Installation Requirements
4.1 Code Reference
The “authority having jurisdiction” should be
referenced to determine what law, ordinance or code
shall apply in the use of flexible duct.
Ducts conforming to NFPA 90A or 90B shall meet the
following requirements:
a. Shall be tested in accordance with Sections
7 to 23 of Underwriters Laboratories Standard
for Factory-Made Air Ducts and Air
Connectors, UL 181.
b. Shall be installed in accordance with the
conditions of their listing.
c. Shall be installed within the limitations of the
applicable NFPA 90A or 90B Standard.
4.2 Installation Restrictions
and Use Limitations
There are specific restrictions and limitations related to
the use of flexible ducts. Some are due to NFPA
Standards, model codes and various state/local codes.
Others are due to end use performance where the
product was not designed for that specific use. Some,
but not all inclusive, are as follows:
a. Shall not be used for vertical risers serving
more than two stories in height.
b. Shall not be used in systems with entering air
temperature higher than 250°F[121°C].
c. Shall be installed in accordance with the
conditions of their listing.
d. When installed in a fire-rated floor/roof ceiling
assembly, ducts shall conform with the design
of the tested fire-resistive assembly.
e. Shall be interrupted at the immediate area of
operation of electric, fossil fuel or solar
energy collection heat sources to meet listed
equipment clearances specified.
4
9
ADCFlexibleDuctPerformance&InstallationStandards,5thEdition
f. Air Connectors (does not apply to Air Ducts)
shall not be installed in lengths greater than
14 ft. [4.3 m] for any given run; shall not pass
through any wall, partition or enclosure of a
vertical shaft with a 1 hour or more fire
resistive rating; shall not pass through floors.
g. Shall not penetrate walls where fire dampers
are required.
h. Shall not be used outdoors unless specifically
designed to withstand exposure to direct
sunlight and the weathering elements.
i. Shall not be used to vent appliances for
cooking, heating and clothes drying unless
approved and recommended by the appliance
manufacturer.
j. Shall not be installed in concrete, buried
below grade or in contact with the ground.
4.3 General
The routing of flexible duct, the number of bends, the
degrees in each bend, and the amount of sag or
direction changes (snaking) allowed between support
joints will have serious effects on system performance
due to the increased resistance each introduces (See
Fig 6 & 7). Use the minimum length of flexible duct to
make connections (See Section 4.5). Excess length of
flexible duct shall not be installed to allow for possible
future relocations of air terminal devices.
Avoid installations where exposure to direct sunlight
can occur, e.g. turbine vents, sky lights, canopy
windows, etc. Prolonged exposure to sunlight will
cause degradation of the vapor barrier. Direct
exposure to UV light from a source lamp installed
within the HVAC system will cause degradation of
some inner core/liner materials.
Terminal devices shall be supported independently of
the flexible duct.
Repair torn or damaged vapor barrier/jacket with duct
tape listed and labeled to Standard UL 181B. If internal
core is penetrated, replace flexible duct or treat as a
connection.
Flexible Ducts
Installation Requirements . . . continued
Do not bend ducts across a sharp corner of building
materials such as joists or truss supports.
The bend radius at the center line of ducts shall be
equal to or greater than one duct diameter (See
Figures 8 and 11). Sharper bends increase pressure
drop significantly and reduce airflow.
Avoid incidental contact with metal fixtures, water
lines, pipes, or conduits. Do not install near hot
equipment (e.g. furnaces, boilers, steam pipes, etc.)
that is above the recommended flexible duct use
temperature.
Figure 9 - Incorrect. Contact with steam pipes.
10
ADCFlexibleDuctPerformance&InstallationStandards,5thEdition
Figure 8 - Correct. Minimum 1 duct diameter
bend radius reduces pressure drop
and improves air flow.
4.4 Installation and Usage
Install ducts fully extended. Do not install in the
compressed state or use excess length as this will
noticeably increase friction losses. (Refer to Section
4.5 for more specific information regarding pressure
loss and duct sizing.)
Figure 6 - Minimum duct length and bend
radius reduces pressure drop and
improves airflow.
Figure 7 - Excess length and tight bend radius
increases pressure drop and
reduces airflow.
4.5 Duct Sizing and Routing
The combined friction and dynamic pressure losses
shall be taken into consideration to properly size any
duct. Pressure losses caused by the roughness of the
duct wall resisting air movement are know as friction
losses. Pressure losses when air flow changes
direction, as caused by bends or when air flows across
other system components, are known as dynamic
losses.
Key points to prevent undersizing or oversizing of
flexible ducts and achieve the designed air delivery
performance:
a. Use a proven method of duct sizing, one that
has taken into consideration both friction and
dynamic losses.
Design the flexible duct system per the
requirements of ACCA, Manual D
(Residential) and Manual Q (Commercial).
Properly take into account duct length, bend
losses, sagging or routing expectations, fitting
losses, etc.
b. Have a good understanding of and properly
use the air friction chart.
Do not use data for round sheet metal duct.
Since all flexible ducts are not alike, use the
flexible duct manufacturer’s air friction loss
data to size the ducts whenever possible.
If no data is available, use the generic flexible
duct friction loss chart in ACCA Manual D.
c. Use the minimum length of flexible duct
needed to make the connections.
Install ducts extended to their fullest length
without compression. Due to the helical
configuration of flexible duct inner cores,
excess longitudinal compression can
dramatically affect the pressure drop.
If a flexible duct is not fully extended, the
friction rate increases proportionally with the
compression (See Fig. 10).
When a flexible duct is fully extended, it is
said to have no more than 4% longitudinal
compression and the published friction rate
may be used for duct sizing calculations (0 -
4% = 1 x Friction Rate).
For 15% longitudinal compression the friction
rate can increase by a factor of two (15% = 2
x Friction Rate).
For longitudinal compression of 30% the
