condition, in turn, decreases the efficiency. To
solve this problem, some kinds of soft-switching techniques need to be used to operate under high
switching frequency. One simple solution to a soft-switching converter is loaded resonant converters. By
adopting these topologies, either voltage or current is zero during switching transition, which largely
reduce the switching loss and also increase the reliability for the battery charger. It eliminates both low-
and high frequency current ripple on the battery, thus maximizing battery life without penalizing the
volume of the charger.[2]
The isolated unidirectional LLC resonant converter is known for its outstanding efficiency and high
power density.Little information has however been published about the possibility of transferring power in
the reverse direction. This paper presents modulation schemes for making the LLC converter
bidirectional. High efficiencies are predicted for both directions of power flow, though, as the behavior of
the resonant tank is substantially different in the reverse direction, some of the inherent benefits of the
conventional LLC converter are lost.[3]
In this paper a topology for multi-phase interleaved LLC resonant converter is presented. The proposed
solution, based on three LLC modules with transformer primary windings star connection allows to
drastically reduce the output current ripple and consequently to minimize the output filter capacitor size.
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 6, JUNE-2015
4 | P a g e
Differently from other multi-phase solutions, that are greatly susceptible to resonant component mismatch
and consequently can be affected by a considerable current imbalance among modules, the proposed
topology exhibits an inherent balancing capability. Small-signal analysis is presented and the possibility to
turn-off one or two modules (phase shedding) at reduced output current levels is discussed, highlighting
the trade-off between converter efficiency and output capacitor current ripple reduction. Measurements on
a prototype will be included in the paper as validation of assertions and proposals.[4]
Theory
Architecture of Two-Stage Three-Phase Grid-Tie Inverter System
In order to provide galvanic isolation, various isolated converters for high step up applications have
been proposed. In general, the topologies with galvanic isolation suitable for this application can be
categorized into two groups: single-switch topologies and multi switch topologies. Recently, the LLC
resonant topology has become attractive due to its desirable characteristics such as high efficiency and
natural zero voltage switching (ZVS)/zero current switching (ZCS) commutation. Therefore, a full-bridge
LLC resonant converter is employed in the first stage to achieve high efficiency and track the maximum
power point of each PV panel. For the three-phase dc/ac converter in the second stage, a variety of active
soft-switching topologies have been proposed in last three decades. Most of them can be divided into
three groups: auxiliary resonant commutated pole (ARCP) group , resonant dc-link inverter (RDCLI)
group , and resonant ac-link converter (RACLC) ,The ARCP can be applied broadly for the voltage-source
type single-phase or three-phase inverters but it requires a large number of auxiliary components.
Compared to the ARCP, the RDCLI has the advantages of fewer auxiliary switches and a simpler circuit.
Several soft-switching topologies in were proposed to achieve the minimum number of extra components.
However, the driving signals of the auxiliary switches are very sensitive to the noise from the main circuit.
Since the RACLC can achieve voltage boosting and electrical isolation at the same time, it is highly
preferred for renewable energy power generation. Unfortunately, the control circuit for the RACLC is
complex and bidirectional switches are required. In fact, auxiliary components are unavoidable for all of
the soft switching topologies mentioned earlier. The proposed soft-switching technique shown in Fig.1
simplifies the inverter topology and reduces the cost since it does not require any auxiliary components.
The body capacitors of
the main MOSFETs and the output inductor L1 are combined to form a resonant circuit. The inductor
current is intentionally bidirectional within a switching cycle to generate ZVS conditions during
commutation. Meanwhile the average inductor current is controlled to produce a sinusoidal current in L1.
The proposed soft-switching technique is suitable for MIC applications where the switching losses are
usually dominant. Based on the above, Fig. 1 shows the proposed high-efficiency MIC architecture with
both-stage zero-voltage switching consisting of a full-bridge LLC resonant dc–dc step up converter and
three phase four-wire soft-switching dc–ac converter. The detail operating modes in the three-phase four-
wire dc/ac converter will be presented in the following sections.
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 6, JUNE-2015
5 | P a g e
Fig. Two-stage three-phase four-wire grid-tie inverter system.
Full Bridge LLC Resonant Converter
Secondary batteries are widely used in the application of residential, industrial, and commercial energy
storage systems to store electricity and supply the load for various types of electronic equipment [1]–[7].
If the dc source is directly connected to the secondary battery, the output voltage of the dc source is fixed
to the voltage of the secondary battery; therefore, the system cannot always operate at each optimum
operating point. Therefore, it is necessary to install a dc–dc interface between the dc source and the
secondary battery to make the energy storage system always operates at the optimum operating points.
This dc–dc interface is also called the battery charger. The traditional battery charger, which extracts
power from an ac-line source, requires a thyristor ac/dc converter rectifier with an equivalent series
resistance to control the power flow to charge the battery system. Such a charging circuit necessarily
draws a high-ripple charging current. Accordingly, as the concern about the quality of a charger grows, a
charging circuit for reducing the ripple and extending the battery life becomes more important in
designing the battery storage systems. Several charging circuits have been proposed to overcome the
disadvantages of the traditional battery charger. Unlike linear regulators, switching regulators use active
power switches to operate in either the saturation region or the cutoff region. Because either region will
lead to low switching voltage or low switching current, it is possible to convert a dc voltage to a different
level with greater efficiency, as well as with low cost, relatively small size, and light weight between the
two columns. The life and capacity of the secondary batteries depend on several factors e.g., charge mode,
maintenance, temperature and age. Among these factors, the charge mode has a great impact on battery
life and capacity. The secondary batteries should be charged with current and voltage levels with low
ripple. Therefore, a high-performance battery charger is necessary in a battery energy storage system. In
addition, the basic requirements of battery chargers with switching regulators are small sized and high
efficiency . High switching frequency is necessary to achieve a small size. However, the switching loss
will increase as the switching frequency is increased. This condition, in turn, decreases the efficiency of
the battery chargers. To solve this problem, some kinds of soft-switching techniques need to be used to
operate switching frequency.One simple solution to a soft- switching converter is loaded under high
resonant converters. By adopting these topologies, either voltage or current is zero during switching
transition, which largely reduce the switching loss and also increase the reliability for the battery chargers.
To minimize the power losses, it is essential not to waste energy in the conversion process. In relation to
the power electronics and associated control schemes, the main requirement is to guarantee that the
charging system is efficient. Therefore, topologies with high frequencies and soft-switching technique are
used to reduce the charging current ripple and extend battery life. Among these existing soft-switching
converters, Resonant converters are the most popular ones because of their simplicity of circuit
configuration, low switching losses, and high flexibility for charging current regulation. Resonant
converters can be classified, depending on the manner by which energy is extracted from the resonant
tank, into the following three types: 1) series resonant converters; 2) parallel resonant converters; and 3)
series–parallel converters. The series resonant converter is inherently short circuit and protected by the
impedance resonant tank. However, the drawback of the series resonant converter is that the charging
voltage cannot be regulated at no load and light-load conditions. The disadvantage of the parallel
converter is that the current in the resonant components is relatively independent of the load. The
conduction losses are fixed, and the efficiency of the converter is relatively poor for light loads. On the
other hand, the series–parallel converter combines the advantages of the series and parallel converters.
The output is controllable for no load or light load, and the light load efficiency is relatively high.
Accordingly, a series–parallel dc–dc converter is installed between the ac input source and the storage
batteries to control the operating points of the dc source.
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 6, JUNE-2015
6 | P a g e
Fig3.2: Block Diagram Of Full Bridge LLC Resonant Converter For Battery Charging Application.
Operation Mode Of The Proposed ZVS Three-Phase Four-Wire Dc/Ac Converter
Because many articles about LLC resonant converters have been published over the last decade, this
paper does not discuss it in great detail. The operating modes of the proposed ZVS three-phase four-wire
dc/ac converter is presented in this section. As shown in Fig. 3.1, the three phases of the dc/ac second
stage are symmetrical around the neutral point; therefore, the analysis can be performed on a single phase
as shown in Fig. 3and described below.
Interval 1 [t0 − t1 ]: Prior to t0, S7 is off and S8 is still turned ON. Assume that the current direction
through L1, as shown in Fig. 3, is already from right to left at t0 . Then S8 is turned OFF and the voltage
across the parasitic capacitor CS8 of low side MOSFET S8 starts increasing due to the inductor current.
As CS8 charges the voltage across S7 decreases. This interval ends once the voltage across S7 reaches
zero.
Interval 2 [t1 − t2 ]: The body diode of S7 will be conducting at t1 and S7 can be turned ON with ZVS.
The current flow decays linearly from right to left due to the fact that Ubus/2 minus the voltage across L1
This mode ends when the inductor current decays to zero.
Interval 3 [t2 − t3 ]: S7 is conducting and the current direction through L1 is now changed from left to
right and increasing linearly. This is the power delivery interval.
Interval 4 [t3 − t4 ]: At t3, S7 is turned OFF and its parasitic capacitor CS7 is charged by the inductor
current while CS8 is discharging. Once the voltage across CS8 drops to zero, the parasitic body diode of
MOSFET S8 conducts since the current direction through L1 does not change.
Interval 5 [t4 − t5 ]: Continuing from the previous interval 4, the body diode of S8 continues conducting
which creates a ZVS condition when S8 is turned ON. The length of this interval is typically quite short
and ends once S8 is turned ON.
Interval 6 [t5 − t6 ]: S8 is turned ON under ZVS condition at t5 . The current through S8 is gradually
decreasing due to the fact that Ubus/2 plus the output voltage appears across the inductor L1 . During this
interval the energy stored in the inductor is transferred to the load and the current that was flowing in the
body diode of S8 now flows through the MOSFET on resistance thus reducing conduction losses.
Interval 7 [t6 − t0 ]: The current through S8 continues to flow and the current direction will change once
the current decays to zero at t6 . Once the current through S8 changes direction from top to bottom as
shown in Fig. 3.3, a ZVS condition is created for S7 .When the current through S8 reaches the negative
threshold current, the cycle repeats.
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 6, JUNE-2015
7 | P a g e
Fig. Theoretic waveforms and operating intervals of a single-phase dc/ac converter. Interval 1: [t0 − t1],
interval 2: [t1 − t2], interval 3: [t2 − t3], interva4: [t3 − t4],interval 5: [t4 − t5 ], interval 6: [t5 − t6 ], and
interval 7: [t6 − t0 ].
Interleaved Three Phase LLC Resonant Converter
LLC Resonant Converters Exhibit A Large Voltage Ripple On Output Filter Capacitor Because Of The
Rectified Sine-Wave Current Injected Through The Transformer Secondary Windings. In Order To
Reduce The Capacitor Size And/or The Steady-State Output Voltage Ripple, The Interleaved Approach
Can be Profitably Applied. In Xfigure 2Xa Multi-Phase LLC Resonant Converter Is Depicted: Three
Identical Modules (Specifications Listed In Table 1X) Are Parallel Connected And Switched At The Same
Frequency But With 120 Degrees Phase-Shift Of Their Driving Signals. Xfigure 3Xshows The Benefit Of
An Increasing Number Of Parallel Modules On The Total Rectified Current Ripple, That Is The Peak-To-
Peak AC Current Injected Into The Output Filter Capacitor. The Results In Xfigure 3Xare Obtained
From MATLAB Simulink Simulations with 400 V Input Voltage,24 V Output Voltage And Different
Output Currents. The Huge Reduction Of Total Current Ripple In The Three Modules Solution Can Be
Appreciated As Compared To One And Two Modules Counterparts, Suggesting The Possibility To
Drastically Reduce The Output Filter Capacitor Size. The Use of Parallel Connected LLC Resonant
Converters To Supply The Same Load And Share The Same Output Filter Capacitor Presents Limitations
And Drawbacks Caused by Resonant Devices Mismatch. The Modules Are Operated at The Same
Switching Frequency Controlled By The Voltage Regulation Loop, While Resonant Component
Mismatch Causes The Three Phases To Exhibit Different Voltage Conversion Ratios. As A Consequence,
The Load Current Is No Longer Equally Supplied By The Modules And One Of The Phases May Totally
Reduce Its Output Power To Zero Illustrates The Results Of Some Measurements On The Prototype For
Different Operating Conditions In Presence Of Resonant Device Mismatch. In Order To Emphasize The
Mismatch The Third Module Resonant Capacitor Has Been Increased By 12 % By Adding A 2.7 Nf
Capacitor In Parallel To The Nominal One (22 Nf). It Can Be Noticed From The Data In The Left-Half Of
The Table, That The Third Module Delivers Zero Output Current, In Presence of Resonant Component
Mismatch. This Condition Is Confirmed by the Inspection of the Primary-Side Currents (400 V Input
Voltage, 8 A Output Current Conditions): The Primary-Side Current Of The third Module Is Indeed
Interested Only by the Magnetizing current. In Order To Overcome Such Liitation, That Is Unavoidable In
Mass Production, A Three-Phase Topology Is Proposed, Where The Transformers Primary Windings Are
Star Connected. This Modification Allows, By Means Of The Voltage Modulation Of Star Connection
Point, To Greatly Reduce The Mean Current Unbalance Caused By Component Mismatch. From Data
Shown In The Right-Half Of, The Intrinsic Balancing Capability Of This topology Is Pointed Out
Compared To The Simple Parallel Connection. Moreover, Confirm The Great Balancing Ability Of The
Star Connection Topology Compared To A Simple Parallel Interleaved Connection.
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 6, JUNE-2015
8 | P a g e
Fig.3.4. Scheme of a single module LLC resonant converter.
TABLE 1
Specification and component sizing for the LLC resonant
converter
VN 320-420V
V N-NOMINAL 400V
VOUT 24V
IOUT 0-6A
CR 22nF
LR 110 µH
LM 585µH
COUT (4400+470)µF
N1 36 Turns
N2 4 Turns
Fig. Interleaved three phases LLC resonant converter using transformers primary windings star
connectionX.
Capacitance Calculation Of Dc-Link Capacitor And Input Capacitor
The dc/dc stage and dc/ac stage are decoupled due to the action of the dc-link capacitor, simplifying the
controller design for both stages. Because of the three-phase dc/ac converter in the second stage, the value
of the dc-link capacitor can be smaller for a given MIC power rating. Thus, the reliability of whole system
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 6, JUNE-2015
9 | P a g e
will be significantly improved if the electrolytic capacitors are replaced by film capacitors. Although the
capacitance value
DC-Link Capacitance Calculation
Referring to the small-signal model of the dc-link capacitor shown in , the dc-link capacitance is
determined by grid disturbance and generator disturbance. Because the MPPT iteration time is relatively
slow, the dc-link capacitance is only calculated based on grid disturbance of an unbalanced three-phase
system in this paper. Asymmetrical faults lead to drops in one, two, or three phases with not all phases
having the same drop. The resulting voltage drops and phase-angle shifts depend on a number of factors.
The different types of voltage sags present in a generic distribution system are summarized in Table II.
TABLE II
Three-phase unbalanced dips due to different fault types and transformer connections
Fig. Simplified block diagram of two-stage MIC.
Input Capacitance Calculation for LLC Resonant Stage
As mentioned previously, the LLC stage is decoupled from the inverter stage by the dc-link capacitor;
therefore, grid disturbances have little impact on the calculation of input capacitance. The input
capacitance is a function of the steady state and dynamic characteristics of the PV panel and the LLC
resonant converter. Since the execution of MPPT algorithm is slow, PV panel irradiance change is not a
critical factor when calculating input capacitance.
Advantages of Full Bridge LLC
 Using Proposed Converter ( Full Bridge LLC ), we can expect Better Controllability than Half
Bridge for wide voltage range.
 By adopting soft switching topologies, either voltage or current is zero during switching
transition, which largely reduce the switching loss and also increase the reliability for the battery
charger.
 It eliminates both low- and high-frequency current ripple on the battery, without using bulky
filter capacitor, thus maximizing battery life without penalizing the volume of the charger.
 By use of closed loop control operation provides more accuracy and stability under the presence
of nonlinearities.
 Resonant converter topologies can be used to increase circuit switching speeds, improved power
factor and reduced switching losses.
Location of
dip
Fault Type I II III
Three-phase A A A
Three-phase-to-ground A A A
Two-phase-to-ground E F G
Two-phase C D C
Single-phase-to-ground B C D
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 6, JUNE-2015
10 | P a g e
Conclusion
The closed loop control of full bridge LLC Resonant Converter has been analyzed with help of
MATLAB/SIMULINK.. By use soft switching technique, Both low- and high-frequency current ripple are
eliminated on the battery, thus maximizing battery life without penalizing the volume of the charger, and
also reduce the switching loss. Stability is maintained by use of closed loop control operation,and provides
more accuracy under the presence of non-linearity’s .The High effiency achieved with a constant output
voltage The proposed topology is made by three half-bridge LLC converters with transformer primary
windings star connection. This solution allows to drastically reduce the output current ripple compared to
a single module, and exhibits an intrinsic balancing capability that is not common to other resonant
interleaved solutions. Small-signal analysis of the proposed converter has been performed and a suitable
digital control implemented. The possibility of turning off one or two phases depending on the overall
output current level, is investigated, and the trade off between converter efficiency and output capacitor
current ripple is discussed. The ZVS operating mode of the three-phase four-wire dc/ac converter is
illustrated. Average modeling and hybrid control in the dc–ac stage are also discussed.
Acknowledgment
It’s give me a great pleasure to express my deep gratitude to guide Prof. G.K.Mahajan for his valuable
support and help for time to time during work. I am also very thankful to our principal sir, Dr.R.P.Singh
who has provided us such facilities and training to ensure us a bright future finally yet importantly.
References
[1] Lin Chen, Qian Zhang, Nasser Kutkut, “Design and Implementation of Three-Phase Two-Stage Grid-
Connected Module Integrated Converter” ,IEEE Trans. On Power Electronics.,vol. 29,no.8, Aug 2014,
PP. 3881-3892.
[2] J.Hepsy Joseph, R.M.Sekar , J.Velmurugan, “Closed Loop Control of Full Bridge LLC Resonant
Converter for Battery Charging Application” , ‘IOSR Journal of Electrical and Electronics Engineering’
,ISSN 2278-1676,p-ISSN:2320-3331, vol. 9,Issue 1 Ver. IV (Feb. 2014), PP.91-99.
[3] A. Hillers, D. Christen and J. Biela, “Design of a Highly Efficient Bidirectional Isolated LLC
Resonant Converter”, ‘15th International Power Electronics and Motion Control Conference, EPE-PEMC
2012 ECCE Europe, Novi Sad, Serbia’
[4] E. Orietti, P. Mattavelli, G. Spiazzi, C. Adragna, G. Gattavari, “Analysis Of Multi-Phase Llc Resonant
Converters”, Dept. of Information Engineering – University of Padova
[5] E. Roman, R. Alonso, P. Ibanez, S. Elorduizapatarietxe, and D. Goitia, “Intelligent PV module for
grid-connected PV systems,” IEEE Trans. Ind. Electron., vol. 53, no. 4, pp. 1066–1073, Jun. 2006.

