A relay is an electrically operated switch. Many relays use an electromagnet to
mechanically operate a switch, but other operating principles are also used, such
as solid-state relays. Relays are used where it is necessary to control a circuit by a
low-power signal (with complete electrical isolation between control and
controlled circuits), or where several circuits must be controlled by one signal. The
first relays were used in long distance telegraph circuits as amplifiers: they
repeated the signal coming in from one circuit and re-transmitted it on another
circuit. Relays were used extensively in telephone exchanges and early computers
to perform logical operations.
A type of relay that can handle the high power required to directly control an
electric motor or other loads is called a contactor. Solid-state relays control power
circuits with no moving parts, instead using a semiconductor device to perform
switching. Relays with calibrated operating characteristics and sometimes multiple
operating coils are used to protect electrical circuits from overload or faults; in
modern electric power systems these functions are performed by digital
instruments still called "protective relays".
A simple electromagnetic relay consists of a coil of wire wrapped around a soft
iron core, an iron yoke which provides a low reluctance path for magnetic flux, a
movable iron armature, and one or more sets of contacts (there are two in the relay
pictured). The armature is hinged to the yoke and mechanically linked to one or
more sets of moving contacts. It is held in place by a spring so that when the relay
is de-energized there is an air gap in the magnetic circuit. In this condition, one of
the two sets of contacts in the relay pictured is closed, and the other set is open.
Other relays may have more or fewer sets of contacts depending on their function.
The relay in the picture also has a wire connecting the armature to the yoke. This
ensures continuity of the circuit between the moving contacts on the armature, and
the circuit track on the printed circuit board (PCB) via the yoke, which is soldered
to the PCB.
When the coil is energized with direct current, a diode is often placed across the
coil to dissipate the energy from the collapsing magnetic field at deactivation,
which would otherwise generate a voltage spike dangerous to
semiconductor circuit components. Some automotive relays include a diode inside
the relay case. Alternatively, a contact protection network consisting of a capacitor
and resistor in series (snubber circuit) may absorb the surge. If the coil is designed
to be energized with alternating current (AC), a small copper "shading ring" can be
crimped to the end of the solenoid, creating a small out-of-phase current which
increases the minimum pull on the armature during the AC cycle.
Latching relay
Latching relay with permanent magnet
A latching relay (also called "impulse", "keep", or "stay" relays) maintains either
contact position indefinitely without power applied to the coil. The advantage is
that one coil consumes power only for an instant while the relay is being switched,
and the relay contacts retain this setting across a power outage. A latching relay
allows remote control of building lighting without the hum that may be produced
from a continuously (AC) energized coil.
In one mechanism, two opposing coils with an over-center spring or permanent
magnet hold the contacts in position after the coil is de-energized. A pulse to one
coil turns the relay on and a pulse to the opposite coil turns the relay off. This type
is widely used where control is from simple switches or single-ended outputs of a
control system, and such relays are found in avionics and numerous industrial
applications.
Reed relay
Top, middle: reed switches, bottom: reed relay
A reed relay is a reed switch enclosed in a solenoid. The switch has a set of
contacts inside an evacuated or inert gas-filled glass tube which protects the
contacts against atmospheric corrosion; the contacts are made of magnetic material
that makes them move under the influence of the field of the enclosing solenoid or
an external magnet.
Reed relays can switch faster than larger relays and require very little power from
the control circuit. However, they have relatively low switching current and voltage
ratings. Though rare, the reeds can become magnetized over time, which makes
them stick 'on' even when no current is present; changing the orientation of the
reeds with respect to the solenoid's magnetic field can resolve this problem.
Sealed contacts with mercury-wetted contacts have longer operating lives and less
contact chatter than any other kind of relay.
Mercury-wetted relay
A mercury-wetted reed relay that has AC/DC switching specifications of 100 W,
500 V, 2 A maximum
A mercury-wetted reed relay is a form of reed relay in which the contacts are
wetted with mercury. Such relays are used to switch low-voltage signals (one volt
or less) where the mercury reduces the contact resistance and associated voltage
drop, for low-current signals where surface contamination may make for a poor
contact, or for high-speed applications where the mercury eliminates contact
bounce. Mercury wetted relays are position-sensitive and must be mounted
vertically to work properly. Because of the toxicity and expense of liquid mercury,
these relays are now rarely used.
Mercury relay
A mercury relay is a relay that uses mercury as the switching element. They are
used where contact erosion would be a problem for conventional relay contacts.
Owing to environmental considerations about significant amount of mercury used
and modern alternatives, they are now comparatively uncommon.
Machine tool relay
Coaxial relay
Contactor
Solid state contactor relay
Solid-state relay
Forced-guided contacts relay
Overload protection relay
Vacuum relays
Buchholz relay
A Buchholz relay is a safety device sensing the accumulation of gas in large oil-
filled transformers, which will alarm on slow accumulation of gas or shut down the
transformer if gas is produced rapidly in the transformer oil.
Relay performance tests address two questions. Is the relay operating as it was
designed? Is the relay being applied properly? Integrity tests are intended to answer
