SAUDI ARAMCO INDUSTRIAL LIGHTING USING DIALUX 4.11_DAY TWO
1. SAUDI ARAMCO INDUSTRIAL
LIGHTING
USING DIALUX 4.11
Indoor, Emergency, Outdoor & Security
Lighting Applications based on SAES-P-123
Engr. Michael T. Santiago | REE.AILP.MIES
DIALux Accredited Trainer, ID 2013029
Supervisor, Lighting Applications Design Department
Day Two – Outdoor & Security Lighting
4th day of March, 2014
SNC Lavalin Fayez Engineering Office
Auto Moto Complex, Al-Khobar, KSA
2. Saudi Aramco, a fully integrated, global
petroleum and chemicals enterprise, is the
state-owned oil company of the Kingdom of
Saudi Arabia.
Through our 80-year history we have become a
world leader in hydrocarbons exploration,
production, refining, distribution, shipping and
marketing, and the world’s top exporter of
crude oil and natural gas liquids (NGLs).
COURSE DEFINITION:
A two day seminar & hands-on training for
engineering design employees of SNC-Lavalin
Fayez Engineering for the application of SAES-P-
123 (Saudi Aramco Engineering Standards) in
indoor, emergency, outdoor & security lighting of
Saudi Aramco Industrial Projects with the use of
DIALux 4.11 as the lighting calculation software.
SOURCE: http://www.aramco.com.sa
INTRODUCTION
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
3. A. THEORETICAL
Basic Lighting Terminologies
Fundamental Formulas
Manual Calculation & DIALux Verification
SAES Recommended Practices
B. PRACTICAL
Outdoor Lighting Calculation in DIALux
Security Lighting Calculation in DIALux
Print-output & CAD LAyouts
INTRODUCTION
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
4. 1. To refresh participants with the design
recommendations according to SAES P-123, IESNA
and NFPA 70
2. To apply the design recommendations using SLC
Products in future Saudi ARAMCO Substation Projects
3. To build a strong foundation where participant can
design, calculate and estimate lighting for any given
task, room or area in a ARAMCO substation project.
OBJECTIVES
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
5. 1. Adherence to Standards
~ NFPA
~ IESNA
~ OTHER SAUDI REGIONS
2. All Indoor Lighting will be calculated without effect of
obstructions/objects but if future projects will provide a detailed
furniture/equipment/cable tray/HVAC ducts layout, they should be
included in the planning and calculation
3. DIALux, a leading lighting planning / calculating / rendering
software from Germany will be used for evaluation and print
output
CONSIDERATIONS
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
6. (BIDDING) – SLC Gives Technical Offer – {We start here}
(PRICING) – Requests to Verify Quantity - {Procurement}
(REVISION) – Changes due to updated CAD layouts – {Design}
{AS-BUILT} - Changes due to actual equipment, cable tray,
HVAC ducting installations – {Site}
{COMMISSIONING} – Possible issues arising after materials
are supplied or lux levels are tested {Site}
We would appreciate a request containing all
relevant, detailed and updated information so we can
minimize design rebounds.
IMPORTANCE
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
7. 1. GOALS OF A GOOD DESIGN
a. surveillance inspection
b. equipment inspection
c. overall safety & performance status
during nomal and emergency operation
GENERAL INFO ON YARD LIGHTING
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
8. 2. PARTS OF YARD LIGHTING
GENERAL INFO ON YARD LIGHTING
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
Shaded / Unshaded Parking Workers Villa
9. 2. PARTS OF YARD LIGHTING
GENERAL INFO ON YARD LIGHTING
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
Interior / Residential Roads
Interior / Residential Roads
10. 2. PARTS OF YARD LIGHTING
GENERAL INFO ON YARD LIGHTING
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
Platforms
Building Elements
11. 2. PARTS OF YARD LIGHTING
a. Perimeter Fence
b. Gate Houses / Check Points
c. Company Signboard
d. Exterior Doors
e. Main Entrances
f. Roads
g. Area Lighting
(transformer bays, capacitor banks, etc.)
GENERAL INFO ON YARD LIGHTING
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
12. BEAM LUMEN METHOD FOR FLOODLIGHTS
FORMULAS TO BE USED
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
13. POINT-BY-POINT METHOD FOR FLOODLIGHTS
FORMULAS TO BE USED
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
14. Image Source: Zumtobel, The Lighting Handbook
Image Source:
http://sustainabilityworkshop.autodesk.com/buildings/measuring-light-levels
LIGHTING TERMS
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
15. SAMPLE: A point source luminaire is placed at a parapet of 3m height. It
is aimed to the ground 4.5m away. When measured by a lux meter, it
shows 10 lux. How much is the luminaire’s candela power?
Frmla: Given: adj =3m opp=4.5m
E = 10 lux
Solution: get Ɵ, so tan Ɵ = 3/4.5 = 33.69
Ɵ = 56.31°
then, d = 3 ² + 4.5 ²
d = 5.408 m
E x d ² 10 lm/m² x (5.408m) ²
then, I = =
cos Ɵ cos 56.31 °
Therefore : I = 527.249 cd
MANUAL CALCULATION: FORMULA
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
16. Eave = Average Illuminance (E) in lux
Φ = Initial Flux in lumens
CU = Coefficient of Utilization, Street Side
MF = Maintenance Factor or LLF
WR = Width of Roadway in meters
PS = Pole Spacing in meters
Therefore to get Pole Spacing:
SAMPLE PROBLEM:
7435-250W MH Lamp with 19,000 lumens
7m Road width, 6m Pole Height
Maintenance Factor as 70%
What is the ideal Pole Spacing to achieve average
illuminance of 20 lux?
