Synchrophasor Based Ocillation Detection: A
Case Study for Indian Power Grid
Vaishali Rampurkar
Electrical Engineering Department
Veermata Jijabai Technological Institute (VJTI)
Mumbai, India
Abstractโ€”The Indian electrical grid is one of the largest &
complex networks in the world. Such complex system is
subjected to stress or disturbances which manifest in the form of
low frequency oscillations. Monitoring of these oscillations is
necessary as they can disrupt the system if they are sustained for
a longer period of time with significant magnitude. This paper
presents the analysis of low frequency oscillation modes using
the data from Phasor measurement unit located in Western and
northern region of the country. It reports case studies of
disturbances that occurred in the Indian power grid. The modes
with low frequency oscillations were observed in both Western&
northern region of the Indian grid.The Matrix Pencil technique
was used to identify the oscillatory modes in system during the
occurrence of the event. The importance of identifying critical
oscillatory modes to improve the power system operation, has
been brought out in this paper.
Keywordsโ€”Phasor measurement unit, oscillations, power system
stability, inter-area oscillations
I. INTRODUCTION
The Indian electrical grid is one of the largest and complex
power grids in the world with an installed capacity of 227
GW [1]. It consists of five regional grids i.e. NR (northern
Region), ER (Eastern Region), NER (North-Eastern Region),
WR (Western Region) & SR (Southern Region) operating
synchronously since December 2013. The operation &
control of such complex network is carried out by the
hierarchical network of load control centres. National load
dispatch center (NLDC), five regional load despatch centres
(RLDCs) thirty three state load despatch centres (SLDCs).
The system operation has now become complex due to
integration of high capacity transmission lines, renewables
etc. leading to several unforeseen stability problems into the
system. The decision making time by the operator of such a
large grid has to be reduced with the complexity &
stabilityproblems especially small signal stability problems
due tostress in the system caused by higher loading levels.
Thus facilitating the need for advanced monitoring and
visualization tools. The technological advent of phasor
measurement unit (PMU), has come out to be as tool which
provides the grid operator with the real time view of the
system. Indian grid has installed a number of PMUs at
various locations [2].
PMU provides the time synchronised measurements of
voltage and current phasors along with frequency & rateof
change of frequency (ROCOF)synchronised with
GlobalPositioning System (GPS) satellite [3]. These
measurementsare utilised for power system operation & for
analysis of eventsin post-despatch scenario [4].Various
applications with benefits of PMU are explained in [5]. These
PMU measurements canalso be used for Low frequency
oscillation (LFO) detection [6].
This paper presents a case study that demonstrates the
application of PMU to detect LFOs in the system & actions
tobe taken to damp these oscillations.The paper is organised
asfollows:Section II reviews the theoretical background on
smallsignal stability, LFOs and proposed technique for LFO
modedetection Matrix pencil method. Section IIIand IV
presents brief description of the events that occurred in the
WR and discusses the results of modal analysis. Section V,
concludes the paper.
II. THEORETICAL BACKGROUND
A. Small signal stability
Small signal disturbances during power system operationmay
occur due to several reasons thereby affecting the
powersystem. The ability of power system to be in steady
state dueto such disturbances is called small signal stability.
Transientstability is associated with the ability of power
system tomaintain synchronism when subjected to large
disturbanceslike line faults, bus fault, generator trip etc.
During thesedisturbances the electromagnetic & mechanical
torques ofeach synchronous machine need to be maintained.
The electromechanicaltorque of synchronous machine can be
resolvedinto two components: synchronizing torque
component(๐พ๐‘ ) &damping torque component(๐พ๐‘‘ )as shown in
(1).
โˆ†๐‘‡๐‘’ = ๐พ๐‘ โˆ†๐œ• + ๐พ๐‘‘ โˆ†๐œ” = ๐‘‡๐‘  + ๐‘‡๐‘‘ 1
Where:
๐พ๐‘ : Synchronizing torque coefficient
โˆ†๐œ•: Rotor angle perturbation
โˆ†๐œ”: Speed variation
๐พ๐‘‘ : Damping torque coefficient
๐‘‡๐‘  : Synchronizing torque
๐‘‡๐‘‘ : Damping torque
The damping torque (๐‘‡๐‘‘ ) changes with the change in
damping torque coefficient (๐พ๐‘‘ ) & variation in speed
(โˆ†๐œ”).Reduced damping torque (๐‘‡๐‘‘ ) gives rise to low
frequencyoscillations[7]. Undamped oscillations can increase
inmagnitude & lead to instability and are therefore an object
International Journal of Engineering Research & Technology (IJERT)
ISSN: 2278-0181
www.ijert.orgIJERTV4IS040029
(This work is licensed under a Creative Commons Attribution 4.0 International License.)
Vol. 4 Issue 04, April-2015
29
ofstudy by various researchers. These oscillations are
classifiedinto four major types inter-area modes (0.1 Hz - 1
Hz),intra-plant modes (1 Hz - 2.5 Hz), torsional modes (10
Hz-40Hz) & control modes. The inter-area modes are
associatedwith swinging of groups of generators in one area
of thesystem against generators in other area. They usually
occurbecause of weak interconnecting network. The intra-
plantmodes occur due to the swinging of units of generating
stationwith respect to each other. The torsional modes are
associatedwith turbine-generator shaft system and associated
rotationalcomponents. The control modes are present in the
systembecause of poor design of controllers of AVR, HVDC,
SVC,AGC etc.
Disturbances can occur in the interconnected power system
due to faults, load changesand when these disturbances occur
oscillations usually arise in the system. These oscillations are
acceptable as long as they decay [7,8]. It is very important to
monitor theseoscillations to ensure that no lightly damped
oscillatory modes exist in the system asthey threaten the
reliable operation of the power system. The small signal
instabilityissues need to be addressed since most of the
blackouts have been associated with it [9]. The oscillations
can be regarded as the characteristic of the system i.e.
oscillatoryparameters are dependent on the physical
infrastructure. Every power grid is unique inits physical
connections thus presence of oscillations vary with the
networks. The powersystem oscillations are complex and
difficult to analyse.
There exist two techniques for detecting the LFOs of
thepower system: model based techniques & measurement
basedtechniques [10]. In the model based technique the non-
lineardifferential equations governing the system are
linearizedabout an operating point & further the modes are
obtainedvia Eigen value analysis [7]. In the measurement
basedtechniques direct measurements from PMU estimate the
linearmodel. Some of the popular measurement based
techniquesfor estimating LFOs are Fast Fourier Transform
(FFT), Pronyanalysis [11] [12], Matrix Pencil [13], Hilbert
transform [14,15,16],wavelet transform [17,18,19]. A
comparative study ofvarious techniques for identification of
oscillations has beenexamined in [20,21].
B. Matrix Pencil method
Matrix pencil method is an efficient approach to fit
measured date set with sum of exponentials. This method is
just a one step process of finding signal poles directly from
the Eigen values of the matrix developed. It directly estimates
the parameters for the exponential terms in 1 to an observed
measurement [1, 2].
๐‘ฆ ๐‘ก = ๐ด๐‘– ๐‘’ ๐œŽ ๐‘– ๐‘ก
cosโก(๐œ”๐‘– ๐‘ก + ๐œ‘๐‘–)
๐‘›
๐‘–=1
1
Data matrix [Y] is formed using input data shown in 2
๐‘ฆ(0) ๐‘ฆ(1) โ€ฆ ๐‘ฆ(๐ฟ)
๐‘ฆ(1) ๐‘ฆ(2) โ€ฆ ๐‘ฆ(๐ฟ + 1)
: : : :
๐‘ฆ(๐‘ โˆ’ ๐ฟ โˆ’ 1) ๐‘ฆ(๐‘ โˆ’ ๐ฟ) โ€ฆ ๐‘ฆ(๐‘ โˆ’ 1) (๐‘โˆ’๐ฟ)๐‘‹(๐ฟ+1)
2
Where N is number of measured samples, L is pencil
parameter.
Next SVD of matrix [Y] is calculated which gives:
๐‘Œ = ๐‘ˆ ฮฃ ๐‘‰ ๐‘‡
3
Here [U] & [V] are unitary matrices composed of
