SlideShare a Scribd company logo
1 of 22
A Technical seminar on
     “APPLICATION OF A SUB-
     HARMONIC PROTECTION
             RELAY ”

Under the guidance of    Mukund Kumar
Mr.H.S.Sridhar, M.Tech   USN-
  1SI09EE030
Asst. Professor
Department of E&E
SIT, Tumkur
Contents
   Abstract
   Loads Contributing to Sub-Harmonic Disturbances
   Relevant Terminologies
   Sub-Harmonic Protection Relay
   Sub-Harmonic Detection Principle
   Sub-Harmonic Detection Logic Diagram
   Operations/Minute Detection
   Tools For Sub-Synchronous Resonance Monitoring
   Results
   Relay Settings Based On the Results
   Operations/Minute setting
   Conclusion
   References
Abstract
   The required long transmission lines are often constructed with series
    capacitive compensation to electrically shorten the lines.
   These events in the transmission system can cause interactions between
    the series capacitors and the system„s inherent impedance which can
    result in sub-synchronous resonance frequencies.
   Modern wind turbine systems use advanced electronic control and
    converter systems which can generate harmonics and inter harmonics.
    Wind generator speeds vary continuously depending on the availability
    of wind at any particular time. This particular operating characteristic of
    wind farms introduces the challenge of predicting when and how much
    harmonics and sub-harmonics are being introduced to the power system.
   Synchronous generators are often built with shaft torsional modes that
    are in the same range as system sub-synchronous resonance frequencies.
    These torsional modes can interact with transmission network
    resonances to produce damaging oscillations that can damage generators
    and transformers, and cause damage at points of common coupling in
    the electrical grid.
Contd……….

   Thus a sub-synchronous relay provides protection for transmission
    lines, particularly those with serial compensation and wind farm
    interconnections and it can be used together with digital fault recorders
    to monitor the power system to determine the existence of sub-
    synchronous resonance phenomenon.
   This protection scheme goes further, providing possible settings for the
    sub-harmonic protection relay including the protection elements
    associated to sub-harmonics as well as providing over current and other
    protection functions.
Loads Contributing to Sub-Harmonic
Disturbance
    Sub-harmonic currents, i.e. components with frequencies lower than
    60 or 50 Hz, are injected by a many modern loads. A brief list of the
    most significant contributors follows:
   Arc Furnaces
   Cyclo Converters
   Automated spot-welders
   Integral-cycle-controlled furnaces or any type of pulse burst-
    modulation power conditioned load
   Rectifiers supplying fluctuating or cyclic loads
   Motor driving cyclic loads, such as forges, drop hammers, stamping
    tools, saws, compressors and reciprocating pumps
   Wind generators; interaction tower-to-blade causes the modulation
    of the driving torque
Relevant Terminologies

