PROTECTION SETTINGS: INTRODUCTION
 A power system is composed of a number of sections
(equipment) such as generator, transformer, bus bar
and transmission line.
 These sections are protected by protective relaying
systems comprising of instrument transformers (ITs),
protective relays, circuit breakers (CBs) and
communication equipment.
 In case of a fault occurring on a section, its associated
protective relays should detect the fault and issue trip
signals to open their associated CBs to isolate the
faulted section from the rest of the power system, in
order to avoid further damage to the power system.
3
4
Below Fig. 1 is an typical example of power system sections with their
protection systems. Where:
G1 is a generator. T1 is a transformer. B1,...,B5 are bus bars. L45 is
a transmission line (TL).
RG is a generator protective relay. RT is a transformer protective
relay. RB is a bus protective relay. RL-4,...,RL-9 are TL protective
relays. C1,..., C9 are CBs.
Protection Settings: Introduction
Fig. 1 Protection of power system sections
PROTECTION SETTINGS: INTRODUCTION
 Maximum fault clearance times are usually specified by
the regulating bodies and network service providers.
 The clearing times are given for local and remote CBs
and depend on the voltage level and are determined
primarily to meet stability requirements and minimize
plant damage.
 The maximum clearance times of the backup protection
are also specified.
 e.g. the clearing times for faults on the lines specified by
one network service provider in Australia are presented
in Table I (next slide).
5
TABLE I: FAULT CLEARANCE TIMES
Voltage
level [kV]
CB operate correctly
[ms]
CB fail [ms]
Local Remote Local Remote
500 80 100 175 175
330 100 120 250 250
275 100 120 250 250
220 120 140 430 430
132 120 160 430 430
110 120 160 430 430
66 120 160 430 430
≤ 33 1160 - 1500 -
6
FUNCTIONS OF EQUIPMENT PROTECTION
Protection schemes are generally divided into equipment
protection and system protection.
The main function of equipment protection is to selectively
and rapidly detect and disconnect a fault on the protected
circuit to:
 ensure optimal power quality to customers;
 minimize damage to the primary plant;
 prevent damage to healthy equipment that conducts fault
current during faults;
 restore supply over the remaining healthy network;
 sustain stability and integrity of the power system;
 limit safety hazard to the power utility personnel and the
public. 7
FUNCTIONS OF PROTECTIVE RELAYS
 The protection functions are considered adequate when the
protection relays perform correctly in terms of:
 Dependability: The probability of not having a failure to
operate under given conditions for a given time interval.
 Security: The probability of not having an unwanted
operation under given conditions for a given time interval.
 Speed of Operation: The clearance of faults in the shortest
time is a fundamental requirement (transmission system), but
this must be seen in conjunction with the associated cost
implications and the performance requirements for a specific
application. 8
…FUNCTIONS OF PROTECTIVE RELAYS
 Selectivity (Discrimination):
The ability to detect a fault within a specified zone of a
network and to trip the appropriate CB(s) to clear this fault
with a minimum disturbance to the rest of that network.
 Single failure criterion:
A protection design criterion whereby a protection system
must not fail to operate even after one component fails to
operate.
With respect to the protection relay, the single failure criterion
caters primarily for a failed or defective relay, and not a
failure to operate as a result of a performance deficiency
inherent within the design of the relay.
9
…FUNCTIONS OF PROTECTIVE RELAYS
 The setting of protection relays is not a definite
science.
 Depending on local conditions and requirements,
setting of each protective function has to be optimized
to achieve the best balance between reliability, security
and speed of operation.
 Protection settings should therefore be calculated by
protection engineers with vast experience in protective
relaying, power system operation and performance
and quality of supply.
10
REQUIRED INFORMATION FOR PROTECTIVE SETTING
Line Parameters:
 For a new line: final total line length as well as the lengths,
conductor sizes and tower types of each section where
different tower types or conductors have been used.
 This information is used to calculate the parameters (positive
and zero sequence resistance, reactance and susceptance)
for each section.
 Maximum load current or apparent power (MVA)
corresponding to the emergency line which can be obtained
from the table of standard conductor rating (available in each
utility).
 The number of conductors in a bundle has to be taken into
consideration.
11
…REQUIRED INFORMATION FOR PROTECTIVE
SETTING
 Transformer Parameters:
 The manufacturer's positive and zero sequence
impedance test values have to be obtained.
 The transformer nameplate normally provides the
manufacturer's positive sequence impedance values
only.
 Terminal Equipment Rating:
 The rating of terminal equipment (CB, CT, line trap,
links) of the circuit may limit its transfer capability
therefore the rating of each device has to be known.
 Data can be obtained from the single line diagrams.
12
…REQUIRED INFORMATION FOR PROTECTIVE
SETTING
Fault Studies
 Results of fault studies must be provided.
 The developed settings should be checked on future
cases modelled with the system changes that will take
place in the future (e.g. within 5 years).
 Use a maximum fault current case.
CT & VT Ratios:
 Obtain the CT ratios as indicated on the protection
diagrams.
 For existing circuits, it is possible to verify the ratios
indicated on the diagrams by measuring the load
currents on site and comparing with a known ratio.
13
…REQUIRED INFORMATION FOR PROTECTIVE
SETTING
 Checking For CT Saturation:
 Protection systems are adversely affected by CT saturation. It is
the responsibility of protection engineers to establish for which
forms of protection and under what conditions the CT should not
saturate.
 CTs for Transformer Differential Protection:
 MV, HV and LV CTs must be matched as far as possible taking
into consideration the transformer vector group, tap changer
influence and the connection of CTs.
 CTs for Transformer Restricted Earth Fault (REF)
Protection:
 All CT ratios must be the same (as with the bus zone
protection), except if the relay can internally correct
unmatched ratios.
14
PROTECTION SETTINGS PROCESS
 The Protection Settings team obtains all the information
necessary for correct setting calculations.
 The settings are then calculated according to the latest
philosophy, using sound engineering principles. Pre-written
programs may be used as a guide.
 After calculation of the settings, it is important that another
competent person checks them.
 The persons who calculate and who check the settings both
sign the formal settings document.
 The flowchart in Fig. 2 indicates information flow during
protection setting preparation for commissioning of new
