SlideShare a Scribd company logo
1 of 109
Download to read offline
1
GENERAL INTRODUCTION
ipe Shields Inc. pioneered the first insulated pipe support, in 1971, for use on HVAC and plumbing
lines. These supports were designed because fiberglass pipe insulation is not strong enough to carry
the load at the point of support without crushing. The various methods contractors employed to
compensate for this weakness were inconsistent, non-uniform and labor intensive, often resulting in
damage to the vapor barrier and/or pipe insulation. The insulated pipe support filled the need for an
energy efficient, economical and practical support.
Pipe Shields Inc. has developed a large and growing family of insulated pipe supports, using its
“standard concept” of incorporating materials strong enough to carry the load while insulating the pipe at
the same time. No welding to the pipe is required (except for insulated positive anchors and insulated
pipe riser clamps) and no direct metal-to-metal heat path exists. Insulated pipe supports meet an
assortment of requirements, including:
· Pipe supported on:
o Flat Surface
o Pipe Roll
o Clevis Hanger
· Gas
· Steam
· Super Heated Steam
· Chilled Water
· Styrene
· Guide Supports
· Sliding Supports
· Restrained Supports
· Anchors
· Pipe Hangers
· Pipe Riser Clamps
· Thermal Growth – Small or Large
· Maximum Support Spacing
· Light, Medium or Heavy Loads
· Ultra-High Temperatures
· Minimum Overhead Clearance
· Minimum Horizontal Clearance
· Minimum Field Labor
· Minimum Friction Loads
· Easy Installation
Other products designed, manufactured and supplied not included in this catalog are:
1. Cryogenic supports
2. Seismic pipe restraints
3. Heat-traced pre-insulated pipe supports
4. Pipe supports used in computer chip, styrene plants and oil refineries
5. Pipe supports for solar energy projects to accommodate expansion travels in excess of 5’- 0”
Our highly sophisticated products are a direct result of years of research, engineering and design to
develop cost efficient products for the power, petrochemical, chemical and commercial markets. We
work closely with engineering firms and in-house engineering departments of owners to provide working
solutions to meet their engineering challenges. We have established proprietary specifications that have
now become an industry standard used by owners, engineers and contractors throughout the world
markets.
If you have a pipe support need not met by any of the items described in this catalog, please contact us at
713-731-0030 or 1-800-787-5914.
P
FRONEK GROUP
CATALOG PS-2004
2
TEMPERATURE, DIMENSIONAL AND MATERIAL VARIANCES
Temperature Ranges
Pipe Shields Inc. strongly recommends the following temperature ranges for our standard insulation
material:
Material Temperature
Calcium Silicate +40
o
F to + 1200o
F
Urethane -275
o
F to +275
o
F
Foamglasâ -450
o
F to +900
o
F
Material Variances
Our standard paint finish is SP150 Red Oxide Primer which meets full EPA and California safety
regulations. Other paint finished are available upon request:
· Hot dipped galvanized
· In-organic zinc (CZ11HS)
· Dupont (Corlar) 25P epoxy
· SP145 grey oxide
· Carbothane 134HG
· Carbozinc 859
Slide plate material and other field welded material are coated with deoxaluminate (silver coating)
Model Designation for Alternate Insulation Materials
Polyurethane – Add U after Catalog Model Number Example: B1000U
Urethane/Foamglasâ - Add UF after Catalog Model Number Example: B1000UF
Calcium Silicate/Foamglasâ - Add CF after Catalog Model Number Example: B1000CF
FRONEK GROUP
CATALOG PS-2004
3
INSULATED PIPE SUPPORT SELECTION GUIDE
FRONEK GROUP
CATALOG PS-2004
1.
A. Water
B. Steam, Gas, or Air
2. APPLICATION
A. Pipe supported from below
a. On flat surface
b. On pipe roll
B. Pipe supported from above
a. In clevis or 2-bolt hanger
The product data sheets describing each model refer to other models in the catalog with features such as
load rating, axial or lateral travel, or restraint, etc. which you may have an interest.
USE OF THE INSULATED PIPE SUPPORT SELECTION GUIDE
X
X
OR AIR
TABLE 6 X
TABLE 3
TABLE 1
TABLE 2
X
X
X
TABLE 4
TABLE 5
X
X
X
X
X
X
ON
PIPE ROLL
ON FLAT
SURFACE
APPLICATION
PIPE SUPPORTED
FROM ABOVEFROM BELOW
If you have a pipe support need not met by any of the items described in this catalog, please contact us at
713-731-0030 or 1-800-787-5914.
SERVICE
These Selection Guide Tables are organized by:
The table on the following pages will assist you in making a selection of the proper and most economic
insulated pipe support for your application.
WATER
SERVICE
STEAM
GAS IN CLEVIS OR
2-BOLT HANGER
4
INSULATED PIPE SUPPORT SELECTION GUIDE
FRONEK GROUP
CATALOG PS-2004
WATER
PIPE SUPPORTED FROM BELOW ON FLAT SURFACE
B1000 B1100 B1200 B1300
B2000 B2100 B2200 B2300
B3000 B3100 B3200 B3300
B4000 B4100 B4200 B4300
ASME A1000 A3000 A5000 A7000 A7200 A7400 B5000 B5100 B5200 B5300 B7000 B7100 B7200 B7300
B31.1 A2000 A4000 A6000 B6000 B6100 B6200 B6300 B8000 B8100 B8200 B8300
Pipe
Size (Ref)
1/2 7 11 12
3/4 7 12 13
1 7 13 14
1 1/2 9 15 16
2 10 15 17
2 1/2 11 12 14 16 21
3 12 12 13 17 20 35 45 55 32 45 55
3 1/2 13 12 13 16 19 35 45 55 33 45 55
4 14 13 14 17 19 35 45 55 35 45 55
5 16 12 14 16 17 35 45 55 33 45 55
6 17 10 12 13 14 26 34 45 55 30 45 55
8 19 7 8 11 12 21 29 45 55 26 45 55
10 22 6 6 7 10 18 25 24 45 55 21 42 55
12 23 8 14 20 31 20 40 55 65 17 36 54 65
14 25 8 13 22 31 20 40 55 65 18 35 53 65
16 27 12 21 28 19 37 55 65 16 34 50 65
18 28 10 19 26 17 34 52 65 15 30 46 61
20 30 9 17 23 15 31 46 62 14 27 41 55
24 32 14 18 12 24 36 48 10 21 32 43
30 33 10 12 11 21 32 43 9 19 29 39
36 35 9 18 28 37 8 16 24 33
42 36 8 16 24 32 7 14 21 28
Note:
Pipe Diameter: 8" standard weight
Water
20' - 0
Insulated pipe support model number
support spacing. In this case, Model A7200 is selected since it is capable of handling 21'-0 support
spacing. The Index Sheets to Sections "A" & "B" indicate some of the differences between models.
Check Product Data Sheet for description before making a final selection. In this example, if the
support is required to handle +/-4 1/2" of axial travel, Model B2000 would be selected (Section "B"
Index & Product Data Sheet B2000).
The maximum hanger spacing shown in Table 1 are derived from load ratings (see Product Data Sheets) of
Pipe Shields Inc. models, assuming weight of standard pipe, water, and 2" insulation. The customer should be
guided by the hanger spacings allowed by the applicable code or the project engineers' specifications before making
a selection. Refer to the appropriate Product Data Sheets for additional information such as load rating,
compensation for temperature, axial or lateral travel, or restraint, etc.
In table 1, for 8" pipe size, find the model(s) rated for handling 20'- 0 or greater
Service:
Determine:
Support Spacing:
Method:
Example: Given:
TABLE 1
SERVICE:
APPLICATION:
MAXIMUM HANGER SUPPORT SPACING - FEET
FOR VARIOUS PIPE SHIELDS, INC.INSULATED PIPE SUPPORT MODELS
Commercial
Light Industrial
w/ Load Distribution Plate
Heavy Industrial
on Slide Pad
Rated for Combined
Lateral and Vertical Loads
5
INSULATED PIPE SUPPORT SELECTION GUIDE
FRONEK GROUP
CATALOG PS-2004
STEAM, GAS OR AIR
PIPE SUPPORTED FROM BELOW ON FLAT SURFACE
B1000 B1100 B1200 B1300
B2000 B2100 B2200 B2300
B3000 B3100 B3200 B3300
B4000 B4100 B4200 B4300
ASME A1000 A3000 A5000 A7000 A7200 A7400 B5000 B5100 B5200 B5300 B7000 B7100 B7200 B7300
B31.1 A2000 A4000 A6000 B6000 B6100 B6200 B6300 B8000 B8100 B8200 B8300
Pipe
Size (Ref)
1/2 8 11 12
3/4 9 12 13
1 9 14 15
1 1/2 12 17 19
2 13 18 20
2 1/2 14 15 16 20 25
3 15 15 17 21 26 40 50 60 40 50 60
3 1/2 16 16 18 21 25 40 50 60 40 50 60
4 17 17 19 23 26 40 50 60 40 50 60
5 19 17 20 22 25 40 50 60 40 50 60
6 21 16 18 20 22 40 40 50 60 40 50 60
8 24 12 14 17 19 35 40 50 60 40 50 60
10 26 10 10 13 17 31 40 40 50 60 36 50 60
12 30 9 9 15 26 37 45 36 50 60 70 32 50 60 70
14 32 8 9 15 25 40 45 38 50 60 70 34 50 60 70
16 35 8 8 14 24 40 45 39 50 60 70 25 50 60 70
18 37 14 24 40 45 38 50 60 70 34 50 60 70
20 39 14 22 40 45 36 50 60 70 32 50 60 70
24 42 11 20 36 45 32 50 60 70 28 50 60 70
30 44 10 18 32 39 33 50 60 70 30 50 60 70
36 48 9 15 27 33 50 60 70 29 50 60 70
42 50 12 23 31 50 60 70 28 50 60 70
Note:
Pipe Diameter: 8" standard weight
Steam
30' - 0
Insulated pipe support model number
The maximum hanger spacing shown in Table 2 are derived from load ratings (see Product Data Sheets) of
Pipe Shields Inc. models, assuming weight of standard pipe, and 2" insulation. The customer should be guided by
the hanger spacings allowed by the applicable code or the project engineers' specifications before making a
selection. Refer to the appropriate Product Data Sheets for additional information such as load rating, compensation
for temperature, axial or lateral travel, or restraint, etc.
w/ Load Distribution Plate
Heavy Industrial
on Slide Pad
Rated for Combined
Lateral and Vertical Loads
support spacing. In this case, Model A7200 is selected since it is capable of handling 35'-0 support
spacing. The Index Sheets to Sections "A" & "B" indicate some of the differences between models.
Check Product Data Sheet for description before making a final selection. In this example, if the
support is required to handle +/-4 1/2" of axial travel, Model B2000 would be selected (Section "B"
Index & Product Data Sheet B2000).
Example: Given:
TABLE 2
SERVICE:
APPLICATION:
MAXIMUM HANGER SUPPORT SPACING - FEET
FOR VARIOUS PIPE SHIELDS, INC.INSULATED PIPE SUPPORT MODELS
Commercial
Light Industrial
In table 2, for 8" pipe size, find the model(s) rated for handling 30'- 0 or greater
Service:
Determine:
Support Spacing:
Method:
6
INSULATED PIPE SUPPORT SELECTION GUIDE
FRONEK GROUP
CATALOG PS-2004
WATER
PIPE SUPPORTED FROM ABOVE IN CLEVIS OR 2-BOLT HANGER
D1000
D2000
ASME A1000 A3000 D4000 D3000 D3100 D3200 D3300
B31.1 A2000 A4000 A9000 D5000 D6000 D6100 D6200 D6300
Pipe
Size (Ref)
1/2 7 11 12 13
3/4 7 12 13 15
1 7 14 15 17 19
1 1/2 9 16 18 19 22
2 10 17 18 21 29
2 1/2 11 16 18 21 24
3 12 17 18 20 25
3 1/2 13 16 17 19 22
4 14 16 18 19 22
5 16 15 16 19 21 40
6 17 14 15 16 21 40
8 19 13 13 15 22 32
10 22 12 13 14 24 28
12 23 11 12 13 22 26
14 25 11 12 13 20 23
16 27 10 11 12 21 26 40
18 28 9 10 11 18 22 33
20 30 9 9 10 16 18 28 37
24 32 8 9 15 19 29 38
30 33 11 13 19 26
Note:
Pipe Diameter: 8" standard weight
Water
20' - 0
Insulated pipe support model number
MAXIMUM HANGER SUPPORT SPACING - FEET
In table 3, for 8" pipe size, find the model(s) rated for handling 20"- 0 or greater
support spacing. In this case, Model D3000 is selected since it is capable of handling 22'-0 support spacing.
The Index Sheets to Sections "A" & "D" indicate some of the differences between models. Check Product
Data Sheet for description before making a final selection. In this example, if the clearance is above the
support limited, Model D6000 might be selected (Section "D" Index & Product Data Sheet D6000).
Service:
Determine:
Support Spacing:
Method:
Example: Given:
The maximum hanger spacing shown in Table 3 are derived from load ratings (see Product Data Sheets) of
Pipe Shields Inc. models, assuming weight of standard pipe, water, and 2" insulation. The customer should be
guided by the hanger spacings allowed by the applicable code or the project engineers' specifications before making
aection. Refer to the appropriate Product Data Sheets for additional information such as load rating,
compensation for temperature, axial or lateral travel, or restraint, etc.
TABLE 3
SERVICE:
APPLICATION:
Clevis Hanger 2-Bolt Hanger
FOR VARIOUS PIPE SHIELDS, INC.
PRE-INSULATED PIPE SUPPORT MODELS
7
INSULATED PIPE SUPPORT SELECTION GUIDE
FRONEK GROUP
CATALOG PS-2004
STEAM, GAS OR AIR
PIPE SUPPORTED FROM ABOVE IN CLEVIS OR 2-BOLT HANGER
D1000
D2000
ASME A1000 A3000 D4000 D3000 D3100 D3200 D3300
B31.1 A2000 A4000 A9000 D5000 D6000 D6100 D6200 D6300
Pipe
Size (Ref)
1/2 8 11 12 13
3/4 9 12 13 15
1 9 15 16 19 21
1 1/2 12 19 20 22 26
2 13 20 22 25 36
2 1/2 14 20 22 25 29
3 15 21 24 26 32
3 1/2 16 21 23 25 29
4 17 23 24 26 31
5 19 22 24 28 30 55
6 21 22 23 24 32 55
8 24 21 22 25 25 52
10 26 20 22 24 40 45
12 30 20 21 24 40 45
14 32 21 23 25 38 55 60
16 35 21 22 25 40 55 60
18 37 21 22 25 40 49 60
20 39 21 22 25 38 44 60 65
24 42 20 21 24 40 50 60 65
30 44 34 51 60 65
Note:
Pipe Diameter: 8" standard weight
Steam
24' - 0
Insulated pipe support model number
TABLE 4
SERVICE:
APPLICATION:
Clevis Hanger
FOR VARIOUS PIPE SHIELDS, INC.
PRE-INSULATED PIPE SUPPORT MODELS
2-Bolt Hanger
MAXIMUM HANGER SUPPORT SPACING - FEET
The maximum hanger spacing shown in Table 4 are derived from load ratings (see Product Data Sheets) o
Pipe Shields Inc. models, assuming weight of standard pipe, and 2" insulation. The customer should be guided by
the hanger spacings allowed by the applicable code or the project engineers' specifications before making a
selection. Refer to the appropriate Product Data Sheets for additional information such as load rating, compensation
for temperature, axial or lateral travel, or restraint, etc.
support spacing. In this case, Model A9000 is selected since it is capable of handling 25'-0 support spacing.
The Index Sheets to Sections "A" & "D" indicate some of the differences between models. Check Product
Data Sheet for description before making a final selection. In this example, if the clearance is above the
support limited, Model D6000 might be selected (Section "D" Index & Product Data Sheet D6000).
Service:
Determine:
Support Spacing:
Method: In table 4, for 8" pipe size, find the model(s) rated for handling 24'- 0 or greater
Example: Given:
8
INSULATED PIPE SUPPORT SELECTION GUIDE
FRONEK GROUP
CATALOG PS-2004
WATER
PIPE SUPPORTED FROM BELOW ON PIPE ROLL
ASME A5000
B31.1 A6000 A8000 A8200 A8400
Pipe
Size (Ref)
1/2 7
3/4 7
1 7
1 1/2 9
2 10
2 1/2 11 15 18
3 12 15 17
3 1/2 13 12 16
4 14 15 16
5 16 14 15
6 17 12 13 24
8 19 9 10 19
10 22 10 16 22
12 23 12 23 31
14 25 11 21 28
16 27 10 19 25
18 28 9 17 23
20 30 8 15 20
24 32 12 16
30 33 9 12
Note:
Pipe Diameter: 8" standard weight
Water
18' - 0
Insulated pipe support model number
The maximum hanger spacing shown in Table 5 are derived from load ratings (see Product Data Sheets) of
Pipe Shields Inc. models, assuming weight of standard pipe, water, and 2" insulation. The customer should be
guided by the hanger spacings allowed by the applicable code or the project engineers' specifications before making
a selection. Refer to the appropriate Product Data Sheets for additional information such as load rating,
compensation for temperature, axial or lateral travel, or restraint, etc.
13
15
12
12
12
Service:
Determine:
Support Spacing:
Method: In table 5, for 8" pipe size, find the model(s) rated for handling 18'- 0 or greater
support spacing. In this case, Model A8200 is selected since it is capable of handling 19'-0 support spacing.
The Index Sheet to Section "A" indicates some of the differences between models. Check Product Data
Sheet for description before making a final selection. If greater support spacings are desired, see Section "B"
(Base Mounted Supports).
Example: Given:
TABLE 5
SERVICE:
APPLICATION:
A3000
A4000
13
15
Commercial
12
13
Light Insutrial w/Load
Distribution Plate
MAXIMUM HANGER SUPPORT SPACING - FEET
FOR VARIOUS PIPE SHIELDS, INC.
PRE-INSULATED PIPE SUPPORT MODELS
9
INSULATED PIPE SUPPORT SELECTION GUIDE
FRONEK GROUP
CATALOG PS-2004
STEAM, GAS OR AIR
PIPE SUPPORTED FROM BELOW ON PIPE ROLL
ASME A5000
B31.1 A6000 A8000 A8200 A8400
Pipe
Size (Ref)
1/2 8
3/4 9
1 9
1 1/2 12
2 13
2 1/2 14 18 22
3 15 19 21
3 1/2 16 19 21
4 17 20 23
5 19 20 22
6 21 18 20 36
8 24 15 17 31
10 26 11 17 27 38
12 30 13 23 40 50
14 32 13 22 40 50
16 35 13 22 39 50
18 37 12 21 38 50
20 39 12 20 36 49
24 42 11 18 33 44
30 44 9 16 29 39
36 48 8 13 24
42 50 11 20
Note:
Pipe Diameter: 8" standard weight
Steam
25' - 0
Insulated pipe support model number
Light Industrial w/ Load
Distribution Plate
15
Example: Given:
15
16
17
The maximum hanger spacing shown in Table 6 are derived from load ratings (see Product Data Sheets) of
Pipe Shields Inc. models, assuming weight of standard pipe, and 2" insulation. The customer should be guided by
the hanger spacings allowed by the applicable code or the project engineers' specifications before making a
selection. Refer to the appropriate Product Data Sheets for additional information such as load rating, compensation
for temperature, axial or lateral travel, or restraint, etc.
TABLE 6
SERVICE:
APPLICATION:
A3000
MAXIMUM HANGER SUPPORT SPACING - FEET
FOR VARIOUS PIPE SHIELDS, INC.
PRE-INSULATED PIPE SUPPORT MODELS
A4000
14
17
18
Commercial
12
13
Service:
Determine:
Support Spacing:
Method: In table 6, for 8" pipe size, find the model (s) rated for handling 25'-0 or greater
support spacing. In this case, Model A8200 is selected since it is capable of handling 25'-0 or 31'-0 support
spacing. The Index Sheet to Section "A" indicates some of the differences between models. Check Product
Data Sheet for description before making a final selection. If greater support spacings are desired, see
Section "B" (Base Mounted Supports).
FRONEK GROUP
INTRODUCTION SECTION “A”
INTRODUCTION
SECTION “A”
PRE-INSULATED PIPE SUPPORTS
APPLICATION – Commercial and Light Industrial
Most Commercial applications are well served by Models A1000 and A2000, which are
recommended for use on common 10’-0 hanger space for small bore pipe sizes (see Selection
Guide). However, should the need arise, because of increased hanger spacing or the manner in
which the insulated support is mounted, heavier duty supports are available.
As is readily seen in the “Section Index” on the following page, some models are meant for
installation only in a clevis hanger, on a flat surface, or on a pipe roll. Other models may be
installed in any two or all three mounting methods.
The load ratings (see Product Data Sheets) reflect consideration for the manner in which each of
these models will be mounted.
Note that in the A7000 through A7400 Series and the A8000 through A8400 Series, the
higher the model number, the higher the load rating.
We are committed to providing the most economical and appropriate insulated pipe support to
satisfy the requirements of the piping system.
If your requirements are not covered by the Product Data Sheets in this catalog, please contact us at
713-731-0030 or 1-800-787-5914.
Please acquaint yourself with the selection guide at the front of this catalog and the section
index on the page following this introduction, for assistance in determining the most
appropriate support for your application.
FRONEK GROUP
CATALOG PS-2004
PIPE
SIZE FLAT CLEVIS PIPE
MODEL RANGE HOT COLD SURFACE HANGER ROLL DUTY
A1000 1/2 - 24 X X X LIGHT
A2000 1/2 - 24 X X X LIGHT
A3000 1/2 - 24 X X X MEDIUM
A3000 1/2 - 4 X X MEDIUM
A4000 1/2 - 24 X X X MEDIUM
A4000 1/2 - 4 X X MEDIUM
A5000 2 1/2 - 42 X X X MED/HEAVY
A6000 2 1/2 - 42 X X X MED/HEAVY
A7000 2 1/2 - 42 X X X HEAVY
A7200 6 - 42 X X X HEAVIER
A7400 10 - 30 X X X HEAVIEST
A8000 2 1/2 - 42 X X X HEAVY
A8200 6 - 42 X X X HEAVIER
A8400 10 - 30 X X X HEAVIEST
A9000 1/2 - 24 X X X HEAVY
PRE-INSULATED PIPE SUPPORTS
COMMERCIAL AND LIGHT INDUSTRIAL
PRIMARY
APPLICATION
INSTALLED ON
SECTION “A” INDEX
TO ORDER, specify:
1. Quantity 20
2. Pipe Size & Type 2” IPS
3. Insulation Thickness 2-1/2”
4. Model Number A1000
EXAMPLE: (20) 2 x 2-1/2 A1000
FRONEK GROUP
CATALOG PS-2004
MODEL A1000 Insulated Pipe Support Regular Duty
A1
Features:
· Compact
· Easy Installation
· Eliminates welding to pipe
· Overlapping galvanized sheet metal jacket
· Minimizes heat-loss and/or condensation
· Copper tubing sizes available
· Other I.D.'s and/or O.D.'s available on
request
· Clamps available (see G-series)
Performance Test Results on File:
Available upon request.
·
·
·
·
Material Data:
A1000: Applicable PSI spec. doc.: No. 205.
Insulation: Calcium Silicate asbestos-free,
treated with water repellant.
Jackets: Galvanized Steel ASTMA-527.
Glue: Industrial contact adhesive
Formal Submittal Sheets available
Application:
Model A1000 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam ·Air
· Dual Temperature · Chilled Water
Intended for installation on:
· Flat Surfaces
· Band, ring or clevis pipe hanger
Note: Up to 1700°F available upon request.
Temperature Range: °F to +1200°F+40
FRONEK GROUP
CATALOG PS-2004
Hardware sold separately
A B A B A B A B A B A B A B A B A B
4 24 4 24 4 24 4 24 4 24 4 24 6 24 6 24 6 24
6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24
6 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20
6 20 6 20 6 20 6 20 9 20 9 20 9 20
6 20 6 20 6 20 6 20 9 16 9 16 9 16
9 16 9 16 9 16 9 16 9 16 9 16
12 16 12 16 12 16 12 16 12 16 12 16
18 16 18 16 18 16 18 16 18 16 18 16
200
TABLE III
1200
0.75
0.50
0.30
750
1000
350
450
Mult.
Copper
Tubing
Size O.D.
250
550
1000
750
1200
300
Oper.
Temp.
o
F
To develop maximum load rating, use band, ring or clevis hanger with manufacturer's
load rating equal to or greater than values shown in Table I.
To develop maximum load rating, width of support surface should be at least 1/2 of
dimension "A" in Table II.
The load ratings represent average values obtained in accordance with accepted
methods and are subject to normal manufacturing variations. Dimensions and ratings
are subject to change without notice.
Factor
"F"
500 0.90
MAXIMUM LOAD
Pipe On Flat In Clevis
1 1/2
Iron
Contact factory for other dimensions,
temperatures, and loads.
Available in all insulation thicknesses.
Insulation Thickness
2 2 1/2
To obtain load ratings for operating temperatures of 500° F and higher, multiply load
rating by factor "F" in Table III.
1/2 3/4 1
8 1/8 -10 1/8
12 1/8
5/8 - 1 5/8
4
2 1/8
2 5/8 - 4 1/8
550
350
65
80
110
140
150
180
225
270
400
450
3
8
5
6
14
16
18
24
20
1600
1800
2000
3 1/2
TABLE I
750
600
625
675
TABLE II "B" = gauge of sheet metal jacket
Pipe
Size
1/2 - 1 1/2
6 - 7
8 - 10
12 - 18
5
2 1/2 - 4
3
2 1/2
2
20 - 24
5 1/8
6 1/8
2300
10
1400575
500
Note: For higher load ratings, see A3000, A9000.
12
3 1/2
4
70
100
125
1 1/4
1 1/2
2
1
1/2
40
60
Size
3/4
RATING (LBS)
Hanger
(b) (c)
40
Surface
(a) (c)
35
45
A2
MODEL A2000 Insulated Pipe Support
Regular Duty w/
Extended Insulation
Application:
Model A2000 is designed for use on:
· Cold Water
· Chilled Water
Intended for installation on:
· Flat Surfaces
· Band, ring or clevis pipe hangers
Temperature Range: °F to +1200°F+40
Note: Up to 1700°F available upon request.
Features:
· Compact
· Easy Installation
· Eliminates welding to pipe
· Overlapping galvanized sheet metal jacket
· Minimizes heat-loss and/or condensation
· Calcium silicate insulation extends 1'' beyond
the galvanized sheet metal jacket providing
for an easier vapor barrier joint with the pipe
insulation
· Copper tubing sizes available
· Other I.D.'s and/or O.D.'s available on
request
· Clamps available see (G-series)
Performance Test Results on File:
Available upon request.
Material Data:
· A2000: Applicable PSI spec. doc.: No. 205.
· Insulation: Calcium Silicate asbestos-free,
treated with water repellant.
· Jackets: Galvanized Steel ASTMA-527.
· Glue: Industrial contact adhesive
Formal Submittal Sheets available
FRONEK GROUP
CATALOG PS-2004
Hardware sold separately
A B A B A B A B A B A B A B A B A B
6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24
6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24
6 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20
6 20 6 20 6 20 6 20 9 20 9 20 9 20
6 20 6 20 6 20 6 20 9 16 9 16 9 16
9 16 9 16 9 16 9 16 9 16 9 16
12 16 12 16 12 16 12 16 12 16 12 16
18 16 18 16 18 16 18 16 18 16 18 16
0.75
0.50
TABLE III
1200 0.30
FactorTemp.
The load ratings represent average values obtained in accordance with accepted
methods and are subject to normal manufacturing variations. Dimensions and ratings
are subject to change without notice.
o
F "F"
Note: For higher load ratings, see A4000, A9000.
500
750
1000
0.90
10
3 1/2
12
14
4
5
6
8
To obtain load ratings for operating temperatures of 500°F and higher, multiply load
rating by factor "F" in Table III.
18
20
24
To develop maximum load rating, width of support surface should be at least 1/2 of
dimension "A" in Table II.
To develop maximum load rating, use band, ring or clevis hanger with manufacturer's
load rating equal to or greater than values shown in Table I.
Contact factory for other dimensions,
temperatures, and loads.
Available in all insulation thicknesses.
16
2000675
1400
1600
1800625
575
1 1/2
2
2 1/2
3
1/2
3/4
1
1 1/4
12 1/8
750
5/8 - 15/8
Copper
Tubing
Size O.D.
4
2300
6 1/8
8 1/8 -10 1/8
110
140
200
250
450
750
1000
550
70
600
500
150
400
450
550
MAXIMUM LOAD
On Flat
1200
Pipe
225
270
100
125
300
350
3 1/2
RATING (LBS)
In Clevis
40
45
65
80
35
40
60
Oper. Mult.
2 2 1/2
Insulation ThicknessIron
Pipe
180
350
TABLE II "B" = gauge of sheet metal jacket
3/4 1 1 1/2
20 - 24
5
6 - 7
2 1/8
2 5/8 - 4 1/8
5 1/8
1/2 - 1 1/2
1/2
8 - 10
Size
12 - 18
Size
TABLE I
Hanger
(b) (c)
Surface
(a) (c)
2 1/2 - 4
3
2
MODEL A3000 Insulated Pipe Support
A3
Extra Heavy
Bottom Jacket
Features:
· Compact
· Easy Installation
· Eliminates welding to pipe
· Overlapping galvanized sheet metal jacket
· Minimizes heat-loss and/or condensation
· Double thickness bottom jacket for added
structural strength and abrasive wear
resistance
· Copper tubing sizes available
· Other I.D.'s and/or O.D.'s available on
request
· Clamps available (see G-series)
Performance Test Results on File:
Available upon request.
Material Data:
· A3000: Applicable PSI spec. doc.: No. 205.
· Insulation: Calcium Silicate asbestos-free,
treated with water repellant.
· Jackets: Galvanized Steel ASTMA-527.
· Glue: Industrial contact adhesive.
Formal Submittal Sheets available
Application:
Model A3000 is designed for use on:
· Hot Water · Steam
· Cold Water · Air
· Chilled Water · Gas
· Dual Temperature · Vacuum
Intended for installation on:
· Flat Surfaces . Pipe Rolls
· Band, ring or clevis pipe hanger
Note: Up to 1700°F available upon request.
Temperature Range: °F to +1200°F+40
FRONEK GROUP
CATALOG PS-2004
Pipe
Size
1/2
3/4
1
1 1/4
1 1/2
2
Hardware sold separately 2 1/2
3
3 1/2
4
5
6
8
10
12
14
16
18
20
24
A B A B A B A B A B A B A B A B A B
4 24 4 24 4 24 4 24 4 24 4 24 6 24 6 24 6 24
6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24
6 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20
6 20 6 20 6 20 6 20 9 20 9 20 9 20
6 20 6 20 6 20 6 20 9 16 9 16 9 16
9 16 9 16 9 16 9 16 9 16 9 16
12 16 12 16 12 16 12 16 12 16 12 16
18 16 18 16 18 16 18 16 18 16 18 16
TABLE II "B" = gauge of sheet metal jacket (bottom jacket approx. 2 X ga. of top jacket)
12 - 18 12 1/8
20 - 24
6 - 7 6 1/8
8 - 10 8 1/8 -10 1/8
2 1/2 - 4 2 5/8 - 4 1/8
5 5 1/8
1/2 - 1 1/2 5/8 -1 5/8
2 2 1/8
3 1/2 4 Tubing
Size Size O.D.
1 1/2 2 2 1/2 3Pipe
To develop maximum load rating, use band, ring or clevis hanger with manufacturer's
load rating equal to or greater than values shown in Table I. TABLE I
1/2 3/4 1
Contact factory for other dimensions,
temperatures, loads.
Available in all insulation thicknesses.
To obtain load ratings for operating temperatures of 500o
F and higher, multiply load
rating by factor "F" in Table III.
Iron Insulation Thickness Copper
700 2100
775 2400
Divide "A" in Table II by 6 to find maximum allowable travel on pipe roll (+/- from
centered position). 650 1900
600 1500
625 A5000 1700
To develop maximum load rating, width of support surface should be at least 1/2 of
dimension "A" in Table II. 575 1300
500 800
525 See 1100
300 270 375The load ratings represent average values obtained in accordance with accepted
methods and are subject to normal manufacturing variations. Dimensions and ratings
are subject to change without notice.
400 475
450 575
Note: For higher load ratings, see A5000, A9000.
250 225 325
200 180
155
TABLE III
165 150 2201200 0.30
140 125
275
120750 0.75
80
1000 0.50
110 100
50
500 0.90
65 60 70
70 90
(b) (d) (c) (d)
Temp. Factor
40 35 45Oper. Mult.
40
(a) (d)
o
F "F"
45
Surface Roll or Clevis
Hanger
MAXIMUM LOAD
RATING (LBS)
On Flat On Pipe In Ring
A4
MODEL A4000 Insulated Pipe Support
Extra Heavy Bottom
Jacket w/ext. Insulation
Material Data:
· A4000: Applicable PSI spec. doc.: No. 205.
· Insulation: Calcium Silicate asbestos-free,
treated with water repellant.
· Jackets: Galvanized Steel ASTMA-527.
· Glue: Industrial contact adhesive.
Formal Submittal Sheets available
Features:
· Compact
· Easy Installation
· Eliminates welding to pipe
· Overlapping galvanized sheet metal jacket
· Double thickness bottom jacket for added
structural strength and abrasive wear
· Minimizes heat-loss and/or condensation
· Calcium silicate insulation extends 1'' beyond
the galvanized sheet metal jacket providing
for an easier vapor barrier joint with the pipe
· Copper tubing sizes available
· Other I.D.'s and/or O.D.'s available on request
· Clamps available (see G-series)
Performance Test Results on File:
Available upon request.
resistance
Application:
Model A4000 is designed for use on:
· Cold Water · Chilled Water
Intended for installation on:
· Flat Surfaces . Pipe Rolls
· Band, ring or clevis pipe hanger
Note: Up to 1700°F available upon request.
Temperature Range: °F to +1200°F+40
FRONEK GROUP
CATALOG PS-2004
Pipe
Size
1/2
3/4
1
1 1/4
1 1/2
2
Hardware sold separately 2 1/2
3
3 1/2
4
5
6
8
10
12
14
16
18
20
24
A B A B A B A B A B A B A B A B A B
6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24
6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24
6 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20
6 20 6 20 6 20 6 20 9 20 9 20 9 20
6 20 6 20 6 20 6 20 9 16 9 16 9 16
9 16 9 16 9 16 9 16 9 16 9 16
12 16 12 16 12 16 12 16 12 16 12 16
18 16 18 16 18 16 18 16 18 16 18 16
35
40
12 1/8
5/8-1 5/8
2 5/8 - 4 1/8
6 1/8
8 1/8 -10 1/8
See
270
60
70
100
125
80
110
140
165
Surface
40
45
65
On Pipe In Ring
(c) (d)
or ClevisRoll
Temp.
Oper. Mult.
Factor
12 - 18
2 1/2 - 4
TABLE III
2 2 1/2
Iron
Pipe
Size
1/2
2
1/2 - 1 1/2
TABLE II "B" = gauge of sheet metal jacket (bottom jacket approx. 2 X ga. of top jacket)
