1. Introduction
Due to the accelerated shift towards a carbon-free
electricalenergysystem,thepowersystemischangingin
terms of both planning and operation with an increasing
integration of converter-interfaced renewable generation
at all voltage levels. One area strongly affected by
these changes is power quality where, if not managed
correctly, the result can be equipment mis-operation,
accelerated aging, tripping of plant, loss of production
process, etc. Failure to provide adequate supply quality
can have negative impact on system operators, including
customer complaints, reputational damage, financial
liability and regulatory penalties.
The issue of power quality in power systems is not new,
with some publications dating back to the early 1900s
dealing with distorted waveforms in transmission lines
and their effects on transformers, rotating machines and
telephone interference. Significant efforts were devoted
at that time to investigate, understand and mitigate
their negative effects. Standardisation was introduced
throughout the years to control and limit different power
quality parameters resulting in positive effects.
This picture is changing rapidly. Power systems globally
are experiencing a transition towards decarbonisation of
electricity production through large-scale deployment of
central and distributed renewable energy sources (RES),
which are gradually replacing conventional thermal
plant. The connection of RES to the power system is
mostly achieved using power electronic (PE) converters.
Equipment interfaced through PE-converters can have
both a positive or negative effect on power quality,
depending on the type of disturbance evaluated and the
applied control strategy of the PE-converter [1].
Presently, the understanding of the impact of PE-
converters and some related phenomena is not fully
developed. However, it is widely accepted that the
consequences of degraded power quality can have
severe financial implications and most studies in the US
and Europe point to an excessively high level of cost if
serious problems arise [2]. This paper intends to provide
a high-level summary of power quality issues in this
changing environment and by doing that raise awareness
of the main facets of power quality.
2. Harmonics
Harmonics can be present in voltage and current
waveforms, being defined as “a sinusoidal component of
a periodic wave or quantity having a frequency that is an
integral multiple of the fundamental frequency”. Special
sub-categories exist including interharmonics, defined
as “a sinusoidal component at frequencies that are not
integer multiples” and subharmonics “a sinusoidal
component at frequencies below the fundamental”.
Harmonic distortion is caused by non-linear devices
connected to the power system. Unlike linear devices,
a non-linear device reacts to a perfect sinusoidal voltage
waveform with a distorted current. In Figure 1 harmonic
measurements obtained at a 15 kV busbar in Denmark is
shown. Figure 1 (a) shows the time domain waveform
at the location of the arrow, Figure 1 (b) shows the
frequency domain harmonic decomposition per phase at
the same location and Figures 1 (c) and (d) shows 11th
and 13th single harmonic components as function of time
measured over 3 weeks.
Historically, control of harmonic at all levels has been an
important issue requiring system studies, application of
standards, and implementation of mitigation measures.
The deleterious effects of harmonics have been kept
under control because of this coordinated approach.
Currently, the widespread connection of PE-converters
at all voltage levels is driving new concerns and interest
on the topic of harmonics. Furthermore, the planning
and design methods utilized in the past may need to be
updated as a consequence of the new types of equipment
connected to the power system.
Power Quality Trends in the Transition
to Carbon-Free Electrical Energy System
C. F. FLYTKJAER (DK), B. BADRZADEH (AU), M. BOLLEN (SE), Z. EMIN* (GB),
L. KOCEWIAK (DK), G. LIETZ (DE), S. PERERA (AU),
F. F. DA SILVA (DK), M. VAL ESCUDERO (IE)
*zia.emin@cigre.org>
฀ ฀ ฀ ฀ ฀ ฀ ฀
22
there still exists a margin between the harmonic voltage
distortion at the wall outlet and the prescribed limits [4].
Emphasis on limitation of harmonic emissions is gaining
more attention [5]. This leads to an opposite trend that
harmonic emission of new plant, as a whole, is reduced
due to more strict enforcement of grid code requirements
and to a trend of lower emission at individual equipment
level.At equipment level different control strategies and
converter topology, as for instance multi-level converter,
are utilised with the combined effect of low emission of
harmonics. Also, increased use of more energy efficient
equipment with a resulting low load current implies
that the harmonic contribution of for instance lighting
equipment less of a concern [6].
Concurrent with the connection of more converter-
interfaced equipment, power cables are seeing increased
use at all voltage levels in some countries. Due to the
electrical parameters of the cable, circuit resonance
frequencies may be shifted to lower frequencies which
increases the risk of amplification of pre-existing
harmonics [7], [8], [9]. This phenomenon has been
observed at different voltage levels in several countries,
but it has proved to be especially problematic at higher
voltage levels, where it introduces a limitation on the
share of cable that can be safely installed and operated
without introducing a risk of excessive amplification
of harmonics [10]. An example of amplification of
the 11th order harmonic voltage in a 400 kV substation
in Denmark caused by the commissioning of an 8 km
400 kV cable situated 90 km away from the substation
2.1. Trends and Challenges
It is generally expected that power systems around the
world will experience an increase in harmonic distortion
as the green transition progresses [1], [3]. Today, low-
order harmonics are still the dominant harmonics in
most power systems due to the characteristics of existing
equipment. However, due to advances in technologies,
harmonics generated by modern PE-converters also
include the high-frequency harmonic range (>2 kHz),
and the term supraharmonics is increasingly used to
definethisrangeofharmonics.Aswellastheappearance
of high frequency harmonics, there are also indications
of increased emission of interharmonics and even
harmonics (not necessarily attributed to PE converters),
butacompleteoverviewofthesetrendsremainsmissing.
Drivers for this trend at high and extra high voltage
include not only the integration of RES connected via
PE-converters, but also increased connection of FACTS
controllers, HVDC links and general proliferation of
PE converters in the demand, such as large data centres
and large industrial plants. Also, at lower voltage levels
an increase in harmonic generation is expected, caused
by widespread photovoltaic (PV) generation, usage of
energystorage,electricvehiclecharging/dischargingand
increasing converter-interfaced loads at domestic level.
This can eventually set a limit to the hosting capacity
of the distribution grid for unmitigated installations.
Presently, a recent mapping, including 163 measurement
location in 17 countries, admittedly incomplete but
still giving an indication, shows that at most locations
Figure 1 (a) the time domain waveform at the location of the arrow, (b) the frequency domain harmonic decomposition per phase
at the same location and (c) and (d) shows 11th and 13th single harmonic components as function of time measured over 3 weeks.
฀ ฀ ฀ ฀ ฀ ฀ ฀
23
3. Voltage variation
Thequalityofthevoltagewaveformcanalsobemeasured
in terms of its magnitude and temporal deviations with
respect to the nominal parameters. A distinction can be
made between steady-state values, with an acceptable
variation of ±10% of nominal typically, and short-term
events for which higher deviations are acceptable. In
Figure 3 Excessive voltage oscillations following fault
clearance due to the response of solar farms’ control
systems a fluctuating voltage waveform is presented as
an example.
3.1. Trends and Challenges
Steady state refers to slow variations in the RMS value
ofthevoltagewaveformwhichtakeplacethroughoutthe
day due to gradual customer load variation or variable
RES output. A trend towards larger and more frequent
voltage variations can be expected due to increasing
penetration of intermittent generation resources such as
wind and solar. Such voltage variations can lead to both
under voltage and over voltage where both situations can
have an impact on network operation and on customer
equipment.
In distribution networks, over voltage can lead to excess
energy consumption depending on the type of load, core
saturation of transformers and stressing of insulation
leading to its premature failure. Under voltage can lead
to reduced energy consumption depending on the type
of load, malfunctioning of high-intensity discharge
lamps and reduction of torque developed by mains
connected motors. Undervoltage can also result in
overcurrent, as equipment often consumes a constant
power, with accelerated ageing as a consequence. These
slow variations are normally managed by automatic
or manual control actions taken by the grid controllers
to ensure compliance with statutory voltage quality
standards. However, the increased level of wind and
solar is introducing significant challenges in the design
and operation of these networks.
With the proliferation of rooftop solar PVsystems in low
is shown in Figure 2. The instance of energization is
marked by the arrow in the figure.
The net result of many new harmonics sources being
introduced into the power system but with a decreased
individual harmonic emission is difficult to predict.
Moreover, with local resonance introduced by the use of
cables, it will be difficult to generalise.Atrend towards a
moreprofoundfocustoundertakedetailedanalysisatthe
planning stages, to ensure adherence to statutory limits
and hence secure power system operation is however
manifesting [6].
2.2. Opportunities
The main harmonic countermeasure for many years has
been based on passive filters, usually employed as part
of the development scheme (for example during the
installation of line commutated HVDC schemes).As the
harmonic injection and usage of power cables increases,
this approach is showing its limitations. The resonance
frequencies change when the system evolves and/or
changes,andpassivefiltersinstalledinspecificlocations
might become ineffective. Additionally, the installation
of a passive filter changes the resonance frequencies in
a wide area of the power system, and it might increase
the harmonic distortion in other locations of the grid
[10]. One emerging possibility is active filtering, which
has been successfully used at MV levels, mainly in
connection with large wind and PV farms [11]. Another
possibility is to use PE-converters to actively mitigate
harmonics in the system by means of active harmonic
cancellation, which would be achieved by controlling
the phase angle of the injected harmonics, leading to the
associated cancellation. This level of control has only
