SlideShare a Scribd company logo
1 of 81
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Earthing System
• Protection Against Electric Shocks
• Earth Faults Protection
• Protection Against Voltage Surges
2
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Earth: The conductive mass of the Earth, whose
electric potential at any point is conventionally
taken as zero.
• An earth is defined as a connection to the
general mass of earth.
3
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
4
(1) Earth electrode
(2) Earthing conductor
(3) Protective conductor
(4) Electrical installation
(5) Bonding conductor
(6) Main earthing terminal
(7) Removable link
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• A conductor or other metal is ‘earthed’ when it
is effectually connected to the general mass of
earth by means of a metal rod or a system of
metal water pipes or other conducting object.
• ‘Solidly earthed’ or ‘Bolted earthed’ when it is
earthed without the intervention of a fuse,
switch, circuit breaker , resistor, reactor, or
solenoid.
5
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Earthing is meant by having every item of
apparatus and every conductor shall be
prevented from giving rise to earth leakage
currents.
• It is carried out by ensuring any metal liable to
become charge should be earth and every part
of the earthing circuit should be properly
installed.
6
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Other alternatives to earthing that could be
employed are by having an all insulted
construction, double insulation and by having
an isolation.
• Earthing protects people and equipment from
potentially dangerous over-voltages and
leakages associated with electrical equipment
in homes, offices, retail outlets and industrial
plant.
7
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
Grounding
• Connecting equipment and points on electrical systems
to the earth or an earth substitute.
• Purpose is to limit overvoltages between the equipment
and the earth due to lightning, faults, etc.
Bonding
• Connecting equipment together and to the system
neutral point.
• Purpose is to limit voltages between equipment and to
provide a path for ground fault current.
8
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
9
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Reason (1) – Minimise overvoltages
10
Lightning
strike
Lightning
arrester
transformer
Service earth rod
Transformer earth rod
Utility neutral conductor
Utility phase conductor
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Reason (2) – Limit voltage potential on
equipment enclosures
11
400V motor
415V
feeder
conductors
Ungrounded
motor frame
Insulation
breakdown
240V
400V motor
Equipment
earthing
conductor
Grounded
motor frame
Insulation
breakdown
0V
Earthing surface Earthing surface
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Reason (3) – Provide a low-impedance path for
fault current
12
400V motor
415V
feeder
conductors
Ungrounded
motor frame
Insulation
breakdown
400V motor
Equipment
earthing
conductor
Grounded
motor frame
Insulation
breakdown
IF
IF
I = 0A
IF
IF
Overcurrent
devices
Overcurrent
devices
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Designing a safe earthing system means
providing the easiest and shortest path for the
fault current without exposing a person to
electric shock.
• Satisfactory earthing is the most important part
of an electrical installation because operation
of all the protective devices depend upon it.
13
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• The total impedance of the conductor,
connecting the metal-work of the installation
to the earth electrode (earth continuity
conductor) measured between the earth
electrode and any other part of the installation
at supply frequency should not exceed 1.0 .
• If the resistance is higher than 1.0  (excessive
resistance), it is an indication of improper
earthing.
14
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Earth lug terminal rusty
• Loose wire connection
• Layers of paint on the electric apparatus
• Loose connection of earth wire to the plug and
socket outlet
• Loose connection between conduit and
terminal box
15
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• T = Terre (French word for earth)
• I = Isolation (all live parts isolated from earth or
supply connected to earth through an impedance
for isolation.
• N = Neutral (in AC system, the earth point is
normally the neutral point).
• S = Separé (neutral and protective functions
provided by separate conductors).
• C = Combiné (neutral and protective functions
combined in a single conductor, PEN).
16
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• TT system (earthed neutral)
17
One point at the supply source is connected directly to earth. All exposed- and
extraneous-conductive-parts are connected to a separate earth electrode at the
installation. This electrode may or may not be electrically independent of the source
electrode.
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• TN-C system
18
The neutral conductor is also used as a protective conductor and is referred to as a
PEN (Protective Earth and Neutral) conductor.
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• TN-S system
19
The protective conductor and the neutral conductor are separate. On
underground cable systems where lead-sheathed cables exist, the protective
conductor is generally the lead sheath.
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• TN-C-S system
20
In the TN-C-S system, the TN-C (4 wires) system must never be used downstream of
the TN-S (5 wires) system, since any accidental interruption in the neutral on the
upstream part would lead to an interruption in the protective conductor in the
downstream part and therefore a danger.
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• IT system (isolated neutral)
21
No intentional connection is made between the neutral point of the supply source
and earth. Exposed- and extraneous-conductive-parts of the installation are
connected to an earth electrode.
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• IT system (impedance-earthed neutral)
22
An impedance Zs (in the order of 1,000 to 2,000 Ω) is connected permanently
between the neutral point of the transformer LV winding and earth
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
23
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Simplest solution to design and install. Used in
installations supplied directly by the public LV distribution
network.
• Does not require continuous monitoring during operation.
• Protection is ensured by special devices, the residual
current devices (RCD), which also prevent the risk of fire
when they are set to 500 mA.
• Each insulation fault results in an interruption in the
supply of power, however the outage is limited to the
faulty circuit by installing the RCDs in series or in parallel.
• Loads or parts of the installation which, during normal
operation, cause high leakage currents, require special
measures to avoid nuisance tripping.
24
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
25
TN-C system
TN-S system
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Requires the installation of earth electrodes at regular
intervals throughout the installation.
• Requires that the initial check on effective tripping for the
first insulation fault be carried out by calculations during the
design stage, followed by mandatory measurements to
confirm tripping during commissioning.
• Requires that any modification or extension be designed and
carried out by a qualified electrician.
• May result, in the case of insulation faults, in greater damage
to the windings of rotating machines.
• May, on premises with a risk of fire, represent a greater
danger due to the higher fault currents
26
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
27
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Solution offering the best continuity of service during
operation.
• Indication of the first insulation fault, followed by mandatory
location and clearing, ensures systematic prevention of
supply outages.
• Generally used in installations supplied by a private MV/LV or
LV/LV transformer.
• Requires maintenance personnel for monitoring and
operation.
• Requires a high level of insulation in the network (implies
breaking up the network if it is very large and the use of
circuit-separation transformers to supply loads with high
leakage currents).
28
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• An electric shock is the pathophysiological effect
of an electric current through the human body.
• The degree of danger for the victim is a function of
the magnitude of the current, the parts of the
body through which the current passes, and the
duration of current flow.
• When a current greater than 30 mA passes
through a human being from one hand to feet, the
person concerned is likely to be killed, unless the
current is interrupted in a relatively short time.
29
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
30
Zones time/current of effects of AC current on human body when passing from left hand to feet
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• A direct contact refers to a person coming into
contact with a conductor which is live in
normal circumstances.
31
Is = Touch current
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• An indirect contact refers to a person coming
into contact with an exposed-conductive-part
which is not normally alive, but has become
alive accidentally (due to insulation failure or
some other cause).
32
Id = Insulation fault current
Is = Touch current
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
33
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Protection by the insulation of live parts
• Protection by means of barriers or enclosures
• Use of residual current operating device, which
operate at 30 mA or less, and are referred to as
RCDs of high sensitivity
34
RCD
Envelope
Insulation
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• The earthing of all exposed-conductive-parts of
electrical equipment in the installation and the
constitution of an equi-potential bonding
network.
35
• Automatic disconnection of the
supply of the section of the
installation concerned, in such a
way that the touch-voltage/time
safety requirements are
respected for any level of touch
voltage (Vc).
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
Vc (V) 50 < Vc  120 120 < Vc  230 230 < Vc  400 Vc > 400
System
TN or IT 0.8 0.4 0.2 0.1
TT 0.3 0.2 0.07 0.04
36
• Maximum safe duration (disconnecting time) of
the assumed values of AC touch voltage (in
seconds) not exceeding 32 A:
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
37
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• The impedance of the earth-fault loop consists mainly
in the two earth electrodes (i.e. the source and
installation electrodes) in series.
• The magnitude of the earth fault current is generally
too small to operate overcurrent relay or fuses, and
the use of a residual current operated device is
essential.
• Protection by automatic disconnection of the supply
used in TT system is by RCD of sensitivity:
38
A
n
R
I
50

