Vector Group defines the relationship between the
Primary Voltage Vectors and the Secondary Voltage
Vectors. The Primary or Secondary Voltage Vectors may
Star or Delta.
 It is necessary to ensure that transformers to be
connected in parallel have the same vector group to
avoid circulating currents in the paralleled transformers
among other including same voltage level, same
percentage impedance and the same frequency.
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
The concept of vector groups was adopted for transformers in the Generation,
Transmission and Distribution Networks in a manner so as to avoid the transfer
of Zero Sequence Current from each of the networks into the other. Delta Blocks
the flow of Zero Sequence Current.
The vector groups was also chosen in manner so as to enable the Earthing or
grounding of the various networks to facilitate the control of earth fault current
by the use of Neutral Ground Resistor(NGR). Where the Network is solidly
earthed, the earthing system is designed based on the exact short circuit level of
the Network, be it Generation, Transmission and Distribution.
Resonant Grounding (Peterson Coil) is also used in countries like Germany,
where the Reactance of the Peterson coil is tuned to match the Fictitious
Capacitance of the network. This way the earth fault current is reduced to
approximately Zero at the instant of fault (Inductive Current minus (-) Capacitive
Current). By this means countries with these scheme do not normally trip on
earth fault.
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
The concept of vector groups was adopted for
transformers in the Generation, Transmission and
Distribution Networks in a manner so as to make
the overall phase shift Zero (0) at the Distribution
end close to the Customer.
The following slides analysis the various vector
group of the Generation, Transmission and
Distribution Network of the Ghana Power System.
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
Generation (Ynd1) Transmission (Ynd11)
Shifts Star ahead Delta Nullifies the Phase shift
by 30° by 30° by shifting Delta at 30 °
ahead Star
Distribution (MV) (Dyn1) Distribution (LV) (Dyn11)
Shifts Delta ahead Star Nullifies the Phase shift
by 30° by 30° by shifting Star at 30 °
ahead Delta
•RESULTANT PHASE SHIFT = ZERO (0)
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
It can be seen clearly that the Resultant Phase Shift in the
overall Vector Group of the Ghana Power System from
Generation through to the Distribution (LV) Network is
Zero (0). This way Customer end power is not affected by the
overall vector group of the power system.
The following slides show the various vector groups
available for Star-Delta, Star-Star, Delta-Star and Delta-Delta
Transformers.
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
Delta – Star
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary
Delta
Equi. Secondary
Star
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
11 3 7
Delta – Star
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary
Delta
Equi. Secondary
Star
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
5 9 1
As clearly shown above, there are six vector group options available for Delta –
Star Transformer Configuration. These are;
Dy1 Dy3 Dy5 Dyn1 Dyn3 Dyn5
Or
Dy7 Dy9 Dy11 Dyn7 Dyn9 Dyn11
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
Star – Delta
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary Star Equi. Secondary
Delta
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
1 9 5
Star – Delta
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary Star Equi. Secondary
Delta
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a a a
11 3 7
As clearly shown above, there are six vector group options available for Star –
Delta Transformer Configuration. These are;
Yd1 Yd3 Yd5 Ynd1 Ynd3 Ynd5
Or
Yd7 Yd9 Yd11 Ynd7 Ynd9 Ynd11
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
 Yd1 or Ynd1 is the same as Dy11 or Dyn11 as in both cases Star (Y) leads
Delta (D) by 30°.
 Yd11 or Ynd11 is the same as Dy1 or Dyn1 as in both cases Delta (D) leads
Star (Y) by 30°.
Note: By Inspection
Delta – Delta
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary
Delta
Equi. Secondary
Delta
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
0 8 4
Delta – Delta
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary
Delta
Equi. Secondary
Delta
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
6 2 10
As clearly shown above, there are six vector group options available for Delta –
Delta Transformer Configuration. These are;
Dd0 Dd2 Dd4
Dd6 Dd8 Dd10
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
Star – Star
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary Star Equi. Secondary
Star
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
0 8 4
Star – Star
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary Star Equi. Secondary
Star
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
6 2 10
As clearly shown above, there are six vector group options available for Star – Star
Transformer Configuration. These are;
Yy0 Yy2 Yy4 Yyn0 Yyn2 Yyn4
Or
Yy6 Yy8 Yy10 Yyn6 Yyn8 Yyn10
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
As clearly shown in the previous slides, there are Twenty-Four (24) vector groups
for Star Delta Transformers. Below is the reiteration of these vector groups;
Dy1 Dy3 Dy5 Or Dyn1 Dyn3 Dyn5
Dy7 Dy9 Dy11 Dyn7 Dyn9 Dyn11
Dd0 Dd2 Dd4
Dd6 Dd8 Dd10
Yd1 Yd3 Yd5 Or Ynd1 Ynd3 Ynd5
Yd7 Yd9 Yd11 Ynd7 Ynd9 Ynd11
Yy0 Yy2 Yy4 Or Ynyn0 Ynyn2 Ynyn4
Yy6 Yy8 Yy10 Ynyn6 Ynyn8 Ynyn10
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
Dyn1
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
A
C B
c
b
a
30°
30°
30°
The Primary Voltage Vectors (Delta) leads the Secondary Voltage Vectors
(Star) by 30°. This is also known as lag in Aspen DistriView
Dyn11
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
A
C B
c
b
a
30°
30°
30°
The Primary Voltage Vectors (Delta) lags the Secondary Voltage Vectors
(Star) by 30°. This is also known as lead in Aspen DistriView
Thank You Very Much For
Your Kind Attention
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana

More Related Content

What's hot

Distribution Transformer Design (Electrical Machine Design)
Distribution Transformer Design (Electrical Machine Design)Distribution Transformer Design (Electrical Machine Design)
Distribution Transformer Design (Electrical Machine Design)
Md. Rayid Hasan Mojumder
 
Transformer
TransformerTransformer
Transformer
Ashvani Shukla
 
Ac fundamental
Ac fundamental Ac fundamental
Ac fundamental
sanjeet kumar
 
Short circuit test in brief
Short circuit test in briefShort circuit test in brief
Short circuit test in brief
Muthar Hussain
 
Iec 60364 4-442
Iec 60364 4-442Iec 60364 4-442
Iec 60364 4-442
Maria Jimenez
 
Sag calculation
Sag calculationSag calculation
Sag calculation
Darshil Shah
 
Ieee inrush tutorial
Ieee inrush tutorialIeee inrush tutorial
Ieee inrush tutorial
mahmoud motamedi
 
Mallas de tierra
Mallas de tierraMallas de tierra
Mallas de tierra
Javier Naal Gil
 
Coordinacion de-aislamiento
Coordinacion de-aislamientoCoordinacion de-aislamiento
Coordinacion de-aislamiento
Rafael Abadie Rodriguez
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformer
SMRITI KESHARWANI
 
Short circuit current calculations
Short circuit current calculationsShort circuit current calculations
Short circuit current calculations
Ronald Santos
 
Electrical Protection Schemes in detail
Electrical Protection Schemes in detailElectrical Protection Schemes in detail
Electrical Protection Schemes in detail
Slides Hub
 
Tan delta test for power transformers
Tan delta test for power transformersTan delta test for power transformers
Tan delta test for power transformers
jibinjoy1988
 
Transformer design-and-design-parameters
Transformer design-and-design-parametersTransformer design-and-design-parameters
Transformer design-and-design-parameters
Mubarak Suliman
 
Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
Modal Holong Education
 
transformer_design.pdf
transformer_design.pdftransformer_design.pdf
transformer_design.pdf
NerupaSharma
 
Underground cables
Underground cablesUnderground cables
Underground cables
Poonam Sarawgi
 
Calculo de conductores electricos jam
Calculo de conductores electricos jamCalculo de conductores electricos jam
Calculo de conductores electricos jam
Jaime Felipe Alvarido Machado
 
Fuse and its types
Fuse and its typesFuse and its types
Fuse and its types
Slides Hub
 
MALLA DE TIERRA PARA UN EDIFICIO
MALLA DE TIERRA PARA UN EDIFICIOMALLA DE TIERRA PARA UN EDIFICIO
MALLA DE TIERRA PARA UN EDIFICIO
Widmar Aguilar Gonzalez
 

What's hot (20)

Distribution Transformer Design (Electrical Machine Design)
Distribution Transformer Design (Electrical Machine Design)Distribution Transformer Design (Electrical Machine Design)
Distribution Transformer Design (Electrical Machine Design)
 
