IEEE TRANSACTIONS ON POWER SYSTEMS 1
A Novel Approach to Determine the Optimal
Location of SFCL in Electric Power Grid
to Improve Power System Stability
G. Didier, Jean Lévêque, and Abderrezak Rezzoug
Abstract—This paper presents a novel approach to determine
the optimal location of a resistive superconducting fault current
limiter (SFCL) for enhancing the transient stability of an electric
power grid (EPG). To select the optimal location of the SFCL, the
sensitivity analysis of the angular separation of the rotors of syn-
chronous machines present in the power system is introduced. The
optimal location of the SFCL in EPG is coordinated with the corre-
sponding optimal resistive value to improve transient stability and
low-frequency oscillation damping performance of the system. It is
shown that the SFCL can have different impacts (positive and neg-
ative) in function of its location in the EPG when a fault occurs.
To evaluate the effectiveness of the proposed method, the IEEE
benchmarked four-machine two-area test system is used to carry
out several case studies. The results show that the optimal location
of SFCL combined with its optimal resistive value reduces the an-
gular separation of the rotors that improves effectively the system
stability during a fault.
Index Terms—Damping performance, electric power grid, op-
timal location, superconducting fault current limiter, transient sta-
bility.
I. INTRODUCTION
WITH the increasing of system capacity, fault occurrence
probability becomes higher, that can induce severe
damages in electrical power system [1]. For example, the high
value of the short-circuit current can damage the insulation
strength of electrical devices, synchronous generators, pro-
tective relays, lines transmission, and loads. In addition, the
electrical power needed by the system when a fault occurs is
modified and induced instable state of the power generators [2].
Recently, the development of superconducting fault current
limiters (SFCL) offers one of the most attractive alternatives
to solve the fault current problems [3]–[5]. Thanks to their fast
transition from a low to a high impedance, superconducting de-
vices can limit, in a very short time, the value of any fault cur-
rent. What is attractive is that the transition is due to an in-
trinsic behavior of the material itself [6]–[9]. It was shown that
Manuscript received November 18, 2011; revised December 03, 2011, April
12, 2012, and July 25, 2012; accepted October 06, 2012. Paper no. TPWRS-
01120-2011.
The authors are with the Groupe de Recherche en Electrotechnique et Elec-
tronique de Nancy (GREEN), EA4366, Faculté des Sciences et Technologies-
Université de Lorraine, 54506 Vandoeuvre lès Nancy, France (e-mail: gaetan.di-
dier@green.uhp-nancy.fr).
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org.
Digital Object Identifier 10.1109/TPWRS.2012.2224386
the presence of the SFCL in a power system can increase the
system stability and distributed energy quality [10]–[15]. When
an SFCL is introduced in an electric power grid (EPG), three
important factors must be considered:
1) optimal location of the SFCL in the EPG [16];
2) optimal resistive value of the SFCL [17];
3) protection-coordination problem with other existing de-
vices (circuit breaker, OCR, etc.) [5], [18], [21], [22].
The presented paper focuses on factors 1 and 2. Nowadays,
the optimal location of SFCL to improve the transient stability
is studied for a simple power system like single machine infinite
bus (SMIB) [2], [3], [15]. So far, the remaining open question is
the selection of optimal location of the SFCL in a large-scale
power system to improve its transient stability. In this paper
we consider a multi-generator system and we use their rotor
angular difference to define a sensitivity index which leads to
finding the best location of the SFCL in the grid. This sensitivity
index is calculated with respect to the resistive value of the used
SFCL. The effectiveness of the proposed method is evaluated
on the IEEE benchmark four-machine two-area test system. The
toolbox SimPowerSystems of MATLAB/SIMULINK software
is used to carry out simulations studies.
The simulation results show the effectiveness of the proposed
method. In fact, the optimal location determined for the SFCL
improves the transient stability of the power system and de-
creases the low frequency oscillation of the generators speed
when a severe damage is introduced (three-phase fault). The ad-
vantage of the proposed method is that the selected location of
the SFCL takes into account the fact that the fault can occur any-
where in the studied grid.
II. SFCL MODEL APPLIED TO POWER SYSTEM
The operation of an SFCL is based on the natural transition
of the superconducting state to normal state by exceeding the
critical current of the material. This transition from the su-
perconducting to the normal state must be done in a very short
time, generally, to limit the first current peak to a threshold value
not exceeding three to five times the rated current, below the
short-circuit current without limitation.
These limiters use the variation of resistivity during the tran-
sition. Indeed, the resistivity of these materials is very high to
normal state, much more than a classical conductor, both for
NbTi and for the YBaCuO 77 K.
The SFCL is placed in series with a circuit breaker. During
the fault, the current increases up to reach the threshold of tran-
sition from superconducting wire. This transition from the su-
0885-8950/$31.00 © 2012 IEEE
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
2 IEEE TRANSACTIONS ON POWER SYSTEMS
perconducting element to normal state causes the development
of resistance that limits or triggers the current limit. The time
between threshold crossing and the limitation is small (a few
micro-seconds). The circuit breaker isolates the line as soon as
possible after the beginning of the limitation. These supercon-
ducting fault current limiters use one of the fundamental prop-
erties of superconductors.
The qualifications of SFCL are:
• Very low impedance during normal operation.
The current limiter must be “invisible” in this mode. Some
transients such as those caused during the switching of a
transformer should not inadvertently cause a transition of
the limiter.
• High impedance system during short-circuit.
The limiter must perform its function in the case of massive
short circuit but also in the case of low short-circuit fault.
• Very good dynamic.
The system must transit in very quickly (within mil-
lisecond) to effectively limit the value of the short circuit.
There are several types of SFCL; the main ones include:
• The resistive limiter.
This is a coil of superconductive material, non-inductive by
construction, mounted in series on the line. In case of fault,
the winding initially at the superconducting state changes
to the normal state. Its impedance appears in the line, which
limits the fault current. This limiter can be applied in AC
or DC systems.
• The inductive limiter.
It consists in its simplest form, two windings connected in
parallel. This association is made so that the impedance of
all is the lowest possible. In case of fault, one of the coils
(made of superconducting material) returns to its normal
state. The other winding made either copper or supercon-
ducting material limit the current through the inductance.
• The limiting transformer.
It consists of a superconducting secondary short-circuit
and primary winding of a conventional copper. In normal
operation, the impedance of this transformer is mainly due
to the coupling between the windings and may be very low.
Under fault, the secondary winding quenches under the ef-
fect of fault current and acts as a switch that opens the sec-
ondary of the transformer. Therefore, we obtain the no load
impedance of a transformer which is very important.
As we said, the first function of an SFCL is to limit the fault
current induced in the faulty line. In this case, the passage to its
superconducting state to its normal state can only be achieved
if the fault appears in the line where the limiter is placed. The
probability that a fault appears at a specific location in the power
system is very low. Consequently, if the fault appears at a dif-
ferent location in the power system, the SFCL cannot be used
for its first function because the current value through the SFCL
will be not sufficient to ensure a transition of this last. The orig-
inality of the presented work is that the SFCL is used if the fault
appears anywhere in the system. In this case, the SFCL can be
seen as a rapid switch that introduces a resistance in the power
system. The presence of this additional resistance improves the
power system stability in case of short-circuit and this, regard-
less of the position of the fault. The SFCL is not used to limit the
fault current but to improve the stability of the power system.
If the fault appears in the line where the limiter is placed, the
two functions of the SFCL are used (limitation of the fault cur-
rent in the line and improvement of the power system stability).
By cons, if a fault appears at a different location, the SFCL in-
troduce its resistance in the power system to improve the tran-
sient stability of generators. In this case, the passage to its su-
perconducting state to its normal state will be accomplished by
applying a magnetic field superior to its critical magnetic field
after the detection of the fault in the EPG. The results presented
in this paper show the effectiveness of the proposed method.
We can represent the SFCL by impedance, which depends on
current, or by a resistance, which varies during time. The SFCL
used in simulation is represented by a resistance which varies
with time as follows:
(1)
where represents the maximum resistance that the SFCL
can introduce in the lines of the power system. Also, is the
time of transition from the superconducting state to the normal
state, which is assumed, in this study, to be 1 ms [16].
III. DESCRIPTION OF THE PROPOSED METHOD
For an EPG with more than one generator, a necessary con-
dition for satisfactory system operation is that all synchronous
machines remain in synchronism when a severe transient dis-
turbance appears (loss of transmission line, important increase
of load, three-phase short-circuit). This aspect of stability is in-
fluenced by the dynamics of generators rotor angle and power-
angle relationships.
When a fault occurs in the system, the operating point of gen-
erators suddenly changes. Owing to inertia, the angular separa-
tion between the rotor position of each generators is modified
until the fault is cleared. At the beginning of the perturbation,
this angular separation increases with a magnitude that depends
on the time necessary to clear the fault. If the fault clearing time
is small, the power system is perturbed but a stable point is found
