Transmission and distribution systems- D.C 2-wire and 3- wire systems, A.C single phase, three phase and 4-wire systems, comparison of copper efficiency. Primary and secondary
distribution systems, concentrated & uniformly distributed loads on distributors fed at both ends, ring distributor, voltage drop and power loss calculation, Kelvinβslaw.
2. ο¨ Unit-i Electric Power Generation& Economic
Considerations
ο¨ Unit-ii Power Supply Systems& Distribution
Systems
ο¨ Unit-iii Inductance & Capacitance Calculations
ο¨ Unit-iv Performance Of Transmission Lines
ο¨ Unit-v Overhead Line Insulators
6 October 2020 D.Rajesh Asst.Prof. EEE Department 2
3. POWER SUPPLY SYSTEMS& DISTRIBUTION
SYSTEMS:
ο¨ Transmission and distribution systems- D.C 2-wire
and 3- wire systems, A.C single phase , three phase
and 4-wire systems, comparison of copper efficiency.
ο¨ Primary and secondary distribution systems,
concentrated & uniformly distributed loads on
distributors fed at both ends, ring distributor,
voltage drop and power loss calculation,
ο¨ Kelvinβslaw.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 3
4. Power
Transmission
D.C
D.C. two-wire
D.C. two-wire
with mid-point
earthed
D.C. three-wire
A.C
Single-phase A.C.
system
Single-phase two-
wire
Single-phase two-
wire with mid-
point earthed
Single-phase
three-wire
Two-phase A.C.
system
Two-phase four-
wire
Two-phase three
wire.
Three-phase A.C.
system
Three-phase
three-wire
Three-phase four-
wire
6 October 2020 D.Rajesh Asst.Prof. EEE Department 4
5. 6 October 2020 D.Rajesh Asst.Prof. EEE Department 5
Overhead
Under ground
6. (i) Same power (P watts) transmitted by each system.
(ii) The distance (l metres) over which power is
transmitted remains the same.
(iii) The line losses (W watts) are the same in each
case.
(iv) The maximum voltage between any conductor
and earth (π
π) is the same in each case.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 6
7. Max. voltage between conductors = π
π ,
Power to be transmitted = P= π
ππΌ1 1
β΄ Load current, πΌ1 = P/ π
π
If π 1 is the resistance of each line conductor, then,
π 1 = Ο l/ π1
where π1 is the area of X-section of the conductor.
copper losses in line W = πΌ1
2
π 1 + πΌ1
2
π 1
=2πΌ1
2
π 1
6 October 2020 D.Rajesh Asst.Prof. EEE Department 7
1
1
2
8. The maximum voltage between any conductor and earth is π
π so that maximum
voltage between conductors is 2 π
π. π 2 is the resistance of each line conductor
Power to be transmitted
P= π
ππΌ2+ π
ππΌ2=2 π
ππΌ2
Load current, πΌ2 = P/2 π
π
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 3
2π
ππΌ2= π
ππΌ1
πΌ2 =
πΌ1
2
copper losses in line W = πΌ2
2
π 2+ πΌ2
2
π 2 = 2 πΌ2
2
π 2
From eq 4
W=2(
πΌ1
2
)2
π 2 =
πΌ1
2
2
π 2
6 October 2020 D.Rajesh Asst.Prof. EEE Department 8
3
4
5
9. ο¨ Compare eq 2 & 5
2πΌ1
2
π 1 = (
πΌ1
2
2
) π 2
π 1
π 2
=
1
4
π1
π2
=4 (where R = Ο l/ π)
π1=X-area of conductor in 2 wire dc system
π2= X-area of conductor in 2 wire dc system with mid-point earthed
Then
volume of copper wire Twoβwire D.C system with midβpoint earthed
volume of copper wire Twoβwire D.C system
=
π2βπ2
π1βπ1
=
1
4
π1β2π
π1β2π
=
1
4
where π1 = π2=l+l
Hence, the volume of conductor material required in Twoβwire D.C system with
midβpoint earthed is one-fourth of that required in a two-wire D.C system with
one conductor earthed.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 9
10. If the load is balanced, the current in the neutral wire is zero. Assuming balanced loads,
Power to be transmitted
P= π
ππΌ3+ π
ππΌ3=2 π
ππΌ3 6
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 6
2π
ππΌ3= π
ππΌ1
πΌ3 =
πΌ1
2
7
Let π 3 is the resistance of each line conductor,
the area of X-section of neutral wire to be half that of the outer wire,
copper losses in line W = πΌ3
2
π 3+ πΌ3
2
π 3 = 2πΌ3
2
π 3 8
From eq 7
W=2(
πΌ1
2
)2
π 3 =
πΌ1
2
2
π 3 9
6 October 2020 D.Rajesh Asst.Prof. EEE Department 10
11. ο¨ Compare eq 2 & 8
2πΌ1
2
π 1 =
πΌ1
2
2
π 3
π 1
π 3
=
1
4
π 3 = Ο l/ π3 where π3 is the area of X-section of the conductor.
π1
π3
=4
Then
volume of copper wire Threeβwire D.C
volume of copper wire Twoβwire D.C system
=
π3βπ3
π1βπ1
=
1
4
π1β2.5π
π1β2π
=
2.5
8
where π3=l+l+0.5l
=0.3125
Hence, the volume of conductor material required in Threeβwire D.C system is 0.3125
times of that required in a two-wire D.C system with one conductor earthed.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 11
12. The maximum voltage between conductors is π
π, so that r.m.s. value of voltage
between them is
ππ
2
. Assuming the load power factor to be cos Ο, load current πΌ4
Power supplied P=
ππ
2
πΌ4 cos Ο 10
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 10
ππ
2
πΌ4 cos Ο= π
ππΌ1
πΌ4=
2πΌ1
cos Ο
11
Let π 4 is the resistance of each line conductor
copper losses in line W = πΌ4
2
π 4+ πΌ4
2
π 4 = 2πΌ4
2
π 4
=2(
2πΌ1
cos Ο
)2 π 4 =4
πΌ1
2
πππ 2Ο
π 4 12
6 October 2020 D.Rajesh Asst.Prof. EEE Department 12
13. ο¨ Comparing copper losses with 2 wire d.c system
4
πΌ1
2
πππ 2Ο
π 4= 2πΌ1
2
π 1
π 4
π 1
=
πππ 2Ο
2
π4
π1
=
2
πππ 2Ο
13
volume of copper wire 1βphase 2β wire
volume of copper wire Twoβwire D.C system
=
π4π4
π1π1
=
2
πππ 2Οπ12π
π12π
=
2
πππ 2Ο
Hence, the volume of conductor material required in this system is
2
πππ 2Ο
times
that of 2-wire d.c. system with the one conductor earthed.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 13
14. ο¨ The two wires possess equal and opposite voltages to earth (i.e., π
π).
ο¨ Therefore, the maximum voltage between the two wires is
ππ
2
. The
r.m.s. value of voltage between conductors is =2
ππ
2
= 2 π
π.
Assuming the power factor of the load to be cos Ο, load current πΌ5
ο¨ Power supplied P= 2 π
ππΌ5 cos Ο 14
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 14
2 π
ππΌ5 cos Ο= π
ππΌ1
πΌ5=
πΌ1
2 cos Ο
15
6 October 2020 D.Rajesh Asst.Prof. EEE Department 14
15. Let π 5 is the resistance of each line conductor
copper losses in line W = πΌ5
2
π 5+ πΌ5
2
π 5 = 2πΌ5
2
π 5
=2(
πΌ1
2 cos Ο
)2 π 5 =
πΌ1
2
πππ 2Ο
π 5
Comparing copper losses with 2 wire d.c system
πΌ1
2
πππ 2Ο
π 5 =2πΌ1
2
π 1
π 5
π 1
= 2πππ 2Ο
π5
π1
=
1
2πππ 2Ο
volume of copper wire 1βphase 2β wire π€ππ‘β πππ β πππππ‘ ππππ‘βππ
volume of copper wire Twoβwire D.C system
π5π5
π1π1
=
1
2πππ 2Ο π12π
π12π
=
1
2πππ 2Ο
Hence the volume of conductor material required in this system is
1
2πππ 2Ο
times that of 2-wire d.c. system with one conductor earthed.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 15
16. ο¨ If the load is balanced, the current through the neutral wire is zero.