   Sub-Synchronous Frequency (SSF): The frequency of an oscillation
    that is less than the nominal frequency of the power system, not be
    confused with power system fundamental frequency that becomes
    slightly lower than nominal that may temporarily occur under normal
    conditions.
   Harmonics: Frequencies that are multiples of the fundamental
    frequency (i.e. 2nd - 120Hz, 3rd – 180 Hz for a 60 Hz fundamental).
   Sub-Harmonics: Frequencies that are less than the fundamental but at
    reflections of the harmonics (i.e. 1/2 - 30 Hz, 1/3rd - 20 Hz for a 60
    Hz fundamental).
   Sub-Synchronous Interactions (SSI): Defines two parts of an electric
    system exchanging energy with each other at one or more of the
    natural frequencies of the combined system below the fundamental
    frequency of the system.
   Sub-Synchronous Resonance (SSR): Defines the known problem of
    synchronous generators near a series capacitor when the mechanical
    mass resonates with the effective impedance of the system, known
    to cause damage in generators.
   Sub-Synchronous Control Instability (SSCI): Defines a relatively
    new problem of a “Interactions between a power electronic
    device(such as HVDC link, SVC, wind turbine, etc….)and a series
    compensated system.”
FIG: SYSTEM ONE LINE SHOWING GENERATION AND SERIES
                 COMPENSATED LINE
Fig: Sub-harmonic oscillations at wind farm
interconnections.
Sub-harmonic Protection Relay
   The relay protects against sub-harmonic oscillations by measuring the
    voltages and currents with frequencies in the range of 5-40Hz. The
    relay not only initiates protective actions, it can also record individual
    sub-harmonic currents and voltages that can be used for future system
    studies.
   The sub-harmonic relay is composed of four sets of currents and two
    sets of 3-phase voltage inputs. Each input can be set to detect individual
    frequencies from 5-40Hz with two levels of detection.
   The device also has the ability to sum quantities from two of the current
    inputs, a useful feature that allows the monitoring of currents in lines
    that are associated to two breakers, applying the level detectors to these
    summated quantities.
   Moreover, the device also has triggered-recording capability to alarm or
    take action for cyclical sub-harmonic quantities that may be oscillating
    just below the tripping levels.
Sub-Harmonic Detection Principle
Contd…….
   The theory behind the sub-harmonic detection is to compare the
    magnitude of each of the sub-harmonic currents and voltages that are
    observed between the user-defined minimum (Fmin) and maximum
    (Fmax) frequency range, with the settings specified by the user (Lset)
    magnitude.
         Trip or Alarm: = max (f2, f3, f4, f5, f6, f7) > Lset      --------(1)
   The nominal sub-harmonic detector compares the level by estimating
    the ratio of sub-harmonic magnitude to the nominal CT/PT ratio. For
    eg: assuming nominal CT ratio of 5A and an estimated sub-harmonic
    magnitude of 2.5 A at 5 Hz. The nominal sub-harmonic level is then
    compared as follows:
                      f15Hz (%) = (2.5/5) * 100         -------------(2)
   The Total Sub-Harmonic Distortion (TSHD) detector calculates the
    distortion level as follows:
    TSHD(%) = √(f²5Hz+f²6Hz+f²7Hz+……….+f²40Hz)/f50Hz*100-----
     ----------(3)
Sub-harmonic Detection Logic Diagram
Operations/Minute Detection

   The time Tact corresponds to
    the actual duration of the sub-
    harmonic signal which is
    asserted.
   30    operations      (assertion
    above set limit) will be
    internally     counted      and
    monitored.      If   the      set
    operations per minute count
    exceeds      the     calculated
    count, then this special
    detector will issue a trip or an    Fig: Operations/Minute Detector
    alarm as per the configuration               Functionality.
Tools for Sub-Synchronous Resonance
    Monitoring
   The increased use of wind generators feeding HV and EHV utility
    networks with series compensated lines in the near vicinity has made
    to ensure that sub-harmonic oscillations are monitored, and that the
    electrical grid is protected from any resulting detrimental effects.
    Monitoring voltage and current signals for sub-harmonics becomes a
    critical factor.
   Digital Fault Recorder(DFR) is the tool for sub-synchronous resonance
    monitoring along with the sub-harmonic protection relay.
   Due to their ability to sample at a higher rate, digital fault recorders
    (DFRs) provide better quality recording when compared to
    oscilliographic records captured by digital relays. DFRs do not filter
    any frequencies and provide the true signal observed during the event.
    Furthermore, due to their storage capacity, DFRs can capture records
    of longer duration, with sufficient data before and after the event.
Results

   Figure shows the current
    oscilliography         record
    captured during the event.
   It can be observed, the
    currents         are   not
    sinusoidal, but rather are
    quite distorted.
   An oscillographic record of
    this nature suggests that the
    waveform is rich with
    multiple frequencies.
                                Fig: Current response to sub- synchronous
                                                resonance
Fig:(a)Sub-harmonic magnitudes   Fig:(b)Sub-harmonic magnitude values
           (RMS).                             per phase.
Relay Settings based on above results

   Eg: The highest sub-harmonic current observed during the event was the
    11th harmonic with a magnitude of 172 primary amps with a current
    transformer ratio of 400:1. The relay current inputs were 5A inputs.
    Fundamental current was observed to be 1300A with CT ratio of 400:1:

   Nominal Ratio   = (Highest Sub-Harmonic Current) = 172/400
                        (Nominal Current 1A or5A)         5A
                                                     = 8%
                        Set nominal ratio > 6%
   Fundamental Ratio = (Highest Sub-Harmonic Current)
                              (Fundamental Current )
                   = 172/400 =13.5% Set fundamental ratio > 10%
                     1300/400
   TSHD Setting = √(I²(5hz)+ I²(6hz)+…………….+ I²(40hz)
                                  I(50hz)
Operations/minute setting

   The record in Fig (b) shows a
    captured value of total sub-
    harmonic distortion (TSHD)
    between 160% and 165%.
    Thus a TSHD setting greater
    than    100%     would    be
    appropriate.
   In this case, a minimum of 30
    op/min is required for any of
    the     other     sub-harmonic
    settings to take effect.


                                     Fig:(c) Sub-harmonic current relay
                                                  setting.
Conclusion

   Thus it can be concluded sub-harmonics can create problems in the
    power system.
   In addition, solutions were presented on how to mitigate sub-
    harmonic oscillations by describing the application of a sub-
    harmonic protection relay.
   It is clearly depicted here that sub-harmonic relay provides diverse
    functionality and adequate protection functions to detect sub-
    harmonic frequencies. Some of the those features include:
   Protect against sustained sub-harmonics in wind farm operations
   Low cost and efficiently reliable with easy installation
   Improved Overall Response Time
References

   IEEE Paper On APPLICATION OF A SUBHARMONIC
    PROTECTION RELAY by
   Mark Peterson, P.E., René Midence, Joe Perez, P.E.,
   www.erlphase.com
   Ravindranath and Chander -Power System Protection and Switch
    Gear, New Age Publication
   IET-Digital Library
   IEEE Paper On New Microprocessor Based Relay to Monitor and
    Protect Power Systems Against Sub-Harmonics[November 2011]
   Power System Protection 3 Application edited by The Electricity
    Training Association, Institution of Electrical Engineers
Technical Seminar on Application of a Sub-Harmonic Protection Relay

More Related Content

What's hot

Distortion annalyser
Distortion annalyserDistortion annalyser
Distortion annalysermks mk
 
P010439497.jeee [zsep02]
P010439497.jeee [zsep02]P010439497.jeee [zsep02]
P010439497.jeee [zsep02]IOSR Journals
 
Transformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsTransformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsPower System Operation
 
Reflectometer Product Cal/Test Signal Simulation
Reflectometer Product Cal/Test Signal  SimulationReflectometer Product Cal/Test Signal  Simulation
Reflectometer Product Cal/Test Signal SimulationStephen Nibblett
 
AM diode envelope demodulator
AM diode envelope demodulatorAM diode envelope demodulator
AM diode envelope demodulatormpsrekha83
 
Protection, Control and Operation of Transformer Using Numerical Relay
Protection, Control and Operation of Transformer Using Numerical RelayProtection, Control and Operation of Transformer Using Numerical Relay
Protection, Control and Operation of Transformer Using Numerical Relayidescitation
 
Advanced techniques of PULSE WIDTH MODULATION.
Advanced techniques of PULSE WIDTH MODULATION.Advanced techniques of PULSE WIDTH MODULATION.
Advanced techniques of PULSE WIDTH MODULATION.Subashini Puchalapalli
 
Electronic instrumentation in NMT
Electronic instrumentation in NMTElectronic instrumentation in NMT
Electronic instrumentation in NMTSUMAN GOWNDER
 
Stability test of transformer
Stability test of transformerStability test of transformer
Stability test of transformerSantu Mondal
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current ProtectionSARAVANAN A
 
pulse width modulated inverter techniques
pulse width modulated inverter techniquespulse width modulated inverter techniques
pulse width modulated inverter techniquesSAURABH KUMAR
 
Sample calculation-for-differential-relays
Sample calculation-for-differential-relaysSample calculation-for-differential-relays
Sample calculation-for-differential-relaysRoberto Costa
 
Zero setting PSB protection_CBIP
Zero setting PSB protection_CBIPZero setting PSB protection_CBIP
Zero setting PSB protection_CBIPBadal Patnaik
 
Power Electronics Chapter 7
Power Electronics  Chapter 7Power Electronics  Chapter 7
Power Electronics Chapter 7guest8ae54cfb
 

