Underground transmission line:
The aim of this unit are to: Analyze the resistance,inductance and capacitance of underground transmission lines
t the end of this unit, you will be able to:
explain where Underground Cables are applicable and the Requirements of choosing underground cables in electrical networks
determine the values of C,L and R per unit length in underground electrical line
Select the right type of cable for a particular system based on the voltage to deliver
estimate the right parameters for a single core for a given transmission line
determine the current rating for a given network and also know how underground cables are installed
explain the method of testing, locating, confirming, and troubleshooting any fault in the underground cables for a given electrical network
Indicative resources:
Principles of power systems, by Mehta and Mehta
A_Textbook_of_Electrical_Technology_Volume_III
Electrical Power systems by Wadhwa
Power system Analysis by Weedy and Cory
Power system by Grainger and Stevenson
Introduction to IEEE STANDARDS and its different types.pptx
underground of electrical power system.pptx
1. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 1
Inductance of underground transmission lines, capacitance of
underground transmission lines, electric equivalent circuit of
underground transmission line under steady state;
Types of cables; selection of right type of cable for a particular
system; parameter of single core cables; current rating; cable
installation; breakdown of cables; cable faults and their
location;
The grid system with particular reference to Rwanda National
Grid system; Application of computer control on grid system.
Underground transmission line:
3. COLLEGE OF SCIENCE
AND TECHNOLOGY
Introduction
4/5/2024 3
• Electric power can be transmitted or
distributed either by overhead system or
by underground cables.
• An underground cable consists of one or
more conductors covered with suitable
insulation and surrounded by a protecting
cover.
4. COLLEGE OF SCIENCE
AND TECHNOLOGY
Applications Of Underground Cables
• Underground cables are employed where it is impracticable to use
overhead lines, such as:
populated areas where municipal authorities prohibit overhead lines
for reasons of safety,
around plants and substations where maintenance conditions do not
permit the use of overhead construction.
Underground cables can also be used for supply connection in the
electrical plants, in generating stations, transmission system and
distribution systems, and so on.
4/5/2024 4
5. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 5
List of example of underground cable application for connecting one
apparatus with the others for the following:
- Supply power to the individual machine apparatus in electrical plants
- Connection between switchgear and individual load, group load
- Connection between auxiliary transformer and switchgear
-Sub transmission line between receiving substation and distribution
substation
-Submarine crossing
-Airports
-Etc.
6. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 6
Requirements of underground cables
• Several types of cables are available, the type of cable to be used will
depend upon the working voltage and service requirements.
• In general, a cable must fulfil the following necessary requirements :
(i)The conductor used in cables should be tinned stranded copper or aluminium
of high conductivity. Stranding is done so that conductor may become flexible
and carry more current.
(ii) The conductor size should be such that the cable carries the desired load
current without overheating and causes voltage drop within permissible limits.
(iii) The cable must have proper thickness of insulation in order to give high
degree of safety and reliability at the voltage for which it is designed.
(iv) The cable must be provided with suitable mechanical protection so that it
may withstand the rough use in laying it.
(v) The materials used in the manufacture of cables should be such that there is
complete chemical and physical stability throughout.
7. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 7
Cable Constructions
The main various part of
underground cables are:
• Cores or Conductors.
• Insulation.
• Metallic sheath.
• Bedding.
• Armouring.
• Serving.
8. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 8
• Cores or Conductors. To allow electricity to flow through them. A
cable may have one or more than one core (conductor) depending
upon the type of service for which it is intended. The conductors
are made of tinned copper or aluminium and are usually stranded
in order to provide flexibility to the cable.
• Insulation. To avoid leakage current in cable. Each core or
conductor is provided with a suitable thickness of insulation, the
thickness of layer depending upon the voltage to be withstood
by the cable. The commonly used materials for insulation are
impregnated paper, varnished cambric or rubber mineral
compound.
• Metallic sheath. To protect the cable from moisture, gases or
other damaging liquids (acids or alkalies) in the soil and
atmosphere, a metallic sheath of lead is provided over the
insulation
9. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 9
• Bedding. Over the metallic sheath is applied a layer of
bedding which consists of a fibrous material like jute or
hessian tape. The purpose of bedding is to protect the
metallic sheath against corrosion and from mechanical injury
due to armouring.
• Armouring. Over the bedding, armouring is provided which
consists of one or two layers of galvanized steel wire or steel
tape to protect the cable from mechanical injury. Armouring
may not be done in the case of some cables.
• Serving. (Outer cover ) In order to protect armouring from
atmospheric conditions, a layer of fibrous material (like jute)
similar to bedding is provided over the armouring. This is
known as serving.
10. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 10
Insulating Materials for Cables
• the proper choice of insulating material for cables is of considerable
importance
• The insulating materials used in cables should have the following
properties:
High insulation resistance to avoid leakage current.