 RA is the resistance of the earth electrode for the installation
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
39
TN-C
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• In all TN systems, any insulation fault to earth
results in a phase to neutral short-circuit.
• High fault current levels allow to use overcurrent
protection but can give rise to touch voltages
exceeding 50% of the phase to neutral voltage at
the fault position during the short disconnection
time.
• The use of CB, fuses, and RCDs may be necessary
on TN-earthed systems.
40
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
41
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• A permanent monitoring of the insulation to earth
must be provided, coupled with an alarm signal (audio
and/or flashing lights, etc.) operating in the event of a
first earth fault.
• During a phase to earth fault, the current passing
through the electrode resistance RnA is the vector sum
of the capacitive currents in the two healthy phases.
• The use of CB, fuses, and RCDs may be necessary on
IT-earthed systems
42
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Earth leakage devices are based on the principle
that the amount of current entering a device
should be exactly the same as the amount of
current leaving the device.
• Earth leakage protection devices are designed to
trip for fault currents between 10 and 100 mA and
for interrupt times between 40 and 100
milliseconds after a fault current is sensed.
• It has been gradually replaced by Residue Current
Devices (RCD) such as RCCB.
43
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
44
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• For regular houses 40A / 63A, single phase or
depends on supply demand and main switch
capacity, ELCB's sensitivity is not exceeding
100mA.
• For heater water, it should posses separate
additional ELCB (other than no. 1 above) with
sensitivity is not exceeding 10mA is needed.
• For load which higher than 100A, 3 phases,
ELCB's sensitivity must not exceed 100mA.
45
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
46
3wire 3phase supply
Circuit Breaker
Trip coil
Current Transformer
To load
earth
fault
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• During normal operation the current from supply L flows
through N1, to the load and then flow through N2 before
returning to N.
• Since the number of turns of N1 and N2 are the same
and the current through them is also the same the
resulting flux in the iron core is zero.
• However, if there is a leakage from the load to the
ground, a certain amount of current will flow to the
ground.
• As such current through N1 and N2 will not be the same
resulting in some magnetic flux setting up in the core.
• The fault sensing winding will trip the tripping device if
the leakage current falls within 10 to 100 milliampere.
• A test circuit consisting of a push button and a test
resistor is normally included in the ELCB as shown. Its
function is to create an unbalance current in the N1 and
N2 windings, and the current flow through the test
resistor is great enough for the fault sensing winding to
trip the circuit breaker.
47
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• There are two main reasons why RCD’s are used:
– To provide additional and a higher level of protection than
that given by direct earthing, against electric shock and also
against fire risk caused by earth leakage currents. Where
fuses and miniature circuit breakers (MCB’s) are the only
means of earth fault protection, it is possible for earth fault
currents to flow undetected and cause fire risk (or touch
voltage problems).
– The use of an RCD will prevent the flow of a sustained
leakage current above the sensitivity of the RCD thus
greatly reducing shock and fire risk. All live conductors in
the protected circuits should be disconnected in the event
of earth leakage current flowing.
48
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Terms associated with RCD’s:
– RCCB:
Residual Current Circuit Breaker used in distribution boards to protect individual
or groups of circuits
– RCBO:
Residual Circuit Breaker with overcurrent protection. This is a combined
MCB/RCD and provides overload, short circuit and earth fault protection in one
unit
– SRCD:
Socket outlet with combined RCD
– PRCD:
This is a portable RCD unit with an inbuilt plug top and socket
outlet
49
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Single Phase RCD
50
LOAD
Relay
Neutral
Phase
Detection Coil
Test Button
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Three Phase RCD
51
Earthed
Metalwork
Amplifier
Magnetic Core
L1
L3
L2
Test Resistor
LOAD
Trip Relay
Neutral
Detection Coil
Test Button
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
Regulation D22 (Basic Earthing Requirements)
States that earth leakage protection may be provided by means of
fuses or excess current circuit breakers if the earth fault current
available to operate the protective device and so make the faulty
circuit dead exceeds:
1. 3 times the current rating of any semi enclosed fuse or any
cartridge fuse having a fusing factor exceeding 1.5, used to
protect the circuit, or
2. 2.4 times the rating of any cartridge fuse having a fusing
factor not exceeding 1.5, used to protect the circuit, or
3. 1.5 times the tripping current of any excess current circuit
breaker used to protect the circuit.
52
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• A single phase 240 V, 15 kW 50Hz motor circuit
operating at 0.8 power factor lagging is protected by a
cartridge fuse having blowing current of 110 A. A fault
occurs in the circuit causes a current of 220 amperes to
flow through the earth continuity path. As a result of
poor contact due to a lock nut and bush connecting a
steel conduit to a metal box, the resistance of this
conduit connection alone is 1.35 Ω. State:
a) whether the fuse will rupture
b) the amount of heat produced at the metal box
c) the degree of risk, if any, of a fire developing
53
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Yes. The rating current:
Fusing factor:
• I2R = (220)2 x 1.35 Ohms = 65.34 kW.
• High Risk
54
A
V
kW
Ir 125
.
78
8
.
0
240
15



