Renewable Integration and
Resiliency of the Power Grid
Sandip Sharma
Manager, Operations Planning
ERCOT
Discussion Outline
• An Introduction to ERCOT
• Who we are & what we do
• Renewables @ ERCOT
• Strategies to enhance Grid Resiliency
• Transmission Networks
• Grid Code
• Renewable Forecasts
• Ancillary Services i.e. Reserves
PUBLIC 3
What is ERCOT?
The Texas Legislature
restructured the Texas electric
market in 1999 and assigned
ERCOT four primary
responsibilities:
• System Reliability
• Competitive Wholesale Market
• Open Access to Transmission
• Competitive Retail Market
ERCOT is a nonprofit organization and regulated by the Public Utility Commission of Texas,
with oversight by the Texas Legislature.
ERCOT is not a market participant and does not own generation or transmission/distribution
wires.
PUBLIC 4
Current Records
Peak Demand Record: 71,110 megawatts (MW)
 Aug. 11, 2016, 4-5 p.m.
Weekend Record: 66,921 MW
 Sunday, Aug. 7, 2016, 5-6 p.m.
Winter Peak Record: 59,650 MW
 Jan. 6, 2017, 6-7 p.m.
Wind Generation Records (instantaneous)
 Output: 16,141 MW
‒ March 31, 2017, 8:56 p.m.
 Penetration (load served): 50%
‒ March 23, 2017, 3:50 a.m.
‒ Total Load = 28,780 MW
Recent Monthly Peak Demand Records
2017
• January: 59,650 MW (Jan. 6, 6-7 p.m.)
2016
• August: 71,110 MW
(All-time record)
• September: 66,949 MW (Sept. 19, 4-5 p.m.)
• October: 59,864 MW (Oct. 5, 4-5 p.m.)
• December: 57,932 MW (Dec. 19, 7-8 a.m.)
2015
• July: 67,650 MW (July 30, 4-5 p.m.)
PUBLIC 5
Changing Resource Mix – Installed Capacity
Other
1.1%
2015
Renewables
17.4%
Cogen
4.6%
Nuclear
5.4%
Gas-CT/CC
36.8%
Gas-Steam
13.8%
Coal
20.9%
Gas-Steam
50%
Coal
25%
Gas-CT/CC
5%
Nuclear
8%
Cogen
11%
Other
0.9%
Renewables
0.008%
1999
PUBLIC 6
Wind Generation Capacity – March 2017
• Steady growth continues, with some spikes.
• Largest annual increase: 3,294 MW in 2015
(A close second: 3,220 MW in 2008)
• Incentives, uncertainty and other factors affect
construction decisions and schedules.
• Not all planned projects will get built.
• Texas continues to lead U.S. in wind capacity.
Future outcomes uncertain
PUBLIC 7
Utility Scale Solar Generation Capacity – March 2017
The data presented here is based upon the latest registration data provided to ERCOT by the resource owners and can change without notice. Any capacity changes will be reflected in current and
subsequent years' totals. Scheduling delays will also be reflected in the planned projects as that information is received. This chart reflects planned units in the calendar year of submission rather
than installations by peak of year shown.
Future outcomes uncertain
PUBLIC 8
Divider Slide
Divider Slide (optional)
BUILDING TRANSMISSION NETWORKS
PUBLIC 9
Moving Wind Energy from the West to
East
Dallas-Fort Worth
Austin
San Antonio
Houston
PUBLIC 1
0
CREZ Transmission
Connecting West Texas and
Panhandle wind power to
the ERCOT grid
PUBLIC 1
1
Estimated Curtailment – Monthly Average
PUBLIC 1
2
Divider Slide
Divider Slide (optional)
ENHANCING GRID RESILIENCY
DEVELOPING ROBUST GRID CODES
PUBLIC 1
3
Interconnection Requirements
Frequency
Response
Voltage
Ride-through
Ramp Rate
Limitation
Short Circuit
Ratio
Secondary
Frequency
Control
Primary
Frequency
Control
Large
Ramps
INTERCONNECTION REQUIREMENTS
SYSTEM IMPACTS
Voltage
Support
PUBLIC 1
4
Frequency Control