eigenvectors of Y ๐‘‡
๐‘Œ & ๐‘Œ Y ๐‘‡
respectively, and ฮฃ is
diagonal matrix consisting of singular values of [Y].
Next consider the filtered matrix ๐‘‰โ€ฒ
, it contains n
dominant right singular vector of [V].
Thus
๐‘Œ1 = ๐‘ˆ ฮฃโ€ฒ [๐‘‰1โ€ฒ] ๐‘‡
4
๐‘Œ2 = ๐‘ˆ ฮฃโ€ฒ [๐‘‰2โ€ฒ] ๐‘‡
5
The poles of the signal are given by non-zero Eigen values
of
{ ๐‘‰1โ€ฒ] ๐‘‡ +
[๐‘‰2โ€ฒ] ๐‘‡
6
Once n & poles (๐œŽ๐‘–) are known residues are solved using least
square sense.
๐‘ฆ(0)
๐‘ฆ(1)
:
๐‘ฆ(๐‘ โˆ’ 1)
=
1 1 โ€ฆ 1
๐‘ง1 ๐‘ง2 โ€ฆ ๐‘ง ๐‘›
: : : :
๐‘ง1
๐‘โˆ’1
๐‘ง2
๐‘โˆ’1
โ€ฆ ๐‘ง ๐‘›
๐‘โˆ’1
๐ต1
๐ต2
:
๐ต๐‘›
III. CASE STUDY-I
This section analyses the event that took place in the WR of
the Indian power grid. On 3rd
March 2013 at 18:04 hours, a
bus fault occurred at Parli in Maharashtra state. The
frequency and rate of change of frequency (ROCOF)
recorded by PMU located at Badrawati are shown in Fig. 1
Fig. 1. Frequency and ROCOF at Bhadrawati
International Journal of Engineering Research & Technology (IJERT)
ISSN: 2278-0181
www.ijert.orgIJERTV4IS040029
(This work is licensed under a Creative Commons Attribution 4.0 International License.)
Vol. 4 Issue 04, April-2015
30
The measurements at Badrawati indicate sharp fall in the
frequency and ROCOF. Three spikes were observed in the
measurements with, and the third spike was the severe one
indicating tripping of all elements. The ROCOF reached
approximately 0.17 Hz/sec when the event occurred. The
frequency also started dropping and reached 49.8 Hz within 1
sec.
Fig. 2. Line voltages recorded at Badrawati
The line voltages recorded by PMU placed at Bhadrawati are
shown in Fig. 2. The disturbance at Parli is indicated by sharp
pulses.It can observed that after the event occurred at Parli,
line voltages reduced.
Fig.3. Phase currents recorded at Badrawati
Fig-3, shows the plot for linecurrents recorded by PMU at
Badrawati. The measurements show sharp pulses indicating
loss of elements in the system. The line currents were
observed to have reduced values after the disturbance. The
measurements also show the presence of oscillations in the
system.
Fig. 4. Frequency plots NR and WR
After the bus fault at Parli in WR, the frequency
measurement obtained from at Raipur in WR and Agra,
Ballia, Hissar in NR were compared for the behavior of the
system. It can be clearly observed from Fig-4 that WR
machines are oscillating against the NR machines till the new
equilibrium point reached in 3 secs.
TABLE I. RESULTS OF MODAL ANALYSIS CASE STUDY- I
Sr.No. Location of PMU Freq
(Hz)
Damping Amplitude
1
Raipur (WR)
0.6 -0.01509 0.04124
2 0.8
0.06814 0.08434
3 1.5 0.0365 0.031
4 2.7 0.0025 0.0042
1
Agra (NR)
0.6
-0.03529 0.02148
2 0.8
0.01722 0.01041
3 1.5 0.00235 0.006
4 2.7 0.00079 0.00378
The results of modal analysis using Prony method have been
tabulated in Table-1. The voltage measurements at recorded
by PMU at Raipur in WR and Agra in NR have been used for
analysis. It can be observed from the results that the modes
with frequencies of 0.6 Hz, 0.8 Hz, 1.5 Hz and 2.7 Hz, were
identified with negative and close to zero damping.
The 0.6 Hz oscillatory mode was estimated to have negative
damping both in Raipur as well as Agra. The 0.8 Hz, 1.5Hz
and 2.7 Hz modes were observed to have close to zero
damping but comparatively lower amplitudes as compared to
the 0.6 Hz mode. Since the 0.6 Hz inter-area oscillatory mode
has negative damping and higher amplitude is quantified as
the critical mode in the system. The amplitude of all the
oscillatory modes at Raipur are more than those observed at
Agra. This is because Agra is located far from the place
where the event occurred (i.e. Parli).
International Journal of Engineering Research & Technology (IJERT)
ISSN: 2278-0181
www.ijert.orgIJERTV4IS040029
(This work is licensed under a Creative Commons Attribution 4.0 International License.)
Vol. 4 Issue 04, April-2015
31
IV. CASE STUDY -II
This section analyses a disturbance that occurred at Sipat in
WR on 14th
September 2012 at 18:58:22 hours. The PMU
measurements at recorded at Raipur in WR clearly indicate
unstable behavior of the system.
Fig.5. Frequency and ROCOF at Raipur
The frequency and ROCOF measurements at recorded at
Raipur during the disturbance in Sipat as shown in Fig. 5.
The measurements at Raipur clearly indicate when the event
was triggered at Sipat i.e. at 18:58:22.320 hours as shown in
the encircled section in the figure. It can also be observed that
when Sipat unit tripped Raipur PMU shows that ROCOF
reached a value of -0.15 Hz/sec.
Fig.6. Raipur-Bhadrawati power flow
The real power flow on Raipur- Bhadrawati line also
indicates the occurrence of disturbance at Sipat. It can be
clearly observed in Fig.6 that with the loss of units at Sipat
the power flow on Raipur- Bhadrawati increased.
Fig.7. Line voltages recorded by PMU located at Raipur
The voltage measurements at Raipur also indicate sharp
voltage dips at the time of disturbance. With the disturbance
at Sipat, increased power flow on Raipur- Bhadrawati line
resulted in decrease in line voltages at Raipur as shown in
Fig. 7.
The line currents measurements for Raipur- Bhadrawati line
are shown in Fig.8. This recorded data also indicates the
event occurrence with the sharp pulses. It can also be
observed that with the event occurrence power flow on this
line increased which lead to decreased line voltages at Raipur
thus leading to increased line currents. This can be clearly
observed in Fig. 8.
Modal analysis of the power flow measurement on Raipur-
Bhadrawati line was carried out using matrix pencil technique
in-order to identify the oscillatory modes excited in the
system due to the disturbance. The analysis was carried out
for two instances Duration 1 (before) and Duration 2 (after)
the disturbance in-order study the behavior of the modes.
Fig.8. Raipur- Bhadrawati Line current
48.4
48.6
48.8
49
49.2
49.4
49.6
49.8
50
50.2
50.4
-0.2
-0.15
-0.1
-0.05
0
0.05
0.1
0.15
0.2
18:45:00.000
18:45:23.559
18:45:47.120
18:46:10.679
18:46:34.240
18:46:57.800
18:47:21.360
18:47:44.920
18:48:08.480
18:48:32.040
18:48:55.600
18:49:19.160
18:49:42.720
18:50:06.280
18:50:29.840
18:50:53.400
18:51:16.960
18:51:40.520
18:52:04.080
18:52:27.640
18:52:51.200
18:53:14.760
18:53:38.320
18:54:01.880
18:54:25.440
18:54:49.000
18:55:12.559
18:55:36.120
18:55:59.679
18:56:23.240
18:56:46.800
18:57:10.360
18:57:33.920
18:57:57.480
18:58:21.040
18:58:44.600
18:59:08.160
18:59:31.720
18:59:55.280
19:00:18.840
19:00:42.400
19:01:05.960
19:01:29.520
19:01:53.080
19:02:16.640
19:02:40.200
19:03:03.760
19:03:27.320
19:03:50.880
19:04:14.440
19:04:38.000
Frequency(Hz)
df/dt
Raipur df/dt Raipur freq
RaipurPMU shows that df/dt whenSipat unit
strippedreacheda value of - 0.15 Hz/sec
Eventtriggeredat
18:58:22.320 Hrs
48.4
48.6
48.8
49
49.2
49.4
49.6
49.8
50
50.2
50.4
380
400
420
440
460
480
500
520
540
560
18:45:00.000
18:45:23.080
18:45:46.160
18:46:09.240
18:46:32.320
18:46:55.400
18:47:18.480
18:47:41.559
18:48:04.640
18:48:27.720
18:48:50.800
18:49:13.880
18:49:36.960
18:50:00.040
18:50:23.120
18:50:46.200
18:51:09.280
18:51:32.360
18:51:55.440
18:52:18.520
18:52:41.600
18:53:04.679
18:53:27.760
18:53:50.840
18:54:13.920
18:54:37.000
18:55:00.080
18:55:23.160
18:55:46.240
18:56:09.320
18:56:32.400
18:56:55.480
18:57:18.559
18:57:41.640
18:58:04.720
18:58:27.800
18:58:50.880
18:59:13.960
18:59:37.040
19:00:00.120
19:00:23.200
19:00:46.280
19:01:09.360
19:01:32.440
19:01:55.520
19:02:18.600
19:02:41.679
19:03:04.760
19:03:27.840
19:03:50.920
19:04:14.000
19:04:37.080
Frequency(Hz)
RealPower(MW)
Raipur Bwati Ckt 1 Real Power Raipur freq
With each occurence the power flow in
Raipur-Bhadrawati T/C increased
48.4
48.6
48.8
49
49.2
49.4
49.6
49.8
50
50.2
50.4
220
225
230
235
240
245
250
18:45:00.000
18:45:23.080
18:45:46.160
18:46:09.240
18:46:32.320
18:46:55.400
18:47:18.480
18:47:41.559
18:48:04.640
18:48:27.720
18:48:50.800
18:49:13.880
18:49:36.960
18:50:00.040
18:50:23.120
18:50:46.200
18:51:09.280
18:51:32.360
18:51:55.440
18:52:18.520
18:52:41.600
18:53:04.679
18:53:27.760
18:53:50.840
18:54:13.920
18:54:37.000