41
.
1
125
.
78
110


A
A
FF
Since according to regulation
D22, the protection is by a
cartridge having a fusing factor
not exceeding 1.5. Then the
maximum current in the fault is
2.4 x 78.125 A = 187.5 A.
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• What is a voltage surge?
– A voltage surge is a voltage impulse or wave which
is superposed on the rated network voltage.
55
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Voltage surge is characterised by:
– The rise time (tf) measured in μs
– The gradient (S) measured in kV/μs
• A voltage surge disturbs equipment and causes
electromagnetic radiation.
• Furthermore, the duration of the voltage surge
(T) causes a surge of energy in the electrical
circuits which is likely to destroy the
equipment.
56
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
57
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Atmospheric voltage surges
• Operating voltage surges
• Transient overvoltage at industrial frequency
• Voltage surges caused by electrostatic
discharge
58
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Lightning risk. Between 2,000 and 5,000 storms are
constantly forming around the earth. These storms
are accompanied by lightning which constitutes a
serious risk for both people and equipment.
• Strokes of lightning hit the ground at a rate of 30 to
100 strokes per second.
• Lightning affects transformers, electricity meters,
household appliances, and all electrical and
electronic installations in the residential sector and
in industry.
59
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Lightning discharge values given by the IEC
lightning protection committee:
60
Beyond peak
probability
P%
Current peak,
I (kA)
Gradient,
S (kA/μs)
Total duration
(s)
Number of
discharges
n
95 7 9.1 0.001 1
50 33 24 0.01 2
5 85 65 1.1 6
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• A sudden change in the established operating
conditions in an electrical network causes
transient phenomena to occur.
• These are generally high frequency or damped
oscillation voltage surge waves.
61
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• The opening of protection devices (fuse, circuit-
breaker), and the opening or closing of control
devices (relays, contactors, etc.).
• Inductive circuits due to motors starting and
stopping, or the opening of transformers such as
MV/LV substations.
• Capacitive circuits due to the connection of
capacitor banks to the network.
• All devices that contain a coil, a capacitor or a
transformer at the power supply inlet: relays,
contactors, television sets, printers, computers,
electric ovens, filters, etc.
62
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• These overvoltages have the same frequency as
the network (50, 60 or 400 Hz).
63
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Phase/frame or phase/earth insulating faults on a
network with an insulated or impedance-neutral,
or by the breakdown of the neutral conductor.
When this happens, single phase devices will be
supplied in 400 V instead of 230 V.
• A cable breakdown. For example, a medium
voltage cable which falls on a low voltage line.
• The arcing of a high or medium voltage protective
spark-gap causing a rise in earth potential during
the action of the protection devices.
64
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• In a dry environment, electrical charges accumulate
and create a very strong electrostatic field.
• For example, a person walking on carpet with
insulating soles will become electrically charged to a
voltage of several kilovolts. If the person walks close
to a conductive structure, he will give off an
electrical discharge of several amperes in a very
short rise time of a few nanoseconds.
• If the structure contains sensitive electronics, a
computer for example, its components or circuit
boards maybe damaged.
65
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Primary protection devices (protection of
installations against lightning).
• Secondary protection devices (protection of
internal installations against lightning).
66
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• The purpose of primary protection devices is to
protect installations against direct strokes of
lightning.
• They catch and run the lightning current into the
ground. The principle is based on a protection area
determined by a structure which is higher than the
rest.
• There are three types of primary protection:
– Lightning conductors
– Overhead earth wires
– The meshed cage or Faraday cage
67
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• The lightning conductor is
a tapered rod placed on
top of the building. It is
earthed by one or more
conductors (often copper
strips).
68
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• These wires are stretched over the structure to be
protected. They are used for special structures: rocket
launch pads, military applications and lightning protection
cables for overhead high voltage power lines.
69
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• This principle is used for
very sensitive buildings
housing computer or
integrated circuit
production equipment.
• It consists in
symmetrically multiplying
the number of down strips
outside the building.
70
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• These handle the effects of atmospheric,
operating or industrial frequency voltage
surges.
• They can be classified according to the way
they are connected in an installation: serial or
parallel protection.
71
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• This is connected in series to the power supply
wires of the system to be protected.
72
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Transformers
– They reduce voltage surges by inductor effect and make
certain harmonics disappear by coupling. This
protection is not very effective.
• Filters
– Based on components such as resistors, inductance
coils and capacitors they are suitable for voltage surges
caused by industrial and operation disturbance
corresponding to a clearly defined frequency band. This
protection device is not suitable for atmospheric
disturbance.
73
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Wave absorbers
– They are essentially made up of air inductance coils
which limit the voltage surges, and surge arresters
which absorb the currents. They are extremely
suitable for protecting sensitive electronic and
computing equipment.
74
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Network conditioners and static uninterrupted
power supplies (UPS)
– These devices are essentially used to protect highly
sensitive equipment, such as computer equipment,
which requires a high quality electrical power supply.
– They can be used to regulate the voltage and frequency,
stop interference and ensure a continuous electrical
power supply even in the event of a mains power
failure (for the UPS).
– On the other hand, they are not protected against
large, atmospheric type voltage surges against which it
is still necessary to use surge arresters.
75
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• The parallel protection is adapted to any
installation power level. This type of
overvoltage protection is the most commonly
used.
76
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• Main characteristics
– The rated voltage of the protection device must
correspond to the network voltage at the installation
terminals.
– When there is no voltage surge, a leakage current
should not go through the protection device which is on
standby.
– When a voltage surge above the allowable voltage
threshold of the installation to be protected occurs, the
protection device abruptly conducts the voltage surge
current to the earth by limiting the voltage to the
desired protection level, Vp.
77
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
• When the voltage surge disappears, the protection
device stops conducting and returns to standby
without a holding current. This is the ideal U/I
characteristic curve:
– The protection device response time (tr) must be as short
as possible to protect the installation as quickly as
possible.
– The protection device must have the capacity to be able
to conduct the energy caused by the foreseeable voltage
surge on the site to be protected.
– The surge arrester protection device must be able to
withstand the rated current, In.
78
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
(1) Voltage limiters
• They are used in MV/LV
substations at the
transformer output, in
IT earthing scheme.
• They can run voltage
surges to the earth,
especially industrial
frequency surges.
79
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
(2) LV surge arresters
• Low voltage surge arresters come in the form of
modules to be installed inside LV switchboard.
• They ensure secondary protection of nearby
elements but have a small flow capacity.
• Some are even built into loads although they
cannot protect against strong voltage surges.
80
BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy
(3) Low current surge arresters
• These protect telephone or switching networks
against voltage surges from the outside
(lightning), as well as from the inside (polluting
equipment, switchgear switching, etc.).
• Low current voltage surge arresters are also
installed in distribution boxes or built into
loads.
81

More Related Content

Similar to CHAPTER 5 - System Protection.pptx

Protection Devices and the Lightning
Protection Devices and the LightningProtection Devices and the Lightning
Protection Devices and the LightningAmeen San
 
Earthing &amp; grounding difference
Earthing &amp; grounding differenceEarthing &amp; grounding difference
Earthing &amp; grounding differenceAnurag Singh
 
Presentation best practice earthing and protection
Presentation   best practice earthing and protectionPresentation   best practice earthing and protection
Presentation best practice earthing and protectionMahesh Chandra Manav
 
samatha2-160203134304 (1) (1).pptx
samatha2-160203134304 (1) (1).pptxsamatha2-160203134304 (1) (1).pptx
samatha2-160203134304 (1) (1).pptxDipeshBaviskar
 
Earthing System in Building services
Earthing System in Building servicesEarthing System in Building services
Earthing System in Building servicesJeelkumar Patel
 
Earthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspectsEarthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspectsBruno De Wachter
 
#Building wiring system#presentation#Wire is a single electrical conductor, w...
#Building wiring system#presentation#Wire is a single electrical conductor, w...#Building wiring system#presentation#Wire is a single electrical conductor, w...
#Building wiring system#presentation#Wire is a single electrical conductor, w...Bint Shameem
 
Electric wiring and earthing
Electric wiring and earthingElectric wiring and earthing
Electric wiring and earthingHARISH J
 
buildinggroupppt-130512115915-phpapp02.pptx
buildinggroupppt-130512115915-phpapp02.pptxbuildinggroupppt-130512115915-phpapp02.pptx
buildinggroupppt-130512115915-phpapp02.pptxNirmalSivarajan3
 
Design of Electrical Installation of Buildings.ppt
Design of Electrical Installation of Buildings.pptDesign of Electrical Installation of Buildings.ppt
Design of Electrical Installation of Buildings.pptSameeraShaman
 
Importance of Earth Mat in Substation.docx
Importance of Earth Mat in Substation.docxImportance of Earth Mat in Substation.docx
Importance of Earth Mat in Substation.docxvikram desai
 
Project 2 building service
Project 2  building serviceProject 2  building service
Project 2 building serviceOng Shi Hui
 
6a_ELECTRIC SAFETY.ppt
6a_ELECTRIC SAFETY.ppt6a_ELECTRIC SAFETY.ppt
6a_ELECTRIC SAFETY.pptSyamKazuma1
 