• Renewable resources are required to assist in ERCOT’s frequency control and
provide a “governor-like” response (Primary Frequency Response) to
frequency deviations.
– Implemented NERC’s BAL-001-TRE regional standard in 2015 which has reduced the Governor
Dead-band for most resources including renewables from 36 mHz to 17 mHZ.
164
166
168
170
172
174
176
178
180
59.85
59.875
59.9
59.925
59.95
59.975
60
60.025
60.05
13:25 13:28 13:31 13:34 13:37 13:40
WIND RESOURCE RESPONSE TO LOW
FREQUENCY 07/13/2016
Frequency Nominal Frequency MW
80
90
100
110
120
130
140
59.925
59.944
59.963
59.981
60.000
60.019
60.038
60.056
60.075
16:13 16:16 16:19 16:22 16:25 16:28
WIND RESOURCE RESPONSE TO HIGH
FREQUENCY 08/25/2015
Frequency Nominal Frequency MW
PUBLIC 1
5
Disturbance Ride Through
• Renewable resources are required to ride through i.e. stay online during
abnormal disturbances in voltage and frequency.
No Tripping
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
-1 0 1 2
Voltage
(per
unit)
@
POI
0.15
(9 cycles)
Pre-fault Period Voltage Recovery Period
Fault Clearing Period
Time (Seconds)
PUBLIC 1
6
Voltage Support Service
• Renewable resources that have an aggregated gross rating > 20MVA are
required to provide Voltage Support.
• Renewable resources are required too have reactive power capability at all MW
output levels at or above 10% of nameplate capacity.
– Reactive Power profile is depicted graphically as a rectangle ((+/-) 0.328 * HSL)
– This requirement can be met through a combination of the unit’s dynamic leading/lagging capability
and/or dynamic VAr capable devices.
3.15 Voltage Support
Each Generation Resource required to provide VSS shall comply with the following Reactive Power Requirements:
a) An over-excited (lagging or producing) power factor capability of 0.95 or less determined at the generating unit's maximum net
power to be supplied to the ERCOT Transmission Grid and the Generation Resource’s set point in the Voltage Profile measured
at the POI;
b) An under-excited (leading or absorbing) power factor capability of 0.95 or less, determined at the generating unit's maximum net
power to be supplied to the ERCOT Transmission Grid and the Generation Resource’s set point in the Voltage Profile measured
at the POI;
c) Reactive Power capability shall be available at all MW output levels and may be met through a combination of the Generation
Resource’s Unit Reactive Limit (URL), which is the generating unit’s dynamic leading and lagging operating capability, and/or
dynamic VAr capable devices. This Reactive Power profile is depicted graphically as a rectangle. For Intermittent Renewable
Resources (IRRs), the Reactive Power requirements shall be available at all MW output levels at or above 10% of the IRR’s
nameplate capacity. When an IRR is operating below 10% of its nameplate capacity and is unable to support voltage at the POI,
ERCOT may require an IRR to disconnect from the ERCOT System for purposes of maintaining reliability
PUBLIC 1
7
Ramp Rate Limitation
• Renewable resources are required to implement controls which limit per minute
ramping to 20% of the unit’s nameplate rating.
6.5.7.10 Intermittent Renewable Resource Ramp Rate Limitations
1) Each Intermittent Renewable Resource (IRR) that is part of a Standard Generation Interconnection Agreement
