Study on the effect of Viscous Dampers
for RCC Frame Structure
Under the Guidance of
P.M.Biradar
Asst. Professor
B.L.D.E Association’s
Vachana Pitamaha Dr. P. G. Halakatti College of Engineering and
Technology, Vijayapur
Puneeth Sajjan
M.Tech IVth Sem
2BL14CSE10
Introduction
• From the past years and present records, the world has experienced number
of destroying earthquakes, causing in number of increase the loss of human
being due to structural collapse and severe damages to structure.
• Serious efforts have been undertaken to develop the structural control
concept into a workable technology and such devices are installed in
structures.
• The structural control system is usually classified by three method. The three
classes of structural control system are
1. Active Energy Dissipation,
2. Semi-Active Energy Dissipation.
3. Passive Energy Dissipation.
Dampers:- Dampers are the devices which are used to absorb or
dissipate the vibration caused by the earthquake to the structure and to
increase the damping and stiffness of the structure.
Types of dampers:-
1. Tuned mass damper (TMDs).
2. Tuned liquid mass damper (TLDs).
3. Friction damper.
4. Metallic damper.
5. Viscous damper.
6. Elasto plastic damper.
Tuned Mass Damper
Fig 1: Tuned Mass Damper in Structure Fig 2: Tuned Mass Damper
 Tuned mass damper is a system/device fixed in structure to diminish the
amplitude of mechanical vibrations and also known as a harmonic absorber.
Tuned Liquid Mass Damper
A tuned liquid mass damper is a device which consist of liquid slush tank
and liquid mass depth. This type of damper is highly non-linear and it is
dependent on frequency.
Friction Damper
A friction damper is a device which are used in the structure to
dissipate the vibration caused by earthquake hazards. In this damper there are
steel plates which are fixed with high strength bolts.
Metallic Damper
The metallic damper are the devices which are constructed with mild
steel plates. The energy is dissipated from the in-elastic deformations of
plate which are made up of mild steel.
VISCOUS DAMPER
• Viscous damper are the energy dissipation device. This type of damper are
very robust and they are used in both new and existing structure.
• Viscous dampers works in the presence of fluid which will flow through
orifice.
• When piston moves this forces the liquid to move from one chamber to
another generating the resisting force.
Objectives of the Project
1. To study the behaviour of the symmetrical plan of 8-story reinforced concrete
structure for gravity loads in ETABs 2015.
2. Modelling and analyse of the structure for static and dynamic analyses will be
carried out in ETABs 2015 as per IS 1893-2002, (Part 1).
3. Modelling and anlyse of the structure with addition of viscous damper is
carried out in ETABs 2015.
4. Comparative study will be done on displacement, story drift and story shear
for the model with and without viscous dampers.
Methodology
In this present study, the ETABs 2015 abbreviated as “Extended Three-dimensional
Analysis of Building system” software is used for modelling as well as analysis of the
structure. The symmetrical plan of reinforced concrete structure having 8-story is
considered. The structure without damper is modelled and analysed in ETABs 2015.
The model is assigned the class of gravity loads.
First the Earthquake loads as per IS1893-2002, Part1 is applied for structure
located in zone 3. And dynamic analyses i.e. Response spectrum method is carried out
for 5% damping and scale factor considered as per IS code in both X and Y directions.
To control the seismic response of the structure and to absorb or to transfer the
lateral loads of the structure, the viscous damper is provided. The viscous damper is
modelled in the ETABs software. And the parameters like displacement, storey drift and
storey shears are studied and will be presented in the report.
1. Application of dampers for vibration control of
structures: An overview
LITERATURE REVIEW
By: Vajreshwari Umachangi, Katta Venkataramana, G.R.Reddy, Rajeev
Verma
The author explains about the type of dampers which has become
most popular now a days for vibration control in the structure.
This paper presents a knowledge or introduction to the behaviour
of the damper in seismically affected areas in which the structures
are build.
The author conclude that in recent years, the use of seismic
or earthquake control system has been increased but it is very
important that selecting the appropriate damper and installing in
the structure to reduce the vibration in the structure.
By: SU MYAT AYE, DR. KYAW MOE AUNG
The author explain that, earthquake is one of the main natural
hazards in the world. The building which is used for the proposed study
is in Mandalay, Myanmar which comes in earthquake zone IV. The
structure is of 15 story RC structure which is L-shaped used for
residential purpose. The members of the structure are designed according
to ACI 318-99 and load considered according UBC-97. The model of the
structure is generated in ETABs v9.7.1 and analysed by using response
spectrum method is used for dynamic analysis. As to control the seismic
hazards of the building, the author took two types of damper 1. Viscous
fluid damper 2.viscoelastic damper. The mechanical properties of the
damper are taken by the manufacture’s report. The damper are applied to
the base story in X-direction. After the analysis the results are compared.
By comparing the result of the three cases of the proposed structure,
the author concluded that the viscous damper is the most effective for
decreasing the seismic response of the structure. According to the
obtained results, the viscous damper reduce the results upto 40% to 50%
but about viscoelastic damper it allows to reduce only 15% to 25% for all
parameters. Hence is concluded that adding dampers to the structure will
definitely reduce the seismic response of the structure.
YUVRAJ BISHT, SARASWATI SETIA
In this paper, the author studied about the behaviour of the viscous damper which are applied the
structure. He explains that, the use of the viscous damper in the structure will give in reducing the
seismic effect to the structure. The practice of this type damper is now cost effective and it will advance
the seismic act of existing as well as new buildings.
For study the author proposed or generated a five story RC structure with open ground story which
is used to analyse with and without viscous damper. The analysis is carried out in SAP 2000 which is
non-linear time history analysis. The model which is five story with open ground story is modelled. The
ground story is without masonry wall. Therefore the dampers is good to provide at ground story.
Because of less elasticity at the ground story which is absence of the masonry wall. The El Centro
earthquake data is considered for time history dynamic analysis. The dampers are provided in the
diagonal bracing at the ground story.
The model is analysed in SAP 2000 from those result the author come to
conclusion that If the damper are applied in the structure then this will definitely
reduce the seismic loading during earthquake. By providing viscous damper
there will be reduce in drift of 3.7% to 0.86% and increase in base shear of 0.8%
to 1.67%.
ABOUT THE VISCOUS DAMPER
History
During the period of cold war which is from the end of
World War II and approximate 1990. The missiles were
developed by both countries the US and Russia. While testing
of the missile, the shock and vibration produced should be
absorbed by the structure which are adjacent to the testing
site. To overcome that problem the dampers are provided in
the structure.
During the period of 1990’s, the use of damper become
very large i.e., it is used not only for military and defence
structure but also to the commercial structures. A New York
based company Taylor Devices, Inc. manufactured these type
device and produced in the market for all type of structure.
The Viscous dampers are passive energy dissipation device which
is added to structure to increase the effective stiffness of new and
existing buildings. They are very robust material and energy is
transferred by piston and absorbed or vanishes by silicone-based
fluid flowing between the piston-cylinder arrangements.
The damping force of viscous damper is given by
F=CVα
where,
F -The damping force.
C - The damping coefficient.
V - The velocity of piston.
α – The velocity exponent.
• The viscous damper works on the principle of flow of fluid
through the orifice in the chamber.
• The silicone-based fluid is used in the chamber. The piston
which is made up of stainless steel which travels in the
chamber which is filled by the silicone oil.
• The characteristic of the silicone oil is inert, non-flammable,
nontoxic and extremely stable for a period of long time.
• This difference in pressure between two chambers will force
the oil to flow through orifice in piston head. The inside
energy is transferred into heat which will dissipate into the
atmosphere.
WORKING PROCEDURE OF VISCOUS DAMPER
The three basic way to attach the damper to the building are:
1. Base isolation.
2. Damper for chevron bracing system.
3. Damper for diagonal bracing system.
Basic Way of Applying Damper
In this present study, the dampers are provided throughout the story in the corners
of the structure. The way of attachment of the damper is chevron brace type to the
structure. The elements of viscous damper is modelled in ETABs by assigning a panel
zone with non-linear link property to the mid-span point object where the chevrons
intersect the beams throughout the structure.
Advantages
1. At low displacement also these are activated.
2. It has minimal restoring force.
3. The properties largely frequency and temperature independent.
4. The performance in the military application has made the record.
Disadvantage
1. Leakage of fluid (reliability concern).
MODELLING AND ANALYSIS
In this present work, the structure of eight story’s is considered
