Secure Power design considerations
Confidential Property of Schneider Electric |
Summary
Page 2Confidential Property of Schneider Electric |
1 Introduction
2 How do we ensure reliable power..?
3 How can ...
More
ELECTRIC
Increase by 50% in the
next 25 years
More
CONNECTED
Connect 50bn devices
by 2020
More
DISTRIBUTED
Solar PV a...
Back to index
Mining (Metals & Minerals)
Water & Wastewater
Datacenter
Healthcare
Oil and Gas
Building
No matter the type ...
Confidential Property of Schneider Electric | Page 5
Confidential Property of Schneider Electric |
How do we ensure reliab...
Heavy
Industry
Commercial
& Industrial
Industry
Buildings
Data Centres
Residential
Infrastructure
EHV/HV
Centralised
Gener...
Heavy
Industry
Commercial
& Industrial
Industry
Buildings
Data Centres
Residential
Infrastructure
EHV/HV
Centralised
Gener...
Confidential Property of Schneider Electric | Page 8
Confidential Property of Schneider Electric |
How can we reduce these...
UPS - “Uninterruptible Power
Supply”
Page 9Confidential Property of Schneider Electric |
PFC
Rectifier
UPS
AC: Alternating Current
DC: Direct Current
PFC: Power Factor Correction
What is a “UPS” & what is the
pu...
Heavy
Industry
Commercial
& Industrial
Industry
Buildings
Data Centres
Residential
Infrastructure
EHV/HV
Centralised
Gener...
Heavy
Industry
Commercial
& Industrial
Industry
Buildings
Data Centres
Residential
Infrastructure
EHV/HV
Centralised
Gener...
UPS Topologies
Page 13Confidential Property of Schneider Electric |
- The simplest solution, used for applications that support a cut of 4 to 10ms when detecting the fault of the
source and ...
UPS’s - Different topologies – Line-interactive Easy UPS BV
Smart-UPS green
- This technology is an improvement of the fir...
UPS’s - Different topologies – On-line Double conversion
- The load is permanently supplied by the converter, which allows...
Installation considerations
Click each logo to learn more.
Because these are the primary organizations that create the requirements for UPS systems,
y...
Appro : 550kg
3-Phase UPS - Installation considerations - Dimensions
Example of dimension of UPS : Galaxy 3500 => 20kVA 3:...
3-Phase UPS - Installation considerations - Battery room
layout
Page 23Confidential Property of Schneider Electric |
• Ven...
Technical room airflow requirements : example : Galaxy VM 160kVA
Page 24Confidential Property of Schneider Electric |
3-Ph...
Galaxy 3500
IP 51
Galaxy 5500 Marine IP 22 Gutor PXC
IP 42
Some applications where a reinforcement of IP level is required...
UPS Architectures
Page 26Confidential Property of Schneider Electric |
Page 27Confidential Property of Schneider Electric |
UPS efficiency
• ECO mode
• Intelligent inverter
• Efficiency Booster...
Single UPS
Page 28Confidential Property of Schneider Electric |
20kVA
UPS
A
UPS
B
In Out
For Capacity
40kVA
In Out
UPS
A
U...
Pros:
• Cost efficient, Low footprint
Cons:
• Service capability
Availability Maintainability Upgradeability
MediumMediumH...
Single UPS
Input Supply Output to Equipment
Availability Maintainability Upgradeability
MediumMediumMedium
UPS
A
UPS
B
For...
Input Supply Output to Equipment
Availability Maintainability Upgradeability
MediumHighVery High
UPS
A
UPS
B
Office, ATM, ...
WhitespaceRow:B
16kW
32kW
48kW
64kW
160kW
144kW
128kW
112kW
96kW
80kW
Available Power
20KW40KW60KW80KW100KW120KW140KW 160K...
Single UPS
Page 33Confidential Property of Schneider Electric |
20kVA
UPS
A
UPS
B
In Out
For Capacity
40kVA
In Out
UPS
A
U...
