COMPARISON ANALYSIS OF SHUNT ACTIVE
FILTER AND TRANSFORMERLESS PARALLEL
HYBRID ACTIVE FILTER
Sakshi Bangia1
, P.R.Sharma2
and Maneesha Garg3
1,2
Department of Electrical Engineering, YMCA University Of Science and
Technology, Faridabad
1
sakshibangia@gmail.com,2
prsharma1966@gmail.com
3
Department of Humanities and Applied Science , YMCA University Of
Science and Technology, Faridabad
Garg_maneesha@yahoo.com
ABSTRACT
This research work presents the comparison analysis of Shunt Active Filter (SAF) with Parallel
Hybrid Active Filter (PHAF). The performances of SAF and PHAF have been analyzed with PI
controllers based on Synchronous Reference Frame theory. In each case, simulation is carried
out for three phase unbalanced non liner load conditions. The advantages of the designed
system and the proposed current reference calculation methods are verified by simulations
using MATLAB Power system Toolbox.
KEYWORDS
Power quality, shunt active filter, transformer-less shunt hybrid active filter, Total Harmonic
Distortion
1. INTRODUCTION
Harmonics are injected in source current due to the application of non-linear load. These
harmonic currents influence the function of other equipment connected on the similar distribution
feeder, including the harmonic producing loads. Among number of solutions conventionally
passive filters offers a low cost solution. They generally offer high series impedance or low shunt
impedance to block the particular harmonic content. However there are certain disadvantages like
fixed compensation characteristics and resonances with the source impedance. Thus in orders to
prevail over the demerits associated with traditional passive filters, Active Power Filters (APF)
have been introduced in recent years. APF plays a vital role for controlling the amount of
harmonic pollution present in a distribution system. They can be connected in series, shunt or
combination of series and shunt with the supply impedance.
Typically shunt APF consists of a three phase voltage source inverter with capacitor on dc side.
For large power applications, it is difficult to implement a low loss and a low cost PWM
374 Computer Science & Information Technology (CS & IT)
converter. When this equipment is connected in shunt to the ac source impedance it is possible to
improve the compensation characteristics of the passive filters in parallel connection [1], [2].This
forms the transformerless Parallel Hybrid Active Filter The aim of PHAF is to mitigate the
problems associated with SAF and passive filters and to complement and enhance their
performance by adding active or passive components to their structure [3].Figure 1 shows the
block diagram of transformerless parallel hybrid filter.
Figure 1. Block Diagram of Parallel Hybrid Active Filter
2. PRINCIPLE OF OPERATION
Hybrid active filters effectively mitigate the problems of a passive and an active filter and provide
cost-effective harmonic compensation, particularly for high-power nonlinear loads [4].The
parallel hybrid filter consists of three phase voltage source inverter with capacitor on the dc side
connected in shunt with the tuned passive filter. Shunt passive filter is a series combination of a
capacitor and a reactor tuned to a specific harmonic frequency. Since nonlinear load contributes
the major contribution of harmonics in the source current mainly due to lower order harmonics
thus tuned filter provides low impedance trap to harmonic. Remaining higher order harmonics
only are to be filtered by shunt active filter; hence its power rating can be reduced The
compensation of harmonics in the source current through enhancement of the compensation
characteristics of the passive filters also eliminates the chances of resonance [5].
The performance of the PHAF depends on the computation of reference compensating signal.
Among many control strategies mentioned for estimating the reference compensating current
Instantaneous Reactive Power (IRP) theory [6, 7] and Synchronous Reference Frame (SRF) are
mostly used. [8].These schemes employ the computation of the reference components through
subtraction of positive sequence fundamental current component from the load/source current.
These control strategies are very attractive for their simplicity and ease of implementation, but
lack in providing adequate solution under extreme or severe condition of fault conditions in
Computer Science & Information Technology (CS & IT) 375
passive filter branch. SRF control technique using proportional integral (PI) type controller are is
implemented to strength the currents of the filter to follow their reference values.
3. SYSTEM CONFIGURATION
A three phase parallel hybrid active filter is implemented for unbalance nonlinear load. The test
system consists of shunt connected active filter with shunt passive LC elements tuned 5th
harmonic frequency which the most prominent frequency is causing the distortion in source
current. Passive filters are designed to result in minimum Root Mean Square (RMS) value of
supply current at full load [9,10]. Proposal of Synchronous Reference Frame theory is included
in [11].
4. DESIGN PARAMETERS OF SHUNT ACTIVE FILTER
A shunt active filter consists of three phase, 6 pulse voltage source inverter. The line-line voltage
is considered as 415V. The design for dc bus capacitor, dc bus voltage and ac inductor are as
follows.
4.1. DC Capacitor Voltage
The minimum dc bus voltage should be greater than twice of the peak of the phase voltage of the
system [13]. The dc bus voltage is calculated as
V dc
=
m
V LL−
3
22
(1)
where, m is the modulation index =1 and is considered as 1 and VLL is the ac line voltage of
three phase source.
4.2. DC Bus Capacitor
The value of dc bus capacitor (Cdc)is given by
taIVVVC dcdcdc
)(3)]()[(
2
1 2
1
2
=− (2)
where, Vdc is the reference dc voltage and Vdc1 is the minimum voltage level of dc bus, a is the
over loading factor taken as 1.2, V is the phase voltage, I is the phase current and t is time by
which the dc bus voltage is to be recovered.
4.3. AC Filter
The ac inductance (Lf) depends on the current ripple icr,p-p, switching frequency fs, dc bus voltage
(Vdc) .Thus Lf is given as
376 Computer Science & Information Technology (CS & IT)
Lf=
if
V
pcrps
dc
a
m
−
12
3
(3)
where, i crp-p ,= 5%
5. DESIGN PARAMETERS OF PASSIVE FILTER
The basic of shunt passive filter is to trap the tuned harmonic component in the source current
using LC circuit. At resonance frequency inductive reactance is equal to that of capacitive
reactance. Hence for single tuned filter, resonance frequency is given by
CL ff
f
π2
1
= (4)
Thus to design the size of capacitor, first step is to fixed the reactive power compensation .Hence
capacitance can be calculated by
filterkVAR
V
X LL
c
.
2
−
= (5)
where VL-L is line –line source voltage
kVAR is the fixed reactive power compensation
6. CONTROL STRATEGY
The main function of the SRF control strategy is to provide high resistance at the fundamental
frequency and also zero impedance is presented to harmonic current flowing in to the passive
filter. [12].The control diagram is shown in Fig 2.
Fig 2 Synchronous Reference Frame Control Scheme
Computer Science & Information Technology (CS & IT) 377
In this three phase load current is transformed into d-q stationary reference frame using Parks
Transformation. Using this fundamental component appears as DC quantities and all other
harmonics are transformed as non-DC quantities. These quantities are not required hence these
can be filter out using low pass filter. The extracted dc components and are transformed back into
a–b–c coordinates to obtain the fundamental components of source currents. To compensate for
the inverter losses PI controller is applied to regulate the DC bus voltage.
The output of PI controller at the dc bus voltage of active filter is considered as the current (iloss)
for meeting its losses.
vkvvkii ndeidndendepdnlossnloss )()1()()1()(
)( +−+= −−
(6)
where, vv ndede )1( −
− is the error between the reference(vdc*) and sensed (vdc) dc
voltage at the nth sampling instant. Kpd and Kid are the proportional and the integral gains of the
dc bus voltage PI controller.
The reference source current is therefore expressed as,
iii lossddd
+=
*
(7)
Similarly PI controller is used to regulate reactive power
vkvvkii nteiqntentepqnqrsnqr )()1()()1()(
)( +−+= −−
(8)
The reference supply quadrature axis current is as
iii qrqdq
+=
*
(9)
where, vvv nsnte )(
*
)(
−= denotes the error between reference (vs*) and actual(vs(n)) terminal
voltage amplitudes at the n sampling instant. Kpq and Kiq are the proportional and the integral
gains of the PI controller.
7. MATLAB IMPLEMENTATION
A three phase transformerless hybrid active filter is implemented using MATLAB Power system
Toolbox. Three phase input source voltage of 415V, 50 Hz frequency with source resistance of
0.2 ohms and inductance of 2mH is considered. A three phase unbalance nonlinear load drawing
5A is considered for simulation. Shunt active filter is constituted of 6 pulse VSI with 2200 e-6F
of capacitance attached to the DC side. A small-rated filter has been included to minimize the
switching ripples at the inverter output. Passive elements of the filter are calculated using the
mathematical relation s considering 50% of fixed reactive compensation. Table1 gives the
detailed parameters of the system.
378 Computer Science & Information Technology (CS & IT)
Table 1. Detailed Parameters of the System.
Parameters Values
Supply voltage 415V (L-L), 50 Hz
Loads: (i) Linear: phase a= 25
Phase b=10 and 80mH
Phase c =10 and 80 mH
(ii) Nonlinear: Three phase
full bridge rectifier drawing
15A
Shunt Active Filter:
Interfacing
Inductance
Lf = 5.5 mH
DC bus capacitance 22000e-6F.
Referenced Dc
voltage
750 V
Tuned Passive Filter C5=129.4e-6F ;L5=3.1mH
8. RESULTS AND DISCUSSION
The performance of the presented SRF control strategy is evaluated using by comparison of pure
shunt active power filter and parallel hybrid power filter. The three phase unbalance nonlinear
load considered here in the present system contains 5th harmonic content as the most prominent
factor which causes the distortion in the source current. Hence the passive elements of the hybrid
filter are tuned for the resonance frequency of 250Hz. The VA rating required for the inverter in
the hybrid filter is much lesser than that required in a pure shunt active filter.
The VA rating required of the inverter in parallel hybrid power active filter is given by
VA rating= 3
22
IV FMAXdc
××
Where I FMAX A13≅ is the maximum filter current.
Also the apparent power rating of nonlinear load is given by
VA rating= IV LrmsSrms
××3
Where VSrms and ILrms are the RMS value of source voltage taken as 415 V and load current taken
as 38A.
The apparent ratio of the parallel hybrid filter and nonlinear load is greatly reduced by 16%.
Another factor which determines the validation of active filters is Total Harmonic Distortion
(THD) is reduced from14.74 % to 2.65 % for phase a. Table II shows the THD for all three
phases for different types of filter. It can be seen from Fig 5 and Table III that parallel hybrid
filter system is able to reduce the 5th harmonic of supply current to 1.68% .The THD of the ac
supply current reduces to 3.27% with pure shunt active power filters alone as the major
component of the load current without any filter is composed of 5th harmonic.
Computer Science & Information Technology (CS & IT) 379
TABLE III Harmonic Current in Percentage of Fundamental Current
5th 7th 11th 13th 17th 19th
Load current 12.76 5.42 3.92 2.23 1.55 0.97
Source current
with Passive Filter
0.20 2.69 2.57 1.64 1.13 0.89
Source current
with Pure Shunt
Active Filter
1.83 0.54 0.64 0.65 0.83 0.05
Source current
with Shunt Hybrid
Active Filter
1.68 1.03 0.23 0.21 0.19 0.13
Figure 3 shows the waveform of load current without filter. Fig 4 and 5 shows the waveform of
source current with pure shunt active filter and parallel hybrid active filter respectively. These
waveforms clearly illustrates that load current is very distorted that implies source current at this
time without filtering is also very distorted . With the application of power filter source currents
can be made sinusoidal .Clearly with the application of parallel hybrid active filter source current
is less distorted and contains less harmonics content as compared to pure shunt active filter. Fig 6
shows the uncompensated and compensated reactive power using parallel hybrid active filter
.Since the passive elements are tuned at fixed 50% compensation, fig 6 clearly validates the
passive parameters of hybrid filter. Fig7 demonstrates the source voltage, source current, load
voltage, load current, DC bus voltage, and filter current for parallel hybrid active filter.
TABLE II THD For Different Phases (in percentage)
Phase
Phase a Phas
e b
Phase
cType of filter
Load current
without filter
14.74 16.27 19.66
Pure shunt active
filter
3.27 4.58 3.75
Parallel hybrid filter 2.65 3.15 2.64
380 Computer Science & Information Technology (CS & IT)
Figure 3 Load current
Figure 4 Source Current with Pure Active Filter
Figure 4 Source Current with Parallel Hybrid Active Filter
Figure 6 Load Reactive Power and Source Reactive power using parallel Hybrid Active Filter
Computer Science & Information Technology (CS & IT) 381
Figure 7 Source Voltage, Source Current, Load Voltage, Load Current, DC Bus Voltage, Filter Current.
9. CONCLUSIONS
In this work, concept of transformerless parallel hybrid active filter is defined and verified by
MATLAB simulation. Simulation results verify that presented method has good performance in
the elimination of selective harmonic content and Total Harmonic Distortion. It has much better
dynamic response with less rating compared with the pure shunt active filter.
REFERENCES
[1] B. Singh, K. Al-Haddad, and A. Chandra, “A review of active filters for power quality improvement,”
IEEE Trans. Ind. Electron., vol. 46, no. 5, pp. 960–971, Oct. 1999.
[2] J.W. Dixon, G. Venegas, and L. A.Moran, “A series active power filter based on a sinusoidal current-
controlled voltage-source inverter,” IEEE Trans. Ind. Electron., vol. 44, no. 5, pp. 612–620, Oct.
1997.
[3] Bhattacharya,Divan,”Synchronous Frame based controller implementation for a hybrid series active
filter,Confeence record of IEEE Industry Apllications Conference Vol, 3,pp. 2531-2540 October
1995.
[4] S. Srianthumrong and H. Akagi, “A medium-voltage transformerless AC/DC power conversion
system consisting of a diode rectifier and a shunt hybrid filter,” IEEE Trans. Ind. Appl., vol. 39, no. 3,
pp. 874–882, May/Jun. 2003.
[5] H. Fujita, T. Yamasaki and H. Akagi, "A hybrid active filter for damping of harmonic resonance in
industrial power systems," IEEE Trans. on Power Electronics, vol. 15, no. 2, pp. 215-222, March
2000.
382 Computer Science & Information Technology (CS & IT)
[6] H. Fujita, H. Akagi, "A Practical Approach to Harmonic Compensation in Power Systems-Series
Connection of Passive, Active Filters," IEEE Trans. on Ind.. Appl., vol.27, no.6, pp. 1020-1025,
Nov./Dec. 1991.
[7] F.B. Libano, J.A.Cobos, J. Uceda, "Simplified control strategy for Hybrid Active Filters", IEEE
PESC Record, 1 997, pp 1102-1108.
[8] P.T. Cheng, S. Bhattacharya and D. Divan, "Experimental Verification of Dominant Harmonic Active
Filter for High Power Applications",IEEE Trans. on Ind. Appl., vol. 36, pp.567-577, March/April,
2000.
[9] IEEE Guide for Application and Specification of Harmonic Filters IEEE Std 1531-2003.
[10] V, Verma, S. Shanker, B. Singh, A. Chandra, and Kamal Al- Haddad, "Genetic Algorithm Based
Design of Passive Filters for Offshore Applications," Proc. ofIEEE PCIC '04, 2004, pp 55-62.
[11] S. Bhattacharya, D. Divan and B. Banerjee, “Synchronous frame harmonic isolator using active series
filter,” EPE-Firenze, Vol. 3, pp. 30-35, 1991.
[12] V, Verma, S. Shanker, B. Singh,’Design and Implemention of Current Controlled Parallel Hybrid
Power Filter.
[13] B.N.Singh, P.Rastgoufard, B.Singh, A.Chandra and K.Al.Haddad, “Design,simulation and
implementation of three pole/ four pole topologies for active filters,” IEE Eletr. Power Appl., vol.
151, no. 4, pp. 467-476, July 2004.
Authors
Sakshi Bangia received the B.Tech degree in Instrumentation and Control from MDU
Rohtak and M.Tech degree in Electrical Engg. from YMCA UST in 2004 and 2006,
respectively. She is pursuing Ph.D in Power Quality from Maharishi Dayanand
University, India. Presently she is working as Assistant Professor in Electrical
Engineering Department at YMCA UST Faridabad.
Dr. P.R.Sharma was born in 1966 in India. He is currently working as Chairman of
the Department in Electrical Engg. in YMCA University Of Science and
Technology, Faridabad. He received his B.E Electrical Engineering in 1988 from
Punjab University Chandigarh, M.Tech in Electrical Engineering (Power System)
from Regional Engineering College Kurukshetra in 1990 and Ph.D from
M.D.University Rohtak in 2005. He started his carrier from industry. He has vast
experience in the industry and teaching. His area of interest is Optimal location and
coordinated control of FACTS devices ,power system stability and control
Dr. Maneesha Garg did her Ph.D(Physics) in 2002 from Kurukshetra University,
India. After that she worked as Research Associate granted by CSIR, in NIT
Kurukshetra for 4 years. She has 18 publications in national, international journals
and more than 30 papers in conferences to her credit. Presently she is working as
Assistant Professor in Humanities and Applied Science Department, YMCA UST,
Faridabad and guiding 4 scholars for their research work.