Similar to CHAPTER 5 - System Protection.pptx (20)

Protection Devices and the Lightning
Protection Devices and the LightningProtection Devices and the Lightning
Protection Devices and the Lightning
 
4th chapter.pptx
4th chapter.pptx4th chapter.pptx
4th chapter.pptx
 
Presentation jmv internal
Presentation jmv internalPresentation jmv internal
Presentation jmv internal
 
Earthing &amp; grounding difference
Earthing &amp; grounding differenceEarthing &amp; grounding difference
Earthing &amp; grounding difference
 
Presentation best practice earthing and protection
Presentation   best practice earthing and protectionPresentation   best practice earthing and protection
Presentation best practice earthing and protection
 
samatha2-160203134304 (1) (1).pptx
samatha2-160203134304 (1) (1).pptxsamatha2-160203134304 (1) (1).pptx
samatha2-160203134304 (1) (1).pptx
 
Effect of grounding
Effect of groundingEffect of grounding
Effect of grounding
 
Earthing system
Earthing system   Earthing system
Earthing system
 
Earthing System in Building services
Earthing System in Building servicesEarthing System in Building services
Earthing System in Building services
 
Grounding and Bonding
Grounding and BondingGrounding and Bonding
Grounding and Bonding
 
Earthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspectsEarthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspects
 
#Building wiring system#presentation#Wire is a single electrical conductor, w...
#Building wiring system#presentation#Wire is a single electrical conductor, w...#Building wiring system#presentation#Wire is a single electrical conductor, w...
#Building wiring system#presentation#Wire is a single electrical conductor, w...
 
Elect. presentation (04).ppt
Elect. presentation (04).pptElect. presentation (04).ppt
Elect. presentation (04).ppt
 
Electric wiring and earthing
Electric wiring and earthingElectric wiring and earthing
Electric wiring and earthing
 
buildinggroupppt-130512115915-phpapp02.pptx
buildinggroupppt-130512115915-phpapp02.pptxbuildinggroupppt-130512115915-phpapp02.pptx
buildinggroupppt-130512115915-phpapp02.pptx
 
Design of Electrical Installation of Buildings.ppt
Design of Electrical Installation of Buildings.pptDesign of Electrical Installation of Buildings.ppt
Design of Electrical Installation of Buildings.ppt
 
Importance of Earth Mat in Substation.docx
Importance of Earth Mat in Substation.docxImportance of Earth Mat in Substation.docx
Importance of Earth Mat in Substation.docx
 
Project 2 building service
Project 2  building serviceProject 2  building service
Project 2 building service
 
6a_ELECTRIC SAFETY.ppt
6a_ELECTRIC SAFETY.ppt6a_ELECTRIC SAFETY.ppt
6a_ELECTRIC SAFETY.ppt
 
Gss herapura report
Gss herapura reportGss herapura report
Gss herapura report
 

More from LiewChiaPing

chapter4 DC to AC Converter.ppt
chapter4 DC to AC Converter.pptchapter4 DC to AC Converter.ppt
chapter4 DC to AC Converter.pptLiewChiaPing
 
chapter_2 AC to DC Converter.pptx
chapter_2 AC to DC Converter.pptxchapter_2 AC to DC Converter.pptx
chapter_2 AC to DC Converter.pptxLiewChiaPing
 
chapter_1 Intro. to electonic Devices.ppt
chapter_1 Intro. to electonic Devices.pptchapter_1 Intro. to electonic Devices.ppt
chapter_1 Intro. to electonic Devices.pptLiewChiaPing
 
Chapter 7 Application of Electronic Converters.pdf
Chapter 7 Application of Electronic Converters.pdfChapter 7 Application of Electronic Converters.pdf
Chapter 7 Application of Electronic Converters.pdfLiewChiaPing
 
Chapter 6 AC-AC Converters.pdf
Chapter 6 AC-AC Converters.pdfChapter 6 AC-AC Converters.pdf
Chapter 6 AC-AC Converters.pdfLiewChiaPing
 
Chapter 5 DC-DC Converters.pdf
Chapter 5 DC-DC Converters.pdfChapter 5 DC-DC Converters.pdf
Chapter 5 DC-DC Converters.pdfLiewChiaPing
 
Chapter 4 Inverters.pdf
Chapter 4 Inverters.pdfChapter 4 Inverters.pdf
Chapter 4 Inverters.pdfLiewChiaPing
 
Chapter 3 Controlled Rectifier.pdf
Chapter 3 Controlled Rectifier.pdfChapter 3 Controlled Rectifier.pdf
Chapter 3 Controlled Rectifier.pdfLiewChiaPing
 
Chapter 2 Uncontrolled Rectifiers.pdf
Chapter 2 Uncontrolled Rectifiers.pdfChapter 2 Uncontrolled Rectifiers.pdf
Chapter 2 Uncontrolled Rectifiers.pdfLiewChiaPing
 
Chapter 1 Introduction to power Electronic Devices.pdf
Chapter 1 Introduction to power Electronic Devices.pdfChapter 1 Introduction to power Electronic Devices.pdf
Chapter 1 Introduction to power Electronic Devices.pdfLiewChiaPing
 
BEF43303_-_201620171_W13 Overcurrent Protection.pdf
BEF43303_-_201620171_W13 Overcurrent Protection.pdfBEF43303_-_201620171_W13 Overcurrent Protection.pdf
BEF43303_-_201620171_W13 Overcurrent Protection.pdfLiewChiaPing
 
BEF43303_-_201620171_W12 Overcurrent Protection.pdf
BEF43303_-_201620171_W12 Overcurrent Protection.pdfBEF43303_-_201620171_W12 Overcurrent Protection.pdf
BEF43303_-_201620171_W12 Overcurrent Protection.pdfLiewChiaPing
 
BEF43303_-_201620171_W11 Distance Protection.pdf
BEF43303_-_201620171_W11 Distance Protection.pdfBEF43303_-_201620171_W11 Distance Protection.pdf
BEF43303_-_201620171_W11 Distance Protection.pdfLiewChiaPing
 
BEF43303_-_201620171_W10.pdf
BEF43303_-_201620171_W10.pdfBEF43303_-_201620171_W10.pdf
BEF43303_-_201620171_W10.pdfLiewChiaPing
 
BEF43303_-_201620171_W8 Power System Stability.pdf
BEF43303_-_201620171_W8 Power System Stability.pdfBEF43303_-_201620171_W8 Power System Stability.pdf
BEF43303_-_201620171_W8 Power System Stability.pdfLiewChiaPing
 
BEF43303_-_201620171_W7 Power System Stability.pdf
BEF43303_-_201620171_W7 Power System Stability.pdfBEF43303_-_201620171_W7 Power System Stability.pdf
BEF43303_-_201620171_W7 Power System Stability.pdfLiewChiaPing
 
BEF43303_-_201620171_W6 Analysis of Fault.pdf
BEF43303_-_201620171_W6 Analysis of Fault.pdfBEF43303_-_201620171_W6 Analysis of Fault.pdf
BEF43303_-_201620171_W6 Analysis of Fault.pdfLiewChiaPing
 
BEF43303_-_201620171_W5 Analysis of fault.pdf
BEF43303_-_201620171_W5 Analysis of fault.pdfBEF43303_-_201620171_W5 Analysis of fault.pdf
BEF43303_-_201620171_W5 Analysis of fault.pdfLiewChiaPing
 
