VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER DEVICES; D-STATCOM AND DVR. 
Presented 
By 
Gaddafi Sani Shehu
INTRODUCTION 
•Duetorapidtechnologicalinnovationsandhikeinworldpopulation, highqualityandreliableelectricalpowerdemandhassignificantlyincreasedrecentlywhichisroughlyestimatedtodoublebynextdecade. 
•Thisheavyburdenonthepresenttraditionalpowersystemsleadstomanypowerqualityproblems;voltageinconstancy,poorreliability, frequencyfluctuations,causedontransmissionanddistributionlines. 
•Morethan90%ofalltheproblemsinpowersystemsareconsequenttovoltagesagsandswells.
Toovercomethesehurdles,widerangeofpowerelectronicsdevicesemergedandmodifiedtoimprovetheirperformance. 
•SecondgenerationpowerElectronicsdevicesundertheumbrellaofFlexibleAlternatingCurrentTransmissionSystem(FACTS)andCustomPower(CP)arethebestoptionwhenitcomestovoltagestability,reactivepowercompensation,powerfactorcorrectionandharmonicslevelreduction. 
•Amongthesedevices,D-STATCOMandDVRhaveshownanexceptionalperformanceduetotheirfastresponseandreal-timecontrolability.
CUSTOM POWER DEVICES; D-STATCOM AND DVR 
DistributionStaticCompensator(D-STATCOM) 
DSTATCOM Schematic representation
D-STATCOM TEST DISTRIBUTION SYSTEM 
3.5 [ohm] #1#2 dcCurDC Current 12 800.0 [uF] 3252426222 V_dcDC VoltageILRMS VoltageVpu150 [ohm] 1.35 [H] VABus 1 g4g6g2g5g3g1 VpuPWMControlVoltageControlVpuShftBus 2TimedBreakerLogicOpen@t0SWITCHBSWITCHATimedBreakerLogicOpen@t0SWITCHARLSWITCHB26.0 [ohm] VACapacitiveload20 [uF] CouplingTransformerBalanced three phase fault, forcreating voltage sag at asimluation period of 0.25sec andlasted for additional 0.25sec. D-STATC... VnInst. VoltageTimedFaultLogicABC 1.0 [ohm] 0.33 [H] Measurements andControls
DYNAMIC VOLTAGE RESTORER (DVR) 
. DVR building components
DVR TEST DISTRIBUTION SYSTEM 
dcCurDC CurrentdcVltgDC VoltageFAULTSCBAABC->GTimedFaultLogicRMS VoltageVpuVpuPWMControlVoltageContolVpuShftBRK2Instanteneous VoltageVn5.25 [ohm] 12 350.0 [uF] 3252426222 VA g4g6g2g5g3g1 BRK2BRK3BRK1BRK3BRK1 #1#2 TimedBreakerLogicClosed@t00.02263 [H] 0.02263 [H] 0.02263 [H] .55 [ohm] .55 [ohm] #1#2#1#2 R=0Balanced Three Phase Fault forcreating the Voltage Sag at 0.75sec which lasted for 1.00 secBy-Pass SwitchesControlsVoltage SourceConverterBy-Pass SwitchesCouplingTransformersVoltage and PWMControlsTimedBreakerLogicClosed@t0TimedBreakerLogicClosed@t0ABCR=0CBASWTCHSWTCHTimedBreakerLogicOpen@t0VA0.0052 [ohm] ABCABC11 [kV] #2#111 [kV] 100.0 [MVA] 2.50 [uF]0.0052 [ohm] 0.0052 [ohm]2.50 [uF] 2.50 [uF] 1.0 [ohm] 1.0 [ohm] 1.0 [ohm]
TEST SYSTEM AND SIMULATION RESULTS 
(D-STATCOM SIMULATIONS AND RESULTS) 
• Voltage Variation at Load Point without D-STATCOM • Voltage Variation at Load Point with D-STATCOM 
System Voltage at PCC w ithout D-STATCOM 
Time(s) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 ... 
... 
... 
0.00 
0.20 
0.40 
0.60 
0.80 
1.00 
1.20 
Voltage (pu) 
RMS Voltage w ithout D-STATCOM 
-15.0 
-10.0 
-5.0 
0.0 
5.0 
10.0 
15.0 
Voltage (kV) 
Instanteneous Voltage Without D-STATCOM 
System voltage at PCC w ithout D-STATCOM 
Time(s) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 ... 
... 
... 
0.00 
0.20 
0.40 
0.60 
0.80 
1.00 
1.20 
Voltage (pu) 
RMS Voltage w ithout D-STATCOM RMS Voltage w ith D-STATCOM 
-10.0 
-5.0 
0.0 
5.0 
10.0 
Voltage (kV) 
Instanteneous Voltage w ith D-STATCOM
SUMMARY OF VOLTAGE SAG AND SWELL ALLEVIATION USING D-STATCOM. 
Voltage 
Simulation 
Time (sec) 
Without 
DSTATCOM 
With 
DSTATCOM 
RMS 
(pu) 
Normal supply 
0.952 
0.998 
0.25 ≤ ts ≤ 0.50 
0.793 
0.995 
0.75 ≤ ts ≤ 1.00 
1.146 
1.002 
Instantaneous 
(kV) 
Normal supply 
10.472 
10.978 
0.25 ≤ ts ≤ 0.50 
8.778 
10.945 
0.75 ≤ ts≤ 1.00 
12.606 
11.022
DVR SIMULATIONS AND RESULTS 
System voltage at PCC without D-STATCOMTime(s)0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 ... ... ... 0.00 0.20 0.40 0.60 0.80 1.00 1.20 Voltage (pu) RMS Voltage without DVRRMS Voltage-10.0 -5.0 0.0 5.0 10.0 Voltage (kV) Inst. Voltage
SUMMARY OF THE RESULTS 
Voltage 
Simulation 
Time (sec) 
Without DVR 
With DVR 
RMS 
(pu) 
Normal supply 
0.932 
0.998 
0.25 ≤ ts ≤ 0.50 
1.140 
1.001 
0.75 ≤ ts ≤ 1.00 
0.778 
0.996 
Instantaneous 
(kV) 
Normal supply 
10.252 
10.978 
0.25 ≤ ts ≤ 0.50 
12.540 
11.011 
0.75 ≤ ts ≤ 1.00 
8.558 
10.956
CONCLUSION 
•AnelectromagnetictransientmodelofembeddedDistributionStaticCompensator(D-STATCOM)andthatofDynamicVoltageRestorer(DVRs)hasbeenpresentedusingPSCAD/ETDMCsoftwaretotesttheefficacyofthesedevicesinassuagingvoltagedipsandswells. 
•Thedevicespresentedhaveshowngreatperformanceinalleviatingthedisturbances.ItcanbededucedfromtheresultsobtainedthatDVRclearsthevoltageinstabilityandrestoressystemvoltagemuchbetterthanD-STATCOM. 
•Additionalbenefitderivablefromtheseschemesistheabsenceoffiltercomponentasthereactanceofthecouplingtransformersservethatpurpose. .