Overview and Design
EX.SE RVNL/KOL-PIU/E&M
Asst. Prof. KIIT University
 Safety of human life.
 Protection of costly devices.
 Continuous and smooth operation.
 Early detection of any abnormality.
 The purpose of the fire alarm system shall be
primarily to provide notification of fire alarm,
supervisory, and trouble conditions; to alert the
occupants; to summon aid; and to control fire
safety functions.
 It is suitable for highly congested and electrical
hazards where area is prone to fire.
 Places where safety of continuous operation is
important.
 The sensing device.
 Power supply.
 Control and processing unit.
 Indicating Devices.
 Wiring and Colour Code.
 Light Intensity and Sound intensity.
 Protection.
 Heat detector.
 Smoke detector.
 Rate of temperature rise detector.
 The objective of the heat detector is that it must
respond when the fire reaches a critical heat
release rate within a specified time.
 Apollo XP95 Heat Detector:(Fixed Temperature)
 Fixed temperature heat detector.
 Rate of rise heat detector.
 Another type of heat detector is flame detector.
 Fixed temperature detectors operate when the heat sensitive alloy
reaches the critical point changing state from a solid to a liquid. It
sends a low voltage signal to controller so that it can take action
accordingly.
 The most common fixed temperature point for electrically
connected heat detectors is 136.4°F (58°C). Technological
developments have enabled the perfection of detectors that
activate at a temperature of 117°F (47°C), increasing the
available reaction time and margin of safety.
 NFPA 72.[ National Fire Alarm Code]
 IS 2189 : 2008.[Selection, installation and maintenance of
the Automatic Fire Detection and Alarm System Code of
Practice]
 IS 15908 : 2011.[Selection, installation and maintenance of
control and indicating equipments for Fire Detection And Alarm
System-Code of Practice]
 For normal ceiling ,
100 sq-mm area= one heat detector.
 For large open space,
Total area is subdivided by zones.
2000 sq-mm= one zone
ceiling height 5-7m , spacing=3.5m
 Maximum no of fire detector in a zone = 20 nos.
 For false ceiling sensitivity of fire detector must be high than normal
ceiling.
 All heat detector are connected in series with isolator in proper
locations.
ASS/TSS Room, Pump
Room, Signaling Room,
Other electrical Control
room
Platform and Traction
Other room within
premises.
Correct
Wrong
 A device that detects visible and invisible particles
of combustion.
 Ionization smoke detector.
 Photo-electric smoke detector.
 Projected beam (optical) smoke detector.
 Aspirating smoke detector.
 Video smoke detector.
Photoelectric Smoke Detector Ionization Smoke Detector
 For normal ceiling ,
100 sq-mm area= one smoke detector.
 For large open space,
Total area is subdivided by zones.
2000 sq-mm= one zone
ceiling height 7-10m , spacing=5m
 Maximum no of fire detector in a zone = 20 nos.
 Main Power Supply ( single phase dedicated supply only for
fire alarm). DG set (automatic/ manual ) may be separately
installed for main power supply.
 If main power supply fails changeover within 10 seconds to
back up battery supply.
 Battery back up should maintain 48.5 h normal operation
after main supply fails.
 In high rise building and special buildings a control centre
minimum floor space required is (15-20) sq-m .
 Emergency lighting module must be there.
 Control centre room shall be provided with intercon and
direct telephone facility on emergency.
 Control panel:
Acknowledge button.
Alarm cancel indication.
Isolation/Reset facility.
Related fuse/ protective devices.
 Small distance of C and I devices, manual call point from
safety staff and fire fighters. The minimum distance is 30
m from the entrance of any zone.
 Repeat control is used for multiple entrances.
 All C and I and Power supply equipments require routine
tests.
 Noise level should be low in protected area for clearance
of audible instruction.
 C and I equipment is not centralized. It is distributed
among number of sub-panels.
 Ring or loop network is more useful.
 All sub-panels are stand alone.
Speaker.
LED light.
 Single stage continuous alarm:
Continuous alarm sound
throughout the zone or sector. This scheme is for smaller
premises.
 Two stage general alarm:
Continuous alarm for fire
affected zone and intermittent alarm in other zone through
automatic switch from control centre. This scheme is for
large and multiple entrances premises.
 The cable from the main supply and standby supply should be
fire resistant.
 Color coding is red to discriminate from other cable.
 Cables shall be exclusively for fire detection system. Multi core
shall not share other load.
 Type: Armoured or Unarmoured FRLS cables of minimum
2X1.5 sq-mm. ATC cables for conventional fire alarm and
multistand twisted pair shielded cable for addressable alarm
system.
 PVC insulated copper conductor cable of 1.5 sq-mm can also be
used.
 Mineral insulated cables with overall LSF( low smoke fume)
(It is required for High hazard industry: Oil and Hydrocarbon, Metro
rail, Jetty, Airports, Power plant)
 Cable shall be laid down in metallic/ rigid PVC condute.
 There shall not be any joint between detector to detector,
detector to alarm, detector to manual call point.
 Proper junction box is required if there is a shortage of
cable for wiring.
Red
Yellow
Yellow
• For Alarm
• For Fault
• For Isolate
 The surrounding ambient illumination level in the
vicinity of all control and indicating equipment
shall be such that visible indications can be clearly
seen, controls easily operated and any instruction
can be easily read.
 Frequency range of hooters/horns/electronic bell
is within 500 to 1000 Hz.
 Minimum sound level is 65 dB (A) . 75 dB (A) is
required for sleeping person to awake with all
door shut.
 Maximum sound level is 120 dB (A).
 Mechanical Protection:
Break Glass Unit.
or, Manual call point. Search distance
<30m from the
Entry of any zone.
 Public addressing:
 Electrical Protection:
An over-current protective device
of suitable current-carrying capacity that is
capable of interrupting the maximum short-circuit
current is used for electrical protection.
Overview
THANK YOU

