The Foundation Layer
Product Brochure
250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution
eSTS Automatically Transfers Between Two Power Sources
The Series 70 eSTS is a solid-state transfer switch that automatically or manually provides solid state transfers between two
in-phase AC sources in a quarter cycle. The eSTS performs open-transition transfer in such a manner that the connected
load disruption is minimized without ever cross-connecting the power sources. One power source is selected to be
the preferred source. If the preferred source fails the load is automatically and seamlessly connected to the alternate
source by means of an open-transition static transfer.
The LayerZero Integrated Solution: eSTS + Distribution
Maximizes Power Reliability
* Optional Sub-feed Monitor
2 © Copyright 2016 LayerZero Power Systems, Inc.
250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution
;; Optional Triple Modular Redundancy: TMR Contains Fully-Independent Control Paths With No Single Point-Of-Failure
;; Safe Bypass Procedure: Mechanical Bypass Interlock Eliminates Human Error When Performing Bypass Procedures
;; Voice Guided Bypass: Step-By-Step Instructions With Audio and Video Guidance To Assist Operators Through Bypass
;; Convection Cooling: Natural Convection-Cooled Heat Dissipation System is Maintenance-Free
;; Epoxy Coated Buswork: Maximizes Reliability By Eliminating The Possibility of Bus-To-Bus Faults
;; Silver Plated Terminals: Silver Has Excellent Conductivity To Provide Superior Electrical Performance and Reliability
;; Maintenance-Free Joints: Brazed Joints Are Permanent And Maintenance-Free, Maximizing Product Life
;; Machined Hardware: Machined Cap Screws and Engineered Disc Springs Maintain Constant Torque Throughout Product Life
;; Screw Thread Inserts: Prevents Screws From Loosening Under Vibration For Long-Term Reliability
;; Optical Fiber Based Controls: Eliminates Noise and Interference While Isolating Components from High Voltage
;; Serialized Critical Board Tracking: Critical Boards Are Serialized And Cataloged in an Active Database For Traceability
Reliability
4-Pole eSTS Static Transfer Switch Product Features
Safety
;; InSight™ IR Portholes: Bolted Connections & Critical Boards Can Be IR Scanned With the Dead-Front Doors Closed
;; Sectionalized Components: Isolated Sections That Can Be Safely De-Energized For Performing Maintenance
;; Polycarbonate Windows: Allows Critical Board LEDs To Be Viewed With The Dead-Front Door Closed
;; Front-Only Access: Installation and Maintenance Can Be Safely Performed Without Side or Rear Access
;; Dead Front Hinged Doors: Barrier To Provide A Safe Working Area With No Exposed Live Parts
Connectivity
;; Ethernet Connectivity: Secure VPN Router Connects To Network For Advanced Remote Monitoring Capabilities
;; Modbus/TCP: Open Connectivity to Existing Monitoring Systems Without Proprietary Limitations
;; NTP Time Clock Synchronization: Facilitates Timeline-Based Logging For Post-Event Reconstruction
;; SNMP Connectivity: Permits Remote Management Via Simple Network Management Protocol
;; Real-Time Waveform Capture: Automatically Captures A Picture Of The Power Three-Cycles Before and After Every Event
;; Local Touch-Screen Interface: Password-Protected Color Touch-Screen GUI For Local STS Setup/Operation/Administration
;; Black-Box Forensics: Captures and Records All Events To Provide Vital Information In Root-Cause Analysis
;; Waveforms Automatically Emailed: Capability to Send Waveform Captures To Designated Individuals For Every Transfer
3 © Copyright 2016 LayerZero Power Systems, Inc.
250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution
Substation 1 or UPS 1 Substation 2 or UPS 2
4-Pole
Static Transfer Switch
480 V, 600 V, or MV
120/208 V
or 240/415V
120/208 V
or 240/415V
480 V, 600 V, or MV
Remote
Power
Panels
Wall-
Mounted
Power
Panels
Overhead
Busways
Distribution
The 4-Pole eSTS Lowers Infrastructure Costs While Maintaining High Reliability
Increasingly, data center operators aspire to increase their energy efficiency; and thus reduce their operating costs and their carbon
footprint. A popular technique deployed to achieve higher efficiency of critical operations is to minimize the number of AC power
transformations between the building entrance to the eventual critical load. Facilities are being designed to step down voltage at the
incoming sub-station to 240/415 V level; and UPS systems are being deployed with native 4-wire, 240/415 V output. Critical loads
are operated at 240 V L-N. The cost of cabling in the facility is optimized at a higher voltage; and the loss of efficiency from another
voltage transformation to 120/208 V is avoided.
Against this back drop and in an environment which provides two independent sources of power, if a static transfer switch is needed
to increase the reliability of power to the critical load; and/or to increase the concurrent maintainability of the facility’s electrical
infrastructure then the static transfer switch must be a four pole switch. The transfer mechanism must transfer phase conductors (A,
B & C) in an open transition manner; while ensuring that the transfer of the neutral between adjacent sources is completed without
interruption to the neutral conductor.
LayerZero’s 4-pole eSTS is the most reliable, connected and information centric product designed for this application. LayerZero
uniquely uses SCR based solid-state transfers for phases A, B, C and Neutral. Further, for operator safety LayerZero deploys 4-pole
breakers for input, output and bypass isolation.
4 © Copyright 2016 LayerZero Power Systems, Inc.
250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution
CB Section Contains:
4-Pole Input isolation switches
4-Pole Bypass isolation Switches
4-Pole Output isolation switches
Source connection terminals
Load connection terminals
eSTS Controls Section Contains:
Control Electronics
• System Control & Data Acquisition 	
Boards
• SCR Gate Drives
• Redundant Power Supply System
• I/O system; VPN Router
Equipment Layout
Power electronics
• SCRs (Silicon Control Rectifier) in
Convection Cooled Heat Sinks for
Phases A, B, AC and Neutral Transfer
15” Color Touch Screen (Standard)
1. Stereo Speakers for Guided Bypass Prompts
2. Output On Light (Remains Lit in Bypass Isolate Mode)
3. Alarm & Bypass Indicator
4. SCB Status Indicator
5. Logged In User
6. Navigation Menu
7. Customer & Project Information
8. Date & Time
1 2
3
4 5
6
207 8
5 © Copyright 2016 LayerZero Power Systems, Inc.
250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution
Equipment Construction Detail
1. Alarmed Doors
2. Hinged Dead Front Doors
3. 15” (38.1 cm) Color Touch Screen GUI
4. Polycarbonate Window
5. InSight™ IR Portholes
6. Convection Cooled Heat Sinks
7. Isolation Molded Case Switches
8. Redundant Power Supplies
9. Convection Cooled Intake
1
2
3
4
5
6
8
8
9
10
12
13
14
10. SafePanel™ with Finger Safe Construction
11. SafePanel™ Shrouds
12. Universal Dead Front Door
13. Load Cable Supports
14. Up to 12 Subfeed Circuit Breakers (400 AF or 250 AF)
15. Load Neutral Terminals
16. Load Ground Terminals
•	 Mounted on the right side of 4-Pole eSTS
•	 Adds 12” Width; Right Side Access Required
11
15
16
6 © Copyright 2016 LayerZero Power Systems, Inc.
250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution
Reliability Overview
LayerZero eSTS Reliability Overview
The LayerZero eSTS Provides Many Dimensions of Reliability:
•	 Control System Reliability
•	 SMR (Single Module Redundancy, Standard)
•	 TMR (Triple Modular Redundancy, Optional)
•	 Control Power Supply Reliability
•	 Signal Reliability
•	 Operator Procedural Reliability
7 © Copyright 2016 LayerZero Power Systems, Inc.
250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution
Reliability Features: Control System Reliability
WAN Port
Gate Drive
Source 1 A
Gate Drive
Source 1 B
Gate Drive
Source 1 C
Gate Drive
Source 1 N
Gate Drive
Source 2 A
Gate Drive
Source 2 B
Gate Drive
Source 2 C
Gate Drive
Source 2 N
Source 1
Control
Source 2
Control
Source 1
Control
Source 2
Control
Source 1
Control
Source 2
Control
Fiber Optics
SCB 1
SCB 2
(TMR)
SCB 3
(TMR)
Triple Modular Redundancy (TMR) Reliability (Optional)
LayerZero TMR has all the redundancy of SMR, plus each STS has
three independent sets of analog and digital data acquisition and
control systems. There is no direct communication between the
three systems. The three systems do not even share a common
system clock.
•	 Each control system acquires voltage and current data
independently
•	 Each control system determines whether a source is good/bad
independently
•	 Upon loss of a source, each control system makes decisions to
transfer independently
Even if an entire control path or its subcomponent were to fail;
and then if the active power source were to fail, the STS is able to
complete its mission of transferring to the alternate source.
WAN Port
Gate Drive
Source 1 A
Gate Drive
Source 1 B
Gate Drive
Source 1 C
Gate Drive
Source 1 N
Gate Drive
Source 2 A
Gate Drive
Source 2 B
Gate Drive
Source 2 C
Gate Drive
Source 2 N
Source 1
Control
Source 2
Control
Fiber Optics
SCB 1
Single Module Redundancy (SMR) Reliability (Standard)
Single Module Redundancy is a cost-effective topology that provides
redundant power paths to mission-critical equipment. In SMR
systems, sources each have built-in triple redundancy of processors.
In addition, every phase is controlled with a separate gate drive
board.
LayerZero Single Modular Redundant topology is unique that it the
system is fail-safe, maintaining full switching functionality even if a
critical board were to fail.
8 © Copyright 2016 LayerZero Power Systems, Inc.
250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution
Control Power Supply Reliability
Divided into five (5) logical failure groups:
•	 System controls
•	 Source 1 gate drives
•	 Source 2 gate drives
•	 Neutral gate drives
•	 Peripherals.
The three (3) available source of power from which to supply control
power to each failure group are:
•	 Source 1
•	 Source 2
•	 STS Output.
LayerZero’s STS design incorporates eighteen (18) power supplies. The
resultant control power topology utilizes all possible power paths to
the four logical STS failure groups; and is the most comprehensive and
redundant STS power supply system in existence.
Reliability Features: Control Power Supply Reliability/Signal Reliability
Peripherals
PS 1
S1 A-B
Source 1
A B C N
Source 2
A B C N
PS 4
S1 B-C
PS 7
S1 A-C
PS 10
S1 A-B
PS 3
S2 B-C
PS 6
S2 A-C
PS 9
S2 A-B
PS 12
S2 B-C
System Controls
Gate Drives,
Source 1
Gate Drives,
Source 2
GD 1 GD 3 GD 5
SCB 1 SCB 2
TMR Only
SCB 3
TMR Only
GD 2 GD 4 GD 6
PS 13
S1 B-C
PS 15
S2 A-C
Gate Drives,
Neutral S1
PS 16
S1 A-C
PS 18
S2 A-B
Gate Drives,
Neutral S1
PS 5
Out B-N
System Controls
PS 8
Out C-N
Gate Drives S1
PS 11
Out B-N
PS 14
Out C-N
Gate Drives S2 Gate Drives N S1
PS 17
Out A-N
Gate Drives N S2
PS 2
Out A-N
Peripherals
Output
Bus
A
B
C
N
GD 7
GD 8
Signal Reliability
Fiber optic based controls eliminate noise and interference, while
isolating components from high voltage.