More Related Content

What's hot

Optimize Controlling of Active Filters Controlled by Pi Controller
Optimize Controlling of Active Filters Controlled by Pi ControllerOptimize Controlling of Active Filters Controlled by Pi Controller
Optimize Controlling of Active Filters Controlled by Pi ControllerIRJET Journal
 
Volume 2-issue-6-1950-1954
Volume 2-issue-6-1950-1954Volume 2-issue-6-1950-1954
Volume 2-issue-6-1950-1954Editor IJARCET
 
Modified Synchronous Reference Frame based Harmonic Extraction for Shunt Acti...
Modified Synchronous Reference Frame based Harmonic Extraction for Shunt Acti...Modified Synchronous Reference Frame based Harmonic Extraction for Shunt Acti...
Modified Synchronous Reference Frame based Harmonic Extraction for Shunt Acti...IJPEDS-IAES
 
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...IJMTST Journal
 
REDUCTION IN THE TRANSIENT TIME OF SHUNT ACTIVE FILTERS USING INTELLIGENT CON...
REDUCTION IN THE TRANSIENT TIME OF SHUNT ACTIVE FILTERS USING INTELLIGENT CON...REDUCTION IN THE TRANSIENT TIME OF SHUNT ACTIVE FILTERS USING INTELLIGENT CON...
REDUCTION IN THE TRANSIENT TIME OF SHUNT ACTIVE FILTERS USING INTELLIGENT CON...ijscmc
 
Neural Network based p-q-r Theory for Harmonic Reduction and Neutral Current ...
Neural Network based p-q-r Theory for Harmonic Reduction and Neutral Current ...Neural Network based p-q-r Theory for Harmonic Reduction and Neutral Current ...
Neural Network based p-q-r Theory for Harmonic Reduction and Neutral Current ...IJECEIAES
 
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...INFOGAIN PUBLICATION
 
IRJET- Power Quality Improvement using Active Power Filter
IRJET- Power Quality Improvement using Active Power FilterIRJET- Power Quality Improvement using Active Power Filter
IRJET- Power Quality Improvement using Active Power FilterIRJET Journal
 
Load Flow Analysis of Jamshoro Thermal Power Station (JTPS) Pakistan Using MA...
Load Flow Analysis of Jamshoro Thermal Power Station (JTPS) Pakistan Using MA...Load Flow Analysis of Jamshoro Thermal Power Station (JTPS) Pakistan Using MA...
Load Flow Analysis of Jamshoro Thermal Power Station (JTPS) Pakistan Using MA...sunny katyara
 
IJCER (www.ijceronline.com) International Journal of computational Engineerin...
IJCER (www.ijceronline.com) International Journal of computational Engineerin...IJCER (www.ijceronline.com) International Journal of computational Engineerin...
IJCER (www.ijceronline.com) International Journal of computational Engineerin...ijceronline
 

What's hot (19)

[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
[IJET V2I2P30] Authors: AnkurGheewala, Jay Chanawala,Nikhil Jadav,Modi Rishit...
 
Lr3421092114
Lr3421092114Lr3421092114
Lr3421092114
 
Optimize Controlling of Active Filters Controlled by Pi Controller
Optimize Controlling of Active Filters Controlled by Pi ControllerOptimize Controlling of Active Filters Controlled by Pi Controller
Optimize Controlling of Active Filters Controlled by Pi Controller
 
Volume 2-issue-6-1950-1954
Volume 2-issue-6-1950-1954Volume 2-issue-6-1950-1954
Volume 2-issue-6-1950-1954
 
K1102016673
K1102016673K1102016673
K1102016673
 
Modified Synchronous Reference Frame based Harmonic Extraction for Shunt Acti...
Modified Synchronous Reference Frame based Harmonic Extraction for Shunt Acti...Modified Synchronous Reference Frame based Harmonic Extraction for Shunt Acti...
Modified Synchronous Reference Frame based Harmonic Extraction for Shunt Acti...
 
Predictive Approach for Power Quality Improvement Based Direct Power Control
Predictive Approach for Power Quality Improvement Based Direct Power ControlPredictive Approach for Power Quality Improvement Based Direct Power Control
Predictive Approach for Power Quality Improvement Based Direct Power Control
 
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...
 
REDUCTION IN THE TRANSIENT TIME OF SHUNT ACTIVE FILTERS USING INTELLIGENT CON...
REDUCTION IN THE TRANSIENT TIME OF SHUNT ACTIVE FILTERS USING INTELLIGENT CON...REDUCTION IN THE TRANSIENT TIME OF SHUNT ACTIVE FILTERS USING INTELLIGENT CON...
REDUCTION IN THE TRANSIENT TIME OF SHUNT ACTIVE FILTERS USING INTELLIGENT CON...
 