18:55:00.080
18:55:23.160
18:55:46.240
18:56:09.320
18:56:32.400
18:56:55.480
18:57:18.559
18:57:41.640
18:58:04.720
18:58:27.800
18:58:50.880
18:59:13.960
18:59:37.040
19:00:00.120
19:00:23.200
19:00:46.280
19:01:09.360
19:01:32.440
19:01:55.520
19:02:18.600
19:02:41.679
19:03:04.760
19:03:27.840
19:03:50.920
19:04:14.000
19:04:37.080
Frequency(Hz)
LineVoltage(kV)
Va Vb Vc Raipur freq
Voltage at Raipur decreses with in
crease in line loading
International Journal of Engineering Research & Technology (IJERT)
ISSN: 2278-0181
www.ijert.orgIJERTV4IS040029
(This work is licensed under a Creative Commons Attribution 4.0 International License.)
Vol. 4 Issue 04, April-2015
32
TABLE II. RESULTS OF MODAL ANALYSIS CASE STUDY- II
Event 1
Time Instant Frequency Damping Amplitude
Duration 1 0.35 0.06561 11.00855
0.69 0.1065 11.33678
1.2 0.05737 7.1932
Duration 2 0.34 0.16818 8048.51036
0.7 0.1334 162507.274
1.2 0.05391 683.88899
Event 2
Duration 1 0.33 0.26122 44.43362
0.71 0.06076 3.44972
1.2 -0.0087 0.18098
Duration 2 0.36 0.01412 1.17597
0.69 0.05844 16.34748
1.18 -0.00506 0.31271
The results of modal analysis are tabulated in TABLE II. It
can be observed for event 1 in the system the oscillatory
modes with frequencies of 0.35 Hz, 0.7 Hz and 1.2 Hz for
both the time instants before and after the disturbance. The
1.2 Hz mode was identified to have low damping for both the
time instances.All the oscillatory modes were observed to
have higher amplitudes after the event 1.
Analyzing event 2 in the network (i.e. second spike in the
measurements) indicated presence of 0.3 Hz, 0.7 Hz and 1.2
Hz modes. The 0.3 Hz mode had improved damping before
the second disturbance and it reduced to 0.014 after the
disturbance. Similarly the damping of 0.7 Hz mode also
reduced after the event 2. After the occurrence of event 1 the
1.2 Hz mode was observed to have negative damping for both
time instants for event 2.
V. CONCLUSION
Low frequency oscillations (LFOs) are inherent to
interconnected power systems. These oscillations need to be
stable in order to have secure power system operations. The
Indian grid has recently installed a number of PMUs in the
system which increase the situational awareness amongst the
operators. This paper tries to demonstrate one possible
application of PMU measurements in the power system i.e.
identification of low frequency oscillations. This paper uses
Matrix pencil for identification of LFOs. This paper also
indicates that as the location of PMU increases from the event
located the amplitude of modal parameters is observed to
have reduced. Thus it can be concluded that the PMU placed
far away from the event location will indicate lower
amplitude for a critical mode observed in the system.
Some of the devices in the power system to counteract
negative damping include PSS inexcitation system of
generator & controls of FACTS devices.The real time actions
by system operator include generationre-despatch, load
shedding, circuit switching etc. to relievethe stress in the
system. This case study has indicated theimportance of PMUs
& their location towards identificationof LFOs and its source
identification. Extensive research needs to be carried out on
theoptimum placement of PMUs to record the events &
foranalysis of LFOs in the system.
Ongoing work deals with developing tools for advanced
monitoring of the power grid operations. With increase in the
number of PMUs placed in the system will lead to increased
observability.
ACKNOWLEDGMENT
The authors gratefully acknowledge the support provided
byCenter of Excellence in Complex and Nonlinear
DynamicalSystems, VJTI, Mumbai & Western Region Load
DespatchCentre for valuable discussions & support.
REFERENCES
[1] CEA
[2] Synchrophasor Initiatives in India- Report by POSOCO
[3] A.G.Phadke, โ€œSynchronised Phasor Measurement units in power
systems,โ€ IEEE Comput.Appl.Power, vol.6, No.2, pp. 10-15, April
1993
[4] Jaime De La Ree, Virgilio Centono, James S. Thorp, A.G.
Phadke,โ€œSynchronized Phasor Measurement Applications in Power
Systemsโ€, IEEE Transactions on smart grid, vol.1,no.1, pp. 20-27, June
2010.
[5] Damir Novosel, Khoi Vu, โ€œ Benefits of PMU technology for various
applicationsโ€ International Council on large electric systems -Cigre,
7th
Symposium on Power system Management, 2006
[6] Wuxing Liang, Harmeet Kang, and Liangzhong Yao, โ€œDetection of
Power System Oscillations Using Moving Window Prony Methodโ€
Power System Technology (POWERCON), 2010 International
Conference,October 2010.
[7] P. Kundur, โ€œPower system stability and Controlโ€ McGraw-Hill, 1994.
[8] G. Rogers, Power System Oscillations: Kluwer Academic, 2000.
[9] G. Andersson, P. Donalek, R. Farmer, N. Hatziargyriou, I. Kamwa, P.
Kundur, N. Martins, J. Paserba, P. Pourbeik,J. Sanchez-Gasca, R.
Schulz, A. Stankovic, C. Taylor, and V. Vittal"Causes of the 2003
Major Grid Blackouts in North America and Europe, and
Recommended Means to Improve System Dynamic Performance,"
IEEE Transactions on Power SystemS,vol. 20, No. 4, November 2005
[10] Ning Zhou; Trudnowski, D.J.; Pierre, J.W.; Mittelstadt, W.A.,
โ€ElectromechanicalMode Online Estimation Using Regularized
RobustRLS Methods, IEEE Transactions on Power Systems,vol.23,
no.4,pp.1670,1680,Nov-2008
[11] Hauer, J.F.; Demeure, C.J.; Scharf, L.L., โ€Initial results in Prony
analysisof power system response signals,โ€ IEEE Transactions Power
Systems,,vol.5, no.1, pp.80-89, Feb1990
[12] D. Trudnowski, J. Johnson, and J. Hauer, Making prony analysis
moreaccurate using multiple signals, IEEE Trans. Power Syst., vol. 14,
no.1,pp. 226231, Feb. 1999.
[13] Lisa L. Grant ,Mariesa L. Crow, Comparison of Matrix Pencil & Prony
Methodsfor power system modal analysis of noisy signals", North
American Power Symposium(NAPS) , August 2011
[14] Messina, A.R.; Vittal, V., "Nonlinear, non-stationary analysis of
interarea oscillations via Hilbert spectral analysis,"IEEE Transactions
Power Systemson , vol.21, no.3,pp.1234,1241, Aug. 2006
[15] Laila, D.S.; Messina, A.R.; Pal, B.C., "A Rened HilbertHuang
Transform WithApplications to Inter-area Oscillation
Monitoring,"IEEE Transactions Power Systems,vol.24, no.2,
pp.610,620, May 2009
[16] Dechang Yang; Rehtanz, C.; Yong Li; Deyou Yang, "A hybrid method
and itsapplications to analyse the low frequency oscillations in the
interconnected power system,"IET, Generation, Transmission &
Distribution , vol.7, no.8, pp.874,884, Aug.2013
[17] Rueda, J.L.; Juarez, C.A.; Erlich, I., "Wavelet-Based Analysis of Power
SystemLow-Frequency Electromechanical Oscillations," IEEE
Transactions on Power Sys-tems, vol.26, no.3, pp.1733,1743, Aug.
2011
[18] Bruno, S.; De Benedictis, M.; La Scala, M., ""Taking the pulse" of
Power Systems: Monitoring Oscillations by Wavelet Analysis and
International Journal of Engineering Research & Technology (IJERT)
ISSN: 2278-0181
www.ijert.orgIJERTV4IS040029
(This work is licensed under a Creative Commons Attribution 4.0 International License.)
Vol. 4 Issue 04, April-2015
33
Wide Area Measurement System,"IEEE PES, Power Systems
Conference and Exposition, 2006. PSCE '06, vol.,no., pp.436,443, Oct.
29 2006-Nov. 1 2006
[19] Xueping Pan; Venkatasubramanian, V., "Multi-power system
oscillation monitoring using synchrophasors,"IEEE PES
InnovativeSmart Grid Technologies (ISGT), 2012, vol., no., pp.1,10,
16-20 Jan. 2012
[20] Vaishali Rampurkar, Faruk Kazi, Harivittal Mangalvedekar, P.
Pentayya, ChandanKumar and Rajkumar A, "A comparative analysis of
Modal analysis techniques ACase study for Western Region of India"
5th International Conference on Power &Energy Systems,2013
[21] Rampurkar, V.; Kazi, F.; Mangalvedekar, H.A.; Pentayya, P.; Kumar,
C.; Rajkumar, A., "PMU based identification of low frequency
oscillations A case study,"IEEE,Innovative Smart Grid Technologies -
Asia (ISGT Asia), 2013, vol., no., pp.1,5, 10-13Nov. 2013
International Journal of Engineering Research & Technology (IJERT)
ISSN: 2278-0181
www.ijert.orgIJERTV4IS040029
(This work is licensed under a Creative Commons Attribution 4.0 International License.)
Vol. 4 Issue 04, April-2015
34