What's hot (19)

Distortion annalyser
Distortion annalyserDistortion annalyser
Distortion annalyser
 
G010334953
G010334953G010334953
G010334953
 
About Sine Pulse Width Modulation
About Sine Pulse Width Modulation About Sine Pulse Width Modulation
About Sine Pulse Width Modulation
 
P010439497.jeee [zsep02]
P010439497.jeee [zsep02]P010439497.jeee [zsep02]
P010439497.jeee [zsep02]
 
Ieee inrush tutorial
Ieee inrush tutorialIeee inrush tutorial
Ieee inrush tutorial
 
Inverter
InverterInverter
Inverter
 
Transformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsTransformer Differential Protection Setting Calculations
Transformer Differential Protection Setting Calculations
 
Reflectometer Product Cal/Test Signal Simulation
Reflectometer Product Cal/Test Signal  SimulationReflectometer Product Cal/Test Signal  Simulation
Reflectometer Product Cal/Test Signal Simulation
 
AM diode envelope demodulator
AM diode envelope demodulatorAM diode envelope demodulator
AM diode envelope demodulator
 
Protection, Control and Operation of Transformer Using Numerical Relay
Protection, Control and Operation of Transformer Using Numerical RelayProtection, Control and Operation of Transformer Using Numerical Relay
Protection, Control and Operation of Transformer Using Numerical Relay
 
Advanced techniques of PULSE WIDTH MODULATION.
Advanced techniques of PULSE WIDTH MODULATION.Advanced techniques of PULSE WIDTH MODULATION.
Advanced techniques of PULSE WIDTH MODULATION.
 
Electronic instrumentation in NMT
Electronic instrumentation in NMTElectronic instrumentation in NMT
Electronic instrumentation in NMT
 
Stability test of transformer
Stability test of transformerStability test of transformer
Stability test of transformer
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current Protection
 
pulse width modulated inverter techniques
pulse width modulated inverter techniquespulse width modulated inverter techniques
pulse width modulated inverter techniques
 
Sample calculation-for-differential-relays
Sample calculation-for-differential-relaysSample calculation-for-differential-relays
Sample calculation-for-differential-relays
 
Zero setting PSB protection_CBIP
Zero setting PSB protection_CBIPZero setting PSB protection_CBIP
Zero setting PSB protection_CBIP
 
DC Component of Fault Current
DC Component of Fault CurrentDC Component of Fault Current
DC Component of Fault Current
 
Power Electronics Chapter 7
Power Electronics  Chapter 7Power Electronics  Chapter 7
Power Electronics Chapter 7
 

Similar to Technical Seminar on Application of a Sub-Harmonic Protection Relay

International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)ijceronline
 
06 Cap 5 - interharmonics-and-flicker-2015.pdf
06 Cap 5 - interharmonics-and-flicker-2015.pdf06 Cap 5 - interharmonics-and-flicker-2015.pdf
06 Cap 5 - interharmonics-and-flicker-2015.pdfROCIOMAMANIALATA1
 
Identification and minimization of Harmonics
Identification and minimization of HarmonicsIdentification and minimization of Harmonics
Identification and minimization of HarmonicsMayur Hiwale
 
Power System Harmonics Causes and Effect.ppt
Power System Harmonics Causes and Effect.pptPower System Harmonics Causes and Effect.ppt
Power System Harmonics Causes and Effect.pptrajeshplacherikunnel
 
Bus ele tech_lib_short_circuit_current_calculations (1)
Bus ele tech_lib_short_circuit_current_calculations (1)Bus ele tech_lib_short_circuit_current_calculations (1)
Bus ele tech_lib_short_circuit_current_calculations (1)ingcortez
 
Are Harmonics Still a Problem in Data Centers ?
Are Harmonics Still a Problem in Data Centers ?Are Harmonics Still a Problem in Data Centers ?
Are Harmonics Still a Problem in Data Centers ?Edarat Group
 
Ac Power Problems And Measurement Sreevidhya@Students
Ac Power Problems And Measurement Sreevidhya@StudentsAc Power Problems And Measurement Sreevidhya@Students
Ac Power Problems And Measurement Sreevidhya@StudentsB Bhargav Reddy
 
