Performance of Single Pass earth-Tube
Heat Exchanger: An Experimental Study
Girja Sharan
Professor
Coordinator Cummins-IIMA Lab
Centre for Mgt in Agriculture
Indian Institute of Management,
Ahmedabad
Ratan Jadhav
Project Officer
SEWA
Ahmedabad
Abstract
A single pass earth-tube heat exchanger (ETHE) was installed to study its
performance in cooling and heating mode. ETHE is made of 50 m long ms
pipe of 10 cm nominal diameter and 3 mm wall thickness. ETHE is buried
3 m deep below surface. Ambient air is pumped through it by a 400 w
blower. Air velocity in the pipe is 11 m/s. Air temperature is measured at
the inlet of the pipe, in the middle (25 m), and at the outlet (50 m), by
thermisters placed inside the pipe. Cooling tests were carried out three
consecutive days in each month. On each day system was operated for 7
hours during the day and shut down for the night. Heating tests were carried
out at night in January. Test results are presented in summary form for each
month. Detailed analysis is presented for two months only -- May for cooling
and January for heating.
ETHE cools the ambient air in May by as much as 14o
C. It heats the
ambient air in January nights also by similar amount.
Key Words : Earth Tube Heat Exchanger, air tunnel
2
Introduction
We have been developing earth-tube heat exchanger (ETHE) for use in greenhouse in
arid areas like Kutch. As a first step, deep soil temperature regime was studied in
Ahmedabad, Sharan and Jhadav (2002). After year-long measurements they reported that
the soil strata between 2m to 3m depth had stable temperature regime suitable for
installation of ETHE. Temperature in this stratum displays no diurnal fluctuation. It
does display annual fluctuation, but the amplitude is small. Average temperature in this
stratum is 27o
C As a second step one single pass ETHE was built to investigate the
actual cooling and heating performance. This ETHE is made of 50m long ms pipe of 10
cm nominal diameter. It is buried 3m deep below surface. We report here the results of
investigation carried out on this facility. Specific aim of those investigations is:
(a) to determine the operating characteristics of ETHE in cooling and
heating mode
(b) to develop data base of its performance in each of the twelve months
In this paper, details of the experimental facility are described. Performance data has been
collected for all the twelve months, but for reasons of space only May and January results
are presented and discussed in detail. May month is the hottest part of summer, January
the coolest part of winter in Ahmedabad region. Basic results of tests in the remaining
months of the year are however given in summary form.
3
Review of Literature
Earth-Tube Heat Exchanger (ETHE) is a device that enables transfer of heat from
ambient air to deeper layers of soil and vice versa. Since the early exploration of its use in
cooling commercial livestock buildings (Scott et al 1965) there has been considerable
increase in its application. ETHE is used to condition the air in livestock buildings
(Spengler and Stombaugh 1983). It is used in North America and Europe to cool and
heat greenhouses (Santa Mouris et al 1995). There have also been works aiming at
gaining better understanding of its working in cooling and heating mode (Baxter 1992,
1994). Mathematical models of ETHE have also been developed (Puri 1985; Goswami
and Dhaliwal 1985). There has also been some work in India. Sawhney et al (1998)
installed a ETHE based system to cool part of a guesthouse. Sharan et al (2001)
installed a ETHE based cooling system for tiger dwelling at Ahmedabad Zoological
Garden. Authors have visited Tata Energy Research Institute, where a system is installed
to cool rooms in its training center near Delhi.
The experimental system we have built is similar to Baxter's, though smaller and less
elaborately instrumented. Baxter's facility at Knoxville, Tennessee (USA) is a single pass
earth-tube heat exchanger 64-m long, 15-cm diameter, made of 18- gauge spirally
corrugated galvanized metal. The tube is buried at 1.8-m depth, and is elaborately
instrumented with temperature sensors inside the tube and in soil around it. Air is
4
pumped by a high pressure industrial blower of about 572 w power. Instrumentation
permits measurement of air temperature along the tube and in soil around the tube.
Experimental Set-up
Site
The installation is on an open field at village, Thor, some 40 km from IIM, Ahmedabad
campus. Soil at the site was tested at Soil Mechanics Laboratory of L.D. Engineering
College, Ahmedabad and found to be sandy-silt (sand 48%, silt 41%, clay 11%).
Moisture content at the time of excavation was 12.61% (d b). Experimental set-up
consists of an ETHE, fan house, temperature sensors and back-up risers. A schematic
diagram of the set-up is shown in figure-1.
Earth-Tube Heat Exchanger
ETHE consists of a 50 m long 10 cm diameter ms pipe with wall thickness of 3 mm.
Especially made fins have been installed on the outer surface of the pipe, all along the 50
m length. Fins are made of thin GI strip spirally wound over the pipe and then spot-
welded at several points. There are 40 fins per meter length. Strip that makes the fins is
2 cm wide, 2 mm thick. A 1 m wide, 3 m deep and 50 m long trench was first
excavated by a bucket excavator. Trench floor was properly leveled and a 15 cm thick
bed of sand placed on it. ETHE was then placed on it and covered with sand up to about
15 cm above it. After that trench was back-filled with the original soil. The inlet and
outlet of the ETHE rise 0.5 m above ground. Inlet is connected to the delivery end of
5
blower and outlet is open to atmosphere. A 90 elbow at the end makes the outlet
horizontal to the entry of rain water.
Instrumentation
It was desired to obtain air temperature in the ETHE at three location -- at the entrance,
at the middle (25 m) and at the end (50 m). One thermister was installed at each of these
three locations inside the tube at the center. Figure-2 shows the thermister assembly
configuration. A 15 cm long 10 cm dia coupler was used to build the thermister
assembly. A acrylic strip, 10 cm long (to fit snug across the inner dia of the coupler)
2 cm wide and 2 mm thick and was placed horizontally at the center in the coupler as
shown. Its ends were bonded to the pipe wall with adhesive. Thermister (AD 590) was
placed at the center and bonded to upper surface of the strip using a very thin layer of
adhesive. Leads were taken out of the coupler via a 2 mm hole drilled on the side.
Hole was then sealed to make it air tight. A 25 mm threaded hole was made on the top
side of the coupler. A PVC pipe of 25 mm dia was connected to the coupler as shown.
The PVC pipe was 3.5 m long. It is placed vertically and rises above the ground about
0.5 m. Upper end of the riser is normally closed with a cap. Risers were provided to act
as a back-up for obtaining tube air temperature, if built in sensors failed. The leads also
are taped to the outside of PVC pipe and brought above ground and connected to a
digital indicator. Indicators were housed in a wooden box to protect these from weather.
Three such assemblies were made. One is installed at the entrance of the ETHE, one in
the middle, and one at the end. Air velocity in the pipe is not high and therefore the
6
convective cooling of thermisters due to their being immersed in air stream will be
negligible.
Basic soil temperature at 3 m depth was measured using a separate vertical probe, of
the type described in detail by Sharan and Jadhav (2003). The Probe was in place just one
meter away from the pipe entrance.
Fan House
Blower, motor and controls are placed inside a over-ground fan house. Fan is direct drive
industrial type 0.5 hp blower with radial blades. It is custom built to provide air flow rate
of 5.6 m3
/min at 25 mm static water pressure. Fan housing is insulated to prevent motor
heat from entering. Motor rating is 400 watts. Actual energy used during operations
was measured independently, using an energy meter.
Cooling Mode Tests
The air velocity was 11 m/s. Velocity was measured by a portable, digital vane type
anemometer (Thermo-Anemometer, PROVA Instruments). The vane size is 66 x 132 x
29.2 mm and velocity range 0.3 to 45 m/s. The anemometer measures mean air
velocity. The volume flow rate of air was 0.0863 m3
/s and mass flow rate 0.0975 kg/s.
The ETHE system was operated for seven hours a day for three consecutive days of each
month. The tube air temperature at the inlet, middle and outlet, and soil temperature
at 3-meter depth were noted at the interval of one hour. System was turned on at 10.00
AM and shut down at 5 PM. Tests in May were carried out on 28th
, 29th
, and 30th
(2000).
7
The ambient temperature on these three days was very similar. The results of the three
days were therefore averaged. Table-1 shows the data, which is mean of the three days.
Figure-3 shows the data graphically.