Optical fiber allows service to be reliably connected, while protecting
the equipment.
In LayerZero’s eSTS design, the gate drives (at Power Circuit Voltage)
recieve control signsals via optical fibers.
9 © Copyright 2016 LayerZero Power Systems, Inc.
250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution
Mechanical Bypass Interlock
In order to minimize the possibility of operator error during equipment
bypass operations, LayerZero provides:
1.	 Interlocked breakers
2.	 Mechanisms to ensure that a source cannot be bypassed without
the STS on the correct source.
3.	 Safeguards to make certain that sources cannot be connected to
each other inadvertently.
4.	 A voice-prompted bypass procedure that guides the operator
through the sequence.
5.	 A step-wise pictorial & video presentation is provided on the
touch-screen display during bypass.
Voice Guided Bypass
Operator error during maintenance bypass has been known to be
a reliability hazard. To help prevent operators from completing the
bypass procedure out-of-sequence, our product features a voice
prompted bypass procedure. This instructs the operator in a step-
by-step course of action of the process, with only one operation
per screen. Visual and audio cues provide clear instructions on the
bypassing sequence, reducing the probability of operator error.
Reliability Features: Operator Procedural Reliability
10 © Copyright 2016 LayerZero Power Systems, Inc.
250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution
No Fans, Dust Filters, or Fan Fuses
The Series 70: eSTS Static Transfer Switch utilizes a natural convection-
cooled heat dissipation system. Fans and fan sensors can be some of
the most common components to fail.
For maximum uptime, LayerZero’s eSTS systems do not contain any
fans, dust filters to change, or fan fuses to replace.
Reliability Features: Heat Dissipation, Serialized Components
Serialized circuit boards
We serialize and track all critical circuit boards and memory cards
through our eBOSS portal, which allows customers to reference
which components their machines are made from, who tested the
components, as well as the ability to view notes generated from
testing.
Serialized components offer the ability to drill-down on prospective
component failure utilizing predictive modeling techniques, so if part
fails, the instance can be cross-referenced with similar parts. This
preventative maintenance helps ensure maximum uptime.
11 © Copyright 2016 LayerZero Power Systems, Inc.
250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution
Safety Features
4-Pole Isolation Molded Case Switches
The 4-Pole eSTS utilizes four pole molded case switches (MCS) for
source, load, and bypass isolation.
Solid-state switches transfer three phases (A-B-C) and the Neutral
(N).
By utilizing 4-pole MCS, the neutral can be completed isolated from
feeder circuits during maintenance.
View Critical Board LEDs with Dead Front Doors Closed
The Series 70: ePODs: 4-Pole eSTS is equipped with a polycarbonate
window located on the inner door of the power control section.
12 © Copyright 2016 LayerZero Power Systems, Inc.
250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution
InSight™ IR Portholes Permit Scanning of Bolted
Connections with Dead-Front Doors Closed
Strategically positioned IR-scan portholes to enable safe thermal
scanning of all bolted connections with the deadfront closed, without
exposing the operator to power circuit voltage. Thermal scans can be
done from the front – without ever having to open the dead-front door.
The IR window swivels upward and unlocks with key-hole access to
reveal a mesh, allowing the operator to point-and-shoot thermal
cameras to obtain readings.
CB101 CB102
CB201 CB202
CB302
Source 1 Source 2
CB301
Load
1
2
1
2 2
IR Portholes in eSTS
(Door and side panel hidden for visibility)
Safety Features/Ease of Maintenance
13 © Copyright 2016 LayerZero Power Systems, Inc.
250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution
The Breaker Is Inserted Into The SafePanel The Handle Is Unlocked
Screws Help Secure The Breaker For Maximum Safety, The SafePanel Has
Recessed Bus Work and Finger Safe Lattice.
SafePanel™ Distribution 1200 A Circuit Breaker Installation Process
The LayerZero SafePanel™
The Series 70 eSTS + Distribution features an IP-20, finger-safe
panel board, meaning that the opening will not allow ingress of ½”
(12.5mm) diameter probe, for maximum operator safety.
An arc can form as two live conductors are separated – such as
the removal of a circuit breaker from a panel board. The SafePanel
design ensures that a potential arc would be contained in the
connection well so that even if a branch breaker were to be
removed, the arc would be contained in the connection well.
Insulated with the components deeply isolated, removal of the
breaker is safe and easy.
Safety Features
14 © Copyright 2016 LayerZero Power Systems, Inc.
250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution
Modbus/TCP http:// through a
standard web browser
Network Time Protocol
(NTP) Compliant
For Clock Synchronization
Simple Network
Management Protocol
(SNMP)
Waveforms
Automatically Emailed
Series 70: eSTS
Standard
Ethernet
Dry Contacts
• Meters
• Alarms
• Meters
• Alarms
• Waveforms
• History/Event Log
• Diagnostics
• Summary Alarm
• On Source 1
• On Source 2
• Source 1 Available
• Source 2 Available
eSTS Connectivity Options
Power Quality Monitoring/Connectivity Options
The Series 70: eSTS is equipped with Zen SSQM (Static Switch
Quality Monitoring), an all encompassing monitoring system with
local and remote communications options.
From basic monitoring & alarm reporting, to advanced power
quality monitoring functionality, Zen SSQM provides a wide-range
of options to help you be aware, be vigilant, be proactive in your
quest to create a safe, stable and reliable operation.
15 © Copyright 2016 LayerZero Power Systems, Inc.
250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution
Zen SSQM Parameters Mains
Voltage Inputs and Output
Voltage (Volts)
Voltage Average of Phases (Volts)
Frequency (Hertz)
Total Harmonic Distortion (Percent VTHD)
Phase Rotation
Current Inputs
Current (Amps)
Current Average of Phases (Amps)
Current Imbalance (Percent)
Real Power (kilowatts)
Apparent Power (kilovolt-amperes)
Reactive Power (kilovolt-amperes reactive)
Power Factor
Crest Factor
Crest Factor Average of Phases
Phase Difference Between Sources
Phase Difference Between Sources and Output
Alarms
Summary Alarm
On Source (1/2)
Source Fail (1/2)
Source Preferred (1/2)
Source 1st Alternate (1/2)
Source Over/Under Voltage (1/2)
Source Over/Under Frequency (1/2)
Source Not Available (1/2)
Output Failure
Source Overcurrent (1/2)
Source Exceeds Manual Limit (1/2)
Source Exceeds Automatic Limit (1/2)
Bypassed to Source (1/2)
Zen SSQM Technical Specifications
All product specifications are subject to change without notice.
16 © Copyright 2016 LayerZero Power Systems, Inc.
250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution
Mechanical Characteristics
Access Front Only
Cable Entry Top (Connection Box Required)/Bottom
Cable Exit Top (Connection Box Required)/Bottom
Frame Construction Welded Frame
Electrical Connections Silver-Plated Solid Busbar
Color Textured Powder Coat White (RAL 7035), Blue (RAL 5017), Black, Custom
Floor Stands Optional
Seismic floor stands Optional
Junction Boxes Optional
Sectionalization Engineered Composite Insulation, Dead Front Doors
Electrical Characteristics
Number of Inputs 2
Number of Output MCS 1, 2
Frequency 50 Hz, 60 Hz
Poles 4-pole
Phases 3 Phase, 4 Wire + Ground
Neutral Rating 100%
Transfer Time Nominal 1/4- cycle for in-phase sources
Redundancy Single Module Redundancy, Triple Modular Redundancy (Optional)
Circuit Breaker Type Molded Case Switch (Standard), Electronic Trip (Optional)
Circuit Breaker Mounting Type Plug-In 250 A, 400 A; Draw-Out 800 A
SPD Type 2
Power Quality Monitoring
Power Quality Monitoring Technology Zen SSQM™ (Static Switch Quality Monitoring)
Waveform Capture Local Display, Remote Display via Web Browser, Waveforms Automatically Emailed
Voltmeter Input sources and Output, for each phase
Ammeter Input sources and Output, for each phase
Frequency Meter Both Sources
Synchroscope Phase Angle Meter Between Sources
Metering Apparent Power, Real Power, Power Factor, Output Total Harmonic Distortion
Time Stamped Transfer Count From First Day Use, From Last Reset
CB Status Indicator Open/Closed/Tripped Circuit Breaker
Source Indicator Preferred Source
Power Path Indicator On Live Mimic
Distribution Section
Dimensions Add 12” (30.48 cm) to Width
Access Front & Right Side
Technical Specifications: 4-Pole Static Transfer Switch
4-Pole eSTS Models with Withstand Ratings
eSTS Rating (100%) Voltage Withstand Dimensions Weight Heat Dissipation
250 A *
120/208 V
220/380 V
230/400 V
240/415 V
277/480 V
65 kA
48” W x 36” D x 90” H
(1219.2 mm x 914.4 mm x 2286 mm)
1,800 lbs.
(816 kg)
6,000 BTU/Hr.
400 A *
2,000 lbs.
(907 kg)
8,000 BTU/Hr.
800 A
84” W x 40” D x 86” H
(2133.6 mm x 1016 mm x 2184.4
mm)
2,950 lbs.
(1338 kg)
8,000 BTU/Hr
* Available Spring 2016All product specifications are subject to change without notice.
17 © Copyright 2016 LayerZero Power Systems, Inc.
250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution
Operational Characteristics
Transfer Modes Automatic; Manual (via Preferred Source Selection)
Cooling Convection Cooling
Service Access Front Only
Bypass Interlock Mechanism Mechanical
Noise & Interference Isolation Optical Fiber in Critical Control Paths
IR Scan Port Type InSight™ IR Portholes
SCR Type Puck
Display Type 15” (38.1 cm) Color Touch Screen
Display Resolution 1024x768
Bypass Assistance Voice-Guided Bypass
Audio Bezel-Mounted Stereo Speakers
Languages English, French
Mimic Panel Digital
Setpoints Control Digital
Power Supplies Redundant (4 Failure Groups. Triple Redundant Supplies.)
Connectivity
Meters Local Display, Ethernet, Modbus/TCP, http via Web Browser (Non-Proprietary)
Alarms Local Display, Ethernet, Modbus/TCP, http via Web Browser (Non-Proprietary)
Summary Alarm Dry Contacts; Local Display; Modbus/TCP; Web Browser
Waveforms Local Display, Ethernet, http via Web Browser (Non-Proprietary)
History/Event Log Local Display, Ethernet, http via Web Browser (Non-Proprietary)
Diagnostics Local Display, Ethernet, http via Web Browser (Non-Proprietary)
Time Synchronization Network Time Protocol (NTP)
Standards Conformance: Static Transfer Switch
UL ETL Listed to UL 1008S
CSA ETL Listed to C22.22 No 107.
Standards Conformance: SafePanel Distribution
UL ETL Listed to UL 60950
CSA C22.2 No 29-M1989
Technical Specifications
All product specifications are subject to change without notice.
18 © Copyright 2016 LayerZero Power Systems, Inc.
LayerZero Power Systems, Inc.
1500 Danner Drive
Aurora, OH 44202 U.S.A.
© 2016 LayerZero Power Systems, Inc.
LayerZero Power Systems, LayerZero.com and the LayerZero logo are registered trademark of LayerZero.
Learn more at www.LayerZero.com
All product specifications are subject to change without notice.
Rev. 7/16 #9

