Indonesian Journal of Electrical Engineering and Informatics (IJEEI)
Vol. 4, No. 2, June 2016, pp. 93~101
ISSN: 2089-3272, DOI: 10.11591/ijeei.v4i2.209  93
Received December 11, 2015; Revised March 16, 2016; Accepted April 8, 2016
Effect of HVTL Phase Transposition on Pipelines
Induced Voltage
Adedeji Kazeem B
Department of Electrical Engineering, Tshwane University of Technology, Pretoria, South Africa.
e-mail: kezman0474@yahoo.com
Abstract
In this work, a study of the effect of the phase conductor transposition for a multi-circuit high
voltage power transmission lines on the induced voltage on a buried pipeline was conducted and
considered through modelling. The modelling was done applying Carson’s concept of mutual impedances
for a double circuit, three circuits and four circuit power transmission line on a buried pipeline. The
simulated results obtained showed that the transmission line with un-transposed phase combination has
the greater effect on the induced voltage while for the one or more of the other combinations, a
cancellation or reduction can occur. This also is dependent on the tower geometry and the relative position
of the pipeline and the transmission line. Also, the magnitude of the induced voltage increases with
increasing number of circuits.
Keywords: AC interference, Inductive coupling, Induce voltage, Phase transposition, pipelines,
Transmission lines
1. Introduction
As a result of the ever increasing cost of right of way suitable for transmission line and
pipelines, coupled with environmental factors to protect nature and wildlife, there are more
tendencies of installing pipelines near an existing power transmission lines. The current flowing
through this transmission line phase conductors produces a time-varying magnetic field which
couples to metallic structures in its right of way as shown in Figure 1.
Figure 1. Coupling from a high voltage power transmission line on a buried pipeline
As a result of this coupling, voltage is induced in such structure. The induction can
occur under both steady state and fault condition of the power transmission line [1, 2]. The
interference from a high voltage power transmission line and a neighbouring pipeline can occur
due to inductive, conductive and capacitive coupling [3-10]. Inductive coupling affects both
aerial and underground pipelines that run parallel to or at an angle with a power transmission
line while capacitive coupling only affects metallic structures located above the ground [8, 9]. In
this type of coupling (capacitive coupling), “the pipeline picks up a voltage relative to the soil,
which is proportional to the voltage on the transmission line [11, 12]. For structures located
below the earth’s surface, the effect of capacitive coupling is negligible because of the
screening effect of the earth against electric fields. The resistive coupling between a
transmission line and a nearby buried pipeline is only relevant during ground faults where
Indonesian Journal of Electrical Engineering and Informatics (IJEEI)
Vol. 4, No. 2, June 2016, pp. 93~101
ISSN: 2089-3272, DOI: 10.11591/ijeei.v4i2.209  93
Received December 11, 2015; Revised March 16, 2016; Accepted April 8, 2016
Effect of HVTL Phase Transposition on Pipelines
Induced Voltage
Adedeji Kazeem B
Department of Electrical Engineering, Tshwane University of Technology, Pretoria, South Africa.
e-mail: kezman0474@yahoo.com
Abstract
In this work, a study of the effect of the phase conductor transposition for a multi-circuit high
voltage power transmission lines on the induced voltage on a buried pipeline was conducted and
considered through modelling. The modelling was done applying Carson’s concept of mutual impedances
for a double circuit, three circuits and four circuit power transmission line on a buried pipeline. The
simulated results obtained showed that the transmission line with un-transposed phase combination has
the greater effect on the induced voltage while for the one or more of the other combinations, a
cancellation or reduction can occur. This also is dependent on the tower geometry and the relative position
of the pipeline and the transmission line. Also, the magnitude of the induced voltage increases with
increasing number of circuits.
Keywords: AC interference, Inductive coupling, Induce voltage, Phase transposition, pipelines,
Transmission lines
1. Introduction
As a result of the ever increasing cost of right of way suitable for transmission line and
pipelines, coupled with environmental factors to protect nature and wildlife, there are more
tendencies of installing pipelines near an existing power transmission lines. The current flowing
through this transmission line phase conductors produces a time-varying magnetic field which
couples to metallic structures in its right of way as shown in Figure 1.
Figure 1. Coupling from a high voltage power transmission line on a buried pipeline
As a result of this coupling, voltage is induced in such structure. The induction can
occur under both steady state and fault condition of the power transmission line [1, 2]. The
interference from a high voltage power transmission line and a neighbouring pipeline can occur
due to inductive, conductive and capacitive coupling [3-10]. Inductive coupling affects both
aerial and underground pipelines that run parallel to or at an angle with a power transmission
line while capacitive coupling only affects metallic structures located above the ground [8, 9]. In
this type of coupling (capacitive coupling), “the pipeline picks up a voltage relative to the soil,
which is proportional to the voltage on the transmission line [11, 12]. For structures located
below the earth’s surface, the effect of capacitive coupling is negligible because of the
screening effect of the earth against electric fields. The resistive coupling between a
transmission line and a nearby buried pipeline is only relevant during ground faults where
Indonesian Journal of Electrical Engineering and Informatics (IJEEI)
Vol. 4, No. 2, June 2016, pp. 93~101
ISSN: 2089-3272, DOI: 10.11591/ijeei.v4i2.209  93
Received December 11, 2015; Revised March 16, 2016; Accepted April 8, 2016
Effect of HVTL Phase Transposition on Pipelines
Induced Voltage
Adedeji Kazeem B
Department of Electrical Engineering, Tshwane University of Technology, Pretoria, South Africa.
e-mail: kezman0474@yahoo.com
Abstract
In this work, a study of the effect of the phase conductor transposition for a multi-circuit high
voltage power transmission lines on the induced voltage on a buried pipeline was conducted and
considered through modelling. The modelling was done applying Carson’s concept of mutual impedances
for a double circuit, three circuits and four circuit power transmission line on a buried pipeline. The
simulated results obtained showed that the transmission line with un-transposed phase combination has
the greater effect on the induced voltage while for the one or more of the other combinations, a
cancellation or reduction can occur. This also is dependent on the tower geometry and the relative position
of the pipeline and the transmission line. Also, the magnitude of the induced voltage increases with
increasing number of circuits.
Keywords: AC interference, Inductive coupling, Induce voltage, Phase transposition, pipelines,
Transmission lines
1. Introduction
As a result of the ever increasing cost of right of way suitable for transmission line and
pipelines, coupled with environmental factors to protect nature and wildlife, there are more
tendencies of installing pipelines near an existing power transmission lines. The current flowing
through this transmission line phase conductors produces a time-varying magnetic field which
couples to metallic structures in its right of way as shown in Figure 1.
Figure 1. Coupling from a high voltage power transmission line on a buried pipeline
As a result of this coupling, voltage is induced in such structure. The induction can
occur under both steady state and fault condition of the power transmission line [1, 2]. The
interference from a high voltage power transmission line and a neighbouring pipeline can occur
due to inductive, conductive and capacitive coupling [3-10]. Inductive coupling affects both
aerial and underground pipelines that run parallel to or at an angle with a power transmission
line while capacitive coupling only affects metallic structures located above the ground [8, 9]. In
this type of coupling (capacitive coupling), “the pipeline picks up a voltage relative to the soil,
which is proportional to the voltage on the transmission line [11, 12]. For structures located
below the earth’s surface, the effect of capacitive coupling is negligible because of the
screening effect of the earth against electric fields. The resistive coupling between a
transmission line and a nearby buried pipeline is only relevant during ground faults where
 ISSN: 2089-3272
IJEEI Vol. 4, No. 2, June 2016 : 93 – 101
94
significant levels of current flows into the ground [7, 13, 14]. Irrespective of the type of coupling,
buried pipeline experience induction through any of these coupling or a combination of them
which can pose danger to personnel working on the pipeline and can also compromise the
materials of the pipe.
The interference from the power transmission lines on buried pipelines which varies
with the electrical characteristics and geometry of the individual system [15], is also known to
accelerate the corrosion process of pipelines [16-19]. AC corrosion case histories can be traced
back to 1970 when cathodically protected pipeline was found perforated in Germany, as a result
of AC interfering with the pipeline [20], thereby accelerating the corrosion process. In particular,
there have been increasing reports of AC induced corrosion and failure of pipelines in recent
years, drawing attention to this important problem. This problem has been a threat to the
integrity of pipeline and therefore became a major topic of discussion among authors around the
world. The subject has become more important for safety of personnel and prevention of
pipeline from corrosion. Thereafter, NACE recommended that for safety of personnel working on
the pipeline, the steady state induced potential should be considered dangerous and be
mitigated if the measured or calculated potential on the pipeline exceeds 15 Vr.m.s [21].
Furthermore, because of the increasing growth of energy demand and to ensure
adequate supply of electric power and to cater for losses on the line, more multi-circuits, power
transmission line is being used to transmit power for several kilometres across the Nation. The
phase conductors of these multi-circuit lines are not always symmetrical, allowing for phase
transpositions of the first circuit with respect to the other. The relative position of each phase
with respect to the other is known to affect the magnetic field produced by the line current and
can cause a drastic reduction in the magnetic field which in turn will have the effect of the
voltage induced on buried metallic structure in this energy utility corridor. To ensure safety of the
personnel touching the exposed part of the buried structure, the worst-case phase transposition
which will give a minimal inductive effect on metallic structures needed to be obtained for the
multi-circuits lines.
Pipeline being installed near an existing high voltage power transmission line is subject
to inductive coupling from the line as a result of the time varying magnetic field produced by the
transmission line current. The strength of the coupling depends, among other factors, on the
relative position of the pipeline and the transmission line phase conductors. Different research
works in the past and in recent times, have worked on the effect of the transmission line phase
conductor combination [22, 23] and phase shifts [24-26] on the magnetic field produced by the
line. However, the effect of this phase transposition/combination on the induced voltage on
pipelines for safety of personnel and protection of pipelines from corrosion has not been fully
covered yet. This work annexes the effect of the phase transposition of a multi-circuit power
transmission lines on the induced voltage on buried steel pipeline, using one of the Rand Water
sites, South Africa as a case study. In a double-circuit power transmission line, there are six
possible phase combination/transposition of the first circuit with respect to the other as shown
Figure 2. These phase transpositions are RWB-RWB, RWB-BWR, RWB-BRW, RWB-WRB,
RWB-RBW, and RWB-WBR as shown in Figure 2.
Figure 2. Possible phase transposition of a double circuit power transmission line
Assuming identical phase conductor characteristics and steady state current in each
circuit with a different phase combination, the worst case phase transposition can be obtained
which will be useful in designing AC mitigation system accordingly and reduce the danger of
 ISSN: 2089-3272
IJEEI Vol. 4, No. 2, June 2016 : 93 – 101
94
significant levels of current flows into the ground [7, 13, 14]. Irrespective of the type of coupling,
buried pipeline experience induction through any of these coupling or a combination of them
which can pose danger to personnel working on the pipeline and can also compromise the
materials of the pipe.
The interference from the power transmission lines on buried pipelines which varies
with the electrical characteristics and geometry of the individual system [15], is also known to
accelerate the corrosion process of pipelines [16-19]. AC corrosion case histories can be traced
back to 1970 when cathodically protected pipeline was found perforated in Germany, as a result
of AC interfering with the pipeline [20], thereby accelerating the corrosion process. In particular,
there have been increasing reports of AC induced corrosion and failure of pipelines in recent
years, drawing attention to this important problem. This problem has been a threat to the
integrity of pipeline and therefore became a major topic of discussion among authors around the
world. The subject has become more important for safety of personnel and prevention of
pipeline from corrosion. Thereafter, NACE recommended that for safety of personnel working on
the pipeline, the steady state induced potential should be considered dangerous and be
mitigated if the measured or calculated potential on the pipeline exceeds 15 Vr.m.s [21].
Furthermore, because of the increasing growth of energy demand and to ensure
adequate supply of electric power and to cater for losses on the line, more multi-circuits, power
transmission line is being used to transmit power for several kilometres across the Nation. The
phase conductors of these multi-circuit lines are not always symmetrical, allowing for phase
transpositions of the first circuit with respect to the other. The relative position of each phase
with respect to the other is known to affect the magnetic field produced by the line current and
can cause a drastic reduction in the magnetic field which in turn will have the effect of the
voltage induced on buried metallic structure in this energy utility corridor. To ensure safety of the
personnel touching the exposed part of the buried structure, the worst-case phase transposition
which will give a minimal inductive effect on metallic structures needed to be obtained for the
multi-circuits lines.
Pipeline being installed near an existing high voltage power transmission line is subject
to inductive coupling from the line as a result of the time varying magnetic field produced by the
transmission line current. The strength of the coupling depends, among other factors, on the
relative position of the pipeline and the transmission line phase conductors. Different research
works in the past and in recent times, have worked on the effect of the transmission line phase
conductor combination [22, 23] and phase shifts [24-26] on the magnetic field produced by the
line. However, the effect of this phase transposition/combination on the induced voltage on
pipelines for safety of personnel and protection of pipelines from corrosion has not been fully
covered yet. This work annexes the effect of the phase transposition of a multi-circuit power
transmission lines on the induced voltage on buried steel pipeline, using one of the Rand Water
sites, South Africa as a case study. In a double-circuit power transmission line, there are six
possible phase combination/transposition of the first circuit with respect to the other as shown
Figure 2. These phase transpositions are RWB-RWB, RWB-BWR, RWB-BRW, RWB-WRB,
RWB-RBW, and RWB-WBR as shown in Figure 2.
Figure 2. Possible phase transposition of a double circuit power transmission line
Assuming identical phase conductor characteristics and steady state current in each
circuit with a different phase combination, the worst case phase transposition can be obtained
which will be useful in designing AC mitigation system accordingly and reduce the danger of
 ISSN: 2089-3272
IJEEI Vol. 4, No. 2, June 2016 : 93 – 101
94
significant levels of current flows into the ground [7, 13, 14]. Irrespective of the type of coupling,
buried pipeline experience induction through any of these coupling or a combination of them
which can pose danger to personnel working on the pipeline and can also compromise the
materials of the pipe.
The interference from the power transmission lines on buried pipelines which varies
with the electrical characteristics and geometry of the individual system [15], is also known to
accelerate the corrosion process of pipelines [16-19]. AC corrosion case histories can be traced
back to 1970 when cathodically protected pipeline was found perforated in Germany, as a result
of AC interfering with the pipeline [20], thereby accelerating the corrosion process. In particular,
there have been increasing reports of AC induced corrosion and failure of pipelines in recent
years, drawing attention to this important problem. This problem has been a threat to the
integrity of pipeline and therefore became a major topic of discussion among authors around the
world. The subject has become more important for safety of personnel and prevention of
pipeline from corrosion. Thereafter, NACE recommended that for safety of personnel working on
the pipeline, the steady state induced potential should be considered dangerous and be
mitigated if the measured or calculated potential on the pipeline exceeds 15 Vr.m.s [21].
Furthermore, because of the increasing growth of energy demand and to ensure
adequate supply of electric power and to cater for losses on the line, more multi-circuits, power
transmission line is being used to transmit power for several kilometres across the Nation. The
phase conductors of these multi-circuit lines are not always symmetrical, allowing for phase
transpositions of the first circuit with respect to the other. The relative position of each phase
with respect to the other is known to affect the magnetic field produced by the line current and
can cause a drastic reduction in the magnetic field which in turn will have the effect of the
voltage induced on buried metallic structure in this energy utility corridor. To ensure safety of the
personnel touching the exposed part of the buried structure, the worst-case phase transposition
which will give a minimal inductive effect on metallic structures needed to be obtained for the
multi-circuits lines.
Pipeline being installed near an existing high voltage power transmission line is subject
to inductive coupling from the line as a result of the time varying magnetic field produced by the
transmission line current. The strength of the coupling depends, among other factors, on the
relative position of the pipeline and the transmission line phase conductors. Different research
works in the past and in recent times, have worked on the effect of the transmission line phase
conductor combination [22, 23] and phase shifts [24-26] on the magnetic field produced by the
line. However, the effect of this phase transposition/combination on the induced voltage on
pipelines for safety of personnel and protection of pipelines from corrosion has not been fully
covered yet. This work annexes the effect of the phase transposition of a multi-circuit power
transmission lines on the induced voltage on buried steel pipeline, using one of the Rand Water
sites, South Africa as a case study. In a double-circuit power transmission line, there are six
possible phase combination/transposition of the first circuit with respect to the other as shown
Figure 2. These phase transpositions are RWB-RWB, RWB-BWR, RWB-BRW, RWB-WRB,
RWB-RBW, and RWB-WBR as shown in Figure 2.
Figure 2. Possible phase transposition of a double circuit power transmission line
Assuming identical phase conductor characteristics and steady state current in each
circuit with a different phase combination, the worst case phase transposition can be obtained
which will be useful in designing AC mitigation system accordingly and reduce the danger of
IJEEI ISSN: 2089-3272 
Effect of HVTL Phase Transposition on Pipelines Induced Voltage (Adedeji Kazeem B)
95
shock hazard to personnel. With three or more circuits on a power line, the number of possible
combinations to simulate increases.
2. Materials and Method
2.1. Model Description and Evaluation
In this work, the effect of the phase conductor transposition of a double-circuit, three-
circuit and four circuit power transmission lines on the inductive coupling effect resulting in an
induced voltage on a buried steel pipeline was modelled and simulated. Figure 3 and Figure 4
show the schematic diagram and snapshot of the transmission line-pipeline right of way under
study.
Figure 3. Schematic diagram and snapshot of the transmission line-pipeline right of way (a)
double-circuit line (b) three-circuit line
Figure 4. Schematic diagram and snapshot of a four-circuit transmission line-pipeline right of
way
IJEEI ISSN: 2089-3272 
Effect of HVTL Phase Transposition on Pipelines Induced Voltage (Adedeji Kazeem B)
95
shock hazard to personnel. With three or more circuits on a power line, the number of possible
combinations to simulate increases.
2. Materials and Method
2.1. Model Description and Evaluation
In this work, the effect of the phase conductor transposition of a double-circuit, three-
circuit and four circuit power transmission lines on the inductive coupling effect resulting in an
induced voltage on a buried steel pipeline was modelled and simulated. Figure 3 and Figure 4
show the schematic diagram and snapshot of the transmission line-pipeline right of way under
study.
Figure 3. Schematic diagram and snapshot of the transmission line-pipeline right of way (a)
double-circuit line (b) three-circuit line
Figure 4. Schematic diagram and snapshot of a four-circuit transmission line-pipeline right of
way
IJEEI ISSN: 2089-3272 
Effect of HVTL Phase Transposition on Pipelines Induced Voltage (Adedeji Kazeem B)
95
shock hazard to personnel. With three or more circuits on a power line, the number of possible
combinations to simulate increases.
2. Materials and Method
2.1. Model Description and Evaluation
In this work, the effect of the phase conductor transposition of a double-circuit, three-
circuit and four circuit power transmission lines on the inductive coupling effect resulting in an
induced voltage on a buried steel pipeline was modelled and simulated. Figure 3 and Figure 4
show the schematic diagram and snapshot of the transmission line-pipeline right of way under
study.
Figure 3. Schematic diagram and snapshot of the transmission line-pipeline right of way (a)
double-circuit line (b) three-circuit line
Figure 4. Schematic diagram and snapshot of a four-circuit transmission line-pipeline right of
way
 ISSN: 2089-3272
IJEEI Vol. 4, No. 2, June 2016 : 93 – 101
96
The simulation was done for the effect of the inductive coupling from these lines on the buried
pipeline under steady state operation, using the Carson’s concept of mutual impedance
between the transmission line phase/earth wire conductors and the pipeline [27]. Using this
concept, the longitudinal induced electromotive force (emf) on the pipeline due to the inductive
coupling effect of the transmission line is given by
1 1 1 1
j j j
i i i j i i i j i i i j
j j j
N k k k
g p g p g p
p R R p R g W W p W g B B p B g
i j j jg g g
Z Z Z
E I Z Z I Z Z I Z Z
Z Z Z   
           