The ambient temperature started with 31.3o
C at 10.00 AM and rose to a maximum of
40.8o
C at 2 PM. The temperature of air at outlet was 26.8o
C ;as the system started and
rose only slightly to 27.2o
C at which it stayed through the 7 hour of test run. The outlet
temperature was just above the basic soil temperature (26.6o
C) at 3 m depth, suggesting
that the tube was exchanging heat quite effectively. As can be seen from the table most
of the cooling occurred in the first half of the tube (25 m). At 2 PM, air temperature
reduced from 40.8o
C to 29.7o
C by the middle (25 m), i.e. by 11.1o
C. In the next 25 the
further reduction was only 2.5o
C. This is expected, because as the difference between air
temperature and that of the soil reduces, heat transfer rates are reduced.
Coefficient of Performance (COP)
Coefficient of performance is one of the measures of heat exchanger efficiency. It is
defined as (ASHRAE 1985)
cp Specific heat of air ( J / kg o
C )
inW
outQ
COP
•
•
=
)blowerbyusedenergy(exchangerheattheintoinputenergyofRate
soilcoolerandairhotbetweenexchangedisheatat whichRate
in
out
W
Q
•
•
)TT(Cmout
Q oipa −=
• •
)s/kg(airofrateflowMassma
•
8
Ti Temperature of air entering the tube ( o
C )
To Temprature of air at the outlet ( o
C )
Ti and To are both treated as bulk temperatures, independent of radial variation. This is
realistic, pipe diameter being only 10 cm.
Energy input into the heat exchanger is just the energy used by the blower (300 w). In
the first hour of operation (10.00 - 11.00 AM ) the ambient air temperature rose from
31.3o
C to 33.7o
C. The mean of this works out to 32.5o
C. We shall assume this to be, Ti,
during this first hour. Properties of air used in computation relate to temperature of
35o
C.
Hourly, values of COP are shown in Table-1. COP value was 1.73 at the start, rising to
a maximum of 4.4 at 2 PM, when the ambient temperature was at peak. Mean value of
COP over the test run of 7 hours is 3.3.
Baxter presented detailed analysis of ETHE performance during three weekly periods --
first week of June, third week of July and last week of August. These represent periods
where high ambient temperatures prevail and cooling is greatly needed. During these
periods the value of COP in the hours of high energy exchange (day time when ambient
temperatures were high) ranged from 4.37 to 6.31. The mean hourly values for the entire
73.1
300
)26.832.5(x1007x0.0975
COP
=
−
=
9
period of test ranged from 1.4 to 2.69. During these periods basic soil temperature varied
from 14.8o
C to 18.2o
C. The maximum ambient temperature varied from 33.9o
C to
35.6 o
C. The cooling effected in the three weekly periods was 8.3 o
C, 8.9o
C and 5o
C.
Heating Mode Tests
Heating mode tests were carried out for three nights of January 2000 (28th
, 29th
, & 30th
).
The system was turned on at 6 PM and operated for 12 hours continuously, till 6 AM next
day. Temperature readings were noted at hourly interval. Here also the conditions on the
three consecutive nights were similar and therefore the results combined. Table 2 shows
the data, which is the mean of three test runs. Fig. 4 shows the same data graphically.
The ambient temperature started at 23.6o
C (5 PM), falling to the lowest value 8.3o
C at 2
AM. Thereafter it began to rise again and was 9.8o
C at 6 AM when the test was closed.
Basic soil temperature at 3 m depth was constant at 24.2o
C. Temperature of the air at the
outlet stayed virtually constant at 23o
C; varying from 22.8o
C to 23.3o
C. ETHE was able
to raise the ambient air temperature at 2 AM from 8.3o
C to 23o
C or by 14.7o
C. The table
also shows the COP values. The mean hourly COP is 3.8. The greatest hourly values of
COP in heating mode reported by Baxter ranged from 3.2 to 10.3. Mean hourly value
over the entire period of test ranged from 1.6 to 4.2.
As stated earlier, the tests were conducted for three days of each month. For reasons of
space, all results are not presented in detail. But a summary is given in Table-3 showing
basic results of each month.
10
Summary and Conclusion
A single pass earth-tube heat exchanger (ETHE) was installed to study its performance in
cooling and heating mode. ETHE is made of 50 m long ms pipe of 10 cm nominal
diameter and 3 mm wall thickness. ETHE is buried 3 m deep below surface. A 400 w
blower pumps ambient air through it. Air velocity in the pipe is 11 m/s.
ETHE was able to reduce the temperature of hot ambient air by as much as 14o
C in
May. The basic soil temperature in May was 26.6o
C. It was able to warm up the cold
ambient air by a similar amount in the nights of January. The basic soil temperature in
January was 24.2o
C.
The coefficient of performance (COP) in cooling mode averaged to 3.3. Cooling tests
were of 7 hour continuous duration during the day. In heating mode it averaged to 3.8.
Heating tests were of 14 hour continuous duration through the night.
Based on the results it can be stated that ETHE holds considerable promise as a means to
cool or heat ambient air for a variety of applications such as the livestock buildings and
greenhouses.
Acknowledgement
This facility was built and study carried out by grants from Gujarat Energy Development
Agency (GEDA), Vadodara and the Ministry of Agriculture, New Delhi.
11
Table 1: Air Temperature inside ETHE and
Soil Temperature ( MAY )
Time Ta Ts Tmd To COP
10:00 31.3 26.6 29.1 26.8 1.73
11:00 33.7 26.6 29.2 26.8 2.6
12:00 36.4 26.6 29.5 27.2 3.2
13:00 37.8 26.6 29.5 27.2 3.9
14:00 40.8 26.6 29.7 27.2 4.4
15:00 40.4 26.6 29.7 27.2 4.2
16:00 39.8 26.6 29.8 27.2 4.1
17.00 39.6 26.5 30 27.2 4.0
Values are mean of three consecutive days of tests (28,29,30 May)
12
Table 2 : Air Temperature inside ETHE and
Soil Temperature ( JANUARY )
Time Ta Ts Tmd To COP
18:00 19.8 24.2 22.3 23.4 1.5
19:00 17.6 24.2 22.2 23.4 2.6
20:00 13.3 24.2 22.1 23.3 3.5
21:00 11.9 24.2 21.9 23.3 3.4
22:00 10.4 24.2 21.8 23.3 4.3
23:00 9.6 24.2 21.7 23.3 4.5
0:00 9.1 24.2 21.6 23.2 4.6
1:00 8.7 24.2 21.5 23.2 4.7
2:00 8.3 24.2 21.5 23.0 5.0
3:00 8.7 24.2 21.4 23.0 4.5
4:00 9.1 24.2 21.3 22.9 4.4
5:00 9.6 24.2 21.2 22.9 4.3
6:00 9.8 24.2 21.2 22.8 4.2
Values are mean of three consecutive nights of tests (28,29,30 Jan.)
13
Table 3 : Summary of Cooling Test Results
Month Ambient Temperature
At 14 hours (o
C)
Basic Soil
Temperature
Ts (o
C)
Outlet Temperature
At 14 hours (o
C)
January Heating test
February 37.9 25.2 26.4
March 39.4 25.8 26.4
April 41.4 26.6 28.0
May 40.8 26.6 27.2
June 37.5 29.8 31.9
July No test due to rain - -
August No test due to rain - -
September 39.1 28.9 30.0
October 34.8 25.6 26.2
November 30.6 24.2 24.2
December 30.7 24.4 24.4
Values are mean of three consecutive days of test in each month.
14
Figure-1 :
15
Figure-2 : Thermister Assembly
2.5 cm dia riser
10 cm
Coupler
Leads
Thermister
Acralic
Stripe
Section A - A
Figure-3:AirtemperatureinsideETHEandsoiltemperature (May)
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
10:00 11:00 12:00 13:00 14:00 15:00 16:00
HourofDay
Temperature(0C)
Ta Ts
Tmd To
2
Figure-4: Airtemperatureinside ETHEandsoil temperature(January)
0.0
5.0
10.0
15.0
20.0
25.0
30.0
17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00 1:00 2:00 3:00 4:00 5:00 6:00 7:00
Hourof Day
Temperature(0C)
Ta Ts
Tmd To
References
Sharan G. and Jadhav R. (2003). Soil temperature regime at Ahmedabad. Journal of
Agricultural Engineering . (forthcoming)
Scott N.R.; Parsons R.A. and Kochler T.A. (1965). Analysis and performance of an
earth-tube heat exchanger. ASAE paper no.65-840. St. Joseph, Michigan, ASAE.
Spengler R. W. and Stombaugh D.P (1983). Optimization of earth-tube heat exchanger
for winter ventilation of swine housing. Trans ASAE, pp 1186 - 1193.
Santamouris M., Mihalakaha G. Balaras C.A. Argirioua Asimakopoulos D. and
Vallinaras M. (1995). Use of Buried pipes for energy conservation in cooling of
agricultural greenhouse. Solar Energy. Vol. 35 PP 111-124
Baxter, D.O. (1992) Energy exchange and related temperature of an earth-tube heat
exchanger in heating mode. Trans ASAE, 35 (1) : 275 - 285.
Baxter, D.O. (1994). Energy exchange and related temperature of an earth-tube heat
exchanger in cooling mode. Trans ASAE, 37 (1) : 257 - 267.
Puri V.M. (1986). Feasibility and performance curves for intermittent earth-tube heat
exchangers. Trans ASAE, 29(2). March-April, pp.526-532.
Goswamy D.Y. and Dhaliwal A.S. (1985). Heat transfer analysis in environmental
control using an underground air tunnel. Journal of Solar Energy Engineering, vol.107,
pp.141-145.
Sawhnay R.L, Budhi D. and Thanu N.M. (1998). An experimental study of summer
performance of a recirculation type underground air-pipe air conditioning system,
Building and Environment, 34, pp 189 - 196.
Sharan G.; Sahu R.K. and Jadhav R. (2001). Earth-tube heat exchanger based air-
conditioning for tiger dwellings. Zoos' Print, 16:5, May (RNI 2:8).
ASHRAE (1985). Handbook of application. Atlanta Ga. American Society of Heating
Refrigerating and Air Conditioning engineers Inc.

