International Journal of Power Electronics and Drive System (IJPEDS)
Vol. 12, No. 2, Jun 2021, pp. 772~782
ISSN: 2088-8694, DOI: 10.11591/ijpeds.v12.i2.pp772-782  772
Journal homepage: http://ijpeds.iaescore.com
Detailed analysis of grid connected and islanded operation
modes based on P/U and Q/f droop characteristics
Qusay Salem1
, Khaled Alzaareer2
1
Department of Electrical Engineering, Princess Sumaya University for Technology, Jordan
2
Department of Electrical Engineering, Quebec University, Montreal QuΓ©bec, Canada
Article Info ABSTRACT
Article history:
Received Dec 30, 2020
Revised Apr 7, 2021
Accepted Apr 20, 2021
This paper presents a thorough control structure of the distributed generators
inside the microgrid during both grid-connected and islanded operation
modes. These control structures of the DGs voltage source inverters are
implemented in synchronous reference frame (SRF) and controlled using
linear PI controllers. By implementing the control structures, the desired real
and reactive power can be efficiently transferred to the local loads and the
utility load by the microgrid generating units. A modified droop control
technique is introduced to facilitate the microgrid performance during both
modes of operation. The active and reactive power sharing of the load
demand between the utility grid and the microgrid can be performed by this
droop control technique during the islanded mode. The system performance
during intentional islanding event and utility load increase is investigated.
The effectiveness of the offered control structures is confirmed through
simulation results during both modes of operation.
Keywords:
Distributed generators
Droop control
Grid connected and Islanded
Modes
Microgrid
Voltage source inverter
This is an open access article under the CC BY-SA license.
Corresponding Author:
Qusay Salem
Department of Electrical Engineering
Princess Sumaya University for Technology
Amman, Jordan
Email: q.salem@psut.edu.jo
1. INTRODUCTION
Microgrids are energy networks which have small-scale and low-voltage feature. They are utilized
to guarantee the distribution and generation locally in the autonomous or remote societies [1]. Microgrids can
be interconnected with large power systems through power electronic converters and can even work
autonomously [2], [3]. In the normal operation where the microgrid is connected to the massive grid, DGs
into the power network can track the grid energy flow and operate without control requirment. In the event of
short circuit or planned interruption, the microgrid can be disconnected from the large grid to operate in
autonomous mode where proper control methods are applied in order to ensure stability of power [4], [5].
The autonomous functionality can provide more elacticity to the DGs involvement and bring a more efficient
power supply. However, autonomous microgrids might have powerless condition than conventional massive
grids because of limited capacities of the DGs [6].
The microgrid notion advocates coordinated control where retrieving trustworthy and high-quality
energy can be ensured to customers by DGs cooperation [7]. The controlled voltage source converters-based
power electronic interfaces are utilized widely to connect the DGs to the point of common coupling of the
network. Moreover, two main categories of microgrid control methods are existed which are divided into
either centralized control or decentralized control methods [8]-[10]. A high bandwidth communication link is
employed in centralized control methods to transfer feedback and control signals between the centralized
Int J Pow Elec & Dri Syst ISSN: 2088-8694 
Detailed analysis of grid connected and islanded operation modes based on P/U … (Qusay Salem)
773
controller and the DGs. Centralized controllers are found to be less reliable since system instability might
appear due to any communication interruption beside the communication system higher costs [11]-[14].
That’s why decentralized control methods are considered more feasible as performing the system online
maintenance and achieving self-organizing can be accomplished easily [15], [16]. The methods of
decentralized control employ 𝑃 βˆ’ 𝑓 & 𝑄 βˆ’ 𝐸 droop characteristics to regulate the flow of real and reactive
power in the microgrid. These droop characteristics are based on highly inductive networks where the
decoupling of real and reactive power flow equations can be applied. Slow dynamics and voltage drifts with
load change are some features of these droop characteristics which are compatbile with the network
impedance high 𝑋/𝑅 ratio and large inertia in conventional power systems [17], [18]. However, since line
impedances in microgrids are resistive at most, DGs have small inertia and persistent load variations may
happen. The 𝑋/𝑅 ratio in microgrids is not large like the case in conventional power systems. Consequently,
the active and reactive power flow is dependent on 𝛿 and 𝐸 as they are highly coupled. That’s why the
traditional droop technique which employs decoupled 𝑃 βˆ’ 𝑓 & 𝑄 βˆ’ 𝐸 droops bring out weak performance.
Different controllers have been proposed in this context where [19] introduces a virtual resistance so that the
system acts in a resistive manner where 𝑃 and 𝑄 might be regulated by respectively drooping 𝐸 and 𝑓. [20]
and [21] have introduced a virtual reactance and a virtual PQ method, respectively to mimic the inductive
system by increasing the 𝑋/𝑅 ratio. The 𝑃 βˆ’ 𝑓 & 𝑄 βˆ’ 𝐸 droop scheme has the disadvantage of exhibiting
power quality problems in terms of frequency and voltage deviations. Replacing the 𝑃 βˆ’ 𝑓 droop by 𝑃 βˆ’ 𝛿
droop can eliminate the frequency deviations problem where a global positioning system is introduced to
synchronize the DG units [22]. E. Rokrok and M. Golshan [23] have introduced an adaptive voltage droop
method for improving the regulation of voltage at PCC and mitigating the coupling between 𝑃 and 𝑄 droop
controllers. In [24], synchronizing the global frequency to a nominal value with better disturbance rejection
properties has been realized by considering a finite-time control protocol for frequency restoration, based on
feedback linearization. DG self-frequency restoration control has corrected the frequency deviation by droop
compensation without the need of utilizing a secondary controller [25]. However, resistive line impedance in
low voltage microgrids causes power coupling in 𝑃 βˆ’ 𝑓 droop control which hasn’t been considered and was
only applied to high or medium voltage networks.
The current communication-less microgrid control methods have utilized 𝑃 βˆ’ 𝑓 & 𝑄 βˆ’ 𝐸 droop
characteristics. An alternative approach is proposed in this paper where a 𝑃 βˆ’ π‘ˆ and 𝑄 βˆ’ 𝑓 droop control
technique is proposed for a microgrid connected to the utility or main grid. The control structures that are
implemented to execute the grid-connected and islanded operations of DGs are investigated. An intentional
islanding condition is performed to investigate the performance of the microgrid control structures.
Moreover, a step change in the utility load has been proposed to prove the control structures performance.
The proposed control strategies can control the voltage and power of the DGs in addition to sharing the load
demand during all modes of operation. The main contribution of this work is accomplished by considering
the abovementioned issues.
The organization of the paper is divided into five sections. At first is the introduction, then section 2
presents the general schematic diagram of the proposed microgrid model. The real and reactive power
generation in relation to the proposed droop control methodology is introduced in section 3. Section 4 shows
the simulation results which are performed to confirm the applicability and efficiency of the proposed control
structures. Finally, section 5 presents the conclusion of the proposed work.
2. THE PROPOSED NETWORK DESCRIPTION
Figure 1 shows a single-line diagram of the proposed microgrid model which can operate in grid
connected and islanded modes. All the distributed generators are supposed to inject the required active and
reactive power to support their own loads and the utility load then the remnant of power moves out to the
main utility grid. A circuit breaker is placed in the system either to maintain the microgrid online with the
main grid or to isolate the faulty sections from the microgrid in case of short circuits. A utility load is
connected directly to the point of common coupling (PCC) to be supported by real and reactive power in both
modes of operation.
2.1. Modeling and control of grid-connected DC/AC voltage source inverter
Variables in synchronous reference frame (SRF) are used for the control of grid connected inverters
in which they described as DC quantities. Figure 2 depicts the circuit diagram of the three-phase voltage
source inverter connected to the grid. π‘ˆπ‘Ž, π‘ˆπ‘, π‘ˆπ‘ are the inverter output voltages, πΈπ‘Ž, 𝐸𝑏, 𝐸𝑐 are the output
voltages of the grid. The inductance of the inverter is denoted by 𝐿𝑖 and 𝐿𝑔 is the inductance of the
grid. π‘–π‘Ž, 𝑖𝑏, 𝑖𝑐 are the injected currents in the main grid.
The equation of the diagram depicted in Figure 2 is formulated differentially as:
 ISSN: 2088-8694
Int J Pow Elec & Dri Syst, Vol. 12, No. 2, June 2021 : 772 – 782
774
𝐿[
𝑑𝑖
𝑑𝑑
]π‘Žπ‘π‘ = [π‘ˆ]π‘Žπ‘π‘ βˆ’ [𝐸]π‘Žπ‘π‘ βˆ’ 𝑅[𝑖]π‘Žπ‘π‘ (1)
Where, the total inductance of the inverter is denoted by 𝐿, which means 𝐿 = 𝐿𝑖 + 𝐿𝑔. If πœ” = 2πœ‹π‘“, where πœ”
is the frequency of the grid, then (1) can be formulated in synchronous reference frame as:
π‘ˆπ‘‘π‘ž,π‘Ÿπ‘’π‘“ = 𝐿
π‘‘π‘–π‘‘π‘ž
𝑑𝑑
+ (𝑅 + π‘—πœ”πΏ)π‘–π‘‘π‘ž + π‘ˆπ‘‘π‘ž (2)
Figure 1. The proposed microgrid model