More Related Content

What's hot

High Step-Up Converter with Voltage Multiplier Module for Renewable Energy Sy...
High Step-Up Converter with Voltage Multiplier Module for Renewable Energy Sy...High Step-Up Converter with Voltage Multiplier Module for Renewable Energy Sy...
High Step-Up Converter with Voltage Multiplier Module for Renewable Energy Sy...IJRES Journal
 
IRJET- High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...
IRJET-  	  High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...IRJET-  	  High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...
IRJET- High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...IRJET Journal
 
Power quality improvement of distributed generation integrated ne
Power quality improvement of distributed generation integrated nePower quality improvement of distributed generation integrated ne
Power quality improvement of distributed generation integrated neNagaraj Madival
 
IRJET- A Novel Modified Switched Capacitor Nine Level Inverter Topology with ...
IRJET- A Novel Modified Switched Capacitor Nine Level Inverter Topology with ...IRJET- A Novel Modified Switched Capacitor Nine Level Inverter Topology with ...
IRJET- A Novel Modified Switched Capacitor Nine Level Inverter Topology with ...IRJET Journal
 
Impacts of distributed generation on electricity market
Impacts of distributed generation on electricity marketImpacts of distributed generation on electricity market
Impacts of distributed generation on electricity marketHarsh Dhiman
 
Smart Inverters and Their Role in the Modern Electric Grid
Smart Inverters and Their Role in the Modern Electric GridSmart Inverters and Their Role in the Modern Electric Grid
Smart Inverters and Their Role in the Modern Electric GridPower System Operation
 
