SlideShare a Scribd company logo
1 of 15
1
AGC 3
1.0 Introduction
The primary controller response to a
load/generation imbalance results in generation
adjustment so as to maintain load/generation
balance. However, due to droop, it also results
in a non-zero steady-state frequency deviation.
This frequency deviation must be corrected.
Also, the net scheduled export must be
maintained according to the purchase
agreements.
Primary control does nothing to correct the
steady-state frequency error or the net scheduled
export. These two problems are handled by
providing a supplementary signal from the
control center to each generation unit on
automatic generation control (AGC).
2
The signal is derived from the Area Control
Error (ACE) and, when received at a generation
plant, activates the “speed changer motor” to
adjust the energy supply set point to the
generator.
In these notes, we will learn how the ACE is
computed, and we will see how it is used in
correcting steady-state frequency error.
2.0 Review
From our notes AGC1, we defined the following
terms:
 Net Actual Interchange: APij
 Net Scheduled Interchange: SPij
 Interchange Deviation (defined pg 396 of text):
ΔPij=APij-SPij (1)
Note that the above terms are each defined with
respect to two distinct areas.
3
We also defined, in AGC1, the following terms:
 Actual Export: 

n
j
iji APAP
1
(2)
 Scheduled Export: 

n
j
iji SPSP
1
(3)
 Net Deviation: 

n
j
iji PP
1
(4)
Note that the above three terms are each defined
with respect to a single area.
We also saw that the net deviation is related to
the net actual and scheduled interchanges, and
to the actual and scheduled exports, by:
ii
n
j
ij
n
j
ij
ij
n
j
ij
n
j
iji
SPAPSPAP
SPAPPP






11
11
)(
(5)
Although your text does not define net
deviation, it does use it as the first term in the
ACE expression of eq. (11.30).
4
Finally, we saw in our notes AGC2, when
discussing the multi-machine case, that












Kpu
RK
pu
R
R
S
R
S
Pf
...
60
1
1 (6)













Kpu
RK
pu
Rpui
Ri
pui
Ri
Mi
R
S
R
S
P
R
Sf
R
S
P
...
60
1
1 (7)
If all units have the same per-unit droop
constant, i.e., if R1pu=R2pu=…=RKpu, then eqs.
(6) and (7) become
 RKR
pu
SS
PRf




...60 1
(8)
 RKR
Ri
pu
Ri
Mi
SS
PSf
R
S
P





...60 1
(9)
In eqs. (8) and (9), ΔP represents the change in
total load so that it is
 positive if load increases and negative if load
decrease;
 positive if generation decreases and negative if
generation increases.
5
3.0 Area Control Error
The Area Control Error (ACE) is composed of
 Net Deviation ΔPi, from eq. (5), written more
compactly below:
iii SPAPP  (5)
When ΔPi>0, it means that the actual export
exceeds the scheduled export, and so the
generation in area i should be reduced.
 Steady-state frequency deviation
60 ff (10)
When Δf>0, it means the generation in the
system exceeds the load and therefore we
should reduce generation in the area.
From the above, our first impulse may be to
immediately write down the ACE for area i as:
fPACE ii  (11a)
Alternatively (and consistent with the text)
 ii PACE (11b)
6
But we note 2 problems with eq. (11). First, we
are adding 2 quantities that have different units.
Anytime you come across a relation that adds 2
or more units having different units, beware.
The second problem is that the magnitudes of
the two terms in eq. (11) may differ
dramatically. If we are working in MW and Hz
(or rad/sec), then we may see ΔPi in the 100’s of
MW whereas we will see Δf (or Δω) in the
hundredths or at most tenths of a Hz. The
implication is that the control signal, per eq.
(11), will greatly favor the export deviations
over the frequency deviations.
Therefore we need to scale one of them. To do
so, we define area i frequency bias as βi. It has
units of MW/Hz. Your text shows (pg. 393) that
fi
Lfififi
R
DD
1

