Catalog thiết bị đóng cắt Fuji Electric - Fuji Molded Case Circuit Breakers BW0 series, 32 Ampere Frame MCCB
*********************************************************************
CTY TNHH HẠO PHƯƠNG - Nhà phân phối chính thức các thiết bị điện công nghiệp và tự động hóa của hãng FUJI ELECTRIC JAPAN tại Việt Nam
Xem chi tiết các sản phẩm Fuji Electric tại
http://haophuong.com/b1033533/fuji-electric
1. Fuji Molded Case Circuit Breakers
BW0 series,
32 Ampere Frame MCCB
BW33A0
NEW
Features
Compact design
• 2P: W 36mm x H 80mm x D 60mm
• 3P: W 54mm x H 80mm x D 60mm
Cost and space saving for building a control panel
AC440V application
• Icu : 1.5kA at 440V AC, 2.5kA at 240V AC
Available accessories
• Auxiliary switch
• Alarm switch
• Shunt trip device
Standards
• IEC 60947-2 with CE mark
Certifications
• TÜV (IEC/EN 60947-2)
Type number nomenclature
BW 3 3 A0 - 032 W K FA A
Product category
BW : MCCB
Accessories
Terminal block
A : with terminal block
Shunt trip device *1
FA : 100VAC to 120VAC
FK : 200VAC to 240VAC
FD : 100VDC
Alarm switch *2
K : 1c / alarm switch
Auxiliary switch *2
W : 1c / auxiliary switch
Frame size
3 : 32AF
Number of poles
2 : 2 poles
3 : 3 poles
Breaking capacity
A0 : 1.5kA at 440V AC
Rated current
005 : 5A
010 : 10A
015 : 15A
020 : 20A
032 : 32A
Notes
*1 A shunt trip device can be installed on 3-pole models only.
*2 For 2-pole models, only one alarm switch or one auxiliary switch
can be installed.
62D9-E-0085
2. Ha Noi Office:
No. 95 - TT4, My Dinh Urban Area,
My Dinh, Nam Tu Liem, Hanoi.
Tel: (84 4) 3568 3740
Fax: (84 4) 3568 3741
Cambodia Office:
#140, Room 1-B, St430, Sangkat Toul
Tompuong II, Khan Chamkamon, PP.
Tel: 855 2322 3635
Fax: 855 2322 3645
Head Office:
No 88, Vinh Phu 40, Hoa Long,
Vinh Phu, Thuan An, Binh Duong.
Tel: (84 650) 37 37 619
Fax: (84 650) 37 37 620
1800 6547
THINK TOGETHER
Nhà phân phối thiết bị điện công nghiệp
hàng đầu Việt Nam
T
3. Specifications
Type BW32A0 BW33A0
Number of poles and elements 2P2E 3P3E
Rated insulation voltage Ui [V] AC 440
Rated impulse withstand voltage Uipm [kV] 4
Rated frequency [Hz] 50/60
Rated current In [A] 5, 10, 15, 20, 32
Rated breaking capacity
Icu/Ics [kA]
IEC60947-2
EN60947-2
JIS C8201-2-1 Ann1,Ann2
AC380/400/415/440V 1.5/1
AC230/240V 2.5/2
GB14048.2 AC400V 1.5/1
AC230V 2.5/2
Overcurrent tripping device Thermal - Magnetic
Utilization category A
Reverse connection Yes
Suitable for isolation No
Rear wire connection Available
PS E No
CE marking Yes
CCC marking Pending
Compliance with IEC60947-1,2 TÜV
Standard conditions Ambient temperature -10℃ to +40℃
Relative humidity Without dew condensation and freezing
Altitude 2000m or less
Atmosphere Normal use
Type Contact capacity Wire size Input
W, K
AC125V 3A
DC30V 2A
AWG24 –
F – AWG24 150VA
Internal accessories
Available configurations Specifications
Pole 2 3
W
K
F
Auxiliary switch :
Alarm switch :
Shunt trip device :
W + K
W + F
K + F
W + K + F
BW32A0Type BW33A0
Note: Terminal block is installed on the same side of the accessory.
3-pole
Handle
RightLeft
2-pole
Handle
Left Shunt trip: F
Auxiliary switch: W
Alarm switch: K
Lead wire
5. 48
14.5
54
80
18
36
2P
Panel drilling
3P
60
14.5
48
80
6767
6767
832328
34
Trip Button
832328
52
18
Trip Button
36
6.5
76
12.2
6.5
24
M5x12
Terminal section
48
M4 or ø5M4 or ø5
CL
CLCL
Printed in Japan 2012-10 PDF FOLS 62D9-E-0085Information in this catalog is subject to change without notice.
5-7, Nihonbashi Odemma-cho, Chuo-ku, Tokyo, 103-0011, Japan
URL http://www.fujielectric.co.jp/fcs/eng
Safety Considerations
• Operate (keep) in the environment specified in the operating instructions and manual. High temperature, high humidity, condensation, dust,
corrosive gases, oil, organic solvents, excessive vibration or shock might cause electric shock, fire, erratic operation or failure.
• For safe operation, before using the product read the instruction manual or user manual that comes with the product carefully or consult the
Fuji sales representative from which you purchased the product.
• Products introduced in this catalog have not been designed or manufactured for such applications in a system or equipment that will affect
human bodies or lives.
• Customers, who want to use the products introduced in this catalog for special systems or devices such as for atomic-energy control,
aerospace use, medical use, passenger vehicle, and traffic control, are requested to consult with Fuji Electric FA.
• Customers are requested to prepare safety measures when they apply the products introduced in this catalog to such systems or facilities
that will affect human lives or cause severe damage to property if the products become faulty.
• For safe operation, wiring should be conducted only by qualified engineers who have sufficient technical knowledge about electrical work or
wiring.
• Follow the regulations of industrial wastes when the product is to be discarded.
• For further questions, please contact your Fuji sales representative or Fuji Electric FA.
Dimensions, mm