friction rate can increase as much as four
times (30% = 4 x Friction Rate).
Figure 10 - Compressed duct (not fully ex-
tended) increases friction rate.
11
ADCFlexibleDuctPerformance&InstallationStandards,5thEdition
Installation Requirements . . . continued
Figure 11
d. Keep bends greater than or equal to one (1)
duct diameter bend radius.
12
ADCFlexibleDuctPerformance&InstallationStandards,5thEdition
Installation Requirements . . . continued
e. Properly route and support the flexible duct
runs.
Figure 12
Care shall be taken to minimize sagging or
snaking of the duct between supports and
minimize pressure loss caused by excessive
direction changes to the airflow.
Figure 13
Ducts shall not be crimped against joist or
truss members, pipes, wires, etc. as this in-
creases pressure loss and reduces air flow.
Figure 14
A 180-degree offset has pressure drop equal
to about forty (40) lineal feet of flexible duct.
Add forty (40) equivalent feet to the length for
each sharp 180-degree offset.
Installation Requirements . . . continued
13
ADCFlexibleDuctPerformance&InstallationStandards,5thEdition
A gradual 45-degree bend has pressure drop
equal to about ten (10) lineal feet of flexible
duct. Add ten (10) equivalent feet to the
length for each gradual bend (see Fig. 16).
Figure 16
f. Properly account for bends in the duct runs.
A 90-degree bend has pressure drop equal to
approximately twenty (20) lineal feet of flexi-
ble duct. So each 90-degree bend will add
twenty (20) equivalent feet to the length used
for sizing calculations.
Figure 15
Figure 17
14
ADCFlexibleDuctPerformance&InstallationStandards,5thEdition
Installation Requirements . . . continued
Figure 18
Duct fittings and any bends and turns in flexible duct
all produce a resistance to airflow. This resistance
creates a pressure drop measured in inches water
column (IWC) which is physically equivalent to the
pressure drop produced by a straight section of duct.
So the total pressure drop for any duct run equals the
sum of the fitting pressure drops and the pressure drop
of the straight duct section.
To determine the correct duct size, take into account
the total equivalent length of the duct run, including
entrance and exit losses from the plenum to the duct
and from the duct into the terminal device, the added
length due to any bends, and the total length of the
duct itself.
Use ACCA Manual D (App. 3) equivalent length values
for bends and fittings.
A typical duct run from plenum to terminal device is
illustrated in Figure 18.
The worksheet for determining the total pressure drop
of the duct run depicted in Figure 18 will look like this:
Entrance fitting = 35 ft.
Total duct length = 14 ft.
2 x 45° bends (2 x 10’) = 20 ft.
1 x 90° bend (1 x 20’) = 20 ft.
Exit fitting = 35 ft.
Total Equivalent Length = 124 ft.
Although the distance from plenum to terminal end in
this example is approximately 12 feet, the total
equivalent length used to determine the correct duct
diameter would be 124 feet.
The equivalent length values for bends & fittings
represented above are default values from ACCA
Manual D and based on 900 fpm at 0.08 IWC/100’ for
supply ducts and 700 fpm at 0.08 IWC/100’ for return
ducts.
Installation Requirements . . . continued
4.6 Supporting Flexible Duct
Flexible duct shall be supported at manufacturer’s
recommended intervals, but at no greater distance
than 4’ [1.2 m]. Supporting shall be provided so that
the maximum centerline sag is ½ " per foot [42 mm per
meter] of spacing between supports (See Fig 19). A
connection to rigid duct or equipment may be
considered a support joint.
Hanger or saddle material in contact with the flexible
duct shall be of sufficient width to prevent any
restriction of the internal diameter of the duct when
the weight of the supported section rests on the
hanger or saddle material. In no case will the material
contacting the flexible duct be less than 1½ ” [38 mm]
wide (See Fig 21).
Figure 19
Figure 21
Figure 22
15
ADCFlexibleDuctPerformance&InstallationStandards,5thEdition
Long horizontal duct runs with sharp bends shall have
additional supports before and after the bend
approximately one duct diameter from the center line
of the bend (See Fig 20).
Figure 20
Do not secure support straps in a manner that
compresses the inner core and constricts the air flow.
Care shall be taken to insure the vapor barrier and
insulation material are not excessively compressed
by the support straps. Compressing the insulation
could lead to condensation at the point of contact
between the duct and the strap or saddle material.
Installation Requirements . . . continued
Factory installed suspension systems integral to the
flexible duct are an acceptable alternative hanging
method when manufacturer’s recommended proce-
dures are followed.
Support the duct between a metal connection and
bend by allowing the duct to extend straight for at least
one duct diameter before making the bend. This will
avoid possible damage of the flexible duct by the edge
of the metal collar and allow for efficient air flow and
fitting performance (See Fig 25).
Figure 23
Figure 25
Vertically installed ducts
shall be stabilized by
support straps at a max.
of 6’ [1.8 m] on center.
Figure 26
Figure 24
Note:
Factory-made air ducts may not be used for vertical risers
in air duct systems serving more than two adjacent stories.
16
ADCFlexibleDuctPerformance&InstallationStandards,5thEdition
Flexible ducts may rest on ceiling joists or truss
supports. Maximum spacing between supports shall
not exceed the maximum spacing per manufacturer’s
installation instruction.
17
ADCFlexibleDuctPerformance&InstallationStandards,5thEdition
Installation Requirements . . . continued
4.7 Connecting, Joining and Splicing
Flexible Ducts
All connections, joints and splices shall be made in
accordance with the manufacturer’s installation
instructions.
Standardized installation instructions conforming to the
connecting and sealing requirements of the national
building codes and this standard are shown in
Sections 4.7.1 through 4.7.3.
Section 4.7.1 - “Installation Instructions for Air Ducts
and Air Connectors - Nonmetallic With Plain
Ends” (uses tape and clamp to seal and secure the
duct core to the fitting).
Section 4.7.2 - “Alternate Installation Instructions for
Air Ducts and Air Connectors - Nonmetallic With Plain
Ends” (uses mastic and clamp to seal and secure the
duct core to the fitting).