“SBC”SystemBypassCabinet
GalaxyVX1250kW
“UPS A” “BBC”
BatteryBreakerCabinet
“BATT”
BatteryCabinet
Input
Output
1
1 2
2 3
3...
Multi-mode-operation
Page 35Confidential Property of Schneider Electric |
Galaxy VX
Galaxy VM
Galaxy VS “2018”
Multi-mode operation - for best performance for a given environment
Battery
DC/DC
PFC Recfifier Inverter
LoadAC in
AC in
B...
Multi-mode operation - for best performance for a given environment
What if.. we could have the best from both?
• Load is ...
• Main flow of power is through bypass path => High efficiency
• Inverter is kept on => Reduced drop of output voltage at ...
Back to index
Battery
DC/DC
PFC Recfifier Inverter
LoadAC in
AC in
Bypass Switch
Efficiency in On-line mode, ECO mode & th...
SPoT mode
Page 40Confidential Property of Schneider Electric |
Galaxy VX
Galaxy VM
Galaxy 7000
Back to index
SPoT: Load
bank test
savings
-15%
Power
Module
Scalability
250kW
Galaxy VX - Smart Power Test “SPoT mode”
Th...
Inverter, PFC &
SSW Test
• Inverter is turned on while UPS is in Requested Static Bypass
• Output power from Inverter is r...
Energy Storage
Page 43Confidential Property of Schneider Electric |
Customer Need:
Frequent
Flywheel Ultracaps
Energy Storage available
Page 44Confidential Property of Schneider Electric |
E...
Li-ion Battery
Page 45Confidential Property of Schneider Electric |
Range available
• Galaxy VX
• Galaxy VM
• Galaxy 7000
...
Back to index
Lithium-ion Battery
Page 46Confidential Property of Schneider Electric |
The Schneider Electric Li-ion batte...
Back to index
Li-ion Battery Technology vs. VRLA
Less Footprint
40-60%
Less Weight
60-70%
Expected Life
2-3X
# Cycles
10X
...
Back to index
Schneider Electric’s LIB Solution
A modular solution accomodating a wider range of needs
13 or 17
per rack
C...
Back to index
Food and Beverage
Large data centers -and
other critical sites- are
striving to improve their
competitivenes...
UPS Range
1-Phase UPS - Offer
375-1100 VA 0,55 – 1,5 kVA 0,75 - 5 kVA 0,5 – 1,1 kVA
Surge Arrest
Smart UPS
SMT
Back UPS
Line
interac...
10kVA 40kVA 200kVA
Symmetra PX
3-Phase UPS - Offer
Symmetra MW 500-1600kVA
Galaxy
3500
Smart-UPS
VT
10-40 kVA
10-40 kVA 10...
5
Upcoming SlideShare
Loading in …5
×

Secure Power Design Considerations

2,969 views

Published on

More Electric:
Our world is becoming More Electric. Almost everything we interact with today is either already electric or becoming electric. Think about it. From the time you start your day in the morning to the time you finish your day – your home, your car, your work, your devices, your entertainment – almost everything is electric. Imagine the energy needed to power this. Electricity consumption will increase by 80% in next 25 years

 
More Connected: Our lives are also becoming more connected. The Internet has already transformed the way we live, work and play. Now the Connected Things is going to take this to a brand new level. 50 billion things connected in the next 5 years.
 
More Distributed: With such a widespread electrification and connectivity, energy models need rethinking as well. Which is why the generation of power needs to be closer to users. Distributed Energy is rapidly evolving globally. This is positive energy – renewable. In 2014 , Renewables overtook fossil fuels in investment value, with $295bn invested in renewables compared to $289bn invested in fossil fuels. And it is getting cheaper to do this.
 
More Efficient: When our world is more electric, more connected and more distributed, new opportunities emerge and allows us to tap into even more efficiency – in industrial processes, in the energy value chain, in buildings, in transportation, in the global supply chain and even in the comfort and peace-of-mind of our homes.