More Related Content

What's hot

IRJET- Location Identification for FACTs Device
IRJET- Location Identification for FACTs DeviceIRJET- Location Identification for FACTs Device
IRJET- Location Identification for FACTs DeviceIRJET Journal
ย 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
ย 
Power System Stabilizer with Induction Motor on Inter Area Oscillation of Int...
Power System Stabilizer with Induction Motor on Inter Area Oscillation of Int...Power System Stabilizer with Induction Motor on Inter Area Oscillation of Int...
Power System Stabilizer with Induction Motor on Inter Area Oscillation of Int...IJMTST Journal
ย 
Load frequency control in co ordination with
Load frequency control in co ordination withLoad frequency control in co ordination with
Load frequency control in co ordination witheSAT Publishing House
ย 
A review on SVC control for power system stability with and without auxiliary...
A review on SVC control for power system stability with and without auxiliary...A review on SVC control for power system stability with and without auxiliary...
A review on SVC control for power system stability with and without auxiliary...journalBEEI
ย 
Fault Ride-Through capability of DSTATCOM for Distributed Wind Generation System
Fault Ride-Through capability of DSTATCOM for Distributed Wind Generation SystemFault Ride-Through capability of DSTATCOM for Distributed Wind Generation System
Fault Ride-Through capability of DSTATCOM for Distributed Wind Generation SystemIJPEDS-IAES
ย 
IEEE International Conference Presentation
IEEE International Conference PresentationIEEE International Conference Presentation
IEEE International Conference PresentationAnmol Dwivedi
ย 
Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing Da...
Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing Da...Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing Da...
Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing Da...IOSRJEEE
ย 
TRANSIENT STABILITY ENHANCEMENT BY USING DSSC AND PSS
TRANSIENT STABILITY ENHANCEMENT BY USING DSSC AND PSSTRANSIENT STABILITY ENHANCEMENT BY USING DSSC AND PSS
TRANSIENT STABILITY ENHANCEMENT BY USING DSSC AND PSSIAEME Publication
ย 
IRJET- Analysis of Power System Stability using Various FACTS Controllers
IRJET- Analysis of Power System Stability using Various FACTS ControllersIRJET- Analysis of Power System Stability using Various FACTS Controllers
IRJET- Analysis of Power System Stability using Various FACTS ControllersIRJET Journal
ย 
IRJET- Control of Induction Motor using Neural Network
IRJET- Control of Induction Motor using Neural NetworkIRJET- Control of Induction Motor using Neural Network
IRJET- Control of Induction Motor using Neural NetworkIRJET Journal
ย 
Transient stability analysis and enhancement of ieee 9 bus system
Transient stability analysis and enhancement of ieee  9 bus system Transient stability analysis and enhancement of ieee  9 bus system
Transient stability analysis and enhancement of ieee 9 bus system ecij
ย 
07 7924 9058-1-pb
07 7924 9058-1-pb07 7924 9058-1-pb
07 7924 9058-1-pbIAESIJEECS
ย 
Fuzzy logic based direct torque control of induction motor with space vector ...
Fuzzy logic based direct torque control of induction motor with space vector ...Fuzzy logic based direct torque control of induction motor with space vector ...
Fuzzy logic based direct torque control of induction motor with space vector ...ijscai
ย 
F0315040047
F0315040047F0315040047
F0315040047theijes
ย 
Fuzzy logic based direct torque control of induction motor with space vector ...
Fuzzy logic based direct torque control of induction motor with space vector ...Fuzzy logic based direct torque control of induction motor with space vector ...
Fuzzy logic based direct torque control of induction motor with space vector ...ijscai
ย 
Phasor measurement unit
Phasor measurement unitPhasor measurement unit
Phasor measurement unitSathriGiridhar
ย 
A robust dlqg controller for damping of sub synchronous oscillations in a se...
A robust dlqg controller for damping of sub  synchronous oscillations in a se...A robust dlqg controller for damping of sub  synchronous oscillations in a se...
A robust dlqg controller for damping of sub synchronous oscillations in a se...eSAT Publishing House
ย 

What's hot (20)

IRJET- Location Identification for FACTs Device
IRJET- Location Identification for FACTs DeviceIRJET- Location Identification for FACTs Device
IRJET- Location Identification for FACTs Device
ย 
Review of the Most Applicable Regulator Collections to Control the Parallel A...
Review of the Most Applicable Regulator Collections to Control the Parallel A...Review of the Most Applicable Regulator Collections to Control the Parallel A...
Review of the Most Applicable Regulator Collections to Control the Parallel A...
ย 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
ย 
Power System Stabilizer with Induction Motor on Inter Area Oscillation of Int...
Power System Stabilizer with Induction Motor on Inter Area Oscillation of Int...Power System Stabilizer with Induction Motor on Inter Area Oscillation of Int...
Power System Stabilizer with Induction Motor on Inter Area Oscillation of Int...
ย 
Load frequency control in co ordination with
Load frequency control in co ordination withLoad frequency control in co ordination with
Load frequency control in co ordination with
ย 
Artificial Neural Network Based Speed and Torque Control of Three Phase Induc...
Artificial Neural Network Based Speed and Torque Control of Three Phase Induc...Artificial Neural Network Based Speed and Torque Control of Three Phase Induc...
Artificial Neural Network Based Speed and Torque Control of Three Phase Induc...
ย 
A review on SVC control for power system stability with and without auxiliary...
A review on SVC control for power system stability with and without auxiliary...A review on SVC control for power system stability with and without auxiliary...
A review on SVC control for power system stability with and without auxiliary...
ย 
Fault Ride-Through capability of DSTATCOM for Distributed Wind Generation System
Fault Ride-Through capability of DSTATCOM for Distributed Wind Generation SystemFault Ride-Through capability of DSTATCOM for Distributed Wind Generation System
Fault Ride-Through capability of DSTATCOM for Distributed Wind Generation System
ย 
IEEE International Conference Presentation
IEEE International Conference PresentationIEEE International Conference Presentation
IEEE International Conference Presentation
ย 
Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing Da...
Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing Da...Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing Da...
Tuning of PI and PID Controller with STATCOM, SSSC and UPFC for Minimizing Da...
ย 
TRANSIENT STABILITY ENHANCEMENT BY USING DSSC AND PSS
TRANSIENT STABILITY ENHANCEMENT BY USING DSSC AND PSSTRANSIENT STABILITY ENHANCEMENT BY USING DSSC AND PSS
TRANSIENT STABILITY ENHANCEMENT BY USING DSSC AND PSS
ย 
IRJET- Analysis of Power System Stability using Various FACTS Controllers
IRJET- Analysis of Power System Stability using Various FACTS ControllersIRJET- Analysis of Power System Stability using Various FACTS Controllers
IRJET- Analysis of Power System Stability using Various FACTS Controllers
ย 
IRJET- Control of Induction Motor using Neural Network
IRJET- Control of Induction Motor using Neural NetworkIRJET- Control of Induction Motor using Neural Network
IRJET- Control of Induction Motor using Neural Network
ย 
Transient stability analysis and enhancement of ieee 9 bus system
Transient stability analysis and enhancement of ieee  9 bus system Transient stability analysis and enhancement of ieee  9 bus system
Transient stability analysis and enhancement of ieee 9 bus system
ย 
07 7924 9058-1-pb
07 7924 9058-1-pb07 7924 9058-1-pb
07 7924 9058-1-pb
ย 
Fuzzy logic based direct torque control of induction motor with space vector ...
Fuzzy logic based direct torque control of induction motor with space vector ...Fuzzy logic based direct torque control of induction motor with space vector ...
Fuzzy logic based direct torque control of induction motor with space vector ...
ย 
F0315040047
F0315040047F0315040047
F0315040047
ย 
Fuzzy logic based direct torque control of induction motor with space vector ...
Fuzzy logic based direct torque control of induction motor with space vector ...Fuzzy logic based direct torque control of induction motor with space vector ...
Fuzzy logic based direct torque control of induction motor with space vector ...
ย 
Phasor measurement unit
Phasor measurement unitPhasor measurement unit
Phasor measurement unit
ย 
A robust dlqg controller for damping of sub synchronous oscillations in a se...
A robust dlqg controller for damping of sub  synchronous oscillations in a se...A robust dlqg controller for damping of sub  synchronous oscillations in a se...
A robust dlqg controller for damping of sub synchronous oscillations in a se...
ย 

Similar to Synchrophasor Based Ocillation Detection: A Case Study for Indian Power Grid

H044023944
H044023944H044023944
H044023944IJERA Editor
ย 
Fuzzy-Logic-Controller-Based Fault Isolation in PWM VSI for Vector Controlled...
Fuzzy-Logic-Controller-Based Fault Isolation in PWM VSI for Vector Controlled...Fuzzy-Logic-Controller-Based Fault Isolation in PWM VSI for Vector Controlled...
Fuzzy-Logic-Controller-Based Fault Isolation in PWM VSI for Vector Controlled...iosrjce
ย 
PLACEMENT OF POWER SYSTEM STABILIZER (PSS) IN NIGERIA 28-BUS POWER NETWORK FO...
PLACEMENT OF POWER SYSTEM STABILIZER (PSS) IN NIGERIA 28-BUS POWER NETWORK FO...PLACEMENT OF POWER SYSTEM STABILIZER (PSS) IN NIGERIA 28-BUS POWER NETWORK FO...
PLACEMENT OF POWER SYSTEM STABILIZER (PSS) IN NIGERIA 28-BUS POWER NETWORK FO...IRJET Journal
ย 
DESIGN OF MPSS AND TCSC DAMPING CONTROLLERS IN MULTI- MACHINE POWER SYSTEM U...
DESIGN OF MPSS AND TCSC DAMPING CONTROLLERS  IN MULTI- MACHINE POWER SYSTEM U...DESIGN OF MPSS AND TCSC DAMPING CONTROLLERS  IN MULTI- MACHINE POWER SYSTEM U...
DESIGN OF MPSS AND TCSC DAMPING CONTROLLERS IN MULTI- MACHINE POWER SYSTEM U...Editor IJMTER
ย 
6843 traveling wave_ag_20171107_web2
6843 traveling wave_ag_20171107_web26843 traveling wave_ag_20171107_web2
6843 traveling wave_ag_20171107_web2HAYMANOTTAKELE1
ย 
ANN Approach for Fault Classification in Induction Motors using Current and V...
ANN Approach for Fault Classification in Induction Motors using Current and V...ANN Approach for Fault Classification in Induction Motors using Current and V...
ANN Approach for Fault Classification in Induction Motors using Current and V...IRJET Journal
ย 
Advance Current Monitoring Techniques to Detect and Diagnosis the Inter-Turn ...
Advance Current Monitoring Techniques to Detect and Diagnosis the Inter-Turn ...Advance Current Monitoring Techniques to Detect and Diagnosis the Inter-Turn ...
Advance Current Monitoring Techniques to Detect and Diagnosis the Inter-Turn ...theijes
ย 
Transient Stability Assessment and Enhancement in Power System
Transient Stability Assessment and Enhancement in Power  SystemTransient Stability Assessment and Enhancement in Power  System
Transient Stability Assessment and Enhancement in Power SystemIJMER
ย 
Evaluation of Voltage Phase Fluctuations in Power Networks with Rapid Variabl...
Evaluation of Voltage Phase Fluctuations in Power Networks with Rapid Variabl...Evaluation of Voltage Phase Fluctuations in Power Networks with Rapid Variabl...
Evaluation of Voltage Phase Fluctuations in Power Networks with Rapid Variabl...AM Publications
ย 
Multi-machine system with Series FACTS device: Static synchronous series comp...
Multi-machine system with Series FACTS device: Static synchronous series comp...Multi-machine system with Series FACTS device: Static synchronous series comp...
Multi-machine system with Series FACTS device: Static synchronous series comp...IRJET Journal
ย 
IRJET- Low Cost Harmonic Measurement using Arduino UNO
IRJET-  	  Low Cost Harmonic Measurement using Arduino UNOIRJET-  	  Low Cost Harmonic Measurement using Arduino UNO
IRJET- Low Cost Harmonic Measurement using Arduino UNOIRJET Journal
ย 
Al4201250256
Al4201250256Al4201250256
Al4201250256IJERA Editor
ย 
OPTIMAL TORQUE RIPPLE CONTROL OF ASYNCHRONOUS DRIVE USING INTELLIGENT CONTROL...
OPTIMAL TORQUE RIPPLE CONTROL OF ASYNCHRONOUS DRIVE USING INTELLIGENT CONTROL...OPTIMAL TORQUE RIPPLE CONTROL OF ASYNCHRONOUS DRIVE USING INTELLIGENT CONTROL...
OPTIMAL TORQUE RIPPLE CONTROL OF ASYNCHRONOUS DRIVE USING INTELLIGENT CONTROL...elelijjournal
ย 
Condition monitoring of induction motor with a case study
Condition monitoring of induction motor with a case studyCondition monitoring of induction motor with a case study
Condition monitoring of induction motor with a case studyIAEME Publication
ย 
Condition monitoring of induction motor with a case study
Condition monitoring of induction motor with a case studyCondition monitoring of induction motor with a case study
Condition monitoring of induction motor with a case studyIAEME Publication
ย 
Online voltage stability margin assessment
Online voltage stability margin assessmentOnline voltage stability margin assessment
Online voltage stability margin assessmentNaganathan G Sesaiyan
ย 
Improvise 3-Level DTC of Induction Machine using Constant Switching Frequency...
Improvise 3-Level DTC of Induction Machine using Constant Switching Frequency...Improvise 3-Level DTC of Induction Machine using Constant Switching Frequency...
Improvise 3-Level DTC of Induction Machine using Constant Switching Frequency...IJPEDS-IAES
ย 