Section 4.7.3 - “Installation Instructions for Air Ducts
and Air Connectors - Metallic With Plain Ends (optional
use of tape or mastic and metal screws to seal and
secure the duct core to the fitting).
Due to the wide variety of ducts and duct assemblies
with special end treatments (factory installed fittings,
taped ends, crimped metal ends, etc.), only these
standardized installation instructions are shown.
Always reference the manufacturer’s installation
instructions for more detailed requirements.
All tapes, mastics, and nonmetallic clamps used for
field installation of flexible ducts shall be listed and
labeled to Standard UL 181B - Closure Systems for
Use With Flexible Air Ducts and Air Connectors.
Sheet metal fittings to which flexible ducts with plain
ends are attached shall be beaded and have a
minimum of 2 inches [50 mm] collar length. Beads are
optional for fittings when using metal worm-gear
clamps or when attaching metallic flexible ducts using
sheet metal screws.
Sheet metal sleeves used for joining two sections of
flexible duct with plain ends shall be a minimum of 4
inches [100 mm] in length and beaded on each end.
Beads are optional for sleeves when using metal
worm-gear clamps or when joining metallic flexible
ducts using sheet metal screws.
Flexible ducts secured with nonmetallic clamps shall
be limited to 6 inches w.g. [1500 Pa] positive pressure.
18
ADCFlexibleDuctPerformance&InstallationStandards,5thEdition
Installation Requirements . . . continued
Connections - Using Tape and Fasteners Splices - Using Tape and Fasteners
4.7.1 Installation Instructions for Air Ducts and Air Connectors - Nonmetallic with Plain Ends
1. After desired length is determined, cut completely
around and through duct with knife or scissors. Cut
wire with wire cutters. Fold back jacket and insulation.
2. Tape cores together with at least 2 wraps of duct
tape. Secure connection with 2 clamps placed over the
taped core ends and past the beads.
2. Slide at least 1" [25 mm] of core over fitting and
past the bead. Seal core to collar with at least 2 wraps
of duct tape. Secure connection with clamp placed
over the core and tape and past the bead.
3. Pull jacket and insulation back over core. Tape
jacket with at least 2 wraps of duct tape. A clamp may
be used in place of or in combination with the duct
tape.
3. Pull jacket and insulation back over cores. Tape
jackets together with at least 2 wraps of duct tape.
NOTES:
1. For uninsulated air ducts and air connectors, disregard references to insulation and jacket.
2. Use beaded sheet metal fittings and sleeves when using nonmetallic clamps.
3. Use tapes listed and labeled in accordance with Standard UL 181B and marked “181B-FX”.
4. Nonmetallic clamps shall be listed and labeled in accordance with Standard UL 181B and marked “181B-C”.
Use of nonmetallic clamps shall be limited to 6 in. w.g. [1500 Pa] positive pressure.
1. Fold back jacket and insulation from core. Butt two
cores together on a 4" [100 mm] min. length metal
sleeve.
19
ADCFlexibleDuctPerformance&InstallationStandards,5thEdition
Installation Requirements . . . continued
4.7.2 Alternate Installation Instructions for Air Ducts and Air Connectors - Nonmetallic with
Plain Ends
Connections and Splices - Using Mastic and Fasteners
Step 1
After desired length is determined, cut completely around and
through duct with knife or scissors. Cut wire with wire cutters.
Pull back jacket and insulation from core.
Step 2
Apply mastic approximately 2" [50 mm] wide uniformly around
the collar of the metal fitting or over the ends of a 4" [100 mm]
min. length metal sleeve. Reference data on mastic container
for application rate, application thickness, cure times and
handling information.
Step 3
Slide at least 2" [50 mm] of core over the fitting or sleeve ends
and past the bead.
Step 4
Secure core to collar with a clamp applied past the bead.
Secure cores to sleeve ends with 2 clamps applied past the
beads.
Step 5
Pull jacket and insulation back over core ends. Tape jacket(s)
with at least 2 wraps of duct tape. A clamp may be used in
place of or in combination with the duct tape.
NOTES:
1. For uninsulated air ducts and air connectors, disregard references to insulation and jacket.
2. Use beaded sheet metal fittings and sleeves when using nonmetallic clamps.
3. Use mastics listed and labeled in accordance with Standard UL 181B and marked “181B-M” on container.
4. Use tapes listed and labeled in accordance with Standard UL 181B and marked “181B-FX”.
5. Nonmetallic clamps shall be listed and labeled in accordance with standard UL 181B and marked “181B-C”.
Use of nonmetallic clamps shall be limited to 6 in. w.g. [1500 Pa] positive pressure.
Installation Requirements . . . continued
4.7.3 Installation Instruction for Air Ducts and Air Connectors - Metallic with Plain Ends
Connections and Splices - Using Tape or Mastic and Sheet Metal Screws
NOTES:
1. For uninsulated air ducts and air connectors, disregard references to insulation and jacket.
2. Use mastics listed and labeled to Standard UL 181B and marked”181B-M” on container.
3. Use tapes listed and labeled to Standard UL 181B and marked “181B-FX”.
4. Nonmetallic clamps shall be listed and labeled in accordance with Standard UL 181B and marked “181B-C”.
1. After cutting duct to desired length, fold back jacket
and insulation exposing core. Trim core ends squarely
using suitable metal shears. Determine optional
sealing method (Steps 2 or 5) before proceeding.
4. Secure to collar/sleeve using #8 sheet metal
screws spaced equally around circumference. Use 3
screws for diameters under 12" [300 mm] and 5
screws for diameters 12" [300 mm] and over.
2. When mastics are required and for pressures 4"
w.g. [1000 Pa] and over, seal joint with mastic applied
uniformly to the outside surface of collar/sleeve.
(Disregard this step when not using mastics and pro-
ceed to Step 3).
3. Slide at least 1" [25 mm] of core over metal collar
for attaching duct to take off or over ends of a 4" [100
mm] metal sleeve for splicing 2 lengths of duct.
5. For pressures under 4" w.g. [1000 Pa] seal joint
using 2 wraps of duct tape applied over screw heads
and spirally lapping tape to collar/sleeve. (Disregard
this step when using mastics per Step 2).
6. Pull jacket and insulation back over core. Tape
jacket with 2 wraps of duct tape. A clamp may be used
in place of or in combination with the duct tape.
20
ADCFlexibleDuctPerformance&InstallationStandards,5thEdition