(SGIA) signed on or after January 1, 2009 shall limit its ramp rate to 20% per minute of its nameplate rating (MWs)
as registered with ERCOT when responding to or released from an ERCOT deployment.
2) The requirement of paragraph (1) above does not apply during a Force Majeure Event or during intervals in which a
decremental deployment instruction coincides with a demonstrated decrease in the available IRR.
3) Each IRR that is part of an SGIA signed on or before December 31, 2008 and that controls power output by means
other than turbine stoppage shall limit its ramp rate to 20% per minute of its nameplate rating (MWs) as registered
with ERCOT when responding to or released from an ERCOT deployment.
PUBLIC 1
8
Divider Slide
Divider Slide (optional)
ENHANCING GRID RESILIENCY
REFINING RESERVE DETERMINATION
METHODOLOGIES
PUBLIC 1
9
Ancillary Service Methodology
• Several changes have been made to methodology for determining reserves
– Since 2017, Regulation Service is procured based on historical variability of wind & solar.
– Since 2015, Responsive Reserve Service is procured based on expected system inertia.
– Since 2016, Non-Spin Reserve Service is procured based on risk of net load (load - wind) ramp
and net load forecast error.
RRS requirement (MW)
1 3 5 7 9 11 13 15 17 19 21 23
Jan
Feb
Mar
April
May
June
July
Aug
Sep
Oct
Nov
Dec
2300
2400
2500
2600
2700
2800
2900
3000
NSRS requirement (MW)
1 3 5 7 9 11 13 15 17 19 21 23
Jan
Feb
Mar
April
May
June
July
Aug
Sep
Oct
Nov
Dec
800
1000
1200
1400
1600
1800
2000
2200
2400
2600
PUBLIC 2
0
Responsive Reserves
• Responsive Reserves are procured to ensure sufficient capacity is
available to respond to frequency disturbances due to unit trips
• ERCOT procures RRS to avoid triggering UFLS at 50.30 Hz for loss of
two largest generators (2,750 MW).
‒ Capacity reserved from generators to provide Primary Frequency Response (PFR)
 Response must be proportional to frequency deviation using a droop setting no
greater than 5%.
‒ Up to 50% of Responsive requirement can be provided by Load Resources on
under-frequency relays
 Full response within 30 cycles
PUBLIC 2
1
3-hour-ahead Forecast Error in 2016
Wind – Under forecast
Load – Over forecast
Wind – Over forecast
Load – Under forecast
Wind Under forecast
Wind Over forecast
Load
Under
forecast
Load
Over
forecast
Act. Demand is High
Act. Wind in High
Act. Demand is Low
Act. Wind in Low
Act. Demand is High
Act. Wind in Low
Act. Demand is Low
Act. Wind in High
PUBLIC 2
2
Real Time Curtailment of a WGR
PUBLIC 2
3
Frequency Control & CPS1 Score
CPS1 12 Month Rolling Average = 175.47%
PUBLIC 2
4
Wind Installed Capacity vs. Reg-Up Requirement
PUBLIC 2
5
Reliability Risk Desk Goals
• Facilitate improved accuracy of renewable forecasts
– Promote improved telemetry performance from wind/solar plants
– Perform forecast adjustments during icing and other extreme weather events
• Maintain sufficient frequency responsive reserves
– Confirm critical level of inertia is online
– Ensure frequency responsive capacity is available to cover actual inertia conditions
• Maintain sufficient temporally available capacity to cover remaining forecast
errors and net load ramps
1. Renewable Forecast
and Extreme Weather
Monitoring
2. Inertia Monitoring
and RRS Sufficiency
3. Forecast Error Risk
and NSRS Sufficiency
4. Intra-Hour Resource
Monitoring
PUBLIC 2
6
QUESTIONS?