Assuming balanced load,
ο¨ The two wires possess equal and opposite voltages to earth (i.e., π
π).
ο¨ Therefore, the maximum voltage between the two wires is
ππ
2
. The r.m.s.
value of voltage between conductors is 2
ππ
2
= 2 π
π. Assuming the
power factor of the load to be cos Ο, load current πΌ6
ο¨ Power supplied P= 2 π
ππΌ6 cos Ο 16
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 16
2 π
ππΌ6 cos Ο= π
ππΌ1
πΌ6=
πΌ1
2 cos Ο
17
6 October 2020 D.Rajesh Asst.Prof. EEE Department 16
17. Let π 6 is the resistance of each line conductor
copper losses in line W = πΌ6
2
π 6+ πΌ6
2
π 6 = 2πΌ6
2
π 6
=2(
πΌ1
2 cos Ο
)2 π 6 =
πΌ1
2
πππ 2Ο
π 6
Comparing copper losses with 2 wire d.c system
πΌ1
2
πππ 2Ο
π 6 =2πΌ1
2
π 1
π 6
π 1
= 2πππ 2Ο
π6
π1
=
1
2πππ 2Ο
volume of copper wire 1βphase3βwire system
volume of copper wire Twoβwire D.C system
π6π6
π1π1
=
1
2πππ 2Ο π12.5π
π12π
=
0.625
πππ 2Ο
Hence the volume of conductr material required in this system is
0.625
πππ 2Ο
times that of 2-wire d.c. system with one conductor earthed.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 17
18. ο¨ This system can be considered as two independent single-
phase systems, each transmitting one half of the total power.
ο¨ As the voltage is same (π
π) as in a Single phase 2-wire system
with mid-point earthed, so the current will be half of the
Single phase system
ο¨ i.e. πΌ7=
πΌ5
2
=
πΌ1
2 cos Ο
2
=
πΌ1
2 2 cos Ο
ο¨ If the current density remains constant the
X-area will be half of the single-phase system
ο¨ i.e. π7=
π5
2
=
1
2πππ 2Ο π1
2
=
π1
4πππ 2Ο
6 October 2020 D.Rajesh Asst.Prof. EEE Department 18
19. ο¨ Since wires are four
ο¨ Then
ο¨
volume of copper wireTwo phase, 4βwire a.c. system
volume of copper wire Twoβwire D.C system
π7π7
π1π1
=
1
4πππ 2Ο π14π
π12π
=
1
2πππ 2Ο
Hence the volume of conductor material required in this system
is
1
2πππ 2Ο
times that of 2-wire d.c. system with one conductor
earthed.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 19
20. The third or neutral wire is taken from the junction of two-phase windings whose
voltages are in quadrature with each other. Obviously, each phase transmits one
half of the total power. The R.M.S. voltage between outgoing conductor and
neutral =
ππ
2
, Let π 8 is the resistance of each line conductor
Total power transmitted=2
ππ
2
πΌ8 cos Ο
Comparing the power with 2-wire D.C
2
ππ
2
πΌ8 cos Ο= π
ππΌ1
πΌ8 =
πΌ1
2cos Ο
The middle wire will act as a common return and the current through it will be
πΌ8
2
+ πΌ8
2
= 2 πΌ8
6 October 2020 D.Rajesh Asst.Prof. EEE Department 20
21. ο¨ Assuming the current density to be constant, the area of X-section of the neutral wire will be
2 times that of either of the outers.
ο¨ β΄ Resistance of neutral wire=
π 8
2
ο¨ Copper losses in this system
W= πΌ8
2
π 8+ πΌ8
2
π 8 + ( 2 πΌ8)2π 8
2
= 2πΌ8
2
π 8+ 2πΌ8
2
π 8=(2+ 2) πΌ8
2
π 8
Where πΌ8 =
πΌ1
2cos Ο
W=(2+ 2) (
πΌ1
2cos Ο)2 π 8=(2+ 2)
πΌ1
2π 8
2πππ 2Ο
Comparing copper losses with 2 wire d.c system
(2+ 2)
πΌ1
2π 8
2πππ 2Ο
= 2πΌ1
2
π 1
π 8
π 1
=
4πππ 2Ο
(2+ 2)
π8
π1
=
(2+ 2)
4πππ 2Ο
volume of copper wireTwo phase, 3βwire a.c. system
volume of copper wire Twoβwire D.C system
π8π8
π1π1
=
(2+ 2)
4πππ 2Ο π1(2+ 2)π
π12π
=
1.457
πππ 2Ο
Hence, the volume of conductor material required for this system is
1.457
πππ 2Ο times that of 2-wire d.c.
system with one conductor earthed.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 21
22. This system is almost universally adopted for transmission of electric power.
The 3-phase, 3- wire system may be star connected or delta connected.
Maximum voltage between each conductor and neutral =π
π
Let π 9 is the resistance of each line conductor
R.M.S. voltage per phase =
ππ
2
Power supplied=3(
ππ
2
I9cos Ο )
ο¨ Comparing the power with 2-wire D.C
3
ππ
2
πΌ9 cos Ο= π
ππΌ1
πΌ9 =
2πΌ1
3cos Ο
6 October 2020 D.Rajesh Asst.Prof. EEE Department 22
23. ο¨ Total copper losses= 3πΌ9
2
π 9 =3 (
2πΌ1
3cos Ο
)2 π 9=
2πΌ1
2
π 9
3πππ 2Ο
ο¨ Comparing copper losses with 2 wire d.c system
2πΌ1
2
π 9
3πππ 2Ο
= 2πΌ1
2
π 1
π 9
π 1
= 3πππ 2Ο
π9
π1
=
1
3πππ 2Ο
volume of copper wire3βPhase, 3βwire system
volume of copper wire Twoβwire D.C system
=
π9π9
π1π1
=
1
3πππ 2Οπ13π
π12π
=
0.5
πππ 2Ο
Hence, the volume of conductor material required for this system is
0.5
πππ 2Ο times that required for 2-wire d.c. system with one conductor earthed.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 23
24. In this case, 4th or neutral wire is taken from the neutral point. The area of X-
section of the neutral wire is generally one-half that of the line conductor. If the
loads are balanced, then current through the neutral wire is zero. Assuming
balanced loads and p.f. of the load as cos Ο,
Let π 10 is the resistance of each line conductor
R.M.S. voltage per phase =
ππ
2
Power supplied=3(
ππ
2
I10cos Ο )
ο¨ Comparing the power with 2-wire D.C
3
ππ
2
πΌ10 cos Ο= π
ππΌ1
πΌ10 =
2πΌ1
3cos Ο
6 October 2020 D.Rajesh Asst.Prof. EEE Department 24
25. ο¨ Total copper losses= 3πΌ10
2
π 10 =3 (
2πΌ1
3cos Ο
)2 π 10=
2πΌ1
2
π 10
3πππ 2Ο
ο¨ Comparing copper losses with 2 wire d.c system
2πΌ1
2
π 10
3πππ 2Ο
= 2πΌ1
2
π 1
π 10
π 1
= 3πππ 2Ο
π10
π1
=
1
3πππ 2Ο
volume of copper wire3βPhase, 3βwire system
volume of copper wire Twoβwire D.C system
=
π10π10
π1π1
=
1
3πππ 2Οπ13.5π
π12π
=
0.583
πππ 2Ο
Hence, the volume of conductor material required for this system is
0.583
πππ 2Ο times that required for 2-wire d.c. system with one conductor earthed.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 25
26. In the under-ground system the maximum stress exists
on the insulation between the conductors.
(i) Same power (P watts) transmitted by each system.
(ii) The distance (l meters) over which power is
transmitted remains the same.
(iii) The line losses (W watts) are the same in each case.