More Related Content

What's hot

Effect of artificial roughness on Thermal and Thermohydraulic efficiency in R...
Effect of artificial roughness on Thermal and Thermohydraulic efficiency in R...Effect of artificial roughness on Thermal and Thermohydraulic efficiency in R...
Effect of artificial roughness on Thermal and Thermohydraulic efficiency in R...IJMER
 
Experimental study of the structure of a thermal plume inside a rectangular t...
Experimental study of the structure of a thermal plume inside a rectangular t...Experimental study of the structure of a thermal plume inside a rectangular t...
Experimental study of the structure of a thermal plume inside a rectangular t...IOSR Journals
 
microclimatic modeling and analysis of a fog cooled naturally ventilated gree...
microclimatic modeling and analysis of a fog cooled naturally ventilated gree...microclimatic modeling and analysis of a fog cooled naturally ventilated gree...
microclimatic modeling and analysis of a fog cooled naturally ventilated gree...IJEAB
 
Experimental investigation on the effect of fin pitch on the performance of p...
Experimental investigation on the effect of fin pitch on the performance of p...Experimental investigation on the effect of fin pitch on the performance of p...
Experimental investigation on the effect of fin pitch on the performance of p...eSAT Publishing House
 
Thermal Performance Analysis for Optimal Passive Cooling Heat Sink Design
Thermal Performance Analysis for Optimal Passive Cooling Heat Sink DesignThermal Performance Analysis for Optimal Passive Cooling Heat Sink Design
Thermal Performance Analysis for Optimal Passive Cooling Heat Sink DesignTELKOMNIKA JOURNAL
 
Air Conditioning System with Ground Source Heat Exchanger
Air Conditioning System with Ground Source Heat ExchangerAir Conditioning System with Ground Source Heat Exchanger
Air Conditioning System with Ground Source Heat ExchangerIOSR Journals
 
Cold weather destratification energy savings of a warehousing facility.
Cold weather destratification energy savings of a warehousing facility.Cold weather destratification energy savings of a warehousing facility.
Cold weather destratification energy savings of a warehousing facility.accidentaltorpo90
 
A Thesis on Design Optimization of Heat Sink in Power Electronics
A Thesis on Design Optimization of Heat Sink in Power ElectronicsA Thesis on Design Optimization of Heat Sink in Power Electronics
A Thesis on Design Optimization of Heat Sink in Power ElectronicsIJERA Editor
 
15. experimental investigation of heat transfer characteristics of
15. experimental investigation of heat transfer characteristics of15. experimental investigation of heat transfer characteristics of
15. experimental investigation of heat transfer characteristics ofNEERAJKUMAR1898
 
IRJET- Experiment Investigation of Heat Transfer Rate of Fins with Blind Hole...
IRJET- Experiment Investigation of Heat Transfer Rate of Fins with Blind Hole...IRJET- Experiment Investigation of Heat Transfer Rate of Fins with Blind Hole...
IRJET- Experiment Investigation of Heat Transfer Rate of Fins with Blind Hole...IRJET Journal
 
Heat transfer augmentation in different geometries of dimpled surface under n...
Heat transfer augmentation in different geometries of dimpled surface under n...Heat transfer augmentation in different geometries of dimpled surface under n...
Heat transfer augmentation in different geometries of dimpled surface under n...eSAT Publishing House
 
Heat transfer augmentation in different geometries of dimpled surface under n...
Heat transfer augmentation in different geometries of dimpled surface under n...Heat transfer augmentation in different geometries of dimpled surface under n...
Heat transfer augmentation in different geometries of dimpled surface under n...eSAT Journals
 
Chap5 space heat load calculations
Chap5 space heat load  calculationsChap5 space heat load  calculations
Chap5 space heat load calculationsCharlton Inao
 

What's hot (18)

Effect of artificial roughness on Thermal and Thermohydraulic efficiency in R...
Effect of artificial roughness on Thermal and Thermohydraulic efficiency in R...Effect of artificial roughness on Thermal and Thermohydraulic efficiency in R...
Effect of artificial roughness on Thermal and Thermohydraulic efficiency in R...
 
Experimental study of the structure of a thermal plume inside a rectangular t...
Experimental study of the structure of a thermal plume inside a rectangular t...Experimental study of the structure of a thermal plume inside a rectangular t...
Experimental study of the structure of a thermal plume inside a rectangular t...
 
microclimatic modeling and analysis of a fog cooled naturally ventilated gree...
microclimatic modeling and analysis of a fog cooled naturally ventilated gree...microclimatic modeling and analysis of a fog cooled naturally ventilated gree...
microclimatic modeling and analysis of a fog cooled naturally ventilated gree...
 
20320140502007
2032014050200720320140502007
20320140502007
 
Ld35191119013
Ld35191119013Ld35191119013
Ld35191119013
 
Experimental investigation on the effect of fin pitch on the performance of p...
Experimental investigation on the effect of fin pitch on the performance of p...Experimental investigation on the effect of fin pitch on the performance of p...
Experimental investigation on the effect of fin pitch on the performance of p...
 
Thermal Performance Analysis for Optimal Passive Cooling Heat Sink Design
Thermal Performance Analysis for Optimal Passive Cooling Heat Sink DesignThermal Performance Analysis for Optimal Passive Cooling Heat Sink Design
Thermal Performance Analysis for Optimal Passive Cooling Heat Sink Design
 
235 r. sengupta
235 r. sengupta235 r. sengupta
235 r. sengupta
 
Air Conditioning System with Ground Source Heat Exchanger
Air Conditioning System with Ground Source Heat ExchangerAir Conditioning System with Ground Source Heat Exchanger
Air Conditioning System with Ground Source Heat Exchanger
 
Cold weather destratification energy savings of a warehousing facility.
Cold weather destratification energy savings of a warehousing facility.Cold weather destratification energy savings of a warehousing facility.
Cold weather destratification energy savings of a warehousing facility.
 