More Related Content

Similar to Requerimientos ERCOT para Recursos Renovables.pdf

Reliability Indices Evaluation of a Real Time Rural Radial Distribution Feeder
Reliability Indices Evaluation of a Real Time Rural Radial Distribution FeederReliability Indices Evaluation of a Real Time Rural Radial Distribution Feeder
Reliability Indices Evaluation of a Real Time Rural Radial Distribution FeederIOSR Journals
 
Comparative Study on Forecasting & Scheduling - Solar & Wind 05.03.19
Comparative Study on Forecasting & Scheduling - Solar & Wind 05.03.19Comparative Study on Forecasting & Scheduling - Solar & Wind 05.03.19
Comparative Study on Forecasting & Scheduling - Solar & Wind 05.03.19Gensol Engineering Limited
 
IRJET- Improvement of Wind Turbine DFIG using Fault Ride Through Capability T...
IRJET- Improvement of Wind Turbine DFIG using Fault Ride Through Capability T...IRJET- Improvement of Wind Turbine DFIG using Fault Ride Through Capability T...
IRJET- Improvement of Wind Turbine DFIG using Fault Ride Through Capability T...IRJET Journal
 
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...IRJET Journal
 
Review of different Fault Ride through (FRT) Control Strategies for a DFIG Wi...
Review of different Fault Ride through (FRT) Control Strategies for a DFIG Wi...Review of different Fault Ride through (FRT) Control Strategies for a DFIG Wi...
Review of different Fault Ride through (FRT) Control Strategies for a DFIG Wi...IRJET Journal
 
Professor Isam Shahrour Summer Course « Smart and Sustainable City » Chapter...
Professor Isam Shahrour Summer Course « Smart and Sustainable City »  Chapter...Professor Isam Shahrour Summer Course « Smart and Sustainable City »  Chapter...
Professor Isam Shahrour Summer Course « Smart and Sustainable City » Chapter...Isam Shahrour
 
The merits of integrating renewables with smarter grid carilec
The merits of integrating renewables with smarter grid   carilecThe merits of integrating renewables with smarter grid   carilec
The merits of integrating renewables with smarter grid carilecRick Case, PMP, P.E.
 
Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3IAEME Publication
 
Grid integration of renewable energy-Priyabrata Patnaik
Grid integration of renewable energy-Priyabrata PatnaikGrid integration of renewable energy-Priyabrata Patnaik
Grid integration of renewable energy-Priyabrata PatnaikDr.Priyabrata Patnaik
 
SwRI_Mitchem_2NMC_09122014
SwRI_Mitchem_2NMC_09122014SwRI_Mitchem_2NMC_09122014
SwRI_Mitchem_2NMC_09122014Sean Mitchem
 
Study of DFIG Connected to Grid using Wind Energy System
Study of DFIG Connected to Grid using Wind Energy SystemStudy of DFIG Connected to Grid using Wind Energy System
Study of DFIG Connected to Grid using Wind Energy SystemIRJET Journal
 
Power Plant Controller-Putting the Power back into the hands of the Developer
Power Plant Controller-Putting the Power back into the hands of the DeveloperPower Plant Controller-Putting the Power back into the hands of the Developer
Power Plant Controller-Putting the Power back into the hands of the DeveloperSgurrEnergy Pvt. Ltd.
 
Design of Low-Voltage Distributed Photovoltaic Systems Oriented to Improve ...
Design of Low-Voltage Distributed Photovoltaic Systems Oriented to   Improve ...Design of Low-Voltage Distributed Photovoltaic Systems Oriented to   Improve ...
Design of Low-Voltage Distributed Photovoltaic Systems Oriented to Improve ...IRJET Journal
 
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSLOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSEditor IJMTER
 
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...IRJET Journal
 
Enhanced Crowbar Protection for Fault Ride through Capability of Wind Generat...
Enhanced Crowbar Protection for Fault Ride through Capability of Wind Generat...Enhanced Crowbar Protection for Fault Ride through Capability of Wind Generat...
Enhanced Crowbar Protection for Fault Ride through Capability of Wind Generat...IAES-IJPEDS
 
IRJET- Adaptive Observer-Based Fault Estimation for DFIG based Wind Turbine S...
IRJET- Adaptive Observer-Based Fault Estimation for DFIG based Wind Turbine S...IRJET- Adaptive Observer-Based Fault Estimation for DFIG based Wind Turbine S...
IRJET- Adaptive Observer-Based Fault Estimation for DFIG based Wind Turbine S...IRJET Journal
 

Similar to Requerimientos ERCOT para Recursos Renovables.pdf (20)