Figure 2. Three phase DC/AC voltage source converter connected to grid
Then the real part and the imaginary part of (2) can be written as:
π‘ˆπ‘‘,π‘Ÿπ‘’π‘“ = 𝐿
𝑑𝑖𝑑
𝑑𝑑
+ 𝑅𝑖𝑑 βˆ’ πœ”πΏπ‘–π‘ž + π‘ˆπ‘‘ (3)
π‘ˆπ‘ž,π‘Ÿπ‘’π‘“ = 𝐿
π‘‘π‘–π‘ž
𝑑𝑑
+ π‘…π‘–π‘ž + πœ”πΏπ‘–π‘‘ + π‘ˆπ‘ž (4)
Depending on (3) and (4) the arrangement of the grid connected voltage source inverter current control in dq-
reference frame is illustrated as shown in Figure 3. Where, 𝑖𝑑,π‘Ÿπ‘’π‘“, π‘–π‘ž,π‘Ÿπ‘’π‘“ are the dq reference currents. A PLL
is used for tracking the phase angle of the grid to be synchronized with DGs. PI controllers are used to
compensate the voltage drop caused by the line impedance.
Int J Pow Elec & Dri Syst ISSN: 2088-8694 
Detailed analysis of grid connected and islanded operation modes based on P/U … (Qusay Salem)
775
Figure 3. Block diagram of VSI current control
The control equations for π‘ˆπ‘‘,π‘Ÿπ‘’π‘“ and π‘ˆπ‘ž,π‘Ÿπ‘’π‘“ are as the following:
π‘ˆπ‘‘,π‘Ÿπ‘’π‘“ = π‘ˆπ‘‘ βˆ’ πœ”πΏπ‘–π‘ž + (π‘˜π‘ +
π‘˜π‘–
𝑠
) (𝑖𝑑,π‘Ÿπ‘’π‘“ βˆ’ 𝑖𝑑) (5)
π‘ˆπ‘ž,π‘Ÿπ‘’π‘“ = π‘ˆπ‘ž βˆ’ πœ”πΏπ‘–π‘‘ + (π‘˜π‘ +
π‘˜π‘–
𝑠
) (π‘–π‘ž,π‘Ÿπ‘’π‘“ βˆ’ π‘–π‘ž) (6)
Hence, the formulas of active and reactive power are written in synchronous reference frame as:
𝑃 =
3
2
(π‘ˆπ‘‘,π‘Ÿπ‘’π‘“ 𝑖𝑑 + π‘ˆπ‘ž,π‘Ÿπ‘’π‘“ π‘–π‘ž) (7)
𝑄 =
3
2
(π‘ˆπ‘‘,π‘Ÿπ‘’π‘“ π‘–π‘ž βˆ’ π‘ˆπ‘ž,π‘Ÿπ‘’π‘“ 𝑖𝑑) (8)
It can be seen from (7) and (8) that a mutual coupled voltage exists between the d and q axis quantities.
However, this coupling will not cause independent control of P and Q. In other words, if the delivered real
power changes, the reactive power will change accordingly. The elimination of this mutual coupling is
achieved by considering π‘ˆπ‘ž,π‘Ÿπ‘’π‘“ = 0. Hence, the modified real and reactive power can be written as:
𝑃 =
3
2
π‘ˆπ‘‘,π‘Ÿπ‘’π‘“ 𝑖𝑑 (9)
𝑄 =
3
2
π‘ˆπ‘‘,π‘Ÿπ‘’π‘“ π‘–π‘ž (10)
Consequently, the d-axis current monitors directly the active power and the q-axis current monitors the
reactive power.
2.2. Control of DC/AC voltage source inverter in islanded mode
Once the main utility grid is seperated from the microgrid, every DG inside the microgrid will lose
stability in terms of very high values of current or voltage transients. In island mode, the grid feeding power
converters can not work unless if a grid forming or grid supporting power converter is existed so that the
voltage amplitude and frequency of the ac microgrid can be adjusted [26]. In this paper, a power converter
which is grid forming one is activated at PCC when the microgrid becomes islanded. The circuit diagram of
the grid forming power converter in islanded mode is depicted in Figure 4.
The reference values of the frequency and voltage is determined by a reference sinewave generator.
This is because the microgrid has no physical connection with the main grid. Thus, the DG reference voltage
in islanded mode is extracted as:
 ISSN: 2088-8694
Int J Pow Elec & Dri Syst, Vol. 12, No. 2, June 2021 : 772 – 782
776
{
π‘ˆπ‘Ž = 𝐸 sin (πœ”π‘‘)
π‘ˆπ‘ = 𝐸 sin (πœ”π‘‘ βˆ’
2πœ‹
3
)
π‘ˆπ‘ = 𝐸 sin (πœ”π‘‘ +
2πœ‹
3
)
} (11)
Figure 4. Circuit diagram of grid forming power converter in islanded mode
The voltage and current control circuit for the grid forming power converter in islanded mode is
shown in Figure 5. In the islanded mode, the existing control acts as voltage control through compensation of
current. The control unit employs voltage regulators to extract the desired current references. After that, using
proper PI controllers, π‘ˆπ‘‘ and π‘ˆπ‘ž will successfully track their references. The output current references
𝑖𝑑,π‘Ÿπ‘’π‘“ and π‘–π‘ž,π‘Ÿπ‘’π‘“ are compared with 𝑖𝑑 and π‘–π‘ž, and the difference is inserted to another PI controller. Finally,
the resultant output of the current loop performs as a voltage reference signal which is delivered to the gating
signals of the three-phase power converter.
3. REAL AND REACTIVE POWER BASED ON DROOP CONTROL TECHNIQUE
Giving consideration to the converter as a voltage source which is controllable and taking into
account that the converter is attached to the main grid via a line impedance as illustrated in Figure 6 (a), then
the transmitted real and reactive power to the main grid can be formulated as:
𝑃𝐴 =
π‘ˆπ΄
𝑅2+𝑋2
[𝑅(π‘ˆπ΄ βˆ’ π‘ˆπ‘ π‘π‘œπ‘ π›Ώ) + π‘‹π‘ˆπ΅π‘ π‘–π‘›π›Ώ] (12)
𝑄𝐴 =
π‘ˆπ΄
𝑅2+𝑋2
[βˆ’π‘…(π‘ˆπ΅ 𝑠𝑖𝑛𝛿) + 𝑋(π‘ˆπ΄ βˆ’ π‘ˆπ΅π‘π‘œπ‘ π›Ώ)] (13)
Where, the real and reactive power passing to the grid from the power converter are denoted by 𝑃𝐴
and 𝑄𝐴, the voltages of the two power converters are denoted by π‘ˆπ΄, π‘ˆπ‘, the phase angle difference between
both converter voltages is denoted by 𝛿, the line impedance is denoted by 𝑍 = 𝑅 + 𝑗𝑋 and the impedance
angle is denoted by πœ‘. Thus, as 𝑅 = 𝑍. π‘π‘œπ‘ πœ‘ and 𝑋 = 𝑍. π‘ π‘–π‘›πœ‘, the vector representation of the given model
can be represented in Figure 6 (b).
Int J Pow Elec & Dri Syst ISSN: 2088-8694 
Detailed analysis of grid connected and islanded operation modes based on P/U … (Qusay Salem)
777
Figure 5. Voltage and current control of the power converter in the islanded mode
(a) (b)
Figure 6. Modelling of power converter connected to the distribution network, (a) equivalent circuit
(b) phasor diagram
In low-voltage networks, the impedance of the grid is principally resistive and thus the inductive
part can approximately be neglected. If we assume a small value of the phase angle 𝛿, then (12) and (13) can
be rewritten as:
𝑃𝐴 =
π‘ˆπ΄
𝑅
(π‘ˆπ΄ βˆ’ π‘ˆπ΅π‘π‘œπ‘ π›Ώ) =≫ π‘ˆπ΄ βˆ’ π‘ˆπ΅ β‰ˆ
𝑅𝑃𝐴
π‘ˆπ΄
(14)
𝑄𝐴 = βˆ’
π‘ˆπ΄.π‘ˆπ΅
𝑅
𝑠𝑖𝑛𝛿 =≫ 𝛿 = βˆ’
𝑅𝑄𝐴
π‘ˆπ΄π‘ˆπ΅
(15)
Based on the previous two equations, it can be noticed that the voltage magnitude in low-voltage
distribution networks and the real power are dependent to each other. Also, the reactive power and the
frequency are influenced by each other. From (14) and (15), the expressions of the droop control are
demonstrated as:
π‘ˆ βˆ’ π‘ˆπ‘œ = βˆ’π‘˜π‘(𝑃 βˆ’ π‘ƒπ‘œ) (16)
𝑓 βˆ’ π‘“π‘œ = π‘˜π‘ž(𝑄 βˆ’ π‘„π‘œ) (17)
The characteristics of the proposed droop control are illustrated in Figure 7. The characteristics
demonstrate that the voltage magnitude and the active power are mainly dependent. On the other hand, it is
clear that the frequency and the reactive power are also dependent on each other.
 ISSN: 2088-8694
Int J Pow Elec & Dri Syst, Vol. 12, No. 2, June 2021 : 772 – 782
778
Figure 7. P/U and Q/f droop control characteristics
4. DISCUSSION OF SIMULATION RESULTS
Realization and robustness of the proposed droop control strategies in the microgrid model have
been assessed in steady state and transient operating conditions employing β€˜SimPowerSystems’ library
toolbox in Matlab/Simulink. The parameters of the single line diagram shown in Figure 1 are given in Table
1. Two scenarios have been evaluated through simulations to examine the system behavior. The first scenario
is when an intentional islanding condition takes place. The other scenario is when the utility load increases
during the islanding period. The significance and novel aspects of the results are obvious by the operation of
the proposed droop control technique where the DGs share the real power to fulfill the total load demand for
both scenarios. Moreover, the obtained results reflect the stability and solidity of the DG VSI control strategy
during both grid-connected and islanded operation modes.
Table 1. Parameters of the proposed model
Grid π‘‰π‘Ÿπ‘šπ‘  = 230 𝑉, 𝑓 = 50 𝐻𝑧
DG 1 𝑃 = 12 π‘˜π‘€, 𝑄 = 4 π‘˜π‘£π‘Žπ‘Ÿ
DG 2 𝑃 = 14 π‘˜π‘€, 𝑄 = 6 π‘˜π‘£π‘Žπ‘Ÿ
DG 3 𝑃 = 16 π‘˜π‘€, 𝑄 = 8 π‘˜π‘£π‘Žπ‘Ÿ
DG 4 𝑃 = 18 π‘˜π‘€, 𝑄 = 10 π‘˜π‘£π‘Žπ‘Ÿ
Utility Load 𝑃 = 30 π‘˜π‘€, 𝑄 = 5 π‘˜π‘£π‘Žπ‘Ÿ
DGs Loads 𝑃 = 5 π‘˜π‘€, 𝑄 = 0 π‘˜π‘£π‘Žπ‘Ÿ
Line impedance 𝑅 = 0.5 𝛺, 𝐿 = 0.8 π‘šπ»
4.1. Intentional islanding scenario
The microgrid is assumed to work in grid-connected mode at (0 ≀ 𝑑 ≀ 1) and then disconnected
from the utility following an intentional islanding condition at PCC which is proposed at 𝑑 = 1𝑠 and lasts for
1000π‘šπ‘  (1 ≀ 𝑑 ≀ 2). After that the system regains its operation to relate to the main grid at (2 ≀ 𝑑 ≀
3). Figure 8 (a)-(d) depicts the microgrid performance concerning the real power, reactive power, rms
voltage and frequency while subfigures (e)-(h) depict the grid performance in terms of real power, rms
voltage, current and frequency.
It is noticed from the results that the proposed droop control strategies are functioning effectively
during grid-connected and islanded modes. Furthermore, it can be noticed that when islanding occurs, the
DGs share the real power to fulfill the total load demand since the power supply of the main grid is lost. As a
result, the rms voltage of the DGs inverters is increased based on the droop characteristics. The reactive
power and frequency of DGs inverters show a little transient at the time of islanding and reconnection due to
the circuit breaker operation. At the grid side, it can be noticed that the system is completely islanded at
(1 ≀ 𝑑 ≀ 2) as the grid real power and current reach zeros. In addition, it is also noticed that a small
fluctuation on grid frequency is existed at the time of islanding and reconnection conditions. Every DG in the
microgrid is equipped with identical droop characteristic is applied for where the DGs real power are shared
equally to satisfy the local loads and the utility load during the islanding period (1 ≀ 𝑑 ≀ 2).
Int J Pow Elec & Dri Syst ISSN: 2088-8694 
Detailed analysis of grid connected and islanded operation modes based on P/U … (Qusay Salem)
779
Figure 8. Microgrid and grid performance during intentional islanding scenario
4.2. Utility load increase scenario
Figure 9 (a)-(d) shows the behavior of the microgrid when the utility load increases. The utility load
has been increased from 30π‘˜π‘€ to 50 π‘˜π‘€ in order to investigate the performance of real and reactive power