More Related Content

Similar to Flexible Ducts

DW143-Ductwork-Leakage-Testing.pdf
DW143-Ductwork-Leakage-Testing.pdfDW143-Ductwork-Leakage-Testing.pdf
DW143-Ductwork-Leakage-Testing.pdfwrsconsultoria1
 
Fire Safety (Common Design Issues) .pptx
Fire Safety (Common Design Issues) .pptxFire Safety (Common Design Issues) .pptx
Fire Safety (Common Design Issues) .pptxRafat30
 
Experimental investigation of air flow characteristics in rectangular channel...
Experimental investigation of air flow characteristics in rectangular channel...Experimental investigation of air flow characteristics in rectangular channel...
Experimental investigation of air flow characteristics in rectangular channel...eSAT Journals
 
Design and Analysis of an Air Conditioning Duct Using Equal Friction Method
Design and Analysis of an Air Conditioning Duct Using Equal Friction MethodDesign and Analysis of an Air Conditioning Duct Using Equal Friction Method
Design and Analysis of an Air Conditioning Duct Using Equal Friction MethodIRJET Journal
 
Pipe shields inc
Pipe shields incPipe shields inc
Pipe shields incopenmind56
 
010 115-001-03 ESPECIFICACIONES DE TUBERÍA
010 115-001-03 ESPECIFICACIONES DE TUBERÍA010 115-001-03 ESPECIFICACIONES DE TUBERÍA
010 115-001-03 ESPECIFICACIONES DE TUBERÍAJuan Novillo Ramos
 
line sizing-mustang.pdf
line sizing-mustang.pdfline sizing-mustang.pdf
line sizing-mustang.pdfZeeshanAlam90
 
Air-5 final - Copy.pptx
Air-5 final - Copy.pptxAir-5 final - Copy.pptx
Air-5 final - Copy.pptxdejene1234567
 
Thermal Dispersion Flow Measurement Device
Thermal Dispersion Flow Measurement DeviceThermal Dispersion Flow Measurement Device
Thermal Dispersion Flow Measurement DeviceMiller Energy, Inc.
 
Design of duct for a three storey retail shop
Design of duct for a three storey retail shopDesign of duct for a three storey retail shop
Design of duct for a three storey retail shopIRJET Journal
 
How To Install A Flexible Air Duct-mmihomeimprovement.com
How To Install A Flexible Air Duct-mmihomeimprovement.comHow To Install A Flexible Air Duct-mmihomeimprovement.com
How To Install A Flexible Air Duct-mmihomeimprovement.comangelinarobert1
 
specif-dust-extraction-system.pdf
specif-dust-extraction-system.pdfspecif-dust-extraction-system.pdf
specif-dust-extraction-system.pdfSergioPereira229337
 
SMACNA HVAC Duct Construction Examples.ppt
SMACNA HVAC Duct Construction Examples.pptSMACNA HVAC Duct Construction Examples.ppt
SMACNA HVAC Duct Construction Examples.pptMijhaelFernandez
 
Hvac duct construction wasilewski
Hvac duct construction   wasilewskiHvac duct construction   wasilewski
Hvac duct construction wasilewskiIyan Gutierrez
 

Similar to Flexible Ducts (20)

045
045045
045
 
DW143-Ductwork-Leakage-Testing.pdf
DW143-Ductwork-Leakage-Testing.pdfDW143-Ductwork-Leakage-Testing.pdf
DW143-Ductwork-Leakage-Testing.pdf
 
Auxilliary ventilation system final ppt.pptx
Auxilliary ventilation system final ppt.pptxAuxilliary ventilation system final ppt.pptx
Auxilliary ventilation system final ppt.pptx
 
Fire Safety (Common Design Issues) .pptx
Fire Safety (Common Design Issues) .pptxFire Safety (Common Design Issues) .pptx
Fire Safety (Common Design Issues) .pptx
 
Experimental investigation of air flow characteristics in rectangular channel...
Experimental investigation of air flow characteristics in rectangular channel...Experimental investigation of air flow characteristics in rectangular channel...
Experimental investigation of air flow characteristics in rectangular channel...
 