Solid state transformer
Solid state transformerSolid state transformer
Solid state transformervivatechijri
 
IRJET- Design and Analysis of Typical Chemical Industry Electrical Distributi...
IRJET- Design and Analysis of Typical Chemical Industry Electrical Distributi...IRJET- Design and Analysis of Typical Chemical Industry Electrical Distributi...
IRJET- Design and Analysis of Typical Chemical Industry Electrical Distributi...IRJET Journal
 
IRJET- Power Quality Improvement of Grid Connected Renewable System using...
IRJET-  	  Power Quality Improvement of Grid Connected Renewable System using...IRJET-  	  Power Quality Improvement of Grid Connected Renewable System using...
IRJET- Power Quality Improvement of Grid Connected Renewable System using...IRJET Journal
 
Distributed generation b 3
Distributed generation b 3Distributed generation b 3
Distributed generation b 3Naresh Thakur
 
Epcos Capacitors Dealers In India-System controls switchgear
Epcos Capacitors Dealers In India-System controls switchgearEpcos Capacitors Dealers In India-System controls switchgear
Epcos Capacitors Dealers In India-System controls switchgearsystemcontrols
 
A High Static Gain Modified SEPIC Converter With PV Module and MPPT
A High Static Gain Modified SEPIC Converter With PV Module and MPPTA High Static Gain Modified SEPIC Converter With PV Module and MPPT
A High Static Gain Modified SEPIC Converter With PV Module and MPPTIRJET Journal
 
seminar report on optimal placement and optimal sizing of DG
seminar report on optimal placement and optimal sizing of DGseminar report on optimal placement and optimal sizing of DG
seminar report on optimal placement and optimal sizing of DGkhemraj298
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Scienceinventy
 

What's hot (20)

High Step-Up Converter with Voltage Multiplier Module for Renewable Energy Sy...
High Step-Up Converter with Voltage Multiplier Module for Renewable Energy Sy...High Step-Up Converter with Voltage Multiplier Module for Renewable Energy Sy...
High Step-Up Converter with Voltage Multiplier Module for Renewable Energy Sy...
 
IRJET- High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...
IRJET-  	  High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...IRJET-  	  High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...
IRJET- High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...
 
Power quality improvement of distributed generation integrated ne
Power quality improvement of distributed generation integrated nePower quality improvement of distributed generation integrated ne
Power quality improvement of distributed generation integrated ne
 
IRJET- A Novel Modified Switched Capacitor Nine Level Inverter Topology with ...
IRJET- A Novel Modified Switched Capacitor Nine Level Inverter Topology with ...IRJET- A Novel Modified Switched Capacitor Nine Level Inverter Topology with ...
IRJET- A Novel Modified Switched Capacitor Nine Level Inverter Topology with ...
 
Impacts of distributed generation on electricity market
Impacts of distributed generation on electricity marketImpacts of distributed generation on electricity market
Impacts of distributed generation on electricity market
 
Nonlinear control of GTI for stabilizing future smart grids
Nonlinear control of GTI for stabilizing future smart gridsNonlinear control of GTI for stabilizing future smart grids
Nonlinear control of GTI for stabilizing future smart grids
 
Smart Inverters and Their Role in the Modern Electric Grid
Smart Inverters and Their Role in the Modern Electric GridSmart Inverters and Their Role in the Modern Electric Grid
Smart Inverters and Their Role in the Modern Electric Grid
 
Solid state transformer
Solid state transformerSolid state transformer
Solid state transformer
 
IRJET- Design and Analysis of Typical Chemical Industry Electrical Distributi...
IRJET- Design and Analysis of Typical Chemical Industry Electrical Distributi...IRJET- Design and Analysis of Typical Chemical Industry Electrical Distributi...
IRJET- Design and Analysis of Typical Chemical Industry Electrical Distributi...
 
98X- didier2013.pdf
98X- didier2013.pdf98X- didier2013.pdf
98X- didier2013.pdf
 
IRJET- Power Quality Improvement of Grid Connected Renewable System using...
IRJET-  	  Power Quality Improvement of Grid Connected Renewable System using...IRJET-  	  Power Quality Improvement of Grid Connected Renewable System using...
IRJET- Power Quality Improvement of Grid Connected Renewable System using...
 
www.ijerd.com
www.ijerd.comwww.ijerd.com
www.ijerd.com
 
Distributed generation b 3
Distributed generation b 3Distributed generation b 3
Distributed generation b 3
 
Epcos Capacitors Dealers In India-System controls switchgear
Epcos Capacitors Dealers In India-System controls switchgearEpcos Capacitors Dealers In India-System controls switchgear
Epcos Capacitors Dealers In India-System controls switchgear
 
E1102023442
E1102023442E1102023442
E1102023442
 
A High Static Gain Modified SEPIC Converter With PV Module and MPPT
A High Static Gain Modified SEPIC Converter With PV Module and MPPTA High Static Gain Modified SEPIC Converter With PV Module and MPPT
A High Static Gain Modified SEPIC Converter With PV Module and MPPT
 
Microgrid
MicrogridMicrogrid
Microgrid
 
OPEN LOOP ANALYSIS OF CASCADED HBRIDGE MULTILEVEL INVERTER USING PDPWM FOR PH...
OPEN LOOP ANALYSIS OF CASCADED HBRIDGE MULTILEVEL INVERTER USING PDPWM FOR PH...OPEN LOOP ANALYSIS OF CASCADED HBRIDGE MULTILEVEL INVERTER USING PDPWM FOR PH...
OPEN LOOP ANALYSIS OF CASCADED HBRIDGE MULTILEVEL INVERTER USING PDPWM FOR PH...
 
seminar report on optimal placement and optimal sizing of DG
seminar report on optimal placement and optimal sizing of DGseminar report on optimal placement and optimal sizing of DG
seminar report on optimal placement and optimal sizing of DG
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Science
 

Similar to A REVIEW ON IMPLEMENTATION OF THREE-PHASE TWO-STAGE GRID-CONNECTED MIC

A Multilevel Energy Buffer and Voltage Modulator for Grid-Interfaced Micro-In...
A Multilevel Energy Buffer and Voltage Modulator for Grid-Interfaced Micro-In...A Multilevel Energy Buffer and Voltage Modulator for Grid-Interfaced Micro-In...
A Multilevel Energy Buffer and Voltage Modulator for Grid-Interfaced Micro-In...Projectsatbangalore
 
High Step-Up Converter with Voltage Multiplier Module for Renewable Energy Sy...
High Step-Up Converter with Voltage Multiplier Module for Renewable Energy Sy...High Step-Up Converter with Voltage Multiplier Module for Renewable Energy Sy...
High Step-Up Converter with Voltage Multiplier Module for Renewable Energy Sy...irjes
 
Dz3212381244
Dz3212381244Dz3212381244
Dz3212381244IJMER
 
SIMULATION OF SMART MICROGRID
SIMULATION OF SMART MICROGRIDSIMULATION OF SMART MICROGRID
SIMULATION OF SMART MICROGRIDIRJET Journal
 
Grid connected pv system using 9 level flying capacitor multilevel inverter
Grid connected pv system using 9 level flying capacitor multilevel inverterGrid connected pv system using 9 level flying capacitor multilevel inverter
Grid connected pv system using 9 level flying capacitor multilevel inverterIAEME Publication
 
Modelling and Control of a Microgrid with100kW PV System and Electrochemical ...
Modelling and Control of a Microgrid with100kW PV System and Electrochemical ...Modelling and Control of a Microgrid with100kW PV System and Electrochemical ...
Modelling and Control of a Microgrid with100kW PV System and Electrochemical ...usman1441
 
Photovoltaic Connected Cascaded H bridge Multilevel Inverters with Improved H...
Photovoltaic Connected Cascaded H bridge Multilevel Inverters with Improved H...Photovoltaic Connected Cascaded H bridge Multilevel Inverters with Improved H...
Photovoltaic Connected Cascaded H bridge Multilevel Inverters with Improved H...ijtsrd
 
IRJET-Analysis and Rectification of Fault in Power System by Multilevel Modul...
IRJET-Analysis and Rectification of Fault in Power System by Multilevel Modul...IRJET-Analysis and Rectification of Fault in Power System by Multilevel Modul...
IRJET-Analysis and Rectification of Fault in Power System by Multilevel Modul...IRJET Journal
 
IRJET- Comparative Study of Carrier-Based Pwm Techniques for Control of Doubl...
IRJET- Comparative Study of Carrier-Based Pwm Techniques for Control of Doubl...IRJET- Comparative Study of Carrier-Based Pwm Techniques for Control of Doubl...
IRJET- Comparative Study of Carrier-Based Pwm Techniques for Control of Doubl...IRJET Journal
 
IRJET- 127 Multilevel Inverter
IRJET- 127 Multilevel InverterIRJET- 127 Multilevel Inverter
IRJET- 127 Multilevel InverterIRJET Journal
 
A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...
A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...
A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...IJMTST Journal
 
Presentation on DC-DC converter for EV
Presentation on DC-DC converter for EVPresentation on DC-DC converter for EV
Presentation on DC-DC converter for EVUdayaKumar120822
 
Analysis and Design of Solar Photo voltaic Grid Connected Inverter
Analysis and Design of Solar Photo voltaic Grid Connected InverterAnalysis and Design of Solar Photo voltaic Grid Connected Inverter
Analysis and Design of Solar Photo voltaic Grid Connected Inverterijeei-iaes
 
Implementation Of A High-Efficiency, High-Lifetime, And Low-Cost Converter Us...
Implementation Of A High-Efficiency, High-Lifetime, And Low-Cost Converter Us...Implementation Of A High-Efficiency, High-Lifetime, And Low-Cost Converter Us...
Implementation Of A High-Efficiency, High-Lifetime, And Low-Cost Converter Us...irjes
 
IRJET- Modular Multilevel Converter for Power Quality Improvement
IRJET- Modular Multilevel Converter for Power Quality ImprovementIRJET- Modular Multilevel Converter for Power Quality Improvement
IRJET- Modular Multilevel Converter for Power Quality ImprovementIRJET Journal
 
Performance of Photovoltaic Assisted Five Level Diode Clamped Inverter fed In...
Performance of Photovoltaic Assisted Five Level Diode Clamped Inverter fed In...Performance of Photovoltaic Assisted Five Level Diode Clamped Inverter fed In...
Performance of Photovoltaic Assisted Five Level Diode Clamped Inverter fed In...IJMTST Journal
 

Similar to A REVIEW ON IMPLEMENTATION OF THREE-PHASE TWO-STAGE GRID-CONNECTED MIC (20)

IJET-V2I6P10
IJET-V2I6P10IJET-V2I6P10
IJET-V2I6P10
 
A Multilevel Energy Buffer and Voltage Modulator for Grid-Interfaced Micro-In...
A Multilevel Energy Buffer and Voltage Modulator for Grid-Interfaced Micro-In...A Multilevel Energy Buffer and Voltage Modulator for Grid-Interfaced Micro-In...
A Multilevel Energy Buffer and Voltage Modulator for Grid-Interfaced Micro-In...
 