                
                      
    (1)
where, i and j are positive integers with range of i=1,2,……N, and j=1,2,…k. N represents the
number of circuits while k is the number of overhead earth wire on the transmission line. IRi, Iwi
and IBi are the steady state current on the i
th
circuit of the transmission line, ZRip, ZWip and ZBip
are the mutual impedances between the R-W-B phase conductor of the i
th
circuit and the
pipeline. More also, Zgjp represents the mutual impedance between the j
th
earth wire conductor
and the pipeline while ZRigj, ZRigj and ZRigj are the mutual impedance between the R-W-B phase
conductors of the i
th
circuit and the j
th
earth wire. In addition to this, Zgj is the self-impedance of
the j
th
earth wire conductor.
The mutual impedance (in Ω/m) between a pipeline p, and an overhead transmission line phase
conductor R, W, B or earth wire conductor g, with earth return is evaluated using Equation (2)
[28] as
0 0
log
8 2
e
pn e
pn
Z j
D
    

  
      
  
where n=Ri, Wi, Bi or gj (2)
where, µ0 is the magnetic permeability of free space, ω is the angular frequency of operation of
the transmission line, δe is the depth of equivalent earth return and Dpn is the geometric mean
distances (GMDs) between the pipeline, transmission line phase conductor R-W-B or earth wire
conductor g of the i
th
transmission line circuit. Also, the self-impedance of the j
th
earth wire
conductor transmission line, with earth return is given as
0 0 1
log
8 2 4j j
j
e
g g e
GM
Z R j
R
    

   
      
      
(3)
In Equation (3), Rgj is the AC resistance of the earth j
th
wire and RGMj is the geometric mean
radius of the earth wire conductors of the transmission line. The depth of equivalent earth return
is a function of soil resistivity ρsoil and the transmission line operating frequency f [28-30],
evaluated as
658.87 soil
e
f

  (4)
The various GMDs between the phase conductors of each circuit and the pipeline or the ground
wire for the three case studies are derived from the Powerline-pipeline coordinates system
shown in Figure 5.
IJEEI ISSN: 2089-3272 
Effect of HVTL Phase Transposition on Pipelines Induced Voltage (Adedeji Kazeem B)
97
Figure 5. Powerline-pipeline coordinate system (a) double-circuits, (b) three-circuits (c) four-
circuits
From Figure 5 (a), the GMD between the R-W-B phase conductors of the i
th
transmission line
circuit and the pipeline is given by
   
   
   
1
2 2 2
1
2 2 2
1
2 2 2
i i i
i i i
i i i
R p p R R p
W p p W W p
B p p B B p
D x x y y
D x x y y
D x x y y

     
   

        

     
   
(5)
xp, yp, xRi, xWi, xBi; yRi, yWi and yBi are the horizontal and vertical position of the pipeline and the
phase conductors of the i
th
circuit as shown in Figure 5. Also, the GMD between the j
th
earth
wire conductors and the pipeline is given by
   
1
2 2 2
j j jg p p g g pD x x y y    
  
(6)
Other GMDs are derived using the same method. Thereafter, the induced voltage Vp, on the
entire parallel exposure length L, of the pipeline is given by
p pV E L  (7)
2.2. Case Study Parameter used for Simulation
As stated earlier, the effect of phase transposition for three different multi-circuit lines on
the induced voltage on an 800 mm diameter pipe buried 1 m beneath the soil surface, was
considered. The pipeline was parallel with the transmission line for a length of 1 km. The three
phase current on the line were considered under steady state condition with maximum load
current of 410 A for zebra typed conductor used in South Africa. The transmission lines
operating at 50 Hz, have phase conductors separated at a distance of 6 m from each other with
a ground clearance of 12 m. The transmission line overhead earth wires with a 13.48 mm
diameter has an AC resistance of 3.44 /km. The earth is assumed to be flat, free from
irregularities and homogenous with a resistivity of 100 m.
3. Results and Analysis
The induced voltage on a buried steel pipeline due to the inductive coupling effect of the
phase conductor transposition of multi-circuits, power transmission lines have been computed
and the results presented. Figure 6 shows the effect of the phase transposition of a double-
circuit power transmission line on the magnitude of the induced voltage on the pipeline.
IJEEI ISSN: 2089-3272 
Effect of HVTL Phase Transposition on Pipelines Induced Voltage (Adedeji Kazeem B)
97
Figure 5. Powerline-pipeline coordinate system (a) double-circuits, (b) three-circuits (c) four-
circuits
From Figure 5 (a), the GMD between the R-W-B phase conductors of the i
th
transmission line
circuit and the pipeline is given by
   