the first, and application tests the second. In the past, users have concentrated on
integrity tests using relatively simple equipment in the field. Application tests
required bulky and expensive equipment which was usually only available in relay
manufacturers' plants, or in research laboratories. Historically, field test equipment
was only suitable for steady-state tests and limited dynamic state simulations.
Manufacturers and users developed comprehensive test plans to ensure the integrity
of relays using passive test equipment. Integrity tests were also designed to be
performed in the field using simple equipment. With common applications, the
manufacturers application tests done during relay development will usually suffice
to ensure correct operation under normal circumstances.
Type Tests
Type tests are required to prove that a relay meets the published specification and
complies with all relevant standards. Since the principal function of a protection
relay is to operate correctly under abnormal power conditions, it is essential that
the performance be assessed under such conditions. Comprehensive type tests
simulating the operational conditions are therefore conducted at the manufacturer's
works during the development and certification of the equipment.
The standards that cover most aspects of relay performance are IEC 60255 and
ANSI C37.90. However compliance may also involve consideration of the
requirements of IEC 61000, 60068 and 60529, while products intended for use in
the EEC also have to comply with the requirements of Directives 89/336/EEC and
73/23/EEC. Since type testing of a digital or numerical relay involves testing of
software as well as hardware, the type testing process is very complicated and more
involved than a static or electromechanical relay.
Commissioning Tests
These tests are designed to prove that a particular protection scheme has been
installed correctly prior to setting to work. All aspects of the scheme are thoroughly
checked, from installation of the correct equipment through wiring checks and
operation checks of the individual items of equipment, finishing with testing of the
complete scheme.
Periodic Maintenance Checks
These are required to identify equipment failures and degradation in service, so that
corrective action can be taken. Because a protection scheme only operates under
fault conditions, defects may not be revealed for a significant period of time, until a
fault occurs. Regular testing assists in detecting faults that would otherwise remain
undetected until a fault occurs.
Rating Tests
Rating type tests are conducted to ensure that components are used within their
specified ratings and that there are no fire or electric shock hazards under a normal
load or fault condition of the power system. This is in addition to checking that the
product complies with its technical specification. The following are amongst the
rating type tests conducted on protection relays, the specified parameters are
normally to IEC 60255-6.
Functional Tests
The functional tests consist of applying the appropriate inputs to the relay under
test and measuring the performance to determine if it meets the specification. They
are usually carried out under controlled environmental conditions. The testing may
be extensive, even where only a simple relay function is being tested., as can be
realised by considering the simple overcurrent relay element of Table 21.1.
To determine compliance with the specification, the tests listed in Table 21.2 are
required to be carried out. This is a time consuming task, involving many engineers
and technicians. Hence it is expensive.
When a modern numerical relay with many functions is considered, each of which
has to be type-tested, the functional type-testing involved is a major issue. In the
case of a recent relay development project, it was calculated that if one person had
to do all the work, it would take 4 years to write the functional type-test
specifications, 30 years to perform the tests and several years to write the test
reports that result.
D.C Interrupt Test
This is a test to determine the maximum length of time that the relay can withstand
an interruption in the auxiliary supply without de-energising, e.g. switching off,
and that when this time is exceeded and it does transiently switch off, that no
maloperation occurs.
It simulates the effect of a loose fuse in the battery circuit, or a short circuit in the
common d.c. supply, interrupted by a fuse. Another source of d.c. interruption is if
there is a power system fault and the battery is supplying both the relay and the
circuit breaker trip coils. When the battery energises the coils to initiate the circuit
breaker trip, the voltage may fall below the required level for operation of the relay
and hence a d.c. interrupt occurs. The test is specified in IEC 60255-11 and
comprises a interruptions of 2, 5, 10, 20, 50, 100 and 200ms. For interruptions
lasting up to and including 20ms, the relay must not de-energise of maloperate,
while for longer interruptions it must not maloperate.
Dynamic Relay Testing
Dynamic relay testing means testing under true simulated power system conditions.
Depending on the level of testing reąuired, test values can be easily calculated with
PC-based short circuit or EMTP programs. For dynamic-state testing, a short
circuit program would be used to calculate the fundamentai component of voltage
and current values for pre-fault and fault conditions. For transient simulations, an
EMTP program would be used to create waveforms that represent the fault
condition. Dynamic-state testing and transient simulations provide a faster and
more meaningful way to test relays and relay systems. These techniąues provide
the user with a far better understanding of how the relay system performs and can
aid both relay application and test engineers in evaluating relay operations.
Dynamic-state testing is based on a power system model that is used to simulate
different events selected according to the application. Events are played back
through power system simulators that also monitor scheme performance. Each
event is modeled to simulate conditions for the tested relay circuit but only for the
time period needed to test.
QUESTIONS ?
Power System Protection and Testing of Electrical Equipment.pptx