To get CU,
Road Width / Pole Height
= 7m / 6m = 1.6
Therefore,
Street Side CU is 0.4
MANUAL CALCULATION: ROAD LIGHTING
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
17. MANUAL CALCULATION: ROAD LIGHTING
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
DIALux Verified Calculation
18. MANUAL CALCULATION: ROAD LIGHTING
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
DIALux Verified Calculation
19. LAMPS TO BE USED
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
SAES –P-123
Article 5.8.2 &
5.8.3
MINIMUM ACCEPTABLE EFFICACY CRI CCT
HPS 87 lm/W -- --
LED < 50W 120 lm/W 90 or better 4000K & up
LED > 50W 1240 lm/W 90 or better 4000K & up
MH > 400W 58 lm/W -- --
Fluorescent 82.55 lm/W 82 3500k & up
Incandescent 16 lm/W -- --
a. High Pressure Sodium, tubular clear
~ 250W (27500 lum) - OSRAM NAV-T 250 (28000 lum)
~ 400W (50000 lum) – GE LU-400/40 (51000 lum)
~1000W (140000 lum) – GE LU-1000/40 (140000 lum)
~100W (9500 lum), 127Vac – GE LU-100/ECO
Connected to Indoor LP
20. MINIMUM LUX LEVELS PER AREA
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
a. Overall Area – maintained Min of 20 lux on ground
b. Transformer Bay - 100 lux Min
c. Building Entrance – 50 lux average
d. Gate Houses – 300 lux Min
e. Trenches – 100 lux Min
f. Roadways – 15 lux
g. Parking – 10 lux
21. 4. FIXTURES PER AREA
~DC Emergency – Lighting is not Required
~AC Normal
a. Main Entrances (3m or Top of Door/Gate)
- To the Substation
- Gate Post
- Outdoor Transformer Bay
- Station Service for Transformers
~V2FW / 5-100, 100W HPS-T, 127 Vac
MOUNTING SUGGESTIONS
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
22. 4. FIXTURES PER AREA
~DC Emergency – Lighting is not Required
~AC Normal
b. All other Exterior Doors
- 60W incandescent lamp, 127 Vac
~ 8513W/11-60x
c. Road Lighting
~ tubular clear HPS lamp
7435/5-250
7435/5-250
MOUNTING SUGGESTIONS
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
23. 4. FIXTURES PER AREA
~DC Emergency – Lighting is not Required
~AC Normal
d. Fence Lighting
- Assymetrical Floodlight
~ A6TG/5-400
e. Large Area Lighting
- NEMA 6x5 Floodlight
~ PF1K/5-400
~ PF1K/5-1000
MOUNTING SUGGESTIONS
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
24. 4. FIXTURES PER AREA
~DC Emergency – Lighting is not Required
~AC Normal
d. Bay Area
- Small Floodlight
~ FL42/5-250
~ FL42/5-400
MOUNTING SUGGESTIONS
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
25. INDUSTRIAL LIGHTING USING DIALUX – DAY 2 - OUTDOOR
AREA LIGHTING
1. POSSIBLE MOUNTING
A. Generally, Poles need to be as high as 10 meters
B. Floodlights aimed close to an angle of 54.7 to Vertical
26. INDUSTRIAL LIGHTING USING DIALUX – DAY 2 - OUTDOOR
AREA LIGHTING
1. POSSIBLE MOUNTING
c. Transmission Tower/Gantry on both sides
d. Building Parapet
e. Localized, wall-bracketed around transformer
f. For signboards, use of 2 x 250W fixtures, preferably
A6TG/3-250, 250W clear tubular Metal Halide
Very Good example is Qassim Project
27. PERIMETER LIGHTING
1. Adherence to SSD/13
a. Use of 400w
Assymetrical
Floodlight
b. 3 m high Pole, 10
m spacing,
c. 10 m inside fence
MOUNTING SUGGESTIONS
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
28. ROAD LIGHTING
1. ROAD LIGHTING SCEMES
MOUNTING SUGGESTIONS
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
29. ROAD LIGHTING
MOUNTING SUGGESTIONS
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
TYPICAL POLE
SETBACKDesign
Speed
Pole
Setback
50 kmh 0.8 m
80 kmh 1.0 m
100 kmh 1.5 m
120 kmh 1.5 m
BS EN 5489-1:2003 Section 5.2.1.2
Pole
Heights
Pole Arm
Length
Arm Tilts
6.0 m 0.5 m 5°, 10°, 15°
8.0 m 1.0 m 5°, 10°, 15°
10.0 m 1.5 m 5°, 10°, 15°
≥ 12.0 m 2.0 m 5°, 10°, 15°
*Common Practice
RECOMMENDATIONS*
30. HELPFUL LINKS
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
For DIALux support: http://dxboard.dialux.com/
For Lighting Fundamentals: http://www.ies.org/lighting/
For Lighting Applications: http://www.licht.de/en/lighting-for-professionals/lighting-design/lighting-design-
in-practice/
For Design Tips:http://www.ieslightlogic.org/
For free 3DS models: http://archive3d.net/
For free 3D Textures: http://archivetextures.net/
For Free DIALux M3D models: https://sites.google.com/site/dialux3d/home
For Free Indoor M3D Models: https://sites.google.com/site/ezzatbaroudi/dialux-evo-m3d-furniture-free-
download
31. CLOSING
SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
THANK YOU FOR VALUED
ATTENTION!
Please submit your Evaluation of the
Training
As well Day One & Day Two Exercises
Michael T. Santiago | REE.AILP.MIES
LAD Supervisor
Lighting Applications Design (LAD)
Department
Saudi Lighting Company
http://www.saudilighting.com
Riyadh, Saudi Arabia
Tel: +966-11-4741515 Ext 113
Fax: +966-11-4743698
Cell: +966-56 262-3490
Email: michael@saudilighting.com