Acca duct slide rule users manual
Acca duct slide rule users manualAcca duct slide rule users manual
Acca duct slide rule users manual
 
Design and Analysis of an Air Conditioning Duct Using Equal Friction Method
Design and Analysis of an Air Conditioning Duct Using Equal Friction MethodDesign and Analysis of an Air Conditioning Duct Using Equal Friction Method
Design and Analysis of an Air Conditioning Duct Using Equal Friction Method
 
Pipe shields inc
Pipe shields incPipe shields inc
Pipe shields inc
 
010 115-001-03 ESPECIFICACIONES DE TUBERÍA
010 115-001-03 ESPECIFICACIONES DE TUBERÍA010 115-001-03 ESPECIFICACIONES DE TUBERÍA
010 115-001-03 ESPECIFICACIONES DE TUBERÍA
 
line sizing-mustang.pdf
line sizing-mustang.pdfline sizing-mustang.pdf
line sizing-mustang.pdf
 
HVAC
HVACHVAC
HVAC
 
Air-5 final - Copy.pptx
Air-5 final - Copy.pptxAir-5 final - Copy.pptx
Air-5 final - Copy.pptx
 
Thermal Dispersion Flow Measurement Device
Thermal Dispersion Flow Measurement DeviceThermal Dispersion Flow Measurement Device
Thermal Dispersion Flow Measurement Device
 
Design of duct for a three storey retail shop
Design of duct for a three storey retail shopDesign of duct for a three storey retail shop
Design of duct for a three storey retail shop
 
How To Install A Flexible Air Duct-mmihomeimprovement.com
How To Install A Flexible Air Duct-mmihomeimprovement.comHow To Install A Flexible Air Duct-mmihomeimprovement.com
How To Install A Flexible Air Duct-mmihomeimprovement.com
 
Aircraft hoses
Aircraft hosesAircraft hoses
Aircraft hoses
 
specif-dust-extraction-system.pdf
specif-dust-extraction-system.pdfspecif-dust-extraction-system.pdf
specif-dust-extraction-system.pdf
 
SMACNA HVAC Duct Construction Examples.ppt
SMACNA HVAC Duct Construction Examples.pptSMACNA HVAC Duct Construction Examples.ppt
SMACNA HVAC Duct Construction Examples.ppt
 
Rehab Solutions for Today's Infrastructure
Rehab Solutions for Today's InfrastructureRehab Solutions for Today's Infrastructure
Rehab Solutions for Today's Infrastructure
 
Hvac duct construction wasilewski
Hvac duct construction   wasilewskiHvac duct construction   wasilewski
Hvac duct construction wasilewski
 

More from Mostafa Al Wakeel

More from Mostafa Al Wakeel (9)

BMS Design (BAS-Building Automation System)
BMS Design (BAS-Building Automation System)BMS Design (BAS-Building Automation System)
BMS Design (BAS-Building Automation System)
 
Basics of building fire protection design
Basics of building fire protection designBasics of building fire protection design
Basics of building fire protection design
 
Air Duct Leakage
Air Duct LeakageAir Duct Leakage
Air Duct Leakage
 
Fire pumps in brief
Fire pumps in briefFire pumps in brief
Fire pumps in brief
 
Interactive damper selection guide
Interactive damper selection guideInteractive damper selection guide
Interactive damper selection guide
 
Fire suppression
Fire suppressionFire suppression
Fire suppression
 
Engineer Mostafa Al Wakeel C.V.-2019
Engineer Mostafa Al Wakeel C.V.-2019Engineer Mostafa Al Wakeel C.V.-2019
Engineer Mostafa Al Wakeel C.V.-2019
 
Fm 200 calculator
Fm 200 calculatorFm 200 calculator
Fm 200 calculator
 
Fire Protection System Design
Fire Protection System DesignFire Protection System Design
Fire Protection System Design
 

Recently uploaded

Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 

Recently uploaded (20)

Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 

Flexible Ducts

  • 1. Installation Requirements 4.1 Code Reference The “authority having jurisdiction” should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming to NFPA 90A or 90B shall meet the following requirements: a. Shall be tested in accordance with Sections 7 to 23 of Underwriters Laboratories Standard for Factory-Made Air Ducts and Air Connectors, UL 181. b. Shall be installed in accordance with the conditions of their listing. c. Shall be installed within the limitations of the applicable NFPA 90A or 90B Standard. 4.2 Installation Restrictions and Use Limitations There are specific restrictions and limitations related to the use of flexible ducts. Some are due to NFPA Standards, model codes and various state/local codes. Others are due to end use performance where the product was not designed for that specific use. Some, but not all inclusive, are as follows: a. Shall not be used for vertical risers serving more than two stories in height. b. Shall not be used in systems with entering air temperature higher than 250°F[121°C]. c. Shall be installed in accordance with the conditions of their listing. d. When installed in a fire-rated floor/roof ceiling assembly, ducts shall conform with the design of the tested fire-resistive assembly. e. Shall be interrupted at the immediate area of operation of electric, fossil fuel or solar energy collection heat sources to meet listed equipment clearances specified. 4 9 ADCFlexibleDuctPerformance&InstallationStandards,5thEdition f. Air Connectors (does not apply to Air Ducts) shall not be installed in lengths greater than 14 ft. [4.3 m] for any given run; shall not pass through any wall, partition or enclosure of a vertical shaft with a 1 hour or more fire resistive rating; shall not pass through floors. g. Shall not penetrate walls where fire dampers are required. h. Shall not be used outdoors unless specifically designed to withstand exposure to direct sunlight and the weathering elements. i. Shall not be used to vent appliances for cooking, heating and clothes drying unless approved and recommended by the appliance manufacturer. j. Shall not be installed in concrete, buried below grade or in contact with the ground. 4.3 General The routing of flexible duct, the number of bends, the degrees in each bend, and the amount of sag or direction changes (snaking) allowed between support joints will have serious effects on system performance due to the increased resistance each introduces (See Fig 6 & 7). Use the minimum length of flexible duct to make connections (See Section 4.5). Excess length of flexible duct shall not be installed to allow for possible future relocations of air terminal devices. Avoid installations where exposure to direct sunlight can occur, e.g. turbine vents, sky lights, canopy windows, etc. Prolonged exposure to sunlight will cause degradation of the vapor barrier. Direct exposure to UV light from a source lamp installed within the HVAC system will cause degradation of some inner core/liner materials. Terminal devices shall be supported independently of the flexible duct. Repair torn or damaged vapor barrier/jacket with duct tape listed and labeled to Standard UL 181B. If internal core is penetrated, replace flexible duct or treat as a connection. Flexible Ducts
  • 2. Installation Requirements . . . continued Do not bend ducts across a sharp corner of building materials such as joists or truss supports. The bend radius at the center line of ducts shall be equal to or greater than one duct diameter (See Figures 8 and 11). Sharper bends increase pressure drop significantly and reduce airflow. Avoid incidental contact with metal fixtures, water lines, pipes, or conduits. Do not install near hot equipment (e.g. furnaces, boilers, steam pipes, etc.) that is above the recommended flexible duct use temperature. Figure 9 - Incorrect. Contact with steam pipes. 10 ADCFlexibleDuctPerformance&InstallationStandards,5thEdition Figure 8 - Correct. Minimum 1 duct diameter bend radius reduces pressure drop and improves air flow. 4.4 Installation and Usage Install ducts fully extended. Do not install in the compressed state or use excess length as this will noticeably increase friction losses. (Refer to Section 4.5 for more specific information regarding pressure loss and duct sizing.) Figure 6 - Minimum duct length and bend radius reduces pressure drop and improves airflow. Figure 7 - Excess length and tight bend radius increases pressure drop and reduces airflow.
  • 3. 4.5 Duct Sizing and Routing The combined friction and dynamic pressure losses shall be taken into consideration to properly size any duct. Pressure losses caused by the roughness of the duct wall resisting air movement are know as friction losses. Pressure losses when air flow changes direction, as caused by bends or when air flows across other system components, are known as dynamic losses. Key points to prevent undersizing or oversizing of flexible ducts and achieve the designed air delivery performance: a. Use a proven method of duct sizing, one that has taken into consideration both friction and dynamic losses. Design the flexible duct system per the requirements of ACCA, Manual D (Residential) and Manual Q (Commercial). Properly take into account duct length, bend losses, sagging or routing expectations, fitting losses, etc. b. Have a good understanding of and properly use the air friction chart. Do not use data for round sheet metal duct. Since all flexible ducts are not alike, use the flexible duct manufacturer’s air friction loss data to size the ducts whenever possible. If no data is available, use the generic flexible duct friction loss chart in ACCA Manual D. c. Use the minimum length of flexible duct needed to make the connections. Install ducts extended to their fullest length without compression. Due to the helical configuration of flexible duct inner cores, excess longitudinal compression can dramatically affect the pressure drop. If a flexible duct is not fully extended, the friction rate increases proportionally with the compression (See Fig. 10). When a flexible duct is fully extended, it is said to have no more than 4% longitudinal compression and the published friction rate may be used for duct sizing calculations (0 - 4% = 1 x Friction Rate). For 15% longitudinal compression the friction rate can increase by a factor of two (15% = 2 x Friction Rate). For longitudinal compression of 30% the friction rate can increase as much as four times (30% = 4 x Friction Rate). Figure 10 - Compressed duct (not fully ex- tended) increases friction rate. 11 ADCFlexibleDuctPerformance&InstallationStandards,5thEdition Installation Requirements . . . continued
