Residual Current is a critical condition impacting hospitals, data centres, industrial plants, etc. It can lead to dangerous situations for both personnel and equipment.
Moreover, it can cause unexpected interruptions, malfunctions and EMC problems that cost time and money. Hence, Residual Current Monitoring is critical for safety, high availability and productivity in industrial and purpose-built environments.
Inside environments like data centres where shielded cables are present, residual current may spread through cable shielding across different parts of the data centre if the racks are insufficiently earthed. This can lead to fires, unexplained IT systems failures, tripping and disconnecting of critical equipment.
For Electrical and Maintenance engineers working in Manufacturing and Hospitality sector, the challenge is tosupervise plant-wide energy utilisation and manage their electric infrastructure in a systematic, optimised way.
Janitza GmbH is a globally renowned and leading supplier of energy efficiency systems. Their digital energy meters, power quality analysers, digital measurement equipment, universal-measurement devices, power factor controller, peak demand management systems etc. are well acceptedall over the world.
Integrating fire protection and fire alarm systems with building automation systems (BAS) can offer efficient and cost-effective operation. The design and installation of an integrated system must also be well-planned and coordinated, and the system must be properly maintained over its lifetime. The need for multidisciplinary coordination between the fire protection engineer and the mechanical and electrical engineers during design and construction are of key importance. Design engineers also must involve the building owner and/or operator in establishing (or at least influencing) the design criteria of the building. The owner/operator must understand that the efficiencies gained by integration will pay dividends long into the lifecycle of the building.
Like a BAS, fire protection and alarm systems have also evolved into sophisticated computer-based systems, which offers more opportunities to integrate these systems to develop a more complete building response as part of overall building operations during an emergency event.
Practical Fundamentals of E-Manufacturing, MES and SupplyLiving Online
Supply chain management involves the optimization of the way in which a company plans the production of goods or services, procures raw materials from various suppliers, manufactures the goods or services, delivers it to customers and handles returns.
E-Manufacturing starts with an order for a product and then encompasses the entire manufacturing cycle of the product. Manufacturers need a highly responsive supply chain and manufacturing system to ensure that they meet the high expectations of their customers who, in today’s economy, demand absolutely the best service, price, delivery time and product quality.
Manufacturing Execution Systems (MES) provide up-to-the-minute mission-critical information about production activities across the factory and supply chain via communications networks (e.g. Local Area Networks), resulting in the optimisation of activities throughout all aspects of the manufacturing process. MES accomplish this task by guiding, initiating, responding to, and reporting on plant activities in real time, by using current and accurate data. This rapid response to changing conditions, together with a focus on reducing non-profitable activities, lead to more efficient plant operations and processes.
MES reduces cycle times, levels of WIP (Work In Progress), data entry time, paperwork and scrap. It also improves utilization of plant capacity, process control quality, arrangement of plant activities, tracking of orders and customer service.
Implementation of MES invariably results in improved returns on production assets, on-time delivery, faster inventory turnover, larger net profits (through increased cost reduction) and improved cash flow.
WHO SHOULD ATTEND?
Business managers
CEOs and CFOs
E-commerce managers
Finance managers
IT managers
Network and telecommunications managers
Operations managers and engineers
Production managers and engineers
Senior process engineers
Strategy managers
MORE INFORMATION: http://www.idc-online.com/content/practical-fundamentals-e-manufacturing-mes-and-supply-chain-management-3
Portable flow meter for measurement of compressed air, gases, and heat quanti...Classic Controls, Inc.
The FLUXUS G601 CA Energy is the ideal tool for carrying out complete energy efficiency tasks in the industry as well as within facility management by allowing the measurement of compressed air flow rates as well as the monitoring of thermal energy quantities and the flow rate determination of any kind of liquid or gaseous media with just one device.
For Electrical and Maintenance engineers working in Manufacturing and Hospitality sector, the challenge is tosupervise plant-wide energy utilisation and manage their electric infrastructure in a systematic, optimised way.
Janitza GmbH is a globally renowned and leading supplier of energy efficiency systems. Their digital energy meters, power quality analysers, digital measurement equipment, universal-measurement devices, power factor controller, peak demand management systems etc. are well acceptedall over the world.