A Thesis on Design Optimization of Heat Sink in Power Electronics
A Thesis on Design Optimization of Heat Sink in Power ElectronicsA Thesis on Design Optimization of Heat Sink in Power Electronics
A Thesis on Design Optimization of Heat Sink in Power Electronics
 
15. experimental investigation of heat transfer characteristics of
15. experimental investigation of heat transfer characteristics of15. experimental investigation of heat transfer characteristics of
15. experimental investigation of heat transfer characteristics of
 
A43010109
A43010109A43010109
A43010109
 
IRJET- Experiment Investigation of Heat Transfer Rate of Fins with Blind Hole...
IRJET- Experiment Investigation of Heat Transfer Rate of Fins with Blind Hole...IRJET- Experiment Investigation of Heat Transfer Rate of Fins with Blind Hole...
IRJET- Experiment Investigation of Heat Transfer Rate of Fins with Blind Hole...
 
Heat transfer augmentation in different geometries of dimpled surface under n...
Heat transfer augmentation in different geometries of dimpled surface under n...Heat transfer augmentation in different geometries of dimpled surface under n...
Heat transfer augmentation in different geometries of dimpled surface under n...
 
Heat transfer augmentation in different geometries of dimpled surface under n...
Heat transfer augmentation in different geometries of dimpled surface under n...Heat transfer augmentation in different geometries of dimpled surface under n...
Heat transfer augmentation in different geometries of dimpled surface under n...
 
Fm35978984
Fm35978984Fm35978984
Fm35978984
 
Chap5 space heat load calculations
Chap5 space heat load  calculationsChap5 space heat load  calculations
Chap5 space heat load calculations
 

Similar to Earth tubes2003 01-07 girjasharan

Comparative Study of Transient Conditions for Continuous Operation and Interm...
Comparative Study of Transient Conditions for Continuous Operation and Interm...Comparative Study of Transient Conditions for Continuous Operation and Interm...
Comparative Study of Transient Conditions for Continuous Operation and Interm...IRJET Journal
 
Comparative Study of Transient Conditions for Continuous Operation and Interm...
Comparative Study of Transient Conditions for Continuous Operation and Interm...Comparative Study of Transient Conditions for Continuous Operation and Interm...
Comparative Study of Transient Conditions for Continuous Operation and Interm...IRJET Journal
 
CFD Base Performance Evaluation of Earth-Air Tube Heat Exchanger for Natural ...
CFD Base Performance Evaluation of Earth-Air Tube Heat Exchanger for Natural ...CFD Base Performance Evaluation of Earth-Air Tube Heat Exchanger for Natural ...
CFD Base Performance Evaluation of Earth-Air Tube Heat Exchanger for Natural ...journal ijrtem
 
Experimental analysis of solar water heater using porous medium and agitator
Experimental analysis of solar water heater using porous medium and agitatorExperimental analysis of solar water heater using porous medium and agitator
Experimental analysis of solar water heater using porous medium and agitatorIAEME Publication
 
Heat transfer case study
Heat transfer case studyHeat transfer case study
Heat transfer case studyMANI SINGH
 
Experimental Investigation of Natural Convection Heat Transfer Enhancement fr...
Experimental Investigation of Natural Convection Heat Transfer Enhancement fr...Experimental Investigation of Natural Convection Heat Transfer Enhancement fr...
Experimental Investigation of Natural Convection Heat Transfer Enhancement fr...IRJET Journal
 
A Study of Thermoacoustic Refrigeration System
A Study of Thermoacoustic Refrigeration SystemA Study of Thermoacoustic Refrigeration System
A Study of Thermoacoustic Refrigeration SystemCarnegie Mellon University
 
EXPERMENTATIONAL DATA ANALYSIS OF CHIMNEY OPERATED SOLAR POWER PLANT
EXPERMENTATIONAL DATA ANALYSIS OF CHIMNEY OPERATED SOLAR POWER PLANTEXPERMENTATIONAL DATA ANALYSIS OF CHIMNEY OPERATED SOLAR POWER PLANT
EXPERMENTATIONAL DATA ANALYSIS OF CHIMNEY OPERATED SOLAR POWER PLANTIAEME Publication
 
HEAT TRANSFER AND FLOW FRICTION CHARACTERISTICS OF SOLAR WATER HEATER WITH IN...
HEAT TRANSFER AND FLOW FRICTION CHARACTERISTICS OF SOLAR WATER HEATER WITH IN...HEAT TRANSFER AND FLOW FRICTION CHARACTERISTICS OF SOLAR WATER HEATER WITH IN...
HEAT TRANSFER AND FLOW FRICTION CHARACTERISTICS OF SOLAR WATER HEATER WITH IN...IAEME Publication
 
Design of active winter cooling system
Design of active winter cooling systemDesign of active winter cooling system
Design of active winter cooling systemAjay Singh Lodhi
 
Finite Volume Analysis of Swirl Flow Diffuser at Variable Swirl Angle and Dif...
Finite Volume Analysis of Swirl Flow Diffuser at Variable Swirl Angle and Dif...Finite Volume Analysis of Swirl Flow Diffuser at Variable Swirl Angle and Dif...
Finite Volume Analysis of Swirl Flow Diffuser at Variable Swirl Angle and Dif...IJSRD
 
thermo-acoustic-refrigeration.pptx
thermo-acoustic-refrigeration.pptxthermo-acoustic-refrigeration.pptx
thermo-acoustic-refrigeration.pptxTECHNICALEDUCATIONMY
 

Similar to Earth tubes2003 01-07 girjasharan (20)

Comparative Study of Transient Conditions for Continuous Operation and Interm...
Comparative Study of Transient Conditions for Continuous Operation and Interm...Comparative Study of Transient Conditions for Continuous Operation and Interm...
Comparative Study of Transient Conditions for Continuous Operation and Interm...
 
Comparative Study of Transient Conditions for Continuous Operation and Interm...
Comparative Study of Transient Conditions for Continuous Operation and Interm...Comparative Study of Transient Conditions for Continuous Operation and Interm...
Comparative Study of Transient Conditions for Continuous Operation and Interm...
 
CFD Base Performance Evaluation of Earth-Air Tube Heat Exchanger for Natural ...
CFD Base Performance Evaluation of Earth-Air Tube Heat Exchanger for Natural ...CFD Base Performance Evaluation of Earth-Air Tube Heat Exchanger for Natural ...
CFD Base Performance Evaluation of Earth-Air Tube Heat Exchanger for Natural ...
 
FINAL_POSTER
FINAL_POSTERFINAL_POSTER
FINAL_POSTER
 
Dana Gilbert - second year lab report
Dana Gilbert - second year lab reportDana Gilbert - second year lab report
Dana Gilbert - second year lab report
 
B04120610
B04120610B04120610
B04120610
 
Experimental analysis of solar water heater using porous medium and agitator
Experimental analysis of solar water heater using porous medium and agitatorExperimental analysis of solar water heater using porous medium and agitator
Experimental analysis of solar water heater using porous medium and agitator
 
Heat transfer case study
Heat transfer case studyHeat transfer case study
Heat transfer case study
 
As4101256260
As4101256260As4101256260
As4101256260
 
Experimental Investigation of Natural Convection Heat Transfer Enhancement fr...
Experimental Investigation of Natural Convection Heat Transfer Enhancement fr...Experimental Investigation of Natural Convection Heat Transfer Enhancement fr...
Experimental Investigation of Natural Convection Heat Transfer Enhancement fr...
 