Similar to Synchrophasor Based Ocillation Detection: A Case Study for Indian Power Grid (20)

H044023944
H044023944H044023944
H044023944
ย 
Fuzzy-Logic-Controller-Based Fault Isolation in PWM VSI for Vector Controlled...
Fuzzy-Logic-Controller-Based Fault Isolation in PWM VSI for Vector Controlled...Fuzzy-Logic-Controller-Based Fault Isolation in PWM VSI for Vector Controlled...
Fuzzy-Logic-Controller-Based Fault Isolation in PWM VSI for Vector Controlled...
ย 
B010620715
B010620715B010620715
B010620715
ย 
PLACEMENT OF POWER SYSTEM STABILIZER (PSS) IN NIGERIA 28-BUS POWER NETWORK FO...
PLACEMENT OF POWER SYSTEM STABILIZER (PSS) IN NIGERIA 28-BUS POWER NETWORK FO...PLACEMENT OF POWER SYSTEM STABILIZER (PSS) IN NIGERIA 28-BUS POWER NETWORK FO...
PLACEMENT OF POWER SYSTEM STABILIZER (PSS) IN NIGERIA 28-BUS POWER NETWORK FO...
ย 
DESIGN OF MPSS AND TCSC DAMPING CONTROLLERS IN MULTI- MACHINE POWER SYSTEM U...
DESIGN OF MPSS AND TCSC DAMPING CONTROLLERS  IN MULTI- MACHINE POWER SYSTEM U...DESIGN OF MPSS AND TCSC DAMPING CONTROLLERS  IN MULTI- MACHINE POWER SYSTEM U...
DESIGN OF MPSS AND TCSC DAMPING CONTROLLERS IN MULTI- MACHINE POWER SYSTEM U...
ย 
6843 traveling wave_ag_20171107_web2
6843 traveling wave_ag_20171107_web26843 traveling wave_ag_20171107_web2
6843 traveling wave_ag_20171107_web2
ย 
ANN Approach for Fault Classification in Induction Motors using Current and V...
ANN Approach for Fault Classification in Induction Motors using Current and V...ANN Approach for Fault Classification in Induction Motors using Current and V...
ANN Approach for Fault Classification in Induction Motors using Current and V...
ย 
Advance Current Monitoring Techniques to Detect and Diagnosis the Inter-Turn ...
Advance Current Monitoring Techniques to Detect and Diagnosis the Inter-Turn ...Advance Current Monitoring Techniques to Detect and Diagnosis the Inter-Turn ...
Advance Current Monitoring Techniques to Detect and Diagnosis the Inter-Turn ...
ย 
Transient Stability Assessment and Enhancement in Power System
Transient Stability Assessment and Enhancement in Power  SystemTransient Stability Assessment and Enhancement in Power  System
Transient Stability Assessment and Enhancement in Power System
ย 
Evaluation of Voltage Phase Fluctuations in Power Networks with Rapid Variabl...
Evaluation of Voltage Phase Fluctuations in Power Networks with Rapid Variabl...Evaluation of Voltage Phase Fluctuations in Power Networks with Rapid Variabl...
Evaluation of Voltage Phase Fluctuations in Power Networks with Rapid Variabl...
ย 
Multi-machine system with Series FACTS device: Static synchronous series comp...
Multi-machine system with Series FACTS device: Static synchronous series comp...Multi-machine system with Series FACTS device: Static synchronous series comp...
Multi-machine system with Series FACTS device: Static synchronous series comp...
ย 
[IJET-V1I5P10] Author: K.Dhivya, S.Nirmalrajan
[IJET-V1I5P10] Author: K.Dhivya, S.Nirmalrajan [IJET-V1I5P10] Author: K.Dhivya, S.Nirmalrajan
[IJET-V1I5P10] Author: K.Dhivya, S.Nirmalrajan
ย 
IRJET- Low Cost Harmonic Measurement using Arduino UNO
IRJET-  	  Low Cost Harmonic Measurement using Arduino UNOIRJET-  	  Low Cost Harmonic Measurement using Arduino UNO
IRJET- Low Cost Harmonic Measurement using Arduino UNO
ย 
Al4201250256
Al4201250256Al4201250256
Al4201250256
ย 
F010324347
F010324347F010324347
F010324347
ย 
OPTIMAL TORQUE RIPPLE CONTROL OF ASYNCHRONOUS DRIVE USING INTELLIGENT CONTROL...
OPTIMAL TORQUE RIPPLE CONTROL OF ASYNCHRONOUS DRIVE USING INTELLIGENT CONTROL...OPTIMAL TORQUE RIPPLE CONTROL OF ASYNCHRONOUS DRIVE USING INTELLIGENT CONTROL...
OPTIMAL TORQUE RIPPLE CONTROL OF ASYNCHRONOUS DRIVE USING INTELLIGENT CONTROL...
ย 
Condition monitoring of induction motor with a case study
Condition monitoring of induction motor with a case studyCondition monitoring of induction motor with a case study
Condition monitoring of induction motor with a case study
ย 
Condition monitoring of induction motor with a case study
Condition monitoring of induction motor with a case studyCondition monitoring of induction motor with a case study
Condition monitoring of induction motor with a case study
ย 
Online voltage stability margin assessment
Online voltage stability margin assessmentOnline voltage stability margin assessment
Online voltage stability margin assessment
ย 
Improvise 3-Level DTC of Induction Machine using Constant Switching Frequency...
Improvise 3-Level DTC of Induction Machine using Constant Switching Frequency...Improvise 3-Level DTC of Induction Machine using Constant Switching Frequency...
Improvise 3-Level DTC of Induction Machine using Constant Switching Frequency...
ย 

More from Power System Operation

ENERGY TRANSITION OUTLOOK 2021
ENERGY TRANSITION OUTLOOK  2021ENERGY TRANSITION OUTLOOK  2021
ENERGY TRANSITION OUTLOOK 2021Power System Operation
ย 
Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panelsPower System Operation
ย 
Power System Restoration Guide
Power System Restoration Guide  Power System Restoration Guide
Power System Restoration Guide Power System Operation
ย 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsPower System Operation
ย 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action SchemePower System Operation
ย 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...Power System Operation
ย 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePower System Operation
ย 
Gas Insulated Switchgear? Gas-Insulated High-Voltageย Switchgearย (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltageย Switchgearย (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltageย Switchgearย (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltageย Switchgearย (GIS)Power System Operation
ย 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & PartsPower System Operation
ย 
What are Balancing Services ?
What are  Balancing Services ?What are  Balancing Services ?
What are Balancing Services ?Power System Operation
ย 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools Power System Operation
ย 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy SystemPower System Operation
ย 
Power Purchase Agreement PPA
Power Purchase Agreement PPA Power Purchase Agreement PPA
Power Purchase Agreement PPA Power System Operation
ย 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testingPower System Operation
ย 

More from Power System Operation (20)

ENERGY TRANSITION OUTLOOK 2021
ENERGY TRANSITION OUTLOOK  2021ENERGY TRANSITION OUTLOOK  2021
ENERGY TRANSITION OUTLOOK 2021
ย 
Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panels
ย 
What does peak shaving mean
What does peak shaving meanWhat does peak shaving mean
What does peak shaving mean
ย 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
ย 
Power System Restoration Guide
Power System Restoration Guide  Power System Restoration Guide
Power System Restoration Guide
ย 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid Operations
ย 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action Scheme
ย 
Substation Neutral Earthing
Substation Neutral EarthingSubstation Neutral Earthing
Substation Neutral Earthing
ย 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
ย 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground Resistance
ย 
Gas Insulated Switchgear? Gas-Insulated High-Voltageย Switchgearย (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltageย Switchgearย (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltageย Switchgearย (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltageย Switchgearย (GIS)
ย 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & Parts
ย 
What is load management
What is load managementWhat is load management
What is load management
ย 
What does merit order mean
What does merit order meanWhat does merit order mean
What does merit order mean
ย 
What are Balancing Services ?
What are  Balancing Services ?What are  Balancing Services ?
What are Balancing Services ?
ย 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
ย 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
ย 
Power Purchase Agreement PPA
Power Purchase Agreement PPA Power Purchase Agreement PPA
Power Purchase Agreement PPA
ย 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
ย 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
ย 