which is of reinforced concert structure. The plan of the structure is
symmetrical plan, having the area of 20m X 20m. Each spacing of the
gridline is 5m on both side. The height of each story of the structure is
3m. the overall height f the structure is 24m. the frame of the structure is
modelled in ETABs software.
Grade of Concrete M 25
Modulus of Elasticity of Concrete (E) 25000 MPa
Grade of Steel Fe-415
Modulus of Elasticity of Steel (E) 200000 MPa
Density of Brick 20kN/m3
Poisson’s ratio 0.2
The material properties of the structure for modeling is considered as
below,
Beam 230mm X 450mm
Column 500mm X 500mm
Slab Thickness 150mm
Wall thickness 230mm
150mm
The sectional details like size of beam, column, slab and wall are
considered as below in the table.
Section Details of the Structure
Load Consideration
The model is generated in the software which should be consist of
loads. Loads which are considered for this work are
Dead load is a load which is self weight of structural element. The
dead load of the structural element like beam, column and slab is
calculated by the software directly. The dead load consist of floor finish
of 1.5kN/m2 and wall load of 230mm wall having a dead weight of 12
kN/m and 150mm wall having a weight of 7.8 kN/m.
Live load is a load which is not constant in its place. The live load of
3 kN/m2 is considered for the current project work as per IS 875-part II.
Seismic Zone Zone III
Importance Factor 1
Reduction Factor 5
Damping Ratio 5%
The seismic load is considered according to the Indian Standards
code IS 1893:2002. The load combination for the concrete frame
structure is considered as by default from the software which are
according to the IS 1893-2002.
Application of Viscous Damper and Its Properties
Damper is a device which is applied to the structure to reduce the seismic
effect of the structure. In ETABs the viscous damper element is assigned to the
structure in the form of chevron bracing through out the height of the structure at all
corners of the structure. A panel zone is defined at the mid point of the beam with
non linear link property. The chevron will intersect to the mid point of the beam
where the panel zone is assigned. In the panel zone, the beam-brace connectivity is
selected with non-linear behaviour in U2 direction for assigning the damper.
The properties of the Viscous Damper is considered as provided by the
manufacturing company Taylor Device Inc.,
Damping coefficient 810 kN-s/m
Velocity exponent 0.3
The stiffness value of the viscous damper is calculated by the
following formula by considering the force and displacement of the
bare structure.
Force = Stiffness * Displacement i.e., F=K*δ
50= K*(0.084/1000)
K = 5,95,238.0953 kN/m
RESULT AND DISCUSSION”
In the present study, viscous dampers are used to reduce the seismic effect
of the structure which are subjected to the earthquake load. The frames (with
and without viscous damper) is modelled according to the properties of the
structure which are explained in the work. Because of the symmetric model the
values in both direction will be same. The seismic behaviour of the Reinforced
Concrete structure is judged by observing the parameters such as
1. Displacement.
2. Story Drift.
3. Story Shear.
1. Displacement
Displacement is the parameter of maximum importance as it governs the
failure pattern of the structure.
Table : Displacement (mm)
Story
Elevation
(m)
Displacement (mm)
without
damper
with viscous
damper
8 24 29.63 10.73
7 21 28.22 9.70
6 18 25.87 8.39
5 15 22.57 6.87
4 12 18.42 5.22
3 9 13.53 3.52
2 6 8.14 1.86
1 3 2.92 0.46
Base 0 0 0
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
8 7 6 5 4 3 2 1 BASE
Displacement(mm)
Story Level
Displacement
without damper with viscous damper
2. Story Drift
As the number of story increases in the structure, the drift is the
common factor for multi-story building. The variance between the lateral
displacements of two adjacent floors of the structure is defined as the
story drift. Table 5.2: Story Drift (mm)
Story
Elevation
(m)
Story Drift (mm)
without
damper
with viscous
damper
8 24 0.00059 0.00035
7 21 0.00094 0.00045
6 18 0.00125 0.00052
5 15 0.00149 0.00056
4 12 0.00168 0.00057
3 9 0.00181 0.00055
2 6 0.00174 0.00047
1 3 0.00097 0.00015
0.00000
0.00020
0.00040
0.00060
0.00080
0.00100
0.00120
0.00140
0.00160
0.00180
0.00200
8 7 6 5 4 3 2 1 Base
StoryDrift(mm)
Story Level
Story Drift
without damper with viscous damper
From the above table and graph we can observe that:
1) The values of drift is more at middle story i.e., 2 to 5 story and less at top and bottom story.
2) The reduction in story drift at mid-stories of model with addition of viscous damper is 70% when
compared with bare model.
3) By applying damper to the structure there is reduction of about 60% to 80% in drift value at top and
bottom stories.
3. Story Shear (kN)
The story shear is the shear value obtained from the sum of design lateral
forces at the levels above the story consideration of the structure. The shear values of
the both models are below in the table.
Table: Story Shear (kN)
Story
Elevation
(m)
Story Shear
without
damper
with viscous
damper
8 24 288.26 293.36
7 21 571.35 623.03
6 18 758.14 881.01
5 15 891.75 1088.39
4 12 1007.25 1254.22
3 9 1124.19 1381.26
2 6 1232.17 1463.58
1 3 1291.18 1487.82
Base 0 0 0
From the below graph,
1. By observing that the values of model with damper is little bit more as compared to without
damper model.
2. The value of the story shear has been linearly decreasing as height of the story increases.
0.00
200.00
400.00
600.00
800.00
1000.00
1200.00
1400.00
1600.00
8 7 6 5 4 3 2 1 BASE
StoryShear(kN)
Story Level
Story Shear(kN)
without damper with viscous damper
CONCLUSION
After the analyses of structure the results obtained and compared. And the
conclusion are as follows,
1. According to the obtained results, viscous damper in structure results in the
decrease of building displacement and building drift.
2. The bare frame model which is without damper is analysed and obtained the
results of displacement as 29.63mm and story drift as 0.00181mm.
3. The results obtained from the model with addition of viscous damper are
displacement as 10.73mm and story drift as 0.00055mm.
4. By observing, the displacement values increases over the height of the
structure.
5. From the comparison, the displacement value of the structure is reduced
about 60% to 85% when viscous dampers are applied to the structure.
6. With the placement of viscous damper into the structure maximum drift
reduces in the structure during seismic loading.
7. By using viscous damper in the structure, the story drift at mid-stories is
reduced by 70% when compared with bare model.
8. By applying viscous damper to the structure there is reduction of about 60%
to 80% in drift value at top and bottom stories.
9. The base shear value of bare frame model is 1291.18 kN and that to model
with viscous damper is 1487.82 kN.
10. By observing the shear value, the difference is less because of the weight
of the damper provided to the structure.
11. From the study, by applying viscous dampers to the structure its behaviour
change under seismic loading.
12. By observing, these viscous damper devices perform a vital role in reducing
and controlling the seismic response of the structure.
REFERENCE:
1) Vajreshwari Umachagi, Katta Venkataramana, G. R. Reddy, Rajeev Verma, “Applications of
Dampers for Vibration Control Of Structures: An Overview” International Journal of
Research in Engineering and Technology, Nov-2013.
2) Liya Mathew & C. Prabha, “Effect of Fluid Viscous Dampers in Multi-Storeyed Buildings”,
International Journal of Research in Engineering & Technology, Vol. 2, Issue 9, Sep 2014, 55-
60.
3) Su Myat Aye, Dr. Kyaw Moe Aung, “Comparative Study on Seismic Response of RC
Structure Using Viscous Dampers and Viscoelastic Dampers”, International Journal Of
Scientific Engineering And Technology Research, Vol.03, Issue.08, May-2014, Pages:1468-
1478.
4) Mohammad Javad Dehghan, Mostafa Soleymannejad, “Improving Seismic Performance of
Concrete Buildings with Special Moment Frames Using Viscous Damper”, International
Journal of Modern Engineering Research, Vol. 5, Issue. 7, July 2015.
5) Yuvraj Bisht, Saraswati Setia, “Seismic Behaviour Of A Soft Storey Building With & Without
Viscous Dampers”, International Journal of Engineering Research and Applications (IJERA)
ISSN: 2248-9622, pg. no 10-15
6) V. Sadeghi Balkanlou, M. Reza Bagerzadeh Karimi, B. Bagheri Azar And Alaeddin
Behravesh, “Evaluating Effects of Viscous Dampers on optimizing Seismic Behaviour of
Structures”, International Journal of Current Engineering and Technology,Vol.3, No.4
(October 2013), pg.no 1150-1157.
7) Douglas Taylor, President, Taylor Devices Inc., “History, Design and Application of Fluid
Dampers in Structural engineering”
8) Godhat Kishan J. and Yashwantsinh Zala, “A Review on Effect of Actual Site Specific
Response Analysis of Tall Building with Viscous Damper”, International Journal of Trend in
Research and Development, Volume 2(6), Nov - Dec 2015, pg.no.298-302.
9) The manufacturer of the Viscous Damper product Taylor Devices Inc., India.
10) Lee. D., and Taylor. D. P, “Viscous damper development and future trends”, Struct., Des., Tall
Build, vol-10(5), 2001, pg.no-(311–320).
11) Alireza Heysami, “Types of Dampers and their Seismic Performance during an Earthquake”,
Current World Environment, Vol. 10(Special Issue 1), 1002-1015 (2015).
12) Dharmesh Chandnani, Riddhi Joshi, Kumarpal Trivedi, “Characteristics & Applications of
Different Types of Dampers as Seismic Energy Dissipater”, International Journal of
Computer Science and Network, Volume 5, Issue 2, April 2016 pg.no (369-372).
13) Jenn-Shin Hwang, Chun-Hsiang Tsai, Shiang-Jung Wang, Yin-Nan Huang, “Experimental
study of RC building structures with supplemental viscous dampers and lightly reinforced
walls”, Engineering Structures, accepted 6 March 2006, pg.no (1-9), at 2006 Elsevier Ltd.
THANK YOU