(12a)
i
iLii
R
DD


1

(12b)
7
where
 Di is the damping coefficient from the swing
equation (and represents the effect of
synchronous generator windage and friction);
 DLi is the load damping coefficient and
represents the tendency of the load to decrease
as frequency decreases (an effect mainly
attributed to induction motors).
 The f or ω subscripts indicate whether we will
compute ACE using f or ω (text uses ω).
The damping terms of eq. (12) are usually
significantly smaller than the regulation term, so
that a reasonable approximation is that
fi
fi
R
1

(12c)
i
i
R

1

(12d)
Then the ACE equation becomes:
fPACE fiii   (12e)
  iii PACE (12f)
8
4.0 Example
Consider the two-area interconnection shown in
Fig. 1 with data given as below.
A1 A2
1000 MW
Fig. 1
Area 1 Area 2
Load=20,000 MW Load=40,000 MW
Capacity=20,000 MW Capacity=42,000 MW
Gen=19,000 MW Gen=41,000 MW
R1pu=0.05 R1pu=0.05
The scheduled interchange is 1000 MW flowing
from A2 to A1, so that scheduled exports are:
 SP1=-1000 MW
 SP2=1000 MW
There are two parts to this problem:
1.Determine frequency and generation of each
area and the tie line flow after a 1000 MW
loss of load in A1, but before supplementary
control has taken effect (this means we will
determine only the effect of primary control).
9
2.Repeat (1) after supplementary control action
has taken effect.
Solution:
We assume that area capacities are the ratings:
SR1=20000
SR2=42000
We also note that the load decreases, therefore
ΔP=-1000 MW.
1.From eq. (8),
 
pu
SS
PRf
RKR
pu
000806.0
]4200020000[
)1000(05.0
...60 1








Therefore
Hzf 0484.060*000806.0 
so that f=60.0484 Hz.
Then we can compute the increase in generation
in each area per eq. (9). For Area 1:
 
MW
SS
PS
P
RR
R
M 6.322
4200020000
)1000)(20000(
11
1
1 






Therefore
MWPM 4.677,186.322190001 
10
For Area 2:
 
MW
SS
PS
P
RR
R
M 4.677
4200020000
)1000)(42000(
11
2
2 






Therefore
MWPM 6.322,404.677410002 
It is of interest now to obtain the actual exports,
and we can do this for each area by taking the
difference between load and generation. The
loads in areas 1 and 2 were 20000 and 40000,
but remember that we lost 1000 MW of load in
area 1, so that its value is now 19000.
Generation levels were computed above.
Therefore
AP1=18,677-19,000=-322.6 MW
AP2=40,322.6-40,000=322.6 MW
So clearly the new tie-line flow is 322.6 MW
from A2 to A1.
Note: For multiple areas, calculating tie-line
flows requires a power flow solution (DC power
flow is suitable to use here).
11
From eq. (5), net deviation is:
4.677)1000(6.322111  SPAPP
4.677)1000(6.322222  SPAPP
2.To find the effect of supplementary control,
we first need to compute the frequency bias
parameters. We neglect effects of damping
terms, so that we use eq. (12c) or (12d):
fi
fi
R
1

(12c)
i
i
R

1

(12d)
But note that the droop constant in (12c) or
(12d) is not in per-unit. To convert to per-unit,
recall eqs. (13) and (14) from AGC2 notes:
M
f
P
f
R



(13a)
MP
R




 (13b)
Mpu
pu
Mpu
pu
rMrM
pu
PP
f
SPSP
ff
R













/
/
/
/ 00
(14)
12
Substituting eq. (13a) or (13b) into (14) gives:
00
0
/
/
f
S
R
f
S
P
f
SP
ff
R r
f
r
MrM
pu 