again after a few seconds. Otherwise, the synchronism of the
power system is lost.
Fig. 1 presents the evolution of the angular separation of a
simple power system (2 generators and 1 load) when a three-
phase short-circuit occurs at 1 sec near one of the generators.
In the presented figure, the angular separation represents the
difference between the angular position of the rotors of the two
generators. If the fault is cleared at 1,2 sec, the power system
remains stable and the angle oscillates between two extreme
values. On the other hand, if the fault is cleared at 1,3 sec, the
kinetic energy gained during the time of fault has not been yet
completely expended to the system. The angle continues to
increase after the fault cleared. The power system is not capable
to return to a stable position, leading to loss of synchronism.
Sung et al. in [15] have demonstrated theoretically that the
presence of a resistive SFCL in a single-machine infinite-bus
(SMIB) increases the fault clearing time. In terms of angular
variation, the presence of an SFCL reduces the two boundary
markers of the angular separation of the rotors of the generators
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
DIDIER et al.: NOVEL APPROACH TO DETERMINE THE OPTIMAL LOCATION OF SFCL IN ELECTRIC POWER GRID 3
Fig. 1. Evolution of the angular separation of the rotors with a fault cleared
at 1,2 s (stable case) and a fault cleared at 1,3 s (unstable case).
Fig. 2. IEEE benchmarked four-machine two-area test system.
when a fault occurs. Consequently, the transient stability of the
system is increased.
Starting from this observation, we propose a method to select
the optimal location of the SFCL in EPG based on the study of
the angular separation of the rotors of synchronous genera-
tors in case of fault. Many studies have dealt with the increase
of transient stability in power systems thanks to SFCL but most
of them have limited the study to a simple power system such
as generator, transmission line, and infinite bus. Now, the re-
maining open questions are the selection of optimal location of
the SFCL in a power system with more than 2 generators. We
present a method which is not limited to a simple system like
an SMIB but extended to the IEEE benchmarked four-machine
two-area test system presented in Fig. 2. This power system is
composed of four generators, two loads and a long transmission
line (220 km), that is a advantage to study the optimal location
of an SFCL in a power system in comparison with SMIB.
The details on this system, including the systems parameters,
are given in [19]. All generators (G1 to G4) are equipped with
power system stabilizers (PSSs).
To determine the optimal location of the SFCL, the method
focuses on the angular separation between the rotors of all gen-
erators. If the rotor angle of generator G4 is taken as reference,
the angular separation of the rotors of generators G1 to G3 (rel-
ative to G4) can be noted as . The variation of each
( to 3) is depending on the fault severity introduced in
the EPG. If we consider that subscripts , , and represent,
respectively, the position of SFCL in the system, the position of
the fault in the system and the number of fault position studied
(which will be identical to in this study), we can determine the
optimal location of the SFCL in EPG by the analysis of a tran-
sient stability index given in (3). To obtain the value
of index with respect to the resistive value of the SFCL,
noted , we determine in advance an index (2) by
considering the sum of the maximum deviations of ( to
3) given by when a fault appears at position in the system
(the maximum value of is equal to ):
(2)
(3)
Consequently, the value of indexes and will
give us an accurate information to find the optimal location of
the SFCL if a fault occurs in the system. Indeed, these indices
reflect the contribution of the SFCL in the system in terms of
stability when a fault occurs.
IV. SIMULATIONS RESULTS
To evaluate the effectiveness of the proposed method, ten lo-
cations ( to in the middle of each line) are considered in
Fig. 2.
For a given position of the SFCL ( to 10), a 100-ms
three-phase short-circuit is applied at each location (
to 10). For each case ( and ), the maximum
deviation ( to 3) of generators are calculated to obtain
. In a second time, index and finally, index are
evaluated with respect to the corresponding value of the SFCL
resistance used in simulation. When the SFCL will be positioned
at each location , the study of indexes and will
give us the best location of the SFCL in the system in case a
three-phase fault can appear at any position in the system.
The time simulation required until the system is restored to its
original steady-state operation point after applying the fault is
considered to be equal to 20 s. Before calculating values of index
, it is necessary to compute the load flow of the presented
power system. The results show that the power generated by
generators G1 and G2 is mostly consumed by Load 1. In area 2,
the power generated by generators G3 and G4 is consumed by
Load 2 but it is not sufficient. The rest of the power required by
Load 2, i.e., 413 MW, is transferred from area 1 to area 2 by the
220-km transmission line.
A. Sensitivity Analysis for Optimal Location of SFCL
To select the optimal location of the SFCL, the corre-
sponding value of in (2) is computed for each location
. This gives the global separation angle of the rotors of the
synchronous generators. Finally, the value of (3) is cal-
culated. According to the variation of , the reduction of
index in (2) means that the SFCL increases the system
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
4 IEEE TRANSACTIONS ON POWER SYSTEMS
TABLE I
VALUES OF INDEX DURING THE FAULT AT EACH LOCATION (DEG)
TABLE II
VALUES OF INDEX AT EACH LOCATION
stability in case of fault. Therefore, if the value of (3) is
greater for a given resistive value, the corresponding location
becomes more optimal. The determination of optimal resistive
value of SFCL is presented in the next sub-section.
Before performing simulations with SFCL, it is necessary to
obtain the value of index when a three-phase short-cir-
cuit is introduced at each location when no SFCL is used.
The result of this test gives a SMD of 1282 (the subscript
is not indicated on this index SMD because no SFCL is used).
When the proposed method is performed on the power system
presented in Fig. 2, the results of indexes and are
given, respectively, in Tables I and II with a resistive SFCL of
10 , 20 and 50 [16].
As we can see, the localization of SFCL in the EPG when a
fault occurs gives different results concerning index and
index . When index presents a negative value (for
example, location with equal to 20 ), the SFCL con-
tributes to increase the global rotor angles variations of genera-
tors. Consequently, the selected location weakens the transient
stability of the power system. However, in most cases studied,
the value of index is positive which means that the pres-
ence of SFCL increases the transient stability of EPG in case of
three-phase fault by reducing the variation of separation angle
between the rotors. The optimal location of SFCL is obtained
when index is maximal for a given resistive value of
SFCL. In this case, if is equal to 10 , the optimal loca-
tion of the limiter, to increase the EPG transient stability, is .
If we consider a resistive value of 20 and 50 , the optimal
location determined by the proposed method is .
We give in Fig. 3 the variation of (rotor angle separation
between generators G1 and G4) versus time when a three-phase
short-circuit occurs at . Simulations are made without the
SFCL, with an SFCL of 10 and with an SFCL of 50 in-
troduced at location .
In addition, results given in Tables I and II show that an SFCL
cannot be placed between two areas. The presence of SFCL at
location and , i.e., at the beginning or in the middle of a
long transmission line, increases the instability of the system in
case of fault.
Fig. 3. Variation of when the SFCL (with different value of ) is
connected at when a fault appears at .
We can note that the presence of the SFCL in EPG reduces
the variation of and consequently, the maximum deviation
when a fault occurs in the power system. If a fault occurs in
area 2 (for example at location ), the evolution of when
the SFCL is placed at location gives the same results but
the reduction of its magnitude is influenced by the length of the
transmission line (265 km).
B. Sensitivity Analysis for Optimal Resistive Value of SFCL
The proposed method shows that the optimal location of the
SFCL depends on its resistive value . We, respectively,
present at Figs. 4 and 5 the variation of index in function
of for the two optimal locations and determined
by the presented method.
If the SFCL is placed at location , the best value of
is about 10 as we can see in Fig. 4. In the case of location
, it is for a resistance value about 50 that the index
is the best. This study shows that the SFCL resistance is
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
DIDIER et al.: NOVEL APPROACH TO DETERMINE THE OPTIMAL LOCATION OF SFCL IN ELECTRIC POWER GRID 5
Fig. 4. Variation of in function of when the SFCL is placed at
location .
Fig. 5. Variation of in function of when the SFCL is placed at
location .
an important parameter in the case of EPG stability study. Other
considerations have to be taken into account to choose the posi-
tion and the resistive value of the SFCL. In fact, a SFCL with a
resistance of 10 is easier to manufacture than an SFCL with
a resistance of 50 . However, the easiness of implementation
in terms of geographical point in the EPG must be taken into
account. A third point to be considered could be the damping
improvement of generators speed (or system frequency) intro-
duced by the SFCL.
Table III gives the ratio of the rotor speed deviation of
the th generator when the SFCL (with, respectively, a resistance
of 10 and 50 ) is placed at location and when a 100-ms
three-phase short-circuit is applied at each location :
(4)
If the SFCL is placed at location , we can see in Table III
that its influence on is more significant if the fault occurs
at locations , , or . However, we can note that the pres-
ence of SFCL at this location increases the ratio if the
fault occurs at or . In the case where the SFCL is placed
at location , it is when a fault occurs at , , , , , or
that the damping performance is more effective. The posi-
tion is better than if we consider the number of locations
influenced, but if we take a look on the damping performance,
we can see that the effectiveness of the SFCL placed at is the
most important (we obtain the better reduction of ratio ).
We give in Fig. 6 the rotor speed response of generators G1,
G2, G3, and G4 when a fault occurs at location . Three cases
are considered:
— no SFCL is used;
— an SFCL of 10 is placed at location ;
— an SFCL of 50 is placed at location .
As we can see, the SFCL placed at location improves the
damping performance of the generators G3 and G4. Concerning
generators G1 and G2, it is when the SFCL of 10 is placed at
location that the rotor speed oscillations are the smallest. In
a general way, the results show that the position of the SFCL in
the power system reduces the low frequency oscillation of the
generators speed.
However, the simulation results and Table III show us that
the damping performance is a function of the location and the
resistance value of the SFCL.
To determine the better position between locations and ,
we could calculate the mean of the ratio by taking into
account all locations and all generators. If the SFCL is placed at
location , we obtain a reduction of the low frequency oscilla-
tion of the rotors speeds equal to 9.17%. If the SFCL is placed
at location , the reduction of the low frequency oscillation of
the rotors speeds is equal to 19.18%. From the above results,
the optimal location selected by the proposed method is val-
idated to be effective for application of the resistive SFCL to the
IEEE Benchmark four-machine two-area test system.
Concerning the coordination of the protective devices present
in the power system, You et al. in [5] have shown that the re-
covery time of the SFCL, which depends on its resistive value,
can modify the operation of the recloser and the over current
relay (OCR) of the faulty transmission line. Two solutions can
be considered. The first is to select the resistance of the SFCL
to be within the limited range of the protection devices to keep
the protection coordination. The second is to modify the setting
parameters such as the time dial (TD) and the pickup current of
the protective devices.
In our case, the modification of the resistance value of the
SFCL is difficult because it has been determined to obtain the
best reduction of the rotor angle deviations of generators and
an increase of the system damping performance in case of fault.
Consequently, in our case, the solution is to modify the setting
parameters to ensure the protection coordination of the power
system. Recent works have shown that a good coordination of
the protective devices with SFCL can be obtained by the modi-
fication of the TD [21] or the pick up current [22] of the OCR,
these two last parameters being a function of the resistance of
the SFCL used in the power system.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
6 IEEE TRANSACTIONS ON POWER SYSTEMS
TABLE III
RATIO OF THE ROTOR SPEED DEVIATION WITH THE SFCL PLACED AT LOCATIONS AND (%)
Fig. 6. Rotor speed response of the four generators with no SFCL, with an
SFCL at (10 ), and with an SFCL at (50 ) when a fault occurs at .
V. APPLICATION OF THE PROPOSED METHOD
TO A LARGE-SCALE POWER SYSTEM
If we consider a large-scale power system, it is not possible
to use only one SFCL to improve the stability of the system in
case of fault. The idea is to split the power system into smaller
areas depending on the coherency of the areas when subjected
to disturbances. In this case, we will have a number of sub-sys-
tems equal to the number of areas. To improve the stability of the
power system, an SFCL has to be associated to each sub-system.
The optimal location of each SFCL can be determined thanks to
the proposed method by considering a three-phase fault at dif-
ferent locations in the considered area. Consequently, the pro-
posed method uses only a reduced number of generators to eval-
uate the optimal location and the optimal resistance of SFCLs.
For example, if we consider the IEEE 39-bus test system (10
generators, 39 bus, and 34 lines) [20], we can divide it into three
Fig. 7. IEEE 39-bus test system split into three areas (or three sub-systems).
areas as shown in Fig. 7. For each area (or sub-system), the pro-
posed method can be applied to determine the optimal location
of the associated SFCL.
VI. CONCLUSIONS
This paper presents a novel approach to select the optimal
location of a resistive SFCL in an EPG. The proposed method is
based on the study of the angular separation between the rotors
of the generators present in the power system. This approach
allows to find the optimal location of SFCL when the power
system studied presents several generators.
We have shown that the optimal location of SFCL selected by
the proposed method, in accordance with the own resistive value
, increases the transient stability of the power system
studied by reducing the angular deviation between the rotors of
the synchronous machines in case of three-phase fault. In addi-
tion, the method takes into account the study of the frequency
oscillations of the generator speed in order to select the optimal
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
DIDIER et al.: NOVEL APPROACH TO DETERMINE THE OPTIMAL LOCATION OF SFCL IN ELECTRIC POWER GRID 7
resistance of SFCL. The main advantage is that the optimal loca-
tion of the SFCL determined by the analysis of indexes
and takes into account that the three-phase short-circuit
can appear anywhere in the EPG.
REFERENCES
[1] W. D. Stevenson, Elements of Power System Analysis, 4th ed. New
York: McGraw-Hill, 1968.
[2] M. Sjodtrom, R. Cherkaoui, and B. Dutoit, “Enhancement of power
system transient stability using superconducting fault current limiters,”
IEEE Trans. Appl. Supercond., vol. 9, no. 2, pp. 1328–1330, Jun. 1999.
[3] L. Ye et al., “Application studies of superconducting fault current lim-
iters in electric power systems,” IEEE Trans. Appl. Supercond., vol.
17, no. 1, pp. 900–903, Mar. 2002.
[4] L. Ye and A. Campbell, “Behavior investigations of superconducting
fault current limiters in power systems,” IEEE Trans. Appl. Supercond.,
vol. 16, no. 2, pp. 662–665, Jun. 2006.
[5] L. You et al., “Study on protection coordination between protective
devices in a power distribution system with an SFCL,” IEEE Trans.
Appl. Supercond., vol. 20, no. 3, pp. 1168–1171, Jun. 2010.
[6] L. Ye and K. P. Juengst, “Modeling and simulation of HTc resistive
superconducting fault current limiters,” IEEE Trans. Appl. Supercond.,
vol. 14, no. 2, pp. 839–842, Jun. 2004.
[7] Y. Cai et al., “Study on three-phase superconducting fault current lim-
iter,” IEEE Trans. Appl. Supercond., vol. 20, no. 3, pp. 1127–1130, Jun.
2010.
[8] J. Shi et al., “The application of active superconducting DC fault cur-
rent limiter in hybrid AC/DC power supply system,” IEEE Trans. Appl.
Supercond., vol. 18, no. 2, pp. 672–675, Jun. 2008.
[9] D. Hui et al., “Development and test of 10.5 kV/1.5 k1 HTS fault
current limiter,” IEEE Trans. Appl. Supercond., vol. 16, no. 2, pp.
687–6690, Jun. 2006.
[10] M. Heydari et al., “Optimization scheme in combinatorial UPQC and
SFCL using normalized simulated annealing,” IEEE Trans. Power
Del., vol. 26, no. 3, pp. 1489–1498, Jul. 2011.
[11] L. Ye et al., “ sample tests for possible applications of super-
conducting fault current limiters,” IEEE Trans. Appl. Supercond., vol.
17, no. 2, pp. 2826–2829, Jun. 2007.
[12] I. Muta, T. Doshita, T. Nakamura, T. Egi, and T. Hoshino, “Influences
of Superconducting Fault Current Limiter (SFCL) on superconducting
generator in one-machine double-line system,” IEEE Trans. Appl. Su-
percond., vol. 13, no. 2, pp. 2206–2209, Jun. 2003.
[13] L. Ye et al., “System studies of the superconducting fault current limiter
in electrical distribution grids,” IEEE Trans. Appl. Supercond., vol. 17,
no. 2, pp. 2339–2342, Jun. 2007.
[14] L. Ye and L. Z. Lin, “Study of superconducting fault current limiters
for system integration of wind farms,” IEEE Trans. Appl. Supercond.,
vol. 20, no. 3, pp. 1233–1237, Jun. 2010.
[15] B. Sung et al., “Study on a series resistive SFCL to improve power tran-
sient stability: Modeling, simulation, experimental verification,” IEEE
Trans. Ind. Electron., vol. 56, no. 7, pp. 2412–2419, Jun. 2009.
[16] B. Sung et al., “Study optimal location of a resistive SFCL applied to
an electric power grid,” IEEE Trans. Appl. Supercond., vol. 19, no. 3,
pp. 2048–202052, Jun. 2009.
[17] B. Sung et al., “Optimal parameter selection of resistive SFCL applied
to a power system using eigenvalue analysis,” IEEE Trans. Appl. Su-
percond., vol. 20, no. 3, pp. 1147–1150, Jun. 2010.
[18] M. Elsamahy et al., “Impact of superconducting fault current limiters
on the coordination between generator distance phase backup protec-
tion and generator capability curves,” IEEE Trans. Power Del., vol. 26,
no. 3, pp. 1854–1863, Jul. 2011.
[19] P. Kundur, Power System Stability and Control. New York: Mc-
Graw-Hill, 1993, EPRI Editor.
[20] K. R. Padiyar, Power System Dynamics—Stability and Control, 2nd
ed. Hyderabad, Andhra Pradesh, India: BS Publications, 2002.
[21] J. S. Kim et al., “Study on protection coordination for application of
superconducting fault current limiter,” IEEE Trans. Appl. Supercond.,
vol. 21, no. 3, pp. 2174–2178, Jun. 2011.
[22] J. S. Kim et al., “Study on application method of superconducting fault
current limiter for protection coordination of protective devices in a
power distribution system,” IEEE Trans. Appl. Supercond., vol. 22, no.
3, Jun. 2012, 5601504.
G. Didier was born in Saint-Dié des Vosges, France, in 1978. He received the
degree in electrical engineering and the Ph.D. degree from the Université de
Lorraine, Nancy, France, in 2004.
In 2004, he joined the Groupe de Recherche en Electrotechnique et Electron-
ique de Nancy as an Assistant Professor. Until 2009, he has working on the diag-
nosis and modeling of induction motor under faults. Actually, his main research
interest concerns superconducting fault current limiters (SFCLs) and their appli-
cations in enhancing the power system performance and power system stability.
Jean Lévêque was born in Angers, France, in 1963. In 1993, he received
the Ph.D. degree in electrical engineering from the University of Grenoble,
Grenoble, France.
He joined the laboratory GREEN in the University de Lorraine, Nancy,
France, in 1993. His research interests include two main topics, the application
of the superconductor’s material in electrical engineering, especially super-
conducting motor, fault current limiter, and electrical characterization, and
modelization of superconducting material.
Abderrezak Rezzoug received the electrical engineer degree from ENSEM
INPL, Nancy, France, in 1972, and the Dr. Ing. diploma and the Ph.D. degree
from INPL, in 1979 and 1987, respectively.
After working at the INPL as an Assistant Professor until 1991, he is
currently a Professor of Electrical Engineering at the University de Lorraine,
Nancy, France. As a member of the Groupe de Recherche en Electrotechnique
et Electronique de Nancy, his main subjects of research concern supercon-
ducting applications to electrical devices, and the control and diagnosis of
electrical machines.