Design of PI and Fuzzy Logic Controllers for Distribution Static Compensator
Design of PI and Fuzzy Logic Controllers for Distribution Static CompensatorDesign of PI and Fuzzy Logic Controllers for Distribution Static Compensator
Design of PI and Fuzzy Logic Controllers for Distribution Static Compensator
 
Load flow studies 19
Load flow studies 19Load flow studies 19
Load flow studies 19
 
Neural Network based p-q-r Theory for Harmonic Reduction and Neutral Current ...
Neural Network based p-q-r Theory for Harmonic Reduction and Neutral Current ...Neural Network based p-q-r Theory for Harmonic Reduction and Neutral Current ...
Neural Network based p-q-r Theory for Harmonic Reduction and Neutral Current ...
 
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
 
Comparison of Cascaded H-bridge Inverters for Harmonic Mitigation Considerin...
Comparison of Cascaded H-bridge Inverters for Harmonic  Mitigation Considerin...Comparison of Cascaded H-bridge Inverters for Harmonic  Mitigation Considerin...
Comparison of Cascaded H-bridge Inverters for Harmonic Mitigation Considerin...
 
IRJET- Power Quality Improvement using Active Power Filter
IRJET- Power Quality Improvement using Active Power FilterIRJET- Power Quality Improvement using Active Power Filter
IRJET- Power Quality Improvement using Active Power Filter
 
Load Flow Analysis of Jamshoro Thermal Power Station (JTPS) Pakistan Using MA...
Load Flow Analysis of Jamshoro Thermal Power Station (JTPS) Pakistan Using MA...Load Flow Analysis of Jamshoro Thermal Power Station (JTPS) Pakistan Using MA...
Load Flow Analysis of Jamshoro Thermal Power Station (JTPS) Pakistan Using MA...
 
Computer Application in Power system: Chapter two - load flow analysis
Computer Application in Power system: Chapter two - load flow analysisComputer Application in Power system: Chapter two - load flow analysis
Computer Application in Power system: Chapter two - load flow analysis
 
Power System Review
Power System ReviewPower System Review
Power System Review
 
IJCER (www.ijceronline.com) International Journal of computational Engineerin...
IJCER (www.ijceronline.com) International Journal of computational Engineerin...IJCER (www.ijceronline.com) International Journal of computational Engineerin...
IJCER (www.ijceronline.com) International Journal of computational Engineerin...
 

Viewers also liked

An exploration of periocular region with reduced region for authentication re...
An exploration of periocular region with reduced region for authentication re...An exploration of periocular region with reduced region for authentication re...
An exploration of periocular region with reduced region for authentication re...csandit
 
OLICO Youth facilitators' handbook
OLICO Youth facilitators' handbookOLICO Youth facilitators' handbook
OLICO Youth facilitators' handbookNathalia von Witt
 
Ação Direta de Inconstitucionalidade contra acordos de leniência
Ação Direta de Inconstitucionalidade contra acordos de leniênciaAção Direta de Inconstitucionalidade contra acordos de leniência
Ação Direta de Inconstitucionalidade contra acordos de leniênciaRaul Jungmann
 
THE DIGITAL STORY OF THE NATIVITY - História do Natal Digital
THE DIGITAL STORY OF THE NATIVITY - História do Natal DigitalTHE DIGITAL STORY OF THE NATIVITY - História do Natal Digital
THE DIGITAL STORY OF THE NATIVITY - História do Natal DigitalJorge Teixeira
 
Soap Opera Trailer Pitch
Soap Opera Trailer PitchSoap Opera Trailer Pitch
Soap Opera Trailer PitchBelinda Raji
 
WpMoney — 5 способов заработать с WordPress
WpMoney — 5 способов заработать с WordPressWpMoney — 5 способов заработать с WordPress
WpMoney — 5 способов заработать с WordPressNikolay Mironov
 
Différents types de riz gluant du vietnamien
Différents types de riz gluant du vietnamienDifférents types de riz gluant du vietnamien
Différents types de riz gluant du vietnamienVietnam Original Travel
 
Go deep to the sewer
Go deep to the sewer Go deep to the sewer
Go deep to the sewer uploadlessons
 
La critique de cinéma en France: du professionnel omniscient au spectateur pa...
La critique de cinéma en France: du professionnel omniscient au spectateur pa...La critique de cinéma en France: du professionnel omniscient au spectateur pa...
La critique de cinéma en France: du professionnel omniscient au spectateur pa...Marie Massou
 
Phrasal verbs - Luz Mary Rodriguez
Phrasal verbs - Luz Mary RodriguezPhrasal verbs - Luz Mary Rodriguez
Phrasal verbs - Luz Mary RodriguezDeyna Riascos
 
Contextual model of recommending resources on an academic networking portal
Contextual model of recommending resources on an academic networking portalContextual model of recommending resources on an academic networking portal
Contextual model of recommending resources on an academic networking portalcsandit
 
Baromètre Odoxa pour Aviva / BFM / Challenges - novembre 2015
Baromètre Odoxa pour Aviva / BFM / Challenges - novembre 2015Baromètre Odoxa pour Aviva / BFM / Challenges - novembre 2015
Baromètre Odoxa pour Aviva / BFM / Challenges - novembre 2015Abeille Assurances
 

Viewers also liked (18)

Weekly Market Review - October 4, 2013
Weekly Market Review - October 4, 2013Weekly Market Review - October 4, 2013
Weekly Market Review - October 4, 2013
 
An exploration of periocular region with reduced region for authentication re...
An exploration of periocular region with reduced region for authentication re...An exploration of periocular region with reduced region for authentication re...
An exploration of periocular region with reduced region for authentication re...
 
OLICO Youth facilitators' handbook
OLICO Youth facilitators' handbookOLICO Youth facilitators' handbook
OLICO Youth facilitators' handbook
 
Ação Direta de Inconstitucionalidade contra acordos de leniência
Ação Direta de Inconstitucionalidade contra acordos de leniênciaAção Direta de Inconstitucionalidade contra acordos de leniência
Ação Direta de Inconstitucionalidade contra acordos de leniência
 
File Ramos
File RamosFile Ramos
File Ramos
 
THE DIGITAL STORY OF THE NATIVITY - História do Natal Digital
THE DIGITAL STORY OF THE NATIVITY - História do Natal DigitalTHE DIGITAL STORY OF THE NATIVITY - História do Natal Digital
THE DIGITAL STORY OF THE NATIVITY - História do Natal Digital
 
Soap Opera Trailer Pitch
Soap Opera Trailer PitchSoap Opera Trailer Pitch
Soap Opera Trailer Pitch
 
WpMoney — 5 способов заработать с WordPress
WpMoney — 5 способов заработать с WordPressWpMoney — 5 способов заработать с WordPress
WpMoney — 5 способов заработать с WordPress
 
Tamadi.
Tamadi.Tamadi.
Tamadi.
 
Différents types de riz gluant du vietnamien
Différents types de riz gluant du vietnamienDifférents types de riz gluant du vietnamien
Différents types de riz gluant du vietnamien
 
Go deep to the sewer
Go deep to the sewer Go deep to the sewer
Go deep to the sewer
 
TURISMO EN EL ECUADOR RAQUEL JIMÈNEZ
TURISMO EN EL ECUADOR RAQUEL JIMÈNEZTURISMO EN EL ECUADOR RAQUEL JIMÈNEZ
TURISMO EN EL ECUADOR RAQUEL JIMÈNEZ
 
La critique de cinéma en France: du professionnel omniscient au spectateur pa...
La critique de cinéma en France: du professionnel omniscient au spectateur pa...La critique de cinéma en France: du professionnel omniscient au spectateur pa...
La critique de cinéma en France: du professionnel omniscient au spectateur pa...
 