More Related Content

What's hot

Jassim al hamad open substation automation system for oil & gas industry
Jassim al hamad  open substation automation system for oil & gas industryJassim al hamad  open substation automation system for oil & gas industry
Jassim al hamad open substation automation system for oil & gas industry
sarah7887
 
PRESENTATION THESIS
PRESENTATION THESISPRESENTATION THESIS
PRESENTATION THESIS
Umair Abbasi
 
ABB Relay
ABB RelayABB Relay
ABB Relay
Amit Kumar
 
Scada
ScadaScada
Scada
Amit Kumar
 
Mc9 s08sh8
Mc9 s08sh8Mc9 s08sh8
Terra firmware plant-controller_data_sheet-v1
Terra firmware plant-controller_data_sheet-v1Terra firmware plant-controller_data_sheet-v1
Terra firmware plant-controller_data_sheet-v1
MatthewCharles20
 
7SR110 Argus Relay
7SR110 Argus Relay7SR110 Argus Relay
7SR110 Argus Relay
ashwini reliserv
 
Wireless agro automation system
Wireless agro automation systemWireless agro automation system
Wireless agro automation system
karthikpunuru
 
Project
ProjectProject
Project
ATUL KUJUR
 
AUTOMATIC WIRELESS POWER GRID CONTROL
AUTOMATIC WIRELESS POWER GRID CONTROLAUTOMATIC WIRELESS POWER GRID CONTROL
AUTOMATIC WIRELESS POWER GRID CONTROL
shiv kapil
 
Design of embedded based three phase preventor and selector system for indust...
Design of embedded based three phase preventor and selector system for indust...Design of embedded based three phase preventor and selector system for indust...
Design of embedded based three phase preventor and selector system for indust...
IAEME Publication
 
Renesas RX23T Inverter Kit - Deep dive
Renesas RX23T Inverter Kit - Deep diveRenesas RX23T Inverter Kit - Deep dive
Renesas RX23T Inverter Kit - Deep dive
Renesas Electronics Corporation
 
PLC based Multichannel Automatic Liquid Level Controller
PLC based Multichannel Automatic Liquid Level ControllerPLC based Multichannel Automatic Liquid Level Controller
PLC based Multichannel Automatic Liquid Level Controller
Vijay Badgujar
 
File 1389427052
File 1389427052File 1389427052
File 1389427052
Aman_preet
 
MPC of TWT based Transmitter
MPC of TWT based TransmitterMPC of TWT based Transmitter
MPC of TWT based Transmitter
Abhishek Sutrave
 
Scada presentation
Scada presentationScada presentation
Scada presentation
Amit Kumar
 
Project ppt
Project pptProject ppt
Project ppt
Rahul Yadav
 
A low cost short range wireless embedded system for multiple parameter control
A low cost short range wireless embedded system for multiple parameter controlA low cost short range wireless embedded system for multiple parameter control
A low cost short range wireless embedded system for multiple parameter control
eSAT Publishing House
 
A low cost short range wireless embedded system for multiple parameter control
A low cost short range wireless embedded system for multiple parameter controlA low cost short range wireless embedded system for multiple parameter control
A low cost short range wireless embedded system for multiple parameter control
eSAT Journals
 
7SR220 Overcurrent Relay
7SR220 Overcurrent Relay7SR220 Overcurrent Relay
7SR220 Overcurrent Relay
ashwini reliserv
 

What's hot (20)

Jassim al hamad open substation automation system for oil & gas industry
Jassim al hamad  open substation automation system for oil & gas industryJassim al hamad  open substation automation system for oil & gas industry
Jassim al hamad open substation automation system for oil & gas industry
 
PRESENTATION THESIS
PRESENTATION THESISPRESENTATION THESIS
PRESENTATION THESIS
 
ABB Relay
ABB RelayABB Relay
ABB Relay
 
Scada
ScadaScada
Scada
 
Mc9 s08sh8
Mc9 s08sh8Mc9 s08sh8
Mc9 s08sh8
 
Terra firmware plant-controller_data_sheet-v1
Terra firmware plant-controller_data_sheet-v1Terra firmware plant-controller_data_sheet-v1
Terra firmware plant-controller_data_sheet-v1
 
7SR110 Argus Relay
7SR110 Argus Relay7SR110 Argus Relay
7SR110 Argus Relay
 
Wireless agro automation system
Wireless agro automation systemWireless agro automation system
Wireless agro automation system
 
Project
ProjectProject
Project
 
AUTOMATIC WIRELESS POWER GRID CONTROL
AUTOMATIC WIRELESS POWER GRID CONTROLAUTOMATIC WIRELESS POWER GRID CONTROL
AUTOMATIC WIRELESS POWER GRID CONTROL
 
Design of embedded based three phase preventor and selector system for indust...
Design of embedded based three phase preventor and selector system for indust...Design of embedded based three phase preventor and selector system for indust...
Design of embedded based three phase preventor and selector system for indust...
 