Integrating fire protection and fire alarm systems with building automation systems (BAS) can offer efficient and cost-effective operation. The design and installation of an integrated system must also be well-planned and coordinated, and the system must be properly maintained over its lifetime. The need for multidisciplinary coordination between the fire protection engineer and the mechanical and electrical engineers during design and construction are of key importance. Design engineers also must involve the building owner and/or operator in establishing (or at least influencing) the design criteria of the building. The owner/operator must understand that the efficiencies gained by integration will pay dividends long into the lifecycle of the building.
Like a BAS, fire protection and alarm systems have also evolved into sophisticated computer-based systems, which offers more opportunities to integrate these systems to develop a more complete building response as part of overall building operations during an emergency event.
Practical Fundamentals of E-Manufacturing, MES and SupplyLiving Online
Supply chain management involves the optimization of the way in which a company plans the production of goods or services, procures raw materials from various suppliers, manufactures the goods or services, delivers it to customers and handles returns.
E-Manufacturing starts with an order for a product and then encompasses the entire manufacturing cycle of the product. Manufacturers need a highly responsive supply chain and manufacturing system to ensure that they meet the high expectations of their customers who, in today’s economy, demand absolutely the best service, price, delivery time and product quality.
Manufacturing Execution Systems (MES) provide up-to-the-minute mission-critical information about production activities across the factory and supply chain via communications networks (e.g. Local Area Networks), resulting in the optimisation of activities throughout all aspects of the manufacturing process. MES accomplish this task by guiding, initiating, responding to, and reporting on plant activities in real time, by using current and accurate data. This rapid response to changing conditions, together with a focus on reducing non-profitable activities, lead to more efficient plant operations and processes.
MES reduces cycle times, levels of WIP (Work In Progress), data entry time, paperwork and scrap. It also improves utilization of plant capacity, process control quality, arrangement of plant activities, tracking of orders and customer service.
Implementation of MES invariably results in improved returns on production assets, on-time delivery, faster inventory turnover, larger net profits (through increased cost reduction) and improved cash flow.
WHO SHOULD ATTEND?
Business managers
CEOs and CFOs
E-commerce managers
Finance managers
IT managers
Network and telecommunications managers
Operations managers and engineers
Production managers and engineers
Senior process engineers
Strategy managers
MORE INFORMATION: http://www.idc-online.com/content/practical-fundamentals-e-manufacturing-mes-and-supply-chain-management-3
Portable flow meter for measurement of compressed air, gases, and heat quanti...Classic Controls, Inc.
The FLUXUS G601 CA Energy is the ideal tool for carrying out complete energy efficiency tasks in the industry as well as within facility management by allowing the measurement of compressed air flow rates as well as the monitoring of thermal energy quantities and the flow rate determination of any kind of liquid or gaseous media with just one device.
Yokogawa has a long history of supplying process gas chromatographs to the oil & gas, refining and petrochemical industries around the world. The new process GC that meets the ever growing demands for analytical reliability and precision while improving the total cost-of ownership through built-in automated maintenance functions never seen before.
From the innovative 12-inch color touch screen HMI to the powerful predictive diagnostics, the GC8000 is truly a process GC for the 21st century. But the GC8000 is not just all about new electronics; it also brings a number of important innovations in gas chromatograph analytical capabilities. For the first time, parallel chromatography is made practical with the introduction of the GC Module (GCM) concept. By setting up virtual GCs within a single analyzer, all chromatograph settings, displays, and data are truly segregated for easy understanding and maintenance. There are even built-in graphical overview screens showing each of the individual GC Modules.
The GC8000 sets new standards for process gas chromatography while at the same time offering hardware and electronics that are recognized for robust and reliable operation.
Our professional weather stations provide instantaneous, on-site weather data for operational decisions in public safety and industries affected by meteorological conditions. Trusted by industry and government agencies worldwide.
VKAT, Vijaykrishna Automation Technology offers CCTV surveillance systems, Access control and BMS systems for home, small & medium offices, Large corporates, Hospitals, Educational institutions, Hospital, Govt departments and many more....