More Related Content

What's hot

Connection and Bracing
Connection and BracingConnection and Bracing
Connection and Bracingsuddal
 
Seismic retrofitting techniques & rehabilitation
Seismic retrofitting techniques & rehabilitationSeismic retrofitting techniques & rehabilitation
Seismic retrofitting techniques & rehabilitationShuvam Sarkar
 
Seismic Analysis
Seismic AnalysisSeismic Analysis
Seismic AnalysisKrishnagnr
 
Response Spectrum
Response SpectrumResponse Spectrum
Response SpectrumTeja Ande
 
Advantages and types of prestressing
Advantages and types of prestressingAdvantages and types of prestressing
Advantages and types of prestressingSaurav Chaudhary
 
Retrofitting of concrete structure
Retrofitting of concrete structureRetrofitting of concrete structure
Retrofitting of concrete structureshlok patel
 
REINFORCEMENT CONCRETE chapter 1
REINFORCEMENT CONCRETE chapter 1REINFORCEMENT CONCRETE chapter 1
REINFORCEMENT CONCRETE chapter 1Natalie Ulza
 
Seismic retrofitting techniques
Seismic retrofitting techniquesSeismic retrofitting techniques
Seismic retrofitting techniquesghildiyal8811
 
CE 72.32 (January 2016 Semester): Lecture 1a - Overview of Tall Buildings
CE 72.32 (January 2016 Semester): Lecture 1a - Overview of Tall BuildingsCE 72.32 (January 2016 Semester): Lecture 1a - Overview of Tall Buildings
CE 72.32 (January 2016 Semester): Lecture 1a - Overview of Tall BuildingsFawad Najam
 
Redistribution of moments-Part-1
Redistribution of moments-Part-1Redistribution of moments-Part-1
Redistribution of moments-Part-1Subhash Patankar
 
Earthquake resistant structure
Earthquake resistant structureEarthquake resistant structure
Earthquake resistant structureVikrant Sabat
 
Infilled frame,a type of tubular frame structural system
Infilled frame,a type of tubular frame structural systemInfilled frame,a type of tubular frame structural system
Infilled frame,a type of tubular frame structural systemMUSTAFEEZ UR RAHMAN
 
Precast construction
Precast constructionPrecast construction
Precast constructionDivya Vishnoi
 
Design of columns axial load as per IS 456-2000
Design of columns  axial load as per IS 456-2000Design of columns  axial load as per IS 456-2000
Design of columns axial load as per IS 456-2000PraveenKumar Shanmugam
 

What's hot (20)

Shear wall ppt
Shear wall ppt Shear wall ppt
Shear wall ppt
 
Connection and Bracing
Connection and BracingConnection and Bracing
Connection and Bracing
 
Seismic retrofitting techniques & rehabilitation
Seismic retrofitting techniques & rehabilitationSeismic retrofitting techniques & rehabilitation
Seismic retrofitting techniques & rehabilitation
 
Seismic Analysis
Seismic AnalysisSeismic Analysis
Seismic Analysis
 
Shear walls
Shear wallsShear walls
Shear walls
 
Rcc jacketing
Rcc jacketingRcc jacketing
Rcc jacketing
 
Response Spectrum
Response SpectrumResponse Spectrum
Response Spectrum
 
Advantages and types of prestressing
Advantages and types of prestressingAdvantages and types of prestressing
Advantages and types of prestressing
 
Retrofitting of concrete structure
Retrofitting of concrete structureRetrofitting of concrete structure
Retrofitting of concrete structure
 
REINFORCEMENT CONCRETE chapter 1
REINFORCEMENT CONCRETE chapter 1REINFORCEMENT CONCRETE chapter 1
REINFORCEMENT CONCRETE chapter 1
 
Seismic retrofitting techniques
Seismic retrofitting techniquesSeismic retrofitting techniques
Seismic retrofitting techniques
 
CE 72.32 (January 2016 Semester): Lecture 1a - Overview of Tall Buildings
CE 72.32 (January 2016 Semester): Lecture 1a - Overview of Tall BuildingsCE 72.32 (January 2016 Semester): Lecture 1a - Overview of Tall Buildings
CE 72.32 (January 2016 Semester): Lecture 1a - Overview of Tall Buildings
 
TALL BUILDINGS
TALL BUILDINGSTALL BUILDINGS
TALL BUILDINGS
 
Redistribution of moments-Part-1
Redistribution of moments-Part-1Redistribution of moments-Part-1
Redistribution of moments-Part-1
 
Earthquake resistant structure
Earthquake resistant structureEarthquake resistant structure
Earthquake resistant structure
 
Shear walls
Shear wallsShear walls
Shear walls
 
Load analysis and structural consideration
Load analysis and structural considerationLoad analysis and structural consideration
Load analysis and structural consideration
 
Infilled frame,a type of tubular frame structural system
Infilled frame,a type of tubular frame structural systemInfilled frame,a type of tubular frame structural system
Infilled frame,a type of tubular frame structural system
 