High Step-Up Converter with Voltage Multiplier Module for Renewable Energy Sy...
High Step-Up Converter with Voltage Multiplier Module for Renewable Energy Sy...High Step-Up Converter with Voltage Multiplier Module for Renewable Energy Sy...
High Step-Up Converter with Voltage Multiplier Module for Renewable Energy Sy...
 
Dz3212381244
Dz3212381244Dz3212381244
Dz3212381244
 
SIMULATION OF SMART MICROGRID
SIMULATION OF SMART MICROGRIDSIMULATION OF SMART MICROGRID
SIMULATION OF SMART MICROGRID
 
Grid connected pv system using 9 level flying capacitor multilevel inverter
Grid connected pv system using 9 level flying capacitor multilevel inverterGrid connected pv system using 9 level flying capacitor multilevel inverter
Grid connected pv system using 9 level flying capacitor multilevel inverter
 
Modelling and Control of a Microgrid with100kW PV System and Electrochemical ...
Modelling and Control of a Microgrid with100kW PV System and Electrochemical ...Modelling and Control of a Microgrid with100kW PV System and Electrochemical ...
Modelling and Control of a Microgrid with100kW PV System and Electrochemical ...
 
Photovoltaic Connected Cascaded H bridge Multilevel Inverters with Improved H...
Photovoltaic Connected Cascaded H bridge Multilevel Inverters with Improved H...Photovoltaic Connected Cascaded H bridge Multilevel Inverters with Improved H...
Photovoltaic Connected Cascaded H bridge Multilevel Inverters with Improved H...
 
IRJET-Analysis and Rectification of Fault in Power System by Multilevel Modul...
IRJET-Analysis and Rectification of Fault in Power System by Multilevel Modul...IRJET-Analysis and Rectification of Fault in Power System by Multilevel Modul...
IRJET-Analysis and Rectification of Fault in Power System by Multilevel Modul...
 
IRJET- Comparative Study of Carrier-Based Pwm Techniques for Control of Doubl...
IRJET- Comparative Study of Carrier-Based Pwm Techniques for Control of Doubl...IRJET- Comparative Study of Carrier-Based Pwm Techniques for Control of Doubl...
IRJET- Comparative Study of Carrier-Based Pwm Techniques for Control of Doubl...
 
High efficiency three phase nine level diode clamped multilevel inverter
High efficiency three phase nine level diode clamped multilevel inverterHigh efficiency three phase nine level diode clamped multilevel inverter
High efficiency three phase nine level diode clamped multilevel inverter
 
2
22
2
 
IRJET- 127 Multilevel Inverter
IRJET- 127 Multilevel InverterIRJET- 127 Multilevel Inverter
IRJET- 127 Multilevel Inverter
 
A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...
A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...
A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...
 
Presentation on DC-DC converter for EV
Presentation on DC-DC converter for EVPresentation on DC-DC converter for EV
Presentation on DC-DC converter for EV
 
Analysis and Design of Solar Photo voltaic Grid Connected Inverter
Analysis and Design of Solar Photo voltaic Grid Connected InverterAnalysis and Design of Solar Photo voltaic Grid Connected Inverter
Analysis and Design of Solar Photo voltaic Grid Connected Inverter
 
A bidirectional resonant converter based on wide input range and high efficie...
A bidirectional resonant converter based on wide input range and high efficie...A bidirectional resonant converter based on wide input range and high efficie...
A bidirectional resonant converter based on wide input range and high efficie...
 
Implementation Of A High-Efficiency, High-Lifetime, And Low-Cost Converter Us...
Implementation Of A High-Efficiency, High-Lifetime, And Low-Cost Converter Us...Implementation Of A High-Efficiency, High-Lifetime, And Low-Cost Converter Us...
Implementation Of A High-Efficiency, High-Lifetime, And Low-Cost Converter Us...
 
IRJET- Modular Multilevel Converter for Power Quality Improvement
IRJET- Modular Multilevel Converter for Power Quality ImprovementIRJET- Modular Multilevel Converter for Power Quality Improvement
IRJET- Modular Multilevel Converter for Power Quality Improvement
 
Performance of Photovoltaic Assisted Five Level Diode Clamped Inverter fed In...
Performance of Photovoltaic Assisted Five Level Diode Clamped Inverter fed In...Performance of Photovoltaic Assisted Five Level Diode Clamped Inverter fed In...
Performance of Photovoltaic Assisted Five Level Diode Clamped Inverter fed In...
 

More from ijiert bestjournal

CRACKS IN STEEL CASTING FOR VOLUTE CASING OF A PUMP
 CRACKS IN STEEL CASTING FOR VOLUTE CASING OF A PUMP CRACKS IN STEEL CASTING FOR VOLUTE CASING OF A PUMP
CRACKS IN STEEL CASTING FOR VOLUTE CASING OF A PUMPijiert bestjournal
 
A COMPARATIVE STUDY OF DESIGN OF SIMPLE SPUR GEAR TRAIN AND HELICAL GEAR TRAI...
A COMPARATIVE STUDY OF DESIGN OF SIMPLE SPUR GEAR TRAIN AND HELICAL GEAR TRAI...A COMPARATIVE STUDY OF DESIGN OF SIMPLE SPUR GEAR TRAIN AND HELICAL GEAR TRAI...
A COMPARATIVE STUDY OF DESIGN OF SIMPLE SPUR GEAR TRAIN AND HELICAL GEAR TRAI...ijiert bestjournal
 
COMPARATIVE ANALYSIS OF CONVENTIONAL LEAF SPRING AND COMPOSITE LEAF
COMPARATIVE ANALYSIS OF CONVENTIONAL LEAF SPRING AND COMPOSITE LEAFCOMPARATIVE ANALYSIS OF CONVENTIONAL LEAF SPRING AND COMPOSITE LEAF
COMPARATIVE ANALYSIS OF CONVENTIONAL LEAF SPRING AND COMPOSITE LEAFijiert bestjournal
 
POWER GENERATION BY DIFFUSER AUGMENTED WIND TURBINE
 POWER GENERATION BY DIFFUSER AUGMENTED WIND TURBINE POWER GENERATION BY DIFFUSER AUGMENTED WIND TURBINE
POWER GENERATION BY DIFFUSER AUGMENTED WIND TURBINEijiert bestjournal
 
FINITE ELEMENT ANALYSIS OF CONNECTING ROD OF MG-ALLOY
FINITE ELEMENT ANALYSIS OF CONNECTING ROD OF MG-ALLOY FINITE ELEMENT ANALYSIS OF CONNECTING ROD OF MG-ALLOY
FINITE ELEMENT ANALYSIS OF CONNECTING ROD OF MG-ALLOY ijiert bestjournal
 
REVIEW ON CRITICAL SPEED IMPROVEMENT IN SINGLE CYLINDER ENGINE VALVE TRAIN
REVIEW ON CRITICAL SPEED IMPROVEMENT IN SINGLE CYLINDER ENGINE VALVE TRAINREVIEW ON CRITICAL SPEED IMPROVEMENT IN SINGLE CYLINDER ENGINE VALVE TRAIN
REVIEW ON CRITICAL SPEED IMPROVEMENT IN SINGLE CYLINDER ENGINE VALVE TRAINijiert bestjournal
 
ENERGY CONVERSION PHENOMENON IN IMPLEMENTATION OF WATER LIFTING BY USING PEND...
ENERGY CONVERSION PHENOMENON IN IMPLEMENTATION OF WATER LIFTING BY USING PEND...ENERGY CONVERSION PHENOMENON IN IMPLEMENTATION OF WATER LIFTING BY USING PEND...
ENERGY CONVERSION PHENOMENON IN IMPLEMENTATION OF WATER LIFTING BY USING PEND...ijiert bestjournal
 
SCUDERI SPLIT CYCLE ENGINE: REVOLUTIONARY TECHNOLOGY & EVOLUTIONARY DESIGN RE...
SCUDERI SPLIT CYCLE ENGINE: REVOLUTIONARY TECHNOLOGY & EVOLUTIONARY DESIGN RE...SCUDERI SPLIT CYCLE ENGINE: REVOLUTIONARY TECHNOLOGY & EVOLUTIONARY DESIGN RE...
SCUDERI SPLIT CYCLE ENGINE: REVOLUTIONARY TECHNOLOGY & EVOLUTIONARY DESIGN RE...ijiert bestjournal
 
EXPERIMENTAL EVALUATION OF TEMPERATURE DISTRIBUTION IN JOURNAL BEARING OPERAT...
EXPERIMENTAL EVALUATION OF TEMPERATURE DISTRIBUTION IN JOURNAL BEARING OPERAT...EXPERIMENTAL EVALUATION OF TEMPERATURE DISTRIBUTION IN JOURNAL BEARING OPERAT...
EXPERIMENTAL EVALUATION OF TEMPERATURE DISTRIBUTION IN JOURNAL BEARING OPERAT...ijiert bestjournal
 
STUDY OF SOLAR THERMAL CAVITY RECEIVER FOR PARABOLIC CONCENTRATING COLLECTOR
STUDY OF SOLAR THERMAL CAVITY RECEIVER FOR PARABOLIC CONCENTRATING COLLECTOR STUDY OF SOLAR THERMAL CAVITY RECEIVER FOR PARABOLIC CONCENTRATING COLLECTOR
STUDY OF SOLAR THERMAL CAVITY RECEIVER FOR PARABOLIC CONCENTRATING COLLECTOR ijiert bestjournal
 