Published in: Technology
  • Real Ways To Make Money, Most online opportunities are nothing but total scams! ♣♣♣ https://tinyurl.com/y4urott2
       Reply 
    Are you sure you want to  Yes  No
    Your message goes here

Secure Power Design Considerations

  1. 1. Secure Power design considerations Confidential Property of Schneider Electric |
  2. 2. Summary Page 2Confidential Property of Schneider Electric | 1 Introduction 2 How do we ensure reliable power..? 3 How can we reduce these risk? 4 UPS Topologies 5 Installation considerations 6 UPS Architectures 7 Multi- mode - operation 8 Energy Storage UPS range9
  3. 3. More ELECTRIC Increase by 50% in the next 25 years More CONNECTED Connect 50bn devices by 2020 More DISTRIBUTED Solar PV and Storage to Account for ~50% of new capacity additions by 2030 More EFFICIENT Still.. 2/3 energy efficiency potential.. remains untapped .!! Our World Will Be…
  4. 4. Back to index Mining (Metals & Minerals) Water & Wastewater Datacenter Healthcare Oil and Gas Building No matter the type of business… reliable power is essential
  5. 5. Confidential Property of Schneider Electric | Page 5 Confidential Property of Schneider Electric | How do we ensure reliable power..?
  6. 6. Heavy Industry Commercial & Industrial Industry Buildings Data Centres Residential Infrastructure EHV/HV Centralised Generation HV/MV Substation (Primary substation) Switching Substation MV/MV Heavy Industry MV / LV Substation Connexion to HV network Connexion to MV network ConsumersEnergy Producers Utility Transmission Utility Distribution
  7. 7. Heavy Industry Commercial & Industrial Industry Buildings Data Centres Residential Infrastructure EHV/HV Centralised Generation HV/MV Substation (Primary substation) Switching Substation MV/MV Heavy Industry MV / LV Substation Connexion to HV network Connexion to MV network ConsumersEnergy Producers Utility Transmission Utility Distribution Power failure, Voltage spikes, Under voltage, Frequency variations Harmonics, Power Factor Disturbances Voltage variations Frequency variations Micro outages Long outages
  8. 8. Confidential Property of Schneider Electric | Page 8 Confidential Property of Schneider Electric | How can we reduce these risk? - Power failure - Voltage spikes - Under voltage - Frequency variations
  9. 9. UPS - “Uninterruptible Power Supply” Page 9Confidential Property of Schneider Electric |
  10. 10. PFC Rectifier UPS AC: Alternating Current DC: Direct Current PFC: Power Factor Correction What is a “UPS” & what is the purpose of a UPS? Main functions of a UPS: “Uninterruptible Power Supply” •Short term backup (Batteries) •Input current conditioned by the PFC •Output Voltage conditioned by the Inverter •Isolation / Protection against: • Voltage spikes • Over voltage • Under voltage • Frequency variations • Harmonics • Power Factor
  11. 11. Heavy Industry Commercial & Industrial Industry Buildings Data Centres Residential Infrastructure EHV/HV Centralised Generation HV/MV Substation (Primary substation) Switching Substation MV/MV Heavy Industry MV / LV Substation Connexion to HV network Connexion to MV network Energy Producers Utility Transmission Utility Distribution Power failure, Voltage spikes, Under voltage, Frequency variations Harmonics, Power Factor UPS Consumers
  12. 12. Heavy Industry Commercial & Industrial Industry Buildings Data Centres Residential Infrastructure EHV/HV Centralised Generation HV/MV Substation (Primary substation) Switching Substation MV/MV Heavy Industry MV / LV Substation Connexion to HV network Connexion to MV network Energy Producers Utility Transmission Utility Distribution Power failure, Voltage spikes, Under voltage, Frequency variations Harmonics, Power Factor Power Grid Customer Grid UPS Consumers Reliable & safe Power Harmonics created by the load is reduced by the UPS UPS ON