Transmission plant.
15
16
Project leader of the Protection
Settings team determines scope
of work and target dates
Summary and comparison of inputs
IED manufacturers provide bay
specific IED details
Engineering team provides bay
specific proformas and drawings
Corrective actions and re-issue of
drawings
Study new protection and create
necessary setting templates in
liaison with engineering team and
IED manufactureres
OK
Not OK
Calculation and verification of settings
Settings stored in central database
and formal document issued
Implementation date and responsible
field person stored in the central
database -> implementation action
Implementation sheet completed
by field staff and returned to
Protection Settings team
Interface with the Expansion Planing
team and IED manufacturers to obtain
relevant equipment parameters for
correct system modelling
Centralised Settings Management
System sends the action documents
to the field staff
Corrective actions required to
ensure implementation
Fig. 2 Information flow during
protection settings preparation
FUNCTIONAL ELEMENTS OF
PROTECTIVE RELAYS
 To achieve maximum flexibility, relays is designed using the concept
of functional elements which include protection elements, control
elements, input and output contacts etc.
 The protection elements are arranged to detect the system condition,
make a decision if the observed variables are over/under the
acceptable limit, and take proper action if acceptable limits are
crossed.
 Protection element measures system quantities such as voltages and
currents, and compares these quantities or their combination against
a threshold setting (pickup values).
 If this comparison indicates that the thresholds are crossed, a
decision element is triggered.
 This may involve a timing element, to determine if the condition is
permanent or temporary. If all checks are satisfied, the relay (action
element) operates.
17
18
Fault
Pickup of
protection element
Operation of
protection element
Assertion of relay
trip logic signal
Action of relay
trip contact
Circuit breaker
opening
Fault cleared
Fig. 3 Sequence of operation.
Sequence of protection operation initiated by a fault is
shown in Fig. 3.
OPERATING CHARACTERISTICS OF
PROTECTIVE RELAYS
 Protective relays respond and operate according to defined
operating characteristic and applied settings.
 Each type of protective relay has distinctive operating
characteristic to achieve implementation objective: sensitivity,
selectivity, reliability and adequate speed of operation.
 Basic operating characteristics of protective elements is as
follows:
 Overcurrent protection function: the overcurrent element
operates or picks up when its input current exceeds a
predetermined value.
 Directional function: an element picks up for faults in one
direction, and remains stable for faults in the other direction.
19
…OPERATING CHARACTERISTICS OF
PROTECTIVE RELAYS
 Distance protection function: an element used for
protection of transmission lines whose response is a
function of the measured electrical distance between
the relay location and the fault point.
 Differential protection function: it senses a difference
between incoming and outgoing currents flowing
through the protected apparatus.
 Communications-Assisted Tripping Schemes: a form
of the transmission line protection that uses a
communication between distance relays at opposite line
ends resulting in selective clearing of all line faults
without time delay. 20
OVERCURRENT AND DIRECTIONAL
PROTECTION ELEMENTS
 An overcurrent condition occurs when the maximum
continuous load current permissible for a particular piece of
equipment is exceeded.
 A phase overcurrent protection element continuously
monitors the phase current being conducted in the system
and issue a trip command to a CB when the measured
current exceeds a predefined setting.
 The biggest area of concern for over-current protection is
how to achieve selectivity.
 Some possible solutions have been developed, including
monitoring current levels (current grading), introducing time
delays (time grading) or combining the two as well as
including a directional element to detect the direction of
current flow.
21
CURRENT GRADING
 Current grading will achieve selectivity by determine the
location of a fault using purely magnitude of current.
 It is difficult to implement this in practice unless feeder
sections have sufficient differences in impedance to
cause noticeable variations in fault current.
 In a network where there are several sections of line
connected in series, without significant impedances at
their junctions there will be little difference in currents,
so discrimination or selectivity cannot be achieved using
current grading.
22
TIME DELAYS
 An alternate means of grading is introducing time delays between
subsequent relays.
 Time delays are set so that the appropriate relay has sufficient time
to open its breaker and clear the fault on its section of line before
the relay associated with the adjacent section acts.
 Hence, the relay at the remote end is set up to have the shortest
time delay and each successive relay back toward the source has
an increasingly longer time delay.
 This eliminates some of the problems with current grading and
achieves a system where the minimum amount of equipment is
isolated during a fault.
 However, there is one main problem which arises due to the fact
that timing is based solely on position, not fault current level.
 So, faults nearer to the source, which carry the highest current, will
take longer to clear, which is very contradictory and can prove to be
quite costly.
23
DIRECTIONAL ELEMENTS
 Selectivity can be achieved by using directional elements in
conjunction with instantaneous or definite-time overcurrent
elements.
 Directional overcurrent protection schemes respond to faults in only
one direction which allows the relay to be set in coordination with
other relays downstream from the relay location.
 This is explained using example in Fig. 4.
24
DIRECTIONAL ELEMENTS
 By providing directional elements
at the remote ends of this
system, which would only
operate for fault currents flowing
in one direction we can maintain
redundancy during a fault.
 This is in line with one of the
main outcomes of ensuring
selectivity, which is to minimize
amount of circuitry that is isolated
in order to clear a fault.
25
Fig. 4: Use of direction element
example
DIRECTION OF CURRENT FLOW
 In AC systems, it is difficult to determine the direction of current flow
and the only way to achieve this is to perform measurements with
reference to another alternating quantity, namely voltage. The main
principle of how directional elements operate is based on the
following equations for torque:
 If current is in the forward direction, then the sign of the torque
equation will be positive and as soon as the direction of current flow
reverses, the sign of the torque equation becomes negative. These
calculations are constantly being performed internally inside
directional element. 26
)
cos( A
BC
A
BC
A I
V
I
V
T 





)
cos( B
CA
B
CA
B I
V
I
V
T 





)
cos( C
AB
C
AB
C I
V
I
V
T 





DISTANCE PROTECTION FUNCTION
 A distance protection element measures the
quotient V/I (impedance), considering the phase
angle between the voltage V and the current I.
 In the event of a fault, sudden changes occur in
measured voltage and current, causing a variation
in the measured impedance.
 The measured impedance is then compared
against the set value.
 Distance element will trip the relay (a trip command
will be issued to the CB associated with the relay) if
the measured value of the impedance is less then
the value set.
27
…DISTANCE PROTECTION FUNCTION
 In Fig. 5 the impedance measured at the relay point A is
, where x is the distance to the fault (short circuit), and R
and L are transmission line parameters in per unit length.
The line length is l in the fig.. 28
Fig. 5 Distance protection principle of operation.
 
in
Z R j L x

 
…DISTANCE PROTECTION FUNCTION
 We can see that the impedance value of a fault loop
increases from zero for a short circuit at the source end
A, up to some finite value at the remote end B. We can
use this principle to set up zones of distance protection
as well as to provide feedback about where a fault
occurred (distance to fault).
 Operating characteristics of distance protection elements
are usually represented using R-X diagrams.
 Fig. 6 shows an example of Mho R-X operating
characteristic. The relay is considered to be at the origin.
29
…DISTANCE PROTECTION FUNCTION
30
Region of
operation
Zone 1
Region of
non-operation
outside the circle
Load
region
R
X
Zone 2
A
B
80%
120%
Line P
Line Q
RS
Z
Fig. 6 Mho positive-sequence R-X operating
characteristic of a distance element.
…DISTANCE PROTECTION
FUNCTION
 The need for zones shown in Fig. 6 arises from the
need of selective protection; i.e. the distance element
should only trip faulty section.
 We can set the distance element to only trigger a trip
signal for faults within a certain distance from the relay,
which is called the distance element reach.
 The setting impedance is represented by ,
where ZL is the line impedance. The distance element
will only trip when the measured impedance ZR is less
than or equal to the setting impedance hsZL.
31
RS s L
Z h Z

…DISTANCE PROTECTION FUNCTION
 Typically hs is set to protect 80% of the line between two buses
and this forms protection Zone 1.
 Errors in the VTs and CTs, modeled transmission line data, and
fault study data do not permit setting Zone 1 for 100% of the
transmission line.
 If we set Zone 1 for 100% of the transmission line, unwanted
tripping could occur for faults just beyond the remote end of the
line.
32
…DISTANCE PROTECTION
FUNCTION
 Zone 2 is set to protect 120% of the line, hence
making it over-reaching, because it extends into the
section of line protected by the relay at point B. To
avoid nuisance tripping, any fault occurring in Zone
1 is cleared instantaneously, while faults which
occur in Zone 2 are cleared after a time delay in
order to allow relay B to clear that fault first.
 This provides redundancy in the protection system
(backup), whilst maintaining selectivity.
33

More Related Content

Similar to protectionsettings-120425102109-phpapp01.ppt

The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)theijes
 
Transformer Protection using PLC
Transformer Protection using PLCTransformer Protection using PLC
Transformer Protection using PLCSageer Ali Khan
 
Electrical network protection guide schneider electric
Electrical network protection guide schneider electricElectrical network protection guide schneider electric
Electrical network protection guide schneider electricSouvik Dutta
 
Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...
Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...
Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...Kashif Mehmood
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONPower System Operation
 
Review on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power TransformerReview on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power TransformerIRJET Journal
 
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...iosrjce
 
IRJET - Automated Monitoring Test Rig for Circuit Breaker Operation
IRJET -  	  Automated Monitoring Test Rig for Circuit Breaker OperationIRJET -  	  Automated Monitoring Test Rig for Circuit Breaker Operation
IRJET - Automated Monitoring Test Rig for Circuit Breaker OperationIRJET Journal
 
Ipsa mv relay co-ordiantion shaik adam
Ipsa  mv relay  co-ordiantion shaik adamIpsa  mv relay  co-ordiantion shaik adam
Ipsa mv relay co-ordiantion shaik adamShaik Abdullah Adam
 
Power system protection seminar report
Power system protection seminar reportPower system protection seminar report
Power system protection seminar reportRahul Aman
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptxMuhd Hafizi Idris
 
EDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptxEDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptxDr. Rohit Babu
 
IRJET- PLC Based Intelligent Control of Substation
IRJET- PLC Based Intelligent Control of SubstationIRJET- PLC Based Intelligent Control of Substation
IRJET- PLC Based Intelligent Control of SubstationIRJET Journal
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
1.9 protection of power system
1.9 protection of power system1.9 protection of power system
1.9 protection of power systemW3Edify
 

Similar to protectionsettings-120425102109-phpapp01.ppt (20)

The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)
 
E011123541
E011123541E011123541
E011123541
 
Transformer Protection using PLC
Transformer Protection using PLCTransformer Protection using PLC
Transformer Protection using PLC
 
Electrical network protection guide schneider electric
Electrical network protection guide schneider electricElectrical network protection guide schneider electric
Electrical network protection guide schneider electric
 
128 electrical power-protection_guide
128 electrical power-protection_guide128 electrical power-protection_guide
128 electrical power-protection_guide
 
Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...
Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...
Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...
 
PPT.pptx
PPT.pptxPPT.pptx
PPT.pptx
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
 
Review on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power TransformerReview on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power Transformer
 
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
 
D010622334
D010622334D010622334
D010622334
 
IRJET - Automated Monitoring Test Rig for Circuit Breaker Operation
IRJET -  	  Automated Monitoring Test Rig for Circuit Breaker OperationIRJET -  	  Automated Monitoring Test Rig for Circuit Breaker Operation
IRJET - Automated Monitoring Test Rig for Circuit Breaker Operation
 
Ipsa mv relay co-ordiantion shaik adam
Ipsa  mv relay  co-ordiantion shaik adamIpsa  mv relay  co-ordiantion shaik adam
Ipsa mv relay co-ordiantion shaik adam
 
Power system protection seminar report
Power system protection seminar reportPower system protection seminar report
Power system protection seminar report
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
 
EDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptxEDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptx
 
Sistem Tenaga Listrik
Sistem Tenaga Listrik Sistem Tenaga Listrik
Sistem Tenaga Listrik
 
IRJET- PLC Based Intelligent Control of Substation
IRJET- PLC Based Intelligent Control of SubstationIRJET- PLC Based Intelligent Control of Substation
IRJET- PLC Based Intelligent Control of Substation
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
1.9 protection of power system
1.9 protection of power system1.9 protection of power system
1.9 protection of power system
 

More from Thien Phan Bản

Breaker_Failure_Protection.ppt
Breaker_Failure_Protection.pptBreaker_Failure_Protection.ppt
Breaker_Failure_Protection.pptThien Phan Bản
 
'docslide.us_hv-testing.ppt
'docslide.us_hv-testing.ppt'docslide.us_hv-testing.ppt
'docslide.us_hv-testing.pptThien Phan Bản
 
megger-150210211712-conversion-gate01.ppt
megger-150210211712-conversion-gate01.pptmegger-150210211712-conversion-gate01.ppt
megger-150210211712-conversion-gate01.pptThien Phan Bản
 
Breaker_Failure_Protection.ppt
Breaker_Failure_Protection.pptBreaker_Failure_Protection.ppt
Breaker_Failure_Protection.pptThien Phan Bản
 
21955068-High-Low-Impedance-BusBar-Protection.ppt
21955068-High-Low-Impedance-BusBar-Protection.ppt21955068-High-Low-Impedance-BusBar-Protection.ppt
21955068-High-Low-Impedance-BusBar-Protection.pptThien Phan Bản
 
basic-partial-discharge.pdf
basic-partial-discharge.pdfbasic-partial-discharge.pdf
basic-partial-discharge.pdfThien Phan Bản
 
FUNDAMENTALS_OF_BUS_PROTECTION_Handouts.pdf
FUNDAMENTALS_OF_BUS_PROTECTION_Handouts.pdfFUNDAMENTALS_OF_BUS_PROTECTION_Handouts.pdf
FUNDAMENTALS_OF_BUS_PROTECTION_Handouts.pdfThien Phan Bản
 
High_Low_Impedance_BusBar_Protection.ppt
High_Low_Impedance_BusBar_Protection.pptHigh_Low_Impedance_BusBar_Protection.ppt
High_Low_Impedance_BusBar_Protection.pptThien Phan Bản
 
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.pptbasicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.pptThien Phan Bản
 
47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptx47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptxThien Phan Bản
 
14009762-ABB-Protection-Book.pdf
14009762-ABB-Protection-Book.pdf14009762-ABB-Protection-Book.pdf
14009762-ABB-Protection-Book.pdfThien Phan Bản
 
ppt100-110425022440-phpapp02.ppt
ppt100-110425022440-phpapp02.pptppt100-110425022440-phpapp02.ppt
ppt100-110425022440-phpapp02.pptThien Phan Bản
 
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.pptbasicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.pptThien Phan Bản
 
Basic_Protection_Theory_2013_BW.pdf
Basic_Protection_Theory_2013_BW.pdfBasic_Protection_Theory_2013_BW.pdf
Basic_Protection_Theory_2013_BW.pdfThien Phan Bản
 
17648889-Introduction-to-Power-System-Protection-Relays.pdf
17648889-Introduction-to-Power-System-Protection-Relays.pdf17648889-Introduction-to-Power-System-Protection-Relays.pdf
17648889-Introduction-to-Power-System-Protection-Relays.pdfThien Phan Bản
 
pptpdf-131117235616-phpapp02.pdf
pptpdf-131117235616-phpapp02.pdfpptpdf-131117235616-phpapp02.pdf
pptpdf-131117235616-phpapp02.pdfThien Phan Bản
 

More from Thien Phan Bản (20)

Breaker_Failure_Protection.ppt
Breaker_Failure_Protection.pptBreaker_Failure_Protection.ppt
Breaker_Failure_Protection.ppt
 
75181713.pdf
75181713.pdf75181713.pdf
75181713.pdf
 
'docslide.us_hv-testing.ppt
'docslide.us_hv-testing.ppt'docslide.us_hv-testing.ppt
'docslide.us_hv-testing.ppt
 
megger-150210211712-conversion-gate01.ppt
megger-150210211712-conversion-gate01.pptmegger-150210211712-conversion-gate01.ppt
megger-150210211712-conversion-gate01.ppt
 
Breaker_Failure_Protection.ppt
Breaker_Failure_Protection.pptBreaker_Failure_Protection.ppt
Breaker_Failure_Protection.ppt
 
21955068-High-Low-Impedance-BusBar-Protection.ppt
21955068-High-Low-Impedance-BusBar-Protection.ppt21955068-High-Low-Impedance-BusBar-Protection.ppt
21955068-High-Low-Impedance-BusBar-Protection.ppt
 
basic-partial-discharge.pdf
basic-partial-discharge.pdfbasic-partial-discharge.pdf
basic-partial-discharge.pdf
 
FUNDAMENTALS_OF_BUS_PROTECTION_Handouts.pdf
FUNDAMENTALS_OF_BUS_PROTECTION_Handouts.pdfFUNDAMENTALS_OF_BUS_PROTECTION_Handouts.pdf
FUNDAMENTALS_OF_BUS_PROTECTION_Handouts.pdf
 
High_Low_Impedance_BusBar_Protection.ppt
High_Low_Impedance_BusBar_Protection.pptHigh_Low_Impedance_BusBar_Protection.ppt
High_Low_Impedance_BusBar_Protection.ppt
 
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.pptbasicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
 
11042019104945.pdf
11042019104945.pdf11042019104945.pdf
11042019104945.pdf
 
47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptx47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptx
 
14009762-ABB-Protection-Book.pdf
14009762-ABB-Protection-Book.pdf14009762-ABB-Protection-Book.pdf
14009762-ABB-Protection-Book.pdf
 
ppt100-110425022440-phpapp02.ppt
ppt100-110425022440-phpapp02.pptppt100-110425022440-phpapp02.ppt
ppt100-110425022440-phpapp02.ppt
 
chuong_1.ppt
chuong_1.pptchuong_1.ppt
chuong_1.ppt
 
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.pptbasicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
 
Basic_Protection_Theory_2013_BW.pdf
Basic_Protection_Theory_2013_BW.pdfBasic_Protection_Theory_2013_BW.pdf
Basic_Protection_Theory_2013_BW.pdf
 
17649136-Relays.pdf
17649136-Relays.pdf17649136-Relays.pdf
17649136-Relays.pdf
 
17648889-Introduction-to-Power-System-Protection-Relays.pdf
17648889-Introduction-to-Power-System-Protection-Relays.pdf17648889-Introduction-to-Power-System-Protection-Relays.pdf
17648889-Introduction-to-Power-System-Protection-Relays.pdf
 
pptpdf-131117235616-phpapp02.pdf
pptpdf-131117235616-phpapp02.pdfpptpdf-131117235616-phpapp02.pdf
pptpdf-131117235616-phpapp02.pdf
 

Recently uploaded

Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...RajaP95
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 

Recently uploaded (20)

Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 

protectionsettings-120425102109-phpapp01.ppt

  • 1. ELEC 4302/7311 POWER SYSTEM PROTECTION: PROTECTION SETTINGS BY MOHD MOIZUDDIN 1
  • 2. Contents  Introduction  Functions of Equipment Protection  Functions of Protective Relays  Required Information for Protective Setting  Protection Settings Process  Functional Elements of Protective Relays  Operating Characteristics of Protective Relays  Overcurrent and Directional Protection Elements  Distance Protection Function 2
  • 3. PROTECTION SETTINGS: INTRODUCTION  A power system is composed of a number of sections (equipment) such as generator, transformer, bus bar and transmission line.  These sections are protected by protective relaying systems comprising of instrument transformers (ITs), protective relays, circuit breakers (CBs) and communication equipment.  In case of a fault occurring on a section, its associated protective relays should detect the fault and issue trip signals to open their associated CBs to isolate the faulted section from the rest of the power system, in order to avoid further damage to the power system. 3
  • 4. 4 Below Fig. 1 is an typical example of power system sections with their protection systems. Where: G1 is a generator. T1 is a transformer. B1,...,B5 are bus bars. L45 is a transmission line (TL). RG is a generator protective relay. RT is a transformer protective relay. RB is a bus protective relay. RL-4,...,RL-9 are TL protective relays. C1,..., C9 are CBs. Protection Settings: Introduction Fig. 1 Protection of power system sections
  • 5. PROTECTION SETTINGS: INTRODUCTION  Maximum fault clearance times are usually specified by the regulating bodies and network service providers.  The clearing times are given for local and remote CBs and depend on the voltage level and are determined primarily to meet stability requirements and minimize plant damage.  The maximum clearance times of the backup protection are also specified.  e.g. the clearing times for faults on the lines specified by one network service provider in Australia are presented in Table I (next slide). 5
  • 6. TABLE I: FAULT CLEARANCE TIMES Voltage level [kV] CB operate correctly [ms] CB fail [ms] Local Remote Local Remote 500 80 100 175 175 330 100 120 250 250 275 100 120 250 250 220 120 140 430 430 132 120 160 430 430 110 120 160 430 430 66 120 160 430 430 ≤ 33 1160 - 1500 - 6
  • 7. FUNCTIONS OF EQUIPMENT PROTECTION Protection schemes are generally divided into equipment protection and system protection. The main function of equipment protection is to selectively and rapidly detect and disconnect a fault on the protected circuit to:  ensure optimal power quality to customers;  minimize damage to the primary plant;  prevent damage to healthy equipment that conducts fault current during faults;  restore supply over the remaining healthy network;  sustain stability and integrity of the power system;  limit safety hazard to the power utility personnel and the public. 7
  • 8. FUNCTIONS OF PROTECTIVE RELAYS  The protection functions are considered adequate when the protection relays perform correctly in terms of:  Dependability: The probability of not having a failure to operate under given conditions for a given time interval.  Security: The probability of not having an unwanted operation under given conditions for a given time interval.  Speed of Operation: The clearance of faults in the shortest time is a fundamental requirement (transmission system), but this must be seen in conjunction with the associated cost implications and the performance requirements for a specific application. 8
  • 9. …FUNCTIONS OF PROTECTIVE RELAYS  Selectivity (Discrimination): The ability to detect a fault within a specified zone of a network and to trip the appropriate CB(s) to clear this fault with a minimum disturbance to the rest of that network.  Single failure criterion: A protection design criterion whereby a protection system must not fail to operate even after one component fails to operate. With respect to the protection relay, the single failure criterion caters primarily for a failed or defective relay, and not a failure to operate as a result of a performance deficiency inherent within the design of the relay. 9
  • 10. …FUNCTIONS OF PROTECTIVE RELAYS  The setting of protection relays is not a definite science.  Depending on local conditions and requirements, setting of each protective function has to be optimized to achieve the best balance between reliability, security and speed of operation.  Protection settings should therefore be calculated by protection engineers with vast experience in protective relaying, power system operation and performance and quality of supply. 10
  • 11. REQUIRED INFORMATION FOR PROTECTIVE SETTING Line Parameters:  For a new line: final total line length as well as the lengths, conductor sizes and tower types of each section where different tower types or conductors have been used.  This information is used to calculate the parameters (positive and zero sequence resistance, reactance and susceptance) for each section.  Maximum load current or apparent power (MVA) corresponding to the emergency line which can be obtained from the table of standard conductor rating (available in each utility).  The number of conductors in a bundle has to be taken into consideration. 11
  • 12. …REQUIRED INFORMATION FOR PROTECTIVE SETTING  Transformer Parameters:  The manufacturer's positive and zero sequence impedance test values have to be obtained.  The transformer nameplate normally provides the manufacturer's positive sequence impedance values only.  Terminal Equipment Rating:  The rating of terminal equipment (CB, CT, line trap, links) of the circuit may limit its transfer capability therefore the rating of each device has to be known.  Data can be obtained from the single line diagrams. 12
  • 13. …REQUIRED INFORMATION FOR PROTECTIVE SETTING Fault Studies  Results of fault studies must be provided.  The developed settings should be checked on future cases modelled with the system changes that will take place in the future (e.g. within 5 years).  Use a maximum fault current case. CT & VT Ratios:  Obtain the CT ratios as indicated on the protection diagrams.  For existing circuits, it is possible to verify the ratios indicated on the diagrams by measuring the load currents on site and comparing with a known ratio. 13
  • 14. …REQUIRED INFORMATION FOR PROTECTIVE SETTING  Checking For CT Saturation:  Protection systems are adversely affected by CT saturation. It is the responsibility of protection engineers to establish for which forms of protection and under what conditions the CT should not saturate.  CTs for Transformer Differential Protection:  MV, HV and LV CTs must be matched as far as possible taking into consideration the transformer vector group, tap changer influence and the connection of CTs.  CTs for Transformer Restricted Earth Fault (REF) Protection:  All CT ratios must be the same (as with the bus zone protection), except if the relay can internally correct unmatched ratios. 14
  • 15. PROTECTION SETTINGS PROCESS  The Protection Settings team obtains all the information necessary for correct setting calculations.  The settings are then calculated according to the latest philosophy, using sound engineering principles. Pre-written programs may be used as a guide.  After calculation of the settings, it is important that another competent person checks them.  The persons who calculate and who check the settings both sign the formal settings document.  The flowchart in Fig. 2 indicates information flow during protection setting preparation for commissioning of new Transmission plant. 15
  • 16. 16 Project leader of the Protection Settings team determines scope of work and target dates Summary and comparison of inputs IED manufacturers provide bay specific IED details Engineering team provides bay specific proformas and drawings Corrective actions and re-issue of drawings Study new protection and create necessary setting templates in liaison with engineering team and IED manufactureres OK Not OK Calculation and verification of settings Settings stored in central database and formal document issued Implementation date and responsible field person stored in the central database -> implementation action Implementation sheet completed by field staff and returned to Protection Settings team Interface with the Expansion Planing team and IED manufacturers to obtain relevant equipment parameters for correct system modelling Centralised Settings Management System sends the action documents to the field staff Corrective actions required to ensure implementation Fig. 2 Information flow during protection settings preparation
  • 17. FUNCTIONAL ELEMENTS OF PROTECTIVE RELAYS  To achieve maximum flexibility, relays is designed using the concept of functional elements which include protection elements, control elements, input and output contacts etc.  The protection elements are arranged to detect the system condition, make a decision if the observed variables are over/under the acceptable limit, and take proper action if acceptable limits are crossed.  Protection element measures system quantities such as voltages and currents, and compares these quantities or their combination against a threshold setting (pickup values).  If this comparison indicates that the thresholds are crossed, a decision element is triggered.  This may involve a timing element, to determine if the condition is permanent or temporary. If all checks are satisfied, the relay (action element) operates. 17
  • 18. 18 Fault Pickup of protection element Operation of protection element Assertion of relay trip logic signal Action of relay trip contact Circuit breaker opening Fault cleared Fig. 3 Sequence of operation. Sequence of protection operation initiated by a fault is shown in Fig. 3.
  • 19. OPERATING CHARACTERISTICS OF PROTECTIVE RELAYS  Protective relays respond and operate according to defined operating characteristic and applied settings.  Each type of protective relay has distinctive operating characteristic to achieve implementation objective: sensitivity, selectivity, reliability and adequate speed of operation.  Basic operating characteristics of protective elements is as follows:  Overcurrent protection function: the overcurrent element operates or picks up when its input current exceeds a predetermined value.  Directional function: an element picks up for faults in one direction, and remains stable for faults in the other direction. 19
  • 20. …OPERATING CHARACTERISTICS OF PROTECTIVE RELAYS  Distance protection function: an element used for protection of transmission lines whose response is a function of the measured electrical distance between the relay location and the fault point.  Differential protection function: it senses a difference between incoming and outgoing currents flowing through the protected apparatus.  Communications-Assisted Tripping Schemes: a form of the transmission line protection that uses a communication between distance relays at opposite line ends resulting in selective clearing of all line faults without time delay. 20
  • 21. OVERCURRENT AND DIRECTIONAL PROTECTION ELEMENTS  An overcurrent condition occurs when the maximum continuous load current permissible for a particular piece of equipment is exceeded.  A phase overcurrent protection element continuously monitors the phase current being conducted in the system and issue a trip command to a CB when the measured current exceeds a predefined setting.  The biggest area of concern for over-current protection is how to achieve selectivity.  Some possible solutions have been developed, including monitoring current levels (current grading), introducing time delays (time grading) or combining the two as well as including a directional element to detect the direction of current flow. 21
  • 22. CURRENT GRADING  Current grading will achieve selectivity by determine the location of a fault using purely magnitude of current.  It is difficult to implement this in practice unless feeder sections have sufficient differences in impedance to cause noticeable variations in fault current.  In a network where there are several sections of line connected in series, without significant impedances at their junctions there will be little difference in currents, so discrimination or selectivity cannot be achieved using current grading. 22
  • 23. TIME DELAYS  An alternate means of grading is introducing time delays between subsequent relays.  Time delays are set so that the appropriate relay has sufficient time to open its breaker and clear the fault on its section of line before the relay associated with the adjacent section acts.  Hence, the relay at the remote end is set up to have the shortest time delay and each successive relay back toward the source has an increasingly longer time delay.  This eliminates some of the problems with current grading and achieves a system where the minimum amount of equipment is isolated during a fault.  However, there is one main problem which arises due to the fact that timing is based solely on position, not fault current level.  So, faults nearer to the source, which carry the highest current, will take longer to clear, which is very contradictory and can prove to be quite costly. 23
  • 24. DIRECTIONAL ELEMENTS  Selectivity can be achieved by using directional elements in conjunction with instantaneous or definite-time overcurrent elements.  Directional overcurrent protection schemes respond to faults in only one direction which allows the relay to be set in coordination with other relays downstream from the relay location.  This is explained using example in Fig. 4. 24
  • 25. DIRECTIONAL ELEMENTS  By providing directional elements at the remote ends of this system, which would only operate for fault currents flowing in one direction we can maintain redundancy during a fault.  This is in line with one of the main outcomes of ensuring selectivity, which is to minimize amount of circuitry that is isolated in order to clear a fault. 25 Fig. 4: Use of direction element example
  • 26. DIRECTION OF CURRENT FLOW  In AC systems, it is difficult to determine the direction of current flow and the only way to achieve this is to perform measurements with reference to another alternating quantity, namely voltage. The main principle of how directional elements operate is based on the following equations for torque:  If current is in the forward direction, then the sign of the torque equation will be positive and as soon as the direction of current flow reverses, the sign of the torque equation becomes negative. These calculations are constantly being performed internally inside directional element. 26 ) cos( A BC A BC A I V I V T       ) cos( B CA B CA B I V I V T       ) cos( C AB C AB C I V I V T      
  • 27. DISTANCE PROTECTION FUNCTION  A distance protection element measures the quotient V/I (impedance), considering the phase angle between the voltage V and the current I.  In the event of a fault, sudden changes occur in measured voltage and current, causing a variation in the measured impedance.  The measured impedance is then compared against the set value.  Distance element will trip the relay (a trip command will be issued to the CB associated with the relay) if the measured value of the impedance is less then the value set. 27
  • 28. …DISTANCE PROTECTION FUNCTION  In Fig. 5 the impedance measured at the relay point A is , where x is the distance to the fault (short circuit), and R and L are transmission line parameters in per unit length. The line length is l in the fig.. 28 Fig. 5 Distance protection principle of operation.   in Z R j L x   
  • 29. …DISTANCE PROTECTION FUNCTION  We can see that the impedance value of a fault loop increases from zero for a short circuit at the source end A, up to some finite value at the remote end B. We can use this principle to set up zones of distance protection as well as to provide feedback about where a fault occurred (distance to fault).  Operating characteristics of distance protection elements are usually represented using R-X diagrams.  Fig. 6 shows an example of Mho R-X operating characteristic. The relay is considered to be at the origin. 29
  • 30. …DISTANCE PROTECTION FUNCTION 30 Region of operation Zone 1 Region of non-operation outside the circle Load region R X Zone 2 A B 80% 120% Line P Line Q RS Z Fig. 6 Mho positive-sequence R-X operating characteristic of a distance element.
  • 31. …DISTANCE PROTECTION FUNCTION  The need for zones shown in Fig. 6 arises from the need of selective protection; i.e. the distance element should only trip faulty section.  We can set the distance element to only trigger a trip signal for faults within a certain distance from the relay, which is called the distance element reach.  The setting impedance is represented by , where ZL is the line impedance. The distance element will only trip when the measured impedance ZR is less than or equal to the setting impedance hsZL. 31 RS s L Z h Z 
  • 32. …DISTANCE PROTECTION FUNCTION  Typically hs is set to protect 80% of the line between two buses and this forms protection Zone 1.  Errors in the VTs and CTs, modeled transmission line data, and fault study data do not permit setting Zone 1 for 100% of the transmission line.  If we set Zone 1 for 100% of the transmission line, unwanted tripping could occur for faults just beyond the remote end of the line. 32
  • 33. …DISTANCE PROTECTION FUNCTION  Zone 2 is set to protect 120% of the line, hence making it over-reaching, because it extends into the section of line protected by the relay at point B. To avoid nuisance tripping, any fault occurring in Zone 1 is cleared instantaneously, while faults which occur in Zone 2 are cleared after a time delay in order to allow relay B to clear that fault first.  This provides redundancy in the protection system (backup), whilst maintaining selectivity. 33