We promote Top brands and Affordable brands which are at the top in quality. Our after sales support team is one of the best in the industry.
this ppt covers the entire control room in National Building Code of India which prescribe code of safety in NBC and design standards for planning control room. and rest of the missing data will fine in NBC, 2016
In this session you will learn:
History of Industrial Automation
Types of Industrial Automation
Process Industries
Overview of Continuous & Batch Process
For more information, visit: https://www.mindsmapped.com/courses/industrial-automation/complete-training-on-industrial-automation-for-beginners/
Session 03 - History of Automation and Process IntroductionVidyaIA
In this session you will learn:
History of Industrial Automation
Types of Industrial Automation
Process Industries
Overview of Continuous & Batch Process
We are a complete solution provider in the field of Industrial Automation, Instrumentation and Electrical. Also we Provide PLC and Scada Monitoring solution for Solar power plants, Oil and Gas Industries, Sugar Industries, Dairy Plants and Water treatment plants.
Yokogawa has a long history of supplying process gas chromatographs to the oil & gas, refining and petrochemical industries around the world. The new process GC that meets the ever growing demands for analytical reliability and precision while improving the total cost-of ownership through built-in automated maintenance functions never seen before.
From the innovative 12-inch color touch screen HMI to the powerful predictive diagnostics, the GC8000 is truly a process GC for the 21st century. But the GC8000 is not just all about new electronics; it also brings a number of important innovations in gas chromatograph analytical capabilities. For the first time, parallel chromatography is made practical with the introduction of the GC Module (GCM) concept. By setting up virtual GCs within a single analyzer, all chromatograph settings, displays, and data are truly segregated for easy understanding and maintenance. There are even built-in graphical overview screens showing each of the individual GC Modules.
The GC8000 sets new standards for process gas chromatography while at the same time offering hardware and electronics that are recognized for robust and reliable operation.
Our professional weather stations provide instantaneous, on-site weather data for operational decisions in public safety and industries affected by meteorological conditions. Trusted by industry and government agencies worldwide.
VKAT, Vijaykrishna Automation Technology offers CCTV surveillance systems, Access control and BMS systems for home, small & medium offices, Large corporates, Hospitals, Educational institutions, Hospital, Govt departments and many more....
We promote Top brands and Affordable brands which are at the top in quality. Our after sales support team is one of the best in the industry.
this ppt covers the entire control room in National Building Code of India which prescribe code of safety in NBC and design standards for planning control room. and rest of the missing data will fine in NBC, 2016
In this session you will learn:
History of Industrial Automation
Types of Industrial Automation
Process Industries
Overview of Continuous & Batch Process
For more information, visit: https://www.mindsmapped.com/courses/industrial-automation/complete-training-on-industrial-automation-for-beginners/
Session 03 - History of Automation and Process IntroductionVidyaIA
In this session you will learn:
History of Industrial Automation
Types of Industrial Automation
Process Industries
Overview of Continuous & Batch Process
We are a complete solution provider in the field of Industrial Automation, Instrumentation and Electrical. Also we Provide PLC and Scada Monitoring solution for Solar power plants, Oil and Gas Industries, Sugar Industries, Dairy Plants and Water treatment plants.
Introduction to Power Quality: Terms and definitions of transients,
Long Duration Voltage Variations: under Voltage, Under Voltage and Sustained Interruptions
; Short Duration Voltage Variations: interruption, Sag, Swell; Voltage Imbalance; Notching D C offset,; waveform distortion; voltage fluctuation; power frequency variations
Electrical Technology was founded on the remarkable discovery by Faraday that a changing magnetic flux creates an electric field. Out of that discovery, grew the largest and most complex engineering achievement of man : the electric power system. Indeed, life without electricity is now unimaginable. Electric power systems form the basic infrastructure of a country. Even as we read this, electrical energy is being produced at rates in excess of hundreds of giga-watts (1 GW = 1,000,000,000 W). Giant rotors spinning at speeds up to 3000 rotations per minute bring us the energy stored in the potential energy of water, or in fossil fuels. Yet we notice electricity only when the lights go out!
While the basic features of the electrical power system have remained practically unchanged in the past century, but there are some significant milestones in the evolution of electrical power systems.
Indian Railways Electrical ,S&T ,Station Development ,National Railway Plan , Metro Rail Projects,DFCC,High Speed Train ,Bullet Train Project India , RVNL ,RITES,IRCON ,Railtel,Kalindee Rail Nirman,MRVC,RSO
Self sustained, continues functioning using internal lithium battery even after the main incomer feeder has tripped.
Safe, complies with the IEC 61010-1 safety standards.
Simple, DIP switch based setting for configuration and diagnostic testing.
katalog fluke digital multimeter, jual fluke digital multimeter, beli, info,harga, spesifikasi review.