Renesas RX23T Inverter Kit - Deep dive
Renesas RX23T Inverter Kit - Deep diveRenesas RX23T Inverter Kit - Deep dive
Renesas RX23T Inverter Kit - Deep dive
 
PLC based Multichannel Automatic Liquid Level Controller
PLC based Multichannel Automatic Liquid Level ControllerPLC based Multichannel Automatic Liquid Level Controller
PLC based Multichannel Automatic Liquid Level Controller
 
File 1389427052
File 1389427052File 1389427052
File 1389427052
 
MPC of TWT based Transmitter
MPC of TWT based TransmitterMPC of TWT based Transmitter
MPC of TWT based Transmitter
 
Scada presentation
Scada presentationScada presentation
Scada presentation
 
Project ppt
Project pptProject ppt
Project ppt
 
A low cost short range wireless embedded system for multiple parameter control
A low cost short range wireless embedded system for multiple parameter controlA low cost short range wireless embedded system for multiple parameter control
A low cost short range wireless embedded system for multiple parameter control
 
A low cost short range wireless embedded system for multiple parameter control
A low cost short range wireless embedded system for multiple parameter controlA low cost short range wireless embedded system for multiple parameter control
A low cost short range wireless embedded system for multiple parameter control
 
7SR220 Overcurrent Relay
7SR220 Overcurrent Relay7SR220 Overcurrent Relay
7SR220 Overcurrent Relay
 

Similar to LayerZero 4-Pole eSTS Static Transfer Switch with SafePanel Distribution

Chapter 10 Introduction to Air Insulation Substation .pptx
Chapter 10 Introduction to Air Insulation Substation .pptxChapter 10 Introduction to Air Insulation Substation .pptx
Chapter 10 Introduction to Air Insulation Substation .pptx
borapring
 
Why the Hybrid Rack Transfer Switch is Superior to ATS and STS
Why the Hybrid Rack Transfer Switch is Superior to ATS and STSWhy the Hybrid Rack Transfer Switch is Superior to ATS and STS
Why the Hybrid Rack Transfer Switch is Superior to ATS and STS
Raritan
 
Riello master-switch-sts-3p
Riello master-switch-sts-3pRiello master-switch-sts-3p
Riello master-switch-sts-3p
Electrical and renewable energy engineering
 
Gemini_3__3008_web
Gemini_3__3008_webGemini_3__3008_web
Gemini_3__3008_web
Alex Bogias, Phd
 
LayerZero Series 70: eRPP Remote Power Panel
LayerZero Series 70: eRPP Remote Power PanelLayerZero Series 70: eRPP Remote Power Panel
LayerZero Series 70: eRPP Remote Power Panel
LayerZero Power Systems, Inc.
 
7SR191 Capa Protection Relays
7SR191 Capa Protection Relays7SR191 Capa Protection Relays
7SR191 Capa Protection Relays
ashwini reliserv
 
LayerZero Series 70: ePanel-1 Wall-Mounted Power Panel
LayerZero Series 70: ePanel-1 Wall-Mounted Power PanelLayerZero Series 70: ePanel-1 Wall-Mounted Power Panel
LayerZero Series 70: ePanel-1 Wall-Mounted Power Panel
LayerZero Power Systems, Inc.
 
LayerZero Series 70: eRPP-FS Front/Side Access Remote Power Panel
LayerZero Series 70: eRPP-FS Front/Side Access Remote Power PanelLayerZero Series 70: eRPP-FS Front/Side Access Remote Power Panel
LayerZero Series 70: eRPP-FS Front/Side Access Remote Power Panel
LayerZero Power Systems, Inc.
 
NetSure-502-Brochure
NetSure-502-BrochureNetSure-502-Brochure
NetSure-502-Brochure
Carlos Sierra Durocher
 
7SR157 Synchronising Protective Relay
7SR157 Synchronising Protective Relay7SR157 Synchronising Protective Relay
7SR157 Synchronising Protective Relay
ashwini reliserv
 
Joseph Staniowski - Design Project
Joseph Staniowski - Design ProjectJoseph Staniowski - Design Project
Joseph Staniowski - Design Project
Joseph Staniowski
 
Eaton ATS Automatic Transfer Switch ATS-PWR
Eaton ATS Automatic Transfer Switch ATS-PWREaton ATS Automatic Transfer Switch ATS-PWR
Eaton ATS Automatic Transfer Switch ATS-PWR
Thorne & Derrick International
 
Eaton ats automatic transfer switch ats pwr
Eaton ats automatic transfer switch ats pwrEaton ats automatic transfer switch ats pwr
Eaton ats automatic transfer switch ats pwr
Thorne & Derrick International
 
7SR12 Directional Over Current Relay
7SR12 Directional Over Current Relay7SR12 Directional Over Current Relay
7SR12 Directional Over Current Relay
ashwini reliserv
 
Abb pvs 100-tl
Abb pvs 100-tlAbb pvs 100-tl
Ats brochure
Ats brochureAts brochure
Ats brochure
Bimad Sinha
 
LayerZero Series 70: ePanel-HD2 High Density Power Panel
LayerZero Series 70: ePanel-HD2 High Density Power PanelLayerZero Series 70: ePanel-HD2 High Density Power Panel
LayerZero Series 70: ePanel-HD2 High Density Power Panel
LayerZero Power Systems, Inc.
 
5 Reasons You Need the Latest Generation of iPDU
5 Reasons You Need the Latest Generation of iPDU5 Reasons You Need the Latest Generation of iPDU
5 Reasons You Need the Latest Generation of iPDU
Raritan
 
7VK61 Breaker Management Protective Relay
7VK61 Breaker Management Protective Relay7VK61 Breaker Management Protective Relay
7VK61 Breaker Management Protective Relay
ashwini reliserv
 
7SR158 Argus Relay
7SR158 Argus Relay7SR158 Argus Relay
7SR158 Argus Relay
ashwini reliserv
 

Similar to LayerZero 4-Pole eSTS Static Transfer Switch with SafePanel Distribution (20)

Chapter 10 Introduction to Air Insulation Substation .pptx
Chapter 10 Introduction to Air Insulation Substation .pptxChapter 10 Introduction to Air Insulation Substation .pptx
Chapter 10 Introduction to Air Insulation Substation .pptx
 
Why the Hybrid Rack Transfer Switch is Superior to ATS and STS
Why the Hybrid Rack Transfer Switch is Superior to ATS and STSWhy the Hybrid Rack Transfer Switch is Superior to ATS and STS
Why the Hybrid Rack Transfer Switch is Superior to ATS and STS
 
Riello master-switch-sts-3p
Riello master-switch-sts-3pRiello master-switch-sts-3p
Riello master-switch-sts-3p
 
Gemini_3__3008_web
Gemini_3__3008_webGemini_3__3008_web
Gemini_3__3008_web
 
LayerZero Series 70: eRPP Remote Power Panel
LayerZero Series 70: eRPP Remote Power PanelLayerZero Series 70: eRPP Remote Power Panel
LayerZero Series 70: eRPP Remote Power Panel
 
7SR191 Capa Protection Relays
7SR191 Capa Protection Relays7SR191 Capa Protection Relays
7SR191 Capa Protection Relays
 
LayerZero Series 70: ePanel-1 Wall-Mounted Power Panel
LayerZero Series 70: ePanel-1 Wall-Mounted Power PanelLayerZero Series 70: ePanel-1 Wall-Mounted Power Panel
LayerZero Series 70: ePanel-1 Wall-Mounted Power Panel
 
LayerZero Series 70: eRPP-FS Front/Side Access Remote Power Panel
LayerZero Series 70: eRPP-FS Front/Side Access Remote Power PanelLayerZero Series 70: eRPP-FS Front/Side Access Remote Power Panel
LayerZero Series 70: eRPP-FS Front/Side Access Remote Power Panel
 
NetSure-502-Brochure
NetSure-502-BrochureNetSure-502-Brochure
NetSure-502-Brochure
 
7SR157 Synchronising Protective Relay
7SR157 Synchronising Protective Relay7SR157 Synchronising Protective Relay
7SR157 Synchronising Protective Relay
 
Joseph Staniowski - Design Project
Joseph Staniowski - Design ProjectJoseph Staniowski - Design Project
Joseph Staniowski - Design Project
 
Eaton ATS Automatic Transfer Switch ATS-PWR
Eaton ATS Automatic Transfer Switch ATS-PWREaton ATS Automatic Transfer Switch ATS-PWR
Eaton ATS Automatic Transfer Switch ATS-PWR
 
Eaton ats automatic transfer switch ats pwr
Eaton ats automatic transfer switch ats pwrEaton ats automatic transfer switch ats pwr
Eaton ats automatic transfer switch ats pwr
 
7SR12 Directional Over Current Relay
7SR12 Directional Over Current Relay7SR12 Directional Over Current Relay
7SR12 Directional Over Current Relay
 
Abb pvs 100-tl
Abb pvs 100-tlAbb pvs 100-tl
Abb pvs 100-tl
 
Ats brochure
Ats brochureAts brochure
Ats brochure
 
LayerZero Series 70: ePanel-HD2 High Density Power Panel
LayerZero Series 70: ePanel-HD2 High Density Power PanelLayerZero Series 70: ePanel-HD2 High Density Power Panel
LayerZero Series 70: ePanel-HD2 High Density Power Panel
 
5 Reasons You Need the Latest Generation of iPDU
5 Reasons You Need the Latest Generation of iPDU5 Reasons You Need the Latest Generation of iPDU
5 Reasons You Need the Latest Generation of iPDU
 
7VK61 Breaker Management Protective Relay
7VK61 Breaker Management Protective Relay7VK61 Breaker Management Protective Relay
7VK61 Breaker Management Protective Relay
 
7SR158 Argus Relay
7SR158 Argus Relay7SR158 Argus Relay
7SR158 Argus Relay
 

More from LayerZero Power Systems, Inc.