Transformer
TransformerTransformer
Transformer
 
Ac fundamental
Ac fundamental Ac fundamental
Ac fundamental
 
Short circuit test in brief
Short circuit test in briefShort circuit test in brief
Short circuit test in brief
 
Iec 60364 4-442
Iec 60364 4-442Iec 60364 4-442
Iec 60364 4-442
 
Sag calculation
Sag calculationSag calculation
Sag calculation
 
Ieee inrush tutorial
Ieee inrush tutorialIeee inrush tutorial
Ieee inrush tutorial
 
Mallas de tierra
Mallas de tierraMallas de tierra
Mallas de tierra
 
Coordinacion de-aislamiento
Coordinacion de-aislamientoCoordinacion de-aislamiento
Coordinacion de-aislamiento
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformer
 
Short circuit current calculations
Short circuit current calculationsShort circuit current calculations
Short circuit current calculations
 
Electrical Protection Schemes in detail
Electrical Protection Schemes in detailElectrical Protection Schemes in detail
Electrical Protection Schemes in detail
 
Tan delta test for power transformers
Tan delta test for power transformersTan delta test for power transformers
Tan delta test for power transformers
 
Transformer design-and-design-parameters
Transformer design-and-design-parametersTransformer design-and-design-parameters
Transformer design-and-design-parameters
 
Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
 
transformer_design.pdf
transformer_design.pdftransformer_design.pdf
transformer_design.pdf
 
Underground cables
Underground cablesUnderground cables
Underground cables
 
Calculo de conductores electricos jam
Calculo de conductores electricos jamCalculo de conductores electricos jam
Calculo de conductores electricos jam
 
Fuse and its types
Fuse and its typesFuse and its types
Fuse and its types
 
MALLA DE TIERRA PARA UN EDIFICIO
MALLA DE TIERRA PARA UN EDIFICIOMALLA DE TIERRA PARA UN EDIFICIO
MALLA DE TIERRA PARA UN EDIFICIO
 

Viewers also liked

Simulink Analysis of Vector groups of Transformers installed at 132kV Grid St...
Simulink Analysis of Vector groups of Transformers installed at 132kV Grid St...Simulink Analysis of Vector groups of Transformers installed at 132kV Grid St...
Simulink Analysis of Vector groups of Transformers installed at 132kV Grid St...
sunny katyara
 
Three phase vector groups
Three phase vector groupsThree phase vector groups
Three phase vector groups
MUHAMMAD USMAN
 
Test vector compression
Test vector compressionTest vector compression
Test vector compression
Amr Abd El Latief
 
Guide to transformer resistance testing
Guide to transformer resistance testing Guide to transformer resistance testing
Guide to transformer resistance testing
bbatlle
 
PP10 startup manual (Unofficial as Requested)
PP10 startup manual (Unofficial as Requested)PP10 startup manual (Unofficial as Requested)
PP10 startup manual (Unofficial as Requested)
Muhammad Gulzar
 
Installation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of TransformersInstallation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of Transformers
Living Online
 
Transformer basic
Transformer basicTransformer basic
Transformer basic
BHAGWAN PRASAD
 
Best transformer-test-procedures-en
Best transformer-test-procedures-enBest transformer-test-procedures-en
Best transformer-test-procedures-en
Suresh Patil
 
Optical Current Transformer (OCT)
Optical Current Transformer (OCT)Optical Current Transformer (OCT)
Optical Current Transformer (OCT)
Seminar Links
 
Transformer testing
Transformer testingTransformer testing
Transformer testing
ajayknows
 
industrial training on 132 kv substation
industrial training on 132 kv substationindustrial training on 132 kv substation
industrial training on 132 kv substation
pk130992
 
Startup Ideas and Validation
Startup Ideas and ValidationStartup Ideas and Validation
Startup Ideas and Validation
Yevgeniy Brikman
 

Viewers also liked (12)

Simulink Analysis of Vector groups of Transformers installed at 132kV Grid St...
Simulink Analysis of Vector groups of Transformers installed at 132kV Grid St...Simulink Analysis of Vector groups of Transformers installed at 132kV Grid St...
Simulink Analysis of Vector groups of Transformers installed at 132kV Grid St...
 