3/4 1 1 1/2
20 - 24
5
6 - 7
8 - 10
220
275200
250
150
180
225 325
1200
0.90
0.75
0.50
0.30
500
"F"
750
1000
o
F 70
90
120
155
MAXIMUM LOAD
On Flat
375
475
45
Hanger
(b) (d)
RATING (LBS)
(a) (d)
50
575
3 1/2
1700
1900
2100
2400
4
Insulation Thickness
700
300
400
450
650
500
625
525
575
600
5 1/8
Copper
Tubing
Size O.D.
1500
775
2 1/8
TABLE I
3
A6000
Note: For higher load ratings, see A6000, A9000
To obtain load ratings for operating temperatures of 500°F and higher, multiply load
rating by factor "F" in Table III.
Contact factory for other dimensions,
temperatures, loads.
Available in all insulation thicknesses.
The load ratings represent average values obtained in accordance with accepted
methods and are subject to normal manufacturing variations. Dimensions and ratings
are subject to change without notice.
To develop maximum load rating, width of support surface should be at least 1/2 of
dimension "A" in Table II.
Divide "A" in Table II by 6 to find maximum allowable travel on pipe roll (+/- from
centered position).
To develop maximum load rating use band, ring or clevis hanger with manufacturer's
load rating equal to or greater than values shown in Table I.
800
1100
1300
A5
MODEL A5000 Insulated Pipe Support
With load
distribution plate
Features:
· Compact
· Easy Installation
· Eliminates welding to pipe
· Copper tubing sizes available
· Overlapping galvanized sheet metal jacket
· Minimizes heat-loss and/or condensation
· Load distribution plate integral with bottom
jacket
· Other I.D.'s and/or O.D.'s available upon
request
Performance Test Results on File:
Available upon request.
Material Data:
· A5000: Applicable PSI spec. doc.: No. 205.
· Insulation: Calcium Silicate asbestos-free,
treated with water repellant.
· Jackets: Galvanized Steel ASTM A-527.
· Load distribution Plate: Carbon steel
ASTM A-36
· Coating: Primer coated or hot-dip galvanized.
Other coatings available upon request.
· Glue: Industrial contact adhesive.
Formal Submittal Sheets available
Application:
Model A5000 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam · Air
· Dual Temperature · Chilled Water
Intended for installation on:
· Flat Surfaces · Pipe Rolls
Note: Up to 1700°F available upon request.
Temperature Range: °F to +1200°F+40
FRONEK GROUP
CATALOG PS-2004
A B C
9 6 1/4
9 6 1/4
9 6 1/4
9 6 1/4
9 6 1/4
9 6 1/4
9 6 1/4
9 6 1/4
12 9 3/8
12 9 3/8
12 9 1/2
12 9 1/2
12 9 1/2
12 9 3/4
12 9 3/4
12 9 3/4
12 9 3/4
Hardware sold separately
Note: For higher load ratings, see A7000
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing
variations. Dimensions and ratings are subject to change without notice. Contact factory for current information.
To develop maximum load rating, width of support surface should be at least 1/2 of dimension "B" in Table I.
To obtain load ratings for operating temperatures of 500o
F and higher, multiply maximum load rating by factor "F" in Table II.
Contact factory for other dimensions, temperatures, and loads. Available
in all insulation thicknesses.1200 0.30
TABLE II
750 0.75
1000 0.50
1350 3
500 0.90 TABLE I
o
F "F" 42 1500
1350 3
Temp. Factor 36 1500 1350 3
Oper. Mult. 30 1500
24 1400 1250 3
20 1300 1150 3
18 1200 1075 3
16 1100 975 3
14 1000 900 3
12 925 825 3
10 650 575 2
8 625 550 2
6 500 450 2
5 450 400 2
4 350 315 2
3 1/2 300 270 2
3 250 225 2
2 1/2 200 180 2
Pipe Roll
(a) (b) (b) +/-
Size Surface Roll on
Pipe On Flat On Pipe (inches)
MAXIMUM LOAD Max. Axial
RATING (LBS) Travel
With load distribution
plate w/ext. InsulationMODEL A6000 Insulated Pipe Support
A6
Features:
· Compact
· Easy Installation
· Eliminates welding to pipe
· Copper tubing sizes available
· Overlapping galvanized sheet metal jacket
· Minimizes heat-loss and/or condensation
· Load distribution plate integral with bottom
jacket
· Calcium silicate insulation extends 1'' beyond
the galvanized sheet metal jacket providing
for an easier vapor barrier joint with the pipe
· Other I.D.'s and/or O.D.'s available on request
Performance Test Results on File:
Available upon request.
·
·
·
·
·
·
Material Data:
A6000: Applicable PSI spec. doc.: No. 205.
Insulation: Calcium Silicate asbestos-free,
treated with water repellant.
Jackets: Galvanized Steel ASTMA-527.
Load distribution Plate: Carbon steel
ASTM A-36
Coating: Primer coated or hot-dip galvanized.
Other coatings available upon request.
Glue: Industrial contact adhesive
Formal Submittal Sheets available
Application:
Model A6000 is designed for use on:
· Cold Water
· Chilled Water
Intended for installation on:
· Flat Surfaces · Pipe Rolls
Note: Up to 1700°F available upon request.
Temperature Range: °F to +1200°F+40
FRONEK GROUP
CATALOG PS-2004
A B C
9 6 1/4
9 6 1/4
9 6 1/4
9 6 1/4
9 6 1/4
9 6 1/4
9 6 1/4
9 6 1/4
12 9 3/8
12 9 3/8
12 9 1/2
12 9 1/2
12 9 1/2
12 9 3/4
12 9 3/4
12 9 3/4
12 9 3/4
Hardware sold separately
MAXIMUM LOAD Max. Axial
RATING (LBS) Travel
Pipe On Flat On Pipe (inches)
Size Surface Roll on
Pipe Roll
(a) (b) (b) +/-
2 1/2 200 180 2
3 250 225 2
3 1/2 300 270 2
4 350 315 2
5 450 400 2
6 500 450 2
8 625 550 2
10 650 575 2
12 925 825 3
14 1000 900 3
16 1100 975 3
18 1200 1075 3
1250 3
20 1300 1150 3
30 1500
24 1400
1350 3
Temp. Factor 36 1500 1350 3
Oper. Mult.
1350 3
500 0.90 TABLE I
o
F "F" 42 1500
750 0.75
1000 0.50 Contact factory for other dimensions, temperatures, and loads. Available
in all insulation thicknesses.1200 0.30
TABLE II
Note: For higher load ratings, see A7000
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing
variations. Dimensions and ratings are subject to change without notice. Contact factory for current information.
To develop maximum load rating, width of support surface should be at least 1/2 of dimension "B" in Table I.
To obtain load ratings for operating temperatures of 500o
F and higher, multiply maximum load rating by factor "F" in Table II.
A7
MODEL A7000 Insulated Pipe Support
Heavy Duty with
load bearing plate
Features:
· Compact
· Easy Installation
· Eliminates welding to pipe
· Copper tubing sizes available
· Minimizes heat-loss and/or condensation
· Insulating structural inserts for load transfer
· Overlapping galvanized sheet metal jacket
· Other I.D.'s and/or O.D.'s available on request
· Load distribution plate integral with bottom
jacket
Performance Test Results on File:
Available upon request.
Material Data:
· A7000: Applicable PSI spec. doc.: No. 205.
· Insulation: Calcium Silicate asbestos-free,
treated with water repellant.
· Jackets: Galvanized Steel ASTM A-527.
· Structural Inserts: High-density calcium
silicate asbestos-free, treated with water
· Load Distribution Plate: Carbon steel ASTM
A-36
· Coating: Primer coated or hot-dip galvanized.
Other coatings available upon request.
· Glue: Industrial contact adhesive.
Formal Submittal Sheets available
repellant.
Application:
Model A7000 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam · Air
· Dual Temperature · Chilled Water
Intended for installation on:
· Flat Surfaces
· Pipe rolls, see A8200
· Clevis hangers, see A9000
Note: Up to 1700°F available upon request.
Temperature Range: °F to +1200°F+40
FRONEK GROUP
CATALOG PS-2004
A B C
6 3 1/4
6 3 1/4
6 3 1/4
6 3 1/4
6 3 1/4
6 3 1/4
6 3 1/4
9 6 3/8
9 6 3/8
9 6 3/8
9 6 1/2
9 6 1/2
9 6 1/2
9 6 3/4
9 6 3/4
9 6 3/4
9 6 3/4
Surface
350
Pipe (LBS)
(a)
3
TABLE I
MAXIMUM
LOAD RTG.
2 1/2 250
300
1850
8
3 1/2
2500
6
4
5
2000
400
10
12
14 1650
500
16
18
20
24
2500
2500
30
36
On FlatSize
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal
manufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information.
550
700
875
1600
42
2100
2300
To develop maximum load rating, width of support surface should be at least 1/2 of dimension "B" in Table I.
Contact factory for other dimensions,
temperatures, and loads. Available in all
insulation thicknesses.
Note: For higher load ratings, see A7200
A8
MODEL A7200 Insulated Pipe Support
Heavy Duty with
load bearing plate
Features:
· Compact
· Easy Installation
· Eliminates welding to pipe
· Copper tubing sizes available
· Minimizes heat-loss and/or condensation
· Insulating structural inserts for load transfer
· Overlapping galvanized sheet metal jacket
· Other I.D.'s and/or O.D.'s available on
request
· Load distribution plate integral with bottom
jacket
Performance Test Results on File:
Available upon request
Material Data:
· A7200: Applicable PSI spec. doc.: No. 205.
· Insulation: Calcium Silicate asbestos-free,
treated with water repellant.
· Jackets: Galvanized Steel ASTM A-527.
· Structural Inserts: High-density calcium
silicate asbestos-free, treated with water
· Load distribution Plate: Carbon steel ASTM
A-36
· Coating: Primer coated or hot-dip galvanized.
Other coatings available upon request.
· Glue: Industrial contact adhesive.
Formal Submittal Sheets available
repellant.
Application:
Model A7200 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam · Air
· Chilled Water
· Dual Temperature
Intended for installation on:
· Flat Surfaces
· Pipe rolls, see A8200
· Clevis hangers, see A9000
Note: Up to 1700°F available upon request.
Temperature Range: °F to +1200°F+40
FRONEK GROUP
CATALOG PS-2004
A B C
9 6 1/2
9 6 1/2
9 6 5/8
9 6 5/8
9 6 5/8
9 6 3/4
9 6 3/4
9 6 3/4
9 6 1
9 6 1
9 6 1
9 6 1
MAXIMUM
LOAD RTG.
Pipe (LBS)
Size On Flat
Surface
(a)
6 1000
8 1250
10 1550
12 2250
14 2780
16 3300
18 3600
20 3800
24 4100
30 4500
Contact factory for other dimensions,
temperatures, and loads. Available in all
insulation thicknesses.
TABLE I
36 4500
42 4500
Note: For higher load ratings, see A7400, B1100
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal
manufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information.
To develop maximum load rating, width of support surface should be at least 1/2 of dimension "B" in Table I.
A9
MODEL A7400 Insulated Pipe Support
Heavy Duty with
load bearing plate
·
Features:
Compact
· Easy Installation
· Eliminates welding to pipe
· Copper tubing sizes available
· Minimizes heat-loss and/or condensation
· Insulating structural inserts for load transfer
· Overlapping galvanized sheet metal jacket
· Other I.D.'s and/or O.D.'s available on
request
· Load distribution plate integral with bottom
jacket
Performance Test Results on File:
Available upon request.
Material Data:
· A7400: Applicable PSI spec. doc.: No. 205.
· Insulation: Calcium Silicate asbestos-free,
treated with water repellant.
· Jackets: Galvanized Steel ASTM A-527.
· Structural Inserts: High-density calcium
silicate asbestos-free, treated with water
· Load distribution Plate: Carbon steel ASTM
A-36
· Coating: Primer coated or hot-dip galvanized.
Other coatings available upon request.
· Glue: Industrial contact adhesive
Formal Submittal Sheets available
repellant.
Application:
Model A7400 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam · Air
· Chilled Water
· Dual Temperature
Intended for installation on:
· Flat Surfaces
· Pipe rolls, see A8400
· Clevis hangers, see A9000
Note: Up to 1700°F available upon request.
Temperature Range: °F to +1200°F+40
FRONEK GROUP
CATALOG PS-2004
A B C
9 6 3/4
9 6 3/4
9 6 3/4
9 6 1
9 6 1
9 6 1
9 6 1
9 6 1
MAXIMUM
LOAD RTG.
Pipe (LBS)
Size On Flat
Surface
(a)
10 2100
12 3400
14 3900
16 4400
18 4800
20 5100
24 5500
30 5500
Table I
Contact factory for other dimensions,
temperatures, and loads. Available in all
insulation thicknesses.
Note: For higher load ratings, see B1200
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal
manufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information.
To develop maximum load rating, width of support surface should be at least 1/2 of dimension "B" in Table I.
A10
MODEL A8000 Insulated Pipe Support
Heavy Duty with
load bearing plate
Features:
· Compact
· Easy Installation
· Eliminates welding to pipe
· Copper tubing sizes available
· Minimizes heat-loss and/or condensation
· Insulating structural inserts for load transfer
· Overlapping galvanized sheet metal jacket
· Other I.D.'s and/or O.D.'s available on request
· Load distribution plate integral with bottom
jacket
Performance Test Results on File:
Available upon request.
Material Data:
· A8000: Applicable PSI spec. doc. No. 205.
· Insulation: Calcium Silicate asbestos-free,
treated with water repellant.
· Jackets: Galvanized Steel ASTM A-527.
· Structural Inserts: High-density calcium
silicate asbestos-free, treated with water
repellant.
· Load Distribution Plate: Carbon steel ASTM
A-36
· Coating: Primer coated or hot-dip galvanized.
Other coatings available upon request.
· Glue: Industrial contact adhesive.
Formal Submittal Sheets available
Application:
Model A8000 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam · Air
· Chilled Water
· Dual Temperature
Intended for installation on:
· Flat Surfaces
· Pipe rolls, see A7000
· Clevis hangers, see A9000
Note: Up to 1700°F available upon request.
Temperature Range: °F to +1200°F+40
FRONEK GROUP
CATALOG PS-2004
A B C
9 6 1/4
9 6 1/4
9 6 1/4
9 6 1/4
9 6 1/4
9 6 1/4
9 6 1/4
12 9 3/8
12 9 3/8
12 9 3/8
12 9 1/2
12 9 1/2
12 9 1/2
12 9 3/4
12 9 3/4
12 9 3/4
12 9 3/4
Hardware sold separately
MAXIMUM Max. Axial
LOAD RTG. Travel
Pipe (LBS) (Inches)
Size On on
Pipe Pipe Roll
Roll
2 1/2 225 2
3 250 2
3 1/2 300 2
4 350 2
5 450 2
6 500 2
8 625 2
10 875 4
12 1400 4
14 1475 4
16 1650 4
18 1800 4
20 1875 4
24 2050 4
4
36 2250 4
30 2250
4
TABLE I
42 2250
Contact factory for other dimensions, temperatures, and
loads. Available in all insulation thicknesses.
Note: For higher load ratings, see A8200
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal
manufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information.
A11
MODEL A8200 Insulated Pipe Support
Heavy Duty with
load bearing plate
Features:
· Compact
· Easy Installation
· Eliminates welding to pipe
· Copper tubing sizes available
· Minimizes heat-loss and/or condensation
· Insulating structural inserts for load transfer
· Overlapping galvanized sheet metal jacket
· Other I.D.'s and/or O.D.'s available on request
· Load distribution plate integral with bottom
jacket
Performance Test Results on File:
Available upon request.
Material Data:
· A8200: Applicable PSI spec. doc.: No. 205.
· Insulation: Calcium Silicate asbestos-free,
treated with water repellant.
· Jackets: Galvanized Steel ASTM A-527.
· Structural Inserts: High-density calcium
silicate asbestos-free, treated with water
repellant.
· Load distribution Plate: Carbon steel ASTM
A-36
· Coating: Primer coated or hot-dip galvanized.
Other coatings available upon request.
· Glue: Industrial contact adhesive.
Formal Submittal Sheets available
Application:
Model A8200 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam · Air
· Chilled Water
· Dual Temperature
Intended for installation on:
· Pipe rolls
· Flat surface, see A7200
· Clevis hangers, see A9000
Note: Up to 1700°F available upon request.
Temperature Range: °F to +1200°F+40
FRONEK GROUP
CATALOG PS-2004
A B C
12 9 1/2
12 9 1/2
12 9 5/8
12 9 5/8
12 9 5/8
12 9 3/4
12 9 3/4
12 9 3/4
12 9 1
12 9 1
12 9 1
12 9 1
Hardware sold separately
Note: For higher load ratings, see A8400, B1100
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal
manufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information.
TABLE I
Contact factory for other dimensions, temperatures, and
loads. Available in all insulation thicknesses.
36 4050 3
42 4050 3
24 3675 3
30 4050 3
18 3200 3
20 3375 3
14 2650 3
16 2950 3
10 1375 3
12 2550 3
6 900 3
8 1125 3
Pipe Pipe Roll
Roll
Pipe (LBS) (Inches)
Size On on
MAXIMUM Max. Axial
LOAD RTG. Travel
A12
MODEL A8400 Insulated Pipe Support
Heavy Duty with
load bearing plate
Features:
· Compact
· Easy Installation
· Eliminates welding to pipe
· Copper tubing sizes available
· Minimizes heat-loss and/or condensation
· Insulating structural inserts for load transfer
· Overlapping galvanized sheet metal jacket
· Other I.D.'s and/or O.D.'s Available on
request
· Load distribution plate integral with bottom
jacket
Performance Test Results on File:
Available upon request.
Material Data:
· A8400: Applicable PSI spec. doc.: No. 205.
· Insulation: Calcium Silicate asbestos-free,
treated with water repellant.
· Jackets: Galvanized Steel ASTM A-527.
· Structural Inserts: High-density calcium
silicate asbestos-free, treated with water
· Load distribution Plate: Carbon steel ASTM
A-36
· Coating: Primer coated or hot-dip galvanized.
Other coatings Available upon request.
· Glue: Industrial contact adhesive.
Formal Submittal Sheets available
repellant.
Application:
Model A8400 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam · Air
· Chilled Water
· Dual Temperature
Intended for installation on:
· Pipe rolls
· Flat surface, see A7400
· Clevis hangers, see A9000
Note: Up to 1700°F available upon request.
Temperature Range: °F to +1200°F+40
FRONEK GROUP
CATALOG PS-2004
A B C
12 9 1
12 9 1
12 9 1
12 9 1
12 9 1
12 9 1
12 9 1
12 9 1
Hardware sold separately
MAXIMUM Max. Axial
LOAD RTG. Travel
Pipe (LBS) (Inches)
Size On on
Pipe Pipe Roll
Roll
10 1875 2 1/4
12 3400 2 1/4
14 3500 2 1/4
16 3950 2 1/4
18 4300 2 1/4
20 4550 2 1/4
24 4950 2 1/4
30 5450 2 1/4
TABLE I
Contact factory for other dimensions,
temperatures, and loads. Available in all
insulation thicknesses.
Note: For higher load ratings, see B1200
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal
manufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information.
A13
MODEL A9000 Insulated Pipe Support Heavy Duty for use
with rod hangers
Features:
· Compact
· Easy Installation
· Eliminates welding to pipe
· Overlapping galvanized sheet metal jacket
· Minimizes heat-loss and/or condensation
· Insulating structural inserts for load transfer
· Copper Tubing available
· Other I.D.'s and/or O.D.'s available on
request
Performance Test Results on File:
Available upon request.
Material Data:
· A9000: Applicable PSI spec. doc.: No. 205.
· Insulation: Calcium Silicate asbestos-free,
treated with water repellant.
· Jackets: Galvanized Steel ASTM A-527.
· Structural Inserts : High-density calcium
silicate asbestos-free, treated with water
repellant.
· Glue: Industrial contact adhesive.
Formal Submittal Sheets available
Application:
Model A9000 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam · Air
· Chilled Water
· Dual Temperature
Intended for installation on:
· Band, ring or clevis pipe hangers
· Flat surfaces, see A7000
· Pipe rolls, see A8000
Note: Up to 1700°F available upon request.
Temperature Range: °F to +1200°F+40
FRONEK GROUP
CATALOG PS-2004
Hardware sold separately
A B A B A B A B A B A B A B A B A B
4 24 4 24 4 24 4 24 4 24 4 24 6 24 6 24 6 24
6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24
6 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20
6 20 6 20 6 20 6 20 9 20 9 20 9 20
6 20 6 20 6 20 6 20 9 16 9 16 9 16
9 16 9 16 9 16 9 16 9 16 9 16
12 16 12 16 12 16 12 16 12 16 12 16
18 16 18 16 18 16 18 16 18 16 18 1620 - 24
TABLE II "B" = gauge of sheet metal jacket (bottom jacket approx. 2 X ga. of top jacket)
8 - 10 8 1/8 -10 1/8
12 - 18 12 1/8
5 5 1/8
6 - 7 6 1/8
5/8-1 5/8
2 2 1/8
2 1/2 - 4 2 5/8 - 4 1/8
1/2 3/4 1
1/2 - 1 1/2
3 1/2 4 Tubing
Size Size O.D.
1 1/2 2 2 1/2 3Pipe
TABLE I
Iron Insulation Thickness Copper
Contact factory for other dimensions,
temperatures, loads.
Available in all insulation thicknesses.
To develop maximum load rating use band, ring or clevis hanger with manufacturer's load
rating equal to or greater than values shown in Table I.
20 2400
24 2750
Note: For higher load ratings, see D1000, D3000
The load ratings represent average values obtained in accordance with accepted methods
and are subject to normal manufacturing variations. Dimensions and ratings are subject to
change without notice.
6 600
8 900
16
18
1200
1450
4 400
5 550
3 300
3 1/2 350
2 175
2 1/2 250
1 1/4 100
1 1/2 130
1/2 50
55
80
3/4
1
or Clevis
Hanger
(a)
Size
MAXIMUM
(LBS)
In RingPipe
LOAD RTG.
1650
1900
2150
10
12
14
FRONEK GROUP
INTRODUCTION SECTION “B”
INTRODUCTION
SECTION “B”
PRE-INSULATED PIPE SUPPORTS - Base Mounted
APPLICATION – Heavy Industrial and Large HVAC Distribution Systems
Features:
· Accommodation of thermal movement
· Provision or lateral guide or restraint
· Minimization of side friction loads
· Wide range of maximum load requirements for each pipe size
In each model number series (for example: B1000 through B1300 Series), the higher the model
number, the higher the load rating.
Models B1000 - B1300 Sliding supports free to travel axially and laterally.
Models B2000 - B2300 Same as B1000 - B1300 except can accommodate greater axial travel.
Models B3000 - B3300 Sliding supports with lateral guides.
Models B4000 - B4300 Same as B3000 - B3300 except can accommodate greater axial travel.
Models B5000 - B5300 Same as B1000 - B1300 except can accommodate greater lateral travel.
Models B6000 - B6300 Same as B2000 - B2300 except can accommodate greater lateral travel.
Models B7000 - B7300 Same as B3000 - B3300 except with reduced vertical load ratings to
allow greater lateral loads. Minimum side friction is assured by the
addition of lateral slide pads.
Models B8000 - B8300 Same as B4000 - B4300 except with reduced vertical load ratings to
allow greater lateral loads. Minimum side friction is assured by the
addition of lateral slide pads.
To meet special thermal movement requirements, Pipe Shields Inc. has provided supports that have
accommodated axial travels in excess of five (5) feet. By modifying our standard pipe support concept
with combinations of structural insulation materials, steel base and strap design, and slide plate
configuration, we can readily and economically respond to virtually any pipe support requirement.
If your requirements are not covered by the Product Data Sheets in this catalog, please contact us at
713-731-0030 or 1-800-787-5914.
Please acquaint yourself with the selection guide at the front of this catalog and the section
index on the page following this introduction, for assistance in determining the most
appropriate support for your application.
FRONEK GROUP
CATALOG PS-2004
PIPE
SIZE LATERAL
MODEL RANGE AXIAL LATERAL GUIDE DUTY
B1000 1/2 - 42 1.5 1.5 NO MEDIUM
B1100 1/2 - 42 1.5 1.5 NO HEAVY
B1200 1/2 - 42 1.5 1.5 NO HEAVIER
B1300 1/2 - 42 1.5 1.5 NO HEAVIEST
B2000 1/2 - 42 4.5 1.5 NO MEDIUM
B2100 1/2 - 42 4.5 1.5 NO HEAVY
B2200 1/2 - 42 4.5 1.5 NO HEAVIER
B2300 1/2 - 42 4.5 1.5 NO HEAVIEST
B3000 1/2 - 42 1.5 0 YES MEDIUM
B3100 1/2 - 42 1.5 0 YES HEAVY
B3200 1/2 - 42 1.5 0 YES HEAVIER
B3300 1/2 - 42 1.5 0 YES HEAVIEST
B4000 1/2 - 42 4.5 0 YES MEDIUM
B4100 1/2 - 42 4.5 0 YES HEAVY
B4200 1/2 - 42 4.5 0 YES HEAVIER
B4300 1/2 - 42 4.5 0 YES HEAVIEST
PRE-INSULATED PIPE SUPPORTS
HEAVY INDUSTRIAL - BASE MOUNTED
TRAVEL
(INCHES) +/-
SECTION “B” INDEX
FRONEK GROUP
CATALOG PS-2004
PIPE
SIZE LATERAL
MODEL RANGE AXIAL LATERAL GUIDE DUTY
B5000 1/2 - 42 1.5 1.5 - 4.5 NO MEDIUM
B5100 1/2 - 42 1.5 1.5 - 4.5 NO HEAVY
B5200 1/2 - 42 1.5 1.5 - 4.5 NO HEAVIER
B5300 1/2 - 42 1.5 1.5 - 4.5 NO HEAVIEST
B6000 1/2 - 42 4.5 1.5 - 4.5 NO MEDIUM
B6100 1/2 - 42 4.5 1.5 - 4.5 NO HEAVY
B6200 1/2 - 42 4.5 1.5 - 4.5 NO HEAVIER
B6300 1/2 - 42 4.5 1.5 - 4.5 NO HEAVIEST
B7000 1/2 - 42 1.5 0 W/SLIDE PADS MEDIUM
B7100 1/2 - 42 1.5 0 W/SLIDE PADS HEAVY
B7200 1/2 - 42 1.5 0 W/SLIDE PADS HEAVIER
B7300 1/2 - 42 1.5 0 W/SLIDE PADS HEAVIEST
B8000 1/2 - 42 4.5 0 W/SLIDE PADS MEDIUM
B8100 1/2 - 42 4.5 0 W/SLIDE PADS HEAVY
B8200 1/2 - 42 4.5 0 W/SLIDE PADS HEAVIER
B8300 1/2 - 42 4.5 0 W/SLIDE PADS HEAVIEST
PRE-INSULATED PIPE SUPPORTS
HEAVY INDUSTRIAL - BASE MOUNTED
TRAVEL
(INCHES) +/-
SECTION “B” INDEX
FRONEK GROUP
CATALOG PS-2004
SECTION “B” INDEX
TO ORDER, specify:
1. Quantity 20
2. Pipe Size & Type 18” IPS
3. Insulation Thickness 2”
4. Model Number B1000
EXAMPLE: (20) 18 x 2 B1000
FRONEK GROUP
CATALOG PS-2004
PIPE
SIZE 3 1/2 4 1/2 5 1/2 6 1/2
3 6 6 8 8
3 1/2 6 6 8 8
4 6 6 8 8
5 6 6 8 8
6 6 6 8 8
8 6 8 8 10
10 6 8 8 10
12 6 8 8 10
14 6 8 8 10
16 6 8 8 10
18 6 8 8 10
20 6 8 8 10
24 6 8 8 10
30 8 8 10 10
36 8 8 10 10
42 8 8 10 10
The Table above provides Bottom-of-Pipe to Top-of Steel dimensions ("B" dimensions) for
3 1/2", 4 1/2", 5 1/2" and 6 1/2 " insulation thicknesses. Check with your salesperson if you
require a "B" dimension other than those shown in this table.
INSULATION THICKNESS
THE FOLLOWING TABLE ILLUSTRATES
BOTTOM-OF-PIPE TO TOP-OF STEEL DIMENSIONS
(DIMENSION "B") FOR "B" MODEL PIPE SUPPORTS AND "C" MODEL PIPE ANCHORS
FOR INTERMEDIATE INSULATION THICKNESS
B1
Application:
Model B1000 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam · Air
· Dual Temperature · Chilled Water
Intended for installation on:
· Flat Surfaces
Temperature Range: +40°F to +1200°F
Note: Up to 1700° F available upon request.
Features:
· All pipe sizes
· Easy Installation
· Eliminates welding to pipe
· Overlapping galvanized sheet metal jacket
· Insulating structural inserts for load transfer
· Stainless steel to UHMW polyethylene slide
· Other I.D.'s and/or O.D.'s available on request
· Factory mounted polyethylene slide pad on steel
mounting plate
Performance Test Results on File:
Available upon request.
Material Data:
· B1000: Applicable PSI spec. doc.: No. 209.
· Insulation: Calcium Silicate asbestos-free, treated
with water repellant.
· Jackets: Galvanized Steel ASTMA-527.
· Glue: Industrial contact adhesive
· Structural Inserts: High-density calcium silicate
asbestos free, treated with water repellant.
· Steel Straps/Base: Carbon Steel ASTM A-36.
· Fasteners: ASTM A-307 plated.
· Slide Pad: UHMW Polythylene (Teflon Optional).
· Coating: Primer coated or hot dipped galvanized.
Other coatings available upon request.
Formal Submittal Sheets available.
Heavy Duty,
Base MountedMODEL B1000 Sliding Insulated Pipe Support
FRONEK GROUP
CATALOG PS-2004
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.
Note: For higher load ratings, see: B1100 - For greater axial travel, see: B2000 - For lateral restraint, see: B3000 - For lateral travel, see: B5000
Pipe Vert.
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 140 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
3/4 175 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
1 225 4 2 3.875 4 2.5 4.875 4 3 5.937 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 1/2 325 4 2 4.375 4 2.5 5.5 4 4 7 4 4.5 8 6 5.5 9 6 7.5 11.25 8 9 13.25
2 375 4 2.5 5 4 3 6.0625 4 4 7 4 4.5 8 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 460 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5
3 530 4 3 6.062 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 840 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 1050 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 4 7.5 11.375 6 8 12.375 6 9.5 14.875 8 11 16.875
6 1275 4 5.5 9.25 4 6.5 10.25 4 7.5 11.375 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 1700 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 17.875 8 13 20.125
10 2000 4 9 13.625 4 9.5 14.875 4 10.5 15.875 6 11 16.875 6 12 18.125 6 13 20.125 8 14.5 22.125
12 2200 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 2500 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 2900 4 12.5 19.125 4 13 20.125 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 3200 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 3400 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 3600 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 4700 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 5500 4 26.5 39.625 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 6200 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125
Contact factory for other dimensional, temperature, load, or axial travel, requirements.
Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
B2
Heavy Duty,
Base MountedMODEL B1100 Sliding Insulated Pipe Support
Application:
Model B1100 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam · Air
· Dual Temperature · Chilled Water
Intended for installation on:
· Flat Surfaces
Temperature Range: +40°F to +1200°F
Note: Up to 1700° F available upon request.
Features:
· All pipe sizes
· Easy Installation
· Eliminates welding to pipe
· Overlapping galvanized sheet metal jacket
· Insulating structural inserts for load transfer
· Stainless steel to UHMW polyethylene slide
· Other I.D.'s and/or O.D.'s available on request
· Factory mounted polyethylene slide pad on steel
mounting plate
Performance Test Results on File:
Available upon request.
Material Data:
· B1100: Applicable PSI spec. doc.: No. 209.
· Insulation: Calcium Silicate asbestos-free, treated
with water repellant.
· Jackets: Galvanized Steel ASTMA-527.
· Glue: Industrial contact adhesive
· Structural Inserts: High-density calcium silicate
asbestos free, treated with water repellant.
· Steel Straps/Base: Carbon Steel ASTM A-36.
· Fasteners: ASTM A-307 plated.
· Slide Pad: UHMW Polythylene (Teflon Optional).
· Coating: Primer coated or hot dipped galvanized.
Other coatings available upon request.
Formal Submittal Sheets available.
FRONEK GROUP
CATALOG PS-2004
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.
Note: For higher load ratings, see: B1200 - For greater axial travel, see: B2100 - For lateral restraint, see: B3100 - For lateral travel, see: B5100
Pipe Vert.
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 280 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
3/4 350 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 450 4 2 3.875 4 2.5 5 4 3 6.062 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 1/2 650 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 750 4 2.5 5 4 3 6.0625 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 920 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5
3 1060 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 1680 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 2100 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875
6 2550 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 3400 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125
10 4000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125