DESIGN, OPTIMIZATION AND FINITE ELEMENT ANALYSIS OF CRANKSHAFT
DESIGN, OPTIMIZATION AND FINITE ELEMENT ANALYSIS OF CRANKSHAFTDESIGN, OPTIMIZATION AND FINITE ELEMENT ANALYSIS OF CRANKSHAFT
DESIGN, OPTIMIZATION AND FINITE ELEMENT ANALYSIS OF CRANKSHAFTijiert bestjournal
 
ELECTRO CHEMICAL MACHINING AND ELECTRICAL DISCHARGE MACHINING PROCESSES MICRO...
ELECTRO CHEMICAL MACHINING AND ELECTRICAL DISCHARGE MACHINING PROCESSES MICRO...ELECTRO CHEMICAL MACHINING AND ELECTRICAL DISCHARGE MACHINING PROCESSES MICRO...
ELECTRO CHEMICAL MACHINING AND ELECTRICAL DISCHARGE MACHINING PROCESSES MICRO...ijiert bestjournal
 
HEAT TRANSFER ENHANCEMENT BY USING NANOFLUID JET IMPINGEMENT
HEAT TRANSFER ENHANCEMENT BY USING NANOFLUID JET IMPINGEMENTHEAT TRANSFER ENHANCEMENT BY USING NANOFLUID JET IMPINGEMENT
HEAT TRANSFER ENHANCEMENT BY USING NANOFLUID JET IMPINGEMENTijiert bestjournal
 
MODIFICATION AND OPTIMIZATION IN STEEL SANDWICH PANELS USING ANSYS WORKBENCH
MODIFICATION AND OPTIMIZATION IN STEEL SANDWICH PANELS USING ANSYS WORKBENCH MODIFICATION AND OPTIMIZATION IN STEEL SANDWICH PANELS USING ANSYS WORKBENCH
MODIFICATION AND OPTIMIZATION IN STEEL SANDWICH PANELS USING ANSYS WORKBENCH ijiert bestjournal
 
IMPACT ANALYSIS OF ALUMINUM HONEYCOMB SANDWICH PANEL BUMPER BEAM: A REVIEW
IMPACT ANALYSIS OF ALUMINUM HONEYCOMB SANDWICH PANEL BUMPER BEAM: A REVIEW IMPACT ANALYSIS OF ALUMINUM HONEYCOMB SANDWICH PANEL BUMPER BEAM: A REVIEW
IMPACT ANALYSIS OF ALUMINUM HONEYCOMB SANDWICH PANEL BUMPER BEAM: A REVIEW ijiert bestjournal
 
DESIGN OF WELDING FIXTURES AND POSITIONERS
DESIGN OF WELDING FIXTURES AND POSITIONERSDESIGN OF WELDING FIXTURES AND POSITIONERS
DESIGN OF WELDING FIXTURES AND POSITIONERSijiert bestjournal
 
ADVANCED TRANSIENT THERMAL AND STRUCTURAL ANALYSIS OF DISC BRAKE BY USING ANS...
ADVANCED TRANSIENT THERMAL AND STRUCTURAL ANALYSIS OF DISC BRAKE BY USING ANS...ADVANCED TRANSIENT THERMAL AND STRUCTURAL ANALYSIS OF DISC BRAKE BY USING ANS...
ADVANCED TRANSIENT THERMAL AND STRUCTURAL ANALYSIS OF DISC BRAKE BY USING ANS...ijiert bestjournal
 
REVIEW ON MECHANICAL PROPERTIES OF NON-ASBESTOS COMPOSITE MATERIAL USED IN BR...
REVIEW ON MECHANICAL PROPERTIES OF NON-ASBESTOS COMPOSITE MATERIAL USED IN BR...REVIEW ON MECHANICAL PROPERTIES OF NON-ASBESTOS COMPOSITE MATERIAL USED IN BR...
REVIEW ON MECHANICAL PROPERTIES OF NON-ASBESTOS COMPOSITE MATERIAL USED IN BR...ijiert bestjournal
 
PERFORMANCE EVALUATION OF TRIBOLOGICAL PROPERTIES OF COTTON SEED OIL FOR MULT...
PERFORMANCE EVALUATION OF TRIBOLOGICAL PROPERTIES OF COTTON SEED OIL FOR MULT...PERFORMANCE EVALUATION OF TRIBOLOGICAL PROPERTIES OF COTTON SEED OIL FOR MULT...
PERFORMANCE EVALUATION OF TRIBOLOGICAL PROPERTIES OF COTTON SEED OIL FOR MULT...ijiert bestjournal
 

More from ijiert bestjournal (20)

CRACKS IN STEEL CASTING FOR VOLUTE CASING OF A PUMP
 CRACKS IN STEEL CASTING FOR VOLUTE CASING OF A PUMP CRACKS IN STEEL CASTING FOR VOLUTE CASING OF A PUMP
CRACKS IN STEEL CASTING FOR VOLUTE CASING OF A PUMP
 
A COMPARATIVE STUDY OF DESIGN OF SIMPLE SPUR GEAR TRAIN AND HELICAL GEAR TRAI...
A COMPARATIVE STUDY OF DESIGN OF SIMPLE SPUR GEAR TRAIN AND HELICAL GEAR TRAI...A COMPARATIVE STUDY OF DESIGN OF SIMPLE SPUR GEAR TRAIN AND HELICAL GEAR TRAI...
A COMPARATIVE STUDY OF DESIGN OF SIMPLE SPUR GEAR TRAIN AND HELICAL GEAR TRAI...
 
COMPARATIVE ANALYSIS OF CONVENTIONAL LEAF SPRING AND COMPOSITE LEAF
COMPARATIVE ANALYSIS OF CONVENTIONAL LEAF SPRING AND COMPOSITE LEAFCOMPARATIVE ANALYSIS OF CONVENTIONAL LEAF SPRING AND COMPOSITE LEAF
COMPARATIVE ANALYSIS OF CONVENTIONAL LEAF SPRING AND COMPOSITE LEAF
 
POWER GENERATION BY DIFFUSER AUGMENTED WIND TURBINE
 POWER GENERATION BY DIFFUSER AUGMENTED WIND TURBINE POWER GENERATION BY DIFFUSER AUGMENTED WIND TURBINE
POWER GENERATION BY DIFFUSER AUGMENTED WIND TURBINE
 
FINITE ELEMENT ANALYSIS OF CONNECTING ROD OF MG-ALLOY
FINITE ELEMENT ANALYSIS OF CONNECTING ROD OF MG-ALLOY FINITE ELEMENT ANALYSIS OF CONNECTING ROD OF MG-ALLOY
FINITE ELEMENT ANALYSIS OF CONNECTING ROD OF MG-ALLOY
 
REVIEW ON CRITICAL SPEED IMPROVEMENT IN SINGLE CYLINDER ENGINE VALVE TRAIN
REVIEW ON CRITICAL SPEED IMPROVEMENT IN SINGLE CYLINDER ENGINE VALVE TRAINREVIEW ON CRITICAL SPEED IMPROVEMENT IN SINGLE CYLINDER ENGINE VALVE TRAIN
REVIEW ON CRITICAL SPEED IMPROVEMENT IN SINGLE CYLINDER ENGINE VALVE TRAIN
 
ENERGY CONVERSION PHENOMENON IN IMPLEMENTATION OF WATER LIFTING BY USING PEND...
ENERGY CONVERSION PHENOMENON IN IMPLEMENTATION OF WATER LIFTING BY USING PEND...ENERGY CONVERSION PHENOMENON IN IMPLEMENTATION OF WATER LIFTING BY USING PEND...
ENERGY CONVERSION PHENOMENON IN IMPLEMENTATION OF WATER LIFTING BY USING PEND...
 
SCUDERI SPLIT CYCLE ENGINE: REVOLUTIONARY TECHNOLOGY & EVOLUTIONARY DESIGN RE...
SCUDERI SPLIT CYCLE ENGINE: REVOLUTIONARY TECHNOLOGY & EVOLUTIONARY DESIGN RE...SCUDERI SPLIT CYCLE ENGINE: REVOLUTIONARY TECHNOLOGY & EVOLUTIONARY DESIGN RE...
SCUDERI SPLIT CYCLE ENGINE: REVOLUTIONARY TECHNOLOGY & EVOLUTIONARY DESIGN RE...
 
EXPERIMENTAL EVALUATION OF TEMPERATURE DISTRIBUTION IN JOURNAL BEARING OPERAT...
EXPERIMENTAL EVALUATION OF TEMPERATURE DISTRIBUTION IN JOURNAL BEARING OPERAT...EXPERIMENTAL EVALUATION OF TEMPERATURE DISTRIBUTION IN JOURNAL BEARING OPERAT...
EXPERIMENTAL EVALUATION OF TEMPERATURE DISTRIBUTION IN JOURNAL BEARING OPERAT...
 
STUDY OF SOLAR THERMAL CAVITY RECEIVER FOR PARABOLIC CONCENTRATING COLLECTOR
STUDY OF SOLAR THERMAL CAVITY RECEIVER FOR PARABOLIC CONCENTRATING COLLECTOR STUDY OF SOLAR THERMAL CAVITY RECEIVER FOR PARABOLIC CONCENTRATING COLLECTOR
STUDY OF SOLAR THERMAL CAVITY RECEIVER FOR PARABOLIC CONCENTRATING COLLECTOR
 
DESIGN, OPTIMIZATION AND FINITE ELEMENT ANALYSIS OF CRANKSHAFT
DESIGN, OPTIMIZATION AND FINITE ELEMENT ANALYSIS OF CRANKSHAFTDESIGN, OPTIMIZATION AND FINITE ELEMENT ANALYSIS OF CRANKSHAFT
DESIGN, OPTIMIZATION AND FINITE ELEMENT ANALYSIS OF CRANKSHAFT
 
ELECTRO CHEMICAL MACHINING AND ELECTRICAL DISCHARGE MACHINING PROCESSES MICRO...
ELECTRO CHEMICAL MACHINING AND ELECTRICAL DISCHARGE MACHINING PROCESSES MICRO...ELECTRO CHEMICAL MACHINING AND ELECTRICAL DISCHARGE MACHINING PROCESSES MICRO...
ELECTRO CHEMICAL MACHINING AND ELECTRICAL DISCHARGE MACHINING PROCESSES MICRO...
 