High dielectric strength to avoid electrical breakdown
High mechanical strength to withstand mechanical handling.
Unaffected by acids and alkalies to avoid chemical actions.
Non-hygroscopic i.e. it should not absorb moisture from air or soil. The
moisture tends to decrease the insulation resistance and cause the
breakdown of the cable. In case the insulating material is hygroscopic, it
must be enclosed in a waterproof covering like lead sheath.
Non-inflammable.
Low cost so as to make the underground system a viable proposition.
11. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 11
1. Rubber:
• has reasonably high insulating properties, it suffers form some major
drawbacks viz., readily absorbs moisture, maximum
safe temperature is low (about 38ºC), soft and liable to damage due
to rough handling and ages when exposed to light. It has dielectric
capacity of 30 KV/mm. Relative permittivity varying between 2 and 3.
• Therefore, pure rubber cannot be used as an insulating material in
underground cables.
Types of Insulation Materials
2. Vulcanized Indian Rubber (V.I.R).
• It is prepared by mixing pure rubber with mineral matter such as zine oxide,
red lead etc., and 3 to 5% of Sulphur.
• has greater mechanical strength, durability and wear resistant property than
pure rubber. VIR Cables Temperature range is 25°C to 60°C.
• It has a dielectric strength of about 10-20 kV/mm
• The VIR insulation is generally used for low and moderate voltage cables
12. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 12
3. Impregnated paper.
• It consists of chemically pulped paper and impregnated with some
compound such as paraffinic.
• This type of insulation has almost superseded the rubber insulation.
• it has the advantages of low cost, low capacitance, high dielectric
strength and high insulation resistance.
• The only disadvantage is that paper is hygroscopic. Since the paper
insulated cables have the tendency to absorb moisture, they are used
where the cable route has a few joints.
• It has the high dielectric strength (40 – 50 kV/mm) and continuous
temperature rating of 80oC. It is used in high voltage power cable
manufacturing
4. Varnished cambric.
• It is a cotton cloth impregnated and coated with varnish.
• The varnished cambric is hygroscopic, therefore, such cables are always provided
with metallic sheath.
• Its dielectric strength is about 4kV/mm and permittivity is 2.5 to 3.8.
13. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 13
The PVC cables can be bent to smaller radii which make them particularly
suitable for laying in industrial places.
As the mechanical properties (i.e., elasticity etc.) of PVC are not so good
as those of rubber, therefore, PVC insulated cables are generally used for
low and medium domestic lights and power installations.
Due to a high dielectric, mechanical strength and exceptional resistance
to moisture, the PVC cables have almost completely replaced the paper
and rubber insulated cables in the range up to 11 kV.
5. Polyvinyl chloride (PVC).
It is a thermoplastic synthetic compound. It is
generally used to insulate the cables.
It has a good dielectric strength (17 kV/mm) and
maximum continuous temperature rating of 75oC.
14. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 14
6. XLPE Cables (Cross Linked Poly-ethene)
• This material has temperature range beyond 250 – 300 C
• This material gives good insulating properties. It is light in weight, small
overall dimensions, low dielectric constant and high mechanical strength,
low water absorption.
• These cables permit conductor temperature of 90 C and 250 C under
normal and short circuit conditions.
• Long-term working temperature can reach 90℃ and thermal life can
reach 40 years.
• These cables are suitable up to voltages of 33 KV.
15. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 15
Classification of Cables
Cables for underground service may be classified
according to:
(i) the voltage for which they are manufactured
(ii)the type of insulating material used in their
manufacture
(iii) the number of Cores
Classification according to the voltage
Low-tension (L.T.) cables - up to 1000 V
High-tension (H.T.) cables - up to 11,000 V
Super-tension (S.T.) cables - from 22 kV to 33 kV
Extra high-tension (E.H.T) cables - from 33 kV to 66 kV
Extra super voltage cables - beyond 132 kV
17. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 17
Classification of cable according to the type of
insulating material used in their manufacture
18. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 18
Classification of cable according to the type of
insulating material used in their manufacture cont…..
19. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 19
Classification of cable according to the type of
insulating material used in their manufacture cont…..
20. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 20
Classification according to the number of Cores
• It may be:
(ii) single-core
(ii) two-core
(iii) three-core
(iv) four-core etc.
• For a 3-phase service, either 3-
single-core cables or three-core
cable can be used depending
upon the operating voltage and
load demand.
• A cable may have one or more than one core depending upon the
type of service for which it is intended.
21. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 21
Cables for 3-Phase Service
• In practice, underground cables are generally required to deliver 3-phase
power. For the purpose, either three-core cable or three single core cables
may be used.