LayerZero Series 70: eRDP-FS Remote Distribution Panel with Front/Side Access
LayerZero Series 70: eRDP-FS Remote Distribution Panel with Front/Side AccessLayerZero Series 70: eRDP-FS Remote Distribution Panel with Front/Side Access
LayerZero Series 70: eRDP-FS Remote Distribution Panel with Front/Side Access
LayerZero Power Systems, Inc.
 
LayerZero Series 70: eRDP Remote Distribution Panel
LayerZero Series 70: eRDP Remote Distribution PanelLayerZero Series 70: eRDP Remote Distribution Panel
LayerZero Series 70: eRDP Remote Distribution Panel
LayerZero Power Systems, Inc.
 
LayerZero Series 70: ePanel-2 Wall-Mounted Power Panel
LayerZero Series 70: ePanel-2 Wall-Mounted Power PanelLayerZero Series 70: ePanel-2 Wall-Mounted Power Panel
LayerZero Series 70: ePanel-2 Wall-Mounted Power Panel
LayerZero Power Systems, Inc.
 
LayerZero Series 70: eRPP-SL2 Slim Remote Power Panel
LayerZero Series 70: eRPP-SL2 Slim Remote Power PanelLayerZero Series 70: eRPP-SL2 Slim Remote Power Panel
LayerZero Series 70: eRPP-SL2 Slim Remote Power Panel
LayerZero Power Systems, Inc.
 
LayerZero Series 70 ePODs: Type-X Power Distribution Unit with Transformer an...
LayerZero Series 70 ePODs: Type-X Power Distribution Unit with Transformer an...LayerZero Series 70 ePODs: Type-X Power Distribution Unit with Transformer an...
LayerZero Series 70 ePODs: Type-X Power Distribution Unit with Transformer an...
LayerZero Power Systems, Inc.
 
LayerZero Power Systems Corporate Brochure
LayerZero Power Systems Corporate BrochureLayerZero Power Systems Corporate Brochure
LayerZero Power Systems Corporate Brochure
LayerZero Power Systems, Inc.
 

More from LayerZero Power Systems, Inc. (6)

LayerZero Series 70: eRDP-FS Remote Distribution Panel with Front/Side Access
LayerZero Series 70: eRDP-FS Remote Distribution Panel with Front/Side AccessLayerZero Series 70: eRDP-FS Remote Distribution Panel with Front/Side Access
LayerZero Series 70: eRDP-FS Remote Distribution Panel with Front/Side Access
 
LayerZero Series 70: eRDP Remote Distribution Panel
LayerZero Series 70: eRDP Remote Distribution PanelLayerZero Series 70: eRDP Remote Distribution Panel
LayerZero Series 70: eRDP Remote Distribution Panel
 
LayerZero Series 70: ePanel-2 Wall-Mounted Power Panel
LayerZero Series 70: ePanel-2 Wall-Mounted Power PanelLayerZero Series 70: ePanel-2 Wall-Mounted Power Panel
LayerZero Series 70: ePanel-2 Wall-Mounted Power Panel
 
LayerZero Series 70: eRPP-SL2 Slim Remote Power Panel
LayerZero Series 70: eRPP-SL2 Slim Remote Power PanelLayerZero Series 70: eRPP-SL2 Slim Remote Power Panel
LayerZero Series 70: eRPP-SL2 Slim Remote Power Panel
 
LayerZero Series 70 ePODs: Type-X Power Distribution Unit with Transformer an...
LayerZero Series 70 ePODs: Type-X Power Distribution Unit with Transformer an...LayerZero Series 70 ePODs: Type-X Power Distribution Unit with Transformer an...
LayerZero Series 70 ePODs: Type-X Power Distribution Unit with Transformer an...
 
LayerZero Power Systems Corporate Brochure
LayerZero Power Systems Corporate BrochureLayerZero Power Systems Corporate Brochure
LayerZero Power Systems Corporate Brochure
 

Recently uploaded

Let's Integrate MuleSoft RPA, COMPOSER, APM with AWS IDP along with Slack
Let's Integrate MuleSoft RPA, COMPOSER, APM with AWS IDP along with SlackLet's Integrate MuleSoft RPA, COMPOSER, APM with AWS IDP along with Slack
Let's Integrate MuleSoft RPA, COMPOSER, APM with AWS IDP along with Slack
shyamraj55
 
Generating privacy-protected synthetic data using Secludy and Milvus
Generating privacy-protected synthetic data using Secludy and MilvusGenerating privacy-protected synthetic data using Secludy and Milvus
Generating privacy-protected synthetic data using Secludy and Milvus
Zilliz
 
“I’m still / I’m still / Chaining from the Block”
“I’m still / I’m still / Chaining from the Block”“I’m still / I’m still / Chaining from the Block”
“I’m still / I’m still / Chaining from the Block”
Claudio Di Ciccio
 
20240609 QFM020 Irresponsible AI Reading List May 2024
20240609 QFM020 Irresponsible AI Reading List May 202420240609 QFM020 Irresponsible AI Reading List May 2024
20240609 QFM020 Irresponsible AI Reading List May 2024
Matthew Sinclair
 
Full-RAG: A modern architecture for hyper-personalization
Full-RAG: A modern architecture for hyper-personalizationFull-RAG: A modern architecture for hyper-personalization
Full-RAG: A modern architecture for hyper-personalization
Zilliz
 
How to Get CNIC Information System with Paksim Ga.pptx
How to Get CNIC Information System with Paksim Ga.pptxHow to Get CNIC Information System with Paksim Ga.pptx
How to Get CNIC Information System with Paksim Ga.pptx
danishmna97
 
Serial Arm Control in Real Time Presentation
Serial Arm Control in Real Time PresentationSerial Arm Control in Real Time Presentation
Serial Arm Control in Real Time Presentation
tolgahangng
 
Building Production Ready Search Pipelines with Spark and Milvus
Building Production Ready Search Pipelines with Spark and MilvusBuilding Production Ready Search Pipelines with Spark and Milvus
Building Production Ready Search Pipelines with Spark and Milvus
Zilliz
 
Video Streaming: Then, Now, and in the Future
Video Streaming: Then, Now, and in the FutureVideo Streaming: Then, Now, and in the Future
Video Streaming: Then, Now, and in the Future
Alpen-Adria-Universität
 
How to use Firebase Data Connect For Flutter
How to use Firebase Data Connect For FlutterHow to use Firebase Data Connect For Flutter
How to use Firebase Data Connect For Flutter
Daiki Mogmet Ito
 
Microsoft - Power Platform_G.Aspiotis.pdf
Microsoft - Power Platform_G.Aspiotis.pdfMicrosoft - Power Platform_G.Aspiotis.pdf
Microsoft - Power Platform_G.Aspiotis.pdf
Uni Systems S.M.S.A.
 
“Building and Scaling AI Applications with the Nx AI Manager,” a Presentation...
“Building and Scaling AI Applications with the Nx AI Manager,” a Presentation...“Building and Scaling AI Applications with the Nx AI Manager,” a Presentation...
“Building and Scaling AI Applications with the Nx AI Manager,” a Presentation...
Edge AI and Vision Alliance
 
Columbus Data & Analytics Wednesdays - June 2024
Columbus Data & Analytics Wednesdays - June 2024Columbus Data & Analytics Wednesdays - June 2024
Columbus Data & Analytics Wednesdays - June 2024
Jason Packer
 
Driving Business Innovation: Latest Generative AI Advancements & Success Story
Driving Business Innovation: Latest Generative AI Advancements & Success StoryDriving Business Innovation: Latest Generative AI Advancements & Success Story
Driving Business Innovation: Latest Generative AI Advancements & Success Story
Safe Software
 
OpenID AuthZEN Interop Read Out - Authorization
OpenID AuthZEN Interop Read Out - AuthorizationOpenID AuthZEN Interop Read Out - Authorization
OpenID AuthZEN Interop Read Out - Authorization
David Brossard
 
GenAI Pilot Implementation in the organizations
GenAI Pilot Implementation in the organizationsGenAI Pilot Implementation in the organizations
GenAI Pilot Implementation in the organizations
kumardaparthi1024
 
Choosing The Best AWS Service For Your Website + API.pptx
Choosing The Best AWS Service For Your Website + API.pptxChoosing The Best AWS Service For Your Website + API.pptx
Choosing The Best AWS Service For Your Website + API.pptx
Brandon Minnick, MBA
 