More Related Content

What's hot

What is Distributed Generation
What is Distributed GenerationWhat is Distributed Generation
What is Distributed GenerationAjay Singh
 
Impact of distributed generations on power system protection
Impact of distributed generations  on power system protectionImpact of distributed generations  on power system protection
Impact of distributed generations on power system protectionAdeen Syed
 
seminar report on optimal placement and optimal sizing of DG
seminar report on optimal placement and optimal sizing of DGseminar report on optimal placement and optimal sizing of DG
seminar report on optimal placement and optimal sizing of DGkhemraj298
 
Webinar - Distributed and Renewable Power Generation
Webinar - Distributed and Renewable Power GenerationWebinar - Distributed and Renewable Power Generation
Webinar - Distributed and Renewable Power GenerationWPICPE
 
Impacts of Distributed Generation on Power Quality
Impacts of Distributed Generation on Power QualityImpacts of Distributed Generation on Power Quality
Impacts of Distributed Generation on Power QualityParth Patel
 
Optimal Placement of Distributed Generation on Radial Distribution System for...
Optimal Placement of Distributed Generation on Radial Distribution System for...Optimal Placement of Distributed Generation on Radial Distribution System for...
Optimal Placement of Distributed Generation on Radial Distribution System for...IJMER
 
Distributed Generation By Roland Desouza
Distributed Generation By Roland DesouzaDistributed Generation By Roland Desouza
Distributed Generation By Roland DesouzaIEEEP Karachi
 
Distributed Generation Operation for Distribution System Volt/Var Control
Distributed Generation Operation for Distribution System Volt/Var ControlDistributed Generation Operation for Distribution System Volt/Var Control
Distributed Generation Operation for Distribution System Volt/Var ControlNovalio Daratha Asteria
 
Grid integration issues and solutions
Grid integration issues and solutionsGrid integration issues and solutions
Grid integration issues and solutionsSwathi Venugopal
 
Impact_of_distributed_generation_on_dist (1).pdf
Impact_of_distributed_generation_on_dist (1).pdfImpact_of_distributed_generation_on_dist (1).pdf
Impact_of_distributed_generation_on_dist (1).pdfAashishChoudhary23
 
Hybrid distributed generation
Hybrid distributed generationHybrid distributed generation
Hybrid distributed generationNIT MEGHALAYA
 
Power Electronic Interface
Power Electronic InterfacePower Electronic Interface
Power Electronic Interfaceijtsrd
 
Flexibility of Power System (Sources of flexibility & flexibility markets)
Flexibility of Power System (Sources of flexibility & flexibility markets)Flexibility of Power System (Sources of flexibility & flexibility markets)
Flexibility of Power System (Sources of flexibility & flexibility markets)Bilal Amjad
 
PV solar system with battery storage - design
PV solar system with battery storage - designPV solar system with battery storage - design
PV solar system with battery storage - designJaroslaw Iskierski
 
Challenges and Benefits of Integrating the Renewable Energy Technologies into...
Challenges and Benefits of Integrating the Renewable Energy Technologies into...Challenges and Benefits of Integrating the Renewable Energy Technologies into...
Challenges and Benefits of Integrating the Renewable Energy Technologies into...Power System Operation
 
Integration of Renewable Energy Sources
Integration of Renewable Energy SourcesIntegration of Renewable Energy Sources
Integration of Renewable Energy SourcesSandeep Kaushal
 
Dist.gen 1
Dist.gen 1Dist.gen 1
Dist.gen 1sanjivkj
 

What's hot (20)

What is Distributed Generation
What is Distributed GenerationWhat is Distributed Generation
What is Distributed Generation
 
Impact of distributed generations on power system protection
Impact of distributed generations  on power system protectionImpact of distributed generations  on power system protection
Impact of distributed generations on power system protection
 
seminar report on optimal placement and optimal sizing of DG
seminar report on optimal placement and optimal sizing of DGseminar report on optimal placement and optimal sizing of DG
seminar report on optimal placement and optimal sizing of DG
 
Webinar - Distributed and Renewable Power Generation
Webinar - Distributed and Renewable Power GenerationWebinar - Distributed and Renewable Power Generation
Webinar - Distributed and Renewable Power Generation
 
Impacts of Distributed Generation on Power Quality
Impacts of Distributed Generation on Power QualityImpacts of Distributed Generation on Power Quality
Impacts of Distributed Generation on Power Quality
 
Distributed Generation
Distributed Generation  Distributed Generation
Distributed Generation
 
Optimal Placement of Distributed Generation on Radial Distribution System for...
Optimal Placement of Distributed Generation on Radial Distribution System for...Optimal Placement of Distributed Generation on Radial Distribution System for...
Optimal Placement of Distributed Generation on Radial Distribution System for...
 
Distributed Generation By Roland Desouza
Distributed Generation By Roland DesouzaDistributed Generation By Roland Desouza
Distributed Generation By Roland Desouza
 
Impacts of Photovoltaic Distributed Generation Location and Size on Distribut...
Impacts of Photovoltaic Distributed Generation Location and Size on Distribut...Impacts of Photovoltaic Distributed Generation Location and Size on Distribut...
Impacts of Photovoltaic Distributed Generation Location and Size on Distribut...
 
Distributed Generation Operation for Distribution System Volt/Var Control
Distributed Generation Operation for Distribution System Volt/Var ControlDistributed Generation Operation for Distribution System Volt/Var Control
Distributed Generation Operation for Distribution System Volt/Var Control
 
Grid integration issues and solutions
Grid integration issues and solutionsGrid integration issues and solutions
Grid integration issues and solutions
 
Impact_of_distributed_generation_on_dist (1).pdf
Impact_of_distributed_generation_on_dist (1).pdfImpact_of_distributed_generation_on_dist (1).pdf
Impact_of_distributed_generation_on_dist (1).pdf
 
Hybrid distributed generation
Hybrid distributed generationHybrid distributed generation
Hybrid distributed generation
 
Power Electronic Interface
Power Electronic InterfacePower Electronic Interface
Power Electronic Interface
 
Flexibility of Power System (Sources of flexibility & flexibility markets)
Flexibility of Power System (Sources of flexibility & flexibility markets)Flexibility of Power System (Sources of flexibility & flexibility markets)
Flexibility of Power System (Sources of flexibility & flexibility markets)
 
Distributed Generation
Distributed Generation Distributed Generation
Distributed Generation
 
PV solar system with battery storage - design
PV solar system with battery storage - designPV solar system with battery storage - design
PV solar system with battery storage - design
 
Challenges and Benefits of Integrating the Renewable Energy Technologies into...
Challenges and Benefits of Integrating the Renewable Energy Technologies into...Challenges and Benefits of Integrating the Renewable Energy Technologies into...
Challenges and Benefits of Integrating the Renewable Energy Technologies into...
 
Integration of Renewable Energy Sources
Integration of Renewable Energy SourcesIntegration of Renewable Energy Sources
Integration of Renewable Energy Sources
 
Dist.gen 1
Dist.gen 1Dist.gen 1
Dist.gen 1
 

Similar to 98X- didier2013.pdf

iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant i...
iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant i...iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant i...
iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant i...Iaetsd Iaetsd
 
Surge Protection Devices Paper (SPD) SM54
Surge Protection Devices Paper (SPD) SM54Surge Protection Devices Paper (SPD) SM54
Surge Protection Devices Paper (SPD) SM54Subhash Mahla
 
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...AEIJjournal2
 
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...AEIJjournal2
 
Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...IOSR Journals
 
A Fault Current Limiter Circuit to Improve Transient Stability in Power System
A Fault Current Limiter Circuit to Improve Transient Stability in Power SystemA Fault Current Limiter Circuit to Improve Transient Stability in Power System
A Fault Current Limiter Circuit to Improve Transient Stability in Power SystemIAES-IJPEDS
 
12 16134 paper 064 ijeecs(edit)
12 16134 paper 064 ijeecs(edit)12 16134 paper 064 ijeecs(edit)
12 16134 paper 064 ijeecs(edit)IAESIJEECS
 
Solid State Fault Current Limiter for Improvement of Smart Grid Performance
Solid State Fault Current Limiter for Improvement of Smart Grid PerformanceSolid State Fault Current Limiter for Improvement of Smart Grid Performance
Solid State Fault Current Limiter for Improvement of Smart Grid PerformanceIRJET Journal
 
IRJET- Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET-  	  Design a Fuzzy Distance Relay Including STATCOM EffectsIRJET-  	  Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET- Design a Fuzzy Distance Relay Including STATCOM EffectsIRJET Journal
 
A Review on Impact of Solar Panels on Power Quality of Distribution Networks ...
A Review on Impact of Solar Panels on Power Quality of Distribution Networks ...A Review on Impact of Solar Panels on Power Quality of Distribution Networks ...
A Review on Impact of Solar Panels on Power Quality of Distribution Networks ...IRJET Journal
 
Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...IAEME Publication
 
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...eeiej_journal
 
IRJET- Review on Various Topologis used for Decoupling of Fluctuating Power i...
IRJET- Review on Various Topologis used for Decoupling of Fluctuating Power i...IRJET- Review on Various Topologis used for Decoupling of Fluctuating Power i...
IRJET- Review on Various Topologis used for Decoupling of Fluctuating Power i...IRJET Journal
 
Single core configurations of saturated core fault current limiter performanc...
Single core configurations of saturated core fault current limiter performanc...Single core configurations of saturated core fault current limiter performanc...
Single core configurations of saturated core fault current limiter performanc...IJECEIAES
 
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET Journal
 

Similar to 98X- didier2013.pdf (20)

iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant i...
iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant i...iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant i...
iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant i...
 
Surge Protection Devices Paper (SPD) SM54
Surge Protection Devices Paper (SPD) SM54Surge Protection Devices Paper (SPD) SM54
Surge Protection Devices Paper (SPD) SM54
 
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
 
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
TRANSIENT STABILITY IMPROVEMENT OF POWER SYSTEMS BY OPTIMAL SIZING AND ALLOCA...
 
Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...
 
A Fault Current Limiter Circuit to Improve Transient Stability in Power System
A Fault Current Limiter Circuit to Improve Transient Stability in Power SystemA Fault Current Limiter Circuit to Improve Transient Stability in Power System
A Fault Current Limiter Circuit to Improve Transient Stability in Power System
 
12 16134 paper 064 ijeecs(edit)
12 16134 paper 064 ijeecs(edit)12 16134 paper 064 ijeecs(edit)
12 16134 paper 064 ijeecs(edit)
 
Solid State Fault Current Limiter for Improvement of Smart Grid Performance
Solid State Fault Current Limiter for Improvement of Smart Grid PerformanceSolid State Fault Current Limiter for Improvement of Smart Grid Performance
Solid State Fault Current Limiter for Improvement of Smart Grid Performance
 
fault
faultfault
fault
 
Analysis and Design of Single Phase High Efficiency Transformer less PV Inver...
Analysis and Design of Single Phase High Efficiency Transformer less PV Inver...Analysis and Design of Single Phase High Efficiency Transformer less PV Inver...
Analysis and Design of Single Phase High Efficiency Transformer less PV Inver...
 
IRJET- Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET-  	  Design a Fuzzy Distance Relay Including STATCOM EffectsIRJET-  	  Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET- Design a Fuzzy Distance Relay Including STATCOM Effects
 
A Review on Impact of Solar Panels on Power Quality of Distribution Networks ...
A Review on Impact of Solar Panels on Power Quality of Distribution Networks ...A Review on Impact of Solar Panels on Power Quality of Distribution Networks ...
A Review on Impact of Solar Panels on Power Quality of Distribution Networks ...
 
Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...
 
Ppt super
Ppt superPpt super
Ppt super
 
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...
 
R01043105113
R01043105113R01043105113
R01043105113
 
IRJET- Review on Various Topologis used for Decoupling of Fluctuating Power i...
IRJET- Review on Various Topologis used for Decoupling of Fluctuating Power i...IRJET- Review on Various Topologis used for Decoupling of Fluctuating Power i...
IRJET- Review on Various Topologis used for Decoupling of Fluctuating Power i...
 
Single core configurations of saturated core fault current limiter performanc...
Single core configurations of saturated core fault current limiter performanc...Single core configurations of saturated core fault current limiter performanc...
Single core configurations of saturated core fault current limiter performanc...
 
Comparative Application of Load Tap-Changing Transformer (LTCT) and Shunt Cap...
Comparative Application of Load Tap-Changing Transformer (LTCT) and Shunt Cap...Comparative Application of Load Tap-Changing Transformer (LTCT) and Shunt Cap...
Comparative Application of Load Tap-Changing Transformer (LTCT) and Shunt Cap...
 
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
 

Recently uploaded

Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfme23b1001
 
Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvLewisJB
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHC Sai Kiran
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEroselinkalist12
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfROCENODodongVILLACER
 
EduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AIEduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AIkoyaldeepu123
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfAsst.prof M.Gokilavani
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...Chandu841456
 

Recently uploaded (20)

Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdf
 
Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvv
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECH
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdf
 
EduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AIEduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AI
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...
 

98X- didier2013.pdf

  • 1. This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination. IEEE TRANSACTIONS ON POWER SYSTEMS 1 A Novel Approach to Determine the Optimal Location of SFCL in Electric Power Grid to Improve Power System Stability G. Didier, Jean Lévêque, and Abderrezak Rezzoug Abstract—This paper presents a novel approach to determine the optimal location of a resistive superconducting fault current limiter (SFCL) for enhancing the transient stability of an electric power grid (EPG). To select the optimal location of the SFCL, the sensitivity analysis of the angular separation of the rotors of syn- chronous machines present in the power system is introduced. The optimal location of the SFCL in EPG is coordinated with the corre- sponding optimal resistive value to improve transient stability and low-frequency oscillation damping performance of the system. It is shown that the SFCL can have different impacts (positive and neg- ative) in function of its location in the EPG when a fault occurs. To evaluate the effectiveness of the proposed method, the IEEE benchmarked four-machine two-area test system is used to carry out several case studies. The results show that the optimal location of SFCL combined with its optimal resistive value reduces the an- gular separation of the rotors that improves effectively the system stability during a fault. Index Terms—Damping performance, electric power grid, op- timal location, superconducting fault current limiter, transient sta- bility. I. INTRODUCTION WITH the increasing of system capacity, fault occurrence probability becomes higher, that can induce severe damages in electrical power system [1]. For example, the high value of the short-circuit current can damage the insulation strength of electrical devices, synchronous generators, pro- tective relays, lines transmission, and loads. In addition, the electrical power needed by the system when a fault occurs is modified and induced instable state of the power generators [2]. Recently, the development of superconducting fault current limiters (SFCL) offers one of the most attractive alternatives to solve the fault current problems [3]–[5]. Thanks to their fast transition from a low to a high impedance, superconducting de- vices can limit, in a very short time, the value of any fault cur- rent. What is attractive is that the transition is due to an in- trinsic behavior of the material itself [6]–[9]. It was shown that Manuscript received November 18, 2011; revised December 03, 2011, April 12, 2012, and July 25, 2012; accepted October 06, 2012. Paper no. TPWRS- 01120-2011. The authors are with the Groupe de Recherche en Electrotechnique et Elec- tronique de Nancy (GREEN), EA4366, Faculté des Sciences et Technologies- Université de Lorraine, 54506 Vandoeuvre lès Nancy, France (e-mail: gaetan.di- dier@green.uhp-nancy.fr). Color versions of one or more of the figures in this paper are available online at http://ieeexplore.ieee.org. Digital Object Identifier 10.1109/TPWRS.2012.2224386 the presence of the SFCL in a power system can increase the system stability and distributed energy quality [10]–[15]. When an SFCL is introduced in an electric power grid (EPG), three important factors must be considered: 1) optimal location of the SFCL in the EPG [16]; 2) optimal resistive value of the SFCL [17]; 3) protection-coordination problem with other existing de- vices (circuit breaker, OCR, etc.) [5], [18], [21], [22]. The presented paper focuses on factors 1 and 2. Nowadays, the optimal location of SFCL to improve the transient stability is studied for a simple power system like single machine infinite bus (SMIB) [2], [3], [15]. So far, the remaining open question is the selection of optimal location of the SFCL in a large-scale power system to improve its transient stability. In this paper we consider a multi-generator system and we use their rotor angular difference to define a sensitivity index which leads to finding the best location of the SFCL in the grid. This sensitivity index is calculated with respect to the resistive value of the used SFCL. The effectiveness of the proposed method is evaluated on the IEEE benchmark four-machine two-area test system. The toolbox SimPowerSystems of MATLAB/SIMULINK software is used to carry out simulations studies. The simulation results show the effectiveness of the proposed method. In fact, the optimal location determined for the SFCL improves the transient stability of the power system and de- creases the low frequency oscillation of the generators speed when a severe damage is introduced (three-phase fault). The ad- vantage of the proposed method is that the selected location of the SFCL takes into account the fact that the fault can occur any- where in the studied grid. II. SFCL MODEL APPLIED TO POWER SYSTEM The operation of an SFCL is based on the natural transition of the superconducting state to normal state by exceeding the critical current of the material. This transition from the su- perconducting to the normal state must be done in a very short time, generally, to limit the first current peak to a threshold value not exceeding three to five times the rated current, below the short-circuit current without limitation. These limiters use the variation of resistivity during the tran- sition. Indeed, the resistivity of these materials is very high to normal state, much more than a classical conductor, both for NbTi and for the YBaCuO 77 K. The SFCL is placed in series with a circuit breaker. During the fault, the current increases up to reach the threshold of tran- sition from superconducting wire. This transition from the su- 0885-8950/$31.00 © 2012 IEEE
  • 2. This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination. 2 IEEE TRANSACTIONS ON POWER SYSTEMS perconducting element to normal state causes the development of resistance that limits or triggers the current limit. The time between threshold crossing and the limitation is small (a few micro-seconds). The circuit breaker isolates the line as soon as possible after the beginning of the limitation. These supercon- ducting fault current limiters use one of the fundamental prop- erties of superconductors. The qualifications of SFCL are: • Very low impedance during normal operation. The current limiter must be “invisible” in this mode. Some transients such as those caused during the switching of a transformer should not inadvertently cause a transition of the limiter. • High impedance system during short-circuit. The limiter must perform its function in the case of massive short circuit but also in the case of low short-circuit fault. • Very good dynamic. The system must transit in very quickly (within mil- lisecond) to effectively limit the value of the short circuit. There are several types of SFCL; the main ones include: • The resistive limiter. This is a coil of superconductive material, non-inductive by construction, mounted in series on the line. In case of fault, the winding initially at the superconducting state changes to the normal state. Its impedance appears in the line, which limits the fault current. This limiter can be applied in AC or DC systems. • The inductive limiter. It consists in its simplest form, two windings connected in parallel. This association is made so that the impedance of all is the lowest possible. In case of fault, one of the coils (made of superconducting material) returns to its normal state. The other winding made either copper or supercon- ducting material limit the current through the inductance. • The limiting transformer. It consists of a superconducting secondary short-circuit and primary winding of a conventional copper. In normal operation, the impedance of this transformer is mainly due to the coupling between the windings and may be very low. Under fault, the secondary winding quenches under the ef- fect of fault current and acts as a switch that opens the sec- ondary of the transformer. Therefore, we obtain the no load impedance of a transformer which is very important. As we said, the first function of an SFCL is to limit the fault current induced in the faulty line. In this case, the passage to its superconducting state to its normal state can only be achieved if the fault appears in the line where the limiter is placed. The probability that a fault appears at a specific location in the power system is very low. Consequently, if the fault appears at a dif- ferent location in the power system, the SFCL cannot be used for its first function because the current value through the SFCL will be not sufficient to ensure a transition of this last. The orig- inality of the presented work is that the SFCL is used if the fault appears anywhere in the system. In this case, the SFCL can be seen as a rapid switch that introduces a resistance in the power system. The presence of this additional resistance improves the power system stability in case of short-circuit and this, regard- less of the position of the fault. The SFCL is not used to limit the fault current but to improve the stability of the power system. If the fault appears in the line where the limiter is placed, the two functions of the SFCL are used (limitation of the fault cur- rent in the line and improvement of the power system stability). By cons, if a fault appears at a different location, the SFCL in- troduce its resistance in the power system to improve the tran- sient stability of generators. In this case, the passage to its su- perconducting state to its normal state will be accomplished by applying a magnetic field superior to its critical magnetic field after the detection of the fault in the EPG. The results presented in this paper show the effectiveness of the proposed method. We can represent the SFCL by impedance, which depends on current, or by a resistance, which varies during time. The SFCL used in simulation is represented by a resistance which varies with time as follows: (1) where represents the maximum resistance that the SFCL can introduce in the lines of the power system. Also, is the time of transition from the superconducting state to the normal state, which is assumed, in this study, to be 1 ms [16]. III. DESCRIPTION OF THE PROPOSED METHOD For an EPG with more than one generator, a necessary con- dition for satisfactory system operation is that all synchronous machines remain in synchronism when a severe transient dis- turbance appears (loss of transmission line, important increase of load, three-phase short-circuit). This aspect of stability is in- fluenced by the dynamics of generators rotor angle and power- angle relationships. When a fault occurs in the system, the operating point of gen- erators suddenly changes. Owing to inertia, the angular separa- tion between the rotor position of each generators is modified until the fault is cleared. At the beginning of the perturbation, this angular separation increases with a magnitude that depends on the time necessary to clear the fault. If the fault clearing time is small, the power system is perturbed but a stable point is found again after a few seconds. Otherwise, the synchronism of the power system is lost. Fig. 1 presents the evolution of the angular separation of a simple power system (2 generators and 1 load) when a three- phase short-circuit occurs at 1 sec near one of the generators. In the presented figure, the angular separation represents the difference between the angular position of the rotors of the two generators. If the fault is cleared at 1,2 sec, the power system remains stable and the angle oscillates between two extreme values. On the other hand, if the fault is cleared at 1,3 sec, the kinetic energy gained during the time of fault has not been yet completely expended to the system. The angle continues to increase after the fault cleared. The power system is not capable to return to a stable position, leading to loss of synchronism. Sung et al. in [15] have demonstrated theoretically that the presence of a resistive SFCL in a single-machine infinite-bus (SMIB) increases the fault clearing time. In terms of angular variation, the presence of an SFCL reduces the two boundary markers of the angular separation of the rotors of the generators
  • 3. This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination. DIDIER et al.: NOVEL APPROACH TO DETERMINE THE OPTIMAL LOCATION OF SFCL IN ELECTRIC POWER GRID 3 Fig. 1. Evolution of the angular separation of the rotors with a fault cleared at 1,2 s (stable case) and a fault cleared at 1,3 s (unstable case). Fig. 2. IEEE benchmarked four-machine two-area test system. when a fault occurs. Consequently, the transient stability of the system is increased. Starting from this observation, we propose a method to select the optimal location of the SFCL in EPG based on the study of the angular separation of the rotors of synchronous genera- tors in case of fault. Many studies have dealt with the increase of transient stability in power systems thanks to SFCL but most of them have limited the study to a simple power system such as generator, transmission line, and infinite bus. Now, the re- maining open questions are the selection of optimal location of the SFCL in a power system with more than 2 generators. We present a method which is not limited to a simple system like an SMIB but extended to the IEEE benchmarked four-machine two-area test system presented in Fig. 2. This power system is composed of four generators, two loads and a long transmission line (220 km), that is a advantage to study the optimal location of an SFCL in a power system in comparison with SMIB. The details on this system, including the systems parameters, are given in [19]. All generators (G1 to G4) are equipped with power system stabilizers (PSSs). To determine the optimal location of the SFCL, the method focuses on the angular separation between the rotors of all gen- erators. If the rotor angle of generator G4 is taken as reference, the angular separation of the rotors of generators G1 to G3 (rel- ative to G4) can be noted as . The variation of each ( to 3) is depending on the fault severity introduced in the EPG. If we consider that subscripts , , and represent, respectively, the position of SFCL in the system, the position of the fault in the system and the number of fault position studied (which will be identical to in this study), we can determine the optimal location of the SFCL in EPG by the analysis of a tran- sient stability index given in (3). To obtain the value of index with respect to the resistive value of the SFCL, noted , we determine in advance an index (2) by considering the sum of the maximum deviations of ( to 3) given by when a fault appears at position in the system (the maximum value of is equal to ): (2) (3) Consequently, the value of indexes and will give us an accurate information to find the optimal location of the SFCL if a fault occurs in the system. Indeed, these indices reflect the contribution of the SFCL in the system in terms of stability when a fault occurs. IV. SIMULATIONS RESULTS To evaluate the effectiveness of the proposed method, ten lo- cations ( to in the middle of each line) are considered in Fig. 2. For a given position of the SFCL ( to 10), a 100-ms three-phase short-circuit is applied at each location ( to 10). For each case ( and ), the maximum deviation ( to 3) of generators are calculated to obtain . In a second time, index and finally, index are evaluated with respect to the corresponding value of the SFCL resistance used in simulation. When the SFCL will be positioned at each location , the study of indexes and will give us the best location of the SFCL in the system in case a three-phase fault can appear at any position in the system. The time simulation required until the system is restored to its original steady-state operation point after applying the fault is considered to be equal to 20 s. Before calculating values of index , it is necessary to compute the load flow of the presented power system. The results show that the power generated by generators G1 and G2 is mostly consumed by Load 1. In area 2, the power generated by generators G3 and G4 is consumed by Load 2 but it is not sufficient. The rest of the power required by Load 2, i.e., 413 MW, is transferred from area 1 to area 2 by the 220-km transmission line. A. Sensitivity Analysis for Optimal Location of SFCL To select the optimal location of the SFCL, the corre- sponding value of in (2) is computed for each location . This gives the global separation angle of the rotors of the synchronous generators. Finally, the value of (3) is cal- culated. According to the variation of , the reduction of index in (2) means that the SFCL increases the system
  • 4. This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination. 4 IEEE TRANSACTIONS ON POWER SYSTEMS TABLE I VALUES OF INDEX DURING THE FAULT AT EACH LOCATION (DEG) TABLE II VALUES OF INDEX AT EACH LOCATION stability in case of fault. Therefore, if the value of (3) is greater for a given resistive value, the corresponding location becomes more optimal. The determination of optimal resistive value of SFCL is presented in the next sub-section. Before performing simulations with SFCL, it is necessary to obtain the value of index when a three-phase short-cir- cuit is introduced at each location when no SFCL is used. The result of this test gives a SMD of 1282 (the subscript is not indicated on this index SMD because no SFCL is used). When the proposed method is performed on the power system presented in Fig. 2, the results of indexes and are given, respectively, in Tables I and II with a resistive SFCL of 10 , 20 and 50 [16]. As we can see, the localization of SFCL in the EPG when a fault occurs gives different results concerning index and index . When index presents a negative value (for example, location with equal to 20 ), the SFCL con- tributes to increase the global rotor angles variations of genera- tors. Consequently, the selected location weakens the transient stability of the power system. However, in most cases studied, the value of index is positive which means that the pres- ence of SFCL increases the transient stability of EPG in case of three-phase fault by reducing the variation of separation angle between the rotors. The optimal location of SFCL is obtained when index is maximal for a given resistive value of SFCL. In this case, if is equal to 10 , the optimal loca- tion of the limiter, to increase the EPG transient stability, is . If we consider a resistive value of 20 and 50 , the optimal location determined by the proposed method is . We give in Fig. 3 the variation of (rotor angle separation between generators G1 and G4) versus time when a three-phase short-circuit occurs at . Simulations are made without the SFCL, with an SFCL of 10 and with an SFCL of 50 in- troduced at location . In addition, results given in Tables I and II show that an SFCL cannot be placed between two areas. The presence of SFCL at location and , i.e., at the beginning or in the middle of a long transmission line, increases the instability of the system in case of fault. Fig. 3. Variation of when the SFCL (with different value of ) is connected at when a fault appears at . We can note that the presence of the SFCL in EPG reduces the variation of and consequently, the maximum deviation when a fault occurs in the power system. If a fault occurs in area 2 (for example at location ), the evolution of when the SFCL is placed at location gives the same results but the reduction of its magnitude is influenced by the length of the transmission line (265 km). B. Sensitivity Analysis for Optimal Resistive Value of SFCL The proposed method shows that the optimal location of the SFCL depends on its resistive value . We, respectively, present at Figs. 4 and 5 the variation of index in function of for the two optimal locations and determined by the presented method. If the SFCL is placed at location , the best value of is about 10 as we can see in Fig. 4. In the case of location , it is for a resistance value about 50 that the index is the best. This study shows that the SFCL resistance is
  • 5. This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination. DIDIER et al.: NOVEL APPROACH TO DETERMINE THE OPTIMAL LOCATION OF SFCL IN ELECTRIC POWER GRID 5 Fig. 4. Variation of in function of when the SFCL is placed at location . Fig. 5. Variation of in function of when the SFCL is placed at location . an important parameter in the case of EPG stability study. Other considerations have to be taken into account to choose the posi- tion and the resistive value of the SFCL. In fact, a SFCL with a resistance of 10 is easier to manufacture than an SFCL with a resistance of 50 . However, the easiness of implementation in terms of geographical point in the EPG must be taken into account. A third point to be considered could be the damping improvement of generators speed (or system frequency) intro- duced by the SFCL. Table III gives the ratio of the rotor speed deviation of the th generator when the SFCL (with, respectively, a resistance of 10 and 50 ) is placed at location and when a 100-ms three-phase short-circuit is applied at each location : (4) If the SFCL is placed at location , we can see in Table III that its influence on is more significant if the fault occurs at locations , , or . However, we can note that the pres- ence of SFCL at this location increases the ratio if the fault occurs at or . In the case where the SFCL is placed at location , it is when a fault occurs at , , , , , or that the damping performance is more effective. The posi- tion is better than if we consider the number of locations influenced, but if we take a look on the damping performance, we can see that the effectiveness of the SFCL placed at is the most important (we obtain the better reduction of ratio ). We give in Fig. 6 the rotor speed response of generators G1, G2, G3, and G4 when