(15a)
00
0
/
/



rr
MrM
pu
S
R
S
PSP
R 






(15b)
Therefore
r
puf
S
f
RR 0

(16a)
r
pu
S
RR 0
 
(16b)
We can use (16a) to calculate the frequency bias
term of (12c), which is used in the ACE
equation of (12d):
fPACE fiii   (12d)
Alternatively, we can use (16b) to calculate the
frequency bias terms of (12d), which is used in
the ACE equation of (12e):
  iii PACE (12e)
In the rest of this example, we will use (16a),
(12c), and (12d).
13
Applying eq. (16a) to obtain Rf1 and Rf2, we get
MWHz
S
f
RR
r
puf /00015.0
20000
60
05.0
1
0
1 
MWHz
S
f
RR
r
puf /000071429.0
42000
60
05.0
2
0
2 
Then the frequency bias terms are obtained as
HzMW
Rf
f /7.6666
00015.0
11
1
1 
HzMW
Rf
f /14000
000071429.0
11
2
2 
Now we can compute the ACE in each area:
MW
fSPAPfPACE ff
100068.3224.677
484)6666.7(0.0-1000)--322.6(
)( 111111


 
MW
fSPAPfPACE ff
06.6774.677
84)14000(0.041000)-322.6(
)( 222222


 
14
So what does this mean?
 ACE1 indicates that the generators in A1
receive a signal to decrease generation by 1000
MW. Recall from page 9 that after primary
control action, PM1=18,677.4 MW. With a
1000 MW decrease, then PM1=17,677.4 MW.
 ACE2 indicates that the generators in A2 do not
change, so PM2=40,322.6 MW.
But now consider that previous to the secondary
control action, we were at a steady state (with
steady-state frequency deviation of 0.0484 so
that f=60.0484 Hz). Now the ACE signal has
cause a decrease in A1 generation by 1000 MW.
This action creates a load-generation imbalance
of ΔP=+1000 MW that will cause unit primary
controllers to act in both areas. From eq. (8):
 
pu
SS
PRf
RKR
pu
000806.0
]4200020000[
)1000(05.0
...60 1








Therefore
Hzf 0484.060*000806.0 
so that f=60.0484 - 0.0484 = 60Hz.
15
Then we compute the increase in generation in
each area per eq. (9). For Area 1:
 
MW
SS
PS
P
RR
R
M 6.322
4200020000
)1000)(20000(
11
1
1 






Therefore
MWPM 000,186.3224.176771 
For Area 2:
 
MW
SS
PS
P
RR
R
M 4.677
4200020000
)1000)(42000(
11
2
2 






Therefore
MWPM 000,414.6776.322,402 
The exports for the two areas will then be:
AP1=18,000-19,000=-1000 MW
AP2=41,000-40,000=+1000 MW
A summary of the situation is given below,
where we see that the final control action has
resulted in A1 generation entirely compensating
for the A1 load decrease of 1000 MW (with area
exports unchanged).
Area 1 Area 2
Load=19,000 MW Load=40,000 MW
Gen=18,000 MW Gen=41,000 MW

More Related Content

What's hot

Design and Simulation of Power Factor Correction Boost Converter using Hyster...
Design and Simulation of Power Factor Correction Boost Converter using Hyster...Design and Simulation of Power Factor Correction Boost Converter using Hyster...
Design and Simulation of Power Factor Correction Boost Converter using Hyster...
ijtsrd
 
Reactive power compensation using statcom
Reactive power compensation using statcomReactive power compensation using statcom
Reactive power compensation using statcom
Amit Meena
 

What's hot (20)

PRIME MOVERS & GOVERNING SYSTEMS
PRIME MOVERS & GOVERNING SYSTEMSPRIME MOVERS & GOVERNING SYSTEMS
PRIME MOVERS & GOVERNING SYSTEMS
 
Chapter 5
Chapter 5Chapter 5
Chapter 5
 
V and inverted v curves of synchronous motor
V and inverted v curves of synchronous motorV and inverted v curves of synchronous motor
V and inverted v curves of synchronous motor
 
Small signal stability analysis
Small signal stability analysisSmall signal stability analysis
Small signal stability analysis
 
upfc
upfcupfc
upfc
 
Load Frequency Control of Two Area System
Load Frequency Control of Two Area SystemLoad Frequency Control of Two Area System
Load Frequency Control of Two Area System
 
Design and Simulation of Power Factor Correction Boost Converter using Hyster...
Design and Simulation of Power Factor Correction Boost Converter using Hyster...Design and Simulation of Power Factor Correction Boost Converter using Hyster...
Design and Simulation of Power Factor Correction Boost Converter using Hyster...
 
Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)
 
Reactive power compensation using statcom
Reactive power compensation using statcomReactive power compensation using statcom
Reactive power compensation using statcom
 
Unit 4 Automatic Generation Control
Unit 4 Automatic Generation ControlUnit 4 Automatic Generation Control
Unit 4 Automatic Generation Control
 
induction generator final.pptx
induction generator final.pptxinduction generator final.pptx
induction generator final.pptx
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
Power quality improvement techniques
Power quality improvement techniquesPower quality improvement techniques
Power quality improvement techniques
 
Fault analysis
Fault analysisFault analysis
Fault analysis
 
Load flow studies
Load flow studiesLoad flow studies
Load flow studies
 
Thyristor switched capacitor
Thyristor switched capacitorThyristor switched capacitor
Thyristor switched capacitor
 
Speed control of Three phase Induction motor using AC voltage regulator
Speed control of Three phase Induction motor using AC voltage regulatorSpeed control of Three phase Induction motor using AC voltage regulator
Speed control of Three phase Induction motor using AC voltage regulator
 
Power System Stablity
Power System StablityPower System Stablity
Power System Stablity
 
Power system voltage stability
Power system voltage stabilityPower system voltage stability
Power system voltage stability
 
Upfc & fact
Upfc & factUpfc & fact
Upfc & fact
 

Similar to Automatic Generation Control-3

ENEL301 report _Joseph Haystead_1132999
ENEL301 report _Joseph Haystead_1132999ENEL301 report _Joseph Haystead_1132999
ENEL301 report _Joseph Haystead_1132999
Joseph Haystead
 

Similar to Automatic Generation Control-3 (20)

A novel voltage reference without the operational amplifier and resistors
A novel voltage reference without the operational amplifier and resistorsA novel voltage reference without the operational amplifier and resistors
A novel voltage reference without the operational amplifier and resistors
 
Operational Amplifier Design
Operational Amplifier DesignOperational Amplifier Design
Operational Amplifier Design
 
「SPICEの活用方法」セミナー資料(28JAN2011) PPT
「SPICEの活用方法」セミナー資料(28JAN2011) PPT「SPICEの活用方法」セミナー資料(28JAN2011) PPT
「SPICEの活用方法」セミナー資料(28JAN2011) PPT
 
ALFC.pdf
ALFC.pdfALFC.pdf
ALFC.pdf
 
19212757
1921275719212757
19212757
 
Chapter 2 automatic_load_frequency_contr
Chapter 2 automatic_load_frequency_contrChapter 2 automatic_load_frequency_contr
Chapter 2 automatic_load_frequency_contr
 
Design, Simulation and Implementation of Flyback based, True Single Stage, Is...
Design, Simulation and Implementation of Flyback based, True Single Stage, Is...Design, Simulation and Implementation of Flyback based, True Single Stage, Is...
Design, Simulation and Implementation of Flyback based, True Single Stage, Is...
 
PWM Step-down Converter(NJM2309)
PWM Step-down Converter(NJM2309)PWM Step-down Converter(NJM2309)
PWM Step-down Converter(NJM2309)
 
pwm inverter
pwm inverterpwm inverter
pwm inverter
 
PWM Buck Converter using Average Model
PWM Buck Converter using Average ModelPWM Buck Converter using Average Model
PWM Buck Converter using Average Model
 
IEMCON-2015
IEMCON-2015IEMCON-2015
IEMCON-2015
 
Chapter two Part two.pptx
Chapter two Part two.pptxChapter two Part two.pptx
Chapter two Part two.pptx
 
ENEL301 report _Joseph Haystead_1132999
ENEL301 report _Joseph Haystead_1132999ENEL301 report _Joseph Haystead_1132999
ENEL301 report _Joseph Haystead_1132999
 
Performance analysis of High Speed ADC using SR F/F
Performance analysis of High Speed ADC using SR F/FPerformance analysis of High Speed ADC using SR F/F
Performance analysis of High Speed ADC using SR F/F
 