Mind map of terminologies used in context of Generative AI
Mind map of terminologies used in context of Generative AIMind map of terminologies used in context of Generative AI
Mind map of terminologies used in context of Generative AI
Kumud Singh
 
HCL Notes und Domino Lizenzkostenreduzierung in der Welt von DLAU
HCL Notes und Domino Lizenzkostenreduzierung in der Welt von DLAUHCL Notes und Domino Lizenzkostenreduzierung in der Welt von DLAU
HCL Notes und Domino Lizenzkostenreduzierung in der Welt von DLAU
panagenda
 
June Patch Tuesday
June Patch TuesdayJune Patch Tuesday
June Patch Tuesday
Ivanti
 

Recently uploaded (20)

Let's Integrate MuleSoft RPA, COMPOSER, APM with AWS IDP along with Slack
Let's Integrate MuleSoft RPA, COMPOSER, APM with AWS IDP along with SlackLet's Integrate MuleSoft RPA, COMPOSER, APM with AWS IDP along with Slack
Let's Integrate MuleSoft RPA, COMPOSER, APM with AWS IDP along with Slack
 
Generating privacy-protected synthetic data using Secludy and Milvus
Generating privacy-protected synthetic data using Secludy and MilvusGenerating privacy-protected synthetic data using Secludy and Milvus
Generating privacy-protected synthetic data using Secludy and Milvus
 
“I’m still / I’m still / Chaining from the Block”
“I’m still / I’m still / Chaining from the Block”“I’m still / I’m still / Chaining from the Block”
“I’m still / I’m still / Chaining from the Block”
 
20240609 QFM020 Irresponsible AI Reading List May 2024
20240609 QFM020 Irresponsible AI Reading List May 202420240609 QFM020 Irresponsible AI Reading List May 2024
20240609 QFM020 Irresponsible AI Reading List May 2024
 
Full-RAG: A modern architecture for hyper-personalization
Full-RAG: A modern architecture for hyper-personalizationFull-RAG: A modern architecture for hyper-personalization
Full-RAG: A modern architecture for hyper-personalization
 
How to Get CNIC Information System with Paksim Ga.pptx
How to Get CNIC Information System with Paksim Ga.pptxHow to Get CNIC Information System with Paksim Ga.pptx
How to Get CNIC Information System with Paksim Ga.pptx
 
Serial Arm Control in Real Time Presentation
Serial Arm Control in Real Time PresentationSerial Arm Control in Real Time Presentation
Serial Arm Control in Real Time Presentation
 
Building Production Ready Search Pipelines with Spark and Milvus
Building Production Ready Search Pipelines with Spark and MilvusBuilding Production Ready Search Pipelines with Spark and Milvus
Building Production Ready Search Pipelines with Spark and Milvus
 
Video Streaming: Then, Now, and in the Future
Video Streaming: Then, Now, and in the FutureVideo Streaming: Then, Now, and in the Future
Video Streaming: Then, Now, and in the Future
 
How to use Firebase Data Connect For Flutter
How to use Firebase Data Connect For FlutterHow to use Firebase Data Connect For Flutter
How to use Firebase Data Connect For Flutter
 
Microsoft - Power Platform_G.Aspiotis.pdf
Microsoft - Power Platform_G.Aspiotis.pdfMicrosoft - Power Platform_G.Aspiotis.pdf
Microsoft - Power Platform_G.Aspiotis.pdf
 
“Building and Scaling AI Applications with the Nx AI Manager,” a Presentation...
“Building and Scaling AI Applications with the Nx AI Manager,” a Presentation...“Building and Scaling AI Applications with the Nx AI Manager,” a Presentation...
“Building and Scaling AI Applications with the Nx AI Manager,” a Presentation...
 
Columbus Data & Analytics Wednesdays - June 2024
Columbus Data & Analytics Wednesdays - June 2024Columbus Data & Analytics Wednesdays - June 2024
Columbus Data & Analytics Wednesdays - June 2024
 
Driving Business Innovation: Latest Generative AI Advancements & Success Story
Driving Business Innovation: Latest Generative AI Advancements & Success StoryDriving Business Innovation: Latest Generative AI Advancements & Success Story
Driving Business Innovation: Latest Generative AI Advancements & Success Story
 
OpenID AuthZEN Interop Read Out - Authorization
OpenID AuthZEN Interop Read Out - AuthorizationOpenID AuthZEN Interop Read Out - Authorization
OpenID AuthZEN Interop Read Out - Authorization
 
GenAI Pilot Implementation in the organizations
GenAI Pilot Implementation in the organizationsGenAI Pilot Implementation in the organizations
GenAI Pilot Implementation in the organizations
 
Choosing The Best AWS Service For Your Website + API.pptx
Choosing The Best AWS Service For Your Website + API.pptxChoosing The Best AWS Service For Your Website + API.pptx
Choosing The Best AWS Service For Your Website + API.pptx
 
Mind map of terminologies used in context of Generative AI
Mind map of terminologies used in context of Generative AIMind map of terminologies used in context of Generative AI
Mind map of terminologies used in context of Generative AI
 
HCL Notes und Domino Lizenzkostenreduzierung in der Welt von DLAU
HCL Notes und Domino Lizenzkostenreduzierung in der Welt von DLAUHCL Notes und Domino Lizenzkostenreduzierung in der Welt von DLAU
HCL Notes und Domino Lizenzkostenreduzierung in der Welt von DLAU
 