A Study of Thermoacoustic Refrigeration System
A Study of Thermoacoustic Refrigeration SystemA Study of Thermoacoustic Refrigeration System
A Study of Thermoacoustic Refrigeration System
 
EXPERMENTATIONAL DATA ANALYSIS OF CHIMNEY OPERATED SOLAR POWER PLANT
EXPERMENTATIONAL DATA ANALYSIS OF CHIMNEY OPERATED SOLAR POWER PLANTEXPERMENTATIONAL DATA ANALYSIS OF CHIMNEY OPERATED SOLAR POWER PLANT
EXPERMENTATIONAL DATA ANALYSIS OF CHIMNEY OPERATED SOLAR POWER PLANT
 
HEAT TRANSFER AND FLOW FRICTION CHARACTERISTICS OF SOLAR WATER HEATER WITH IN...
HEAT TRANSFER AND FLOW FRICTION CHARACTERISTICS OF SOLAR WATER HEATER WITH IN...HEAT TRANSFER AND FLOW FRICTION CHARACTERISTICS OF SOLAR WATER HEATER WITH IN...
HEAT TRANSFER AND FLOW FRICTION CHARACTERISTICS OF SOLAR WATER HEATER WITH IN...
 
30120140504003
3012014050400330120140504003
30120140504003
 
IJERA
IJERAIJERA
IJERA
 
Design of active winter cooling system
Design of active winter cooling systemDesign of active winter cooling system
Design of active winter cooling system
 
Finite Volume Analysis of Swirl Flow Diffuser at Variable Swirl Angle and Dif...
Finite Volume Analysis of Swirl Flow Diffuser at Variable Swirl Angle and Dif...Finite Volume Analysis of Swirl Flow Diffuser at Variable Swirl Angle and Dif...
Finite Volume Analysis of Swirl Flow Diffuser at Variable Swirl Angle and Dif...
 
thermo-acoustic-refrigeration.pptx
thermo-acoustic-refrigeration.pptxthermo-acoustic-refrigeration.pptx
thermo-acoustic-refrigeration.pptx
 
E012142024
E012142024E012142024
E012142024
 
20120140505012
2012014050501220120140505012
20120140505012
 

Recently uploaded

Andreas Schleicher presents at the launch of What does child empowerment mean...
Andreas Schleicher presents at the launch of What does child empowerment mean...Andreas Schleicher presents at the launch of What does child empowerment mean...
Andreas Schleicher presents at the launch of What does child empowerment mean...EduSkills OECD
 
Climbers and Creepers used in landscaping
Climbers and Creepers used in landscapingClimbers and Creepers used in landscaping
Climbers and Creepers used in landscapingDr. M. Kumaresan Hort.
 
The Story of Village Palampur Class 9 Free Study Material PDF
The Story of Village Palampur Class 9 Free Study Material PDFThe Story of Village Palampur Class 9 Free Study Material PDF
The Story of Village Palampur Class 9 Free Study Material PDFVivekanand Anglo Vedic Academy
 
TỔNG HỢP HƠN 100 ĐỀ THI THỬ TỐT NGHIỆP THPT TOÁN 2024 - TỪ CÁC TRƯỜNG, TRƯỜNG...
TỔNG HỢP HƠN 100 ĐỀ THI THỬ TỐT NGHIỆP THPT TOÁN 2024 - TỪ CÁC TRƯỜNG, TRƯỜNG...TỔNG HỢP HƠN 100 ĐỀ THI THỬ TỐT NGHIỆP THPT TOÁN 2024 - TỪ CÁC TRƯỜNG, TRƯỜNG...
TỔNG HỢP HƠN 100 ĐỀ THI THỬ TỐT NGHIỆP THPT TOÁN 2024 - TỪ CÁC TRƯỜNG, TRƯỜNG...Nguyen Thanh Tu Collection
 
Stl Algorithms in C++ jjjjjjjjjjjjjjjjjj
Stl Algorithms in C++ jjjjjjjjjjjjjjjjjjStl Algorithms in C++ jjjjjjjjjjjjjjjjjj
Stl Algorithms in C++ jjjjjjjjjjjjjjjjjjMohammed Sikander
 
The Liver & Gallbladder (Anatomy & Physiology).pptx
The Liver &  Gallbladder (Anatomy & Physiology).pptxThe Liver &  Gallbladder (Anatomy & Physiology).pptx
The Liver & Gallbladder (Anatomy & Physiology).pptxVishal Singh
 
Major project report on Tata Motors and its marketing strategies
Major project report on Tata Motors and its marketing strategiesMajor project report on Tata Motors and its marketing strategies
Major project report on Tata Motors and its marketing strategiesAmanpreetKaur157993
 
ANTI PARKISON DRUGS.pptx
ANTI         PARKISON          DRUGS.pptxANTI         PARKISON          DRUGS.pptx
ANTI PARKISON DRUGS.pptxPoojaSen20
 
Spring gala 2024 photo slideshow - Celebrating School-Community Partnerships
Spring gala 2024 photo slideshow - Celebrating School-Community PartnershipsSpring gala 2024 photo slideshow - Celebrating School-Community Partnerships
Spring gala 2024 photo slideshow - Celebrating School-Community Partnershipsexpandedwebsite
 
Transparency, Recognition and the role of eSealing - Ildiko Mazar and Koen No...
Transparency, Recognition and the role of eSealing - Ildiko Mazar and Koen No...Transparency, Recognition and the role of eSealing - Ildiko Mazar and Koen No...
Transparency, Recognition and the role of eSealing - Ildiko Mazar and Koen No...EADTU
 
24 ĐỀ THAM KHẢO KÌ THI TUYỂN SINH VÀO LỚP 10 MÔN TIẾNG ANH SỞ GIÁO DỤC HẢI DƯ...
24 ĐỀ THAM KHẢO KÌ THI TUYỂN SINH VÀO LỚP 10 MÔN TIẾNG ANH SỞ GIÁO DỤC HẢI DƯ...24 ĐỀ THAM KHẢO KÌ THI TUYỂN SINH VÀO LỚP 10 MÔN TIẾNG ANH SỞ GIÁO DỤC HẢI DƯ...
24 ĐỀ THAM KHẢO KÌ THI TUYỂN SINH VÀO LỚP 10 MÔN TIẾNG ANH SỞ GIÁO DỤC HẢI DƯ...Nguyen Thanh Tu Collection
 
How to Send Pro Forma Invoice to Your Customers in Odoo 17
How to Send Pro Forma Invoice to Your Customers in Odoo 17How to Send Pro Forma Invoice to Your Customers in Odoo 17
How to Send Pro Forma Invoice to Your Customers in Odoo 17Celine George
 
Đề tieng anh thpt 2024 danh cho cac ban hoc sinh
Đề tieng anh thpt 2024 danh cho cac ban hoc sinhĐề tieng anh thpt 2024 danh cho cac ban hoc sinh
Đề tieng anh thpt 2024 danh cho cac ban hoc sinhleson0603
 
UChicago CMSC 23320 - The Best Commit Messages of 2024
UChicago CMSC 23320 - The Best Commit Messages of 2024UChicago CMSC 23320 - The Best Commit Messages of 2024
UChicago CMSC 23320 - The Best Commit Messages of 2024Borja Sotomayor
 
Improved Approval Flow in Odoo 17 Studio App
Improved Approval Flow in Odoo 17 Studio AppImproved Approval Flow in Odoo 17 Studio App
Improved Approval Flow in Odoo 17 Studio AppCeline George
 
When Quality Assurance Meets Innovation in Higher Education - Report launch w...
When Quality Assurance Meets Innovation in Higher Education - Report launch w...When Quality Assurance Meets Innovation in Higher Education - Report launch w...
When Quality Assurance Meets Innovation in Higher Education - Report launch w...Gary Wood
 
An overview of the various scriptures in Hinduism
An overview of the various scriptures in HinduismAn overview of the various scriptures in Hinduism
An overview of the various scriptures in HinduismDabee Kamal
 
Analyzing and resolving a communication crisis in Dhaka textiles LTD.pptx
Analyzing and resolving a communication crisis in Dhaka textiles LTD.pptxAnalyzing and resolving a communication crisis in Dhaka textiles LTD.pptx
Analyzing and resolving a communication crisis in Dhaka textiles LTD.pptxLimon Prince
 
How To Create Editable Tree View in Odoo 17
How To Create Editable Tree View in Odoo 17How To Create Editable Tree View in Odoo 17
How To Create Editable Tree View in Odoo 17Celine George
 

Recently uploaded (20)

Andreas Schleicher presents at the launch of What does child empowerment mean...
Andreas Schleicher presents at the launch of What does child empowerment mean...Andreas Schleicher presents at the launch of What does child empowerment mean...
Andreas Schleicher presents at the launch of What does child empowerment mean...
 