More Related Content

Similar to Power System Protection and Testing of Electrical Equipment.pptx

TOPIC 2.1- Relays.pptx
TOPIC 2.1- Relays.pptxTOPIC 2.1- Relays.pptx
TOPIC 2.1- Relays.pptxMartMantilla1
 
Relay and Transducers
Relay and TransducersRelay and Transducers
Relay and TransducersJessa Arnado
 
Engineering plant facilities 09 mechanics building instrumentation
Engineering plant facilities 09 mechanics building instrumentationEngineering plant facilities 09 mechanics building instrumentation
Engineering plant facilities 09 mechanics building instrumentationLuis Cabrera
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERRitesh Kumawat
 
Electromagnetic Protection (PART I)
Electromagnetic Protection (PART I)Electromagnetic Protection (PART I)
Electromagnetic Protection (PART I)Dr. Rohit Babu
 
Report on 220kv substation at Jassure
Report on 220kv substation at JassureReport on 220kv substation at Jassure
Report on 220kv substation at JassureShuvam Pathania
 
132 KV Substation Gajraula.pptx
132 KV Substation Gajraula.pptx132 KV Substation Gajraula.pptx
132 KV Substation Gajraula.pptxAsif682330
 
What Are Relays, and What Kinds Are There.pdf
What Are Relays, and What Kinds Are There.pdfWhat Are Relays, and What Kinds Are There.pdf
What Are Relays, and What Kinds Are There.pdfexpess-technology
 
Measurement and Relay Indications.pptx
Measurement and Relay Indications.pptxMeasurement and Relay Indications.pptx
Measurement and Relay Indications.pptxEngrSyedGhulamMustaf
 
Report On Industrial Tour At Khulshi Grid Sub-Station
Report On Industrial Tour At Khulshi Grid Sub-StationReport On Industrial Tour At Khulshi Grid Sub-Station
Report On Industrial Tour At Khulshi Grid Sub-StationEkram Bin Mamun
 
Anurag Attri.pptx
Anurag Attri.pptxAnurag Attri.pptx
Anurag Attri.pptxAsif682330
 
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...rohit nadella
 
Switchgears and protection devices
Switchgears and protection devicesSwitchgears and protection devices
Switchgears and protection devicesManojkarader
 
Module 3-electrical
Module  3-electricalModule  3-electrical
Module 3-electricalManojkarader
 