Precast construction
Precast constructionPrecast construction
Precast construction
 
Design of columns axial load as per IS 456-2000
Design of columns  axial load as per IS 456-2000Design of columns  axial load as per IS 456-2000
Design of columns axial load as per IS 456-2000
 

Viewers also liked

Seismic performance of adjacent building using fluid viscous dampers
Seismic performance of adjacent building using fluid viscous dampersSeismic performance of adjacent building using fluid viscous dampers
Seismic performance of adjacent building using fluid viscous dampersAyaz Malik
 
Frame Structures including sap2000
Frame Structures including sap2000Frame Structures including sap2000
Frame Structures including sap2000Wolfgang Schueller
 
Earthquake resistant structure
Earthquake resistant structureEarthquake resistant structure
Earthquake resistant structurevikskyn
 
Seismic performance of structure with fixed base, base isolated structure and...
Seismic performance of structure with fixed base, base isolated structure and...Seismic performance of structure with fixed base, base isolated structure and...
Seismic performance of structure with fixed base, base isolated structure and...eSAT Journals
 
Vibration and damping
Vibration and dampingVibration and damping
Vibration and dampingDivya Lattoo
 
Earthquake resistant construction
Earthquake resistant constructionEarthquake resistant construction
Earthquake resistant constructionHarsh Jain
 
Earthquake resistant buildings in india
Earthquake resistant buildings in indiaEarthquake resistant buildings in india
Earthquake resistant buildings in indiaViva Bella Interiors
 
Fundamentals of sdh
Fundamentals of sdhFundamentals of sdh
Fundamentals of sdhsreejithkt
 
STRUCTURAL RESPONSE CONTROL OF RCC MOMENT RESISTING FRAME USING FLUID VISCOUS...
STRUCTURAL RESPONSE CONTROL OF RCC MOMENT RESISTING FRAME USING FLUID VISCOUS...STRUCTURAL RESPONSE CONTROL OF RCC MOMENT RESISTING FRAME USING FLUID VISCOUS...
STRUCTURAL RESPONSE CONTROL OF RCC MOMENT RESISTING FRAME USING FLUID VISCOUS...IAEME Publication
 
Technical writing on earthquake sustainable building using Fluid Viscous Damper
Technical writing on earthquake sustainable building using Fluid Viscous DamperTechnical writing on earthquake sustainable building using Fluid Viscous Damper
Technical writing on earthquake sustainable building using Fluid Viscous DamperRakibul Hasan
 
Anti seismic devices
Anti seismic devices Anti seismic devices
Anti seismic devices EUROPAGES
 
Qcl 14-v3 pareto-diagram_bansthali_univercity_astha_srivastava
Qcl 14-v3 pareto-diagram_bansthali_univercity_astha_srivastavaQcl 14-v3 pareto-diagram_bansthali_univercity_astha_srivastava
Qcl 14-v3 pareto-diagram_bansthali_univercity_astha_srivastavaAstha811
 
Applications of dampers for vibration control of structures an overview
Applications of dampers for vibration control of structures   an overviewApplications of dampers for vibration control of structures   an overview
Applications of dampers for vibration control of structures an overvieweSAT Journals
 
Presentation in the Franhoufer IIS about my thesis: A wavelet transform based...
Presentation in the Franhoufer IIS about my thesis: A wavelet transform based...Presentation in the Franhoufer IIS about my thesis: A wavelet transform based...
Presentation in the Franhoufer IIS about my thesis: A wavelet transform based...Pedro Cerón Colás
 
EXPERIMENTAL INVESTIGATION OF A DI DIESEL ENGINE USING TYRE PYROLYSIS OIL-DIE...
EXPERIMENTAL INVESTIGATION OF A DI DIESEL ENGINE USING TYRE PYROLYSIS OIL-DIE...EXPERIMENTAL INVESTIGATION OF A DI DIESEL ENGINE USING TYRE PYROLYSIS OIL-DIE...
EXPERIMENTAL INVESTIGATION OF A DI DIESEL ENGINE USING TYRE PYROLYSIS OIL-DIE...IAEME Publication
 
Effect of damper on sesmic demand ond diffrent soil with help of staad
Effect of damper on sesmic demand ond diffrent  soil with help of staadEffect of damper on sesmic demand ond diffrent  soil with help of staad
Effect of damper on sesmic demand ond diffrent soil with help of staadPushkar Kokane
 
Analitical and Experimental Studies to Reduce Seismic Vibratioin in Critical ...
Analitical and Experimental Studies to Reduce Seismic Vibratioin in Critical ...Analitical and Experimental Studies to Reduce Seismic Vibratioin in Critical ...
Analitical and Experimental Studies to Reduce Seismic Vibratioin in Critical ...Global Risk Forum GRFDavos
 
Qcl 14-v3 [pareto diagram]-[banathali_university]_[suyashi_rastogi]
Qcl 14-v3 [pareto diagram]-[banathali_university]_[suyashi_rastogi]Qcl 14-v3 [pareto diagram]-[banathali_university]_[suyashi_rastogi]
Qcl 14-v3 [pareto diagram]-[banathali_university]_[suyashi_rastogi]Suyashi Rastogi
 

Viewers also liked (20)

Seismic performance of adjacent building using fluid viscous dampers
Seismic performance of adjacent building using fluid viscous dampersSeismic performance of adjacent building using fluid viscous dampers
Seismic performance of adjacent building using fluid viscous dampers
 
Frame Structures including sap2000
Frame Structures including sap2000Frame Structures including sap2000
Frame Structures including sap2000
 
Earthquake resistant structure
Earthquake resistant structureEarthquake resistant structure
Earthquake resistant structure
 
Seismic performance of structure with fixed base, base isolated structure and...
Seismic performance of structure with fixed base, base isolated structure and...Seismic performance of structure with fixed base, base isolated structure and...
Seismic performance of structure with fixed base, base isolated structure and...
 
Vibration and damping
Vibration and dampingVibration and damping
Vibration and damping
 
SDH Frame Structure
SDH Frame StructureSDH Frame Structure
SDH Frame Structure
 
Earthquake resistant construction
Earthquake resistant constructionEarthquake resistant construction
Earthquake resistant construction
 
Earthquake resistant buildings in india
Earthquake resistant buildings in indiaEarthquake resistant buildings in india
Earthquake resistant buildings in india
 
Fundamentals of sdh
Fundamentals of sdhFundamentals of sdh
Fundamentals of sdh
 
Types of structures
Types of structuresTypes of structures
Types of structures
 
STRUCTURAL RESPONSE CONTROL OF RCC MOMENT RESISTING FRAME USING FLUID VISCOUS...
STRUCTURAL RESPONSE CONTROL OF RCC MOMENT RESISTING FRAME USING FLUID VISCOUS...STRUCTURAL RESPONSE CONTROL OF RCC MOMENT RESISTING FRAME USING FLUID VISCOUS...
STRUCTURAL RESPONSE CONTROL OF RCC MOMENT RESISTING FRAME USING FLUID VISCOUS...
 
Technical writing on earthquake sustainable building using Fluid Viscous Damper
Technical writing on earthquake sustainable building using Fluid Viscous DamperTechnical writing on earthquake sustainable building using Fluid Viscous Damper
Technical writing on earthquake sustainable building using Fluid Viscous Damper
 
Anti seismic devices
Anti seismic devices Anti seismic devices
Anti seismic devices
 
Qcl 14-v3 pareto-diagram_bansthali_univercity_astha_srivastava
Qcl 14-v3 pareto-diagram_bansthali_univercity_astha_srivastavaQcl 14-v3 pareto-diagram_bansthali_univercity_astha_srivastava
Qcl 14-v3 pareto-diagram_bansthali_univercity_astha_srivastava
 
Applications of dampers for vibration control of structures an overview
Applications of dampers for vibration control of structures   an overviewApplications of dampers for vibration control of structures   an overview
Applications of dampers for vibration control of structures an overview
 
Presentation in the Franhoufer IIS about my thesis: A wavelet transform based...
Presentation in the Franhoufer IIS about my thesis: A wavelet transform based...Presentation in the Franhoufer IIS about my thesis: A wavelet transform based...
Presentation in the Franhoufer IIS about my thesis: A wavelet transform based...
 