Impact of harmonics on tripping time of the relay
Impact of harmonics on tripping time of the relayImpact of harmonics on tripping time of the relay
Impact of harmonics on tripping time of the relaysuyash chaurasiya
 
Fuzzy Logic Controlled Harmonic Suppressor in Cascaded Multilevel Inverter
Fuzzy Logic Controlled Harmonic Suppressor in Cascaded Multilevel InverterFuzzy Logic Controlled Harmonic Suppressor in Cascaded Multilevel Inverter
Fuzzy Logic Controlled Harmonic Suppressor in Cascaded Multilevel InverterIJPEDS-IAES
 
A Simulink Model for Damping Power System Oscillations Using Fact Devices
A Simulink Model for Damping Power System Oscillations Using Fact DevicesA Simulink Model for Damping Power System Oscillations Using Fact Devices
A Simulink Model for Damping Power System Oscillations Using Fact DevicesIOSR Journals
 
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Power System Operation
 
Design of Active Filter for Reducing Harmonic Distortion in Distribution Network
Design of Active Filter for Reducing Harmonic Distortion in Distribution NetworkDesign of Active Filter for Reducing Harmonic Distortion in Distribution Network
Design of Active Filter for Reducing Harmonic Distortion in Distribution Networkijtsrd
 

Similar to Technical Seminar on Application of a Sub-Harmonic Protection Relay (20)

Tech sem ppt
Tech sem pptTech sem ppt
Tech sem ppt
 
International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)
 
06 Cap 5 - interharmonics-and-flicker-2015.pdf
06 Cap 5 - interharmonics-and-flicker-2015.pdf06 Cap 5 - interharmonics-and-flicker-2015.pdf
06 Cap 5 - interharmonics-and-flicker-2015.pdf
 
Ads harmonic balance
Ads harmonic balanceAds harmonic balance
Ads harmonic balance
 
Identification and minimization of Harmonics
Identification and minimization of HarmonicsIdentification and minimization of Harmonics
Identification and minimization of Harmonics
 
Hormonics impact and_mitigation
Hormonics impact and_mitigationHormonics impact and_mitigation
Hormonics impact and_mitigation
 
PQ-1.ppt
PQ-1.pptPQ-1.ppt
PQ-1.ppt
 
Power System Harmonics Causes and Effect.ppt
Power System Harmonics Causes and Effect.pptPower System Harmonics Causes and Effect.ppt
Power System Harmonics Causes and Effect.ppt
 
12
1212
12
 
Bus ele tech_lib_short_circuit_current_calculations (1)
Bus ele tech_lib_short_circuit_current_calculations (1)Bus ele tech_lib_short_circuit_current_calculations (1)
Bus ele tech_lib_short_circuit_current_calculations (1)
 
Are Harmonics Still a Problem in Data Centers ?
Are Harmonics Still a Problem in Data Centers ?Are Harmonics Still a Problem in Data Centers ?
Are Harmonics Still a Problem in Data Centers ?
 
Ac Power Problems And Measurement Sreevidhya@Students
Ac Power Problems And Measurement Sreevidhya@StudentsAc Power Problems And Measurement Sreevidhya@Students
Ac Power Problems And Measurement Sreevidhya@Students
 
Impact of harmonics on tripping time of the relay
Impact of harmonics on tripping time of the relayImpact of harmonics on tripping time of the relay
Impact of harmonics on tripping time of the relay
 
Averaging - 1.docx
Averaging - 1.docxAveraging - 1.docx
Averaging - 1.docx
 
Inverter 2003
Inverter 2003Inverter 2003
Inverter 2003
 
Fuzzy Logic Controlled Harmonic Suppressor in Cascaded Multilevel Inverter
Fuzzy Logic Controlled Harmonic Suppressor in Cascaded Multilevel InverterFuzzy Logic Controlled Harmonic Suppressor in Cascaded Multilevel Inverter
Fuzzy Logic Controlled Harmonic Suppressor in Cascaded Multilevel Inverter
 