More Related Content

What's hot

Fundamental training on Fire Detection & Alarm System
Fundamental training on Fire Detection & Alarm SystemFundamental training on Fire Detection & Alarm System
Fundamental training on Fire Detection & Alarm SystemSabrul Jamil
 
Fire detection and alarm system
Fire detection and alarm systemFire detection and alarm system
Fire detection and alarm systemsakshisankpal
 
Fire alarm system and common types of detectors
Fire alarm system and common types of detectorsFire alarm system and common types of detectors
Fire alarm system and common types of detectorsMuhammad Farid
 
Fire Alarm System.pdf
Fire Alarm System.pdfFire Alarm System.pdf
Fire Alarm System.pdfssuser06d7b51
 
Fire alarm , detection and suppression system
Fire alarm , detection and suppression systemFire alarm , detection and suppression system
Fire alarm , detection and suppression systemKamran Hassan
 
Fire Alarm, Smoke Detector and Automatic Sprinkle System
Fire Alarm, Smoke Detector and Automatic Sprinkle SystemFire Alarm, Smoke Detector and Automatic Sprinkle System
Fire Alarm, Smoke Detector and Automatic Sprinkle SystemKhairul Azhar
 
FIRE DETECTION AND ELETRICAL POWER ON/OFF CONTROL IN HOME/INDUSTRY USING GSM
FIRE DETECTION AND ELETRICAL POWER ON/OFF CONTROL IN HOME/INDUSTRY USING GSMFIRE DETECTION AND ELETRICAL POWER ON/OFF CONTROL IN HOME/INDUSTRY USING GSM
FIRE DETECTION AND ELETRICAL POWER ON/OFF CONTROL IN HOME/INDUSTRY USING GSMSaikiran Perfect
 
Fire Hydrant System/Sprinkler System Fire Fighting Systems Fire Hydrant Syst...
Fire Hydrant System/Sprinkler System Fire Fighting Systems  Fire Hydrant Syst...Fire Hydrant System/Sprinkler System Fire Fighting Systems  Fire Hydrant Syst...
Fire Hydrant System/Sprinkler System Fire Fighting Systems Fire Hydrant Syst...RajyogFireServicesPv
 
Chapter 12
Chapter 12Chapter 12
Chapter 12Joe
 

What's hot (20)