EXPERIMENTAL INVESTIGATION OF A DI DIESEL ENGINE USING TYRE PYROLYSIS OIL-DIE...
EXPERIMENTAL INVESTIGATION OF A DI DIESEL ENGINE USING TYRE PYROLYSIS OIL-DIE...EXPERIMENTAL INVESTIGATION OF A DI DIESEL ENGINE USING TYRE PYROLYSIS OIL-DIE...
EXPERIMENTAL INVESTIGATION OF A DI DIESEL ENGINE USING TYRE PYROLYSIS OIL-DIE...
 
Effect of damper on sesmic demand ond diffrent soil with help of staad
Effect of damper on sesmic demand ond diffrent  soil with help of staadEffect of damper on sesmic demand ond diffrent  soil with help of staad
Effect of damper on sesmic demand ond diffrent soil with help of staad
 
Analitical and Experimental Studies to Reduce Seismic Vibratioin in Critical ...
Analitical and Experimental Studies to Reduce Seismic Vibratioin in Critical ...Analitical and Experimental Studies to Reduce Seismic Vibratioin in Critical ...
Analitical and Experimental Studies to Reduce Seismic Vibratioin in Critical ...
 
Qcl 14-v3 [pareto diagram]-[banathali_university]_[suyashi_rastogi]
Qcl 14-v3 [pareto diagram]-[banathali_university]_[suyashi_rastogi]Qcl 14-v3 [pareto diagram]-[banathali_university]_[suyashi_rastogi]
Qcl 14-v3 [pareto diagram]-[banathali_university]_[suyashi_rastogi]
 

Similar to Study on the effect of viscous dampers for RCC frame Structure

Analysis of Moment Resisting Reinforced Concrete Frames for Seismic Response ...
Analysis of Moment Resisting Reinforced Concrete Frames for Seismic Response ...Analysis of Moment Resisting Reinforced Concrete Frames for Seismic Response ...
Analysis of Moment Resisting Reinforced Concrete Frames for Seismic Response ...IRJET Journal
 
IRJET- Structural Analysis of Seismic Friction Dampers
IRJET-  	  Structural Analysis of Seismic Friction DampersIRJET-  	  Structural Analysis of Seismic Friction Dampers
IRJET- Structural Analysis of Seismic Friction DampersIRJET Journal
 
IRJET- A Review of Seismic Analysis of Different Shape of RC Building by usin...
IRJET- A Review of Seismic Analysis of Different Shape of RC Building by usin...IRJET- A Review of Seismic Analysis of Different Shape of RC Building by usin...
IRJET- A Review of Seismic Analysis of Different Shape of RC Building by usin...IRJET Journal
 
IRJET- Comparative Analysis of Effects of Base Isolator & Fluid Viscous Dampe...
IRJET- Comparative Analysis of Effects of Base Isolator & Fluid Viscous Dampe...IRJET- Comparative Analysis of Effects of Base Isolator & Fluid Viscous Dampe...
IRJET- Comparative Analysis of Effects of Base Isolator & Fluid Viscous Dampe...IRJET Journal
 
IRJET- Performance Analysis of High Rise RCC Frame Structure using Various Ty...
IRJET- Performance Analysis of High Rise RCC Frame Structure using Various Ty...IRJET- Performance Analysis of High Rise RCC Frame Structure using Various Ty...
IRJET- Performance Analysis of High Rise RCC Frame Structure using Various Ty...IRJET Journal
 
DESIGN AND ANALYSIS OF CURVED BEAM WITH DIFFERENT OPENINGS
DESIGN AND ANALYSIS OF CURVED BEAM WITH DIFFERENT OPENINGSDESIGN AND ANALYSIS OF CURVED BEAM WITH DIFFERENT OPENINGS
DESIGN AND ANALYSIS OF CURVED BEAM WITH DIFFERENT OPENINGSIRJET Journal
 
Strengthening of R.C Framed Structure Using Energy Dissipating Devices
Strengthening of R.C Framed Structure Using Energy Dissipating DevicesStrengthening of R.C Framed Structure Using Energy Dissipating Devices
Strengthening of R.C Framed Structure Using Energy Dissipating Devicespaperpublications3
 
Seismic Analysis of Multi Storey RC Building with and Without Fluid Viscous D...
Seismic Analysis of Multi Storey RC Building with and Without Fluid Viscous D...Seismic Analysis of Multi Storey RC Building with and Without Fluid Viscous D...
Seismic Analysis of Multi Storey RC Building with and Without Fluid Viscous D...ijtsrd
 
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...IRJET Journal
 
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...IRJET Journal
 
IRJET- A Review on Seismic Analysis of Buildings using Passive Energy Dis...
IRJET-  	  A Review on Seismic Analysis of Buildings using Passive Energy Dis...IRJET-  	  A Review on Seismic Analysis of Buildings using Passive Energy Dis...
IRJET- A Review on Seismic Analysis of Buildings using Passive Energy Dis...IRJET Journal
 
Review on Viscoelastic Materials used in Viscoelastic Dampers
Review on Viscoelastic Materials used in Viscoelastic DampersReview on Viscoelastic Materials used in Viscoelastic Dampers
Review on Viscoelastic Materials used in Viscoelastic DampersIRJET Journal
 
IRJET- Seismic Performance Evaluation of RC Building Connected with and witho...
IRJET- Seismic Performance Evaluation of RC Building Connected with and witho...IRJET- Seismic Performance Evaluation of RC Building Connected with and witho...
IRJET- Seismic Performance Evaluation of RC Building Connected with and witho...IRJET Journal
 
IRJET- A Review of Seismic Behaviour of Multi-Story Building using various En...
IRJET- A Review of Seismic Behaviour of Multi-Story Building using various En...IRJET- A Review of Seismic Behaviour of Multi-Story Building using various En...
IRJET- A Review of Seismic Behaviour of Multi-Story Building using various En...IRJET Journal
 
Seismic Analysis of Framed R.C. Structure with Base Isolation Technique using...
Seismic Analysis of Framed R.C. Structure with Base Isolation Technique using...Seismic Analysis of Framed R.C. Structure with Base Isolation Technique using...
Seismic Analysis of Framed R.C. Structure with Base Isolation Technique using...ijtsrd
 
Study About Seismic Device Dampers: A review
Study About Seismic Device Dampers: A reviewStudy About Seismic Device Dampers: A review
Study About Seismic Device Dampers: A reviewIRJET Journal
 
Analysis and Design of RCC Building Retrofitted by Accordion Metallic Damper
Analysis and Design of RCC Building Retrofitted by Accordion Metallic DamperAnalysis and Design of RCC Building Retrofitted by Accordion Metallic Damper
Analysis and Design of RCC Building Retrofitted by Accordion Metallic DamperIRJET Journal
 
Modelling Visco-elastic material for Building structure
Modelling Visco-elastic material for Building structureModelling Visco-elastic material for Building structure
Modelling Visco-elastic material for Building structureDigvijay Gaikwad
 

Similar to Study on the effect of viscous dampers for RCC frame Structure (20)

Analysis of Moment Resisting Reinforced Concrete Frames for Seismic Response ...
Analysis of Moment Resisting Reinforced Concrete Frames for Seismic Response ...Analysis of Moment Resisting Reinforced Concrete Frames for Seismic Response ...
Analysis of Moment Resisting Reinforced Concrete Frames for Seismic Response ...
 