been used to a small extend in HVDC but is generally
not possible today, as measurement of the phase angles
of the harmonics presented in the system is typically not
reliable, but it is an interesting area for future research.
A further option is to create a” virtual resistor” using
converter control to deliberately create a counter-voltage
to the load current. This is mostly used in large HVDCs
and not practical in smaller converter-interfaced plants.
Figure 2Amplification of the 11th order harmonic voltage due to the commissioning of an 8 km 400 kV cable.
฀ ฀ ฀ ฀ ฀ ฀ ฀
24
new system services. The objective is to incentivize
wind farm owners to invest in technologies capable of
providing enhanced voltage and reactive power control
performance over and above the minimum grid code
requirements with the introduction of new products
such as Steady State Reactive Power (SRP) [12] - other
countries are following this trend.
Short-term voltage variations refer to rapid
voltage changes and voltage dips, typically caused
by connection and disconnection of loads, network
switching operations, electric arc furnaces, transformer
energization, motor starting and system faults.
One of the main concerns with fast voltage variations
at low voltage levels is the resulting lamp flicker
which can be problematic in distribution systems.
The proliferation of converter-interfaced renewable
generation connections, with intermittent power output,
combined with a reduction in system strength through
displacement of conventional plant, results in a higher
volatility in the system voltage at transmission level.
Therefore, fast voltage variations can now become also
prominent at high voltage levels.
The trend towards reduction in system strength at
transmission levels means that voltage dips, typically
causedbysystemfaults,transformerenergisationorlarge
motorstarting,canbecomemorefrequentandsevereand
will also propagate to downstream distribution networks
[1]. If large shares of converter-interfaced generation
get disconnected from the grid during a voltage dip,
the initial voltage disturbance will evolve into a large
power imbalance introducing a risk to the stability of
the system frequency, which could result in a system
blackout. Fault Ride Through (FRT) requirements for
converter-interfaced generation have been introduced in
many countries to address this challenge. In most grid
codes, these requirements include not only the need to
remain connected during the voltage dip but also the
provision of reactive current in an attempt to support the
system voltage and limit the extent and magnitude of the
disturbance.
Grid-connected converters in modern power systems
are designed to provide specific functionality. Typically,
the voltage and power control loops, as well as the grid
synchronization control, are cascaded with the current
control. The cascaded control system is characterized
voltage distribution systems, already many networks
around the world are experiencing excessive steady
state voltage variation issues when the PV systems are
generating at their peak level during the daytime. These
distribution radial networks were originally designed
to carry power in one direction whereas they now
tend to also operate with a reversed power flow. The
tap settings of the upstream transformers and the line
drop compensation systems were originally designed
assuming upstream to downstream power flow and
are unsuitable to accommodate bi-directional flows in
compliance with statutory limits from a steady state
voltage point of view.
The shift from large centralized conventional plant
to a dispersed renewable generation portfolio also
introduces operational challenges at transmission
level due to the reduction in available controllable
reactive power resources. A compounding factor is the
traditional practice of operating embedded generation
at fixed power factor (normally absorbing reactive
power), which introduces additional challenges in
the absence of reactive power exchange limitations
between transmission and distribution systems (some
geographies do apply limits). In some cases, deployment
of dynamic reactive compensation equipment is required
at transmission level to manage the variable reactive
power demand from downstream distribution networks.
This, however, is normally considered in operational
security frameworks between system operators rather
than as power quality aspects and will not be discussed
in detail in this paper.
Some wind generation technologies have limitations
in the provision of reactive power at low wind speeds,
especially when connected to weak networks. With the
proliferation of long HVAC cables deployed to connect
on-shore and off-shore wind farms to transmission
grids, over-voltages are frequent during periods of
low wind output. This situation gets exacerbated
if passive harmonic filters are installed to manage
harmonic distortion (either active emissions or passive
amplification). Some grid codes address this challenge
with mandatory requirements to provide full reactive
power capability within the entire contracted active
power range. In Ireland an alternative approach has
been adopted through the introduction of a market for
฀ ฀ ฀ ฀ ฀ ฀ ฀
25
and duration of the event, voltage oscillations can in turn
manifest in power quality indices; e.g. as flicker due
to rapid voltage variations. As an example of this new
phenomenon, Figure 3 shows the simulated sustained
voltage oscillations following a credible system
network fault taking out a transmission line being the
key source of system strength support for the inverter-
connected generator under consideration. These types
of oscillations have already been observed in practical
power systems involving two or more inverter-based
resources.An example of measured flicker during a sub-
harmonic interaction event is shown in Figure 4. These
oscillatory responses cause the inverter-based resources
breach of their technical performance requirements.
Undamped and sustained oscillations are inconsistent
with the definition of adequately damped oscillation
and cause short-term flicker levels well in excess of the
maximum permissible level of 1.0 as per [14].
by multiple timescales, whose damping effect is
dependent on the grid strength and operating points. The
combination of low damping in the transmission system,
resonance characteristics in the power system, weak
grid characteristic, and negative damping in converter
frequency response can (but not necessarily) cause
unwanted oscillations within a frequency range defined
by the controller dynamics. Thus, the oscillations can be
basically at any frequency, i.e. harmonic, inter-harmonic
or even sub-synchronous. This new phenomenon is
referred as converter multi-frequency stability and is
the focus of CIGRE Working Group C4.49 [13]. The
continuously expanding utilization of PE-converters
is expected to create new challenges with respect to
performance, interoperability, robustness and stability.
Oscillations between any combination of active and
passive component in the power system will manifest
itself in the system voltage. Depending on the frequency
Figure 3 Excessive voltage oscillations following fault clearance due to the response of
solar farms’control systems
Figure 4 Measured short-term flicker (Pst) level due to an adverse sub-harmonic interaction
฀ ฀ ฀ ฀ ฀ ฀ ฀
26
investment in new functionalities that provide benefits
to the overall power system.
Withregardtonewphenomena,thereareseveralpossible
ways to optimize the power system design and operation
to reduce (or even completely avoid) grid-connected
converter instability and therefore related power quality
issues. One can distinguish four main methods of
converter instability mitigation in power systems:
the robustness,
resonances,
to avoid critical topology changes,
sensitive frequency range.
4. Voltage unbalance
Voltage unbalance is defined as a “condition in a poly-
phase system in which the magnitudes of the phase
voltages and/or the phase angles between consecutive
phase voltages, are not all equal [17]. Such three-phase
unbalanced voltages can be decomposed into three
balanced systems, namely: positive sequence, negative
sequence and zero sequence. For a three-phase system,
thedegreeofunbalanceisgenerallyexpressedastheratio
of the negative- and zero-sequence components to the
positive-sequence component. The negative-sequence
component is normally the main concern considering
the impact on three-phase rotating machinery and hence
unbalanceusuallyreferstonegativesequenceunbalance.
Figure 5 shows actual recorded three phase voltages at
a 150 kV substation measured over a period of 2 weeks
with the corresponding positive sequence voltage,
negativesequencevoltageandvoltageunbalancefactors.
To understand this in practice, the example of a three-
phase induction motor can be used. The positive-
sequence set of voltages will drive the motor in a
particular direction of rotation whereas the negative-
sequence set of voltages will work against this direction
of rotation, as two counter-rotating magnetic fields are
created in the induction motor. Even with a relatively
small negative sequence voltage, the resulting negative
sequence current in a three-phase induction motor can be
showntoberelativelylarge.Asaconsequence,induction
3.2. Opportunities
Low voltage (LV) systems operating at the high end of
the allowable voltage range can lead to increased energy
consumption depending on the types of loads, stressing
of connected equipment and tripping of connected PV
systems thus defeating the purpose of investment of the
PV systems. Compared to older solar PV inverters which
operate at unity power factor, the newer inverters are able
to control the voltage at the point of connection through
reactive power absorption or injection. While such
approachesarenotmandatoryatthispointintimeinmany
countries and the owners of the PV systems would like
to benefit from the maximum real power injection, there
is an opportunity to utilize new equipment capabilities to
support the system in a cost-effective manner.
The network wide deployment of low voltage
STATCOMs which are able to manage the steady state
and dynamic voltages in LV networks are now being
trialed in some countries such asAustralia [15]. Studies
are still required to investigate the effects on the overall
network energy savings by employing such network
wide solutions and the associated incentive schemes
required to drive that investment.
There are also opportunities for enhanced co-ordination
of voltage control strategies and share of reactive
power resources between TSOs and DSOs. Some
interesting examples and proof of concept of co-
ordinated approaches are described in [16], including the
deployment of voltage controllers in large DERs clusters
in Ireland, Spain and Germany.
Most of the challenges associated with integration of
converter-interfaced renewable generation relate to the
displacement of conventional plant and reduction in
available dynamic reactive power resources to provide
voltage regulation. Furthermore, fluctuations in power
output caused by local weather conditions (e.g. wind
speed or sun radiation) can cause additional voltage