BEF43303_-_201620171_W4 Analysis of Balance and Unbalance Fault.pdf
BEF43303_-_201620171_W4 Analysis of Balance and Unbalance Fault.pdfBEF43303_-_201620171_W4 Analysis of Balance and Unbalance Fault.pdf
BEF43303_-_201620171_W4 Analysis of Balance and Unbalance Fault.pdfLiewChiaPing
 
BEF43303 - 201620171 W3 Power Flow Analysis.pdf
BEF43303 - 201620171 W3 Power Flow Analysis.pdfBEF43303 - 201620171 W3 Power Flow Analysis.pdf
BEF43303 - 201620171 W3 Power Flow Analysis.pdfLiewChiaPing
 

More from LiewChiaPing (20)

chapter4 DC to AC Converter.ppt
chapter4 DC to AC Converter.pptchapter4 DC to AC Converter.ppt
chapter4 DC to AC Converter.ppt
 
chapter_2 AC to DC Converter.pptx
chapter_2 AC to DC Converter.pptxchapter_2 AC to DC Converter.pptx
chapter_2 AC to DC Converter.pptx
 
chapter_1 Intro. to electonic Devices.ppt
chapter_1 Intro. to electonic Devices.pptchapter_1 Intro. to electonic Devices.ppt
chapter_1 Intro. to electonic Devices.ppt
 
Chapter 7 Application of Electronic Converters.pdf
Chapter 7 Application of Electronic Converters.pdfChapter 7 Application of Electronic Converters.pdf
Chapter 7 Application of Electronic Converters.pdf
 
Chapter 6 AC-AC Converters.pdf
Chapter 6 AC-AC Converters.pdfChapter 6 AC-AC Converters.pdf
Chapter 6 AC-AC Converters.pdf
 
Chapter 5 DC-DC Converters.pdf
Chapter 5 DC-DC Converters.pdfChapter 5 DC-DC Converters.pdf
Chapter 5 DC-DC Converters.pdf
 
Chapter 4 Inverters.pdf
Chapter 4 Inverters.pdfChapter 4 Inverters.pdf
Chapter 4 Inverters.pdf
 
Chapter 3 Controlled Rectifier.pdf
Chapter 3 Controlled Rectifier.pdfChapter 3 Controlled Rectifier.pdf
Chapter 3 Controlled Rectifier.pdf
 
Chapter 2 Uncontrolled Rectifiers.pdf
Chapter 2 Uncontrolled Rectifiers.pdfChapter 2 Uncontrolled Rectifiers.pdf
Chapter 2 Uncontrolled Rectifiers.pdf
 
Chapter 1 Introduction to power Electronic Devices.pdf
Chapter 1 Introduction to power Electronic Devices.pdfChapter 1 Introduction to power Electronic Devices.pdf
Chapter 1 Introduction to power Electronic Devices.pdf
 
BEF43303_-_201620171_W13 Overcurrent Protection.pdf
BEF43303_-_201620171_W13 Overcurrent Protection.pdfBEF43303_-_201620171_W13 Overcurrent Protection.pdf
BEF43303_-_201620171_W13 Overcurrent Protection.pdf
 
BEF43303_-_201620171_W12 Overcurrent Protection.pdf
BEF43303_-_201620171_W12 Overcurrent Protection.pdfBEF43303_-_201620171_W12 Overcurrent Protection.pdf
BEF43303_-_201620171_W12 Overcurrent Protection.pdf
 
BEF43303_-_201620171_W11 Distance Protection.pdf
BEF43303_-_201620171_W11 Distance Protection.pdfBEF43303_-_201620171_W11 Distance Protection.pdf
BEF43303_-_201620171_W11 Distance Protection.pdf
 
BEF43303_-_201620171_W10.pdf
BEF43303_-_201620171_W10.pdfBEF43303_-_201620171_W10.pdf
BEF43303_-_201620171_W10.pdf
 
BEF43303_-_201620171_W8 Power System Stability.pdf
BEF43303_-_201620171_W8 Power System Stability.pdfBEF43303_-_201620171_W8 Power System Stability.pdf
BEF43303_-_201620171_W8 Power System Stability.pdf
 
BEF43303_-_201620171_W7 Power System Stability.pdf
BEF43303_-_201620171_W7 Power System Stability.pdfBEF43303_-_201620171_W7 Power System Stability.pdf
BEF43303_-_201620171_W7 Power System Stability.pdf
 
BEF43303_-_201620171_W6 Analysis of Fault.pdf
BEF43303_-_201620171_W6 Analysis of Fault.pdfBEF43303_-_201620171_W6 Analysis of Fault.pdf
BEF43303_-_201620171_W6 Analysis of Fault.pdf
 
BEF43303_-_201620171_W5 Analysis of fault.pdf
BEF43303_-_201620171_W5 Analysis of fault.pdfBEF43303_-_201620171_W5 Analysis of fault.pdf
BEF43303_-_201620171_W5 Analysis of fault.pdf
 
BEF43303_-_201620171_W4 Analysis of Balance and Unbalance Fault.pdf
BEF43303_-_201620171_W4 Analysis of Balance and Unbalance Fault.pdfBEF43303_-_201620171_W4 Analysis of Balance and Unbalance Fault.pdf
BEF43303_-_201620171_W4 Analysis of Balance and Unbalance Fault.pdf
 
BEF43303 - 201620171 W3 Power Flow Analysis.pdf
BEF43303 - 201620171 W3 Power Flow Analysis.pdfBEF43303 - 201620171 W3 Power Flow Analysis.pdf
BEF43303 - 201620171 W3 Power Flow Analysis.pdf
 

Recently uploaded

Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104misteraugie
 
How to Make a Pirate ship Primary Education.pptx
How to Make a Pirate ship Primary Education.pptxHow to Make a Pirate ship Primary Education.pptx
How to Make a Pirate ship Primary Education.pptxmanuelaromero2013
 
Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)eniolaolutunde
 
Accessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactAccessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactdawncurless
 
Z Score,T Score, Percential Rank and Box Plot Graph
Z Score,T Score, Percential Rank and Box Plot GraphZ Score,T Score, Percential Rank and Box Plot Graph
Z Score,T Score, Percential Rank and Box Plot GraphThiyagu K
 
Web & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdfWeb & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdfJayanti Pande
 
Hybridoma Technology ( Production , Purification , and Application )
Hybridoma Technology  ( Production , Purification , and Application  ) Hybridoma Technology  ( Production , Purification , and Application  )
Hybridoma Technology ( Production , Purification , and Application ) Sakshi Ghasle
 
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdfssuser54595a
 
Mastering the Unannounced Regulatory Inspection
Mastering the Unannounced Regulatory InspectionMastering the Unannounced Regulatory Inspection
Mastering the Unannounced Regulatory InspectionSafetyChain Software
 
mini mental status format.docx
mini    mental       status     format.docxmini    mental       status     format.docx
mini mental status format.docxPoojaSen20
 
The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13Steve Thomason
 
The basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxThe basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxheathfieldcps1
 
Employee wellbeing at the workplace.pptx
Employee wellbeing at the workplace.pptxEmployee wellbeing at the workplace.pptx
Employee wellbeing at the workplace.pptxNirmalaLoungPoorunde1
 
Activity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfActivity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfciinovamais
 
CARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptxCARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptxGaneshChakor2
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdfQucHHunhnh
 
Interactive Powerpoint_How to Master effective communication
Interactive Powerpoint_How to Master effective communicationInteractive Powerpoint_How to Master effective communication
Interactive Powerpoint_How to Master effective communicationnomboosow
 
Introduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxIntroduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxpboyjonauth
 
Q4-W6-Restating Informational Text Grade 3
Q4-W6-Restating Informational Text Grade 3Q4-W6-Restating Informational Text Grade 3
Q4-W6-Restating Informational Text Grade 3JemimahLaneBuaron
 
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...Marc Dusseiller Dusjagr
 

Recently uploaded (20)

Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104
 
How to Make a Pirate ship Primary Education.pptx
How to Make a Pirate ship Primary Education.pptxHow to Make a Pirate ship Primary Education.pptx
How to Make a Pirate ship Primary Education.pptx
 
Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)
 
Accessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactAccessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impact
 
Z Score,T Score, Percential Rank and Box Plot Graph
Z Score,T Score, Percential Rank and Box Plot GraphZ Score,T Score, Percential Rank and Box Plot Graph
Z Score,T Score, Percential Rank and Box Plot Graph
 
Web & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdfWeb & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdf
 
Hybridoma Technology ( Production , Purification , and Application )
Hybridoma Technology  ( Production , Purification , and Application  ) Hybridoma Technology  ( Production , Purification , and Application  )
Hybridoma Technology ( Production , Purification , and Application )
 
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
 
Mastering the Unannounced Regulatory Inspection
Mastering the Unannounced Regulatory InspectionMastering the Unannounced Regulatory Inspection
Mastering the Unannounced Regulatory Inspection
 
mini mental status format.docx
mini    mental       status     format.docxmini    mental       status     format.docx
mini mental status format.docx
 
The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13
 
The basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxThe basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptx
 
Employee wellbeing at the workplace.pptx
Employee wellbeing at the workplace.pptxEmployee wellbeing at the workplace.pptx
Employee wellbeing at the workplace.pptx
 
Activity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfActivity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdf
 
CARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptxCARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptx
 
1029-Danh muc Sach Giao Khoa khoi 6.pdf
1029-Danh muc Sach Giao Khoa khoi  6.pdf1029-Danh muc Sach Giao Khoa khoi  6.pdf
1029-Danh muc Sach Giao Khoa khoi 6.pdf
 
Interactive Powerpoint_How to Master effective communication
Interactive Powerpoint_How to Master effective communicationInteractive Powerpoint_How to Master effective communication
Interactive Powerpoint_How to Master effective communication
 
Introduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxIntroduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptx
 
Q4-W6-Restating Informational Text Grade 3
Q4-W6-Restating Informational Text Grade 3Q4-W6-Restating Informational Text Grade 3
Q4-W6-Restating Informational Text Grade 3
 