June Patch Tuesday
June Patch TuesdayJune Patch Tuesday
June Patch Tuesday
 

LayerZero 4-Pole eSTS Static Transfer Switch with SafePanel Distribution

  • 1. Series 70 eSTS 4-Pole STS + Optional SafePanel™ Distribution The Foundation Layer Product Brochure
  • 2. 250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution eSTS Automatically Transfers Between Two Power Sources The Series 70 eSTS is a solid-state transfer switch that automatically or manually provides solid state transfers between two in-phase AC sources in a quarter cycle. The eSTS performs open-transition transfer in such a manner that the connected load disruption is minimized without ever cross-connecting the power sources. One power source is selected to be the preferred source. If the preferred source fails the load is automatically and seamlessly connected to the alternate source by means of an open-transition static transfer. The LayerZero Integrated Solution: eSTS + Distribution Maximizes Power Reliability * Optional Sub-feed Monitor 2 © Copyright 2016 LayerZero Power Systems, Inc.
  • 3. 250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution ;; Optional Triple Modular Redundancy: TMR Contains Fully-Independent Control Paths With No Single Point-Of-Failure ;; Safe Bypass Procedure: Mechanical Bypass Interlock Eliminates Human Error When Performing Bypass Procedures ;; Voice Guided Bypass: Step-By-Step Instructions With Audio and Video Guidance To Assist Operators Through Bypass ;; Convection Cooling: Natural Convection-Cooled Heat Dissipation System is Maintenance-Free ;; Epoxy Coated Buswork: Maximizes Reliability By Eliminating The Possibility of Bus-To-Bus Faults ;; Silver Plated Terminals: Silver Has Excellent Conductivity To Provide Superior Electrical Performance and Reliability ;; Maintenance-Free Joints: Brazed Joints Are Permanent And Maintenance-Free, Maximizing Product Life ;; Machined Hardware: Machined Cap Screws and Engineered Disc Springs Maintain Constant Torque Throughout Product Life ;; Screw Thread Inserts: Prevents Screws From Loosening Under Vibration For Long-Term Reliability ;; Optical Fiber Based Controls: Eliminates Noise and Interference While Isolating Components from High Voltage ;; Serialized Critical Board Tracking: Critical Boards Are Serialized And Cataloged in an Active Database For Traceability Reliability 4-Pole eSTS Static Transfer Switch Product Features Safety ;; InSight™ IR Portholes: Bolted Connections & Critical Boards Can Be IR Scanned With the Dead-Front Doors Closed ;; Sectionalized Components: Isolated Sections That Can Be Safely De-Energized For Performing Maintenance ;; Polycarbonate Windows: Allows Critical Board LEDs To Be Viewed With The Dead-Front Door Closed ;; Front-Only Access: Installation and Maintenance Can Be Safely Performed Without Side or Rear Access ;; Dead Front Hinged Doors: Barrier To Provide A Safe Working Area With No Exposed Live Parts Connectivity ;; Ethernet Connectivity: Secure VPN Router Connects To Network For Advanced Remote Monitoring Capabilities ;; Modbus/TCP: Open Connectivity to Existing Monitoring Systems Without Proprietary Limitations ;; NTP Time Clock Synchronization: Facilitates Timeline-Based Logging For Post-Event Reconstruction ;; SNMP Connectivity: Permits Remote Management Via Simple Network Management Protocol ;; Real-Time Waveform Capture: Automatically Captures A Picture Of The Power Three-Cycles Before and After Every Event ;; Local Touch-Screen Interface: Password-Protected Color Touch-Screen GUI For Local STS Setup/Operation/Administration ;; Black-Box Forensics: Captures and Records All Events To Provide Vital Information In Root-Cause Analysis ;; Waveforms Automatically Emailed: Capability to Send Waveform Captures To Designated Individuals For Every Transfer 3 © Copyright 2016 LayerZero Power Systems, Inc.
  • 4. 250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution Substation 1 or UPS 1 Substation 2 or UPS 2 4-Pole Static Transfer Switch 480 V, 600 V, or MV 120/208 V or 240/415V 120/208 V or 240/415V 480 V, 600 V, or MV Remote Power Panels Wall- Mounted Power Panels Overhead Busways Distribution The 4-Pole eSTS Lowers Infrastructure Costs While Maintaining High Reliability Increasingly, data center operators aspire to increase their energy efficiency; and thus reduce their operating costs and their carbon footprint. A popular technique deployed to achieve higher efficiency of critical operations is to minimize the number of AC power transformations between the building entrance to the eventual critical load. Facilities are being designed to step down voltage at the incoming sub-station to 240/415 V level; and UPS systems are being deployed with native 4-wire, 240/415 V output. Critical loads are operated at 240 V L-N. The cost of cabling in the facility is optimized at a higher voltage; and the loss of efficiency from another voltage transformation to 120/208 V is avoided. Against this back drop and in an environment which provides two independent sources of power, if a static transfer switch is needed to increase the reliability of power to the critical load; and/or to increase the concurrent maintainability of the facility’s electrical infrastructure then the static transfer switch must be a four pole switch. The transfer mechanism must transfer phase conductors (A, B & C) in an open transition manner; while ensuring that the transfer of the neutral between adjacent sources is completed without interruption to the neutral conductor. LayerZero’s 4-pole eSTS is the most reliable, connected and information centric product designed for this application. LayerZero uniquely uses SCR based solid-state transfers for phases A, B, C and Neutral. Further, for operator safety LayerZero deploys 4-pole breakers for input, output and bypass isolation. 4 © Copyright 2016 LayerZero Power Systems, Inc.
  • 5. 250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution CB Section Contains: 4-Pole Input isolation switches 4-Pole Bypass isolation Switches 4-Pole Output isolation switches Source connection terminals Load connection terminals eSTS Controls Section Contains: Control Electronics • System Control & Data Acquisition Boards • SCR Gate Drives • Redundant Power Supply System • I/O system; VPN Router Equipment Layout Power electronics • SCRs (Silicon Control Rectifier) in Convection Cooled Heat Sinks for Phases A, B, AC and Neutral Transfer 15” Color Touch Screen (Standard) 1. Stereo Speakers for Guided Bypass Prompts 2. Output On Light (Remains Lit in Bypass Isolate Mode) 3. Alarm & Bypass Indicator 4. SCB Status Indicator 5. Logged In User 6. Navigation Menu 7. Customer & Project Information 8. Date & Time 1 2 3 4 5 6 207 8 5 © Copyright 2016 LayerZero Power Systems, Inc.
  • 6. 250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution Equipment Construction Detail 1. Alarmed Doors 2. Hinged Dead Front Doors 3. 15” (38.1 cm) Color Touch Screen GUI 4. Polycarbonate Window 5. InSight™ IR Portholes 6. Convection Cooled Heat Sinks 7. Isolation Molded Case Switches 8. Redundant Power Supplies 9. Convection Cooled Intake 1 2 3 4 5 6 8 8 9 10 12 13 14 10. SafePanel™ with Finger Safe Construction 11. SafePanel™ Shrouds 12. Universal Dead Front Door 13. Load Cable Supports 14. Up to 12 Subfeed Circuit Breakers (400 AF or 250 AF) 15. Load Neutral Terminals 16. Load Ground Terminals • Mounted on the right side of 4-Pole eSTS • Adds 12” Width; Right Side Access Required 11 15 16 6 © Copyright 2016 LayerZero Power Systems, Inc.
  • 7. 250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution Reliability Overview LayerZero eSTS Reliability Overview The LayerZero eSTS Provides Many Dimensions of Reliability: • Control System Reliability • SMR (Single Module Redundancy, Standard) • TMR (Triple Modular Redundancy, Optional) • Control Power Supply Reliability • Signal Reliability • Operator Procedural Reliability 7 © Copyright 2016 LayerZero Power Systems, Inc.
  • 8. 250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution Reliability Features: Control System Reliability WAN Port Gate Drive Source 1 A Gate Drive Source 1 B Gate Drive Source 1 C Gate Drive Source 1 N Gate Drive Source 2 A Gate Drive Source 2 B Gate Drive Source 2 C Gate Drive Source 2 N Source 1 Control Source 2 Control Source 1 Control Source 2 Control Source 1 Control Source 2 Control Fiber Optics SCB 1 SCB 2 (TMR) SCB 3 (TMR) Triple Modular Redundancy (TMR) Reliability (Optional) LayerZero TMR has all the redundancy of SMR, plus each STS has three independent sets of analog and digital data acquisition and control systems. There is no direct communication between the three systems. The three systems do not even share a common system clock. • Each control system acquires voltage and current data independently • Each control system determines whether a source is good/bad independently • Upon loss of a source, each control system makes decisions to transfer independently Even if an entire control path or its subcomponent were to fail; and then if the active power source were to fail, the STS is able to complete its mission of transferring to the alternate source. WAN Port Gate Drive Source 1 A Gate Drive Source 1 B Gate Drive Source 1 C Gate Drive Source 1 N Gate Drive Source 2 A Gate Drive Source 2 B Gate Drive Source 2 C Gate Drive Source 2 N Source 1 Control Source 2 Control Fiber Optics SCB 1 Single Module Redundancy (SMR) Reliability (Standard) Single Module Redundancy is a cost-effective topology that provides redundant power paths to mission-critical equipment. In SMR systems, sources each have built-in triple redundancy of processors. In addition, every phase is controlled with a separate gate drive board. LayerZero Single Modular Redundant topology is unique that it the system is fail-safe, maintaining full switching functionality even if a critical board were to fail. 8 © Copyright 2016 LayerZero Power Systems, Inc.
  • 9. 250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution Control Power Supply Reliability Divided into five (5) logical failure groups: • System controls • Source 1 gate drives • Source 2 gate drives • Neutral gate drives • Peripherals. The three (3) available source of power from which to supply control power to each failure group are: • Source 1 • Source 2 • STS Output. LayerZero’s STS design incorporates eighteen (18) power supplies. The resultant control power topology utilizes all possible power paths to the four logical STS failure groups; and is the most comprehensive and redundant STS power supply system in existence. Reliability Features: Control Power Supply Reliability/Signal Reliability Peripherals PS 1 S1 A-B Source 1 A B C N Source 2 A B C N PS 4 S1 B-C PS 7 S1 A-C PS 10 S1 A-B PS 3 S2 B-C PS 6 S2 A-C PS 9 S2 A-B PS 12 S2 B-C System Controls Gate Drives, Source 1 Gate Drives, Source 2 GD 1 GD 3 GD 5 SCB 1 SCB 2 TMR Only SCB 3 TMR Only GD 2 GD 4 GD 6 PS 13 S1 B-C PS 15 S2 A-C Gate Drives, Neutral S1 PS 16 S1 A-C PS 18 S2 A-B Gate Drives, Neutral S1 PS 5 Out B-N System Controls PS 8 Out C-N Gate Drives S1 PS 11 Out B-N PS 14 Out C-N Gate Drives S2 Gate Drives N S1 PS 17 Out A-N Gate Drives N S2 PS 2 Out A-N Peripherals Output Bus A B C N GD 7 GD 8 Signal Reliability Fiber optic based controls eliminate noise and interference, while isolating components from high voltage. Optical fiber allows service to be reliably connected, while protecting the equipment. In LayerZero’s eSTS design, the gate drives (at Power Circuit Voltage) recieve control signsals via optical fibers. 9 © Copyright 2016 LayerZero Power Systems, Inc.