For voltages up to 66 kV, 3-core cable (i.e., multi-core construction) is
preferred due to economic reasons.
For voltages beyond 66 kV, the insulation required for that cable is too much
hence, single-core cables are used in order to prevent the thermal in cable.
For higher voltages, 3 cored become too large and unwieldy hence, even
with some limitations we employ single cored cables
• The following types of cables are generally used for 3-phase service :
1. Belted cables — up to 11 kV
2. Screened cables — from 22 kV to 66 kV
3. Pressure cables — beyond 66 kV.
22. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 22
1. Belted cables
These cables are used for voltages up to
11kV but in extraordinary cases, their use
may be extended up to 22kV.
• The cores are not in circular shape.
• The cores are insulated from each
other by use of impregnated paper.
• The gaps are filled with fibrous
material like jute.
• The belt is covered with lead
sheath and provides flexibility as
well as a circular shape
23. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 23
2. Screened cables.
These cables are meant for use up to 33 kV, but in
particular cases their use may be extended to
operating voltages up to 66 kV.
The two types of screened cables are:
• H(Hochstetler )-Type cables
• S.L.(separate lead) Type cables
Screened cables (i) H-type cables
(ii) S.L. Type cables
24. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 24
H- Type cables :
• Designed by M. Hochstetler and hence named H-type cable.
• No paper belt in this type of cable.
• Each conductor is insulated with a paper, covered with a
metallic screen.
Advantages
• Perforations in the metallic screens assist in the complete impregnation
of the cable with the compound and thus the possibility of air pockets
or voids (vacuous spaces) in the dielectric is eliminated.
• Metallic screens increase the heat-dissipating power of the cable.
• The cores are laid in such a way that metallic screens make contact with one
another.
• The conducting belt (copper woven fabric tape) is wrapped round the three cores
25. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 25
Advantages
• Separate sheaths minimize the possibility of core-to-core breakdown.
• Bending of cables becomes easy due to the elimination of overall lead
sheath.
Disadvantage
• Three lead sheaths of S.L. cable are much thinner than the single
sheath of H-cable and, therefore, call for greater care in manufacture.
S.L.(separate lead) Cables :
• S.L. leads for Separate Lead Screened
Cables.
• Each core is insulated with impregnated
paper than covered by separate sheath
lead
26. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 26
3. Pressure Cables
• When the operating voltages are greater than 66 kV and up to
230 kV, pressure cables are used.
• In such cables, voids are eliminated by increasing the pressure
of compound and for this reason they are called pressure
cables.
• Two types of pressure cables viz oil-filled cables and gas
pressure cables are commonly used.
• Oil or gas is kept under pressure either within the cable sheath
itself or a containing pipe
27. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 27
(i) Oil-filled cables
• In case of oil filled cables, the channels or ducts
are provided within or adjacent to the cores,
through which oil under pressure is circulated.
28. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 28
Advantages :
• Thickness of insulation required is less.
• Thermal resistance is less.
• Possibility of voids is completely eliminated.
• Temperature range is high.
• Perfect impregnation is possible.
Disadvantages :
• Initial cost is very high.
• Long lengths are not possible.
• Oil leakage is serious problem.
• Complicated maintenance.
Oil-filled cables ……
29. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 29
ii) Gas Pressure Cables
• An inert gas like N at high pressure is introduced
lead sheath and dielectric.
• Gas like SF6 is also used in cables.
• Pressure is about 12-15 atmosphere.
• Working power factors is also high
Advantages :
• These can carry 1.5 times of the normal load current.
• Maintenance cost is small.
• No reservoirs or tanks required.
• Power factor is improved.
• Ionization and possible void completely eliminated.
Disadvantages :
• The only disadvantage is that the initial cost is extremely high.
30. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 30
4. SUPER TENSION (S.T.) CABLES
• The S.T. cables are intended for 132 kV
to 275 kV voltage levels.
• In such cables, the following methods
are specially used to eliminate the
possibility of void formation:
Instead of solid type insulation, low
viscosity oils under pressure is used for
impregnation.
Using inert gas at high pressure in
between the lead sheath & dielectric.
31. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 31
Power Cable Installation methods
There are three main methods of Laying underground cables:
• Direct laying
• Draw in system
• Solid system
32. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 32
• A trench of about 1.5 meters deep and 45 cm wide is dug.
• Then the trench is covered with a 10 cm thick layer of fine sand.
• The cable is laid over the sand bed. The sand bed protects the
cable from the moisture from the ground.
• Then the laid cable is again covered with a layer of sand of about
10 cm thick.
• When multiple cables are to be laid in the same trench, a
horizontal or vertical spacing of about 30 cm is provided to
reduce the effect of mutual heating. Spacing between the cables
also ensures a fault occurring on one cable does not damage the
adjacent cable.