A Simulink Model for Damping Power System Oscillations Using Fact Devices
A Simulink Model for Damping Power System Oscillations Using Fact DevicesA Simulink Model for Damping Power System Oscillations Using Fact Devices
A Simulink Model for Damping Power System Oscillations Using Fact Devices
 
IEEE 2004
IEEE 2004IEEE 2004
IEEE 2004
 
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
 
Design of Active Filter for Reducing Harmonic Distortion in Distribution Network
Design of Active Filter for Reducing Harmonic Distortion in Distribution NetworkDesign of Active Filter for Reducing Harmonic Distortion in Distribution Network
Design of Active Filter for Reducing Harmonic Distortion in Distribution Network
 

Recently uploaded

Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni
 
Cash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call GirlsCash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call GirlsApsara Of India
 
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesMysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesDipal Arora
 
Tech Startup Growth Hacking 101 - Basics on Growth Marketing
Tech Startup Growth Hacking 101  - Basics on Growth MarketingTech Startup Growth Hacking 101  - Basics on Growth Marketing
Tech Startup Growth Hacking 101 - Basics on Growth MarketingShawn Pang
 
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Tina Ji
 
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature SetCreating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature SetDenis Gagné
 
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Dipal Arora
 
Sales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessSales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessAggregage
 
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...noida100girls
 
GD Birla and his contribution in management
GD Birla and his contribution in managementGD Birla and his contribution in management
GD Birla and his contribution in managementchhavia330
 
The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024christinemoorman
 
M.C Lodges -- Guest House in Jhang.
M.C Lodges --  Guest House in Jhang.M.C Lodges --  Guest House in Jhang.
M.C Lodges -- Guest House in Jhang.Aaiza Hassan
 
Grateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfGrateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfPaul Menig
 
A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMANIlamathiKannappan
 
Monthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxMonthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxAndy Lambert
 
Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023Neil Kimberley
 
RE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman LeechRE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman LeechNewman George Leech
 
Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Roland Driesen
 
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service DewasVip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewasmakika9823
 

Recently uploaded (20)

Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.
 
Cash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call GirlsCash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call Girls
 
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesMysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
 
Tech Startup Growth Hacking 101 - Basics on Growth Marketing
Tech Startup Growth Hacking 101  - Basics on Growth MarketingTech Startup Growth Hacking 101  - Basics on Growth Marketing
Tech Startup Growth Hacking 101 - Basics on Growth Marketing
 
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
 
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature SetCreating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
 
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
 
Sales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessSales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for Success
 
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...
 
GD Birla and his contribution in management
GD Birla and his contribution in managementGD Birla and his contribution in management
GD Birla and his contribution in management
 
The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024
 
M.C Lodges -- Guest House in Jhang.
M.C Lodges --  Guest House in Jhang.M.C Lodges --  Guest House in Jhang.
M.C Lodges -- Guest House in Jhang.
 
Grateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfGrateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdf
 
A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMAN
 
Monthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxMonthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptx
 
Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023
 
RE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman LeechRE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman Leech
 
Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...
 
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service DewasVip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
 
Forklift Operations: Safety through Cartoons
Forklift Operations: Safety through CartoonsForklift Operations: Safety through Cartoons
Forklift Operations: Safety through Cartoons
 

Technical Seminar on Application of a Sub-Harmonic Protection Relay

  • 1. A Technical seminar on “APPLICATION OF A SUB- HARMONIC PROTECTION RELAY ” Under the guidance of Mukund Kumar Mr.H.S.Sridhar, M.Tech USN- 1SI09EE030 Asst. Professor Department of E&E SIT, Tumkur
  • 2. Contents  Abstract  Loads Contributing to Sub-Harmonic Disturbances  Relevant Terminologies  Sub-Harmonic Protection Relay  Sub-Harmonic Detection Principle  Sub-Harmonic Detection Logic Diagram  Operations/Minute Detection  Tools For Sub-Synchronous Resonance Monitoring  Results  Relay Settings Based On the Results  Operations/Minute setting  Conclusion  References
  • 3. Abstract  The required long transmission lines are often constructed with series capacitive compensation to electrically shorten the lines.  These events in the transmission system can cause interactions between the series capacitors and the system„s inherent impedance which can result in sub-synchronous resonance frequencies.  Modern wind turbine systems use advanced electronic control and converter systems which can generate harmonics and inter harmonics. Wind generator speeds vary continuously depending on the availability of wind at any particular time. This particular operating characteristic of wind farms introduces the challenge of predicting when and how much harmonics and sub-harmonics are being introduced to the power system.  Synchronous generators are often built with shaft torsional modes that are in the same range as system sub-synchronous resonance frequencies. These torsional modes can interact with transmission network resonances to produce damaging oscillations that can damage generators and transformers, and cause damage at points of common coupling in the electrical grid.
  • 4. Contd……….  Thus a sub-synchronous relay provides protection for transmission lines, particularly those with serial compensation and wind farm interconnections and it can be used together with digital fault recorders to monitor the power system to determine the existence of sub- synchronous resonance phenomenon.  This protection scheme goes further, providing possible settings for the sub-harmonic protection relay including the protection elements associated to sub-harmonics as well as providing over current and other protection functions.
  • 5. Loads Contributing to Sub-Harmonic Disturbance Sub-harmonic currents, i.e. components with frequencies lower than 60 or 50 Hz, are injected by a many modern loads. A brief list of the most significant contributors follows:  Arc Furnaces  Cyclo Converters  Automated spot-welders  Integral-cycle-controlled furnaces or any type of pulse burst- modulation power conditioned load  Rectifiers supplying fluctuating or cyclic loads  Motor driving cyclic loads, such as forges, drop hammers, stamping tools, saws, compressors and reciprocating pumps  Wind generators; interaction tower-to-blade causes the modulation of the driving torque
  • 6. Relevant Terminologies  Sub-Synchronous Frequency (SSF): The frequency of an oscillation that is less than the nominal frequency of the power system, not be confused with power system fundamental frequency that becomes slightly lower than nominal that may temporarily occur under normal conditions.  Harmonics: Frequencies that are multiples of the fundamental frequency (i.e. 2nd - 120Hz, 3rd – 180 Hz for a 60 Hz fundamental).  Sub-Harmonics: Frequencies that are less than the fundamental but at reflections of the harmonics (i.e. 1/2 - 30 Hz, 1/3rd - 20 Hz for a 60 Hz fundamental).  Sub-Synchronous Interactions (SSI): Defines two parts of an electric system exchanging energy with each other at one or more of the natural frequencies of the combined system below the fundamental frequency of the system.
  • 7. Sub-Synchronous Resonance (SSR): Defines the known problem of synchronous generators near a series capacitor when the mechanical mass resonates with the effective impedance of the system, known to cause damage in generators.  Sub-Synchronous Control Instability (SSCI): Defines a relatively new problem of a “Interactions between a power electronic device(such as HVDC link, SVC, wind turbine, etc….)and a series compensated system.”
  • 8. FIG: SYSTEM ONE LINE SHOWING GENERATION AND SERIES COMPENSATED LINE
  • 9. Fig: Sub-harmonic oscillations at wind farm interconnections.
  • 10. Sub-harmonic Protection Relay  The relay protects against sub-harmonic oscillations by measuring the voltages and currents with frequencies in the range of 5-40Hz. The relay not only initiates protective actions, it can also record individual sub-harmonic currents and voltages that can be used for future system studies.  The sub-harmonic relay is composed of four sets of currents and two sets of 3-phase voltage inputs. Each input can be set to detect individual frequencies from 5-40Hz with two levels of detection.  The device also has the ability to sum quantities from two of the current inputs, a useful feature that allows the monitoring of currents in lines that are associated to two breakers, applying the level detectors to these summated quantities.  Moreover, the device also has triggered-recording capability to alarm or take action for cyclical sub-harmonic quantities that may be oscillating just below the tripping levels.