HEAT TRANSFER ENHANCEMENT BY USING NANOFLUID JET IMPINGEMENT
HEAT TRANSFER ENHANCEMENT BY USING NANOFLUID JET IMPINGEMENTHEAT TRANSFER ENHANCEMENT BY USING NANOFLUID JET IMPINGEMENT
HEAT TRANSFER ENHANCEMENT BY USING NANOFLUID JET IMPINGEMENT
 
MODIFICATION AND OPTIMIZATION IN STEEL SANDWICH PANELS USING ANSYS WORKBENCH
MODIFICATION AND OPTIMIZATION IN STEEL SANDWICH PANELS USING ANSYS WORKBENCH MODIFICATION AND OPTIMIZATION IN STEEL SANDWICH PANELS USING ANSYS WORKBENCH
MODIFICATION AND OPTIMIZATION IN STEEL SANDWICH PANELS USING ANSYS WORKBENCH
 
IMPACT ANALYSIS OF ALUMINUM HONEYCOMB SANDWICH PANEL BUMPER BEAM: A REVIEW
IMPACT ANALYSIS OF ALUMINUM HONEYCOMB SANDWICH PANEL BUMPER BEAM: A REVIEW IMPACT ANALYSIS OF ALUMINUM HONEYCOMB SANDWICH PANEL BUMPER BEAM: A REVIEW
IMPACT ANALYSIS OF ALUMINUM HONEYCOMB SANDWICH PANEL BUMPER BEAM: A REVIEW
 
DESIGN OF WELDING FIXTURES AND POSITIONERS
DESIGN OF WELDING FIXTURES AND POSITIONERSDESIGN OF WELDING FIXTURES AND POSITIONERS
DESIGN OF WELDING FIXTURES AND POSITIONERS
 
ADVANCED TRANSIENT THERMAL AND STRUCTURAL ANALYSIS OF DISC BRAKE BY USING ANS...
ADVANCED TRANSIENT THERMAL AND STRUCTURAL ANALYSIS OF DISC BRAKE BY USING ANS...ADVANCED TRANSIENT THERMAL AND STRUCTURAL ANALYSIS OF DISC BRAKE BY USING ANS...
ADVANCED TRANSIENT THERMAL AND STRUCTURAL ANALYSIS OF DISC BRAKE BY USING ANS...
 
REVIEW ON MECHANICAL PROPERTIES OF NON-ASBESTOS COMPOSITE MATERIAL USED IN BR...
REVIEW ON MECHANICAL PROPERTIES OF NON-ASBESTOS COMPOSITE MATERIAL USED IN BR...REVIEW ON MECHANICAL PROPERTIES OF NON-ASBESTOS COMPOSITE MATERIAL USED IN BR...
REVIEW ON MECHANICAL PROPERTIES OF NON-ASBESTOS COMPOSITE MATERIAL USED IN BR...
 
PERFORMANCE EVALUATION OF TRIBOLOGICAL PROPERTIES OF COTTON SEED OIL FOR MULT...
PERFORMANCE EVALUATION OF TRIBOLOGICAL PROPERTIES OF COTTON SEED OIL FOR MULT...PERFORMANCE EVALUATION OF TRIBOLOGICAL PROPERTIES OF COTTON SEED OIL FOR MULT...
PERFORMANCE EVALUATION OF TRIBOLOGICAL PROPERTIES OF COTTON SEED OIL FOR MULT...
 
MAGNETIC ABRASIVE FINISHING
MAGNETIC ABRASIVE FINISHINGMAGNETIC ABRASIVE FINISHING
MAGNETIC ABRASIVE FINISHING
 

Recently uploaded

power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxvipinkmenon1
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfme23b1001
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 

Recently uploaded (20)

young call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Serviceyoung call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Service
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptx
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdf
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 