Climbers and Creepers used in landscaping
Climbers and Creepers used in landscapingClimbers and Creepers used in landscaping
Climbers and Creepers used in landscaping
 
The Story of Village Palampur Class 9 Free Study Material PDF
The Story of Village Palampur Class 9 Free Study Material PDFThe Story of Village Palampur Class 9 Free Study Material PDF
The Story of Village Palampur Class 9 Free Study Material PDF
 
TỔNG HỢP HƠN 100 ĐỀ THI THỬ TỐT NGHIỆP THPT TOÁN 2024 - TỪ CÁC TRƯỜNG, TRƯỜNG...
TỔNG HỢP HƠN 100 ĐỀ THI THỬ TỐT NGHIỆP THPT TOÁN 2024 - TỪ CÁC TRƯỜNG, TRƯỜNG...TỔNG HỢP HƠN 100 ĐỀ THI THỬ TỐT NGHIỆP THPT TOÁN 2024 - TỪ CÁC TRƯỜNG, TRƯỜNG...
TỔNG HỢP HƠN 100 ĐỀ THI THỬ TỐT NGHIỆP THPT TOÁN 2024 - TỪ CÁC TRƯỜNG, TRƯỜNG...
 
Stl Algorithms in C++ jjjjjjjjjjjjjjjjjj
Stl Algorithms in C++ jjjjjjjjjjjjjjjjjjStl Algorithms in C++ jjjjjjjjjjjjjjjjjj
Stl Algorithms in C++ jjjjjjjjjjjjjjjjjj
 
The Liver & Gallbladder (Anatomy & Physiology).pptx
The Liver &  Gallbladder (Anatomy & Physiology).pptxThe Liver &  Gallbladder (Anatomy & Physiology).pptx
The Liver & Gallbladder (Anatomy & Physiology).pptx
 
Major project report on Tata Motors and its marketing strategies
Major project report on Tata Motors and its marketing strategiesMajor project report on Tata Motors and its marketing strategies
Major project report on Tata Motors and its marketing strategies
 
ANTI PARKISON DRUGS.pptx
ANTI         PARKISON          DRUGS.pptxANTI         PARKISON          DRUGS.pptx
ANTI PARKISON DRUGS.pptx
 
Spring gala 2024 photo slideshow - Celebrating School-Community Partnerships
Spring gala 2024 photo slideshow - Celebrating School-Community PartnershipsSpring gala 2024 photo slideshow - Celebrating School-Community Partnerships
Spring gala 2024 photo slideshow - Celebrating School-Community Partnerships
 
Transparency, Recognition and the role of eSealing - Ildiko Mazar and Koen No...
Transparency, Recognition and the role of eSealing - Ildiko Mazar and Koen No...Transparency, Recognition and the role of eSealing - Ildiko Mazar and Koen No...
Transparency, Recognition and the role of eSealing - Ildiko Mazar and Koen No...
 
24 ĐỀ THAM KHẢO KÌ THI TUYỂN SINH VÀO LỚP 10 MÔN TIẾNG ANH SỞ GIÁO DỤC HẢI DƯ...
24 ĐỀ THAM KHẢO KÌ THI TUYỂN SINH VÀO LỚP 10 MÔN TIẾNG ANH SỞ GIÁO DỤC HẢI DƯ...24 ĐỀ THAM KHẢO KÌ THI TUYỂN SINH VÀO LỚP 10 MÔN TIẾNG ANH SỞ GIÁO DỤC HẢI DƯ...
24 ĐỀ THAM KHẢO KÌ THI TUYỂN SINH VÀO LỚP 10 MÔN TIẾNG ANH SỞ GIÁO DỤC HẢI DƯ...
 
How to Send Pro Forma Invoice to Your Customers in Odoo 17
How to Send Pro Forma Invoice to Your Customers in Odoo 17How to Send Pro Forma Invoice to Your Customers in Odoo 17
How to Send Pro Forma Invoice to Your Customers in Odoo 17
 
Đề tieng anh thpt 2024 danh cho cac ban hoc sinh
Đề tieng anh thpt 2024 danh cho cac ban hoc sinhĐề tieng anh thpt 2024 danh cho cac ban hoc sinh
Đề tieng anh thpt 2024 danh cho cac ban hoc sinh
 
Mattingly "AI & Prompt Design: Named Entity Recognition"
Mattingly "AI & Prompt Design: Named Entity Recognition"Mattingly "AI & Prompt Design: Named Entity Recognition"
Mattingly "AI & Prompt Design: Named Entity Recognition"
 
UChicago CMSC 23320 - The Best Commit Messages of 2024
UChicago CMSC 23320 - The Best Commit Messages of 2024UChicago CMSC 23320 - The Best Commit Messages of 2024
UChicago CMSC 23320 - The Best Commit Messages of 2024
 
Improved Approval Flow in Odoo 17 Studio App
Improved Approval Flow in Odoo 17 Studio AppImproved Approval Flow in Odoo 17 Studio App
Improved Approval Flow in Odoo 17 Studio App
 
When Quality Assurance Meets Innovation in Higher Education - Report launch w...
When Quality Assurance Meets Innovation in Higher Education - Report launch w...When Quality Assurance Meets Innovation in Higher Education - Report launch w...
When Quality Assurance Meets Innovation in Higher Education - Report launch w...
 
An overview of the various scriptures in Hinduism
An overview of the various scriptures in HinduismAn overview of the various scriptures in Hinduism
An overview of the various scriptures in Hinduism
 
Analyzing and resolving a communication crisis in Dhaka textiles LTD.pptx
Analyzing and resolving a communication crisis in Dhaka textiles LTD.pptxAnalyzing and resolving a communication crisis in Dhaka textiles LTD.pptx
Analyzing and resolving a communication crisis in Dhaka textiles LTD.pptx
 
How To Create Editable Tree View in Odoo 17
How To Create Editable Tree View in Odoo 17How To Create Editable Tree View in Odoo 17
How To Create Editable Tree View in Odoo 17
 