Fire detection and alarm systems
Fire detection and alarm systemsFire detection and alarm systems
Fire detection and alarm systems
 
Fundamental training on Fire Detection & Alarm System
Fundamental training on Fire Detection & Alarm SystemFundamental training on Fire Detection & Alarm System
Fundamental training on Fire Detection & Alarm System
 
Fire Detection and Alarm System (FDAS).pptx
Fire Detection and Alarm System (FDAS).pptxFire Detection and Alarm System (FDAS).pptx
Fire Detection and Alarm System (FDAS).pptx
 
Fire detection and alarm system
Fire detection and alarm systemFire detection and alarm system
Fire detection and alarm system
 
Fire alarm system and common types of detectors
Fire alarm system and common types of detectorsFire alarm system and common types of detectors
Fire alarm system and common types of detectors
 
Fire alarm systems
Fire alarm systems Fire alarm systems
Fire alarm systems
 
Fire Alarm System.pdf
Fire Alarm System.pdfFire Alarm System.pdf
Fire Alarm System.pdf
 
Fire Alarm System, BMS
Fire Alarm System, BMSFire Alarm System, BMS
Fire Alarm System, BMS
 
Fire alarm , detection and suppression system
Fire alarm , detection and suppression systemFire alarm , detection and suppression system
Fire alarm , detection and suppression system
 
Smoke detector
Smoke detectorSmoke detector
Smoke detector
 
Fire Alarm, Smoke Detector and Automatic Sprinkle System
Fire Alarm, Smoke Detector and Automatic Sprinkle SystemFire Alarm, Smoke Detector and Automatic Sprinkle System
Fire Alarm, Smoke Detector and Automatic Sprinkle System
 
FIRE DETECTION AND ELETRICAL POWER ON/OFF CONTROL IN HOME/INDUSTRY USING GSM
FIRE DETECTION AND ELETRICAL POWER ON/OFF CONTROL IN HOME/INDUSTRY USING GSMFIRE DETECTION AND ELETRICAL POWER ON/OFF CONTROL IN HOME/INDUSTRY USING GSM
FIRE DETECTION AND ELETRICAL POWER ON/OFF CONTROL IN HOME/INDUSTRY USING GSM
 
Fire Hydrant System/Sprinkler System Fire Fighting Systems Fire Hydrant Syst...
Fire Hydrant System/Sprinkler System Fire Fighting Systems  Fire Hydrant Syst...Fire Hydrant System/Sprinkler System Fire Fighting Systems  Fire Hydrant Syst...
Fire Hydrant System/Sprinkler System Fire Fighting Systems Fire Hydrant Syst...
 
Fire Fighting system
Fire Fighting systemFire Fighting system
Fire Fighting system
 
Fire Protection
Fire ProtectionFire Protection
Fire Protection
 
Chapter 12
Chapter 12Chapter 12
Chapter 12
 
Fire safety FM 200
Fire safety FM 200Fire safety FM 200
Fire safety FM 200
 
Fire detection & alarm system
Fire detection & alarm systemFire detection & alarm system
Fire detection & alarm system
 
Bms for security systems
Bms for security systemsBms for security systems
Bms for security systems
 
Fire safety arrangement
Fire safety arrangementFire safety arrangement
Fire safety arrangement
 

Viewers also liked

Basic Fire Alarm Systems
Basic Fire Alarm SystemsBasic Fire Alarm Systems
Basic Fire Alarm Systemsmalcolmfd
 
Somke detector project presentation
Somke detector project presentationSomke detector project presentation
Somke detector project presentationRija Fatima
 
Fire alarm system_nec_september[1]
Fire alarm system_nec_september[1]Fire alarm system_nec_september[1]
Fire alarm system_nec_september[1]Jennifer Kleinhenz
 
Fire alarm
Fire alarmFire alarm
Fire alarmarjunex
 
Fire alarm basics 1-5
Fire alarm basics 1-5Fire alarm basics 1-5
Fire alarm basics 1-5grantlerc
 
Chris Preuss_State of Confusion
Chris Preuss_State of ConfusionChris Preuss_State of Confusion
Chris Preuss_State of ConfusionW2O Group
 