sharing between the grid and microgrid especially when the system is islanded. It is clearly shown that the
real power of DGs inverters in islanding mode have increased to compensate the shortage of generation from
the main grid in order to support the demand of utility load. Again, identical droop characteristics are applied
 ISSN: 2088-8694
Int J Pow Elec & Dri Syst, Vol. 12, No. 2, June 2021 : 772 – 782
780
for each DG to satisfy the increase in the utility load during the islanding period. This was done by sharing
the real power of all DGs such that the utility load increase is divided on the four DGs equally.
Consequently, the DGs rms voltage has decreased based on the droop characteristics. The reactive
power and frequency of DGs remain as before with a little transient at the time of islanding and reconnection.
However, it can be seen from subfigures (e)-(h) that the main grid real power and current approaches zero as
a result of the islanding condition while the voltage and frequency remain within their permissible limits
during both grid connected and islanded modes.
Figure 9. Microgrid and grid performance during utility load increase scenario
Int J Pow Elec & Dri Syst ISSN: 2088-8694 
Detailed analysis of grid connected and islanded operation modes based on P/U … (Qusay Salem)
781
5. CONCLUSION
The system efficacy and behavior of the proposed droop control have been investigated during both
grid-connected and islanded modes by proposing an intentional islanding condition at PCC and by increasing
of the utility load. Two control interfaces are employed to design the control strategies, the first one
represents the grid connected mode and the other one represents the islanded mode. The simulation results
confirmed that the response of the proposed control strategies and the droop control can maintain the system
parameters within acceptable limits during both modes of operation. The addition of anti-islanding
algorithms or techniques to the control units of the microgrid is a proper path of the future work.
REFERENCES
[1] C.-S. Karavas, G. Kyriakarakos, K. Arvanitis and G. Papadakis, β€œA multi-agent decentralized energy management
system based on distributed intelligence for the design and control of autonomous polygeneration microgrids,”
Energy Conversion and Management , vol. 103, pp. 166-179, 2015, DOI: 10.1016/j.enconman.2015.06.021.
[2] J. Li, Y. Liu and L. Wu, β€œOptimal Operation for Community-Based Multi-Party Microgrid in Grid-Connected and
Islanded Modes,” IEEE Transactions on Smart Grid, vol. 9, no. 2, pp. 756-765, 2018, doi:
10.1109/TSG.2016.2564645.
[3] H. Ali, A. Hussain, V. Bui and H. Kim, β€œConsensus Algorithm-Based Distributed Operation of Microgrids During
Grid-Connected and Islanded Modes,” IEEE Access, vol. 8, pp. 78151-78165, 2020, DOI:
10.1109/ACCESS.2020.2989457.
[4] C. Dou, Z. Zhang, D. Yue and H. Gao, β€œAn Improved Droop Control Strategy Based on Changeable Reference in
Low-Voltage Microgrids,” Energies , vol. 10, pp. 1-18, 2017, DOI: 10.3390/en10081080.
[5] Q. Salem, L. Liu and J. Xie, β€œDual Operation Mode of a Transformerless H-Bridge Inverter in Low-Voltage
Microgrid,” IEEE Transactions on Industry Applications, vol. 55, no. 5, pp. 5289-5299, 2019, DOI:
10.1109/TIA.2019.2917807.
[6] X. Wang, F. Blaabjerg and Z. Chen, β€œAutonomous Control of Inverter-Interfaced Distributed Generation Units for
Harmonic Current Filtering and Resonance Damping in an Islanded Microgrid,” IEEE Transactions on Industry
Applications, vol. 50, no. 1, pp. 452 - 461, 2014, DOI: 10.1109/TIA.2013.2268734.
[7] M. S. Golsorkhi and D. D. C. Lu, β€œA Control Method for Inverter-Based Islanded Microgrids Based on V-I Droop
Characteristics,” IEEE Transactions on Power Delivery, vol. 30, no. 3, pp. 1196-1204, 2015, DOI:
10.1109/TPWRD.2014.2357471.
[8] E. Espina, J. Llanos, C. Burgos-Mellado, R. CΓ‘rdenas-Dobson, M. MartΓ­nez-GΓ³mez and D. SΓ‘ez, β€œDistributed
Control Strategies for Microgrids: An Overview,” IEEE Access, vol. 8, pp. 193412-193448, 2020, DOI:
10.1109/ACCESS.2020.3032378.
[9] Q. Salem and J. Xie, β€œDecentralized power control management with series transformerless H-bridge inverter in
low-voltage smart microgrid based P/V droop control,” International Journal of Electrical Power & Energy
Systems, vol. 99, pp. 500-515, 2018, DOI: 10.1016/j.ijepes.2018.01.047.
[10] Q. Salem and K. Alzaareer, β€œFault ride-through capability with mutual inductance in low-voltage single-phase
microgrid,” IETE Journal of Research, 2020, DOI: 10.1080/03772063.2020.1800524.
[11] Y. K. e. al, β€œOn the Secondary Control Architectures of AC Microgrids: An Overview," in IEEE Transactions on
Power Electronics,” IEEE Transactions on Power Electronics, vol. 35, no. 6, pp. 6482-6500, 2020.
[12] Q. Xu, J. Xiao, P. Wang and C. Wen, β€œA Decentralized Control Strategy for Economic Operation of Autonomous
AC, DC, and Hybrid AC/DC Microgrids,” IEEE Transactions on Energy Conversion, vol. 32, no. 4, pp. 1345-
1355, 2017, DOI: 10.1109/TEC.2017.2696979.
[13] J. Wang, C. Jin and P. Wang, β€œA Uniform Control Strategy for the Interlinking Converter in Hierarchical
Controlled Hybrid AC/DC Microgrids,” IEEE Transactions on Industrial Electronics, vol. 65, no. 8, pp. 6188-
6197, 2018, DOI: 10.1109/TIE.2017.2784349.
[14] S. Ansari, A. Chandel and M. Tariq, β€œA Comprehensive Review on Power Converters Control and Control
Strategies of AC/DC Microgrid,” IEEE Access, vol. 9, pp. 17998-18015, 2021, DOI:
10.1109/ACCESS.2020.3020035.
[15] I. U. Nutkani, P. C. Loh, P. Wang and F. Blaabjerg, β€œDecentralized Economic Dispatch Scheme With Online
Power Reserve for Microgrids,” IEEE Transactions on Smart Grid, vol. 8, no. 1, pp. 139-148, 2017, DOI:
10.1109/TSG.2015.2451133.
[16] A. Vaccaro, V. Loia, G. Formato, P. Wall and . V. Terzija, β€œA Self-Organizing Architecture for Decentralized
Smart Microgrids Synchronization, Control, and Monitoring,” IEEE Transactions on Industrial Informatics, vol.
11, no. 1, pp. 289-298, 2015, DOI: 10.1109/TII.2014.2342876.
[17] M. A. Awal, H. Yu, H. Tu, S. M. Lukic and I. Husain, β€œHierarchical Control for Virtual Oscillator Based Grid-
Connected and Islanded Microgrids,” IEEE Transactions on Power Electronics, vol. 35, no. 1, pp. 988-1001, 2020,
DOI: 10.1109/TPEL.2019.2912152.
[18] M. Naderi, Y. Khayat, Q. Shafiee, T. Dragicevic, H. Bevrani and F. Blaabjerg, β€œInterconnected Autonomous AC
Microgrids via Back-to-Back Convertersβ€”Part I: Small-Signal Modeling,” IEEE Transactions on Power
Electronics, vol. 35, no. 5, pp. 4728-4740, 2020, DOI: 10.1109/TPEL.2019.2943996.
[19] J. M. Guerrero, J. Matas, L. G. d. Vicuna, M. Castilla and J. Miret, β€œDecentralized Control for Parallel Operation of
Distributed Generation Inverters Using Resistive Output Impedance,” IEEE Transactions on Industrial Electronics,
vol. 54, no. 2, pp. 994-1004, 2007, DOI: 10.1109/TIE.2007.892621.
 ISSN: 2088-8694
Int J Pow Elec & Dri Syst, Vol. 12, No. 2, June 2021 : 772 – 782
782
[20] Y. C. C. Wong, C. S. Lim, M. D. Rotaru, A. Cruden and X. Kong, β€œConsensus Virtual Output Impedance Control
Based on the Novel Droop Equivalent Impedance Concept for a Multi-Bus Radial Microgrid,” IEEE Transactions
on Energy Conversion, vol. 35, no. 2, pp. 1078-1087, 2020, DOI: 10.1109/TEC.2020.2972002.
[21] M. Naderi, Q. Shafiee, F. Blaabjerg and H. Bevrani, β€œLow-Frequency Small-Signal Modeling of Interconnected AC
Microgrids,” IEEE Transactions on Power Systems, 2020, DOI: 10.1109/TPWRS.2020.3040804.
[22] R. Majumder, A. Ghosh, G. Ledwich and F. Zare, β€œAngle droop versus frequency droop in a voltage source
converter based autonomous microgrid,” in 2009 IEEE Power & Energy Society General Meeting, 2009, pp. 1-8,
DOI: 10.1109/PES.2009.5275987.
[23] E. Rokrok and M. Golshan, β€œAdaptive voltage droop scheme for voltage source converters in an islanded multibus
microgrid,” IET Generation, Transmission & Distribution, vol. 4, no. 5, pp. 562-578, 2010, DOI: 10.1049/iet-
gtd.2009.0146.
[24] S. Zuo, A. Davoudi, Y. Song and F. L. Lewis, β€œDistributed Finite-Time Voltage and Frequency Restoration in
Islanded AC Microgrids,” IEEE Transactions on Industrial Electronics, vol. 63, no. 10, pp. 5988-5997, 2016, DOI:
10.1109/TIE.2016.2577542.
[25] Y.-S. Kim, E.-S. Kim and S.-I. Moon, β€œDistributed Generation Control Method for Active Power Sharing and Self-
Frequency Recovery in an Islanded Microgrid,” IEEE Transactions on Power Systems, vol. 32, no. 1, pp. 544-551,
2017, DOI: 10.1109/TPWRS.2016.2543231.
[26] J. Chen, F. Milano and T. O'Donnell, β€œAssessment of Grid-Feeding Converter Voltage Stability,” IEEE
Transactions on Power Systems, vol. 34, no. 5, pp. 3980-3982, 2019, DOI: 10.1109/TPWRS.2019.2920516.
BIOGRAPHIES OF AUTHORS
Qusay Salem has been awarded the PhD degree in Electrical Power and Energy Engineering
from University of Ulm – Germany, in 2020. He received the B.Sc. and M.Sc. Degree both in
Electrical Power Engineering from University of Mutah and Yarmouk University – Jordan, in
2009 and 2013, respectively. Currently, he serves as an Assistant Professor with the
Department of Electrical Engineering at Princess Sumaya University for Technology. His
research interests include power control and energy management in low-voltage smart
microgrids, Islanding detection schemes, Series power flow controllers.
Khaled Alzaareer received the PhD degree in Electrical Engineering/ Power Systems from
Quebec University (ETS), Montreal, QC, Canada in Dec. 2020. He also received the
bachelor’s and master’s degrees in electrical power engineering from Yarmouk University,
Irbid, Jordan, in 2010 and 2012, respectively. His research interests are smart grid, sensitivity
analysis, renewable energy integration, voltage stability and control.