IRJET- Structural Analysis of Seismic Friction Dampers
IRJET-  	  Structural Analysis of Seismic Friction DampersIRJET-  	  Structural Analysis of Seismic Friction Dampers
IRJET- Structural Analysis of Seismic Friction Dampers
 
IRJET- A Review of Seismic Analysis of Different Shape of RC Building by usin...
IRJET- A Review of Seismic Analysis of Different Shape of RC Building by usin...IRJET- A Review of Seismic Analysis of Different Shape of RC Building by usin...
IRJET- A Review of Seismic Analysis of Different Shape of RC Building by usin...
 
IRJET- Comparative Analysis of Effects of Base Isolator & Fluid Viscous Dampe...
IRJET- Comparative Analysis of Effects of Base Isolator & Fluid Viscous Dampe...IRJET- Comparative Analysis of Effects of Base Isolator & Fluid Viscous Dampe...
IRJET- Comparative Analysis of Effects of Base Isolator & Fluid Viscous Dampe...
 
IRJET- Performance Analysis of High Rise RCC Frame Structure using Various Ty...
IRJET- Performance Analysis of High Rise RCC Frame Structure using Various Ty...IRJET- Performance Analysis of High Rise RCC Frame Structure using Various Ty...
IRJET- Performance Analysis of High Rise RCC Frame Structure using Various Ty...
 
DESIGN AND ANALYSIS OF CURVED BEAM WITH DIFFERENT OPENINGS
DESIGN AND ANALYSIS OF CURVED BEAM WITH DIFFERENT OPENINGSDESIGN AND ANALYSIS OF CURVED BEAM WITH DIFFERENT OPENINGS
DESIGN AND ANALYSIS OF CURVED BEAM WITH DIFFERENT OPENINGS
 
Strengthening of R.C Framed Structure Using Energy Dissipating Devices
Strengthening of R.C Framed Structure Using Energy Dissipating DevicesStrengthening of R.C Framed Structure Using Energy Dissipating Devices
Strengthening of R.C Framed Structure Using Energy Dissipating Devices
 
Seismic Analysis of Multi Storey RC Building with and Without Fluid Viscous D...
Seismic Analysis of Multi Storey RC Building with and Without Fluid Viscous D...Seismic Analysis of Multi Storey RC Building with and Without Fluid Viscous D...
Seismic Analysis of Multi Storey RC Building with and Without Fluid Viscous D...
 
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...
 
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...
 
IRJET- A Review on Seismic Analysis of Buildings using Passive Energy Dis...
IRJET-  	  A Review on Seismic Analysis of Buildings using Passive Energy Dis...IRJET-  	  A Review on Seismic Analysis of Buildings using Passive Energy Dis...
IRJET- A Review on Seismic Analysis of Buildings using Passive Energy Dis...
 
Review on Viscoelastic Materials used in Viscoelastic Dampers
Review on Viscoelastic Materials used in Viscoelastic DampersReview on Viscoelastic Materials used in Viscoelastic Dampers
Review on Viscoelastic Materials used in Viscoelastic Dampers
 
IRJET- Seismic Performance Evaluation of RC Building Connected with and witho...
IRJET- Seismic Performance Evaluation of RC Building Connected with and witho...IRJET- Seismic Performance Evaluation of RC Building Connected with and witho...
IRJET- Seismic Performance Evaluation of RC Building Connected with and witho...
 
IRJET- A Review of Seismic Behaviour of Multi-Story Building using various En...
IRJET- A Review of Seismic Behaviour of Multi-Story Building using various En...IRJET- A Review of Seismic Behaviour of Multi-Story Building using various En...
IRJET- A Review of Seismic Behaviour of Multi-Story Building using various En...
 
Seismic Analysis of Framed R.C. Structure with Base Isolation Technique using...
Seismic Analysis of Framed R.C. Structure with Base Isolation Technique using...Seismic Analysis of Framed R.C. Structure with Base Isolation Technique using...
Seismic Analysis of Framed R.C. Structure with Base Isolation Technique using...
 
research paper draft 2
research paper draft 2research paper draft 2
research paper draft 2
 
Study About Seismic Device Dampers: A review
Study About Seismic Device Dampers: A reviewStudy About Seismic Device Dampers: A review
Study About Seismic Device Dampers: A review
 
Analysis and Design of RCC Building Retrofitted by Accordion Metallic Damper
Analysis and Design of RCC Building Retrofitted by Accordion Metallic DamperAnalysis and Design of RCC Building Retrofitted by Accordion Metallic Damper
Analysis and Design of RCC Building Retrofitted by Accordion Metallic Damper
 
Synopsis tit
Synopsis titSynopsis tit
Synopsis tit
 
Modelling Visco-elastic material for Building structure
Modelling Visco-elastic material for Building structureModelling Visco-elastic material for Building structure
Modelling Visco-elastic material for Building structure
 

Recently uploaded

(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 

Recently uploaded (20)