Contoh data
Contoh dataContoh data
Contoh data
 
Phrasal verbs - Luz Mary Rodriguez
Phrasal verbs - Luz Mary RodriguezPhrasal verbs - Luz Mary Rodriguez
Phrasal verbs - Luz Mary Rodriguez
 
Я.Ю.Якунін. Упровадження мультипрофільного навчання в середній загальноосвітн...
Я.Ю.Якунін. Упровадження мультипрофільного навчання в середній загальноосвітн...Я.Ю.Якунін. Упровадження мультипрофільного навчання в середній загальноосвітн...
Я.Ю.Якунін. Упровадження мультипрофільного навчання в середній загальноосвітн...
 
Contextual model of recommending resources on an academic networking portal
Contextual model of recommending resources on an academic networking portalContextual model of recommending resources on an academic networking portal
Contextual model of recommending resources on an academic networking portal
 
Baromètre Odoxa pour Aviva / BFM / Challenges - novembre 2015
Baromètre Odoxa pour Aviva / BFM / Challenges - novembre 2015Baromètre Odoxa pour Aviva / BFM / Challenges - novembre 2015
Baromètre Odoxa pour Aviva / BFM / Challenges - novembre 2015
 

Similar to Comparison analysis of shunt active filter and transformerless parallel hybrid active filter

Three-phase four-wire shunt hybrid active power filter model with model pred...
Three-phase four-wire shunt hybrid active power filter model  with model pred...Three-phase four-wire shunt hybrid active power filter model  with model pred...
Three-phase four-wire shunt hybrid active power filter model with model pred...IJECEIAES
 
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...IRJET Journal
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Scienceresearchinventy
 
Power System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power FilterPower System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power FilterIJERA Editor
 
HARMONIC MITIGATION USING D STATCOM THROUGH A CURRENT CONTROL TECHNIQUE
HARMONIC MITIGATION USING D STATCOM THROUGH A CURRENT CONTROL TECHNIQUEHARMONIC MITIGATION USING D STATCOM THROUGH A CURRENT CONTROL TECHNIQUE
HARMONIC MITIGATION USING D STATCOM THROUGH A CURRENT CONTROL TECHNIQUEJournal For Research
 
Volume 2-issue-6-1950-1954
Volume 2-issue-6-1950-1954Volume 2-issue-6-1950-1954
Volume 2-issue-6-1950-1954Editor IJARCET
 
Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...
Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...
Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...IJERA Editor
 
Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...
Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...
Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...IJERA Editor
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
T Source Inverter Based Shunt Active Filter with LCL Passive Filter for the 4...
T Source Inverter Based Shunt Active Filter with LCL Passive Filter for the 4...T Source Inverter Based Shunt Active Filter with LCL Passive Filter for the 4...
T Source Inverter Based Shunt Active Filter with LCL Passive Filter for the 4...IJPEDS-IAES
 
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...IJERA Editor
 
An Improved Double Fuzzy PI Controller For Shunt Active Power Filter DC Bus R...
An Improved Double Fuzzy PI Controller For Shunt Active Power Filter DC Bus R...An Improved Double Fuzzy PI Controller For Shunt Active Power Filter DC Bus R...
An Improved Double Fuzzy PI Controller For Shunt Active Power Filter DC Bus R...IJPEDS-IAES
 
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...IJPEDS-IAES
 
PI and fuzzy logic controllers for shunt active power filter
PI and fuzzy logic controllers for shunt active power filterPI and fuzzy logic controllers for shunt active power filter
PI and fuzzy logic controllers for shunt active power filterISA Interchange
 
Power system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filterPower system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filtereSAT Publishing House
 
Dd31477485
Dd31477485Dd31477485
Dd31477485IJMER
 

Similar to Comparison analysis of shunt active filter and transformerless parallel hybrid active filter (20)

Three-phase four-wire shunt hybrid active power filter model with model pred...
Three-phase four-wire shunt hybrid active power filter model  with model pred...Three-phase four-wire shunt hybrid active power filter model  with model pred...
Three-phase four-wire shunt hybrid active power filter model with model pred...
 
Adaptive Method for Power Quality Improvement through Minimization of Harmoni...
Adaptive Method for Power Quality Improvement through Minimization of Harmoni...Adaptive Method for Power Quality Improvement through Minimization of Harmoni...
Adaptive Method for Power Quality Improvement through Minimization of Harmoni...
 
Fractional Order PID Controlled Interleaved Boost converter Fed Shunt Active ...
Fractional Order PID Controlled Interleaved Boost converter Fed Shunt Active ...Fractional Order PID Controlled Interleaved Boost converter Fed Shunt Active ...
Fractional Order PID Controlled Interleaved Boost converter Fed Shunt Active ...
 
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...
 
B360614
B360614B360614
B360614
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Science
 
Power System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power FilterPower System Harmonic Compensation Using Shunt Active Power Filter
Power System Harmonic Compensation Using Shunt Active Power Filter
 
HARMONIC MITIGATION USING D STATCOM THROUGH A CURRENT CONTROL TECHNIQUE
HARMONIC MITIGATION USING D STATCOM THROUGH A CURRENT CONTROL TECHNIQUEHARMONIC MITIGATION USING D STATCOM THROUGH A CURRENT CONTROL TECHNIQUE
HARMONIC MITIGATION USING D STATCOM THROUGH A CURRENT CONTROL TECHNIQUE
 
Volume 2-issue-6-1950-1954
Volume 2-issue-6-1950-1954Volume 2-issue-6-1950-1954
Volume 2-issue-6-1950-1954
 
Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...
Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...
Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...
 
Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...
Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...
Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
T Source Inverter Based Shunt Active Filter with LCL Passive Filter for the 4...
T Source Inverter Based Shunt Active Filter with LCL Passive Filter for the 4...T Source Inverter Based Shunt Active Filter with LCL Passive Filter for the 4...
T Source Inverter Based Shunt Active Filter with LCL Passive Filter for the 4...
 
Sapf2
Sapf2Sapf2
Sapf2
 
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
 
An Improved Double Fuzzy PI Controller For Shunt Active Power Filter DC Bus R...
An Improved Double Fuzzy PI Controller For Shunt Active Power Filter DC Bus R...An Improved Double Fuzzy PI Controller For Shunt Active Power Filter DC Bus R...
An Improved Double Fuzzy PI Controller For Shunt Active Power Filter DC Bus R...
 