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
 

CHAPTER 5 - System Protection.pptx

  • 1.
  • 2. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Earthing System • Protection Against Electric Shocks • Earth Faults Protection • Protection Against Voltage Surges 2
  • 3. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Earth: The conductive mass of the Earth, whose electric potential at any point is conventionally taken as zero. • An earth is defined as a connection to the general mass of earth. 3
  • 4. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy 4 (1) Earth electrode (2) Earthing conductor (3) Protective conductor (4) Electrical installation (5) Bonding conductor (6) Main earthing terminal (7) Removable link
  • 5. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • A conductor or other metal is ‘earthed’ when it is effectually connected to the general mass of earth by means of a metal rod or a system of metal water pipes or other conducting object. • ‘Solidly earthed’ or ‘Bolted earthed’ when it is earthed without the intervention of a fuse, switch, circuit breaker , resistor, reactor, or solenoid. 5
  • 6. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Earthing is meant by having every item of apparatus and every conductor shall be prevented from giving rise to earth leakage currents. • It is carried out by ensuring any metal liable to become charge should be earth and every part of the earthing circuit should be properly installed. 6
  • 7. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Other alternatives to earthing that could be employed are by having an all insulted construction, double insulation and by having an isolation. • Earthing protects people and equipment from potentially dangerous over-voltages and leakages associated with electrical equipment in homes, offices, retail outlets and industrial plant. 7
  • 8. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy Grounding • Connecting equipment and points on electrical systems to the earth or an earth substitute. • Purpose is to limit overvoltages between the equipment and the earth due to lightning, faults, etc. Bonding • Connecting equipment together and to the system neutral point. • Purpose is to limit voltages between equipment and to provide a path for ground fault current. 8
  • 9. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy 9
  • 10. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Reason (1) – Minimise overvoltages 10 Lightning strike Lightning arrester transformer Service earth rod Transformer earth rod Utility neutral conductor Utility phase conductor
  • 11. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Reason (2) – Limit voltage potential on equipment enclosures 11 400V motor 415V feeder conductors Ungrounded motor frame Insulation breakdown 240V 400V motor Equipment earthing conductor Grounded motor frame Insulation breakdown 0V Earthing surface Earthing surface
  • 12. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Reason (3) – Provide a low-impedance path for fault current 12 400V motor 415V feeder conductors Ungrounded motor frame Insulation breakdown 400V motor Equipment earthing conductor Grounded motor frame Insulation breakdown IF IF I = 0A IF IF Overcurrent devices Overcurrent devices
  • 13. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Designing a safe earthing system means providing the easiest and shortest path for the fault current without exposing a person to electric shock. • Satisfactory earthing is the most important part of an electrical installation because operation of all the protective devices depend upon it. 13
  • 14. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • The total impedance of the conductor, connecting the metal-work of the installation to the earth electrode (earth continuity conductor) measured between the earth electrode and any other part of the installation at supply frequency should not exceed 1.0 . • If the resistance is higher than 1.0  (excessive resistance), it is an indication of improper earthing. 14
  • 15. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Earth lug terminal rusty • Loose wire connection • Layers of paint on the electric apparatus • Loose connection of earth wire to the plug and socket outlet • Loose connection between conduit and terminal box 15
  • 16. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • T = Terre (French word for earth) • I = Isolation (all live parts isolated from earth or supply connected to earth through an impedance for isolation. • N = Neutral (in AC system, the earth point is normally the neutral point). • S = Separé (neutral and protective functions provided by separate conductors). • C = Combiné (neutral and protective functions combined in a single conductor, PEN). 16
  • 17. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • TT system (earthed neutral) 17 One point at the supply source is connected directly to earth. All exposed- and extraneous-conductive-parts are connected to a separate earth electrode at the installation. This electrode may or may not be electrically independent of the source electrode.
  • 18. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • TN-C system 18 The neutral conductor is also used as a protective conductor and is referred to as a PEN (Protective Earth and Neutral) conductor.
  • 19. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • TN-S system 19 The protective conductor and the neutral conductor are separate. On underground cable systems where lead-sheathed cables exist, the protective conductor is generally the lead sheath.
  • 20. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • TN-C-S system 20 In the TN-C-S system, the TN-C (4 wires) system must never be used downstream of the TN-S (5 wires) system, since any accidental interruption in the neutral on the upstream part would lead to an interruption in the protective conductor in the downstream part and therefore a danger.
  • 21. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • IT system (isolated neutral) 21 No intentional connection is made between the neutral point of the supply source and earth. Exposed- and extraneous-conductive-parts of the installation are connected to an earth electrode.
  • 22. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • IT system (impedance-earthed neutral) 22 An impedance Zs (in the order of 1,000 to 2,000 Ω) is connected permanently between the neutral point of the transformer LV winding and earth
  • 23. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy 23
  • 24. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Simplest solution to design and install. Used in installations supplied directly by the public LV distribution network. • Does not require continuous monitoring during operation. • Protection is ensured by special devices, the residual current devices (RCD), which also prevent the risk of fire when they are set to 500 mA. • Each insulation fault results in an interruption in the supply of power, however the outage is limited to the faulty circuit by installing the RCDs in series or in parallel. • Loads or parts of the installation which, during normal operation, cause high leakage currents, require special measures to avoid nuisance tripping. 24
  • 25. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy 25 TN-C system TN-S system
  • 26. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Requires the installation of earth electrodes at regular intervals throughout the installation. • Requires that the initial check on effective tripping for the first insulation fault be carried out by calculations during the design stage, followed by mandatory measurements to confirm tripping during commissioning. • Requires that any modification or extension be designed and carried out by a qualified electrician. • May result, in the case of insulation faults, in greater damage to the windings of rotating machines. • May, on premises with a risk of fire, represent a greater danger due to the higher fault currents 26
  • 27. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy 27
  • 28. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Solution offering the best continuity of service during operation. • Indication of the first insulation fault, followed by mandatory location and clearing, ensures systematic prevention of supply outages. • Generally used in installations supplied by a private MV/LV or LV/LV transformer. • Requires maintenance personnel for monitoring and operation. • Requires a high level of insulation in the network (implies breaking up the network if it is very large and the use of circuit-separation transformers to supply loads with high leakage currents). 28
  • 29. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • An electric shock is the pathophysiological effect of an electric current through the human body. • The degree of danger for the victim is a function of the magnitude of the current, the parts of the body through which the current passes, and the duration of current flow. • When a current greater than 30 mA passes through a human being from one hand to feet, the person concerned is likely to be killed, unless the current is interrupted in a relatively short time. 29
  • 30. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy 30 Zones time/current of effects of AC current on human body when passing from left hand to feet
  • 31. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • A direct contact refers to a person coming into contact with a conductor which is live in normal circumstances. 31 Is = Touch current
  • 32. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • An indirect contact refers to a person coming into contact with an exposed-conductive-part which is not normally alive, but has become alive accidentally (due to insulation failure or some other cause). 32 Id = Insulation fault current Is = Touch current
  • 33. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy 33
  • 34. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Protection by the insulation of live parts • Protection by means of barriers or enclosures • Use of residual current operating device, which operate at 30 mA or less, and are referred to as RCDs of high sensitivity 34 RCD Envelope Insulation
  • 35. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • The earthing of all exposed-conductive-parts of electrical equipment in the installation and the constitution of an equi-potential bonding network. 35 • Automatic disconnection of the supply of the section of the installation concerned, in such a way that the touch-voltage/time safety requirements are respected for any level of touch voltage (Vc).
  • 36. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy Vc (V) 50 < Vc  120 120 < Vc  230 230 < Vc  400 Vc > 400 System TN or IT 0.8 0.4 0.2 0.1 TT 0.3 0.2 0.07 0.04 36 • Maximum safe duration (disconnecting time) of the assumed values of AC touch voltage (in seconds) not exceeding 32 A:
  • 37. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy 37
  • 38. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • The impedance of the earth-fault loop consists mainly in the two earth electrodes (i.e. the source and installation electrodes) in series. • The magnitude of the earth fault current is generally too small to operate overcurrent relay or fuses, and the use of a residual current operated device is essential. • Protection by automatic disconnection of the supply used in TT system is by RCD of sensitivity: 38 A n R I 50   RA is the resistance of the earth electrode for the installation
  • 39. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy 39 TN-C
  • 40. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • In all TN systems, any insulation fault to earth results in a phase to neutral short-circuit. • High fault current levels allow to use overcurrent protection but can give rise to touch voltages exceeding 50% of the phase to neutral voltage at the fault position during the short disconnection time. • The use of CB, fuses, and RCDs may be necessary on TN-earthed systems. 40
  • 41. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy 41
  • 42. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • A permanent monitoring of the insulation to earth must be provided, coupled with an alarm signal (audio and/or flashing lights, etc.) operating in the event of a first earth fault. • During a phase to earth fault, the current passing through the electrode resistance RnA is the vector sum of the capacitive currents in the two healthy phases. • The use of CB, fuses, and RCDs may be necessary on IT-earthed systems 42
  • 43. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Earth leakage devices are based on the principle that the amount of current entering a device should be exactly the same as the amount of current leaving the device. • Earth leakage protection devices are designed to trip for fault currents between 10 and 100 mA and for interrupt times between 40 and 100 milliseconds after a fault current is sensed. • It has been gradually replaced by Residue Current Devices (RCD) such as RCCB. 43
  • 44. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy 44
  • 45. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • For regular houses 40A / 63A, single phase or depends on supply demand and main switch capacity, ELCB's sensitivity is not exceeding 100mA. • For heater water, it should posses separate additional ELCB (other than no. 1 above) with sensitivity is not exceeding 10mA is needed. • For load which higher than 100A, 3 phases, ELCB's sensitivity must not exceed 100mA. 45
  • 46. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy 46 3wire 3phase supply Circuit Breaker Trip coil Current Transformer To load earth fault
  • 47. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • During normal operation the current from supply L flows through N1, to the load and then flow through N2 before returning to N. • Since the number of turns of N1 and N2 are the same and the current through them is also the same the resulting flux in the iron core is zero. • However, if there is a leakage from the load to the ground, a certain amount of current will flow to the ground. • As such current through N1 and N2 will not be the same resulting in some magnetic flux setting up in the core. • The fault sensing winding will trip the tripping device if the leakage current falls within 10 to 100 milliampere. • A test circuit consisting of a push button and a test resistor is normally included in the ELCB as shown. Its function is to create an unbalance current in the N1 and N2 windings, and the current flow through the test resistor is great enough for the fault sensing winding to trip the circuit breaker. 47
  • 48. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • There are two main reasons why RCD’s are used: – To provide additional and a higher level of protection than that given by direct earthing, against electric shock and also against fire risk caused by earth leakage currents. Where fuses and miniature circuit breakers (MCB’s) are the only means of earth fault protection, it is possible for earth fault currents to flow undetected and cause fire risk (or touch voltage problems). – The use of an RCD will prevent the flow of a sustained leakage current above the sensitivity of the RCD thus greatly reducing shock and fire risk. All live conductors in the protected circuits should be disconnected in the event of earth leakage current flowing. 48
  • 49. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Terms associated with RCD’s: – RCCB: Residual Current Circuit Breaker used in distribution boards to protect individual or groups of circuits – RCBO: Residual Circuit Breaker with overcurrent protection. This is a combined MCB/RCD and provides overload, short circuit and earth fault protection in one unit – SRCD: Socket outlet with combined RCD – PRCD: This is a portable RCD unit with an inbuilt plug top and socket outlet 49
  • 50. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Single Phase RCD 50 LOAD Relay Neutral Phase Detection Coil Test Button
  • 51. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Three Phase RCD 51 Earthed Metalwork Amplifier Magnetic Core L1 L3 L2 Test Resistor LOAD Trip Relay Neutral Detection Coil Test Button
  • 52. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy Regulation D22 (Basic Earthing Requirements) States that earth leakage protection may be provided by means of fuses or excess current circuit breakers if the earth fault current available to operate the protective device and so make the faulty circuit dead exceeds: 1. 3 times the current rating of any semi enclosed fuse or any cartridge fuse having a fusing factor exceeding 1.5, used to protect the circuit, or 2. 2.4 times the rating of any cartridge fuse having a fusing factor not exceeding 1.5, used to protect the circuit, or 3. 1.5 times the tripping current of any excess current circuit breaker used to protect the circuit. 52
  • 53. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • A single phase 240 V, 15 kW 50Hz motor circuit operating at 0.8 power factor lagging is protected by a cartridge fuse having blowing current of 110 A. A fault occurs in the circuit causes a current of 220 amperes to flow through the earth continuity path. As a result of poor contact due to a lock nut and bush connecting a steel conduit to a metal box, the resistance of this conduit connection alone is 1.35 Ω. State: a) whether the fuse will rupture b) the amount of heat produced at the metal box c) the degree of risk, if any, of a fire developing 53
  • 54. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Yes. The rating current: Fusing factor: • I2R = (220)2 x 1.35 Ohms = 65.34 kW. • High Risk 54 A V kW Ir 125 . 78 8 . 0 240 15    41 . 1 125 . 78 110   A A FF Since according to regulation D22, the protection is by a cartridge having a fusing factor not exceeding 1.5. Then the maximum current in the fault is 2.4 x 78.125 A = 187.5 A.
  • 55. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • What is a voltage surge? – A voltage surge is a voltage impulse or wave which is superposed on the rated network voltage. 55
  • 56. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Voltage surge is characterised by: – The rise time (tf) measured in μs – The gradient (S) measured in kV/μs • A voltage surge disturbs equipment and causes electromagnetic radiation. • Furthermore, the duration of the voltage surge (T) causes a surge of energy in the electrical circuits which is likely to destroy the equipment. 56
  • 57. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy 57
  • 58. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Atmospheric voltage surges • Operating voltage surges • Transient overvoltage at industrial frequency • Voltage surges caused by electrostatic discharge 58
  • 59. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Lightning risk. Between 2,000 and 5,000 storms are constantly forming around the earth. These storms are accompanied by lightning which constitutes a serious risk for both people and equipment. • Strokes of lightning hit the ground at a rate of 30 to 100 strokes per second. • Lightning affects transformers, electricity meters, household appliances, and all electrical and electronic installations in the residential sector and in industry. 59
  • 60. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Lightning discharge values given by the IEC lightning protection committee: 60 Beyond peak probability P% Current peak, I (kA) Gradient, S (kA/μs) Total duration (s) Number of discharges n 95 7 9.1 0.001 1 50 33 24 0.01 2 5 85 65 1.1 6
  • 61. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • A sudden change in the established operating conditions in an electrical network causes transient phenomena to occur. • These are generally high frequency or damped oscillation voltage surge waves. 61
  • 62. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • The opening of protection devices (fuse, circuit- breaker), and the opening or closing of control devices (relays, contactors, etc.). • Inductive circuits due to motors starting and stopping, or the opening of transformers such as MV/LV substations. • Capacitive circuits due to the connection of capacitor banks to the network. • All devices that contain a coil, a capacitor or a transformer at the power supply inlet: relays, contactors, television sets, printers, computers, electric ovens, filters, etc. 62
  • 63. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • These overvoltages have the same frequency as the network (50, 60 or 400 Hz). 63
  • 64. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Phase/frame or phase/earth insulating faults on a network with an insulated or impedance-neutral, or by the breakdown of the neutral conductor. When this happens, single phase devices will be supplied in 400 V instead of 230 V. • A cable breakdown. For example, a medium voltage cable which falls on a low voltage line. • The arcing of a high or medium voltage protective spark-gap causing a rise in earth potential during the action of the protection devices. 64
  • 65. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • In a dry environment, electrical charges accumulate and create a very strong electrostatic field. • For example, a person walking on carpet with insulating soles will become electrically charged to a voltage of several kilovolts. If the person walks close to a conductive structure, he will give off an electrical discharge of several amperes in a very short rise time of a few nanoseconds. • If the structure contains sensitive electronics, a computer for example, its components or circuit boards maybe damaged. 65
  • 66. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Primary protection devices (protection of installations against lightning). • Secondary protection devices (protection of internal installations against lightning). 66
  • 67. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • The purpose of primary protection devices is to protect installations against direct strokes of lightning. • They catch and run the lightning current into the ground. The principle is based on a protection area determined by a structure which is higher than the rest. • There are three types of primary protection: – Lightning conductors – Overhead earth wires – The meshed cage or Faraday cage 67
  • 68. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • The lightning conductor is a tapered rod placed on top of the building. It is earthed by one or more conductors (often copper strips). 68
  • 69. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • These wires are stretched over the structure to be protected. They are used for special structures: rocket launch pads, military applications and lightning protection cables for overhead high voltage power lines. 69
  • 70. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • This principle is used for very sensitive buildings housing computer or integrated circuit production equipment. • It consists in symmetrically multiplying the number of down strips outside the building. 70
  • 71. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • These handle the effects of atmospheric, operating or industrial frequency voltage surges. • They can be classified according to the way they are connected in an installation: serial or parallel protection. 71
  • 72. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • This is connected in series to the power supply wires of the system to be protected. 72
  • 73. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Transformers – They reduce voltage surges by inductor effect and make certain harmonics disappear by coupling. This protection is not very effective. • Filters – Based on components such as resistors, inductance coils and capacitors they are suitable for voltage surges caused by industrial and operation disturbance corresponding to a clearly defined frequency band. This protection device is not suitable for atmospheric disturbance. 73
  • 74. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Wave absorbers – They are essentially made up of air inductance coils which limit the voltage surges, and surge arresters which absorb the currents. They are extremely suitable for protecting sensitive electronic and computing equipment. 74
  • 75. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Network conditioners and static uninterrupted power supplies (UPS) – These devices are essentially used to protect highly sensitive equipment, such as computer equipment, which requires a high quality electrical power supply. – They can be used to regulate the voltage and frequency, stop interference and ensure a continuous electrical power supply even in the event of a mains power failure (for the UPS). – On the other hand, they are not protected against large, atmospheric type voltage surges against which it is still necessary to use surge arresters. 75
  • 76. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • The parallel protection is adapted to any installation power level. This type of overvoltage protection is the most commonly used. 76
  • 77. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • Main characteristics – The rated voltage of the protection device must correspond to the network voltage at the installation terminals. – When there is no voltage surge, a leakage current should not go through the protection device which is on standby. – When a voltage surge above the allowable voltage threshold of the installation to be protected occurs, the protection device abruptly conducts the voltage surge current to the earth by limiting the voltage to the desired protection level, Vp. 77
  • 78. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy • When the voltage surge disappears, the protection device stops conducting and returns to standby without a holding current. This is the ideal U/I characteristic curve: – The protection device response time (tr) must be as short as possible to protect the installation as quickly as possible. – The protection device must have the capacity to be able to conduct the energy caused by the foreseeable voltage surge on the site to be protected. – The surge arrester protection device must be able to withstand the rated current, In. 78
  • 79. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy (1) Voltage limiters • They are used in MV/LV substations at the transformer output, in IT earthing scheme. • They can run voltage surges to the earth, especially industrial frequency surges. 79
  • 80. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy (2) LV surge arresters • Low voltage surge arresters come in the form of modules to be installed inside LV switchboard. • They ensure secondary protection of nearby elements but have a small flow capacity. • Some are even built into loads although they cannot protect against strong voltage surges. 80
  • 81. BEX 42803/ BEF 33203/ BEE 4213 – Utilisation of Electrical Energy (3) Low current surge arresters • These protect telephone or switching networks against voltage surges from the outside (lightning), as well as from the inside (polluting equipment, switchgear switching, etc.). • Low current voltage surge arresters are also installed in distribution boxes or built into loads. 81