Similar to Power System Protection and Testing of Electrical Equipment.pptx (20)

TOPIC 2.1- Relays.pptx
TOPIC 2.1- Relays.pptxTOPIC 2.1- Relays.pptx
TOPIC 2.1- Relays.pptx
 
Adaptive Relaying,Report
Adaptive Relaying,ReportAdaptive Relaying,Report
Adaptive Relaying,Report
 
Relay and protection
Relay and protection Relay and protection
Relay and protection
 
Relays
  Relays  Relays
Relays
 
Relays
RelaysRelays
Relays
 
Relay and Transducers
Relay and TransducersRelay and Transducers
Relay and Transducers
 
Engineering plant facilities 09 mechanics building instrumentation
Engineering plant facilities 09 mechanics building instrumentationEngineering plant facilities 09 mechanics building instrumentation
Engineering plant facilities 09 mechanics building instrumentation
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
 
Electromagnetic Protection (PART I)
Electromagnetic Protection (PART I)Electromagnetic Protection (PART I)
Electromagnetic Protection (PART I)
 
PPT.pptx
PPT.pptxPPT.pptx
PPT.pptx
 
Report on 220kv substation at Jassure
Report on 220kv substation at JassureReport on 220kv substation at Jassure
Report on 220kv substation at Jassure
 
132 KV Substation Gajraula.pptx
132 KV Substation Gajraula.pptx132 KV Substation Gajraula.pptx
132 KV Substation Gajraula.pptx
 
What Are Relays, and What Kinds Are There.pdf
What Are Relays, and What Kinds Are There.pdfWhat Are Relays, and What Kinds Are There.pdf
What Are Relays, and What Kinds Are There.pdf
 
Measurement and Relay Indications.pptx
Measurement and Relay Indications.pptxMeasurement and Relay Indications.pptx
Measurement and Relay Indications.pptx
 
Ashwani kumar
Ashwani kumarAshwani kumar
Ashwani kumar
 
Report On Industrial Tour At Khulshi Grid Sub-Station
Report On Industrial Tour At Khulshi Grid Sub-StationReport On Industrial Tour At Khulshi Grid Sub-Station
Report On Industrial Tour At Khulshi Grid Sub-Station
 
Anurag Attri.pptx
Anurag Attri.pptxAnurag Attri.pptx
Anurag Attri.pptx
 
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
 
Switchgears and protection devices
Switchgears and protection devicesSwitchgears and protection devices
Switchgears and protection devices
 
Module 3-electrical
Module  3-electricalModule  3-electrical
Module 3-electrical
 

Recently uploaded

Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 

Recently uploaded (20)

Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 

Power System Protection and Testing of Electrical Equipment.pptx

  • 1.
  • 2. A relay is an electrically operated switch. Many relays use an electromagnet to mechanically operate a switch, but other operating principles are also used, such as solid-state relays. Relays are used where it is necessary to control a circuit by a low-power signal (with complete electrical isolation between control and controlled circuits), or where several circuits must be controlled by one signal. The first relays were used in long distance telegraph circuits as amplifiers: they repeated the signal coming in from one circuit and re-transmitted it on another circuit. Relays were used extensively in telephone exchanges and early computers to perform logical operations. A type of relay that can handle the high power required to directly control an electric motor or other loads is called a contactor. Solid-state relays control power circuits with no moving parts, instead using a semiconductor device to perform switching. Relays with calibrated operating characteristics and sometimes multiple operating coils are used to protect electrical circuits from overload or faults; in modern electric power systems these functions are performed by digital instruments still called "protective relays".
  • 3. A simple electromagnetic relay consists of a coil of wire wrapped around a soft iron core, an iron yoke which provides a low reluctance path for magnetic flux, a movable iron armature, and one or more sets of contacts (there are two in the relay pictured). The armature is hinged to the yoke and mechanically linked to one or more sets of moving contacts. It is held in place by a spring so that when the relay is de-energized there is an air gap in the magnetic circuit. In this condition, one of the two sets of contacts in the relay pictured is closed, and the other set is open. Other relays may have more or fewer sets of contacts depending on their function. The relay in the picture also has a wire connecting the armature to the yoke. This ensures continuity of the circuit between the moving contacts on the armature, and the circuit track on the printed circuit board (PCB) via the yoke, which is soldered to the PCB.
  • 4. When the coil is energized with direct current, a diode is often placed across the coil to dissipate the energy from the collapsing magnetic field at deactivation, which would otherwise generate a voltage spike dangerous to semiconductor circuit components. Some automotive relays include a diode inside the relay case. Alternatively, a contact protection network consisting of a capacitor and resistor in series (snubber circuit) may absorb the surge. If the coil is designed to be energized with alternating current (AC), a small copper "shading ring" can be crimped to the end of the solenoid, creating a small out-of-phase current which increases the minimum pull on the armature during the AC cycle.
  • 5. Latching relay Latching relay with permanent magnet A latching relay (also called "impulse", "keep", or "stay" relays) maintains either contact position indefinitely without power applied to the coil. The advantage is that one coil consumes power only for an instant while the relay is being switched, and the relay contacts retain this setting across a power outage. A latching relay allows remote control of building lighting without the hum that may be produced from a continuously (AC) energized coil. In one mechanism, two opposing coils with an over-center spring or permanent magnet hold the contacts in position after the coil is de-energized. A pulse to one coil turns the relay on and a pulse to the opposite coil turns the relay off. This type is widely used where control is from simple switches or single-ended outputs of a control system, and such relays are found in avionics and numerous industrial applications.
  • 6. Reed relay Top, middle: reed switches, bottom: reed relay A reed relay is a reed switch enclosed in a solenoid. The switch has a set of contacts inside an evacuated or inert gas-filled glass tube which protects the contacts against atmospheric corrosion; the contacts are made of magnetic material that makes them move under the influence of the field of the enclosing solenoid or an external magnet. Reed relays can switch faster than larger relays and require very little power from the control circuit. However, they have relatively low switching current and voltage ratings. Though rare, the reeds can become magnetized over time, which makes them stick 'on' even when no current is present; changing the orientation of the reeds with respect to the solenoid's magnetic field can resolve this problem. Sealed contacts with mercury-wetted contacts have longer operating lives and less contact chatter than any other kind of relay.
  • 7. Mercury-wetted relay A mercury-wetted reed relay that has AC/DC switching specifications of 100 W, 500 V, 2 A maximum A mercury-wetted reed relay is a form of reed relay in which the contacts are wetted with mercury. Such relays are used to switch low-voltage signals (one volt or less) where the mercury reduces the contact resistance and associated voltage drop, for low-current signals where surface contamination may make for a poor contact, or for high-speed applications where the mercury eliminates contact bounce. Mercury wetted relays are position-sensitive and must be mounted vertically to work properly. Because of the toxicity and expense of liquid mercury, these relays are now rarely used. Mercury relay A mercury relay is a relay that uses mercury as the switching element. They are used where contact erosion would be a problem for conventional relay contacts. Owing to environmental considerations about significant amount of mercury used and modern alternatives, they are now comparatively uncommon.
  • 8. Machine tool relay Coaxial relay Contactor Solid state contactor relay Solid-state relay Forced-guided contacts relay Overload protection relay Vacuum relays Buchholz relay A Buchholz relay is a safety device sensing the accumulation of gas in large oil- filled transformers, which will alarm on slow accumulation of gas or shut down the transformer if gas is produced rapidly in the transformer oil.
  • 9. Relay performance tests address two questions. Is the relay operating as it was designed? Is the relay being applied properly? Integrity tests are intended to answer the first, and application tests the second. In the past, users have concentrated on integrity tests using relatively simple equipment in the field. Application tests required bulky and expensive equipment which was usually only available in relay manufacturers' plants, or in research laboratories. Historically, field test equipment was only suitable for steady-state tests and limited dynamic state simulations. Manufacturers and users developed comprehensive test plans to ensure the integrity of relays using passive test equipment. Integrity tests were also designed to be performed in the field using simple equipment. With common applications, the manufacturers application tests done during relay development will usually suffice to ensure correct operation under normal circumstances.
  • 10. Type Tests Type tests are required to prove that a relay meets the published specification and complies with all relevant standards. Since the principal function of a protection relay is to operate correctly under abnormal power conditions, it is essential that the performance be assessed under such conditions. Comprehensive type tests simulating the operational conditions are therefore conducted at the manufacturer's works during the development and certification of the equipment. The standards that cover most aspects of relay performance are IEC 60255 and ANSI C37.90. However compliance may also involve consideration of the requirements of IEC 61000, 60068 and 60529, while products intended for use in the EEC also have to comply with the requirements of Directives 89/336/EEC and 73/23/EEC. Since type testing of a digital or numerical relay involves testing of software as well as hardware, the type testing process is very complicated and more involved than a static or electromechanical relay.
  • 11. Commissioning Tests These tests are designed to prove that a particular protection scheme has been installed correctly prior to setting to work. All aspects of the scheme are thoroughly checked, from installation of the correct equipment through wiring checks and operation checks of the individual items of equipment, finishing with testing of the complete scheme. Periodic Maintenance Checks These are required to identify equipment failures and degradation in service, so that corrective action can be taken. Because a protection scheme only operates under fault conditions, defects may not be revealed for a significant period of time, until a fault occurs. Regular testing assists in detecting faults that would otherwise remain undetected until a fault occurs. Rating Tests Rating type tests are conducted to ensure that components are used within their specified ratings and that there are no fire or electric shock hazards under a normal load or fault condition of the power system. This is in addition to checking that the product complies with its technical specification. The following are amongst the rating type tests conducted on protection relays, the specified parameters are normally to IEC 60255-6.
  • 12. Functional Tests The functional tests consist of applying the appropriate inputs to the relay under test and measuring the performance to determine if it meets the specification. They are usually carried out under controlled environmental conditions. The testing may be extensive, even where only a simple relay function is being tested., as can be realised by considering the simple overcurrent relay element of Table 21.1. To determine compliance with the specification, the tests listed in Table 21.2 are required to be carried out. This is a time consuming task, involving many engineers and technicians. Hence it is expensive. When a modern numerical relay with many functions is considered, each of which has to be type-tested, the functional type-testing involved is a major issue. In the case of a recent relay development project, it was calculated that if one person had to do all the work, it would take 4 years to write the functional type-test specifications, 30 years to perform the tests and several years to write the test reports that result.
  • 13. D.C Interrupt Test This is a test to determine the maximum length of time that the relay can withstand an interruption in the auxiliary supply without de-energising, e.g. switching off, and that when this time is exceeded and it does transiently switch off, that no maloperation occurs. It simulates the effect of a loose fuse in the battery circuit, or a short circuit in the common d.c. supply, interrupted by a fuse. Another source of d.c. interruption is if there is a power system fault and the battery is supplying both the relay and the circuit breaker trip coils. When the battery energises the coils to initiate the circuit breaker trip, the voltage may fall below the required level for operation of the relay and hence a d.c. interrupt occurs. The test is specified in IEC 60255-11 and comprises a interruptions of 2, 5, 10, 20, 50, 100 and 200ms. For interruptions lasting up to and including 20ms, the relay must not de-energise of maloperate, while for longer interruptions it must not maloperate.
  • 14. Dynamic Relay Testing Dynamic relay testing means testing under true simulated power system conditions. Depending on the level of testing reąuired, test values can be easily calculated with PC-based short circuit or EMTP programs. For dynamic-state testing, a short circuit program would be used to calculate the fundamentai component of voltage and current values for pre-fault and fault conditions. For transient simulations, an EMTP program would be used to create waveforms that represent the fault condition. Dynamic-state testing and transient simulations provide a faster and more meaningful way to test relays and relay systems. These techniąues provide the user with a far better understanding of how the relay system performs and can aid both relay application and test engineers in evaluating relay operations. Dynamic-state testing is based on a power system model that is used to simulate different events selected according to the application. Events are played back through power system simulators that also monitor scheme performance. Each event is modeled to simulate conditions for the tested relay circuit but only for the time period needed to test.