More Related Content

What's hot

Control of Two Stage PV Power System under the Unbalanced Three Phase Grid Vo...
Control of Two Stage PV Power System under the Unbalanced Three Phase Grid Vo...Control of Two Stage PV Power System under the Unbalanced Three Phase Grid Vo...
Control of Two Stage PV Power System under the Unbalanced Three Phase Grid Vo...ijtsrd
Β 
Intelligent Power Management of Islanded DC Microgrid based on Droop Fuzzy Co...
Intelligent Power Management of Islanded DC Microgrid based on Droop Fuzzy Co...Intelligent Power Management of Islanded DC Microgrid based on Droop Fuzzy Co...
Intelligent Power Management of Islanded DC Microgrid based on Droop Fuzzy Co...AI Publications
Β 
IRJET- The Study of Various Control Techniques and Configurations for Grid Co...
IRJET- The Study of Various Control Techniques and Configurations for Grid Co...IRJET- The Study of Various Control Techniques and Configurations for Grid Co...
IRJET- The Study of Various Control Techniques and Configurations for Grid Co...IRJET Journal
Β 
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultsComparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultselelijjournal
Β 
A CONTROL APPROACH FOR GRID INTERFACING INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
A CONTROL APPROACH FOR GRID INTERFACING  INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...A CONTROL APPROACH FOR GRID INTERFACING  INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
A CONTROL APPROACH FOR GRID INTERFACING INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...IJMER
Β 
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...IAES-IJPEDS
Β 
Decentralized cooperative control strategy of microsources for stabilizing au...
Decentralized cooperative control strategy of microsources for stabilizing au...Decentralized cooperative control strategy of microsources for stabilizing au...
Decentralized cooperative control strategy of microsources for stabilizing au...Jamerson Ramos
Β 
The transient stability analysis of wind turbines interconected to grid under...
The transient stability analysis of wind turbines interconected to grid under...The transient stability analysis of wind turbines interconected to grid under...
The transient stability analysis of wind turbines interconected to grid under...IJECEIAES
Β 
Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...
Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...
Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...IJMTST Journal
Β 
Ijmer 46061528
Ijmer 46061528Ijmer 46061528
Ijmer 46061528IJMER
Β 
Optimal parameters of inverter-based microgrid to improve transient response
Optimal parameters of inverter-based microgrid to improve transient response Optimal parameters of inverter-based microgrid to improve transient response
Optimal parameters of inverter-based microgrid to improve transient response IJECEIAES
Β 
IRJET- Series Voltage Regulator for Radial DC – Microgrid
IRJET- Series Voltage Regulator for Radial DC – MicrogridIRJET- Series Voltage Regulator for Radial DC – Microgrid
IRJET- Series Voltage Regulator for Radial DC – MicrogridIRJET Journal
Β 

What's hot (18)

Droop control approach for power sharing in AC microgrid
Droop control approach for power sharing in AC microgrid Droop control approach for power sharing in AC microgrid
Droop control approach for power sharing in AC microgrid
Β 
Control of Two Stage PV Power System under the Unbalanced Three Phase Grid Vo...
Control of Two Stage PV Power System under the Unbalanced Three Phase Grid Vo...Control of Two Stage PV Power System under the Unbalanced Three Phase Grid Vo...
Control of Two Stage PV Power System under the Unbalanced Three Phase Grid Vo...
Β 
Intelligent Power Management of Islanded DC Microgrid based on Droop Fuzzy Co...
Intelligent Power Management of Islanded DC Microgrid based on Droop Fuzzy Co...Intelligent Power Management of Islanded DC Microgrid based on Droop Fuzzy Co...
Intelligent Power Management of Islanded DC Microgrid based on Droop Fuzzy Co...
Β 
IRJET- The Study of Various Control Techniques and Configurations for Grid Co...
IRJET- The Study of Various Control Techniques and Configurations for Grid Co...IRJET- The Study of Various Control Techniques and Configurations for Grid Co...
IRJET- The Study of Various Control Techniques and Configurations for Grid Co...
Β 
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultsComparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Β 
Power System Restoration
Power System RestorationPower System Restoration
Power System Restoration
Β 
Droop control technique for equal power sharing in islanded microgrid
Droop control technique for equal power sharing in islanded microgridDroop control technique for equal power sharing in islanded microgrid
Droop control technique for equal power sharing in islanded microgrid
Β 
ISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEM
ISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEMISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEM
ISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEM
Β 
A CONTROL APPROACH FOR GRID INTERFACING INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
A CONTROL APPROACH FOR GRID INTERFACING  INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...A CONTROL APPROACH FOR GRID INTERFACING  INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
A CONTROL APPROACH FOR GRID INTERFACING INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
Β 
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Β 
Decentralized cooperative control strategy of microsources for stabilizing au...
Decentralized cooperative control strategy of microsources for stabilizing au...Decentralized cooperative control strategy of microsources for stabilizing au...
Decentralized cooperative control strategy of microsources for stabilizing au...
Β 
The transient stability analysis of wind turbines interconected to grid under...
The transient stability analysis of wind turbines interconected to grid under...The transient stability analysis of wind turbines interconected to grid under...
The transient stability analysis of wind turbines interconected to grid under...
Β 
Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...
Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...
Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...
Β 
Ijmer 46061528
Ijmer 46061528Ijmer 46061528
Ijmer 46061528
Β 
Optimal parameters of inverter-based microgrid to improve transient response
Optimal parameters of inverter-based microgrid to improve transient response Optimal parameters of inverter-based microgrid to improve transient response
Optimal parameters of inverter-based microgrid to improve transient response
Β 
Load modelling in distributed generation planning
Load modelling in distributed generation planningLoad modelling in distributed generation planning
Load modelling in distributed generation planning
Β 
Asymmetrical four-wire cascaded h-bridge multi-level inverter based shunt act...
Asymmetrical four-wire cascaded h-bridge multi-level inverter based shunt act...Asymmetrical four-wire cascaded h-bridge multi-level inverter based shunt act...
Asymmetrical four-wire cascaded h-bridge multi-level inverter based shunt act...
Β 
IRJET- Series Voltage Regulator for Radial DC – Microgrid
IRJET- Series Voltage Regulator for Radial DC – MicrogridIRJET- Series Voltage Regulator for Radial DC – Microgrid
IRJET- Series Voltage Regulator for Radial DC – Microgrid
Β 

Similar to Detailed analysis of grid connected and islanded operation modes based on P/U and Q/f droop characteristics

Enhanced dynamic performance of grid feeding distributed generation under va...
Enhanced dynamic performance of grid feeding distributed  generation under va...Enhanced dynamic performance of grid feeding distributed  generation under va...
Enhanced dynamic performance of grid feeding distributed generation under va...IJECEIAES
Β 
Control strategies for seamless transfer between the grid-connected and isla...
Control strategies for seamless transfer between  the grid-connected and isla...Control strategies for seamless transfer between  the grid-connected and isla...
Control strategies for seamless transfer between the grid-connected and isla...IJECEIAES
Β 
A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...
A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...
A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...IJERD Editor
Β 
Design and Implementation of Fuzzy logic based Multilevel Inverter for Micro ...
Design and Implementation of Fuzzy logic based Multilevel Inverter for Micro ...Design and Implementation of Fuzzy logic based Multilevel Inverter for Micro ...
Design and Implementation of Fuzzy logic based Multilevel Inverter for Micro ...IRJET Journal
Β 
Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...
Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...
Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...IRJET Journal
Β 
Reactive power sharing in microgrid using virtual voltage
Reactive power sharing in microgrid using virtual voltage Reactive power sharing in microgrid using virtual voltage
Reactive power sharing in microgrid using virtual voltage IJECEIAES
Β 
IRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
IRJET- Level of Service & Throughput Maximization at Operational Toll PlazasIRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
IRJET- Level of Service & Throughput Maximization at Operational Toll PlazasIRJET Journal
Β 
Voltage Support and Reactive Power Control in Micro-grid using DG
Voltage Support and Reactive Power Control in Micro-grid using  DGVoltage Support and Reactive Power Control in Micro-grid using  DG
Voltage Support and Reactive Power Control in Micro-grid using DGIJMER
Β 
Power Quality Improvement with Multilevel Inverter Based IPQC for Microgrid
Power Quality Improvement with Multilevel Inverter Based IPQC for MicrogridPower Quality Improvement with Multilevel Inverter Based IPQC for Microgrid
Power Quality Improvement with Multilevel Inverter Based IPQC for MicrogridIJMTST Journal
Β 
06200347
0620034706200347
06200347sru12345
Β 
Optimal Power Flow Using LQR-Based CCVS Inverter for the Grid- Integrated Ren...
Optimal Power Flow Using LQR-Based CCVS Inverter for the Grid- Integrated Ren...Optimal Power Flow Using LQR-Based CCVS Inverter for the Grid- Integrated Ren...
Optimal Power Flow Using LQR-Based CCVS Inverter for the Grid- Integrated Ren...IRJET Journal
Β 
Autonomous microgrid based parallel inverters using droop controller for impr...
Autonomous microgrid based parallel inverters using droop controller for impr...Autonomous microgrid based parallel inverters using droop controller for impr...
Autonomous microgrid based parallel inverters using droop controller for impr...journalBEEI
Β 
An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...
An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...
An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...IAES-IJPEDS
Β 
IRJET- A Review on Hybrid AC/DC Microgrid System and its Coordination Con...
IRJET-  	  A Review on Hybrid AC/DC Microgrid System and its Coordination Con...IRJET-  	  A Review on Hybrid AC/DC Microgrid System and its Coordination Con...
IRJET- A Review on Hybrid AC/DC Microgrid System and its Coordination Con...IRJET Journal
Β 
Transient Power Flow in Micro grids with Signal Stability Energy
Transient Power Flow in Micro grids with Signal Stability EnergyTransient Power Flow in Micro grids with Signal Stability Energy
Transient Power Flow in Micro grids with Signal Stability EnergyIOSR Journals
Β 