Three phase vector groups
Three phase vector groupsThree phase vector groups
Three phase vector groups
 
Test vector compression
Test vector compressionTest vector compression
Test vector compression
 
Guide to transformer resistance testing
Guide to transformer resistance testing Guide to transformer resistance testing
Guide to transformer resistance testing
 
PP10 startup manual (Unofficial as Requested)
PP10 startup manual (Unofficial as Requested)PP10 startup manual (Unofficial as Requested)
PP10 startup manual (Unofficial as Requested)
 
Installation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of TransformersInstallation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of Transformers
 
Transformer basic
Transformer basicTransformer basic
Transformer basic
 
Best transformer-test-procedures-en
Best transformer-test-procedures-enBest transformer-test-procedures-en
Best transformer-test-procedures-en
 
Optical Current Transformer (OCT)
Optical Current Transformer (OCT)Optical Current Transformer (OCT)
Optical Current Transformer (OCT)
 
Transformer testing
Transformer testingTransformer testing
Transformer testing
 
industrial training on 132 kv substation
industrial training on 132 kv substationindustrial training on 132 kv substation
industrial training on 132 kv substation
 
Startup Ideas and Validation
Startup Ideas and ValidationStartup Ideas and Validation
Startup Ideas and Validation
 

Similar to Presentation on Vector Groups by Armstrong

IRJET- Review Paper on SVPWM Technique based D-STATCOM to Improve Power Q...
IRJET-  	  Review Paper on SVPWM Technique based D-STATCOM to Improve Power Q...IRJET-  	  Review Paper on SVPWM Technique based D-STATCOM to Improve Power Q...
IRJET- Review Paper on SVPWM Technique based D-STATCOM to Improve Power Q...
IRJET Journal
 
332038674-Vector-Group-of-Transformers.ppt
332038674-Vector-Group-of-Transformers.ppt332038674-Vector-Group-of-Transformers.ppt
332038674-Vector-Group-of-Transformers.ppt
Satish Pydimarla
 
A novel four wire inverter system using SVPWM technique for ups applications
A novel four wire inverter system using SVPWM technique for ups applicationsA novel four wire inverter system using SVPWM technique for ups applications
A novel four wire inverter system using SVPWM technique for ups applications
IRJET Journal
 
IRJET- A Review on Three-Phase to Seven-Phase Power Converter using Transformer
IRJET- A Review on Three-Phase to Seven-Phase Power Converter using TransformerIRJET- A Review on Three-Phase to Seven-Phase Power Converter using Transformer
IRJET- A Review on Three-Phase to Seven-Phase Power Converter using Transformer
IRJET Journal
 
IRJET- Three-Phase to Seven-Phase Power Converter using PI Controller and Tra...
IRJET- Three-Phase to Seven-Phase Power Converter using PI Controller and Tra...IRJET- Three-Phase to Seven-Phase Power Converter using PI Controller and Tra...
IRJET- Three-Phase to Seven-Phase Power Converter using PI Controller and Tra...
IRJET Journal
 
FAULT Analysis presentation Armstrong
FAULT Analysis presentation ArmstrongFAULT Analysis presentation Armstrong
FAULT Analysis presentation Armstrong
Armstrong Okai Ababio
 
A044040108
A044040108A044040108
A044040108
IJERA Editor
 
IRJET- SVPWM Technique based D-STATCOM to Improve Power Quality in Distributi...
IRJET- SVPWM Technique based D-STATCOM to Improve Power Quality in Distributi...IRJET- SVPWM Technique based D-STATCOM to Improve Power Quality in Distributi...
IRJET- SVPWM Technique based D-STATCOM to Improve Power Quality in Distributi...
IRJET Journal
 
Selection of Passive Component for Cockroft Walton Voltage Multiplier: A Low ...
Selection of Passive Component for Cockroft Walton Voltage Multiplier: A Low ...Selection of Passive Component for Cockroft Walton Voltage Multiplier: A Low ...
Selection of Passive Component for Cockroft Walton Voltage Multiplier: A Low ...
IRJET Journal
 
Question bank Electrical Engineering
Question bank Electrical Engineering Question bank Electrical Engineering
Question bank Electrical Engineering
ELECTRICAL ENGINEERING BY ASHUTOSH
 
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...
paperpublications3
 
Two-level inverter and three-level neutral point diode clamped inverter for t...
Two-level inverter and three-level neutral point diode clamped inverter for t...Two-level inverter and three-level neutral point diode clamped inverter for t...
Two-level inverter and three-level neutral point diode clamped inverter for t...
International Journal of Power Electronics and Drive Systems
 