  13. 13. UPS Topologies Page 13Confidential Property of Schneider Electric |
  14. 14. - The simplest solution, used for applications that support a cut of 4 to 10ms when detecting the fault of the source and transfer to the battery - This technology is for low powers (Apparent Power: 330 VA – 900 VA) - This solution is inexpensive with a good efficiency UPS’s - Different topologies – Off-Line Back-UPS ® ES Surge Filter Static Switch Batteries charger Batteries Inverter
  15. 15. UPS’s - Different topologies – Line-interactive Easy UPS BV Smart-UPS green - This technology is an improvement of the first, the coupling / decoupling device is more sophisticated (static or fast system) and a regulating device of the mains voltage can be added - The DC / AC converter is generally a bi-directional converter or reversible, providing the battery and the load power in case of power cut - This solution is used little above 5000 VA Static switch Voltage regulator Filter Rectifier Inverter Batteries
  16. 16. UPS’s - Different topologies – On-line Double conversion - The load is permanently supplied by the converter, which allows to regulate frequency and voltage - This technology is particularly suitable for very disturbed networks or very sensitive applications - This technology is used for power supplies up to 1,6 MVA Smart-UPS RT Gamme Galaxy By-pass static switch Rectifier Inverter Batteries
  17. 17. Installation considerations
  18. 18. Click each logo to learn more. Because these are the primary organizations that create the requirements for UPS systems, you should have a general understanding of how they work and how Schneider Electric works with them. Page 18Confidential Property of Schneider Electric | Standards - UPS Requirements
  19. 19. Appro : 550kg 3-Phase UPS - Installation considerations - Dimensions Example of dimension of UPS : Galaxy 3500 => 20kVA 3:3 15min Page 22Confidential Property of Schneider Electric |
  20. 20. 3-Phase UPS - Installation considerations - Battery room layout Page 23Confidential Property of Schneider Electric | • Ventilation (2) • Layout of cells (3) • Service flooring (4) • Battery connection (5) • Battery-protection circuit breaker (6) • Fire-fighting equipment (7) • Safety equipment (8) • Inspection equipment (9) • Sensors (10)
  21. 21. Technical room airflow requirements : example : Galaxy VM 160kVA Page 24Confidential Property of Schneider Electric | 3-Phase UPS - Installation considerations - Ventilation, air- conditioning
  22. 22. Galaxy 3500 IP 51 Galaxy 5500 Marine IP 22 Gutor PXC IP 42 Some applications where a reinforcement of IP level is required : Emergency application (smoke extraction systems) => IP 30 Marine : IP 22 Industry where corrosion or dust are there => up to IP 55. Above IP32, Gutor offer is required 3-Phase UPS - Installation considerations - IP degree of protection Note: Most of UPS’s are IP 20 Page 25Confidential Property of Schneider Electric |
  23. 23. UPS Architectures Page 26Confidential Property of Schneider Electric |
  24. 24. Page 27Confidential Property of Schneider Electric | UPS efficiency • ECO mode • Intelligent inverter • Efficiency Booster Mode • High efficiency UPS’s Architectures - Industry dilemma Power availability • UPS architecture • Redundancy • MTTR/MTBF • Ease operation • Flexibility
  25. 25. Single UPS Page 28Confidential Property of Schneider Electric | 20kVA UPS A UPS B In Out For Capacity 40kVA In Out UPS A UPS B For Redundancy 20kVA N+1 In Out For Modularity UPS A 16kW, 32kW or 48kW 16kW, 32kW N+1 In Out UPS’s - Understanding the costumer needs (Various UPS protection levels)