variations outside the continuous operational range.
Power electronics, however, can help to mitigate these
issues through fast controls that can respond to voltage
fluctuations or sudden changes in reactive power profile
in less than a cycle. While minimum performance
requirements can be introduced in grid codes to utilize
these new functionalities, there are also opportunities for
the development of new market products to incentivize
฀ ฀ ฀ ฀ ฀ ฀ ฀
27
only single-phase laterals are available, all connections
end up on the same phase which can lead to significant
voltage unbalance levels on three-phase LV systems.
Other technologies that will have an impact include
electric vehicle charging points and heat pumps at the
low voltage level. These will have an increased level
power capacity and are likely to introduce more voltage
unbalance and hence their capacities may be limited
depending on the fault level at the point of connection.
Due to time intermittency of such loads, distributing
them among the available phases is not expected to
lessen the effect substantially.
Large scale wind and solar farms are often connected
at remote locations supplied by relatively long un-
transposed lines, and hence voltage unbalance can arise
due to the lines [19] although the wind or the solar farms
inject balanced currents.
4.2. Opportunities
With single-phase PV connections, their capacities
need to be controlled in comparison to the fault level
at the point of connection and their distribution across
the phases by setting appropriate guidelines, rules
and regulations. These limiting capacities need to be
determined through extensive studies covering typical
networks. An example is shown in [20].
With regard to large solar and wind farm applications
that are connected at the end of relatively long un-
transposed lines, to mitigate or reduce the resulting
voltage unbalance, instead of using dedicated network
STATCOMs, the power electronic inverters within the
motorswillexperienceexcessivestatorandrotorheating,
torque ripple (at twice the supply frequency) and hence
noise and vibration and sometimes leading to premature
failure. For this reason, induction motors need to be
derated under voltage unbalance conditions [18]. A
similar type of impact can take place in synchronous
machines if they are connected to networks with voltage
unbalance, and for this reason limits exist on allowable
network voltage unbalance under both normal and
contingency conditions. Furthermore, voltage unbalance
can also lead to the generation of uncharacteristic
harmonics by three-phase rectifier systems which form
the front end of manyAC variable speed drives.
Voltage unbalance in electricity networks is primarily
caused by asymmetrical three-phase loads, unequal
distribution of single-phase loads (especially in
low voltage distribution systems) and asymmetrical
transmission and distribution lines. The latter is due
to the asymmetry introduced by the electromagnetic
coupling between the different phases on one circuit but
also between two circuits on the same tower or right-
of-way. Although low voltage distribution lines which
are relatively short are not transposed, long high voltage
lines normally are transposed.
4.1. Trend and Challenges
Proliferation of technologies such as photovoltaic
systems at the LV level is taking place as single-phase
connections. Depending on the geographic availability
ofthree-phaseconnections,single-phasePVconnections
can be altered between the phases but in places where
Figure 5 Unbalance between magnitudes of the three phases: (a) phase voltages, (b) positive sequence voltage,
(c) negative sequence voltage and voltage unbalance factor.
฀ ฀ ฀ ฀ ฀ ฀ ฀
28
interfaced intermittent generation resources such as
wind and solar, and response of associated control
systems. Such voltage variations can lead to both under
voltage and over voltage where both situations can
have an impact on network operation and on customer
equipment. Reduced system strength at transmission
level means that voltage dips, typicallycaused by system
faults, transformer energization or large motor starting,
can become more frequent and severe and they will
also propagate to downstream distribution networks.
Intermittent power output, combined with a reduction in
system strength will result in a higher volatility in the
system voltage at transmission level making fast voltage
variations a possible issue.
Proliferationofconverter-interfacedtechnologiessuchas
photovoltaicsystemsatthelowandmediumvoltagelevel
is commonly taking place as single-phase connections.
Single-phase PV connections can be altered between
the phases but in places where only single-phase laterals
are available, all connections end up on the same phase
which can lead to significant voltage unbalance levels
on three-phase low voltage systems. Other converter-
interfaced technologies that will have an impact include
electric vehicle charging points and heat pumps at the
low voltage level. These will have an increased level
power capacity and are likely to introduce more voltage
unbalance and hence their capacities may be limited
depending on the fault level at the point of connection.
Large scale wind and solar farms at transmission level
are often connected at remote locations supplied by
relatively long un-transposed lines, and hence voltage
unbalance can arise due to the lines despite the wind or
the solar farms injecting balanced currents.
6. References
[1] CIGRE TB 719, “Power quality and EMC issues with future
electricity networks”, March 2018, ISBN 978-2-85873-421-4.
[2] R.Targosz, J. Manson, “European Power Quality Survey Report”,
Leonardo ENERGY, European Copper Institute, 2008.
[3] B. Kelly, M. Val Escudero, P. Horan, C. Geaney, A. Martin and
D. Lewis “Investigation of Harmonics Trends and Characteristics
on the Irish Transmission System by analyzing Historical PQ
Measurements and SCADA Records”. CIGRE 2016 Biennial
Session, Paper C4-114.
[4] M.H.J. Bollen. A. Gil de Castro and S.K. Rönnberg, “Typical
harmonic levels and spectra with low-voltage customers”, CIRED
2019.
[5] D. O. Brasil, C. Buchhagen, Z. Emin, C. F. Jensen, L. Soto Cano
solar and wind farms may be able to compensate such
voltage unbalance by injecting appropriate currents.
However, it is important that mitigation of voltage
unbalance through such approaches is not carried out in
isolation without consideration of broader issues.
Substantial single-phase loads such as traction supplies,
can be fed strategically such that the unbalance
introduced by these loads can create a negative-sequence
voltage with an opposing phase angle to that already on
the system, acting like a counterbalance. Additional
compensation can be implemented in the form of
dynamic voltage support such as SVC or STATCOM
that can provide phase-based reactive power.
5. Concluding Remarks
Thepowerqualityinthefuturepowersystemisexpected
to be significantly affected by the shift towards a carbon-
free electrical energy system. Several trends point to
degraded power quality indices of future power systems
duetotheintegrationofmanypowerelectronicsdevices,
use of power cables at all voltage levels, increasing
amount of fluctuating production and generally reduced
system strength. However, with the ability to control
power electronics new possibilities are emerging and
if used correct many of the challenges introduced can
be mitigated by the same components that create them.
Doing so successfully requires high focus on power
quality studies both at individual connection and system
wide level, focus on grid code requirements and their
implementation and robust system monitoring with a
strategic approach.
It is generally expected that power systems around the
world will experience an increase in harmonic distortion
as the green transition progresses. This is partly due to
the sheer number of converter-interfaced equipment
being connected and partly due to possible modification
of existing distortion levels. However, emphasis on
limitation of harmonic emissions is gaining more
attentionanddrivingatrendintheoppositedirection,that
harmonic emission of new plant, as a whole, is reduced
at equipment level due to more advanced switching and
control technologies being implemented and the stricter
enforcement of grid code requirements.
Larger and more frequent voltage variations can be
expected due to increasing penetration of converter-
฀ ฀ ฀ ฀ ฀ ฀ ฀
29
[13] Ł. Kocewiak, Ch. Buchhagen, Y. Sun, X. Wang, G. Lietz and
M. Larsson, “Overview, Status and Outline of the New CIGRE
Working Group C4.49 on Converter Stability in Power Systems,” in
Proc. The 18th
International Workshop on Large-Scale Integration
of Wind Power into Power Systems as well as Transmission
Networks for Offshore Wind Farms, 16-18 October 2019, Dublin,
Ireland.
[14] IEC TR 61000-3-7:2008 Electromagnetic compatibility (EMC) -
Part 3-7: Limits - Assessment of emission limits for the connection
of fluctuating installations to MV, HV and EHV power systems.
[15] https://ecojoule.com/ecovar/
[16] “System Operation Emphasizing DSO/TSO Interaction and
Coordination”. Tutorial presented by CIGRE JWG C2/C6.36.
CIGRE 2018 Biennial Session. 29th
August 2018.
[17] CIGRE TB 261, “Power quality indices and objectives”, October
2004,
[18] IEC 60034-26:2006: Rotating electrical machines - Part 26: Effects
of unbalanced voltages on the performance of three-phase cage
induction motors.
[19] Z. Emin and D. S. Crisford, “Negative Phase-Sequence Voltages
on E&W Transmission System”, IEEE Transaction on Power
Delivery, Vol. 21, No.3, July 2006, pp.1607-1612.
[20] D. Schwanz, F. Möller, S. K. Rönnberg, J. Meyer, and M. H.J.
Bollen, “Stochastic Assessment of Voltage Unbalance due to
Single-Phase-Connected Solar Power”, IEEE Transactions on
Power Delivery, Vol.32, No.2, April 2017, pp.852-861.
and M. Val Escudero, “International comparison of harmonic
assessment approaches and implications”. CIGRE 2018 Biennial
Session, Paper C4-111.
[6] CIGRE TB 766, “Network modelling for harmonic studies,” April
2019, ISBN 978-2-85873-468-9.
[7] C. F. Jensen, Ł. H. Kocewiak and Z. Emin, “Amplification of
Harmonic Background Distortion in Wind Power Plants with
Long High Voltage Connections,” CIGRE 2016 Biennial Session,
Paper C4-112.
[8] C.F. Jensen” Harmonic Background Amplification in Long
Asymmetrical High Voltage Cable Systems”, Electric Power
Systems Research (EPSR) Special IPST 2017 edition
[9] M. Val Escudero, A. Martin, L. Fisher and I. Dudurych, “Technical
Challenges Associated with the Integration of Long HV AC Cables
and Inverter Based Renewable Generation in Weak Transmission
Networks: The Irish Experience”. CIGRE 2018 Biennial Session,
Paper C4-310.
[10] Energinet “Technical issues related to new transmission lines in
Denmark”, 2018.
[11] Ł. H. Kocewiak, B. Laudal Øhlenschlæger Kramer, O. Holmstrøm,
K. Høj Jensen, L. Shuai, “Resonance Damping in Array Cable
Systems by Wind Turbine Active Filtering in Large Offshore Wind
Power Plants,” IET Renewable Power Generation, Vol. 11, Issue 7,
July 2017, pp 1069-1077.
[12] Detailed information about DS3 System Services is
available at http://www.eirgridgroup.com/how-the-grid-works/
ds3-programme/