Similar to Detailed analysis of grid connected and islanded operation modes based on P/U and Q/f droop characteristics (20)

D010132026
D010132026D010132026
D010132026
Β 
Enhanced dynamic performance of grid feeding distributed generation under va...
Enhanced dynamic performance of grid feeding distributed  generation under va...Enhanced dynamic performance of grid feeding distributed  generation under va...
Enhanced dynamic performance of grid feeding distributed generation under va...
Β 
Control strategies for seamless transfer between the grid-connected and isla...
Control strategies for seamless transfer between  the grid-connected and isla...Control strategies for seamless transfer between  the grid-connected and isla...
Control strategies for seamless transfer between the grid-connected and isla...
Β 
A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...
A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...
A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...
Β 
Design and Implementation of Fuzzy logic based Multilevel Inverter for Micro ...
Design and Implementation of Fuzzy logic based Multilevel Inverter for Micro ...Design and Implementation of Fuzzy logic based Multilevel Inverter for Micro ...
Design and Implementation of Fuzzy logic based Multilevel Inverter for Micro ...
Β 
Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...
Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...
Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...
Β 
Aq33247251
Aq33247251Aq33247251
Aq33247251
Β 
Aq33247251
Aq33247251Aq33247251
Aq33247251
Β 
Reactive power sharing in microgrid using virtual voltage
Reactive power sharing in microgrid using virtual voltage Reactive power sharing in microgrid using virtual voltage
Reactive power sharing in microgrid using virtual voltage
Β 
IRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
IRJET- Level of Service & Throughput Maximization at Operational Toll PlazasIRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
IRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
Β 
Voltage Support and Reactive Power Control in Micro-grid using DG
Voltage Support and Reactive Power Control in Micro-grid using  DGVoltage Support and Reactive Power Control in Micro-grid using  DG
Voltage Support and Reactive Power Control in Micro-grid using DG
Β 
Power Quality Improvement with Multilevel Inverter Based IPQC for Microgrid
Power Quality Improvement with Multilevel Inverter Based IPQC for MicrogridPower Quality Improvement with Multilevel Inverter Based IPQC for Microgrid
Power Quality Improvement with Multilevel Inverter Based IPQC for Microgrid
Β 
Stability analysis of photovoltaic system under grid faults
Stability analysis of photovoltaic system under grid faultsStability analysis of photovoltaic system under grid faults
Stability analysis of photovoltaic system under grid faults
Β 
Performance improvement of decentralized control for bidirectional converters...
Performance improvement of decentralized control for bidirectional converters...Performance improvement of decentralized control for bidirectional converters...
Performance improvement of decentralized control for bidirectional converters...
Β 
06200347
0620034706200347
06200347
Β 
Optimal Power Flow Using LQR-Based CCVS Inverter for the Grid- Integrated Ren...
Optimal Power Flow Using LQR-Based CCVS Inverter for the Grid- Integrated Ren...Optimal Power Flow Using LQR-Based CCVS Inverter for the Grid- Integrated Ren...
Optimal Power Flow Using LQR-Based CCVS Inverter for the Grid- Integrated Ren...
Β 
Autonomous microgrid based parallel inverters using droop controller for impr...
Autonomous microgrid based parallel inverters using droop controller for impr...Autonomous microgrid based parallel inverters using droop controller for impr...
Autonomous microgrid based parallel inverters using droop controller for impr...
Β 
An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...
An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...
An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...
Β 
IRJET- A Review on Hybrid AC/DC Microgrid System and its Coordination Con...
IRJET-  	  A Review on Hybrid AC/DC Microgrid System and its Coordination Con...IRJET-  	  A Review on Hybrid AC/DC Microgrid System and its Coordination Con...
IRJET- A Review on Hybrid AC/DC Microgrid System and its Coordination Con...
Β 
Transient Power Flow in Micro grids with Signal Stability Energy
Transient Power Flow in Micro grids with Signal Stability EnergyTransient Power Flow in Micro grids with Signal Stability Energy
Transient Power Flow in Micro grids with Signal Stability Energy
Β 

More from International Journal of Power Electronics and Drive Systems

More from International Journal of Power Electronics and Drive Systems (20)

Adaptive backstepping controller design based on neural network for PMSM spee...
Adaptive backstepping controller design based on neural network for PMSM spee...Adaptive backstepping controller design based on neural network for PMSM spee...
Adaptive backstepping controller design based on neural network for PMSM spee...
Β 
Classification and direction discrimination of faults in transmission lines u...
Classification and direction discrimination of faults in transmission lines u...Classification and direction discrimination of faults in transmission lines u...
Classification and direction discrimination of faults in transmission lines u...
Β 
Integration of artificial neural networks for multi-source energy management ...
Integration of artificial neural networks for multi-source energy management ...Integration of artificial neural networks for multi-source energy management ...
Integration of artificial neural networks for multi-source energy management ...
Β 
Rotating blade faults classification of a rotor-disk-blade system using artif...
Rotating blade faults classification of a rotor-disk-blade system using artif...Rotating blade faults classification of a rotor-disk-blade system using artif...
Rotating blade faults classification of a rotor-disk-blade system using artif...
Β 
Artificial bee colony algorithm applied to optimal power flow solution incorp...
Artificial bee colony algorithm applied to optimal power flow solution incorp...Artificial bee colony algorithm applied to optimal power flow solution incorp...
Artificial bee colony algorithm applied to optimal power flow solution incorp...
Β 
Soft computing and IoT based solar tracker
Soft computing and IoT based solar trackerSoft computing and IoT based solar tracker
Soft computing and IoT based solar tracker
Β 
Comparison of roughness index for Kitka and Koznica wind farms
Comparison of roughness index for Kitka and Koznica wind farmsComparison of roughness index for Kitka and Koznica wind farms
Comparison of roughness index for Kitka and Koznica wind farms
Β 
Primary frequency control of large-scale PV-connected multi-machine power sys...
Primary frequency control of large-scale PV-connected multi-machine power sys...Primary frequency control of large-scale PV-connected multi-machine power sys...
Primary frequency control of large-scale PV-connected multi-machine power sys...
Β 
Performance of solar modules integrated with reflector
Performance of solar modules integrated with reflectorPerformance of solar modules integrated with reflector
Performance of solar modules integrated with reflector
Β 
Generator and grid side converter control for wind energy conversion system
Generator and grid side converter control for wind energy conversion systemGenerator and grid side converter control for wind energy conversion system
Generator and grid side converter control for wind energy conversion system
Β 
Wind speed modeling based on measurement data to predict future wind speed wi...
Wind speed modeling based on measurement data to predict future wind speed wi...Wind speed modeling based on measurement data to predict future wind speed wi...
Wind speed modeling based on measurement data to predict future wind speed wi...
Β 
Comparison of PV panels MPPT techniques applied to solar water pumping system
Comparison of PV panels MPPT techniques applied to solar water pumping systemComparison of PV panels MPPT techniques applied to solar water pumping system
Comparison of PV panels MPPT techniques applied to solar water pumping system
Β 
Prospect of renewable energy resources in Bangladesh
Prospect of renewable energy resources in BangladeshProspect of renewable energy resources in Bangladesh
Prospect of renewable energy resources in Bangladesh
Β 
A novel optimization of the particle swarm based maximum power point tracking...
A novel optimization of the particle swarm based maximum power point tracking...A novel optimization of the particle swarm based maximum power point tracking...
A novel optimization of the particle swarm based maximum power point tracking...
Β 
Voltage stability enhancement for large scale squirrel cage induction generat...
Voltage stability enhancement for large scale squirrel cage induction generat...Voltage stability enhancement for large scale squirrel cage induction generat...
Voltage stability enhancement for large scale squirrel cage induction generat...
Β 
Electrical and environmental parameters of the performance of polymer solar c...
Electrical and environmental parameters of the performance of polymer solar c...Electrical and environmental parameters of the performance of polymer solar c...
Electrical and environmental parameters of the performance of polymer solar c...
Β 
Short and open circuit faults study in the PV system inverter
Short and open circuit faults study in the PV system inverterShort and open circuit faults study in the PV system inverter
Short and open circuit faults study in the PV system inverter
Β 
A modified bridge-type nonsuperconducting fault current limiter for distribut...
A modified bridge-type nonsuperconducting fault current limiter for distribut...A modified bridge-type nonsuperconducting fault current limiter for distribut...
A modified bridge-type nonsuperconducting fault current limiter for distribut...
Β 
The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...
The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...
The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...
Β 
Comparison of electronic load using linear regulator and boost converter
Comparison of electronic load using linear regulator and boost converterComparison of electronic load using linear regulator and boost converter
Comparison of electronic load using linear regulator and boost converter
Β 

Recently uploaded

GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
Β 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
Β 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
Β 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
Β 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
Β 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
Β 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
Β 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
Β 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
Β 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
Β 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
Β 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
Β 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
Β 
Model Call Girl in Narela Delhi reach out to us at πŸ”8264348440πŸ”
Model Call Girl in Narela Delhi reach out to us at πŸ”8264348440πŸ”Model Call Girl in Narela Delhi reach out to us at πŸ”8264348440πŸ”
Model Call Girl in Narela Delhi reach out to us at πŸ”8264348440πŸ”soniya singh
Β 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
Β 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
Β 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
Β 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
Β 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
Β 

Recently uploaded (20)

GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
Β 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
Β 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
Β 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
Β 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
Β 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
Β 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
Β 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Β 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
Β 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
Β 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
Β 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
Β 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
Β 
Model Call Girl in Narela Delhi reach out to us at πŸ”8264348440πŸ”
Model Call Girl in Narela Delhi reach out to us at πŸ”8264348440πŸ”Model Call Girl in Narela Delhi reach out to us at πŸ”8264348440πŸ”
Model Call Girl in Narela Delhi reach out to us at πŸ”8264348440πŸ”
Β 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
Β 
β˜… CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
β˜… CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCRβ˜… CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
β˜… CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
Β 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
Β 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
Β 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
Β 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
Β 

Detailed analysis of grid connected and islanded operation modes based on P/U and Q/f droop characteristics