ECE 626 project report Switched Capacitor
ECE 626 project report Switched CapacitorECE 626 project report Switched Capacitor
ECE 626 project report Switched Capacitor
 
Automatic Generation Control -1
Automatic Generation Control -1Automatic Generation Control -1
Automatic Generation Control -1
 
DESIGNED A 350NM TWO STAGE OPERATIONAL AMPLIFIER
DESIGNED A 350NM TWO STAGE OPERATIONAL AMPLIFIERDESIGNED A 350NM TWO STAGE OPERATIONAL AMPLIFIER
DESIGNED A 350NM TWO STAGE OPERATIONAL AMPLIFIER
 
Final Project
Final ProjectFinal Project
Final Project
 
CVT design
CVT designCVT design
CVT design
 
ECE4762011_Lect14.ppt
ECE4762011_Lect14.pptECE4762011_Lect14.ppt
ECE4762011_Lect14.ppt
 

More from Power System Operation

SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action Scheme
Power System Operation
 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
Power System Operation
 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
Power System Operation
 

More from Power System Operation (20)

ENERGY TRANSITION OUTLOOK 2021
ENERGY TRANSITION OUTLOOK  2021ENERGY TRANSITION OUTLOOK  2021
ENERGY TRANSITION OUTLOOK 2021
 
Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panels
 
What does peak shaving mean
What does peak shaving meanWhat does peak shaving mean
What does peak shaving mean
 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
 
Power System Restoration Guide
Power System Restoration Guide  Power System Restoration Guide
Power System Restoration Guide
 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid Operations
 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action Scheme
 
Substation Neutral Earthing
Substation Neutral EarthingSubstation Neutral Earthing
Substation Neutral Earthing
 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground Resistance
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & Parts
 
What is load management
What is load managementWhat is load management
What is load management
 
What does merit order mean
What does merit order meanWhat does merit order mean
What does merit order mean
 
What are Balancing Services ?
What are  Balancing Services ?What are  Balancing Services ?
What are Balancing Services ?
 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
 
Power Purchase Agreement PPA
Power Purchase Agreement PPA Power Purchase Agreement PPA
Power Purchase Agreement PPA
 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
 

Recently uploaded

Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Christo Ananth
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 

Recently uploaded (20)

Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
 

Automatic Generation Control-3

  • 1. 1 AGC 3 1.0 Introduction The primary controller response to a load/generation imbalance results in generation adjustment so as to maintain load/generation balance. However, due to droop, it also results in a non-zero steady-state frequency deviation. This frequency deviation must be corrected. Also, the net scheduled export must be maintained according to the purchase agreements. Primary control does nothing to correct the steady-state frequency error or the net scheduled export. These two problems are handled by providing a supplementary signal from the control center to each generation unit on automatic generation control (AGC).
  • 2. 2 The signal is derived from the Area Control Error (ACE) and, when received at a generation plant, activates the “speed changer motor” to adjust the energy supply set point to the generator. In these notes, we will learn how the ACE is computed, and we will see how it is used in correcting steady-state frequency error. 2.0 Review From our notes AGC1, we defined the following terms:  Net Actual Interchange: APij  Net Scheduled Interchange: SPij  Interchange Deviation (defined pg 396 of text): ΔPij=APij-SPij (1) Note that the above terms are each defined with respect to two distinct areas.
  • 3. 3 We also defined, in AGC1, the following terms:  Actual Export:   n j iji APAP 1 (2)  Scheduled Export:   n j iji SPSP 1 (3)  Net Deviation:   n j iji PP 1 (4) Note that the above three terms are each defined with respect to a single area. We also saw that the net deviation is related to the net actual and scheduled interchanges, and to the actual and scheduled exports, by: ii n j ij n j ij ij n j ij n j iji SPAPSPAP SPAPPP       11 11 )( (5) Although your text does not define net deviation, it does use it as the first term in the ACE expression of eq. (11.30).
  • 4. 4 Finally, we saw in our notes AGC2, when discussing the multi-machine case, that             Kpu RK pu R R S R S Pf ... 60 1 1 (6)              Kpu RK pu Rpui Ri pui Ri Mi R S R S P R Sf R S P ... 60 1 1 (7) If all units have the same per-unit droop constant, i.e., if R1pu=R2pu=…=RKpu, then eqs. (6) and (7) become  RKR pu SS PRf     ...60 1 (8)  RKR Ri pu Ri Mi SS PSf R S P      ...60 1 (9) In eqs. (8) and (9), ΔP represents the change in total load so that it is  positive if load increases and negative if load decrease;  positive if generation decreases and negative if generation increases.
  • 5. 5 3.0 Area Control Error The Area Control Error (ACE) is composed of  Net Deviation ΔPi, from eq. (5), written more compactly below: iii SPAPP  (5) When ΔPi>0, it means that the actual export exceeds the scheduled export, and so the generation in area i should be reduced.  Steady-state frequency deviation 60 ff (10) When Δf>0, it means the generation in the system exceeds the load and therefore we should reduce generation in the area. From the above, our first impulse may be to immediately write down the ACE for area i as: fPACE ii  (11a) Alternatively (and consistent with the text)  ii PACE (11b)
  • 6. 6 But we note 2 problems with eq. (11). First, we are adding 2 quantities that have different units. Anytime you come across a relation that adds 2 or more units having different units, beware. The second problem is that the magnitudes of the two terms in eq. (11) may differ dramatically. If we are working in MW and Hz (or rad/sec), then we may see ΔPi in the 100’s of MW whereas we will see Δf (or Δω) in the hundredths or at most tenths of a Hz. The implication is that the control signal, per eq. (11), will greatly favor the export deviations over the frequency deviations. Therefore we need to scale one of them. To do so, we define area i frequency bias as βi. It has units of MW/Hz. Your text shows (pg. 393) that fi Lfififi R DD 1  (12a) i iLii R DD   1  (12b)
  • 7. 7 where  Di is the damping coefficient from the swing equation (and represents the effect of synchronous generator windage and friction);  DLi is the load damping coefficient and represents the tendency of the load to decrease as frequency decreases (an effect mainly attributed to induction motors).  The f or ω subscripts indicate whether we will compute ACE using f or ω (text uses ω). The damping terms of eq. (12) are usually significantly smaller than the regulation term, so that a reasonable approximation is that fi fi R 1  (12c) i i R  1  (12d) Then the ACE equation becomes: fPACE fiii   (12e)   iii PACE (12f)