A REVIEW ON IMPLEMENTATION OF THREE-PHASE TWO-STAGE GRID-CONNECTED MIC

  • 1. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 6, JUNE-2015 1 | P a g e Miss. R.S.Firke P. G. Student Prof. G.K.Mahajan Asso. Prof. Electrical Engg Dept. Prof. A.P.Chaudhari Assi.Prof.Electrical Engg Dept. S.S.G.B.C.O.E.T. Bhusawal , India Abstract Module integrated converters (MICs) in single phase have witnessed recent market success due to unique features such as improved energy harvest, improved system efficiency, lower installation costs, plug-and- play operation, and enhanced flexibility and modularity. The MIC sector has grown from a niche market to mainstream, especially in the United States. Assuming further expansion of the MIC market, this paper presents the micro inverter concept incorporated in large size photovoltaic (PV) installations such as megawatts (MW)-class solar farms where a three-phase ac connection is employed. A high-efficiency three-phase MIC with two-stage zero voltage switching (ZVS) operation for the grid-tied PV system is proposed which will reduce cost per watt, improve re-liability, and increase scalability of MW-class solar farms through the development of new solar farm system architectures. The first stage consists of a high- efficiency full-bridge LLC resonant dc–dc converter which interfaces to the PV panel and produces a dc- link voltage. A center points iteration algorithm developed specifically for LLC resonant topologies is used to track the maximum power point of the PV panel. The second stage is comprised of a three-phase dc–ac inverter circuit which employs a simple soft-switching scheme without adding auxiliary components. The modeling and control strategy of this three-phase dc–ac inverter is described. Because the dc-link capacitor plays such an important role for dual-stage MIC, the capacitance calculation is given under type D voltage dip conditions. Keywords: Center points iteration (CPI), maximum power point tracking (MPPT), module integrated converter (MIC), three phase, two stage. Introduction With ever dwindling natural resources and increasing demands for power, the need to seek out viable alter-native sources of renewable energy is not just acute but urgent. Due to the fact that solar energy offers extraordinary merits including environmentally neutral, unlimited availability and low cost capable of competing with conventional sources with technology advances and mass production in the coming few years. The photovoltaic (PV) industry has seen over 25% growth on an average over the last 10 years. Other than the PV panel itself, the inverter is the most critical device in a PV system both for off-grid or grid-connection applications. Currently, the PV system architectures can be categorized into three basic classes with respect to the types of grid-tied inverter: central inverter, string or multistring inverter, and module integrated converter (MIC) (also called micro inverter). Although the central inverter can operate at high efficiency with only one dc/ac power conversion stage, this structure has some disadvantages: 1) A REVIEW ON IMPLEMENTATION OF THREE-PHASE TWO-STAGE GRID-CONNECTED MIC
  • 2. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 6, JUNE-2015 2 | P a g e each PV module may not operate at its maximum power point which results in less energy harvested; 2) additional losses are introduced by string diodes and junction box; and 3) single point of failure and mismatch of each string or PV panel affects the PV array efficiency greatly. The string inverter is a modified version of the central inverter. It partially overcomes the issues arising in central inverters; however, it still suffers some of the disadvantages of the central inverter. In an effort to maximize the power from each PV panel, a new approach was recently proposed which can be applied to either central or string inverter architectures. A power maximize (usually in the form of a dc/dc converter) is attached to each PV panel to implement maximum power tracking. Although the architecture maximizes power from each PV panel at the cost of additional dc/dc module, it still suffers from drawbacks such as high-voltage hazard, single-point failure, and difficulty in maintenance. The MIC typically used in distributed PV systems is a small grid-tie inverter of 150–400 W that converts the output of a single PV panel to ac. The MIC ac outputs are connected in parallel and routed to a common ac coupling point. No series or parallel dc connections are made leaving all dc wiring at a relatively low voltage level of a single panel. The MIC can be further integrated into PV modules to realize a true plug-and-play solar ac PV generation system. Thus, ac PV modules with integrated MIC have significant advantages over traditional PV systems since they allow maximum peak power tracking on each solar panel to maximize energy harvesting, and offer distributed and redundant system architecture. In addition, MIC and ac PV systems greatly simplify system design, eliminate safety hazards, and reduce installation costs With these advantages, the ac module has become the trend for future PV system development. Although MIC and ac PV modules have witnessed recent market success, MIC still has many technical challenges remaining such as high efficiency, high reliability at module level, low-cost and high-level control issues. To date, research of the MIC has mainly focused on isolated topologies for the following two reasons: 1) from reported literature, most topologies with a few exceptions cannot meet the dual grounding requirement without transformer isolation according to the UL1741 standard; and 2) using transformer is the best way to boost the low input voltage to high output voltage for ac grid with high efficiency. Since line transformers are bulky and costly, this architecture is not practical for MIC. This paper mainly focuses on the architecture employing a high-frequency transformer. The MIC with its high-frequency transformer can be grouped into three architectures based on the dc-link configurations: dc-link, pseudo-dc-link, and high-frequency ac. Usually the MIC just pumps the power from PV to ac grid with unidirectional power flow. However, with the presence of the power decoupling capacitor, MIC can support the ac grid not only as an ac power source, but as a VAR and possibly a harmonics compensator as well. For the latter two cases, bidirectional power flow is needed between ac grid and the power decoupling capacitor requiring MIC with bidirectional power flow capability. For applications with power levels under several kilowatts, the single-phase connection is commonly used. Literature Survey Resonant converters have been confined in the last thirty years to niche applications such as very high- voltage applications or high fidelity audio systems while much effort was spent in research by industries and universities because of its attractive features: smooth waveforms, high efficiency and high power density. In recent times the LLC resonant Converter in particular in its half-bridge implementation, has been widely and successfully applied to flat panel TV, 80+ ATX and small form factor PC, where the requirements on efficiency, power density and EMC compliance of their switching mode power supplies (SMPS) are getting more and more stringent. However future SMPS requirements will have to face one of the few remaining drawbacks of LLC resonant converter topology that is related to the output filter capacitors volume that represents the major limit for such applications. The injection of rectified sine wave currents into the output filter capacitor can be adequately mitigated by the parallel use of multiple
  • 3. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 6, JUNE-2015 3 | P a g e modules such as in interleaved buck solutions for voltage regulator modules. This topology has been presented in for two modules operating with 90 degrees phase shift. One of the drawbacks of this solution is represented by the inherent current unbalance caused by resonant component mismatch that may cause one of the two modules to reduce its output power down to zero, thus requiring mandatory workarounds to overcome the problem Resonant converters are commonly selected for applications which demand for a high power density and a high energy efficiency. By featuring soft-switching, the switching frequency can in general be chosen much higher than the switching frequency of a comparable hard-switching converter. As a consequence, the volume required for the passive components is drastically reduced, enabling high power densities and high power conversion efficiencies. In this paper, a highly efficient battery charger is designed, which is capable of bidirectionally charging light electric vehicles (LEVs). The charger will be connected to a dc micro-grid at Vdc = 450V and will feature an output voltage range from 17Vto56V. To limit the duty-cycle and/or frequency variation, and to provide galvanic separation from the dc-bus, a transformer is needed. For this type of application, the LLC resonant converter promises remarkable unidirectional performance. In, a bidirectional LLC prototype was built, but no optimized modulation schemes were employed and the converter did not achieve satisfactory power conversion efficiency. In a symmetric fourth-order resonant converter was built based on an LLC resonant tank, featuring an additional resonant capacitor. However, the proposed CLLC converter operates in boost-mode in both directions and is therefore not very suitable for use as a voltage-regulating converter. the LLC resonant converter has drawn a lot of attention due to its advantages over the conventional series resonant converter and parallel resonant converter: narrow frequency variation over wide load and input variation and Zero Voltage Switching (ZVS) of the switches for entire load range. This paper presents an analysis and reviews practical design considerations for the LLC-type resonant converter. It includes designing the transformer and selecting the components. The step-by-step design procedure explained with a design example will help engineers design the LLC resonant converter easily. The effect of resonant component mismatch will also be explored and a suitable star connection solution will be investigated to overcome current derating limits by means of intrinsic balancing. Section XIVX will investigate the feasibility of phase-shedding for the three phase LLC resonant converter with star connection exploring the benefits in terms of converter efficiency, effects on current ripple reduction and switching frequency design. Measurements on a prototype will be included in the paper as validation of assertions and proposals. [1] The Basic requirements of battery chargers with switching regulators are small sized and high efficiency. High switching frequency is necessary to achieve a small size. However, the switching loss will increase as the switching frequency is increased. This condition, in turn, decreases the efficiency. To solve this problem, some kinds of soft-switching techniques need to be used to operate under high switching frequency. One simple solution to a soft-switching converter is loaded resonant converters. By adopting these topologies, either voltage or current is zero during switching transition, which largely reduce the switching loss and also increase the reliability for the battery charger. It eliminates both low- and high frequency current ripple on the battery, thus maximizing battery life without penalizing the volume of the charger.[2] The isolated unidirectional LLC resonant converter is known for its outstanding efficiency and high power density.Little information has however been published about the possibility of transferring power in the reverse direction. This paper presents modulation schemes for making the LLC converter bidirectional. High efficiencies are predicted for both directions of power flow, though, as the behavior of the resonant tank is substantially different in the reverse direction, some of the inherent benefits of the conventional LLC converter are lost.[3] In this paper a topology for multi-phase interleaved LLC resonant converter is presented. The proposed solution, based on three LLC modules with transformer primary windings star connection allows to drastically reduce the output current ripple and consequently to minimize the output filter capacitor size.
  • 4. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 6, JUNE-2015 4 | P a g e Differently from other multi-phase solutions, that are greatly susceptible to resonant component mismatch and consequently can be affected by a considerable current imbalance among modules, the proposed topology exhibits an inherent balancing capability. Small-signal analysis is presented and the possibility to turn-off one or two modules (phase shedding) at reduced output current levels is discussed, highlighting the trade-off between converter efficiency and output capacitor current ripple reduction. Measurements on a prototype will be included in the paper as validation of assertions and proposals.[4] Theory Architecture of Two-Stage Three-Phase Grid-Tie Inverter System In order to provide galvanic isolation, various isolated converters for high step up applications have been proposed. In general, the topologies with galvanic isolation suitable for this application can be categorized into two groups: single-switch topologies and multi switch topologies. Recently, the LLC resonant topology has become attractive due to its desirable characteristics such as high efficiency and natural zero voltage switching (ZVS)/zero current switching (ZCS) commutation. Therefore, a full-bridge LLC resonant converter is employed in the first stage to achieve high efficiency and track the maximum power point of each PV panel. For the three-phase dc/ac converter in the second stage, a variety of active soft-switching topologies have been proposed in last three decades. Most of them can be divided into three groups: auxiliary resonant commutated pole (ARCP) group , resonant dc-link inverter (RDCLI) group , and resonant ac-link converter (RACLC) ,The ARCP can be applied broadly for the voltage-source type single-phase or three-phase inverters but it requires a large number of auxiliary components. Compared to the ARCP, the RDCLI has the advantages of fewer auxiliary switches and a simpler circuit. Several soft-switching topologies in were proposed to achieve the minimum number of extra components. However, the driving signals of the auxiliary switches are very sensitive to the noise from the main circuit. Since the RACLC can achieve voltage boosting and electrical isolation at the same time, it is highly preferred for renewable energy power generation. Unfortunately, the control circuit for the RACLC is complex and bidirectional switches are required. In fact, auxiliary components are unavoidable for all of the soft switching topologies mentioned earlier. The proposed soft-switching technique shown in Fig.1 simplifies the inverter topology and reduces the cost since it does not require any auxiliary components. The body capacitors of the main MOSFETs and the output inductor L1 are combined to form a resonant circuit. The inductor current is intentionally bidirectional within a switching cycle to generate ZVS conditions during commutation. Meanwhile the average inductor current is controlled to produce a sinusoidal current in L1. The proposed soft-switching technique is suitable for MIC applications where the switching losses are usually dominant. Based on the above, Fig. 1 shows the proposed high-efficiency MIC architecture with both-stage zero-voltage switching consisting of a full-bridge LLC resonant dc–dc step up converter and three phase four-wire soft-switching dc–ac converter. The detail operating modes in the three-phase four- wire dc/ac converter will be presented in the following sections.