12 4400 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 5000 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 5800 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 6400 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 6800 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 7200 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 9400 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 11000 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 12400 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125
Contact factory for other dimensional, temperature, load, or axial travel, requirements.
Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
B3
Heavy Duty,
Base MountedMODEL B1200 Sliding Insulated Pipe Support
Application:
Model B1200 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam · Air
· Dual Temperature · Chilled Water
Intended for installation on:
· Flat Surfaces
Temperature Range: +40°F to +1200°F
Note: Up to 1700° F available upon request.
Features:
· All pipe sizes
· Easy Installation
· Eliminates welding to pipe
· Overlapping galvanized sheet metal jacket
· Insulating structural inserts for load transfer
· Stainless steel to UHMW polyethylene slide
· Other I.D.'s and/or O.D.'s available on request
· Factory mounted polyethylene slide pad on steel
mounting plate
Performance Test Results on File:
Available upon request.
Material Data:
· B1200: Applicable PSI spec. doc.: No. 209.
· Insulation: Calcium Silicate asbestos-free, treated
with water repellant.
· Jackets: Galvanized Steel ASTM A-527.
· Glue: Industrial contact adhesive
· Structural Inserts: High-density calcium silicate
asbestos free, treated with water repellant.
· Steel Straps/Base: Carbon Steel ASTM A-36.
· Fasteners: ASTM A-307 plated.
· Slide Pad: UHMW Polyethylene (Teflon Optional).
· Coating: Primer coated or hot dipped galvanized.
Other coatings available upon request.
Formal Submittal Sheets available.
FRONEK GROUP
CATALOG PS-2004
Contact factory for other dimensional, temperature, load, or axial travel, requirements.
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.
Note: For higher load ratings, see: B1300 - For greater axial travel, see: B2200 - For lateral restraint, see: B3200 - For lateral travel, see: B5200
Pipe Vert.
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 400 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
3/4 500 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 650 4 2 4 4 2.5 5 4 3 6.062 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 1/2 950 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1100 4 2.5 5 4 3 6.1875 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 1350 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5
3 1600 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 2500 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 3100 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875
6 3800 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 5100 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125
10 6000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125
12 6600 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 7500 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 8700 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 9600 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 10200 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 10800 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 14100 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 16500 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 18600 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125
Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
B4
Heavy Duty,
Base MountedMODEL B1300 Sliding Insulated Pipe Support
Application:
Model B1300 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam · Air
· Dual Temperature · Chilled Water
Intended for installation on:
· Flat Surfaces
Temperature Range: +40°F to +1200°F
Note: Up to 1700° F available upon request.
Features:
· All pipe sizes
· Easy Installation
· Eliminates welding to pipe
· Overlapping galvanized sheet metal jacket
· Insulating structural inserts for load transfer
· Stainless steel to UHMW polyethylene slide
· Other I.D.'s and/or O.D.'s available on request
· Factory mounted polyethylene slide pad on steel
mounting plate
Performance Test Results on File:
Available upon request.
Material Data:
· B1300: Applicable PSI spec. doc.: No. 209.
· Insulation: Calcium Silicate asbestos-free, treated
with water repellant.
· Jackets: Galvanized Steel ASTM A-527.
· Glue: Industrial contact adhesive
· Structural Inserts: High-density calcium silicate
asbestos free, treated with water repellant.
· Steel Straps/Base: Carbon Steel ASTM A-36.
· Fasteners: ASTM A-307 plated.
· Slide Pad: UHMW Polyethylene (Teflon Optional).
· Coating: Primer coated or hot dipped galvanized.
Other coatings available upon request.
Formal Submittal Sheets available.
FRONEK GROUP
CATALOG PS-2004
Contact factory for other dimensional, temperature, load, or axial travel, requirements.
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.
Note: For greater axial travel, see: B2300 - For lateral restraint, see: B3300 - For lateral travel, see: B5300
Pipe Vert.
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 550 4 1.5 3.375 4 2 4.5 4 2.5 5.5 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
3/4 700 4 1.5 3.375 4 2 4.5 4 2.5 5.5 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 900 4 2 4 4 2.5 5 4 3 6.062 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 1/2 1300 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1500 4 2.5 5 4 3 6.0625 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 1800 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
3 2100 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 3350 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 4200 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875
6 5100 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 6800 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125
10 8000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125
12 8800 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 10000 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 11600 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 12800 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 13600 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 14400 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 18800 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 22000 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 24800 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125
Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
B5
Heavy Duty,
Base MountedMODEL B2000 Sliding Insulated Pipe Support
Application:
Model B2000 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam · Air
· Dual Temperature · Chilled Water
Intended for installation on:
· Flat Surfaces
Temperature Range: +40°F to +1200°F
Note: Up to 1700° F available upon request.
Features:
· All pipe sizes
· Easy Installation
· Eliminates welding to pipe
· Overlapping galvanized sheet metal jacket
· Insulating structural inserts for load transfer
· Stainless steel to UHMW polyethylene slide
· Other I.D.'s and/or O.D.'s available on request
· Factory mounted polyethylene slide pad on steel
mounting plate
Performance TestResults on File:
Available upon request.
Material Data:
· B2000: Applicable PSI spec. doc.: No. 209.
· Insulation: Calcium Silicate asbestos-free, treated
with water repellant.
· Jackets: Galvanized Steel ASTM A-527.
· Glue: Industrial contact adhesive
· Structural Inserts: High-density calcium silicate
asbestos free, treated with water repellant.
· Steel Straps/Base: Carbon Steel ASTM A-36.
· Fasteners: ASTM A-307 plated.
· Slide Pad: UHMW Polyethylene (Teflon Optional).
· Coating: Primer coated or hot dipped galvanized.
Other coatings available upon request.
Formal Submittal Sheets available.
FRONEK GROUP
CATALOG PS-2004
Contact factory for other dimensional, temperature, load, or axial travel, requirements.
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.
Note: For higher load ratings, see: B2100 - For lesser axial travel, see: B1000 - For lateral restraint, see: B4000 - For lateral travel, see: B6000
Pipe Vert.
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 140 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
3/4 175 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
1 225 4 2 3.875 4 2.5 4.875 4 3 5.937 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 1/2 325 4 2 4.375 4 2.5 5.5 4 4 7 4 4.5 8 6 5.5 9 6 7.5 11.25 8 9 13.25
2 375 4 2.5 5 4 3 6.0625 4 4 7 4 4.5 8 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 460 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5
3 530 4 3 6.062 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 840 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 1050 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 4 7.5 11.375 6 8 12.375 6 9.5 14.875 8 11 16.875
6 1275 4 5.5 9.25 4 6.5 10.25 4 7.5 11.375 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 1700 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 17.875 8 13 20.125
10 2000 4 9 13.625 4 9.5 14.875 4 10.5 15.875 6 11 16.875 6 12 18.125 6 13 20.125 8 14.5 22.125
12 2200 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 2500 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 2900 4 12.5 19.125 4 13 20.125 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 3200 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 3400 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 3600 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 4700 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 5500 4 26.5 39.625 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 6200 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125
Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
B6
Heavy Duty,
Base MountedMODEL B2100 Sliding Insulated Pipe Support
Application:
Model B2100 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam ·Air
· Dual Temperature · Chilled Water
Intended for installation on:
· Flat Surfaces
Temperature Range: +40°F to +1200°F
Note: Up to 1700° F available upon request.
Features:
· All pipe sizes
· Easy Installation
· Eliminates welding to pipe
· Overlapping galvanized sheet metal jacket
· Insulating structural inserts for load transfer
· Stainless steel to UHMW polyethylene slide
· Other I.D.'s and/or O.D.'s available on request
· Factory mounted polyethylene slide pad on steel
mounting plate
Performance Test Results on File:
Available upon request.
Material Data:
· B2100: Applicable PSI spec. doc.: No. 209.
· Insulation: Calcium Silicate asbestos-free, treated
with water repellant.
· Jackets: Galvanized Steel ASTMA-527.
· Glue: Industrial contact adhesive
· Structural Inserts: High-density calcium silicate
asbestos free, treated with water repellant.
· Steel Straps/Base: Carbon Steel ASTM A-36.
· Fasteners: ASTM A-307 plated.
· Slide Pad: UHMW Polyethylene (Teflon Optional).
· Coating: Primer coated or hot dipped galvanized.
Other coatings available upon request.
Formal Submittal Sheets available.
FRONEK GROUP
CATALOG PS-2004
Contact factory for other dimensional, temperature, load, or axial travel, requirements.
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.
Note: For higher load ratings, see: B2200 - For lesser axial travel, see: B1100 - For lateral restraint, see: B4100 - For lateral travel, see: B6100
Pipe Vert.
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 280 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
3/4 350 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 450 4 2 3.875 4 2.5 5 4 3 6.062 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 1/2 650 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 750 4 2.5 5 4 3 6.0625 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 920 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5
3 1060 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 1680 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 2100 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875
6 2550 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 3400 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125
10 4000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125
12 4400 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 5000 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 5800 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 6400 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 6800 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 7200 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 9400 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 11000 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 12400 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125
Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
B7
Heavy Duty,
Base MountedMODEL B2200 Sliding Insulated Pipe Support
Application:
Model B2200 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam ·Air
· Dual Temperature · Chilled Water
Intended for installation on:
· Flat Surfaces
Temperature Range: +40°F to +1200°F
Note: Up to 1700° F available upon request.
Features:
· All pipe sizes
· Easy Installation
· Eliminates welding to pipe
· Overlapping galvanized sheet metal jacket
· Insulating structural inserts for load transfer
· Stainless steel to UHMW polyethylene slide
· Other I.D.'s and/or O.D.'s available on request
· Factory mounted polyethylene slide pad on steel
mounting plate
Performance Test Results on File:
Available upon request.
Material Data:
· B2200: Applicable PSI spec. doc.: No. 209.
· Insulation: Calcium Silicate asbestos-free, treated
with water repellant.
· Jackets: Galvanized Steel ASTMA-527.
· Glue: Industrial contact adhesive
· Structural Inserts: High-density calcium silicate
asbestos free, treated with water repellant.
· Steel Straps/Base: Carbon Steel ASTM A-36.
· Fasteners: ASTM A-307 plated.
· Slide Pad: UHMW Polyethylene (Teflon Optional).
· Coating: Primer coated or hot dipped galvanized.
Other coatings available upon request.
Formal Submittal Sheets available.
FRONEK GROUP
CATALOG PS-2004
Contact factory for other dimensional, temperature, load, or axial travel, requirements.
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.
Note: For higher load ratings, see: B2300 - For lesser axial travel, see: B1200 - For lateral restraint, see: B4200 - For lateral travel, see: B6200
Pipe Vert.
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 400 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125
3/4 500 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25
1 650 4 2 4 4 2.5 5 4 3 6.062 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 1/2 950 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1100 4 2.5 5 4 3 6.1875 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 1350 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5
3 1600 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 2500 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 3100 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875
6 3800 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 5100 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125
10 6000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125
12 6600 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 7500 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 8700 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 9600 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 10200 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 10800 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 14100 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 16500 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 18600 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125
Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
B8
Heavy Duty,
Base MountedMODEL B2300 Sliding Insulated Pipe Support
Application:
Model B2300 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam · Air
· Dual Temperature · Chilled Water
Intended for installation on:
· Flat Surfaces
Temperature Range: +40°F to +1200°F
Note: Up to 1700° F available upon request.
Features:
· All pipe sizes
· Easy Installation
· Eliminates welding to pipe
· Overlapping galvanized sheet metal jacket
· Insulating structural inserts for load transfer
· Stainless steel to UHMW polyethylene slide
· Other I.D.'s and/or O.D.'s available on request
· Factory mounted polyethylene slide pad on steel
mounting plate
Performance Test Results on File:
Available upon request.
Material Data:
· B2300: Applicable PSI spec. doc.: No. 209.
· Insulation: Calcium Silicate asbestos-free, treated
with water repellant.
· Jackets: Galvanized Steel ASTM A-527.
· Glue: Industrial contact adhesive
· Structural Inserts: High-density calcium silicate
asbestos free, treated with water repellant.
· Steel Straps/Base: Carbon Steel ASTM A-36.
· Fasteners: ASTM A-307 plated.
· Slide Pad: UHMW Polyethylene (Teflon Optional).
· Coating: Primer coated or hot dipped galvanized.
Other coatings available upon request.
Formal Submittal Sheets available.
FRONEK GROUP
CATALOG PS-2004
Contact factory for other dimensional, temperature, load, or axial travel, requirements.
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.
Note: For lesser axial travel, see: B1300 - For lateral restraint, see: B4300 - For lateral travel, see: B6300
Pipe Vert.
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 550 4 1.5 3.375 4 2 4.5 4 2.5 5.5 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
3/4 700 4 1.5 3.375 4 2 4.5 4 2.5 5.5 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 900 4 2 4 4 2.5 5 4 3 6.062 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25
1 1/2 1300 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1500 4 2.5 5 4 3 6.0625 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25
2 1/2 1800 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
3 2100 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625
4 3350 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625
5 4200 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875
6 5100 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875
8 6800 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125
10 8000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125
12 8800 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125
14 10000 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125
16 11600 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375
18 12800 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375
20 13600 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375
24 14400 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375
30 18800 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625
36 22000 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125
42 24800 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125
Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
B9
Heavy Duty,
Base MountedMODEL B3000 Guided Insulated Pipe Support
Application:
Model B3000 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam · Air
· Dual Temperature · Chilled Water
Intended for installation on:
· Flat Surfaces
Temperature Range: +40°F to +1200°F
Note: Up to 1700° F available upon request.
Features:
· All pipe sizes
· Easy Installation
· Eliminates welding to pipe
· Overlapping galvanized sheet metal jacket
· Insulating structural inserts for load transfer
· Stainless steel to UHMW polyethylene slide
· Other I.D.'s and/or O.D.'s available on request
· Factory mounted polyethylene slide pad on steel
mounting plate
Performance Test Results on File:
Available upon request.
Material Data:
· B3000: Applicable PSI spec. doc.: No. 209.
· Insulation: Calcium Silicate asbestos-free, treated
with water repellant.
· Jackets: Galvanized Steel ASTM A-527.
· Glue: Industrial contact adhesive
· Structural Inserts: High-density calcium silicate
asbestos free, treated with water repellant.
· Steel Straps/Base: Carbon Steel ASTM A-36.
· Fasteners: ASTM A-307 plated.
· Slide Pad: UHMW Polyethylene (Teflon Optional).
· Coating: Primer coated or hot dipped galvanized.
Other coatings available upon request.
Formal Submittal Sheets available.
FRONEK GROUP
CATALOG PS-2004
Contact factory for other dimensional, temperature, load, or axial travel, requirements. If lateral load is greater than 20% of vertical load, contact factory.
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.
Note: For higher load ratings, see: B3100 - For greater axial travel, see: B4000 - For lateral travel, see: B5000
Pipe Vert.
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 140 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.125
3/4 175 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.125
1 225 4 6.5 3.875 4 7 4.875 4 7.5 5.937 4 8.5 7 6 9 8 6 11 10 8 12.5 12.25
1 1/2 325 4 6.5 4.375 4 7 5.5 4 8.5 7 4 9 8 6 10 9 6 12 11.25 8 13.5 13.25
2 375 4 7 5 4 7.5 6.0625 4 8.5 7 4 9 8 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1/2 460 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.25 8 14 14.5
3 530 4 7.5 6.062 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
4 840 4 8.5 7.25 4 9 8.25 4 10 9.25 4 11 10.25 6 12 11.375 6 13.5 13.375 8 15 15.625
5 1050 4 10 8.25 4 11 9.25 4 12 10.25 4 13 11.375 6 13.5 12.375 6 15 14.875 8 16.5 16.875
6 1275 4 11 9.25 4 12 10.25 4 13 11.375 4 13.5 12.625 6 14.5 13.625 6 16 15.875 8 17.5 17.875
8 1700 4 13.5 11.625 4 14 12.625 4 15 13.625 6 15.5 14.875 6 16.5 15.875 6 18 17.875 8 19 20.125
10 2000 4 15 13.625 4 15.5 14.875 4 16.5 15.875 6 17 16.875 6 18 18.125 6 19 20.125 8 20.5 22.125
12 2200 4 17 16.125 4 17.5 17.125 4 18.5 18.125 6 19 19.125 6 19.5 20.125 6 21 22.125 8 22.5 24.125
14 2500 4 17.5 17.125 4 18.5 18.125 4 19 19.125 6 19.5 20.125 6 20.5 21.125 6 22 23.125 8 23 25.125
16 2900 4 20.5 19.125 4 21 20.125 6 22 21.375 6 22.5 22.375 6 23.5 23.375 8 24.5 25.375 8 26 27.375
18 3200 4 22 21.375 4 22.5 22.375 6 23.5 23.375 6 24 24.375 6 24.5 25.375 8 26 27.375 8 27.5 29.375
20 3400 4 23.5 23.375 4 24 24.375 6 24.5 25.375 6 25.5 26.375 6 26 27.375 8 27.5 29.375 8 29 31.375
24 3600 4 26 27.375 4 27 28.375 6 27.5 29.375 6 28.5 30.375 6 29 31.375 8 30.5 33.375 8 32 35.375
30 4700 4 32.5 33.625 6 33 34.625 6 34 35.625 6 34.5 36.625 6 35 37.625 8 36.5 39.625 8 38 41.625
36 5500 4 36.5 39.625 6 37.5 41.125 6 38 42.125 6 38.5 43.125 6 39.5 44.125 8 41 46.125 8 42.5 48.125
42 6200 4 41 46.125 6 41.5 47.125 6 42.5 48.125 6 43 49.125 6 43.5 50.125 8 45 52.125 8 46.5 54.125
Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
B10
Heavy Duty,
Base MountedMODEL B3100 Guided Insulated Pipe Support
Application:
Model B3100 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam · Air
· Dual Temperature · Chilled Water
Intended for installation on:
· Flat Surfaces
Temperature Range: +40°F to +1200°F
Note: Up to 1700° F available upon request.
Features:
· All pipe sizes
· Easy Installation
· Eliminates welding to pipe
· Overlapping galvanized sheet metal jacket
· Insulating structural inserts for load transfer
· Stainless steel to UHMW polyethylene slide
· Other I.D.'s and/or O.D.'s available on request
· Factory mounted polyethylene slide pad on steel
mounting plate
Performance Test Results on File:
Available upon request.
Material Data:
· B3100: Applicable PSI spec. doc.: No. 209.
· Insulation: Calcium Silicate asbestos-free, treated
with water repellant.
· Jackets: Galvanized Steel ASTM A-527.
· Glue: Industrial contact adhesive
· Structural Inserts: High-density calcium silicate
asbestos free, treated with water repellant.
· Steel Straps/Base: Carbon Steel ASTM A-36.
· Fasteners: ASTM A-307 plated.
· Slide Pad: UHMW Polyethylene (Teflon Optional).
· Coating: Primer coated or hot dipped galvanized.
Other coatings available upon request.
Formal Submittal Sheets available.
FRONEK GROUP
CATALOG PS-2004
Contact factory for other dimensional, temperature, load, or axial travel, requirements. If lateral load is greater than 20% of vertical load, contact factory.
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.
Note: For higher load ratings, see: B3200 - For greater axial travel, see: B4100 - For lateral travel, see: B5100
Pipe Vert.
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 280 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.125
3/4 350 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.25
1 450 4 6.5 3.875 4 7 5 4 7.5 6.062 4 8.5 7 6 9 8 6 11 10 8 12.5 12.25
1 1/2 650 4 6.5 4.5 4 7 5.5 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 750 4 7 5 4 7.5 6.0625 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1/2 920 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.25 8 14 14.5
3 1060 4 7.5 6.187 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
4 1680 4 8.5 7.25 4 9 8.25 4 10 9.25 4 11 10.25 6 12 11.375 6 13.5 13.375 8 15 15.625
5 2100 4 10 8.5 4 11 9.5 4 12 10.5 4 13 11.625 6 13.5 12.625 6 15 14.875 8 16.5 16.875
6 2550 4 11 9.5 4 12 10.5 4 13 11.625 4 13.5 12.625 6 14.5 13.625 6 16 15.875 8 17.5 17.875
8 3400 4 13.5 11.625 4 14 12.625 4 15 13.625 6 15.5 14.875 6 16.5 15.875 6 18 18.125 8 19 20.125
10 4000 4 15 13.875 4 15.5 15.125 4 16.5 16.125 6 17 17.125 6 18 18.125 6 19 20.125 8 20.5 22.125
12 4400 4 17 16.125 4 17.5 17.125 4 18.5 18.125 6 19 19.125 6 19.5 20.125 6 21 22.125 8 22.5 24.125
14 5000 4 17.5 17.125 4 18.5 18.125 4 19 19.125 6 19.5 20.125 6 20.5 21.125 6 22 23.125 8 23 25.125
16 5800 4 20.5 19.375 4 21 20.375 6 22 21.375 6 22.5 22.375 6 23.5 23.375 8 24.5 25.375 8 26 27.375
18 6400 4 22 21.375 4 22.5 22.375 6 23.5 23.375 6 24 24.375 6 24.5 25.375 8 26 27.375 8 27.5 29.375
20 6800 4 23.5 23.375 4 24 24.375 6 24.5 25.375 6 25.5 26.375 6 26 27.375 8 27.5 29.375 8 29 31.375
24 7200 4 26 27.375 4 27 28.375 6 27.5 29.375 6 28.5 30.375 6 29 31.375 8 30.5 33.375 8 32 35.375
30 9400 4 32.5 33.625 6 33 34.625 6 34 35.625 6 34.5 36.625 6 35 37.625 8 36.5 39.625 8 38 41.625
36 11000 4 36.5 40.125 6 37.5 41.125 6 38 42.125 6 38.5 43.125 6 39.5 44.125 8 41 46.125 8 42.5 48.125
42 12400 4 41 46.125 6 41.5 47.125 6 42.5 48.125 6 43 49.125 6 43.5 50.125 8 45 52.125 8 46.5 54.125
Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
B11
Heavy Duty,
Base MountedMODEL B3200 Guided Insulated Pipe Support
Application:
Model B3200 is designed for use on:
· Hot Water · Vacuum · Gas
· Cold Water · Steam · Air
· Dual Temperature · Chilled Water
Intended for installation on:
· Flat Surfaces
Temperature Range: +40°F to +1200°F
Note: Up to 1700° F available upon request.
Features:
· All pipe sizes
· Easy Installation
· Eliminates welding to pipe
· Overlapping galvanized sheet metal jacket
· Insulating structural inserts for load transfer
· Stainless steel to UHMW polyethylene slide
· Other I.D.'s and/or O.D.'s available on request
· Factory mounted polyethylene slide pad on steel
mounting plate
Performance Test Results on File:
Available upon request.
Material Data:
· B3200: Applicable PSI spec. doc.: No. 209.
· Insulation: Calcium Silicate asbestos-free, treated
with water repellant.
· Jackets: Galvanized Steel ASTM A-527.
· Glue: Industrial contact adhesive
· Structural Inserts: High-density calcium silicate
asbestos free, treated with water repellant.
· Steel Straps/Base: Carbon Steel ASTM A-36.
· Fasteners: ASTM A-307 plated.
· Slide Pad: UHMW Polyethylene (Teflon Optional).
· Coating: Primer coated or hot dipped galvanized.
Other coatings available upon request.
Formal Submittal Sheets available.
FRONEK GROUP
CATALOG PS-2004
Contact factory for other dimensional, temperature, load, or axial travel, requirements. If lateral load is greater than 20% of vertical load, contact factory.
The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations.
Dimensions and ratings are subject to change without notice.
Note: For higher load ratings, see: B3300 - For greater axial travel, see: B4200 - For lateral travel, see: B5200
Pipe Vert.
Size Load B C E B C E B C E B C E B C E B C E B C E
1/2 400 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.125
3/4 500 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.25
1 650 4 6.5 4 4 7 5 4 7.5 6.062 4 8.5 7.125 6 9 8.125 6 11 10.125 8 12.5 12.25
1 1/2 950 4 6.5 4.5 4 7 5.5 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1100 4 7 5 4 7.5 6.1875 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25
2 1/2 1350 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.25 8 14 14.5
3 1600 4 7.5 6.187 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625
4 2500 4 8.5 7.25 4 9 8.25 4 10 9.25 4 11 10.25 6 12 11.375 6 13.5 13.375 8 15 15.625
5 3100 4 10 8.5 4 11 9.5 4 12 10.5 4 13 11.625 6 13.5 12.625 6 15 14.875 8 16.5 16.875
6 3800 4 11 9.5 4 12 10.5 4 13 11.625 4 13.5 12.625 6 14.5 13.625 6 16 15.875 8 17.5 17.875
8 5100 4 13.5 11.625 4 14 12.625 4 15 13.625 6 15.5 14.875 6 16.5 15.875 6 18 18.125 8 19 20.125
10 6000 4 15 13.875 4 15.5 15.125 4 16.5 16.125 6 17 17.125 6 18 18.125 6 19 20.125 8 20.5 22.125
12 6600 4 17 16.125 4 17.5 17.125 4 18.5 18.125 6 19 19.125 6 19.5 20.125 6 21 22.125 8 22.5 24.125
14 7500 4 17.5 17.125 4 18.5 18.125 4 19 19.125 6 19.5 20.125 6 20.5 21.125 6 22 23.125 8 23 25.125
16 8700 4 20.5 19.375 4 21 20.375 6 22 21.375 6 22.5 22.375 6 23.5 23.375 8 24.5 25.375 8 26 27.375
18 9600 4 22 21.375 4 22.5 22.375 6 23.5 23.375 6 24 24.375 6 24.5 25.375 8 26 27.375 8 27.5 29.375
20 10200 4 23.5 23.375 4 24 24.375 6 24.5 25.375 6 25.5 26.375 6 26 27.375 8 27.5 29.375 8 29 31.375
24 10800 4 26 27.375 4 27 28.375 6 27.5 29.375 6 28.5 30.375 6 29 31.375 8 30.5 33.375 8 32 35.375
30 14100 4 32.5 33.625 6 33 34.625 6 34 35.625 6 34.5 36.625 6 35 37.625 8 36.5 39.625 8 38 41.625
36 16500 4 36.5 40.125 6 37.5 41.125 6 38 42.125 6 38.5 43.125 6 39.5 44.125 8 41 46.125 8 42.5 48.125
42 18600 4 41 46.125 6 41.5 47.125 6 42.5 48.125 6 43 49.125 6 43.5 50.125 8 45 52.125 8 46.5 54.125
Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc
Pipe shields inc