130908 com confusion by ps. kevin york
130908 com  confusion by ps. kevin york130908 com  confusion by ps. kevin york
130908 com confusion by ps. kevin yorkeaglepointcf
 
Firetrace Fume Hood Fire Protection
Firetrace Fume Hood Fire ProtectionFiretrace Fume Hood Fire Protection
Firetrace Fume Hood Fire Protectionnjgrant
 
NFPA 72 FAS Certificate-Ragy
NFPA 72 FAS Certificate-RagyNFPA 72 FAS Certificate-Ragy
NFPA 72 FAS Certificate-RagyRagy Ramadan
 
130906 fire alarm_2013_nfpa_72_changes[1]
130906 fire alarm_2013_nfpa_72_changes[1]130906 fire alarm_2013_nfpa_72_changes[1]
130906 fire alarm_2013_nfpa_72_changes[1]Jennifer Kleinhenz
 
Rapidly developing IoT (Internet of Things) applications - Part 2: Arduino, B...
Rapidly developing IoT (Internet of Things) applications - Part 2: Arduino, B...Rapidly developing IoT (Internet of Things) applications - Part 2: Arduino, B...
Rapidly developing IoT (Internet of Things) applications - Part 2: Arduino, B...Raul Chong
 
Polymer Tube Firetrace Based Automatic Fire Detection and Suppression System
Polymer Tube Firetrace Based Automatic Fire Detection and Suppression SystemPolymer Tube Firetrace Based Automatic Fire Detection and Suppression System
Polymer Tube Firetrace Based Automatic Fire Detection and Suppression SystemAnil Mishra
 
Building lightning protection for Metro Railway
Building lightning protection for Metro RailwayBuilding lightning protection for Metro Railway
Building lightning protection for Metro RailwaySubhendu Bikash Santra
 

Viewers also liked (20)

Basic Fire Alarm Systems
Basic Fire Alarm SystemsBasic Fire Alarm Systems
Basic Fire Alarm Systems
 
Chapter 07
Chapter 07Chapter 07
Chapter 07
 
Fire alarm system
Fire alarm system Fire alarm system
Fire alarm system
 
Somke detector project presentation
Somke detector project presentationSomke detector project presentation
Somke detector project presentation
 
Fire alarm system_nec_september[1]
Fire alarm system_nec_september[1]Fire alarm system_nec_september[1]
Fire alarm system_nec_september[1]
 
Back to Basics
Back to BasicsBack to Basics
Back to Basics
 
Fire alarm
Fire alarmFire alarm
Fire alarm
 
Basics of Fire fighting
Basics of Fire fightingBasics of Fire fighting
Basics of Fire fighting
 
Fire alarm basics 1-5
Fire alarm basics 1-5Fire alarm basics 1-5
Fire alarm basics 1-5
 
Chris Preuss_State of Confusion
Chris Preuss_State of ConfusionChris Preuss_State of Confusion
Chris Preuss_State of Confusion
 
130908 com confusion by ps. kevin york
130908 com  confusion by ps. kevin york130908 com  confusion by ps. kevin york
130908 com confusion by ps. kevin york
 
Firetrace Fume Hood Fire Protection
Firetrace Fume Hood Fire ProtectionFiretrace Fume Hood Fire Protection
Firetrace Fume Hood Fire Protection
 
NFPA 72 FAS Certificate-Ragy
NFPA 72 FAS Certificate-RagyNFPA 72 FAS Certificate-Ragy
NFPA 72 FAS Certificate-Ragy
 
130906 fire alarm_2013_nfpa_72_changes[1]
130906 fire alarm_2013_nfpa_72_changes[1]130906 fire alarm_2013_nfpa_72_changes[1]
130906 fire alarm_2013_nfpa_72_changes[1]
 
Rapidly developing IoT (Internet of Things) applications - Part 2: Arduino, B...
Rapidly developing IoT (Internet of Things) applications - Part 2: Arduino, B...Rapidly developing IoT (Internet of Things) applications - Part 2: Arduino, B...
Rapidly developing IoT (Internet of Things) applications - Part 2: Arduino, B...
 