  • 5. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 6, JUNE-2015 5 | P a g e Fig. Two-stage three-phase four-wire grid-tie inverter system. Full Bridge LLC Resonant Converter Secondary batteries are widely used in the application of residential, industrial, and commercial energy storage systems to store electricity and supply the load for various types of electronic equipment [1]–[7]. If the dc source is directly connected to the secondary battery, the output voltage of the dc source is fixed to the voltage of the secondary battery; therefore, the system cannot always operate at each optimum operating point. Therefore, it is necessary to install a dc–dc interface between the dc source and the secondary battery to make the energy storage system always operates at the optimum operating points. This dc–dc interface is also called the battery charger. The traditional battery charger, which extracts power from an ac-line source, requires a thyristor ac/dc converter rectifier with an equivalent series resistance to control the power flow to charge the battery system. Such a charging circuit necessarily draws a high-ripple charging current. Accordingly, as the concern about the quality of a charger grows, a charging circuit for reducing the ripple and extending the battery life becomes more important in designing the battery storage systems. Several charging circuits have been proposed to overcome the disadvantages of the traditional battery charger. Unlike linear regulators, switching regulators use active power switches to operate in either the saturation region or the cutoff region. Because either region will lead to low switching voltage or low switching current, it is possible to convert a dc voltage to a different level with greater efficiency, as well as with low cost, relatively small size, and light weight between the two columns. The life and capacity of the secondary batteries depend on several factors e.g., charge mode, maintenance, temperature and age. Among these factors, the charge mode has a great impact on battery life and capacity. The secondary batteries should be charged with current and voltage levels with low ripple. Therefore, a high-performance battery charger is necessary in a battery energy storage system. In addition, the basic requirements of battery chargers with switching regulators are small sized and high efficiency . High switching frequency is necessary to achieve a small size. However, the switching loss will increase as the switching frequency is increased. This condition, in turn, decreases the efficiency of the battery chargers. To solve this problem, some kinds of soft-switching techniques need to be used to operate switching frequency.One simple solution to a soft- switching converter is loaded under high resonant converters. By adopting these topologies, either voltage or current is zero during switching transition, which largely reduce the switching loss and also increase the reliability for the battery chargers. To minimize the power losses, it is essential not to waste energy in the conversion process. In relation to the power electronics and associated control schemes, the main requirement is to guarantee that the charging system is efficient. Therefore, topologies with high frequencies and soft-switching technique are used to reduce the charging current ripple and extend battery life. Among these existing soft-switching converters, Resonant converters are the most popular ones because of their simplicity of circuit configuration, low switching losses, and high flexibility for charging current regulation. Resonant converters can be classified, depending on the manner by which energy is extracted from the resonant tank, into the following three types: 1) series resonant converters; 2) parallel resonant converters; and 3) series–parallel converters. The series resonant converter is inherently short circuit and protected by the impedance resonant tank. However, the drawback of the series resonant converter is that the charging voltage cannot be regulated at no load and light-load conditions. The disadvantage of the parallel converter is that the current in the resonant components is relatively independent of the load. The conduction losses are fixed, and the efficiency of the converter is relatively poor for light loads. On the other hand, the series–parallel converter combines the advantages of the series and parallel converters. The output is controllable for no load or light load, and the light load efficiency is relatively high. Accordingly, a series–parallel dc–dc converter is installed between the ac input source and the storage batteries to control the operating points of the dc source.
  • 6. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 6, JUNE-2015 6 | P a g e Fig3.2: Block Diagram Of Full Bridge LLC Resonant Converter For Battery Charging Application. Operation Mode Of The Proposed ZVS Three-Phase Four-Wire Dc/Ac Converter Because many articles about LLC resonant converters have been published over the last decade, this paper does not discuss it in great detail. The operating modes of the proposed ZVS three-phase four-wire dc/ac converter is presented in this section. As shown in Fig. 3.1, the three phases of the dc/ac second stage are symmetrical around the neutral point; therefore, the analysis can be performed on a single phase as shown in Fig. 3and described below. Interval 1 [t0 − t1 ]: Prior to t0, S7 is off and S8 is still turned ON. Assume that the current direction through L1, as shown in Fig. 3, is already from right to left at t0 . Then S8 is turned OFF and the voltage across the parasitic capacitor CS8 of low side MOSFET S8 starts increasing due to the inductor current. As CS8 charges the voltage across S7 decreases. This interval ends once the voltage across S7 reaches zero. Interval 2 [t1 − t2 ]: The body diode of S7 will be conducting at t1 and S7 can be turned ON with ZVS. The current flow decays linearly from right to left due to the fact that Ubus/2 minus the voltage across L1 This mode ends when the inductor current decays to zero. Interval 3 [t2 − t3 ]: S7 is conducting and the current direction through L1 is now changed from left to right and increasing linearly. This is the power delivery interval. Interval 4 [t3 − t4 ]: At t3, S7 is turned OFF and its parasitic capacitor CS7 is charged by the inductor current while CS8 is discharging. Once the voltage across CS8 drops to zero, the parasitic body diode of MOSFET S8 conducts since the current direction through L1 does not change. Interval 5 [t4 − t5 ]: Continuing from the previous interval 4, the body diode of S8 continues conducting which creates a ZVS condition when S8 is turned ON. The length of this interval is typically quite short and ends once S8 is turned ON. Interval 6 [t5 − t6 ]: S8 is turned ON under ZVS condition at t5 . The current through S8 is gradually decreasing due to the fact that Ubus/2 plus the output voltage appears across the inductor L1 . During this interval the energy stored in the inductor is transferred to the load and the current that was flowing in the body diode of S8 now flows through the MOSFET on resistance thus reducing conduction losses. Interval 7 [t6 − t0 ]: The current through S8 continues to flow and the current direction will change once the current decays to zero at t6 . Once the current through S8 changes direction from top to bottom as shown in Fig. 3.3, a ZVS condition is created for S7 .When the current through S8 reaches the negative threshold current, the cycle repeats.
  • 7. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 6, JUNE-2015 7 | P a g e Fig. Theoretic waveforms and operating intervals of a single-phase dc/ac converter. Interval 1: [t0 − t1], interval 2: [t1 − t2], interval 3: [t2 − t3], interva4: [t3 − t4],interval 5: [t4 − t5 ], interval 6: [t5 − t6 ], and interval 7: [t6 − t0 ]. Interleaved Three Phase LLC Resonant Converter LLC Resonant Converters Exhibit A Large Voltage Ripple On Output Filter Capacitor Because Of The Rectified Sine-Wave Current Injected Through The Transformer Secondary Windings. In Order To Reduce The Capacitor Size And/or The Steady-State Output Voltage Ripple, The Interleaved Approach Can be Profitably Applied. In Xfigure 2Xa Multi-Phase LLC Resonant Converter Is Depicted: Three Identical Modules (Specifications Listed In Table 1X) Are Parallel Connected And Switched At The Same Frequency But With 120 Degrees Phase-Shift Of Their Driving Signals. Xfigure 3Xshows The Benefit Of An Increasing Number Of Parallel Modules On The Total Rectified Current Ripple, That Is The Peak-To- Peak AC Current Injected Into The Output Filter Capacitor. The Results In Xfigure 3Xare Obtained From MATLAB Simulink Simulations with 400 V Input Voltage,24 V Output Voltage And Different Output Currents. The Huge Reduction Of Total Current Ripple In The Three Modules Solution Can Be Appreciated As Compared To One And Two Modules Counterparts, Suggesting The Possibility To Drastically Reduce The Output Filter Capacitor Size. The Use of Parallel Connected LLC Resonant Converters To Supply The Same Load And Share The Same Output Filter Capacitor Presents Limitations And Drawbacks Caused by Resonant Devices Mismatch. The Modules Are Operated at The Same Switching Frequency Controlled By The Voltage Regulation Loop, While Resonant Component Mismatch Causes The Three Phases To Exhibit Different Voltage Conversion Ratios. As A Consequence, The Load Current Is No Longer Equally Supplied By The Modules And One Of The Phases May Totally Reduce Its Output Power To Zero Illustrates The Results Of Some Measurements On The Prototype For Different Operating Conditions In Presence Of Resonant Device Mismatch. In Order To Emphasize The Mismatch The Third Module Resonant Capacitor Has Been Increased By 12 % By Adding A 2.7 Nf Capacitor In Parallel To The Nominal One (22 Nf). It Can Be Noticed From The Data In The Left-Half Of The Table, That The Third Module Delivers Zero Output Current, In Presence of Resonant Component Mismatch. This Condition Is Confirmed by the Inspection of the Primary-Side Currents (400 V Input Voltage, 8 A Output Current Conditions): The Primary-Side Current Of The third Module Is Indeed Interested Only by the Magnetizing current. In Order To Overcome Such Liitation, That Is Unavoidable In Mass Production, A Three-Phase Topology Is Proposed, Where The Transformers Primary Windings Are Star Connected. This Modification Allows, By Means Of The Voltage Modulation Of Star Connection Point, To Greatly Reduce The Mean Current Unbalance Caused By Component Mismatch. From Data Shown In The Right-Half Of, The Intrinsic Balancing Capability Of This topology Is Pointed Out Compared To The Simple Parallel Connection. Moreover, Confirm The Great Balancing Ability Of The Star Connection Topology Compared To A Simple Parallel Interleaved Connection.
  • 8. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 6, JUNE-2015 8 | P a g e Fig.3.4. Scheme of a single module LLC resonant converter. TABLE 1 Specification and component sizing for the LLC resonant converter VN 320-420V V N-NOMINAL 400V VOUT 24V IOUT 0-6A CR 22nF LR 110 µH LM 585µH COUT (4400+470)µF N1 36 Turns N2 4 Turns Fig. Interleaved three phases LLC resonant converter using transformers primary windings star connectionX. Capacitance Calculation Of Dc-Link Capacitor And Input Capacitor The dc/dc stage and dc/ac stage are decoupled due to the action of the dc-link capacitor, simplifying the controller design for both stages. Because of the three-phase dc/ac converter in the second stage, the value of the dc-link capacitor can be smaller for a given MIC power rating. Thus, the reliability of whole system
  • 9. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 6, JUNE-2015 9 | P a g e will be significantly improved if the electrolytic capacitors are replaced by film capacitors. Although the capacitance value DC-Link Capacitance Calculation Referring to the small-signal model of the dc-link capacitor shown in , the dc-link capacitance is determined by grid disturbance and generator disturbance. Because the MPPT iteration time is relatively slow, the dc-link capacitance is only calculated based on grid disturbance of an unbalanced three-phase system in this paper. Asymmetrical faults lead to drops in one, two, or three phases with not all phases having the same drop. The resulting voltage drops and phase-angle shifts depend on a number of factors. The different types of voltage sags present in a generic distribution system are summarized in Table II. TABLE II Three-phase unbalanced dips due to different fault types and transformer connections Fig. Simplified block diagram of two-stage MIC. Input Capacitance Calculation for LLC Resonant Stage As mentioned previously, the LLC stage is decoupled from the inverter stage by the dc-link capacitor; therefore, grid disturbances have little impact on the calculation of input capacitance. The input capacitance is a function of the steady state and dynamic characteristics of the PV panel and the LLC resonant converter. Since the execution of MPPT algorithm is slow, PV panel irradiance change is not a critical factor when calculating input capacitance. Advantages of Full Bridge LLC  Using Proposed Converter ( Full Bridge LLC ), we can expect Better Controllability than Half Bridge for wide voltage range.  By adopting soft switching topologies, either voltage or current is zero during switching transition, which largely reduce the switching loss and also increase the reliability for the battery charger.  It eliminates both low- and high-frequency current ripple on the battery, without using bulky filter capacitor, thus maximizing battery life without penalizing the volume of the charger.  By use of closed loop control operation provides more accuracy and stability under the presence of nonlinearities.  Resonant converter topologies can be used to increase circuit switching speeds, improved power factor and reduced switching losses. Location of dip Fault Type I II III Three-phase A A A Three-phase-to-ground A A A Two-phase-to-ground E F G Two-phase C D C Single-phase-to-ground B C D
  • 10. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 6, JUNE-2015 10 | P a g e Conclusion The closed loop control of full bridge LLC Resonant Converter has been analyzed with help of MATLAB/SIMULINK.. By use soft switching technique, Both low- and high-frequency current ripple are eliminated on the battery, thus maximizing battery life without penalizing the volume of the charger, and also reduce the switching loss. Stability is maintained by use of closed loop control operation,and provides more accuracy under the presence of non-linearity’s .The High effiency achieved with a constant output voltage The proposed topology is made by three half-bridge LLC converters with transformer primary windings star connection. This solution allows to drastically reduce the output current ripple compared to a single module, and exhibits an intrinsic balancing capability that is not common to other resonant interleaved solutions. Small-signal analysis of the proposed converter has been performed and a suitable digital control implemented. The possibility of turning off one or two phases depending on the overall output current level, is investigated, and the trade off between converter efficiency and output capacitor current ripple is discussed. The ZVS operating mode of the three-phase four-wire dc/ac converter is illustrated. Average modeling and hybrid control in the dc–ac stage are also discussed. Acknowledgment It’s give me a great pleasure to express my deep gratitude to guide Prof. G.K.Mahajan for his valuable support and help for time to time during work. I am also very thankful to our principal sir, Dr.R.P.Singh who has provided us such facilities and training to ensure us a bright future finally yet importantly. References [1] Lin Chen, Qian Zhang, Nasser Kutkut, “Design and Implementation of Three-Phase Two-Stage Grid- Connected Module Integrated Converter” ,IEEE Trans. On Power Electronics.,vol. 29,no.8, Aug 2014, PP. 3881-3892. [2] J.Hepsy Joseph, R.M.Sekar , J.Velmurugan, “Closed Loop Control of Full Bridge LLC Resonant Converter for Battery Charging Application” , ‘IOSR Journal of Electrical and Electronics Engineering’ ,ISSN 2278-1676,p-ISSN:2320-3331, vol. 9,Issue 1 Ver. IV (Feb. 2014), PP.91-99. [3] A. Hillers, D. Christen and J. Biela, “Design of a Highly Efficient Bidirectional Isolated LLC Resonant Converter”, ‘15th International Power Electronics and Motion Control Conference, EPE-PEMC 2012 ECCE Europe, Novi Sad, Serbia’ [4] E. Orietti, P. Mattavelli, G. Spiazzi, C. Adragna, G. Gattavari, “Analysis Of Multi-Phase Llc Resonant Converters”, Dept. of Information Engineering – University of Padova [5] E. Roman, R. Alonso, P. Ibanez, S. Elorduizapatarietxe, and D. Goitia, “Intelligent PV module for grid-connected PV systems,” IEEE Trans. Ind. Electron., vol. 53, no. 4, pp. 1066–1073, Jun. 2006.