Reliability Indices Evaluation of a Real Time Rural Radial Distribution Feeder
Reliability Indices Evaluation of a Real Time Rural Radial Distribution FeederReliability Indices Evaluation of a Real Time Rural Radial Distribution Feeder
Reliability Indices Evaluation of a Real Time Rural Radial Distribution Feeder
 
Cy36602610
Cy36602610Cy36602610
Cy36602610
 
Comparative Study on Forecasting & Scheduling - Solar & Wind 05.03.19
Comparative Study on Forecasting & Scheduling - Solar & Wind 05.03.19Comparative Study on Forecasting & Scheduling - Solar & Wind 05.03.19
Comparative Study on Forecasting & Scheduling - Solar & Wind 05.03.19
 
8.1.1_PAR 2030.7_Bower_EPRI/SNL Microgrid Symposium
8.1.1_PAR 2030.7_Bower_EPRI/SNL Microgrid Symposium8.1.1_PAR 2030.7_Bower_EPRI/SNL Microgrid Symposium
8.1.1_PAR 2030.7_Bower_EPRI/SNL Microgrid Symposium
 
IRJET- Improvement of Wind Turbine DFIG using Fault Ride Through Capability T...
IRJET- Improvement of Wind Turbine DFIG using Fault Ride Through Capability T...IRJET- Improvement of Wind Turbine DFIG using Fault Ride Through Capability T...
IRJET- Improvement of Wind Turbine DFIG using Fault Ride Through Capability T...
 
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
 
Review of different Fault Ride through (FRT) Control Strategies for a DFIG Wi...
Review of different Fault Ride through (FRT) Control Strategies for a DFIG Wi...Review of different Fault Ride through (FRT) Control Strategies for a DFIG Wi...
Review of different Fault Ride through (FRT) Control Strategies for a DFIG Wi...
 
Professor Isam Shahrour Summer Course « Smart and Sustainable City » Chapter...
Professor Isam Shahrour Summer Course « Smart and Sustainable City »  Chapter...Professor Isam Shahrour Summer Course « Smart and Sustainable City »  Chapter...
Professor Isam Shahrour Summer Course « Smart and Sustainable City » Chapter...
 
The merits of integrating renewables with smarter grid carilec
The merits of integrating renewables with smarter grid   carilecThe merits of integrating renewables with smarter grid   carilec
The merits of integrating renewables with smarter grid carilec
 
Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3
 
Grid integration of renewable energy-Priyabrata Patnaik
Grid integration of renewable energy-Priyabrata PatnaikGrid integration of renewable energy-Priyabrata Patnaik
Grid integration of renewable energy-Priyabrata Patnaik
 
SwRI_Mitchem_2NMC_09122014
SwRI_Mitchem_2NMC_09122014SwRI_Mitchem_2NMC_09122014
SwRI_Mitchem_2NMC_09122014
 
Study of DFIG Connected to Grid using Wind Energy System
Study of DFIG Connected to Grid using Wind Energy SystemStudy of DFIG Connected to Grid using Wind Energy System
Study of DFIG Connected to Grid using Wind Energy System
 
Power Plant Controller-Putting the Power back into the hands of the Developer
Power Plant Controller-Putting the Power back into the hands of the DeveloperPower Plant Controller-Putting the Power back into the hands of the Developer
Power Plant Controller-Putting the Power back into the hands of the Developer
 
Design of Low-Voltage Distributed Photovoltaic Systems Oriented to Improve ...
Design of Low-Voltage Distributed Photovoltaic Systems Oriented to   Improve ...Design of Low-Voltage Distributed Photovoltaic Systems Oriented to   Improve ...
Design of Low-Voltage Distributed Photovoltaic Systems Oriented to Improve ...
 
