2. PLC Fundamantel
• What Is PLC ?????
Programmable Logic Controller
Hardware
- Ladder Logic
- FBD
- SFC
Reprogramming
• Let's come next page how to use thsi system parcticaly
3. PLC Fundamantel
• Example:- Water Level Control
INPUT OUTPUTProcessor
PLC
80%
60%
40%
20%
0%
NO/OFF
Valve
Automatic
Manualy
ValveTank
• This System INPUT is User level
requirment like 50% ,80% ,20%.
• And Output is solenoid valve
• This All system runing in
processor means this work on
PLC.so this is functioning of PLC.
• This Fundamantel of PLC...
4. PLC INPUT Wiring
What is Sink and Source:-Sink and source refer to the direction
of current flow between an I/O point on an I/O module and the connected
device. It is only relevant for DC circuits with positive and negative
polarities since current flows both directions in an AC circuit.more
explain..
S/S
X0
X1
X2
X3
INPUT
S/S
X0
0V
24V
24V
0V
_
+
_
+
This Circuit Call Opto
couplor
• If input 24v
then we gives
S/S 0V so it will
be depand on
INPUT
10. PLC OUTPUT Wiring
Hear Is Two Types Of PLC output.
Transistor Type
Output
Relay Type
Output
Transistor type PLC output capcity 0.1A as per PLC
configuration so we can not use havy load out put.
If you want to use havy load output in transistor type
plc you can use external rely then we use havy load
output.
Transistor type PLC mostly use in high speed
application.e.g Servo motor,steppar motor etc.
Relay Type PLC have 1A to 10A capacity so we can
directly use havy load output.
its was used in genral purpos
motor,contector,solenoid valve application
11. PLC OUTPUT Wiring
0V
LAMP 24V
0v
This Lap taks 0.1amp
Transister Type PLC OUTPUT.
C0
Y0
C1
Y1
0V
This load 4AmpThis relay 10Amp
24V
12. PLC OUTPUT Wiring
0V
LAMP 24V
0v
This Lap taks 0.1amp
Relay Type PLC OUTPUT.
C0
Y0
C1
Y1
0V
This load 4Amp
24V