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
 
PI and fuzzy logic controllers for shunt active power filter
PI and fuzzy logic controllers for shunt active power filterPI and fuzzy logic controllers for shunt active power filter
PI and fuzzy logic controllers for shunt active power filter
 
Power system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filterPower system harmonic reduction using shunt active filter
Power system harmonic reduction using shunt active filter
 
Dd31477485
Dd31477485Dd31477485
Dd31477485
 

Recently uploaded

Install Stable Diffusion in windows machine
Install Stable Diffusion in windows machineInstall Stable Diffusion in windows machine
Install Stable Diffusion in windows machinePadma Pradeep
 
Designing IA for AI - Information Architecture Conference 2024
Designing IA for AI - Information Architecture Conference 2024Designing IA for AI - Information Architecture Conference 2024
Designing IA for AI - Information Architecture Conference 2024Enterprise Knowledge
 
Pigging Solutions Piggable Sweeping Elbows
Pigging Solutions Piggable Sweeping ElbowsPigging Solutions Piggable Sweeping Elbows
Pigging Solutions Piggable Sweeping ElbowsPigging Solutions
 
Transcript: New from BookNet Canada for 2024: BNC BiblioShare - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC BiblioShare - Tech Forum 2024Transcript: New from BookNet Canada for 2024: BNC BiblioShare - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC BiblioShare - Tech Forum 2024BookNet Canada
 
APIForce Zurich 5 April Automation LPDG
APIForce Zurich 5 April  Automation LPDGAPIForce Zurich 5 April  Automation LPDG
APIForce Zurich 5 April Automation LPDGMarianaLemus7
 
Scanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsScanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsRizwan Syed
 
Unlocking the Potential of the Cloud for IBM Power Systems
Unlocking the Potential of the Cloud for IBM Power SystemsUnlocking the Potential of the Cloud for IBM Power Systems
Unlocking the Potential of the Cloud for IBM Power SystemsPrecisely
 
08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking MenDelhi Call girls
 
Unleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubUnleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubKalema Edgar
 
Presentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreterPresentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreternaman860154
 
Breaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountBreaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountPuma Security, LLC
 
The Codex of Business Writing Software for Real-World Solutions 2.pptx
The Codex of Business Writing Software for Real-World Solutions 2.pptxThe Codex of Business Writing Software for Real-World Solutions 2.pptx
The Codex of Business Writing Software for Real-World Solutions 2.pptxMalak Abu Hammad
 
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | DelhiFULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhisoniya singh
 
Pigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food ManufacturingPigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food ManufacturingPigging Solutions
 
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024BookNet Canada
 
Enhancing Worker Digital Experience: A Hands-on Workshop for Partners
Enhancing Worker Digital Experience: A Hands-on Workshop for PartnersEnhancing Worker Digital Experience: A Hands-on Workshop for Partners
Enhancing Worker Digital Experience: A Hands-on Workshop for PartnersThousandEyes
 
Beyond Boundaries: Leveraging No-Code Solutions for Industry Innovation
Beyond Boundaries: Leveraging No-Code Solutions for Industry InnovationBeyond Boundaries: Leveraging No-Code Solutions for Industry Innovation
Beyond Boundaries: Leveraging No-Code Solutions for Industry InnovationSafe Software
 
How to convert PDF to text with Nanonets
How to convert PDF to text with NanonetsHow to convert PDF to text with Nanonets
How to convert PDF to text with Nanonetsnaman860154
 

Recently uploaded (20)

Install Stable Diffusion in windows machine
Install Stable Diffusion in windows machineInstall Stable Diffusion in windows machine
Install Stable Diffusion in windows machine
 
Designing IA for AI - Information Architecture Conference 2024
Designing IA for AI - Information Architecture Conference 2024Designing IA for AI - Information Architecture Conference 2024
Designing IA for AI - Information Architecture Conference 2024
 
Pigging Solutions Piggable Sweeping Elbows
Pigging Solutions Piggable Sweeping ElbowsPigging Solutions Piggable Sweeping Elbows
Pigging Solutions Piggable Sweeping Elbows
 
Transcript: New from BookNet Canada for 2024: BNC BiblioShare - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC BiblioShare - Tech Forum 2024Transcript: New from BookNet Canada for 2024: BNC BiblioShare - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC BiblioShare - Tech Forum 2024
 
APIForce Zurich 5 April Automation LPDG
APIForce Zurich 5 April  Automation LPDGAPIForce Zurich 5 April  Automation LPDG
APIForce Zurich 5 April Automation LPDG
 
E-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptx
E-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptxE-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptx
E-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptx
 
Scanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsScanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL Certs
 
Unlocking the Potential of the Cloud for IBM Power Systems
Unlocking the Potential of the Cloud for IBM Power SystemsUnlocking the Potential of the Cloud for IBM Power Systems
Unlocking the Potential of the Cloud for IBM Power Systems
 
08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men
 
Unleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubUnleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding Club
 
Presentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreterPresentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreter
 
Breaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountBreaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path Mount
 
The Codex of Business Writing Software for Real-World Solutions 2.pptx
The Codex of Business Writing Software for Real-World Solutions 2.pptxThe Codex of Business Writing Software for Real-World Solutions 2.pptx
The Codex of Business Writing Software for Real-World Solutions 2.pptx
 
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | DelhiFULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
 
Pigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food ManufacturingPigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food Manufacturing
 
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
 
Enhancing Worker Digital Experience: A Hands-on Workshop for Partners
Enhancing Worker Digital Experience: A Hands-on Workshop for PartnersEnhancing Worker Digital Experience: A Hands-on Workshop for Partners
Enhancing Worker Digital Experience: A Hands-on Workshop for Partners
 
Beyond Boundaries: Leveraging No-Code Solutions for Industry Innovation
Beyond Boundaries: Leveraging No-Code Solutions for Industry InnovationBeyond Boundaries: Leveraging No-Code Solutions for Industry Innovation
Beyond Boundaries: Leveraging No-Code Solutions for Industry Innovation
 
Vulnerability_Management_GRC_by Sohang Sengupta.pptx
Vulnerability_Management_GRC_by Sohang Sengupta.pptxVulnerability_Management_GRC_by Sohang Sengupta.pptx
Vulnerability_Management_GRC_by Sohang Sengupta.pptx
 
How to convert PDF to text with Nanonets
How to convert PDF to text with NanonetsHow to convert PDF to text with Nanonets
How to convert PDF to text with Nanonets
 

Comparison analysis of shunt active filter and transformerless parallel hybrid active filter