• The trench is then covered with bricks and soil to protect the
cable from mechanical injury.
Direct Laying Of Underground Cables
33. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 33
Advantages
• Simpler and cheaper than the other two methods
• Heat generated in cables is easily dissipated in the ground.
• It is clean and safe
Disadvantages
• To install new cables for fulfilling an increased load demand,
completely new excavation has to be done which costs as much
as the new installation.
• Alterations in the cable network are not easy.
• Maintenance cost is higher.
• Identifying the location of a fault is difficult.
• This method can not be used in congested areas such as metro
cities where excavation is too expensive.
34. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 34
Draw in system
• Draw in system cable layout methods is widely
used for heavily populated areas such as
urban cities and towns.
• the cables are layout in ducts or pipelines on
the ground with certain manholes
Draw in system Disadvantages
• It is very high initial cost
• Heat dissipation conditions are not good
• This method is suitable for congested areas
where excavation in expensive and
inconvenient
• This is generally used for short lenghts cable route such as in
workshops,road crossings where frequent digging is costlier and impossible
35. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 35
Solid System
• In this system the cable is laid in open pipes or troughs dug
out in earth along the cable route
• The troughing is of cast iron or treated wood
• Troughing is filled with a bituminous after cable is laid
• It provides good mechanical strength
• the cables are filled with bituminous materials for providing
protection and avoid heat dissipation.
• Asphalt cover layer around the cable and bituminous
material area for further protection
Disadvantages
• More expensive than direct laid system
• Requires skilled labour and favourable weather conditions
• Due to poor heat dissipation facilities, the current carrying capacity of the cable is
reduced
• In view of these disadvantages, this method of laying underground cables is
rarely used nowadays
36. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 36
The depth of burial shall be sufficient to
protect the cable from damage imposed by
expected surface usage
• LV cable (1.1 kV) 0.75m
• MV cable (11 kV) 0.90 m
• HV cable (33 kV) 1.20 m
• Sand – covered with 150 mm
• Width of the trench 350 mm minimum
Depth of Burial
37. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 37
Calculation of high voltage cable parameters
38. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 38
Insulation Resistance of a Single-Core Cable
Radius of conductor=r1
Radius of sheath=r2
small layer of insulation of
thickness dx at a radius x
This shows that insulation resistance of a cable is inversely
proportional to its length. In other words, if the cable length
increases, its insulation resistance decreases and vice-versa.
the leakage resistance is inversely proportional to the length of cable.
Solve example 11.1. up to 11.3 from pages 273-274
39. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 39
Capacitance of a Single Core Cable
A single-core cable can be considered to be
equivalent to two long co-axial cylinders. The
conductor (or core) of the cable is the inner
cylinder while the outer cylinder is represented
by lead sheath which is at earth potential.
Consider a single core cable with conductor
diameter d and inner sheath diameter D
Conductor diameter=d
Inner sheath diameter=D
the charge per metre axial length of the cable be Q coulombs and ε be the
permittivity of the insulation material between core and lead sheath. Obviously ε =
ε0 εr where εr is the relative permittivity of the insulation.
40. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 40
Consider a cylinder of radius x metres and axial length 1 metre. The surface
area of this cylinder is
41. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 41
Solve example 11.1.
up to 11.6 from
pages 275-276
42. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 42
Example
Solution
A 33 kV, 50 Hz, 3-phase underground cable, 4 km long uses three single
core cables. Each of the conductor has a diameter of 2·5 cm and the radial
thickness of insulation is 0·5 cm. Determine (i) capacitance of the
cable/phase (ii) charging current/phase (iii) total charging kVAR. The relative
permittivity of insulation is 3.
43. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 43
Dielectric Stress in a Single-Core Cable
• Under operating conditions, the insulation of a cable is
subjected to electrostatic forces. This is known as dielectric
stress. The dielectric stress at any point in a cable is the
potential gradient (or electric intensity) at that point.
• Consider a single core cable with core diameter d and internal
sheath diameter D. the electric intensity at a point x metres from
the centre of the cable is
• Electric intensity is equal to potential
gradient. Therefore, potential gradient g at a
point x metres from the centre of cable is
Potential difference V between
conductor and sheath is
from slide 41
44. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 44
• The potential gradient varies inversely as the distance x. Therefore, potential
gradient will be maximum when x is minimum i.e., when x = d/2 or at the
surface of the conductor and it will be minimum at x = D/2 or at sheath
surface.
Maximum potential
gradient is
Minimum potential
gradient is
The variation of stress in the dielectric is shown in the above fig. The dielectric
stress is maximum at the conductor surface and its value goes on
decreasing as we move away from the conductor.
45. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 45
• It may be noted that maximum stress is an important consideration in the
design of a cable.