(iv) The maximum voltage between conductors (π
π) is
the same in each case.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 26
27. Max. voltage between conductors = π
π ,
Power to be transmitted = P= π
ππΌ1 1
β΄ Load current, πΌ1 = P/ π
π
If π 1 is the resistance of each line conductor, then,
π 1 = Ο l/ π1
where π1 is the area of X-section of the conductor.
copper losses in line W = πΌ1
2
π 1 + πΌ1
2
π 1
=2πΌ1
2
π 1
6 October 2020 D.Rajesh Asst.Prof. EEE Department 27
1
1
2
28. Maximum voltage between conductors is π
π. π 2 is the resistance of each line
conductor
Power to be transmitted
P= π
ππΌ2
Load current, πΌ2 = P/ π
π
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 3
π
ππΌ2= π
ππΌ1
πΌ2 = πΌ1
copper losses in line W = πΌ2
2
π 2+ πΌ2
2
π 2 = 2 πΌ2
2
π 2
From eq 4
W=2( πΌ1)2 π 2 =2πΌ1
2
π 2
6 October 2020 D.Rajesh Asst.Prof. EEE Department 28
3
4
5
29. ο¨ Compare eq 2 & 5
2πΌ1
2
π 1 = (πΌ1
2
) π 2
π 1
π 2
=1
π1
π2
=1 (where R = Ο l/ π)
π1=X-area of conductor in 2 wire dc system
π2= X-area of conductor in 2 wire dc system with mid-point earthed
Then
volume of copper wire Twoβwire D.C system with midβpoint earthed
volume of copper wire Twoβwire D.C system
=
π2βπ2
π1βπ1
=
π1β2π
π1β2π
=1 where π1 = π2=l+l
Hence, the volume of conductor material required in this system is the same as
that for 2-wire d.c. system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 29
30. If the load is balanced, the current in the neutral wire is zero. Assuming balanced loads,
Power to be transmitted
P= π
ππΌ3 6
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 6
π
ππΌ3= π
ππΌ1
πΌ3 = πΌ1 7
Let π 3 is the resistance of each line conductor,
the area of X-section of neutral wire to be half that of the outer wire,
copper losses in line W = πΌ3
2
π 3+ πΌ3
2
π 3 = 2πΌ3
2
π 3 8
From eq 7
W=2( πΌ1)2
π 3 =2πΌ1
2
π 3 9
6 October 2020 D.Rajesh Asst.Prof. EEE Department 30
31. ο¨ Compare eq 2 & 8
2πΌ1
2
π 1 = 2(πΌ1
2
) π 3
π 1
π 3
=1
π1
π3
=1 π 3 = Ο l/ π3
where π3 is the area of X-section of the conductor.
Then
volume of copper wire Threeβwire D.C
volume of copper wire Twoβwire D.C system
=
π3βπ3
π1βπ1
=
π1β2.5π
π1β2π
=
2.5
2
where π3=l+l+0.5l
=1.25
Hence, the volume of conductor material required in the system is 1Β·25 times
that required for 2-wire d.c. system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 31
32. The maximum voltage between conductors is π
π, so that r.m.s. value of voltage
between them is
ππ
2
. Assuming the load power factor to be cos Ο, load current πΌ4
Power supplied P=
ππ
2
πΌ4 cos Ο 10
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 10
ππ
2
πΌ4 cos Ο= π
ππΌ1
πΌ4=
2πΌ1
cos Ο
11
Let π 4 is the resistance of each line conductor
copper losses in line W = πΌ4
2
π 4+ πΌ4
2
π 4 = 2πΌ4
2
π 4
=2(
2πΌ1
cos Ο
)2 π 4 =4
πΌ1
2
πππ 2Ο
π 4 12
6 October 2020 D.Rajesh Asst.Prof. EEE Department 32
33. ο¨ Comparing copper losses with 2 wire d.c system
4
πΌ1
2
πππ 2Ο
π 4= 2πΌ1
2
π 1
π 4
π 1
=
πππ 2Ο
2
π4
π1
=
2
πππ 2Ο
13
volume of copper wire 1βphase 2β wire
volume of copper wire Twoβwire D.C system
=
π4π4
π1π1
=
2
πππ 2Οπ12π
π12π
=
2
πππ 2Ο
Hence, the volume of conductor material required in this system is
2
πππ 2Ο
times
that of 2-wire d.c. system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 33
34. The maximum value of voltage between the outers is π
π.
Therefore, the r.m.s. value of voltage is
ππ
2
Assuming the power factor of the load to be cos Ο, load current πΌ5
Power supplied P=
ππ
2
πΌ5 cos Ο 14
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 14
ππ
2
πΌ5 cos Ο= π
ππΌ1
πΌ5=
2πΌ1
cos Ο
15
6 October 2020 D.Rajesh Asst.Prof. EEE Department 34
35. Let π 5 is the resistance of each line conductor
copper losses in line W = πΌ5
2
π 5+ πΌ5
2
π 5 = 2πΌ5
2
π 5
=2(
2πΌ1
cos Ο
)2 π 5 =
4πΌ1
2
πππ 2Ο
π 5
Comparing copper losses with 2 wire d.c system
4πΌ1
2
πππ 2Ο
π 5 =2πΌ1
2
π 1
π 5
π 1
=
πππ 2Ο
2
π5
π1
=
2
πππ 2Ο
volume of copper wire 1βphase 2β wire π€ππ‘β πππ β πππππ‘ ππππ‘βππ
volume of copper wire Twoβwire D.C system
π5π5
π1π1
=
2
πππ 2Ο π12π
π12π
=
2
πππ 2Ο
Hence, the volume of conductor material required in this system is
2
πππ 2Ο
times that required in 2-wire d.c. system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 35
36. ο¨ If the load is balanced, the current through the neutral wire is zero.
Assuming balanced load,
ο¨ The maximum value of voltage between the outers is π
π. Therefore, the
r.m.s. value of voltage is
ππ
2
.
ο¨ Assuming the power factor of the load to be cos Ο, load current πΌ6
ο¨ Power supplied P=
ππ
2
πΌ6 cos Ο 16
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 16
ππ
2
πΌ6 cos Ο= π
ππΌ1
πΌ6=
2πΌ1
cos Ο
17
6 October 2020 D.Rajesh Asst.Prof. EEE Department 36
37. Let π 6 is the resistance of each line conductor
copper losses in line W = πΌ6
2
π 6+ πΌ6
2
π 6 = 2πΌ6
2
π 6
=2(
2πΌ1
cos Ο
)2 π 6 =
4πΌ1
2
πππ 2Ο
π 6
Comparing copper losses with 2 wire d.c system
4πΌ1
2
πππ 2Ο
π 6 =2πΌ1
2
π 1
π 6
π 1
=
πππ 2Ο
2
π6
π1
=
2
πππ 2Ο
volume of copper wire 1βphase 2β wire π€ππ‘β πππ β πππππ‘ ππππ‘βππ
volume of copper wire Twoβwire D.C system
π6π6
π1π1
= =
2
πππ 2Ο π12.5π
π12π
=
2.5
πππ 2Ο
ο¨ Hence, the volume of conductor material required in this system is
2.5
πππ 2Ο
times that required in 2-wire d.c. system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 37
38. ο¨ This system can be considered as two independent single-phase
systems, each transmitting one half of the total power.
ο¨ Current (πΌ7) in each conductor will be half that in single-phase 2-
wire system. Consequently, area of X-section of each conductor is
also half but as there are four wires, so volume of conductor material
used is the same as in a single phase, 2-wire system
ο¨ i.e. πΌ7=
πΌ5
2
=
2πΌ1
cos Ο
2
=
πΌ1
2 cos Ο
ο¨ If the current density remains constant the
X-area will be half of the single-phase system
ο¨ i.e. π7=
π5
2
=
2
πππ 2Ο
2
=
1
πππ 2Ο
6 October 2020 D.Rajesh Asst.Prof. EEE Department 38
39. ο¨ Since wires are four
ο¨ Then
ο¨
volume of copper wireTwo phase, 4βwire a.c. system
volume of copper wire Twoβwire D.C system
π7π7
π1π1
=
1
πππ 2Ο π14π
π12π
=
2
πππ 2Ο
Hence, volume of conductor material required in this
system is
2
πππ 2Ο
times that required in 2- wire d.c. system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 39
40. ο¨ Let us suppose that maximum voltage between the outers is π
π. Then
maximum voltage between either outer and neutral wire is
ππ
2
ο¨ R.M.S. voltage between outer and neutral wire=
ππ
2
2
=
ππ
2
ο¨ Total power transmitted=2
ππ
2
πΌ8 cos Ο = π
π πΌ8 cos Ο
ο¨ Comparing the power with 2-wire D.C
π
π πΌ8 cos Ο= π
ππΌ1
πΌ8 =
πΌ1
cos Ο
The middle wire will act as a common return and the current through it will be
πΌ8
2
+ πΌ8
2
= 2 πΌ8
6 October 2020 D.Rajesh Asst.Prof. EEE Department 40
41. ο¨ Assuming the current density to be constant, the area of X-section of the neutral wire will be
2 times that of either of the outers.
ο¨ β΄ Resistance of neutral wire=
π 8
2
ο¨ Copper losses in this system
W= πΌ8
2
π 8+ πΌ8
2
π 8 + ( 2 πΌ8)2π 8
2
= 2πΌ8
2
π 8+ 2πΌ8
2
π 8=(2+ 2) πΌ8
2
π 8
Where πΌ8 =
πΌ1
cos Ο
W=(2+ 2) (
πΌ1
cos Ο)2
π 8=(2+ 2)
πΌ1
2π 8
πππ 2Ο
Comparing copper losses with 2 wire d.c system
(2+ 2)
πΌ1
2π 8
πππ 2Ο
= 2πΌ1
2
π 1
π 8
π 1
=
2πππ 2Ο
(2+ 2)
π8
π1
=
(2+ 2)
2πππ 2Ο
volume of copper wireTwo phase, 3βwire a.c. system
volume of copper wire Twoβwire D.C system
π8π8
π1π1
=
(2+ 2)
2πππ 2Ο π1(2+ 2)π
π12π
=
2.914
πππ 2Ο
Hence, the volume of conductor material required for this system is
2.914
πππ 2Ο times that of 2-wire d.c.
system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 41
42. This system is almost universally adopted for transmission of electric power. The 3-phase,
3- wire system may be star connected or delta connected.
Maximum voltage between conductors =π
π, Let π 9 is the resistance of each line conductor
Then maximum voltage between each phase and neutral is
ππ
3
R.M.S. voltage per phase =
ππ
3
2
=
ππ
6
Power supplied=3(
ππ
6
I9cos Ο )
ο¨ Comparing the power with 2-wire D.C
3
ππ
6
πΌ9 cos Ο= π
ππΌ1
πΌ9 =
6πΌ1
3cos Ο
6 October 2020 D.Rajesh Asst.Prof. EEE Department 42
43. ο¨ Total copper losses= 3πΌ9
2
π 9 =3 (
6πΌ1
3cos Ο
)2 π 9=
2πΌ1
2
π 9
πππ 2Ο
ο¨ Comparing copper losses with 2 wire d.c system
2πΌ1
2
π 9
πππ 2Ο
= 2πΌ1
2
π 1
π 9
π 1
= πππ 2Ο
π9
π1
=
1
πππ 2Ο
volume of copper wire3βPhase, 3βwire system
volume of copper wire Twoβwire D.C system
=
π9π9
π1π1
=
1
πππ 2Οπ13π
π12π
=
1.5
πππ 2Ο
Hence, the volume of conductor material required for this system is
1.5
πππ 2Ο times that required for 2-wire d.c. system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 43
44. In this case, 4th or neutral wire is taken from the neutral point. The area of X-
section of the neutral wire is generally one-half that of the line conductor. If the
loads are balanced, then current through the neutral wire is zero. Assuming
balanced loads and p.f. of the load as cos Ο,
Let π 10 is the resistance of each line conductor
R.M.S. voltage per phase =
ππ
6
Power supplied=3(
ππ
6
I10cos Ο )
ο¨ Comparing the power with 2-wire D.C
3
ππ
6
πΌ10 cos Ο= π
ππΌ1
πΌ10 =
6πΌ1
3cos Ο
6 October 2020 D.Rajesh Asst.Prof. EEE Department 44
45. ο¨ Total copper losses= 3πΌ10
2
π 10 =3 (
6πΌ1
3cos Ο
)2 π 10=
2πΌ1
2
π 10
πππ 2Ο
ο¨ Comparing copper losses with 2 wire d.c system
2πΌ1
2
π 10
πππ 2Ο
= 2πΌ1
2
π 1
π 10
π 1
= πππ 2Ο
π10
π1
=
1
πππ 2Ο
volume of copper wire3βPhase, 3βwire system
volume of copper wire Twoβwire D.C system
=
π10π10
π1π1
=
1
πππ 2Οπ13.5π
π12π
=
1.75
πππ 2Ο
Hence, the volume of conductor material required for this system
is
1.75
πππ 2Οtimes that required for 2-wire d.c. system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 45
46. System Same maximum
voltage to earth
Same maximum
voltage
between conductors
1. D.C. system
(i) Two-wire
(ii) Two-wire mid-point earthed
(iii) 3-wire
1
0.25
0.3125
1
1
1.25
2. Single phase system
(i) Two-wire
(ii) Two-wire mid-point earthed
(iii) 3-wire
2
πππ 2Ο
0.5
πππ 2Ο
1.625
πππ 2Ο
2
πππ 2Ο
0.5
πππ 2Ο
2.5
πππ 2Ο
6 October 2020 D.Rajesh Asst.Prof. EEE Department 46
47. System Same maximum voltage to
earth
Same maximum voltage
between conductors
3. Two-phase system
(i) 2βphase 4-wire
(ii)2-phase 3-wire
0.5
πππ 2Ο
1.457
πππ 2Ο
2
πππ 2Ο
2.914
πππ 2Ο
4. Three-phase system
(i) 3-phase 3-wire
(ii)3-phase 4-wire
,
0.5
πππ 2Ο
0.583
πππ 2Ο
1.5
πππ 2Ο
1.75
πππ 2Ο
6 October 2020 D.Rajesh Asst.Prof. EEE Department 47
48. What is the percentage saving in feeder copper if
the line voltage in a 2-wire d.c. system is raised
from 200 volts to 400 volts for the same power
transmitted over the same distance and having the
same power loss ?
6 October 2020 D.Rajesh Asst.Prof. EEE Department 48
49. ο¨ (i) Conductors
ο¨ (ii) Step-up and step-down transformers
ο¨ (iii) Line insulators
ο¨ (iv) Support
ο¨ (v) Protective devices
ο¨ (vi) Voltage regulating devices
6 October 2020 D.Rajesh Asst.Prof. EEE Department 49
50. The following two fundamental economic
principles which closely influence the electrical
design of a transmission line
(i) Economic choice of transmission voltage
(ii) Economic choice of conductor size
6 October 2020 D.Rajesh Asst.Prof. EEE Department 50
51. ο¨ The effect of increased voltage level of
transmission on
1. Volume of conductor material
used for transmission
2. Line Drop
6 October 2020 D.Rajesh Asst.Prof. EEE Department 51
52. Let a 3-phase A.C. system is used for the transmission, The resistance per conductor is given by
R= Ο l/A
Power transmitted P= 3ππΌcos Ο
I=
π
3πcos Ο
Total copper losses πππ’= 3πΌ2R =3(
π
3πcos Ο
)2Ο l
π΄
A=
π2Ο l
πππ’π2πππ 2Ο
The volume of copper used is V=3(A*l)
Volume of copper=
3π2Ο π2
πππ’π2πππ 2Ο
Volume of copper πΌ
1
π2πππ 2Ο
6 October 2020 D.Rajesh Asst.Prof. EEE Department 52
Thus greater is the
transmission voltage level,
lesser is the volume of the
copper required.
53. Line Drop=IR=I Ο l/A
Current density(J)=
πΌ
π΄
Then Line Drop=
πΌΟ l
πΌ
π½
= JΟ l
%Line Drop=
JΟ l
π
*100
Higher the transmission voltage level, then lesser the
%Line Drop
6 October 2020 D.Rajesh Asst.Prof. EEE Department 53
54. ο¨ The most economical area of conductor is that
for which the total annual cost of transmission
line is minimum . This is known as Kelvinβs
Law
ο¨ The total annual cost of transmission line can
be divided broadly into two parts viz.,
ο‘ Annual charge on capital outlay
ο‘ Annual cost of energy wasted in the conductor.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 54
55. ο¨ This is on account of interest and depreciation on the capital cost of
complete installation of transmission line. In case of overhead system,
it will be the annual interest and depreciation on the capital cost of
conductors, supports and insulators and the cost of their erection.
ο¨ Now, for an overhead line, insulator cost is constant, the conductor
cost is proportional to the area of X-section and the cost of supports
and their erection is partly constant annual charge.
ο¨ Transmission line can be expressed as :
π΄πππ’ππ πβππππ = π1 + π2π
π1 constant depending on the copper conductor
π2 constant depending on the X-area of the conductor
a is the area of X-section of the conductor
6 October 2020 D.Rajesh Asst.Prof. EEE Department 55
56. ο¨ This is on account of energy lost mainly in the conductor due to πΌ2R losses.
ο¨ Assuming a constant current in the conductor throughout the year,
ο¨ The energy lost in the conductor is proportional to resistance.
where R = Ο l/ π
ο¨ The energy lost in the conductor is inversely proportional to area of X-section.
energy lost Ξ±
1
π
ο¨ Thus, the annual cost of energy wasted in an overhead transmission line can
be expressed as :
Annual cost of energy wasted =
π3
π
where P3 is a constant.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 56
57. ο¨ Total annual cost, C=π1 + π2π+
π3
π
only area of X-section a is variable. Therefore, the total annual cost of
transmission line will be minimum if differentiation of C w.r.t. a is zero i.e.
β πΆ
β π
=0
β
β π
(π1 + π2π+
π3
π
)=0
π2π β
π3
π2=0
π2π =
π3
π2
i.e. Variable part of annual charge = Annual cost of energy wasted
Therefore Kelvinβs Law can also be stated
The most economical area of conductor is that for which the variable part of
annual charge is equal to the cost of energy losses per year.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 57
58. ο¨ The straight line shows the relation between the
annual charge (i.e., π1 + π2π) and the area of X-
section a of the conductor
ο¨ The rectangular hyperbola
gives the relation between
annual cost of energy wasted (
π3
π
)
and X-sectional area a.
ο¨ Curve 3 shows the relation between total annual
cost of transmission line and area of X-section a.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 58
59. ο¨ (i) It is not easy to estimate the energy loss in the line without actual load
curves, which are not available at the time of estimation.
ο¨ (ii) The assumption that annual cost on account of interest and
depreciation on the capital outlay is in the form π1 + π2π is strictly
speaking not true. For instance, in cables neither the cost of cable dielectric
and sheath nor the cost of laying vary in this manner.
ο¨ (iii) This law does not take into account several physical factors like safe
current density, mechanical strength, corona loss etc.
ο¨ (iv) The conductor size determined by this law may not always be
practicable one because it may be too small for the safe carrying of
necessary current.
ο¨ (v) Interest and depreciation on the capital outlay cannot be determined
accurately.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 59
61. ο¨ Annual cost of energy lost = Cost per kWh Γ Annual energy loss
=Rs 0.05*
121238.4
π
kWh=Rs
6062
π
The capital cost (variable) of the cable is given to be Rs 20 a per metre.
Therefore, for 1 km length of the cable, the capital cost (variable) is Rs. 20 a Γ
1000 = Rs. 20,000 a.
Variable annual charge = Annual interest and depreciation on
capital cost (variable) of cable
= Rs 0Β·1 Γ 20,000 a
= Rs 2000 a
According to Kelvinβs law, for most economical X-section of the conductor,
Variable annual charge = Annual cost of energy lost
2000 a =
6062
π
a=
6062
2000
=1.74 ππ2
6 October 2020 D.Rajesh Asst.Prof. EEE Department 61
63. ο¨ Annual cost of energy lost = Cost per kWh Γ Annual energy loss
=Rs 0.05*
18,94,350
π
β 10β8
kWh=Rs
94,717.5
π
β 10β8
Mass of 1 metre feeder = 2 (Volume Γ density)
= 2 Γ a Γ 1 Γ 8Β·93 Γ 103kg
= 17Β·86 Γ 103 a kg
Capital cost (variable) = Rs 5 Γ 17Β·86 Γ 103
a
= Rs 89Β·3 Γ 103
a
Variable annual charge = 10% of capital cost (variable)
= 0Β·1 Γ 89Β·3 Γ 103 a = Rs 8930 a
According to Kelvinβs law, for most economical X-section of the conductor,
Variable annual charge = Annual cost of energy lost
8930 a =
94,717.5
π
β 10β8
a=
94,717.5
8930
β 10β8
=3.25β 10β4
π2
= 3.25 ππ2
6 October 2020 D.Rajesh Asst.Prof. EEE Department 63
64. Determine the most economical cross-section for a 3-phase
transmission line, 1 km long to supply at a constant voltage of
110 kV for the following daily load cycle :
6 hours 20 MW at p.f. 0Β·8 lagging
12 hours 5 MW at p.f. 0Β·8 lagging
6 hours 6 MW at p.f. 0Β·8 lagging
The line is used for 365 days yearly. The cost per km of line
including erection is Rs (9000 +6000 a) where βaβ is the area of X-
section of conductor in cm2. The annual rate of interest and
depreciation is 10% and the energy costs 6P per kWh. The
resistance per km of each conductor is0Β·176/a.
Power transmitted P= 3ππΌcos Ο
Energy lost per annum=3R(πΌ2
π‘)
6 October 2020 D.Rajesh Asst.Prof. EEE Department 64
65. ο¨ The load currents at various loads are :
ο¨ At 20 MW, πΌ1=
π
3πcos Ο
=
20β106
3β110β103β0.8
= 131.2π΄
ο¨ At 5 MW, πΌ1=
π
3πcos Ο
=
5β106
3β110β103β0.8
= 32.8π΄
ο¨ At 6 MW, πΌ1=
π
3πcos Ο
=
6β106
3β110β103β0.8
= 39.36π΄
ο¨ Energy loss per day in 3-phase line
=3*
0.176
π
(131.22
β 6+ 32.82
β 12+ 36.362
β 6)
=
66.26
π
kWh
Energy lost per annum =
66.26
π
*365= =
24,184.9
π
kWh
Annual cost of energy=Rs
6
100
β
24,184.9
π
= =
1451.09
π
Variable annual charge = 10% of capital cost (variable) of line
= Rs 0Β·1 Γ 6000 a = Rs 600 a
According to Kelvinβs law, for most economical X-section of the conductor,
Variable annual charge = Annual cost of energy
600 a=
1451.09
π
a=
1451.09
600
=1.56 ππ2
6 October 2020 D.Rajesh Asst.Prof. EEE Department 65
66. The conveyance of electric power from a power station to
consumersβ premises is known as electric supply system.
ο¨ Electric supply system consist of three principle components:
1) Power station
2) Transmission lines
3) Distribution system
ο¨ The electric supply system can be broadly classified into:
1) DC or AC system
2)Overhead or underground system
6 October 2020 D.Rajesh Asst.Prof. EEE Department 66
67. Different blocks of typical acpowersupply scheme are asper
following::
1)Generating Station:
Ingenerating station power is producedby three phase alternators
operating inparallel.
The usual generation voltage is 11kV.
Foreconomy in the transmission of electric power, the generation
voltage is stepped upto 132 kVor more at generating station with the
help of three phase transformer.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 67
68. 2)Primarytransmission:
Theelectric power at 132 kVis transmitted by 3-phase,3 wire overhead system to the out
3)Secondary transmission:
Atthe receiving station the voltage is reduced to33kV by step down transformer.
4)Primary distribution:
Atthe substation voltage is reduced 33kV to 11kV.The11kV line run along important
roadsides to city. This forms the primary distribution.
69. 5)Secondarydistribution:
Theelectric power form primary distribution line is delivered to distribution substation. The
substation is located nearthe consumers location and step down the voltage to 400V, 3-
phase ,4-wire for secondary distribution.
The voltage between any two phases is 400V and between any phase and neutral is 230V.
70. Basis for Comparison AC Transmission Line DC Transmission Line
Definition The ac transmission line transmit the
alternating current.
The dc transmission line is used for
transmitting the direct current.
Number of Conductors Three Two
Inductance & surges Have Donβt Have
Voltage drop High Low
Skin Effect Occurs Absent
Need of Insulation More Less
Interference Have Donβt Have
Corona Loss Occur Donβt occur
Dielectric Loss Have Donβt have
Synchronizing and Stability Problem No difficulties Difficulties
Cost Expensive Cheap
Length of conductors Small More
Repairing and Maintenance Easy and Inexpensive Difficult and Expensive
Transformer Requires Not Requires
6 October 2020 D.Rajesh Asst.Prof. EEE Department 70
73. Which distributes
electric power for
local use is known as
distribution system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 73
74. ο¨ (i) Feeders. A feeder is a
conductor which connects the
sub-station to the area where
power is to be distributed.
ο¨ (ii) Distributor. A distributor is
a conductor from which
tappings are taken for supply
to the consumers.
ο¨ (iii) Service mains. A service
mains is generally a small cable
which connects the distributor
to the consumersβ terminals.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 74
80. ο¨ (i) Radial System.
In this system, separate feeders radiate from a single substation and feed
the distributors at one end only.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 80
81. ο¨ Limitations
ο¨ (a) The end of the distributor nearest to the feeding point will be
heavily loaded.
ο¨ (b) The consumers are dependent on a single feeder and single
distributor. Therefore, any fault on the feeder or distributor cuts off
supply to the consumers who are on the side of the fault away from
the substation.
ο¨ (c) The consumers at the distant end of the distributor would be
subjected to serious voltage fluctuations when the load on the
distributor changes.
Due to these limitations, this system is used for short
distances only.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 81
82. ο¨ (ii) Ring main system.
In this system, the primaries of distribution transformers form a loop. The
loop circuit starts from the substation bus-bars, makes a loop through the area to be served,
and returns to the substation.
β substation supplies to the
closed feeder LMNOPQRS.
β The distributors are tapped
from different points M, O and Q
of the feeder through distribution
transformers.
β’ There are less voltage fluctuations
at consumerβs terminals.
β’ The system is very reliable as each
distributor is fed via two feeders.
β’ In the event of fault
on any section of the feeder,
the continuity of supply is maintained.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 82
83. ο¨ (iii) Interconnected system. When the feeder ring is energized by two or
more than two generating stations or substations, it is called inter-connected
system.
(a) It increases the service reliability.
(b) Any area fed from one generating station during peak load hours can be fed
from the other generating station. This reduces reserve power capacity and
increase efficiency of the system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 83
84. ο¨ (i) Proper voltage.
ο¨ One important requirement of a distribution system is that voltage
variations at consumerβs terminals should be as low as possible.
ο¨ The changes in voltage are generally caused due to the variation of
load on the system.
ο¨ Low voltage causes loss of revenue, inefficient lighting and possible
burning out of motors.
ο¨ High voltage causes lamps to burn out permanently and may cause
failure of other appliances.
ο¨ Thus, if the declared voltage is 230 V, then the highest voltage of the
consumer should not exceed 244 V while the lowest voltage of the
consumer should not be less than 216 V.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 84
85. ο¨ (ii) Availability of power on demand. Power must be
available to the consumers in any amount that they
may require from time to time.
ο¨ (iii) Reliability. Modern industry is almost dependent
on electric power for its operation.
ο¨ The reliability can be improved to a considerable extent
by
(a) interconnected system
(b) reliable automatic control system
(c) providing additional reserve facilities.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 85
86. (i) Distributor fed at one end
(ii) Distributor fed at both ends
(iii) Distributor fed at the centre
(iv) Ring distributor.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 86
87. ο¨ (i) Distributor fed
at one end
6 October 2020 D.Rajesh Asst.Prof. EEE Department 87
ο¨ (ii) Distributor
fed at both ends
88. ο¨ (iii) Distributor
fed at the centre
6 October 2020 D.Rajesh Asst.Prof. EEE Department 88
ο¨ (iv) Ring
distributor
90. ο¨ 2-wire d.c. distributor AB fed at one end A and having concentrated loads πΌ1,
πΌ2, πΌ3 and πΌ4 tapped off at points C, D, E and F respectively.
ο¨ Let π1 , π2, π3 πππ π4 be the resistances of both wires (go and return) of the sections AC,
CD, DE and EF of the distributor respectively.
ο¨ Current fed from point A = πΌ1 + πΌ2 + πΌ3 + πΌ4 Current in section AC = πΌ1 + πΌ2 + πΌ3 + πΌ4
ο¨ Current in section CD = πΌ2 + πΌ3 + πΌ4 Current in section DE = πΌ3 + πΌ4
ο¨ Current in section EF = πΌ4
ο¨ Voltage drop in section AC = π1 (πΌ1 + πΌ2 + πΌ3 + πΌ4)
ο¨ Voltage drop in section CD = π2 (πΌ2 + πΌ3 + πΌ4) Voltage drop in section DE = π3 (πΌ3 + πΌ4)
ο¨ Voltage drop in section EF = π4 πΌ4
ο¨ β΄ Total voltage drop in the distributor
=π1 (πΌ1 + πΌ2 + πΌ3 + πΌ4)+π2 (πΌ2 + πΌ3 + πΌ4)+π3 (πΌ3 + πΌ4)+ π4 πΌ4
6 October 2020 D.Rajesh Asst.Prof. EEE Department 90
91. ο¨ 2-wire d.c. distributor AB fed at one end A and
loaded uniformly with i amperes per metre length.
ο¨ The load tapped is i amperes. Let π metres be the
length of the distributor and r ohm be the
resistance per metre run.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 91
92. ο¨ Consider a point C on the distributor at a distance x metres from the feeding point A
ο¨ Then current at point C is
= i πβ i x amperes = i (πβ x) amperes
Now, consider a small length dx near point C. Its resistance is r dx and the voltage drop over
length dx is
dv = i (π β x) r dx = i r (π β x) dx
Total voltage drop in the distributor upto point C is
v =β«Χ¬β¬0
π₯
ir (l β x)dx =ir ππ₯ β
π₯2
2
The voltage drop upto point B (i.e. over the whole distributor) can be obtained by putting x = π in
the above expression.
β΄ Voltage drop over the distributor AB
= ir π β π β
π2
2
=
1
2
πππ2
=
1
2
ππ ππ =
1
2
πΌπ
Thus, in a uniformly loaded distributor fed at one end, the total voltage drop is equal to that
produced by the whole of the load assumed to be concentrated at the middle point.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 92
93. ο¨ The two ends of the distributor may be supplied
with (i) equal voltages (ii) unequal voltages.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 93
94. ο¨ Consider a distributor AB fed at both ends with equal voltages V volts and having
concentrated loads πΌ1, πΌ2, πΌ3, πΌ4 and πΌ5 at points C, D, E, F and G respectively
ο¨ As we move away from one of the feeding points, say A, p.d. goes on decreasing till it
reaches the minimum value at some load point, say E, and then again starts rising and
becomes V volts as we reach the other feeding point B.
ο¨ All the currents tapped off between points A and E (minimum p.d. point) will be
supplied from the feeding point A while those tapped off between B and E will be
supplied from the feeding point B.
ο¨ The current tapped off at point E itself will be partly supplied from A and partly from
B. If these currents are x and y respectively, then,
x+y= πΌ3
ο¨ Therefore, we arrive at a very important conclusion that at the point of minimum
potential, current comes from both ends of the distributor.
ο¨ Voltage drop from feeding point A to the point of minimum potential difference is
equal to the voltage drop from feeding point B to the point of minimum potential
difference
6 October 2020 D.Rajesh Asst.Prof. EEE Department 94
95. ο¨ Distributor AB fed with unequal voltages ; end A being fed at π1volts
and end B at π2 volts.
ο¨ In order to determine the point of minimum potential, assume of πΌπ΄
amperes is supplied from feeding point A
ο¨ Let r be the resistance of each conductor per unit length(l=1) for both go
& return
ο¨ Resistance of portions AC,CD, DE,EF,FB are π1 , π2, π3 , π4, πππ π5
respectively
ο¨ Voltage drop between A and B = Voltage drop over AB
π1 β π2 = πΌπ΄π1+(πΌπ΄- πΌ1) π2 + (πΌπ΄- πΌ1- πΌ2) π3 + (πΌπ΄- πΌ1- πΌ2- πΌ3) π4+ (πΌπ΄- πΌ1- πΌ2- πΌ3 β πΌ4) π5
The load point at which currents are coming from both sides of the
distributor will be the point of minimum potential
6 October 2020 D.Rajesh Asst.Prof. EEE Department 95
97. ο¨ Actual distribution of currents in the various sections of the
distributor is
ο¨ Current in section EF, πΌπΈπΉ = πΌπ΄β110 =61Β·7β110 =β48Β·3A from E to F
= 48Β·3 A from F to E
ο¨ Current in section DE, πΌπ·πΈ = πΌπ΄ β60=61.7-60=1.7A from D to E
6 October 2020 D.Rajesh Asst.Prof. EEE Department 97
It is clear that currents are coming to load point E from both sides i.e.
from point D and point F. Hence, E is the point of minimum potential.
β΄ Minimum consumer voltage,
ππΈ = ππ΄-(πΌπ΄πΆ π1+ πΌπΆπ· π2+ πΌπ·πΈ π3)
=220-(61Β·7 Γ 0Β·034 + 41Β·7 Γ 0Β·051 + 1Β·7 Γ 0Β·051]
=215.69V
99. ο¨ Voltage drop between A and B = Voltage drop over AB
ο¨ ππ΄ β ππ΅ = πΌπ΄π1+(πΌπ΄- πΌ1) π2 + (πΌπ΄- πΌ1- πΌ2) π3 + (πΌπ΄- πΌ1- πΌ2- πΌ3) π4+ (πΌπ΄- πΌ1- πΌ2- πΌ3 β πΌ4) π5
ο¨ 440-430=0.03 πΌπ΄+(πΌπ΄-100)0.03+ (πΌπ΄-300)0.01+(πΌπ΄-550)0.02+(πΌπ΄-850)0.03
πΌπ΄=437.5A
ο¨ The actual distribution of currents in the various sections of the distributor are
ο¨ Current supplied from end A, πΌπ΄ = πΌπ΄πΆ = 437Β·5 A
ο¨ Current supplied from end B, πΌπ΅ = πΌπΉπ΅ = πΌπ΄ -850= - 412Β·5 A
ο¨ πΌπΆπ· = 337.5π΄ πΌπ·πΈ = 137.5π΄ πΌπΈπΉ = β112.5π΄
ο¨ Therefore E is the point of minimum potential.
ο¨ Power loss in the distributor
=πΌπ΄πΆ
2
π1+ πΌπΆπ·
2
π2 + πΌπ·πΈ
2
π3+ πΌπΈπΉ
2
π4+ πΌπΉπ΅
2
π5
=(437.5)2
β 0.03 + 337.5 2
β 0.03 + 137.5 2
β 0.01 + 112.5 2
β 0.02 + (412.5)2
β 0.03
=14.705kW
6 October 2020 D.Rajesh Asst.Prof. EEE Department 99
100. ο¨ (i) Distributor fed at both ends with equal voltages.
ο¨ Consider a distributor AB of length π metres, having resistance r
ohms per metre run and with uniform loading of π amperes per
metre run.
ο¨ Let the distributor be fed at the feeding points A and B at equal
voltages, say V volts.
ο¨ The total current supplied to the distributor is ππ.
ο¨ As the two end voltages are equal, therefore, current supplied from
each feeding point is
ππ
2
i.e.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 100
101. ο¨ Consider a point C at a distance x metres from the feeding point A. Then
current at point C is
=
ππ
2
- ππ₯= π(
π
2
-π₯)
Now, consider a small length dx near point C. Its resistance is r dx and the
voltage drop over length dx is
dv = i (
π
2
β x) r dx = i r (
π
2
β x) dx
Total voltage drop in the distributor upto point C is
v =β«Χ¬β¬
0
π₯
ir (
π
2
β x)dx =ir
ππ₯
2
β
π₯2
2
=
ππ
2
(ππ₯- π₯2)
Obviously, the point of minimum potential will be the mid-point. Therefore,
maximum voltage drop will occur at mid-point i.e. where x =
π
2
Max. voltage drop=
ππ
2
(ππ₯- π₯2)=
ππ
2
(π
π
2
- (
π
2
)2)=
1
8
πππ2=
1
8
ππ ππ =
1
8
IR
Minimum voltage=V-
1
8
IR volts
6 October 2020 D.Rajesh Asst.Prof. EEE Department 101
102. ο¨ (ii) Distributor fed at both ends with unequal voltages.
ο¨ Consider a distributor AB of length l metres having resistance r
ohms per metre run and with a uniform loading of i amperes
permetre run. Let the distributor be fed from feeding points A and B
at voltages ππ΄ and ππ΅ respectively.
ο¨ Suppose that the point of minimum potential C is situated at a
distance x metres from the feeding point A. Then current supplied
by the feeding point A will be i x.
ο¨ β΄ Voltage drop in section AC=
1
2
πππ₯2 volts
ο¨ As the distance of C from feeding point B is (l β x), therefore, current
fed from B is i (l β x).
ο¨ β΄ Voltage drop in section BC =
1
2
ππ(π β π₯)2
volts
6 October 2020 D.Rajesh Asst.Prof. EEE Department 102
103. ο¨ Voltage at point C, ππΆ = ππ΄ β Drop over AC
= ππ΄ -
1
2
πππ₯2
Voltage at point C, ππΆ = ππ΅ β Drop over BC
= ππ΅ -
1
2
ππ(π β π₯)2
From above equations we get,
ππ΄ -
1
2
πππ₯2 = ππ΅ -
1
2
ππ(π β π₯)2
ππ΄- ππ΅ =
1
2
πππ₯2
-
1
2
ππ(π β π₯)2
=
1
2
πππ₯2
-
1
2
πππ2
-
1
2
πππ₯2
+
1
2
ππ2ππ₯
= πππ {π₯-
1
2
π }
π₯=
ππ΄β ππ΅
πππ
+
π
2
The point on the distributor where minimum potential occurs can be calculated
6 October 2020 D.Rajesh Asst.Prof. EEE Department 103
104. ο¨ Expression for the power loss in a uniformly loaded distributor fed at both ends
ο¨ current supplied from each feeding point is
ππ
2
ο¨ Consider a small length dx of the distributor at point P which is at a distance x from
the feeding end A.
ο¨ Resistance of length dx = r dx
ο¨ Current in length dx =
ππ
2
- ππ₯= π(
π
2
-π₯)
ο¨ Power loss in length dx
= (current in dx)2 Γ Resistance of dx
= π(
π
2
βπ₯)
2
Γrdx
ο¨ Total power loss in the distributor is=β«Χ¬β¬
0
π
π(
π
2
βπ₯)
2
Γrdx
=π2
π β«Χ¬β¬
0
π π2
4
β ππ₯ + π₯2
ππ₯
= π2π
π2π₯
4
β
ππ₯2
2
+
π₯3
3
π
0
P=
π2ππ3
12
6 October 2020 D.Rajesh Asst.Prof. EEE Department 104
109. The total drop over any section of the distributor
is equal to the sum of drops due to concentrated
and uniform loading in that section.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 109
111. ο¨ Voltage drop between A and B = Voltage drop over AB
ο¨ ππ΄ β ππ΅ = πΌπ΄π1+(πΌπ΄- πΌ1) π2 + (πΌπ΄- πΌ1- πΌ2) π3 + (πΌπ΄- πΌ1- πΌ2- πΌ3)
π4+ (πΌπ΄- πΌ1- πΌ2- πΌ3 β πΌ4) π5
ο¨ 0= 10β4(
)
200 πΌπ΄+(πΌπ΄β120)200+
(πΌπ΄β180)300+(πΌπ΄β280)200+(πΌπ΄β320)100
πΌπ΄=166A
The actual distribution of currents in the various sections of the
distributor due to concentrated loading.
It is clear from this figure that D is the point of minimum
potential.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 111
112. (ii) The feeding point A will supply 166 A due to concentrated loading
plus 0Β·5 Γ 400 = 200 A due to uniform loading.
β΄ Current supplied byA, πΌπ΄ = 166 + 200 = 366 A
The feeding point B will supply a current of 154 A due to concentrated
loading plus 0Β·5 Γ 600 = 300 A due to uniform loading.
β΄ Current supplied by B, πΌπ΅ = 154 + 300 = 454 A
(iii) β΄ Minimum potential, ππ· = ππ΄ β Drop in AD due to conc. loading β
Drop in AD due to uniform loading ππ·
Now, Drop in AD due to conc. loading = πΌπ΄πΆ π π΄πΆ + πΌπΆπ· π πΆπ·
= 166 Γ 10β4
Γ 200 + 46 Γ 10β4
Γ 200
= 3Β·32 + 0Β·92 = 4Β·24 V
Drop in AD due to uniform loading =
1
2
πππ2
=
1
2
0.5 β 10β4
β (400)2
=4V
β΄ ππ· = 240 β 4Β·24 β 4 = 231Β·76 V
6 October 2020 D.Rajesh Asst.Prof. EEE Department 112
114. ο¨ (i) If r is the resistance of the distributor (go and return) per metre length,
then,
Voltage drop in length AD = πΌπ΄πΆ π π΄πΆ + πΌπΆπ· π πΆπ·
=(100+x)*100r+x*150r
Voltage drop in length BD=
1
2
πππ2
+(60-x)*250r
=
1
2
1 β π β (200)2 +(60-x)*250r
Since the feeding points A and B are at the same potential
(100+x)*100r+x*150r=
1
2
1 β π β (200)2 +(60-x)*250r
X=50A
The actual directions of currents in the various sections of the distributor are
currents supplied by A and B meet at D. Hence point D is the point of minimum
6 October 2020 D.Rajesh Asst.Prof. EEE Department 114
115. ο¨ (ii) Total current = 160 + 1 Γ 200 = 360 A
ο¨ Current supplied by A, πΌπ΄ = 100 + x = 100 + 50 = 150 A
ο¨ Current supplied by B, πΌπ΅ = 360 β 150 = 210 A
ο¨ Minimum potential, ππ· = ππ΄ β (πΌπ΄πΆ π π΄πΆ + πΌπΆπ· π πΆπ· )
= 240 β 150 Γ (100 Γ 0Β·001) β 50 Γ (150 Γ 0Β·001)
= 240 β 15 β 7Β·5 = 217Β·5 V
6 October 2020 D.Rajesh Asst.Prof. EEE Department 115
116. ο¨ A distributor arranged to form a closed loop and
fed at one or more points is called a ring
distributor.
ο¨ For the purpose of calculating voltage distribution,
the distributor can be considered as consisting of a
series of open distributors fed at both ends.
ο¨ The principal advantage of ring distributor is that
by proper choice in the number of feeding points,
great economy in copper can be affected.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 116
117. ο¨ Sometimes a ring distributor has to
serve a large area. In such a case,
voltage drops in the various
sections of the distributor may
become excessive.
ο¨ In order to reduce voltage drops in
various sections, distant points of
the distributor are joined through a
conductor called interconnector.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 117
118. ο¨ The ring distributor ABCDEA. The points B and D of the ring distributor are joined
through an interconnector BD.
ο¨ Network can be obtained by applying Theveninβs theorem.
ο¨ (i) Consider the interconnector BD to be disconnected and find the potential difference
between B and D. This gives Theveninβs equivalent circuit voltage πΈ0.
ο¨ (ii) Next, calculate the resistance viewed from points B and D of the network composed
of distribution lines only. This gives Theveninβs equivalent circuit series resistance π 0.
ο¨ (iii) If π π΅π· is the resistance of the interconnector BD, then Theveninβs equivalent circuit
will be
β΄ Current in interconnector BD =
πΈ0
π 0+π π΅π·
ο¨ Therefore, current distribution in each section and the voltage of load points can be
calculated.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 118
120. ο¨ (ii) Current in section AB = I = 29Β·04 A from A to B
ο¨ Current in section BC = I β 10 = 29Β·04 β 10 = 19Β·04 A from B to C
ο¨ Current in section CD = I β 30 = 29Β·04 β 30 = β 0Β·96 A = 0Β·96 A from D to C
ο¨ Current in section DE = I β 60 = 29Β·04 β 60 = β 30Β·96 A = 30Β·96 A from E to D
ο¨ Current in section EA = I β 70 = 29Β·04 β 70 = β 40Β·96 A = 40Β·96 A from A to E
6 October 2020 D.Rajesh Asst.Prof. EEE Department 120
β΄ C is the point of minimum potential.
122. The actual distribution of currents are ..
ο¨ Current in section AB = I = 336.75 A from A to B
ο¨ Current in section BC = I β 150 = 336.75 β 150 = 186.75 A from B to C
ο¨ Current in section CD = I β 450 = 336.75 β 450 = β 113.25 A = 113.25 A from D to C
ο¨ Current in section DA = I β 700 = 336.75 β 700 = β 363.25A = 363.25 A from A to D
Voltage drop in AB = 336Β·75 Γ 0Β·02 = 6Β·735 V
Voltage drop in BC = 186Β·75 Γ 0Β·018 = 3Β·361 V
Voltage drop in CD = 113Β·25 Γ 0Β·025 = 2Β·831 V
Voltage drop in DA = 363Β·25 Γ 0Β·02 = 7Β·265 V
β΄ Voltage at point B = 250 β 6Β·735 = 243Β·265 V
Voltage at point C = 243Β·265 β 3Β·361 = 239Β·904 V
Voltage at point D = 239Β·904 + 2Β·831 = 242Β·735 V
6 October 2020 D.Rajesh Asst.Prof. EEE Department 122
124. The actual distribution of currents are ..
ο¨ Current in section AB = πΌ1 = 203.15A from A to B
ο¨ Current in section BC = πΌ1 β 150 = 203.15 β 150 = 53.15 A from B to C
ο¨ Current in section CD = πΌ1 β 450+252.4 = 203.15β 450 +252.4= 5.55A C to D
ο¨ Current in section DA = πΌ1 β 700 = 203.15+252.5 β 700 = β 244.45A = 244.45A
from A to D
ο¨ Drop in AB = 203Β·15 Γ 0Β·02 = 4Β·063 V
ο¨ Drop in BC = 53Β·15 Γ 0Β·018= 0Β·960 V
ο¨ Drop in AD = 244Β·45 Γ 0Β·02 = 4Β·9 V
ο¨ β΄ Potential of B = 250 β 4Β·063= 245Β·93 V
ο¨ Potential of C = 245Β·93 β 0Β·96 = 244Β·97 V
ο¨ Potential of D = 250 β 4Β·9 = 245Β·1 V
It may be seen that with the use of interconnector, the voltage drops in the various
sections of the distributor are reduced.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 124
125. ο¨ A.C. distribution calculations differ from those of d.c. distribution in the
following respects :
ο¨ (i) In case of d.c. system, the voltage drop is due to resistance alone.
However, in a.c. system, the voltage drops are due to the combined effects of
resistance, inductance and capacitance.
ο¨ (ii) In a d.c. system, additions and subtractions of currents or voltages are
done arithmetically but in case of a.c. system, these operations are done
vectorially.
ο¨ (iii) In an a.c. system, power factor (p.f.) has to be taken into account. Loads
tapped off form the distributor are generally at different power factors. There
are two ways of referring power factor viz
(a) It may be referred to supply or receiving end voltage which is
regarded as the reference vector.
(b) It may be referred to the voltage at the load point itself.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 125
126. ο¨ The power factors of load currents may be
given
(i) w.r.t. receiving or sending end voltage
or
(ii) w.r.t. to load voltage itself.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 126
127. ο¨ (i) Power factors referred to receiving end voltage.
Consider an a.c. distributor AB with concentrated loads of πΌ1and πΌ2 tapped off at
points C and B. Taking the receiving end voltage ππ΅ as the reference vector, let
lagging power factors at C and B be cos Ο1 and cos Ο2 w.r.t. ππ΅ . Let π 1, π1 and
π 2, π2 be the resistance and reactance of sections AC and CB of the distributor.
Impedance of section AC, ππ΄πΆ= π 1 + j π1
Impedance of section CB,ππΆπ΅ = π 2 + j π2
Load current at point C, πΌ1 = πΌ1 (cos Ο1 β j sin Ο1)
Load current at point B, πΌ2 = πΌ2 (cos Ο2 β j sin Ο2)
Current in section CB, πΌπΆπ΅= πΌ2 = πΌ2 (cos Ο2 β j sin Ο2)
Current in section AC, πΌπ΄πΆ = πΌ1+ πΌ2
=πΌ1 (cos Ο1 β j sin Ο1)+πΌ2 (cos Ο2 β j sin Ο2)
6 October 2020 D.Rajesh Asst.Prof. EEE Department 127
131. ο¨ A single phase ring distributor ABC is fed at A. The loads at B
and C are 20 A at 0.8 p.f. lagging and 15 A at 0.6 p.f. lagging
respectively ; both expressed with reference to the voltage at
A. The total impedance of the three sections AB, BC and CA
are (1 + j 1), (1+ j2) and (1 + j3) ohms respectively. Find the
total current fed at A and the current in each section. Use
Theveninβs theorem to obtain the results.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 131