More Related Content

What's hot

Energy Conservation in Compressed Air System.
Energy Conservation in Compressed Air System.Energy Conservation in Compressed Air System.
Energy Conservation in Compressed Air System.AffanDabir
 
Feedwater heaters in thermal power plants
Feedwater heaters in thermal power plantsFeedwater heaters in thermal power plants
Feedwater heaters in thermal power plantsSHIVAJI CHOUDHURY
 
Boiler & It's Types
Boiler & It's Types Boiler & It's Types
Boiler & It's Types Ihsan Wassan
 
U3 design of connecting rod-(i section, big&small eng, bolt, whipping str...
U3 design of connecting rod-(i section, big&small eng, bolt, whipping str...U3 design of connecting rod-(i section, big&small eng, bolt, whipping str...
U3 design of connecting rod-(i section, big&small eng, bolt, whipping str...karuppusamy pitchai
 
Actual vapour compression cycle
Actual vapour compression cycleActual vapour compression cycle
Actual vapour compression cyclevipul kumar sharma
 
Design of End Closure in pressure vessel
Design of End Closure in pressure vessel Design of End Closure in pressure vessel
Design of End Closure in pressure vessel Nilraj Vasandia
 
Hydraulic Power Pack and Hydraulic Symbols
Hydraulic Power Pack and Hydraulic SymbolsHydraulic Power Pack and Hydraulic Symbols
Hydraulic Power Pack and Hydraulic SymbolsMohammad Azam Khan
 
Types, Operations and Maintenance of Air Compressor Plants
Types, Operations and Maintenance of Air  Compressor PlantsTypes, Operations and Maintenance of Air  Compressor Plants
Types, Operations and Maintenance of Air Compressor PlantsNejat Öztezcan
 
Project Report on Analysis of Boiler- Aditya
Project Report on Analysis of Boiler- AdityaProject Report on Analysis of Boiler- Aditya
Project Report on Analysis of Boiler- AdityaAditya Bhattacharjee
 
Basics of Compressor
Basics of CompressorBasics of Compressor
Basics of CompressorSLA1987
 
Energy conservation in compressed air systems
Energy conservation in compressed air systemsEnergy conservation in compressed air systems
Energy conservation in compressed air systemsmohammed kazi
 
Fluid power introduction
Fluid power introductionFluid power introduction
Fluid power introductionsukusobhaa
 
High pressure boilers
High pressure boilersHigh pressure boilers
High pressure boilerssneh patel
 

What's hot (20)

Energy Conservation in Compressed Air System.
Energy Conservation in Compressed Air System.Energy Conservation in Compressed Air System.
Energy Conservation in Compressed Air System.
 
Feedwater heaters in thermal power plants
Feedwater heaters in thermal power plantsFeedwater heaters in thermal power plants
Feedwater heaters in thermal power plants
 
Boiler & It's Types
Boiler & It's Types Boiler & It's Types
Boiler & It's Types
 
Rankine cycle
Rankine cycleRankine cycle
Rankine cycle
 
Basics of fans
Basics of fansBasics of fans
Basics of fans
 
Bearings
BearingsBearings
Bearings
 
fans and blowers
fans and blowersfans and blowers
fans and blowers
 
U3 design of connecting rod-(i section, big&small eng, bolt, whipping str...
U3 design of connecting rod-(i section, big&small eng, bolt, whipping str...U3 design of connecting rod-(i section, big&small eng, bolt, whipping str...
U3 design of connecting rod-(i section, big&small eng, bolt, whipping str...
 