a fault occurs at location . Three cases are considered: — no SFCL is used; — an SFCL of 10 is placed at location ; — an SFCL of 50 is placed at location . As we can see, the SFCL placed at location improves the damping performance of the generators G3 and G4. Concerning generators G1 and G2, it is when the SFCL of 10 is placed at location that the rotor speed oscillations are the smallest. In a general way, the results show that the position of the SFCL in the power system reduces the low frequency oscillation of the generators speed. However, the simulation results and Table III show us that the damping performance is a function of the location and the resistance value of the SFCL. To determine the better position between locations and , we could calculate the mean of the ratio by taking into account all locations and all generators. If the SFCL is placed at location , we obtain a reduction of the low frequency oscilla- tion of the rotors speeds equal to 9.17%. If the SFCL is placed at location , the reduction of the low frequency oscillation of the rotors speeds is equal to 19.18%. From the above results, the optimal location selected by the proposed method is val- idated to be effective for application of the resistive SFCL to the IEEE Benchmark four-machine two-area test system. Concerning the coordination of the protective devices present in the power system, You et al. in [5] have shown that the re- covery time of the SFCL, which depends on its resistive value, can modify the operation of the recloser and the over current relay (OCR) of the faulty transmission line. Two solutions can be considered. The first is to select the resistance of the SFCL to be within the limited range of the protection devices to keep the protection coordination. The second is to modify the setting parameters such as the time dial (TD) and the pickup current of the protective devices. In our case, the modification of the resistance value of the SFCL is difficult because it has been determined to obtain the best reduction of the rotor angle deviations of generators and an increase of the system damping performance in case of fault. Consequently, in our case, the solution is to modify the setting parameters to ensure the protection coordination of the power system. Recent works have shown that a good coordination of the protective devices with SFCL can be obtained by the modi- fication of the TD [21] or the pick up current [22] of the OCR, these two last parameters being a function of the resistance of the SFCL used in the power system.
  • 6. This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination. 6 IEEE TRANSACTIONS ON POWER SYSTEMS TABLE III RATIO OF THE ROTOR SPEED DEVIATION WITH THE SFCL PLACED AT LOCATIONS AND (%) Fig. 6. Rotor speed response of the four generators with no SFCL, with an SFCL at (10 ), and with an SFCL at (50 ) when a fault occurs at . V. APPLICATION OF THE PROPOSED METHOD TO A LARGE-SCALE POWER SYSTEM If we consider a large-scale power system, it is not possible to use only one SFCL to improve the stability of the system in case of fault. The idea is to split the power system into smaller areas depending on the coherency of the areas when subjected to disturbances. In this case, we will have a number of sub-sys- tems equal to the number of areas. To improve the stability of the power system, an SFCL has to be associated to each sub-system. The optimal location of each SFCL can be determined thanks to the proposed method by considering a three-phase fault at dif- ferent locations in the considered area. Consequently, the pro- posed method uses only a reduced number of generators to eval- uate the optimal location and the optimal resistance of SFCLs. For example, if we consider the IEEE 39-bus test system (10 generators, 39 bus, and 34 lines) [20], we can divide it into three Fig. 7. IEEE 39-bus test system split into three areas (or three sub-systems). areas as shown in Fig. 7. For each area (or sub-system), the pro- posed method can be applied to determine the optimal location of the associated SFCL. VI. CONCLUSIONS This paper presents a novel approach to select the optimal location of a resistive SFCL in an EPG. The proposed method is based on the study of the angular separation between the rotors of the generators present in the power system. This approach allows to find the optimal location of SFCL when the power system studied presents several generators. We have shown that the optimal location of SFCL selected by the proposed method, in accordance with the own resistive value , increases the transient stability of the power system studied by reducing the angular deviation between the rotors of the synchronous machines in case of three-phase fault. In addi- tion, the method takes into account the study of the frequency oscillations of the generator speed in order to select the optimal
  • 7. This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination. DIDIER et al.: NOVEL APPROACH TO DETERMINE THE OPTIMAL LOCATION OF SFCL IN ELECTRIC POWER GRID 7 resistance of SFCL. The main advantage is that the optimal loca- tion of the SFCL determined by the analysis of indexes and takes into account that the three-phase short-circuit can appear anywhere in the EPG. REFERENCES [1] W. D. Stevenson, Elements of Power System Analysis, 4th ed. New York: McGraw-Hill, 1968. [2] M. Sjodtrom, R. Cherkaoui, and B. Dutoit, “Enhancement of power system transient stability using superconducting fault current limiters,” IEEE Trans. Appl. Supercond., vol. 9, no. 2, pp. 1328–1330, Jun. 1999. [3] L. Ye et al., “Application studies of superconducting fault current lim- iters in electric power systems,” IEEE Trans. Appl. Supercond., vol. 17, no. 1, pp. 900–903, Mar. 2002. [4] L. Ye and A. Campbell, “Behavior investigations of superconducting fault current limiters in power systems,” IEEE Trans. Appl. Supercond., vol. 16, no. 2, pp. 662–665, Jun. 2006. [5] L. You et al., “Study on protection coordination between protective devices in a power distribution system with an SFCL,” IEEE Trans. Appl. Supercond., vol. 20, no. 3, pp. 1168–1171, Jun. 2010. [6] L. Ye and K. P. Juengst, “Modeling and simulation of HTc resistive superconducting fault current limiters,” IEEE Trans. Appl. Supercond., vol. 14, no. 2, pp. 839–842, Jun. 2004. [7] Y. Cai et al., “Study on three-phase superconducting fault current lim- iter,” IEEE Trans. Appl. Supercond., vol. 20, no. 3, pp. 1127–1130, Jun. 2010. [8] J. Shi et al., “The application of active superconducting DC fault cur- rent limiter in hybrid AC/DC power supply system,” IEEE Trans. Appl. Supercond., vol. 18, no. 2, pp. 672–675, Jun. 2008. [9] D. Hui et al., “Development and test of 10.5 kV/1.5 k1 HTS fault current limiter,” IEEE Trans. Appl. Supercond., vol. 16, no. 2, pp. 687–6690, Jun. 2006. [10] M. Heydari et al., “Optimization scheme in combinatorial UPQC and SFCL using normalized simulated annealing,” IEEE Trans. Power Del., vol. 26, no. 3, pp. 1489–1498, Jul. 2011. [11] L. Ye et al., “ sample tests for possible applications of super- conducting fault current limiters,” IEEE Trans. Appl. Supercond., vol. 17, no. 2, pp. 2826–2829, Jun. 2007. [12] I. Muta, T. Doshita, T. Nakamura, T. Egi, and T. Hoshino, “Influences of Superconducting Fault Current Limiter (SFCL) on superconducting generator in one-machine double-line system,” IEEE Trans. Appl. Su- percond., vol. 13, no. 2, pp. 2206–2209, Jun. 2003. [13] L. Ye et al., “System studies of the superconducting fault current limiter in electrical distribution grids,” IEEE Trans. Appl. Supercond., vol. 17, no. 2, pp. 2339–2342, Jun. 2007. [14] L. Ye and L. Z. Lin, “Study of superconducting fault current limiters for system integration of wind farms,” IEEE Trans. Appl. Supercond., vol. 20, no. 3, pp. 1233–1237, Jun. 2010. [15] B. Sung et al., “Study on a series resistive SFCL to improve power tran- sient stability: Modeling, simulation, experimental verification,” IEEE Trans. Ind. Electron., vol. 56, no. 7, pp. 2412–2419, Jun. 2009. [16] B. Sung et al., “Study optimal location of a resistive SFCL applied to an electric power grid,” IEEE Trans. Appl. Supercond., vol. 19, no. 3, pp. 2048–202052, Jun. 2009. [17] B. Sung et al., “Optimal parameter selection of resistive SFCL applied to a power system using eigenvalue analysis,” IEEE Trans. Appl. Su- percond., vol. 20, no. 3, pp. 1147–1150, Jun. 2010. [18] M. Elsamahy et al., “Impact of superconducting fault current limiters on the coordination between generator distance phase backup protec- tion and generator capability curves,” IEEE Trans. Power Del., vol. 26, no. 3, pp. 1854–1863, Jul. 2011. [19] P. Kundur, Power System Stability and Control. New York: Mc- Graw-Hill, 1993, EPRI Editor. [20] K. R. Padiyar, Power System Dynamics—Stability and Control, 2nd ed. Hyderabad, Andhra Pradesh, India: BS Publications, 2002. [21] J. S. Kim et al., “Study on protection coordination for application of superconducting fault current limiter,” IEEE Trans. Appl. Supercond., vol. 21, no. 3, pp. 2174–2178, Jun. 2011. [22] J. S. Kim et al., “Study on application method of superconducting fault current limiter for protection coordination of protective devices in a power distribution system,” IEEE Trans. Appl. Supercond., vol. 22, no. 3, Jun. 2012, 5601504. G. Didier was born in Saint-Dié des Vosges, France, in 1978. He received the degree in electrical engineering and the Ph.D. degree from the Université de Lorraine, Nancy, France, in 2004. In 2004, he joined the Groupe de Recherche en Electrotechnique et Electron- ique de Nancy as an Assistant Professor. Until 2009, he has working on the diag- nosis and modeling of induction motor under faults. Actually, his main research interest concerns superconducting fault current limiters (SFCLs) and their appli- cations in enhancing the power system performance and power system stability. Jean Lévêque was born in Angers, France, in 1963. In 1993, he received the Ph.D. degree in electrical engineering from the University of Grenoble, Grenoble, France. He joined the laboratory GREEN in the University de Lorraine, Nancy, France, in 1993. His research interests include two main topics, the application of the superconductor’s material in electrical engineering, especially super- conducting motor, fault current limiter, and electrical characterization, and modelization of superconducting material. Abderrezak Rezzoug received the electrical engineer degree from ENSEM INPL, Nancy, France, in 1972, and the Dr. Ing. diploma and the Ph.D. degree from INPL, in 1979 and 1987, respectively. After working at the INPL as an Assistant Professor until 1991, he is currently a Professor of Electrical Engineering at the University de Lorraine, Nancy, France. As a member of the Groupe de Recherche en Electrotechnique et Electronique de Nancy, his main subjects of research concern supercon- ducting applications to electrical devices, and the control and diagnosis of electrical machines.