(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 

Study on the effect of viscous dampers for RCC frame Structure

  • 1. Study on the effect of Viscous Dampers for RCC Frame Structure Under the Guidance of P.M.Biradar Asst. Professor B.L.D.E Association’s Vachana Pitamaha Dr. P. G. Halakatti College of Engineering and Technology, Vijayapur Puneeth Sajjan M.Tech IVth Sem 2BL14CSE10
  • 2. Introduction • From the past years and present records, the world has experienced number of destroying earthquakes, causing in number of increase the loss of human being due to structural collapse and severe damages to structure. • Serious efforts have been undertaken to develop the structural control concept into a workable technology and such devices are installed in structures. • The structural control system is usually classified by three method. The three classes of structural control system are 1. Active Energy Dissipation, 2. Semi-Active Energy Dissipation. 3. Passive Energy Dissipation.
  • 3. Dampers:- Dampers are the devices which are used to absorb or dissipate the vibration caused by the earthquake to the structure and to increase the damping and stiffness of the structure. Types of dampers:- 1. Tuned mass damper (TMDs). 2. Tuned liquid mass damper (TLDs). 3. Friction damper. 4. Metallic damper. 5. Viscous damper. 6. Elasto plastic damper.
  • 4. Tuned Mass Damper Fig 1: Tuned Mass Damper in Structure Fig 2: Tuned Mass Damper  Tuned mass damper is a system/device fixed in structure to diminish the amplitude of mechanical vibrations and also known as a harmonic absorber.
  • 5. Tuned Liquid Mass Damper A tuned liquid mass damper is a device which consist of liquid slush tank and liquid mass depth. This type of damper is highly non-linear and it is dependent on frequency.
  • 6. Friction Damper A friction damper is a device which are used in the structure to dissipate the vibration caused by earthquake hazards. In this damper there are steel plates which are fixed with high strength bolts.
  • 7. Metallic Damper The metallic damper are the devices which are constructed with mild steel plates. The energy is dissipated from the in-elastic deformations of plate which are made up of mild steel.
  • 8. VISCOUS DAMPER • Viscous damper are the energy dissipation device. This type of damper are very robust and they are used in both new and existing structure. • Viscous dampers works in the presence of fluid which will flow through orifice. • When piston moves this forces the liquid to move from one chamber to another generating the resisting force.
  • 9. Objectives of the Project 1. To study the behaviour of the symmetrical plan of 8-story reinforced concrete structure for gravity loads in ETABs 2015. 2. Modelling and analyse of the structure for static and dynamic analyses will be carried out in ETABs 2015 as per IS 1893-2002, (Part 1). 3. Modelling and anlyse of the structure with addition of viscous damper is carried out in ETABs 2015. 4. Comparative study will be done on displacement, story drift and story shear for the model with and without viscous dampers.
  • 10. Methodology In this present study, the ETABs 2015 abbreviated as “Extended Three-dimensional Analysis of Building system” software is used for modelling as well as analysis of the structure. The symmetrical plan of reinforced concrete structure having 8-story is considered. The structure without damper is modelled and analysed in ETABs 2015. The model is assigned the class of gravity loads. First the Earthquake loads as per IS1893-2002, Part1 is applied for structure located in zone 3. And dynamic analyses i.e. Response spectrum method is carried out for 5% damping and scale factor considered as per IS code in both X and Y directions. To control the seismic response of the structure and to absorb or to transfer the lateral loads of the structure, the viscous damper is provided. The viscous damper is modelled in the ETABs software. And the parameters like displacement, storey drift and storey shears are studied and will be presented in the report.
  • 11. 1. Application of dampers for vibration control of structures: An overview LITERATURE REVIEW By: Vajreshwari Umachangi, Katta Venkataramana, G.R.Reddy, Rajeev Verma The author explains about the type of dampers which has become most popular now a days for vibration control in the structure. This paper presents a knowledge or introduction to the behaviour of the damper in seismically affected areas in which the structures are build. The author conclude that in recent years, the use of seismic or earthquake control system has been increased but it is very important that selecting the appropriate damper and installing in the structure to reduce the vibration in the structure.
  • 12. By: SU MYAT AYE, DR. KYAW MOE AUNG The author explain that, earthquake is one of the main natural hazards in the world. The building which is used for the proposed study is in Mandalay, Myanmar which comes in earthquake zone IV. The structure is of 15 story RC structure which is L-shaped used for residential purpose. The members of the structure are designed according to ACI 318-99 and load considered according UBC-97. The model of the structure is generated in ETABs v9.7.1 and analysed by using response spectrum method is used for dynamic analysis. As to control the seismic hazards of the building, the author took two types of damper 1. Viscous fluid damper 2.viscoelastic damper. The mechanical properties of the damper are taken by the manufacture’s report. The damper are applied to the base story in X-direction. After the analysis the results are compared.
  • 13. By comparing the result of the three cases of the proposed structure, the author concluded that the viscous damper is the most effective for decreasing the seismic response of the structure. According to the obtained results, the viscous damper reduce the results upto 40% to 50% but about viscoelastic damper it allows to reduce only 15% to 25% for all parameters. Hence is concluded that adding dampers to the structure will definitely reduce the seismic response of the structure.
  • 14. YUVRAJ BISHT, SARASWATI SETIA In this paper, the author studied about the behaviour of the viscous damper which are applied the structure. He explains that, the use of the viscous damper in the structure will give in reducing the seismic effect to the structure. The practice of this type damper is now cost effective and it will advance the seismic act of existing as well as new buildings. For study the author proposed or generated a five story RC structure with open ground story which is used to analyse with and without viscous damper. The analysis is carried out in SAP 2000 which is non-linear time history analysis. The model which is five story with open ground story is modelled. The ground story is without masonry wall. Therefore the dampers is good to provide at ground story. Because of less elasticity at the ground story which is absence of the masonry wall. The El Centro earthquake data is considered for time history dynamic analysis. The dampers are provided in the diagonal bracing at the ground story.
  • 15. The model is analysed in SAP 2000 from those result the author come to conclusion that If the damper are applied in the structure then this will definitely reduce the seismic loading during earthquake. By providing viscous damper there will be reduce in drift of 3.7% to 0.86% and increase in base shear of 0.8% to 1.67%.
  • 16. ABOUT THE VISCOUS DAMPER History During the period of cold war which is from the end of World War II and approximate 1990. The missiles were developed by both countries the US and Russia. While testing of the missile, the shock and vibration produced should be absorbed by the structure which are adjacent to the testing site. To overcome that problem the dampers are provided in the structure. During the period of 1990’s, the use of damper become very large i.e., it is used not only for military and defence structure but also to the commercial structures. A New York based company Taylor Devices, Inc. manufactured these type device and produced in the market for all type of structure.
  • 17. The Viscous dampers are passive energy dissipation device which is added to structure to increase the effective stiffness of new and existing buildings. They are very robust material and energy is transferred by piston and absorbed or vanishes by silicone-based fluid flowing between the piston-cylinder arrangements. The damping force of viscous damper is given by F=CVα where, F -The damping force. C - The damping coefficient. V - The velocity of piston. α – The velocity exponent.
  • 18. • The viscous damper works on the principle of flow of fluid through the orifice in the chamber. • The silicone-based fluid is used in the chamber. The piston which is made up of stainless steel which travels in the chamber which is filled by the silicone oil. • The characteristic of the silicone oil is inert, non-flammable, nontoxic and extremely stable for a period of long time. • This difference in pressure between two chambers will force the oil to flow through orifice in piston head. The inside energy is transferred into heat which will dissipate into the atmosphere. WORKING PROCEDURE OF VISCOUS DAMPER
  • 19.
  • 20. The three basic way to attach the damper to the building are: 1. Base isolation. 2. Damper for chevron bracing system. 3. Damper for diagonal bracing system. Basic Way of Applying Damper
  • 21. In this present study, the dampers are provided throughout the story in the corners of the structure. The way of attachment of the damper is chevron brace type to the structure. The elements of viscous damper is modelled in ETABs by assigning a panel zone with non-linear link property to the mid-span point object where the chevrons intersect the beams throughout the structure. Advantages 1. At low displacement also these are activated. 2. It has minimal restoring force. 3. The properties largely frequency and temperature independent. 4. The performance in the military application has made the record. Disadvantage 1. Leakage of fluid (reliability concern).