  26. 26. Pros: • Cost efficient, Low footprint Cons: • Service capability Availability Maintainability Upgradeability MediumMediumHigh Single UPS 20kVA Input Supply Output to Equipment Up to 20 kVA Office, ATM, Cash register & others UPS configuration - for a fixed load
  27. 27. Single UPS Input Supply Output to Equipment Availability Maintainability Upgradeability MediumMediumMedium UPS A UPS B For Capacity 40kVA Office, ATM, Cash register & others Pros: • Cons: • Installation cost, Service ability, Service cost UPS configuration - for increased load Up to 40 kVA
  28. 28. Input Supply Output to Equipment Availability Maintainability Upgradeability MediumHighVery High UPS A UPS B Office, ATM, Cash register & others For Redundancy 20kVA N+1 Pros: • High Reliability, Good Serviceability Cons: • Footprint, Higher upfront Cost, Lower Efficiency UPS BUPS A UPS configuration - for power Redundancy N+1 Up to 20 kVA
  29. 29. WhitespaceRow:B 16kW 32kW 48kW 64kW 160kW 144kW 128kW 112kW 96kW 80kW Available Power 20KW40KW60KW80KW100KW120KW140KW 160KW Data Center Pros: • Modularity, Scalability, Efficiency, Serviceability, Reliability Cons: • Higher Cost Input Supply Output to Equipment Availability Maintainability Upgradeability Very HighVery HighVery High 16 to 160kW UPS configuration - for modularity, Scalability & Redundancy Page 32Confidential Property of Schneider Electric |
  30. 30. Single UPS Page 33Confidential Property of Schneider Electric | 20kVA UPS A UPS B In Out For Capacity 40kVA In Out UPS A UPS B For Redundancy 20kVA N+1 In Out For Modularity UPS A 16kW, 32kW or 48kW 16kW, 32kW N+1 In Out Availability Maintainability Upgradeability Medium High Medium Availability Maintainability Upgradeability Medium Medium Medium Availability Maintainability Upgradeability Medium Very High High Availability Maintainability Upgradeability Very High Very High Very High UPS’s - Understanding the costumer needs (Various UPS protection levels)
  31. 31. “SBC”SystemBypassCabinet GalaxyVX1250kW “UPS A” “BBC” BatteryBreakerCabinet “BATT” BatteryCabinet Input Output 1 1 2 2 3 3 4 4 UPS’s - Understanding Single UPS configuration with all Aux. Page 34Confidential Property of Schneider Electric |
  32. 32. Multi-mode-operation Page 35Confidential Property of Schneider Electric | Galaxy VX Galaxy VM Galaxy VS “2018”
  33. 33. Multi-mode operation - for best performance for a given environment Battery DC/DC PFC Recfifier Inverter LoadAC in AC in Bypass Switch Battery DC/DC PFC Recfifier Inverter LoadAC in AC in Bypass Switch May be on to allow battery recharge Battery DC/DC PFC Recfifier Inverter LoadAC in AC in Bypass Switch Double conversion mode with 4-level inverter provide best performance with >96% efficiency up to 30% load. ECO mode supply to load a bypass mains power without power conditioning and provides highest efficiency of 99%. ECOnversion mode provides near double conversion performance at near ECO mode efficiency. ECOnversion provides power conditioning at efficiency >98% to 99%. This unique flexibility of Galaxy VM & VX allows customer to operate the UPS in any of the above mode depending on load profile, site environment and schedule during the lifecycle of the UPS. ECOnversion mode™Double conversion ECO mode Page 36Confidential Property of Schneider Electric |
  34. 34. Multi-mode operation - for best performance for a given environment What if.. we could have the best from both? • Load is powered through PFC and Inverter • Conditioned output voltage by inverter • Conditioned input current by PFC • Grid and load is coupled through DC bus • Efficiency above 96% • Load is powered through Bypass by unconditioned grid • Output voltage by grid (No filtering, No protection) • Input current by load (No current correction of the Load) • Small ”break” in output Voltage doing transfer to Battery • Efficiency above 99% Double Conversion mode ECO mode (not recommended to use) Page 37Confidential Property of Schneider Electric |