Actual vapour compression cycle
Actual vapour compression cycleActual vapour compression cycle
Actual vapour compression cycle
 
compressor notes.pdf
compressor notes.pdfcompressor notes.pdf
compressor notes.pdf
 
Design of End Closure in pressure vessel
Design of End Closure in pressure vessel Design of End Closure in pressure vessel
Design of End Closure in pressure vessel
 
Hydraulic Power Pack and Hydraulic Symbols
Hydraulic Power Pack and Hydraulic SymbolsHydraulic Power Pack and Hydraulic Symbols
Hydraulic Power Pack and Hydraulic Symbols
 
Types, Operations and Maintenance of Air Compressor Plants
Types, Operations and Maintenance of Air  Compressor PlantsTypes, Operations and Maintenance of Air  Compressor Plants
Types, Operations and Maintenance of Air Compressor Plants
 
Air Compressor
Air CompressorAir Compressor
Air Compressor
 
Project Report on Analysis of Boiler- Aditya
Project Report on Analysis of Boiler- AdityaProject Report on Analysis of Boiler- Aditya
Project Report on Analysis of Boiler- Aditya
 
Basics of Compressor
Basics of CompressorBasics of Compressor
Basics of Compressor
 
Gas turbine cycles
Gas turbine cyclesGas turbine cycles
Gas turbine cycles
 
Energy conservation in compressed air systems
Energy conservation in compressed air systemsEnergy conservation in compressed air systems
Energy conservation in compressed air systems
 
Fluid power introduction
Fluid power introductionFluid power introduction
Fluid power introduction
 
High pressure boilers
High pressure boilersHigh pressure boilers
High pressure boilers
 

Viewers also liked (20)

Mi vida
Mi vidaMi vida
Mi vida
 
Gr 3words,hobby,family
Gr 3words,hobby,familyGr 3words,hobby,family
Gr 3words,hobby,family
 
Quantities How to buy something
Quantities How to buy somethingQuantities How to buy something
Quantities How to buy something
 
South africa ppt
South africa pptSouth africa ppt
South africa ppt
 
Sepeakeasy D.C: Rebrand
Sepeakeasy D.C: Rebrand Sepeakeasy D.C: Rebrand
Sepeakeasy D.C: Rebrand
 
Cape town ppt
Cape town pptCape town ppt
Cape town ppt
 
Film genres
 Film genres Film genres
Film genres
 
Gambling
GamblingGambling
Gambling
 
Jobs and Occupations
Jobs and OccupationsJobs and Occupations
Jobs and Occupations
 
Counters ibrahem
Counters ibrahemCounters ibrahem
Counters ibrahem
 
Whats you favourte fruit
Whats you favourte fruitWhats you favourte fruit
Whats you favourte fruit
 
Week 6 hema 1990
Week 6   hema 1990Week 6   hema 1990
Week 6 hema 1990
 
American culture
American cultureAmerican culture
American culture
 
Mahar Mubarok CV
Mahar Mubarok CVMahar Mubarok CV
Mahar Mubarok CV
 
3.3 capacitors
3.3 capacitors3.3 capacitors
3.3 capacitors
 
Capacitors new
Capacitors newCapacitors new
Capacitors new
 
Compact Spring Supports Webinar
Compact Spring Supports WebinarCompact Spring Supports Webinar
Compact Spring Supports Webinar
 
Gr4 week1
Gr4 week1Gr4 week1
Gr4 week1
 
Pipe shields for beginners
Pipe shields for beginnersPipe shields for beginners
Pipe shields for beginners
 
Dairy farming
Dairy farmingDairy farming
Dairy farming
 

Similar to Pipe shields inc

Valvulas globo - Globe valves
Valvulas globo - Globe valvesValvulas globo - Globe valves
Valvulas globo - Globe valvesJLX Valve
 
Válvulas de mariposa - Butterfly Valves
Válvulas de mariposa - Butterfly ValvesVálvulas de mariposa - Butterfly Valves
Válvulas de mariposa - Butterfly ValvesJLX Valve
 
Itt grinnell products standard and line pipe catalog 2008
Itt grinnell products standard and line pipe catalog 2008Itt grinnell products standard and line pipe catalog 2008
Itt grinnell products standard and line pipe catalog 2008ITTGRINNELL
 
Ericson Pocket Guide-2014
Ericson Pocket Guide-2014Ericson Pocket Guide-2014
Ericson Pocket Guide-2014Nicole Mezic
 
Atomac Lined Ball Valves
Atomac Lined Ball ValvesAtomac Lined Ball Valves
Atomac Lined Ball ValvesCTi Controltech
 
Lined Ball Valves Provide Corrosion Protection
Lined Ball Valves Provide Corrosion ProtectionLined Ball Valves Provide Corrosion Protection
Lined Ball Valves Provide Corrosion ProtectionCTi Controltech
 
Itt grinnell pipe hanger design & engineering 2008
Itt grinnell pipe hanger design & engineering 2008 Itt grinnell pipe hanger design & engineering 2008
Itt grinnell pipe hanger design & engineering 2008 ITTGRINNELL
 
Liquid level specification
Liquid level specificationLiquid level specification
Liquid level specificationIPEC
 
As 7703-iso-fe-serie-en
As 7703-iso-fe-serie-enAs 7703-iso-fe-serie-en
As 7703-iso-fe-serie-enMihai Tache
 
Kraus & naimer optional extras and enclosures kn101 gb0715-dienhathe.vn
Kraus & naimer optional extras and enclosures kn101 gb0715-dienhathe.vnKraus & naimer optional extras and enclosures kn101 gb0715-dienhathe.vn
Kraus & naimer optional extras and enclosures kn101 gb0715-dienhathe.vnDien Ha The
 
Kraus & naimer optional extras and enclosures kn101 gb0715
Kraus & naimer optional extras and enclosures kn101 gb0715Kraus & naimer optional extras and enclosures kn101 gb0715
Kraus & naimer optional extras and enclosures kn101 gb0715Dien Ha The
 
STAUFF-Catalogue-3-STAUFF-Flanges-English.pdf
STAUFF-Catalogue-3-STAUFF-Flanges-English.pdfSTAUFF-Catalogue-3-STAUFF-Flanges-English.pdf
STAUFF-Catalogue-3-STAUFF-Flanges-English.pdfAhmedSalem460811
 
Wika Pressure and Temperature Measurement Product Catalog
Wika Pressure and Temperature Measurement Product CatalogWika Pressure and Temperature Measurement Product Catalog
Wika Pressure and Temperature Measurement Product CatalogProcess Control Solutions, LLC
 
RACI SPACER 2016 CATALOG
RACI SPACER 2016 CATALOGRACI SPACER 2016 CATALOG
RACI SPACER 2016 CATALOGRaci srl Italy
 

Similar to Pipe shields inc (20)

Pipe Shields Catalog
Pipe Shields CatalogPipe Shields Catalog
Pipe Shields Catalog
 
Valvulas globo - Globe valves
Valvulas globo - Globe valvesValvulas globo - Globe valves
Valvulas globo - Globe valves
 
Válvulas de mariposa - Butterfly Valves
Válvulas de mariposa - Butterfly ValvesVálvulas de mariposa - Butterfly Valves
Válvulas de mariposa - Butterfly Valves
 
Itt grinnell products standard and line pipe catalog 2008
Itt grinnell products standard and line pipe catalog 2008Itt grinnell products standard and line pipe catalog 2008
Itt grinnell products standard and line pipe catalog 2008
 
Ericson Pocket Guide-2014
Ericson Pocket Guide-2014Ericson Pocket Guide-2014
Ericson Pocket Guide-2014
 
Atomac Lined Ball Valves
Atomac Lined Ball ValvesAtomac Lined Ball Valves
Atomac Lined Ball Valves
 
045
045045
045
 
Lined Ball Valves Provide Corrosion Protection
Lined Ball Valves Provide Corrosion ProtectionLined Ball Valves Provide Corrosion Protection
Lined Ball Valves Provide Corrosion Protection
 
Itt grinnell pipe hanger design & engineering 2008
Itt grinnell pipe hanger design & engineering 2008 Itt grinnell pipe hanger design & engineering 2008
Itt grinnell pipe hanger design & engineering 2008
 
Liquid level specification
Liquid level specificationLiquid level specification
Liquid level specification
 
6A CAT-M
6A CAT-M6A CAT-M
6A CAT-M
 
6A CAT-M.PDF
6A CAT-M.PDF6A CAT-M.PDF
6A CAT-M.PDF
 
As 7703-iso-fe-serie-en
As 7703-iso-fe-serie-enAs 7703-iso-fe-serie-en
As 7703-iso-fe-serie-en
 
Kraus & naimer optional extras and enclosures kn101 gb0715-dienhathe.vn
Kraus & naimer optional extras and enclosures kn101 gb0715-dienhathe.vnKraus & naimer optional extras and enclosures kn101 gb0715-dienhathe.vn
Kraus & naimer optional extras and enclosures kn101 gb0715-dienhathe.vn
 
Kraus & naimer optional extras and enclosures kn101 gb0715
Kraus & naimer optional extras and enclosures kn101 gb0715Kraus & naimer optional extras and enclosures kn101 gb0715
Kraus & naimer optional extras and enclosures kn101 gb0715
 
STAUFF-Catalogue-3-STAUFF-Flanges-English.pdf
STAUFF-Catalogue-3-STAUFF-Flanges-English.pdfSTAUFF-Catalogue-3-STAUFF-Flanges-English.pdf
STAUFF-Catalogue-3-STAUFF-Flanges-English.pdf
 
Wika Pressure and Temperature Measurement Product Catalog
Wika Pressure and Temperature Measurement Product CatalogWika Pressure and Temperature Measurement Product Catalog
Wika Pressure and Temperature Measurement Product Catalog
 
Perfect Engineers, Mumbai, Camlock Coupler
Perfect Engineers, Mumbai, Camlock CouplerPerfect Engineers, Mumbai, Camlock Coupler
Perfect Engineers, Mumbai, Camlock Coupler
 
Olga Software
Olga SoftwareOlga Software
Olga Software
 
RACI SPACER 2016 CATALOG
RACI SPACER 2016 CATALOGRACI SPACER 2016 CATALOG
RACI SPACER 2016 CATALOG
 

Recently uploaded

KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapRishantSharmaFr
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfRagavanV2
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptDineshKumar4165
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTbhaskargani46
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptMsecMca
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756dollysharma2066
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdfKamal Acharya
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueBhangaleSonal
 
Intro To Electric Vehicles PDF Notes.pdf
Intro To Electric Vehicles PDF Notes.pdfIntro To Electric Vehicles PDF Notes.pdf
Intro To Electric Vehicles PDF Notes.pdfrs7054576148
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXssuser89054b
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...SUHANI PANDEY
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Arindam Chakraborty, Ph.D., P.E. (CA, TX)
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptNANDHAKUMARA10
 

Recently uploaded (20)

KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdf
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Intro To Electric Vehicles PDF Notes.pdf
Intro To Electric Vehicles PDF Notes.pdfIntro To Electric Vehicles PDF Notes.pdf
Intro To Electric Vehicles PDF Notes.pdf
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 

Pipe shields inc

  • 1.
  • 2.
  • 3. 1 GENERAL INTRODUCTION ipe Shields Inc. pioneered the first insulated pipe support, in 1971, for use on HVAC and plumbing lines. These supports were designed because fiberglass pipe insulation is not strong enough to carry the load at the point of support without crushing. The various methods contractors employed to compensate for this weakness were inconsistent, non-uniform and labor intensive, often resulting in damage to the vapor barrier and/or pipe insulation. The insulated pipe support filled the need for an energy efficient, economical and practical support. Pipe Shields Inc. has developed a large and growing family of insulated pipe supports, using its “standard concept” of incorporating materials strong enough to carry the load while insulating the pipe at the same time. No welding to the pipe is required (except for insulated positive anchors and insulated pipe riser clamps) and no direct metal-to-metal heat path exists. Insulated pipe supports meet an assortment of requirements, including: · Pipe supported on: o Flat Surface o Pipe Roll o Clevis Hanger · Gas · Steam · Super Heated Steam · Chilled Water · Styrene · Guide Supports · Sliding Supports · Restrained Supports · Anchors · Pipe Hangers · Pipe Riser Clamps · Thermal Growth – Small or Large · Maximum Support Spacing · Light, Medium or Heavy Loads · Ultra-High Temperatures · Minimum Overhead Clearance · Minimum Horizontal Clearance · Minimum Field Labor · Minimum Friction Loads · Easy Installation Other products designed, manufactured and supplied not included in this catalog are: 1. Cryogenic supports 2. Seismic pipe restraints 3. Heat-traced pre-insulated pipe supports 4. Pipe supports used in computer chip, styrene plants and oil refineries 5. Pipe supports for solar energy projects to accommodate expansion travels in excess of 5’- 0” Our highly sophisticated products are a direct result of years of research, engineering and design to develop cost efficient products for the power, petrochemical, chemical and commercial markets. We work closely with engineering firms and in-house engineering departments of owners to provide working solutions to meet their engineering challenges. We have established proprietary specifications that have now become an industry standard used by owners, engineers and contractors throughout the world markets. If you have a pipe support need not met by any of the items described in this catalog, please contact us at 713-731-0030 or 1-800-787-5914. P FRONEK GROUP CATALOG PS-2004
  • 4. 2 TEMPERATURE, DIMENSIONAL AND MATERIAL VARIANCES Temperature Ranges Pipe Shields Inc. strongly recommends the following temperature ranges for our standard insulation material: Material Temperature Calcium Silicate +40 o F to + 1200o F Urethane -275 o F to +275 o F Foamglasâ -450 o F to +900 o F Material Variances Our standard paint finish is SP150 Red Oxide Primer which meets full EPA and California safety regulations. Other paint finished are available upon request: · Hot dipped galvanized · In-organic zinc (CZ11HS) · Dupont (Corlar) 25P epoxy · SP145 grey oxide · Carbothane 134HG · Carbozinc 859 Slide plate material and other field welded material are coated with deoxaluminate (silver coating) Model Designation for Alternate Insulation Materials Polyurethane – Add U after Catalog Model Number Example: B1000U Urethane/Foamglasâ - Add UF after Catalog Model Number Example: B1000UF Calcium Silicate/Foamglasâ - Add CF after Catalog Model Number Example: B1000CF FRONEK GROUP CATALOG PS-2004
  • 5. 3 INSULATED PIPE SUPPORT SELECTION GUIDE FRONEK GROUP CATALOG PS-2004 1. A. Water B. Steam, Gas, or Air 2. APPLICATION A. Pipe supported from below a. On flat surface b. On pipe roll B. Pipe supported from above a. In clevis or 2-bolt hanger The product data sheets describing each model refer to other models in the catalog with features such as load rating, axial or lateral travel, or restraint, etc. which you may have an interest. USE OF THE INSULATED PIPE SUPPORT SELECTION GUIDE X X OR AIR TABLE 6 X TABLE 3 TABLE 1 TABLE 2 X X X TABLE 4 TABLE 5 X X X X X X ON PIPE ROLL ON FLAT SURFACE APPLICATION PIPE SUPPORTED FROM ABOVEFROM BELOW If you have a pipe support need not met by any of the items described in this catalog, please contact us at 713-731-0030 or 1-800-787-5914. SERVICE These Selection Guide Tables are organized by: The table on the following pages will assist you in making a selection of the proper and most economic insulated pipe support for your application. WATER SERVICE STEAM GAS IN CLEVIS OR 2-BOLT HANGER
  • 6. 4 INSULATED PIPE SUPPORT SELECTION GUIDE FRONEK GROUP CATALOG PS-2004 WATER PIPE SUPPORTED FROM BELOW ON FLAT SURFACE B1000 B1100 B1200 B1300 B2000 B2100 B2200 B2300 B3000 B3100 B3200 B3300 B4000 B4100 B4200 B4300 ASME A1000 A3000 A5000 A7000 A7200 A7400 B5000 B5100 B5200 B5300 B7000 B7100 B7200 B7300 B31.1 A2000 A4000 A6000 B6000 B6100 B6200 B6300 B8000 B8100 B8200 B8300 Pipe Size (Ref) 1/2 7 11 12 3/4 7 12 13 1 7 13 14 1 1/2 9 15 16 2 10 15 17 2 1/2 11 12 14 16 21 3 12 12 13 17 20 35 45 55 32 45 55 3 1/2 13 12 13 16 19 35 45 55 33 45 55 4 14 13 14 17 19 35 45 55 35 45 55 5 16 12 14 16 17 35 45 55 33 45 55 6 17 10 12 13 14 26 34 45 55 30 45 55 8 19 7 8 11 12 21 29 45 55 26 45 55 10 22 6 6 7 10 18 25 24 45 55 21 42 55 12 23 8 14 20 31 20 40 55 65 17 36 54 65 14 25 8 13 22 31 20 40 55 65 18 35 53 65 16 27 12 21 28 19 37 55 65 16 34 50 65 18 28 10 19 26 17 34 52 65 15 30 46 61 20 30 9 17 23 15 31 46 62 14 27 41 55 24 32 14 18 12 24 36 48 10 21 32 43 30 33 10 12 11 21 32 43 9 19 29 39 36 35 9 18 28 37 8 16 24 33 42 36 8 16 24 32 7 14 21 28 Note: Pipe Diameter: 8" standard weight Water 20' - 0 Insulated pipe support model number support spacing. In this case, Model A7200 is selected since it is capable of handling 21'-0 support spacing. The Index Sheets to Sections "A" & "B" indicate some of the differences between models. Check Product Data Sheet for description before making a final selection. In this example, if the support is required to handle +/-4 1/2" of axial travel, Model B2000 would be selected (Section "B" Index & Product Data Sheet B2000). The maximum hanger spacing shown in Table 1 are derived from load ratings (see Product Data Sheets) of Pipe Shields Inc. models, assuming weight of standard pipe, water, and 2" insulation. The customer should be guided by the hanger spacings allowed by the applicable code or the project engineers' specifications before making a selection. Refer to the appropriate Product Data Sheets for additional information such as load rating, compensation for temperature, axial or lateral travel, or restraint, etc. In table 1, for 8" pipe size, find the model(s) rated for handling 20'- 0 or greater Service: Determine: Support Spacing: Method: Example: Given: TABLE 1 SERVICE: APPLICATION: MAXIMUM HANGER SUPPORT SPACING - FEET FOR VARIOUS PIPE SHIELDS, INC.INSULATED PIPE SUPPORT MODELS Commercial Light Industrial w/ Load Distribution Plate Heavy Industrial on Slide Pad Rated for Combined Lateral and Vertical Loads
  • 7. 5 INSULATED PIPE SUPPORT SELECTION GUIDE FRONEK GROUP CATALOG PS-2004 STEAM, GAS OR AIR PIPE SUPPORTED FROM BELOW ON FLAT SURFACE B1000 B1100 B1200 B1300 B2000 B2100 B2200 B2300 B3000 B3100 B3200 B3300 B4000 B4100 B4200 B4300 ASME A1000 A3000 A5000 A7000 A7200 A7400 B5000 B5100 B5200 B5300 B7000 B7100 B7200 B7300 B31.1 A2000 A4000 A6000 B6000 B6100 B6200 B6300 B8000 B8100 B8200 B8300 Pipe Size (Ref) 1/2 8 11 12 3/4 9 12 13 1 9 14 15 1 1/2 12 17 19 2 13 18 20 2 1/2 14 15 16 20 25 3 15 15 17 21 26 40 50 60 40 50 60 3 1/2 16 16 18 21 25 40 50 60 40 50 60 4 17 17 19 23 26 40 50 60 40 50 60 5 19 17 20 22 25 40 50 60 40 50 60 6 21 16 18 20 22 40 40 50 60 40 50 60 8 24 12 14 17 19 35 40 50 60 40 50 60 10 26 10 10 13 17 31 40 40 50 60 36 50 60 12 30 9 9 15 26 37 45 36 50 60 70 32 50 60 70 14 32 8 9 15 25 40 45 38 50 60 70 34 50 60 70 16 35 8 8 14 24 40 45 39 50 60 70 25 50 60 70 18 37 14 24 40 45 38 50 60 70 34 50 60 70 20 39 14 22 40 45 36 50 60 70 32 50 60 70 24 42 11 20 36 45 32 50 60 70 28 50 60 70 30 44 10 18 32 39 33 50 60 70 30 50 60 70 36 48 9 15 27 33 50 60 70 29 50 60 70 42 50 12 23 31 50 60 70 28 50 60 70 Note: Pipe Diameter: 8" standard weight Steam 30' - 0 Insulated pipe support model number The maximum hanger spacing shown in Table 2 are derived from load ratings (see Product Data Sheets) of Pipe Shields Inc. models, assuming weight of standard pipe, and 2" insulation. The customer should be guided by the hanger spacings allowed by the applicable code or the project engineers' specifications before making a selection. Refer to the appropriate Product Data Sheets for additional information such as load rating, compensation for temperature, axial or lateral travel, or restraint, etc. w/ Load Distribution Plate Heavy Industrial on Slide Pad Rated for Combined Lateral and Vertical Loads support spacing. In this case, Model A7200 is selected since it is capable of handling 35'-0 support spacing. The Index Sheets to Sections "A" & "B" indicate some of the differences between models. Check Product Data Sheet for description before making a final selection. In this example, if the support is required to handle +/-4 1/2" of axial travel, Model B2000 would be selected (Section "B" Index & Product Data Sheet B2000). Example: Given: TABLE 2 SERVICE: APPLICATION: MAXIMUM HANGER SUPPORT SPACING - FEET FOR VARIOUS PIPE SHIELDS, INC.INSULATED PIPE SUPPORT MODELS Commercial Light Industrial In table 2, for 8" pipe size, find the model(s) rated for handling 30'- 0 or greater Service: Determine: Support Spacing: Method:
  • 8. 6 INSULATED PIPE SUPPORT SELECTION GUIDE FRONEK GROUP CATALOG PS-2004 WATER PIPE SUPPORTED FROM ABOVE IN CLEVIS OR 2-BOLT HANGER D1000 D2000 ASME A1000 A3000 D4000 D3000 D3100 D3200 D3300 B31.1 A2000 A4000 A9000 D5000 D6000 D6100 D6200 D6300 Pipe Size (Ref) 1/2 7 11 12 13 3/4 7 12 13 15 1 7 14 15 17 19 1 1/2 9 16 18 19 22 2 10 17 18 21 29 2 1/2 11 16 18 21 24 3 12 17 18 20 25 3 1/2 13 16 17 19 22 4 14 16 18 19 22 5 16 15 16 19 21 40 6 17 14 15 16 21 40 8 19 13 13 15 22 32 10 22 12 13 14 24 28 12 23 11 12 13 22 26 14 25 11 12 13 20 23 16 27 10 11 12 21 26 40 18 28 9 10 11 18 22 33 20 30 9 9 10 16 18 28 37 24 32 8 9 15 19 29 38 30 33 11 13 19 26 Note: Pipe Diameter: 8" standard weight Water 20' - 0 Insulated pipe support model number MAXIMUM HANGER SUPPORT SPACING - FEET In table 3, for 8" pipe size, find the model(s) rated for handling 20"- 0 or greater support spacing. In this case, Model D3000 is selected since it is capable of handling 22'-0 support spacing. The Index Sheets to Sections "A" & "D" indicate some of the differences between models. Check Product Data Sheet for description before making a final selection. In this example, if the clearance is above the support limited, Model D6000 might be selected (Section "D" Index & Product Data Sheet D6000). Service: Determine: Support Spacing: Method: Example: Given: The maximum hanger spacing shown in Table 3 are derived from load ratings (see Product Data Sheets) of Pipe Shields Inc. models, assuming weight of standard pipe, water, and 2" insulation. The customer should be guided by the hanger spacings allowed by the applicable code or the project engineers' specifications before making aection. Refer to the appropriate Product Data Sheets for additional information such as load rating, compensation for temperature, axial or lateral travel, or restraint, etc. TABLE 3 SERVICE: APPLICATION: Clevis Hanger 2-Bolt Hanger FOR VARIOUS PIPE SHIELDS, INC. PRE-INSULATED PIPE SUPPORT MODELS
  • 9. 7 INSULATED PIPE SUPPORT SELECTION GUIDE FRONEK GROUP CATALOG PS-2004 STEAM, GAS OR AIR PIPE SUPPORTED FROM ABOVE IN CLEVIS OR 2-BOLT HANGER D1000 D2000 ASME A1000 A3000 D4000 D3000 D3100 D3200 D3300 B31.1 A2000 A4000 A9000 D5000 D6000 D6100 D6200 D6300 Pipe Size (Ref) 1/2 8 11 12 13 3/4 9 12 13 15 1 9 15 16 19 21 1 1/2 12 19 20 22 26 2 13 20 22 25 36 2 1/2 14 20 22 25 29 3 15 21 24 26 32 3 1/2 16 21 23 25 29 4 17 23 24 26 31 5 19 22 24 28 30 55 6 21 22 23 24 32 55 8 24 21 22 25 25 52 10 26 20 22 24 40 45 12 30 20 21 24 40 45 14 32 21 23 25 38 55 60 16 35 21 22 25 40 55 60 18 37 21 22 25 40 49 60 20 39 21 22 25 38 44 60 65 24 42 20 21 24 40 50 60 65 30 44 34 51 60 65 Note: Pipe Diameter: 8" standard weight Steam 24' - 0 Insulated pipe support model number TABLE 4 SERVICE: APPLICATION: Clevis Hanger FOR VARIOUS PIPE SHIELDS, INC. PRE-INSULATED PIPE SUPPORT MODELS 2-Bolt Hanger MAXIMUM HANGER SUPPORT SPACING - FEET The maximum hanger spacing shown in Table 4 are derived from load ratings (see Product Data Sheets) o Pipe Shields Inc. models, assuming weight of standard pipe, and 2" insulation. The customer should be guided by the hanger spacings allowed by the applicable code or the project engineers' specifications before making a selection. Refer to the appropriate Product Data Sheets for additional information such as load rating, compensation for temperature, axial or lateral travel, or restraint, etc. support spacing. In this case, Model A9000 is selected since it is capable of handling 25'-0 support spacing. The Index Sheets to Sections "A" & "D" indicate some of the differences between models. Check Product Data Sheet for description before making a final selection. In this example, if the clearance is above the support limited, Model D6000 might be selected (Section "D" Index & Product Data Sheet D6000). Service: Determine: Support Spacing: Method: In table 4, for 8" pipe size, find the model(s) rated for handling 24'- 0 or greater Example: Given:
  • 10. 8 INSULATED PIPE SUPPORT SELECTION GUIDE FRONEK GROUP CATALOG PS-2004 WATER PIPE SUPPORTED FROM BELOW ON PIPE ROLL ASME A5000 B31.1 A6000 A8000 A8200 A8400 Pipe Size (Ref) 1/2 7 3/4 7 1 7 1 1/2 9 2 10 2 1/2 11 15 18 3 12 15 17 3 1/2 13 12 16 4 14 15 16 5 16 14 15 6 17 12 13 24 8 19 9 10 19 10 22 10 16 22 12 23 12 23 31 14 25 11 21 28 16 27 10 19 25 18 28 9 17 23 20 30 8 15 20 24 32 12 16 30 33 9 12 Note: Pipe Diameter: 8" standard weight Water 18' - 0 Insulated pipe support model number The maximum hanger spacing shown in Table 5 are derived from load ratings (see Product Data Sheets) of Pipe Shields Inc. models, assuming weight of standard pipe, water, and 2" insulation. The customer should be guided by the hanger spacings allowed by the applicable code or the project engineers' specifications before making a selection. Refer to the appropriate Product Data Sheets for additional information such as load rating, compensation for temperature, axial or lateral travel, or restraint, etc. 13 15 12 12 12 Service: Determine: Support Spacing: Method: In table 5, for 8" pipe size, find the model(s) rated for handling 18'- 0 or greater support spacing. In this case, Model A8200 is selected since it is capable of handling 19'-0 support spacing. The Index Sheet to Section "A" indicates some of the differences between models. Check Product Data Sheet for description before making a final selection. If greater support spacings are desired, see Section "B" (Base Mounted Supports). Example: Given: TABLE 5 SERVICE: APPLICATION: A3000 A4000 13 15 Commercial 12 13 Light Insutrial w/Load Distribution Plate MAXIMUM HANGER SUPPORT SPACING - FEET FOR VARIOUS PIPE SHIELDS, INC. PRE-INSULATED PIPE SUPPORT MODELS
  • 11. 9 INSULATED PIPE SUPPORT SELECTION GUIDE FRONEK GROUP CATALOG PS-2004 STEAM, GAS OR AIR PIPE SUPPORTED FROM BELOW ON PIPE ROLL ASME A5000 B31.1 A6000 A8000 A8200 A8400 Pipe Size (Ref) 1/2 8 3/4 9 1 9 1 1/2 12 2 13 2 1/2 14 18 22 3 15 19 21 3 1/2 16 19 21 4 17 20 23 5 19 20 22 6 21 18 20 36 8 24 15 17 31 10 26 11 17 27 38 12 30 13 23 40 50 14 32 13 22 40 50 16 35 13 22 39 50 18 37 12 21 38 50 20 39 12 20 36 49 24 42 11 18 33 44 30 44 9 16 29 39 36 48 8 13 24 42 50 11 20 Note: Pipe Diameter: 8" standard weight Steam 25' - 0 Insulated pipe support model number Light Industrial w/ Load Distribution Plate 15 Example: Given: 15 16 17 The maximum hanger spacing shown in Table 6 are derived from load ratings (see Product Data Sheets) of Pipe Shields Inc. models, assuming weight of standard pipe, and 2" insulation. The customer should be guided by the hanger spacings allowed by the applicable code or the project engineers' specifications before making a selection. Refer to the appropriate Product Data Sheets for additional information such as load rating, compensation for temperature, axial or lateral travel, or restraint, etc. TABLE 6 SERVICE: APPLICATION: A3000 MAXIMUM HANGER SUPPORT SPACING - FEET FOR VARIOUS PIPE SHIELDS, INC. PRE-INSULATED PIPE SUPPORT MODELS A4000 14 17 18 Commercial 12 13 Service: Determine: Support Spacing: Method: In table 6, for 8" pipe size, find the model (s) rated for handling 25'-0 or greater support spacing. In this case, Model A8200 is selected since it is capable of handling 25'-0 or 31'-0 support spacing. The Index Sheet to Section "A" indicates some of the differences between models. Check Product Data Sheet for description before making a final selection. If greater support spacings are desired, see Section "B" (Base Mounted Supports).
  • 13. INTRODUCTION SECTION “A” INTRODUCTION SECTION “A” PRE-INSULATED PIPE SUPPORTS APPLICATION – Commercial and Light Industrial Most Commercial applications are well served by Models A1000 and A2000, which are recommended for use on common 10’-0 hanger space for small bore pipe sizes (see Selection Guide). However, should the need arise, because of increased hanger spacing or the manner in which the insulated support is mounted, heavier duty supports are available. As is readily seen in the “Section Index” on the following page, some models are meant for installation only in a clevis hanger, on a flat surface, or on a pipe roll. Other models may be installed in any two or all three mounting methods. The load ratings (see Product Data Sheets) reflect consideration for the manner in which each of these models will be mounted. Note that in the A7000 through A7400 Series and the A8000 through A8400 Series, the higher the model number, the higher the load rating. We are committed to providing the most economical and appropriate insulated pipe support to satisfy the requirements of the piping system. If your requirements are not covered by the Product Data Sheets in this catalog, please contact us at 713-731-0030 or 1-800-787-5914. Please acquaint yourself with the selection guide at the front of this catalog and the section index on the page following this introduction, for assistance in determining the most appropriate support for your application. FRONEK GROUP CATALOG PS-2004
  • 14. PIPE SIZE FLAT CLEVIS PIPE MODEL RANGE HOT COLD SURFACE HANGER ROLL DUTY A1000 1/2 - 24 X X X LIGHT A2000 1/2 - 24 X X X LIGHT A3000 1/2 - 24 X X X MEDIUM A3000 1/2 - 4 X X MEDIUM A4000 1/2 - 24 X X X MEDIUM A4000 1/2 - 4 X X MEDIUM A5000 2 1/2 - 42 X X X MED/HEAVY A6000 2 1/2 - 42 X X X MED/HEAVY A7000 2 1/2 - 42 X X X HEAVY A7200 6 - 42 X X X HEAVIER A7400 10 - 30 X X X HEAVIEST A8000 2 1/2 - 42 X X X HEAVY A8200 6 - 42 X X X HEAVIER A8400 10 - 30 X X X HEAVIEST A9000 1/2 - 24 X X X HEAVY PRE-INSULATED PIPE SUPPORTS COMMERCIAL AND LIGHT INDUSTRIAL PRIMARY APPLICATION INSTALLED ON SECTION “A” INDEX TO ORDER, specify: 1. Quantity 20 2. Pipe Size & Type 2” IPS 3. Insulation Thickness 2-1/2” 4. Model Number A1000 EXAMPLE: (20) 2 x 2-1/2 A1000 FRONEK GROUP CATALOG PS-2004
  • 15. MODEL A1000 Insulated Pipe Support Regular Duty A1 Features: · Compact · Easy Installation · Eliminates welding to pipe · Overlapping galvanized sheet metal jacket · Minimizes heat-loss and/or condensation · Copper tubing sizes available · Other I.D.'s and/or O.D.'s available on request · Clamps available (see G-series) Performance Test Results on File: Available upon request. · · · · Material Data: A1000: Applicable PSI spec. doc.: No. 205. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTMA-527. Glue: Industrial contact adhesive Formal Submittal Sheets available Application: Model A1000 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam ·Air · Dual Temperature · Chilled Water Intended for installation on: · Flat Surfaces · Band, ring or clevis pipe hanger Note: Up to 1700°F available upon request. Temperature Range: °F to +1200°F+40 FRONEK GROUP CATALOG PS-2004 Hardware sold separately A B A B A B A B A B A B A B A B A B 4 24 4 24 4 24 4 24 4 24 4 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20 6 20 6 20 6 20 6 20 9 16 9 16 9 16 9 16 9 16 9 16 9 16 9 16 9 16 12 16 12 16 12 16 12 16 12 16 12 16 18 16 18 16 18 16 18 16 18 16 18 16 200 TABLE III 1200 0.75 0.50 0.30 750 1000 350 450 Mult. Copper Tubing Size O.D. 250 550 1000 750 1200 300 Oper. Temp. o F To develop maximum load rating, use band, ring or clevis hanger with manufacturer's load rating equal to or greater than values shown in Table I. To develop maximum load rating, width of support surface should be at least 1/2 of dimension "A" in Table II. The load ratings represent average values obtained in accordance with accepted methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Factor "F" 500 0.90 MAXIMUM LOAD Pipe On Flat In Clevis 1 1/2 Iron Contact factory for other dimensions, temperatures, and loads. Available in all insulation thicknesses. Insulation Thickness 2 2 1/2 To obtain load ratings for operating temperatures of 500° F and higher, multiply load rating by factor "F" in Table III. 1/2 3/4 1 8 1/8 -10 1/8 12 1/8 5/8 - 1 5/8 4 2 1/8 2 5/8 - 4 1/8 550 350 65 80 110 140 150 180 225 270 400 450 3 8 5 6 14 16 18 24 20 1600 1800 2000 3 1/2 TABLE I 750 600 625 675 TABLE II "B" = gauge of sheet metal jacket Pipe Size 1/2 - 1 1/2 6 - 7 8 - 10 12 - 18 5 2 1/2 - 4 3 2 1/2 2 20 - 24 5 1/8 6 1/8 2300 10 1400575 500 Note: For higher load ratings, see A3000, A9000. 12 3 1/2 4 70 100 125 1 1/4 1 1/2 2 1 1/2 40 60 Size 3/4 RATING (LBS) Hanger (b) (c) 40 Surface (a) (c) 35 45
  • 16. A2 MODEL A2000 Insulated Pipe Support Regular Duty w/ Extended Insulation Application: Model A2000 is designed for use on: · Cold Water · Chilled Water Intended for installation on: · Flat Surfaces · Band, ring or clevis pipe hangers Temperature Range: °F to +1200°F+40 Note: Up to 1700°F available upon request. Features: · Compact · Easy Installation · Eliminates welding to pipe · Overlapping galvanized sheet metal jacket · Minimizes heat-loss and/or condensation · Calcium silicate insulation extends 1'' beyond the galvanized sheet metal jacket providing for an easier vapor barrier joint with the pipe insulation · Copper tubing sizes available · Other I.D.'s and/or O.D.'s available on request · Clamps available see (G-series) Performance Test Results on File: Available upon request. Material Data: · A2000: Applicable PSI spec. doc.: No. 205. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTMA-527. · Glue: Industrial contact adhesive Formal Submittal Sheets available FRONEK GROUP CATALOG PS-2004 Hardware sold separately A B A B A B A B A B A B A B A B A B 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20 6 20 6 20 6 20 6 20 9 16 9 16 9 16 9 16 9 16 9 16 9 16 9 16 9 16 12 16 12 16 12 16 12 16 12 16 12 16 18 16 18 16 18 16 18 16 18 16 18 16 0.75 0.50 TABLE III 1200 0.30 FactorTemp. The load ratings represent average values obtained in accordance with accepted methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. o F "F" Note: For higher load ratings, see A4000, A9000. 500 750 1000 0.90 10 3 1/2 12 14 4 5 6 8 To obtain load ratings for operating temperatures of 500°F and higher, multiply load rating by factor "F" in Table III. 18 20 24 To develop maximum load rating, width of support surface should be at least 1/2 of dimension "A" in Table II. To develop maximum load rating, use band, ring or clevis hanger with manufacturer's load rating equal to or greater than values shown in Table I. Contact factory for other dimensions, temperatures, and loads. Available in all insulation thicknesses. 16 2000675 1400 1600 1800625 575 1 1/2 2 2 1/2 3 1/2 3/4 1 1 1/4 12 1/8 750 5/8 - 15/8 Copper Tubing Size O.D. 4 2300 6 1/8 8 1/8 -10 1/8 110 140 200 250 450 750 1000 550 70 600 500 150 400 450 550 MAXIMUM LOAD On Flat 1200 Pipe 225 270 100 125 300 350 3 1/2 RATING (LBS) In Clevis 40 45 65 80 35 40 60 Oper. Mult. 2 2 1/2 Insulation ThicknessIron Pipe 180 350 TABLE II "B" = gauge of sheet metal jacket 3/4 1 1 1/2 20 - 24 5 6 - 7 2 1/8 2 5/8 - 4 1/8 5 1/8 1/2 - 1 1/2 1/2 8 - 10 Size 12 - 18 Size TABLE I Hanger (b) (c) Surface (a) (c) 2 1/2 - 4 3 2
  • 17. MODEL A3000 Insulated Pipe Support A3 Extra Heavy Bottom Jacket Features: · Compact · Easy Installation · Eliminates welding to pipe · Overlapping galvanized sheet metal jacket · Minimizes heat-loss and/or condensation · Double thickness bottom jacket for added structural strength and abrasive wear resistance · Copper tubing sizes available · Other I.D.'s and/or O.D.'s available on request · Clamps available (see G-series) Performance Test Results on File: Available upon request. Material Data: · A3000: Applicable PSI spec. doc.: No. 205. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTMA-527. · Glue: Industrial contact adhesive. Formal Submittal Sheets available Application: Model A3000 is designed for use on: · Hot Water · Steam · Cold Water · Air · Chilled Water · Gas · Dual Temperature · Vacuum Intended for installation on: · Flat Surfaces . Pipe Rolls · Band, ring or clevis pipe hanger Note: Up to 1700°F available upon request. Temperature Range: °F to +1200°F+40 FRONEK GROUP CATALOG PS-2004 Pipe Size 1/2 3/4 1 1 1/4 1 1/2 2 Hardware sold separately 2 1/2 3 3 1/2 4 5 6 8 10 12 14 16 18 20 24 A B A B A B A B A B A B A B A B A B 4 24 4 24 4 24 4 24 4 24 4 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20 6 20 6 20 6 20 6 20 9 16 9 16 9 16 9 16 9 16 9 16 9 16 9 16 9 16 12 16 12 16 12 16 12 16 12 16 12 16 18 16 18 16 18 16 18 16 18 16 18 16 TABLE II "B" = gauge of sheet metal jacket (bottom jacket approx. 2 X ga. of top jacket) 12 - 18 12 1/8 20 - 24 6 - 7 6 1/8 8 - 10 8 1/8 -10 1/8 2 1/2 - 4 2 5/8 - 4 1/8 5 5 1/8 1/2 - 1 1/2 5/8 -1 5/8 2 2 1/8 3 1/2 4 Tubing Size Size O.D. 1 1/2 2 2 1/2 3Pipe To develop maximum load rating, use band, ring or clevis hanger with manufacturer's load rating equal to or greater than values shown in Table I. TABLE I 1/2 3/4 1 Contact factory for other dimensions, temperatures, loads. Available in all insulation thicknesses. To obtain load ratings for operating temperatures of 500o F and higher, multiply load rating by factor "F" in Table III. Iron Insulation Thickness Copper 700 2100 775 2400 Divide "A" in Table II by 6 to find maximum allowable travel on pipe roll (+/- from centered position). 650 1900 600 1500 625 A5000 1700 To develop maximum load rating, width of support surface should be at least 1/2 of dimension "A" in Table II. 575 1300 500 800 525 See 1100 300 270 375The load ratings represent average values obtained in accordance with accepted methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. 400 475 450 575 Note: For higher load ratings, see A5000, A9000. 250 225 325 200 180 155 TABLE III 165 150 2201200 0.30 140 125 275 120750 0.75 80 1000 0.50 110 100 50 500 0.90 65 60 70 70 90 (b) (d) (c) (d) Temp. Factor 40 35 45Oper. Mult. 40 (a) (d) o F "F" 45 Surface Roll or Clevis Hanger MAXIMUM LOAD RATING (LBS) On Flat On Pipe In Ring
  • 18. A4 MODEL A4000 Insulated Pipe Support Extra Heavy Bottom Jacket w/ext. Insulation Material Data: · A4000: Applicable PSI spec. doc.: No. 205. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTMA-527. · Glue: Industrial contact adhesive. Formal Submittal Sheets available Features: · Compact · Easy Installation · Eliminates welding to pipe · Overlapping galvanized sheet metal jacket · Double thickness bottom jacket for added structural strength and abrasive wear · Minimizes heat-loss and/or condensation · Calcium silicate insulation extends 1'' beyond the galvanized sheet metal jacket providing for an easier vapor barrier joint with the pipe · Copper tubing sizes available · Other I.D.'s and/or O.D.'s available on request · Clamps available (see G-series) Performance Test Results on File: Available upon request. resistance Application: Model A4000 is designed for use on: · Cold Water · Chilled Water Intended for installation on: · Flat Surfaces . Pipe Rolls · Band, ring or clevis pipe hanger Note: Up to 1700°F available upon request. Temperature Range: °F to +1200°F+40 FRONEK GROUP CATALOG PS-2004 Pipe Size 1/2 3/4 1 1 1/4 1 1/2 2 Hardware sold separately 2 1/2 3 3 1/2 4 5 6 8 10 12 14 16 18 20 24 A B A B A B A B A B A B A B A B A B 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20 6 20 6 20 6 20 6 20 9 16 9 16 9 16 9 16 9 16 9 16 9 16 9 16 9 16 12 16 12 16 12 16 12 16 12 16 12 16 18 16 18 16 18 16 18 16 18 16 18 16 35 40 12 1/8 5/8-1 5/8 2 5/8 - 4 1/8 6 1/8 8 1/8 -10 1/8 See 270 60 70 100 125 80 110 140 165 Surface 40 45 65 On Pipe In Ring (c) (d) or ClevisRoll Temp. Oper. Mult. Factor 12 - 18 2 1/2 - 4 TABLE III 2 2 1/2 Iron Pipe Size 1/2 2 1/2 - 1 1/2 TABLE II "B" = gauge of sheet metal jacket (bottom jacket approx. 2 X ga. of top jacket) 3/4 1 1 1/2 20 - 24 5 6 - 7 8 - 10 220 275200 250 150 180 225 325 1200 0.90 0.75 0.50 0.30 500 "F" 750 1000 o F 70 90 120 155 MAXIMUM LOAD On Flat 375 475 45 Hanger (b) (d) RATING (LBS) (a) (d) 50 575 3 1/2 1700 1900 2100 2400 4 Insulation Thickness 700 300 400 450 650 500 625 525 575 600 5 1/8 Copper Tubing Size O.D. 1500 775 2 1/8 TABLE I 3 A6000 Note: For higher load ratings, see A6000, A9000 To obtain load ratings for operating temperatures of 500°F and higher, multiply load rating by factor "F" in Table III. Contact factory for other dimensions, temperatures, loads. Available in all insulation thicknesses. The load ratings represent average values obtained in accordance with accepted methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. To develop maximum load rating, width of support surface should be at least 1/2 of dimension "A" in Table II. Divide "A" in Table II by 6 to find maximum allowable travel on pipe roll (+/- from centered position). To develop maximum load rating use band, ring or clevis hanger with manufacturer's load rating equal to or greater than values shown in Table I. 800 1100 1300