  • 1. International Journal of Power Electronics and Drive System (IJPEDS) Vol. 12, No. 2, Jun 2021, pp. 772~782 ISSN: 2088-8694, DOI: 10.11591/ijpeds.v12.i2.pp772-782  772 Journal homepage: http://ijpeds.iaescore.com Detailed analysis of grid connected and islanded operation modes based on P/U and Q/f droop characteristics Qusay Salem1 , Khaled Alzaareer2 1 Department of Electrical Engineering, Princess Sumaya University for Technology, Jordan 2 Department of Electrical Engineering, Quebec University, Montreal QuΓ©bec, Canada Article Info ABSTRACT Article history: Received Dec 30, 2020 Revised Apr 7, 2021 Accepted Apr 20, 2021 This paper presents a thorough control structure of the distributed generators inside the microgrid during both grid-connected and islanded operation modes. These control structures of the DGs voltage source inverters are implemented in synchronous reference frame (SRF) and controlled using linear PI controllers. By implementing the control structures, the desired real and reactive power can be efficiently transferred to the local loads and the utility load by the microgrid generating units. A modified droop control technique is introduced to facilitate the microgrid performance during both modes of operation. The active and reactive power sharing of the load demand between the utility grid and the microgrid can be performed by this droop control technique during the islanded mode. The system performance during intentional islanding event and utility load increase is investigated. The effectiveness of the offered control structures is confirmed through simulation results during both modes of operation. Keywords: Distributed generators Droop control Grid connected and Islanded Modes Microgrid Voltage source inverter This is an open access article under the CC BY-SA license. Corresponding Author: Qusay Salem Department of Electrical Engineering Princess Sumaya University for Technology Amman, Jordan Email: q.salem@psut.edu.jo 1. INTRODUCTION Microgrids are energy networks which have small-scale and low-voltage feature. They are utilized to guarantee the distribution and generation locally in the autonomous or remote societies [1]. Microgrids can be interconnected with large power systems through power electronic converters and can even work autonomously [2], [3]. In the normal operation where the microgrid is connected to the massive grid, DGs into the power network can track the grid energy flow and operate without control requirment. In the event of short circuit or planned interruption, the microgrid can be disconnected from the large grid to operate in autonomous mode where proper control methods are applied in order to ensure stability of power [4], [5]. The autonomous functionality can provide more elacticity to the DGs involvement and bring a more efficient power supply. However, autonomous microgrids might have powerless condition than conventional massive grids because of limited capacities of the DGs [6]. The microgrid notion advocates coordinated control where retrieving trustworthy and high-quality energy can be ensured to customers by DGs cooperation [7]. The controlled voltage source converters-based power electronic interfaces are utilized widely to connect the DGs to the point of common coupling of the network. Moreover, two main categories of microgrid control methods are existed which are divided into either centralized control or decentralized control methods [8]-[10]. A high bandwidth communication link is employed in centralized control methods to transfer feedback and control signals between the centralized
  • 2. Int J Pow Elec & Dri Syst ISSN: 2088-8694  Detailed analysis of grid connected and islanded operation modes based on P/U … (Qusay Salem) 773 controller and the DGs. Centralized controllers are found to be less reliable since system instability might appear due to any communication interruption beside the communication system higher costs [11]-[14]. That’s why decentralized control methods are considered more feasible as performing the system online maintenance and achieving self-organizing can be accomplished easily [15], [16]. The methods of decentralized control employ 𝑃 βˆ’ 𝑓 & 𝑄 βˆ’ 𝐸 droop characteristics to regulate the flow of real and reactive power in the microgrid. These droop characteristics are based on highly inductive networks where the decoupling of real and reactive power flow equations can be applied. Slow dynamics and voltage drifts with load change are some features of these droop characteristics which are compatbile with the network impedance high 𝑋/𝑅 ratio and large inertia in conventional power systems [17], [18]. However, since line impedances in microgrids are resistive at most, DGs have small inertia and persistent load variations may happen. The 𝑋/𝑅 ratio in microgrids is not large like the case in conventional power systems. Consequently, the active and reactive power flow is dependent on 𝛿 and 𝐸 as they are highly coupled. That’s why the traditional droop technique which employs decoupled 𝑃 βˆ’ 𝑓 & 𝑄 βˆ’ 𝐸 droops bring out weak performance. Different controllers have been proposed in this context where [19] introduces a virtual resistance so that the system acts in a resistive manner where 𝑃 and 𝑄 might be regulated by respectively drooping 𝐸 and 𝑓. [20] and [21] have introduced a virtual reactance and a virtual PQ method, respectively to mimic the inductive system by increasing the 𝑋/𝑅 ratio. The 𝑃 βˆ’ 𝑓 & 𝑄 βˆ’ 𝐸 droop scheme has the disadvantage of exhibiting power quality problems in terms of frequency and voltage deviations. Replacing the 𝑃 βˆ’ 𝑓 droop by 𝑃 βˆ’ 𝛿 droop can eliminate the frequency deviations problem where a global positioning system is introduced to synchronize the DG units [22]. E. Rokrok and M. Golshan [23] have introduced an adaptive voltage droop method for improving the regulation of voltage at PCC and mitigating the coupling between 𝑃 and 𝑄 droop controllers. In [24], synchronizing the global frequency to a nominal value with better disturbance rejection properties has been realized by considering a finite-time control protocol for frequency restoration, based on feedback linearization. DG self-frequency restoration control has corrected the frequency deviation by droop compensation without the need of utilizing a secondary controller [25]. However, resistive line impedance in low voltage microgrids causes power coupling in 𝑃 βˆ’ 𝑓 droop control which hasn’t been considered and was only applied to high or medium voltage networks. The current communication-less microgrid control methods have utilized 𝑃 βˆ’ 𝑓 & 𝑄 βˆ’ 𝐸 droop characteristics. An alternative approach is proposed in this paper where a 𝑃 βˆ’ π‘ˆ and 𝑄 βˆ’ 𝑓 droop control technique is proposed for a microgrid connected to the utility or main grid. The control structures that are implemented to execute the grid-connected and islanded operations of DGs are investigated. An intentional islanding condition is performed to investigate the performance of the microgrid control structures. Moreover, a step change in the utility load has been proposed to prove the control structures performance. The proposed control strategies can control the voltage and power of the DGs in addition to sharing the load demand during all modes of operation. The main contribution of this work is accomplished by considering the abovementioned issues. The organization of the paper is divided into five sections. At first is the introduction, then section 2 presents the general schematic diagram of the proposed microgrid model. The real and reactive power generation in relation to the proposed droop control methodology is introduced in section 3. Section 4 shows the simulation results which are performed to confirm the applicability and efficiency of the proposed control structures. Finally, section 5 presents the conclusion of the proposed work. 2. THE PROPOSED NETWORK DESCRIPTION Figure 1 shows a single-line diagram of the proposed microgrid model which can operate in grid connected and islanded modes. All the distributed generators are supposed to inject the required active and reactive power to support their own loads and the utility load then the remnant of power moves out to the main utility grid. A circuit breaker is placed in the system either to maintain the microgrid online with the main grid or to isolate the faulty sections from the microgrid in case of short circuits. A utility load is connected directly to the point of common coupling (PCC) to be supported by real and reactive power in both modes of operation. 2.1. Modeling and control of grid-connected DC/AC voltage source inverter Variables in synchronous reference frame (SRF) are used for the control of grid connected inverters in which they described as DC quantities. Figure 2 depicts the circuit diagram of the three-phase voltage source inverter connected to the grid. π‘ˆπ‘Ž, π‘ˆπ‘, π‘ˆπ‘ are the inverter output voltages, πΈπ‘Ž, 𝐸𝑏, 𝐸𝑐 are the output voltages of the grid. The inductance of the inverter is denoted by 𝐿𝑖 and 𝐿𝑔 is the inductance of the grid. π‘–π‘Ž, 𝑖𝑏, 𝑖𝑐 are the injected currents in the main grid. The equation of the diagram depicted in Figure 2 is formulated differentially as:
  • 3.  ISSN: 2088-8694 Int J Pow Elec & Dri Syst, Vol. 12, No. 2, June 2021 : 772 – 782 774 𝐿[ 𝑑𝑖 𝑑𝑑 ]π‘Žπ‘π‘ = [π‘ˆ]π‘Žπ‘π‘ βˆ’ [𝐸]π‘Žπ‘π‘ βˆ’ 𝑅[𝑖]π‘Žπ‘π‘ (1) Where, the total inductance of the inverter is denoted by 𝐿, which means 𝐿 = 𝐿𝑖 + 𝐿𝑔. If πœ” = 2πœ‹π‘“, where πœ” is the frequency of the grid, then (1) can be formulated in synchronous reference frame as: π‘ˆπ‘‘π‘ž,π‘Ÿπ‘’π‘“ = 𝐿 π‘‘π‘–π‘‘π‘ž 𝑑𝑑 + (𝑅 + π‘—πœ”πΏ)π‘–π‘‘π‘ž + π‘ˆπ‘‘π‘ž (2) Figure 1. The proposed microgrid model Figure 2. Three phase DC/AC voltage source converter connected to grid Then the real part and the imaginary part of (2) can be written as: π‘ˆπ‘‘,π‘Ÿπ‘’π‘“ = 𝐿 𝑑𝑖𝑑 𝑑𝑑 + 𝑅𝑖𝑑 βˆ’ πœ”πΏπ‘–π‘ž + π‘ˆπ‘‘ (3) π‘ˆπ‘ž,π‘Ÿπ‘’π‘“ = 𝐿 π‘‘π‘–π‘ž 𝑑𝑑 + π‘…π‘–π‘ž + πœ”πΏπ‘–π‘‘ + π‘ˆπ‘ž (4) Depending on (3) and (4) the arrangement of the grid connected voltage source inverter current control in dq- reference frame is illustrated as shown in Figure 3. Where, 𝑖𝑑,π‘Ÿπ‘’π‘“, π‘–π‘ž,π‘Ÿπ‘’π‘“ are the dq reference currents. A PLL is used for tracking the phase angle of the grid to be synchronized with DGs. PI controllers are used to compensate the voltage drop caused by the line impedance.
  • 4. Int J Pow Elec & Dri Syst ISSN: 2088-8694  Detailed analysis of grid connected and islanded operation modes based on P/U … (Qusay Salem) 775 Figure 3. Block diagram of VSI current control The control equations for π‘ˆπ‘‘,π‘Ÿπ‘’π‘“ and π‘ˆπ‘ž,π‘Ÿπ‘’π‘“ are as the following: π‘ˆπ‘‘,π‘Ÿπ‘’π‘“ = π‘ˆπ‘‘ βˆ’ πœ”πΏπ‘–π‘ž + (π‘˜π‘ + π‘˜π‘– 𝑠 ) (𝑖𝑑,π‘Ÿπ‘’π‘“ βˆ’ 𝑖𝑑) (5) π‘ˆπ‘ž,π‘Ÿπ‘’π‘“ = π‘ˆπ‘ž βˆ’ πœ”πΏπ‘–π‘‘ + (π‘˜π‘ + π‘˜π‘– 𝑠 ) (π‘–π‘ž,π‘Ÿπ‘’π‘“ βˆ’ π‘–π‘ž) (6) Hence, the formulas of active and reactive power are written in synchronous reference frame as: 𝑃 = 3 2 (π‘ˆπ‘‘,π‘Ÿπ‘’π‘“ 𝑖𝑑 + π‘ˆπ‘ž,π‘Ÿπ‘’π‘“ π‘–π‘ž) (7) 𝑄 = 3 2 (π‘ˆπ‘‘,π‘Ÿπ‘’π‘“ π‘–π‘ž βˆ’ π‘ˆπ‘ž,π‘Ÿπ‘’π‘“ 𝑖𝑑) (8) It can be seen from (7) and (8) that a mutual coupled voltage exists between the d and q axis quantities. However, this coupling will not cause independent control of P and Q. In other words, if the delivered real power changes, the reactive power will change accordingly. The elimination of this mutual coupling is achieved by considering π‘ˆπ‘ž,π‘Ÿπ‘’π‘“ = 0. Hence, the modified real and reactive power can be written as: 𝑃 = 3 2 π‘ˆπ‘‘,π‘Ÿπ‘’π‘“ 𝑖𝑑 (9) 𝑄 = 3 2 π‘ˆπ‘‘,π‘Ÿπ‘’π‘“ π‘–π‘ž (10) Consequently, the d-axis current monitors directly the active power and the q-axis current monitors the reactive power. 2.2. Control of DC/AC voltage source inverter in islanded mode Once the main utility grid is seperated from the microgrid, every DG inside the microgrid will lose stability in terms of very high values of current or voltage transients. In island mode, the grid feeding power converters can not work unless if a grid forming or grid supporting power converter is existed so that the voltage amplitude and frequency of the ac microgrid can be adjusted [26]. In this paper, a power converter which is grid forming one is activated at PCC when the microgrid becomes islanded. The circuit diagram of the grid forming power converter in islanded mode is depicted in Figure 4. The reference values of the frequency and voltage is determined by a reference sinewave generator. This is because the microgrid has no physical connection with the main grid. Thus, the DG reference voltage in islanded mode is extracted as:
  • 5.  ISSN: 2088-8694 Int J Pow Elec & Dri Syst, Vol. 12, No. 2, June 2021 : 772 – 782 776 { π‘ˆπ‘Ž = 𝐸 sin (πœ”π‘‘) π‘ˆπ‘ = 𝐸 sin (πœ”π‘‘ βˆ’ 2πœ‹ 3 ) π‘ˆπ‘ = 𝐸 sin (πœ”π‘‘ + 2πœ‹ 3 ) } (11) Figure 4. Circuit diagram of grid forming power converter in islanded mode The voltage and current control circuit for the grid forming power converter in islanded mode is shown in Figure 5. In the islanded mode, the existing control acts as voltage control through compensation of current. The control unit employs voltage regulators to extract the desired current references. After that, using proper PI controllers, π‘ˆπ‘‘ and π‘ˆπ‘ž will successfully track their references. The output current references 𝑖𝑑,π‘Ÿπ‘’π‘“ and π‘–π‘ž,π‘Ÿπ‘’π‘“ are compared with 𝑖𝑑 and π‘–π‘ž, and the difference is inserted to another PI controller. Finally, the resultant output of the current loop performs as a voltage reference signal which is delivered to the gating signals of the three-phase power converter. 3. REAL AND REACTIVE POWER BASED ON DROOP CONTROL TECHNIQUE Giving consideration to the converter as a voltage source which is controllable and taking into account that the converter is attached to the main grid via a line impedance as illustrated in Figure 6 (a), then the transmitted real and reactive power to the main grid can be formulated as: 𝑃𝐴 = π‘ˆπ΄ 𝑅2+𝑋2 [𝑅(π‘ˆπ΄ βˆ’ π‘ˆπ‘ π‘π‘œπ‘ π›Ώ) + π‘‹π‘ˆπ΅π‘ π‘–π‘›π›Ώ] (12) 𝑄𝐴 = π‘ˆπ΄ 𝑅2+𝑋2 [βˆ’π‘…(π‘ˆπ΅ 𝑠𝑖𝑛𝛿) + 𝑋(π‘ˆπ΄ βˆ’ π‘ˆπ΅π‘π‘œπ‘ π›Ώ)] (13) Where, the real and reactive power passing to the grid from the power converter are denoted by 𝑃𝐴 and 𝑄𝐴, the voltages of the two power converters are denoted by π‘ˆπ΄, π‘ˆπ‘, the phase angle difference between both converter voltages is denoted by 𝛿, the line impedance is denoted by 𝑍 = 𝑅 + 𝑗𝑋 and the impedance angle is denoted by πœ‘. Thus, as 𝑅 = 𝑍. π‘π‘œπ‘ πœ‘ and 𝑋 = 𝑍. π‘ π‘–π‘›πœ‘, the vector representation of the given model can be represented in Figure 6 (b).
  • 6. Int J Pow Elec & Dri Syst ISSN: 2088-8694  Detailed analysis of grid connected and islanded operation modes based on P/U … (Qusay Salem) 777 Figure 5. Voltage and current control of the power converter in the islanded mode (a) (b) Figure 6. Modelling of power converter connected to the distribution network, (a) equivalent circuit (b) phasor diagram In low-voltage networks, the impedance of the grid is principally resistive and thus the inductive part can approximately be neglected. If we assume a small value of the phase angle 𝛿, then (12) and (13) can be rewritten as: 𝑃𝐴 = π‘ˆπ΄ 𝑅 (π‘ˆπ΄ βˆ’ π‘ˆπ΅π‘π‘œπ‘ π›Ώ) =≫ π‘ˆπ΄ βˆ’ π‘ˆπ΅ β‰ˆ 𝑅𝑃𝐴 π‘ˆπ΄ (14) 𝑄𝐴 = βˆ’ π‘ˆπ΄.π‘ˆπ΅ 𝑅 𝑠𝑖𝑛𝛿 =≫ 𝛿 = βˆ’ 𝑅𝑄𝐴 π‘ˆπ΄π‘ˆπ΅ (15) Based on the previous two equations, it can be noticed that the voltage magnitude in low-voltage distribution networks and the real power are dependent to each other. Also, the reactive power and the frequency are influenced by each other. From (14) and (15), the expressions of the droop control are demonstrated as: π‘ˆ βˆ’ π‘ˆπ‘œ = βˆ’π‘˜π‘(𝑃 βˆ’ π‘ƒπ‘œ) (16) 𝑓 βˆ’ π‘“π‘œ = π‘˜π‘ž(𝑄 βˆ’ π‘„π‘œ) (17) The characteristics of the proposed droop control are illustrated in Figure 7. The characteristics demonstrate that the voltage magnitude and the active power are mainly dependent. On the other hand, it is clear that the frequency and the reactive power are also dependent on each other.
  • 7.  ISSN: 2088-8694 Int J Pow Elec & Dri Syst, Vol. 12, No. 2, June 2021 : 772 – 782 778 Figure 7. P/U and Q/f droop control characteristics 4. DISCUSSION OF SIMULATION RESULTS Realization and robustness of the proposed droop control strategies in the microgrid model have been assessed in steady state and transient operating conditions employing β€˜SimPowerSystems’ library toolbox in Matlab/Simulink. The parameters of the single line diagram shown in Figure 1 are given in Table 1. Two scenarios have been evaluated through simulations to examine the system behavior. The first scenario is when an intentional islanding condition takes place. The other scenario is when the utility load increases during the islanding period. The significance and novel aspects of the results are obvious by the operation of the proposed droop control technique where the DGs share the real power to fulfill the total load demand for both scenarios. Moreover, the obtained results reflect the stability and solidity of the DG VSI control strategy during both grid-connected and islanded operation modes. Table 1. Parameters of the proposed model Grid π‘‰π‘Ÿπ‘šπ‘  = 230 𝑉, 𝑓 = 50 𝐻𝑧 DG 1 𝑃 = 12 π‘˜π‘€, 𝑄 = 4 π‘˜π‘£π‘Žπ‘Ÿ DG 2 𝑃 = 14 π‘˜π‘€, 𝑄 = 6 π‘˜π‘£π‘Žπ‘Ÿ DG 3 𝑃 = 16 π‘˜π‘€, 𝑄 = 8 π‘˜π‘£π‘Žπ‘Ÿ DG 4 𝑃 = 18 π‘˜π‘€, 𝑄 = 10 π‘˜π‘£π‘Žπ‘Ÿ Utility Load 𝑃 = 30 π‘˜π‘€, 𝑄 = 5 π‘˜π‘£π‘Žπ‘Ÿ DGs Loads 𝑃 = 5 π‘˜π‘€, 𝑄 = 0 π‘˜π‘£π‘Žπ‘Ÿ Line impedance 𝑅 = 0.5 𝛺, 𝐿 = 0.8 π‘šπ» 4.1. Intentional islanding scenario The microgrid is assumed to work in grid-connected mode at (0 ≀ 𝑑 ≀ 1) and then disconnected from the utility following an intentional islanding condition at PCC which is proposed at 𝑑 = 1𝑠 and lasts for 1000π‘šπ‘  (1 ≀ 𝑑 ≀ 2). After that the system regains its operation to relate to the main grid at (2 ≀ 𝑑 ≀ 3). Figure 8 (a)-(d) depicts the microgrid performance concerning the real power, reactive power, rms voltage and frequency while subfigures (e)-(h) depict the grid performance in terms of real power, rms voltage, current and frequency. It is noticed from the results that the proposed droop control strategies are functioning effectively during grid-connected and islanded modes. Furthermore, it can be noticed that when islanding occurs, the DGs share the real power to fulfill the total load demand since the power supply of the main grid is lost. As a result, the rms voltage of the DGs inverters is increased based on the droop characteristics. The reactive power and frequency of DGs inverters show a little transient at the time of islanding and reconnection due to the circuit breaker operation. At the grid side, it can be noticed that the system is completely islanded at (1 ≀ 𝑑 ≀ 2) as the grid real power and current reach zeros. In addition, it is also noticed that a small fluctuation on grid frequency is existed at the time of islanding and reconnection conditions. Every DG in the microgrid is equipped with identical droop characteristic is applied for where the DGs real power are shared equally to satisfy the local loads and the utility load during the islanding period (1 ≀ 𝑑 ≀ 2).
  • 8. Int J Pow Elec & Dri Syst ISSN: 2088-8694  Detailed analysis of grid connected and islanded operation modes based on P/U … (Qusay Salem) 779 Figure 8. Microgrid and grid performance during intentional islanding scenario 4.2. Utility load increase scenario Figure 9 (a)-(d) shows the behavior of the microgrid when the utility load increases. The utility load has been increased from 30π‘˜π‘€ to 50 π‘˜π‘€ in order to investigate the performance of real and reactive power sharing between the grid and microgrid especially when the system is islanded. It is clearly shown that the real power of DGs inverters in islanding mode have increased to compensate the shortage of generation from the main grid in order to support the demand of utility load. Again, identical droop characteristics are applied
  • 9.  ISSN: 2088-8694 Int J Pow Elec & Dri Syst, Vol. 12, No. 2, June 2021 : 772 – 782 780 for each DG to satisfy the increase in the utility load during the islanding period. This was done by sharing the real power of all DGs such that the utility load increase is divided on the four DGs equally. Consequently, the DGs rms voltage has decreased based on the droop characteristics. The reactive power and frequency of DGs remain as before with a little transient at the time of islanding and reconnection. However, it can be seen from subfigures (e)-(h) that the main grid real power and current approaches zero as a result of the islanding condition while the voltage and frequency remain within their permissible limits during both grid connected and islanded modes. Figure 9. Microgrid and grid performance during utility load increase scenario
  • 10. Int J Pow Elec & Dri Syst ISSN: 2088-8694  Detailed analysis of grid connected and islanded operation modes based on P/U … (Qusay Salem) 781 5. CONCLUSION The system efficacy and behavior of the proposed droop control have been investigated during both grid-connected and islanded modes by proposing an intentional islanding condition at PCC and by increasing of the utility load. Two control interfaces are employed to design the control strategies, the first one represents the grid connected mode and the other one represents the islanded mode. The simulation results confirmed that the response of the proposed control strategies and the droop control can maintain the system parameters within acceptable limits during both modes of operation. The addition of anti-islanding algorithms or techniques to the control units of the microgrid is a proper path of the future work. REFERENCES [1] C.-S. Karavas, G. Kyriakarakos, K. Arvanitis and G. Papadakis, β€œA multi-agent decentralized energy management system based on distributed intelligence for the design and control of autonomous polygeneration microgrids,” Energy Conversion and Management , vol. 103, pp. 166-179, 2015, DOI: 10.1016/j.enconman.2015.06.021. [2] J. Li, Y. Liu and L. Wu, β€œOptimal Operation for Community-Based Multi-Party Microgrid in Grid-Connected and Islanded Modes,” IEEE Transactions on Smart Grid, vol. 9, no. 2, pp. 756-765, 2018, doi: 10.1109/TSG.2016.2564645. [3] H. Ali, A. Hussain, V. Bui and H. Kim, β€œConsensus Algorithm-Based Distributed Operation of Microgrids During Grid-Connected and Islanded Modes,” IEEE Access, vol. 8, pp. 78151-78165, 2020, DOI: 10.1109/ACCESS.2020.2989457. [4] C. Dou, Z. Zhang, D. Yue and H. Gao, β€œAn Improved Droop Control Strategy Based on Changeable Reference in Low-Voltage Microgrids,” Energies , vol. 10, pp. 1-18, 2017, DOI: 10.3390/en10081080. [5] Q. Salem, L. Liu and J. Xie, β€œDual Operation Mode of a Transformerless H-Bridge Inverter in Low-Voltage Microgrid,” IEEE Transactions on Industry Applications, vol. 55, no. 5, pp. 5289-5299, 2019, DOI: 10.1109/TIA.2019.2917807. [6] X. Wang, F. Blaabjerg and Z. Chen, β€œAutonomous Control of Inverter-Interfaced Distributed Generation Units for Harmonic Current Filtering and Resonance Damping in an Islanded Microgrid,” IEEE Transactions on Industry Applications, vol. 50, no. 1, pp. 452 - 461, 2014, DOI: 10.1109/TIA.2013.2268734. [7] M. S. Golsorkhi and D. D. C. Lu, β€œA Control Method for Inverter-Based Islanded Microgrids Based on V-I Droop Characteristics,” IEEE Transactions on Power Delivery, vol. 30, no. 3, pp. 1196-1204, 2015, DOI: 10.1109/TPWRD.2014.2357471. [8] E. Espina, J. Llanos, C. Burgos-Mellado, R. CΓ‘rdenas-Dobson, M. MartΓ­nez-GΓ³mez and D. SΓ‘ez, β€œDistributed Control Strategies for Microgrids: An Overview,” IEEE Access, vol. 8, pp. 193412-193448, 2020, DOI: 10.1109/ACCESS.2020.3032378. [9] Q. Salem and J. Xie, β€œDecentralized power control management with series transformerless H-bridge inverter in low-voltage smart microgrid based P/V droop control,” International Journal of Electrical Power & Energy Systems, vol. 99, pp. 500-515, 2018, DOI: 10.1016/j.ijepes.2018.01.047. [10] Q. Salem and K. Alzaareer, β€œFault ride-through capability with mutual inductance in low-voltage single-phase microgrid,” IETE Journal of Research, 2020, DOI: 10.1080/03772063.2020.1800524. [11] Y. K. e. al, β€œOn the Secondary Control Architectures of AC Microgrids: An Overview," in IEEE Transactions on Power Electronics,” IEEE Transactions on Power Electronics, vol. 35, no. 6, pp. 6482-6500, 2020. [12] Q. Xu, J. Xiao, P. Wang and C. Wen, β€œA Decentralized Control Strategy for Economic Operation of Autonomous AC, DC, and Hybrid AC/DC Microgrids,” IEEE Transactions on Energy Conversion, vol. 32, no. 4, pp. 1345- 1355, 2017, DOI: 10.1109/TEC.2017.2696979. [13] J. Wang, C. Jin and P. Wang, β€œA Uniform Control Strategy for the Interlinking Converter in Hierarchical Controlled Hybrid AC/DC Microgrids,” IEEE Transactions on Industrial Electronics, vol. 65, no. 8, pp. 6188- 6197, 2018, DOI: 10.1109/TIE.2017.2784349. [14] S. Ansari, A. Chandel and M. Tariq, β€œA Comprehensive Review on Power Converters Control and Control Strategies of AC/DC Microgrid,” IEEE Access, vol. 9, pp. 17998-18015, 2021, DOI: 10.1109/ACCESS.2020.3020035. [15] I. U. Nutkani, P. C. Loh, P. Wang and F. Blaabjerg, β€œDecentralized Economic Dispatch Scheme With Online Power Reserve for Microgrids,” IEEE Transactions on Smart Grid, vol. 8, no. 1, pp. 139-148, 2017, DOI: 10.1109/TSG.2015.2451133. [16] A. Vaccaro, V. Loia, G. Formato, P. Wall and . V. Terzija, β€œA Self-Organizing Architecture for Decentralized Smart Microgrids Synchronization, Control, and Monitoring,” IEEE Transactions on Industrial Informatics, vol. 11, no. 1, pp. 289-298, 2015, DOI: 10.1109/TII.2014.2342876. [17] M. A. Awal, H. Yu, H. Tu, S. M. Lukic and I. Husain, β€œHierarchical Control for Virtual Oscillator Based Grid- Connected and Islanded Microgrids,” IEEE Transactions on Power Electronics, vol. 35, no. 1, pp. 988-1001, 2020, DOI: 10.1109/TPEL.2019.2912152. [18] M. Naderi, Y. Khayat, Q. Shafiee, T. Dragicevic, H. Bevrani and F. Blaabjerg, β€œInterconnected Autonomous AC Microgrids via Back-to-Back Convertersβ€”Part I: Small-Signal Modeling,” IEEE Transactions on Power Electronics, vol. 35, no. 5, pp. 4728-4740, 2020, DOI: 10.1109/TPEL.2019.2943996. [19] J. M. Guerrero, J. Matas, L. G. d. Vicuna, M. Castilla and J. Miret, β€œDecentralized Control for Parallel Operation of Distributed Generation Inverters Using Resistive Output Impedance,” IEEE Transactions on Industrial Electronics, vol. 54, no. 2, pp. 994-1004, 2007, DOI: 10.1109/TIE.2007.892621.
  • 11.  ISSN: 2088-8694 Int J Pow Elec & Dri Syst, Vol. 12, No. 2, June 2021 : 772 – 782 782 [20] Y. C. C. Wong, C. S. Lim, M. D. Rotaru, A. Cruden and X. Kong, β€œConsensus Virtual Output Impedance Control Based on the Novel Droop Equivalent Impedance Concept for a Multi-Bus Radial Microgrid,” IEEE Transactions on Energy Conversion, vol. 35, no. 2, pp. 1078-1087, 2020, DOI: 10.1109/TEC.2020.2972002. [21] M. Naderi, Q. Shafiee, F. Blaabjerg and H. Bevrani, β€œLow-Frequency Small-Signal Modeling of Interconnected AC Microgrids,” IEEE Transactions on Power Systems, 2020, DOI: 10.1109/TPWRS.2020.3040804. [22] R. Majumder, A. Ghosh, G. Ledwich and F. Zare, β€œAngle droop versus frequency droop in a voltage source converter based autonomous microgrid,” in 2009 IEEE Power & Energy Society General Meeting, 2009, pp. 1-8, DOI: 10.1109/PES.2009.5275987. [23] E. Rokrok and M. Golshan, β€œAdaptive voltage droop scheme for voltage source converters in an islanded multibus microgrid,” IET Generation, Transmission & Distribution, vol. 4, no. 5, pp. 562-578, 2010, DOI: 10.1049/iet- gtd.2009.0146. [24] S. Zuo, A. Davoudi, Y. Song and F. L. Lewis, β€œDistributed Finite-Time Voltage and Frequency Restoration in Islanded AC Microgrids,” IEEE Transactions on Industrial Electronics, vol. 63, no. 10, pp. 5988-5997, 2016, DOI: 10.1109/TIE.2016.2577542. [25] Y.-S. Kim, E.-S. Kim and S.-I. Moon, β€œDistributed Generation Control Method for Active Power Sharing and Self- Frequency Recovery in an Islanded Microgrid,” IEEE Transactions on Power Systems, vol. 32, no. 1, pp. 544-551, 2017, DOI: 10.1109/TPWRS.2016.2543231. [26] J. Chen, F. Milano and T. O'Donnell, β€œAssessment of Grid-Feeding Converter Voltage Stability,” IEEE Transactions on Power Systems, vol. 34, no. 5, pp. 3980-3982, 2019, DOI: 10.1109/TPWRS.2019.2920516. BIOGRAPHIES OF AUTHORS Qusay Salem has been awarded the PhD degree in Electrical Power and Energy Engineering from University of Ulm – Germany, in 2020. He received the B.Sc. and M.Sc. Degree both in Electrical Power Engineering from University of Mutah and Yarmouk University – Jordan, in 2009 and 2013, respectively. Currently, he serves as an Assistant Professor with the Department of Electrical Engineering at Princess Sumaya University for Technology. His research interests include power control and energy management in low-voltage smart microgrids, Islanding detection schemes, Series power flow controllers. Khaled Alzaareer received the PhD degree in Electrical Engineering/ Power Systems from Quebec University (ETS), Montreal, QC, Canada in Dec. 2020. He also received the bachelor’s and master’s degrees in electrical power engineering from Yarmouk University, Irbid, Jordan, in 2010 and 2012, respectively. His research interests are smart grid, sensitivity analysis, renewable energy integration, voltage stability and control.