Untuk informasi dan pemesanan hubungi :
sales@tridinamika.com
lihat produk lainnya di :
www.tridinamika.com
Usable in grounded, isolated and compensated net-works.
Directional short-circuit and ground fault detection.
Exact and fast fault localization minimizes staff and traveling expenses.
Electrical power is an intrinsic and essential part of modern life. It is generated and delivered across miles to power homes and businesses,operate a wide range of equipment and devices. We take power for granted, rarely bothering to ask “how good is the quality ofthe power I am using?”; “am I using it correctly?”; “is my equipment compatible to function with the power provided?” etc.
-What are power quality meters.
-What is Class A type Power Quality meter
-Janitza UMG PRO Series
-How to use power quality meter in a manufacturing set-up
According to Institute of Electrical and Electronic Engineers (IEEE) standard IEEE 1100, power quality is defined as “the concept of powering and grounding sensitive electronic equipment in a manner suitable for the equipment”.
WHY POWER QUALITY MATTERS
Power quality and supply reliability are extremely important. Our world is increasingly dependent on electronic equipment and controls, and high sensitivity devices and processes are heavily dependent on a clearly defined power quality. Some facilities operate 7 days a week, 24 hours a day, so incur a high cost of downtime.
WHAT IS POWER QUALITY AND WHY YOU SHOULD CARE
Power Quality
"The concept of powering and grounding sensitive equipment in a manner that is suitable to the operation of that equipment."
Electronic equipment & controls are increasing
System control and energy efficiency is a priority
The modern power grid is changing
High dependence on reliable electrical systems
Some Facilities operate 7 days a week, 24 hours a day
Many facilities have high cost of downtime
Every day, enterprises face the challenges of energy costs and efficiency optimisation.
For ecological as well as economic reasons, industries need to implement an energy management system (EMS) according to the ISO 50001 standard.
Only a comprehensive energy data acquisition system will provide the transparency needed.
Robust energy management that covers the full spectrum of buildings, production facilities and machines can help.
Massive cost savings are possible only with complete, transparent acquisition and processing of all energy consumption data from the whole enterprise.
Then, businesses can make informed energy management decisions to best drive down costs.
Every day, enterprises face the challenges of energy costs and efficiency optimisation.
For ecological as well as economic reasons, industries need to implement an energy management system (EMS) according to the ISO 50001 standard.
Only a comprehensive energy data acquisition system will provide the transparency needed.
Robust energy management that covers the full spectrum of buildings, production facilities and machines can help.
Massive cost savings are possible only with complete, transparent acquisition and processing of all energy consumption data from the whole enterprise.
Then, businesses can make informed energy management decisions to best drive down costs.
Every day, enterprises face the challenges of energy costs and efficiency optimisation.
For ecological as well as economic reasons, industries need to implement an energy management system (EMS) according to the ISO 50001 standard.
Only a comprehensive energy data acquisition system will provide the transparency needed.
Robust energy management that covers the full spectrum of buildings, production facilities and machines can help.
Massive cost savings are possible only with complete, transparent acquisition and processing of all energy consumption data from the whole enterprise.
Then, businesses can make informed energy management decisions to best drive down costs.
The Industry-leading electrical power distribution systems. Explore Messung Wöhner track busbar. Our Industrial-grade power distribution reduces downtime.
The Industry-leading electrical power distribution systems. Explore Messung Wöhner track busbar. Our Industrial-grade power distribution reduces downtime.
VAT Registration Outlined In UAE: Benefits and Requirementsuae taxgpt
Vat Registration is a legal obligation for businesses meeting the threshold requirement, helping companies avoid fines and ramifications. Contact now!
https://viralsocialtrends.com/vat-registration-outlined-in-uae/
What is the TDS Return Filing Due Date for FY 2024-25.pdfseoforlegalpillers
It is crucial for the taxpayers to understand about the TDS Return Filing Due Date, so that they can fulfill your TDS obligations efficiently. Taxpayers can avoid penalties by sticking to the deadlines and by accurate filing of TDS. Timely filing of TDS will make sure about the availability of tax credits. You can also seek the professional guidance of experts like Legal Pillers for timely filing of the TDS Return.