  • 4. Figure 11 d. Keep bends greater than or equal to one (1) duct diameter bend radius. 12 ADCFlexibleDuctPerformance&InstallationStandards,5thEdition Installation Requirements . . . continued e. Properly route and support the flexible duct runs. Figure 12 Care shall be taken to minimize sagging or snaking of the duct between supports and minimize pressure loss caused by excessive direction changes to the airflow. Figure 13 Ducts shall not be crimped against joist or truss members, pipes, wires, etc. as this in- creases pressure loss and reduces air flow. Figure 14
  • 5. A 180-degree offset has pressure drop equal to about forty (40) lineal feet of flexible duct. Add forty (40) equivalent feet to the length for each sharp 180-degree offset. Installation Requirements . . . continued 13 ADCFlexibleDuctPerformance&InstallationStandards,5thEdition A gradual 45-degree bend has pressure drop equal to about ten (10) lineal feet of flexible duct. Add ten (10) equivalent feet to the length for each gradual bend (see Fig. 16). Figure 16 f. Properly account for bends in the duct runs. A 90-degree bend has pressure drop equal to approximately twenty (20) lineal feet of flexi- ble duct. So each 90-degree bend will add twenty (20) equivalent feet to the length used for sizing calculations. Figure 15 Figure 17
  • 6. 14 ADCFlexibleDuctPerformance&InstallationStandards,5thEdition Installation Requirements . . . continued Figure 18 Duct fittings and any bends and turns in flexible duct all produce a resistance to airflow. This resistance creates a pressure drop measured in inches water column (IWC) which is physically equivalent to the pressure drop produced by a straight section of duct. So the total pressure drop for any duct run equals the sum of the fitting pressure drops and the pressure drop of the straight duct section. To determine the correct duct size, take into account the total equivalent length of the duct run, including entrance and exit losses from the plenum to the duct and from the duct into the terminal device, the added length due to any bends, and the total length of the duct itself. Use ACCA Manual D (App. 3) equivalent length values for bends and fittings. A typical duct run from plenum to terminal device is illustrated in Figure 18. The worksheet for determining the total pressure drop of the duct run depicted in Figure 18 will look like this: Entrance fitting = 35 ft. Total duct length = 14 ft. 2 x 45° bends (2 x 10’) = 20 ft. 1 x 90° bend (1 x 20’) = 20 ft. Exit fitting = 35 ft. Total Equivalent Length = 124 ft. Although the distance from plenum to terminal end in this example is approximately 12 feet, the total equivalent length used to determine the correct duct diameter would be 124 feet. The equivalent length values for bends & fittings represented above are default values from ACCA Manual D and based on 900 fpm at 0.08 IWC/100’ for supply ducts and 700 fpm at 0.08 IWC/100’ for return ducts.
  • 7. Installation Requirements . . . continued 4.6 Supporting Flexible Duct Flexible duct shall be supported at manufacturer’s recommended intervals, but at no greater distance than 4’ [1.2 m]. Supporting shall be provided so that the maximum centerline sag is ½ " per foot [42 mm per meter] of spacing between supports (See Fig 19). A connection to rigid duct or equipment may be considered a support joint. Hanger or saddle material in contact with the flexible duct shall be of sufficient width to prevent any restriction of the internal diameter of the duct when the weight of the supported section rests on the hanger or saddle material. In no case will the material contacting the flexible duct be less than 1½ ” [38 mm] wide (See Fig 21). Figure 19 Figure 21 Figure 22 15 ADCFlexibleDuctPerformance&InstallationStandards,5thEdition Long horizontal duct runs with sharp bends shall have additional supports before and after the bend approximately one duct diameter from the center line of the bend (See Fig 20). Figure 20 Do not secure support straps in a manner that compresses the inner core and constricts the air flow. Care shall be taken to insure the vapor barrier and insulation material are not excessively compressed by the support straps. Compressing the insulation could lead to condensation at the point of contact between the duct and the strap or saddle material.
  • 8. Installation Requirements . . . continued Factory installed suspension systems integral to the flexible duct are an acceptable alternative hanging method when manufacturer’s recommended proce- dures are followed. Support the duct between a metal connection and bend by allowing the duct to extend straight for at least one duct diameter before making the bend. This will avoid possible damage of the flexible duct by the edge of the metal collar and allow for efficient air flow and fitting performance (See Fig 25). Figure 23 Figure 25 Vertically installed ducts shall be stabilized by support straps at a max. of 6’ [1.8 m] on center. Figure 26 Figure 24 Note: Factory-made air ducts may not be used for vertical risers in air duct systems serving more than two adjacent stories. 16 ADCFlexibleDuctPerformance&InstallationStandards,5thEdition Flexible ducts may rest on ceiling joists or truss supports. Maximum spacing between supports shall not exceed the maximum spacing per manufacturer’s installation instruction.