8.2_IEEE 1547 and Microgrids_Key_EPRI/SNL Microgrid Symposium
8.2_IEEE 1547 and Microgrids_Key_EPRI/SNL Microgrid Symposium8.2_IEEE 1547 and Microgrids_Key_EPRI/SNL Microgrid Symposium
8.2_IEEE 1547 and Microgrids_Key_EPRI/SNL Microgrid Symposium
 
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSLOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
 
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
 
Enhanced Crowbar Protection for Fault Ride through Capability of Wind Generat...
Enhanced Crowbar Protection for Fault Ride through Capability of Wind Generat...Enhanced Crowbar Protection for Fault Ride through Capability of Wind Generat...
Enhanced Crowbar Protection for Fault Ride through Capability of Wind Generat...
 
IRJET- Adaptive Observer-Based Fault Estimation for DFIG based Wind Turbine S...
IRJET- Adaptive Observer-Based Fault Estimation for DFIG based Wind Turbine S...IRJET- Adaptive Observer-Based Fault Estimation for DFIG based Wind Turbine S...
IRJET- Adaptive Observer-Based Fault Estimation for DFIG based Wind Turbine S...
 

Recently uploaded

OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...RajaP95
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 

Recently uploaded (20)

OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 

Requerimientos ERCOT para Recursos Renovables.pdf

  • 1. Renewable Integration and Resiliency of the Power Grid Sandip Sharma Manager, Operations Planning ERCOT
  • 2. Discussion Outline • An Introduction to ERCOT • Who we are & what we do • Renewables @ ERCOT • Strategies to enhance Grid Resiliency • Transmission Networks • Grid Code • Renewable Forecasts • Ancillary Services i.e. Reserves
  • 3. PUBLIC 3 What is ERCOT? The Texas Legislature restructured the Texas electric market in 1999 and assigned ERCOT four primary responsibilities: • System Reliability • Competitive Wholesale Market • Open Access to Transmission • Competitive Retail Market ERCOT is a nonprofit organization and regulated by the Public Utility Commission of Texas, with oversight by the Texas Legislature. ERCOT is not a market participant and does not own generation or transmission/distribution wires.
  • 4. PUBLIC 4 Current Records Peak Demand Record: 71,110 megawatts (MW)  Aug. 11, 2016, 4-5 p.m. Weekend Record: 66,921 MW  Sunday, Aug. 7, 2016, 5-6 p.m. Winter Peak Record: 59,650 MW  Jan. 6, 2017, 6-7 p.m. Wind Generation Records (instantaneous)  Output: 16,141 MW ‒ March 31, 2017, 8:56 p.m.  Penetration (load served): 50% ‒ March 23, 2017, 3:50 a.m. ‒ Total Load = 28,780 MW Recent Monthly Peak Demand Records 2017 • January: 59,650 MW (Jan. 6, 6-7 p.m.) 2016 • August: 71,110 MW (All-time record) • September: 66,949 MW (Sept. 19, 4-5 p.m.) • October: 59,864 MW (Oct. 5, 4-5 p.m.) • December: 57,932 MW (Dec. 19, 7-8 a.m.) 2015 • July: 67,650 MW (July 30, 4-5 p.m.)
  • 5. PUBLIC 5 Changing Resource Mix – Installed Capacity Other 1.1% 2015 Renewables 17.4% Cogen 4.6% Nuclear 5.4% Gas-CT/CC 36.8% Gas-Steam 13.8% Coal 20.9% Gas-Steam 50% Coal 25% Gas-CT/CC 5% Nuclear 8% Cogen 11% Other 0.9% Renewables 0.008% 1999
  • 6. PUBLIC 6 Wind Generation Capacity – March 2017 • Steady growth continues, with some spikes. • Largest annual increase: 3,294 MW in 2015 (A close second: 3,220 MW in 2008) • Incentives, uncertainty and other factors affect construction decisions and schedules. • Not all planned projects will get built. • Texas continues to lead U.S. in wind capacity. Future outcomes uncertain
  • 7. PUBLIC 7 Utility Scale Solar Generation Capacity – March 2017 The data presented here is based upon the latest registration data provided to ERCOT by the resource owners and can change without notice. Any capacity changes will be reflected in current and subsequent years' totals. Scheduling delays will also be reflected in the planned projects as that information is received. This chart reflects planned units in the calendar year of submission rather than installations by peak of year shown. Future outcomes uncertain