Personal Brand Statement:
As an Army veteran dedicated to lifelong learning, I bring a disciplined, strategic mindset to my pursuits. I am constantly expanding my knowledge to innovate and lead effectively. My journey is driven by a commitment to excellence, and to make a meaningful impact in the world.
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...BBPMedia1
Grote partijen zijn al een tijdje onderweg met retail media. Ondertussen worden in dit domein ook de kansen zichtbaar voor andere spelers in de markt. Maar met die kansen ontstaan ook vragen: Zelf retail media worden of erop adverteren? In welke fase van de funnel past het en hoe integreer je het in een mediaplan? Wat is nu precies het verschil met marketplaces en Programmatic ads? In dit half uur beslechten we de dilemma's en krijg je antwoorden op wanneer het voor jou tijd is om de volgende stap te zetten.
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...BBPMedia1
Marvin neemt je in deze presentatie mee in de voordelen van non-endemic advertising op retail media netwerken. Hij brengt ook de uitdagingen in beeld die de markt op dit moment heeft op het gebied van retail media voor niet-leveranciers.
Retail media wordt gezien als het nieuwe advertising-medium en ook mediabureaus richten massaal retail media-afdelingen op. Merken die niet in de betreffende winkel liggen staan ook nog niet in de rij om op de retail media netwerken te adverteren. Marvin belicht de uitdagingen die er zijn om echt aansluiting te vinden op die markt van non-endemic advertising.
Putting the SPARK into Virtual Training.pptxCynthia Clay
This 60-minute webinar, sponsored by Adobe, was delivered for the Training Mag Network. It explored the five elements of SPARK: Storytelling, Purpose, Action, Relationships, and Kudos. Knowing how to tell a well-structured story is key to building long-term memory. Stating a clear purpose that doesn't take away from the discovery learning process is critical. Ensuring that people move from theory to practical application is imperative. Creating strong social learning is the key to commitment and engagement. Validating and affirming participants' comments is the way to create a positive learning environment.
Memorandum Of Association Constitution of Company.pptseri bangash
www.seribangash.com
A Memorandum of Association (MOA) is a legal document that outlines the fundamental principles and objectives upon which a company operates. It serves as the company's charter or constitution and defines the scope of its activities. Here's a detailed note on the MOA:
Contents of Memorandum of Association:
Name Clause: This clause states the name of the company, which should end with words like "Limited" or "Ltd." for a public limited company and "Private Limited" or "Pvt. Ltd." for a private limited company.
https://seribangash.com/article-of-association-is-legal-doc-of-company/
Registered Office Clause: It specifies the location where the company's registered office is situated. This office is where all official communications and notices are sent.
Objective Clause: This clause delineates the main objectives for which the company is formed. It's important to define these objectives clearly, as the company cannot undertake activities beyond those mentioned in this clause.
www.seribangash.com
Liability Clause: It outlines the extent of liability of the company's members. In the case of companies limited by shares, the liability of members is limited to the amount unpaid on their shares. For companies limited by guarantee, members' liability is limited to the amount they undertake to contribute if the company is wound up.
https://seribangash.com/promotors-is-person-conceived-formation-company/
Capital Clause: This clause specifies the authorized capital of the company, i.e., the maximum amount of share capital the company is authorized to issue. It also mentions the division of this capital into shares and their respective nominal value.
Association Clause: It simply states that the subscribers wish to form a company and agree to become members of it, in accordance with the terms of the MOA.
Importance of Memorandum of Association:
Legal Requirement: The MOA is a legal requirement for the formation of a company. It must be filed with the Registrar of Companies during the incorporation process.
Constitutional Document: It serves as the company's constitutional document, defining its scope, powers, and limitations.
Protection of Members: It protects the interests of the company's members by clearly defining the objectives and limiting their liability.
External Communication: It provides clarity to external parties, such as investors, creditors, and regulatory authorities, regarding the company's objectives and powers.
https://seribangash.com/difference-public-and-private-company-law/
Binding Authority: The company and its members are bound by the provisions of the MOA. Any action taken beyond its scope may be considered ultra vires (beyond the powers) of the company and therefore void.
Amendment of MOA:
While the MOA lays down the company's fundamental principles, it is not entirely immutable. It can be amended, but only under specific circumstances and in compliance with legal procedures. Amendments typically require shareholder
Premium MEAN Stack Development Solutions for Modern BusinessesSynapseIndia
Stay ahead of the curve with our premium MEAN Stack Development Solutions. Our expert developers utilize MongoDB, Express.js, AngularJS, and Node.js to create modern and responsive web applications. Trust us for cutting-edge solutions that drive your business growth and success.