  • 12. Contd…….  The theory behind the sub-harmonic detection is to compare the magnitude of each of the sub-harmonic currents and voltages that are observed between the user-defined minimum (Fmin) and maximum (Fmax) frequency range, with the settings specified by the user (Lset) magnitude. Trip or Alarm: = max (f2, f3, f4, f5, f6, f7) > Lset --------(1)  The nominal sub-harmonic detector compares the level by estimating the ratio of sub-harmonic magnitude to the nominal CT/PT ratio. For eg: assuming nominal CT ratio of 5A and an estimated sub-harmonic magnitude of 2.5 A at 5 Hz. The nominal sub-harmonic level is then compared as follows: f15Hz (%) = (2.5/5) * 100 -------------(2)  The Total Sub-Harmonic Distortion (TSHD) detector calculates the distortion level as follows: TSHD(%) = √(f²5Hz+f²6Hz+f²7Hz+……….+f²40Hz)/f50Hz*100----- ----------(3)
  • 14. Operations/Minute Detection  The time Tact corresponds to the actual duration of the sub- harmonic signal which is asserted.  30 operations (assertion above set limit) will be internally counted and monitored. If the set operations per minute count exceeds the calculated count, then this special detector will issue a trip or an Fig: Operations/Minute Detector alarm as per the configuration Functionality.
  • 15. Tools for Sub-Synchronous Resonance Monitoring  The increased use of wind generators feeding HV and EHV utility networks with series compensated lines in the near vicinity has made to ensure that sub-harmonic oscillations are monitored, and that the electrical grid is protected from any resulting detrimental effects. Monitoring voltage and current signals for sub-harmonics becomes a critical factor.  Digital Fault Recorder(DFR) is the tool for sub-synchronous resonance monitoring along with the sub-harmonic protection relay.  Due to their ability to sample at a higher rate, digital fault recorders (DFRs) provide better quality recording when compared to oscilliographic records captured by digital relays. DFRs do not filter any frequencies and provide the true signal observed during the event. Furthermore, due to their storage capacity, DFRs can capture records of longer duration, with sufficient data before and after the event.
  • 16. Results  Figure shows the current oscilliography record captured during the event.  It can be observed, the currents are not sinusoidal, but rather are quite distorted.  An oscillographic record of this nature suggests that the waveform is rich with multiple frequencies. Fig: Current response to sub- synchronous resonance
  • 17. Fig:(a)Sub-harmonic magnitudes Fig:(b)Sub-harmonic magnitude values (RMS). per phase.
  • 18. Relay Settings based on above results  Eg: The highest sub-harmonic current observed during the event was the 11th harmonic with a magnitude of 172 primary amps with a current transformer ratio of 400:1. The relay current inputs were 5A inputs. Fundamental current was observed to be 1300A with CT ratio of 400:1:  Nominal Ratio = (Highest Sub-Harmonic Current) = 172/400 (Nominal Current 1A or5A) 5A = 8% Set nominal ratio > 6%  Fundamental Ratio = (Highest Sub-Harmonic Current) (Fundamental Current ) = 172/400 =13.5% Set fundamental ratio > 10% 1300/400  TSHD Setting = √(I²(5hz)+ I²(6hz)+…………….+ I²(40hz) I(50hz)
  • 19. Operations/minute setting  The record in Fig (b) shows a captured value of total sub- harmonic distortion (TSHD) between 160% and 165%. Thus a TSHD setting greater than 100% would be appropriate.  In this case, a minimum of 30 op/min is required for any of the other sub-harmonic settings to take effect. Fig:(c) Sub-harmonic current relay setting.
  • 20. Conclusion  Thus it can be concluded sub-harmonics can create problems in the power system.  In addition, solutions were presented on how to mitigate sub- harmonic oscillations by describing the application of a sub- harmonic protection relay.  It is clearly depicted here that sub-harmonic relay provides diverse functionality and adequate protection functions to detect sub- harmonic frequencies. Some of the those features include:  Protect against sustained sub-harmonics in wind farm operations  Low cost and efficiently reliable with easy installation  Improved Overall Response Time
  • 21. References  IEEE Paper On APPLICATION OF A SUBHARMONIC PROTECTION RELAY by  Mark Peterson, P.E., René Midence, Joe Perez, P.E.,  www.erlphase.com  Ravindranath and Chander -Power System Protection and Switch Gear, New Age Publication  IET-Digital Library  IEEE Paper On New Microprocessor Based Relay to Monitor and Protect Power Systems Against Sub-Harmonics[November 2011]  Power System Protection 3 Application edited by The Electricity Training Association, Institution of Electrical Engineers