• For instance, if a cable is to be operated at such a voltage that maximum stress
is 5 kV/mm, then the insulation used must have a dielectric strength of at least
5 kV/mm, otherwise breakdown of the cable will become inevitable.
Solve example 11.7. up to 11.9 ; pages 278-279
46. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 46
The maximum and minimum stresses in the dielectric of a single core cable
are 40 kV/cm (r.m.s.) and 10 kV/cm (r.m.s.) respectively. If the conductor
diameter is 2 cm, find : (i) thickness of insulation (ii) operating voltage
Example
Solution
47. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 47
Capacitance of 3-Core Cables
The capacitance of an underground cable system is much more important than
that of overhead line because in cables:
(i) conductors are nearer to each other and to the earthed sheath
(ii) they are separated by a dielectric of permittivity much greater than that of air.
Since potential difference
exists between pairs of
conductors and between
each conductor and the
sheath, electrostatic fields
are set up in the cable as
shown in the above Fig.
48. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 48
These electrostatic fields give rise to core-core capacitances Cc and conductor-
earth capacitances Ce as shown in Fig. (ii).
The three Cc are delta connected whereas the three Ce are star connected, the
sheath forming the star point [See Fig. (iii)].
49. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 49
They lay of a belted cable makes it reasonable to assume equality of each Cc and
each Ce. The three delta connected capacitances Cc [See Fig. (i)] can be
converted into equivalent star connected capacitances as shown in Fig. (ii). It can
be easily shown that equivalent star capacitance Ceq is equal to three times the
delta capacitance Cc i.e. Ceq = 3Cc.
50. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 50
The system of capacitances shown in Fig. (iii)
reduces to the equivalent circuit shown in
Fig. (i). Therefore, the whole cable is
equivalent to three star-connected
capacitors each of capacitance [See Fig. (ii)]
51. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 51
Current-Carrying Capacity of Underground Cables
• The safe current-carrying capacity of an underground cable is determined
by the maximum permissible temperature rise.
• The cause of temperature rise is the losses that occur in a cable which
appear as heat. These losses are :
(i) Copper losses in the conductors
(ii) Hysteresis losses in the dielectric
(iii) Eddy current losses in the sheath
The safe working conductor temperature is 65ºC for armoured cables and 50ºC
for lead-sheathed cables laid in ducts. The maximum steady temperature
conditions prevail when the heat generated in the cable is equal to the heat
dissipated. The heat dissipation of the conductor losses is by conduction
through the insulation to the sheath from which the total losses (including
dielectric and sheath losses) may be conducted to the earth. Therefore, in order
to find permissible current loading, the thermal resistivity of the insulation,
the protective covering and the soil must be known.
52. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 52
Thermal Resistance
The thermal resistance between two points in a medium (e.g. insulation) is
equal to temperature difference between these points divided by the heat
flowing between them in a unit time i.e.
Thermal resistance(ºC per watt),
S=
Temperature difference
Heat flowing in a unit time(watt)
=
Temperature rise(𝑡)
Watts dissipated(𝑃)
=
𝑡
𝑃
Like electrical resistance, thermal resistance is directly proportional to
length l in the direction of transmission of heat and inversely proportional to
the cross-section area a at right angles to that direction.
where 𝒌 is the constant of proportionality
and is known as thermal resistivity.
53. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 53
Thermal Resistance of Dielectric of a Single-Core Cable
Consider 1m length of the cable. The thermal resistance of
small element of thickness dx at radius x is
r = radius of the core in metre r1 = inside radius of the sheath
in metre k = thermal resistivity of the insulation
∴ Thermal resistance of the dielectric is
The thermal resistance of lead sheath is small and is generally neglected
in calculations.
54. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 54
Permissible Current Loading
• When considering heat dissipation in underground cables, the various thermal
resistances providing a heat dissipation path are in series. Therefore, they
add up like electrical resistances in series. Consider a cable laid in soil.
• Let I = permissible current per conductor; n = number of conductors ;
R = electrical resistance per metre length of the conductor at the working temperature
S = total thermal resistance (i.e. sum of thermal resistances of dielectric and soil) per
metre length and t = temperature difference (rise) between the conductor and the soil
• Neglecting the
dielectric and
sheath losses, we
have,
𝑷𝒐𝒘𝒆𝒓 𝒅𝒊𝒔𝒔𝒊𝒑𝒂𝒕𝒆𝒅 = 𝒏𝑰𝟐𝑹
𝑷𝒐𝒘𝒆𝒓 𝒅𝒊𝒔𝒔𝒊𝒑𝒂𝒕𝒆𝒅 =
𝑻𝒆𝒎𝒑𝒆𝒓𝒂𝒕𝒖𝒓𝒆 𝒓𝒊𝒔𝒆
𝑻𝒉𝒆𝒓𝒎𝒂𝒍 𝒓𝒆𝒔𝒊𝒔𝒕𝒂𝒏𝒄𝒆
Or n 𝑰𝟐𝑹 =
𝒕
𝑺
Permissible current
per conductor in given
by;
• It should be noted that when cables are laid in proximity to each other, the
permissible current is reduced further on account of mutual heating.
55. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 55
A single-core cable is laid in the ground, the core diameter being 30 mm and the
dielectric thickness 40 mm. The thermal resistivity of the dielectric is 5 thermal
ohm-metres and the thermal resistance between the sheath and the ground
surface is 0·45 thermal ohm per metre length of the cable. Neglecting dielectric
and sheath losses, estimate the maximum permissible current loading if the
temperature difference between the conductor and the ground surface is not to
exceed 55ºC. The electrical resistance of the cable is 110 µΩ per metre length.
Solution.
The thermal resistance of the dielectric
of the cable is
Example.
Here t = 55ºC ; n = 1,
R = 110 × 10−6 Ω ; S = 1·48
56. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 56
Types of Cable Faults
• Cables are generally laid in the ground or in ducts in the underground
distribution system. For this reason, there are little chances of faults in
underground cables. However, if a fault does occur it is difficult to locate
and repair the fault because conductors are not visible.
• The causes of damage to the lead sheath are: crystallization of the lead
through vibration; chemical action on the lead when buried in the earth
and insufficiently protected; and mechanical damage.
• Main equipment to determine cable fault is ohmmeter beside that, a
few test can be done to determine cable fault such as :
1. Continuity Test
2. Insulation Resistance Test.
• Cable Fault Location instruments (cable fault locators) are used for
short circuit faults , cable cuts, resistive faults, intermittent faults, and
sheath faults.
57. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 57
Major factors that cause failure of underground cable are:
Damaged accidentally by external mechanical means, like external
damage due to digging
Damage was caused as a result of mishandling the cable during
layout(Excessive pull, Sharp bend, Accident crush).
Poor workmanship in cable jointing. The cables are jointed together with
poor workmanship can lead to cable faults after a period of time.
Natural causes due to aging of cable. May occur due to deterioration of
insulation due to aging or irreversible change of material properties after
exposure to an environment for an interval of time
Damaged caused by movement of soil and erosion
58. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 58
• The following are the faults most likely to occur in underground
cables:
1) open circuit fault
2) short circuit fault
3) earth fault
59. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 59
Open circuit fault
• When the conductor of cable is broken or joint is pulled out there is no
current in the cable it is called open circuit fault.
• The open circuit fault can be checked by Megger. For this purpose, three
measurements are to be carried out between R-Y, Y-B, B-R. The two
conductors of the 3-core cable at the far end are shorted.
• The resistance between two conductors is measured by a megger and it will
indicate zero resistance in the circuit of the conductor that is not broken. If
the continuity of the cable is sound, insulation resistance from one end is
sufficient.
• However, if the conductor is broken, the megger will indicate infinite
resistance in its circuit
60. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 60
Short circuit fault
• When the insulation between two cable or two cores of a multi-core cable
gets damaged, the currents start flowing from one cable to another cable
or from one core to another core of a multi-core cable directly(without
passing through core).
• When two conductors of a multi-core cable come in electrical contact
with each other due to insulation failure, it is called a short circuit fault.
• Again, we can seek the help of a megger to check this fault.
• For this purpose the two terminals of the megger are connected to any two
conductors.
• If the megger gives zero reading, it indicates short circuit fault between
these conductors. If the megger will indicate infinite resistance in its circuit,
no short circuit
• The same steps is repeated for other conductors taking two a time.
61. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 61
Ground or Earth Faults (Break-down of cable insulation)
• When the insulation of the cable gets damaged, the current start
flowing from core to earth or to cable sheath.
• When the conductor of a cable comes in contact with earth, it is
called earth fault or ground fault.
• To identify this fault, one terminal of the megger is connected to the
conductor and the other terminal connected to earth.
• If the megger indicates zero reading, it means the conductor is
earthed. The same procedure is repeated for other conductors of the
cable
62. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 62
• FAULT LOCATION PROCEDURE
The proper sequence of cable fault location are as follows:
Analysis of fault
Pre-location
Pin Pointing
Confirmation and re-test
https://www.cablejoints.co.uk/upload/Cable_Locating,_Detection_&_Cable_Fault_Finding___
Guidebook.pdf
• By repairing and re-testing, we ensure that the
underground cable fault is corrected; all the while
ensuring safety of field personnel.
63. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 63
Analysis of Cable Fault
Analysis of cable fault normally consists of insulation resistance(IR) test and
continuity test
To analyze a cable fault is to determine and confirm the nature or characteristics
of the fault.