  • 10. 250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution Mechanical Bypass Interlock In order to minimize the possibility of operator error during equipment bypass operations, LayerZero provides: 1. Interlocked breakers 2. Mechanisms to ensure that a source cannot be bypassed without the STS on the correct source. 3. Safeguards to make certain that sources cannot be connected to each other inadvertently. 4. A voice-prompted bypass procedure that guides the operator through the sequence. 5. A step-wise pictorial & video presentation is provided on the touch-screen display during bypass. Voice Guided Bypass Operator error during maintenance bypass has been known to be a reliability hazard. To help prevent operators from completing the bypass procedure out-of-sequence, our product features a voice prompted bypass procedure. This instructs the operator in a step- by-step course of action of the process, with only one operation per screen. Visual and audio cues provide clear instructions on the bypassing sequence, reducing the probability of operator error. Reliability Features: Operator Procedural Reliability 10 © Copyright 2016 LayerZero Power Systems, Inc.
  • 11. 250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution No Fans, Dust Filters, or Fan Fuses The Series 70: eSTS Static Transfer Switch utilizes a natural convection- cooled heat dissipation system. Fans and fan sensors can be some of the most common components to fail. For maximum uptime, LayerZero’s eSTS systems do not contain any fans, dust filters to change, or fan fuses to replace. Reliability Features: Heat Dissipation, Serialized Components Serialized circuit boards We serialize and track all critical circuit boards and memory cards through our eBOSS portal, which allows customers to reference which components their machines are made from, who tested the components, as well as the ability to view notes generated from testing. Serialized components offer the ability to drill-down on prospective component failure utilizing predictive modeling techniques, so if part fails, the instance can be cross-referenced with similar parts. This preventative maintenance helps ensure maximum uptime. 11 © Copyright 2016 LayerZero Power Systems, Inc.
  • 12. 250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution Safety Features 4-Pole Isolation Molded Case Switches The 4-Pole eSTS utilizes four pole molded case switches (MCS) for source, load, and bypass isolation. Solid-state switches transfer three phases (A-B-C) and the Neutral (N). By utilizing 4-pole MCS, the neutral can be completed isolated from feeder circuits during maintenance. View Critical Board LEDs with Dead Front Doors Closed The Series 70: ePODs: 4-Pole eSTS is equipped with a polycarbonate window located on the inner door of the power control section. 12 © Copyright 2016 LayerZero Power Systems, Inc.
  • 13. 250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution InSight™ IR Portholes Permit Scanning of Bolted Connections with Dead-Front Doors Closed Strategically positioned IR-scan portholes to enable safe thermal scanning of all bolted connections with the deadfront closed, without exposing the operator to power circuit voltage. Thermal scans can be done from the front – without ever having to open the dead-front door. The IR window swivels upward and unlocks with key-hole access to reveal a mesh, allowing the operator to point-and-shoot thermal cameras to obtain readings. CB101 CB102 CB201 CB202 CB302 Source 1 Source 2 CB301 Load 1 2 1 2 2 IR Portholes in eSTS (Door and side panel hidden for visibility) Safety Features/Ease of Maintenance 13 © Copyright 2016 LayerZero Power Systems, Inc.
  • 14. 250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution The Breaker Is Inserted Into The SafePanel The Handle Is Unlocked Screws Help Secure The Breaker For Maximum Safety, The SafePanel Has Recessed Bus Work and Finger Safe Lattice. SafePanel™ Distribution 1200 A Circuit Breaker Installation Process The LayerZero SafePanel™ The Series 70 eSTS + Distribution features an IP-20, finger-safe panel board, meaning that the opening will not allow ingress of ½” (12.5mm) diameter probe, for maximum operator safety. An arc can form as two live conductors are separated – such as the removal of a circuit breaker from a panel board. The SafePanel design ensures that a potential arc would be contained in the connection well so that even if a branch breaker were to be removed, the arc would be contained in the connection well. Insulated with the components deeply isolated, removal of the breaker is safe and easy. Safety Features 14 © Copyright 2016 LayerZero Power Systems, Inc.
  • 15. 250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution Modbus/TCP http:// through a standard web browser Network Time Protocol (NTP) Compliant For Clock Synchronization Simple Network Management Protocol (SNMP) Waveforms Automatically Emailed Series 70: eSTS Standard Ethernet Dry Contacts • Meters • Alarms • Meters • Alarms • Waveforms • History/Event Log • Diagnostics • Summary Alarm • On Source 1 • On Source 2 • Source 1 Available • Source 2 Available eSTS Connectivity Options Power Quality Monitoring/Connectivity Options The Series 70: eSTS is equipped with Zen SSQM (Static Switch Quality Monitoring), an all encompassing monitoring system with local and remote communications options. From basic monitoring & alarm reporting, to advanced power quality monitoring functionality, Zen SSQM provides a wide-range of options to help you be aware, be vigilant, be proactive in your quest to create a safe, stable and reliable operation. 15 © Copyright 2016 LayerZero Power Systems, Inc.
  • 16. 250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution Zen SSQM Parameters Mains Voltage Inputs and Output Voltage (Volts) Voltage Average of Phases (Volts) Frequency (Hertz) Total Harmonic Distortion (Percent VTHD) Phase Rotation Current Inputs Current (Amps) Current Average of Phases (Amps) Current Imbalance (Percent) Real Power (kilowatts) Apparent Power (kilovolt-amperes) Reactive Power (kilovolt-amperes reactive) Power Factor Crest Factor Crest Factor Average of Phases Phase Difference Between Sources Phase Difference Between Sources and Output Alarms Summary Alarm On Source (1/2) Source Fail (1/2) Source Preferred (1/2) Source 1st Alternate (1/2) Source Over/Under Voltage (1/2) Source Over/Under Frequency (1/2) Source Not Available (1/2) Output Failure Source Overcurrent (1/2) Source Exceeds Manual Limit (1/2) Source Exceeds Automatic Limit (1/2) Bypassed to Source (1/2) Zen SSQM Technical Specifications All product specifications are subject to change without notice. 16 © Copyright 2016 LayerZero Power Systems, Inc.
  • 17. 250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution Mechanical Characteristics Access Front Only Cable Entry Top (Connection Box Required)/Bottom Cable Exit Top (Connection Box Required)/Bottom Frame Construction Welded Frame Electrical Connections Silver-Plated Solid Busbar Color Textured Powder Coat White (RAL 7035), Blue (RAL 5017), Black, Custom Floor Stands Optional Seismic floor stands Optional Junction Boxes Optional Sectionalization Engineered Composite Insulation, Dead Front Doors Electrical Characteristics Number of Inputs 2 Number of Output MCS 1, 2 Frequency 50 Hz, 60 Hz Poles 4-pole Phases 3 Phase, 4 Wire + Ground Neutral Rating 100% Transfer Time Nominal 1/4- cycle for in-phase sources Redundancy Single Module Redundancy, Triple Modular Redundancy (Optional) Circuit Breaker Type Molded Case Switch (Standard), Electronic Trip (Optional) Circuit Breaker Mounting Type Plug-In 250 A, 400 A; Draw-Out 800 A SPD Type 2 Power Quality Monitoring Power Quality Monitoring Technology Zen SSQM™ (Static Switch Quality Monitoring) Waveform Capture Local Display, Remote Display via Web Browser, Waveforms Automatically Emailed Voltmeter Input sources and Output, for each phase Ammeter Input sources and Output, for each phase Frequency Meter Both Sources Synchroscope Phase Angle Meter Between Sources Metering Apparent Power, Real Power, Power Factor, Output Total Harmonic Distortion Time Stamped Transfer Count From First Day Use, From Last Reset CB Status Indicator Open/Closed/Tripped Circuit Breaker Source Indicator Preferred Source Power Path Indicator On Live Mimic Distribution Section Dimensions Add 12” (30.48 cm) to Width Access Front & Right Side Technical Specifications: 4-Pole Static Transfer Switch 4-Pole eSTS Models with Withstand Ratings eSTS Rating (100%) Voltage Withstand Dimensions Weight Heat Dissipation 250 A * 120/208 V 220/380 V 230/400 V 240/415 V 277/480 V 65 kA 48” W x 36” D x 90” H (1219.2 mm x 914.4 mm x 2286 mm) 1,800 lbs. (816 kg) 6,000 BTU/Hr. 400 A * 2,000 lbs. (907 kg) 8,000 BTU/Hr. 800 A 84” W x 40” D x 86” H (2133.6 mm x 1016 mm x 2184.4 mm) 2,950 lbs. (1338 kg) 8,000 BTU/Hr * Available Spring 2016All product specifications are subject to change without notice. 17 © Copyright 2016 LayerZero Power Systems, Inc.
  • 18. 250 A -800 A, 4-Pole Static Transfer SwitchSeries 70 eSTS + Optional Distribution Operational Characteristics Transfer Modes Automatic; Manual (via Preferred Source Selection) Cooling Convection Cooling Service Access Front Only Bypass Interlock Mechanism Mechanical Noise & Interference Isolation Optical Fiber in Critical Control Paths IR Scan Port Type InSight™ IR Portholes SCR Type Puck Display Type 15” (38.1 cm) Color Touch Screen Display Resolution 1024x768 Bypass Assistance Voice-Guided Bypass Audio Bezel-Mounted Stereo Speakers Languages English, French Mimic Panel Digital Setpoints Control Digital Power Supplies Redundant (4 Failure Groups. Triple Redundant Supplies.) Connectivity Meters Local Display, Ethernet, Modbus/TCP, http via Web Browser (Non-Proprietary) Alarms Local Display, Ethernet, Modbus/TCP, http via Web Browser (Non-Proprietary) Summary Alarm Dry Contacts; Local Display; Modbus/TCP; Web Browser Waveforms Local Display, Ethernet, http via Web Browser (Non-Proprietary) History/Event Log Local Display, Ethernet, http via Web Browser (Non-Proprietary) Diagnostics Local Display, Ethernet, http via Web Browser (Non-Proprietary) Time Synchronization Network Time Protocol (NTP) Standards Conformance: Static Transfer Switch UL ETL Listed to UL 1008S CSA ETL Listed to C22.22 No 107. Standards Conformance: SafePanel Distribution UL ETL Listed to UL 60950 CSA C22.2 No 29-M1989 Technical Specifications All product specifications are subject to change without notice. 18 © Copyright 2016 LayerZero Power Systems, Inc.
  • 19. LayerZero Power Systems, Inc. 1500 Danner Drive Aurora, OH 44202 U.S.A. © 2016 LayerZero Power Systems, Inc. LayerZero Power Systems, LayerZero.com and the LayerZero logo are registered trademark of LayerZero. Learn more at www.LayerZero.com All product specifications are subject to change without notice. Rev. 7/16 #9