  • 8. PUBLIC 8 Divider Slide Divider Slide (optional) BUILDING TRANSMISSION NETWORKS
  • 9. PUBLIC 9 Moving Wind Energy from the West to East Dallas-Fort Worth Austin San Antonio Houston
  • 10. PUBLIC 1 0 CREZ Transmission Connecting West Texas and Panhandle wind power to the ERCOT grid
  • 11. PUBLIC 1 1 Estimated Curtailment – Monthly Average
  • 12. PUBLIC 1 2 Divider Slide Divider Slide (optional) ENHANCING GRID RESILIENCY DEVELOPING ROBUST GRID CODES
  • 13. PUBLIC 1 3 Interconnection Requirements Frequency Response Voltage Ride-through Ramp Rate Limitation Short Circuit Ratio Secondary Frequency Control Primary Frequency Control Large Ramps INTERCONNECTION REQUIREMENTS SYSTEM IMPACTS Voltage Support
  • 14. PUBLIC 1 4 Frequency Control • Renewable resources are required to assist in ERCOT’s frequency control and provide a “governor-like” response (Primary Frequency Response) to frequency deviations. – Implemented NERC’s BAL-001-TRE regional standard in 2015 which has reduced the Governor Dead-band for most resources including renewables from 36 mHz to 17 mHZ. 164 166 168 170 172 174 176 178 180 59.85 59.875 59.9 59.925 59.95 59.975 60 60.025 60.05 13:25 13:28 13:31 13:34 13:37 13:40 WIND RESOURCE RESPONSE TO LOW FREQUENCY 07/13/2016 Frequency Nominal Frequency MW 80 90 100 110 120 130 140 59.925 59.944 59.963 59.981 60.000 60.019 60.038 60.056 60.075 16:13 16:16 16:19 16:22 16:25 16:28 WIND RESOURCE RESPONSE TO HIGH FREQUENCY 08/25/2015 Frequency Nominal Frequency MW
  • 15. PUBLIC 1 5 Disturbance Ride Through • Renewable resources are required to ride through i.e. stay online during abnormal disturbances in voltage and frequency. No Tripping 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 -1 0 1 2 Voltage (per unit) @ POI 0.15 (9 cycles) Pre-fault Period Voltage Recovery Period Fault Clearing Period Time (Seconds)
  • 16. PUBLIC 1 6 Voltage Support Service • Renewable resources that have an aggregated gross rating > 20MVA are required to provide Voltage Support. • Renewable resources are required too have reactive power capability at all MW output levels at or above 10% of nameplate capacity. – Reactive Power profile is depicted graphically as a rectangle ((+/-) 0.328 * HSL) – This requirement can be met through a combination of the unit’s dynamic leading/lagging capability and/or dynamic VAr capable devices. 3.15 Voltage Support Each Generation Resource required to provide VSS shall comply with the following Reactive Power Requirements: a) An over-excited (lagging or producing) power factor capability of 0.95 or less determined at the generating unit's maximum net power to be supplied to the ERCOT Transmission Grid and the Generation Resource’s set point in the Voltage Profile measured at the POI; b) An under-excited (leading or absorbing) power factor capability of 0.95 or less, determined at the generating unit's maximum net power to be supplied to the ERCOT Transmission Grid and the Generation Resource’s set point in the Voltage Profile measured at the POI; c) Reactive Power capability shall be available at all MW output levels and may be met through a combination of the Generation Resource’s Unit Reactive Limit (URL), which is the generating unit’s dynamic leading and lagging operating capability, and/or dynamic VAr capable devices. This Reactive Power profile is depicted graphically as a rectangle. For Intermittent Renewable Resources (IRRs), the Reactive Power requirements shall be available at all MW output levels at or above 10% of the IRR’s nameplate capacity. When an IRR is operating below 10% of its nameplate capacity and is unable to support voltage at the POI, ERCOT may require an IRR to disconnect from the ERCOT System for purposes of maintaining reliability