  • 8. 8 4.0 Example Consider the two-area interconnection shown in Fig. 1 with data given as below. A1 A2 1000 MW Fig. 1 Area 1 Area 2 Load=20,000 MW Load=40,000 MW Capacity=20,000 MW Capacity=42,000 MW Gen=19,000 MW Gen=41,000 MW R1pu=0.05 R1pu=0.05 The scheduled interchange is 1000 MW flowing from A2 to A1, so that scheduled exports are:  SP1=-1000 MW  SP2=1000 MW There are two parts to this problem: 1.Determine frequency and generation of each area and the tie line flow after a 1000 MW loss of load in A1, but before supplementary control has taken effect (this means we will determine only the effect of primary control).
  • 9. 9 2.Repeat (1) after supplementary control action has taken effect. Solution: We assume that area capacities are the ratings: SR1=20000 SR2=42000 We also note that the load decreases, therefore ΔP=-1000 MW. 1.From eq. (8),   pu SS PRf RKR pu 000806.0 ]4200020000[ )1000(05.0 ...60 1         Therefore Hzf 0484.060*000806.0  so that f=60.0484 Hz. Then we can compute the increase in generation in each area per eq. (9). For Area 1:   MW SS PS P RR R M 6.322 4200020000 )1000)(20000( 11 1 1        Therefore MWPM 4.677,186.322190001 
  • 10. 10 For Area 2:   MW SS PS P RR R M 4.677 4200020000 )1000)(42000( 11 2 2        Therefore MWPM 6.322,404.677410002  It is of interest now to obtain the actual exports, and we can do this for each area by taking the difference between load and generation. The loads in areas 1 and 2 were 20000 and 40000, but remember that we lost 1000 MW of load in area 1, so that its value is now 19000. Generation levels were computed above. Therefore AP1=18,677-19,000=-322.6 MW AP2=40,322.6-40,000=322.6 MW So clearly the new tie-line flow is 322.6 MW from A2 to A1. Note: For multiple areas, calculating tie-line flows requires a power flow solution (DC power flow is suitable to use here).
  • 11. 11 From eq. (5), net deviation is: 4.677)1000(6.322111  SPAPP 4.677)1000(6.322222  SPAPP 2.To find the effect of supplementary control, we first need to compute the frequency bias parameters. We neglect effects of damping terms, so that we use eq. (12c) or (12d): fi fi R 1  (12c) i i R  1  (12d) But note that the droop constant in (12c) or (12d) is not in per-unit. To convert to per-unit, recall eqs. (13) and (14) from AGC2 notes: M f P f R    (13a) MP R      (13b) Mpu pu Mpu pu rMrM pu PP f SPSP ff R              / / / / 00 (14)
  • 12. 12 Substituting eq. (13a) or (13b) into (14) gives: 00 0 / / f S R f S P f SP ff R r f r MrM pu        (15a) 00 0 / /    rr MrM pu S R S PSP R        (15b) Therefore r puf S f RR 0  (16a) r pu S RR 0   (16b) We can use (16a) to calculate the frequency bias term of (12c), which is used in the ACE equation of (12d): fPACE fiii   (12d) Alternatively, we can use (16b) to calculate the frequency bias terms of (12d), which is used in the ACE equation of (12e):   iii PACE (12e) In the rest of this example, we will use (16a), (12c), and (12d).
  • 13. 13 Applying eq. (16a) to obtain Rf1 and Rf2, we get MWHz S f RR r puf /00015.0 20000 60 05.0 1 0 1  MWHz S f RR r puf /000071429.0 42000 60 05.0 2 0 2  Then the frequency bias terms are obtained as HzMW Rf f /7.6666 00015.0 11 1 1  HzMW Rf f /14000 000071429.0 11 2 2  Now we can compute the ACE in each area: MW fSPAPfPACE ff 100068.3224.677 484)6666.7(0.0-1000)--322.6( )( 111111     MW fSPAPfPACE ff 06.6774.677 84)14000(0.041000)-322.6( )( 222222    
  • 14. 14 So what does this mean?  ACE1 indicates that the generators in A1 receive a signal to decrease generation by 1000 MW. Recall from page 9 that after primary control action, PM1=18,677.4 MW. With a 1000 MW decrease, then PM1=17,677.4 MW.  ACE2 indicates that the generators in A2 do not change, so PM2=40,322.6 MW. But now consider that previous to the secondary control action, we were at a steady state (with steady-state frequency deviation of 0.0484 so that f=60.0484 Hz). Now the ACE signal has cause a decrease in A1 generation by 1000 MW. This action creates a load-generation imbalance of ΔP=+1000 MW that will cause unit primary controllers to act in both areas. From eq. (8):   pu SS PRf RKR pu 000806.0 ]4200020000[ )1000(05.0 ...60 1         Therefore Hzf 0484.060*000806.0  so that f=60.0484 - 0.0484 = 60Hz.
  • 15. 15 Then we compute the increase in generation in each area per eq. (9). For Area 1:   MW SS PS P RR R M 6.322 4200020000 )1000)(20000( 11 1 1        Therefore MWPM 000,186.3224.176771  For Area 2:   MW SS PS P RR R M 4.677 4200020000 )1000)(42000( 11 2 2        Therefore MWPM 000,414.6776.322,402  The exports for the two areas will then be: AP1=18,000-19,000=-1000 MW AP2=41,000-40,000=+1000 MW A summary of the situation is given below, where we see that the final control action has resulted in A1 generation entirely compensating for the A1 load decrease of 1000 MW (with area exports unchanged). Area 1 Area 2 Load=19,000 MW Load=40,000 MW Gen=18,000 MW Gen=41,000 MW