1. Insulation resistance(IR) test, Six
measurement are to be taken R-E, Y-
E, B-E, R-Y, Y-B, B-R.
2. Continuity Test, this test will determine
whether any of the cable is open
circuited. Three measurements are to be
carried out between R-Y, Y-B, B-R
https://slideplayer.com/slide/16374650/
65. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 65
Pre- Location of fault
• Pre-location is the application of a test at the terminals of a given cable to
give an indication of the distance to the fault from the test point.
• The purpose of pre-location is to give an indication, as quick as possible, of
the vicinity in which to commence the final pin-pointing tests.
66. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 66
PIN POINTING
Pin Pointing is the application of a test that positively confirms the exact position of the
fault.
Before the commencement of pinpointing, the pre-located fault distance should be
marked on the cable route which is measured using a trumpeter. Pinpointing is
normally carried out by the shock wave discharge method.
The fault can be detected by the use of a semisphone.
Confirmation and Re-Test
After the pin-pointed position of the fault has been marked and exposed, check for
physical sign of fault. If there is the fault is confirm.
After confirmation, the fault should be cut away, IR and continuity test should be
carried out on the remaining cable sections to determine the soundeness of these cable
sections. The insulation resistance test are again carried out after jointing followed by
pressure test before supply can be restored.
While undertaking the entire process of pinpointing cable fault, identifying appropriate
cable and repairing and re-testing, ensure that all essential safety precautions are
followed.
67. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 67
Location Cable Fault in an Underground Cables
• Cable fault locator is a combination of Surge generator, Reflectometer and
Digipoint which are used for fault location in LT up to 11kV cables
• Van Mounted Cable Fault Locator, System designed for locating fault in LT to HT
underground cables
• The underground cable fault distance
locator is develop to detect the exact
fault location and the distance of
underground cable fault from based
station in kilometers as the system will
detect the faulted cable on underground
and will send the information to the
control room by using a relay.
68. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 68
Surge generator
• It is used to produce high voltage surges,
perform DC high voltage testing and
provide the burning facility.
• Perform DC high voltage testing up to
16kV to find out which phase is faulty and
determine its breakdown voltage and
leakage current.
https://pdf.indiamart.com/impdf/23056748430/MY-1084010/underground-power-cable-
fault-locators-suitable-from-lt-to-ht-11kv-cables.pdf
1. Cable fault locator
69. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 69
• It is a digital time domain reflectometer used for finding the distance to the fault
from one end of the cable (Pre-Location).
Reflectometer
• Pulse Echo(TDR), Impulse current(ICM)& Decay method
provided to get the distance to almost all types of faults
Pulse Echo Method
Low voltage pulses are injected into the cable to locate open or
short circuit low resistive faults up to 200 ohm (measured by
multimeter) only. Provides total length of the cable fault.
The distance to the fault Lf (m) is given by Lf = T x Vp/2
Where: T, the duration of the pulse transmitted, till the pulse
is reflected back from the point of irregularity, If the fault
distance is Lf, the velocity of propagation (VOP) is Vp
The waveform generated can be monitored using an
oscilloscope
70. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 70
Impulse Current Method (ICM)
High voltage surges with the help of surge generator are injected into
the power cables. It gives the fault distance of almost all types of faults
including low resistive, high resistive and intermittent faults.
Decay Method
Decay method is most suitable for accurate pre-location of Flashing
faults
Interactive Software
The interactive menu based graphical user interface makes it easy for even
a layman to pre-locate the fault distance. The software automatically saves
all the test results for future review and analysis with a huge storage
capacity of more than 100,000 graphs. It also allows us to compare any 5
selected graphs to review the fault conditions for more accurate result.
71. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 71
Digi point
• It is used with a Surge Generator to determine the exact position of faults in
underground power cables. Pinpointing the exact location of the fault
• Magnetic and Acoustic signal strength through bar graph and digits on LCD
• Route indication of cable under test
It indicates the route of the cable under test by
sensing and amplifying the electromagnetic
signals produced at the time of surging and displays
the magnetic strength of those signals through
strength bars and digits on an LCD screen
• The surge generated by the surge generator will create an
acoustic signal at the fault point. The Digipoint displays the
strength of that signal through strength bars and digits on an
LCD screen. The headphones help users to hear the sound
generated.
https://www.youtube.com/watch?v=33qL3HR0HGo&t=1356s
72. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 72
2. Van Mounted Cable Fault Locator
• System designed for locating fault in LT to HT underground
cables, with system integrated and easy operation.
• The Cable fault locating van system is used to perform DC hi-
pot/ burn/ proof test, pre-location of fault distance, and pinpoint
underground cable fault by acoustic method with the help of
suitable DIGIPOINT in power transmission and distribution
with cable networks or service provider companies.