  • 9. 17 ADCFlexibleDuctPerformance&InstallationStandards,5thEdition Installation Requirements . . . continued 4.7 Connecting, Joining and Splicing Flexible Ducts All connections, joints and splices shall be made in accordance with the manufacturer’s installation instructions. Standardized installation instructions conforming to the connecting and sealing requirements of the national building codes and this standard are shown in Sections 4.7.1 through 4.7.3. Section 4.7.1 - “Installation Instructions for Air Ducts and Air Connectors - Nonmetallic With Plain Ends” (uses tape and clamp to seal and secure the duct core to the fitting). Section 4.7.2 - “Alternate Installation Instructions for Air Ducts and Air Connectors - Nonmetallic With Plain Ends” (uses mastic and clamp to seal and secure the duct core to the fitting). Section 4.7.3 - “Installation Instructions for Air Ducts and Air Connectors - Metallic With Plain Ends (optional use of tape or mastic and metal screws to seal and secure the duct core to the fitting). Due to the wide variety of ducts and duct assemblies with special end treatments (factory installed fittings, taped ends, crimped metal ends, etc.), only these standardized installation instructions are shown. Always reference the manufacturer’s installation instructions for more detailed requirements. All tapes, mastics, and nonmetallic clamps used for field installation of flexible ducts shall be listed and labeled to Standard UL 181B - Closure Systems for Use With Flexible Air Ducts and Air Connectors. Sheet metal fittings to which flexible ducts with plain ends are attached shall be beaded and have a minimum of 2 inches [50 mm] collar length. Beads are optional for fittings when using metal worm-gear clamps or when attaching metallic flexible ducts using sheet metal screws. Sheet metal sleeves used for joining two sections of flexible duct with plain ends shall be a minimum of 4 inches [100 mm] in length and beaded on each end. Beads are optional for sleeves when using metal worm-gear clamps or when joining metallic flexible ducts using sheet metal screws. Flexible ducts secured with nonmetallic clamps shall be limited to 6 inches w.g. [1500 Pa] positive pressure.
  • 10. 18 ADCFlexibleDuctPerformance&InstallationStandards,5thEdition Installation Requirements . . . continued Connections - Using Tape and Fasteners Splices - Using Tape and Fasteners 4.7.1 Installation Instructions for Air Ducts and Air Connectors - Nonmetallic with Plain Ends 1. After desired length is determined, cut completely around and through duct with knife or scissors. Cut wire with wire cutters. Fold back jacket and insulation. 2. Tape cores together with at least 2 wraps of duct tape. Secure connection with 2 clamps placed over the taped core ends and past the beads. 2. Slide at least 1" [25 mm] of core over fitting and past the bead. Seal core to collar with at least 2 wraps of duct tape. Secure connection with clamp placed over the core and tape and past the bead. 3. Pull jacket and insulation back over core. Tape jacket with at least 2 wraps of duct tape. A clamp may be used in place of or in combination with the duct tape. 3. Pull jacket and insulation back over cores. Tape jackets together with at least 2 wraps of duct tape. NOTES: 1. For uninsulated air ducts and air connectors, disregard references to insulation and jacket. 2. Use beaded sheet metal fittings and sleeves when using nonmetallic clamps. 3. Use tapes listed and labeled in accordance with Standard UL 181B and marked “181B-FX”. 4. Nonmetallic clamps shall be listed and labeled in accordance with Standard UL 181B and marked “181B-C”. Use of nonmetallic clamps shall be limited to 6 in. w.g. [1500 Pa] positive pressure. 1. Fold back jacket and insulation from core. Butt two cores together on a 4" [100 mm] min. length metal sleeve.
  • 11. 19 ADCFlexibleDuctPerformance&InstallationStandards,5thEdition Installation Requirements . . . continued 4.7.2 Alternate Installation Instructions for Air Ducts and Air Connectors - Nonmetallic with Plain Ends Connections and Splices - Using Mastic and Fasteners Step 1 After desired length is determined, cut completely around and through duct with knife or scissors. Cut wire with wire cutters. Pull back jacket and insulation from core. Step 2 Apply mastic approximately 2" [50 mm] wide uniformly around the collar of the metal fitting or over the ends of a 4" [100 mm] min. length metal sleeve. Reference data on mastic container for application rate, application thickness, cure times and handling information. Step 3 Slide at least 2" [50 mm] of core over the fitting or sleeve ends and past the bead. Step 4 Secure core to collar with a clamp applied past the bead. Secure cores to sleeve ends with 2 clamps applied past the beads. Step 5 Pull jacket and insulation back over core ends. Tape jacket(s) with at least 2 wraps of duct tape. A clamp may be used in place of or in combination with the duct tape. NOTES: 1. For uninsulated air ducts and air connectors, disregard references to insulation and jacket. 2. Use beaded sheet metal fittings and sleeves when using nonmetallic clamps. 3. Use mastics listed and labeled in accordance with Standard UL 181B and marked “181B-M” on container. 4. Use tapes listed and labeled in accordance with Standard UL 181B and marked “181B-FX”. 5. Nonmetallic clamps shall be listed and labeled in accordance with standard UL 181B and marked “181B-C”. Use of nonmetallic clamps shall be limited to 6 in. w.g. [1500 Pa] positive pressure.
  • 12. Installation Requirements . . . continued 4.7.3 Installation Instruction for Air Ducts and Air Connectors - Metallic with Plain Ends Connections and Splices - Using Tape or Mastic and Sheet Metal Screws NOTES: 1. For uninsulated air ducts and air connectors, disregard references to insulation and jacket. 2. Use mastics listed and labeled to Standard UL 181B and marked”181B-M” on container. 3. Use tapes listed and labeled to Standard UL 181B and marked “181B-FX”. 4. Nonmetallic clamps shall be listed and labeled in accordance with Standard UL 181B and marked “181B-C”. 1. After cutting duct to desired length, fold back jacket and insulation exposing core. Trim core ends squarely using suitable metal shears. Determine optional sealing method (Steps 2 or 5) before proceeding. 4. Secure to collar/sleeve using #8 sheet metal screws spaced equally around circumference. Use 3 screws for diameters under 12" [300 mm] and 5 screws for diameters 12" [300 mm] and over. 2. When mastics are required and for pressures 4" w.g. [1000 Pa] and over, seal joint with mastic applied uniformly to the outside surface of collar/sleeve. (Disregard this step when not using mastics and pro- ceed to Step 3). 3. Slide at least 1" [25 mm] of core over metal collar for attaching duct to take off or over ends of a 4" [100 mm] metal sleeve for splicing 2 lengths of duct. 5. For pressures under 4" w.g. [1000 Pa] seal joint using 2 wraps of duct tape applied over screw heads and spirally lapping tape to collar/sleeve. (Disregard this step when using mastics per Step 2). 6. Pull jacket and insulation back over core. Tape jacket with 2 wraps of duct tape. A clamp may be used in place of or in combination with the duct tape. 20 ADCFlexibleDuctPerformance&InstallationStandards,5thEdition