  • 17. PUBLIC 1 7 Ramp Rate Limitation • Renewable resources are required to implement controls which limit per minute ramping to 20% of the unit’s nameplate rating. 6.5.7.10 Intermittent Renewable Resource Ramp Rate Limitations 1) Each Intermittent Renewable Resource (IRR) that is part of a Standard Generation Interconnection Agreement (SGIA) signed on or after January 1, 2009 shall limit its ramp rate to 20% per minute of its nameplate rating (MWs) as registered with ERCOT when responding to or released from an ERCOT deployment. 2) The requirement of paragraph (1) above does not apply during a Force Majeure Event or during intervals in which a decremental deployment instruction coincides with a demonstrated decrease in the available IRR. 3) Each IRR that is part of an SGIA signed on or before December 31, 2008 and that controls power output by means other than turbine stoppage shall limit its ramp rate to 20% per minute of its nameplate rating (MWs) as registered with ERCOT when responding to or released from an ERCOT deployment.
  • 18. PUBLIC 1 8 Divider Slide Divider Slide (optional) ENHANCING GRID RESILIENCY REFINING RESERVE DETERMINATION METHODOLOGIES
  • 19. PUBLIC 1 9 Ancillary Service Methodology • Several changes have been made to methodology for determining reserves – Since 2017, Regulation Service is procured based on historical variability of wind & solar. – Since 2015, Responsive Reserve Service is procured based on expected system inertia. – Since 2016, Non-Spin Reserve Service is procured based on risk of net load (load - wind) ramp and net load forecast error. RRS requirement (MW) 1 3 5 7 9 11 13 15 17 19 21 23 Jan Feb Mar April May June July Aug Sep Oct Nov Dec 2300 2400 2500 2600 2700 2800 2900 3000 NSRS requirement (MW) 1 3 5 7 9 11 13 15 17 19 21 23 Jan Feb Mar April May June July Aug Sep Oct Nov Dec 800 1000 1200 1400 1600 1800 2000 2200 2400 2600
  • 20. PUBLIC 2 0 Responsive Reserves • Responsive Reserves are procured to ensure sufficient capacity is available to respond to frequency disturbances due to unit trips • ERCOT procures RRS to avoid triggering UFLS at 50.30 Hz for loss of two largest generators (2,750 MW). ‒ Capacity reserved from generators to provide Primary Frequency Response (PFR)  Response must be proportional to frequency deviation using a droop setting no greater than 5%. ‒ Up to 50% of Responsive requirement can be provided by Load Resources on under-frequency relays  Full response within 30 cycles
  • 21. PUBLIC 2 1 3-hour-ahead Forecast Error in 2016 Wind – Under forecast Load – Over forecast Wind – Over forecast Load – Under forecast Wind Under forecast Wind Over forecast Load Under forecast Load Over forecast Act. Demand is High Act. Wind in High Act. Demand is Low Act. Wind in Low Act. Demand is High Act. Wind in Low Act. Demand is Low Act. Wind in High
  • 22. PUBLIC 2 2 Real Time Curtailment of a WGR
  • 23. PUBLIC 2 3 Frequency Control & CPS1 Score CPS1 12 Month Rolling Average = 175.47%
  • 24. PUBLIC 2 4 Wind Installed Capacity vs. Reg-Up Requirement
  • 25. PUBLIC 2 5 Reliability Risk Desk Goals • Facilitate improved accuracy of renewable forecasts – Promote improved telemetry performance from wind/solar plants – Perform forecast adjustments during icing and other extreme weather events • Maintain sufficient frequency responsive reserves – Confirm critical level of inertia is online – Ensure frequency responsive capacity is available to cover actual inertia conditions • Maintain sufficient temporally available capacity to cover remaining forecast errors and net load ramps 1. Renewable Forecast and Extreme Weather Monitoring 2. Inertia Monitoring and RRS Sufficiency 3. Forecast Error Risk and NSRS Sufficiency 4. Intra-Hour Resource Monitoring