More Related Content

What's hot

An algorithm for selection and design of hybrid power supplies for MEMS with ...
An algorithm for selection and design of hybrid power supplies for MEMS with ...An algorithm for selection and design of hybrid power supplies for MEMS with ...
An algorithm for selection and design of hybrid power supplies for MEMS with ...
Kimberly Cook-Chennault
 
Modeling and control of HVDC grids: a key challenge for the future power system
Modeling and control of HVDC grids: a key challenge for the future power systemModeling and control of HVDC grids: a key challenge for the future power system
Modeling and control of HVDC grids: a key challenge for the future power system
Power System Operation
 
Informations about energy in hagen, germany
Informations about energy in hagen, germanyInformations about energy in hagen, germany
Informations about energy in hagen, germany
mrshansen
 
Impact of Positive Sequence Admittance and Negative Sequence Conductance of D...
Impact of Positive Sequence Admittance and Negative Sequence Conductance of D...Impact of Positive Sequence Admittance and Negative Sequence Conductance of D...
Impact of Positive Sequence Admittance and Negative Sequence Conductance of D...
ijtsrd
 
Regulatory Guidelines to set up Voltage Quality Monitoring
Regulatory Guidelines to set up Voltage Quality MonitoringRegulatory Guidelines to set up Voltage Quality Monitoring
Regulatory Guidelines to set up Voltage Quality Monitoring
Leonardo ENERGY
 

What's hot (18)

IRJET- Design Constraints of an Radio Frequency Energy Harvesting
IRJET- Design Constraints of an Radio Frequency Energy HarvestingIRJET- Design Constraints of an Radio Frequency Energy Harvesting
IRJET- Design Constraints of an Radio Frequency Energy Harvesting
 
Grid Connected PV System with Power Quality Improvement Using Intelligent Con...
Grid Connected PV System with Power Quality Improvement Using Intelligent Con...Grid Connected PV System with Power Quality Improvement Using Intelligent Con...
Grid Connected PV System with Power Quality Improvement Using Intelligent Con...
 
Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...
 
Protection of Converter Dense Power Systems
Protection of Converter Dense Power Systems Protection of Converter Dense Power Systems
Protection of Converter Dense Power Systems
 
IRJET- Voltage Swells and Transient Research Considering ARC Load
IRJET-  	  Voltage Swells and Transient Research Considering ARC LoadIRJET-  	  Voltage Swells and Transient Research Considering ARC Load
IRJET- Voltage Swells and Transient Research Considering ARC Load
 
Electric09
Electric09Electric09
Electric09
 
High electron mobility transistor
High electron mobility transistorHigh electron mobility transistor
High electron mobility transistor
 
State of the art GAN on Silicon - the grail of power electronics
State of the art   GAN on Silicon  - the grail of power electronicsState of the art   GAN on Silicon  - the grail of power electronics
State of the art GAN on Silicon - the grail of power electronics
 
Two-Stage Power Conversion Architecture Suitable for Wide Range Input Voltage
Two-Stage Power Conversion Architecture Suitable for Wide Range Input VoltageTwo-Stage Power Conversion Architecture Suitable for Wide Range Input Voltage
Two-Stage Power Conversion Architecture Suitable for Wide Range Input Voltage
 
Power loss reduction in radial distribution system by using plant growth simu...
Power loss reduction in radial distribution system by using plant growth simu...Power loss reduction in radial distribution system by using plant growth simu...
Power loss reduction in radial distribution system by using plant growth simu...
 
An algorithm for selection and design of hybrid power supplies for MEMS with ...
An algorithm for selection and design of hybrid power supplies for MEMS with ...An algorithm for selection and design of hybrid power supplies for MEMS with ...
An algorithm for selection and design of hybrid power supplies for MEMS with ...
 
Modeling and control of HVDC grids: a key challenge for the future power system
Modeling and control of HVDC grids: a key challenge for the future power systemModeling and control of HVDC grids: a key challenge for the future power system
Modeling and control of HVDC grids: a key challenge for the future power system
 
Electricpowersystem 111205110736-phpapp01
Electricpowersystem 111205110736-phpapp01Electricpowersystem 111205110736-phpapp01
Electricpowersystem 111205110736-phpapp01
 
Design of Optimal LLCL Filter with an Improved Control Strategy for Single Ph...
Design of Optimal LLCL Filter with an Improved Control Strategy for Single Ph...Design of Optimal LLCL Filter with an Improved Control Strategy for Single Ph...
Design of Optimal LLCL Filter with an Improved Control Strategy for Single Ph...
 
Current Monitoring for Power GaN Transistors-SenseGaN Technique
Current Monitoring for Power GaN Transistors-SenseGaN TechniqueCurrent Monitoring for Power GaN Transistors-SenseGaN Technique
Current Monitoring for Power GaN Transistors-SenseGaN Technique
 
Informations about energy in hagen, germany
Informations about energy in hagen, germanyInformations about energy in hagen, germany
Informations about energy in hagen, germany
 
Impact of Positive Sequence Admittance and Negative Sequence Conductance of D...
Impact of Positive Sequence Admittance and Negative Sequence Conductance of D...Impact of Positive Sequence Admittance and Negative Sequence Conductance of D...
Impact of Positive Sequence Admittance and Negative Sequence Conductance of D...
 