  • 1. Jan Zizka (Eds) : CCSIT, SIPP, AISC, PDCTA - 2013 pp. 373–382, 2013. © CS & IT-CSCP 2013 DOI : 10.5121/csit.2013.3642 COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRID ACTIVE FILTER Sakshi Bangia1 , P.R.Sharma2 and Maneesha Garg3 1,2 Department of Electrical Engineering, YMCA University Of Science and Technology, Faridabad 1 sakshibangia@gmail.com,2 prsharma1966@gmail.com 3 Department of Humanities and Applied Science , YMCA University Of Science and Technology, Faridabad Garg_maneesha@yahoo.com ABSTRACT This research work presents the comparison analysis of Shunt Active Filter (SAF) with Parallel Hybrid Active Filter (PHAF). The performances of SAF and PHAF have been analyzed with PI controllers based on Synchronous Reference Frame theory. In each case, simulation is carried out for three phase unbalanced non liner load conditions. The advantages of the designed system and the proposed current reference calculation methods are verified by simulations using MATLAB Power system Toolbox. KEYWORDS Power quality, shunt active filter, transformer-less shunt hybrid active filter, Total Harmonic Distortion 1. INTRODUCTION Harmonics are injected in source current due to the application of non-linear load. These harmonic currents influence the function of other equipment connected on the similar distribution feeder, including the harmonic producing loads. Among number of solutions conventionally passive filters offers a low cost solution. They generally offer high series impedance or low shunt impedance to block the particular harmonic content. However there are certain disadvantages like fixed compensation characteristics and resonances with the source impedance. Thus in orders to prevail over the demerits associated with traditional passive filters, Active Power Filters (APF) have been introduced in recent years. APF plays a vital role for controlling the amount of harmonic pollution present in a distribution system. They can be connected in series, shunt or combination of series and shunt with the supply impedance. Typically shunt APF consists of a three phase voltage source inverter with capacitor on dc side. For large power applications, it is difficult to implement a low loss and a low cost PWM
  • 2. 374 Computer Science & Information Technology (CS & IT) converter. When this equipment is connected in shunt to the ac source impedance it is possible to improve the compensation characteristics of the passive filters in parallel connection [1], [2].This forms the transformerless Parallel Hybrid Active Filter The aim of PHAF is to mitigate the problems associated with SAF and passive filters and to complement and enhance their performance by adding active or passive components to their structure [3].Figure 1 shows the block diagram of transformerless parallel hybrid filter. Figure 1. Block Diagram of Parallel Hybrid Active Filter 2. PRINCIPLE OF OPERATION Hybrid active filters effectively mitigate the problems of a passive and an active filter and provide cost-effective harmonic compensation, particularly for high-power nonlinear loads [4].The parallel hybrid filter consists of three phase voltage source inverter with capacitor on the dc side connected in shunt with the tuned passive filter. Shunt passive filter is a series combination of a capacitor and a reactor tuned to a specific harmonic frequency. Since nonlinear load contributes the major contribution of harmonics in the source current mainly due to lower order harmonics thus tuned filter provides low impedance trap to harmonic. Remaining higher order harmonics only are to be filtered by shunt active filter; hence its power rating can be reduced The compensation of harmonics in the source current through enhancement of the compensation characteristics of the passive filters also eliminates the chances of resonance [5]. The performance of the PHAF depends on the computation of reference compensating signal. Among many control strategies mentioned for estimating the reference compensating current Instantaneous Reactive Power (IRP) theory [6, 7] and Synchronous Reference Frame (SRF) are mostly used. [8].These schemes employ the computation of the reference components through subtraction of positive sequence fundamental current component from the load/source current. These control strategies are very attractive for their simplicity and ease of implementation, but lack in providing adequate solution under extreme or severe condition of fault conditions in
  • 3. Computer Science & Information Technology (CS & IT) 375 passive filter branch. SRF control technique using proportional integral (PI) type controller are is implemented to strength the currents of the filter to follow their reference values. 3. SYSTEM CONFIGURATION A three phase parallel hybrid active filter is implemented for unbalance nonlinear load. The test system consists of shunt connected active filter with shunt passive LC elements tuned 5th harmonic frequency which the most prominent frequency is causing the distortion in source current. Passive filters are designed to result in minimum Root Mean Square (RMS) value of supply current at full load [9,10]. Proposal of Synchronous Reference Frame theory is included in [11]. 4. DESIGN PARAMETERS OF SHUNT ACTIVE FILTER A shunt active filter consists of three phase, 6 pulse voltage source inverter. The line-line voltage is considered as 415V. The design for dc bus capacitor, dc bus voltage and ac inductor are as follows. 4.1. DC Capacitor Voltage The minimum dc bus voltage should be greater than twice of the peak of the phase voltage of the system [13]. The dc bus voltage is calculated as V dc = m V LL− 3 22 (1) where, m is the modulation index =1 and is considered as 1 and VLL is the ac line voltage of three phase source. 4.2. DC Bus Capacitor The value of dc bus capacitor (Cdc)is given by taIVVVC dcdcdc )(3)]()[( 2 1 2 1 2 =− (2) where, Vdc is the reference dc voltage and Vdc1 is the minimum voltage level of dc bus, a is the over loading factor taken as 1.2, V is the phase voltage, I is the phase current and t is time by which the dc bus voltage is to be recovered. 4.3. AC Filter The ac inductance (Lf) depends on the current ripple icr,p-p, switching frequency fs, dc bus voltage (Vdc) .Thus Lf is given as
  • 4. 376 Computer Science & Information Technology (CS & IT) Lf= if V pcrps dc a m − 12 3 (3) where, i crp-p ,= 5% 5. DESIGN PARAMETERS OF PASSIVE FILTER The basic of shunt passive filter is to trap the tuned harmonic component in the source current using LC circuit. At resonance frequency inductive reactance is equal to that of capacitive reactance. Hence for single tuned filter, resonance frequency is given by CL ff f π2 1 = (4) Thus to design the size of capacitor, first step is to fixed the reactive power compensation .Hence capacitance can be calculated by filterkVAR V X LL c . 2 − = (5) where VL-L is line –line source voltage kVAR is the fixed reactive power compensation 6. CONTROL STRATEGY The main function of the SRF control strategy is to provide high resistance at the fundamental frequency and also zero impedance is presented to harmonic current flowing in to the passive filter. [12].The control diagram is shown in Fig 2. Fig 2 Synchronous Reference Frame Control Scheme
  • 5. Computer Science & Information Technology (CS & IT) 377 In this three phase load current is transformed into d-q stationary reference frame using Parks Transformation. Using this fundamental component appears as DC quantities and all other harmonics are transformed as non-DC quantities. These quantities are not required hence these can be filter out using low pass filter. The extracted dc components and are transformed back into a–b–c coordinates to obtain the fundamental components of source currents. To compensate for the inverter losses PI controller is applied to regulate the DC bus voltage. The output of PI controller at the dc bus voltage of active filter is considered as the current (iloss) for meeting its losses. vkvvkii ndeidndendepdnlossnloss )()1()()1()( )( +−+= −− (6) where, vv ndede )1( − − is the error between the reference(vdc*) and sensed (vdc) dc voltage at the nth sampling instant. Kpd and Kid are the proportional and the integral gains of the dc bus voltage PI controller. The reference source current is therefore expressed as, iii lossddd += * (7) Similarly PI controller is used to regulate reactive power vkvvkii nteiqntentepqnqrsnqr )()1()()1()( )( +−+= −− (8) The reference supply quadrature axis current is as iii qrqdq += * (9) where, vvv nsnte )( * )( −= denotes the error between reference (vs*) and actual(vs(n)) terminal voltage amplitudes at the n sampling instant. Kpq and Kiq are the proportional and the integral gains of the PI controller. 7. MATLAB IMPLEMENTATION A three phase transformerless hybrid active filter is implemented using MATLAB Power system Toolbox. Three phase input source voltage of 415V, 50 Hz frequency with source resistance of 0.2 ohms and inductance of 2mH is considered. A three phase unbalance nonlinear load drawing 5A is considered for simulation. Shunt active filter is constituted of 6 pulse VSI with 2200 e-6F of capacitance attached to the DC side. A small-rated filter has been included to minimize the switching ripples at the inverter output. Passive elements of the filter are calculated using the mathematical relation s considering 50% of fixed reactive compensation. Table1 gives the detailed parameters of the system.