Know more: https://www.synapseindia.com/technology/mean-stack-development-company.html
3. www.messungelectricalengineering.com
• What is Residual Current and why
you should care
• Types of Residual Current Monitoring
• Residual Current Monitoring Devices
• Janitza APPs and software for RCM
CONTENTS
5. • Electrical current that occurs in an unwanted
conductive path
• It flows from either AC or DC circuit in
equipment to the chassis, or to the ground
• Residual currents are typically the result of
insulation faults, defective equipment and
components (power supplies, electrical loads)
causing outflow-related residual currents and
stray currents in TN-S systems
• RCM classification is based on frequency
and waveform of the current that they can
detect - Type A, Type B, Type B+
WHAT IS RESIDUAL CURRENT?
www.messungelectricalengineering.com
6. Ensure Continuous System Availability
In Market segments with sensitive applications (e.g.,
Critical power locations, Hospitals, Industrial
Manufacturing), an uninterrupted power system is of
crucial importance.
• Uninterrupted operation (Increased Uptime &
Availability) of an installation is only ensured by
continuous monitoring.
• Continuous Residual Current Monitoring is the only
method to detect dangerous fault currents at an early
stage, thereby avoiding damage to the power system as
well as preventing server or production downtimes.
• RCM measurement in accordance with DIN EN 62020
offers the most reliable and safe alternative wherever the
realization of Insulation Resistance Measurement or
RCDs are not practical in an installation.
www.messungelectricalengineering.com
WHY TO USE RCM
(EARTH LEAKAGE MONITORING)?
Alarm Notification of Leakage Current helps pre-empt Breaker
Tripping
7. • Electric Shock
• Breaker Tripping
• Fire Hazard
• Server and Computer Shutdown
• Interruption of Communication Networks
• Temperature Rise in Conductors resulting
in Insulation Breakdown
• Fast Corrosion of Metal Pipes
• Production Shutdown
• VSD / Inverter Faults
• Sensor Malfunction
• Overvoltage Problems
• Overloaded Neutral Conductor
Data Centre Fire Damage
Overloaded N Conductor
Corrosion in Pipes caused by Leakage Current Damage to the insulation
PROBLEMS CAUSED BY
FAULT CURRENTS
www.messungelectricalengineering.com
8. • Natural deterioration due to aging
• Accelerated by excessive heat and moisture
• Heat, moisture and dirt are main causes of
insulation failure
• Chemical deterioration
• Mechanical damage
• Sunlight
• Excessive voltage stresses
INSULATION FAILURE-REASONS
9. RCM - HOW IT WORKS?
Fault Current ≈ 0
System = OK
Sum >> 0
Failure in the
electrical system
• Conductors (L1, L2, L3, N) of the specific measurement
point are to be monitored and passed through the RCM CT
• In a fault-free system the sum of all currents is ZERO, so
that in the current transformer no current is induced.
• If a fault current is flowing, the current difference induces
in the differential CT a mA current that is detected by our
UMG device
• Residual currents are typically the result of insulation faults,
defective equipment and components (power supplies,
electrical loads)
15. TYPES OF RCM
TYPE B+
TYPE B
TYPE A
Sinusoidal alternating current pulsed
direct current
Smooth & pulsating direct current as well as
alternating currents upto 2 kHz.
Smooth & pulsating direct current as well as
alternating currents upto 20 kHz.
17. • Verification Standard IEC 60364-6;
NEW! Revision… Edition 2.0 2016-04
• When RCM (Earth Leakage Monitoring) is
installed and operational, there is “NO”
requirement for Mains Power disconnection
• Confirmation of correct rating and setting of
monitoring devices
Where a circuit is permanently monitored by
an RCM in accordance with IEC 62020 or an
IMD in accordance with IEC 61557-8, it is
not necessary to measure the insulation
resistance if the functioning of the IMD or
RCM is correct.
RCM STANDARDS
• The functioning of the RCM or IMD shall be verified.