A New Structure of Dynamic Voltage Restorer Based on Asymmetrical ī-source In...
A New Structure of Dynamic Voltage Restorer Based on Asymmetrical ī-source In...A New Structure of Dynamic Voltage Restorer Based on Asymmetrical ī-source In...
A New Structure of Dynamic Voltage Restorer Based on Asymmetrical ī-source In...
International Journal of Power Electronics and Drive Systems
 
Cascaded Open-End Winding Transformer based DVR
Cascaded Open-End Winding Transformer based DVRCascaded Open-End Winding Transformer based DVR
Cascaded Open-End Winding Transformer based DVR
Asoka Technologies
 
Topological Advancement in DVR; A review
Topological Advancement in DVR; A reviewTopological Advancement in DVR; A review
Topological Advancement in DVR; A review
IRJET Journal
 
4.[14 24]modeling, analysis and control of hexagram inverter for three- phase...
4.[14 24]modeling, analysis and control of hexagram inverter for three- phase...4.[14 24]modeling, analysis and control of hexagram inverter for three- phase...
4.[14 24]modeling, analysis and control of hexagram inverter for three- phase...
Alexander Decker
 
11.modeling, analysis and control of hexagram inverter for three phase induc...
11.modeling, analysis and control of hexagram inverter for three  phase induc...11.modeling, analysis and control of hexagram inverter for three  phase induc...
11.modeling, analysis and control of hexagram inverter for three phase induc...
Alexander Decker
 
Compensation of Balanced and Unbalanced Voltage Disturbance using SRF Control...
Compensation of Balanced and Unbalanced Voltage Disturbance using SRF Control...Compensation of Balanced and Unbalanced Voltage Disturbance using SRF Control...
Compensation of Balanced and Unbalanced Voltage Disturbance using SRF Control...
IRJET Journal
 
Cascade Protection with Transient Voltage copy
Cascade Protection with Transient Voltage copyCascade Protection with Transient Voltage copy
Cascade Protection with Transient Voltage copy
Jesus A Borjas P.E., California
 
Analysis of a novel seven phase uncontrolled rectifier system
Analysis of a novel seven phase uncontrolled rectifier systemAnalysis of a novel seven phase uncontrolled rectifier system
Analysis of a novel seven phase uncontrolled rectifier system
IRJET Journal
 

Similar to Presentation on Vector Groups by Armstrong (20)

IRJET- Review Paper on SVPWM Technique based D-STATCOM to Improve Power Q...
IRJET-  	  Review Paper on SVPWM Technique based D-STATCOM to Improve Power Q...IRJET-  	  Review Paper on SVPWM Technique based D-STATCOM to Improve Power Q...
IRJET- Review Paper on SVPWM Technique based D-STATCOM to Improve Power Q...
 
332038674-Vector-Group-of-Transformers.ppt
332038674-Vector-Group-of-Transformers.ppt332038674-Vector-Group-of-Transformers.ppt
332038674-Vector-Group-of-Transformers.ppt
 
A novel four wire inverter system using SVPWM technique for ups applications
A novel four wire inverter system using SVPWM technique for ups applicationsA novel four wire inverter system using SVPWM technique for ups applications
A novel four wire inverter system using SVPWM technique for ups applications
 
IRJET- A Review on Three-Phase to Seven-Phase Power Converter using Transformer
IRJET- A Review on Three-Phase to Seven-Phase Power Converter using TransformerIRJET- A Review on Three-Phase to Seven-Phase Power Converter using Transformer
IRJET- A Review on Three-Phase to Seven-Phase Power Converter using Transformer
 
IRJET- Three-Phase to Seven-Phase Power Converter using PI Controller and Tra...
IRJET- Three-Phase to Seven-Phase Power Converter using PI Controller and Tra...IRJET- Three-Phase to Seven-Phase Power Converter using PI Controller and Tra...
IRJET- Three-Phase to Seven-Phase Power Converter using PI Controller and Tra...
 
FAULT Analysis presentation Armstrong
FAULT Analysis presentation ArmstrongFAULT Analysis presentation Armstrong
FAULT Analysis presentation Armstrong
 
A044040108
A044040108A044040108
A044040108
 
IRJET- SVPWM Technique based D-STATCOM to Improve Power Quality in Distributi...
IRJET- SVPWM Technique based D-STATCOM to Improve Power Quality in Distributi...IRJET- SVPWM Technique based D-STATCOM to Improve Power Quality in Distributi...
IRJET- SVPWM Technique based D-STATCOM to Improve Power Quality in Distributi...
 