  • 6. 378 Computer Science & Information Technology (CS & IT) Table 1. Detailed Parameters of the System. Parameters Values Supply voltage 415V (L-L), 50 Hz Loads: (i) Linear: phase a= 25 Phase b=10 and 80mH Phase c =10 and 80 mH (ii) Nonlinear: Three phase full bridge rectifier drawing 15A Shunt Active Filter: Interfacing Inductance Lf = 5.5 mH DC bus capacitance 22000e-6F. Referenced Dc voltage 750 V Tuned Passive Filter C5=129.4e-6F ;L5=3.1mH 8. RESULTS AND DISCUSSION The performance of the presented SRF control strategy is evaluated using by comparison of pure shunt active power filter and parallel hybrid power filter. The three phase unbalance nonlinear load considered here in the present system contains 5th harmonic content as the most prominent factor which causes the distortion in the source current. Hence the passive elements of the hybrid filter are tuned for the resonance frequency of 250Hz. The VA rating required for the inverter in the hybrid filter is much lesser than that required in a pure shunt active filter. The VA rating required of the inverter in parallel hybrid power active filter is given by VA rating= 3 22 IV FMAXdc ×× Where I FMAX A13≅ is the maximum filter current. Also the apparent power rating of nonlinear load is given by VA rating= IV LrmsSrms ××3 Where VSrms and ILrms are the RMS value of source voltage taken as 415 V and load current taken as 38A. The apparent ratio of the parallel hybrid filter and nonlinear load is greatly reduced by 16%. Another factor which determines the validation of active filters is Total Harmonic Distortion (THD) is reduced from14.74 % to 2.65 % for phase a. Table II shows the THD for all three phases for different types of filter. It can be seen from Fig 5 and Table III that parallel hybrid filter system is able to reduce the 5th harmonic of supply current to 1.68% .The THD of the ac supply current reduces to 3.27% with pure shunt active power filters alone as the major component of the load current without any filter is composed of 5th harmonic.
  • 7. Computer Science & Information Technology (CS & IT) 379 TABLE III Harmonic Current in Percentage of Fundamental Current 5th 7th 11th 13th 17th 19th Load current 12.76 5.42 3.92 2.23 1.55 0.97 Source current with Passive Filter 0.20 2.69 2.57 1.64 1.13 0.89 Source current with Pure Shunt Active Filter 1.83 0.54 0.64 0.65 0.83 0.05 Source current with Shunt Hybrid Active Filter 1.68 1.03 0.23 0.21 0.19 0.13 Figure 3 shows the waveform of load current without filter. Fig 4 and 5 shows the waveform of source current with pure shunt active filter and parallel hybrid active filter respectively. These waveforms clearly illustrates that load current is very distorted that implies source current at this time without filtering is also very distorted . With the application of power filter source currents can be made sinusoidal .Clearly with the application of parallel hybrid active filter source current is less distorted and contains less harmonics content as compared to pure shunt active filter. Fig 6 shows the uncompensated and compensated reactive power using parallel hybrid active filter .Since the passive elements are tuned at fixed 50% compensation, fig 6 clearly validates the passive parameters of hybrid filter. Fig7 demonstrates the source voltage, source current, load voltage, load current, DC bus voltage, and filter current for parallel hybrid active filter. TABLE II THD For Different Phases (in percentage) Phase Phase a Phas e b Phase cType of filter Load current without filter 14.74 16.27 19.66 Pure shunt active filter 3.27 4.58 3.75 Parallel hybrid filter 2.65 3.15 2.64
  • 8. 380 Computer Science & Information Technology (CS & IT) Figure 3 Load current Figure 4 Source Current with Pure Active Filter Figure 4 Source Current with Parallel Hybrid Active Filter Figure 6 Load Reactive Power and Source Reactive power using parallel Hybrid Active Filter
  • 9. Computer Science & Information Technology (CS & IT) 381 Figure 7 Source Voltage, Source Current, Load Voltage, Load Current, DC Bus Voltage, Filter Current. 9. CONCLUSIONS In this work, concept of transformerless parallel hybrid active filter is defined and verified by MATLAB simulation. Simulation results verify that presented method has good performance in the elimination of selective harmonic content and Total Harmonic Distortion. It has much better dynamic response with less rating compared with the pure shunt active filter. REFERENCES [1] B. Singh, K. Al-Haddad, and A. Chandra, “A review of active filters for power quality improvement,” IEEE Trans. Ind. Electron., vol. 46, no. 5, pp. 960–971, Oct. 1999. [2] J.W. Dixon, G. Venegas, and L. A.Moran, “A series active power filter based on a sinusoidal current- controlled voltage-source inverter,” IEEE Trans. Ind. Electron., vol. 44, no. 5, pp. 612–620, Oct. 1997. [3] Bhattacharya,Divan,”Synchronous Frame based controller implementation for a hybrid series active filter,Confeence record of IEEE Industry Apllications Conference Vol, 3,pp. 2531-2540 October 1995. [4] S. Srianthumrong and H. Akagi, “A medium-voltage transformerless AC/DC power conversion system consisting of a diode rectifier and a shunt hybrid filter,” IEEE Trans. Ind. Appl., vol. 39, no. 3, pp. 874–882, May/Jun. 2003. [5] H. Fujita, T. Yamasaki and H. Akagi, "A hybrid active filter for damping of harmonic resonance in industrial power systems," IEEE Trans. on Power Electronics, vol. 15, no. 2, pp. 215-222, March 2000.
  • 10. 382 Computer Science & Information Technology (CS & IT) [6] H. Fujita, H. Akagi, "A Practical Approach to Harmonic Compensation in Power Systems-Series Connection of Passive, Active Filters," IEEE Trans. on Ind.. Appl., vol.27, no.6, pp. 1020-1025, Nov./Dec. 1991. [7] F.B. Libano, J.A.Cobos, J. Uceda, "Simplified control strategy for Hybrid Active Filters", IEEE PESC Record, 1 997, pp 1102-1108. [8] P.T. Cheng, S. Bhattacharya and D. Divan, "Experimental Verification of Dominant Harmonic Active Filter for High Power Applications",IEEE Trans. on Ind. Appl., vol. 36, pp.567-577, March/April, 2000. [9] IEEE Guide for Application and Specification of Harmonic Filters IEEE Std 1531-2003. [10] V, Verma, S. Shanker, B. Singh, A. Chandra, and Kamal Al- Haddad, "Genetic Algorithm Based Design of Passive Filters for Offshore Applications," Proc. ofIEEE PCIC '04, 2004, pp 55-62. [11] S. Bhattacharya, D. Divan and B. Banerjee, “Synchronous frame harmonic isolator using active series filter,” EPE-Firenze, Vol. 3, pp. 30-35, 1991. [12] V, Verma, S. Shanker, B. Singh,’Design and Implemention of Current Controlled Parallel Hybrid Power Filter. [13] B.N.Singh, P.Rastgoufard, B.Singh, A.Chandra and K.Al.Haddad, “Design,simulation and implementation of three pole/ four pole topologies for active filters,” IEE Eletr. Power Appl., vol. 151, no. 4, pp. 467-476, July 2004. Authors Sakshi Bangia received the B.Tech degree in Instrumentation and Control from MDU Rohtak and M.Tech degree in Electrical Engg. from YMCA UST in 2004 and 2006, respectively. She is pursuing Ph.D in Power Quality from Maharishi Dayanand University, India. Presently she is working as Assistant Professor in Electrical Engineering Department at YMCA UST Faridabad. Dr. P.R.Sharma was born in 1966 in India. He is currently working as Chairman of the Department in Electrical Engg. in YMCA University Of Science and Technology, Faridabad. He received his B.E Electrical Engineering in 1988 from Punjab University Chandigarh, M.Tech in Electrical Engineering (Power System) from Regional Engineering College Kurukshetra in 1990 and Ph.D from M.D.University Rohtak in 2005. He started his carrier from industry. He has vast experience in the industry and teaching. His area of interest is Optimal location and coordinated control of FACTS devices ,power system stability and control Dr. Maneesha Garg did her Ph.D(Physics) in 2002 from Kurukshetra University, India. After that she worked as Research Associate granted by CSIR, in NIT Kurukshetra for 4 years. She has 18 publications in national, international journals and more than 30 papers in conferences to her credit. Presently she is working as Assistant Professor in Humanities and Applied Science Department, YMCA UST, Faridabad and guiding 4 scholars for their research work.