Daylighting[1]
Daylighting[1]Daylighting[1]
Daylighting[1]
 
Polymer Tube Firetrace Based Automatic Fire Detection and Suppression System
Polymer Tube Firetrace Based Automatic Fire Detection and Suppression SystemPolymer Tube Firetrace Based Automatic Fire Detection and Suppression System
Polymer Tube Firetrace Based Automatic Fire Detection and Suppression System
 
Building lightning protection for Metro Railway
Building lightning protection for Metro RailwayBuilding lightning protection for Metro Railway
Building lightning protection for Metro Railway
 
Earth MAT design for Metro Station
Earth MAT design for Metro StationEarth MAT design for Metro Station
Earth MAT design for Metro Station
 
Chapter 09
Chapter 09Chapter 09
Chapter 09
 

Similar to Fundamentals of Fire Alarm System

Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)Jed Concepcion
 
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfcdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfnipunwijewardhana
 
830 and 708 wireless fire alarm system control panel introduction
830 and 708 wireless fire alarm system control panel introduction830 and 708 wireless fire alarm system control panel introduction
830 and 708 wireless fire alarm system control panel introductionVedard Security Alarm System Store
 
Kidde Alarmline SenseTek-NL
Kidde Alarmline SenseTek-NLKidde Alarmline SenseTek-NL
Kidde Alarmline SenseTek-NLHans Bronkhorst
 
Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?Shubham .
 
Honeywell is25100tc-spec-sheet
Honeywell is25100tc-spec-sheetHoneywell is25100tc-spec-sheet
Honeywell is25100tc-spec-sheetAlarm Grid
 
SenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet englishSenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet englishHans Bronkhorst
 
Heat and smoke detectors
Heat and smoke detectors Heat and smoke detectors
Heat and smoke detectors wasim shaikh
 
Fire detectionand alarm systems 090512042400-phpapp01(1)
Fire detectionand alarm systems 090512042400-phpapp01(1)Fire detectionand alarm systems 090512042400-phpapp01(1)
Fire detectionand alarm systems 090512042400-phpapp01(1)Mohammed Ullah
 
project report on fire alarm
project report on fire alarmproject report on fire alarm
project report on fire alarmRattan Pal
 
Lecture 5 Fire Alarm System.pdf
Lecture 5 Fire Alarm System.pdfLecture 5 Fire Alarm System.pdf
Lecture 5 Fire Alarm System.pdfAbdelhaymohamed2
 
Honeywell is2535-spec-sheet
Honeywell is2535-spec-sheetHoneywell is2535-spec-sheet
Honeywell is2535-spec-sheetAlarm Grid
 
Honeywell is2560-spec-sheet
Honeywell is2560-spec-sheetHoneywell is2560-spec-sheet
Honeywell is2560-spec-sheetAlarm Grid
 
Smoke n & Heat Detector- 4098-9714, 9733, 9717.pdf
Smoke n & Heat Detector- 4098-9714, 9733, 9717.pdfSmoke n & Heat Detector- 4098-9714, 9733, 9717.pdf
Smoke n & Heat Detector- 4098-9714, 9733, 9717.pdfSourovSamadder
 
ELECTRICAL SAFETY FOR high rise building.pptx
ELECTRICAL SAFETY FOR high rise building.pptxELECTRICAL SAFETY FOR high rise building.pptx
ELECTRICAL SAFETY FOR high rise building.pptxgprtpo
 

Similar to Fundamentals of Fire Alarm System (20)

Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)
 
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfcdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
 
830 and 708 wireless fire alarm system control panel introduction
830 and 708 wireless fire alarm system control panel introduction830 and 708 wireless fire alarm system control panel introduction
830 and 708 wireless fire alarm system control panel introduction
 
Panel
PanelPanel
Panel
 
Brief introduction of wireless fire alarm
Brief introduction of wireless fire alarmBrief introduction of wireless fire alarm
Brief introduction of wireless fire alarm
 
Kidde Alarmline SenseTek-NL
Kidde Alarmline SenseTek-NLKidde Alarmline SenseTek-NL
Kidde Alarmline SenseTek-NL
 
FAS
FASFAS
FAS
 
Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?
 