INTERNATIONAL STANDARD
• Low Voltage electrical installations –
Part 6: Verification
18. Insulation Testing as part of Preventive Maintenance
• Both the ends of the cable need to be disconnected and then
meggered for finding the insulation
• Long testing times results in long shutdown times
• Cumbersome procedure of disconnecting the terminated cables
• Periodicity of the tests needs long term planning as well
Insulation Monitors - Online
• A popular measuring method is to superimpose a measuring DC
voltage between the phase and PE conductor
• This measurement procedure is suitable for monitoring
conventional AC, 3(N)AC systems. If it is used in AC, 3(N)AC
systems containing galvanically connected DC components, these
DC currents will distort the measurement result.
• Cost prohibitive
Residual Current Breakers / Earth
Leakage Relays
• Trip the circuit causing incidents
• Tripping is a surprise factor in the
Facility
• No Prediction only Prevention of
major fire
ALTERNATIVE FOR RESIDUAL
CURRENT MONITORING
19. BENEFITS OF RESIDUAL CURRENT MONITORING
AVOID SYSTEM
FAILURES
MAINTENANCE COST
OPTIMIZATION
SIGNALING
INSTEAD OF
SHUTDOWN
PREVENT
PRODUCTION
INTERRUPTIONS
IMPROVE FIRE
PROTECTION
MONITOR HIGHLY
AVAILABLE ENERGY
DISTRIBUTION SYSTEMS
20. RCM – WHERE IS IT USED?
APPLICATIONS
• Industrial Manufacturing
• Data Centre & Critical Power Applications
• Power Distribution Busbar
• Rail Networks
• TN-S Systems
• Drive Systems (Frequency Converters)
• DC Applications
• Hospital & Medical Facilities
21. LV Main
Distribution
Switchboard
Chiller Plants
Sub-Distribution
Switchboards,
UPS Outputs
PDU, Critical Power
Supply Points &
Busway Feed Box
Out-going Circuits,
Final Sub-
Measurement &
Busway Tap-Offs
MV & LV Supply
(PCC)
UMG 512-PRO UMG 509-PRO UMG 801 UMG 96-PA UMG 96RM-E UMG 96RM-PN RCM 202-AB RCM 201-
ROGO
UMG 20-CM
FROM UTILITY INCOMER TO THE FINAL CIRCUIT – OUR RCM DEVICES
22. UMG 512 PRO CLASS A PQM UMG 509 PRO UMG 96 RM-E UMG 96 RM-PN
TYPE A RCM DEVICES
23. UMG 96 PA
(with RCM module)
UMG 806 RCM 201-ROGO
TYPE A RCM DEVICES
25. UMG 96 RM-E UMG 96 PA
(with RCM module)
RCM 202 AB
UMG 96 PQ-L
(with RCM module)
TYPE B RCM DEVICES
26. UMG 96 PA
(with RCM module)
UMG 96 PQ-L
(with RCM module)
RCM 202 AB
TYPE B+ RCM DEVICES
27. RCM 202-AB
• Two-channel RCM device for measurement and
monitoring according to the IEC 62020 standard
• Comprehensive analytical tools
• Up to a maximum residual current of 20 A
• Measurement and monitoring of AC/DC residual
currents type A/B/B+ in TN and TT systems (grounded
AC systems)
• Warning and alarm thresholds configurable for each
channel separately
• RS 485 interface (Modbus)
• Two digital outputs
• Two analogue outputs (interfaces 4 … 20 mA)
• Harmonics up to 20 kHz (Type B+)
28. GridVis-RCM REPORT
• Analyze and evaluate residual current violations with the
GridVis RCM report
• Receive statistics regarding threshold violations with
graphically highlighted overviews
• Setting of up to 4 threshold levels
• Support of dynamic thresholds (RCM measuring device
configuration!)
• Custom text, customer logo and export in PDF and XLS
format
• Report creation can be carried out at custom time schedule
• Automatically dispatch per E-Mail
29. RCM ANALYSIS APP
• APP with extensive options for setting limit values and
analyzing fault currents in detail
• Up to 20 RCM channels can be managed and
evaluated via a gateway
• The evaluation covers all types of residual current
with an associated frequency analysis
• For example, 50 Hz, pure DC or high-frequency
residual currents in the 20 kHz range can be displayed
individually
• In addition, the application enables the proven
dynamic limit value formation with Janitza energy
measuring devices
• Energy measuring devices can be assigned to each of
the 20 RCM channels and limit values can be
calculated as a function of power