  • 22. MODELLING AND ANALYSIS In this present work, the structure of eight story’s is considered which is of reinforced concert structure. The plan of the structure is symmetrical plan, having the area of 20m X 20m. Each spacing of the gridline is 5m on both side. The height of each story of the structure is 3m. the overall height f the structure is 24m. the frame of the structure is modelled in ETABs software. Grade of Concrete M 25 Modulus of Elasticity of Concrete (E) 25000 MPa Grade of Steel Fe-415 Modulus of Elasticity of Steel (E) 200000 MPa Density of Brick 20kN/m3 Poisson’s ratio 0.2 The material properties of the structure for modeling is considered as below,
  • 23. Beam 230mm X 450mm Column 500mm X 500mm Slab Thickness 150mm Wall thickness 230mm 150mm The sectional details like size of beam, column, slab and wall are considered as below in the table. Section Details of the Structure
  • 24. Load Consideration The model is generated in the software which should be consist of loads. Loads which are considered for this work are Dead load is a load which is self weight of structural element. The dead load of the structural element like beam, column and slab is calculated by the software directly. The dead load consist of floor finish of 1.5kN/m2 and wall load of 230mm wall having a dead weight of 12 kN/m and 150mm wall having a weight of 7.8 kN/m. Live load is a load which is not constant in its place. The live load of 3 kN/m2 is considered for the current project work as per IS 875-part II.
  • 25. Seismic Zone Zone III Importance Factor 1 Reduction Factor 5 Damping Ratio 5% The seismic load is considered according to the Indian Standards code IS 1893:2002. The load combination for the concrete frame structure is considered as by default from the software which are according to the IS 1893-2002.
  • 26. Application of Viscous Damper and Its Properties Damper is a device which is applied to the structure to reduce the seismic effect of the structure. In ETABs the viscous damper element is assigned to the structure in the form of chevron bracing through out the height of the structure at all corners of the structure. A panel zone is defined at the mid point of the beam with non linear link property. The chevron will intersect to the mid point of the beam where the panel zone is assigned. In the panel zone, the beam-brace connectivity is selected with non-linear behaviour in U2 direction for assigning the damper. The properties of the Viscous Damper is considered as provided by the manufacturing company Taylor Device Inc., Damping coefficient 810 kN-s/m Velocity exponent 0.3
  • 27. The stiffness value of the viscous damper is calculated by the following formula by considering the force and displacement of the bare structure. Force = Stiffness * Displacement i.e., F=K*δ 50= K*(0.084/1000) K = 5,95,238.0953 kN/m
  • 28.
  • 29.
  • 30. RESULT AND DISCUSSION” In the present study, viscous dampers are used to reduce the seismic effect of the structure which are subjected to the earthquake load. The frames (with and without viscous damper) is modelled according to the properties of the structure which are explained in the work. Because of the symmetric model the values in both direction will be same. The seismic behaviour of the Reinforced Concrete structure is judged by observing the parameters such as 1. Displacement. 2. Story Drift. 3. Story Shear.
  • 31. 1. Displacement Displacement is the parameter of maximum importance as it governs the failure pattern of the structure. Table : Displacement (mm) Story Elevation (m) Displacement (mm) without damper with viscous damper 8 24 29.63 10.73 7 21 28.22 9.70 6 18 25.87 8.39 5 15 22.57 6.87 4 12 18.42 5.22 3 9 13.53 3.52 2 6 8.14 1.86 1 3 2.92 0.46 Base 0 0 0
  • 32. 0.00 5.00 10.00 15.00 20.00 25.00 30.00 35.00 8 7 6 5 4 3 2 1 BASE Displacement(mm) Story Level Displacement without damper with viscous damper
  • 33. 2. Story Drift As the number of story increases in the structure, the drift is the common factor for multi-story building. The variance between the lateral displacements of two adjacent floors of the structure is defined as the story drift. Table 5.2: Story Drift (mm) Story Elevation (m) Story Drift (mm) without damper with viscous damper 8 24 0.00059 0.00035 7 21 0.00094 0.00045 6 18 0.00125 0.00052 5 15 0.00149 0.00056 4 12 0.00168 0.00057 3 9 0.00181 0.00055 2 6 0.00174 0.00047 1 3 0.00097 0.00015
  • 34. 0.00000 0.00020 0.00040 0.00060 0.00080 0.00100 0.00120 0.00140 0.00160 0.00180 0.00200 8 7 6 5 4 3 2 1 Base StoryDrift(mm) Story Level Story Drift without damper with viscous damper From the above table and graph we can observe that: 1) The values of drift is more at middle story i.e., 2 to 5 story and less at top and bottom story. 2) The reduction in story drift at mid-stories of model with addition of viscous damper is 70% when compared with bare model. 3) By applying damper to the structure there is reduction of about 60% to 80% in drift value at top and bottom stories.
  • 35. 3. Story Shear (kN) The story shear is the shear value obtained from the sum of design lateral forces at the levels above the story consideration of the structure. The shear values of the both models are below in the table. Table: Story Shear (kN) Story Elevation (m) Story Shear without damper with viscous damper 8 24 288.26 293.36 7 21 571.35 623.03 6 18 758.14 881.01 5 15 891.75 1088.39 4 12 1007.25 1254.22 3 9 1124.19 1381.26 2 6 1232.17 1463.58 1 3 1291.18 1487.82 Base 0 0 0
  • 36. From the below graph, 1. By observing that the values of model with damper is little bit more as compared to without damper model. 2. The value of the story shear has been linearly decreasing as height of the story increases. 0.00 200.00 400.00 600.00 800.00 1000.00 1200.00 1400.00 1600.00 8 7 6 5 4 3 2 1 BASE StoryShear(kN) Story Level Story Shear(kN) without damper with viscous damper
  • 37. CONCLUSION After the analyses of structure the results obtained and compared. And the conclusion are as follows, 1. According to the obtained results, viscous damper in structure results in the decrease of building displacement and building drift. 2. The bare frame model which is without damper is analysed and obtained the results of displacement as 29.63mm and story drift as 0.00181mm. 3. The results obtained from the model with addition of viscous damper are displacement as 10.73mm and story drift as 0.00055mm. 4. By observing, the displacement values increases over the height of the structure. 5. From the comparison, the displacement value of the structure is reduced about 60% to 85% when viscous dampers are applied to the structure.
  • 38. 6. With the placement of viscous damper into the structure maximum drift reduces in the structure during seismic loading. 7. By using viscous damper in the structure, the story drift at mid-stories is reduced by 70% when compared with bare model. 8. By applying viscous damper to the structure there is reduction of about 60% to 80% in drift value at top and bottom stories. 9. The base shear value of bare frame model is 1291.18 kN and that to model with viscous damper is 1487.82 kN. 10. By observing the shear value, the difference is less because of the weight of the damper provided to the structure. 11. From the study, by applying viscous dampers to the structure its behaviour change under seismic loading. 12. By observing, these viscous damper devices perform a vital role in reducing and controlling the seismic response of the structure.
  • 39. REFERENCE: 1) Vajreshwari Umachagi, Katta Venkataramana, G. R. Reddy, Rajeev Verma, “Applications of Dampers for Vibration Control Of Structures: An Overview” International Journal of Research in Engineering and Technology, Nov-2013. 2) Liya Mathew & C. Prabha, “Effect of Fluid Viscous Dampers in Multi-Storeyed Buildings”, International Journal of Research in Engineering & Technology, Vol. 2, Issue 9, Sep 2014, 55- 60. 3) Su Myat Aye, Dr. Kyaw Moe Aung, “Comparative Study on Seismic Response of RC Structure Using Viscous Dampers and Viscoelastic Dampers”, International Journal Of Scientific Engineering And Technology Research, Vol.03, Issue.08, May-2014, Pages:1468- 1478. 4) Mohammad Javad Dehghan, Mostafa Soleymannejad, “Improving Seismic Performance of Concrete Buildings with Special Moment Frames Using Viscous Damper”, International Journal of Modern Engineering Research, Vol. 5, Issue. 7, July 2015.
  • 40. 5) Yuvraj Bisht, Saraswati Setia, “Seismic Behaviour Of A Soft Storey Building With & Without Viscous Dampers”, International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622, pg. no 10-15 6) V. Sadeghi Balkanlou, M. Reza Bagerzadeh Karimi, B. Bagheri Azar And Alaeddin Behravesh, “Evaluating Effects of Viscous Dampers on optimizing Seismic Behaviour of Structures”, International Journal of Current Engineering and Technology,Vol.3, No.4 (October 2013), pg.no 1150-1157. 7) Douglas Taylor, President, Taylor Devices Inc., “History, Design and Application of Fluid Dampers in Structural engineering” 8) Godhat Kishan J. and Yashwantsinh Zala, “A Review on Effect of Actual Site Specific Response Analysis of Tall Building with Viscous Damper”, International Journal of Trend in Research and Development, Volume 2(6), Nov - Dec 2015, pg.no.298-302. 9) The manufacturer of the Viscous Damper product Taylor Devices Inc., India. 10) Lee. D., and Taylor. D. P, “Viscous damper development and future trends”, Struct., Des., Tall Build, vol-10(5), 2001, pg.no-(311–320).
  • 41. 11) Alireza Heysami, “Types of Dampers and their Seismic Performance during an Earthquake”, Current World Environment, Vol. 10(Special Issue 1), 1002-1015 (2015). 12) Dharmesh Chandnani, Riddhi Joshi, Kumarpal Trivedi, “Characteristics & Applications of Different Types of Dampers as Seismic Energy Dissipater”, International Journal of Computer Science and Network, Volume 5, Issue 2, April 2016 pg.no (369-372). 13) Jenn-Shin Hwang, Chun-Hsiang Tsai, Shiang-Jung Wang, Yin-Nan Huang, “Experimental study of RC building structures with supplemental viscous dampers and lightly reinforced walls”, Engineering Structures, accepted 6 March 2006, pg.no (1-9), at 2006 Elsevier Ltd.