Selection of Passive Component for Cockroft Walton Voltage Multiplier: A Low ...
Selection of Passive Component for Cockroft Walton Voltage Multiplier: A Low ...Selection of Passive Component for Cockroft Walton Voltage Multiplier: A Low ...
Selection of Passive Component for Cockroft Walton Voltage Multiplier: A Low ...
 
Question bank Electrical Engineering
Question bank Electrical Engineering Question bank Electrical Engineering
Question bank Electrical Engineering
 
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...
 
Two-level inverter and three-level neutral point diode clamped inverter for t...
Two-level inverter and three-level neutral point diode clamped inverter for t...Two-level inverter and three-level neutral point diode clamped inverter for t...
Two-level inverter and three-level neutral point diode clamped inverter for t...
 
A New Structure of Dynamic Voltage Restorer Based on Asymmetrical ī-source In...
A New Structure of Dynamic Voltage Restorer Based on Asymmetrical ī-source In...A New Structure of Dynamic Voltage Restorer Based on Asymmetrical ī-source In...
A New Structure of Dynamic Voltage Restorer Based on Asymmetrical ī-source In...
 
Cascaded Open-End Winding Transformer based DVR
Cascaded Open-End Winding Transformer based DVRCascaded Open-End Winding Transformer based DVR
Cascaded Open-End Winding Transformer based DVR
 
Topological Advancement in DVR; A review
Topological Advancement in DVR; A reviewTopological Advancement in DVR; A review
Topological Advancement in DVR; A review
 
4.[14 24]modeling, analysis and control of hexagram inverter for three- phase...
4.[14 24]modeling, analysis and control of hexagram inverter for three- phase...4.[14 24]modeling, analysis and control of hexagram inverter for three- phase...
4.[14 24]modeling, analysis and control of hexagram inverter for three- phase...
 
11.modeling, analysis and control of hexagram inverter for three phase induc...
11.modeling, analysis and control of hexagram inverter for three  phase induc...11.modeling, analysis and control of hexagram inverter for three  phase induc...
11.modeling, analysis and control of hexagram inverter for three phase induc...
 
Compensation of Balanced and Unbalanced Voltage Disturbance using SRF Control...
Compensation of Balanced and Unbalanced Voltage Disturbance using SRF Control...Compensation of Balanced and Unbalanced Voltage Disturbance using SRF Control...
Compensation of Balanced and Unbalanced Voltage Disturbance using SRF Control...
 
Cascade Protection with Transient Voltage copy
Cascade Protection with Transient Voltage copyCascade Protection with Transient Voltage copy
Cascade Protection with Transient Voltage copy
 
Analysis of a novel seven phase uncontrolled rectifier system
Analysis of a novel seven phase uncontrolled rectifier systemAnalysis of a novel seven phase uncontrolled rectifier system
Analysis of a novel seven phase uncontrolled rectifier system
 