Recently uploaded

Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxvipinkmenon1
ย 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
ย 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
ย 
Model Call Girl in Narela Delhi reach out to us at ๐Ÿ”8264348440๐Ÿ”
Model Call Girl in Narela Delhi reach out to us at ๐Ÿ”8264348440๐Ÿ”Model Call Girl in Narela Delhi reach out to us at ๐Ÿ”8264348440๐Ÿ”
Model Call Girl in Narela Delhi reach out to us at ๐Ÿ”8264348440๐Ÿ”soniya singh
ย 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
ย 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
ย 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
ย 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
ย 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
ย 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
ย 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
ย 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
ย 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
ย 
Study on Air-Water & Water-Water Heat Exchange in a Finned ๏ปฟTube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned ๏ปฟTube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned ๏ปฟTube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned ๏ปฟTube ExchangerAnamika Sarkar
ย 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
ย 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
ย 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
ย 

Recently uploaded (20)

Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptx
ย 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
ย 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
ย 
Model Call Girl in Narela Delhi reach out to us at ๐Ÿ”8264348440๐Ÿ”
Model Call Girl in Narela Delhi reach out to us at ๐Ÿ”8264348440๐Ÿ”Model Call Girl in Narela Delhi reach out to us at ๐Ÿ”8264348440๐Ÿ”
Model Call Girl in Narela Delhi reach out to us at ๐Ÿ”8264348440๐Ÿ”
ย 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
ย 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
ย 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
ย 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
ย 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
ย 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
ย 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
ย 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
ย 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
ย 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
ย 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
ย 
Study on Air-Water & Water-Water Heat Exchange in a Finned ๏ปฟTube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned ๏ปฟTube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned ๏ปฟTube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned ๏ปฟTube Exchanger
ย 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
ย 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
ย 
โ˜… CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
โ˜… CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCRโ˜… CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
โ˜… CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
ย 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
ย 