Earth tubes2003 01-07 girjasharan

  • 1. Performance of Single Pass earth-Tube Heat Exchanger: An Experimental Study Girja Sharan Professor Coordinator Cummins-IIMA Lab Centre for Mgt in Agriculture Indian Institute of Management, Ahmedabad Ratan Jadhav Project Officer SEWA Ahmedabad Abstract A single pass earth-tube heat exchanger (ETHE) was installed to study its performance in cooling and heating mode. ETHE is made of 50 m long ms pipe of 10 cm nominal diameter and 3 mm wall thickness. ETHE is buried 3 m deep below surface. Ambient air is pumped through it by a 400 w blower. Air velocity in the pipe is 11 m/s. Air temperature is measured at the inlet of the pipe, in the middle (25 m), and at the outlet (50 m), by thermisters placed inside the pipe. Cooling tests were carried out three consecutive days in each month. On each day system was operated for 7 hours during the day and shut down for the night. Heating tests were carried out at night in January. Test results are presented in summary form for each month. Detailed analysis is presented for two months only -- May for cooling and January for heating. ETHE cools the ambient air in May by as much as 14o C. It heats the ambient air in January nights also by similar amount. Key Words : Earth Tube Heat Exchanger, air tunnel
  • 2. 2 Introduction We have been developing earth-tube heat exchanger (ETHE) for use in greenhouse in arid areas like Kutch. As a first step, deep soil temperature regime was studied in Ahmedabad, Sharan and Jhadav (2002). After year-long measurements they reported that the soil strata between 2m to 3m depth had stable temperature regime suitable for installation of ETHE. Temperature in this stratum displays no diurnal fluctuation. It does display annual fluctuation, but the amplitude is small. Average temperature in this stratum is 27o C As a second step one single pass ETHE was built to investigate the actual cooling and heating performance. This ETHE is made of 50m long ms pipe of 10 cm nominal diameter. It is buried 3m deep below surface. We report here the results of investigation carried out on this facility. Specific aim of those investigations is: (a) to determine the operating characteristics of ETHE in cooling and heating mode (b) to develop data base of its performance in each of the twelve months In this paper, details of the experimental facility are described. Performance data has been collected for all the twelve months, but for reasons of space only May and January results are presented and discussed in detail. May month is the hottest part of summer, January the coolest part of winter in Ahmedabad region. Basic results of tests in the remaining months of the year are however given in summary form.
  • 3. 3 Review of Literature Earth-Tube Heat Exchanger (ETHE) is a device that enables transfer of heat from ambient air to deeper layers of soil and vice versa. Since the early exploration of its use in cooling commercial livestock buildings (Scott et al 1965) there has been considerable increase in its application. ETHE is used to condition the air in livestock buildings (Spengler and Stombaugh 1983). It is used in North America and Europe to cool and heat greenhouses (Santa Mouris et al 1995). There have also been works aiming at gaining better understanding of its working in cooling and heating mode (Baxter 1992, 1994). Mathematical models of ETHE have also been developed (Puri 1985; Goswami and Dhaliwal 1985). There has also been some work in India. Sawhney et al (1998) installed a ETHE based system to cool part of a guesthouse. Sharan et al (2001) installed a ETHE based cooling system for tiger dwelling at Ahmedabad Zoological Garden. Authors have visited Tata Energy Research Institute, where a system is installed to cool rooms in its training center near Delhi. The experimental system we have built is similar to Baxter's, though smaller and less elaborately instrumented. Baxter's facility at Knoxville, Tennessee (USA) is a single pass earth-tube heat exchanger 64-m long, 15-cm diameter, made of 18- gauge spirally corrugated galvanized metal. The tube is buried at 1.8-m depth, and is elaborately instrumented with temperature sensors inside the tube and in soil around it. Air is
  • 4. 4 pumped by a high pressure industrial blower of about 572 w power. Instrumentation permits measurement of air temperature along the tube and in soil around the tube. Experimental Set-up Site The installation is on an open field at village, Thor, some 40 km from IIM, Ahmedabad campus. Soil at the site was tested at Soil Mechanics Laboratory of L.D. Engineering College, Ahmedabad and found to be sandy-silt (sand 48%, silt 41%, clay 11%). Moisture content at the time of excavation was 12.61% (d b). Experimental set-up consists of an ETHE, fan house, temperature sensors and back-up risers. A schematic diagram of the set-up is shown in figure-1. Earth-Tube Heat Exchanger ETHE consists of a 50 m long 10 cm diameter ms pipe with wall thickness of 3 mm. Especially made fins have been installed on the outer surface of the pipe, all along the 50 m length. Fins are made of thin GI strip spirally wound over the pipe and then spot- welded at several points. There are 40 fins per meter length. Strip that makes the fins is 2 cm wide, 2 mm thick. A 1 m wide, 3 m deep and 50 m long trench was first excavated by a bucket excavator. Trench floor was properly leveled and a 15 cm thick bed of sand placed on it. ETHE was then placed on it and covered with sand up to about 15 cm above it. After that trench was back-filled with the original soil. The inlet and outlet of the ETHE rise 0.5 m above ground. Inlet is connected to the delivery end of
  • 5. 5 blower and outlet is open to atmosphere. A 90 elbow at the end makes the outlet horizontal to the entry of rain water. Instrumentation It was desired to obtain air temperature in the ETHE at three location -- at the entrance, at the middle (25 m) and at the end (50 m). One thermister was installed at each of these three locations inside the tube at the center. Figure-2 shows the thermister assembly configuration. A 15 cm long 10 cm dia coupler was used to build the thermister assembly. A acrylic strip, 10 cm long (to fit snug across the inner dia of the coupler) 2 cm wide and 2 mm thick and was placed horizontally at the center in the coupler as shown. Its ends were bonded to the pipe wall with adhesive. Thermister (AD 590) was placed at the center and bonded to upper surface of the strip using a very thin layer of adhesive. Leads were taken out of the coupler via a 2 mm hole drilled on the side. Hole was then sealed to make it air tight. A 25 mm threaded hole was made on the top side of the coupler. A PVC pipe of 25 mm dia was connected to the coupler as shown. The PVC pipe was 3.5 m long. It is placed vertically and rises above the ground about 0.5 m. Upper end of the riser is normally closed with a cap. Risers were provided to act as a back-up for obtaining tube air temperature, if built in sensors failed. The leads also are taped to the outside of PVC pipe and brought above ground and connected to a digital indicator. Indicators were housed in a wooden box to protect these from weather. Three such assemblies were made. One is installed at the entrance of the ETHE, one in the middle, and one at the end. Air velocity in the pipe is not high and therefore the
  • 6. 6 convective cooling of thermisters due to their being immersed in air stream will be negligible. Basic soil temperature at 3 m depth was measured using a separate vertical probe, of the type described in detail by Sharan and Jadhav (2003). The Probe was in place just one meter away from the pipe entrance. Fan House Blower, motor and controls are placed inside a over-ground fan house. Fan is direct drive industrial type 0.5 hp blower with radial blades. It is custom built to provide air flow rate of 5.6 m3 /min at 25 mm static water pressure. Fan housing is insulated to prevent motor heat from entering. Motor rating is 400 watts. Actual energy used during operations was measured independently, using an energy meter. Cooling Mode Tests The air velocity was 11 m/s. Velocity was measured by a portable, digital vane type anemometer (Thermo-Anemometer, PROVA Instruments). The vane size is 66 x 132 x 29.2 mm and velocity range 0.3 to 45 m/s. The anemometer measures mean air velocity. The volume flow rate of air was 0.0863 m3 /s and mass flow rate 0.0975 kg/s. The ETHE system was operated for seven hours a day for three consecutive days of each month. The tube air temperature at the inlet, middle and outlet, and soil temperature at 3-meter depth were noted at the interval of one hour. System was turned on at 10.00 AM and shut down at 5 PM. Tests in May were carried out on 28th , 29th , and 30th (2000).