  • 19. A5 MODEL A5000 Insulated Pipe Support With load distribution plate Features: · Compact · Easy Installation · Eliminates welding to pipe · Copper tubing sizes available · Overlapping galvanized sheet metal jacket · Minimizes heat-loss and/or condensation · Load distribution plate integral with bottom jacket · Other I.D.'s and/or O.D.'s available upon request Performance Test Results on File: Available upon request. Material Data: · A5000: Applicable PSI spec. doc.: No. 205. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTM A-527. · Load distribution Plate: Carbon steel ASTM A-36 · Coating: Primer coated or hot-dip galvanized. Other coatings available upon request. · Glue: Industrial contact adhesive. Formal Submittal Sheets available Application: Model A5000 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam · Air · Dual Temperature · Chilled Water Intended for installation on: · Flat Surfaces · Pipe Rolls Note: Up to 1700°F available upon request. Temperature Range: °F to +1200°F+40 FRONEK GROUP CATALOG PS-2004 A B C 9 6 1/4 9 6 1/4 9 6 1/4 9 6 1/4 9 6 1/4 9 6 1/4 9 6 1/4 9 6 1/4 12 9 3/8 12 9 3/8 12 9 1/2 12 9 1/2 12 9 1/2 12 9 3/4 12 9 3/4 12 9 3/4 12 9 3/4 Hardware sold separately Note: For higher load ratings, see A7000 The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information. To develop maximum load rating, width of support surface should be at least 1/2 of dimension "B" in Table I. To obtain load ratings for operating temperatures of 500o F and higher, multiply maximum load rating by factor "F" in Table II. Contact factory for other dimensions, temperatures, and loads. Available in all insulation thicknesses.1200 0.30 TABLE II 750 0.75 1000 0.50 1350 3 500 0.90 TABLE I o F "F" 42 1500 1350 3 Temp. Factor 36 1500 1350 3 Oper. Mult. 30 1500 24 1400 1250 3 20 1300 1150 3 18 1200 1075 3 16 1100 975 3 14 1000 900 3 12 925 825 3 10 650 575 2 8 625 550 2 6 500 450 2 5 450 400 2 4 350 315 2 3 1/2 300 270 2 3 250 225 2 2 1/2 200 180 2 Pipe Roll (a) (b) (b) +/- Size Surface Roll on Pipe On Flat On Pipe (inches) MAXIMUM LOAD Max. Axial RATING (LBS) Travel
  • 20. With load distribution plate w/ext. InsulationMODEL A6000 Insulated Pipe Support A6 Features: · Compact · Easy Installation · Eliminates welding to pipe · Copper tubing sizes available · Overlapping galvanized sheet metal jacket · Minimizes heat-loss and/or condensation · Load distribution plate integral with bottom jacket · Calcium silicate insulation extends 1'' beyond the galvanized sheet metal jacket providing for an easier vapor barrier joint with the pipe · Other I.D.'s and/or O.D.'s available on request Performance Test Results on File: Available upon request. · · · · · · Material Data: A6000: Applicable PSI spec. doc.: No. 205. Insulation: Calcium Silicate asbestos-free, treated with water repellant. Jackets: Galvanized Steel ASTMA-527. Load distribution Plate: Carbon steel ASTM A-36 Coating: Primer coated or hot-dip galvanized. Other coatings available upon request. Glue: Industrial contact adhesive Formal Submittal Sheets available Application: Model A6000 is designed for use on: · Cold Water · Chilled Water Intended for installation on: · Flat Surfaces · Pipe Rolls Note: Up to 1700°F available upon request. Temperature Range: °F to +1200°F+40 FRONEK GROUP CATALOG PS-2004 A B C 9 6 1/4 9 6 1/4 9 6 1/4 9 6 1/4 9 6 1/4 9 6 1/4 9 6 1/4 9 6 1/4 12 9 3/8 12 9 3/8 12 9 1/2 12 9 1/2 12 9 1/2 12 9 3/4 12 9 3/4 12 9 3/4 12 9 3/4 Hardware sold separately MAXIMUM LOAD Max. Axial RATING (LBS) Travel Pipe On Flat On Pipe (inches) Size Surface Roll on Pipe Roll (a) (b) (b) +/- 2 1/2 200 180 2 3 250 225 2 3 1/2 300 270 2 4 350 315 2 5 450 400 2 6 500 450 2 8 625 550 2 10 650 575 2 12 925 825 3 14 1000 900 3 16 1100 975 3 18 1200 1075 3 1250 3 20 1300 1150 3 30 1500 24 1400 1350 3 Temp. Factor 36 1500 1350 3 Oper. Mult. 1350 3 500 0.90 TABLE I o F "F" 42 1500 750 0.75 1000 0.50 Contact factory for other dimensions, temperatures, and loads. Available in all insulation thicknesses.1200 0.30 TABLE II Note: For higher load ratings, see A7000 The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information. To develop maximum load rating, width of support surface should be at least 1/2 of dimension "B" in Table I. To obtain load ratings for operating temperatures of 500o F and higher, multiply maximum load rating by factor "F" in Table II.
  • 21. A7 MODEL A7000 Insulated Pipe Support Heavy Duty with load bearing plate Features: · Compact · Easy Installation · Eliminates welding to pipe · Copper tubing sizes available · Minimizes heat-loss and/or condensation · Insulating structural inserts for load transfer · Overlapping galvanized sheet metal jacket · Other I.D.'s and/or O.D.'s available on request · Load distribution plate integral with bottom jacket Performance Test Results on File: Available upon request. Material Data: · A7000: Applicable PSI spec. doc.: No. 205. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTM A-527. · Structural Inserts: High-density calcium silicate asbestos-free, treated with water · Load Distribution Plate: Carbon steel ASTM A-36 · Coating: Primer coated or hot-dip galvanized. Other coatings available upon request. · Glue: Industrial contact adhesive. Formal Submittal Sheets available repellant. Application: Model A7000 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam · Air · Dual Temperature · Chilled Water Intended for installation on: · Flat Surfaces · Pipe rolls, see A8200 · Clevis hangers, see A9000 Note: Up to 1700°F available upon request. Temperature Range: °F to +1200°F+40 FRONEK GROUP CATALOG PS-2004 A B C 6 3 1/4 6 3 1/4 6 3 1/4 6 3 1/4 6 3 1/4 6 3 1/4 6 3 1/4 9 6 3/8 9 6 3/8 9 6 3/8 9 6 1/2 9 6 1/2 9 6 1/2 9 6 3/4 9 6 3/4 9 6 3/4 9 6 3/4 Surface 350 Pipe (LBS) (a) 3 TABLE I MAXIMUM LOAD RTG. 2 1/2 250 300 1850 8 3 1/2 2500 6 4 5 2000 400 10 12 14 1650 500 16 18 20 24 2500 2500 30 36 On FlatSize The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information. 550 700 875 1600 42 2100 2300 To develop maximum load rating, width of support surface should be at least 1/2 of dimension "B" in Table I. Contact factory for other dimensions, temperatures, and loads. Available in all insulation thicknesses. Note: For higher load ratings, see A7200
  • 22. A8 MODEL A7200 Insulated Pipe Support Heavy Duty with load bearing plate Features: · Compact · Easy Installation · Eliminates welding to pipe · Copper tubing sizes available · Minimizes heat-loss and/or condensation · Insulating structural inserts for load transfer · Overlapping galvanized sheet metal jacket · Other I.D.'s and/or O.D.'s available on request · Load distribution plate integral with bottom jacket Performance Test Results on File: Available upon request Material Data: · A7200: Applicable PSI spec. doc.: No. 205. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTM A-527. · Structural Inserts: High-density calcium silicate asbestos-free, treated with water · Load distribution Plate: Carbon steel ASTM A-36 · Coating: Primer coated or hot-dip galvanized. Other coatings available upon request. · Glue: Industrial contact adhesive. Formal Submittal Sheets available repellant. Application: Model A7200 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam · Air · Chilled Water · Dual Temperature Intended for installation on: · Flat Surfaces · Pipe rolls, see A8200 · Clevis hangers, see A9000 Note: Up to 1700°F available upon request. Temperature Range: °F to +1200°F+40 FRONEK GROUP CATALOG PS-2004 A B C 9 6 1/2 9 6 1/2 9 6 5/8 9 6 5/8 9 6 5/8 9 6 3/4 9 6 3/4 9 6 3/4 9 6 1 9 6 1 9 6 1 9 6 1 MAXIMUM LOAD RTG. Pipe (LBS) Size On Flat Surface (a) 6 1000 8 1250 10 1550 12 2250 14 2780 16 3300 18 3600 20 3800 24 4100 30 4500 Contact factory for other dimensions, temperatures, and loads. Available in all insulation thicknesses. TABLE I 36 4500 42 4500 Note: For higher load ratings, see A7400, B1100 The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information. To develop maximum load rating, width of support surface should be at least 1/2 of dimension "B" in Table I.
  • 23. A9 MODEL A7400 Insulated Pipe Support Heavy Duty with load bearing plate · Features: Compact · Easy Installation · Eliminates welding to pipe · Copper tubing sizes available · Minimizes heat-loss and/or condensation · Insulating structural inserts for load transfer · Overlapping galvanized sheet metal jacket · Other I.D.'s and/or O.D.'s available on request · Load distribution plate integral with bottom jacket Performance Test Results on File: Available upon request. Material Data: · A7400: Applicable PSI spec. doc.: No. 205. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTM A-527. · Structural Inserts: High-density calcium silicate asbestos-free, treated with water · Load distribution Plate: Carbon steel ASTM A-36 · Coating: Primer coated or hot-dip galvanized. Other coatings available upon request. · Glue: Industrial contact adhesive Formal Submittal Sheets available repellant. Application: Model A7400 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam · Air · Chilled Water · Dual Temperature Intended for installation on: · Flat Surfaces · Pipe rolls, see A8400 · Clevis hangers, see A9000 Note: Up to 1700°F available upon request. Temperature Range: °F to +1200°F+40 FRONEK GROUP CATALOG PS-2004 A B C 9 6 3/4 9 6 3/4 9 6 3/4 9 6 1 9 6 1 9 6 1 9 6 1 9 6 1 MAXIMUM LOAD RTG. Pipe (LBS) Size On Flat Surface (a) 10 2100 12 3400 14 3900 16 4400 18 4800 20 5100 24 5500 30 5500 Table I Contact factory for other dimensions, temperatures, and loads. Available in all insulation thicknesses. Note: For higher load ratings, see B1200 The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information. To develop maximum load rating, width of support surface should be at least 1/2 of dimension "B" in Table I.
  • 24. A10 MODEL A8000 Insulated Pipe Support Heavy Duty with load bearing plate Features: · Compact · Easy Installation · Eliminates welding to pipe · Copper tubing sizes available · Minimizes heat-loss and/or condensation · Insulating structural inserts for load transfer · Overlapping galvanized sheet metal jacket · Other I.D.'s and/or O.D.'s available on request · Load distribution plate integral with bottom jacket Performance Test Results on File: Available upon request. Material Data: · A8000: Applicable PSI spec. doc. No. 205. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTM A-527. · Structural Inserts: High-density calcium silicate asbestos-free, treated with water repellant. · Load Distribution Plate: Carbon steel ASTM A-36 · Coating: Primer coated or hot-dip galvanized. Other coatings available upon request. · Glue: Industrial contact adhesive. Formal Submittal Sheets available Application: Model A8000 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam · Air · Chilled Water · Dual Temperature Intended for installation on: · Flat Surfaces · Pipe rolls, see A7000 · Clevis hangers, see A9000 Note: Up to 1700°F available upon request. Temperature Range: °F to +1200°F+40 FRONEK GROUP CATALOG PS-2004 A B C 9 6 1/4 9 6 1/4 9 6 1/4 9 6 1/4 9 6 1/4 9 6 1/4 9 6 1/4 12 9 3/8 12 9 3/8 12 9 3/8 12 9 1/2 12 9 1/2 12 9 1/2 12 9 3/4 12 9 3/4 12 9 3/4 12 9 3/4 Hardware sold separately MAXIMUM Max. Axial LOAD RTG. Travel Pipe (LBS) (Inches) Size On on Pipe Pipe Roll Roll 2 1/2 225 2 3 250 2 3 1/2 300 2 4 350 2 5 450 2 6 500 2 8 625 2 10 875 4 12 1400 4 14 1475 4 16 1650 4 18 1800 4 20 1875 4 24 2050 4 4 36 2250 4 30 2250 4 TABLE I 42 2250 Contact factory for other dimensions, temperatures, and loads. Available in all insulation thicknesses. Note: For higher load ratings, see A8200 The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information.
  • 25. A11 MODEL A8200 Insulated Pipe Support Heavy Duty with load bearing plate Features: · Compact · Easy Installation · Eliminates welding to pipe · Copper tubing sizes available · Minimizes heat-loss and/or condensation · Insulating structural inserts for load transfer · Overlapping galvanized sheet metal jacket · Other I.D.'s and/or O.D.'s available on request · Load distribution plate integral with bottom jacket Performance Test Results on File: Available upon request. Material Data: · A8200: Applicable PSI spec. doc.: No. 205. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTM A-527. · Structural Inserts: High-density calcium silicate asbestos-free, treated with water repellant. · Load distribution Plate: Carbon steel ASTM A-36 · Coating: Primer coated or hot-dip galvanized. Other coatings available upon request. · Glue: Industrial contact adhesive. Formal Submittal Sheets available Application: Model A8200 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam · Air · Chilled Water · Dual Temperature Intended for installation on: · Pipe rolls · Flat surface, see A7200 · Clevis hangers, see A9000 Note: Up to 1700°F available upon request. Temperature Range: °F to +1200°F+40 FRONEK GROUP CATALOG PS-2004 A B C 12 9 1/2 12 9 1/2 12 9 5/8 12 9 5/8 12 9 5/8 12 9 3/4 12 9 3/4 12 9 3/4 12 9 1 12 9 1 12 9 1 12 9 1 Hardware sold separately Note: For higher load ratings, see A8400, B1100 The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information. TABLE I Contact factory for other dimensions, temperatures, and loads. Available in all insulation thicknesses. 36 4050 3 42 4050 3 24 3675 3 30 4050 3 18 3200 3 20 3375 3 14 2650 3 16 2950 3 10 1375 3 12 2550 3 6 900 3 8 1125 3 Pipe Pipe Roll Roll Pipe (LBS) (Inches) Size On on MAXIMUM Max. Axial LOAD RTG. Travel
  • 26. A12 MODEL A8400 Insulated Pipe Support Heavy Duty with load bearing plate Features: · Compact · Easy Installation · Eliminates welding to pipe · Copper tubing sizes available · Minimizes heat-loss and/or condensation · Insulating structural inserts for load transfer · Overlapping galvanized sheet metal jacket · Other I.D.'s and/or O.D.'s Available on request · Load distribution plate integral with bottom jacket Performance Test Results on File: Available upon request. Material Data: · A8400: Applicable PSI spec. doc.: No. 205. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTM A-527. · Structural Inserts: High-density calcium silicate asbestos-free, treated with water · Load distribution Plate: Carbon steel ASTM A-36 · Coating: Primer coated or hot-dip galvanized. Other coatings Available upon request. · Glue: Industrial contact adhesive. Formal Submittal Sheets available repellant. Application: Model A8400 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam · Air · Chilled Water · Dual Temperature Intended for installation on: · Pipe rolls · Flat surface, see A7400 · Clevis hangers, see A9000 Note: Up to 1700°F available upon request. Temperature Range: °F to +1200°F+40 FRONEK GROUP CATALOG PS-2004 A B C 12 9 1 12 9 1 12 9 1 12 9 1 12 9 1 12 9 1 12 9 1 12 9 1 Hardware sold separately MAXIMUM Max. Axial LOAD RTG. Travel Pipe (LBS) (Inches) Size On on Pipe Pipe Roll Roll 10 1875 2 1/4 12 3400 2 1/4 14 3500 2 1/4 16 3950 2 1/4 18 4300 2 1/4 20 4550 2 1/4 24 4950 2 1/4 30 5450 2 1/4 TABLE I Contact factory for other dimensions, temperatures, and loads. Available in all insulation thicknesses. Note: For higher load ratings, see B1200 The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Contact factory for current information.
  • 27. A13 MODEL A9000 Insulated Pipe Support Heavy Duty for use with rod hangers Features: · Compact · Easy Installation · Eliminates welding to pipe · Overlapping galvanized sheet metal jacket · Minimizes heat-loss and/or condensation · Insulating structural inserts for load transfer · Copper Tubing available · Other I.D.'s and/or O.D.'s available on request Performance Test Results on File: Available upon request. Material Data: · A9000: Applicable PSI spec. doc.: No. 205. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTM A-527. · Structural Inserts : High-density calcium silicate asbestos-free, treated with water repellant. · Glue: Industrial contact adhesive. Formal Submittal Sheets available Application: Model A9000 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam · Air · Chilled Water · Dual Temperature Intended for installation on: · Band, ring or clevis pipe hangers · Flat surfaces, see A7000 · Pipe rolls, see A8000 Note: Up to 1700°F available upon request. Temperature Range: °F to +1200°F+40 FRONEK GROUP CATALOG PS-2004 Hardware sold separately A B A B A B A B A B A B A B A B A B 4 24 4 24 4 24 4 24 4 24 4 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 24 6 20 6 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20 6 20 6 20 6 20 6 20 9 20 9 20 9 20 6 20 6 20 6 20 6 20 9 16 9 16 9 16 9 16 9 16 9 16 9 16 9 16 9 16 12 16 12 16 12 16 12 16 12 16 12 16 18 16 18 16 18 16 18 16 18 16 18 1620 - 24 TABLE II "B" = gauge of sheet metal jacket (bottom jacket approx. 2 X ga. of top jacket) 8 - 10 8 1/8 -10 1/8 12 - 18 12 1/8 5 5 1/8 6 - 7 6 1/8 5/8-1 5/8 2 2 1/8 2 1/2 - 4 2 5/8 - 4 1/8 1/2 3/4 1 1/2 - 1 1/2 3 1/2 4 Tubing Size Size O.D. 1 1/2 2 2 1/2 3Pipe TABLE I Iron Insulation Thickness Copper Contact factory for other dimensions, temperatures, loads. Available in all insulation thicknesses. To develop maximum load rating use band, ring or clevis hanger with manufacturer's load rating equal to or greater than values shown in Table I. 20 2400 24 2750 Note: For higher load ratings, see D1000, D3000 The load ratings represent average values obtained in accordance with accepted methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. 6 600 8 900 16 18 1200 1450 4 400 5 550 3 300 3 1/2 350 2 175 2 1/2 250 1 1/4 100 1 1/2 130 1/2 50 55 80 3/4 1 or Clevis Hanger (a) Size MAXIMUM (LBS) In RingPipe LOAD RTG. 1650 1900 2150 10 12 14
  • 29. INTRODUCTION SECTION “B” INTRODUCTION SECTION “B” PRE-INSULATED PIPE SUPPORTS - Base Mounted APPLICATION – Heavy Industrial and Large HVAC Distribution Systems Features: · Accommodation of thermal movement · Provision or lateral guide or restraint · Minimization of side friction loads · Wide range of maximum load requirements for each pipe size In each model number series (for example: B1000 through B1300 Series), the higher the model number, the higher the load rating. Models B1000 - B1300 Sliding supports free to travel axially and laterally. Models B2000 - B2300 Same as B1000 - B1300 except can accommodate greater axial travel. Models B3000 - B3300 Sliding supports with lateral guides. Models B4000 - B4300 Same as B3000 - B3300 except can accommodate greater axial travel. Models B5000 - B5300 Same as B1000 - B1300 except can accommodate greater lateral travel. Models B6000 - B6300 Same as B2000 - B2300 except can accommodate greater lateral travel. Models B7000 - B7300 Same as B3000 - B3300 except with reduced vertical load ratings to allow greater lateral loads. Minimum side friction is assured by the addition of lateral slide pads. Models B8000 - B8300 Same as B4000 - B4300 except with reduced vertical load ratings to allow greater lateral loads. Minimum side friction is assured by the addition of lateral slide pads. To meet special thermal movement requirements, Pipe Shields Inc. has provided supports that have accommodated axial travels in excess of five (5) feet. By modifying our standard pipe support concept with combinations of structural insulation materials, steel base and strap design, and slide plate configuration, we can readily and economically respond to virtually any pipe support requirement. If your requirements are not covered by the Product Data Sheets in this catalog, please contact us at 713-731-0030 or 1-800-787-5914. Please acquaint yourself with the selection guide at the front of this catalog and the section index on the page following this introduction, for assistance in determining the most appropriate support for your application. FRONEK GROUP CATALOG PS-2004
  • 30. PIPE SIZE LATERAL MODEL RANGE AXIAL LATERAL GUIDE DUTY B1000 1/2 - 42 1.5 1.5 NO MEDIUM B1100 1/2 - 42 1.5 1.5 NO HEAVY B1200 1/2 - 42 1.5 1.5 NO HEAVIER B1300 1/2 - 42 1.5 1.5 NO HEAVIEST B2000 1/2 - 42 4.5 1.5 NO MEDIUM B2100 1/2 - 42 4.5 1.5 NO HEAVY B2200 1/2 - 42 4.5 1.5 NO HEAVIER B2300 1/2 - 42 4.5 1.5 NO HEAVIEST B3000 1/2 - 42 1.5 0 YES MEDIUM B3100 1/2 - 42 1.5 0 YES HEAVY B3200 1/2 - 42 1.5 0 YES HEAVIER B3300 1/2 - 42 1.5 0 YES HEAVIEST B4000 1/2 - 42 4.5 0 YES MEDIUM B4100 1/2 - 42 4.5 0 YES HEAVY B4200 1/2 - 42 4.5 0 YES HEAVIER B4300 1/2 - 42 4.5 0 YES HEAVIEST PRE-INSULATED PIPE SUPPORTS HEAVY INDUSTRIAL - BASE MOUNTED TRAVEL (INCHES) +/- SECTION “B” INDEX FRONEK GROUP CATALOG PS-2004
  • 31. PIPE SIZE LATERAL MODEL RANGE AXIAL LATERAL GUIDE DUTY B5000 1/2 - 42 1.5 1.5 - 4.5 NO MEDIUM B5100 1/2 - 42 1.5 1.5 - 4.5 NO HEAVY B5200 1/2 - 42 1.5 1.5 - 4.5 NO HEAVIER B5300 1/2 - 42 1.5 1.5 - 4.5 NO HEAVIEST B6000 1/2 - 42 4.5 1.5 - 4.5 NO MEDIUM B6100 1/2 - 42 4.5 1.5 - 4.5 NO HEAVY B6200 1/2 - 42 4.5 1.5 - 4.5 NO HEAVIER B6300 1/2 - 42 4.5 1.5 - 4.5 NO HEAVIEST B7000 1/2 - 42 1.5 0 W/SLIDE PADS MEDIUM B7100 1/2 - 42 1.5 0 W/SLIDE PADS HEAVY B7200 1/2 - 42 1.5 0 W/SLIDE PADS HEAVIER B7300 1/2 - 42 1.5 0 W/SLIDE PADS HEAVIEST B8000 1/2 - 42 4.5 0 W/SLIDE PADS MEDIUM B8100 1/2 - 42 4.5 0 W/SLIDE PADS HEAVY B8200 1/2 - 42 4.5 0 W/SLIDE PADS HEAVIER B8300 1/2 - 42 4.5 0 W/SLIDE PADS HEAVIEST PRE-INSULATED PIPE SUPPORTS HEAVY INDUSTRIAL - BASE MOUNTED TRAVEL (INCHES) +/- SECTION “B” INDEX FRONEK GROUP CATALOG PS-2004
  • 32. SECTION “B” INDEX TO ORDER, specify: 1. Quantity 20 2. Pipe Size & Type 18” IPS 3. Insulation Thickness 2” 4. Model Number B1000 EXAMPLE: (20) 18 x 2 B1000 FRONEK GROUP CATALOG PS-2004 PIPE SIZE 3 1/2 4 1/2 5 1/2 6 1/2 3 6 6 8 8 3 1/2 6 6 8 8 4 6 6 8 8 5 6 6 8 8 6 6 6 8 8 8 6 8 8 10 10 6 8 8 10 12 6 8 8 10 14 6 8 8 10 16 6 8 8 10 18 6 8 8 10 20 6 8 8 10 24 6 8 8 10 30 8 8 10 10 36 8 8 10 10 42 8 8 10 10 The Table above provides Bottom-of-Pipe to Top-of Steel dimensions ("B" dimensions) for 3 1/2", 4 1/2", 5 1/2" and 6 1/2 " insulation thicknesses. Check with your salesperson if you require a "B" dimension other than those shown in this table. INSULATION THICKNESS THE FOLLOWING TABLE ILLUSTRATES BOTTOM-OF-PIPE TO TOP-OF STEEL DIMENSIONS (DIMENSION "B") FOR "B" MODEL PIPE SUPPORTS AND "C" MODEL PIPE ANCHORS FOR INTERMEDIATE INSULATION THICKNESS
  • 33. B1 Application: Model B1000 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam · Air · Dual Temperature · Chilled Water Intended for installation on: · Flat Surfaces Temperature Range: +40°F to +1200°F Note: Up to 1700° F available upon request. Features: · All pipe sizes · Easy Installation · Eliminates welding to pipe · Overlapping galvanized sheet metal jacket · Insulating structural inserts for load transfer · Stainless steel to UHMW polyethylene slide · Other I.D.'s and/or O.D.'s available on request · Factory mounted polyethylene slide pad on steel mounting plate Performance Test Results on File: Available upon request. Material Data: · B1000: Applicable PSI spec. doc.: No. 209. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTMA-527. · Glue: Industrial contact adhesive · Structural Inserts: High-density calcium silicate asbestos free, treated with water repellant. · Steel Straps/Base: Carbon Steel ASTM A-36. · Fasteners: ASTM A-307 plated. · Slide Pad: UHMW Polythylene (Teflon Optional). · Coating: Primer coated or hot dipped galvanized. Other coatings available upon request. Formal Submittal Sheets available. Heavy Duty, Base MountedMODEL B1000 Sliding Insulated Pipe Support FRONEK GROUP CATALOG PS-2004 The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Note: For higher load ratings, see: B1100 - For greater axial travel, see: B2000 - For lateral restraint, see: B3000 - For lateral travel, see: B5000 Pipe Vert. Size Load B C E B C E B C E B C E B C E B C E B C E 1/2 140 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125 3/4 175 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125 1 225 4 2 3.875 4 2.5 4.875 4 3 5.937 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25 1 1/2 325 4 2 4.375 4 2.5 5.5 4 4 7 4 4.5 8 6 5.5 9 6 7.5 11.25 8 9 13.25 2 375 4 2.5 5 4 3 6.0625 4 4 7 4 4.5 8 6 5.5 9.125 6 7.5 11.25 8 9 13.25 2 1/2 460 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5 3 530 4 3 6.062 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625 4 840 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625 5 1050 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 4 7.5 11.375 6 8 12.375 6 9.5 14.875 8 11 16.875 6 1275 4 5.5 9.25 4 6.5 10.25 4 7.5 11.375 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875 8 1700 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 17.875 8 13 20.125 10 2000 4 9 13.625 4 9.5 14.875 4 10.5 15.875 6 11 16.875 6 12 18.125 6 13 20.125 8 14.5 22.125 12 2200 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125 14 2500 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125 16 2900 4 12.5 19.125 4 13 20.125 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375 18 3200 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375 20 3400 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375 24 3600 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375 30 4700 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625 36 5500 4 26.5 39.625 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125 42 6200 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125 Contact factory for other dimensional, temperature, load, or axial travel, requirements. Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
  • 34. B2 Heavy Duty, Base MountedMODEL B1100 Sliding Insulated Pipe Support Application: Model B1100 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam · Air · Dual Temperature · Chilled Water Intended for installation on: · Flat Surfaces Temperature Range: +40°F to +1200°F Note: Up to 1700° F available upon request. Features: · All pipe sizes · Easy Installation · Eliminates welding to pipe · Overlapping galvanized sheet metal jacket · Insulating structural inserts for load transfer · Stainless steel to UHMW polyethylene slide · Other I.D.'s and/or O.D.'s available on request · Factory mounted polyethylene slide pad on steel mounting plate Performance Test Results on File: Available upon request. Material Data: · B1100: Applicable PSI spec. doc.: No. 209. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTMA-527. · Glue: Industrial contact adhesive · Structural Inserts: High-density calcium silicate asbestos free, treated with water repellant. · Steel Straps/Base: Carbon Steel ASTM A-36. · Fasteners: ASTM A-307 plated. · Slide Pad: UHMW Polythylene (Teflon Optional). · Coating: Primer coated or hot dipped galvanized. Other coatings available upon request. Formal Submittal Sheets available. FRONEK GROUP CATALOG PS-2004 The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Note: For higher load ratings, see: B1200 - For greater axial travel, see: B2100 - For lateral restraint, see: B3100 - For lateral travel, see: B5100 Pipe Vert. Size Load B C E B C E B C E B C E B C E B C E B C E 1/2 280 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125 3/4 350 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25 1 450 4 2 3.875 4 2.5 5 4 3 6.062 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25 1 1/2 650 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25 2 750 4 2.5 5 4 3 6.0625 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25 2 1/2 920 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5 3 1060 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625 4 1680 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625 5 2100 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875 6 2550 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875 8 3400 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125 10 4000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125 12 4400 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125 14 5000 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125 16 5800 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375 18 6400 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375 20 6800 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375 24 7200 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375 30 9400 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625 36 11000 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125 42 12400 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125 Contact factory for other dimensional, temperature, load, or axial travel, requirements. Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
  • 35. B3 Heavy Duty, Base MountedMODEL B1200 Sliding Insulated Pipe Support Application: Model B1200 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam · Air · Dual Temperature · Chilled Water Intended for installation on: · Flat Surfaces Temperature Range: +40°F to +1200°F Note: Up to 1700° F available upon request. Features: · All pipe sizes · Easy Installation · Eliminates welding to pipe · Overlapping galvanized sheet metal jacket · Insulating structural inserts for load transfer · Stainless steel to UHMW polyethylene slide · Other I.D.'s and/or O.D.'s available on request · Factory mounted polyethylene slide pad on steel mounting plate Performance Test Results on File: Available upon request. Material Data: · B1200: Applicable PSI spec. doc.: No. 209. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTM A-527. · Glue: Industrial contact adhesive · Structural Inserts: High-density calcium silicate asbestos free, treated with water repellant. · Steel Straps/Base: Carbon Steel ASTM A-36. · Fasteners: ASTM A-307 plated. · Slide Pad: UHMW Polyethylene (Teflon Optional). · Coating: Primer coated or hot dipped galvanized. Other coatings available upon request. Formal Submittal Sheets available. FRONEK GROUP CATALOG PS-2004 Contact factory for other dimensional, temperature, load, or axial travel, requirements. The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Note: For higher load ratings, see: B1300 - For greater axial travel, see: B2200 - For lateral restraint, see: B3200 - For lateral travel, see: B5200 Pipe Vert. Size Load B C E B C E B C E B C E B C E B C E B C E 1/2 400 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125 3/4 500 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25 1 650 4 2 4 4 2.5 5 4 3 6.062 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25 1 1/2 950 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25 2 1100 4 2.5 5 4 3 6.1875 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25 2 1/2 1350 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5 3 1600 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625 4 2500 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625 5 3100 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875 6 3800 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875 8 5100 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125 10 6000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125 12 6600 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125 14 7500 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125 16 8700 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375 18 9600 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375 20 10200 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375 24 10800 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375 30 14100 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625 36 16500 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125 42 18600 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125 Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
  • 36. B4 Heavy Duty, Base MountedMODEL B1300 Sliding Insulated Pipe Support Application: Model B1300 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam · Air · Dual Temperature · Chilled Water Intended for installation on: · Flat Surfaces Temperature Range: +40°F to +1200°F Note: Up to 1700° F available upon request. Features: · All pipe sizes · Easy Installation · Eliminates welding to pipe · Overlapping galvanized sheet metal jacket · Insulating structural inserts for load transfer · Stainless steel to UHMW polyethylene slide · Other I.D.'s and/or O.D.'s available on request · Factory mounted polyethylene slide pad on steel mounting plate Performance Test Results on File: Available upon request. Material Data: · B1300: Applicable PSI spec. doc.: No. 209. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTM A-527. · Glue: Industrial contact adhesive · Structural Inserts: High-density calcium silicate asbestos free, treated with water repellant. · Steel Straps/Base: Carbon Steel ASTM A-36. · Fasteners: ASTM A-307 plated. · Slide Pad: UHMW Polyethylene (Teflon Optional). · Coating: Primer coated or hot dipped galvanized. Other coatings available upon request. Formal Submittal Sheets available. FRONEK GROUP CATALOG PS-2004 Contact factory for other dimensional, temperature, load, or axial travel, requirements. The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Note: For greater axial travel, see: B2300 - For lateral restraint, see: B3300 - For lateral travel, see: B5300 Pipe Vert. Size Load B C E B C E B C E B C E B C E B C E B C E 1/2 550 4 1.5 3.375 4 2 4.5 4 2.5 5.5 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25 3/4 700 4 1.5 3.375 4 2 4.5 4 2.5 5.5 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25 1 900 4 2 4 4 2.5 5 4 3 6.062 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25 1 1/2 1300 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25 2 1500 4 2.5 5 4 3 6.0625 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25 2 1/2 1800 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625 3 2100 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625 4 3350 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625 5 4200 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875 6 5100 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875 8 6800 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125 10 8000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125 12 8800 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125 14 10000 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125 16 11600 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375 18 12800 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375 20 13600 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375 24 14400 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375 30 18800 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625 36 22000 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125 42 24800 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125 Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
  • 37. B5 Heavy Duty, Base MountedMODEL B2000 Sliding Insulated Pipe Support Application: Model B2000 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam · Air · Dual Temperature · Chilled Water Intended for installation on: · Flat Surfaces Temperature Range: +40°F to +1200°F Note: Up to 1700° F available upon request. Features: · All pipe sizes · Easy Installation · Eliminates welding to pipe · Overlapping galvanized sheet metal jacket · Insulating structural inserts for load transfer · Stainless steel to UHMW polyethylene slide · Other I.D.'s and/or O.D.'s available on request · Factory mounted polyethylene slide pad on steel mounting plate Performance TestResults on File: Available upon request. Material Data: · B2000: Applicable PSI spec. doc.: No. 209. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTM A-527. · Glue: Industrial contact adhesive · Structural Inserts: High-density calcium silicate asbestos free, treated with water repellant. · Steel Straps/Base: Carbon Steel ASTM A-36. · Fasteners: ASTM A-307 plated. · Slide Pad: UHMW Polyethylene (Teflon Optional). · Coating: Primer coated or hot dipped galvanized. Other coatings available upon request. Formal Submittal Sheets available. FRONEK GROUP CATALOG PS-2004 Contact factory for other dimensional, temperature, load, or axial travel, requirements. The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Note: For higher load ratings, see: B2100 - For lesser axial travel, see: B1000 - For lateral restraint, see: B4000 - For lateral travel, see: B6000 Pipe Vert. Size Load B C E B C E B C E B C E B C E B C E B C E 1/2 140 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125 3/4 175 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125 1 225 4 2 3.875 4 2.5 4.875 4 3 5.937 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25 1 1/2 325 4 2 4.375 4 2.5 5.5 4 4 7 4 4.5 8 6 5.5 9 6 7.5 11.25 8 9 13.25 2 375 4 2.5 5 4 3 6.0625 4 4 7 4 4.5 8 6 5.5 9.125 6 7.5 11.25 8 9 13.25 2 1/2 460 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5 3 530 4 3 6.062 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625 4 840 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625 5 1050 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 4 7.5 11.375 6 8 12.375 6 9.5 14.875 8 11 16.875 6 1275 4 5.5 9.25 4 6.5 10.25 4 7.5 11.375 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875 8 1700 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 17.875 8 13 20.125 10 2000 4 9 13.625 4 9.5 14.875 4 10.5 15.875 6 11 16.875 6 12 18.125 6 13 20.125 8 14.5 22.125 12 2200 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125 14 2500 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125 16 2900 4 12.5 19.125 4 13 20.125 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375 18 3200 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375 20 3400 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375 24 3600 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375 30 4700 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625 36 5500 4 26.5 39.625 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125 42 6200 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125 Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
  • 38. B6 Heavy Duty, Base MountedMODEL B2100 Sliding Insulated Pipe Support Application: Model B2100 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam ·Air · Dual Temperature · Chilled Water Intended for installation on: · Flat Surfaces Temperature Range: +40°F to +1200°F Note: Up to 1700° F available upon request. Features: · All pipe sizes · Easy Installation · Eliminates welding to pipe · Overlapping galvanized sheet metal jacket · Insulating structural inserts for load transfer · Stainless steel to UHMW polyethylene slide · Other I.D.'s and/or O.D.'s available on request · Factory mounted polyethylene slide pad on steel mounting plate Performance Test Results on File: Available upon request. Material Data: · B2100: Applicable PSI spec. doc.: No. 209. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTMA-527. · Glue: Industrial contact adhesive · Structural Inserts: High-density calcium silicate asbestos free, treated with water repellant. · Steel Straps/Base: Carbon Steel ASTM A-36. · Fasteners: ASTM A-307 plated. · Slide Pad: UHMW Polyethylene (Teflon Optional). · Coating: Primer coated or hot dipped galvanized. Other coatings available upon request. Formal Submittal Sheets available. FRONEK GROUP CATALOG PS-2004 Contact factory for other dimensional, temperature, load, or axial travel, requirements. The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Note: For higher load ratings, see: B2200 - For lesser axial travel, see: B1100 - For lateral restraint, see: B4100 - For lateral travel, see: B6100 Pipe Vert. Size Load B C E B C E B C E B C E B C E B C E B C E 1/2 280 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125 3/4 350 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25 1 450 4 2 3.875 4 2.5 5 4 3 6.062 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25 1 1/2 650 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25 2 750 4 2.5 5 4 3 6.0625 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25 2 1/2 920 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5 3 1060 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625 4 1680 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625 5 2100 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875 6 2550 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875 8 3400 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125 10 4000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125 12 4400 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125 14 5000 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125 16 5800 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375 18 6400 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375 20 6800 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375 24 7200 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375 30 9400 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625 36 11000 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125 42 12400 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125 Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
  • 39. B7 Heavy Duty, Base MountedMODEL B2200 Sliding Insulated Pipe Support Application: Model B2200 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam ·Air · Dual Temperature · Chilled Water Intended for installation on: · Flat Surfaces Temperature Range: +40°F to +1200°F Note: Up to 1700° F available upon request. Features: · All pipe sizes · Easy Installation · Eliminates welding to pipe · Overlapping galvanized sheet metal jacket · Insulating structural inserts for load transfer · Stainless steel to UHMW polyethylene slide · Other I.D.'s and/or O.D.'s available on request · Factory mounted polyethylene slide pad on steel mounting plate Performance Test Results on File: Available upon request. Material Data: · B2200: Applicable PSI spec. doc.: No. 209. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTMA-527. · Glue: Industrial contact adhesive · Structural Inserts: High-density calcium silicate asbestos free, treated with water repellant. · Steel Straps/Base: Carbon Steel ASTM A-36. · Fasteners: ASTM A-307 plated. · Slide Pad: UHMW Polyethylene (Teflon Optional). · Coating: Primer coated or hot dipped galvanized. Other coatings available upon request. Formal Submittal Sheets available. FRONEK GROUP CATALOG PS-2004 Contact factory for other dimensional, temperature, load, or axial travel, requirements. The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Note: For higher load ratings, see: B2300 - For lesser axial travel, see: B1200 - For lateral restraint, see: B4200 - For lateral travel, see: B6200 Pipe Vert. Size Load B C E B C E B C E B C E B C E B C E B C E 1/2 400 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.125 3/4 500 4 1.5 3.25 4 2 4.375 4 2.5 5.375 4 4 7 6 4.5 8 6 6.5 10 8 8 12.25 1 650 4 2 4 4 2.5 5 4 3 6.062 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25 1 1/2 950 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25 2 1100 4 2.5 5 4 3 6.1875 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25 2 1/2 1350 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.25 8 9.5 14.5 3 1600 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625 4 2500 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625 5 3100 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875 6 3800 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875 8 5100 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125 10 6000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125 12 6600 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125 14 7500 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125 16 8700 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375 18 9600 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375 20 10200 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375 24 10800 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375 30 14100 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625 36 16500 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125 42 18600 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125 Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
  • 40. B8 Heavy Duty, Base MountedMODEL B2300 Sliding Insulated Pipe Support Application: Model B2300 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam · Air · Dual Temperature · Chilled Water Intended for installation on: · Flat Surfaces Temperature Range: +40°F to +1200°F Note: Up to 1700° F available upon request. Features: · All pipe sizes · Easy Installation · Eliminates welding to pipe · Overlapping galvanized sheet metal jacket · Insulating structural inserts for load transfer · Stainless steel to UHMW polyethylene slide · Other I.D.'s and/or O.D.'s available on request · Factory mounted polyethylene slide pad on steel mounting plate Performance Test Results on File: Available upon request. Material Data: · B2300: Applicable PSI spec. doc.: No. 209. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTM A-527. · Glue: Industrial contact adhesive · Structural Inserts: High-density calcium silicate asbestos free, treated with water repellant. · Steel Straps/Base: Carbon Steel ASTM A-36. · Fasteners: ASTM A-307 plated. · Slide Pad: UHMW Polyethylene (Teflon Optional). · Coating: Primer coated or hot dipped galvanized. Other coatings available upon request. Formal Submittal Sheets available. FRONEK GROUP CATALOG PS-2004 Contact factory for other dimensional, temperature, load, or axial travel, requirements. The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Note: For lesser axial travel, see: B1300 - For lateral restraint, see: B4300 - For lateral travel, see: B6300 Pipe Vert. Size Load B C E B C E B C E B C E B C E B C E B C E 1/2 550 4 1.5 3.375 4 2 4.5 4 2.5 5.5 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25 3/4 700 4 1.5 3.375 4 2 4.5 4 2.5 5.5 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25 1 900 4 2 4 4 2.5 5 4 3 6.062 4 4 7.125 6 4.5 8.125 6 6.5 10.125 8 8 12.25 1 1/2 1300 4 2 4.5 4 2.5 5.5 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25 2 1500 4 2.5 5 4 3 6.0625 4 4 7.125 4 4.5 8.125 6 5.5 9.125 6 7.5 11.25 8 9 13.25 2 1/2 1800 4 2.5 5.5 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625 3 2100 4 3 6.187 4 4 7.125 4 4.5 8.125 4 5.5 9.125 6 6.5 10.125 6 8 12.375 8 9.5 14.625 4 3350 4 4 7.25 4 4.5 8.25 4 5.5 9.25 4 6.5 10.25 6 7.5 11.375 6 9 13.375 8 10.5 15.625 5 4200 4 4.5 8.5 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 6 8 12.625 6 9.5 14.875 8 11 16.875 6 5100 4 5.5 9.5 4 6.5 10.5 4 7.5 11.625 4 8 12.625 6 9 13.625 6 10.5 15.875 8 12 17.875 8 6800 4 7.5 11.625 4 8 12.625 4 9 13.625 6 9.5 14.875 6 10.5 15.875 6 12 18.125 8 13 20.125 10 8000 4 9 13.875 4 9.5 15.125 4 10.5 16.125 6 11 17.125 6 12 18.125 6 13 20.125 8 14.5 22.125 12 8800 4 10.5 16.125 4 11 17.125 4 12 18.125 6 12.5 19.125 6 13 20.125 6 14.5 22.125 8 16 24.125 14 10000 4 11 17.125 4 12 18.125 4 12.5 19.125 6 13 20.125 6 14 21.125 6 15.5 23.125 8 16.5 25.125 16 11600 4 12.5 19.375 4 13 20.375 6 14 21.375 6 14.5 22.375 6 15.5 23.375 8 16.5 25.375 8 18 27.375 18 12800 4 14 21.375 4 14.5 22.375 6 15.5 23.375 6 16 24.375 6 16.5 25.375 8 18 27.375 8 19.5 29.375 20 13600 4 15.5 23.375 4 16 24.375 6 16.5 25.375 6 17.5 26.375 6 18 27.375 8 19.5 29.375 8 21 31.375 24 14400 4 18 27.375 4 19 28.375 6 19.5 29.375 6 20.5 30.375 6 21 31.375 8 22.5 33.375 8 24 35.375 30 18800 4 22.5 33.625 6 23 34.625 6 24 35.625 6 24.5 36.625 6 25 37.625 8 26.5 39.625 8 28 41.625 36 22000 4 26.5 40.125 6 27.5 41.125 6 28 42.125 6 28.5 43.125 6 29.5 44.125 8 31 46.125 8 32.5 48.125 42 24800 4 31 46.125 6 31.5 47.125 6 32.5 48.125 6 33 49.125 6 33.5 50.125 8 35 52.125 8 36.5 54.125 Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
  • 41. B9 Heavy Duty, Base MountedMODEL B3000 Guided Insulated Pipe Support Application: Model B3000 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam · Air · Dual Temperature · Chilled Water Intended for installation on: · Flat Surfaces Temperature Range: +40°F to +1200°F Note: Up to 1700° F available upon request. Features: · All pipe sizes · Easy Installation · Eliminates welding to pipe · Overlapping galvanized sheet metal jacket · Insulating structural inserts for load transfer · Stainless steel to UHMW polyethylene slide · Other I.D.'s and/or O.D.'s available on request · Factory mounted polyethylene slide pad on steel mounting plate Performance Test Results on File: Available upon request. Material Data: · B3000: Applicable PSI spec. doc.: No. 209. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTM A-527. · Glue: Industrial contact adhesive · Structural Inserts: High-density calcium silicate asbestos free, treated with water repellant. · Steel Straps/Base: Carbon Steel ASTM A-36. · Fasteners: ASTM A-307 plated. · Slide Pad: UHMW Polyethylene (Teflon Optional). · Coating: Primer coated or hot dipped galvanized. Other coatings available upon request. Formal Submittal Sheets available. FRONEK GROUP CATALOG PS-2004 Contact factory for other dimensional, temperature, load, or axial travel, requirements. If lateral load is greater than 20% of vertical load, contact factory. The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Note: For higher load ratings, see: B3100 - For greater axial travel, see: B4000 - For lateral travel, see: B5000 Pipe Vert. Size Load B C E B C E B C E B C E B C E B C E B C E 1/2 140 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.125 3/4 175 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.125 1 225 4 6.5 3.875 4 7 4.875 4 7.5 5.937 4 8.5 7 6 9 8 6 11 10 8 12.5 12.25 1 1/2 325 4 6.5 4.375 4 7 5.5 4 8.5 7 4 9 8 6 10 9 6 12 11.25 8 13.5 13.25 2 375 4 7 5 4 7.5 6.0625 4 8.5 7 4 9 8 6 10 9.125 6 12 11.25 8 13.5 13.25 2 1/2 460 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.25 8 14 14.5 3 530 4 7.5 6.062 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625 4 840 4 8.5 7.25 4 9 8.25 4 10 9.25 4 11 10.25 6 12 11.375 6 13.5 13.375 8 15 15.625 5 1050 4 10 8.25 4 11 9.25 4 12 10.25 4 13 11.375 6 13.5 12.375 6 15 14.875 8 16.5 16.875 6 1275 4 11 9.25 4 12 10.25 4 13 11.375 4 13.5 12.625 6 14.5 13.625 6 16 15.875 8 17.5 17.875 8 1700 4 13.5 11.625 4 14 12.625 4 15 13.625 6 15.5 14.875 6 16.5 15.875 6 18 17.875 8 19 20.125 10 2000 4 15 13.625 4 15.5 14.875 4 16.5 15.875 6 17 16.875 6 18 18.125 6 19 20.125 8 20.5 22.125 12 2200 4 17 16.125 4 17.5 17.125 4 18.5 18.125 6 19 19.125 6 19.5 20.125 6 21 22.125 8 22.5 24.125 14 2500 4 17.5 17.125 4 18.5 18.125 4 19 19.125 6 19.5 20.125 6 20.5 21.125 6 22 23.125 8 23 25.125 16 2900 4 20.5 19.125 4 21 20.125 6 22 21.375 6 22.5 22.375 6 23.5 23.375 8 24.5 25.375 8 26 27.375 18 3200 4 22 21.375 4 22.5 22.375 6 23.5 23.375 6 24 24.375 6 24.5 25.375 8 26 27.375 8 27.5 29.375 20 3400 4 23.5 23.375 4 24 24.375 6 24.5 25.375 6 25.5 26.375 6 26 27.375 8 27.5 29.375 8 29 31.375 24 3600 4 26 27.375 4 27 28.375 6 27.5 29.375 6 28.5 30.375 6 29 31.375 8 30.5 33.375 8 32 35.375 30 4700 4 32.5 33.625 6 33 34.625 6 34 35.625 6 34.5 36.625 6 35 37.625 8 36.5 39.625 8 38 41.625 36 5500 4 36.5 39.625 6 37.5 41.125 6 38 42.125 6 38.5 43.125 6 39.5 44.125 8 41 46.125 8 42.5 48.125 42 6200 4 41 46.125 6 41.5 47.125 6 42.5 48.125 6 43 49.125 6 43.5 50.125 8 45 52.125 8 46.5 54.125 Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
  • 42. B10 Heavy Duty, Base MountedMODEL B3100 Guided Insulated Pipe Support Application: Model B3100 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam · Air · Dual Temperature · Chilled Water Intended for installation on: · Flat Surfaces Temperature Range: +40°F to +1200°F Note: Up to 1700° F available upon request. Features: · All pipe sizes · Easy Installation · Eliminates welding to pipe · Overlapping galvanized sheet metal jacket · Insulating structural inserts for load transfer · Stainless steel to UHMW polyethylene slide · Other I.D.'s and/or O.D.'s available on request · Factory mounted polyethylene slide pad on steel mounting plate Performance Test Results on File: Available upon request. Material Data: · B3100: Applicable PSI spec. doc.: No. 209. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTM A-527. · Glue: Industrial contact adhesive · Structural Inserts: High-density calcium silicate asbestos free, treated with water repellant. · Steel Straps/Base: Carbon Steel ASTM A-36. · Fasteners: ASTM A-307 plated. · Slide Pad: UHMW Polyethylene (Teflon Optional). · Coating: Primer coated or hot dipped galvanized. Other coatings available upon request. Formal Submittal Sheets available. FRONEK GROUP CATALOG PS-2004 Contact factory for other dimensional, temperature, load, or axial travel, requirements. If lateral load is greater than 20% of vertical load, contact factory. The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Note: For higher load ratings, see: B3200 - For greater axial travel, see: B4100 - For lateral travel, see: B5100 Pipe Vert. Size Load B C E B C E B C E B C E B C E B C E B C E 1/2 280 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.125 3/4 350 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.25 1 450 4 6.5 3.875 4 7 5 4 7.5 6.062 4 8.5 7 6 9 8 6 11 10 8 12.5 12.25 1 1/2 650 4 6.5 4.5 4 7 5.5 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25 2 750 4 7 5 4 7.5 6.0625 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25 2 1/2 920 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.25 8 14 14.5 3 1060 4 7.5 6.187 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625 4 1680 4 8.5 7.25 4 9 8.25 4 10 9.25 4 11 10.25 6 12 11.375 6 13.5 13.375 8 15 15.625 5 2100 4 10 8.5 4 11 9.5 4 12 10.5 4 13 11.625 6 13.5 12.625 6 15 14.875 8 16.5 16.875 6 2550 4 11 9.5 4 12 10.5 4 13 11.625 4 13.5 12.625 6 14.5 13.625 6 16 15.875 8 17.5 17.875 8 3400 4 13.5 11.625 4 14 12.625 4 15 13.625 6 15.5 14.875 6 16.5 15.875 6 18 18.125 8 19 20.125 10 4000 4 15 13.875 4 15.5 15.125 4 16.5 16.125 6 17 17.125 6 18 18.125 6 19 20.125 8 20.5 22.125 12 4400 4 17 16.125 4 17.5 17.125 4 18.5 18.125 6 19 19.125 6 19.5 20.125 6 21 22.125 8 22.5 24.125 14 5000 4 17.5 17.125 4 18.5 18.125 4 19 19.125 6 19.5 20.125 6 20.5 21.125 6 22 23.125 8 23 25.125 16 5800 4 20.5 19.375 4 21 20.375 6 22 21.375 6 22.5 22.375 6 23.5 23.375 8 24.5 25.375 8 26 27.375 18 6400 4 22 21.375 4 22.5 22.375 6 23.5 23.375 6 24 24.375 6 24.5 25.375 8 26 27.375 8 27.5 29.375 20 6800 4 23.5 23.375 4 24 24.375 6 24.5 25.375 6 25.5 26.375 6 26 27.375 8 27.5 29.375 8 29 31.375 24 7200 4 26 27.375 4 27 28.375 6 27.5 29.375 6 28.5 30.375 6 29 31.375 8 30.5 33.375 8 32 35.375 30 9400 4 32.5 33.625 6 33 34.625 6 34 35.625 6 34.5 36.625 6 35 37.625 8 36.5 39.625 8 38 41.625 36 11000 4 36.5 40.125 6 37.5 41.125 6 38 42.125 6 38.5 43.125 6 39.5 44.125 8 41 46.125 8 42.5 48.125 42 12400 4 41 46.125 6 41.5 47.125 6 42.5 48.125 6 43 49.125 6 43.5 50.125 8 45 52.125 8 46.5 54.125 Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"
  • 43. B11 Heavy Duty, Base MountedMODEL B3200 Guided Insulated Pipe Support Application: Model B3200 is designed for use on: · Hot Water · Vacuum · Gas · Cold Water · Steam · Air · Dual Temperature · Chilled Water Intended for installation on: · Flat Surfaces Temperature Range: +40°F to +1200°F Note: Up to 1700° F available upon request. Features: · All pipe sizes · Easy Installation · Eliminates welding to pipe · Overlapping galvanized sheet metal jacket · Insulating structural inserts for load transfer · Stainless steel to UHMW polyethylene slide · Other I.D.'s and/or O.D.'s available on request · Factory mounted polyethylene slide pad on steel mounting plate Performance Test Results on File: Available upon request. Material Data: · B3200: Applicable PSI spec. doc.: No. 209. · Insulation: Calcium Silicate asbestos-free, treated with water repellant. · Jackets: Galvanized Steel ASTM A-527. · Glue: Industrial contact adhesive · Structural Inserts: High-density calcium silicate asbestos free, treated with water repellant. · Steel Straps/Base: Carbon Steel ASTM A-36. · Fasteners: ASTM A-307 plated. · Slide Pad: UHMW Polyethylene (Teflon Optional). · Coating: Primer coated or hot dipped galvanized. Other coatings available upon request. Formal Submittal Sheets available. FRONEK GROUP CATALOG PS-2004 Contact factory for other dimensional, temperature, load, or axial travel, requirements. If lateral load is greater than 20% of vertical load, contact factory. The load ratings represent average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. Dimensions and ratings are subject to change without notice. Note: For higher load ratings, see: B3300 - For greater axial travel, see: B4200 - For lateral travel, see: B5200 Pipe Vert. Size Load B C E B C E B C E B C E B C E B C E B C E 1/2 400 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.125 3/4 500 4 6 3.25 4 6.5 4.375 4 7 5.375 4 8.5 7 6 9 8 6 11 10 8 12.5 12.25 1 650 4 6.5 4 4 7 5 4 7.5 6.062 4 8.5 7.125 6 9 8.125 6 11 10.125 8 12.5 12.25 1 1/2 950 4 6.5 4.5 4 7 5.5 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25 2 1100 4 7 5 4 7.5 6.1875 4 8.5 7.125 4 9 8.125 6 10 9.125 6 12 11.25 8 13.5 13.25 2 1/2 1350 4 7 5.5 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.25 8 14 14.5 3 1600 4 7.5 6.187 4 8.5 7.125 4 9 8.125 4 10 9.125 6 11 10.125 6 12.5 12.375 8 14 14.625 4 2500 4 8.5 7.25 4 9 8.25 4 10 9.25 4 11 10.25 6 12 11.375 6 13.5 13.375 8 15 15.625 5 3100 4 10 8.5 4 11 9.5 4 12 10.5 4 13 11.625 6 13.5 12.625 6 15 14.875 8 16.5 16.875 6 3800 4 11 9.5 4 12 10.5 4 13 11.625 4 13.5 12.625 6 14.5 13.625 6 16 15.875 8 17.5 17.875 8 5100 4 13.5 11.625 4 14 12.625 4 15 13.625 6 15.5 14.875 6 16.5 15.875 6 18 18.125 8 19 20.125 10 6000 4 15 13.875 4 15.5 15.125 4 16.5 16.125 6 17 17.125 6 18 18.125 6 19 20.125 8 20.5 22.125 12 6600 4 17 16.125 4 17.5 17.125 4 18.5 18.125 6 19 19.125 6 19.5 20.125 6 21 22.125 8 22.5 24.125 14 7500 4 17.5 17.125 4 18.5 18.125 4 19 19.125 6 19.5 20.125 6 20.5 21.125 6 22 23.125 8 23 25.125 16 8700 4 20.5 19.375 4 21 20.375 6 22 21.375 6 22.5 22.375 6 23.5 23.375 8 24.5 25.375 8 26 27.375 18 9600 4 22 21.375 4 22.5 22.375 6 23.5 23.375 6 24 24.375 6 24.5 25.375 8 26 27.375 8 27.5 29.375 20 10200 4 23.5 23.375 4 24 24.375 6 24.5 25.375 6 25.5 26.375 6 26 27.375 8 27.5 29.375 8 29 31.375 24 10800 4 26 27.375 4 27 28.375 6 27.5 29.375 6 28.5 30.375 6 29 31.375 8 30.5 33.375 8 32 35.375 30 14100 4 32.5 33.625 6 33 34.625 6 34 35.625 6 34.5 36.625 6 35 37.625 8 36.5 39.625 8 38 41.625 36 16500 4 36.5 40.125 6 37.5 41.125 6 38 42.125 6 38.5 43.125 6 39.5 44.125 8 41 46.125 8 42.5 48.125 42 18600 4 41 46.125 6 41.5 47.125 6 42.5 48.125 6 43 49.125 6 43.5 50.125 8 45 52.125 8 46.5 54.125 Insul. Thk. = 3" Insul. Thk. =4" Insul. Thk. = 5"Insul. Thk. = 1" Insul. Thk. = 1-1/2" Insul. Thk. = 2" Insul. Thk. = 2-1/2"