   
   
1
2 2 2
1
2 2 2
1
2 2 2
i i i
i i i
i i i
R p p R R p
W p p W W p
B p p B B p
D x x y y
D x x y y
D x x y y

     
   

        

     
   
(5)
xp, yp, xRi, xWi, xBi; yRi, yWi and yBi are the horizontal and vertical position of the pipeline and the
phase conductors of the i
th
circuit as shown in Figure 5. Also, the GMD between the j
th
earth
wire conductors and the pipeline is given by
   
1
2 2 2
j j jg p p g g pD x x y y    
  
(6)
Other GMDs are derived using the same method. Thereafter, the induced voltage Vp, on the
entire parallel exposure length L, of the pipeline is given by
p pV E L  (7)
2.2. Case Study Parameter used for Simulation
As stated earlier, the effect of phase transposition for three different multi-circuit lines on
the induced voltage on an 800 mm diameter pipe buried 1 m beneath the soil surface, was
considered. The pipeline was parallel with the transmission line for a length of 1 km. The three
phase current on the line were considered under steady state condition with maximum load
current of 410 A for zebra typed conductor used in South Africa. The transmission lines
operating at 50 Hz, have phase conductors separated at a distance of 6 m from each other with
a ground clearance of 12 m. The transmission line overhead earth wires with a 13.48 mm
diameter has an AC resistance of 3.44 /km. The earth is assumed to be flat, free from
irregularities and homogenous with a resistivity of 100 m.
3. Results and Analysis
The induced voltage on a buried steel pipeline due to the inductive coupling effect of the
phase conductor transposition of multi-circuits, power transmission lines have been computed
and the results presented. Figure 6 shows the effect of the phase transposition of a double-
circuit power transmission line on the magnitude of the induced voltage on the pipeline.
IJEEI ISSN: 2089-3272 
Effect of HVTL Phase Transposition on Pipelines Induced Voltage (Adedeji Kazeem B)
97
Figure 5. Powerline-pipeline coordinate system (a) double-circuits, (b) three-circuits (c) four-
circuits
From Figure 5 (a), the GMD between the R-W-B phase conductors of the i
th
transmission line
circuit and the pipeline is given by
   
   
   
1
2 2 2
1
2 2 2
1
2 2 2
i i i
i i i
i i i
R p p R R p
W p p W W p
B p p B B p
D x x y y
D x x y y
D x x y y

     
   

        

     
   
(5)
xp, yp, xRi, xWi, xBi; yRi, yWi and yBi are the horizontal and vertical position of the pipeline and the
phase conductors of the i
th
circuit as shown in Figure 5. Also, the GMD between the j
th
earth
wire conductors and the pipeline is given by
   
1
2 2 2
j j jg p p g g pD x x y y    
  
(6)
Other GMDs are derived using the same method. Thereafter, the induced voltage Vp, on the
entire parallel exposure length L, of the pipeline is given by
p pV E L  (7)
2.2. Case Study Parameter used for Simulation
As stated earlier, the effect of phase transposition for three different multi-circuit lines on
the induced voltage on an 800 mm diameter pipe buried 1 m beneath the soil surface, was
considered. The pipeline was parallel with the transmission line for a length of 1 km. The three
phase current on the line were considered under steady state condition with maximum load
current of 410 A for zebra typed conductor used in South Africa. The transmission lines
operating at 50 Hz, have phase conductors separated at a distance of 6 m from each other with
a ground clearance of 12 m. The transmission line overhead earth wires with a 13.48 mm
diameter has an AC resistance of 3.44 /km. The earth is assumed to be flat, free from
irregularities and homogenous with a resistivity of 100 m.
3. Results and Analysis
The induced voltage on a buried steel pipeline due to the inductive coupling effect of the
phase conductor transposition of multi-circuits, power transmission lines have been computed
and the results presented. Figure 6 shows the effect of the phase transposition of a double-
circuit power transmission line on the magnitude of the induced voltage on the pipeline.
 ISSN: 2089-3272
IJEEI Vol. 4, No. 2, June 2016 : 93 – 101
98
Figure 6. Induced voltage on buried pipeline due to phase transposition of a double-circuit
power transmission line
Looking at the Figure, it is observed that there is a drastic reduction in the magnitude of
the induced voltage for a directly phase transposed, that is, RWB-BWR while for an un-
transposed condition, its effect is relatively higher than others phase transposition shown in the
Figure. It is also, observed that the directly phase transposed decreases slightly with distance
while for another phase transposition, they decreases drastically with increasing distance.
Considering Figure 7, a different pattern of results is observed. At some points 15 m
beyond the centre line of the transmission line, the phase transposition with RWB-BWR-RWB
gives the least inductive effect on the pipeline. However, as the distance increases beyond 50
m, phase combination with RWB-RWB-WBR has the least effect. This pattern of results is
obtained due to the phase configuration of this type of transmission line (a combination of
horizontal and delta configuration).
Figure 7. Induced voltage on buried pipeline due to phase transposition of a three-circuit power
transmission line
-200 -150 -100 -50 0 50 100 150 200
0
5
10
15
20
25
30
35
40
45
Pipeline position across the transmission line (m)
Inducedvoltage(V)
Induced voltage on the pipeline due to double circuits power transmission line
RWB-RWB
RWB-BWR
RWB-WRB
RWB-BRW
RWB-RBW
RWB-WBR
Phase Transposition
-200 -150 -100 -50 0 50 100 150 200
0
5
10
15
20
25
30
Pipeline position across the transmission line (m)
InducedVoltage(V)
Induced voltage on the pipeline due to three circuts power transmission line
RWB-RWB-RWB
RWB-BWR-RWB
RWB-WRB-RWB
RWB-BRW-RWB
RWB-RBW-RWB
RWB-WBR-RWB
RWB-RBW-BWR
RWB-WBR-WRB
RWB-RWB-BRW
RWB-RWB-RBW
RWB-RWB-WBR
Phase Transposition
IJEEI ISSN: 2089-3272 
Effect of HVTL Phase Transposition on Pipelines Induced Voltage (Adedeji Kazeem B)
99
In Figure 8, the effect of the transmission line phase conductor transposition on the
induced voltage on a pipeline buried near a four-circuit power transmission line is presented.
Considering this figure, in line with Figure 6, the un-transposed phase combination has the
highest effect while the one with RWB-BWR-RWB-BWR and RWB-RWB-BWR-RWB has the
least effect. Some other phase transposition, also gives a little reduction in the magnitude of the
induced voltage as shown in Figure 8. Furthermore, symmetrical and asymmetrical nature is
observed, as some are symmetrical about the centre line of power transmission line tower while
some shows a little offside asymmetry about the centre line. This is related to the results
obtained in [23, 24] for magnetic field produced from a multi-circuits line. All the phase
combinations decrease drastically with distance up to about 50 m, after which they decrease
slightly with increasing distance.
Figure 8. Induced voltage on buried pipeline due to phase transposition of a four-circuit power
transmission line
3.1. Effects of the Number of Circuits
Figure 9 shows the effect of increase in the number of circuits on the induced voltage
on the buried pipeline. It is evident from the figure that this increase has a great effect on the
induced voltage. The effect is more pronounced on the pipeline at few distances (less than 50
m) from the centre line of the transmission line. However, with increasing distance, the effect
reduces gradually to almost a negligible value.
-200 -150 -100 -50 0 50 100 150 200
0
10
20
30
40
50
60
70
Pipeline position across the transmission line (m)
Inducedvoltage(V)
Induced voltage on the pipeline due to four circuts power transmission line
RWB-RWB-RWB-RWB
RWB-BWR-RWB-RWB
RWB-WRB-RWB-RWB
RWB-BRW-RWB-RWB
RWB-RBW-RWB-RWB
RWB-WBR-RWB-RWB
RWB-RWB-BWR-RWB
RWB-RWB-WRB-RWB
RWB-RWB-BRW-RWB
RWB-RWB-RBW-RWB
RWB-RWB-WBR-RWB
RWB-RWB-RWB-BWR
RWB-RWB-RWB-WRB
RWB-RWB-RWB-BRW
RWB-RWB-RWB-RBW
RWB-RWB-RWB-WBR
Phase Transposition
 ISSN: 2089-3272
IJEEI Vol. 4, No. 2, June 2016 : 93 – 101
100
Figure 9. Induced voltage on buried pipeline due to multi-circuits power transmission line
4. Conclusion
The effect of the phase conductor transposition of a multi-circuit power transmission
lines on the magnitude of the induced voltage on a buried steel pipeline have been computed
and the simulated results from MATLAB software presented and analysed. It is obvious from
these results that phase conductors with a direct phase transposition of the first phase with
respect to the other shows a better reduction in the magnitude of the induced voltage on the
pipeline for most of the lines. Also for one or more combination, a cancellation or reduction in
the magnitude of the induced voltage is observed. Therefore, for installing metallic structures
such as pipelines in the energy utility corridor consisting of a multi-circuit high voltage power
transmission lines, the effect of the phase transposition of these lines must be taken into
consideration to limit the danger that might occur due to shock hazard to personnel touching an
exposed part of these metallic structure. The number of circuits on a power transmission line is
also known to have a greater effect on the induced voltage on metallic pipelines buried near
existing lines.
References
[1] Nelson JP. Power Systems in Close Proximity to Pipelines. IEEE Transactions on Industry
Applications. 1986; 1A-22(3): 435-441.
[2] Adedeji KB, Ponnle AA, Abe BT, Jimoh AA. Analysis of the Induced Voltage on Buried Pipeline in the
Vicinity of High AC Voltage Overhead Transmission Lines. Proceedings of the 23
rd
Southern African
Universities Power Engineering Conference (SAUPEC), Johannesburg. 2015: 7-12.
[3] Satsios KJ, Labridis DP, Dokopoulos PS. The Influence of Nonhomogeneous Earth on the Inductive
Interference Caused to Telecommunication Cables by Nearby AC Electric Traction Lines. IEEE
Transactions on Power Delivery. 2000; 15(3): 1016-1021.
[4] Christoforidis GC, Labridis DP, Dokopoulos PS. Inductive Interference Calculation on Imperfect
Coated Pipelines due to Nearby Faulted Parallel Transmission Lines. Electric Power Systems
Research. 2003; 66: 139-148.
[5] Christoforidis GC, Labridis DP, Dokopoulos PS. A Hybrid Method for Calculating the Inductive
Interference Caused by Faulted Power Lines to Nearby Buried Pipelines. IEEE Transactions on
Power Delivery. 2005; 20(2): 1465-1473.
[6] Christoforidis GC, Labridis DP, Dokopoulos PS. Inductive Interference on Pipelines Buried in
Multilayer Soil due to Magnetic Fields from Nearby Faulted Power Lines. IEEE Transactions on
Electromagnetic Compatibility. 2005; 47(2): 254-262.
[7] Kopsidas K, Cotton I. Induced Voltages on Long Aerial and Buried Pipelines due to Transmission
Line Transients. IEEE Transactions on Power Delivery. 2008; 23(3): 1535-1543.
[8] Al-badi A, Ghania SM, El-saadany EF. Prediction of Metallic Conductor Voltage Owing to
Electromagnetic Coupling Using Neuro Fuzzy Modelling. IEEE Transactions on Power Delivery.
2009; 24(1): 319-327.
[9] Qi L, Yuan H, Wu Y, Cui X. Calculation of Overvoltage on Nearby Underground Metal Pipeline due to
the Lightning Strike on UHV AC Transmission Line Tower. Electric Power Systems Research. 2013;
94: 54-63.
-200 -150 -100 -50 0 50 100 150 200
0
10
20
30
40
50
60
70
Pipeline position across the transmission line (m)
Inducedvoltage(V)
Induced voltage on the pipeline due to multi-circuits power transmission line
Due to double circuits
Due to three circuits
Due to four circuits
IJEEI ISSN: 2089-3272 
Effect of HVTL Phase Transposition on Pipelines Induced Voltage (Adedeji Kazeem B)
101
[10] Ouadah MH, Zergoug M. Analysis of the Electromagnetic Interferences between Overhead Power
Lines and Buried Pipelines. Mediterranean Journal of Modelling and Simulation. 2014; 01: 13-23.
[11] Vakilian M, Valadkhani K, Shaigan A, Nasiri A, Gharagozlo H. A Method for Evaluation and Mitigation
of AC Induced Voltage on Buried Gas Pipelines. Scientia Iranica. 2002; 9(4): 311-320.
[12] Shwehdi M, Al-Qahtani B. Cost Effective Mitigation Study of Electromagnetic Interference by Power
Lines on Neighboring Gas Pipeline. CIGRE C4 Colloquium on Lightning and Power System. Kuala
Lumpur. 16-19
th
May, 2010: 11-17.
[13] Southey R, Dawalibi F, Vukonich W. Recent Advances in the Mitigation of AC Voltages Occurring in
Pipelines Located Close to Electric Transmission Lines. IEEE Transactions on Power Delivery. 1994;
9(2): 1090-1097.
[14] Hossam-Eldin A, Mokhtar W, Ali EM. Effect of Electromagnetic Fields from Power Lines on Metallic
Objects and Human Bodies. International Journal of Electromagnetics and Applications. 2012; 2(6):
151-158.
[15] Richard WB. The Effect of Overhead AC Power Line Paralleling Ductile Iron Pipelines. Ductile Iron
Pipe Research Association, Birmingham. 1997: 1-8.
[16] Jiang Z, Du Y, Lu M, Zhang Y, Tang D, Dong L. New Findings on the Factors Accelerating AC
Corrosion of Buried Pipelines. Corrosion Science. 2014; 81: 1-10.
[17] Fu A, Cheng Y. Effect of Alternating Current on Corrosion and Effectiveness of Cathodic Protection of
Pipelines. Canadian Metallurgical Quarterly. 2012; 51(1):81-90.
[18] Goidanich S, Lazzari L, Ormellese M. AC Corrosion-Part 1: Effects on Overpotentials of Anodic and
Cathodic Processes. Corrosion Science. 2010; 52(2):491-497.
[19] Goidanich S, Lazzari L, Ormellese M. AC Corrosion-Part 2: Parameters Influencing Corrosion Rate.
Corrosion science. 2010; 52(3): 916-922.
[20] Gregoor R, Pourbaix A, Carpentiers P. Detection of AC Corrosion. In: CEOCOR Congress. Biarritz,
France. 2001; 2: 1-14.
[21] NACE RP0177. Mitigation of Alternating Current and Lightning Effects on Metallic Structures and
Corrosion Control Systems. NACE International Standard Practice. Houston, Texas. 2007.
[22] Ponnle AA, Adedeji KB, Abe BT, Jimoh AA. Spatial Magnetic Field Polarization below Balanced
Double-Circuit Linear Configured Power Lines for Six Phase Arrangements. Proceedings of the
ACEMP-OPTIM-ELECTROMOTION Joint Conference. Side, Turkey. 2015: 163-169.
[23] Ponnle AA, Adedeji KB, Abe BT, Jimoh AA. Planar Magnetic Field Distribution Underneath Two-
circuit Linear Configured Power Lines in Various Phase Arrangement. Proceedings of the 12
th
IEEE
AFRICON International Conference. Addis Ababa. 2015: 777-781.
[24] Mazzanti G. The Role Played by Current Phase-shift on Magnetic Field Established by Double-circuit
Overhead Transmission Lines-Part I: Static Analysis. IEEE Transactions on Power Delivery. 2006;
21(2): 939-948.
[25] Mazzanti G. The Role Played by Current Phase-shift on Magnetic Field Established by Double-circuit
Overhead Transmission Lines-Part II: Dynamic Analysis. IEEE Transactions on Power Delivery.
2006; 21(2): 949-958.
[26] Mazzanti G, Landini M, Kandia E, Sandrolini L. Simple Calculation Method of the Magnetic Field from
Double-circuit Twisted Three-phase Cables as a Tool for Fault Detection. Proceedings of 8
th
IEEE
Symposium on Diagnostics for Electrical Machines, Power Electronics and Drives (IEEE/SDEMPED
2011). Bologna. 2011.
[27] Carson J.R. Wave Propagation in Overhead Wires with Ground Return. Bell System Technical
Journal. 1926; 5: 539-554.
[28] Tleis N. Power Systems Modelling and Fault Analysis: Theory and Practice. Newnes: Oxford, UK.
2008: 83-85.
[29] Benato R, Dambone Sessa S, Guglielmi F. Determination of Steady-state and Faulty Regimes of
Overhead Lines by means of Multiconductor Cell Analysis (MCA). Energies. 2012; 5(8): 2771-2793.
[30] Djekidel R, Mahi D. Calculation and Analysis of Inductive Coupling Effects for HV Transmission Lines
on Aerial Pipelines. Przeglad Elektrotechniczny. 2014; 90(9): 151- 156.

More Related Content

What's hot

ACSR Overhead Transmission lines Modeling Considering Sag-Tension Estimation ...
ACSR Overhead Transmission lines Modeling Considering Sag-Tension Estimation ...ACSR Overhead Transmission lines Modeling Considering Sag-Tension Estimation ...
ACSR Overhead Transmission lines Modeling Considering Sag-Tension Estimation ...
IJCSIS Research Publications
 
Lecture 09 transmission lines
Lecture 09   transmission linesLecture 09   transmission lines
Lecture 09 transmission lines
bhaavan22
 
EE8402 Transmission and Distribution
EE8402 Transmission and DistributionEE8402 Transmission and Distribution
EE8402 Transmission and Distribution
rmkceteee
 
Study and Analysis of Insulator used in Substation
Study and Analysis of Insulator used in SubstationStudy and Analysis of Insulator used in Substation
Study and Analysis of Insulator used in Substation
ijtsrd
 
Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...
Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...
Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...
ijtsrd
 
Darkawi_et_al_CEIDP_2012_VF_IEEE
Darkawi_et_al_CEIDP_2012_VF_IEEEDarkawi_et_al_CEIDP_2012_VF_IEEE
Darkawi_et_al_CEIDP_2012_VF_IEEE
Abdallah Darkawi
 
Ppt of ehv ac transmission
Ppt of ehv ac transmissionPpt of ehv ac transmission
Ppt of ehv ac transmission
Sumit Kumar
 

What's hot (20)

Design of 230 kV Twin Bundle Double Circuit Overhead Transmission Line
Design of 230 kV Twin Bundle Double Circuit Overhead Transmission LineDesign of 230 kV Twin Bundle Double Circuit Overhead Transmission Line
Design of 230 kV Twin Bundle Double Circuit Overhead Transmission Line
 
Reducing Induced Voltages on Parallel Facilities in Shared Transmission Corri...
Reducing Induced Voltages on Parallel Facilities in Shared Transmission Corri...Reducing Induced Voltages on Parallel Facilities in Shared Transmission Corri...
Reducing Induced Voltages on Parallel Facilities in Shared Transmission Corri...
 
O.H.T.L PRESENTATION ATIK
O.H.T.L PRESENTATION ATIKO.H.T.L PRESENTATION ATIK
O.H.T.L PRESENTATION ATIK
 
ACSR Overhead Transmission lines Modeling Considering Sag-Tension Estimation ...
ACSR Overhead Transmission lines Modeling Considering Sag-Tension Estimation ...ACSR Overhead Transmission lines Modeling Considering Sag-Tension Estimation ...
ACSR Overhead Transmission lines Modeling Considering Sag-Tension Estimation ...
 
Lecture 09 transmission lines
Lecture 09   transmission linesLecture 09   transmission lines
Lecture 09 transmission lines
 
Predictive Direct Power Control (PDPC) of Grid-connected Dual-active Bridge M...
Predictive Direct Power Control (PDPC) of Grid-connected Dual-active Bridge M...Predictive Direct Power Control (PDPC) of Grid-connected Dual-active Bridge M...
Predictive Direct Power Control (PDPC) of Grid-connected Dual-active Bridge M...
 
EE8402 Transmission and Distribution
EE8402 Transmission and DistributionEE8402 Transmission and Distribution
EE8402 Transmission and Distribution
 
Seismic response of transmission tower a case study
Seismic response of transmission tower   a case studySeismic response of transmission tower   a case study
Seismic response of transmission tower a case study
 
Effects on transmission line
Effects on transmission lineEffects on transmission line
Effects on transmission line
 
Electric power grid
Electric power gridElectric power grid
Electric power grid
 
Transmission Line
Transmission LineTransmission Line
Transmission Line
 
Study and Analysis of Insulator used in Substation
Study and Analysis of Insulator used in SubstationStudy and Analysis of Insulator used in Substation
Study and Analysis of Insulator used in Substation
 
Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...
Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...
Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...
 
Types of transmission lines
Types of transmission linesTypes of transmission lines
Types of transmission lines
 
Presentation topic is transmission line
Presentation topic is transmission linePresentation topic is transmission line
Presentation topic is transmission line
 
EHV AC
EHV ACEHV AC
EHV AC
 
Overhead line work ppt
Overhead line work pptOverhead line work ppt
Overhead line work ppt
 
Darkawi_et_al_CEIDP_2012_VF_IEEE
Darkawi_et_al_CEIDP_2012_VF_IEEEDarkawi_et_al_CEIDP_2012_VF_IEEE
Darkawi_et_al_CEIDP_2012_VF_IEEE
 
Transmission lines
Transmission linesTransmission lines
Transmission lines
 
Ppt of ehv ac transmission
Ppt of ehv ac transmissionPpt of ehv ac transmission
Ppt of ehv ac transmission
 

Similar to Effect of HVTL Phase Transposition on Pipelines Induced Voltage

Power transmission lines electromagnetic pollution with consideration of soil...
Power transmission lines electromagnetic pollution with consideration of soil...Power transmission lines electromagnetic pollution with consideration of soil...
Power transmission lines electromagnetic pollution with consideration of soil...
TELKOMNIKA JOURNAL
 
Describe the foration of corona and discus thr factorz which affect corona loss
Describe the foration of corona and discus thr factorz  which affect corona lossDescribe the foration of corona and discus thr factorz  which affect corona loss
Describe the foration of corona and discus thr factorz which affect corona loss
Engr Nazeer Jasser
 
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
IJAPEJOURNAL
 

Similar to Effect of HVTL Phase Transposition on Pipelines Induced Voltage (20)

26 15059 conductive ijeecs 1570310622(edit)
26 15059 conductive ijeecs 1570310622(edit)26 15059 conductive ijeecs 1570310622(edit)
26 15059 conductive ijeecs 1570310622(edit)
 
Lightning protection for overhead distribution lines
Lightning protection for overhead distribution linesLightning protection for overhead distribution lines
Lightning protection for overhead distribution lines
 
Power transmission lines electromagnetic pollution with consideration of soil...
Power transmission lines electromagnetic pollution with consideration of soil...Power transmission lines electromagnetic pollution with consideration of soil...
Power transmission lines electromagnetic pollution with consideration of soil...
 
Mitigation of high voltage induction effect on ICCP system of gas pipelines: ...
Mitigation of high voltage induction effect on ICCP system of gas pipelines: ...Mitigation of high voltage induction effect on ICCP system of gas pipelines: ...
Mitigation of high voltage induction effect on ICCP system of gas pipelines: ...
 
The electromagnetic interferance caused by high voltage power lines along the...
The electromagnetic interferance caused by high voltage power lines along the...The electromagnetic interferance caused by high voltage power lines along the...
The electromagnetic interferance caused by high voltage power lines along the...
 
New Method for Determination of Inductive Influence of One or More Power Line...
New Method for Determination of Inductive Influence of One or More Power Line...New Method for Determination of Inductive Influence of One or More Power Line...
New Method for Determination of Inductive Influence of One or More Power Line...
 
Application of LFAC { Hz} for electrical power transmission system: a compara...
Application of LFAC { Hz} for electrical power transmission system: a compara...Application of LFAC { Hz} for electrical power transmission system: a compara...
Application of LFAC { Hz} for electrical power transmission system: a compara...
 
Effect of Dew and Raindrops on Electric Field around EHV Transmission Lines
Effect of Dew and Raindrops on Electric Field around EHV Transmission LinesEffect of Dew and Raindrops on Electric Field around EHV Transmission Lines
Effect of Dew and Raindrops on Electric Field around EHV Transmission Lines
 
Effects of Vehicle Running Mode on Rail Potential and Stray Current in DC Mas...
Effects of Vehicle Running Mode on Rail Potential and Stray Current in DC Mas...Effects of Vehicle Running Mode on Rail Potential and Stray Current in DC Mas...
Effects of Vehicle Running Mode on Rail Potential and Stray Current in DC Mas...
 
a review on wpt report (WPT) by Mnzeet report
a review on wpt report (WPT)  by Mnzeet reporta review on wpt report (WPT)  by Mnzeet report
a review on wpt report (WPT) by Mnzeet report
 
Comparative Study of Various Filtering Techniques to Reduce Harmonics in HVDC...
Comparative Study of Various Filtering Techniques to Reduce Harmonics in HVDC...Comparative Study of Various Filtering Techniques to Reduce Harmonics in HVDC...
Comparative Study of Various Filtering Techniques to Reduce Harmonics in HVDC...
 
Transient response of grounding systems under impulse lightning current
Transient response of grounding systems under impulse lightning currentTransient response of grounding systems under impulse lightning current
Transient response of grounding systems under impulse lightning current
 
Distribution of traction return current
Distribution of traction return currentDistribution of traction return current
Distribution of traction return current
 
Describe the foration of corona and discus thr factorz which affect corona loss
Describe the foration of corona and discus thr factorz  which affect corona lossDescribe the foration of corona and discus thr factorz  which affect corona loss
Describe the foration of corona and discus thr factorz which affect corona loss
 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy SystemPower Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
 
Tes p-122.10-r0 (1)
Tes p-122.10-r0 (1)Tes p-122.10-r0 (1)
Tes p-122.10-r0 (1)
 
Corona1 150423103048-conversion-gate02
Corona1 150423103048-conversion-gate02Corona1 150423103048-conversion-gate02
Corona1 150423103048-conversion-gate02
 
Corona1
Corona1Corona1
Corona1
 
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
 

More from ijeei-iaes

More from ijeei-iaes (20)

An Heterogeneous Population-Based Genetic Algorithm for Data Clustering
An Heterogeneous Population-Based Genetic Algorithm for Data ClusteringAn Heterogeneous Population-Based Genetic Algorithm for Data Clustering
An Heterogeneous Population-Based Genetic Algorithm for Data Clustering
 
Development of a Wireless Sensors Network for Greenhouse Monitoring and Control
Development of a Wireless Sensors Network for Greenhouse Monitoring and ControlDevelopment of a Wireless Sensors Network for Greenhouse Monitoring and Control
Development of a Wireless Sensors Network for Greenhouse Monitoring and Control
 
Analysis of Genetic Algorithm for Effective power Delivery and with Best Upsurge
Analysis of Genetic Algorithm for Effective power Delivery and with Best UpsurgeAnalysis of Genetic Algorithm for Effective power Delivery and with Best Upsurge
Analysis of Genetic Algorithm for Effective power Delivery and with Best Upsurge
 
Design for Postplacement Mousing based on GSM in Long-Distance
Design for Postplacement Mousing based on GSM in Long-DistanceDesign for Postplacement Mousing based on GSM in Long-Distance
Design for Postplacement Mousing based on GSM in Long-Distance
 
Investigation of TTMC-SVPWM Strategies for Diode Clamped and Cascaded H-bridg...
Investigation of TTMC-SVPWM Strategies for Diode Clamped and Cascaded H-bridg...Investigation of TTMC-SVPWM Strategies for Diode Clamped and Cascaded H-bridg...
Investigation of TTMC-SVPWM Strategies for Diode Clamped and Cascaded H-bridg...
 
Optimal Power Flow with Reactive Power Compensation for Cost And Loss Minimiz...
Optimal Power Flow with Reactive Power Compensation for Cost And Loss Minimiz...Optimal Power Flow with Reactive Power Compensation for Cost And Loss Minimiz...
Optimal Power Flow with Reactive Power Compensation for Cost And Loss Minimiz...
 
Mitigation of Power Quality Problems Using Custom Power Devices: A Review
Mitigation of Power Quality Problems Using Custom Power Devices: A ReviewMitigation of Power Quality Problems Using Custom Power Devices: A Review
Mitigation of Power Quality Problems Using Custom Power Devices: A Review
 
Comparison of Dynamic Stability Response of A SMIB with PI and Fuzzy Controll...
Comparison of Dynamic Stability Response of A SMIB with PI and Fuzzy Controll...Comparison of Dynamic Stability Response of A SMIB with PI and Fuzzy Controll...
Comparison of Dynamic Stability Response of A SMIB with PI and Fuzzy Controll...
 
Embellished Particle Swarm Optimization Algorithm for Solving Reactive Power ...
Embellished Particle Swarm Optimization Algorithm for Solving Reactive Power ...Embellished Particle Swarm Optimization Algorithm for Solving Reactive Power ...
Embellished Particle Swarm Optimization Algorithm for Solving Reactive Power ...
 
Intelligent Management on the Home Consumers with Zero Energy Consumption
Intelligent Management on the Home Consumers with Zero Energy ConsumptionIntelligent Management on the Home Consumers with Zero Energy Consumption
Intelligent Management on the Home Consumers with Zero Energy Consumption
 
Analysing Transportation Data with Open Source Big Data Analytic Tools
Analysing Transportation Data with Open Source Big Data Analytic ToolsAnalysing Transportation Data with Open Source Big Data Analytic Tools
Analysing Transportation Data with Open Source Big Data Analytic Tools
 
A Pattern Classification Based approach for Blur Classification
A Pattern Classification Based approach for Blur ClassificationA Pattern Classification Based approach for Blur Classification
A Pattern Classification Based approach for Blur Classification
 
Computing Some Degree-Based Topological Indices of Graphene
Computing Some Degree-Based Topological Indices of GrapheneComputing Some Degree-Based Topological Indices of Graphene
Computing Some Degree-Based Topological Indices of Graphene
 
A Lyapunov Based Approach to Enchance Wind Turbine Stability
A Lyapunov Based Approach to Enchance Wind Turbine StabilityA Lyapunov Based Approach to Enchance Wind Turbine Stability
A Lyapunov Based Approach to Enchance Wind Turbine Stability
 
Fuzzy Control of a Large Crane Structure
Fuzzy Control of a Large Crane StructureFuzzy Control of a Large Crane Structure
Fuzzy Control of a Large Crane Structure
 
Site Diversity Technique Application on Rain Attenuation for Lagos
Site Diversity Technique Application on Rain Attenuation for LagosSite Diversity Technique Application on Rain Attenuation for Lagos
Site Diversity Technique Application on Rain Attenuation for Lagos
 
Impact of Next Generation Cognitive Radio Network on the Wireless Green Eco s...
Impact of Next Generation Cognitive Radio Network on the Wireless Green Eco s...Impact of Next Generation Cognitive Radio Network on the Wireless Green Eco s...
Impact of Next Generation Cognitive Radio Network on the Wireless Green Eco s...
 
Music Recommendation System with User-based and Item-based Collaborative Filt...
Music Recommendation System with User-based and Item-based Collaborative Filt...Music Recommendation System with User-based and Item-based Collaborative Filt...
Music Recommendation System with User-based and Item-based Collaborative Filt...
 
A Real-Time Implementation of Moving Object Action Recognition System Based o...
A Real-Time Implementation of Moving Object Action Recognition System Based o...A Real-Time Implementation of Moving Object Action Recognition System Based o...
A Real-Time Implementation of Moving Object Action Recognition System Based o...
 
Wireless Sensor Network for Radiation Detection
Wireless Sensor Network for Radiation DetectionWireless Sensor Network for Radiation Detection
Wireless Sensor Network for Radiation Detection
 

Recently uploaded

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ssuser89054b
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
Kamal Acharya
 

Recently uploaded (20)

Theory of Time 2024 (Universal Theory for Everything)
Theory of Time 2024 (Universal Theory for Everything)Theory of Time 2024 (Universal Theory for Everything)
Theory of Time 2024 (Universal Theory for Everything)
 
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxOrlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
 
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Basic Electronics for diploma students as per technical education Kerala Syll...
Basic Electronics for diploma students as per technical education Kerala Syll...Basic Electronics for diploma students as per technical education Kerala Syll...
Basic Electronics for diploma students as per technical education Kerala Syll...
 
Computer Networks Basics of Network Devices
Computer Networks  Basics of Network DevicesComputer Networks  Basics of Network Devices
Computer Networks Basics of Network Devices
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
UNIT 4 PTRP final Convergence in probability.pptx
UNIT 4 PTRP final Convergence in probability.pptxUNIT 4 PTRP final Convergence in probability.pptx
UNIT 4 PTRP final Convergence in probability.pptx
 
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
 
Max. shear stress theory-Maximum Shear Stress Theory ​ Maximum Distortional ...
Max. shear stress theory-Maximum Shear Stress Theory ​  Maximum Distortional ...Max. shear stress theory-Maximum Shear Stress Theory ​  Maximum Distortional ...
Max. shear stress theory-Maximum Shear Stress Theory ​ Maximum Distortional ...
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
 
AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech students
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
Computer Graphics Introduction To Curves
Computer Graphics Introduction To CurvesComputer Graphics Introduction To Curves
Computer Graphics Introduction To Curves
 

Effect of HVTL Phase Transposition on Pipelines Induced Voltage

  • 1. Indonesian Journal of Electrical Engineering and Informatics (IJEEI) Vol. 4, No. 2, June 2016, pp. 93~101 ISSN: 2089-3272, DOI: 10.11591/ijeei.v4i2.209  93 Received December 11, 2015; Revised March 16, 2016; Accepted April 8, 2016 Effect of HVTL Phase Transposition on Pipelines Induced Voltage Adedeji Kazeem B Department of Electrical Engineering, Tshwane University of Technology, Pretoria, South Africa. e-mail: kezman0474@yahoo.com Abstract In this work, a study of the effect of the phase conductor transposition for a multi-circuit high voltage power transmission lines on the induced voltage on a buried pipeline was conducted and considered through modelling. The modelling was done applying Carson’s concept of mutual impedances for a double circuit, three circuits and four circuit power transmission line on a buried pipeline. The simulated results obtained showed that the transmission line with un-transposed phase combination has the greater effect on the induced voltage while for the one or more of the other combinations, a cancellation or reduction can occur. This also is dependent on the tower geometry and the relative position of the pipeline and the transmission line. Also, the magnitude of the induced voltage increases with increasing number of circuits. Keywords: AC interference, Inductive coupling, Induce voltage, Phase transposition, pipelines, Transmission lines 1. Introduction As a result of the ever increasing cost of right of way suitable for transmission line and pipelines, coupled with environmental factors to protect nature and wildlife, there are more tendencies of installing pipelines near an existing power transmission lines. The current flowing through this transmission line phase conductors produces a time-varying magnetic field which couples to metallic structures in its right of way as shown in Figure 1. Figure 1. Coupling from a high voltage power transmission line on a buried pipeline As a result of this coupling, voltage is induced in such structure. The induction can occur under both steady state and fault condition of the power transmission line [1, 2]. The interference from a high voltage power transmission line and a neighbouring pipeline can occur due to inductive, conductive and capacitive coupling [3-10]. Inductive coupling affects both aerial and underground pipelines that run parallel to or at an angle with a power transmission line while capacitive coupling only affects metallic structures located above the ground [8, 9]. In this type of coupling (capacitive coupling), “the pipeline picks up a voltage relative to the soil, which is proportional to the voltage on the transmission line [11, 12]. For structures located below the earth’s surface, the effect of capacitive coupling is negligible because of the screening effect of the earth against electric fields. The resistive coupling between a transmission line and a nearby buried pipeline is only relevant during ground faults where Indonesian Journal of Electrical Engineering and Informatics (IJEEI) Vol. 4, No. 2, June 2016, pp. 93~101 ISSN: 2089-3272, DOI: 10.11591/ijeei.v4i2.209  93 Received December 11, 2015; Revised March 16, 2016; Accepted April 8, 2016 Effect of HVTL Phase Transposition on Pipelines Induced Voltage Adedeji Kazeem B Department of Electrical Engineering, Tshwane University of Technology, Pretoria, South Africa. e-mail: kezman0474@yahoo.com Abstract In this work, a study of the effect of the phase conductor transposition for a multi-circuit high voltage power transmission lines on the induced voltage on a buried pipeline was conducted and considered through modelling. The modelling was done applying Carson’s concept of mutual impedances for a double circuit, three circuits and four circuit power transmission line on a buried pipeline. The simulated results obtained showed that the transmission line with un-transposed phase combination has the greater effect on the induced voltage while for the one or more of the other combinations, a cancellation or reduction can occur. This also is dependent on the tower geometry and the relative position of the pipeline and the transmission line. Also, the magnitude of the induced voltage increases with increasing number of circuits. Keywords: AC interference, Inductive coupling, Induce voltage, Phase transposition, pipelines, Transmission lines 1. Introduction As a result of the ever increasing cost of right of way suitable for transmission line and pipelines, coupled with environmental factors to protect nature and wildlife, there are more tendencies of installing pipelines near an existing power transmission lines. The current flowing through this transmission line phase conductors produces a time-varying magnetic field which couples to metallic structures in its right of way as shown in Figure 1. Figure 1. Coupling from a high voltage power transmission line on a buried pipeline As a result of this coupling, voltage is induced in such structure. The induction can occur under both steady state and fault condition of the power transmission line [1, 2]. The interference from a high voltage power transmission line and a neighbouring pipeline can occur due to inductive, conductive and capacitive coupling [3-10]. Inductive coupling affects both aerial and underground pipelines that run parallel to or at an angle with a power transmission line while capacitive coupling only affects metallic structures located above the ground [8, 9]. In this type of coupling (capacitive coupling), “the pipeline picks up a voltage relative to the soil, which is proportional to the voltage on the transmission line [11, 12]. For structures located below the earth’s surface, the effect of capacitive coupling is negligible because of the screening effect of the earth against electric fields. The resistive coupling between a transmission line and a nearby buried pipeline is only relevant during ground faults where Indonesian Journal of Electrical Engineering and Informatics (IJEEI) Vol. 4, No. 2, June 2016, pp. 93~101 ISSN: 2089-3272, DOI: 10.11591/ijeei.v4i2.209  93 Received December 11, 2015; Revised March 16, 2016; Accepted April 8, 2016 Effect of HVTL Phase Transposition on Pipelines Induced Voltage Adedeji Kazeem B Department of Electrical Engineering, Tshwane University of Technology, Pretoria, South Africa. e-mail: kezman0474@yahoo.com Abstract In this work, a study of the effect of the phase conductor transposition for a multi-circuit high voltage power transmission lines on the induced voltage on a buried pipeline was conducted and considered through modelling. The modelling was done applying Carson’s concept of mutual impedances for a double circuit, three circuits and four circuit power transmission line on a buried pipeline. The simulated results obtained showed that the transmission line with un-transposed phase combination has the greater effect on the induced voltage while for the one or more of the other combinations, a cancellation or reduction can occur. This also is dependent on the tower geometry and the relative position of the pipeline and the transmission line. Also, the magnitude of the induced voltage increases with increasing number of circuits. Keywords: AC interference, Inductive coupling, Induce voltage, Phase transposition, pipelines, Transmission lines 1. Introduction As a result of the ever increasing cost of right of way suitable for transmission line and pipelines, coupled with environmental factors to protect nature and wildlife, there are more tendencies of installing pipelines near an existing power transmission lines. The current flowing through this transmission line phase conductors produces a time-varying magnetic field which couples to metallic structures in its right of way as shown in Figure 1. Figure 1. Coupling from a high voltage power transmission line on a buried pipeline As a result of this coupling, voltage is induced in such structure. The induction can occur under both steady state and fault condition of the power transmission line [1, 2]. The interference from a high voltage power transmission line and a neighbouring pipeline can occur due to inductive, conductive and capacitive coupling [3-10]. Inductive coupling affects both aerial and underground pipelines that run parallel to or at an angle with a power transmission line while capacitive coupling only affects metallic structures located above the ground [8, 9]. In this type of coupling (capacitive coupling), “the pipeline picks up a voltage relative to the soil, which is proportional to the voltage on the transmission line [11, 12]. For structures located below the earth’s surface, the effect of capacitive coupling is negligible because of the screening effect of the earth against electric fields. The resistive coupling between a transmission line and a nearby buried pipeline is only relevant during ground faults where
  • 2.  ISSN: 2089-3272 IJEEI Vol. 4, No. 2, June 2016 : 93 – 101 94 significant levels of current flows into the ground [7, 13, 14]. Irrespective of the type of coupling, buried pipeline experience induction through any of these coupling or a combination of them which can pose danger to personnel working on the pipeline and can also compromise the materials of the pipe. The interference from the power transmission lines on buried pipelines which varies with the electrical characteristics and geometry of the individual system [15], is also known to accelerate the corrosion process of pipelines [16-19]. AC corrosion case histories can be traced back to 1970 when cathodically protected pipeline was found perforated in Germany, as a result of AC interfering with the pipeline [20], thereby accelerating the corrosion process. In particular, there have been increasing reports of AC induced corrosion and failure of pipelines in recent years, drawing attention to this important problem. This problem has been a threat to the integrity of pipeline and therefore became a major topic of discussion among authors around the world. The subject has become more important for safety of personnel and prevention of pipeline from corrosion. Thereafter, NACE recommended that for safety of personnel working on the pipeline, the steady state induced potential should be considered dangerous and be mitigated if the measured or calculated potential on the pipeline exceeds 15 Vr.m.s [21]. Furthermore, because of the increasing growth of energy demand and to ensure adequate supply of electric power and to cater for losses on the line, more multi-circuits, power transmission line is being used to transmit power for several kilometres across the Nation. The phase conductors of these multi-circuit lines are not always symmetrical, allowing for phase transpositions of the first circuit with respect to the other. The relative position of each phase with respect to the other is known to affect the magnetic field produced by the line current and can cause a drastic reduction in the magnetic field which in turn will have the effect of the voltage induced on buried metallic structure in this energy utility corridor. To ensure safety of the personnel touching the exposed part of the buried structure, the worst-case phase transposition which will give a minimal inductive effect on metallic structures needed to be obtained for the multi-circuits lines. Pipeline being installed near an existing high voltage power transmission line is subject to inductive coupling from the line as a result of the time varying magnetic field produced by the transmission line current. The strength of the coupling depends, among other factors, on the relative position of the pipeline and the transmission line phase conductors. Different research works in the past and in recent times, have worked on the effect of the transmission line phase conductor combination [22, 23] and phase shifts [24-26] on the magnetic field produced by the line. However, the effect of this phase transposition/combination on the induced voltage on pipelines for safety of personnel and protection of pipelines from corrosion has not been fully covered yet. This work annexes the effect of the phase transposition of a multi-circuit power transmission lines on the induced voltage on buried steel pipeline, using one of the Rand Water sites, South Africa as a case study. In a double-circuit power transmission line, there are six possible phase combination/transposition of the first circuit with respect to the other as shown Figure 2. These phase transpositions are RWB-RWB, RWB-BWR, RWB-BRW, RWB-WRB, RWB-RBW, and RWB-WBR as shown in Figure 2. Figure 2. Possible phase transposition of a double circuit power transmission line Assuming identical phase conductor characteristics and steady state current in each circuit with a different phase combination, the worst case phase transposition can be obtained which will be useful in designing AC mitigation system accordingly and reduce the danger of  ISSN: 2089-3272 IJEEI Vol. 4, No. 2, June 2016 : 93 – 101 94 significant levels of current flows into the ground [7, 13, 14]. Irrespective of the type of coupling, buried pipeline experience induction through any of these coupling or a combination of them which can pose danger to personnel working on the pipeline and can also compromise the materials of the pipe. The interference from the power transmission lines on buried pipelines which varies with the electrical characteristics and geometry of the individual system [15], is also known to accelerate the corrosion process of pipelines [16-19]. AC corrosion case histories can be traced back to 1970 when cathodically protected pipeline was found perforated in Germany, as a result of AC interfering with the pipeline [20], thereby accelerating the corrosion process. In particular, there have been increasing reports of AC induced corrosion and failure of pipelines in recent years, drawing attention to this important problem. This problem has been a threat to the integrity of pipeline and therefore became a major topic of discussion among authors around the world. The subject has become more important for safety of personnel and prevention of pipeline from corrosion. Thereafter, NACE recommended that for safety of personnel working on the pipeline, the steady state induced potential should be considered dangerous and be mitigated if the measured or calculated potential on the pipeline exceeds 15 Vr.m.s [21]. Furthermore, because of the increasing growth of energy demand and to ensure adequate supply of electric power and to cater for losses on the line, more multi-circuits, power transmission line is being used to transmit power for several kilometres across the Nation. The phase conductors of these multi-circuit lines are not always symmetrical, allowing for phase transpositions of the first circuit with respect to the other. The relative position of each phase with respect to the other is known to affect the magnetic field produced by the line current and can cause a drastic reduction in the magnetic field which in turn will have the effect of the voltage induced on buried metallic structure in this energy utility corridor. To ensure safety of the personnel touching the exposed part of the buried structure, the worst-case phase transposition which will give a minimal inductive effect on metallic structures needed to be obtained for the multi-circuits lines. Pipeline being installed near an existing high voltage power transmission line is subject to inductive coupling from the line as a result of the time varying magnetic field produced by the transmission line current. The strength of the coupling depends, among other factors, on the relative position of the pipeline and the transmission line phase conductors. Different research works in the past and in recent times, have worked on the effect of the transmission line phase conductor combination [22, 23] and phase shifts [24-26] on the magnetic field produced by the line. However, the effect of this phase transposition/combination on the induced voltage on pipelines for safety of personnel and protection of pipelines from corrosion has not been fully covered yet. This work annexes the effect of the phase transposition of a multi-circuit power transmission lines on the induced voltage on buried steel pipeline, using one of the Rand Water sites, South Africa as a case study. In a double-circuit power transmission line, there are six possible phase combination/transposition of the first circuit with respect to the other as shown Figure 2. These phase transpositions are RWB-RWB, RWB-BWR, RWB-BRW, RWB-WRB, RWB-RBW, and RWB-WBR as shown in Figure 2. Figure 2. Possible phase transposition of a double circuit power transmission line Assuming identical phase conductor characteristics and steady state current in each circuit with a different phase combination, the worst case phase transposition can be obtained which will be useful in designing AC mitigation system accordingly and reduce the danger of  ISSN: 2089-3272 IJEEI Vol. 4, No. 2, June 2016 : 93 – 101 94 significant levels of current flows into the ground [7, 13, 14]. Irrespective of the type of coupling, buried pipeline experience induction through any of these coupling or a combination of them which can pose danger to personnel working on the pipeline and can also compromise the materials of the pipe. The interference from the power transmission lines on buried pipelines which varies with the electrical characteristics and geometry of the individual system [15], is also known to accelerate the corrosion process of pipelines [16-19]. AC corrosion case histories can be traced back to 1970 when cathodically protected pipeline was found perforated in Germany, as a result of AC interfering with the pipeline [20], thereby accelerating the corrosion process. In particular, there have been increasing reports of AC induced corrosion and failure of pipelines in recent years, drawing attention to this important problem. This problem has been a threat to the integrity of pipeline and therefore became a major topic of discussion among authors around the world. The subject has become more important for safety of personnel and prevention of pipeline from corrosion. Thereafter, NACE recommended that for safety of personnel working on the pipeline, the steady state induced potential should be considered dangerous and be mitigated if the measured or calculated potential on the pipeline exceeds 15 Vr.m.s [21]. Furthermore, because of the increasing growth of energy demand and to ensure adequate supply of electric power and to cater for losses on the line, more multi-circuits, power transmission line is being used to transmit power for several kilometres across the Nation. The phase conductors of these multi-circuit lines are not always symmetrical, allowing for phase transpositions of the first circuit with respect to the other. The relative position of each phase with respect to the other is known to affect the magnetic field produced by the line current and can cause a drastic reduction in the magnetic field which in turn will have the effect of the voltage induced on buried metallic structure in this energy utility corridor. To ensure safety of the personnel touching the exposed part of the buried structure, the worst-case phase transposition which will give a minimal inductive effect on metallic structures needed to be obtained for the multi-circuits lines. Pipeline being installed near an existing high voltage power transmission line is subject to inductive coupling from the line as a result of the time varying magnetic field produced by the transmission line current. The strength of the coupling depends, among other factors, on the relative position of the pipeline and the transmission line phase conductors. Different research works in the past and in recent times, have worked on the effect of the transmission line phase conductor combination [22, 23] and phase shifts [24-26] on the magnetic field produced by the line. However, the effect of this phase transposition/combination on the induced voltage on pipelines for safety of personnel and protection of pipelines from corrosion has not been fully covered yet. This work annexes the effect of the phase transposition of a multi-circuit power transmission lines on the induced voltage on buried steel pipeline, using one of the Rand Water sites, South Africa as a case study. In a double-circuit power transmission line, there are six possible phase combination/transposition of the first circuit with respect to the other as shown Figure 2. These phase transpositions are RWB-RWB, RWB-BWR, RWB-BRW, RWB-WRB, RWB-RBW, and RWB-WBR as shown in Figure 2. Figure 2. Possible phase transposition of a double circuit power transmission line Assuming identical phase conductor characteristics and steady state current in each circuit with a different phase combination, the worst case phase transposition can be obtained which will be useful in designing AC mitigation system accordingly and reduce the danger of
  • 3. IJEEI ISSN: 2089-3272  Effect of HVTL Phase Transposition on Pipelines Induced Voltage (Adedeji Kazeem B) 95 shock hazard to personnel. With three or more circuits on a power line, the number of possible combinations to simulate increases. 2. Materials and Method 2.1. Model Description and Evaluation In this work, the effect of the phase conductor transposition of a double-circuit, three- circuit and four circuit power transmission lines on the inductive coupling effect resulting in an induced voltage on a buried steel pipeline was modelled and simulated. Figure 3 and Figure 4 show the schematic diagram and snapshot of the transmission line-pipeline right of way under study. Figure 3. Schematic diagram and snapshot of the transmission line-pipeline right of way (a) double-circuit line (b) three-circuit line Figure 4. Schematic diagram and snapshot of a four-circuit transmission line-pipeline right of way IJEEI ISSN: 2089-3272  Effect of HVTL Phase Transposition on Pipelines Induced Voltage (Adedeji Kazeem B) 95 shock hazard to personnel. With three or more circuits on a power line, the number of possible combinations to simulate increases. 2. Materials and Method 2.1. Model Description and Evaluation In this work, the effect of the phase conductor transposition of a double-circuit, three- circuit and four circuit power transmission lines on the inductive coupling effect resulting in an induced voltage on a buried steel pipeline was modelled and simulated. Figure 3 and Figure 4 show the schematic diagram and snapshot of the transmission line-pipeline right of way under study. Figure 3. Schematic diagram and snapshot of the transmission line-pipeline right of way (a) double-circuit line (b) three-circuit line Figure 4. Schematic diagram and snapshot of a four-circuit transmission line-pipeline right of way IJEEI ISSN: 2089-3272  Effect of HVTL Phase Transposition on Pipelines Induced Voltage (Adedeji Kazeem B) 95 shock hazard to personnel. With three or more circuits on a power line, the number of possible combinations to simulate increases. 2. Materials and Method 2.1. Model Description and Evaluation In this work, the effect of the phase conductor transposition of a double-circuit, three- circuit and four circuit power transmission lines on the inductive coupling effect resulting in an induced voltage on a buried steel pipeline was modelled and simulated. Figure 3 and Figure 4 show the schematic diagram and snapshot of the transmission line-pipeline right of way under study. Figure 3. Schematic diagram and snapshot of the transmission line-pipeline right of way (a) double-circuit line (b) three-circuit line Figure 4. Schematic diagram and snapshot of a four-circuit transmission line-pipeline right of way
  • 4.  ISSN: 2089-3272 IJEEI Vol. 4, No. 2, June 2016 : 93 – 101 96 The simulation was done for the effect of the inductive coupling from these lines on the buried pipeline under steady state operation, using the Carson’s concept of mutual impedance between the transmission line phase/earth wire conductors and the pipeline [27]. Using this concept, the longitudinal induced electromotive force (emf) on the pipeline due to the inductive coupling effect of the transmission line is given by 1 1 1 1 j j j i i i j i i i j i i i j j j j N k k k g p g p g p p R R p R g W W p W g B B p B g i j j jg g g Z Z Z E I Z Z I Z Z I Z Z Z Z Z                                                            (1) where, i and j are positive integers with range of i=1,2,……N, and j=1,2,…k. N represents the number of circuits while k is the number of overhead earth wire on the transmission line. IRi, Iwi and IBi are the steady state current on the i th circuit of the transmission line, ZRip, ZWip and ZBip are the mutual impedances between the R-W-B phase conductor of the i th circuit and the pipeline. More also, Zgjp represents the mutual impedance between the j th earth wire conductor and the pipeline while ZRigj, ZRigj and ZRigj are the mutual impedance between the R-W-B phase conductors of the i th circuit and the j th earth wire. In addition to this, Zgj is the self-impedance of the j th earth wire conductor. The mutual impedance (in Ω/m) between a pipeline p, and an overhead transmission line phase conductor R, W, B or earth wire conductor g, with earth return is evaluated using Equation (2) [28] as 0 0 log 8 2 e pn e pn Z j D                    where n=Ri, Wi, Bi or gj (2) where, µ0 is the magnetic permeability of free space, ω is the angular frequency of operation of the transmission line, δe is the depth of equivalent earth return and Dpn is the geometric mean distances (GMDs) between the pipeline, transmission line phase conductor R-W-B or earth wire conductor g of the i th transmission line circuit. Also, the self-impedance of the j th earth wire conductor transmission line, with earth return is given as 0 0 1 log 8 2 4j j j e g g e GM Z R j R                         (3) In Equation (3), Rgj is the AC resistance of the earth j th wire and RGMj is the geometric mean radius of the earth wire conductors of the transmission line. The depth of equivalent earth return is a function of soil resistivity ρsoil and the transmission line operating frequency f [28-30], evaluated as 658.87 soil e f    (4) The various GMDs between the phase conductors of each circuit and the pipeline or the ground wire for the three case studies are derived from the Powerline-pipeline coordinates system shown in Figure 5.
  • 5. IJEEI ISSN: 2089-3272  Effect of HVTL Phase Transposition on Pipelines Induced Voltage (Adedeji Kazeem B) 97 Figure 5. Powerline-pipeline coordinate system (a) double-circuits, (b) three-circuits (c) four- circuits From Figure 5 (a), the GMD between the R-W-B phase conductors of the i th transmission line circuit and the pipeline is given by             1 2 2 2 1 2 2 2 1 2 2 2 i i i i i i i i i R p p R R p W p p W W p B p p B B p D x x y y D x x y y D x x y y                                 (5) xp, yp, xRi, xWi, xBi; yRi, yWi and yBi are the horizontal and vertical position of the pipeline and the phase conductors of the i th circuit as shown in Figure 5. Also, the GMD between the j th earth wire conductors and the pipeline is given by     1 2 2 2 j j jg p p g g pD x x y y        (6) Other GMDs are derived using the same method. Thereafter, the induced voltage Vp, on the entire parallel exposure length L, of the pipeline is given by p pV E L  (7) 2.2. Case Study Parameter used for Simulation As stated earlier, the effect of phase transposition for three different multi-circuit lines on the induced voltage on an 800 mm diameter pipe buried 1 m beneath the soil surface, was considered. The pipeline was parallel with the transmission line for a length of 1 km. The three phase current on the line were considered under steady state condition with maximum load current of 410 A for zebra typed conductor used in South Africa. The transmission lines operating at 50 Hz, have phase conductors separated at a distance of 6 m from each other with a ground clearance of 12 m. The transmission line overhead earth wires with a 13.48 mm diameter has an AC resistance of 3.44 /km. The earth is assumed to be flat, free from irregularities and homogenous with a resistivity of 100 m. 3. Results and Analysis The induced voltage on a buried steel pipeline due to the inductive coupling effect of the phase conductor transposition of multi-circuits, power transmission lines have been computed and the results presented. Figure 6 shows the effect of the phase transposition of a double- circuit power transmission line on the magnitude of the induced voltage on the pipeline. IJEEI ISSN: 2089-3272  Effect of HVTL Phase Transposition on Pipelines Induced Voltage (Adedeji Kazeem B) 97 Figure 5. Powerline-pipeline coordinate system (a) double-circuits, (b) three-circuits (c) four- circuits From Figure 5 (a), the GMD between the R-W-B phase conductors of the i th transmission line circuit and the pipeline is given by             1 2 2 2 1 2 2 2 1 2 2 2 i i i i i i i i i R p p R R p W p p W W p B p p B B p D x x y y D x x y y D x x y y                                 (5) xp, yp, xRi, xWi, xBi; yRi, yWi and yBi are the horizontal and vertical position of the pipeline and the phase conductors of the i th circuit as shown in Figure 5. Also, the GMD between the j th earth wire conductors and the pipeline is given by     1 2 2 2 j j jg p p g g pD x x y y        (6) Other GMDs are derived using the same method. Thereafter, the induced voltage Vp, on the entire parallel exposure length L, of the pipeline is given by p pV E L  (7) 2.2. Case Study Parameter used for Simulation As stated earlier, the effect of