  • 7. 7 The ambient temperature on these three days was very similar. The results of the three days were therefore averaged. Table-1 shows the data, which is mean of the three days. Figure-3 shows the data graphically. The ambient temperature started with 31.3o C at 10.00 AM and rose to a maximum of 40.8o C at 2 PM. The temperature of air at outlet was 26.8o C ;as the system started and rose only slightly to 27.2o C at which it stayed through the 7 hour of test run. The outlet temperature was just above the basic soil temperature (26.6o C) at 3 m depth, suggesting that the tube was exchanging heat quite effectively. As can be seen from the table most of the cooling occurred in the first half of the tube (25 m). At 2 PM, air temperature reduced from 40.8o C to 29.7o C by the middle (25 m), i.e. by 11.1o C. In the next 25 the further reduction was only 2.5o C. This is expected, because as the difference between air temperature and that of the soil reduces, heat transfer rates are reduced. Coefficient of Performance (COP) Coefficient of performance is one of the measures of heat exchanger efficiency. It is defined as (ASHRAE 1985) cp Specific heat of air ( J / kg o C ) inW outQ COP • • = )blowerbyusedenergy(exchangerheattheintoinputenergyofRate soilcoolerandairhotbetweenexchangedisheatat whichRate in out W Q • • )TT(Cmout Q oipa −= • • )s/kg(airofrateflowMassma •
  • 8. 8 Ti Temperature of air entering the tube ( o C ) To Temprature of air at the outlet ( o C ) Ti and To are both treated as bulk temperatures, independent of radial variation. This is realistic, pipe diameter being only 10 cm. Energy input into the heat exchanger is just the energy used by the blower (300 w). In the first hour of operation (10.00 - 11.00 AM ) the ambient air temperature rose from 31.3o C to 33.7o C. The mean of this works out to 32.5o C. We shall assume this to be, Ti, during this first hour. Properties of air used in computation relate to temperature of 35o C. Hourly, values of COP are shown in Table-1. COP value was 1.73 at the start, rising to a maximum of 4.4 at 2 PM, when the ambient temperature was at peak. Mean value of COP over the test run of 7 hours is 3.3. Baxter presented detailed analysis of ETHE performance during three weekly periods -- first week of June, third week of July and last week of August. These represent periods where high ambient temperatures prevail and cooling is greatly needed. During these periods the value of COP in the hours of high energy exchange (day time when ambient temperatures were high) ranged from 4.37 to 6.31. The mean hourly values for the entire 73.1 300 )26.832.5(x1007x0.0975 COP = − =
  • 9. 9 period of test ranged from 1.4 to 2.69. During these periods basic soil temperature varied from 14.8o C to 18.2o C. The maximum ambient temperature varied from 33.9o C to 35.6 o C. The cooling effected in the three weekly periods was 8.3 o C, 8.9o C and 5o C. Heating Mode Tests Heating mode tests were carried out for three nights of January 2000 (28th , 29th , & 30th ). The system was turned on at 6 PM and operated for 12 hours continuously, till 6 AM next day. Temperature readings were noted at hourly interval. Here also the conditions on the three consecutive nights were similar and therefore the results combined. Table 2 shows the data, which is the mean of three test runs. Fig. 4 shows the same data graphically. The ambient temperature started at 23.6o C (5 PM), falling to the lowest value 8.3o C at 2 AM. Thereafter it began to rise again and was 9.8o C at 6 AM when the test was closed. Basic soil temperature at 3 m depth was constant at 24.2o C. Temperature of the air at the outlet stayed virtually constant at 23o C; varying from 22.8o C to 23.3o C. ETHE was able to raise the ambient air temperature at 2 AM from 8.3o C to 23o C or by 14.7o C. The table also shows the COP values. The mean hourly COP is 3.8. The greatest hourly values of COP in heating mode reported by Baxter ranged from 3.2 to 10.3. Mean hourly value over the entire period of test ranged from 1.6 to 4.2. As stated earlier, the tests were conducted for three days of each month. For reasons of space, all results are not presented in detail. But a summary is given in Table-3 showing basic results of each month.
  • 10. 10 Summary and Conclusion A single pass earth-tube heat exchanger (ETHE) was installed to study its performance in cooling and heating mode. ETHE is made of 50 m long ms pipe of 10 cm nominal diameter and 3 mm wall thickness. ETHE is buried 3 m deep below surface. A 400 w blower pumps ambient air through it. Air velocity in the pipe is 11 m/s. ETHE was able to reduce the temperature of hot ambient air by as much as 14o C in May. The basic soil temperature in May was 26.6o C. It was able to warm up the cold ambient air by a similar amount in the nights of January. The basic soil temperature in January was 24.2o C. The coefficient of performance (COP) in cooling mode averaged to 3.3. Cooling tests were of 7 hour continuous duration during the day. In heating mode it averaged to 3.8. Heating tests were of 14 hour continuous duration through the night. Based on the results it can be stated that ETHE holds considerable promise as a means to cool or heat ambient air for a variety of applications such as the livestock buildings and greenhouses. Acknowledgement This facility was built and study carried out by grants from Gujarat Energy Development Agency (GEDA), Vadodara and the Ministry of Agriculture, New Delhi.
  • 11. 11 Table 1: Air Temperature inside ETHE and Soil Temperature ( MAY ) Time Ta Ts Tmd To COP 10:00 31.3 26.6 29.1 26.8 1.73 11:00 33.7 26.6 29.2 26.8 2.6 12:00 36.4 26.6 29.5 27.2 3.2 13:00 37.8 26.6 29.5 27.2 3.9 14:00 40.8 26.6 29.7 27.2 4.4 15:00 40.4 26.6 29.7 27.2 4.2 16:00 39.8 26.6 29.8 27.2 4.1 17.00 39.6 26.5 30 27.2 4.0 Values are mean of three consecutive days of tests (28,29,30 May)
  • 12. 12 Table 2 : Air Temperature inside ETHE and Soil Temperature ( JANUARY ) Time Ta Ts Tmd To COP 18:00 19.8 24.2 22.3 23.4 1.5 19:00 17.6 24.2 22.2 23.4 2.6 20:00 13.3 24.2 22.1 23.3 3.5 21:00 11.9 24.2 21.9 23.3 3.4 22:00 10.4 24.2 21.8 23.3 4.3 23:00 9.6 24.2 21.7 23.3 4.5 0:00 9.1 24.2 21.6 23.2 4.6 1:00 8.7 24.2 21.5 23.2 4.7 2:00 8.3 24.2 21.5 23.0 5.0 3:00 8.7 24.2 21.4 23.0 4.5 4:00 9.1 24.2 21.3 22.9 4.4 5:00 9.6 24.2 21.2 22.9 4.3 6:00 9.8 24.2 21.2 22.8 4.2 Values are mean of three consecutive nights of tests (28,29,30 Jan.)
  • 13. 13 Table 3 : Summary of Cooling Test Results Month Ambient Temperature At 14 hours (o C) Basic Soil Temperature Ts (o C) Outlet Temperature At 14 hours (o C) January Heating test February 37.9 25.2 26.4 March 39.4 25.8 26.4 April 41.4 26.6 28.0 May 40.8 26.6 27.2 June 37.5 29.8 31.9 July No test due to rain - - August No test due to rain - - September 39.1 28.9 30.0 October 34.8 25.6 26.2 November 30.6 24.2 24.2 December 30.7 24.4 24.4 Values are mean of three consecutive days of test in each month.
  • 15. 15 Figure-2 : Thermister Assembly 2.5 cm dia riser 10 cm Coupler Leads Thermister Acralic Stripe Section A - A
  • 17. 2 Figure-4: Airtemperatureinside ETHEandsoil temperature(January) 0.0 5.0 10.0 15.0 20.0 25.0 30.0 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00 1:00 2:00 3:00 4:00 5:00 6:00 7:00 Hourof Day Temperature(0C) Ta Ts Tmd To
  • 18. References Sharan G. and Jadhav R. (2003). Soil temperature regime at Ahmedabad. Journal of Agricultural Engineering . (forthcoming) Scott N.R.; Parsons R.A. and Kochler T.A. (1965). Analysis and performance of an earth-tube heat exchanger. ASAE paper no.65-840. St. Joseph, Michigan, ASAE. Spengler R. W. and Stombaugh D.P (1983). Optimization of earth-tube heat exchanger for winter ventilation of swine housing. Trans ASAE, pp 1186 - 1193. Santamouris M., Mihalakaha G. Balaras C.A. Argirioua Asimakopoulos D. and Vallinaras M. (1995). Use of Buried pipes for energy conservation in cooling of agricultural greenhouse. Solar Energy. Vol. 35 PP 111-124 Baxter, D.O. (1992) Energy exchange and related temperature of an earth-tube heat exchanger in heating mode. Trans ASAE, 35 (1) : 275 - 285. Baxter, D.O. (1994). Energy exchange and related temperature of an earth-tube heat exchanger in cooling mode. Trans ASAE, 37 (1) : 257 - 267. Puri V.M. (1986). Feasibility and performance curves for intermittent earth-tube heat exchangers. Trans ASAE, 29(2). March-April, pp.526-532. Goswamy D.Y. and Dhaliwal A.S. (1985). Heat transfer analysis in environmental control using an underground air tunnel. Journal of Solar Energy Engineering, vol.107, pp.141-145. Sawhnay R.L, Budhi D. and Thanu N.M. (1998). An experimental study of summer performance of a recirculation type underground air-pipe air conditioning system, Building and Environment, 34, pp 189 - 196. Sharan G.; Sahu R.K. and Jadhav R. (2001). Earth-tube heat exchanger based air- conditioning for tiger dwellings. Zoos' Print, 16:5, May (RNI 2:8). ASHRAE (1985). Handbook of application. Atlanta Ga. American Society of Heating Refrigerating and Air Conditioning engineers Inc.