  35. 35. • Main flow of power is through bypass path => High efficiency • Inverter is kept on => Reduced drop of output voltage at mains failure • Regulation of input current => ”Diesel friendly”, no harmonics or VARs • Regulation of DC bus => Allows battery recharge in ECOnversion • Novel control method of bypass SCRs => Tolerant to mains short circuits ECOnversiontm - for reduced operating costs Battery DC/DC PFC Recfifier Inverter LoadAC in AC in Bypass Switch ECOnversiontm mode combines the best from ECO mode & Double conversion mode: Page 38Confidential Property of Schneider Electric |
  36. 36. Back to index Battery DC/DC PFC Recfifier Inverter LoadAC in AC in Bypass Switch Efficiency in On-line mode, ECO mode & the ECOnversiontm On-line mode, ECO mode & the ECOnversiontm Page 39Confidential Property of Schneider Electric | Galaxy VX in Double Conversion with 1000kW load: UPS Efficiency : 95,1% (at 1000kW) UPS Efficiency Losses : 49 kW (of heat) Yearly Efficiency Losses in kW/hours: 429,240 kW Yearly Efficiency Losses in Euro: 51.509 EUR (12 cent/kW) Galaxy VX in ECOnversion with 1000kW load: UPS Efficiency : 99,1% (at 1000kW) UPS Efficiency Losses : 9,4 kW (of heat) Yearly Efficiency Losses in kW/hours: 82.344 kW Yearly Efficiency Losses in Euro: 9.881 EUR (12 cent/kW) Double Conversion vs. ECOnversion mode: Yearly Efficiency Losses savings in kW: 346.896 kW Yearly Efficiency Losses savings in EUR: 41.628 EUR 5 Years Efficiency Losses savings in EUR: 208.140 EUR Galaxy VX - ECOnversiontm - economical comparison Page 39Confidential Property of Schneider Electric |
  37. 37. SPoT mode Page 40Confidential Property of Schneider Electric | Galaxy VX Galaxy VM Galaxy 7000
  38. 38. Back to index SPoT: Load bank test savings -15% Power Module Scalability 250kW Galaxy VX - Smart Power Test “SPoT mode” The Smart Power Test in normal operation is conducted by circulating power from the inverter back through the static bypass switch and into the power factor correction module. By circulating the power, each of the UPS converters is energized and loaded in the same way as though a UPS was feeding a load bank. The test shall be configurable for 100% rated power continuously or 110% of rated power for 10 minutes. During Smart Power Test, the UPS shall draw only enough power from utility to make up for system losses during the test procedure. No need for loadbank Page 41Confidential Property of Schneider Electric | SPoT makes it economical to test UPS before connecting critical load after commissioning and servicing
  39. 39. Inverter, PFC & SSW Test • Inverter is turned on while UPS is in Requested Static Bypass • Output power from Inverter is recycled via bypass to input mains • Power consumption equals system losses in Inverter, PFC, and Static Switch • Requires output to be connected via bypass to input mains • Can run at 100% continuous or 110% for 10min Page 42Confidential Property of Schneider Electric | 1) Normal Operation & SSW Test Galaxy VX - Smart Power Test “SPoT mode” • Charger is turned on while in battery operation and charge power is recycled via PFC back to DC bus • Power consumption equals system loss only in Charger and PFC • Selectable Charger load percentage 100 or 110% of charger capacity 2) Charger Operation Test Charger Test Battery, Inverter & SSW Test • Inverter is turned on while UPS is in Requested Static Bypass • Output power from Inverter is recycled via static bypass to mains • Requires output to be connected via bypass to input mains • Can run at 100% continuous *Back-feeding power to the grid may require local approval 3) Battery Discharge Test