Synchrophasor Based Ocillation Detection: A Case Study for Indian Power Grid

  • 1. Synchrophasor Based Ocillation Detection: A Case Study for Indian Power Grid Vaishali Rampurkar Electrical Engineering Department Veermata Jijabai Technological Institute (VJTI) Mumbai, India Abstractโ€”The Indian electrical grid is one of the largest & complex networks in the world. Such complex system is subjected to stress or disturbances which manifest in the form of low frequency oscillations. Monitoring of these oscillations is necessary as they can disrupt the system if they are sustained for a longer period of time with significant magnitude. This paper presents the analysis of low frequency oscillation modes using the data from Phasor measurement unit located in Western and northern region of the country. It reports case studies of disturbances that occurred in the Indian power grid. The modes with low frequency oscillations were observed in both Western& northern region of the Indian grid.The Matrix Pencil technique was used to identify the oscillatory modes in system during the occurrence of the event. The importance of identifying critical oscillatory modes to improve the power system operation, has been brought out in this paper. Keywordsโ€”Phasor measurement unit, oscillations, power system stability, inter-area oscillations I. INTRODUCTION The Indian electrical grid is one of the largest and complex power grids in the world with an installed capacity of 227 GW [1]. It consists of five regional grids i.e. NR (northern Region), ER (Eastern Region), NER (North-Eastern Region), WR (Western Region) & SR (Southern Region) operating synchronously since December 2013. The operation & control of such complex network is carried out by the hierarchical network of load control centres. National load dispatch center (NLDC), five regional load despatch centres (RLDCs) thirty three state load despatch centres (SLDCs). The system operation has now become complex due to integration of high capacity transmission lines, renewables etc. leading to several unforeseen stability problems into the system. The decision making time by the operator of such a large grid has to be reduced with the complexity & stabilityproblems especially small signal stability problems due tostress in the system caused by higher loading levels. Thus facilitating the need for advanced monitoring and visualization tools. The technological advent of phasor measurement unit (PMU), has come out to be as tool which provides the grid operator with the real time view of the system. Indian grid has installed a number of PMUs at various locations [2]. PMU provides the time synchronised measurements of voltage and current phasors along with frequency & rateof change of frequency (ROCOF)synchronised with GlobalPositioning System (GPS) satellite [3]. These measurementsare utilised for power system operation & for analysis of eventsin post-despatch scenario [4].Various applications with benefits of PMU are explained in [5]. These PMU measurements canalso be used for Low frequency oscillation (LFO) detection [6]. This paper presents a case study that demonstrates the application of PMU to detect LFOs in the system & actions tobe taken to damp these oscillations.The paper is organised asfollows:Section II reviews the theoretical background on smallsignal stability, LFOs and proposed technique for LFO modedetection Matrix pencil method. Section IIIand IV presents brief description of the events that occurred in the WR and discusses the results of modal analysis. Section V, concludes the paper. II. THEORETICAL BACKGROUND A. Small signal stability Small signal disturbances during power system operationmay occur due to several reasons thereby affecting the powersystem. The ability of power system to be in steady state dueto such disturbances is called small signal stability. Transientstability is associated with the ability of power system tomaintain synchronism when subjected to large disturbanceslike line faults, bus fault, generator trip etc. During thesedisturbances the electromagnetic & mechanical torques ofeach synchronous machine need to be maintained. The electromechanicaltorque of synchronous machine can be resolvedinto two components: synchronizing torque component(๐พ๐‘ ) &damping torque component(๐พ๐‘‘ )as shown in (1). โˆ†๐‘‡๐‘’ = ๐พ๐‘ โˆ†๐œ• + ๐พ๐‘‘ โˆ†๐œ” = ๐‘‡๐‘  + ๐‘‡๐‘‘ 1 Where: ๐พ๐‘ : Synchronizing torque coefficient โˆ†๐œ•: Rotor angle perturbation โˆ†๐œ”: Speed variation ๐พ๐‘‘ : Damping torque coefficient ๐‘‡๐‘  : Synchronizing torque ๐‘‡๐‘‘ : Damping torque The damping torque (๐‘‡๐‘‘ ) changes with the change in damping torque coefficient (๐พ๐‘‘ ) & variation in speed (โˆ†๐œ”).Reduced damping torque (๐‘‡๐‘‘ ) gives rise to low frequencyoscillations[7]. Undamped oscillations can increase inmagnitude & lead to instability and are therefore an object International Journal of Engineering Research & Technology (IJERT) ISSN: 2278-0181 www.ijert.orgIJERTV4IS040029 (This work is licensed under a Creative Commons Attribution 4.0 International License.) Vol. 4 Issue 04, April-2015 29
  • 2. ofstudy by various researchers. These oscillations are classifiedinto four major types inter-area modes (0.1 Hz - 1 Hz),intra-plant modes (1 Hz - 2.5 Hz), torsional modes (10 Hz-40Hz) & control modes. The inter-area modes are associatedwith swinging of groups of generators in one area of thesystem against generators in other area. They usually occurbecause of weak interconnecting network. The intra- plantmodes occur due to the swinging of units of generating stationwith respect to each other. The torsional modes are associatedwith turbine-generator shaft system and associated rotationalcomponents. The control modes are present in the systembecause of poor design of controllers of AVR, HVDC, SVC,AGC etc. Disturbances can occur in the interconnected power system due to faults, load changesand when these disturbances occur oscillations usually arise in the system. These oscillations are acceptable as long as they decay [7,8]. It is very important to monitor theseoscillations to ensure that no lightly damped oscillatory modes exist in the system asthey threaten the reliable operation of the power system. The small signal instabilityissues need to be addressed since most of the blackouts have been associated with it [9]. The oscillations can be regarded as the characteristic of the system i.e. oscillatoryparameters are dependent on the physical infrastructure. Every power grid is unique inits physical connections thus presence of oscillations vary with the networks. The powersystem oscillations are complex and difficult to analyse. There exist two techniques for detecting the LFOs of thepower system: model based techniques & measurement basedtechniques [10]. In the model based technique the non- lineardifferential equations governing the system are linearizedabout an operating point & further the modes are obtainedvia Eigen value analysis [7]. In the measurement basedtechniques direct measurements from PMU estimate the linearmodel. Some of the popular measurement based techniquesfor estimating LFOs are Fast Fourier Transform (FFT), Pronyanalysis [11] [12], Matrix Pencil [13], Hilbert transform [14,15,16],wavelet transform [17,18,19]. A comparative study ofvarious techniques for identification of oscillations has beenexamined in [20,21]. B. Matrix Pencil method Matrix pencil method is an efficient approach to fit measured date set with sum of exponentials. This method is just a one step process of finding signal poles directly from the Eigen values of the matrix developed. It directly estimates the parameters for the exponential terms in 1 to an observed measurement [1, 2]. ๐‘ฆ ๐‘ก = ๐ด๐‘– ๐‘’ ๐œŽ ๐‘– ๐‘ก cosโก(๐œ”๐‘– ๐‘ก + ๐œ‘๐‘–) ๐‘› ๐‘–=1 1 Data matrix [Y] is formed using input data shown in 2 ๐‘ฆ(0) ๐‘ฆ(1) โ€ฆ ๐‘ฆ(๐ฟ) ๐‘ฆ(1) ๐‘ฆ(2) โ€ฆ ๐‘ฆ(๐ฟ + 1) : : : : ๐‘ฆ(๐‘ โˆ’ ๐ฟ โˆ’ 1) ๐‘ฆ(๐‘ โˆ’ ๐ฟ) โ€ฆ ๐‘ฆ(๐‘ โˆ’ 1) (๐‘โˆ’๐ฟ)๐‘‹(๐ฟ+1) 2 Where N is number of measured samples, L is pencil parameter. Next SVD of matrix [Y] is calculated which gives: ๐‘Œ = ๐‘ˆ ฮฃ ๐‘‰ ๐‘‡ 3 Here [U] & [V] are unitary matrices composed of eigenvectors of Y ๐‘‡ ๐‘Œ & ๐‘Œ Y ๐‘‡ respectively, and ฮฃ is diagonal matrix consisting of singular values of [Y]. Next consider the filtered matrix ๐‘‰โ€ฒ , it contains n dominant right singular vector of [V]. Thus ๐‘Œ1 = ๐‘ˆ ฮฃโ€ฒ [๐‘‰1โ€ฒ] ๐‘‡ 4 ๐‘Œ2 = ๐‘ˆ ฮฃโ€ฒ [๐‘‰2โ€ฒ] ๐‘‡ 5 The poles of the signal are given by non-zero Eigen values of { ๐‘‰1โ€ฒ] ๐‘‡ + [๐‘‰2โ€ฒ] ๐‘‡ 6 Once n & poles (๐œŽ๐‘–) are known residues are solved using least square sense. ๐‘ฆ(0) ๐‘ฆ(1) : ๐‘ฆ(๐‘ โˆ’ 1) = 1 1 โ€ฆ 1 ๐‘ง1 ๐‘ง2 โ€ฆ ๐‘ง ๐‘› : : : : ๐‘ง1 ๐‘โˆ’1 ๐‘ง2 ๐‘โˆ’1 โ€ฆ ๐‘ง ๐‘› ๐‘โˆ’1 ๐ต1 ๐ต2 : ๐ต๐‘› III. CASE STUDY-I This section analyses the event that took place in the WR of the Indian power grid. On 3rd March 2013 at 18:04 hours, a bus fault occurred at Parli in Maharashtra state. The frequency and rate of change of frequency (ROCOF) recorded by PMU located at Badrawati are shown in Fig. 1 Fig. 1. Frequency and ROCOF at Bhadrawati International Journal of Engineering Research & Technology (IJERT) ISSN: 2278-0181 www.ijert.orgIJERTV4IS040029 (This work is licensed under a Creative Commons Attribution 4.0 International License.) Vol. 4 Issue 04, April-2015 30
  • 3. The measurements at Badrawati indicate sharp fall in the frequency and ROCOF. Three spikes were observed in the measurements with, and the third spike was the severe one indicating tripping of all elements. The ROCOF reached approximately 0.17 Hz/sec when the event occurred. The frequency also started dropping and reached 49.8 Hz within 1 sec. Fig. 2. Line voltages recorded at Badrawati The line voltages recorded by PMU placed at Bhadrawati are shown in Fig. 2. The disturbance at Parli is indicated by sharp pulses.It can observed that after the event occurred at Parli, line voltages reduced. Fig.3. Phase currents recorded at Badrawati Fig-3, shows the plot for linecurrents recorded by PMU at Badrawati. The measurements show sharp pulses indicating loss of elements in the system. The line currents were observed to have reduced values after the disturbance. The measurements also show the presence of oscillations in the system. Fig. 4. Frequency plots NR and WR After the bus fault at Parli in WR, the frequency measurement obtained from at Raipur in WR and Agra, Ballia, Hissar in NR were compared for the behavior of the system. It can be clearly observed from Fig-4 that WR machines are oscillating against the NR machines till the new equilibrium point reached in 3 secs. TABLE I. RESULTS OF MODAL ANALYSIS CASE STUDY- I Sr.No. Location of PMU Freq (Hz) Damping Amplitude 1 Raipur (WR) 0.6 -0.01509 0.04124 2 0.8 0.06814 0.08434 3 1.5 0.0365 0.031 4 2.7 0.0025 0.0042 1 Agra (NR) 0.6 -0.03529 0.02148 2 0.8 0.01722 0.01041 3 1.5 0.00235 0.006 4 2.7 0.00079 0.00378 The results of modal analysis using Prony method have been tabulated in Table-1. The voltage measurements at recorded by PMU at Raipur in WR and Agra in NR have been used for analysis. It can be observed from the results that the modes with frequencies of 0.6 Hz, 0.8 Hz, 1.5 Hz and 2.7 Hz, were identified with negative and close to zero damping. The 0.6 Hz oscillatory mode was estimated to have negative damping both in Raipur as well as Agra. The 0.8 Hz, 1.5Hz and 2.7 Hz modes were observed to have close to zero damping but comparatively lower amplitudes as compared to the 0.6 Hz mode. Since the 0.6 Hz inter-area oscillatory mode has negative damping and higher amplitude is quantified as the critical mode in the system. The amplitude of all the oscillatory modes at Raipur are more than those observed at Agra. This is because Agra is located far from the place where the event occurred (i.e. Parli). International Journal of Engineering Research & Technology (IJERT) ISSN: 2278-0181 www.ijert.orgIJERTV4IS040029 (This work is licensed under a Creative Commons Attribution 4.0 International License.) Vol. 4 Issue 04, April-2015 31