Regulatory Guidelines to set up Voltage Quality Monitoring
Regulatory Guidelines to set up Voltage Quality MonitoringRegulatory Guidelines to set up Voltage Quality Monitoring
Regulatory Guidelines to set up Voltage Quality Monitoring
 

Similar to Power Quality Trends in the Transition to Carbon-Free Electrical Energy System

Power_Electronics_in_Renewable_Energy_Systems.pdf
Power_Electronics_in_Renewable_Energy_Systems.pdfPower_Electronics_in_Renewable_Energy_Systems.pdf
Power_Electronics_in_Renewable_Energy_Systems.pdf
MuammerAlakary
 
A modified bridge-type nonsuperconducting fault current limiter for distribut...
A modified bridge-type nonsuperconducting fault current limiter for distribut...A modified bridge-type nonsuperconducting fault current limiter for distribut...
A modified bridge-type nonsuperconducting fault current limiter for distribut...
International Journal of Power Electronics and Drive Systems
 
Frequency response analysis under faults in weak power systems
Frequency response analysis under faults in weak power  systemsFrequency response analysis under faults in weak power  systems
Frequency response analysis under faults in weak power systems
IJECEIAES
 
Challenges and Benefits of Integrating the Renewable Energy Technologies into...
Challenges and Benefits of Integrating the Renewable Energy Technologies into...Challenges and Benefits of Integrating the Renewable Energy Technologies into...
Challenges and Benefits of Integrating the Renewable Energy Technologies into...
Power System Operation
 
Financial transmission rights
Financial transmission rightsFinancial transmission rights
Financial transmission rights
Springer
 
Grid Integration of Renewables: Challenges and Solutions
Grid Integration of Renewables: Challenges and SolutionsGrid Integration of Renewables: Challenges and Solutions
Grid Integration of Renewables: Challenges and Solutions
Power System Operation
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD Editor
 
To Study and Implement Power Quality Issues and Power Enhancement Techniques ...
To Study and Implement Power Quality Issues and Power Enhancement Techniques ...To Study and Implement Power Quality Issues and Power Enhancement Techniques ...
To Study and Implement Power Quality Issues and Power Enhancement Techniques ...
ijtsrd
 

Similar to Power Quality Trends in the Transition to Carbon-Free Electrical Energy System (20)

AN OUTLINE OF HARMONICS AND MULTILEVEL
AN OUTLINE OF HARMONICS AND MULTILEVELAN OUTLINE OF HARMONICS AND MULTILEVEL
AN OUTLINE OF HARMONICS AND MULTILEVEL
 
EHV AC
EHV ACEHV AC
EHV AC
 
Power Quality Problems Related with the Interconnection of Wind Farms to the ...
Power Quality Problems Related with the Interconnection of Wind Farms to the ...Power Quality Problems Related with the Interconnection of Wind Farms to the ...
Power Quality Problems Related with the Interconnection of Wind Farms to the ...
 
Influence choice of the injection nodes of energy source on on-line losses of...
Influence choice of the injection nodes of energy source on on-line losses of...Influence choice of the injection nodes of energy source on on-line losses of...
Influence choice of the injection nodes of energy source on on-line losses of...
 
windfarmgridissues.pdf
windfarmgridissues.pdfwindfarmgridissues.pdf
windfarmgridissues.pdf
 
Wind farm grid issues
Wind farm grid issuesWind farm grid issues
Wind farm grid issues
 
11.[21 28]voltage stability improvement using the 21st century power transformer
11.[21 28]voltage stability improvement using the 21st century power transformer11.[21 28]voltage stability improvement using the 21st century power transformer
11.[21 28]voltage stability improvement using the 21st century power transformer
 
Power_Electronics_in_Renewable_Energy_Systems.pdf
Power_Electronics_in_Renewable_Energy_Systems.pdfPower_Electronics_in_Renewable_Energy_Systems.pdf
Power_Electronics_in_Renewable_Energy_Systems.pdf
 
A modified bridge-type nonsuperconducting fault current limiter for distribut...
A modified bridge-type nonsuperconducting fault current limiter for distribut...A modified bridge-type nonsuperconducting fault current limiter for distribut...
A modified bridge-type nonsuperconducting fault current limiter for distribut...
 
Frequency response analysis under faults in weak power systems
Frequency response analysis under faults in weak power  systemsFrequency response analysis under faults in weak power  systems
Frequency response analysis under faults in weak power systems
 
Predictive Direct Power Control (PDPC) of Grid-connected Dual-active Bridge M...
Predictive Direct Power Control (PDPC) of Grid-connected Dual-active Bridge M...Predictive Direct Power Control (PDPC) of Grid-connected Dual-active Bridge M...
Predictive Direct Power Control (PDPC) of Grid-connected Dual-active Bridge M...
 
Challenges and Benefits of Integrating the Renewable Energy Technologies into...
Challenges and Benefits of Integrating the Renewable Energy Technologies into...Challenges and Benefits of Integrating the Renewable Energy Technologies into...
Challenges and Benefits of Integrating the Renewable Energy Technologies into...
 
Financial transmission rights
Financial transmission rightsFinancial transmission rights
Financial transmission rights
 
Pc3426502658
Pc3426502658Pc3426502658
Pc3426502658
 
A CONTROL APPROACH FOR GRID INTERFACING INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
A CONTROL APPROACH FOR GRID INTERFACING  INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...A CONTROL APPROACH FOR GRID INTERFACING  INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
A CONTROL APPROACH FOR GRID INTERFACING INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
 
Grid Integration of Renewables: Challenges and Solutions
Grid Integration of Renewables: Challenges and SolutionsGrid Integration of Renewables: Challenges and Solutions
Grid Integration of Renewables: Challenges and Solutions
 
System Operational Challenges from the Energy Transition
System Operational Challenges from the Energy TransitionSystem Operational Challenges from the Energy Transition
System Operational Challenges from the Energy Transition
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
 
To Study and Implement Power Quality Issues and Power Enhancement Techniques ...
To Study and Implement Power Quality Issues and Power Enhancement Techniques ...To Study and Implement Power Quality Issues and Power Enhancement Techniques ...
To Study and Implement Power Quality Issues and Power Enhancement Techniques ...
 
4-isi.pdf
4-isi.pdf4-isi.pdf
4-isi.pdf
 

More from Power System Operation

SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action Scheme
Power System Operation
 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
Power System Operation
 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
Power System Operation
 

More from Power System Operation (20)

ENERGY TRANSITION OUTLOOK 2021
ENERGY TRANSITION OUTLOOK  2021ENERGY TRANSITION OUTLOOK  2021
ENERGY TRANSITION OUTLOOK 2021
 
Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panels
 
What does peak shaving mean
What does peak shaving meanWhat does peak shaving mean
What does peak shaving mean
 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
 
Power System Restoration Guide
Power System Restoration Guide  Power System Restoration Guide
Power System Restoration Guide
 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid Operations
 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action Scheme
 
Substation Neutral Earthing
Substation Neutral EarthingSubstation Neutral Earthing
Substation Neutral Earthing
 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground Resistance
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & Parts
 
What is load management
What is load managementWhat is load management
What is load management
 
What does merit order mean
What does merit order meanWhat does merit order mean
What does merit order mean
 
What are Balancing Services ?
What are  Balancing Services ?What are  Balancing Services ?
What are Balancing Services ?
 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
 
Power Purchase Agreement PPA
Power Purchase Agreement PPA Power Purchase Agreement PPA
Power Purchase Agreement PPA
 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
 
SCADA System ? Supervisory Control & Data Acquisition
SCADA System ? Supervisory Control & Data AcquisitionSCADA System ? Supervisory Control & Data Acquisition
SCADA System ? Supervisory Control & Data Acquisition
 

Recently uploaded

Recently uploaded (20)

Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 

Power Quality Trends in the Transition to Carbon-Free Electrical Energy System

  • 1. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 21 1. Introduction Due to the accelerated shift towards a carbon-free electricalenergysystem,thepowersystemischangingin terms of both planning and operation with an increasing integration of converter-interfaced renewable generation at all voltage levels. One area strongly affected by these changes is power quality where, if not managed correctly, the result can be equipment mis-operation, accelerated aging, tripping of plant, loss of production process, etc. Failure to provide adequate supply quality can have negative impact on system operators, including customer complaints, reputational damage, financial liability and regulatory penalties. The issue of power quality in power systems is not new, with some publications dating back to the early 1900s dealing with distorted waveforms in transmission lines and their effects on transformers, rotating machines and telephone interference. Significant efforts were devoted at that time to investigate, understand and mitigate their negative effects. Standardisation was introduced throughout the years to control and limit different power quality parameters resulting in positive effects. This picture is changing rapidly. Power systems globally are experiencing a transition towards decarbonisation of electricity production through large-scale deployment of central and distributed renewable energy sources (RES), which are gradually replacing conventional thermal plant. The connection of RES to the power system is mostly achieved using power electronic (PE) converters. Equipment interfaced through PE-converters can have both a positive or negative effect on power quality, depending on the type of disturbance evaluated and the applied control strategy of the PE-converter [1]. Presently, the understanding of the impact of PE- converters and some related phenomena is not fully developed. However, it is widely accepted that the consequences of degraded power quality can have severe financial implications and most studies in the US and Europe point to an excessively high level of cost if serious problems arise [2]. This paper intends to provide a high-level summary of power quality issues in this changing environment and by doing that raise awareness of the main facets of power quality. 2. Harmonics Harmonics can be present in voltage and current waveforms, being defined as “a sinusoidal component of a periodic wave or quantity having a frequency that is an integral multiple of the fundamental frequency”. Special sub-categories exist including interharmonics, defined as “a sinusoidal component at frequencies that are not integer multiples” and subharmonics “a sinusoidal component at frequencies below the fundamental”. Harmonic distortion is caused by non-linear devices connected to the power system. Unlike linear devices, a non-linear device reacts to a perfect sinusoidal voltage waveform with a distorted current. In Figure 1 harmonic measurements obtained at a 15 kV busbar in Denmark is shown. Figure 1 (a) shows the time domain waveform at the location of the arrow, Figure 1 (b) shows the frequency domain harmonic decomposition per phase at the same location and Figures 1 (c) and (d) shows 11th and 13th single harmonic components as function of time measured over 3 weeks. Historically, control of harmonic at all levels has been an important issue requiring system studies, application of standards, and implementation of mitigation measures. The deleterious effects of harmonics have been kept under control because of this coordinated approach. Currently, the widespread connection of PE-converters at all voltage levels is driving new concerns and interest on the topic of harmonics. Furthermore, the planning and design methods utilized in the past may need to be updated as a consequence of the new types of equipment connected to the power system. Power Quality Trends in the Transition to Carbon-Free Electrical Energy System C. F. FLYTKJAER (DK), B. BADRZADEH (AU), M. BOLLEN (SE), Z. EMIN* (GB), L. KOCEWIAK (DK), G. LIETZ (DE), S. PERERA (AU), F. F. DA SILVA (DK), M. VAL ESCUDERO (IE) *zia.emin@cigre.org>
  • 2. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 22 there still exists a margin between the harmonic voltage distortion at the wall outlet and the prescribed limits [4]. Emphasis on limitation of harmonic emissions is gaining more attention [5]. This leads to an opposite trend that harmonic emission of new plant, as a whole, is reduced due to more strict enforcement of grid code requirements and to a trend of lower emission at individual equipment level.At equipment level different control strategies and converter topology, as for instance multi-level converter, are utilised with the combined effect of low emission of harmonics. Also, increased use of more energy efficient equipment with a resulting low load current implies that the harmonic contribution of for instance lighting equipment less of a concern [6]. Concurrent with the connection of more converter- interfaced equipment, power cables are seeing increased use at all voltage levels in some countries. Due to the electrical parameters of the cable, circuit resonance frequencies may be shifted to lower frequencies which increases the risk of amplification of pre-existing harmonics [7], [8], [9]. This phenomenon has been observed at different voltage levels in several countries, but it has proved to be especially problematic at higher voltage levels, where it introduces a limitation on the share of cable that can be safely installed and operated without introducing a risk of excessive amplification of harmonics [10]. An example of amplification of the 11th order harmonic voltage in a 400 kV substation in Denmark caused by the commissioning of an 8 km 400 kV cable situated 90 km away from the substation 2.1. Trends and Challenges It is generally expected that power systems around the world will experience an increase in harmonic distortion as the green transition progresses [1], [3]. Today, low- order harmonics are still the dominant harmonics in most power systems due to the characteristics of existing equipment. However, due to advances in technologies, harmonics generated by modern PE-converters also include the high-frequency harmonic range (>2 kHz), and the term supraharmonics is increasingly used to definethisrangeofharmonics.Aswellastheappearance of high frequency harmonics, there are also indications of increased emission of interharmonics and even harmonics (not necessarily attributed to PE converters), butacompleteoverviewofthesetrendsremainsmissing. Drivers for this trend at high and extra high voltage include not only the integration of RES connected via PE-converters, but also increased connection of FACTS controllers, HVDC links and general proliferation of PE converters in the demand, such as large data centres and large industrial plants. Also, at lower voltage levels an increase in harmonic generation is expected, caused by widespread photovoltaic (PV) generation, usage of energystorage,electricvehiclecharging/dischargingand increasing converter-interfaced loads at domestic level. This can eventually set a limit to the hosting capacity of the distribution grid for unmitigated installations. Presently, a recent mapping, including 163 measurement location in 17 countries, admittedly incomplete but still giving an indication, shows that at most locations Figure 1 (a) the time domain waveform at the location of the arrow, (b) the frequency domain harmonic decomposition per phase at the same location and (c) and (d) shows 11th and 13th single harmonic components as function of time measured over 3 weeks.
  • 3. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 23 3. Voltage variation Thequalityofthevoltagewaveformcanalsobemeasured in terms of its magnitude and temporal deviations with respect to the nominal parameters. A distinction can be made between steady-state values, with an acceptable variation of ±10% of nominal typically, and short-term events for which higher deviations are acceptable. In Figure 3 Excessive voltage oscillations following fault clearance due to the response of solar farms’ control systems a fluctuating voltage waveform is presented as an example. 3.1. Trends and Challenges Steady state refers to slow variations in the RMS value ofthevoltagewaveformwhichtakeplacethroughoutthe day due to gradual customer load variation or variable RES output. A trend towards larger and more frequent voltage variations can be expected due to increasing penetration of intermittent generation resources such as wind and solar. Such voltage variations can lead to both under voltage and over voltage where both situations can have an impact on network operation and on customer equipment. In distribution networks, over voltage can lead to excess energy consumption depending on the type of load, core saturation of transformers and stressing of insulation leading to its premature failure. Under voltage can lead to reduced energy consumption depending on the type of load, malfunctioning of high-intensity discharge lamps and reduction of torque developed by mains connected motors. Undervoltage can also result in overcurrent, as equipment often consumes a constant power, with accelerated ageing as a consequence. These slow variations are normally managed by automatic or manual control actions taken by the grid controllers to ensure compliance with statutory voltage quality standards. However, the increased level of wind and solar is introducing significant challenges in the design and operation of these networks. With the proliferation of rooftop solar PVsystems in low is shown in Figure 2. The instance of energization is marked by the arrow in the figure. The net result of many new harmonics sources being introduced into the power system but with a decreased individual harmonic emission is difficult to predict. Moreover, with local resonance introduced by the use of cables, it will be difficult to generalise.Atrend towards a moreprofoundfocustoundertakedetailedanalysisatthe planning stages, to ensure adherence to statutory limits and hence secure power system operation is however manifesting [6]. 2.2. Opportunities The main harmonic countermeasure for many years has been based on passive filters, usually employed as part of the development scheme (for example during the installation of line commutated HVDC schemes).As the harmonic injection and usage of power cables increases, this approach is showing its limitations. The resonance frequencies change when the system evolves and/or changes,andpassivefiltersinstalledinspecificlocations might become ineffective. Additionally, the installation of a passive filter changes the resonance frequencies in a wide area of the power system, and it might increase the harmonic distortion in other locations of the grid [10]. One emerging possibility is active filtering, which has been successfully used at MV levels, mainly in connection with large wind and PV farms [11]. Another possibility is to use PE-converters to actively mitigate harmonics in the system by means of active harmonic cancellation, which would be achieved by controlling the phase angle of the injected harmonics, leading to the associated cancellation. This level of control has only been used to a small extend in HVDC but is generally not possible today, as measurement of the phase angles of the harmonics presented in the system is typically not reliable, but it is an interesting area for future research. A further option is to create a” virtual resistor” using converter control to deliberately create a counter-voltage to the load current. This is mostly used in large HVDCs and not practical in smaller converter-interfaced plants. Figure 2Amplification of the 11th order harmonic voltage due to the commissioning of an 8 km 400 kV cable.
  • 4. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 24 new system services. The objective is to incentivize wind farm owners to invest in technologies capable of providing enhanced voltage and reactive power control performance over and above the minimum grid code requirements with the introduction of new products such as Steady State Reactive Power (SRP) [12] - other countries are following this trend. Short-term voltage variations refer to rapid voltage changes and voltage dips, typically caused by connection and disconnection of loads, network switching operations, electric arc furnaces, transformer energization, motor starting and system faults. One of the main concerns with fast voltage variations at low voltage levels is the resulting lamp flicker which can be problematic in distribution systems. The proliferation of converter-interfaced renewable generation connections, with intermittent power output, combined with a reduction in system strength through displacement of conventional plant, results in a higher volatility in the system voltage at transmission level. Therefore, fast voltage variations can now become also prominent at high voltage levels. The trend towards reduction in system strength at transmission levels means that voltage dips, typically causedbysystemfaults,transformerenergisationorlarge motorstarting,canbecomemorefrequentandsevereand will also propagate to downstream distribution networks [1]. If large shares of converter-interfaced generation get disconnected from the grid during a voltage dip, the initial voltage disturbance will evolve into a large power imbalance introducing a risk to the stability of the system frequency, which could result in a system blackout. Fault Ride Through (FRT) requirements for converter-interfaced generation have been introduced in many countries to address this challenge. In most grid codes, these requirements include not only the need to remain connected during the voltage dip but also the provision of reactive current in an attempt to support the system voltage and limit the extent and magnitude of the disturbance. Grid-connected converters in modern power systems are designed to provide specific functionality. Typically, the voltage and power control loops, as well as the grid synchronization control, are cascaded with the current control. The cascaded control system is characterized voltage distribution systems, already many networks around the world are experiencing excessive steady state voltage variation issues when the PV systems are generating at their peak level during the daytime. These distribution radial networks were originally designed to carry power in one direction whereas they now tend to also operate with a reversed power flow. The tap settings of the upstream transformers and the line drop compensation systems were originally designed assuming upstream to downstream power flow and are unsuitable to accommodate bi-directional flows in compliance with statutory limits from a steady state voltage point of view. The shift from large centralized conventional plant to a dispersed renewable generation portfolio also introduces operational challenges at transmission level due to the reduction in available controllable reactive power resources. A compounding factor is the traditional practice of operating embedded generation at fixed power factor (normally absorbing reactive power), which introduces additional challenges in the absence of reactive power exchange limitations between transmission and distribution systems (some geographies do apply limits). In some cases, deployment of dynamic reactive compensation equipment is required at transmission level to manage the variable reactive power demand from downstream distribution networks. This, however, is normally considered in operational security frameworks between system operators rather than as power quality aspects and will not be discussed in detail in this paper. Some wind generation technologies have limitations in the provision of reactive power at low wind speeds, especially when connected to weak networks. With the proliferation of long HVAC cables deployed to connect on-shore and off-shore wind farms to transmission grids, over-voltages are frequent during periods of low wind output. This situation gets exacerbated if passive harmonic filters are installed to manage harmonic distortion (either active emissions or passive amplification). Some grid codes address this challenge with mandatory requirements to provide full reactive power capability within the entire contracted active power range. In Ireland an alternative approach has been adopted through the introduction of a market for
  • 5. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 25 and duration of the event, voltage oscillations can in turn manifest in power quality indices; e.g. as flicker due to rapid voltage variations. As an example of this new phenomenon, Figure 3 shows the simulated sustained voltage oscillations following a credible system network fault taking out a transmission line being the key source of system strength support for the inverter- connected generator under consideration. These types of oscillations have already been observed in practical power systems involving two or more inverter-based resources.An example of measured flicker during a sub- harmonic interaction event is shown in Figure 4. These oscillatory responses cause the inverter-based resources breach of their technical performance requirements. Undamped and sustained oscillations are inconsistent with the definition of adequately damped oscillation and cause short-term flicker levels well in excess of the maximum permissible level of 1.0 as per [14]. by multiple timescales, whose damping effect is dependent on the grid strength and operating points. The combination of low damping in the transmission system, resonance characteristics in the power system, weak grid characteristic, and negative damping in converter frequency response can (but not necessarily) cause unwanted oscillations within a frequency range defined by the controller dynamics. Thus, the oscillations can be basically at any frequency, i.e. harmonic, inter-harmonic or even sub-synchronous. This new phenomenon is referred as converter multi-frequency stability and is the focus of CIGRE Working Group C4.49 [13]. The continuously expanding utilization of PE-converters is expected to create new challenges with respect to performance, interoperability, robustness and stability. Oscillations between any combination of active and passive component in the power system will manifest itself in the system voltage. Depending on the frequency Figure 3 Excessive voltage oscillations following fault clearance due to the response of solar farms’control systems Figure 4 Measured short-term flicker (Pst) level due to an adverse sub-harmonic interaction
  • 6. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 26 investment in new functionalities that provide benefits to the overall power system. Withregardtonewphenomena,thereareseveralpossible ways to optimize the power system design and operation to reduce (or even completely avoid) grid-connected converter instability and therefore related power quality issues. One can distinguish four main methods of converter instability mitigation in power systems: the robustness, resonances, to avoid critical topology changes, sensitive frequency range. 4. Voltage unbalance Voltage unbalance is defined as a “condition in a poly- phase system in which the magnitudes of the phase voltages and/or the phase angles between consecutive phase voltages, are not all equal [17]. Such three-phase unbalanced voltages can be decomposed into three balanced systems, namely: positive sequence, negative sequence and zero sequence. For a three-phase system, thedegreeofunbalanceisgenerallyexpressedastheratio of the negative- and zero-sequence components to the positive-sequence component. The negative-sequence component is normally the main concern considering the impact on three-phase rotating machinery and hence unbalanceusuallyreferstonegativesequenceunbalance. Figure 5 shows actual recorded three phase voltages at a 150 kV substation measured over a period of 2 weeks with the corresponding positive sequence voltage, negativesequencevoltageandvoltageunbalancefactors. To understand this in practice, the example of a three- phase induction motor can be used. The positive- sequence set of voltages will drive the motor in a particular direction of rotation whereas the negative- sequence set of voltages will work against this direction of rotation, as two counter-rotating magnetic fields are created in the induction motor. Even with a relatively small negative sequence voltage, the resulting negative sequence current in a three-phase induction motor can be showntoberelativelylarge.Asaconsequence,induction 3.2. Opportunities Low voltage (LV) systems operating at the high end of the allowable voltage range can lead to increased energy consumption depending on the types of loads, stressing of connected equipment and tripping of connected PV systems thus defeating the purpose of investment of the PV systems. Compared to older solar PV inverters which operate at unity power factor, the newer inverters are able to control the voltage at the point of connection through reactive power absorption or injection. While such approachesarenotmandatoryatthispointintimeinmany countries and the owners of the PV systems would like to benefit from the maximum real power injection, there is an opportunity to utilize new equipment capabilities to support the system in a cost-effective manner. The network wide deployment of low voltage STATCOMs which are able to manage the steady state and dynamic voltages in LV networks are now being trialed in some countries such asAustralia [15]. Studies are still required to investigate the effects on the overall network energy savings by employing such network wide solutions and the associated incentive schemes required to drive that investment. There are also opportunities for enhanced co-ordination of voltage control strategies and share of reactive power resources between TSOs and DSOs. Some interesting examples and proof of concept of co- ordinated approaches are described in [16], including the deployment of voltage controllers in large DERs clusters in Ireland, Spain and Germany. Most of the challenges associated with integration of converter-interfaced renewable generation relate to the displacement of conventional plant and reduction in available dynamic reactive power resources to provide voltage regulation. Furthermore, fluctuations in power output caused by local weather conditions (e.g. wind speed or sun radiation) can cause additional voltage variations outside the continuous operational range. Power electronics, however, can help to mitigate these issues through fast controls that can respond to voltage fluctuations or sudden changes in reactive power profile in less than a cycle. While minimum performance requirements can be introduced in grid codes to utilize these new functionalities, there are also opportunities for the development of new market products to incentivize
  • 7. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 27 only single-phase laterals are available, all connections end up on the same phase which can lead to significant voltage unbalance levels on three-phase LV systems. Other technologies that will have an impact include electric vehicle charging points and heat pumps at the low voltage level. These will have an increased level power capacity and are likely to introduce more voltage unbalance and hence their capacities may be limited depending on the fault level at the point of connection. Due to time intermittency of such loads, distributing them among the available phases is not expected to lessen the effect substantially. Large scale wind and solar farms are often connected at remote locations supplied by relatively long un- transposed lines, and hence voltage unbalance can arise due to the lines [19] although the wind or the solar farms inject balanced currents. 4.2. Opportunities With single-phase PV connections, their capacities need to be controlled in comparison to the fault level at the point of connection and their distribution across the phases by setting appropriate guidelines, rules and regulations. These limiting capacities need to be determined through extensive studies covering typical networks. An example is shown in [20]. With regard to large solar and wind farm applications that are connected at the end of relatively long un- transposed lines, to mitigate or reduce the resulting voltage unbalance, instead of using dedicated network STATCOMs, the power electronic inverters within the motorswillexperienceexcessivestatorandrotorheating, torque ripple (at twice the supply frequency) and hence noise and vibration and sometimes leading to premature failure. For this reason, induction motors need to be derated under voltage unbalance conditions [18]. A similar type of impact can take place in synchronous machines if they are connected to networks with voltage unbalance, and for this reason limits exist on allowable network voltage unbalance under both normal and contingency conditions. Furthermore, voltage unbalance can also lead to the generation of uncharacteristic harmonics by three-phase rectifier systems which form the front end of manyAC variable speed drives. Voltage unbalance in electricity networks is primarily caused by asymmetrical three-phase loads, unequal distribution of single-phase loads (especially in low voltage distribution systems) and asymmetrical transmission and distribution lines. The latter is due to the asymmetry introduced by the electromagnetic coupling between the different phases on one circuit but also between two circuits on the same tower or right- of-way. Although low voltage distribution lines which are relatively short are not transposed, long high voltage lines normally are transposed. 4.1. Trend and Challenges Proliferation of technologies such as photovoltaic systems at the LV level is taking place as single-phase connections. Depending on the geographic availability ofthree-phaseconnections,single-phasePVconnections can be altered between the phases but in places where Figure 5 Unbalance between magnitudes of the three phases: (a) phase voltages, (b) positive sequence voltage, (c) negative sequence voltage and voltage unbalance factor.
  • 8. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 28 interfaced intermittent generation resources such as wind and solar, and response of associated control systems. Such voltage variations can lead to both under voltage and over voltage where both situations can have an impact on network operation and on customer equipment. Reduced system strength at transmission level means that voltage dips, typicallycaused by system faults, transformer energization or large motor starting, can become more frequent and severe and they will also propagate to downstream distribution networks. Intermittent power output, combined with a reduction in system strength will result in a higher volatility in the system voltage at transmission level making fast voltage variations a possible issue. Proliferationofconverter-interfacedtechnologiessuchas photovoltaicsystemsatthelowandmediumvoltagelevel is commonly taking place as single-phase connections. Single-phase PV connections can be altered between the phases but in places where only single-phase laterals are available, all connections end up on the same phase which can lead to significant voltage unbalance levels on three-phase low voltage systems. Other converter- interfaced technologies that will have an impact include electric vehicle charging points and heat pumps at the low voltage level. These will have an increased level power capacity and are likely to introduce more voltage unbalance and hence their capacities may be limited depending on the fault level at the point of connection. Large scale wind and solar farms at transmission level are often connected at remote locations supplied by relatively long un-transposed lines, and hence voltage unbalance can arise due to the lines despite the wind or the solar farms injecting balanced currents. 6. References [1] CIGRE TB 719, “Power quality and EMC issues with future electricity networks”, March 2018, ISBN 978-2-85873-421-4. [2] R.Targosz, J. Manson, “European Power Quality Survey Report”, Leonardo ENERGY, European Copper Institute, 2008. [3] B. Kelly, M. Val Escudero, P. Horan, C. Geaney, A. Martin and D. Lewis “Investigation of Harmonics Trends and Characteristics on the Irish Transmission System by analyzing Historical PQ Measurements and SCADA Records”. CIGRE 2016 Biennial Session, Paper C4-114. [4] M.H.J. Bollen. A. Gil de Castro and S.K. Rönnberg, “Typical harmonic levels and spectra with low-voltage customers”, CIRED 2019. [5] D. O. Brasil, C. Buchhagen, Z. Emin, C. F. Jensen, L. Soto Cano solar and wind farms may be able to compensate such voltage unbalance by injecting appropriate currents. However, it is important that mitigation of voltage unbalance through such approaches is not carried out in isolation without consideration of broader issues. Substantial single-phase loads such as traction supplies, can be fed strategically such that the unbalance introduced by these loads can create a negative-sequence voltage with an opposing phase angle to that already on the system, acting like a counterbalance. Additional compensation can be implemented in the form of dynamic voltage support such as SVC or STATCOM that can provide phase-based reactive power. 5. Concluding Remarks Thepowerqualityinthefuturepowersystemisexpected to be significantly affected by the shift towards a carbon- free electrical energy system. Several trends point to degraded power quality indices of future power systems duetotheintegrationofmanypowerelectronicsdevices, use of power cables at all voltage levels, increasing amount of fluctuating production and generally reduced system strength. However, with the ability to control power electronics new possibilities are emerging and if used correct many of the challenges introduced can be mitigated by the same components that create them. Doing so successfully requires high focus on power quality studies both at individual connection and system wide level, focus on grid code requirements and their implementation and robust system monitoring with a strategic approach. It is generally expected that power systems around the world will experience an increase in harmonic distortion as the green transition progresses. This is partly due to the sheer number of converter-interfaced equipment being connected and partly due to possible modification of existing distortion levels. However, emphasis on limitation of harmonic emissions is gaining more attentionanddrivingatrendintheoppositedirection,that harmonic emission of new plant, as a whole, is reduced at equipment level due to more advanced switching and control technologies being implemented and the stricter enforcement of grid code requirements. Larger and more frequent voltage variations can be expected due to increasing penetration of converter-
  • 9. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 29 [13] Ł. Kocewiak, Ch. Buchhagen, Y. Sun, X. Wang, G. Lietz and M. Larsson, “Overview, Status and Outline of the New CIGRE Working Group C4.49 on Converter Stability in Power Systems,” in Proc. The 18th International Workshop on Large-Scale Integration of Wind Power into Power Systems as well as Transmission Networks for Offshore Wind Farms, 16-18 October 2019, Dublin, Ireland. [14] IEC TR 61000-3-7:2008 Electromagnetic compatibility (EMC) - Part 3-7: Limits - Assessment of emission limits for the connection of fluctuating installations to MV, HV and EHV power systems. [15] https://ecojoule.com/ecovar/ [16] “System Operation Emphasizing DSO/TSO Interaction and Coordination”. Tutorial presented by CIGRE JWG C2/C6.36. CIGRE 2018 Biennial Session. 29th August 2018. [17] CIGRE TB 261, “Power quality indices and objectives”, October 2004, [18] IEC 60034-26:2006: Rotating electrical machines - Part 26: Effects of unbalanced voltages on the performance of three-phase cage induction motors. [19] Z. Emin and D. S. Crisford, “Negative Phase-Sequence Voltages on E&W Transmission System”, IEEE Transaction on Power Delivery, Vol. 21, No.3, July 2006, pp.1607-1612. [20] D. Schwanz, F. Möller, S. K. Rönnberg, J. Meyer, and M. H.J. Bollen, “Stochastic Assessment of Voltage Unbalance due to Single-Phase-Connected Solar Power”, IEEE Transactions on Power Delivery, Vol.32, No.2, April 2017, pp.852-861. and M. Val Escudero, “International comparison of harmonic assessment approaches and implications”. CIGRE 2018 Biennial Session, Paper C4-111. [6] CIGRE TB 766, “Network modelling for harmonic studies,” April 2019, ISBN 978-2-85873-468-9. [7] C. F. Jensen, Ł. H. Kocewiak and Z. Emin, “Amplification of Harmonic Background Distortion in Wind Power Plants with Long High Voltage Connections,” CIGRE 2016 Biennial Session, Paper C4-112. [8] C.F. Jensen” Harmonic Background Amplification in Long Asymmetrical High Voltage Cable Systems”, Electric Power Systems Research (EPSR) Special IPST 2017 edition [9] M. Val Escudero, A. Martin, L. Fisher and I. Dudurych, “Technical Challenges Associated with the Integration of Long HV AC Cables and Inverter Based Renewable Generation in Weak Transmission Networks: The Irish Experience”. CIGRE 2018 Biennial Session, Paper C4-310. [10] Energinet “Technical issues related to new transmission lines in Denmark”, 2018. [11] Ł. H. Kocewiak, B. Laudal Øhlenschlæger Kramer, O. Holmstrøm, K. Høj Jensen, L. Shuai, “Resonance Damping in Array Cable Systems by Wind Turbine Active Filtering in Large Offshore Wind Power Plants,” IET Renewable Power Generation, Vol. 11, Issue 7, July 2017, pp 1069-1077. [12] Detailed information about DS3 System Services is available at http://www.eirgridgroup.com/how-the-grid-works/ ds3-programme/