  40. 40. Energy Storage Page 43Confidential Property of Schneider Electric |
  41. 41. Customer Need: Frequent Flywheel Ultracaps Energy Storage available Page 44Confidential Property of Schneider Electric | Example : Need 2 min 600 kW • Batteries – Sealed lead-acid The most commonly employed solution today – Vented lead-acid – Nickel cadmium Harsh environment – Lithium-ion Alternative solution to lead-acid • Ultracapacitors • Flywheels The various technologies currently available are the following
  42. 42. Li-ion Battery Page 45Confidential Property of Schneider Electric | Range available • Galaxy VX • Galaxy VM • Galaxy 7000 • Symmetra MW • Symmetra PX250/500
  43. 43. Back to index Lithium-ion Battery Page 46Confidential Property of Schneider Electric | The Schneider Electric Li-ion battery solution for three-phase UPSs is a high-value, innovative energy storage protection solution for data centers, industrial processes, or critical infrastructure. This solution is supported by Schneider Electric Symmetra MW, Galaxy 7000, Galaxy VM, and Galaxy VX UPS’s and brings the following benefits: • Significantly reduced battery footprint & weight to allow for a more effective use of space • Double the life and simplified maintenance vs. traditional batteries • Reduced cooling requirements • Improved backup storage predictability and manageability (BMS system included) • Reduced TCO
  44. 44. Back to index Li-ion Battery Technology vs. VRLA Less Footprint 40-60% Less Weight 60-70% Expected Life 2-3X # Cycles 10X Initial CAPEX 1.5-2X TCO Savings 30-50% AND Recharge Time Faster Operating Temperature Higher BMS Integrated BMS
  45. 45. Back to index Schneider Electric’s LIB Solution A modular solution accomodating a wider range of needs 13 or 17 per rack Cell Module (8 cells) Switch Gear & Rack BMS LIB Rack (W600xD650xH2100mm) LIB Requirements for UPS application • Top safety technology • High energy and power density: 35kWh and up to 230kW per rack • Backup time from 5/6min to 30+min • 15-years design life • Competitive CapEx (~1,5-2X VRLA) • Breakthrough TCO (-30-50%) • Partnership with leading li-ion manufacturer From 1-32 racks depending on power and backup time SMPS & System BMS 1 Gateway (System BMS) per system (1U, fit in one of the LIB racks) Page 48Confidential Property of Schneider Electric |
  46. 46. Back to index Food and Beverage Large data centers -and other critical sites- are striving to improve their competitiveness …improvements in backup storage technology are a key enabler Improve battery lifetime/reduce maintenance Improve backup storage predictability and manageability Reduce footprint Reduce weight Reduce cooling constraints Reduce TCO What can be improved from the current VRLA battery solution? Page 49Confidential Property of Schneider Electric |
  47. 47. UPS Range
  48. 48. 1-Phase UPS - Offer 375-1100 VA 0,55 – 1,5 kVA 0,75 - 5 kVA 0,5 – 1,1 kVA Surge Arrest Smart UPS SMT Back UPS Line interactive Surge protection Back UPS SX3 online 1 - 20 kVA 2 - 16 kVA 1-10 kVA Smart UPS RT Smart UPS SR1 Confidential Property of Schneider Electric Page 51 Symmetra LX Back UPS Pro Back VS Smart RVS IT & Non-IT IT Data Center
  49. 49. 10kVA 40kVA 200kVA Symmetra PX 3-Phase UPS - Offer Symmetra MW 500-1600kVA Galaxy 3500 Smart-UPS VT 10-40 kVA 10-40 kVA 10-80 kVA 20-120 kVA 160-200 kVA 250-500 kVA 500-1500kVA 10-500 kVA 400-1600 kVA PX 40/48 kW PX 250/500 kWPX 100/160kW Galaxy VM Galaxy VXGalaxy 4000/5000/5500 STAND- ALONE MODULAR Galaxy 7000 Fully Customized 5-160 kVA 5-220 kVA Gutor PXC Gutor PXP Gutor PEW & Gutor PDW Confidential Property of Schneider Electric Page 52 Galaxy 300 10- 40 KVA 10-80 kVA IT Data centers Non-IT IT & Non-IT Easy UPS 3S
  50. 50. 5

×