  • 4. IV. CASE STUDY -II This section analyses a disturbance that occurred at Sipat in WR on 14th September 2012 at 18:58:22 hours. The PMU measurements at recorded at Raipur in WR clearly indicate unstable behavior of the system. Fig.5. Frequency and ROCOF at Raipur The frequency and ROCOF measurements at recorded at Raipur during the disturbance in Sipat as shown in Fig. 5. The measurements at Raipur clearly indicate when the event was triggered at Sipat i.e. at 18:58:22.320 hours as shown in the encircled section in the figure. It can also be observed that when Sipat unit tripped Raipur PMU shows that ROCOF reached a value of -0.15 Hz/sec. Fig.6. Raipur-Bhadrawati power flow The real power flow on Raipur- Bhadrawati line also indicates the occurrence of disturbance at Sipat. It can be clearly observed in Fig.6 that with the loss of units at Sipat the power flow on Raipur- Bhadrawati increased. Fig.7. Line voltages recorded by PMU located at Raipur The voltage measurements at Raipur also indicate sharp voltage dips at the time of disturbance. With the disturbance at Sipat, increased power flow on Raipur- Bhadrawati line resulted in decrease in line voltages at Raipur as shown in Fig. 7. The line currents measurements for Raipur- Bhadrawati line are shown in Fig.8. This recorded data also indicates the event occurrence with the sharp pulses. It can also be observed that with the event occurrence power flow on this line increased which lead to decreased line voltages at Raipur thus leading to increased line currents. This can be clearly observed in Fig. 8. Modal analysis of the power flow measurement on Raipur- Bhadrawati line was carried out using matrix pencil technique in-order to identify the oscillatory modes excited in the system due to the disturbance. The analysis was carried out for two instances Duration 1 (before) and Duration 2 (after) the disturbance in-order study the behavior of the modes. Fig.8. Raipur- Bhadrawati Line current 48.4 48.6 48.8 49 49.2 49.4 49.6 49.8 50 50.2 50.4 -0.2 -0.15 -0.1 -0.05 0 0.05 0.1 0.15 0.2 18:45:00.000 18:45:23.559 18:45:47.120 18:46:10.679 18:46:34.240 18:46:57.800 18:47:21.360 18:47:44.920 18:48:08.480 18:48:32.040 18:48:55.600 18:49:19.160 18:49:42.720 18:50:06.280 18:50:29.840 18:50:53.400 18:51:16.960 18:51:40.520 18:52:04.080 18:52:27.640 18:52:51.200 18:53:14.760 18:53:38.320 18:54:01.880 18:54:25.440 18:54:49.000 18:55:12.559 18:55:36.120 18:55:59.679 18:56:23.240 18:56:46.800 18:57:10.360 18:57:33.920 18:57:57.480 18:58:21.040 18:58:44.600 18:59:08.160 18:59:31.720 18:59:55.280 19:00:18.840 19:00:42.400 19:01:05.960 19:01:29.520 19:01:53.080 19:02:16.640 19:02:40.200 19:03:03.760 19:03:27.320 19:03:50.880 19:04:14.440 19:04:38.000 Frequency(Hz) df/dt Raipur df/dt Raipur freq RaipurPMU shows that df/dt whenSipat unit strippedreacheda value of - 0.15 Hz/sec Eventtriggeredat 18:58:22.320 Hrs 48.4 48.6 48.8 49 49.2 49.4 49.6 49.8 50 50.2 50.4 380 400 420 440 460 480 500 520 540 560 18:45:00.000 18:45:23.080 18:45:46.160 18:46:09.240 18:46:32.320 18:46:55.400 18:47:18.480 18:47:41.559 18:48:04.640 18:48:27.720 18:48:50.800 18:49:13.880 18:49:36.960 18:50:00.040 18:50:23.120 18:50:46.200 18:51:09.280 18:51:32.360 18:51:55.440 18:52:18.520 18:52:41.600 18:53:04.679 18:53:27.760 18:53:50.840 18:54:13.920 18:54:37.000 18:55:00.080 18:55:23.160 18:55:46.240 18:56:09.320 18:56:32.400 18:56:55.480 18:57:18.559 18:57:41.640 18:58:04.720 18:58:27.800 18:58:50.880 18:59:13.960 18:59:37.040 19:00:00.120 19:00:23.200 19:00:46.280 19:01:09.360 19:01:32.440 19:01:55.520 19:02:18.600 19:02:41.679 19:03:04.760 19:03:27.840 19:03:50.920 19:04:14.000 19:04:37.080 Frequency(Hz) RealPower(MW) Raipur Bwati Ckt 1 Real Power Raipur freq With each occurence the power flow in Raipur-Bhadrawati T/C increased 48.4 48.6 48.8 49 49.2 49.4 49.6 49.8 50 50.2 50.4 220 225 230 235 240 245 250 18:45:00.000 18:45:23.080 18:45:46.160 18:46:09.240 18:46:32.320 18:46:55.400 18:47:18.480 18:47:41.559 18:48:04.640 18:48:27.720 18:48:50.800 18:49:13.880 18:49:36.960 18:50:00.040 18:50:23.120 18:50:46.200 18:51:09.280 18:51:32.360 18:51:55.440 18:52:18.520 18:52:41.600 18:53:04.679 18:53:27.760 18:53:50.840 18:54:13.920 18:54:37.000 18:55:00.080 18:55:23.160 18:55:46.240 18:56:09.320 18:56:32.400 18:56:55.480 18:57:18.559 18:57:41.640 18:58:04.720 18:58:27.800 18:58:50.880 18:59:13.960 18:59:37.040 19:00:00.120 19:00:23.200 19:00:46.280 19:01:09.360 19:01:32.440 19:01:55.520 19:02:18.600 19:02:41.679 19:03:04.760 19:03:27.840 19:03:50.920 19:04:14.000 19:04:37.080 Frequency(Hz) LineVoltage(kV) Va Vb Vc Raipur freq Voltage at Raipur decreses with in crease in line loading International Journal of Engineering Research & Technology (IJERT) ISSN: 2278-0181 www.ijert.orgIJERTV4IS040029 (This work is licensed under a Creative Commons Attribution 4.0 International License.) Vol. 4 Issue 04, April-2015 32
  • 5. TABLE II. RESULTS OF MODAL ANALYSIS CASE STUDY- II Event 1 Time Instant Frequency Damping Amplitude Duration 1 0.35 0.06561 11.00855 0.69 0.1065 11.33678 1.2 0.05737 7.1932 Duration 2 0.34 0.16818 8048.51036 0.7 0.1334 162507.274 1.2 0.05391 683.88899 Event 2 Duration 1 0.33 0.26122 44.43362 0.71 0.06076 3.44972 1.2 -0.0087 0.18098 Duration 2 0.36 0.01412 1.17597 0.69 0.05844 16.34748 1.18 -0.00506 0.31271 The results of modal analysis are tabulated in TABLE II. It can be observed for event 1 in the system the oscillatory modes with frequencies of 0.35 Hz, 0.7 Hz and 1.2 Hz for both the time instants before and after the disturbance. The 1.2 Hz mode was identified to have low damping for both the time instances.All the oscillatory modes were observed to have higher amplitudes after the event 1. Analyzing event 2 in the network (i.e. second spike in the measurements) indicated presence of 0.3 Hz, 0.7 Hz and 1.2 Hz modes. The 0.3 Hz mode had improved damping before the second disturbance and it reduced to 0.014 after the disturbance. Similarly the damping of 0.7 Hz mode also reduced after the event 2. After the occurrence of event 1 the 1.2 Hz mode was observed to have negative damping for both time instants for event 2. V. CONCLUSION Low frequency oscillations (LFOs) are inherent to interconnected power systems. These oscillations need to be stable in order to have secure power system operations. The Indian grid has recently installed a number of PMUs in the system which increase the situational awareness amongst the operators. This paper tries to demonstrate one possible application of PMU measurements in the power system i.e. identification of low frequency oscillations. This paper uses Matrix pencil for identification of LFOs. This paper also indicates that as the location of PMU increases from the event located the amplitude of modal parameters is observed to have reduced. Thus it can be concluded that the PMU placed far away from the event location will indicate lower amplitude for a critical mode observed in the system. Some of the devices in the power system to counteract negative damping include PSS inexcitation system of generator & controls of FACTS devices.The real time actions by system operator include generationre-despatch, load shedding, circuit switching etc. to relievethe stress in the system. This case study has indicated theimportance of PMUs & their location towards identificationof LFOs and its source identification. Extensive research needs to be carried out on theoptimum placement of PMUs to record the events & foranalysis of LFOs in the system. Ongoing work deals with developing tools for advanced monitoring of the power grid operations. With increase in the number of PMUs placed in the system will lead to increased observability. ACKNOWLEDGMENT The authors gratefully acknowledge the support provided byCenter of Excellence in Complex and Nonlinear DynamicalSystems, VJTI, Mumbai & Western Region Load DespatchCentre for valuable discussions & support. REFERENCES [1] CEA [2] Synchrophasor Initiatives in India- Report by POSOCO [3] A.G.Phadke, โ€œSynchronised Phasor Measurement units in power systems,โ€ IEEE Comput.Appl.Power, vol.6, No.2, pp. 10-15, April 1993 [4] Jaime De La Ree, Virgilio Centono, James S. Thorp, A.G. Phadke,โ€œSynchronized Phasor Measurement Applications in Power Systemsโ€, IEEE Transactions on smart grid, vol.1,no.1, pp. 20-27, June 2010. [5] Damir Novosel, Khoi Vu, โ€œ Benefits of PMU technology for various applicationsโ€ International Council on large electric systems -Cigre, 7th Symposium on Power system Management, 2006 [6] Wuxing Liang, Harmeet Kang, and Liangzhong Yao, โ€œDetection of Power System Oscillations Using Moving Window Prony Methodโ€ Power System Technology (POWERCON), 2010 International Conference,October 2010. [7] P. Kundur, โ€œPower system stability and Controlโ€ McGraw-Hill, 1994. [8] G. Rogers, Power System Oscillations: Kluwer Academic, 2000. [9] G. Andersson, P. Donalek, R. Farmer, N. Hatziargyriou, I. Kamwa, P. Kundur, N. Martins, J. Paserba, P. Pourbeik,J. Sanchez-Gasca, R. Schulz, A. Stankovic, C. Taylor, and V. Vittal"Causes of the 2003 Major Grid Blackouts in North America and Europe, and Recommended Means to Improve System Dynamic Performance," IEEE Transactions on Power SystemS,vol. 20, No. 4, November 2005 [10] Ning Zhou; Trudnowski, D.J.; Pierre, J.W.; Mittelstadt, W.A., โ€ElectromechanicalMode Online Estimation Using Regularized RobustRLS Methods, IEEE Transactions on Power Systems,vol.23, no.4,pp.1670,1680,Nov-2008 [11] Hauer, J.F.; Demeure, C.J.; Scharf, L.L., โ€Initial results in Prony analysisof power system response signals,โ€ IEEE Transactions Power Systems,,vol.5, no.1, pp.80-89, Feb1990 [12] D. Trudnowski, J. Johnson, and J. Hauer, Making prony analysis moreaccurate using multiple signals, IEEE Trans. Power Syst., vol. 14, no.1,pp. 226231, Feb. 1999. [13] Lisa L. Grant ,Mariesa L. Crow, Comparison of Matrix Pencil & Prony Methodsfor power system modal analysis of noisy signals", North American Power Symposium(NAPS) , August 2011 [14] Messina, A.R.; Vittal, V., "Nonlinear, non-stationary analysis of interarea oscillations via Hilbert spectral analysis,"IEEE Transactions Power Systemson , vol.21, no.3,pp.1234,1241, Aug. 2006 [15] Laila, D.S.; Messina, A.R.; Pal, B.C., "A Rened HilbertHuang Transform WithApplications to Inter-area Oscillation Monitoring,"IEEE Transactions Power Systems,vol.24, no.2, pp.610,620, May 2009 [16] Dechang Yang; Rehtanz, C.; Yong Li; Deyou Yang, "A hybrid method and itsapplications to analyse the low frequency oscillations in the interconnected power system,"IET, Generation, Transmission & Distribution , vol.7, no.8, pp.874,884, Aug.2013 [17] Rueda, J.L.; Juarez, C.A.; Erlich, I., "Wavelet-Based Analysis of Power SystemLow-Frequency Electromechanical Oscillations," IEEE Transactions on Power Sys-tems, vol.26, no.3, pp.1733,1743, Aug. 2011 [18] Bruno, S.; De Benedictis, M.; La Scala, M., ""Taking the pulse" of Power Systems: Monitoring Oscillations by Wavelet Analysis and International Journal of Engineering Research & Technology (IJERT) ISSN: 2278-0181 www.ijert.orgIJERTV4IS040029 (This work is licensed under a Creative Commons Attribution 4.0 International License.) Vol. 4 Issue 04, April-2015 33
  • 6. Wide Area Measurement System,"IEEE PES, Power Systems Conference and Exposition, 2006. PSCE '06, vol.,no., pp.436,443, Oct. 29 2006-Nov. 1 2006 [19] Xueping Pan; Venkatasubramanian, V., "Multi-power system oscillation monitoring using synchrophasors,"IEEE PES InnovativeSmart Grid Technologies (ISGT), 2012, vol., no., pp.1,10, 16-20 Jan. 2012 [20] Vaishali Rampurkar, Faruk Kazi, Harivittal Mangalvedekar, P. Pentayya, ChandanKumar and Rajkumar A, "A comparative analysis of Modal analysis techniques ACase study for Western Region of India" 5th International Conference on Power &Energy Systems,2013 [21] Rampurkar, V.; Kazi, F.; Mangalvedekar, H.A.; Pentayya, P.; Kumar, C.; Rajkumar, A., "PMU based identification of low frequency oscillations A case study,"IEEE,Innovative Smart Grid Technologies - Asia (ISGT Asia), 2013, vol., no., pp.1,5, 10-13Nov. 2013 International Journal of Engineering Research & Technology (IJERT) ISSN: 2278-0181 www.ijert.orgIJERTV4IS040029 (This work is licensed under a Creative Commons Attribution 4.0 International License.) Vol. 4 Issue 04, April-2015 34