Presentation on Vector Groups by Armstrong

  • 1. Vector Group defines the relationship between the Primary Voltage Vectors and the Secondary Voltage Vectors. The Primary or Secondary Voltage Vectors may Star or Delta.  It is necessary to ensure that transformers to be connected in parallel have the same vector group to avoid circulating currents in the paralleled transformers among other including same voltage level, same percentage impedance and the same frequency. 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 2. The concept of vector groups was adopted for transformers in the Generation, Transmission and Distribution Networks in a manner so as to avoid the transfer of Zero Sequence Current from each of the networks into the other. Delta Blocks the flow of Zero Sequence Current. The vector groups was also chosen in manner so as to enable the Earthing or grounding of the various networks to facilitate the control of earth fault current by the use of Neutral Ground Resistor(NGR). Where the Network is solidly earthed, the earthing system is designed based on the exact short circuit level of the Network, be it Generation, Transmission and Distribution. Resonant Grounding (Peterson Coil) is also used in countries like Germany, where the Reactance of the Peterson coil is tuned to match the Fictitious Capacitance of the network. This way the earth fault current is reduced to approximately Zero at the instant of fault (Inductive Current minus (-) Capacitive Current). By this means countries with these scheme do not normally trip on earth fault. 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 3. The concept of vector groups was adopted for transformers in the Generation, Transmission and Distribution Networks in a manner so as to make the overall phase shift Zero (0) at the Distribution end close to the Customer. The following slides analysis the various vector group of the Generation, Transmission and Distribution Network of the Ghana Power System. 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 4. Generation (Ynd1) Transmission (Ynd11) Shifts Star ahead Delta Nullifies the Phase shift by 30° by 30° by shifting Delta at 30 ° ahead Star Distribution (MV) (Dyn1) Distribution (LV) (Dyn11) Shifts Delta ahead Star Nullifies the Phase shift by 30° by 30° by shifting Star at 30 ° ahead Delta •RESULTANT PHASE SHIFT = ZERO (0) 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 5. It can be seen clearly that the Resultant Phase Shift in the overall Vector Group of the Ghana Power System from Generation through to the Distribution (LV) Network is Zero (0). This way Customer end power is not affected by the overall vector group of the power system. The following slides show the various vector groups available for Star-Delta, Star-Star, Delta-Star and Delta-Delta Transformers. 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 6. Delta – Star 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Delta Equi. Secondary Star Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 11 3 7
  • 7. Delta – Star 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Delta Equi. Secondary Star Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 5 9 1
  • 8. As clearly shown above, there are six vector group options available for Delta – Star Transformer Configuration. These are; Dy1 Dy3 Dy5 Dyn1 Dyn3 Dyn5 Or Dy7 Dy9 Dy11 Dyn7 Dyn9 Dyn11 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 9. Star – Delta 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Star Equi. Secondary Delta Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 1 9 5
  • 10. Star – Delta 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Star Equi. Secondary Delta Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 11 3 7
  • 11. As clearly shown above, there are six vector group options available for Star – Delta Transformer Configuration. These are; Yd1 Yd3 Yd5 Ynd1 Ynd3 Ynd5 Or Yd7 Yd9 Yd11 Ynd7 Ynd9 Ynd11 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana  Yd1 or Ynd1 is the same as Dy11 or Dyn11 as in both cases Star (Y) leads Delta (D) by 30°.  Yd11 or Ynd11 is the same as Dy1 or Dyn1 as in both cases Delta (D) leads Star (Y) by 30°. Note: By Inspection
  • 12. Delta – Delta 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Delta Equi. Secondary Delta Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 0 8 4
  • 13. Delta – Delta 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Delta Equi. Secondary Delta Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 6 2 10
  • 14. As clearly shown above, there are six vector group options available for Delta – Delta Transformer Configuration. These are; Dd0 Dd2 Dd4 Dd6 Dd8 Dd10 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 15. Star – Star 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Star Equi. Secondary Star Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 0 8 4
  • 16. Star – Star 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Star Equi. Secondary Star Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 6 2 10
  • 17. As clearly shown above, there are six vector group options available for Star – Star Transformer Configuration. These are; Yy0 Yy2 Yy4 Yyn0 Yyn2 Yyn4 Or Yy6 Yy8 Yy10 Yyn6 Yyn8 Yyn10 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 18. As clearly shown in the previous slides, there are Twenty-Four (24) vector groups for Star Delta Transformers. Below is the reiteration of these vector groups; Dy1 Dy3 Dy5 Or Dyn1 Dyn3 Dyn5 Dy7 Dy9 Dy11 Dyn7 Dyn9 Dyn11 Dd0 Dd2 Dd4 Dd6 Dd8 Dd10 Yd1 Yd3 Yd5 Or Ynd1 Ynd3 Ynd5 Yd7 Yd9 Yd11 Ynd7 Ynd9 Ynd11 Yy0 Yy2 Yy4 Or Ynyn0 Ynyn2 Ynyn4 Yy6 Yy8 Yy10 Ynyn6 Ynyn8 Ynyn10 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 19. Dyn1 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana A C B c b a 30° 30° 30° The Primary Voltage Vectors (Delta) leads the Secondary Voltage Vectors (Star) by 30°. This is also known as lag in Aspen DistriView
  • 20. Dyn11 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana A C B c b a 30° 30° 30° The Primary Voltage Vectors (Delta) lags the Secondary Voltage Vectors (Star) by 30°. This is also known as lead in Aspen DistriView
  • 21. Thank You Very Much For Your Kind Attention 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana