International Journal of Modern Engineering Research (IJMER)
                    www.ijmer.com          Vol.3, Issue.1, Jan-Feb. 2013 pp-477-485      ISSN: 2249-6645

                 Fuzzy Based Hysteresis Current Controlled Shunt Active
                          Power Filter for Power Conditioning

                                     P. V. Ram Kumar, 1 M. Surya Kalavathi2
     1
         Department of Electrical and Electronics Engineering, R.S.R Engineering College, Kavali, Nellore District, Andhra
                                                     Pradesh, INDIA–524201
          2
            Department of Electrical and Electronics Engineering, J.N.T.U. College of Engg, Hyderabad, INDIA – 500085

Abstract: Shunt Active power filters (SAPF) technology has emerged nowadays as a very suitable option for power quality
improvement in electrical power systems control. This paper presents the simulation study of a fuzzy logic hysteresis band
current controlled, three-phase SAPF to enhance power quality by harmonic elimination, power-factor correction, reactive
power compensation and balancing of nonlinear loads. The advantage of fuzzy control is that it is based on a linguistic
description and does not require a mathematical model of the system. Further, in this paper, the hysteresis based current
control method is implemented for pulse width-modulation (PWM) switching signals. Results obtained by simulations with
Matlab/Simulink show that dynamic behavior of the fuzzy controller is more effective than the conventional proportional-
integral (PI) controller method on compensating reactive power and harmonic currents of the load. It is found to be more
robust to changes in load and other system parameters compared to the conventional PI controller under steady state and
transient conditions.

Keywords: Fuzzy logic controller, Hysteresis band current control, Power quality improvement, and Shunt active power
filter

                                                      I. INTRODUCTION
         Shunt active power filters (SAPF) represent a feasible solution to the problems caused by the non- linear loads.
These loads draw non-sinusoidal currents from the 3-phase sinusoidal, balanced voltages which are classified as identified
and unidentified loads. The SAPF can compensate for the harmonics, correct the power factor and work as a reactive power
compensator, thus providing enhancement of power quality in the system [1, 2]. The control scheme of a SAPF must
calculate the current reference waveform for each phase of the inverter, maintain the dc voltage constant, and generate
inverter gating signals. The current reference circuit generates the reference currents required to compensate the load current
harmonics and reactive power, and also try to maintain constant the dc voltage across the capacitor [3].
         In literature [1- 14], most reference compensation current strategies of the SAPF are determined either with or
without reference-frame transformations. For instance, the theory proposed in [1, 2] requires transformation of both source
voltages and load currents from the a-b-c reference frame to α-β reference frame to determine the SAPF reference
compensation currents in the three-phase three-wire system. For detecting the reference compensating current, the
instantaneous active and reactive power theory (p-q theory) are widely used, which can provide an instantaneous and
accurate reference compensating current [2, 3]. Grady et al. [4] have presented a survey of active power line conditioning
methodologies with a list of the advantages and limitations of each one. Cavallini and Montanari [5] have proposed the unity
power factor strategy known as classic strategy in which conditions the line currents to fit the voltage waveform, provides
line current RMS values always lower than those obtained by keeping the instantaneous real power equal to its mean value.
Chang and Shree [6] have proposed a simple and efficient compensation strategy that is suitable for three-phase shunt active
power filters without reference-frame transformation requirement. Bhende et al. [7] have proposed Takagi–Sugeno (TS)-
type fuzzy logic controller to a three-phase shunt active power filter and compared to conventional proportional-integral (PI)
controller. Bhim Singh and Verma [8] have an indirect current control scheme of parallel hybrid power filter system consists
of a shunt passive filter with an active filter in series with it connected at the point of common coupling (PCC) in parallel
with nonlinear load. Bhuvaneswari and Nair [9] have proposed an algorithm based on the real component of fundamental
load current (I cosΦ). Suresh et al. [10] have presented the implementation of a hybrid adaptive fuzzy hysteresis current
controller for shunt active power filter using i d–iq strategy. Tang et al. [11] have proposed a LCL-filter-based shunt active
power filter which gives good switching harmonic suppression and minimizes the possibility of over-modulation.
         Chandra et al. [12] have presented an improved control algorithm of the SAPF which used two closed loop PI
controllers and carrier wave PWM signal generation. Akagi [13] has listed trends in active power line conditioners. Singh et
al. [14] have presented a review on classification of active filters for power quality improvement based on converter type,
topology and the number of phases.
         In the generalized instantaneous reactive power theory [2], transformation of a-b-c axes to d–q synchronous
reference frame is done for harmonic and reactive power compensation. However, the synchronous reference frame (SRF)
strategy [3] only computes the sinusoidal fundamental components of the load currents; the reactive power compensation
and a null neutral current thus cannot be achieved if the load imbalance at the fundamental frequency occurs. A phase-locked
loop (PLL) per each phase must be used. In theory, the aforementioned approaches work very well on harmonic and/or
reactive power compensation for nonlinear loads under ideal source voltages. However, if the source voltages are


                                                             www.ijmer.com                                          477 | Page
International Journal of Modern Engineering Research (IJMER)
                 www.ijmer.com          Vol.3, Issue.1, Jan-Feb. 2013 pp-477-485      ISSN: 2249-6645

imbalanced and/or distorted, the generated SAPF reference compensation currents are discrepant and the desired
balanced/sinusoidal source currents cannot be maintained [6].
          Among different PWM methods, hysteresis is one of the most popular PWM strategies [6- 10] and widely applied
in SAPF for current quality compensation, owing to its advantages such as ease of implementation, fast dynamic response
and current limiting capability.
          Recently, fuzzy logic controllers have generated a great deal of interest in various applications and have been
introduced in the power-electronics field. The advantages of fuzzy logic controllers over the conventional PI controller are
that they do not need an accurate mathematical model; they can work with imprecise inputs, can handle nonlinearity, and
may be more robust than the conventional PI controller. The Mamdani type of fuzzy controller used for the control of APF
gives better results compared with the PI controller [7, 10, and 14].
          To achieve full compensation of both reactive power and harmonic/neutral currents of the load, this paper presents a
simple method to determine the SAPF reference compensation currents using dc voltage, PI and Fuzzy controller and source
voltages. This method does not require any reference frame transformations. Hysteresis band current control PWM strategy
is used to drive current controlled voltage source inverter (CC- VSI). The two schemes, conventional PI controller and Fuzzy
controller are compared in this paper. A MATLAB based simulation is performed on proposed system and the results are
presented to discuss in regard to the voltage regulation, harmonic elimination, power-factor correction and load balancing
capabilities of the SAPF system.

                                            II. CONTROL SCHEME OF SAPF
          The control scheme of a shunt active power filter must calculate the current reference waveform for each phase of
the inverter, maintain the dc voltage constant, and generate the inverter gating signals. The block diagram of the control
scheme of a shunt active power filter is shown in Fig. 1. The current reference circuit generates the reference currents
required to compensate the load current harmonics and reactive power, and also try to maintain constant the dc voltage
across the electrolytic capacitors. Also, the compensation effectiveness of an active power filter depends on its ability to
follow with a minimum error and time delay, the reference signal calculated to compensate the distorted load current.
Finally, the dc voltage control unit must keep the total dc bus voltage constant and equal to a given reference value. The dc
voltage control is achieved by adjusting the small amount of real power absorbed by the inverter. This small amount of real
power is adjusted by changing the amplitude of the fundamental component of the reference current. Different control
topologies of SAPF are well documented in recent years [1- 14].

                                                     isa PCC v        ila                             il
                                 a                             sa

                                                     isb              ilb
                                 b                             vsb                                         RL
                                                     isc              i
                                 c                                vsc lc                                   LL
                                        Z s  Ls , Rs 
                                                                                        Non linear load

                                              Z f  Lf , Rf   
                                                                                  icc
                                                                      ica   icb
                                                                                            Cdc Vdc


                                                                            3- Phase VSI

                     Figure 1: Basic Compensation Principle of Shunt Active Power Filter (SAPF)

2.1 Generation of Source Currents
            SAPF is controlled to draw/supply a compensating current from/to the utility, so that it cancels current harmonics
on the ac side and makes the source current in phase with the source voltage. From Fig. 1, the instantaneous currents can be
written as:
is  t  = iL  t  - ic t                                                                                              (1)

Source voltage is given by:

vs  t  = Vmsinωt                                                                                                        (2)

If the nonlinear load is applied, then the load current will have a fundamental component and harmonic components, which
can be expressed as:
           
iL  t  =  I n sin  nωt + φn 
          n=1
                                                                                                                        (3)
                    
    = I1sin nωt + φ1 +  I n sin  nωt + φn 
                            n=2
                                                                  www.ijmer.com                                    478 | Page
International Journal of Modern Engineering Research (IJMER)
                        www.ijmer.com          Vol.3, Issue.1, Jan-Feb. 2013 pp-477-485      ISSN: 2249-6645

The instantaneous load power can be given as:

   p L  t  = vs  t  * i L  t 
                   2
         = Vm I1sin ωt * cosφ1 +Vm I1sinωt * cosωt * sinφ1
                         ¥                                                                                                    (4)
             +Vm sinωt *  I n sin  nωt + φn 
                        n=2
         = p f  t  + pr  t  + ph  t 
From (4), the real power drawn by the load is:

    p f  t  = Vm I1sin ωt * cosφ1 = vs  t  * is t 
                        2
                                                                                                                              (5)
From (5), the current supplied by the source, after compensation is:

             p f t 
is  t  =              = I1 * cosφ1 * sinωt = I sm sinωt
             vs  t 

Where I sm = I1 * cosφ1

         There are also some switching losses in the PWM converter and, hence, the utility must supply a small overhead for
the capacitor leakage and converter switching losses in addition to the real power of the load. The total peak current supplied
by the source (Isp) is therefore:

I sp = I sm + I sl                                                                                                            (6)

Where Isl is the peak value of loss current.

         If the active filter provides total reactive and harmonic power, then i s(t) will be in phase with the utility voltage and
purely sinusoidal. At this time, the active filter must provide the following compensation current:

ic  t  = iL  t  - is t                                                                                                  (7)

2.2 Generation of Reference Source Currents
         There are many possibilities to determine the reference current required to compensating the non-linear load.
Normally, shunt active power filters are used to compensate the displacement power factor and low-frequency current
harmonics generated by non-linear loads. One alternative to determine the current reference required by the VSI is the use of
the instantaneous reactive power theory, proposed by Akagi [1], the other one is to obtain current components in d–q or
synchronous reference frame [2], and the third one to force the system line current to follow a perfectly sinusoidal template
in phase with the respective phase-to-neutral voltage [3]. In this paper, a simple method is used to generate the source
reference currents using DC voltage error and source voltage peak detection. The reason, why it is selected and functioning
of the control method is explained below.

                                          III. Proposed Method With Pi Controller
         The aim of the method is to generate the current reference signal required to compensate reactive power and current
harmonics. Basically, all the different schemes try to obtain the current reference signals that include the reactive
components required to compensate the displacement power factor and the current harmonics generated by the non-linear
load. Fig. 2 shows the PI controller based scheme used to generate the current reference signals required by a shunt active
power filter. In this circuit, the distorted load current is filtered, extracting the fundamental component, Il.
3.1Design of DC Link Voltage PI Controller
         The three phase reference currents (peak value) for the control of active filter are generated in accordance with the
PI controller error between the average dc bus voltage Vdc (n) and its reference value Vdcref (n) of the active filter. The dc bus
voltage error Ve (n) at nth sampling instant is:

Ve  n  = Vdcref        n - Vdc  n                                                                                       (8)



                                                              www.ijmer.com                                             479 | Page
International Journal of Modern Engineering Research (IJMER)
                 www.ijmer.com          Vol.3, Issue.1, Jan-Feb. 2013 pp-477-485      ISSN: 2249-6645

                                   Vdcref        PI
                                                                            Isaref
                                              Controller
                                   Vdc                                    Isa
                                                                product

                                            Vsa         k                                         PWM
                                                                           Isbref    Hysteresis    Gate
                                            Vsb                                       Current     signals
                                                        k                 Isc        Controller
                                                                product


                                                                           Iscref
                                            Vsc         k
                                                                          Isc
                                                                product


         Figure 2: PI -hysteresis current controller based PWM generation using proposed method for SAPF.

This error signal Ve (n) is processed in PI controller and output K (n) at nth sampling instant is expressed as:
K  n  = K  n - 1 + K p Ve  n Ve  n-1  Ki Ve  n                                                                 (9)

Where Kp and Ki are the gains of the PI controller.

         The output of the PI controller has been considered as the amplitude of the desired source current, and the reference
currents are estimated by multiplying this peak value with the unit sine vectors in phase with the source voltages. In order to
provide the reactive power required by the load, the current signal obtained from the PI Controller Il1 is synchronized with
the respective phase to- neutral source voltage so that the inverter ac output current is forced to lead the respective inverter
output voltage, thereby generating the required reactive power and absorbing the real power necessary to supply the
switching losses and also to maintain the dc voltage constant. The real power absorbed by the inverter is controlled by
adjusting the amplitude of the fundamental current reference waveform, Il1, obtained from the reference current generator.
         Ideal compensation requires the mains current to be sinusoidal and in phase with the source voltage, irrespective of
the load current nature. The source reference currents, after compensation, can be given as:

                *
               i sa = I sp sinωt
                *
                               
               i sb = I sp sin ωt - 120
                                        0
                                                                                                                             (10)

               i sc = I sp sin  ωt + 120 
                *                        0


         Where Isp is the amplitude of the desired source current, while the phase angle can be obtained from the source
voltages. Hence, the waveform and phases of the source currents are known, and only the magnitudes of the source currents
need to be determined.
         The main characteristic of this method is the direct derivation of the compensating component by sensing dc
voltage, source voltages and currents, without use of any reference frame transformation. Nevertheless, this PI controller
presents a low frequency oscillation problem in the active power filter dc bus voltage. To improve this technique, fuzzy
hysteresis band current controller has been implemented in this paper.

                                     IV. PROPOSED FUZZY CONTROL ALGORITHM
           Fig. 3 shows the schematic diagram of the fuzzy control scheme. In order to implement the control algorithm of a
shunt active power filter in a closed loop, the dc capacitor voltage Vdc is sensed and then compared with the reference value
Vdcref. In case of a fuzzy logic control scheme, the error e = Vdcref – Vdc and integration of error signal ∫e are used as inputs for
fuzzy processing. The output of the fuzzy controller after a limit is considered as the magnitude of peak reference current
Imax. The switching signals for the PWM converter are obtained by comparing the actual source currents (isa, isb, isc) with the
reference current templates (i*sa, i*sb, i*sc ) in the hysteresis current controller. The output pulses are then given to the
switching devices of the PWM converter.
                                               Fuzzy Logic
                                              Controller with
                                               Ruleviewer
                                   Vdcref                                   Isaref
                                   Vdc                                    Isa
                                                                product

                                            Vsa         k                                         PWM
                                                                           Isbref    Hysteresis    Gate
                                            Vsb                                       Current     signals
                                                        k                 Isc        Controller
                                                                product


                                                                           Iscref
                                            Vsc         k
                                                                          Isc
                                                                product


       Figure 3: Fuzzy -hysteresis current controller based PWM generation using proposed method for SAPF.

                                                                   www.ijmer.com                                          480 | Page
International Journal of Modern Engineering Research (IJMER)
                 www.ijmer.com          Vol.3, Issue.1, Jan-Feb. 2013 pp-477-485      ISSN: 2249-6645

4.1. Basic Fuzzy Algorithm
          In a fuzzy logic controller, the control action is determined from the evaluation of „a’ set of simple linguistic rules.
The development of the rules requires „a’ thorough understanding of the process to be controlled, but it does not require a
mathematical model of the system. The design of a fuzzy logic controller requires the choice of membership functions. The
membership functions should be chosen such that they cover the whole universe of discourse. It should be taken care that the
membership functions overlap each other. This is done in order to avoid any kind of discontinuity with respect to the minor
changes in the inputs. To achieve finer control, the membership functions near the zero region should be made narrow.
Wider membership functions away from the zero region provides faster response to the system. Hence, the membership
functions should be adjusted accordingly. After the appropriate membership functions are chosen, a rule base should be
created. It consists of a number of Fuzzy If-Then rules that completely define the behaviour of the system. These rules very
much resemble the human thought process, thereby providing artificial intelligence to the system [3].
          The internal structure of the fuzzy controller is shown in Fig. 4. The error e and change of error ce are used
numerical variables from the real system. To convert these numerical variables into linguistic variables, the following seven
fuzzy levels or sets are chosen as: NB (negative big), NM (negative medium), NS (negative small), ZE (zero), PS (positive
small), PM (positive medium), and PB (positive big) and presented in input and output normalized membership functions
(Figs. 5 (a) and (b)).

The fuzzy controller is characterized as follows:
(i) Seven fizzy sets for each input and output.
(ii) Triangular membership functions for simplicity.
(iii) Fuzzification using continuous universe of discourse.
(iv) Implication using Mamdani‟s 'min' operator.
(v) Defiizzificatioii using the 'centroid' method.

                                                                         Fuzzy Logic
                                                                          Controller
                                                                                             Imax(n
                                             e(n)                                        ∫     )
                                                                       Fuzzy Interface
                           Vdc                      Fuzzification                                Defuzzification
                                                                           Engine
                                             ce(n)

                                    Vdcref
                                                                            To                  Imax(n)= Imax(n-1)
                                                                         Hysteresis                 +∫ Imax(n)
                                                                         Controller

                                      Figure 4: Internal Structure of Fuzzy controller.




                                   Figure 5(a): Input normalized membership function.




                                  Figure 5(b): Output normalized membership function.

4.2.Rule Base
         The elements of this rule base table are determined based on the theory that in the transient state, large errors need
coarse control, which requires coarse input/output variables; in the steady state, small errors need fine control, which
requires fine input/output variables. Based on this the elements of the rule table are obtained as shown in Table I, with „e‟
and „ce‟ as inputs.
                                                                    www.ijmer.com                                      481 | Page
International Journal of Modern Engineering Research (IJMER)
                 www.ijmer.com          Vol.3, Issue.1, Jan-Feb. 2013 pp-477-485      ISSN: 2249-6645

                                                                                    Table.I Control Rule Base
                                                                            NB       N      NS ZE PS          PM                                                             PB
                                                               ce                    M
                                                               e
                                                               NB           NB            NB           NB                NB                NM              NS                ZE
                                                               N            NB            NB           NB                NM                NS              ZE                PS
                                                               M
                                                               NB           NB            NB           NM                NS                ZE              PS                PM
                                                               ZE           NB            NM           NS                ZE                PS              PM                PB
                                                               PS           NM            NS           ZE                PS                PM              PB                PB
                                                               e
                                                               P            NS            ZE           PS                PM                PB              PB                PB
                                                               M
                                                               PB           ZE            PS           PM                PB                PB              PB                PB

4.3 Hysteresis Current Controller for PWM Switching
          The active filter is comprised of three-phase IGBT based current controlled VSI bridge. The upper device and the
lower device in one phase leg of VSI are switched in complementary manner. The switching logic for “phase-a” is
formulated as follows: if isa < (i*sa- hb), upper switch is OFF and lower switch is ON in the phase “a” leg then S a = 0. If isa >
(i*sa+hb) upper switch is ON and lower switch is OFF in the phase “a” leg then Sa= 1. Between the transitions the previous
value of switches are maintained. Where, is switching function for switches of phase “a” and is the width of the hysteresis
band around reference currents. Similarly, the switching logic of the other two phases (“b” and “c”) is formulated.

                                                                      V. Simulation Results And Discussion
          Following are the system parameters considered for the study of SAPF for both PI and Fuzzy controller. Vs = 100
V (Peak), f = 50 Hz, Rs= 0.1 Ω, Ls= 0.15 mH, Rf = 0.1 Ω, Lf = 0.66 mH, Rl = 6.7, 15 Ω; Ll = 20mH, CDC = 2000 µF, Vdcref =
220 V. In case of PI the gains chosen are kp= 0.2 and ki = 9.32. Initially, the load chosen is of Rl = 6.7 Ω, Ll = 20mH and
later, the load has been changed to Rl = 15 Ω, Ll=20mH. The performance results of shunt active power filter with PI
controller are presented in Figures 7- 9. Fig.6 shows THD content of Load current, Source current with PI controller and
with Fuzzy controller. In Fig.7performance results of SAPF with PI controller are presented and results with fuzzy
controller are presented in Fig. 8. Fig.9 shows results in support of power factor correction ability of SAPF. Comparisons of
PI and fuzzy controllers are presented in Table II, III and IV based on % THD, settling time and overshoot. (Parameters
notation is shown in Fig. 1.)
                                                                                          FFT window: 2 of 25 cycles of selected signal
                                   30

                                   20

                                   10

                                    0

                                   -10

                                   -20

                                   -30
                                     0.35                     0.355          0.36              0.365               0.37                    0.375                 0.38                0.385
                                                                                                                 Time (s)


                                                                                   Fundamental (50Hz) = 26.14 , THD= 28.10%


                                    5


                                    4
                             Mag




                                    3


                                    2


                                    1



                                    0
                                                  0             100          200           300            400              500              600                700            800            900     1000
                                                                                                       Frequency (Hz)


                                                                            Figure 6 (a): THD % of load current
                                                                                           FFT window:     2    of 25   c y c les   of s elec t ed   s ignal
                                     15

                                     10

                                         5

                                         0

                                         -5

                                    -10

                                    -15
                                      0. 25                    0. 255          0. 26             0. 265              0. 27                   0. 275                  0. 28            0. 285
                                                                                                                   Time (s )



                                                                                             Fundament al       (50Hz )   =   11. 68   ,   THD=   1. 95%

                                    0. 4

                                   0. 35

                                    0. 3

                                   0. 25
                             Mag




                                    0. 2

                                   0. 15

                                    0. 1

                                   0. 05

                                         0
                                                      0           100         200            300           400       500                      600               700            800             900    1000
                                                                                                             Frequenc y (Hz )




                                                                      Figure.6 (b): THD % of Source current (PI)
                                                                                             FFT window:       2 of 25 c y c les      of s elec ted s ignal
                                         15

                                         10

                                              5

                                              0

                                          -5

                                         -10

                                         -15
                                           0.3                   0.305             0.31            0.315                  0.32                 0.325                   0.33             0.335
                                                                                                                        Time (s )


                                                                                   Fundamental (50Hz) = 11.93 , THD= 0.51%

                                   0.04
                              0.035
                                   0.03
                              0.025
                       Mag




                                   0.02
                              0.015
                                   0.01
                              0.005
                                          0
                                                          0           100     200             300           400    500     600                                   700           800             900    1000
                                                                                                            Frequency (Hz)



                                                                  Figure.6(c) THD% of Source current (Fuzzy)
                                                                                                           www.ijmer.com                                                                                     482 | Page
International Journal of Modern Engineering Research (IJMER)
                                                   www.ijmer.com          Vol.3, Issue.1, Jan-Feb. 2013 pp-477-485      ISSN: 2249-6645




Figure.7: Performance results of shunt active power filter with PI controller for the load of Rl = 15 Ω, and Ll = 20
                                                       mH.




Figure.8: Performance results of shunt active power filter with fuzzy controller for the load Rl = 15 Ω, and Ll = 20
                                                        mH

                                                  100

                                                   80
         Source Voltage and Current..........pf




                                                   60

                                                   40

                                                   20

                                                    0

                                                   -20

                                                   -40

                                                   -60

                                                   -80

                                                  -100

                                                     0      0.05     0.1     0.15    0.2      0.25    0.3     0.35     0.4    0.45        0.5
                                                                                       Time in Seconds


                                                   Figure 9(a): Source Voltage and current wave forms of Phase ‘a’ of PI controlled SAPF

                                                                                           www.ijmer.com                                        483 | Page
International Journal of Modern Engineering Research (IJMER)
                                          www.ijmer.com          Vol.3, Issue.1, Jan-Feb. 2013 pp-477-485      ISSN: 2249-6645


                                  100


                                   80


                                   60
Source voltage & Source current



                                   40


                                   20


                                    0


                                   -20


                                   -40


                                   -60


                                   -80


                                  -100
                                      0        0.05       0.1       0.15       0.2      0.25          0.3   0.35      0.4       0.45   0.5
                                                                                 Time in second

                                     Figure 9(b): Source Voltage and current wave forms of Phase ‘a’ of Fuzzy controlled SAPF

                                                      TABLE.II: Thd % Comparison between Pi and Fuzzy Controllers
                                                                                  % THD at two different loads

                                                                                             Rl = 6.7 Ω,       Rl = 15Ω, Ll =
                                                                                                               20mH
                                                                                               Ll = 20mH

                                                                Without controller                 28.10             27.72

                                                                With PI controller                 0.81              1.03

                                                            With Fuzzy controller                     1.1            0.51


                                                TABLE.III: Settling Time Comparison between Pi And Fuzzy Controllers
                                                                                   Settling time for two
                                                                                  different loadings (sec)

                                                                                               Rl = 6.7     Rl = 15Ω,
                                                                                               Ω, Ll =      Ll      =
                                                                                               20mH         20mH

                                                                  With PI controller           0.26 s       0.33 s

                                                                  With               Fuzzy     0.18 s       0.24 s
                                                                  controller



                                           TABLE.IV: Response of Pi and Fuzzy Controllers under Dynamic Load Conditions
                                                                                PI           Fuzzy

                                                                  Switch on response           80 A         65 A
                                                                  (peak overshoot)

                                                                  Settling time (after         0.45 s       0.3 s
                                                                  load change)

                                                                  Load            current      45 A         35 A
                                                                  overshoot    (at load
                                                                  change)




                                                                                        www.ijmer.com                                        484 | Page
International Journal of Modern Engineering Research (IJMER)
                  www.ijmer.com          Vol.3, Issue.1, Jan-Feb. 2013 pp-477-485      ISSN: 2249-6645

                                                      VI. CONCLUSION
         This paper has presented a simulation study of fuzzy based hysteresis current controlled shunt active power filter for
harmonic and reactive power compensation of the non-linear load. A simple method is implemented to generate source
reference currents without reference frame transformation using DC voltage regulator and source voltages. It gives less
complexity in realizing the control circuit of the active power filter and still maintains good filter performance. The scheme
has the advantage of simplicity and is able to provide self-supported dc bus of the active filter through power transfer from
ac line at fundamental frequency. The performance of conventional PI controller and fuzzy controller has been studied and
compared. Overall, the fuzzy controller gives the best SAPF performance in comparison with the PI controller in regards
voltage regulation, % THD, settling time, current overshoot etc.

                                                               REFERENCES
[1]    H. Akagi, Y. Kanzawa, and A. Nabae “Instantaneous reactive power compensators comprising switching devices without energy
       Components” IEEE Transactions on Industrial Applications, Vol. 20, No. 3, pp. 625–630, 1984.
[2]    H. Akagi, E. Watanabe, M. Aredes “Instantaneous Power Theory and Applications to Power Conditioning: (Wiley-IEEE Press,
       2007).
[3]    M.H. Rashid “Power Electronics Handbook: Devices, Circuits, and Application”, (Elsevier Inc., Section Edition, 2007)
[4]    W. M. Grady, M. J. Samotyj and A. H. Noyola “Survey of Active Power Line Conditioning Methodologies” IEEETransaction on
       Power Delivery, Vol. 5, No. 3, pp. 1536- 1542, July 1990.
[5]    A. Cavallini and G. C. Montanari “Compensation Strategies for Shunt Active-Filter Control” IEEE Transactions on Power
       Electronics, Vol. 9, No. 6, pp. 587- 593, November 1994.
[6]    G. W. Chang, and T. C. Shee “A Novel Reference Compensation Current Strategy for Shunt Active Power Filter Control” IEEE
       Transactions on Power Delivery, Vol. 19, No. 4, pp. 1751 – 1758, October 2004.
[7]    C. N. Bhende, S. Mishra, and S. K. Jain “TS-Fuzzy-Controlled Active Power Filter for Load Compensation, IEEETransactions on
       Power Delivery, Vol. 21, No. 3, pp. 1459- 1465, July 2006.
[8]    Bhim Singh, and Vishal Verma “An Indirect Current Control of Hybrid Power Filter for Varying Loads” IEEETransactions on
       Power Delivery, Vol. 21, No. 1, pp. 178- 184, January 2006.
[9]    G. Bhubaneswar, and Manjula G. Nair “Design, Simulation, and Analog Circuit Implementation of a Three-Phase Shunt Active
       Filter Using the Icos Φ Algorithm” IEEE Transactions on Power Delivery, Vol. 23, No. 2, pp. 1222 – 1235, April 2008.
[10]   Y. Suresh A.K. Panda and M. Suresh “Real-time implementations of adaptive fuzzy hysteresis-band current control technique for
       shunt active power filter” Vol. 5, Iss. 7, pp. 1188–1195, IET Power Electronics, 2012.
[11]   Y. Tang, P. C. Loh, P. Wang, F. H. Choo, F. Gao, and F. Blaabjerg, “Generalized Design of High Performance Shunt Active Power
       Filter With Output LCL Filter” IEEE Transactions on Industrial Electronics, Vol. 59, No. 3, pp. 1443-1452, March 2012.
[12]   Ambrish Chandra, Bhim Singh, B. N. Singh, and Kamal Al-Haddad, “An Improved Control Algorithm of Shunt Active Filter for
       Voltage Regulation, Harmonic Elimination, Power-Factor Correction, and Balancing of Nonlinear Loads”IEEE Transactions on
       Power Electronics, Vol. 15, No. 3, pp. 495 -507, May 2000.
[13]   H. Akagi, New Trends in Active Filters for Power Conditioning” IEEE Transactions on Industry Applications, Vol32, No 6, pp.
       1312- 1322, December 1996.
[14]   Bhim Singh, Kamal Al-Haddad, and Ambrish Chandra “A Review of Active Filters for Power Quality Improvement” IEEE
       Transactions on Industrial Electronics, Vol. 46, No. 5, pp. 60 – 71, October 1999.




                                                              www.ijmer.com                                              485 | Page

More Related Content

What's hot

A proportional resonant current controller for selective harmonic compensat
A proportional resonant current controller for selective harmonic compensatA proportional resonant current controller for selective harmonic compensat
A proportional resonant current controller for selective harmonic compensathareesh hari
 
Improved dynamic response of dstatcom using genetic algorithm
Improved dynamic response of dstatcom using genetic algorithmImproved dynamic response of dstatcom using genetic algorithm
Improved dynamic response of dstatcom using genetic algorithmAlexander Decker
 
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...IJERA Editor
 
Comparison analysis of shunt active filter and transformerless parallel hybri...
Comparison analysis of shunt active filter and transformerless parallel hybri...Comparison analysis of shunt active filter and transformerless parallel hybri...
Comparison analysis of shunt active filter and transformerless parallel hybri...csandit
 
COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRI...
COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRI...COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRI...
COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRI...cscpconf
 
Design and Simulation of Power Factor Correction Boost Converter using Hyster...
Design and Simulation of Power Factor Correction Boost Converter using Hyster...Design and Simulation of Power Factor Correction Boost Converter using Hyster...
Design and Simulation of Power Factor Correction Boost Converter using Hyster...ijtsrd
 
Power factor correction using bridgeless boost topology
Power factor correction using bridgeless boost topologyPower factor correction using bridgeless boost topology
Power factor correction using bridgeless boost topologyDHEERAJ DHAKAR
 
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur AreaReactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Areaijceronline
 
Selective localization of capacitor banks considering stability aspects in po...
Selective localization of capacitor banks considering stability aspects in po...Selective localization of capacitor banks considering stability aspects in po...
Selective localization of capacitor banks considering stability aspects in po...IAEME Publication
 
presentation of Conference On Electrical And Electronic Engineering 2015
presentation of Conference On Electrical And Electronic Engineering 2015presentation of Conference On Electrical And Electronic Engineering 2015
presentation of Conference On Electrical And Electronic Engineering 2015sager alswed
 
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...IJERA Editor
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
A Predictive Control Strategy for Power Factor Correction
A Predictive Control Strategy for Power Factor CorrectionA Predictive Control Strategy for Power Factor Correction
A Predictive Control Strategy for Power Factor CorrectionIOSR Journals
 
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...IRJET Journal
 
Pll based shunt active harmonic filter to compensate multiple non linear loads
Pll based shunt active harmonic filter to compensate multiple non linear loadsPll based shunt active harmonic filter to compensate multiple non linear loads
Pll based shunt active harmonic filter to compensate multiple non linear loadsIAEME Publication
 
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...Venkata Gowtam Nallamothu
 
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...IJITE
 
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...IJPEDS-IAES
 

What's hot (20)

A proportional resonant current controller for selective harmonic compensat
A proportional resonant current controller for selective harmonic compensatA proportional resonant current controller for selective harmonic compensat
A proportional resonant current controller for selective harmonic compensat
 
Improved dynamic response of dstatcom using genetic algorithm
Improved dynamic response of dstatcom using genetic algorithmImproved dynamic response of dstatcom using genetic algorithm
Improved dynamic response of dstatcom using genetic algorithm
 
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
Modeling & Analysis of Shunt Active Power Filter Using IRP Theory Fed to Indu...
 
Adaptive Method for Power Quality Improvement through Minimization of Harmoni...
Adaptive Method for Power Quality Improvement through Minimization of Harmoni...Adaptive Method for Power Quality Improvement through Minimization of Harmoni...
Adaptive Method for Power Quality Improvement through Minimization of Harmoni...
 
Comparison analysis of shunt active filter and transformerless parallel hybri...
Comparison analysis of shunt active filter and transformerless parallel hybri...Comparison analysis of shunt active filter and transformerless parallel hybri...
Comparison analysis of shunt active filter and transformerless parallel hybri...
 
COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRI...
COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRI...COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRI...
COMPARISON ANALYSIS OF SHUNT ACTIVE FILTER AND TRANSFORMERLESS PARALLEL HYBRI...
 
Design and Simulation of Power Factor Correction Boost Converter using Hyster...
Design and Simulation of Power Factor Correction Boost Converter using Hyster...Design and Simulation of Power Factor Correction Boost Converter using Hyster...
Design and Simulation of Power Factor Correction Boost Converter using Hyster...
 
Power factor correction using bridgeless boost topology
Power factor correction using bridgeless boost topologyPower factor correction using bridgeless boost topology
Power factor correction using bridgeless boost topology
 
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur AreaReactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
 
Selective localization of capacitor banks considering stability aspects in po...
Selective localization of capacitor banks considering stability aspects in po...Selective localization of capacitor banks considering stability aspects in po...
Selective localization of capacitor banks considering stability aspects in po...
 
presentation of Conference On Electrical And Electronic Engineering 2015
presentation of Conference On Electrical And Electronic Engineering 2015presentation of Conference On Electrical And Electronic Engineering 2015
presentation of Conference On Electrical And Electronic Engineering 2015
 
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
A Predictive Control Strategy for Power Factor Correction
A Predictive Control Strategy for Power Factor CorrectionA Predictive Control Strategy for Power Factor Correction
A Predictive Control Strategy for Power Factor Correction
 
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...
IRJET- Harmonic Elimination in Three Phase Distribution System using Shunt Ac...
 
N1102018691
N1102018691N1102018691
N1102018691
 
Pll based shunt active harmonic filter to compensate multiple non linear loads
Pll based shunt active harmonic filter to compensate multiple non linear loadsPll based shunt active harmonic filter to compensate multiple non linear loads
Pll based shunt active harmonic filter to compensate multiple non linear loads
 
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...
Predictive-Control-For-Harmonic-And-Unbalance-Compensation-Using-Active-Power...
 
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
 
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
 

Viewers also liked

An Optimal Risk- Aware Mechanism for Countering Routing Attacks in MANETs
An Optimal Risk- Aware Mechanism for Countering Routing Attacks in MANETsAn Optimal Risk- Aware Mechanism for Countering Routing Attacks in MANETs
An Optimal Risk- Aware Mechanism for Countering Routing Attacks in MANETsIJMER
 
The Effect of Design Parameters of an Integrated Linear Electromagnetic Moto...
The Effect of Design Parameters of an Integrated Linear  Electromagnetic Moto...The Effect of Design Parameters of an Integrated Linear  Electromagnetic Moto...
The Effect of Design Parameters of an Integrated Linear Electromagnetic Moto...IJMER
 
The Impacts of Social Networking and Its Analysis
The Impacts of Social Networking and Its AnalysisThe Impacts of Social Networking and Its Analysis
The Impacts of Social Networking and Its AnalysisIJMER
 
დეპრესია
დეპრესიადეპრესია
დეპრესიაNini Talabadze
 
Education set for collecting and visualizing data using sensor system based ...
Education set for collecting and visualizing data using sensor  system based ...Education set for collecting and visualizing data using sensor  system based ...
Education set for collecting and visualizing data using sensor system based ...IJMER
 
G04013845
G04013845G04013845
G04013845IJMER
 
Effective Devops - Velocity New York 2015
Effective Devops - Velocity New York 2015 Effective Devops - Velocity New York 2015
Effective Devops - Velocity New York 2015 Jennifer Davis
 
Mislaid character analysis using 2-dimensional discrete wavelet transform for...
Mislaid character analysis using 2-dimensional discrete wavelet transform for...Mislaid character analysis using 2-dimensional discrete wavelet transform for...
Mislaid character analysis using 2-dimensional discrete wavelet transform for...IJMER
 
WAP- Mobile Personal Assistant Application
WAP- Mobile Personal Assistant ApplicationWAP- Mobile Personal Assistant Application
WAP- Mobile Personal Assistant ApplicationIJMER
 
A Chord based Service Discovery Approach for Peer- to- Peer Networks
A Chord based Service Discovery Approach for Peer- to- Peer  NetworksA Chord based Service Discovery Approach for Peer- to- Peer  Networks
A Chord based Service Discovery Approach for Peer- to- Peer NetworksIJMER
 
Narrating Fantasy in the Novel Pratimayum Rajakumariyum (The Statue and the P...
Narrating Fantasy in the Novel Pratimayum Rajakumariyum (The Statue and the P...Narrating Fantasy in the Novel Pratimayum Rajakumariyum (The Statue and the P...
Narrating Fantasy in the Novel Pratimayum Rajakumariyum (The Statue and the P...IJMER
 
Intrusion Detection and Forensics based on decision tree and Association rule...
Intrusion Detection and Forensics based on decision tree and Association rule...Intrusion Detection and Forensics based on decision tree and Association rule...
Intrusion Detection and Forensics based on decision tree and Association rule...IJMER
 
Χαλίλ Γκιμπράν
Χαλίλ ΓκιμπράνΧαλίλ Γκιμπράν
Χαλίλ ΓκιμπράνPopi Kaza
 
Review on Digital Elevation Model
Review on Digital Elevation ModelReview on Digital Elevation Model
Review on Digital Elevation ModelIJMER
 
Ay3313861388
Ay3313861388Ay3313861388
Ay3313861388IJMER
 
认识期货与常用术语介绍 (新版)
认识期货与常用术语介绍 (新版)认识期货与常用术语介绍 (新版)
认识期货与常用术语介绍 (新版)ji88749380
 
Electric Load Forecasting Using Genetic Algorithm – A Review
Electric Load Forecasting Using Genetic Algorithm – A Review Electric Load Forecasting Using Genetic Algorithm – A Review
Electric Load Forecasting Using Genetic Algorithm – A Review IJMER
 

Viewers also liked (20)

An Optimal Risk- Aware Mechanism for Countering Routing Attacks in MANETs
An Optimal Risk- Aware Mechanism for Countering Routing Attacks in MANETsAn Optimal Risk- Aware Mechanism for Countering Routing Attacks in MANETs
An Optimal Risk- Aware Mechanism for Countering Routing Attacks in MANETs
 
The Effect of Design Parameters of an Integrated Linear Electromagnetic Moto...
The Effect of Design Parameters of an Integrated Linear  Electromagnetic Moto...The Effect of Design Parameters of an Integrated Linear  Electromagnetic Moto...
The Effect of Design Parameters of an Integrated Linear Electromagnetic Moto...
 
The Impacts of Social Networking and Its Analysis
The Impacts of Social Networking and Its AnalysisThe Impacts of Social Networking and Its Analysis
The Impacts of Social Networking and Its Analysis
 
Reality tv
Reality tvReality tv
Reality tv
 
დეპრესია
დეპრესიადეპრესია
დეპრესია
 
Samecniero akademia
Samecniero akademiaSamecniero akademia
Samecniero akademia
 
Education set for collecting and visualizing data using sensor system based ...
Education set for collecting and visualizing data using sensor  system based ...Education set for collecting and visualizing data using sensor  system based ...
Education set for collecting and visualizing data using sensor system based ...
 
G04013845
G04013845G04013845
G04013845
 
Effective Devops - Velocity New York 2015
Effective Devops - Velocity New York 2015 Effective Devops - Velocity New York 2015
Effective Devops - Velocity New York 2015
 
Green grass
Green grassGreen grass
Green grass
 
Mislaid character analysis using 2-dimensional discrete wavelet transform for...
Mislaid character analysis using 2-dimensional discrete wavelet transform for...Mislaid character analysis using 2-dimensional discrete wavelet transform for...
Mislaid character analysis using 2-dimensional discrete wavelet transform for...
 
WAP- Mobile Personal Assistant Application
WAP- Mobile Personal Assistant ApplicationWAP- Mobile Personal Assistant Application
WAP- Mobile Personal Assistant Application
 
A Chord based Service Discovery Approach for Peer- to- Peer Networks
A Chord based Service Discovery Approach for Peer- to- Peer  NetworksA Chord based Service Discovery Approach for Peer- to- Peer  Networks
A Chord based Service Discovery Approach for Peer- to- Peer Networks
 
Narrating Fantasy in the Novel Pratimayum Rajakumariyum (The Statue and the P...
Narrating Fantasy in the Novel Pratimayum Rajakumariyum (The Statue and the P...Narrating Fantasy in the Novel Pratimayum Rajakumariyum (The Statue and the P...
Narrating Fantasy in the Novel Pratimayum Rajakumariyum (The Statue and the P...
 
Intrusion Detection and Forensics based on decision tree and Association rule...
Intrusion Detection and Forensics based on decision tree and Association rule...Intrusion Detection and Forensics based on decision tree and Association rule...
Intrusion Detection and Forensics based on decision tree and Association rule...
 
Χαλίλ Γκιμπράν
Χαλίλ ΓκιμπράνΧαλίλ Γκιμπράν
Χαλίλ Γκιμπράν
 
Review on Digital Elevation Model
Review on Digital Elevation ModelReview on Digital Elevation Model
Review on Digital Elevation Model
 
Ay3313861388
Ay3313861388Ay3313861388
Ay3313861388
 
认识期货与常用术语介绍 (新版)
认识期货与常用术语介绍 (新版)认识期货与常用术语介绍 (新版)
认识期货与常用术语介绍 (新版)
 
Electric Load Forecasting Using Genetic Algorithm – A Review
Electric Load Forecasting Using Genetic Algorithm – A Review Electric Load Forecasting Using Genetic Algorithm – A Review
Electric Load Forecasting Using Genetic Algorithm – A Review
 

Similar to Dd31477485

IRJET- A Review on Power Quality Improvement using Shunt Active Filter with M...
IRJET- A Review on Power Quality Improvement using Shunt Active Filter with M...IRJET- A Review on Power Quality Improvement using Shunt Active Filter with M...
IRJET- A Review on Power Quality Improvement using Shunt Active Filter with M...IRJET Journal
 
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...IOSR Journals
 
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQCIRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQCIRJET Journal
 
Review of the UPFC Different Models in Recent Years
Review of the UPFC Different Models in Recent YearsReview of the UPFC Different Models in Recent Years
Review of the UPFC Different Models in Recent YearsIJPEDS-IAES
 
Decomposition of current through active power filter for compensating harmoni...
Decomposition of current through active power filter for compensating harmoni...Decomposition of current through active power filter for compensating harmoni...
Decomposition of current through active power filter for compensating harmoni...eSAT Publishing House
 
Simulation Of Interline Power Flow Controller in Power Transmission System
 Simulation Of Interline Power Flow Controller in Power Transmission System Simulation Of Interline Power Flow Controller in Power Transmission System
Simulation Of Interline Power Flow Controller in Power Transmission Systemijsrd.com
 
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...IAES-IJPEDS
 
A New Topology for Power Quality Improvement using 3-Phase 4-Wire UPQC with R...
A New Topology for Power Quality Improvement using 3-Phase 4-Wire UPQC with R...A New Topology for Power Quality Improvement using 3-Phase 4-Wire UPQC with R...
A New Topology for Power Quality Improvement using 3-Phase 4-Wire UPQC with R...IJMTST Journal
 
Adaptive Fuzzy PID Based Control Strategy For 3Phase 4Wire Shunt Active Filte...
Adaptive Fuzzy PID Based Control Strategy For 3Phase 4Wire Shunt Active Filte...Adaptive Fuzzy PID Based Control Strategy For 3Phase 4Wire Shunt Active Filte...
Adaptive Fuzzy PID Based Control Strategy For 3Phase 4Wire Shunt Active Filte...IJERA Editor
 
Power System Stability Enhancement Using Static Synchronous Series Compensato...
Power System Stability Enhancement Using Static Synchronous Series Compensato...Power System Stability Enhancement Using Static Synchronous Series Compensato...
Power System Stability Enhancement Using Static Synchronous Series Compensato...IJMER
 
Design of Shunt Active Power Filter to eliminate harmonics generated by CFL
Design of Shunt Active Power Filter to eliminate harmonics generated by CFLDesign of Shunt Active Power Filter to eliminate harmonics generated by CFL
Design of Shunt Active Power Filter to eliminate harmonics generated by CFLpaperpublications3
 
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...IAES-IJPEDS
 
Comparison of Control Strategies of DSTATACOM for Non-linear Load Compensation
Comparison of Control Strategies of DSTATACOM for Non-linear Load CompensationComparison of Control Strategies of DSTATACOM for Non-linear Load Compensation
Comparison of Control Strategies of DSTATACOM for Non-linear Load Compensationidescitation
 
Harmonic Compensation for Non Linear Load Using PWM Based Active Filter
Harmonic Compensation for Non Linear Load Using PWM Based Active FilterHarmonic Compensation for Non Linear Load Using PWM Based Active Filter
Harmonic Compensation for Non Linear Load Using PWM Based Active Filteridescitation
 
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...IDES Editor
 

Similar to Dd31477485 (20)

IRJET- A Review on Power Quality Improvement using Shunt Active Filter with M...
IRJET- A Review on Power Quality Improvement using Shunt Active Filter with M...IRJET- A Review on Power Quality Improvement using Shunt Active Filter with M...
IRJET- A Review on Power Quality Improvement using Shunt Active Filter with M...
 
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...
 
K010126874
K010126874K010126874
K010126874
 
Sapf2
Sapf2Sapf2
Sapf2
 
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQCIRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
 
Review of the UPFC Different Models in Recent Years
Review of the UPFC Different Models in Recent YearsReview of the UPFC Different Models in Recent Years
Review of the UPFC Different Models in Recent Years
 
Decomposition of current through active power filter for compensating harmoni...
Decomposition of current through active power filter for compensating harmoni...Decomposition of current through active power filter for compensating harmoni...
Decomposition of current through active power filter for compensating harmoni...
 
Predictive Approach for Power Quality Improvement Based Direct Power Control
Predictive Approach for Power Quality Improvement Based Direct Power ControlPredictive Approach for Power Quality Improvement Based Direct Power Control
Predictive Approach for Power Quality Improvement Based Direct Power Control
 
Simulation Of Interline Power Flow Controller in Power Transmission System
 Simulation Of Interline Power Flow Controller in Power Transmission System Simulation Of Interline Power Flow Controller in Power Transmission System
Simulation Of Interline Power Flow Controller in Power Transmission System
 
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
 
A New Topology for Power Quality Improvement using 3-Phase 4-Wire UPQC with R...
A New Topology for Power Quality Improvement using 3-Phase 4-Wire UPQC with R...A New Topology for Power Quality Improvement using 3-Phase 4-Wire UPQC with R...
A New Topology for Power Quality Improvement using 3-Phase 4-Wire UPQC with R...
 
Adaptive Fuzzy PID Based Control Strategy For 3Phase 4Wire Shunt Active Filte...
Adaptive Fuzzy PID Based Control Strategy For 3Phase 4Wire Shunt Active Filte...Adaptive Fuzzy PID Based Control Strategy For 3Phase 4Wire Shunt Active Filte...
Adaptive Fuzzy PID Based Control Strategy For 3Phase 4Wire Shunt Active Filte...
 
Power System Stability Enhancement Using Static Synchronous Series Compensato...
Power System Stability Enhancement Using Static Synchronous Series Compensato...Power System Stability Enhancement Using Static Synchronous Series Compensato...
Power System Stability Enhancement Using Static Synchronous Series Compensato...
 
Design of Shunt Active Power Filter to eliminate harmonics generated by CFL
Design of Shunt Active Power Filter to eliminate harmonics generated by CFLDesign of Shunt Active Power Filter to eliminate harmonics generated by CFL
Design of Shunt Active Power Filter to eliminate harmonics generated by CFL
 
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
 
Experimental Comparative Study of Feedback Linearized Controller and Proporti...
Experimental Comparative Study of Feedback Linearized Controller and Proporti...Experimental Comparative Study of Feedback Linearized Controller and Proporti...
Experimental Comparative Study of Feedback Linearized Controller and Proporti...
 
Comparison of Control Strategies of DSTATACOM for Non-linear Load Compensation
Comparison of Control Strategies of DSTATACOM for Non-linear Load CompensationComparison of Control Strategies of DSTATACOM for Non-linear Load Compensation
Comparison of Control Strategies of DSTATACOM for Non-linear Load Compensation
 
Harmonic Compensation for Non Linear Load Using PWM Based Active Filter
Harmonic Compensation for Non Linear Load Using PWM Based Active FilterHarmonic Compensation for Non Linear Load Using PWM Based Active Filter
Harmonic Compensation for Non Linear Load Using PWM Based Active Filter
 
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...
 
G046033742
G046033742G046033742
G046033742
 

More from IJMER

A Study on Translucent Concrete Product and Its Properties by Using Optical F...
A Study on Translucent Concrete Product and Its Properties by Using Optical F...A Study on Translucent Concrete Product and Its Properties by Using Optical F...
A Study on Translucent Concrete Product and Its Properties by Using Optical F...IJMER
 
Developing Cost Effective Automation for Cotton Seed Delinting
Developing Cost Effective Automation for Cotton Seed DelintingDeveloping Cost Effective Automation for Cotton Seed Delinting
Developing Cost Effective Automation for Cotton Seed DelintingIJMER
 
Study & Testing Of Bio-Composite Material Based On Munja Fibre
Study & Testing Of Bio-Composite Material Based On Munja FibreStudy & Testing Of Bio-Composite Material Based On Munja Fibre
Study & Testing Of Bio-Composite Material Based On Munja FibreIJMER
 
Hybrid Engine (Stirling Engine + IC Engine + Electric Motor)
Hybrid Engine (Stirling Engine + IC Engine + Electric Motor)Hybrid Engine (Stirling Engine + IC Engine + Electric Motor)
Hybrid Engine (Stirling Engine + IC Engine + Electric Motor)IJMER
 
Fabrication & Characterization of Bio Composite Materials Based On Sunnhemp F...
Fabrication & Characterization of Bio Composite Materials Based On Sunnhemp F...Fabrication & Characterization of Bio Composite Materials Based On Sunnhemp F...
Fabrication & Characterization of Bio Composite Materials Based On Sunnhemp F...IJMER
 
Geochemistry and Genesis of Kammatturu Iron Ores of Devagiri Formation, Sandu...
Geochemistry and Genesis of Kammatturu Iron Ores of Devagiri Formation, Sandu...Geochemistry and Genesis of Kammatturu Iron Ores of Devagiri Formation, Sandu...
Geochemistry and Genesis of Kammatturu Iron Ores of Devagiri Formation, Sandu...IJMER
 
Experimental Investigation on Characteristic Study of the Carbon Steel C45 in...
Experimental Investigation on Characteristic Study of the Carbon Steel C45 in...Experimental Investigation on Characteristic Study of the Carbon Steel C45 in...
Experimental Investigation on Characteristic Study of the Carbon Steel C45 in...IJMER
 
Non linear analysis of Robot Gun Support Structure using Equivalent Dynamic A...
Non linear analysis of Robot Gun Support Structure using Equivalent Dynamic A...Non linear analysis of Robot Gun Support Structure using Equivalent Dynamic A...
Non linear analysis of Robot Gun Support Structure using Equivalent Dynamic A...IJMER
 
Static Analysis of Go-Kart Chassis by Analytical and Solid Works Simulation
Static Analysis of Go-Kart Chassis by Analytical and Solid Works SimulationStatic Analysis of Go-Kart Chassis by Analytical and Solid Works Simulation
Static Analysis of Go-Kart Chassis by Analytical and Solid Works SimulationIJMER
 
High Speed Effortless Bicycle
High Speed Effortless BicycleHigh Speed Effortless Bicycle
High Speed Effortless BicycleIJMER
 
Integration of Struts & Spring & Hibernate for Enterprise Applications
Integration of Struts & Spring & Hibernate for Enterprise ApplicationsIntegration of Struts & Spring & Hibernate for Enterprise Applications
Integration of Struts & Spring & Hibernate for Enterprise ApplicationsIJMER
 
Microcontroller Based Automatic Sprinkler Irrigation System
Microcontroller Based Automatic Sprinkler Irrigation SystemMicrocontroller Based Automatic Sprinkler Irrigation System
Microcontroller Based Automatic Sprinkler Irrigation SystemIJMER
 
On some locally closed sets and spaces in Ideal Topological Spaces
On some locally closed sets and spaces in Ideal Topological SpacesOn some locally closed sets and spaces in Ideal Topological Spaces
On some locally closed sets and spaces in Ideal Topological SpacesIJMER
 
Natural Language Ambiguity and its Effect on Machine Learning
Natural Language Ambiguity and its Effect on Machine LearningNatural Language Ambiguity and its Effect on Machine Learning
Natural Language Ambiguity and its Effect on Machine LearningIJMER
 
Evolvea Frameworkfor SelectingPrime Software DevelopmentProcess
Evolvea Frameworkfor SelectingPrime Software DevelopmentProcessEvolvea Frameworkfor SelectingPrime Software DevelopmentProcess
Evolvea Frameworkfor SelectingPrime Software DevelopmentProcessIJMER
 
Material Parameter and Effect of Thermal Load on Functionally Graded Cylinders
Material Parameter and Effect of Thermal Load on Functionally Graded CylindersMaterial Parameter and Effect of Thermal Load on Functionally Graded Cylinders
Material Parameter and Effect of Thermal Load on Functionally Graded CylindersIJMER
 
Studies On Energy Conservation And Audit
Studies On Energy Conservation And AuditStudies On Energy Conservation And Audit
Studies On Energy Conservation And AuditIJMER
 
An Implementation of I2C Slave Interface using Verilog HDL
An Implementation of I2C Slave Interface using Verilog HDLAn Implementation of I2C Slave Interface using Verilog HDL
An Implementation of I2C Slave Interface using Verilog HDLIJMER
 
Discrete Model of Two Predators competing for One Prey
Discrete Model of Two Predators competing for One PreyDiscrete Model of Two Predators competing for One Prey
Discrete Model of Two Predators competing for One PreyIJMER
 
Application of Parabolic Trough Collectorfor Reduction of Pressure Drop in Oi...
Application of Parabolic Trough Collectorfor Reduction of Pressure Drop in Oi...Application of Parabolic Trough Collectorfor Reduction of Pressure Drop in Oi...
Application of Parabolic Trough Collectorfor Reduction of Pressure Drop in Oi...IJMER
 

More from IJMER (20)

A Study on Translucent Concrete Product and Its Properties by Using Optical F...
A Study on Translucent Concrete Product and Its Properties by Using Optical F...A Study on Translucent Concrete Product and Its Properties by Using Optical F...
A Study on Translucent Concrete Product and Its Properties by Using Optical F...
 
Developing Cost Effective Automation for Cotton Seed Delinting
Developing Cost Effective Automation for Cotton Seed DelintingDeveloping Cost Effective Automation for Cotton Seed Delinting
Developing Cost Effective Automation for Cotton Seed Delinting
 
Study & Testing Of Bio-Composite Material Based On Munja Fibre
Study & Testing Of Bio-Composite Material Based On Munja FibreStudy & Testing Of Bio-Composite Material Based On Munja Fibre
Study & Testing Of Bio-Composite Material Based On Munja Fibre
 
Hybrid Engine (Stirling Engine + IC Engine + Electric Motor)
Hybrid Engine (Stirling Engine + IC Engine + Electric Motor)Hybrid Engine (Stirling Engine + IC Engine + Electric Motor)
Hybrid Engine (Stirling Engine + IC Engine + Electric Motor)
 
Fabrication & Characterization of Bio Composite Materials Based On Sunnhemp F...
Fabrication & Characterization of Bio Composite Materials Based On Sunnhemp F...Fabrication & Characterization of Bio Composite Materials Based On Sunnhemp F...
Fabrication & Characterization of Bio Composite Materials Based On Sunnhemp F...
 
Geochemistry and Genesis of Kammatturu Iron Ores of Devagiri Formation, Sandu...
Geochemistry and Genesis of Kammatturu Iron Ores of Devagiri Formation, Sandu...Geochemistry and Genesis of Kammatturu Iron Ores of Devagiri Formation, Sandu...
Geochemistry and Genesis of Kammatturu Iron Ores of Devagiri Formation, Sandu...
 
Experimental Investigation on Characteristic Study of the Carbon Steel C45 in...
Experimental Investigation on Characteristic Study of the Carbon Steel C45 in...Experimental Investigation on Characteristic Study of the Carbon Steel C45 in...
Experimental Investigation on Characteristic Study of the Carbon Steel C45 in...
 
Non linear analysis of Robot Gun Support Structure using Equivalent Dynamic A...
Non linear analysis of Robot Gun Support Structure using Equivalent Dynamic A...Non linear analysis of Robot Gun Support Structure using Equivalent Dynamic A...
Non linear analysis of Robot Gun Support Structure using Equivalent Dynamic A...
 
Static Analysis of Go-Kart Chassis by Analytical and Solid Works Simulation
Static Analysis of Go-Kart Chassis by Analytical and Solid Works SimulationStatic Analysis of Go-Kart Chassis by Analytical and Solid Works Simulation
Static Analysis of Go-Kart Chassis by Analytical and Solid Works Simulation
 
High Speed Effortless Bicycle
High Speed Effortless BicycleHigh Speed Effortless Bicycle
High Speed Effortless Bicycle
 
Integration of Struts & Spring & Hibernate for Enterprise Applications
Integration of Struts & Spring & Hibernate for Enterprise ApplicationsIntegration of Struts & Spring & Hibernate for Enterprise Applications
Integration of Struts & Spring & Hibernate for Enterprise Applications
 
Microcontroller Based Automatic Sprinkler Irrigation System
Microcontroller Based Automatic Sprinkler Irrigation SystemMicrocontroller Based Automatic Sprinkler Irrigation System
Microcontroller Based Automatic Sprinkler Irrigation System
 
On some locally closed sets and spaces in Ideal Topological Spaces
On some locally closed sets and spaces in Ideal Topological SpacesOn some locally closed sets and spaces in Ideal Topological Spaces
On some locally closed sets and spaces in Ideal Topological Spaces
 
Natural Language Ambiguity and its Effect on Machine Learning
Natural Language Ambiguity and its Effect on Machine LearningNatural Language Ambiguity and its Effect on Machine Learning
Natural Language Ambiguity and its Effect on Machine Learning
 
Evolvea Frameworkfor SelectingPrime Software DevelopmentProcess
Evolvea Frameworkfor SelectingPrime Software DevelopmentProcessEvolvea Frameworkfor SelectingPrime Software DevelopmentProcess
Evolvea Frameworkfor SelectingPrime Software DevelopmentProcess
 
Material Parameter and Effect of Thermal Load on Functionally Graded Cylinders
Material Parameter and Effect of Thermal Load on Functionally Graded CylindersMaterial Parameter and Effect of Thermal Load on Functionally Graded Cylinders
Material Parameter and Effect of Thermal Load on Functionally Graded Cylinders
 
Studies On Energy Conservation And Audit
Studies On Energy Conservation And AuditStudies On Energy Conservation And Audit
Studies On Energy Conservation And Audit
 
An Implementation of I2C Slave Interface using Verilog HDL
An Implementation of I2C Slave Interface using Verilog HDLAn Implementation of I2C Slave Interface using Verilog HDL
An Implementation of I2C Slave Interface using Verilog HDL
 
Discrete Model of Two Predators competing for One Prey
Discrete Model of Two Predators competing for One PreyDiscrete Model of Two Predators competing for One Prey
Discrete Model of Two Predators competing for One Prey
 
Application of Parabolic Trough Collectorfor Reduction of Pressure Drop in Oi...
Application of Parabolic Trough Collectorfor Reduction of Pressure Drop in Oi...Application of Parabolic Trough Collectorfor Reduction of Pressure Drop in Oi...
Application of Parabolic Trough Collectorfor Reduction of Pressure Drop in Oi...
 

Dd31477485

  • 1. International Journal of Modern Engineering Research (IJMER) www.ijmer.com Vol.3, Issue.1, Jan-Feb. 2013 pp-477-485 ISSN: 2249-6645 Fuzzy Based Hysteresis Current Controlled Shunt Active Power Filter for Power Conditioning P. V. Ram Kumar, 1 M. Surya Kalavathi2 1 Department of Electrical and Electronics Engineering, R.S.R Engineering College, Kavali, Nellore District, Andhra Pradesh, INDIA–524201 2 Department of Electrical and Electronics Engineering, J.N.T.U. College of Engg, Hyderabad, INDIA – 500085 Abstract: Shunt Active power filters (SAPF) technology has emerged nowadays as a very suitable option for power quality improvement in electrical power systems control. This paper presents the simulation study of a fuzzy logic hysteresis band current controlled, three-phase SAPF to enhance power quality by harmonic elimination, power-factor correction, reactive power compensation and balancing of nonlinear loads. The advantage of fuzzy control is that it is based on a linguistic description and does not require a mathematical model of the system. Further, in this paper, the hysteresis based current control method is implemented for pulse width-modulation (PWM) switching signals. Results obtained by simulations with Matlab/Simulink show that dynamic behavior of the fuzzy controller is more effective than the conventional proportional- integral (PI) controller method on compensating reactive power and harmonic currents of the load. It is found to be more robust to changes in load and other system parameters compared to the conventional PI controller under steady state and transient conditions. Keywords: Fuzzy logic controller, Hysteresis band current control, Power quality improvement, and Shunt active power filter I. INTRODUCTION Shunt active power filters (SAPF) represent a feasible solution to the problems caused by the non- linear loads. These loads draw non-sinusoidal currents from the 3-phase sinusoidal, balanced voltages which are classified as identified and unidentified loads. The SAPF can compensate for the harmonics, correct the power factor and work as a reactive power compensator, thus providing enhancement of power quality in the system [1, 2]. The control scheme of a SAPF must calculate the current reference waveform for each phase of the inverter, maintain the dc voltage constant, and generate inverter gating signals. The current reference circuit generates the reference currents required to compensate the load current harmonics and reactive power, and also try to maintain constant the dc voltage across the capacitor [3]. In literature [1- 14], most reference compensation current strategies of the SAPF are determined either with or without reference-frame transformations. For instance, the theory proposed in [1, 2] requires transformation of both source voltages and load currents from the a-b-c reference frame to α-β reference frame to determine the SAPF reference compensation currents in the three-phase three-wire system. For detecting the reference compensating current, the instantaneous active and reactive power theory (p-q theory) are widely used, which can provide an instantaneous and accurate reference compensating current [2, 3]. Grady et al. [4] have presented a survey of active power line conditioning methodologies with a list of the advantages and limitations of each one. Cavallini and Montanari [5] have proposed the unity power factor strategy known as classic strategy in which conditions the line currents to fit the voltage waveform, provides line current RMS values always lower than those obtained by keeping the instantaneous real power equal to its mean value. Chang and Shree [6] have proposed a simple and efficient compensation strategy that is suitable for three-phase shunt active power filters without reference-frame transformation requirement. Bhende et al. [7] have proposed Takagi–Sugeno (TS)- type fuzzy logic controller to a three-phase shunt active power filter and compared to conventional proportional-integral (PI) controller. Bhim Singh and Verma [8] have an indirect current control scheme of parallel hybrid power filter system consists of a shunt passive filter with an active filter in series with it connected at the point of common coupling (PCC) in parallel with nonlinear load. Bhuvaneswari and Nair [9] have proposed an algorithm based on the real component of fundamental load current (I cosΦ). Suresh et al. [10] have presented the implementation of a hybrid adaptive fuzzy hysteresis current controller for shunt active power filter using i d–iq strategy. Tang et al. [11] have proposed a LCL-filter-based shunt active power filter which gives good switching harmonic suppression and minimizes the possibility of over-modulation. Chandra et al. [12] have presented an improved control algorithm of the SAPF which used two closed loop PI controllers and carrier wave PWM signal generation. Akagi [13] has listed trends in active power line conditioners. Singh et al. [14] have presented a review on classification of active filters for power quality improvement based on converter type, topology and the number of phases. In the generalized instantaneous reactive power theory [2], transformation of a-b-c axes to d–q synchronous reference frame is done for harmonic and reactive power compensation. However, the synchronous reference frame (SRF) strategy [3] only computes the sinusoidal fundamental components of the load currents; the reactive power compensation and a null neutral current thus cannot be achieved if the load imbalance at the fundamental frequency occurs. A phase-locked loop (PLL) per each phase must be used. In theory, the aforementioned approaches work very well on harmonic and/or reactive power compensation for nonlinear loads under ideal source voltages. However, if the source voltages are www.ijmer.com 477 | Page
  • 2. International Journal of Modern Engineering Research (IJMER) www.ijmer.com Vol.3, Issue.1, Jan-Feb. 2013 pp-477-485 ISSN: 2249-6645 imbalanced and/or distorted, the generated SAPF reference compensation currents are discrepant and the desired balanced/sinusoidal source currents cannot be maintained [6]. Among different PWM methods, hysteresis is one of the most popular PWM strategies [6- 10] and widely applied in SAPF for current quality compensation, owing to its advantages such as ease of implementation, fast dynamic response and current limiting capability. Recently, fuzzy logic controllers have generated a great deal of interest in various applications and have been introduced in the power-electronics field. The advantages of fuzzy logic controllers over the conventional PI controller are that they do not need an accurate mathematical model; they can work with imprecise inputs, can handle nonlinearity, and may be more robust than the conventional PI controller. The Mamdani type of fuzzy controller used for the control of APF gives better results compared with the PI controller [7, 10, and 14]. To achieve full compensation of both reactive power and harmonic/neutral currents of the load, this paper presents a simple method to determine the SAPF reference compensation currents using dc voltage, PI and Fuzzy controller and source voltages. This method does not require any reference frame transformations. Hysteresis band current control PWM strategy is used to drive current controlled voltage source inverter (CC- VSI). The two schemes, conventional PI controller and Fuzzy controller are compared in this paper. A MATLAB based simulation is performed on proposed system and the results are presented to discuss in regard to the voltage regulation, harmonic elimination, power-factor correction and load balancing capabilities of the SAPF system. II. CONTROL SCHEME OF SAPF The control scheme of a shunt active power filter must calculate the current reference waveform for each phase of the inverter, maintain the dc voltage constant, and generate the inverter gating signals. The block diagram of the control scheme of a shunt active power filter is shown in Fig. 1. The current reference circuit generates the reference currents required to compensate the load current harmonics and reactive power, and also try to maintain constant the dc voltage across the electrolytic capacitors. Also, the compensation effectiveness of an active power filter depends on its ability to follow with a minimum error and time delay, the reference signal calculated to compensate the distorted load current. Finally, the dc voltage control unit must keep the total dc bus voltage constant and equal to a given reference value. The dc voltage control is achieved by adjusting the small amount of real power absorbed by the inverter. This small amount of real power is adjusted by changing the amplitude of the fundamental component of the reference current. Different control topologies of SAPF are well documented in recent years [1- 14]. isa PCC v ila il a sa isb ilb b vsb RL isc i c vsc lc LL Z s  Ls , Rs  Non linear load Z f  Lf , Rf  icc ica icb Cdc Vdc 3- Phase VSI Figure 1: Basic Compensation Principle of Shunt Active Power Filter (SAPF) 2.1 Generation of Source Currents SAPF is controlled to draw/supply a compensating current from/to the utility, so that it cancels current harmonics on the ac side and makes the source current in phase with the source voltage. From Fig. 1, the instantaneous currents can be written as: is  t  = iL  t  - ic t  (1) Source voltage is given by: vs  t  = Vmsinωt (2) If the nonlinear load is applied, then the load current will have a fundamental component and harmonic components, which can be expressed as:  iL  t  =  I n sin  nωt + φn  n=1  (3)   = I1sin nωt + φ1 +  I n sin  nωt + φn  n=2 www.ijmer.com 478 | Page
  • 3. International Journal of Modern Engineering Research (IJMER) www.ijmer.com Vol.3, Issue.1, Jan-Feb. 2013 pp-477-485 ISSN: 2249-6645 The instantaneous load power can be given as: p L  t  = vs  t  * i L  t  2 = Vm I1sin ωt * cosφ1 +Vm I1sinωt * cosωt * sinφ1 ¥ (4) +Vm sinωt *  I n sin  nωt + φn  n=2 = p f  t  + pr  t  + ph  t  From (4), the real power drawn by the load is: p f  t  = Vm I1sin ωt * cosφ1 = vs  t  * is t  2 (5) From (5), the current supplied by the source, after compensation is: p f t  is  t  = = I1 * cosφ1 * sinωt = I sm sinωt vs  t  Where I sm = I1 * cosφ1 There are also some switching losses in the PWM converter and, hence, the utility must supply a small overhead for the capacitor leakage and converter switching losses in addition to the real power of the load. The total peak current supplied by the source (Isp) is therefore: I sp = I sm + I sl (6) Where Isl is the peak value of loss current. If the active filter provides total reactive and harmonic power, then i s(t) will be in phase with the utility voltage and purely sinusoidal. At this time, the active filter must provide the following compensation current: ic  t  = iL  t  - is t  (7) 2.2 Generation of Reference Source Currents There are many possibilities to determine the reference current required to compensating the non-linear load. Normally, shunt active power filters are used to compensate the displacement power factor and low-frequency current harmonics generated by non-linear loads. One alternative to determine the current reference required by the VSI is the use of the instantaneous reactive power theory, proposed by Akagi [1], the other one is to obtain current components in d–q or synchronous reference frame [2], and the third one to force the system line current to follow a perfectly sinusoidal template in phase with the respective phase-to-neutral voltage [3]. In this paper, a simple method is used to generate the source reference currents using DC voltage error and source voltage peak detection. The reason, why it is selected and functioning of the control method is explained below. III. Proposed Method With Pi Controller The aim of the method is to generate the current reference signal required to compensate reactive power and current harmonics. Basically, all the different schemes try to obtain the current reference signals that include the reactive components required to compensate the displacement power factor and the current harmonics generated by the non-linear load. Fig. 2 shows the PI controller based scheme used to generate the current reference signals required by a shunt active power filter. In this circuit, the distorted load current is filtered, extracting the fundamental component, Il. 3.1Design of DC Link Voltage PI Controller The three phase reference currents (peak value) for the control of active filter are generated in accordance with the PI controller error between the average dc bus voltage Vdc (n) and its reference value Vdcref (n) of the active filter. The dc bus voltage error Ve (n) at nth sampling instant is: Ve  n  = Vdcref  n - Vdc  n  (8) www.ijmer.com 479 | Page
  • 4. International Journal of Modern Engineering Research (IJMER) www.ijmer.com Vol.3, Issue.1, Jan-Feb. 2013 pp-477-485 ISSN: 2249-6645 Vdcref PI Isaref Controller Vdc Isa product Vsa k PWM Isbref Hysteresis Gate Vsb Current signals k Isc Controller product Iscref Vsc k Isc product Figure 2: PI -hysteresis current controller based PWM generation using proposed method for SAPF. This error signal Ve (n) is processed in PI controller and output K (n) at nth sampling instant is expressed as: K  n  = K  n - 1 + K p Ve  n Ve  n-1  Ki Ve  n  (9) Where Kp and Ki are the gains of the PI controller. The output of the PI controller has been considered as the amplitude of the desired source current, and the reference currents are estimated by multiplying this peak value with the unit sine vectors in phase with the source voltages. In order to provide the reactive power required by the load, the current signal obtained from the PI Controller Il1 is synchronized with the respective phase to- neutral source voltage so that the inverter ac output current is forced to lead the respective inverter output voltage, thereby generating the required reactive power and absorbing the real power necessary to supply the switching losses and also to maintain the dc voltage constant. The real power absorbed by the inverter is controlled by adjusting the amplitude of the fundamental current reference waveform, Il1, obtained from the reference current generator. Ideal compensation requires the mains current to be sinusoidal and in phase with the source voltage, irrespective of the load current nature. The source reference currents, after compensation, can be given as: * i sa = I sp sinωt *  i sb = I sp sin ωt - 120 0  (10) i sc = I sp sin  ωt + 120  * 0 Where Isp is the amplitude of the desired source current, while the phase angle can be obtained from the source voltages. Hence, the waveform and phases of the source currents are known, and only the magnitudes of the source currents need to be determined. The main characteristic of this method is the direct derivation of the compensating component by sensing dc voltage, source voltages and currents, without use of any reference frame transformation. Nevertheless, this PI controller presents a low frequency oscillation problem in the active power filter dc bus voltage. To improve this technique, fuzzy hysteresis band current controller has been implemented in this paper. IV. PROPOSED FUZZY CONTROL ALGORITHM Fig. 3 shows the schematic diagram of the fuzzy control scheme. In order to implement the control algorithm of a shunt active power filter in a closed loop, the dc capacitor voltage Vdc is sensed and then compared with the reference value Vdcref. In case of a fuzzy logic control scheme, the error e = Vdcref – Vdc and integration of error signal ∫e are used as inputs for fuzzy processing. The output of the fuzzy controller after a limit is considered as the magnitude of peak reference current Imax. The switching signals for the PWM converter are obtained by comparing the actual source currents (isa, isb, isc) with the reference current templates (i*sa, i*sb, i*sc ) in the hysteresis current controller. The output pulses are then given to the switching devices of the PWM converter. Fuzzy Logic Controller with Ruleviewer Vdcref Isaref Vdc Isa product Vsa k PWM Isbref Hysteresis Gate Vsb Current signals k Isc Controller product Iscref Vsc k Isc product Figure 3: Fuzzy -hysteresis current controller based PWM generation using proposed method for SAPF. www.ijmer.com 480 | Page
  • 5. International Journal of Modern Engineering Research (IJMER) www.ijmer.com Vol.3, Issue.1, Jan-Feb. 2013 pp-477-485 ISSN: 2249-6645 4.1. Basic Fuzzy Algorithm In a fuzzy logic controller, the control action is determined from the evaluation of „a’ set of simple linguistic rules. The development of the rules requires „a’ thorough understanding of the process to be controlled, but it does not require a mathematical model of the system. The design of a fuzzy logic controller requires the choice of membership functions. The membership functions should be chosen such that they cover the whole universe of discourse. It should be taken care that the membership functions overlap each other. This is done in order to avoid any kind of discontinuity with respect to the minor changes in the inputs. To achieve finer control, the membership functions near the zero region should be made narrow. Wider membership functions away from the zero region provides faster response to the system. Hence, the membership functions should be adjusted accordingly. After the appropriate membership functions are chosen, a rule base should be created. It consists of a number of Fuzzy If-Then rules that completely define the behaviour of the system. These rules very much resemble the human thought process, thereby providing artificial intelligence to the system [3]. The internal structure of the fuzzy controller is shown in Fig. 4. The error e and change of error ce are used numerical variables from the real system. To convert these numerical variables into linguistic variables, the following seven fuzzy levels or sets are chosen as: NB (negative big), NM (negative medium), NS (negative small), ZE (zero), PS (positive small), PM (positive medium), and PB (positive big) and presented in input and output normalized membership functions (Figs. 5 (a) and (b)). The fuzzy controller is characterized as follows: (i) Seven fizzy sets for each input and output. (ii) Triangular membership functions for simplicity. (iii) Fuzzification using continuous universe of discourse. (iv) Implication using Mamdani‟s 'min' operator. (v) Defiizzificatioii using the 'centroid' method. Fuzzy Logic Controller Imax(n e(n) ∫ ) Fuzzy Interface Vdc Fuzzification Defuzzification Engine ce(n) Vdcref To Imax(n)= Imax(n-1) Hysteresis +∫ Imax(n) Controller Figure 4: Internal Structure of Fuzzy controller. Figure 5(a): Input normalized membership function. Figure 5(b): Output normalized membership function. 4.2.Rule Base The elements of this rule base table are determined based on the theory that in the transient state, large errors need coarse control, which requires coarse input/output variables; in the steady state, small errors need fine control, which requires fine input/output variables. Based on this the elements of the rule table are obtained as shown in Table I, with „e‟ and „ce‟ as inputs. www.ijmer.com 481 | Page
  • 6. International Journal of Modern Engineering Research (IJMER) www.ijmer.com Vol.3, Issue.1, Jan-Feb. 2013 pp-477-485 ISSN: 2249-6645 Table.I Control Rule Base NB N NS ZE PS PM PB ce M e NB NB NB NB NB NM NS ZE N NB NB NB NM NS ZE PS M NB NB NB NM NS ZE PS PM ZE NB NM NS ZE PS PM PB PS NM NS ZE PS PM PB PB e P NS ZE PS PM PB PB PB M PB ZE PS PM PB PB PB PB 4.3 Hysteresis Current Controller for PWM Switching The active filter is comprised of three-phase IGBT based current controlled VSI bridge. The upper device and the lower device in one phase leg of VSI are switched in complementary manner. The switching logic for “phase-a” is formulated as follows: if isa < (i*sa- hb), upper switch is OFF and lower switch is ON in the phase “a” leg then S a = 0. If isa > (i*sa+hb) upper switch is ON and lower switch is OFF in the phase “a” leg then Sa= 1. Between the transitions the previous value of switches are maintained. Where, is switching function for switches of phase “a” and is the width of the hysteresis band around reference currents. Similarly, the switching logic of the other two phases (“b” and “c”) is formulated. V. Simulation Results And Discussion Following are the system parameters considered for the study of SAPF for both PI and Fuzzy controller. Vs = 100 V (Peak), f = 50 Hz, Rs= 0.1 Ω, Ls= 0.15 mH, Rf = 0.1 Ω, Lf = 0.66 mH, Rl = 6.7, 15 Ω; Ll = 20mH, CDC = 2000 µF, Vdcref = 220 V. In case of PI the gains chosen are kp= 0.2 and ki = 9.32. Initially, the load chosen is of Rl = 6.7 Ω, Ll = 20mH and later, the load has been changed to Rl = 15 Ω, Ll=20mH. The performance results of shunt active power filter with PI controller are presented in Figures 7- 9. Fig.6 shows THD content of Load current, Source current with PI controller and with Fuzzy controller. In Fig.7performance results of SAPF with PI controller are presented and results with fuzzy controller are presented in Fig. 8. Fig.9 shows results in support of power factor correction ability of SAPF. Comparisons of PI and fuzzy controllers are presented in Table II, III and IV based on % THD, settling time and overshoot. (Parameters notation is shown in Fig. 1.) FFT window: 2 of 25 cycles of selected signal 30 20 10 0 -10 -20 -30 0.35 0.355 0.36 0.365 0.37 0.375 0.38 0.385 Time (s) Fundamental (50Hz) = 26.14 , THD= 28.10% 5 4 Mag 3 2 1 0 0 100 200 300 400 500 600 700 800 900 1000 Frequency (Hz) Figure 6 (a): THD % of load current FFT window: 2 of 25 c y c les of s elec t ed s ignal 15 10 5 0 -5 -10 -15 0. 25 0. 255 0. 26 0. 265 0. 27 0. 275 0. 28 0. 285 Time (s ) Fundament al (50Hz ) = 11. 68 , THD= 1. 95% 0. 4 0. 35 0. 3 0. 25 Mag 0. 2 0. 15 0. 1 0. 05 0 0 100 200 300 400 500 600 700 800 900 1000 Frequenc y (Hz ) Figure.6 (b): THD % of Source current (PI) FFT window: 2 of 25 c y c les of s elec ted s ignal 15 10 5 0 -5 -10 -15 0.3 0.305 0.31 0.315 0.32 0.325 0.33 0.335 Time (s ) Fundamental (50Hz) = 11.93 , THD= 0.51% 0.04 0.035 0.03 0.025 Mag 0.02 0.015 0.01 0.005 0 0 100 200 300 400 500 600 700 800 900 1000 Frequency (Hz) Figure.6(c) THD% of Source current (Fuzzy) www.ijmer.com 482 | Page
  • 7. International Journal of Modern Engineering Research (IJMER) www.ijmer.com Vol.3, Issue.1, Jan-Feb. 2013 pp-477-485 ISSN: 2249-6645 Figure.7: Performance results of shunt active power filter with PI controller for the load of Rl = 15 Ω, and Ll = 20 mH. Figure.8: Performance results of shunt active power filter with fuzzy controller for the load Rl = 15 Ω, and Ll = 20 mH 100 80 Source Voltage and Current..........pf 60 40 20 0 -20 -40 -60 -80 -100 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 Time in Seconds Figure 9(a): Source Voltage and current wave forms of Phase ‘a’ of PI controlled SAPF www.ijmer.com 483 | Page
  • 8. International Journal of Modern Engineering Research (IJMER) www.ijmer.com Vol.3, Issue.1, Jan-Feb. 2013 pp-477-485 ISSN: 2249-6645 100 80 60 Source voltage & Source current 40 20 0 -20 -40 -60 -80 -100 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 Time in second Figure 9(b): Source Voltage and current wave forms of Phase ‘a’ of Fuzzy controlled SAPF TABLE.II: Thd % Comparison between Pi and Fuzzy Controllers % THD at two different loads Rl = 6.7 Ω, Rl = 15Ω, Ll = 20mH Ll = 20mH Without controller 28.10 27.72 With PI controller 0.81 1.03 With Fuzzy controller 1.1 0.51 TABLE.III: Settling Time Comparison between Pi And Fuzzy Controllers Settling time for two different loadings (sec) Rl = 6.7 Rl = 15Ω, Ω, Ll = Ll = 20mH 20mH With PI controller 0.26 s 0.33 s With Fuzzy 0.18 s 0.24 s controller TABLE.IV: Response of Pi and Fuzzy Controllers under Dynamic Load Conditions PI Fuzzy Switch on response 80 A 65 A (peak overshoot) Settling time (after 0.45 s 0.3 s load change) Load current 45 A 35 A overshoot (at load change) www.ijmer.com 484 | Page
  • 9. International Journal of Modern Engineering Research (IJMER) www.ijmer.com Vol.3, Issue.1, Jan-Feb. 2013 pp-477-485 ISSN: 2249-6645 VI. CONCLUSION This paper has presented a simulation study of fuzzy based hysteresis current controlled shunt active power filter for harmonic and reactive power compensation of the non-linear load. A simple method is implemented to generate source reference currents without reference frame transformation using DC voltage regulator and source voltages. It gives less complexity in realizing the control circuit of the active power filter and still maintains good filter performance. The scheme has the advantage of simplicity and is able to provide self-supported dc bus of the active filter through power transfer from ac line at fundamental frequency. The performance of conventional PI controller and fuzzy controller has been studied and compared. Overall, the fuzzy controller gives the best SAPF performance in comparison with the PI controller in regards voltage regulation, % THD, settling time, current overshoot etc. REFERENCES [1] H. Akagi, Y. Kanzawa, and A. Nabae “Instantaneous reactive power compensators comprising switching devices without energy Components” IEEE Transactions on Industrial Applications, Vol. 20, No. 3, pp. 625–630, 1984. [2] H. Akagi, E. Watanabe, M. Aredes “Instantaneous Power Theory and Applications to Power Conditioning: (Wiley-IEEE Press, 2007). [3] M.H. Rashid “Power Electronics Handbook: Devices, Circuits, and Application”, (Elsevier Inc., Section Edition, 2007) [4] W. M. Grady, M. J. Samotyj and A. H. Noyola “Survey of Active Power Line Conditioning Methodologies” IEEETransaction on Power Delivery, Vol. 5, No. 3, pp. 1536- 1542, July 1990. [5] A. Cavallini and G. C. Montanari “Compensation Strategies for Shunt Active-Filter Control” IEEE Transactions on Power Electronics, Vol. 9, No. 6, pp. 587- 593, November 1994. [6] G. W. Chang, and T. C. Shee “A Novel Reference Compensation Current Strategy for Shunt Active Power Filter Control” IEEE Transactions on Power Delivery, Vol. 19, No. 4, pp. 1751 – 1758, October 2004. [7] C. N. Bhende, S. Mishra, and S. K. Jain “TS-Fuzzy-Controlled Active Power Filter for Load Compensation, IEEETransactions on Power Delivery, Vol. 21, No. 3, pp. 1459- 1465, July 2006. [8] Bhim Singh, and Vishal Verma “An Indirect Current Control of Hybrid Power Filter for Varying Loads” IEEETransactions on Power Delivery, Vol. 21, No. 1, pp. 178- 184, January 2006. [9] G. Bhubaneswar, and Manjula G. Nair “Design, Simulation, and Analog Circuit Implementation of a Three-Phase Shunt Active Filter Using the Icos Φ Algorithm” IEEE Transactions on Power Delivery, Vol. 23, No. 2, pp. 1222 – 1235, April 2008. [10] Y. Suresh A.K. Panda and M. Suresh “Real-time implementations of adaptive fuzzy hysteresis-band current control technique for shunt active power filter” Vol. 5, Iss. 7, pp. 1188–1195, IET Power Electronics, 2012. [11] Y. Tang, P. C. Loh, P. Wang, F. H. Choo, F. Gao, and F. Blaabjerg, “Generalized Design of High Performance Shunt Active Power Filter With Output LCL Filter” IEEE Transactions on Industrial Electronics, Vol. 59, No. 3, pp. 1443-1452, March 2012. [12] Ambrish Chandra, Bhim Singh, B. N. Singh, and Kamal Al-Haddad, “An Improved Control Algorithm of Shunt Active Filter for Voltage Regulation, Harmonic Elimination, Power-Factor Correction, and Balancing of Nonlinear Loads”IEEE Transactions on Power Electronics, Vol. 15, No. 3, pp. 495 -507, May 2000. [13] H. Akagi, New Trends in Active Filters for Power Conditioning” IEEE Transactions on Industry Applications, Vol32, No 6, pp. 1312- 1322, December 1996. [14] Bhim Singh, Kamal Al-Haddad, and Ambrish Chandra “A Review of Active Filters for Power Quality Improvement” IEEE Transactions on Industrial Electronics, Vol. 46, No. 5, pp. 60 – 71, October 1999. www.ijmer.com 485 | Page