1.Automatic operating mode selection.
2.Convenient, fully automatic system operation with computerized
touch screen.
3.Safety status monitoring on display.
4.Cable library to store the traces.
• Responsible for all the functions from computerized touch
screen operating unit.
5.Separate high voltage unit from operation unit for the safety of operator
https://pdf.indiamart.com/impdf/23755209673/1084010/
automatic-cable-fault-locator-model-t-1032-20a-.pdf
73. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 73
• All fault-finding methods such as DC Testing, Fault Conditioning/ Limited
Burning Capability, Suitable Thumper for Pinpointing are provided in the
Surge Generator unit.
• DC Testing is used for checking the dielectric strength of insulation in the cable
and to identify and confirm fault conditions with a test voltage up to 40kV
• All pre-location methods such as PEM(Pulse Echo Method), ICM(Impulse
Current Method), ARM(Arc Reflection method)/SIM/MIM(Single Impulse Method
/ Multiple Impulse Method and DECAY method are provided in the system for
determination of high resistive faults for HT method
https://www.youtube.com/watch?v=33qL3HR0HGo&t=1356s
74. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 74
Advantages of underground cables:
• less liable to damage through storms or lightning,
• low maintenance cost,
• less chance of faults,
• smaller voltage drop as the Inductive reactance of O.H.T. Lines is more
• better general appearance.
• Conserve valuable land in urban areas and avoid danger to the persons
from accessibility of high-voltage power
Disadvantages of underground cables:
• The major drawback is that they have greater installation cost and introduce
insulation problems at high voltages compared with equivalent overhead
system.
• Capacitance and charging current is high in case of underground cables,
so that for long distance power transmission, the charging current is very high
results in over voltages problems.
75. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 75
Comparison of Overhead vs underground power lines cables
76. COLLEGE OF SCIENCE
AND TECHNOLOGY
4/5/2024 76
Transmission: Underground may be 4-20 times Overhead.
Sub transmission: Underground may be 4-20 times Overhead
Distribution: Underground may be 2-10 times Overhead
Summary of Costs: Overhead vs. Underground
Editor's Notes
Municipal definition, of or relating to a town or city or its local government
Tinned =covered cable rough=irregular = not smooth laying=put down
Tinned copper is primarily used for protection against oxidation and corrosion. ... Chemical stability is the material's ability to withstand change from chemical contact. As more of this oxide forms, it weakens the integrity of the copper making it brittle and crumbly. Corrosive copper wire is less efficient at moving electricity and can cause safety hazards.
Cable shielding functions as an electromagnetic energy interceptor: it prevents electrical interference from traveling to the cable's center conductor and disrupting the data signal.
Impregnated=filled
Fibrous=cawucu The fibrous materials has very broad meaning, and it can be categorized such as plastics, rubber, textiles, paper, glass, food, human body, etc. Fibers can be classified into two major groups as natural and man-made or manufactured.
Non-inflammable=doesn't catch fire and burn easily
Impregnated=filled hygroscopic= it should absorb moisture from air or soil. The moisture tends to decrease the insulation resistance and hastens the breakdown of the cable. Durability=touthness. Dielectric strength is measured as the maximum voltage required to produce a dielectric breakdown through a material
Hygroscopic=absorbe moisture(vapor) from air or soil coated=covered varnish=paint
it is compounded with certain materials known as plasticizers which are liquids with high boiling point
unwieldy = difficult to move because of its size, shape, or weight. https://www.slideshare.net/Anu71/underground-cables
https://www.slideshare.net/surojitmahato121/power-cables
Fibrous=urudodo "Jute(bimeze nki ubudodo)" is the name of the plant or fiber used to make gunny cloth. Jute=protect atmospheric contamination
S.L= metal screen or metallic sheath iba iri around 3conductors H-T= igira metallic screen kuri buri conductor
Perforations= puncture=hole
Oil or gaz biba bikoranye ni urusinga bika bifite akamaro as insulator and cooling system
oil or gaz is kept under pressure either within the cable sheath itself or a containing pipe.
Voids=holes
N= Nitrogene
An inert gas is a gas that has extremely low reactivity with other substances
excavation =dig
Asphalt=trench
Overcome=prevail conduction=transfer
Intermittent fault=discontinuity resistive faults=measurement of cable resistance Intermittent are caused by some mechanical change like temperature, vibration, moisture and physical stress that temporarily changes the electrical characteristics of device under test. sheath faults=testing sheath if is damaged
Six measurement are to be taken R-E, Y-E, B-E, R-Y, Y-B, B-R.
Intermittent=broken
Hipot testing involves applying an overvoltage to the cable system for a short duration to verify the dielectric integrity of the system (cable, splices, and terminations). In most cases hipot testing is applied as a pass/fail or go/no-go test.