phase transposition for three different multi-circuit lines on the induced voltage on an 800 mm diameter pipe buried 1 m beneath the soil surface, was considered. The pipeline was parallel with the transmission line for a length of 1 km. The three phase current on the line were considered under steady state condition with maximum load current of 410 A for zebra typed conductor used in South Africa. The transmission lines operating at 50 Hz, have phase conductors separated at a distance of 6 m from each other with a ground clearance of 12 m. The transmission line overhead earth wires with a 13.48 mm diameter has an AC resistance of 3.44 /km. The earth is assumed to be flat, free from irregularities and homogenous with a resistivity of 100 m. 3. Results and Analysis The induced voltage on a buried steel pipeline due to the inductive coupling effect of the phase conductor transposition of multi-circuits, power transmission lines have been computed and the results presented. Figure 6 shows the effect of the phase transposition of a double- circuit power transmission line on the magnitude of the induced voltage on the pipeline. IJEEI ISSN: 2089-3272  Effect of HVTL Phase Transposition on Pipelines Induced Voltage (Adedeji Kazeem B) 97 Figure 5. Powerline-pipeline coordinate system (a) double-circuits, (b) three-circuits (c) four- circuits From Figure 5 (a), the GMD between the R-W-B phase conductors of the i th transmission line circuit and the pipeline is given by             1 2 2 2 1 2 2 2 1 2 2 2 i i i i i i i i i R p p R R p W p p W W p B p p B B p D x x y y D x x y y D x x y y                                 (5) xp, yp, xRi, xWi, xBi; yRi, yWi and yBi are the horizontal and vertical position of the pipeline and the phase conductors of the i th circuit as shown in Figure 5. Also, the GMD between the j th earth wire conductors and the pipeline is given by     1 2 2 2 j j jg p p g g pD x x y y        (6) Other GMDs are derived using the same method. Thereafter, the induced voltage Vp, on the entire parallel exposure length L, of the pipeline is given by p pV E L  (7) 2.2. Case Study Parameter used for Simulation As stated earlier, the effect of phase transposition for three different multi-circuit lines on the induced voltage on an 800 mm diameter pipe buried 1 m beneath the soil surface, was considered. The pipeline was parallel with the transmission line for a length of 1 km. The three phase current on the line were considered under steady state condition with maximum load current of 410 A for zebra typed conductor used in South Africa. The transmission lines operating at 50 Hz, have phase conductors separated at a distance of 6 m from each other with a ground clearance of 12 m. The transmission line overhead earth wires with a 13.48 mm diameter has an AC resistance of 3.44 /km. The earth is assumed to be flat, free from irregularities and homogenous with a resistivity of 100 m. 3. Results and Analysis The induced voltage on a buried steel pipeline due to the inductive coupling effect of the phase conductor transposition of multi-circuits, power transmission lines have been computed and the results presented. Figure 6 shows the effect of the phase transposition of a double- circuit power transmission line on the magnitude of the induced voltage on the pipeline.
  • 6.  ISSN: 2089-3272 IJEEI Vol. 4, No. 2, June 2016 : 93 – 101 98 Figure 6. Induced voltage on buried pipeline due to phase transposition of a double-circuit power transmission line Looking at the Figure, it is observed that there is a drastic reduction in the magnitude of the induced voltage for a directly phase transposed, that is, RWB-BWR while for an un- transposed condition, its effect is relatively higher than others phase transposition shown in the Figure. It is also, observed that the directly phase transposed decreases slightly with distance while for another phase transposition, they decreases drastically with increasing distance. Considering Figure 7, a different pattern of results is observed. At some points 15 m beyond the centre line of the transmission line, the phase transposition with RWB-BWR-RWB gives the least inductive effect on the pipeline. However, as the distance increases beyond 50 m, phase combination with RWB-RWB-WBR has the least effect. This pattern of results is obtained due to the phase configuration of this type of transmission line (a combination of horizontal and delta configuration). Figure 7. Induced voltage on buried pipeline due to phase transposition of a three-circuit power transmission line -200 -150 -100 -50 0 50 100 150 200 0 5 10 15 20 25 30 35 40 45 Pipeline position across the transmission line (m) Inducedvoltage(V) Induced voltage on the pipeline due to double circuits power transmission line RWB-RWB RWB-BWR RWB-WRB RWB-BRW RWB-RBW RWB-WBR Phase Transposition -200 -150 -100 -50 0 50 100 150 200 0 5 10 15 20 25 30 Pipeline position across the transmission line (m) InducedVoltage(V) Induced voltage on the pipeline due to three circuts power transmission line RWB-RWB-RWB RWB-BWR-RWB RWB-WRB-RWB RWB-BRW-RWB RWB-RBW-RWB RWB-WBR-RWB RWB-RBW-BWR RWB-WBR-WRB RWB-RWB-BRW RWB-RWB-RBW RWB-RWB-WBR Phase Transposition
  • 7. IJEEI ISSN: 2089-3272  Effect of HVTL Phase Transposition on Pipelines Induced Voltage (Adedeji Kazeem B) 99 In Figure 8, the effect of the transmission line phase conductor transposition on the induced voltage on a pipeline buried near a four-circuit power transmission line is presented. Considering this figure, in line with Figure 6, the un-transposed phase combination has the highest effect while the one with RWB-BWR-RWB-BWR and RWB-RWB-BWR-RWB has the least effect. Some other phase transposition, also gives a little reduction in the magnitude of the induced voltage as shown in Figure 8. Furthermore, symmetrical and asymmetrical nature is observed, as some are symmetrical about the centre line of power transmission line tower while some shows a little offside asymmetry about the centre line. This is related to the results obtained in [23, 24] for magnetic field produced from a multi-circuits line. All the phase combinations decrease drastically with distance up to about 50 m, after which they decrease slightly with increasing distance. Figure 8. Induced voltage on buried pipeline due to phase transposition of a four-circuit power transmission line 3.1. Effects of the Number of Circuits Figure 9 shows the effect of increase in the number of circuits on the induced voltage on the buried pipeline. It is evident from the figure that this increase has a great effect on the induced voltage. The effect is more pronounced on the pipeline at few distances (less than 50 m) from the centre line of the transmission line. However, with increasing distance, the effect reduces gradually to almost a negligible value. -200 -150 -100 -50 0 50 100 150 200 0 10 20 30 40 50 60 70 Pipeline position across the transmission line (m) Inducedvoltage(V) Induced voltage on the pipeline due to four circuts power transmission line RWB-RWB-RWB-RWB RWB-BWR-RWB-RWB RWB-WRB-RWB-RWB RWB-BRW-RWB-RWB RWB-RBW-RWB-RWB RWB-WBR-RWB-RWB RWB-RWB-BWR-RWB RWB-RWB-WRB-RWB RWB-RWB-BRW-RWB RWB-RWB-RBW-RWB RWB-RWB-WBR-RWB RWB-RWB-RWB-BWR RWB-RWB-RWB-WRB RWB-RWB-RWB-BRW RWB-RWB-RWB-RBW RWB-RWB-RWB-WBR Phase Transposition
  • 8.  ISSN: 2089-3272 IJEEI Vol. 4, No. 2, June 2016 : 93 – 101 100 Figure 9. Induced voltage on buried pipeline due to multi-circuits power transmission line 4. Conclusion The effect of the phase conductor transposition of a multi-circuit power transmission lines on the magnitude of the induced voltage on a buried steel pipeline have been computed and the simulated results from MATLAB software presented and analysed. It is obvious from these results that phase conductors with a direct phase transposition of the first phase with respect to the other shows a better reduction in the magnitude of the induced voltage on the pipeline for most of the lines. Also for one or more combination, a cancellation or reduction in the magnitude of the induced voltage is observed. Therefore, for installing metallic structures such as pipelines in the energy utility corridor consisting of a multi-circuit high voltage power transmission lines, the effect of the phase transposition of these lines must be taken into consideration to limit the danger that might occur due to shock hazard to personnel touching an exposed part of these metallic structure. The number of circuits on a power transmission line is also known to have a greater effect on the induced voltage on metallic pipelines buried near existing lines. References [1] Nelson JP. Power Systems in Close Proximity to Pipelines. IEEE Transactions on Industry Applications. 1986; 1A-22(3): 435-441. [2] Adedeji KB, Ponnle AA, Abe BT, Jimoh AA. Analysis of the Induced Voltage on Buried Pipeline in the Vicinity of High AC Voltage Overhead Transmission Lines. Proceedings of the 23 rd Southern African Universities Power Engineering Conference (SAUPEC), Johannesburg. 2015: 7-12. [3] Satsios KJ, Labridis DP, Dokopoulos PS. The Influence of Nonhomogeneous Earth on the Inductive Interference Caused to Telecommunication Cables by Nearby AC Electric Traction Lines. IEEE Transactions on Power Delivery. 2000; 15(3): 1016-1021. [4] Christoforidis GC, Labridis DP, Dokopoulos PS. Inductive Interference Calculation on Imperfect Coated Pipelines due to Nearby Faulted Parallel Transmission Lines. Electric Power Systems Research. 2003; 66: 139-148. [5] Christoforidis GC, Labridis DP, Dokopoulos PS. A Hybrid Method for Calculating the Inductive Interference Caused by Faulted Power Lines to Nearby Buried Pipelines. IEEE Transactions on Power Delivery. 2005; 20(2): 1465-1473. [6] Christoforidis GC, Labridis DP, Dokopoulos PS. Inductive Interference on Pipelines Buried in Multilayer Soil due to Magnetic Fields from Nearby Faulted Power Lines. IEEE Transactions on Electromagnetic Compatibility. 2005; 47(2): 254-262. [7] Kopsidas K, Cotton I. Induced Voltages on Long Aerial and Buried Pipelines due to Transmission Line Transients. IEEE Transactions on Power Delivery. 2008; 23(3): 1535-1543. [8] Al-badi A, Ghania SM, El-saadany EF. Prediction of Metallic Conductor Voltage Owing to Electromagnetic Coupling Using Neuro Fuzzy Modelling. IEEE Transactions on Power Delivery. 2009; 24(1): 319-327. [9] Qi L, Yuan H, Wu Y, Cui X. Calculation of Overvoltage on Nearby Underground Metal Pipeline due to the Lightning Strike on UHV AC Transmission Line Tower. Electric Power Systems Research. 2013; 94: 54-63. -200 -150 -100 -50 0 50 100 150 200 0 10 20 30 40 50 60 70 Pipeline position across the transmission line (m) Inducedvoltage(V) Induced voltage on the pipeline due to multi-circuits power transmission line Due to double circuits Due to three circuits Due to four circuits
  • 9. IJEEI ISSN: 2089-3272  Effect of HVTL Phase Transposition on Pipelines Induced Voltage (Adedeji Kazeem B) 101 [10] Ouadah MH, Zergoug M. Analysis of the Electromagnetic Interferences between Overhead Power Lines and Buried Pipelines. Mediterranean Journal of Modelling and Simulation. 2014; 01: 13-23. [11] Vakilian M, Valadkhani K, Shaigan A, Nasiri A, Gharagozlo H. A Method for Evaluation and Mitigation of AC Induced Voltage on Buried Gas Pipelines. Scientia Iranica. 2002; 9(4): 311-320. [12] Shwehdi M, Al-Qahtani B. Cost Effective Mitigation Study of Electromagnetic Interference by Power Lines on Neighboring Gas Pipeline. CIGRE C4 Colloquium on Lightning and Power System. Kuala Lumpur. 16-19 th May, 2010: 11-17. [13] Southey R, Dawalibi F, Vukonich W. Recent Advances in the Mitigation of AC Voltages Occurring in Pipelines Located Close to Electric Transmission Lines. IEEE Transactions on Power Delivery. 1994; 9(2): 1090-1097. [14] Hossam-Eldin A, Mokhtar W, Ali EM. Effect of Electromagnetic Fields from Power Lines on Metallic Objects and Human Bodies. International Journal of Electromagnetics and Applications. 2012; 2(6): 151-158. [15] Richard WB. The Effect of Overhead AC Power Line Paralleling Ductile Iron Pipelines. Ductile Iron Pipe Research Association, Birmingham. 1997: 1-8. [16] Jiang Z, Du Y, Lu M, Zhang Y, Tang D, Dong L. New Findings on the Factors Accelerating AC Corrosion of Buried Pipelines. Corrosion Science. 2014; 81: 1-10. [17] Fu A, Cheng Y. Effect of Alternating Current on Corrosion and Effectiveness of Cathodic Protection of Pipelines. Canadian Metallurgical Quarterly. 2012; 51(1):81-90. [18] Goidanich S, Lazzari L, Ormellese M. AC Corrosion-Part 1: Effects on Overpotentials of Anodic and Cathodic Processes. Corrosion Science. 2010; 52(2):491-497. [19] Goidanich S, Lazzari L, Ormellese M. AC Corrosion-Part 2: Parameters Influencing Corrosion Rate. Corrosion science. 2010; 52(3): 916-922. [20] Gregoor R, Pourbaix A, Carpentiers P. Detection of AC Corrosion. In: CEOCOR Congress. Biarritz, France. 2001; 2: 1-14. [21] NACE RP0177. Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems. NACE International Standard Practice. Houston, Texas. 2007. [22] Ponnle AA, Adedeji KB, Abe BT, Jimoh AA. Spatial Magnetic Field Polarization below Balanced Double-Circuit Linear Configured Power Lines for Six Phase Arrangements. Proceedings of the ACEMP-OPTIM-ELECTROMOTION Joint Conference. Side, Turkey. 2015: 163-169. [23] Ponnle AA, Adedeji KB, Abe BT, Jimoh AA. Planar Magnetic Field Distribution Underneath Two- circuit Linear Configured Power Lines in Various Phase Arrangement. Proceedings of the 12 th IEEE AFRICON International Conference. Addis Ababa. 2015: 777-781. [24] Mazzanti G. The Role Played by Current Phase-shift on Magnetic Field Established by Double-circuit Overhead Transmission Lines-Part I: Static Analysis. IEEE Transactions on Power Delivery. 2006; 21(2): 939-948. [25] Mazzanti G. The Role Played by Current Phase-shift on Magnetic Field Established by Double-circuit Overhead Transmission Lines-Part II: Dynamic Analysis. IEEE Transactions on Power Delivery. 2006; 21(2): 949-958. [26] Mazzanti G, Landini M, Kandia E, Sandrolini L. Simple Calculation Method of the Magnetic Field from Double-circuit Twisted Three-phase Cables as a Tool for Fault Detection. Proceedings of 8 th IEEE Symposium on Diagnostics for Electrical Machines, Power Electronics and Drives (IEEE/SDEMPED 2011). Bologna. 2011. [27] Carson J.R. Wave Propagation in Overhead Wires with Ground Return. Bell System Technical Journal. 1926; 5: 539-554. [28] Tleis N. Power Systems Modelling and Fault Analysis: Theory and Practice. Newnes: Oxford, UK. 2008: 83-85. [29] Benato R, Dambone Sessa S, Guglielmi F. Determination of Steady-state and Faulty Regimes of Overhead Lines by means of Multiconductor Cell Analysis (MCA). Energies. 2012; 5(8): 2771-2793. [30] Djekidel R, Mahi D. Calculation and Analysis of Inductive Coupling Effects for HV Transmission Lines on Aerial Pipelines. Przeglad Elektrotechniczny. 2014; 90(9): 151- 156.