Honeywell is25100tc-spec-sheet
Honeywell is25100tc-spec-sheetHoneywell is25100tc-spec-sheet
Honeywell is25100tc-spec-sheet
 
E3 series system 9000 0574
E3 series system 9000 0574E3 series system 9000 0574
E3 series system 9000 0574
 
SenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet englishSenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet english
 
FIRE ALARM SYSTEM.pdf
FIRE ALARM SYSTEM.pdfFIRE ALARM SYSTEM.pdf
FIRE ALARM SYSTEM.pdf
 
Heat and smoke detectors
Heat and smoke detectors Heat and smoke detectors
Heat and smoke detectors
 
Fire detectionand alarm systems 090512042400-phpapp01(1)
Fire detectionand alarm systems 090512042400-phpapp01(1)Fire detectionand alarm systems 090512042400-phpapp01(1)
Fire detectionand alarm systems 090512042400-phpapp01(1)
 
project report on fire alarm
project report on fire alarmproject report on fire alarm
project report on fire alarm
 
Lecture 5 Fire Alarm System.pdf
Lecture 5 Fire Alarm System.pdfLecture 5 Fire Alarm System.pdf
Lecture 5 Fire Alarm System.pdf
 
Honeywell is2535-spec-sheet
Honeywell is2535-spec-sheetHoneywell is2535-spec-sheet
Honeywell is2535-spec-sheet
 
Honeywell is2560-spec-sheet
Honeywell is2560-spec-sheetHoneywell is2560-spec-sheet
Honeywell is2560-spec-sheet
 
Smoke n & Heat Detector- 4098-9714, 9733, 9717.pdf
Smoke n & Heat Detector- 4098-9714, 9733, 9717.pdfSmoke n & Heat Detector- 4098-9714, 9733, 9717.pdf
Smoke n & Heat Detector- 4098-9714, 9733, 9717.pdf
 
ELECTRICAL SAFETY FOR high rise building.pptx
ELECTRICAL SAFETY FOR high rise building.pptxELECTRICAL SAFETY FOR high rise building.pptx
ELECTRICAL SAFETY FOR high rise building.pptx
 

Recently uploaded

Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...Call Girls in Nagpur High Profile
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdfKamal Acharya
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGSIVASHANKAR N
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 

Recently uploaded (20)

Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 

Fundamentals of Fire Alarm System

  • 1. Overview and Design EX.SE RVNL/KOL-PIU/E&M Asst. Prof. KIIT University
  • 2.  Safety of human life.  Protection of costly devices.  Continuous and smooth operation.  Early detection of any abnormality.
  • 3.  The purpose of the fire alarm system shall be primarily to provide notification of fire alarm, supervisory, and trouble conditions; to alert the occupants; to summon aid; and to control fire safety functions.  It is suitable for highly congested and electrical hazards where area is prone to fire.  Places where safety of continuous operation is important.
  • 4.  The sensing device.  Power supply.  Control and processing unit.  Indicating Devices.  Wiring and Colour Code.  Light Intensity and Sound intensity.  Protection.
  • 5.  Heat detector.  Smoke detector.  Rate of temperature rise detector.
  • 6.  The objective of the heat detector is that it must respond when the fire reaches a critical heat release rate within a specified time.  Apollo XP95 Heat Detector:(Fixed Temperature)
  • 7.  Fixed temperature heat detector.  Rate of rise heat detector.  Another type of heat detector is flame detector.
  • 8.  Fixed temperature detectors operate when the heat sensitive alloy reaches the critical point changing state from a solid to a liquid. It sends a low voltage signal to controller so that it can take action accordingly.  The most common fixed temperature point for electrically connected heat detectors is 136.4°F (58°C). Technological developments have enabled the perfection of detectors that activate at a temperature of 117°F (47°C), increasing the available reaction time and margin of safety.
  • 9.
  • 10.  NFPA 72.[ National Fire Alarm Code]  IS 2189 : 2008.[Selection, installation and maintenance of the Automatic Fire Detection and Alarm System Code of Practice]  IS 15908 : 2011.[Selection, installation and maintenance of control and indicating equipments for Fire Detection And Alarm System-Code of Practice]
  • 11.  For normal ceiling , 100 sq-mm area= one heat detector.  For large open space, Total area is subdivided by zones. 2000 sq-mm= one zone ceiling height 5-7m , spacing=3.5m  Maximum no of fire detector in a zone = 20 nos.  For false ceiling sensitivity of fire detector must be high than normal ceiling.  All heat detector are connected in series with isolator in proper locations.
  • 12. ASS/TSS Room, Pump Room, Signaling Room, Other electrical Control room Platform and Traction Other room within premises.
  • 13.
  • 14.
  • 16.  A device that detects visible and invisible particles of combustion.
  • 17.  Ionization smoke detector.  Photo-electric smoke detector.  Projected beam (optical) smoke detector.  Aspirating smoke detector.  Video smoke detector.
  • 18. Photoelectric Smoke Detector Ionization Smoke Detector
  • 19.  For normal ceiling , 100 sq-mm area= one smoke detector.  For large open space, Total area is subdivided by zones. 2000 sq-mm= one zone ceiling height 7-10m , spacing=5m  Maximum no of fire detector in a zone = 20 nos.
  • 20.  Main Power Supply ( single phase dedicated supply only for fire alarm). DG set (automatic/ manual ) may be separately installed for main power supply.  If main power supply fails changeover within 10 seconds to back up battery supply.  Battery back up should maintain 48.5 h normal operation after main supply fails.
  • 21.
  • 22.
  • 23.  In high rise building and special buildings a control centre minimum floor space required is (15-20) sq-m .  Emergency lighting module must be there.  Control centre room shall be provided with intercon and direct telephone facility on emergency.  Control panel: Acknowledge button. Alarm cancel indication. Isolation/Reset facility. Related fuse/ protective devices.
  • 24.  Small distance of C and I devices, manual call point from safety staff and fire fighters. The minimum distance is 30 m from the entrance of any zone.  Repeat control is used for multiple entrances.  All C and I and Power supply equipments require routine tests.  Noise level should be low in protected area for clearance of audible instruction.  C and I equipment is not centralized. It is distributed among number of sub-panels.  Ring or loop network is more useful.  All sub-panels are stand alone.
  • 26.  Single stage continuous alarm: Continuous alarm sound throughout the zone or sector. This scheme is for smaller premises.  Two stage general alarm: Continuous alarm for fire affected zone and intermittent alarm in other zone through automatic switch from control centre. This scheme is for large and multiple entrances premises.
  • 27.
  • 28.  The cable from the main supply and standby supply should be fire resistant.  Color coding is red to discriminate from other cable.  Cables shall be exclusively for fire detection system. Multi core shall not share other load.  Type: Armoured or Unarmoured FRLS cables of minimum 2X1.5 sq-mm. ATC cables for conventional fire alarm and multistand twisted pair shielded cable for addressable alarm system.  PVC insulated copper conductor cable of 1.5 sq-mm can also be used.  Mineral insulated cables with overall LSF( low smoke fume) (It is required for High hazard industry: Oil and Hydrocarbon, Metro rail, Jetty, Airports, Power plant)
  • 29.  Cable shall be laid down in metallic/ rigid PVC condute.  There shall not be any joint between detector to detector, detector to alarm, detector to manual call point.  Proper junction box is required if there is a shortage of cable for wiring.
  • 30. Red Yellow Yellow • For Alarm • For Fault • For Isolate
  • 31.  The surrounding ambient illumination level in the vicinity of all control and indicating equipment shall be such that visible indications can be clearly seen, controls easily operated and any instruction can be easily read.
  • 32.  Frequency range of hooters/horns/electronic bell is within 500 to 1000 Hz.  Minimum sound level is 65 dB (A) . 75 dB (A) is required for sleeping person to awake with all door shut.  Maximum sound level is 120 dB (A).
  • 33.  Mechanical Protection: Break Glass Unit. or, Manual call point. Search distance <30m from the Entry of any zone.  Public addressing:
  • 34.  Electrical Protection: An over-current protective device of suitable current-carrying capacity that is capable of interrupting the maximum short-circuit current is used for electrical protection.
  • 36.